Siemens AG Switch Disconnectors SENTRON. Configuration. Edition 10/2015. Manual. siemens.com/lowvoltage

Size: px
Start display at page:

Download "Siemens AG Switch Disconnectors SENTRON. Configuration. Edition 10/2015. Manual. siemens.com/lowvoltage"

Transcription

1 SENTRON Configuration Manual Edition 10/2015 siemens.com/lowvoltage

2

3 2 Introduction LD main control and EMERGENCY-STOP switches up to 250 A 4 Introduction 7 Front mounting 10 Floor mounting 11 Distribution board mounting 12 Molded-plastic enclosures 1 Accessories 5TE1 switch disconnectors up to 200 A 15 Introduction 16 General data KD switch disconnectors up to 1600 A 18 Introduction 19 General data 24 Technical features 6 Dimensions and typical circuit diagrams KA, KE switch disconnectors up to 1000 A 80 Introduction 8 Floor mounting VT switch disconnectors up to 1600 A 86 Introduction 88 VT1 switch disconnectors up to 160 A 96 VT2 switch disconnectors up to 250 A 117 VT switch disconnectors up to 60 A 17 VT4 switch disconnectors up to 1000 A 18 VT5 switch disconnectors up to 1600 A KL switch disconnectors with fuses up to 800 A 146 Introduction 148 Floor mounting 150 Fuses KM switch disconnectors with fuses and isolating plug connector up to 400 A 152 Introduction 154 For snapping onto busbar system 157 Fuses 8UD1 door-coupling rotary operating mechanisms 159 For KD switch disconnectors 8UC7 door-coupling rotary operating mechanisms 161 For K switch disconnectors 164 Individual parts 165 Operating mechanisms for fixed mounting NJ62 in-line switch disconnectors with fuses up to 60 A 166 Introduction 169 General data NP1 fuse switch disconnectors up to 60 A 182 Introduction 185 Fuses 188 Dimensions, hole drilling templates, circuit diagrams NP5 fuse switch disconnectors up to 60 A 194 Introduction 198 Fuses NJ4, NJ5 in-line fuse switch disconnectors up to 2000 A 201 Introduction pole, switchable 206 -pole, switchable 207 Accessories For further technical product information: Siemens Industry Online Support: Entry type: Application example Certificate Characteristic Download FAQ Manual Product note Software archive Technical data Siemens 10/2015

4 Introduction Overview Type 1) DC isolators Available -- Not available or value on request LD20 LD21 LD22 LD25 LD27 D28 LD2 LD24 5TE1 KD KA KE Main and EMERGENCY-STOP switches Switch disconnectors Rated uninterrupted current I u At 5 C ambient temperature A 16 / 25 /2 / / / to 1600 Up to to 1600 Rated operational voltage U e 50/60 Hz AC V DC V Up to 800 1) Up to 440 Up to 440 Up to 440 Up to 440 Number of poles -pole 4-pole 6-pole Rated operational power as AC- motor load switches Operational switching of individual motors At V kw.0 / 4.0 / 5.5 / / / At V kw 5.5 / 7.5 / 9.5 / / / At 660/690 V kw 5.5 / 7.5 / 9.5 / / / Rated operational power as AC-2A main control switches, repair switches Frequent, but not operational switching of single motors At V kw 4.0 / 5.0 / 6.0 / / / At V kw 7.5 / 9.5 / 11.5 / / / / 72 / At 660/690 V kw 7.5 / 9.5 / 11.5 / / / / 60 / Mounting Standard mounting rail acc. to EN Busbar mounting Front mounting Centralized Four-hole Floor mounting Centralized Four-hole Distribution board mounting Molded-plastic enclosures Switch accessories 4th pole (N conductor) (leading switch-on, lagging switch-off) N terminals PE terminals Auxiliary contact elements VT 2 Siemens 10/2015

5 Introduction Overview (continued) Type KL KM NJ62 NP1 NP5 NJ4 NJ5 Switch disconnectors with fuses Fuse switch disconnectors Rated uninterrupted current I u At 5 C ambient temperature A 6 to to to to to to 2000 Rated operational voltage U e 50/60 Hz AC V Up to DC V Up to 440 Up to 440 Up to 440 Up to 440 Up to Number of poles 1-pole pole pole 4-pole AC-21 At 400 V At 500 V At 690 V AC-22 At 400 V At 500 V At 690 V AC-2 At 400 V At 500 V At 690 V -- Mounting Front mounting Floor mounting Busbars 40 mm mm mm Molded-plastic enclosures Switch accessories Auxiliary contact elements 1 NO or 2 NO NC or 2 NC NO + 1NC CO or 2 CO Fuse monitoring With circuit breakers With electronics -- Current transformers Available -- Not available Siemens 10/2015

6 LD Main Control and EMERGENCY-STOP Switches up to 250 A Introduction Overview NSG0_00112b 4 1 4th contact (N conductor) 2 N or PE/ground terminal, continuous Auxiliary switch 1 NO + 1 NC 4 Rotary operating mechanism, red/yellow 5 Rotary operating mechanism, black 6 Front plate, English/German 7 Terminal cover, three-pole 8 Terminal cover, single-pole The LD main and EMERGENCY-STOP switches are manually operated switch disconnectors according to IEC / VDE 0660 Part 107 (EN ) and comply with the conditions for switch disconnectors. In EN (VDE 011 Part 1), main control switches are called "disconnector units", while EMERGENCY-STOP switches are termed "devices for emergency shutdown". The LD switches for 16 to 250 A are approved according to UL 508 and can be used as "manual motor controllers" and "motor disconnects". In addition, the LD switch disconnectors have CCC certification. Maintenance personnel can protect themselves against unauthorized startup with padlocks (up to three can be fitted). The LD switches can be used in any mounting position. Application The LD switches are used for switching main and auxiliary circuits, but also for switching induction motors and other loads during maintenance and repair work. The LD switches can be used as: ON-OFF switches EMERGENCY-STOP switches Main control switches according to EN Siemens 10/2015

7 LD Main Control and EMERGENCY-STOP Switches up to 250 A Introduction Design Design of the contacts Each switch has three adjacent contact elements 1). A 4th leading contact for switching the N conductor, a continuous PE terminal, and an auxiliary switch (1 NO + 1 NC) can be fitted to each side of the switch. The auxiliary switches operate as leading contacts on opening. On opening, the NO contact opens before the main contacts, so that a contactor carries the switching capacity in the circuit and the maintenance or safety switch switches at zero current. On closing, the auxiliary switch switches later than or at the same time as the main contacts. Design of rotary operating mechanisms The rotary operating mechanisms of the switches for front or floor mounting are mounted on control cabinet doors, or on front or side panels with four-hole or center-hole mounting with a standard diameter of 22.5 mm and are operated from the outside. In their OFF position, they can be locked with up to three padlocks with a hasp thickness of 8 mm. Controls with defeatable doorcoupling rotary operating mechanism are available in addition. Switching position indicator: The switch position is clearly marked with direction arrows and an "O" for OFF and a "I" for ON at the front. Switches for front mounting: The switches for front mounting are connected directly to the rotary operating mechanism through the fixing screws or in the case of center-hole mounting a special-purpose coupling. Switches for floor mounting: The switches for floor mounting are snapped onto 5 mm standard mounting rails according to EN or screwmounted on mounting plates. The actuators are connected to the lower section of the switch through a door coupling, which can be released in its zero position, and a 00 mm long switch shaft. When the control cabinet door is open, the switch can be protected against inadvertent operation by removing the switch shaft from the lower section of the switch. The mounting depth can be adapted to individual requirements by adjusting the switch shaft length. Switches for distribution board mounting: The switches for distribution board mounting are suited for operation in distribution boards and for switching inside control cabinets or distributors. They have cap and mounting dimensions to DIN 4880 and can be fitted under the same cover together with miniature circuit breakers. The selector switches can be locked in their OFF position with up to 2 padlocks with a hasp thickness of 6 mm. Switches in molded-plastic enclosure: For surface mounting of individual main control and EMERGENCY-STOP switches, molded plastic-enclosed switches to degree of protection IP65 are used. The actuators can be locked in their OFF position with three padlocks with a hasp thickness of 8 mm. The molded-plastic enclosures each contain an N and/or a PE terminal. 1) 16 A versions have four contact elements; -pole changeover switches and 6-pole main control switches have six contact elements. Switch for front mounting with rotary operating mechanism, LD2704-0TK5 -pole changeover switch for front mounting with knob, LD2122-7UK01 Switch for floor mounting with rotary operating mechanism and door coupling, LD2144-0TK5 Switch in molded-plastic enclosure, LD2264-0TB5. Switch for front mounting with knob, LD2222-0TK1 6-pole switch for front mounting with rotary operating mechanism, LD210-VK5 Switch for distribution board mounting with knob, LD250-0TK11 Switch for floor mounting with rotary operating mechanism and defeatable door coupling, LD2217-1TL1 DC isolators, LD2265-8VQ51-0AF6 Switch for floor mounting 250 A, with rotary operating mechanism and door coupling, LD2418-0TK1 Siemens 10/2015 5

