TeSys GS & DF Fuse protection

Size: px
Start display at page:

Download "TeSys GS & DF Fuse protection"

Transcription

1 TeSys GS & DF Fuse protection Simple and effective protection TeSys GS Fuse disconnect switches Total isolation between poles Safe replacement of the fuses (double breaking system) Frontal and right side operation Common auxiliary contacts and accessories New design external handle TeSys DF Fuse holders For NFC and Class CC fuses size x, x, x and x Up to 0V, from 0. to Amps multi-pole configurations: P, N, P+N, P, P, P+N Blown fuse indicator Microswitches providing early break, fuse presence and blown fuse signaling functions

2 Presentation Switch-disconnector-fuses to A, TeSys GS GS DD GS N + handle GS AH0 GS S + handle GS AH0 Presentation TeSys GS switch-disconnector-fuses provide on-load breaking or making, safe isolation and overcurrent protection of all low voltage electrical circuits. They are used, in particular, on the incoming supply to control panels, for protecting and switching off main circuits (including Emergency stop). Their compact design means that they can also be fi tted in small automation system equipment to provide the same disconnect and protection functions on the incoming supply of equipment, generators or motor starters. Conforming to standard IEC 0-, TeSys GS switch-disconnector-fuses are available for use with: b NFC or DIN fuses, b BS fuses. A range for use with UL fuses, specifi cally for the North-American market and meeting the requirements of standards UL and CSA. Nr., is also available. The TeSys GS range includes sturdy and compact handles. These handles are easy to install and operate and are available in the following options: b Direct operator. b front and RH side-mounted operator. b LH side-mounted operator. b Padlockable with up to padlocks. The door is locked when the handle is padlocked. b Locking by means of a key-operated lock (option). b With door interlock in the closed position. When in the Closed position, the door can be opened by means of a tool to be used only by authorised personnel. Locking is automatically re-established when the door is closed. b Black/Grey or Yellow/Red for the Emergency stop function. b IP or IP. This range is completed by auxiliary contacts: b Two auxiliary early break and O and I position signalling contacts, confi gurable and common to all ratings. b Auxiliary contacts GS AN, which are suitable for isolation. Reversibility of these contacts to convert an N/C contact into an N/O contact and vice versa. b Control circuit test facility, off-load, with auxiliary contacts GS AM, GS AM or GS ANT, used in conjunction with handles GS AHT. b Auxiliary blown fuse signalling contacts. Functions Breaking b Quick break and quick tripping mechanism, independent of the fuses. C Opening and closing independent of operator speed. C On-load making and breaking of resistive, inductive or mixed resistive and inductive circuits. C Quality and durability of mechanical and electrical lives. b Utilisation categories AC-/0 V and DC-/0 V. C Durable performance in severe duty applications. C Direct control of motors. Characteristics: pages / to / References: pages / to / Dimensions: pages / to / Schemes: page / version:.0 -EN.indd

3 Presentation (continued) Switch-disconnector-fuses to A, TeSys GS Functions (continued) Isolation b Upstream and downstream breaking of fuses for all ratings C Double break isolation of the power circuit and safe replacement of fuses. C Total isolation of power and control circuits to ensure safety of persons and equipment. b GS AN auxiliary contacts. C Control circuit isolation. b Contacts forced open in the event of welding. C Fully visible break. Open position cannot be indicated unless all contacts are actually open. C Safe opening and clear indication of Open state of switch-disconnector. b Visible isolation distance between the open contacts. C Visible break (0 to A ratings). Protection b Addition of gg (gl) fuses. b C Overload and short-circuit protection of distribution circuits and power switching circuits without signifi cant current peak. b Addition of am fuses (associated with thermal overload relays). C Type coordination (Iq > 0 ka) for motor starters consisting of fuses, contactors, relays. C Short-circuit protection of motors and equipment. b Addition of quick-blow fuses. C Protection of electronic variable speed controllers and soft starters. b Blown fuse detection device. C Protection against single-phasing. b Conditional short-circuit withstand voltage of 0 ka for all ratings. C Equivalence between the breaking capacity of the fuses and the ability of the switch-disconnector-fuse to withstand this maximum capacity. C Use in installations where very high short-circuit currents can develop. b b b b Handles with padlocking facility, with door interlock. Handle locking by means of a key-operated lock (option). Door interlock in Closed position. Operator shafts padlockable with door open. Fuse covers fi tted as standard on all ratings. b C Protection against accidental contact. C Protection of persons. b IP 0 protection with terminal shrouds Information and testing b Up to auxiliary contacts. C Early break, Open and Closed position signalling, and blown fuse signalling. C Use in automation systems. b Control circuit test facility, off-load, by using auxiliary contacts GS AM, GS AM or GS ANT in conjunction with handles GS AHT. In the Test position, the enclosure door can be opened. Characteristics: pages / to / References: pages / to / Dimensions: pages / to / Schemes: page / -EN.indd version:.0

4 Selection guide to A Applications TeSys GS switch-disconnector-fuses provide on-load breaking and making, safe isolation and They are used, in particular, on the incoming supply to control panels, for protecting and switching They provide simultaneous disconnection, together with all the other associated functions such as Their compact design means that they can also be fitted in small automation system equipment to Fuse type NF C or DIN Rated thermal current (Ith) A 0 A A 0 A A A 0 A 00 A 0 A A Number of poles or + Nc or Fuse size x x T00C x x T00 T0 T00 T T T T operator, padlockable and lockable Front and RH side LH side Direct operator, padlockable Front RH side Front Rated operational voltage (Ue) 0 V Rated operational current (Ie) at 00 V, AC- A A 0 A A 0 A A A 0 A 00 A 0 A 00 A Rated making capacity at 00 V, AC-B 0 A 00 A 0 A 00 A A 0 A 00 A 000 A 00 A 000 A Rated breaking capacity at 00 V, AC-B A 00 A 00 A 00 A 00 A A 000 A 00 A 00 A 000 A Rated conditional short-circuit current at 00 V, with gg (gi) fuses 0 ka 0 ka 0 ka 0 ka 0 ka 0 ka 0 ka 0 ka 0 ka 0 ka Switch-disconnector-fuse type references GS DD GSp F Pages / and / GSp G GSp J GSp K or KK GSp L or LL GSp N GSp QQ GS S GS V version:. 0Q-EN.indd

5 overcurrent protection. off main circuits (including Emergency stop). padlocking and interlocking. provide the same disconnect and protection functions on the incoming supply of equipment, generators or starters, including motors. BS A A A 0 A A 00 A 0 A A 00 A 0 A 00 A A or + Nc or A A A-A A Øy mm Front and RH side A B-B B-B B B B B B B C-C C C D Front Front 0 V A A A 0 A A 00 A 0 A A 00 A 0 A 00 A 00 A 0 A 0 A 0 A 00 A 0 A 000 A 00 A A 000 A 00 A 000 A 000 A A A 00 A 00 A A 0 A 000 A 0 A 00 A 00 A 00 A 000 A 0 ka 0 ka 0 ka 0 ka 0 ka 0 ka 0 ka 0 ka 0 ka 0 ka 0 ka 0 ka GS DDB / GS DB GS GB GS JB GS LB or LLB GS MMB GS NB GS PPB GS QQB GS SB GS TB GS VB 0Q-EN.indd version:.

6 Characteristics to A, for use with NF C or DIN fuses Type GS DD GSp F GSp G GSp J Switch-disconnector-fuse characteristics Environment Conforming to standards Switch-disconnector-fuses IEC 0- Circuit-breakers IEC 0- and Product certifications Degree of protection conforming to IEC 0 Ambient air temperature around the device Flame resistance conforming to IEC 0-- ASEFA/LOVAG, LROS (pending) With terminal covers IP 0 Storage C Operation C Body C 0 0 Fuse cover C 0 Pole characteristics Conventional thermal current (Ith) for ambient temperature y 0 C A 0 0 Fuse size x x T00C x Rated insulation voltage (Ui) V Rated impulse withstand voltage (Uimp) kv Rated operational current (Ie) Cat. AC-A/B () a 00 V A 0 0 a 00 V A 0 0 a 0 V A 0 0 () Cat. DC-A/B () c 0 V () A Rated operational power Cat. AC-A/B () a 00 V kw 0 a 00 V kw. 0 a 0 V kw 0 Rated conditional short-circuit current Peak value of permissible current (dynamic short-circuit withstand) I rms at a 00 V with protection by gg (gl) fuses ka Rating of associated fuses A 0 0 Conforming to IEC 0- a 00 V ka... 0 Rated making capacity I rms at 00 V Cat. AC-B A Rated breaking capacity I rms at 00 V Cat. AC-B A Mechanical durability Number of operating cycles Electrical durability Number of operating cycles cat. AC/DC-A/B () 0/00 0/00 0/00 0/00 Cabling Cable (c.s.a. min/max) mm./ / / / Bars (max width) mm 0 Tightening torque N.m.. () Category A : frequent operating cycles, category B : infrequent operating cycles () poles in series per phase. () With terminal covers. () Poles not juxtaposed. Presentation: pages / and / References: pages / to / Dimensions: pages / to / Schemes: page / version:. -EN.indd

7 GSp K GSp KK GSp LL GSp L GSp N GSp QQ GS S GS V IEC 0- IEC 0- and ASEFA/LOVAG, LROS (pending) IP x T00 T00 T0 T T T T () 0 () () () 0 () 0/ / / () 00/0 () / /00 00/ (0) () /00 00/00 00/00 00/00 00/00 00/00 00/00 00/0 / / 0/ 0/ /0 /0 x / x 00 / x Presentation: pages / and / References: pages / to / Dimensions: pages / to / Schemes: page / -EN.indd version:.

