ATyS t M - ATyS g M Automatic Transfer Switching Equipment from 40 to 160 A
|
|
- Gervase George
- 5 years ago
- Views:
Transcription
1 TyS t M - TyS g M utomatic Transfer Switching Equipment Transfer switches new The solution for > High Rise uildings > Data centre > Healthcare buildings TyS g M I-0-II P atys-mg_001_b_1_cat Function TyS t M I-0-II 4P atys-mt_001_b_1_cat TyS t M and TyS g M are three-phase (4P) automatic transfer switches with positive break indication. The TyS g M is also available in P for single phase applications. The TyS t M and TyS g M both include TyS d M functionality together, with an integrated controller for automatic transfer dedicated to mains/mains applications (TyS t M) and mains/ genset applications (TyS g M). They are intended for use in low voltage power supply systems where a brief interruption of the load supply is acceptable during transfer. dvantages Fast commissioning TyS t M and g M transfer switches offer significant time saving during commissioning (the process takes to 3 minutes). Thanks to the design that allows commissioning through just one potentiometer (4 on the TyS g M) and four DIP switches, a screwdriver is all that is required to configure the parameters. TyS g M: specifically designed for mains/ genset applications The TyS g M integrated controller has been designed to provide specific functions for these applications (genset startup, tests on load...) together with the monitoring of the voltage and frequency of both sources for three-phase and single-phase networks. TyS t M: specifically designed for mains/ mains applications The TyS t M integrated controller has been designed to provide all the functions necessary for these applications (operation with or without priority, preferred source selection) together with the monitoring of the voltage and frequency of both sources for three-phase networks. Secured configuration settings In order to prevent any risk of unintended change to the configured settings, a sealable cover is available as an accessory. Strong points > Fast commissioning > TyS d M functions plus an integrated TS controller dedicated to mains/mains or mains/genset applications > Secured configuration settings Conformity to standards > IEC > IEC > G pprovals and certifications (1) (1) Product reference on request. (1) Only on two pole versions
2 TyS t M - TyS g M utomatic Transfer Switching Equipment What you need to know The TyS t M and TyS g M are automatic transfer switching equipment that include a fully integrated TS controller. These products are self powered from incoming supplies: 30 VC ( VC), 50/60 Hz (45/65Hz). s TyS t M No. of poles Network (VC) TyS t M ridging bars Voltage sensing and power supply tap Terminal shrouds uxiliary contact block Sealable cover 40 4P 30/ P 30/ P 30/ P 30/ P 30/ P 30/ P pieces pieces (1) 1 piece Separate common points () Linked common points () (1) The three-phase version (4 P), for upstream and downstream protection, please order the reference twice. For the single-phase version ( P) please order the reference once. () 1 NO/NC contact block for positions I, 0 and II. TyS g M No. of poles Network (VC) (3) TyS g M ridging bars Voltage sensing and power supply tap Terminal shrouds uxiliary contact block Sealable cover 40 P P 30/ P P 30/ P P 30/ P P 30/ P P 30/ P P pieces pieces (1) 1 piece Separate common points () Linked common points () P P P P 30/ (1) The three-phase version (4 P), for upstream and downstream protection, please order the reference twice. For the single-phase version ( P) please order the reference once. () 1 NO/NC contact block for positions I, 0 and II. (3) For 17/30 VC networks, please contact your SOCOMEC office.
3 ccessories ridging bars d to bridge the outgoing common connection between switch I and switch II. The bridging bar does not reduce the connection capacity of the cage terminals. No. of poles P P P P atysm_05_a Voltage sensing and power supply tap It allows connection of x 1.5 mm² voltage sensing or power cables. Pack pieces The single-pole voltage sensing tap can be mounted in any of the terminals (incoming) without reducing their connecting capacity. atysm_06_a Terminal shrouds Protection against direct contact with terminals or connecting parts. dvantages of the terminal shrouds Perforations built in to the terminal shrouds allow remote thermographic inspection without the need to remove the shrouds. Tamper-proof seals can be fitted for increased security. Position top and bottom (1) (1) composed of pieces (4P). Mounting For upstream and downstream protection of three-phase products (4 P), please order the reference twice. For the single-phase products ( P) please order the reference once. atysm_07_a uxiliary contact uxiliary contacts for position indication. maximum of two auxiliary contact blocks can be fitted to each product. Each auxiliary contact block integrates 3 NO/NC auxiliary contacts, one per position (I, 0, II). Type Separate common connection Linked common connection The TyS d M s is supplied with one auxiliary contact block fitted as standard; This /C block has separate common points. Characteristics: 50 VC / 5 maximum. 4 VDC / maximum. access_353_a access_398_a