8 LD Main Control and EMERGENCY-STOP Switches up to 250 A Introduction Technical specifications Standards DIN VDE 0660, IEC Switches Type LD20 LD21 LD22 LD25 LD27 LD28 LD2 LD24 Rated insulation voltage U i V 690 Rated operational voltage U e V AC 690 Rated frequency Hz Rated impulse withstand voltage U imp kv Rated short-time withstand current (1 s current, rms value) A Short-circuit protection, max. back-up fuse (gl) A Rated conditional short-circuit current with upstream fuses ka rms at 50/60 Hz, 690 V AC Maximum permissible let-through I 2 t value ka 2 s Permissible let-through current of the fuse ka Rated uninterrupted current I u A AC-21A load-break switch Rated operational current I e A AC- motor load switches In-service switching of individual motors AC-2A main control switch Repair switch Frequent, but not in-service switching of individual motors Rating At V At V At 660/690 V Rating At V At V At 660/690 V LD main control and EMERGENCY-STOP switches for UL/CSA as "manual motor controllers" kw kw kw kw kw kw 1) Depending on the cable infeed, only small cross-sections are possible with devices in molded-plastic enclosures Power loss per conducting path at I e W Endurance mechanical Operating cycles Switching frequency 1/h 50 Permissible ambient temperature C Isolating features Up to max. V 690 Conductor cross-sections for main conductors 1) Solid or stranded mm Finely stranded with end sleeve (max.) mm Conductor cross-sections Copper cable AWG Torque for terminal Nm Touch protection according to EN Yes Auxiliary switches Rated insulation voltage U i V 500 Rated operational voltage U e V AC 500 Rated uninterrupted current I u A 10 Rated operational current I e, AC-15 At 120 V A 6 At V A At V A 1.8 At 500 V A 1.4 Short-circuit protection, aux. switch, max. back-up fuse (gl/gg) A 10 Conductor cross-sections for auxiliary conductors Connection type Terminals Solid or stranded mm 2 2 ( ), 1 4 Finely stranded with end sleeve mm 2 2 ( ) 1 x 2.5 Torque for terminal Nm 0.8 Standards UL/CSA Switches Type LD20 LD21 LD22 LD25 LD27 LD28 LD2 LD24 Rated operational voltage U e V AC Rated uninterrupted current I u A Current rating A 600 A 600 A Pilot duty P 600 P 600 P Conventional thermal current I th A Maximum rated power (AC-) 120 V HP Alternating current motors Hz 240 V HP (7.5) 2) (HP = PS) 480 V HP (15) 2) V HP (20) 2) V HP V HP Conductor cross-sections Cu cable AWG MCM400 Torque Nm ) Values in brackets apply to devices in molded-plastic enclosure Siemens 10/2015

9 LD Main Control and EMERGENCY-STOP Switches up to 250 A Front mounting Dimensional drawings Switch for center-hole mounting with rotary operating mechanism LD2.54, LD2555 N L K C M G,2 B F 24,1 A NSG0_00206 max. 5,5 mm For LD20 Base element 4-pole 22,5 Type A B C F G K L M 1) N 1) LD LD2154/LD LD ) For additional inscription label, see page 1. Switches for four-hole mounting with rotary operating mechanism LD2.0, LD2.04 M N L K C A1 G D B F A1 A NSG0_00207 max. 5,5 mm Sealing plate behind masking plate Please observe sealing position of the shaft seal For LD20 Base element 4-pole Type A B A1 C D d F G K L M 1) N 1) LD LD LD LD2704/LD ) For additional inscription label, see page 1. Switches for center-hole mounting with knob LD2.50 N M B F G L K C NSG0_00208 Drilling diagram,2 24,1 A max 5,5 mm For LD20 Base element 4-pole Type A B C F G K L M 1) N 1) LD LD2150/LD ) For additional inscription label, see page 1. Siemens 10/2015 7

10 LD Main Control and EMERGENCY-STOP Switches up to 250 A Front mounting Switches for four-hole mounting with knob LD2.22 M N K C G A1 D B F A1 A NSG0_00209 L d max. 5,5 mm Sealing plate behind masking plate Please observe sealing position of the shaft seal For LD20 Base element 4-pole Type A B A1 C D d F G K L M 1) N 1) LD LD2122/LD ) For additional inscription label, see page 1. Switches for four-hole mounting with rotary operating mechanism LD210-.V, LD220-.V..., LD2504-.V N L K C Drilling diagram M A1 G D A B F max. 5,5 mm Sealing plate behind masking plate Please observe sealing position of the shaft seal NSG0_00215 A1 d Type A B A1 C D d F G K L M 1) N 1) LD210-.V LD220-.V LD2504-.V ) For additional inscription label, see page 1. Switches for four-hole mounting with knob LD2122-.V N L K C Drilling diagram M A1 G D A B F max 5,5 mm Sealing plate behind masking plate Please observe sealing position of the shaft seal NSG0_00216 A1 d Type A B A1 C D d F G K L M 1) N 1) LD2122-.V ) For additional inscription label, see page 1. 8 Siemens 10/2015

11 LD Main Control and EMERGENCY-STOP Switches up to 250 A Front mounting Selector switches LD212-7U, LD222-7U, LD2524-7U, LD2724-7U N L K C Drilling diagram M A1 B F G NSG0_00217 A1 D d A max 5,5 mm Sealing plate behind masking plate Please observe sealing position of the shaft seal Type A B A1 C D d F G K L M 1) N 1) LD212-7U LD222-7U LD2524-7U LD2724-7U ) For additional inscription label, see page 1. Siemens 10/2015 9

12 LD Main Control and EMERGENCY-STOP Switches up to 250 A Floor mounting Dimensional drawings Switches for floor mounting with detachable rotary operating mechanism (four-hole mounting) LD2.1, LD214. N M X = L + 52 mm L1 79 K C Driling diagram Door A1 Base B1 A B F Siemens AG 2016 G F 5 L NSG0_00210 A1 D d B2 e Type A B A1 B1 B2 C D d e F G K L L1 M 1) N 1) X min LD LD211/LD LD LD2714/LD ) For additional inscription label, see page 1. Switches for floor mounting with detachable rotary operating mechanism (center-hole mounting) LD2.44, LD2. N 5 A B M G F X = L + 74 mm L1 101 K L C NSG0_00211 Drilling diagram Door,2 22,5 24,1 Base B1 B2 e Type A B B1 B2 C e F G K L L1 M 1) N 1) X min LD LD2144/LD LD ) For additional inscription label, see page 1. Switches for floor mounting with detachable rotary operating mechanism (four-hole mounting) LD211-.V N M B G X = L + 52 mm L1 79 K C NSG0_00218 Driling diagram Door A1 D A1 B2 Base B1 d A 5 L e Type A B A1 B1 B2 C D d e F G K L L1 M 1) N 1) X min LD211-.V ) For additional inscription label, see page Siemens 10/2015

13 LD Main Control and EMERGENCY-STOP Switches up to 250 A Distribution board mounting Dimensional drawings Switches for distribution board mounting LD2.0 A L K K1 C B F NSG0_ Type A B C F K K1 L LD LD LD LD LD LD ) For additional inscription label, see page 1. Siemens 10/

14 LD Main Control and EMERGENCY-STOP Switches up to 250 A Molded-plastic enclosures Dimensional drawings Switches with molded-plastic enclosure and rotary operating mechanism Metric screw connection LD2.64, LD2.65, LD2.66 A K H M Drilling diagram LD2.64 LD2.65 Drilling diagram LD2.66 A1 C F E K B B2 B1 N B1 B1 D NSG0_0021 d G Type A B A1 B1 B2 C d D E F G H K M N LD x M x M x M20, 2 x M40 LD x M2/ x M x M20, 2 x M40 LD x M50/ x M20 4 x M x M20, 2 x M50 LD2566-.V x M2/ x M20 4 x M x M20, 2 x M50 Switches in molded-plastic enclosure with knob LD2.6.-7U A K H M Drilling diagram LD2.65 Drilling diagram LD2.66 A1 C F E K B B2 B1 N B1 B1 D NSG0_00220 d G Type A B A1 B1 B2 C d D E F G H K M N LD2165-7U x M2/ x M x M20, 2 x M40 LD2265-7U x M2/ x M x M20, 2 x M40 LD2566-7U x M2/ x M20 4 x M x M20, 2 x M50 LD2766-7U x M50/ x M20 4 x M x M20, 2 x M50 12 Siemens 10/2015

15 LD Main Control and EMERGENCY-STOP Switches up to 250 A Accessories Dimensional drawings Front mounting LD92.0-0B 4th contact (N conductor) for front mounting, leading switch-on, lagging switch-off Front and floor mounting LD92.4-1B, LD92.4-B Rotary operating mechanisms for four-hole mounting, black, red/yellow A G A C B B NSE0_0094 N NSE0_00928a N C Type A B C G LD9220-0B LD9250-0BA LD9280-0B Type A B C LD9224-1B LD9224-B LD9284-1B LD9284-B LD92.4-1D, LD92.4-D Rotary operating mechanisms for center-hole mounting, black, red/yellow A C LD92.0-2B N or PE terminal For front mounting, leading switch-on, lagging switch-off B A G B NSE0_0095 Type A B C LD9224-1D LD9224-D LD9284-1D LD9284-D LD92.1-2A Terminal covers as additional touch protection For snap-fitting at top and bottom, 1-pole N NSE0_00929a N C A A-A C Type A B C G LD9200-2B LD9220-2B LD9250-2BA LD9280-2B A A B NSE0_0096 LD9286-1A, LD9286-4A Inscription labels German/English, neutral MAIN SWITCH HAUPTSCHALTER NSE0_009a Type A B C LD9201-2A LD9221-2A LD9251-2A LD9281-2A LD92.1-.A Terminal covers as additional touch protection For snap-fitting at top and bottom, 1-pole A A-A A NSE0_0097 A B C Type A B C LD9201-1A LD9221-0A LD9251-0A Siemens 10/2015 1

16 LD Main Control and EMERGENCY-STOP Switches up to 250 A Accessories Floor and distribution board mounting LD92.0-0C 4th contact (N conductor) For rear mounting, leading switch-on, lagging switch-off A G N N C B NSE0_0098a Type A B C G LD9220-0C LD9250-0CA LD9280-0C LD92.0-2C N or PE terminal continuous A G N N C B NSE0_0099a Type A B C G LD9200-2C LD9220-2C LD9250-2CA LD9280-2C LD Auxiliary switches NSJ0_ Siemens 10/2015