8 Characteristics to A, for use with BS fuses Type GS DDB GS DB GS GB GS JB Switch-disconnector-fuse characteristics Environment Conforming to standards Switch-disconnector-fuses IEC 0- Circuit-breakers IEC 0- and Product certifications Degree of protection conforming to IEC 0 Ambient air temperature around the device Flame resistance conforming to IEC 0-- ASEFA/LOVAG, LROS (pending) With terminal covers IP 0 Storage C Operation C Body C 0 Fuse cover C 0 Pole characteristics Conventional thermal current (Ith) for ambient temperature y 0 C A 0 Fuse size A A A-A A Ø y mm Rated insulation voltage (Ui) V Rated impulse withstand voltage (Uimp) kv Rated operational current (Ie) Cat. AC-A/B () a 00 V A 0 a 00 V A 0 a 0 V A 0 () Rated operational power Cat. DC-A/B () Cat. AC-A/B () c 0 V () A a 00 V kw 0 a 00 V kw.. 0 a 0 V kw 0 Rated conditional short-circuit current I rms at a 00 V with protection by gg (gl) fuses ka Rating of associated fuses A 0 Peak value of permissible current (dynamic short-circuit withstand) Conforming to IEC 0- a 00 V ka.. 0 Rated making capacity I rms at 00 V Cat. AC-B A Rated breaking capacity I rms at 00 V Cat. AC-B A Mechanical durability Number of operating cycles Electrical durability Number of operating cycles cat. AC/DC-A/B () 0/00 0/00 0/00 0/00 Cabling Cable (c.s.a. min/max) mm./ / / / Bars (max width) mm 0 Tightening torque N.m.. () Category A : frequent operating cycles, category B : infrequent operating cycles () poles in series per phase. () Fit switch-disconnector-fuses GS LB with B or B fuses and GS LLB with A fuses. () With terminal covers. () Poles not juxtaposed. Presentation: pages / and / References: pages / to / Dimensions: pages / to / Schemes: page / version:. -EN.indd

9 GS LB or LLB () GS MMB GS NB GS PPB GS QQB GS SB GS TB GS VB IEC 0- IEC 0- and ASEFA/LOVAG, LROS (pending) IP A. B-B () B-B B B B B B B C-C C C D () 00/ () 0 () 0/ () 0/ / / () 00/0 () / 0 0/ 0/ / / /00 00/00 00/00 00/00 00/00 00/00 00/0 00/0 0/ /0 /0 /0 /0 x / x 00 x / x 00 / x 0 0 Presentation: pages / and / References: pages / to / Dimensions: pages / to / Schemes: page / -EN.indd version:.

10 Characteristics Auxiliary contacts for to A, for use with NF C or DIN fuses GS AMp, GS AM and GS AM early break and signalling contact characteristics Conventional thermal current (Ith) for ambient temperature y 0 C A Rated operational current (Ie) Cat. AC- A V: ; 0 V: ; 00 / V : ; 0 V : Cat. DC- A V: ; V: ; V: 0.; 0 V: 0. Durability Number of operating cycles Mechanical: Electrical: cat. AC-: Fuse protection gg A max Cabling mm Faston connectors: x. or x. GS AN and GS ANT signalling contact characteristics Conventional thermal current (Ith) for ambient temperature y 0 C A 0 Rated operational current (Ie) Cat. AC- A V: ; 0 V: ; 00/ V: ; 0 V: Cat. DC- A V: ; V:.; 0 V: Durability Number of operating cycles Mechanical: Electrical: cat. AC-: Fuse protection gg A max Cabling Cable (c.s.a. min/max) mm Min:.; max: GS AM and GS AM early break and signalling contact characteristics Conventional thermal current (Ith) for ambient temperature y 0 C A Rated operational current (Ie) Cat. AC- A V: ; 0 V: ; 00 V:.; 0 V:. Cat. DC- A V:.; V:.; V: 0.; 0 V: 0.; 00 V: 0. Durability Number of operating cycles Mechanical: Electrical: cat. AC-: Cabling Cable (c.s.a. min/max) mm Min: x 0.; max: x. GSp AF "blown fuse" signalling contact characteristics Conventional thermal current (Ith) for ambient temperature y 0 C A Rated operational current (Ie) Cat. AC- A 0 V: ; 00 V: Cat. DC- A V: ; V: ; V: 0.; 0 V: 0. Durability Number of operating cycles Mechanical: Electrical: cat. AC-: Cabling mm Faston connectors: x. Presentation: pages / and / References: page / Dimensions: pages / to / Schemes: page / version:. -EN.indd

11 Characteristics to A, for use with BS fuses GS AMp, GS AM and GS AM early break and signalling contact characteristics Conventional thermal current (Ith) for ambient temperature y 0 C A Rated operational current (Ie) Cat. AC- A V: ; 0 V: ; 00/ V: ; 0 V: Cat. DC- A V: ; V: ; V: 0.; 0 V: 0. Durability Number of operating cycles Mechanical: Electrical: cat. AC-: Fuse protection gg A max Cabling mm Faston connectors: x. or x. GS AN and GS ANT signalling contact characteristics Conventional thermal current (Ith) for ambient temperature y 0 C A 0 Rated operational current (Ie) Cat. AC- A V: ; 0 V: ; 00/ V: ; 0 V: Cat. DC- A V: ; V:.; 0 V: Durability Number of operating cycles Mechanical: Electrical: cat. AC-: Fuse protection gg A max Cabling Cable (c.s.a. min/max) mm Min:.; max: GS AM and GS AM early break and signalling contact characteristics Conventional thermal current (Ith) for ambient temperature y 0 C A Rated operational current (Ie) Cat. AC- A V: ; 0 V: ; 00 V:.; 0 V:. Cat. DC- A V:.; V:.; V: 0.; 0 V: 0.; 00 V: 0. Durability Number of operating cycles Mechanical: Electrical: cat. AC-: Cabling Cable (c.s.a. min/max) mm Min: x 0.; max: x. GSp AF "blown fuse" signalling contact characteristics Conventional thermal current (Ith) for ambient temperature y 0 C A Rated operational current (Ie) Cat. AC- A 0 V: ; 00 V: Cat. DC- A V: ; V: ; V: 0.; 0 V: 0. Durability Number of operating cycles Mechanical: Electrical: cat. AC-: Cabling mm Faston connectors: x. Presentation: pages / and / References: page / Dimensions: pages / to / Schemes: page / -EN.indd version:.

12 GS AF, AFp, AFp, AFp GS AF GS APp GS AN 0 00 A - operator GS AN GS AEp GS AMp GS AEp GS AH0 GS AH0 GS AHp GS AHp GS APp version:.0 -EN.indd

13 References to A, for use with NF C or DIN fuses Switch-disconnector-fuse switch bodies for use with NF C or DIN fuses Switch rating Fuse size Number of poles Reference Weight A For external front-mounted and RH side-mounted operators kg x GS DD 0.0 GS DD + Nc () GS DD x GS F 0.00 GS F.000 Size 00C () GS G.000 GS G.00 0 x GS J.00 GS J.000 x GS K.00 GS K.000 Size 00 GS KK.00 GS KK.000 GS F Size 00 GS LL.00 GS LL.00 Size 0 GS L.00 GS L.00 0 Size GS N.00 GS N Size GS QQ.00 GS QQ.0 0 Size GS S.000 GS S GS N Size GS V.000 For external LH side-mounted operators GS V x GS DD Nc () GS DD x GS FG 0.00 GS FG.000 Size 00C () GS GG.000 GS GG.00 0 x GS JG.00 GS JG.000 GS L x GS KG.00 GS KG.000 Size 00 GS KKG.00 GS KKG.000 Size 00 GS LLG.00 GS LLG.00 Size 0 GS LG.00 GS LG.00 0 Size GS NG.00 GS NG Size GS QQG.00 GS QQG.0 0 Size GS SG.000 GS SG Size GS VG.000 ) Nc = Switched neutral. ) Compact fuses for German market. GS VG General : pages / and / Characteristics : pages / to / Dimensions : pages / to / Schemes : page / -EN.indd version:.0

14 GS AF, AFp, AFp, AFp GS AF GS APp GS AM GS AM 0 00 A - Direct operator GS AN GS AN GS APp GS AH0 GS AH0 version:.0 -EN.indd

15 References (continued) to A, for use with NF C or DIN fuses Switch-disconnector-fuse switch bodies for use with NF C or DIN fuses Switch rating Fuse size Type of operator Number of poles Reference Weight A For direct operator x Front GS DD 0.0 kg + Nc () GS DD 0.00 GS JD 0 x RH side GS FD 0.00 GS FD.000 Size 00C () RH side GS GD.000 GS GD.00 0 x RH side GS JD.00 GS JD.000 x RH side GS KD.00 GS KD.000 Size 00 RH side GS KKD.00 GS KKD.000 GS S with handle GS AHp0 or GS AHp0 Size 00 RH side GS LLD.00 GS LLD.00 Size 0 RH side GS LD.00 GS LD.00 0 Size RH side GS ND.00 GS ND Size RH side GS QQD.00 GS QQD.0 0 Size Front GS S.000 GS S Size Front GS V.000 ) Nc = Switched neutral. ) Compact fuses for German market. GS V General : pages / and / Characteristics : pages / to / Dimensions : pages / to / Schemes : page / -EN.indd version:.0