4 Sealable cover Prevents access to the TyS t M and g M configuration panel (seals and screws are included). No. of poles P P atysm_313_a Polycarbonate enclosure Dedicated to the installation of a three-phase TyS M, it enables easy integration of a compact transfer switch solution. H x W x D (mm) x 385 x atysm_036_b_1_cat Extension box for polycarbonate enclosure Combined with the polycarbonate enclosure, the extension unit provides additional space in order to connect 70 mm² cables to the TyS M with ease atysm_039_a_1_x_cat
5 ccessories (continued) Residential enclosure Dedicated to the implementation of a single-phase TyS M, this plastic enclosure provides a compact IP41 transfer switch solution with easy integration. H x W x D (mm) x 305 x atysm_196_a_1_cat uto-transformer For use with TyS M in 400 VC three-phase applications that does not have a distributed neutral. The TyS M includes integrated sensing and power supply circuits, therefore a neutral connection is required for 400 VC three-phase applications. When no neutral connection is available this autotransformer (400/30 VC, 400 V) provides the 30 VC required for the TyS to function trafo_165_b_1 Double power supply - DPS llows an TyS d M to be supplied by two 30 VC, 50/60 Hz networks to have full control in terms of transfer to and from any position with any one of the power supplies available. Input The input is considered active from 00 VC. Maximum voltage: 88 VC. Internal protection: each input is fuse protected Connection on terminals: max. 6 mm. Modular device: 4 module width. 3 Input 1 Input Output 30 VC 0 VC 30 VC (Input 1) 0 VC 30 VC 30 VC (Input ) 30 VC 30 VC 30 VC (Input 1) 0 VC 0 VC 0 VC atys_616_a_1_cat atys_61_a cat Description of accessories DPS and. Input 3. Output
6 Remote interfaces for TyS p M To remotely display source availability and position indication typically used on the front of a panel when the TyS M is enclosed. The remote interface is powered directly from the TyS M via the RJ45 connection cable. Maximum cable length: 3 m. D10 To display source availability and position indication on the front panel of an enclosure. Protection degree: IP1 D0 In addition to the functions of the TyS D10, the D0 displays measurements and enables control and configuration from the front of the display panel. Protection degree: IP1 Door mounting holes Ø.5. TyS M connection via RJ45 cable, not isolated. Cable not provided Description of accessories D D atys_564_c_1_cat atys_597_a_1_cat Interfaces are self powered from the TyS M 96 x 96 Ø.5 = = Drillings atys_565_c_1_cat atys_161_a_1_x_cat Connection cable for remote interfaces To connect between a remote interface (type D10 or D0) and an TyS p M. Type Length RJ45 cable 3 m Characteristics: RJ45 8 wire straight-through, non isolated cable. Length 3m. acces_09_a cat Power connection terminals The power connection terminals allow conversion of the cage terminals into bolt-on type connection terminals, enabling connection of up to two 35mm² cables or one 70mm² cable. Compatible with aluminium terminals. Each power connection terminal is provided with separation screens (1) For complete conversion, order 3 times the reference. acces_5_a_1_cat
7 Enclosed transfer switch solutions General characteristics dapted to mechanical risk and dust hazard. Integrated bridging bar Protection degree: IP3x or IP54. Colour: RL Cable gland plates: top and bottom. Material: steel, thickness 1. mm. Coating: epoxy polyester powder. Wall mounting: 4 fixing lugs supplied loose. Door: hinged metal door, front door cut out 37.4x47.6 mm. Door lock: 3 mm double bar key (included). s TyS d M No. of poles IP 3X IP P P P P P P TyS g M No. of poles IP 3X IP P P P P P P coff_366_b TyS p M + COM RS485 No. of poles IP 3X IP P P P P P P ccessories Customer fit Description Solid neutral Kit IP Dimensions Weight (excluding accessories): 15 kg. Connection (without power connection terminals): min. Cu 10 mm², max. 70 mm². atysm_10_a_1_x_cat
8 Dimensions TyS M 40 to 160 Single-phase TyS M Three-phase TyS M atysm_04_a_1_x_cat atysm_07_a_1_x_cat uxiliary contact ( max) Single-phase TyS M - Door cut-out atysm_008_b_1_x_cat atysm_034_a_1_x_cat x M6 1. uxiliary contact ( max). 34 Three-phase TyS M - Door cut-out Terminals and connections Single-phase TyS d M Three-phase TyS d M atysm_05_a_1_x_cat 7 atysm_040_e_1_x_cat 7 1 : position I control : position II control 3 : position 0 / C control 4 : power supply I (30 VC) 5 : power supply II (30 VC) 6 : voltage tap 7 : auxiliary contact block - 1 NO/NC contact per position I, 0, II (factory fitted) C C 5 : bridging bar (accessories) : single-phase voltage sensing tap (accessories) C: F1 / F = fuse 10 gg 4 4
9 Terminals and connections (continued) Three-phase TyS t M atysm_1_a_1_x_cat 1 preferred source (network) alternate source (network) 1 : position 0 control : preferred source selection 3 : automatic mode inhibition 6 : availability S1 or S : bridging bar (accessories) : auxiliary contact block - 1 NO/NC contact per position I, 0, II (accessories) Single-phase TyS g M Three-phase TyS g M 1 preferred source alternate source atysm_06_a_1_x_cat atysm_1_a_1_x_cat 1 : manual retransfer / priority change : test on load 3 : automatic mode inhibition 6 : product availability relay 7 : genset start / stop control : bridging bar (accessories) : auxiliary contact block - 1 NO/NC contact per position I, 0, II (accessories) Three-phase TyS p M 8 9 atysm_11_a_1_x_cat RJ RS 1 preferred source alternate source : programmable inputs : programmable outputs 7 : genset start / stop control 8 : RJ 45 for connecting a D10/D0 remote interface 9 : RS485 for communication on versions with COM : bridging bar (accessories) : auxiliary contact block - 1 NO/NC contact per position I, 0, II (accessories)