17 Overview The 5TE1 switch disconnectors are available from 100 A to 200 A in and 4-pole versions and can be used as main control switches, repair switches, outgoing feeder switches and emergency mains switching off device. The series corresponds to the requirements of IEC/EN and its key features are its compact and robust design, high short-circuit strength, high DC breaking capacity and comprehensive accessories. Its small footprint means it is easy to install in all types of enclosures, distribution boards and control cabinets. The devices are approved to UL 508 and KEMA certified. 5TE1 up to 200 A Introduction Benefits Transparent enclosures ensure that the contact position is always visible Contacts with double breaks ensure reliable insulation characteristics Can be locked in the OFF position to allow for maintenance work With a red knob and yellow cap, it can also be used as an emergency switching off device Technical specifications 5TE1.1 5TE1.2 5TE1. 5TE1.4 Standards IEC/EN , UL 508 Approvals UL 508 for the following types: 5TE120, 5TE10, 5TE140, 5TE1420, 5TE140 and 5TE1440. UL File No. E02554 Rated operational current I e Per cond. path At U e = 400 V A With utilization category AC-21A 415 V A V A V A Rated operational current I e Per cond. path At U e = 400 V A With utilization category AC-22A 415 V A V A V A Rated operational current I e Per cond. path At U e = 400 V A With utilization category AC-2A 415 V A V A V A Rated operational current I e 2 poles in series 110 V A With utilization category DC-2A 2 poles in series 220 V A poles in series 220 V A Rated operational voltage U e VAC According to UL: 480, acc. to IEC: 690 Rated insulation voltage U i VAC 690 Rated impulse withstand voltage U imp 2000 m kv 8 Impulse test voltage At sea level kv 12. Max. rated operational power At U e = 400 V kw With utilization category AC-2A 415 V kw V kw V kw Thermal rated current I th At 40 C, 50 C and 60 C A Rated making capacity At 415 V AC-2A A Rated breaking capacity At 415 V AC-2A A Rated ultimate short-circuit making capacity I cm Per cond. path At U e = 400 V ka V ka V ka V ka 6.7 Rated short-time withstand current I cw Per cond. path 0.25 s ka 5 6 (peak value) 1s ka 2.5 Rated conditional short-circuit current At U e = 400 V ka 50 With back-up protection with back-up fuse 415 V ka 50 With identical rated current 500 V ka V ka Capacitive load At 400 V kvar Number of poles 2//4 Rated power dissipation P v Per pole VA Frequency Hz 50/60 Conductor cross-sections Solid and stranded mm AWG cables AWG /0 8 Copper busbars mm 2 -- max Endurance Electrical Switch Mechanical cycles Acc. to UL 508 I n A UL 508 General Use 480 V FLA (Full load amperes) A UL 508 Manual Motor Controller 20 V Rating hp UL 508 Manual Motor Controller 480 V Rating hp UL 508 Short-Circuit at 480 V With Class H or K5 fuses ka With J fuses ka Siemens 10/

18 5TE1 up to 200 A General data Dimensional drawings 5TE1 switch disconnectors, 100 A and 125 A 5TE9 auxiliary switches I201_07109a ,5 9 I201_07111c TE1210 5TE1220 5TE110 5TE115 5TE120 5TE125 5TE1410 5TE1415 5TE1420 5TE1425 5TE1610 5TE1620 5TE9005 5TE9006 5TE1 switch disconnectors, 160 A and 200 A 5TE9014 locking units , x 2x x max. 8 mm ON 1 I201_07112a OFF 90 I201_07110a ,5 5TE120 5TE1240 5TE10 5TE15 5TE140 5TE1 5TE140 5TE145 5TE1440 5TE14 5TE160 5TE1640 5TE9 rotary actuators with extension shaft H 165/65 H+5 L H , H 165/65 H+5 L H ,5 H-7 2,5 SW16 6 H-7 2,5 SW16 6 I201_07205b 6 0 7,5 2 I201_07206b With 100 A and 125 A switch disconnectors 5TE9010, 5TE9011, 5TE9012, 5TE901 It is possible to open the door in a disconnected state. With 160 A and 200 A switch disconnectors 5TE9010, 5TE9011, 5TE9012, 5TE901 It is possible to open the door in a disconnected state. 16 Siemens 10/2015

19 5TE1 up to 200 A General data Circuit diagrams Graphical symbols 5TE9 auxiliary switches TE1210 5TE1220 5TE120 5TE TE110 5TE120 5TE10 5TE TE1410 5TE1420 5TE140 5TE1440 L 5TE9005 L1 L2 5TE TE1610 5TE1620 5TE160 5TE TE115 5TE125 5TE15 5TE TE1415 5TE1425 5TE145 5TE14 More information Connection of5te1. and 5TE1.4 switches, 160 A and 200 A max. 12 Nm SW 5 SW 1 I201_08070b Design From 160 A: Supplied with one terminal cover 160 A and 200 A: Version for connection with cable lug Screw fixing on base plate Installation on standard mounting rail to EN 60715, which is raised at least 5 mm from the base plate Ø 8,5 5TE900 5TE9004 SW 5 max. Ø14 20 max. max. 6 Siemens 10/

20 KD up to 1600 A Introduction Overview Devices Description Complete assemblies Complete assemblies with direct operating mechanisms Ready-to-install combinations comprising switch disconnectors and operating mechanisms - and 4-pole switch disconnectors with front operating mechanisms Connections in form of box terminal or flat terminal incl. direct operating mechanism with gray handle Basic units Front operating mechanisms 6-pole up to 1200 V DC Switch disconnectors with front operating mechanisms without handle 6-pole versions Connections in form of flat terminal (sizes 2 to 5) or box terminal (sizes 1 and 2) Operating mechanism module in the center of the switch disconnector -/4-pole up to 690 V AC / 440 V DC - and 4-pole versions Connections in form of flat terminal (sizes 2 to 5) or box terminal (sizes 1 and 2) Operating mechanism module in the center or on the left-hand side of the switch disconnector Accessories and spare parts Side operating mechanism Additional poles Switch disconnectors with side operating mechanisms - and 4-pole versions Connections in form of flat terminal (sizes 2 to 5) or box terminal (sizes 1 and 2) Operating mechanism module on the right or left-hand side of the switch disconnector Additional poles for enhanced functionality 4th contact element (switching pole) N terminal (neutral conductor terminal with removable jumper) N/PE terminal (with permanent jumper) Left: Box terminal Right: Flat terminal Direct operating mechanisms Different handles for mounting on basic units Direct operating mechanisms for direct mounting on switch disconnector Handles available in colors gray or red/yellow Door-coupling rotary operating mechanisms Different handles for mounting on basic units Door-coupling rotary operating mechanisms for operation of switch disconnector outside the control cabinet door 8UD1 series or 8UC7/KD9 series Handles available in colors gray or red/yellow 18 Siemens 10/2015

21 KD up to 1600 A General data Overview Benefits Enhanced touch protection Contact position is clearly visible Locking functions help to prevent unauthorized operation Enhanced protection against inter-phase arcing Safe use in wind farms Compact design saves space Wide variety of applications thanks to a range of different operating mechanism designs Supplementary functions can be retrofitted Various service positions are possible thanks to optimized heat dissipation Test function to ensure safe commissioning Comprehensive support through provision of CAx data KD switch disconnector, complete assembly, -pole Features -pole, 4-pole, and 6-pole versions in 5 different sizes Supplied as a complete assembly including direct operating mechanism or as a basic unit without a handle Direct operating mechanism with handle on switch disconnector Door-coupling rotary operating mechanism for operation of switch disconnector outside the control cabinet door Versions with side operating mechanisms Connections in the form of box terminals or flat terminals Floor mounting or mounting on a standard rail (sizes 1 and 2) Additional poles can be retrofitted: 4th contact element, N or N/PE terminals Auxiliary switches for querying the switch positions Suitable for AC applications up to 690 V + 10 % (wind power) Suitable for DC applications up to 1200 V Application KD switch disconnectors are designed for applications with exacting requirements. They are deployed as main control switches, EMERGENCY-STOP switches and repair switches in industrial plants, infrastructure and buildings. KD switch disconnectors are designed to switch the specified rated current on and off under load. At the same time, they constitute a safety isolating function and isolating distance in all low-voltage circuits. All KD switch disconnectors are climate-proof and meet the requirements of IEC , IEC and VDE Siemens 10/

22 KD up to 1600 A General data Design A KD switch disconnector consists of an operating mechanism module, three, four or six switching poles and a handle to operate the switch disconnector. Handles The direct operating mechanism version of the handle is mounted directly on the switch disconnector. It can also be supplied in the form of a door-coupling rotary operating mechanism for actuation of the switch disconnector outside the control cabinet door. The handle is available in gray, or colored red/yellow for use as an EMERGENCY-STOP switch. Commonly used switch disconnector variants comprising basic unit and handle are available as complete assemblies. I201_1882 Position of operating mechanism modules To allow optimum utilization of the available installation space, units with front operating mechanisms can be supplied with the operating mechanism module in various positions mounted on the left-hand side of the KD switch disconnector or in the center between the switching poles. Number of poles/ application -pole Front operating mechanism on the side Front operating mechanism in the center Handle either as direct operating mechanism or door-coupling rotary operating mechanism On units with side operating mechanisms, the operating mechanism module is positioned on the right or left-hand side of the KD switch disconnector. Side operating mechanism on the left Side operating mechanism on the right 4-pole For 1200 V DC Siemens 10/2015

23 KD up to 1600 A Additional poles All sizes of the KD switch disconnectors can be retrofitted with additional poles on a modular basis. When installing additional poles, it is important to note that only a -pole KD switch disconnector may be retrofitted with an additional switching pole with contact system (4th contact element). Additional poles (4th contact element, N or N/PE terminal) must always be mounted directly adjacent to the switch disconnector on the left or right, i.e. with sizes 1 and 2, therefore, it is not permissible to install an auxiliary switch module between the basic unit and an additional pole. General data Auxiliary switches Auxiliary switches allow remote interrogation of the contact position of the switch disconnector. Installation of auxiliary switches for sizes 1 and 2 The auxiliary switches used for sizes 1 and 2 are microswitches (changeover contacts) which can be snapped into an auxiliary switch module. This auxiliary switch module is mounted on the side of the switch disconnector in the same way as an additional pole. A maximum of two microswitches can be installed in each auxiliary switch module. I201_1884 I201_1885 Installation of an additional pole Available versions: Fourth contact element: The 4th contact element includes a contact system and is identical to the poles installed at the factory. It can be installed to upgrade a -pole switch disconnector to a disconnector with 4 poles. Auxiliary switches with auxiliary switch module for sizes 1 and 2 Installation of auxiliary switches for sizes to 5 With sizes to 5, the auxiliary switches are directly attached to the operating mechanism module. The auxiliary switch with the leading switch function is always installed in the right-hand mounting location. The other locations are provided for simultaneously switching with the main contacts. N N Fourth contact element as an additional pole N terminal (neutral conductor terminal): The N terminal does not include a contact system. A jumper can be removed in order to interrupt the electrical connection between the two terminals. An N terminal can be installed to add a non-switching N pole to a -pole disconnector. N N N terminal as non-switching pole N/PE terminal: The N/PE terminal is identical to the neutral conductor terminal. However, the electrical connection between the two terminals is permanent and cannot be interrupted by removal of a jumper. The N/PE terminal is normally deployed for applications in which it is vital to ensure that this connection can never be interrupted I201_18905 N N N/PE terminal with permanent connections Auxiliary switch, leading 2 Auxiliary switch, simultaneous Auxiliary switches directly attached to the operating mechanism module with sizes to 5. The leading auxiliary switch is highlighted in the drawing. Siemens 10/