16 A - Direct or external operator GS AEp GS AH GS AHp GS AMp GS AD GS AMp GS AEp GS AH0 version:.0 -EN.indd

17 References (continued) to A, for use with BS fuses Switch-disconnector-fuse switch bodies for use with BS fuses Switch rating Fuse size Number of poles Reference Weight A For external front-mounted and RH or LH side-mounted operator kg For direct front-mounted operator A GS DDB 0.00 GS DDB + Nc () GS DDB 0.0 For external front-mounted and RH side-mounted operators () A GS DB 0.00 GS DB.000 A-A GS GB.000 GS GB.00 0 A Ø y mm GS JB.00 GS JB.000 A GS LLB.00 GS LLB.00 GS GB B-B GS LB.00 GS LB B-B GS MMB.00 GS MMB.00 0 B B GS NB.00 GS NB.00 B B GS PPB.00 GS PPB.0 00 B B GS QQB.00 GS QQB.0 0 C -C GS SB ().000 GS SB () C C GS TB ().000 GS TB ().00 D GS VB ().000 GS VB () () Nc: switched neutral. () 0, 00 and A switch-disconnector-fuses can also be fi tted with a direct front-mounted operator. General : pages / and / Characteristics : pages / to / Dimensions : pages / to / Schemes : page / -EN.indd version:.0

18 GS AFp, AFp GS AF GS APp 0 A - operator GS AN GS AN GS AEp GS AMp GS AEp GS AH0 GS AH0 GS AH0 GS APp version:.0 -EN.indd

19 References to A Auxiliary contacts Auxiliary early break and/or O, I and Test position signalling contacts () () () Switch rating Contact type Type of operator Reference Weight A N/O, front or side-mounted () GS AM 0.00 kg N/C, front or side-mounted () GS AM 0.00 Auxiliary O, I and Test position signalling contacts () () Switch rating Contact type Type of operator Reference Weight GS AMpp A Auxiliary O and I position signalling contacts 0 N/C + N/O, front or RH side-mounted Direct kg GS AN 0., LH side GS ANG 0. N/C + N/O, front or RH side-mounted Direct GS AN 0., LH side GS ANG 0. Auxiliary O, I and Test position signalling contacts () 0 00 N/C + N/O, front side-mounted GS ANT 0. GS ANppp N/C + N/O, front side-mounted GS ANT 0. Auxiliary early break and O and I position signalling contacts Switch rating Contact type Type of operator Reference Weight A C/O GS AM 0.00 C/O GS AM 0.00 kg 0 00 C/O Direct, RH side GS AM 0.0 GS AMp C/O Direct, RH side GS AM 0.0 Auxiliary blown fuse signalling contacts for use with NF C and DIN fuses () Contact type Switch rating Fuse size Number of poles Reference Weight A st C/O 0 x or GS AF and x GS AF 0.0 kg GS AF 0.0 Size 0 GS AF 0.0 GS AF and 00 Size and Size GS AF 0.0 GS AF Size GS AF 0.0 GS AF 0.0 Size GS AF 0.00 GS AMp GS AF 0.0 nd C/O 0 or GS AF 0.0 () For A switch-disconnector-fuses, these auxiliary contacts allow: - early break and O and I position signalling, - O and I position signalling, - O, I and Test position signalling, - Test position signalling. For 0 to 00 A switch-disconnector-fuses, they allow: - early break, - O and I position signalling, - O, I and Test position signalling, - Test position signalling. For 0 and A switch-disconnector-fuses, they allow: - early break and O and I position signalling, () Maximum number of auxiliary contacts: Switch rating A Standard With additional bracket Reference of additional bracket + GS AD 0 + GS AD GS AD0 0 () The Test position allows testing of the control circuits off-load. Auxiliary contacts GS AM, GS AM and GS ANTpp only allow the text function with external handles GS AHTppp. () These auxiliary contacts can also be used with 0, 00 and A switch-disconnector-fuses fi tted with a direct frontmounted operator. () Reversible add-on attachments for converting an N/C contact to an N/O contact and vice versa. () For striker fuses (BS fuses are not available with striker). General : pages / and / Characteristics : pages / to / Dimensions : pages / to / Schemes : page / -EN.indd version:.0

20 References to A Handles for external operators GS AHp GS AHp0 GS AHp0 GS AHp0 Handles for external operator Switch rating Handle colour Degree of protection Reference Weight A Handles for front-mounted external operators, padlockable and lockable in position O () Door interlock in I position () Black/Grey IP GS AH 0.00 IP GS AH 0.00 Red/Yellow IP GS AH Black/Grey IP GS AH0 0.0 IP GS AH 0.0 Red/Yellow IP GS AH and 00 Black/Grey IP GS AH0 0.0 Red/Yellow IP GS AH0 0.0 Black/Grey IP GS AH0 0.0 Red/Yellow IP GS AH0 0.0 Handles for front-mounted external operators with test facility (), padlockable and lockable in "O" position (). Door interlock in I position () Black/Grey IP GS AHT 0.00 Red/Yellow IP GS AHT Black/Grey IP GS AHT0 0.0 Red/Yellow IP GS AHT0 0.0 Handles for external RH side-mounted operators, padockable and lockable in "O" position () Black/Grey IP GS AH 0.00 IP GS AH 0.00 Red/Yellow IP GS AH Black/Grey IP GS AH0 0.0 IP GS AH 0.0 Red/Yellow IP GS AH Black/Grey IP GS AH0 0.0 Red/Yellow IP GS AH0 0.0 kg GS AHp0 GS AHp0 GS AHp0 GS AHp0 Handles for external LH side-mounted operators, padockable and lockable in "O" position () Black/Grey IP GS AH 0.00 Red/Yellow IP GS AH Black/Grey IP GS AH0 0.0 Red/Yellow IP GS AH Black/Grey IP GS AH0 0.0 Red/Yellow IP GS AH0 0.0 Shafts for external operators Switch rating Shaft length Shaft cross section Reference Weight A mm mm kg 00 x GS AE x GS AE x GS AE x GS AE 0. 0 x GS AE x GS AE x GS AE x GS AE x GS AE 0.0 () Lockable with device GS AX, to be ordered separately. () Door interlock override by means of a tool. () The Test facility allows testing of the control circuits off-load, by using auxiliary contacts GS AM, GS AM or GS ANTpp. In the Test position, the enclosure door can be opened. 0 version:.0 -EN.indd

21 References to A Handles for external operators Accessories GS AH0 GS AH0 Handles for external operators Switch rating Type of operator Handle colour Reference Weight A Handles for direct operators, padlockable Front Black GS AH and RH side Black GS AH RH side Black GS AH and 00 Front Black GS AH 0.0 Front Black GS AH 0.00 Terminal protection shrouds for upstream or downstream connector plates Switch rating Number of poles Reference Weight A 0 and or () 0 GS AP 0.0 GS AP GS AP 0.0 GS AP GS AP 0.0 GS AP 0.0 GS AP 0.0 GS AP 0.0 Devices for locking fuse covers in "I" position () Switch rating Fuse size Number of poles Reference Weight A 0 x or () Size 00C or GS AV x, Size 00 or GS AV 0.00 Size 0 GS AV 0.0 GS AV Size GS AV 0.0 GS AV Size GS AV 0.0 GS AV 0.0 Cage terminals for connection of bare cables (without lug) Switch rating Number of poles Reference Weight A 0 and or () 0 GS AW 0. GS AW GS AW 0. GS AW 0.0 handle locking device Switch rating Description Reference Weight A Device for RONIS ELAP key lock (lock to be ordered separately). kg kg kg kg kg GS AX 0.00 Height compensation plate for external handles Switch rating A Allows a new GSpp handle to be fi tted on existing cut-outs Description Degree of protection Reference Weight IP GS AH Flat mounting kit Switch rating Description Reference Weight A 0 00 The kit, for use with a front-mounted external handle, includes: b a 00 mm shaft, cross section x mm, b an adapter plate () For these ratings, the switch-disconnector-fuses are fi tted with terminal covers as standard. () For NF C and DIN switch-disconnector-fuses fi tted with right-hand mounted direct operator. () For this rating, switch-disconnector-fuses are fi tted with a cover locking device as standard. () For these ratings, switch-disconnector-fuses are fi tted with cage terminals as standard. kg kg GS ADL EN.indd version:.0

22 GS DD ( A) Direct front-mounted operator GS DD GS DDB,,,,,,,,, xø,, xø front-mounted operator, GS DD Door cut-out min. (), I Ø 0 xø GS DDB 0 0 O Test Ø Door cut-out min. (), Ø 0 xø 0 () With or auxiliary contacts GS AMpp: 0 mm. () With or auxiliary contacts GS AMpp: mm. RH side-mounted operator GS DD I 0 O Test Ø Door cut-out I I Dimensions to A 0, min. 0 Ø xø O 0, 0 Ø GS DDB Door cut-out 0, min. 0 Ø xø, O 0 0 Ø Presentation: pages / and / Characteristics: pages / to / References: pages / to / Schemes: page / version:. -EN.indd

23 I Dimensions (continued) to A GS pp (0 00 A) Direct RH side-mounted operator GS FD (0 A), GD ( A), JD (0 A), KD, KKD ( A), LD, LLD ( A), ND (0 A) and QQD (00 A) c J G L G Q () K() () () 0 M H b b () O R b Ø c c R P P P a a GS a a b b b c c c G G H J K Ø L M P P Q R R Ø FD P... P... GD P... P... JD, KD P KKD, LLD P P P LD P P ND P P QQD P P () Terminal cover. () Mounting on rail only for GS FD and GS GD (0 and A). () Protective screen, lockable in I position. () or auxiliary contacts GS AFpp. () or auxiliary contacts GS AMp. Presentation: pages / and / Characteristics: pages / to / References: pages / to / Schemes: page / -EN.indd version:.