10 Characteristics according to IEC and IEC to 160 Thermal current I th at 40 C Rated insulation voltage U i (V) (power circuit) Rated impulse withstand voltage U imp (kv) (power circuit) Rated insulation voltage U i (V) (operation circuit) Rated impulse withstand voltage U imp (kv) (operation circuit) - TyS d M Rated impulse withstand voltage U imp (kv) (operation circuit) - TyS t M, g M and p M Rated operational currents I e () according to IEC Rated voltage Utilisation category / (1) / (1) / (1) / (1) / (1) / (1) 415 VC C-31 / C-31 40/40 63/63 80/80 100/ /15 100/ VC C-3 / C-3 40/40 63/63 80/80 100/ /15 100/ VC C-33 / C-33 -/40 -/63 -/80 -/100 -/15 -/15 Rated operational currents I e () according to IEC Rated voltage Utilisation category / (1) / (1) / (1) / (1) / (1) / (1) 415 VC C-0 / C-0 40/40 63/63 80/80 100/100 15/15 160/ VC C-1 / C-1 40/40 63/63 80/80 100/100 15/15 160/ VC C- / C- 40/40 63/63 80/80 100/100 15/15 160/ VC C-3 / C-3 40/40 63/63 80/80 100/100 15/15 15/ VC (5) C-1 / C-1 40/40 63/63 80/80 100/100 15/15 160/ VC (5) C- / C- 40/40 63/63 80/80 80/80 100/15 100/ VC (5) C-3 / C-3 40/40 63/63 63/63 80/80 80/80 80/80 Fuse protected short-circuit withstand (k rms prospective) Prospective short-circuit current (k rms) ssociated fuse rating () Circuit breaker protected short-circuit withstand with any circuit breaker that ensures tripping in less than 0.3s (4) Rated short-time withstand current 0.3s I cw (k rms) Short-circuit capacity (without protection) Rated short-time withstand current 1 s. I CW (k rms) Rated peak withstand current (k peak) () Connection Minimum Cu cable cross-section (mm ) Maximum Cu cable cross-section (mm ) Tightening torque (Nm) Switching time (5) I - 0 or II - 0 (ms) (3) I - II or II - I (ms) (3) Duration of "electrical blackout" I - II (ms) minimum Power supply Power supply 30 VC mini / maxi (VC) (TyS d M, t M and g M) 176/88 176/88 176/88 176/88 176/88 176/88 Power supply voltage 30 VC min / max (VC) (TyS p M) 160/ / / / / /305 Control supply power demand Nominal power (V) Max current under 30 VC () - TyS d M, t M and g M Max current under 30 VC () - TyS p M Mechanical characteristics Durability (number of operating cycles) Weight of single-phase versions - without packaging (kg) Weight of single-phase versions - with packaging (kg) Weight of three-phase versions - without packaging (kg) Weight of three-phase versions - with packaging (kg) (1) Category with index = frequent operation - Category with index = infrequent operation. () For a rated operational voltage Ue = 400 VC. (3) etween the command given and reaching of position at Un (under nominal conditions). (4) Value for coordination with any circuit breaker that ensures tripping in less than 0.3s. For coordination with specific circuit-breaker references, higher short-circuit current values are available. Please consult us. (5) t rated voltage - excluding time delays and loss of source detection time when applicable.
ATyS d M Remotely operated Transfer Switching Equipment from 40 to 160 A
ATyS d M Remotely operated Transfer Switching Equipment Transfer switches new The solution for > Applications with an external ATS/AMF controller > Building Management Systems (BMS) atys-md_002_b_1_cat
More informationATyS S - ATyS d S Remotely operated Transfer Switching Equipment from 40 to 125 A
Transfer switches The solution for > Genset < 90 kva > Heating systems > Climate control > Ventilation systems > Telecommunications atys-s_018_a Strong points Function products are 4 pole remotely operated
More informationATyS range ATyS r, ATyS d, ATyS t, ATyS g, ATyS p from 125 to 3200 A
Transfer switches Accessories Terminal shrouds IPX protection against direct contact with terminals or connecting parts. Advantages Perforations allow remote thermographic inspection without the need to
More informationSIRCOVER. Manual transfer switches from 125 to 3200 A. Transfer switches. Function. Advantages. The solution for. Strong points
Transfer switches svr_151_a The solution for > Manufacturing industry > Power distribution SRCOVER 2 Strong points > complete range > Easy connections > Stable positions svr_125_a_1_cat Bypass TS 0 Conformity
More informationEnclosed changeover switches Automatic operation ATSE * - Automatic equipment from 40 to 3200 A Integrated products
ATSE * - Automatic equipment from 40 to 3200 A Integrated products & solutions The solution for > High Rise Buildings. > Data centres. > Energy production. > Healthcare buildings. > Banking and Insurances.
More informationATyS. 63 to 3200 A. Functions. Conformity to standards. General characteristics. Changeover switches. Functions
to 00 A Accessories Enclosed Characteristics M e atysm_007_a cat M s atysm_0_a cat products are and 4pole switches remotely controlled by volt free contacts ( ) or automatic transfer switches ( ). They
More informationSIRCOVER. Manual Transfer Switching Equipment from 125 to 3200 A. Transfer switches. Function. Advantages. The solution for.