24 KD up to 1600 A General data Switching instants of auxiliary switches The auxiliary switches can operate either simultaneously with the main contacts or function as leading switches with all sizes. KD Main circuit Auxiliary switch standard Auxiliary switch leading On Off NO NC NO NC t I201_18906 Types of mounting All KD switch disconnectors are designed for floor mounting. To ensure that the switch can be flexibly adapted to the relevant installation conditions, the mounting bracket can be rotated through 90 with size or larger. I201_18918 One of the possible functions of leading auxiliary switches is to disconnect the circuit with the assistance of a higher-level switching device, such as a circuit breaker, before the main contacts of the KD switch disconnector open. With sizes 1 and 2, the selection of the appropriate auxiliary switch module determines whether the switching instant will be leading or simultaneous. With sizes, 4 and 5, the switching instant is determined by the selection of the mounting location for the auxiliary switch on the operating mechanism module. In this case, only SB auxiliary switches with NO contacts (1 NO or 2 NO) can be used as leading auxiliary switches. Test function for auxiliary switches The test function allows a wiring check to be performed on the auxiliary switches without necessitating closure of the main contacts of the KD switch disconnector. The test function can be used as part of the commissioning process. The test function is activated by turning the handle of a direct operating mechanism in the OFF position by 25 in the counterclockwise direction. The handle must be turned 90 in the clockwise direction in order to switch the main contacts. Floor mounting method Sizes 1 and 2 can be snapped onto a standard mounting rail (TH5 according to EN 60715) as alternative mounting method. Mounting on a standard mounting rail Locking functions KD switch disconnectors can be locked by up to three padlocks in order to prevent unauthorized switch operation. A flat version of the direct operating mechanisms is available for use in confined installation spaces. This can be secured with a lock without increasing the required mounting depth. The auxiliary switch module including test function must be used for sizes 1 and 2. With sizes, 4 and 5, all installed auxiliary switches are switched when the test function is activated. I201_1887 I201_1888 I201_1886 I201_18952 Locking functions involving one or more padlocks 22 Siemens 10/2015

25 KD up to 1600 A Electrical connection KD switch disconnectors are available with a number of different terminal types. Box terminals Box terminals for sizes 1 and 2 (rated currents 16 A to 160 A) are designed to allow the speedy connection of stripped conductors. Terminal covers General data For KD switch disconnectors erected outside a control cabinet, terminal covers can be installed to provide touch protection for all terminals. Connection via box terminals Flat terminals Sizes 2 to 5 (rated currents 80 A to 1600 A) are available with flat terminals for connection of cable lugs or busbar systems. I201_1889 Terminal covers Phase barriers When long, non-insulated cable lugs are used, phase barriers provide enhanced protection against arcing. I201_18910 I201_18841 I201_18909 Connection via flat terminals Terminal covers and phase barriers can be supplied for KD switch disconnectors with flat terminals. Phase barriers Siemens 10/2015 2

26 KD up to 1600 A Technical features Overview LD main control and EMERGENCY-STOP switches KD switch disconnectors: Box terminals KD switch disconnectors: Flat terminal Size 1 2 Type LD2 0 LD2 1 LD2 2 LD2 5 KD...-.M LD2 7 LD2 8 LD2 KD...-.N LD main control and EMERGENCY-STOP switches KD switch disconnectors LD main control and EMERGENCY-STOP switches KD switch disconnectors Rated current I n A Number of poles 4 6 Connection Flat terminals Box terminals -- Operating mechanisms Front operating mechanism Side operating mechanism Operating and short-circuit behavior Rated short-time withstand current I cw (1 s current, rms value) Rated conditional short-circuit current with upstream fuses at 690 V 1) 1) Valid for the combination of KD switch disconnector and fuse type NA, characteristic gg. Available -- Not available ka ka rms For further information about LD main control and EMERGENCY-STOP switches, see Catalog LV 10, Chapter 7 Industry Mall, section "Building Technologies and Electrical Distribution" --> "Low-Voltage Components" --> "SENTRON Protection, Switching, Measuring and Monitoring Devices" --> "Switching Devices" --> "" --> "LD Main Control and EMERGENCY-STOP Switches up to 250 A" 24 Siemens 10/2015

27 KD up to 1600 A Technical features Overview (continued) LD main control and EMERGENCY-STOP switches KD switch disconnectors: Box terminals KD switch disconnectors: Flat terminal Size 4 5 Type LD24 KD...-.P KD...-.Q KD...-.R LD main control and EMERGENCY-STOP switches KD switch disconnectors Rated current I n A Number of poles 4 6 Connection Flat terminal -- Box terminals Operating mechanisms Front operating mechanism Side operating mechanism -- Operating and short-circuit behavior Rated short-time withstand current I cw (1 s current, rms value) Rated conditional short-circuit current with upstream fuses at 690 V 1) 1) Valid for the combination of KD switch disconnector and fuse type NA, characteristic gg. Available -- Not available ka ka rms For further information about LD main control and EMERGENCY-STOP switches, see Catalog LV 10, Chapter 7 Industry Mall, section "Building Technologies and Electrical Distribution" --> "Low-Voltage Components" --> "SENTRON Protection, Switching, Measuring and Monitoring Devices" --> "Switching Devices" --> "" --> "LD Main Control and EMERGENCY-STOP Switches up to 250 A" Siemens 10/

28 KD up to 1600 A Technical features Overview of components and accessories: KD switch disconnectors, /4-pole, sizes 1 and 2, box terminal I201_ KD switch disconnectors Direct operating mechanism (standard version) Direct operating mechanism (suitable for distribution boards) 8UC/KD9 Door-coupling rotary operating mechanism 8UD1 Door-coupling rotary operating mechanism N/PE terminal (with permanent jumper) 7 Neutral conductor terminal (with removable jumper) 8 Mounting bracket (spare part) 9 4th contact element 10 Auxiliary switch module 11 Auxiliary switch 26 Siemens 10/2015

29 KD up to 1600 A Technical features Overview of components and accessories: KD switch disconnectors, 6-pole for DC applications, sizes 1 and 2, box terminal I201_ KD switch disconnectors Direct operating mechanism (standard version) Direct operating mechanism (suitable for distribution boards) 8UC/KD9 Door-coupling rotary operating mechanism Mounting bracket (spare part) Bridging bar Auxiliary switch module Auxiliary switch 5 8UD1 Door-coupling rotary operating mechanism Siemens 10/

30 Siemens AG 2016 KD up to 1600 A Technical features Overview of components and accessories: KD switch disconnectors, /4-pole, size 2, flat terminal KD switch disconnectors 8 Cable connection covers 2 Direct operating mechanism (standard version) 9 N/PE terminal (with permanent jumper) Direct operating mechanism (suitable for distribution boards) 10 Neutral conductor terminal (with removable jumper) 4 8UC Door-coupling rotary operating mechanism 11 Mounting bracket (spare part) 5 8UD Door-coupling rotary operating mechanism 12 4th contact element 6 Phase barriers 1 Auxiliary switch module 7 Cable connection cover, short 14 Auxiliary switch 28 I201_ Siemens 10/2015

31 KD up to 1600 A Overview of components and accessories: KD switch disconnectors, 6-pole, size 2, flat terminal Technical features I201_ KD switch disconnectors Direct operating mechanism (standard version) Direct operating mechanism (suitable for distribution boards) 8UC/KD9 Door-coupling rotary operating mechanism 8UD1 Door-coupling rotary operating mechanism Phase barriers Bridging bar 8 Cable connection cover for bridging bars 9 Cable connection cover, short 10 Cable connection cover 11 Mounting bracket (spare part) 12 Auxiliary switch module 1 Auxiliary switch Siemens 10/

32 KD up to 1600 A Technical features Overview of components and accessories: KD switch disconnectors, /4-pole, sizes to 5, flat terminal I201_ KD switch disconnectors Direct operating mechanism 8UC/KD9 Door-coupling rotary operating mechanism 8UD1 Door-coupling rotary operating mechanism Phase barriers Cable connection covers, short 7 Cable connection covers 8 N/PE terminal (with permanent jumper) 9 Neutral conductor (with removable jumper) 10 4th contact element 11 Auxiliary switch 0 Siemens 10/2015

33 KD up to 1600 A Technical features Overview of components and accessories: KD switch disconnectors, 6-pole for DC applications, sizes to 5, flat terminal I201_ KD switch disconnectors Direct operating mechanism 8UC/KD9 Door-coupling rotary operating mechanism 8UD1 Door-coupling rotary operating mechanism Phase barriers 6 Bridging bar Cable connection cover for bridging bars 8 Cable connection cover, short 9 Cable connection cover 10 Auxiliary switch 7 Siemens 10/2015 1