24 Dimensions (continued) to A GS pp (0 00 A) front and RH side-mounted operator GS DB ( A), F (0 A), G, GB, JB ( A), J (0 A), K, KK ( A), L, LL, LB, LLB ( A), MMB (00 A), N, NB (0 A), PPB ( A), QQ and QQB (00 A) E min. () b () c () () M M P P P b b M H Ø J G a G J J Q 0 min. 0 max. b P P b Ø c P P GS a b b b b c c E min. G G H J J J Ø M M M P P P P Q Ø F, DB P 0 () 0 (). P 0 () 0 (). G, GB P 0. (). 0 J, JB, K KK, LL L, LB, LLB MMB, NB, N PPB, QQB, QQ P 0. (). 0 P () P () P. () P. () P P P P P P () Terminal cover. () Rear access connector plates (option). () to auxiliary contacts GS AMpp. () or auxiliary contacts GS AFpp. () auxiliary contact GS AMpp: +. mm, auxiliary contacts GS AMpp: + mm. () mm with auxiliary contacts GS AMpp. Door cut-out For external front-mounted operator 0 xø Ø I 0 O Ø Test For external RH side-mounted operator 0 xø Ø I O 0 Ø Presentation: pages / and / Characteristics: pages / to / References: pages / to / Schemes: page / version:. -EN.indd

25 Dimensions (continued) to A GS pp (0 A) Direct front-mounted operator GS S, SB (0 A), TB (00 A), V and VB ( A) E min. c Q R G a, (), b 0 (), , () Ø P P c GS a b c c E min. G P Q R S, SB, TB P P V, VB P 0 P 0 () Handle GS AH for GSS, GS SB and GS TB. () Terminal cover. () Rear access connector plates (GS V and GS VB). Handle GS AH for GS V and GS VB (direct front-mounted operator) Connector plates for GS V and GS VB Ø Presentation: pages / and / Characteristics: pages / to / References: pages / to / Schemes: page / -EN.indd version:.

26 I O Dimensions (continued) to A GS pp (0 A) (continued) front and RH side-mounted operator GS S, SB (0 A), TB (00 A), V and VB ( A) E min. min. b Handle GS AH0 or GS AH0 for GS V and GS VB (external front-mounted operator) GS b E min. S, SB, TB P P V, VB P 0 0 P I 0 0 O Door cut-out For external front-mounted operator For external RH side-mounted operator 0 xø I Ø xø 0 Ø Ø 0 0 O Ø Presentation: pages / and / Characteristics: pages / to / References: pages / to / Schemes: page / version:. -EN.indd

27 Dimensions, schemes to A Dimensions with auxiliary contacts GS AM, GS AM GS AM, GS AM Schemes -pole GS -pole GS to A A 0 to A /L /L /L /L /L /L /L /L /L /L /L /T /T /T /T /T /T /T /T /T /T /T Auxiliary contacts GS AM GS AM GS AM and GS AM GS AM and GS AM N/O N/C C/O C/O p p p p GS ANpp GS AFp N/C + N/O N/C + N/O C/O C/O Presentation: pages / and / Characteristics: pages / to / References: pages / to / Dimensions: pages / to / -EN.indd version:.

28 Substitution to A Switch-disconnector-fuses, for use with NF C or DIN fuses Old GS range Reference Type of operator Reference GS DD GS DD GS F GS F New TeSys GS range GS DD GS DD GS F GS F GS FD Direct GS FD GS F GS FD Direct GS FD GS FG GS FG GS G GS G GS F GS FG GS FG GS G GS G GS GD Direct GS GD GS G GS GD Direct GS GD GS GG GS GG GS J GS J GS G GS GG GS GG GS J GS J GS JD Direct GS JD GS J GS JD Direct GS JD GS JG GS JG GS K GS K GS J GS JG GS JG GS K GS K GS KD Direct GS KD GS K GS KD Direct GS KD GS KG GS KG GS KK GS KK GS K GS KG GS KG GS KK GS KK GS KKD Direct GS KKD GS KK GS KKD Direct GS KKD GS KKG GS KKG GS L GS L GS KK GS KKG GS KKG GS L GS L GS LD Direct GS LD GS L GS LD Direct GS LD GS LG GS LG GS LL GS LL GS L GS LG GS LG GS LL GS LL GS LLD Direct GS LLD GS LL GS LLD Direct GS LLD GS LLG GS LL GS LLG version:. 0-EN.indd

29 Substitution to A Switch-disconnector-fuses, for use with NF C or DIN fuses (continued) Old GS range New TeSys GS range Reference Type of operator Reference GS LLG GS N GS N GS LLG GS N GS N GS ND Direct GS ND GS N GS ND Direct GS ND GS NG GS NG GS Q GS Q GS N GS NG GS NG GS QQ GS QQ GS QD Direct GS QQD GS QQ GS QD Direct GS QQD GS QQ GS QQ GS QQ GS QQ GS QQ GS QQD Direct GS QQD GS QQ GS QQD Direct GS QQD GS QQG GS QQG GS S GS S GS SD GS SD GS V GS V GS VD GS VD GS QQ GS QQG GS QQG GS S GS S GS S GS S GS V GS V GS V GS V 0-EN.indd version:.

30 Substitution to A Switch-disconnector-fuses, for use with BS fuses Old GS range Reference Type of operator Reference GS DB GS DB GS DBR Direct GS DBR Direct GS DDB GS DDB GS GB GS GB GS GBR Direct GS GBR Direct GS JB GS JB GS JBR Direct GS JBR Direct GS LB GS LB GS LBR Direct GS LBR Direct GS LLB GS LLB GS LLBR Direct GS LLBR Direct GS MMB GS MMB GS MMBR Direct GS MMBR Direct GS NB GS NB GS NBR Direct GS NBR Direct GS PPB GS PPB GS PPBR Direct GS PPBR Direct GS QB GS QB GS QBR Direct GS QBR Direct GS QQB GS QQB New TeSys GS range GS DB GS DB GS DB GS DB GS DDB GS DDB GS GB GS GB GS GB GS GB GS JB GS JB GS JB GS JB GS LB GS LB GS LB GS LB GS LLB GS LLB GS LLB GS LLB GS MMB GS MMB GS MMB GS MMB GS NB GS NB GS NB GS NB GS PPB GS PPB GS PPB GS PPB GS QQB GS QQB GS QQB GS QQB GS QQB GS QQB 0 version:. 0-EN.indd

31 Substitution to A Switch-disconnector-fuses, for use with BS fuses (continued) Old GS range Reference Type of operator Reference GS QQBR Direct GS QQBR Direct GS SB GS SB GS SBR Direct GS SBR Direct GS TB GS TB GS TBR Direct GS TBR Direct GS VB GS VB GS VBR Direct GS VBR Direct New TeSys GS range GS QQB GS QQB GS SB GS SB GS SB GS SB GS TB GS TB GS TB GS TB GS VB GS VB GS VB GS VB 0-EN.indd version:.

32 Substitution to A Switch-disconnector-fuses, for use with UL fuses Old GS-LK range Reference Type Reference GS DDU GS DU GS EERU0 GS EERU0 GS EEU GS EU GS GU GS JU GS MU GS QU GS SU GS TU New TeSys GS, LK range GS DDU GS DU GS EERU0 GS EERU0 GS EEU GS EU GS GU GS JU GS MU GS QU GS SU GS TU LK DU Without fuses LK DU LK GU Without fuses LK GU LK JU Without fuses LK JU LK MU Without fuses LK MU LK QU Without fuses LK QU LK SU Without fuses LK SU LK TU Without fuses LK TU LK UU Without fuses LK UU LK WU Without fuses LK WU version:. 0-EN.indd

33 Substitution to A Accessories Auxiliary contacts Old GS range Reference Type of operator Type of auxiliary contact GS AD GS AD0 GS AF GS AF GS AF GS AF GS AF GS AF GS AF GS AF GS AF GS AF GS AF GS AF GS AF GS AF GS AFF New TeSys GS range Reference GS AD GS AD0 GS AF GS AF GS AF GS AF GS AF GS AF GS AF GS AF GS AF GS AF GS AF GS AF GS AF GS AM Direct GS AM GS AM GS AM GS AM N/O GS AM N/C GS AM GS AM GS AM GS AM GS AM Direct GS AM GS AM GS AMU N/O GS AM N/C GS AM GS AM GS AMU GS AM N/O GS AM N/C GS AM GS AM N/O GS AM N/C GS AM GS AMU N/O GS AM N/C GS AM GS AMU N/O GS AM GS AN GS ANG GS AN GS ANG GS ANT GS ANT LK AD0 Handles Old GS range N/C GS AM GS AN GS ANG GS AN GS ANG GS ANT GS ANT LK AD0 Reference Range Rating Type of operator Reference GS AH0 GS AH0 New TeSys GS range GS AH0 GS AH0 GS AH A GS AH A GS AH GS AH A GS AH A GS AH GS AH IEC, RH side GS AH UL, front GS AH GS AH GS AH IEC, RH side GS AH0 UL, front GS AH0 GS AH 0-EN.indd version:.