Transfer switches svr_151_a The solution for > Manufacturing > Power distribution SIRCOVER 250 Strong points svr_214_a > Complete range > Easy to connect > Stable positions > On-load switching Conformity
More informationMotorised and automatic transfer enclosed switchess
s Integrated products and solutions coff_538_a.eps atysm_251_b_1_cat.eps The solution for > igh-rise buildings > Data centers > Energy generation > ealthcare buildings > Banks and insurance companies >
More informationSIRCO M and MV Universal load break switches from 16 to 160 A
SRCO M and MV from 16 to 16 A The solution for Load break switches sircm_99_a > Main incoming load break > Distribution load break > Machine control > Local safety load break sircm_13_a 4 pole SRCO MV
More informationSIDERMAT Load break switches for power distribution from 250 to 1800 A with tripping function
The solution for Load break switches sdmat_066_a cat > Main switchboard > Distribution panel > Motor load break unction SIDERMT 4 x 630 External front operation SIDERMT are manually operated 3 or 4 pole
More informationSIRCOVER and SIRCOVER BY-PASS. Changeover switches with fully visualised breaking from 125 to 3200 A. 274 General Catalogue SOCOMEC
and Manual Changeover Switches BY-PSS appli_114_a svr_099_b_1_cat svr_059_a_1_cat Changeover switches with fully visualised breaking from 125 to 3200 Function products are manually operated multipolar
More informationAn innovative technology
The range An innovative technology Description The new are load break switches that combine attractive style and optimised features due to their innovative design. This range, dedicated to industrial applications,
More informationLoad break switches. Load break switches for all your applications... Why choose a load break switch designed for photovoltaic applications?...
Load break switches Load break switches for all your applications.................................... Why choose a load break switch designed for photovoltaic applications?............. Load break switch
More informationSIRCO PV UL98B Load break switches for photovoltaic applications from 100 to 2000 A - up to 1500 VDC
Load break switches sircopv_058_a cat SIRCO PV UL98 from 00 to 2000 up to 500 VDC sircopv_059_a cat Strong points > Patented switching technology. > Positive break indication. > Up to 000 VDC as per characteristics
More informationSIRCO MV PV Load break switches for photovoltaic applications for use up to 1000 VDC from 63 to 80 A
Load break switches SIRCO MV PV sircm-pv_010_a_1_cat The solution for > Residential buildings > Buildings > Solar parks Strong points SIRCO MV PV 1000 V - 80 A direct operation > Modular device > Patented
More informationFUSERBLOC Fuse combination switches with rear connection for industrial fuses up to 400 A
Fuse protection fuser_737_a_1_cat.eps fuser_738_a_1_cat.eps The solution for > Motor load break > Protection of industrial processes FUSERBLOC REAR / FRONT connections 3 x 250 A fuser_739_a_1_cat.eps Strong
More informationSIRCO PV UL98B Load break switches for photovoltaic applications from 100 to 2000 A, up to 1500 VDC
Load break switches sircopv_058_a cat SIRCO PV UL98 new sircopv_059_a cat The solution for > Combiner box > Recombiner box > Inverter Function SIRCO PV UL98 non fusible disconnect switches are heavy duty
More informationFUSOMAT Visible breaking and tripping fuse switches from 250 to 1250 A
Fuse protection The solution for > Motor load break > Protection of industrial cabinet > Electrical distribution fusom_063_b_1_cat Strong points > Tripping upon overload > High breaking capacity > Improved
More informationSIRCO M UL 508 Non-fusible disconnect switches standards UL and CSA from 16 to 100 A
Non-fusible disconnect switches SRCO M UL 58 sircm_132_a sircm_133_a The solution for > ndustrial control systems Rotary switch SRCO M 3 x 8 A Toggle switch SRCO M 3 x 8 A + 2 auxiliary contacts Strong
More informationSIRCO PV IEC Load break switches for photovoltaic applications from 100 to 3200 A, up to 1500 VDC
SIRCO PV IEC 609473 The solution for Load break switches > Combiner box > Recombiner box > Inverter sircopv_058_a_1_cat sircopv_059_a_1_cat Strong points Function SIRCO PV are manually operated multipolar
More informationSIRCO PV IEC Load break switches for photovoltaic applications from 100 to 3200 A, up to 1500 VDC
Load break switches SIRCO PV IEC 609473 new The solution for > Combiner box > Recombiner box > Inverter sircopv_058_a_1_cat sircopv_059_a_1_cat Strong points Function SIRCO PV are manually operated multipolar
More informationFUSERBLOC Fuse combination switches for industrial fuses up to 1250 A
Fuse protection fuser_548_a_1_cat The solution for > Motor load break > Protection of industrial processes FUSERBLOC 63 to 125 A Strong points fuser_532_a_1_cat Function FUSERBLOC 32 to 4 A FUSERBLOC are
More informationNon-fusable disconnect switches standards UL and CSA from 16 to 100 A
Non-fusible disconnect switches sircm_132_a sircm_133_a The solution for > Industrial control systems Rotary switch SIRCO M 3 x 80 A Toggle switch SIRCO M 3 x 80 A + 2 auxiliary contacts Competitive advantages
More informationFUSERBLOC Fuse combination switches for industrial fuses up to 1250 A
Fuse protection fuser_548_a cat The solution for > Motor load break. > Protection of industrial cabinet. FUSERBLOC 6 to 25 A Strong points fuser_52_a cat Function FUSERBLOC 2 to 4 A FUSERBLOC are manually
More information125 to 4000 A. Functions. Conformity to standards. Approvals and certifications (1) General characteristics. Available on request
125 to 4000 A sirco_353_a_1_cat sirco_296_a_1_cat sirco_300_b switches are manually operated or motorised multipolar load break switches. They break on and off under load and provide safety isolation for
More informationGeneral Characteristics
from 63 to 31 lbs_037_a he solution for > ain switchboard > Distribution panel > Emergency switching > us tie Function he CEC ensures making and breaking on load and security breaking of any low voltage
More informationSIRCO UL98 Load break switches standards UL and CSA 100 to 1200 A
The solution for Load break switches sirco-ul_022_b_1_cat > Power distribution. Strong points sirco_093_b_1_cat SIRCO 3 x 200 A > Reliability. > Safety of property and personnel. > Simplicity. > Easy assembling.