34 KD up to 1600 A Technical features Technical specifications KD switch disconnectors, /4-pole, sizes 1 and 2 Standards IEC , IEC Type KD16 KD22 KD26 KD28 KD0 KD2 KD4 KD6...N Size General technical details Rated uninterrupted current I u A ) Conventional free air thermal current I th A Rated operational voltage U e At 50/60 Hz AC (tolerance up to + 10 % permissible) V 690 At DC - 2 conducting paths series-connected V 220 At DC - conducting paths series-connected V 440 Rated insulation voltage U i V 1000 Rated impulse withstand voltage U imp kv Overvoltage category III III III III III III III III Pollution degree Operating and short-circuit behavior Rated operational current I e At AC-21A, AC-22A, V A At AC-2, 400V A At AC-2, 500V A At AC-2, 690 V A At DC-21A, 220/440 V A At DC-22A, 220/440 V A At DC-2A, 220/440 V A Motor switching capacity AC-2A 2) At 400 V kw At 500 V kw At 690 V kw Rated short-time withstand current I cw ka (with t = 1 s, rms value, 690 V AC/440 V DC) Rated ultimate short-circuit making capacity I cm ka (At 690 V AC/440 V DC) Rated current of upstream fuse ) A Rated conditional short-circuit current capacity with upstream fuse ) At 400/500 V AC ka At 690 V AC ka Let-through current combined with upstream fuse ) At 400/500 V AC ka At 690 V AC ka Let-through I 2 t value with upstream fuse ) At 400/500 V ka 2 s At 690 V ka 2 s Power loss per pole with thermal current I th W Endurance, operating cycles Mechanical Electrical, at AC-2A, 690 V/ Hz Electrical, at DC-2A, 220/440 V Degree of protection With masking plate or cable connection cover IP20 IP20 IP20 IP20 IP20 IP20 IP20 IP20 Without masking plate or terminal cover IP20 IP20 IP20 IP00 4) /IP20 IP00 Ambient conditions Ambient temperature during operation C (no derating of I th at -5 to +55 C) Ambient temperature during storage C Mounting position 5) Any Main conductor connections Conductor cross-section, max. mm (95) 6) 70 (95) 6) 70 (95) 6) 70 (95) 6) 95 Busbar systems, max. dimensions (number x width x thickness) Flat terminals mm -- 1 x 20 x 7) Box terminals mm 1 x 9 x 2 1 x 14 x Tightening torque Flat terminals Nm Box terminals Nm ) Configuring note: Max. permissible operating temperature at connections 125 C. 2) Values are provided as a guide only and may vary depending on the make of motor. ) Valid for the combination of KD and fuse type NA8 for I u = A; NA1 for I u = 200 A, characteristic gg. 4) Relevant only for devices with flat terminals. 5) With mounting positions other than the vertical, please contact Technical Support. 6) 95 mm² valid for variants with flat terminals. 7) When using busbars that are 20 mm wide, these must be insulated. 2 Siemens 10/2015

35 KD up to 1600 A Technical features Technical specifications (continued) KD switch disconnectors, /4-pole, sizes to 5 Standards IEC , IEC Type KD6..-.P KD8 KD40 KD42 KD44 KD46 KD48 KD50 KD52 KD54 Size General technical details Rated uninterrupted current I u A ) Conventional free air thermal current I th A Rated operational voltage U e At 50/60 Hz AC (tolerance up to + 10 % permissible) V 690 At DC - 2 conducting paths series-connected V 220 At DC - conducting paths series-connected V 440 Rated insulation voltage U i V 1000 Rated impulse withstand voltage U imp kv Overvoltage category IV IV IV IV IV IV IV IV IV IV Pollution degree Operating and short-circuit behavior Rated operational current I 2) ) e At AC-21A, AC-22A, V A At AC-2, 400V A At AC-2, 500 V A At AC-2, 690 V A At DC-21A, 220/440 V A At DC-22A, 220/440 V A At DC-2A, 220/440 V A Motor switching capacity AC-2A 4) At 400 V kw At 500 V kw At 690 V kw Rated short-time withstand current I cw ka (with t = 1 s, rms value, 690 V AC/440 V DC) Rated short-circuit making capacity I cm ka (at 690 V AC/440 V DC) Rated current of upstream fuse 5) A Rated conditional short-circuit current with upstream fuse 5) At 400/500 V AC ka At 690 V AC ka Let-through current combined with upstream fuse 5) At 400/500 V AC ka At 690 V AC ka Let-through I 2 t value in combination with upstream fuse 5) At 400/500 V ka²s At 690 V ka²s Power loss per pole with thermal current I th W Endurance, operating cycles Mechanical Electrical, at AC-2A, 690 V/ Hz Electrical, at DC-2A, 220/440 V Degree of protection With masking plate or cable connection cover IP20 IP20 IP20 IP20 IP20 IP20 IP20 IP20 IP20 IP20 Without masking plate or terminal cover IP00 IP00 IP00 IP00 IP00 IP00 IP00 IP00 IP00 IP00 Ambient conditions Ambient temperature during operation C (no derating of I th at -5 to +55 C) Ambient temperature during storage C Mounting position 6) Any Main conductor connections Conductor cross-section, max. mm x x 240 Busbar systems, max. dimensions (number x width x thickness) Flat terminal mm 1 x 0 x 10 2 x 40 x 5 2 x 60 x 10 Box terminals mm 1 x 0 x 10 2 x 40 x 5 2 x 60 x 10 Tightening torque Flat terminal Nm Box terminals Nm ) Max. permissible operating temperature at connections 125 C. With size switch disconnectors, phase barriers or terminal covers (accessories) are required for: - Busbar systems at AC-21A, AC-22A and U e >400 V, AC-2A and - When cable lugs are connected With size 4 at AC-2A, phase barriers or terminal covers must 4) Values are provided as a guide only and may vary depending on the make of motor. Valid for the combination of KD and fuse type NA, characteristic gg. Contact Technical Support for other mounting positions. be installed (accessories). Siemens 10/2015

36 KD up to 1600 A Technical features Technical specifications (continued) KD switch disconnectors, 6-pole for DC applications up to 1200 V, sizes 1 and 2 Standards IEC , IEC Type KD16 KD22 KD26 KD28 KD0 KD2 KD4 Size General technical details Rated uninterrupted current I u A ) Conventional free air thermal current I th A Rated operational voltage U e At DC - with pollution degree 2 V At DC - with pollution degree V ) ) ) ) Rated insulation voltage U i At DC - with pollution degree 2 V At DC - with pollution degree V ) 1000 ) 1000 ) 1000 ) Rated impulse withstand voltage U imp kv Overvoltage category III III III III III III III Operating and short-circuit behavior Rated operational current I e At DC-21A, 1200 V A At DC-21B, 1200 V A Rated short-time withstand current I cw With t = 1 s, rms value, 1200 V DC ka Rated ultimate short-circuit making capacity I cm At 1200 V DC ka Power loss per pole with thermal current I th W Endurance, operating cycles Mechanical Electrical, at DC-21, 1200 V Degree of protection With masking plate or cable connection cover IP20 IP20 IP20 IP20 IP20 IP20 IP20 Without masking plate or terminal cover IP20 IP20 IP20 IP00 4) / IP20 Ambient conditions Ambient temperature during operation C (no derating of I th at -5 to +40 C) Ambient temperature during storage C Mounting position Any Main conductor connections Conductor cross-section, max. mm Busbar systems, max. dimensions (number x width x thickness) Flat terminal mm -- 1 x 20 x 5) Box terminals mm 1 x 9 x 2 1 x 14 x Tightening torque Flat terminal Nm Box terminals Nm ) Configuring note: Max. permissible operating temperature at connections 110 C Valid for version with box terminal, version with flat terminal max V Valid for version with box terminal, version with flat terminal max V Relevant only for devices with flat terminals When using busbars that are 20 mm wide, these must be insulated. 4 Siemens 10/2015

37 Technical specifications (continued) KD switch disconnectors, 6-pole for DC applications up to 1200 V, sizes to 5 KD up to 1600 A Technical features Standards IEC , IEC Type KD6 KD8 KD40 KD42 KD44 KD46 KD48 KD50 KD52 KD54 Size General technical details Rated uninterrupted current I u A ) Conventional free air thermal current I th A Rated operational voltage U e At DC - with pollution degree 2 V At DC - with pollution degree V Rated insulation voltage U i At DC - with pollution degree 2 V At DC - with pollution degree V Rated impulse withstand voltage U imp kv Overvoltage category IV IV IV IV IV IV IV IV IV IV Operating and short-circuit behavior Rated operational current I 2) e At DC-21A, 1200 V A At DC-21B, 1200 V A Rated short-time withstand current I cw With t = 1 s, rms value, 1200 V DC ka Rated ultimate short-circuit making capacity I cm At 1200 V DC ka Power loss per pole with thermal current I th W Endurance, operating cycles Mechanical Electrical, at DC-21, 1200 V Degree of protection With masking plate or cable connection cover IP20 IP20 IP20 IP20 IP20 IP20 IP20 IP20 IP20 IP20 Without masking plate or terminal cover IP00 IP00 IP00 IP00 IP00 IP00 IP00 IP00 IP00 IP00 Ambient conditions Ambient temperature during operation C (no derating of I th at -5 to +40 C) Ambient temperature during storage C Mounting position Any Main conductor connections Conductor cross-section, max. mm x x 240 Busbar systems, max. dimensions (number x width x thickness) Flat terminal mm 1 x 0 x 10 2 x 40 x5 2 x 60 x 10 Box terminals mm Tightening torque Flat terminal Nm Box terminals Nm ) Configuring note: Max. permissible operating temperature at connections 110 C 2) For switch disconnectors size and 4, phase barriers or contact connection covers (accessories) are required when connecting cable lugs Siemens 10/2015 5

38 KD up to 1600 A Dimensions Dimensional drawings Size 1 Complete assemblies with direct operating mechanisms All complete assemblies are equipped with direct operating mechanisms that are mounted on the front and left. Ø R I201_ Size 1, complete assembly with direct operating mechanism, front operating mechanism, operating mechanism on the left, -pole, box terminal, KD162-2ME10-0, KD222-2ME10-0, KD262-2ME10-0 Ø R I201_ Size 1, complete assembly with direct operating mechanism, front operating mechanism, operating mechanism on the left, 4-pole, box terminal, KD1642-2ME10-0, KD2242-2ME10-0, KD2642-2ME Siemens 10/2015

39 KD up to 1600 A Size 1 (continued) Basic units without handle Front operating mechanism, operating mechanism on the left Dimensions Ø 4,5 18 Installation depth of extension shaft ,6 9, ,4 I201_ , Size 1, basic unit without handle, front operating mechanism, operating mechanism on the left, -pole, box terminal, KD160-2ME10-0, KD220-2ME10-0, KD260-2ME10-0 Ø 4, Installation depth of extension shaft 46, ,6 9,6 8 I201_ ,4 Size 1, basic unit without handle, front operating mechanism, operating mechanism on the left, 4-pole, box terminal, KD1640-2ME10-0, KD2240-2ME10-0, KD2640-2ME10-0 Siemens 10/2015 7

40 KD up to 1600 A Dimensions Size 1 (continued) Front operating mechanism, operating mechanism in the center, 6-pole for DC applications Ø 4, , , 42 I202_ ,5 6, ,6 Size 1, basic unit without handle, front operating mechanism, operating mechanism in the center, 6-pole, box terminal, KD1660-2ME20-0, KD2260-2ME20-0, KD2660-2ME20-0 Side operating mechanism, operating mechanism on the left Ø 4, , 6 10, 118, 128,9 1,5 6, ,6 2 16,4 46, , I202_065 Size 1, basic unit without handle, side operating mechanism, operating mechanism on the left, -pole, box terminal, KD164-2ME10-0, KD224-2ME10-0, KD264-2ME Siemens 10/2015