34 Substitution to A Accessories Handles (continued) Old GS range Reference Range Rating Type of operator Degree of protection Reference GS AH New TeSys GS range GS AH GS AH IEC IP GS AH UL IP GS AH GS AH GS AH IEC GS AH0 UL GS AH GS AH0 IEC IP GS AH0 UL IP GS AH GS AH0 GS AH IEC GS AH0 UL GS AH GS AH IEC 0-00 A GS AH0 UL A GS AH0 GS AH GS AH IEC 0-00 A GS AH0 GS AH GS AH UL A GS AH0 GS AH GS AH GS AH GS AH IP GS AH GS AH0 IP GS AH GS AH0 GS AH0 IP GS AH0 GS AH0 GS AH0 GS AH0 GS AH GS AH GS AH0 GS AH GS AH0 GS AH0 GS AH GS AH0 GS AH0 GS AH0 IP GS AH GS AH0 GS AH0 GS AH0 GS AH GS AH GS AH0 GS AH0 GS AH0 GS AH0 GS AH GS AH0 GS AH0 GS AH0 GS AHT IEC GS AHT UL GS AHT GS AHT IEC GS AHT0 UL GS AHT GS AHT0 IEC GS AHT0 UL GS AHT0 GS AHT IEC GS AHT0 GS AHT GS AHT0 GS AHT0 GS AHT0 LK AH LK AH LK AH LK AH UL GS AHT GS AHT GS AHT0 GS AHT0 GS AHT0 GS AH GS AH GS AH GS AH version:. 0-EN.indd

35 Substitution to A Accessories Other accessories Old GS range Reference Range Reference GS ADL GS AE GS AE GS AE GS AE New TeSys GS range GS ADL GS AE GS AE GS AE GS AE GS AE GS GS AE LK GS AE GS AE GS GS AE GS AE GS AE GS AE GS AE GS AE GS AE GS AP GS AP GS AP GS AP GS AP GS AP GS AP GS AP GS AP GS AP GS AP GS AP GS APU GS AS GS AU0 GS AU0 GS AU0 GS AU0 GS AU0 GS AV GS AV GS AV GS AV GS AV GS AV GS AV GS AV GS AV GS AV GS AV GS AV GS AW GS AW GS AW GS AW GS AX GS AX GS AX GS AXU LK AP LK AP LK GS AE GS AE GS AE GS AE GS AE GS AE GS AP GS AP GS AP GS AP GS AP GS AP GS AP GS AP GS AP GS AP GS APU GS AU0 GS AU0 GS AU0 GS AU0 GS AU0 GS AV GS AV GS AV GS AV GS AV GS AV GS AV GS AV GS AW GS AW GS AW GS AW GS AX GS AX GS AX GS AXU LK AP LK AP 0-EN.indd version:.

TeSys GS. Data for Designers. Contents

TeSys GS. Data for Designers. Contents TeSys GS Technical Data for Designers Contents Characteristics: > switch-disconnector... B5/16 to B5/21 > auxiliary contacts...b5/22 Dimensions... B5/23 to B5/31 Schemes...B5/31 B5/15 Characteristics -

More information

FUSERBLOC Fuse combination switches with rear connection for industrial fuses up to 400 A

FUSERBLOC Fuse combination switches with rear connection for industrial fuses up to 400 A Fuse protection fuser_737_a_1_cat.eps fuser_738_a_1_cat.eps The solution for > Motor load break > Protection of industrial processes FUSERBLOC REAR / FRONT connections 3 x 250 A fuser_739_a_1_cat.eps Strong

More information

3 - Protection components Motor circuit-breakers

3 - Protection components Motor circuit-breakers Contents 0 - Protection components Motor circuit-breakers protection components for the motor protection Thermal-magnetic motor circuit-breakers Selection guide..............................................page

More information

FUSOMAT Visible breaking and tripping fuse switches from 250 to 1250 A

FUSOMAT Visible breaking and tripping fuse switches from 250 to 1250 A Fuse protection The solution for > Motor load break > Protection of industrial cabinet > Electrical distribution fusom_063_b_1_cat Strong points > Tripping upon overload > High breaking capacity > Improved

More information

FUSERBLOC Fuse combination switches for industrial fuses up to 1250 A

FUSERBLOC Fuse combination switches for industrial fuses up to 1250 A Fuse protection fuser_548_a cat The solution for > Motor load break. > Protection of industrial cabinet. FUSERBLOC 6 to 25 A Strong points fuser_52_a cat Function FUSERBLOC 2 to 4 A FUSERBLOC are manually

More information

FUSERBLOC Fuse combination switches for industrial fuses up to 1250 A

FUSERBLOC Fuse combination switches for industrial fuses up to 1250 A Fuse protection fuser_548_a_1_cat The solution for > Motor load break > Protection of industrial processes FUSERBLOC 63 to 125 A Strong points fuser_532_a_1_cat Function FUSERBLOC 32 to 4 A FUSERBLOC are

More information

Vistop TM isolating switches 63 to 160A

Vistop TM isolating switches 63 to 160A DX 3 - IS main switches 16 to 125A Vistop TM isolating switches 63 to 160A 225 15 225 18 4 064 00 4 064 59 Pack Cat. No. Main switches AC 22 A category as per EN607-3 Grey handle Accept 1 signalling auxiliary

More information

Characteristics TeSys contactors 0 TeSys k contactors and reversing contactors

Characteristics TeSys contactors 0 TeSys k contactors and reversing contactors 90 Characteristics TeSys contactors 0 TeSys k contactors and reversing contactors Environment characteristics Conforming to standards IEC 60947, NF C 63-110, VDE 0660, BS 5424 Product certifications LCp

More information

GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Standard Features

GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Standard Features Standard Features Table : Standard Features GV2ME GV2P GV3P GV7RE/GV7RS 0. to 32 A Up to 20 hp @ 460 V 0 SCCR @ 480 V Push Button Operator 0. to 30 A Up to 5 hp @ 460 V 50 SCCR @ 480 V Rotary Handle Operator

More information

TeSys contactors. Use in category DC-1 (resistive loads; time constant L/R y 1 ms) Rated operational current Ie. to be wired in series

TeSys contactors. Use in category DC-1 (resistive loads; time constant L/R y 1 ms) Rated operational current Ie. to be wired in series Selection 3-pole shockproof contactors FG d.c. supply Selection guide for utilisation categories DC-1 to DC-5 Use in category DC-1 (resistive loads; time constant L/R y 1 ms) Rated operational current

More information

Motor control The essential guide

Motor control The essential guide Motor control The essential guide Motor control TeSys Accurate and reliable control of motors TeSys range provide you more simplicity, compactness, openness and flexibility... so many evolutions and new

More information

Protection components

Protection components Presentation, characteristics Presentation 1 2 3 motor circuit-breakers are 3-pole thermal-magnetic circuit-breakers standards IEC 60947-2 and IEC 60947-4-1. Connection These circuit-breakers are designed

More information

SIRCO UL98 Load break switches standards UL and CSA 100 to 1200 A

SIRCO UL98 Load break switches standards UL and CSA 100 to 1200 A The solution for Load break switches sirco-ul_022_b_1_cat > Power distribution. Strong points sirco_093_b_1_cat SIRCO 3 x 200 A > Reliability. > Safety of property and personnel. > Simplicity. > Easy assembling.

More information

References 4 Fuse carriers

References 4 Fuse carriers References components 000_ -pole basic blocks Rating Cartridge fuse size umber of early break contacts () Single-phase protection device () Reference () Connection by spring terminals A 0 x 8 () Without

More information

PowerLine OS Switch Fuses A, 690V

PowerLine OS Switch Fuses A, 690V Technical Brochure PowerLine OS Switch Fuses 20...160 A, 690V Brochure OS 10 GB 99-04 9902CD04 ABB Control New Switch Fuse Range 2 3 Total user safety Total user safety Fuse carriers fully IP20 protected

More information

Contact gap 7 mm (norm >5.5 mm) ÿ IN ENCLOSURE. ÿ WITH CLUTCH DRIVE

Contact gap 7 mm (norm >5.5 mm) ÿ IN ENCLOSURE. ÿ WITH CLUTCH DRIVE Switch disconnectors A modular and flexible range Contact gap 7 mm (norm 5.5 mm) Reversible terminal feature ÿ IN ENCLOSURE - Degree of protection: up to IP 66 - For 25A to 100A size switches (see Ithe

More information

SIRCO UL98 Non-fusible switches standards UL and CSA 100 to 1200 A

SIRCO UL98 Non-fusible switches standards UL and CSA 100 to 1200 A Non-fusible disconnect switches SIRCO UL98 Non-fusible switches standards UL and CSA sirco-ul_022_b_1_cat The solution for > Power distribution sirco_093_b_1_cat SIRCO 3 x 200 A Strong points > Reliability

More information

MSW. MSW Catalog Number Sequence. Standard Features MSW 25 B- 3

MSW. MSW Catalog Number Sequence. Standard Features MSW 25 B- 3 Introducing the New WEG Series. The was developed according to IEC 60947-3 & UL508. The compact, reliable design of the allows the operator to safely disconnect power and isolate the circuit within the

More information

K50H004UP cam changeover switch - 4-pole A - screw mounting

K50H004UP cam changeover switch - 4-pole A - screw mounting Characteristics cam changeover switch - 4-pole - 60-50 A - screw mounting Main Range of product Product or component type Component name [Ith] conventional free air thermal current Mounting location Fixing

More information

AF40... AF96 3-pole contactors Technical data

AF40... AF96 3-pole contactors Technical data Main pole - Utilization characteristics according to IEC Standards IEC 60947- / 60947-4- and EN 60947- / 60947-4- Rated operational voltage Ue max. 690 V Rated frequency (without derating) 50 / 60 Hz Conventional

More information

K30H001YP cam star-delta switch - 3-pole A - screw mounting

K30H001YP cam star-delta switch - 3-pole A - screw mounting Characteristics cam star-delta switch - 3-pole - 60-32 A - screw mounting Main Range of product Product or component type Component name [Ith] conventional free air thermal current Mounting location Fixing

More information

125 to 4000 A. Functions. Conformity to standards. Approvals and certifications (1) General characteristics. Available on request

125 to 4000 A. Functions. Conformity to standards. Approvals and certifications (1) General characteristics. Available on request 125 to 4000 A sirco_353_a_1_cat sirco_296_a_1_cat sirco_300_b switches are manually operated or motorised multipolar load break switches. They break on and off under load and provide safety isolation for

More information

Introduction. Standard Features. GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Introduction

Introduction. Standard Features. GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Introduction Introduction Introduction Schneider Electric offers a complete line of products for the manual control and protection of motors. This catalog covers those devices designed to meet IEC standards for protection

More information

SIRCO M and MV Universal load break switches from 16 to 160 A

SIRCO M and MV Universal load break switches from 16 to 160 A SRCO M and MV from 16 to 16 A The solution for Load break switches sircm_99_a > Main incoming load break > Distribution load break > Machine control > Local safety load break sircm_13_a 4 pole SRCO MV

More information

MANUALLY OPERATED CHANGEOVER SWITCHES

MANUALLY OPERATED CHANGEOVER SWITCHES are manually operated multipolar changeover switches. They changeover between two low voltage power circuits under load and provide safety disconnection. Application: NORMA/EMERGENCY Application: UPS,

More information

SWITCH FUSES 3KL71 from 32A to 800A Description

SWITCH FUSES 3KL71 from 32A to 800A Description from 32A to 800A Description SWITCH FUSES 3KL71 3KL71 is a range of load-break switches suitable for making and breaking on load and disconnetting low voltage electrical circuits. They are commonly used

More information

TeSys contactors 5. Characteristics 5. Mini-contactors TeSys LC1 SK and LP1 SK. Environment Rated insulation voltage (Ui) 5/30

TeSys contactors 5. Characteristics 5. Mini-contactors TeSys LC1 SK and LP1 SK. Environment Rated insulation voltage (Ui) 5/30 Characteristics TeSys contactors Mini-contactors TeSys LC SK and LP SK Environment Rated insulation voltage (Ui) Conforming to 0, VDE 00 gr C,BS, CSA - n, UL 0 V 0 Conforming to standards IEC 0, NF C -0,

More information

DPX moulded case circuit breakers

DPX moulded case circuit breakers BREAKING AND PROTECTION DEVICES 10 / 2011 DPX moulded case circuit breakers DPX moulded case circuit breakers offer optimum solutions for the protection requirements of commercial and industrial installations.