More informationSIRCO PV Load break switches for photovoltaic applications for use up to 1500 VDC from 100 to 3200 A
Load break switches new SRCO-pv_023_a_1_cat The solution for > Residential buildings. > Buildings. > Solar parks. Strong points Function SRCO PV are manually operated multipolar load break switches. They
More informationATyS t M Automatic Transfer Switching Equipment
Instruction Manual ATyS t M Automatic Transfer Switching Equipment www.socomec.com www.socomec.com www.socomec.com/en/atys-t-m To download, brochures, catalogues and technical manuals. 2 ATyS t M - 542
More informationDPX moulded case circuit breakers
BREAKING AND PROTECTION DEVICES 10 / 2011 DPX moulded case circuit breakers DPX moulded case circuit breakers offer optimum solutions for the protection requirements of commercial and industrial installations.
More informationSIRCOVER Manual transfer switching equipment for source changeover applications from 63 to 3200A
2017 CTLOGUE extract SIRCOVER Manual transfer switching equipment for source changeover applications from 63 to 3200 Transfer switches svr_207_a.eps svr_208_a.eps The solution for > Manufacturing > Power
More informationVistop TM isolating switches 63 to 160A
DX 3 - IS main switches 16 to 125A Vistop TM isolating switches 63 to 160A 225 15 225 18 4 064 00 4 064 59 Pack Cat. No. Main switches AC 22 A category as per EN607-3 Grey handle Accept 1 signalling auxiliary
More informationSIRCO UL98 Non-fusible switches standards UL and CSA 100 to 1200 A
Non-fusible disconnect switches SIRCO UL98 Non-fusible switches standards UL and CSA sirco-ul_022_b_1_cat The solution for > Power distribution sirco_093_b_1_cat SIRCO 3 x 200 A Strong points > Reliability
More informationMS25, MST25, MS20, MST20
Versions: - MS25 with thermal and magnetic releases - MST25 with a thermal release - MS20 - with thermal and magnetic releases for single-phase consumers - MST20 with a thermal for single phase consumers
More informationSystem pro M compact Miniature Circuit Breaker SU200 M for branch circuit protection acc. to UL 489
Data Sheet System pro M compact for branch circuit protection acc. to UL 489 2CDC021004S0014 2CDC021046S0014 The miniature circuit breaker SU200 M is BB s solution for UL 489 branch circuit protection
More information15 16 MCCBs for Power Distribution Technical Specification Frame 100A 250A 250A 400A 400A 630A 800 / 1000 / 1250 Type C DN0-100 D DN1-250 N DN2-250 D N S H DN3B-400 DN3-400 D N D N S V DN3-630 DN4-1250
More informationContents. Volume 5 Motor Control and Protection CA E December
Rotary Disconnects.2 R5 Series Non-Fusible 16 80A Product Description R5 Series (UL 508 listed) products are manually operated modular switches. Load break switching and isolation provide safety solutions
More informationSafety enclosures Normal atmospheres steel enclosure from 50 to 1600 A
Integrated products & solutions The solution for > Iron and steel industry > Cement plants > Paper mills > Sawmills > Hydraulic power packs > Automotive > Mining coff_436_a coff_434_a Strong points Function
More informationWhat you need to know. Â Conformity to standards
SIRCO PV Load break switches for solar applications sirco_343_a_1_cat  What you need to know A solar electrical installation is an application that requires switching devices fully meet the needs of operational
More informationFUSERBLOC Fuse combination switches for industrial fuses up to 1250 A
fuser_548_a_1_cat fuser_532_a_1_cat fuser_539_a_1_cat FUSERBLOC from 25 to 32 A FUSERBLOC from 630 to 1250 A FUSERBLOC from 32 to 400 A Function FUSERBLOC are manually operated multipolar fuse combination
More informationTechnical Information
Miniature Technical Information -09-12 Rated Insulation Voltage U i to IEC947-1 [V] 690V UL/CS [V] 600V Rated Impulse Voltage Withstand U imp [kv] 6 Rated Voltage Ue-Main Contacts C 50/60Hz [V] 230, 240,
More informationTechnical Information
C5 C5- C5- C5- C5- C5-550 ➊ 700 860 1000 1200 Rated Insulation Voltage U i to IEC 947-1 [V] 1000V 1000V 1000V 690V 690V UL/CS [V] 600V Rated Impulse Voltage U imp C5-550 / 700 / 860 [kv] 3.5 C5-1000 /
More informationSeries CA5 Contactors
Series C5 Contactors The contactor for heavy industrial applications from 500HP to 900HP DISCONTINUED This series is being replaced by the C9 Series of contactors C5 Series contactors provide large horsepower
More informationLow Voltage Switches. Switches Motorized change-over switches OTM _C
Low Voltage Switches Switches Motorized change-over switches OTM...12_C II I OTM 12_C Improves your permance OTM II I 0 OFF ON I 0 OFF II I ON I ssembly made easy Bridging bars quick wiring Tunnel terminals
More information3 - Protection components Motor circuit-breakers
Contents 0 - Protection components Motor circuit-breakers protection components for the motor protection Thermal-magnetic motor circuit-breakers Selection guide..............................................page
More informationMotorized switch-disconnectors OTM 40 to 125 Amperes
Motorized switch-disconnectors OTM to 125 mperes With the new range of motorized-switch disconnectors, BB offers now a full range from to 2500 mperes. Thanks to the design, OTM...125 are a good solution
More informationEuroload Changeover Switch
Euroload Features: Quick make & quick break mechanism. High electrical & mechanical endurance. Advance neutral. Enclosed housing to avoid dust ingress. Staggered terminals upto 800A. Load and Line reversibility.