41 KD up to 1600 A Size 1 (continued) Dimensions Ø 4, I202_08 9,6 2 16,4 46, , 15, 121, 16, 146,9 6 1,5 6, Size 1, basic unit without handle, side operating mechanism, operating mechanism on the left, 4-pole, box terminal, KD1644-2ME10-0, KD2244-2ME10-0, KD2644-2ME10-0 Siemens 10/2015 9

42 KD up to 1600 A Dimensions Size 1 (continued) Side operating mechanism, operating mechanism on the right Ø 4, , 46, ,5 1,5 6 15, 44 10, , ,9 9,6 2 16,4 Size 1, basic unit without handle, side operating mechanism, operating mechanism on the right, -pole, box terminal, KD164-2ME40-0, KD224-2ME40-0, KD264-2ME Siemens 10/2015

43 KD up to 1600 A Size 1 (continued) Dimensions 29 Ø 4, , 46, ,5 1,5 6 15, 121, 16, 146,9 9,6 I202_ ,4 Size 1, basic unit without handle, side operating mechanism, operating mechanism on the right, 4-pole, box terminal, KD1644-2ME40-0, KD2244-2ME40-0, KD2644-2ME40-0 Siemens 10/

44 KD up to 1600 A Dimensions Size 1 (continued) Accessories Direct operating mechanisms Extension shaft 78 Extension shaft I201_18746 I201_ Size 1, accessories: Direct operating mechanism, standard version, KD9101-1, KD Size 1, accessories: Direct operating mechanism, flat version (suitable for distribution boards), KD9101-0, KD UD1 door-coupling rotary operating mechanisms I202_0494 Size 1, accessories, 8UD1 door-coupling rotary operating mechanism, inscription 0-I, 8UD1171-2AD11, 8UD1171-2AD I202_0496 Size 1, accessories, 8UD1 door-coupling rotary operating mechanism, inscription TEST-0-1, 8UD1171-2AF21, 8UD1171-2AF25 42 Siemens 10/2015

45 KD up to 1600 A Dimensions Size 1 (continued) I202_0490 I202_0492 Size 1, accessories, 8UD1 door-coupling rotary operating mechanism, handle without extension shaft and coupling driver, inscription 0-1 8UD1771-2AD01, 8UD1771-2AD05, 8UD1771-2CD01, 8UD1771-2CD05 Size 1, accessories, 8UD1 door-coupling rotary operating mechanism, handle without extension shaft and coupling driver, inscription TEST-0-1 8UD1771-2AF01, 8UD1771-2AF05, 8UD1171-2CF01, 8UD1171-2CF05 KD9/8UC7 door-coupling rotary operating mechanisms 75 64,8 75 7,5 I202_2906 Size 1, accessories, door-coupling rotary operating mechanism including 00 mm extension shaft and coupling driver KD9115-1, KD ,8 I202_ ,5 Size 1, accessories: Handles without extension shaft and coupling driver, KD9115-, KD Siemens 10/2015 4

46 KD up to 1600 A Dimensions Size 2 Complete assemblies with direct operating mechanisms All complete assemblies are equipped with direct operating mechanisms that are mounted on the front and left Ø 9 Ø 4.5 R I201_18660 Size 2, complete assembly with direct operating mechanism, -pole, flat terminal, KD02-0NE10-0, KD22-0NE10-0, KD42-0NE10-0, KD62-0NE10-0 Ø R I201_ Size 2, complete assembly with direct operating mechanism, -pole, box terminal, KD282-2NE10-0, KD02-2NE10-0, KD22-2NE10-0, KD42-2NE Siemens 10/2015

47 KD up to 1600 A Dimensions Size 2 (continued) Ø 9 Ø 4.5 R I201_18666 Size 2, complete assembly with direct operating mechanism, 4-pole, flat terminal, KD2842-0NE10-0, KD042-0NE10-0, KD242-0NE10-0, KD442-0NE10-0, KD642-0NE10-0 Ø R I201_ Size 2, complete assembly with direct operating mechanism, 4-pole, box terminal, KD2842-2NE10-0, KD042-2NE10-0, KD242-2NE10-0, KD442-2NE10-0 Siemens 10/2015

48 KD up to 1600 A Dimensions Size 2 (continued) Basic units without handle Front operating mechanism, operating mechanism on the left 27 Installation depth 28, of extension shaft 20 Ø 9 Ø 4,5 46, , I201_18672 Size 2, basic unit without handle, front operating mechanism, operating mechanism on the left, -pole, flat terminal, KD280-0NE10-0, KD00-0NE10-0, KD20-0NE10-0, KD40-0NE10-0, KD60-0NE10-0 Ø 4, Installation depth of extension shaft 42 46, ,6 1,4 I201_ ,8 Size 2, basic unit without handle, front operating mechanism, operating mechanism on the left, -pole, box terminal, KD280-2NE10-0, KD00-2NE10-0, KD20-2NE10-0, KD40-2NE Siemens 10/2015

49 KD up to 1600 A Size 2 (continued) Dimensions 27 28, Installation depth of extension shaft Ø 4,5 20 Ø 9 46, , Size 2, basic unit without handle, front operating mechanism, operating mechanism on the left, 4-pole, flat terminal, KD2840-0NE10-0, KD040-0NE10-0, KD240-0NE10-0, KD440-0NE10-0, KD640-0NE Installation depth of extension shaft Ø 4, , , I201_ ,4 15,8 Size 2, basic unit without handle, front operating mechanism, operating mechanism on the left, 4-pole, box terminal, KD2840-2NE10-0, KD040-2NE10-0, KD240-2NE10-0, KD440-2NE10-0 Siemens 10/

50 KD up to 1600 A Dimensions Size 2 (continued) Front operating mechanism, operating mechanism in the center, 6-pole for DC applications 27 46, , Ø 4, I202_ ,6 1,5 6, Size 2, basic unit without handle, front operating mechanism, operating mechanism in the center, 6-pole, flat terminal, KD2860-0NE20-0, KD060-0NE20-0, KD260-0NE20-0, KD460-0NE20-0 Ø 4, , , 42 I202_ ,5 6, ,6 Size 2, basic unit without handle, front operating mechanism, operating mechanism in the center, 6-pole, box terminal, KD2860-2NE20-0, KD060-2NE20-0, KD260-2NE20-0, KD460-2NE Siemens 10/2015

51 KD up to 1600 A Dimensions Size 2 (continued) Side operating mechanism, operating mechanism on the left ,25 2,5 4, , , I202_055 15, 6 10, 1, 155,9 29 1,5 6, Size 2, basic unit without handle, side operating mechanism, operating mechanism on the left, -pole, flat terminal, KD284-0NE10-0, KD04-0NE10-0, KD24-0NE10-0, KD44-0NE10-0, KD64-0NE Ø 4, , I202_069 5, 15, 6 10, 1, 155,9 1,5 6, ,4 2,5 1, Size 2, basic unit without handle, side operating mechanism, operating mechanism on the left, -pole, box terminal, KD284-2NE10-0, KD04-2NE10-0, KD24-2NE10-0, KD44-2NE10-0 Siemens 10/

52 KD up to 1600 A Dimensions Size 2 (continued) Ø9 26,25 2,5 Ø 4,5 28 I202_ , , 15, 6 157, 172, 182,9 29 1,5 6, Size 2, basic unit without handle, side operating mechanism, operating mechanism on the left, 4-pole, flat terminal, KD2844-0NE10-0, KD044-0NE10-0, KD244-0NE10-0, KD444-0NE10-0, KD644-0NE Ø 4, , , 42 15, 6 157, 172, 182,9 1,5 6, ,4 2,5 1, I202_087 Size 2, basic unit without handle, side operating mechanism, operating mechanism on the left, 4-pole, box terminal, KD2844-2NE10-0, KD044-2NE10-0, KD244-2NE10-0, KD444-2NE Siemens 10/2015

53 KD up to 1600 A Dimensions Size 2 (continued) Side operating mechanism, operating mechanism on the right Ø 9 26,25 2,5 46, Ø 4,5 I202_ , , 10, 1, 155,9 29 1,5 6, Size 2, basic unit without handle, side operating mechanism, operating mechanism on the right, -pole, flat terminal, KD284-0NE40-0, KD04-0NE40-0, KD24-0NE40-0, KD44-0NE40-0, KD64-0NE Ø 4, , 46, , ,5 6 15, 10, 1, 155,9 1,4 2,5 1, I202_071 Size 2, basic unit without handle, side operating mechanism, operating mechanism on the right, -pole, box terminal, KD284-2NE40-0, KD04-2NE40-0, KD24-2NE40-0, KD44-2NE40-0 Siemens 10/

54 KD up to 1600 A Dimensions Size 2 (continued) Ø 9 26,25 2,5 46, Ø 4,5 I202_ , , 157, 172, 182,9 29 1,5 6, Size 2, basic unit without handle, side operating mechanism, operating mechanism on the right, 4-pole, flat terminal, KD2844-0NE40-0, KD044-0NE40-0, KD244-0NE40-0, KD444-0NE40-0, KD644-0NE Ø 4, , 46, , ,5 6 15, 157, 172, 182,9 1,4 2,5 1, I202_089 Size 2, basic unit without handle, side operating mechanism, operating mechanism on the right, 4-pole, box terminal, KD2844-2NE40-0, KD044-2NE40-0, KD244-2NE40-0, KD444-2NE Siemens 10/2015

55 KD up to 1600 A Size 2 (continued) Accessories Direct operating mechanisms Dimensions I201_18708 I201_ Size 2, accessories: Direct operating mechanism, standard version, KD9201-1, KD Size 2, accessories: Direct operating mechanism, flat version (suitable for distribution boards), KD9201-0, KD UD1 door-coupling rotary operating mechanisms I202_0494 Size 2, accessories, 8UD1 door-coupling rotary operating mechanism, inscription 0-I, 8UD1171-2AD11, 8UD1171-2AD I202_0496 Size 2, accessories, 8UD1 door-coupling rotary operating mechanism, inscription TEST-0-1, 8UD1171-2AF21, 8UD1171-2AF25 Siemens 10/2015 5