More information

Manual Motor Starters. Meta-MEC

Manual Motor Starters. Meta-MEC Manual Motor Starters Meta-MEC Manual Motor Starters LS Meta-MEC Manual Motor Starters provide completed ranges up to 100A 45 mm 55 mm 32AF 2 2 45 mm 70 mm 63AF 100AF 3 3 Manual LS Meta-MEC Motor Starters

More information

SIDERMAT Load break switches for power distribution from 250 to 1800 A with tripping function

SIDERMAT Load break switches for power distribution from 250 to 1800 A with tripping function The solution for Load break switches sdmat_066_a cat > Main switchboard > Distribution panel > Motor load break unction SIDERMT 4 x 630 External front operation SIDERMT are manually operated 3 or 4 pole

More information

AF40... AF96 3-pole contactors 30 to 60 hp at 480 V AC AC / DC operated with 1 N.O. + 1 N.C. auxiliary contacts

AF40... AF96 3-pole contactors 30 to 60 hp at 480 V AC AC / DC operated with 1 N.O. + 1 N.C. auxiliary contacts AF4... AF96 -pole contactors to 6 hp at 48 V AC AC / DC operated with N.O. N.C. auxiliary contacts Description AF4... AF96 contactors are mainly used for controlling -phase motors and power circuits up

More information

Non-fusable disconnect switches standards UL and CSA from 16 to 100 A

Non-fusable disconnect switches standards UL and CSA from 16 to 100 A Non-fusible disconnect switches sircm_132_a sircm_133_a The solution for > Industrial control systems Rotary switch SIRCO M 3 x 80 A Toggle switch SIRCO M 3 x 80 A + 2 auxiliary contacts Competitive advantages

More information

Modular contactors and relays

Modular contactors and relays pages /4 to / pages /8 and /9 pages /10 and /11 pages /12 and /13 Presentation and standards Presentation Designed for use in modular panels and enclosures, these contactors feature : i Easy installation

More information

ATyS d M Remotely operated Transfer Switching Equipment from 40 to 160 A

ATyS d M Remotely operated Transfer Switching Equipment from 40 to 160 A ATyS d M Remotely operated Transfer Switching Equipment Transfer switches new The solution for > Applications with an external ATS/AMF controller > Building Management Systems (BMS) atys-md_002_b_1_cat

More information

Index. Manual Motor Starters 1. Auxiliary Contact Blocks 1. Trip Alarm Auxiliary 1. Switch. Shunt Release 1. Under-voltage Release 2.

Index. Manual Motor Starters 1. Auxiliary Contact Blocks 1. Trip Alarm Auxiliary 1. Switch. Shunt Release 1. Under-voltage Release 2. Index Index Page Manual Motor Starters 1 Auxiliary Contact Blocks 1 Trip Alarm Auxiliary 1 Switch Shunt Release 1 Under-voltage Release 2 Accessories 2 Busbar Connectors 2 Enclosures 2 Leistung, kw C mv

More information

Protection Equipment. 5/2 Introduction

Protection Equipment. 5/2 Introduction Protection Equipment /2 Introduction SIRIUS 3RV2 Motor Starter Protectors/ Circuit Breakers up to 40 A /6 General data /12 For motor protection /14 For motor protection with overload relay function /1

More information

Essential equipment for all your requirements

Essential equipment for all your requirements NEW CTX CONTACTORS Essential equipment for all your requirements 9 A TO 310 A THREE-POLE INDUSTRIAL CONTACTORS CTX three-pole industrial contactors, a sense of family The new range of CTX contactors provides

More information

Industrial Contactors CTX 3 3P 185A - 800A

Industrial Contactors CTX 3 3P 185A - 800A 87045 LIMOGES Cedex Telephone: +33 5 55 06 87 87 FAX: +33 5 55 06 88 88 Industrial Contactors CONTENTS PAGES 1. Description - Use... 1 2. Range... 1 3. Overall dimensions... 1 4. Installation - Connection...

More information

Switches disconnectors with fuse-holders. XNF series TF series

Switches disconnectors with fuse-holders. XNF series TF series Switches disconnectors with fuse-holders XNF series TF series Quick Reference Switch-disconnectors with fuse-holders XNF series TF series XNF Series page 155 16 32A with fuse holders 3 4 Pole Auxiliary

More information

DPX Thermal magnetic and trip-free switches DPX 3 -I 160

DPX Thermal magnetic and trip-free switches DPX 3 -I 160 87045 LIMOGES Cedex Phone :+33 05 55 06 87 87 Fax :+33 05 55 06 88 88 DPX 3 160 CONTENTS PAGES 1. USE 1 2. RANGE 1 3. DIMENSIONS 1 4. OVERVIEW 2 5. ELECTRICAL AND MECHANICAL CHARACTERISTICS 3 6. CONFORMITY

More information

UltraSafe US22 Modular fuse-holders

UltraSafe US22 Modular fuse-holders UltraSafe US22 FUSE HOLDERS, FUSE BASES AND SUPPORTS UL/CSA FUSE HOLDERS FEATURES & BENEFITS The innovative and comprehensive UltraSafe range of Mersen fuse-holders. are finger-safe under IEC standards

More information

Protection Equipment

Protection Equipment Protection Equipment Price Groups 101, 102, 121, 131, 143 /2 Introduction Motor Starter Protectors/ Circuit Breakers SIRIUS 3RV2 Motor Starter Protectors up to 40 A new /7 General data /13 For motor protection

More information

AF09... AF30 3-pole Contactors up to 25 HP / 600 VAC

AF09... AF30 3-pole Contactors up to 25 HP / 600 VAC AF09... AF0 -pole Contactors up to 25 HP / 600 VAC Contactors and Overload Relays Overview.../0 AF09... AF0 -pole Contactors.../2 Main Technical Data.../8 Main Accessory Fitting Details.../2 Main Accessory.../24

More information

SD Series Non-Fused Load Switches

SD Series Non-Fused Load Switches SD Series Non-Fused Load Switches The SD1 and SD2 series of non-fused load switches are listed as Manual Motor Controllers and are designed for use in local motor isolation. The SD series of modular load

More information

C -5 to +55 (0.8 to 1.1Uc) Permissible o

C -5 to +55 (0.8 to 1.1Uc) Permissible o T - Line Contactors 3 & 4 Pole Contactors with C operating coils General Characteristics Type Unit TC1-D09 ~ TC1-D95 Rated insulation voltage (Ui) (Conforming to IEC 158-1) V 750 VDEO 110grC/IEC 60947-4

More information

Emergency stop without emergency switching off/emergency stop function. Locking facility Lockable in the 0 (Off) position N/O 0 B 0

Emergency stop without emergency switching off/emergency stop function. Locking facility Lockable in the 0 (Off) position N/O 0 B 0 MainswitchSurfacemounting Partno. T0-2-1/I1/SVB-SW Articleno. 207148 IP65 Deliveryprogramme Product range Switch-disconnectors Basic function Main switches Maintenance switches Manual override switches

More information

Emergency stop As an emergency switching off/emergency stop device. Standards According to IEC/EN , VDE 0113 Part 1

Emergency stop As an emergency switching off/emergency stop device. Standards According to IEC/EN , VDE 0113 Part 1 MainswitchSurfacemounting Partno. T0-2-8900/I1/SVB Articleno. 207151 CatalogNo. CT02-8900-I1CRQ Deliveryprogramme Product range Switch-disconnectors Basic function Main switches Maintenance switches Manual

More information

CI-TI Contactors and motor starters Types CI 61 - CI 98

CI-TI Contactors and motor starters Types CI 61 - CI 98 Data sheet CI-TI Contactors and motor starters s CI 6 - CI 98 Contactors CI 6, CI 7, CI 86 and CI 98 switch powers of up to 0 kw, 7 kw, 45 kw and 55 kw respectively under 80 V - loads. Accessories include

More information

SIRIUS 3RU2 Thermal Overload Relays

SIRIUS 3RU2 Thermal Overload Relays Overview 1 2 3 4 6 1 2 NSB0_0207a Connection for mounting onto contactors: Optimally adapted in electrical, mechanical and design terms to the contactors. The overload relay can be connected directly to

More information

25A 25A 32A 40A 40A 63A 63A 80A

25A 25A 32A 40A 40A 63A 63A 80A ISDC Compact Range 25A - 200A Control Panel Isolation Equipment Craig & Derricott has ranges of Switch-Disconnectors, Fuse Combination Units and Changeover Isolators for panel mounting ranging from 25A

More information

XCKJ390559H29EX limit switch XCKJ - round rod Ø 6 mm - 2NC + NO - ATEX/IECEx

XCKJ390559H29EX limit switch XCKJ - round rod Ø 6 mm - 2NC + NO - ATEX/IECEx Characteristics limit switch XCKJ - round rod Ø 6 mm - 2NC + NO - ATEX/IECEx Main Range of product OsiSense ATEX D Series name Standard format Product or component type Limit switch Device short name XCKJ

More information

A compact range of Switch-Disconnectors with the capacity to add auxiliary and neutral block options to the basic load break switch block.