More informationSeries 230 Automatic Transfer Switch
Series 230 Automatic Transfer Switch Product overview The Series 230 automatic transfer switch consists of an intelligent controller and a modular load break switch which automatically transfers the load
More informationA compact range of Switch-Disconnectors with the capacity to add auxiliary and neutral block options to the basic load break switch block.
PNE ISOTORS Craig & Derricott has a range of products designed specifically for control panel and switchboard construction. Most panels require a means of electrical isolation and the can offer variants
More informationAF09... AF38 4-pole Contactors AC / DC Operated - with Screw Terminals
AF09... AF38 4-pole Contactors AC / DC Operated - with Screw Terminals 25 to 55 A culus CE Application AF09... AF38 4-pole contactors are used for controlling power circuits up to 600 V AC and 240 V DC.
More informationRSC09 RSC16 RSC22 RSC38 RSC43 RSC63 RSC-AUX
IEC-Contactor RSC 1 Features Rated operational current 9 63 (C-3) Coil voltages C 24, 230V 3 main contacts and auxiliary contact Extendable with auxiliary contact block Mounting position any 2 Description
More informationATS* By-Pass solution
ATS* solution Other enclosed switches tablo_22_a_1_cat site_366_483_484_a Enclosed ATS from 4 to 32 A Function ing between 2 sources for reliability of the power supply. Single Line & ouble Line of the
More informationDPX Thermal magnetic and trip-free switches DPX 3 -I 160
87045 LIMOGES Cedex Phone :+33 05 55 06 87 87 Fax :+33 05 55 06 88 88 DPX 3 160 CONTENTS PAGES 1. USE 1 2. RANGE 1 3. DIMENSIONS 1 4. OVERVIEW 2 5. ELECTRICAL AND MECHANICAL CHARACTERISTICS 3 6. CONFORMITY
More informationWall mounted switchgear
Contents Safepact 2... pages /2 to / Enclosed MCCBs 6 to 60A... page /2 Enclosed switch disconnectors 100 to 60A... page / Earth leakage.... page /4 Auxiliaries and accessories... page /5 Enclosed Interpact...page
More informationCABINETS AND ENCLOSURES. XL³ 400 and XL³ 800 GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES
O S O O CABINETS AND ENCLOSURES XL³ 400 and XL³ 800 GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES II With its extensive ranges, the Legrand offer meets your quality standards and
More informationMANUALLY OPERATED CHANGEOVER SWITCHES
are manually operated multipolar changeover switches. They changeover between two low voltage power circuits under load and provide safety disconnection. Application: NORMA/EMERGENCY Application: UPS,
More informationMiniature Circuit Breaker
Introduction - Miniature Circuit Breaker (MCB) SALIENT FEATURES SALIENT FEATURES Standards MCBs conform to the latest standard IS 8828: 1996/IEC: 898 1995 Mid-Trip Position The Mid trip position of the
More informationJunction boxes for control, monitoring and control panel Ex tb
Junction boxes for control, monitoring and control panel - Zone 21, 22 - Category 2D - Aluminium, reinforced polyester or stainless steel enclosures - Standard or custom products Inspection window Padlockable
More informationAF40... AF96 3-pole contactors Technical data
Main pole - Utilization characteristics according to IEC Standards IEC 60947- / 60947-4- and EN 60947- / 60947-4- Rated operational voltage Ue max. 690 V Rated frequency (without derating) 50 / 60 Hz Conventional
More informationTeSys contactors. Use in category DC-1 (resistive loads; time constant L/R y 1 ms) Rated operational current Ie. to be wired in series
Selection 3-pole shockproof contactors FG d.c. supply Selection guide for utilisation categories DC-1 to DC-5 Use in category DC-1 (resistive loads; time constant L/R y 1 ms) Rated operational current
More informationCATALOGUE MARINE APPLICATIONS. Energy performance solutions
CATALOGUE MARINE APPLICATIONS Energy performance solutions 2017 2018 Marine Certifications Our certified products As an independent manufacturer, we, at Socomec are committed to adapting the range and
More informationApproved Standards. Ordering Information. Mini Contactor Relays 4-pole J7KNA-AR. Model Number Legend. Main contactor. Accessories
Mini Contactor Relays 4-pole J7KN-R ) Main contactor C & DC operated 4-, 6- and 8-pole versions in different configurations Positively guided contacts Screw fixing and snap fitting (35 mm DIN rail) Rated
More informationSFS-UFS Single Foot Switches
SFS-UFS Single Foot Switches Technopolymer housing, shock proof Protection degree IP53 or IP65 13 contact blocks available Various auxiliary devices available UFS Series SFS Series Options & Ordering Codes
More informationSpecification for 70mm pole pitch Air circuit breaker up to 1600 A
Specification for 70mm pole pitch Air circuit breaker up to 1600 A Protective device for low voltage electrical installation Last update :2011-07-08-1 - Table of contents: 1 General...3 2 Compliance with
More informationLow voltage Direct Current Network. Compact NSX DC PV. Circuit breakers and switch disconnectors for solar application.