56 KD up to 1600 A Dimensions Size 2 (continued) I202_0490 I202_0492 Size 2, accessories, 8UD1 door-coupling rotary operating mechanism, handle without extension shaft and coupling driver, inscription 0-1 8UD1771-2AD01, 8UD1771-2AD05, 8UD1771-2CD01, 8UD1771-2CD05 Size 2, accessories, 8UD1 door-coupling rotary operating mechanism, handle without extension shaft and coupling driver, inscription TEST-0-1 8UD1771-2AF01, 8UD1771-2AF05, 8UD1171-2CF01, 8UD1171-2CF05 KD9/8UC7 door-coupling rotary operating mechanisms I202_0496 Size 2, accessories, door-coupling rotary operating mechanism including 00 mm extension shaft and coupling driver KD9115-1, KD I201_ Size 2, accessories, handles without extension shaft and coupling driver, KD9115-, KD Siemens 10/2015

57 KD up to 1600 A Size 2 (continued) Other accessories Dimensions I201_ I201_18727 Size 2, accessories, phase barriers KD9108-6, KD Size 2, accessories, cable connection covers, standard version, KD9204-6, KD I201_ Size 2, accessories: Cable connection covers, short version, KD9204-7, KD Siemens 10/

58 KD up to 1600 A Dimensions Size Complete assemblies with direct operating mechanisms All complete assemblies are equipped with direct operating mechanisms that are mounted on the front and the left Ø Dimension Ø4,2 Auxiliary switch type A B C SB400-0B, , 47 SB400-0D, 19 2, SB400-0C, , A SB400-0E, 19 2, 4 6 SB400-0A, 19 2, I201_18661 Auxiliary switches see table R92, C B 85,5 10,5 Size, complete assembly with direct operating mechanism, -pole, flat terminal, KD62-0PE10-0, KD82-0PE10-0, KD402-0PE10-0, KD422-0PE10-0 Ø4, Ø Auxiliary switch type SB400-0B, SB400-0D, SB400-0C, Dimension A B C , 2, 7 6, A SB400-0E, 19 2, 4 6 SB400-0A, 19 2, I201_18667 R92,8 Auxiliary switches see table C B 85,5 10,5 Size, complete assembly with direct operating mechanism, 4-pole, flat terminal, KD642-0PE10-0, KD842-0PE10-0, KD4042-0PE10-0, KD4242-0PE Siemens 10/2015

59 KD up to 1600 A Dimensions Size (continued) Basic units without handle Front operating mechanism, operating mechanism on the left 44 0 Ø11 40 Dimension Ø4,2 A Auxiliary switch type SB400-0B, SB400-0D, SB400-0C, SB400-0E, A B C , 2, 6, 2, SB400-0A, 19 2, Auxiliary switches see table C B 85,5 9, Installation depth of extension shaft I201_18674 Size, basic unit without handle, front operating mechanism, operating mechanism on the left, -pole, flat terminal, KD60-0PE10-0, KD80-0PE10-0, KD400-0PE10-0, KD420-0PE Ø11 40 Ø4, Auxiliary switch type SB400-0B, SB400-0D, SB400-0C, Dimension A B C , 19 2, , A SB400-0E, 19 2, 4 6 SB400-0A, 19 2, I201_18686 Auxiliary switches see table C B 85,5 10, Installation depth of extension shaft Size, basic unit without handle, front operating mechanism, operating mechanism on the left, 4-pole, flat terminal, KD640-0PE10-0, KD840-0PE10-0, KD4040-0PE10-0, KD4240-0PE10-0 Siemens 10/

60 KD up to 1600 A Dimensions Size (continued) Front operating mechanism, operating mechanism in the center, 6-pole for DC applications ,2 I202_ ,5 9,5 Size, basic unit without handle, front operating mechanism, operating mechanism in the center, 6-pole, flat terminal, KD660-0PE20-0, KD860-0PE20-0, KD4060-0PE20-0, KD4260-0PE20-0 Side operating mechanism, operating mechanism on the left , I202_059 4, Size, basic unit without handle, side operating mechanism, operating mechanism on the left, -pole, flat terminal, KD64-0PE10-0, KD84-0PE10-0, KD404-0PE10-0, KD424-0PE10-0 9,5 85, Siemens 10/2015

61 KD up to 1600 A Dimensions Size (continued) 0 44 Ø , I202_ Ø 4, ,5 85,5 95 Size, basic unit without handle, side operating mechanism, operating mechanism on the left, 4-pole, flat terminal, KD644-0PE10-0, KD844-0PE10-0, KD4044-0PE10-0, KD4244-0PE10-0 Side operating mechanism, operating mechanism on the right 8 8, Ø Ø 6,6 106,5 I202_ , ,5 111, Size, basic unit without handle, side operating mechanism, operating mechanism on the right, -pole, flat terminal, KD64-0PE40-0, KD84-0PE40-0, KD404-0PE40-0, KD424-0PE40-0 Siemens 10/

62 KD up to 1600 A Dimensions Size (continued) 8 8, Ø Ø 6,6 106,5 I202_ , ,5 111, Size, basic unit without handle, side operating mechanism, operating mechanism on the right, 4-pole, flat terminal, KD4444-0RE40-0, KD4644-0QE40-0, KD4844-0QE Siemens 10/2015

63 KD up to 1600 A Size (continued) Accessories Dimensions ,25 Extension shaft , I201_ ,5 Size, accessories, direct operating mechanism, standard version, KD901-1, KD UD1 door-coupling rotary operating mechanisms 8UD1 door-coupling rotary operating mechanisms for KD switch disconnectors, size, are available only with the inscription TEST ,4 100 I201_194 Size, accessories, 8UD1 door-coupling rotary operating mechanism, inscription TEST-0-1, 8UD1141-2AF21, 8UD1141-2AF , ,4 100 I201_19448 I201_ Size, accessories, 8UD1 door-coupling rotary operating mechanism, handle without extension shaft and coupling driver, inscription 0-1 8UD1841-2AD01, 8UD1841-2AD05, 8UD1841-2CD01, 8UD1841-2CD05 Size, accessories, 8UD1 door-coupling rotary operating mechanism, handle without extension shaft and coupling driver, inscription TEST-0-1 8UD1841-2AF01, 8UD1841-2AF05, 8UD1841-2CF01, 8UD1841-2CF05 Siemens 10/

64 KD up to 1600 A Dimensions Size (continued) KD9/8UC7 door-coupling rotary operating mechanisms ,8 I202_ Size, accessories, door-coupling rotary operating mechanism including 00 mm extension shaft and coupling driver KD915-1, KD ,8 I202_ Size, accessories, handles without extension shaft and coupling driver, KD915-, KD915-4 Other accessories 106,5 I201_ Size, accessories, phase barriers KD908-6, KD Siemens 10/2015

65 KD up to 1600 A Size (continued) Dimensions ,5 218 I201_ I201_ Size, accessories: Cable connection covers, standard version, KD904-6, KD904-8 Size, accessories: Cable connection covers, short version, KD904-7, KD904-5 Siemens 10/2015 6

66 KD up to 1600 A Dimensions Size 4 Complete assemblies with direct operating mechanisms All complete assemblies are equipped with direct operating mechanisms that are mounted on the front and left Ø14 8 8,5 8 Ø 6, I202_ ,5 R1, ,5 166,5 Size 4, complete assembly with direct operating mechanism, front operating mechanism, operating mechanism on the left, -pole, flat terminal, KD442-0QE10-0, KD462-0QE10-0, KD482-0QE Ø14 46,5 Ø6,6 A Auxiliary switch type SB400-0B, SB400-0D, SB400-0C, SB400-0E, Dimension A B C ,15, ,15,15 8 SB400-0A, 184,15 I201_18668 R140 Auxiliary switches see table C B 101,5 166,5 Size 4, complete assembly with direct operating mechanism, front operating mechanism, operating mechanism on the left, 4-pole, flat terminal, KD4442-0QE10-0, KD4642-0QE10-0, KD4842-0QE Siemens 10/2015

67 KD up to 1600 A Size 4 (continued) Basic units without handle Front operating mechanism, operating mechanism on the left Dimensions Ø6,6 A 67, Ø ,5 Auxiliary switch type SB400-0B, SB400-0D, SB400-0C, SB400-0E, Dimension A B C ,15, ,15,15 Auxiliary switches see table C B 101,5 110 SB400-0A, Installation depth 60 0 of extension shaft ,15 I201_18676 Size 4, basic unit without handle, front operating mechanism, operating mechanism on the left, -pole, flat terminal, KD440-0QE10-0, KD460-0QE10-0, KD480-0QE10-0 Ø6,6 67, Ø ,5 Auxiliary switch type SB400-0B, SB400-0D, SB400-0C, Dimension A B C ,15, ,15 A SB400-0E, 184,15 4 SB400-0A, 184,15 Auxiliary switches see table C B 101,5 110 Installation depth 60 0 of extension shaft -10 I201_18688 Size 4, basic unit without handle, front operating mechanism, operating mechanism on the left, 4-pole, flat terminal, KD4440-0QE10-0, KD4640-0QE10-0, KD4840-0QE10-0 Siemens 10/

68 KD up to 1600 A Dimensions Size 4 (continued) Front operating mechanism, operating mechanism in the center, 6-pole for DC applications , , ,5 I202_ ,5 110 Size 4, basic unit without handle, front operating mechanism, operating mechanism in the center, 6-pole for DC applications, flat terminal, KD4460-0QE20-0, KD4660-0QE20-0, KD4860-0QE Siemens 10/2015

69 KD up to 1600 A Size 4 (continued) Side operating mechanism, operating mechanism on the left Dimensions Ø , ,5 8,5 I202_061 Ø 6, ,5 111,5 Size 4, basic unit without handle, side operating mechanism, operating mechanism on the left, -pole, flat terminal, KD444-0QE10-0, KD464-0QE10-0, KD484-0QE Ø , I202_079 67,5 8,5 Ø 6, ,5 111,5 Size 4, basic unit without handle, side operating mechanism, operating mechanism on the left, 4-pole, flat terminal, KD4444-0QE10-0, KD4644-0QE10-0, KD4844-0QE10-0 Siemens 10/