A compact range of Switch-Disconnectors with the capacity to add auxiliary and neutral block options to the basic load break switch block. PNE ISOTORS Craig & Derricott has a range of products designed specifically for control panel and switchboard construction. Most panels require a means of electrical isolation and the can offer variants

More information

CTX 3 Control relays Cat. N (s) : /06/09..14/16/19..24/26/29

CTX 3 Control relays Cat. N (s) : /06/09..14/16/19..24/26/29 87045 LIMOGES Cedex Telephone: +33 5 55 06 87 87 FAX: +33 5 55 06 88 88 CTX 3 Control relays Cat. N (s) : 4 168 00..04/06/09..14/16/19..24/26/29 CONTENTS PAGES 1. Description - Use... 1 2. Range... 1 3.

More information

Phelan. Electromec ELECTROMEC LOAD BREAK SWITCHES. APPROVALS For Canada and US APPLICATIONS DESIGN FEATURES

Phelan. Electromec ELECTROMEC LOAD BREAK SWITCHES. APPROVALS For Canada and US APPLICATIONS DESIGN FEATURES DESIGN FEATURES Double break contacts Polycarbonate shroud for wired terminal protection included Excellent switching & high short circuit capacity Compact and reliable Easy installation Front, rear and

More information

An innovative technology

An innovative technology The range An innovative technology Description The new are load break switches that combine attractive style and optimised features due to their innovative design. This range, dedicated to industrial applications,

More information

Cylindrical fuse-link

Cylindrical fuse-link Cylindrical fuse-link Technical data Rated voltage Rated current Rated frequency Rated breaking capacity Characteristics ody material 00 V AC, 00 V AC, 90 V AC CH 8 - A/00 V CH 0,- A/00 V, 0-3 A/00 V CH

More information

K50F003UP cam changeover switch - 3-pole A - screw mounting

K50F003UP cam changeover switch - 3-pole A - screw mounting Characteristics cam changeover switch - 3-pole - 60-50 A - screw mounting Complementary Main Range of product Product or component type Component name [Ith] conventional free air thermal current Product

More information

K63F003UP cam changeover switch - 3-pole A - screw mounting

K63F003UP cam changeover switch - 3-pole A - screw mounting Characteristics cam changeover switch - 3-pole - 60-63 A - screw mounting Complementary Main Range of product Product or component type Component name [Ith] conventional free air thermal current Product

More information

Approvals UL 508; CSA-C22.2 No ; CSA-C22.2 No. 94; IEC/EN ; CE marking

Approvals UL 508; CSA-C22.2 No ; CSA-C22.2 No. 94; IEC/EN ; CE marking MainswitchSurfacemounting Partno. P1-25/I2/SVB-SW Articleno. 207294 IP65 Deliveryprogramme Product range Switch-disconnectors Basic function Main switches Maintenance switches Manual override switches

More information

Load break switches. Load break switches for all your applications... Why choose a load break switch designed for photovoltaic applications?...

Load break switches. Load break switches for all your applications... Why choose a load break switch designed for photovoltaic applications?... Load break switches Load break switches for all your applications.................................... Why choose a load break switch designed for photovoltaic applications?............. Load break switch

More information

AF series contactors (9 2650)

AF series contactors (9 2650) R E32527 R E39322 contactors General purpose and motor applications AF series contactors (9 2650) 3- & 4-pole contactors General purpose up to 2700 A Motor applications up to 50 hp, 900 kw NEMA Sizes 00

More information

SIRCOVER. Manual Transfer Switching Equipment from 125 to 3200 A. Transfer switches. Function. Advantages. The solution for.

SIRCOVER. Manual Transfer Switching Equipment from 125 to 3200 A. Transfer switches. Function. Advantages. The solution for. Transfer switches svr_151_a The solution for > Manufacturing > Power distribution SIRCOVER 250 Strong points svr_214_a > Complete range > Easy to connect > Stable positions > On-load switching Conformity

More information

DCX-M. changeover switches ->CATALOGUE PAGES INSIDE THE GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES

DCX-M. changeover switches ->CATALOGUE PAGES INSIDE THE GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES DCX-M changeover switches ->CATALOGUE PAGES INSIDE THE GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES FOR COMMERCIAL BUILDINGS AND DCX-M In = 63 A Quality & design CONFORM TO EN/IEC

More information

Overload Relays. SIRIUS 3RU2 Thermal Overload Relays 3RU2 up to 40 A for standard applications. 5/78 Siemens IC Overview

Overload Relays. SIRIUS 3RU2 Thermal Overload Relays 3RU2 up to 40 A for standard applications. 5/78 Siemens IC Overview SIRIUS 3RU2 Thermal Overload Relays 3RU2 up to 40 A Overview 1 2 3 4 6 1 2 NSB0_0207a Connection for mounting onto contactors: Optimally adapted in electrical, mechanical and design terms to the contactors.

More information

Standard Interlock Safety Switches

Standard Interlock Safety Switches Subminiature Only 78 x 30 x 1m Two actuator entrances provide flexibility for installation options Integrated molded cable reduces wiring time IP67 (IEC60529) Direct Opening Action Actuators comply with

More information

Phase + Neutral, neutral on left side

Phase + Neutral, neutral on left side 87045 LIMOGES Cedex Téléphone : 05 55 06 87 87 Télécopie : 05 55 06 88 88 DX 3 MCB 10000 A / 16 ka CONTENTS PAGE 1. Description, use...1 2. Range...1 3. Overall dimensions...1 4. Preparation - Connection...1

More information

FUSERBLOC Fuse combination switches for industrial fuses up to 1250 A

FUSERBLOC Fuse combination switches for industrial fuses up to 1250 A fuser_548_a_1_cat fuser_532_a_1_cat fuser_539_a_1_cat FUSERBLOC from 25 to 32 A FUSERBLOC from 630 to 1250 A FUSERBLOC from 32 to 400 A Function FUSERBLOC are manually operated multipolar fuse combination

More information

Technical Brochure. Switch Fuses DIN and NFC-Standard. Selection Table. Brochure OESA 2DIN GB Mallipohja. Low Voltage Products

Technical Brochure. Switch Fuses DIN and NFC-Standard. Selection Table. Brochure OESA 2DIN GB Mallipohja. Low Voltage Products Technical Brochure Switch Fuses DN and NFC-Standard Selection Table Brochure ESA 2DN GB 99-12 Mallipohja Powerline S switch fuses 20...160A, 690 V Unique patented design for the 21st century Total user

More information

Manual motor protectors Type MS116 Type MS325 Type MS45X Type MS49X

Manual motor protectors Type MS116 Type MS325 Type MS45X Type MS49X Manual motor protectors Type MS116 Type MS32 Type MS4X Type MS49X Manual motor protectors MS116 MS32 MS4X MS49X Description Type MS116 Suitable for use with 3-phase motors up to 10 HP @ 480V UL ed and

More information

Contactors KNL A 68 KNL6, KNL9, KNL12, KNL16, KNL18, KNL22, KNL30. Dimensional drawing of KNL KNL6, KNL9, KNL12, KNL16, KNL18 KNL22, KNL30

Contactors KNL A 68 KNL6, KNL9, KNL12, KNL16, KNL18, KNL22, KNL30. Dimensional drawing of KNL KNL6, KNL9, KNL12, KNL16, KNL18 KNL22, KNL30 Contactors KNL KNL6, KNL9, KNL12, KNL16, KNL18, KNL22, KNL30 Adaptable to various control requirements with ability of mounting from one to four additional auxiliary contacts. Versatile product capable

More information

Limit switches. 7 Page 71. Presentation. OsiSense XC Basic Compact design, plastic, with reset knob, types XCNR and XCNTR. b XCNR.

Limit switches. 7 Page 71. Presentation. OsiSense XC Basic Compact design, plastic, with reset knob, types XCNR and XCNTR. b XCNR. Presentation Compact design, plastic, with reset knob, types XCNR and XCNTR b XCNR with cable entry v With head for linear movement (plunger) Page v With head for rotary movement (lever) Page b XCNTR with

More information

5 - Contactors. Mini-contactors type LC1 SKGC. TeSys LCp F contactors and reversing contactors

5 - Contactors. Mini-contactors type LC1 SKGC. TeSys LCp F contactors and reversing contactors Contents 0 - Contactors Selection guides.............................................page /2 b General, selection of contactors....................... pages /16 k contactors and reversing contactors b

More information

Limit switches 3. Page 92. Page 92

Limit switches 3. Page 92. Page 92 Presentation, general characteristics b XCKS with cable entry v With head for linear movement (plunger) Page v With head for rotary movement (lever) Page Environment characteristics Conformity to standards

More information

Page. Circuit-Breakers M4 2 for motor protection. Auxiliary contacts 3 Signalling switch Auxiliary releases

Page. Circuit-Breakers M4 2 for motor protection. Auxiliary contacts 3 Signalling switch Auxiliary releases Circuit Breakers M4 Page Circuit-Breakers M4 2 for motor protection Auxiliary contacts 3 Signalling switch Auxiliary releases Insulated 3-pole busbar system 4 Terminal block DIN-rail adapters 5 Busbar