Low voltage Direct Current Network Compact NSX DC PV Circuit breakers and switch disconnectors for solar application Catalogue 2012 Compact NSX DC PV A complete DC offer for solar application from 80
More information500V / V /
LOAD BREAK SWITCHES 125-630 A TECHNICAL DATA ATEX RoHS Compliant 2002/95/EC LOAD BREAK SWITCHES 16A 25A 40A 63A 80A 125A 160A KU / KU / KU / KU / KU / KU / VKA / VKA / KUE KUE KUE KUE KUE KUE EVA EVA VKA
More informationMSW. MSW Catalog Number Sequence. Standard Features MSW 25 B- 3
Introducing the New WEG Series. The was developed according to IEC 60947-3 & UL508. The compact, reliable design of the allows the operator to safely disconnect power and isolate the circuit within the
More informationBreakers and Switches. Switches Change-over and transfer switches
Breakers and Switches Switches Change-over and transfer switches Change-over and transfer switches 16...2500 A Contents: 4 Product overview, features 8 Technical data 8 Manual, motorized and automatic
More informationB115...B180 RF200 RFN200 B250...B400 RF400 RFN400
Page -2 Page -4 Page -6 FOR BG SERIES MINI-CONTACTORS Type RF9, phase failure sensitive, manual resetting Type RFA9, phase failure sensitive, automatic resetting Type RFN9, non-phase failure sensitive,
More informationCATALOGUE. Solutions for Power, Control & Safety
CATALOGUE Solutions for Power, Control & Safety 2015 Contents An independent manufacturer... p.4 Four key applications: the benefit of a specialist... p. 5 A cutting-edge laboratory... p. 6 Socomec in
More informationDPX 1600 Electronic release
87045 LIMOGES Cedex Phone :+33 05 55 06 87 87 Fax :+33 05 55 06 88 88 DPX 1600 CONTENTS PAGES 1. USE 1 2. RANGE 1 3. DIMENSIONS 1 3. DIMENSIONS (NEXT) 2 4. OVERVIEW 2 5. CONNECTION 2 6. ELECTRICAL AND
More informationDCX-M. changeover switches ->CATALOGUE PAGES INSIDE THE GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES
DCX-M changeover switches ->CATALOGUE PAGES INSIDE THE GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES FOR COMMERCIAL BUILDINGS AND DCX-M In = 63 A Quality & design CONFORM TO EN/IEC
More informationsirco-ul_004_b_cat 100A to 2000A - 600VDC and 1000VDC UL98B Listed
site_317_a sirco-ul_22_b_cat sirco-ul_4_b_cat 1A to 2A - 6VDC and 1VDC UL98B Listed  Function non fusible disconnects are heavy duty switches that break and make 6VDC or 1VDC photovoltaic circuits on
More informationLimit switches. 7 Page 71. Presentation. OsiSense XC Basic Compact design, plastic, with reset knob, types XCNR and XCNTR. b XCNR.
Presentation Compact design, plastic, with reset knob, types XCNR and XCNTR b XCNR with cable entry v With head for linear movement (plunger) Page v With head for rotary movement (lever) Page b XCNTR with
More informationTechnical Data Accessories MCBs Ex9B.
Auxiliary and signal contact units AX31, A31, AX31 General parameters With one circuit breaker Ex9B., it can be used up to three contact units with single CO contact or up to two contact units with 2 CO
More informationShort form catalogue. Motor protection & control
Short form catalogue Star Series Motor protection & control Motor Protection and Control up to 25 HP / 600 VAC Overview...2 Contactors and Overload Relays...11 4-pole Contactors...41 Control Relays...59
More informationTAE pole Contactors
TAE9...26 3-pole Contactors d.c. operated with double-winding coil SB8033C3 Utilisation TAE9 to TAE26 contactors are a compliment to the DC control contactor range. The coils have large voltage ranges
More informationTransfer switching solutions
CATALOGUE EXTRACT Transfer switching solutions from 40 to 6300 A 2018 Contents The SOCOMEC Group... Security and reliability for your transfer applications... Remotely operated and Automatic Transfer
More informationPhone: Fax: Web: -
HK1-11 HKF1-11 HK-11 HKS-20 uxiliary contacts Mounting uxiliary contacts position Pilot duty rating Instantaneous Lagging / leading / max. 116 132 5x 9x quantity ac dc NO NC NO NC 2 - - - HK1-20 Right
More informationProtection and Connection Motorized and automatic transfer switches IEC Technical guide
Protection and Connection Motorized and automatic transfer switches IEC 61439 Technical guide Motorized change-over switches Uninterrupted power supply with motorized functionality ABB offers a wide variety
More informationSafety switches with solenoid and separate actuator
Safety switches with solenoid and separate actuator These switches are used on machines where the hazardous conditions remain for a while, even after the machines have been switched off, for example because
More informationIP41. Enclosed Switchgear. Hinged Lid IP41 Enclosures. for technical support call: +44(0) General Description.