More information

D509E. Manual Motor - Starters

D509E. Manual Motor - Starters D509E Manual Motor - Starters Index Page Manual Motors Starters 182 Auxilliary Contact Blocks 182 Trip Alarm Aux. Switch 182 Shunt Release 182 Under-voltage Release 183 Accessories 183 Busbar Connectors

More information

Approvals UL 508; CSA-C22.2 No ; IEC/EN ; CE marking

Approvals UL 508; CSA-C22.2 No ; IEC/EN ; CE marking MainswitchRearmounting Partno. T0-2-1/V/SVB-SW Articleno. 045992 Front IP65 Deliveryprogramme Product range Switch-disconnectors Basic function Main switches Maintenance switches Manual override switches

More information

IEC Power Control SIRIUS. Motor Starter Protectors. Revised 04/20/15. Section Overview... 1/2-1/3. Motor Starter Protectors

IEC Power Control SIRIUS. Motor Starter Protectors. Revised 04/20/15. Section Overview... 1/2-1/3. Motor Starter Protectors 04/20/15 IEC Power Control Motor Starter Protectors Contents Pages Section Overview......................... 1/2-1/3 Motor Starter Protectors 3RV20 MSP, Class 10/20.................... 1/4-1/5 3RV10 MSP,

More information

Switch Disconnectors

Switch Disconnectors Switch Disconnectors Reversible terminals allow the same switch body to be used in both front & rear mount applications 25A - 32A - 50A - 63A - 80A - A versions available Neutral pole, additional poles

More information

LC1F330M7 TeSys F contactor - 3P (3 NO) - AC-3 - <= 440 V 330 A - coil 220 V AC

LC1F330M7 TeSys F contactor - 3P (3 NO) - AC-3 - <= 440 V 330 A - coil 220 V AC Product data sheet Characteristics LC1F330M7 TeSys F contactor - 3P (3 NO) - AC-3 -

More information

Phase + Neutral, neutral on right side

Phase + Neutral, neutral on right side 87045 LIMOGES Cedex Telephone number: +33 5 55 06 87 87 Fax: +33 5 55 06 88 88 DX 3 MCB 6000 A / 10 ka Cat.. N (s): 4 074 67 / 68 / 69 / 70 / 71 / 72 / 73 / 74 / 75 / 76 / 77 / 78 / 79 ; 4 077 33 / 34

More information

15 16 MCCBs for Power Distribution Technical Specification Frame 100A 250A 250A 400A 400A 630A 800 / 1000 / 1250 Type C DN0-100 D DN1-250 N DN2-250 D N S H DN3B-400 DN3-400 D N D N S V DN3-630 DN4-1250

More information

Selection Guide Motor Control Device Solutions

Selection Guide Motor Control Device Solutions Selection Guide Motor Control Device Solutions Expect more and get it from c3controls. Our portfolio of Motor Control Devices consists of worldclass products designed and manufactured to meet your requirements

More information

ATyS t M - ATyS g M Automatic Transfer Switching Equipment from 40 to 160 A

ATyS t M - ATyS g M Automatic Transfer Switching Equipment from 40 to 160 A TyS t M - TyS g M utomatic Transfer Switching Equipment Transfer switches new The solution for > High Rise uildings > Data centre > Healthcare buildings TyS g M I-0-II P atys-mg_001_b_1_cat Function TyS

More information

Short-circuit current limiter S800-SCL-SR

Short-circuit current limiter S800-SCL-SR Short-circuit current limiter S800-SCL-SR 2 ABB Short-circuit current limiter S800-SCL-SR Self-resetting current limiting module S800-SCL-SR is ABB s innovative self-resetting current limiting module which

More information

Siemens AG Switch Disconnectors SENTRON. Configuration. Edition 10/2015. Manual. siemens.com/lowvoltage

Siemens AG Switch Disconnectors SENTRON. Configuration. Edition 10/2015. Manual. siemens.com/lowvoltage SENTRON Configuration Manual Edition 10/2015 siemens.com/lowvoltage 2 Introduction LD main control and EMERGENCY-STOP switches up to 250 A 4 Introduction 7 Front mounting 10 Floor mounting 11 Distribution

More information

LC1F500FD TeSys F contactor - 3P (3 NO) - AC-3 - <= 440 V 500 A - coil 110 V DC

LC1F500FD TeSys F contactor - 3P (3 NO) - AC-3 - <= 440 V 500 A - coil 110 V DC Product datasheet Characteristics LC1F500FD TeSys F contactor - 3P (3 NO) - AC-3 -

More information

AF / AF12Z pole Contactors AC / DC Operated - with Screw Terminals

AF / AF12Z pole Contactors AC / DC Operated - with Screw Terminals Technical Datasheet 1SBC101404D0201 24/03/11-30-10-.. / Z-30-10-.. 3-pole Contactors AC / DC Operated - with Screw Terminals (Z) contactors are used for controlling power circuits up to 690 V AC and 220

More information

, , PREPARATION - CONNECTION. Mounting:. On symmetrical EN rail or DIN 35 rail

, , PREPARATION - CONNECTION. Mounting:. On symmetrical EN rail or DIN 35 rail 87045 LIMOGES Cedex Telephone number: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 DX 3 4500 A / 6 ka CONTENTS PAGES 1. Description, use...1 2. Range...1 3. Overall dimensions...1 4. Preparation - Connection...1

More information

Switches. Fused Switches ITCP for Semiconductor Fuses 32 to 800A CONTROL: FUSE CONNECTING: SWITCHING: MECHANISM: FIXING: CONSTRUCTION:

Switches. Fused Switches ITCP for Semiconductor Fuses 32 to 800A CONTROL: FUSE CONNECTING: SWITCHING: MECHANISM: FIXING: CONSTRUCTION: Fused CONTROL: Side control, padlockable in off position by three padlocks. Safe and reliable of contact position on handles. SWITCHING: Double isolation per phase. Complete isolation of fuse when circuit

More information

Technical data OT16E3 OT160E3 UL & CSA

Technical data OT16E3 OT160E3 UL & CSA Technical data OT16E3 OT16E3 UL & CSA UL & CSA Catalog number 3 pole OT16E3 OT25E3 OT32E3 OT45E3 OT63E3 OT3E3 OT6E3 OT1E3 OT16E3 Approvals 1 2 pole N/A N/A N/A N/A N/A N/A N/A N/A UL98 & EC 3 pole UL58

More information

SIRCO MV PV Load break switches for photovoltaic applications for use up to 1000 VDC from 63 to 80 A

SIRCO MV PV Load break switches for photovoltaic applications for use up to 1000 VDC from 63 to 80 A Load break switches SIRCO MV PV sircm-pv_010_a_1_cat The solution for > Residential buildings > Buildings > Solar parks Strong points SIRCO MV PV 1000 V - 80 A direct operation > Modular device > Patented

More information

General information about motor protection

General information about motor protection Application guide General information about motor protection Typical construction of a motor starter Disconnect Switch UL 98 - UL489 CSA C22.2 # 4 CSA C22.2 # 5 Fuses SIRCO Non-Fusible Disconnect Switch

More information

XMLA002A2C11 pressure switch XMLA 2.5 bar - fixed scale 1 threshold - 1 C/O

XMLA002A2C11 pressure switch XMLA 2.5 bar - fixed scale 1 threshold - 1 C/O Characteristics pressure switch XMLA 2.5 bar - fixed scale 1 threshold - 1 C/O Product availability : Non-Stock - Not normally stocked in distribution facility Main Range of product Product or component

More information

SWITCH DISCONNECTORS PLANET -SWITCH.

SWITCH DISCONNECTORS PLANET -SWITCH. SWITCH DISCONNECTORS 6A to 600A ratings Versions: direct operating handle, door coupling and in housing Wide range of accessories Types for photovoltaic applications up to 50A. PLANET -SWITCH SEC. PAGE

More information

SIRCOVER and SIRCOVER BY-PASS. Changeover switches with fully visualised breaking from 125 to 3200 A. 274 General Catalogue SOCOMEC

SIRCOVER and SIRCOVER BY-PASS. Changeover switches with fully visualised breaking from 125 to 3200 A. 274 General Catalogue SOCOMEC and Manual Changeover Switches BY-PSS appli_114_a svr_099_b_1_cat svr_059_a_1_cat Changeover switches with fully visualised breaking from 125 to 3200 Function products are manually operated multipolar

More information

Contents. Volume 5 Motor Control and Protection CA E December

Contents. Volume 5 Motor Control and Protection CA E December Rotary Disconnects.2 R5 Series Non-Fusible 16 80A Product Description R5 Series (UL 508 listed) products are manually operated modular switches. Load break switching and isolation provide safety solutions

More information

Short form catalogue. Motor protection & control

Short form catalogue. Motor protection & control Short form catalogue Star Series Motor protection & control Motor Protection and Control up to 25 HP / 600 VAC Overview...2 Contactors and Overload Relays...11 4-pole Contactors...41 Control Relays...59

More information

DNX 3 MCB 4500 A / 6 ka Phase + Neutral, neutral on left side

DNX 3 MCB 4500 A / 6 ka Phase + Neutral, neutral on left side 87045 LIMOGES Cedex Telephone number: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 DNX 3 MCB 4500 A / 6 ka CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation

More information

AE 9... AE 40 Contactors NE... Contactor Relays

AE 9... AE 40 Contactors NE... Contactor Relays Technical data AE 9... AE 0 Contactors NE... Contactor Relays AE 9... AE 0 Contactors NE.. Contactor Relays Contents AE 9... AE 0 Contactors Description... 2 Ordering Details... 3 Technical Data... Terminal

More information

AF series contactors (9 2650)

AF series contactors (9 2650) R E32527 R E39322 contactors General purpose and motor applications AF series contactors (9 2650) 3- & 4-pole contactors General purpose up to 2700 A Motor applications up to 50 hp, 900 kw NEMA Sizes 00

More information