General Description Supplied in hinged lid grey powder coated sheet steel enclosures, these IP41 sealed assemblies are eminently suitable for most indoor industrial applications. Supplied as Switch-Disconnectors
More informationAF09... AF30 3-pole Contactors up to 20 HP / 480 VAC
AF0... AF0 -pole Contactors up to 20 HP / 480 VAC Contactors and Overload Relays Overview...2 AF0... AF0 -pole Contactors Ordering Details...4 Main Technical Data...20 DC Circuit switching...2 Main Accessory
More informationGV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Standard Features
Standard Features Table : Standard Features GV2ME GV2P GV3P GV7RE/GV7RS 0. to 32 A Up to 20 hp @ 460 V 0 SCCR @ 480 V Push Button Operator 0. to 30 A Up to 5 hp @ 460 V 50 SCCR @ 480 V Rotary Handle Operator
More informationPROTECTION AND CONNECTION. ABB Compact ATS Compact without compromise
PROTECTION AND CONNECTION ABB Compact ATS Compact without compromise 2 A B B C O M PA C T AT S C O M PA C T W I T H O U T C O M P R O M I S E ABB ARTICLE COMPACT OR CHAPTER ATS COMPACT TITLE WITHOUT COMPROMISE
More informationSubmittal Data Information
Effective: NOVEMBER 3, 2014 JOB CONTRCTOR ITEM NO. Submittal Data Information TS - Taco dvanced Starter ENGINEER REP. 301-2690 Supersedes: NEW TS - Taco dvanced Starter 1Ø, 120-230V, 1/10-30HP 3Ø, 200-600V,
More informationSENTRON Switching and Protection Devices Switch Disconnectors
SENTRON Switching and Protection Devices Switch Disconnectors /2 Introduction 3K, 3KE, 3LD Switch Disconnectors 3K, 3KE Switch Disconnectors up to 1000 /4 General data /8 Floor mounting 3LD Main and EMERGENCY-STOP
More informationMAKING MODERN LIVING POSSIBLE. Technical brochure. Minicontactors CI 5-
MKING MODERN LIVING POSSIBLE Technical brochure Minicontactors CI 5- www.danfoss.com 2 IC.PD.C10.F3.02-520B4167 Danfoss /S, C-SMC, mr, 07-2010 Contents Page Minicontactor CI 5- Introduction...............................................................................4
More informationLimit Switch - Prewired Type Metal Body
Limit Switch - Prewired Type Metal Body Sealed with epoxy resin al the base of the box Degree of protection IP67 Thermoplastic material or diecast zinc alloy body Positive Opening Operation Minimum Actuation
More informationDMX 3 -I 2500 switch disconnectors
8704 LIMOGES Cedex Telephone : 0 0 87 87 Fax : 0 0 88 88 DMX 3 200 circuit breakers DMX 3 -I 200 switch disconnectors References: 0 28 20 / 21 / 22 / 23 / 24 / 2 / 2 / 30 / 31/ 32/ 33/ 34 / 3 / 3 / 40
More informationGE Consumer & Industrial. M-PACT New Air Circuit Breaker A
GE onsumer & Industrial M-PT New ir ircuit reaker 400-4000 M-PT M-PT ir ircuit reaker 400-4000 1 ir circuit breakers 400-4000.4 Fixed ircuit reaker.6 Withdrawable ircuit reaker.7 haracteristics.9 State
More informationNew DX 3 High rating & breaking capacity
New High rating & breaking capacity a new range OF MOduLar CirCuiT BrEakErs up TO 125 a T new dx³ MCBs AN ENHANCED range for HIgH-pErforMANCE INstALLAtIoNs DX³ : the new Legrand MCBs with dx³, Legrand
More informationMINIATURE CIRCUIT BREAKER
Technical Article MINIATURE CIRCUIT BREAKER T 146 PURCHASE he Spaceage MCB protects wires and cables automatically against overload and short-circuits in domestic, commercial and industrial installations.
More informationDPX 160 Thermal magnetic and trip-free switches DPX-I 160
87045 LIMOGES Cedex Phone : +33 05 55 06 87 87 FAX : +33 05 55 06 88 88 DPX 160 CONTENTS PAGES 1. USE 1 2. RANGE 1 3. DIMENSIONS 1 3. DIMENSIONS (NEXT) 2 4. OVERVIEW 2 5. CONNECTION 2 6. ELECTRICAL AND
More informationASL09..S 3-pole Contactors - Spring Terminals
4 kw 5 hp ASL09..S 3-pole Contactors - Spring DC Operated Description - 3-pole contactors with spring terminals, - N.C. or N.O. built-in auxiliary contact, - Low coil consumption, - Polarity on the coil
More informationSHORT FORM CATALOGUE. ATYS & SIRCOVER Transfer Switch Equipment for your power availability UL 1008 & UL 98
2014 2015 SHORT FORM CATALOGUE ATYS & SIRCOVER Transfer Switch Equipment for your power availability UL 1008 & UL 98 ATyS UL 1008 Motorized Transfer Switching Equipment from 100 to 400 A Transfer switches
More informationVB6, VB7 3-pole mini reversing contactors with screw terminals 4 to 5.5 kw AC operated
VB6, VB7 -pole mini reversing contactors with screw terminals 4 to 5.5 kw AC operated VB7-0-10 2CDC211006F0011 Description VB6, VB7 -pole compact design reversing contactors are space optimized control
More informationDPX 630 Thermal magnetic and trip-free switches DPX-I 630
87045 LIMOGES Cedex Phone :+33 05 55 06 87 87 Fax :+33 05 55 06 88 88 DPX 630 CONTENTS PAGES 1. USE 1 2. RANGE 1 3. DIMENSIONS 1 4. OVERVIEW 2 5. CONNECTION 2 6. ELECTRICAL AND MECHANICAL CHARACTERISTICS
More informationInstallation instructions for ATS panel Ref:ATS --/2 M2GC705 Issue
FAQs I have installed the ATS panel but it won t go into the mains supply? First check all cables are in place and properly installed and that the control fuses (A-C on page 4) have not blown. If it still
More informationKey features. DESIGNS: - Conservator type - Hermetically sealed
Package Substations OTDS manufactures a large range of oil filled hermitically sealed and conservator type transformers to be used in conjunction with our package substations. We are able to utalise the
More information