70 KD up to 1600 A Dimensions Size 4 (continued) Side operating mechanism, operating mechanism on the right 8 8, Ø Ø 6,6 106,5 I202_ , ,5 111, Size 4, basic unit without handle, side operating mechanism, operating mechanism on the right, -pole, flat terminal, KD444-0QE40-0, KD464-0QE40-0, KD484-0QE , Ø Ø 6,6 106,5 I202_ , ,5 111, Size 4, basic unit without handle, side operating mechanism, operating mechanism on the right, 4-pole, flat terminal, KD4444-0QE40-0, KD4644-0QE40-0, KD4844-0QE Siemens 10/2015

71 KD up to 1600 A Dimensions Size 4 (continued) Accessories Direct operating mechanisms 171,5 140±0,2 Extension shaft ,5 I201_ ,5 Size 4, accessories, direct operating mechanism, standard version, KD9401-1, KD UD1 door-coupling rotary operating mechanisms 8UD1 door-coupling rotary operating mechanisms for KD switch disconnectors, size 4, available only with inscription TEST ,4 100 I201_19446 Size 4, accessories, 8UD1 door-coupling rotary operating mechanism, inscription TEST-0-1, 8UD1151-AF21, 8UD1151-AF ,4 100 I201_190 Size 4, accessories, 8UD1 door-coupling rotary operating mechanism, handle without extension shaft and coupling driver, inscription 0-1 8UD1851-AD01, 8UD1851-AD05, 8UD1851-CD01, 8UD1851-CD ,4 100 I201_191 Size 4, accessories, 8UD1 door-coupling rotary operating mechanism, handle with lighting without extension shaft and coupling driver, inscription TEST-0-1 8UD1851-AF01, 8UD1851-AF05, 8UD1851-CF01, 8UD1851-CF05 Siemens 10/

72 KD up to 1600 A Dimensions Size 4 (continued) KD9/8UC7 door-coupling rotary operating mechanisms ,8 I202_ Size 4, accessories, door-coupling rotary operating mechanism including 00 mm extension shaft and coupling driver KD9415-1, KD Size 4, accessories, handles without extension shaft and coupling driver, KD9415-, KD Other accessories 122 I201_ I201_ Size 4, accessories, phase barriers, KD9408-6, KD Siemens 10/2015

73 KD up to 1600 A Size 4 (continued) Dimensions 128 I201_ Size 4, accessories, cable connection covers, standard version, KD9404-6, KD I201_ Size 4, accessories, cable connection covers, short version, KD9404-7, KD Siemens 10/

74 KD up to 1600 A Dimensions Size 5 Complete assemblies with direct operating mechanisms All complete assemblies are equipped with direct operating mechanisms that are mounted on the front and left. Ø8, Ø14 61 Dimension 10 Auxiliary switch type A B C 220 A SB400-0B, SB400-0D, SB400-0C, ,5 77,5 81,5 SB400-0E, ,5 1 SB400-0A, ,5 I201_1866 Auxiliary switches see table R C B 140,5 212,5 Size 5, complete assembly with direct operating mechanism, front operating mechanism, operating mechanism on the left, -pole, flat terminal, KD502-0RE10-0, KD522-0RE10-0, KD542-0RE10-0 Ø8, Ø14 61 Dimension 10 Auxiliary switch type A B C 220 A SB400-0B, SB400-0D, SB400-0C, ,5 77,5 81,5 SB400-0E, ,5 1 SB400-0A, ,5 I201_18669 R Auxiliary switches see table C B 140,5 212,5 Size 5, complete assembly with direct operating mechanism, front operating mechanism, operating mechanism on the left, 4-pole, flat terminal, KD5042-0RE10-0, KD5242-0RE10-0, KD5442-0RE Siemens 10/2015

75 KD up to 1600 A Size 5 (continued) Basic units without handle Front operating mechanism, operating mechanism on the left Dimensions Ø Ø14 61 Dimension 10 Auxiliary switch type A B C 220 A SB400-0B, SB400-0D, SB400-0C, ,5 77,5 81,5 SB400-0E, ,5 1 SB400-0A, ,5 I201_ Auxiliary switches see table C B 140,5 152,5 Installation depth 88 0 of extension shaft -10 Size 5, basic unit without handle, front operating mechanism, operating mechanism on the left, -pole, flat terminal, KD500-0RE10-0, KD520-0RE10-0, KD540-0RE10-0 Ø Ø14 61 Dimension 10 Auxiliary switch type A B C 220 A SB400-0B, SB400-0D, SB400-0C, ,5 77,5 81,5 SB400-0E, ,5 1 SB400-0A, ,5 I201_ Auxiliary switches see table C B 140,5 152,5 Installation depth 88 0 of extension shaft -10 Size 5, basic unit without handle, front operating mechanism, operating mechanism on the left, 4-pole, flat terminal, KD5040-0RE10-0, KD5240-0RE10-0, KD5440-0RE10-0 Siemens 10/2015 7

76 KD up to 1600 A Dimensions Size 5 (continued) Front operating mechanism, operating mechanism in the center, 6-pole for DC applications Ø 8, I202_ ,5 152,5 Size 5, basic unit without handle, front operating mechanism, operating mechanism in the center, 6-pole for DC applications, flat terminal, KD5060-0RE20-0, KD5260-0RE20-0, KD5460-0RE20-0 Side operating mechanism, operating mechanism on the left Ø Ø 8, I202_ Size 5, basic unit without handle, side operating mechanism, operating mechanism on the left, -pole, flat terminal, KD504-0RE10-0, KD524-0RE10-0, KD544-0RE ,5 140, Siemens 10/2015

77 KD up to 1600 A Dimensions Size 5 (continued) Ø Ø 8,4 12, I202_ ,5 140,5 154 Size 5, basic unit without handle, side operating mechanism, operating mechanism on the left, 4-pole, flat terminal, KD5044-0RE10-0, KD5244-0RE10-0, KD5444-0RE10-0 Side operating mechanism, operating mechanism on the right Ø 4, I202_08 9,6 2 16,4 46, , 15, 121, 16, 146,9 6 1,5 6, Size 5, basic unit without handle, side operating mechanism, operating mechanism on the right, -pole, flat terminal, KD504-0RE40-0, KD524-0RE40-0, KD544-0RE40-0 Siemens 10/

78 KD up to 1600 A Dimensions Size 5 (continued) 61 Ø Ø8,4 10 Auxiliary switch type Dimension A B C A SB400-0B, SB400-0D, SB400-0C, ,5 77,5 81,5 60,5 B A 140, ,5 Auxiliary switches see table SB400-0E, SB400-0A, Installation depth of extension shaft ,5 77,5 I201_18701 Size 5, basic unit without handle, side operating mechanism, operating mechanism on the right, 4-pole, flat terminal, KD5044-0RE40-0, KD5244-0RE40-0, KD5444-0RE Siemens 10/2015

79 KD up to 1600 A Size 5 (continued) Accessories Direct operating mechanisms Dimensions Extension shaft I201_ , Size 5, accessories, direct operating mechanism, standard version, KD9501-1, KD UD1 door-coupling rotary operating mechanisms: 8UD1 door-coupling rotary operating mechanisms for KD switch disconnectors, size 5, available only with inscription TEST ,4 100 I201_19447 Size 5, accessories, 8UD1 door-coupling rotary operating mechanism, inscription TEST-0-1, 8UD1161-4AF21, 8UD1161-4AF ,4 100 I201_192 Size 5, accessories, 8UD1 door-coupling rotary operating mechanism, handle without extension shaft and coupling driver, inscription 0-1 8UD1861-4AD01, 8UD1861-4AD05, 8UD1861-4CD01, 8UD1861-4CD ,4 100 I201_192 Size 5, accessories, 8UD1 door-coupling rotary operating mechanism, handle with lighting without extension shaft and coupling driver, inscription TEST-0-1, 8UD1861-4AF01, 8UD1861-4AF05, 8UD1861-4CF01, 8UD1861-4CF05 Siemens 10/

80 KD up to 1600 A Dimensions Size 5 (continued) KD9/8UC7 door-coupling rotary operating mechanisms ,8 I202_ Size 5, accessories, door-coupling rotary operating mechanism including 00 mm extension shaft and coupling driver KD9515-1, KD Size 5, accessories, handles without extension shaft and coupling driver, KD9515-, KD Other accessories 15 I201_ I201_ I201_ ,5 Size 5, accessories, phase barriers, KD9508-6, KD Size 5, accessories, cable connection covers, standard version, KD9504-6, KD Siemens 10/2015

81 KD up to 1600 A Typical circuit diagrams Circuit diagrams AC applications N 6 N N N I201_ N 6 N N N I201_18790 AC applications, -pole Note: The 4th contact element is an optional accessory AC applications, 4-pole N N N N N N I201_18789 Options for additional poles DC applications P N P N LOAD LOAD I201_18791 DC applications, 2 series-connected switching poles - max. 220 V DC P N P N P N LOAD LOAD LOAD I201_18792 DC applications, series-connected switching poles - max. 440 V DC Siemens 10/

82 KA, KE up to 1000 A Introduction Overview NSE0_0191d Auxiliary switch (SB for KA; KX for KE) 2 IP20 terminal cover (Operator side) K switch disconnector 4 Arcing contacts (only for KE) 5 Extension shaft 6 7 Coupling driver 8UC7 door-coupling rotary operating mechanism in standard version (ti-grey) or EMERGENCY-STOP version (red/yellow) UC9 handle for fixed mounting in standard version (black) or EMERGENCY-STOP version (red). 4th pole (optional, only for KA) All components from the switch to the actuator are provided with non-interchangeability features. For the KA switch disconnectors, complete kits for standard and EMERGENCY-STOP application are available for installation in the side and rear panels of control cabinets. A changeover operating mechanism is available for the use of two switch disconnectors of the KE series as load changeover switches. Application KA and KE switch disconnectors are used as main control, EMERGENCY-STOP, maintenance and transfer switches in distribution boards for residential and non-residential buildings as well as industrial switchgear. As three and four-pole versions, they ensure making and breaking of the specified rated current under load. At the same time, they constitute a safety isolating function and isolating distance in all low-voltage circuits. A switch coupling permits simultaneous switching of two KE switch disconnectors with identical or different rated operational currents. Identical accessories for KA switch disconnectors and for KL and KM switch disconnectors with fuses simplify stock keeping. All K switch disconnectors are climate-proof and meet the requirements of IEC , IEC and VDE 0660 Part 107. Switch disconnectors in the type-tested 8HP moldedplastic distribution board enclosure (IP65 degree of protection) are available for use as safety switches. For additional data, see catalog LV 10, chapters "Distribution boards" and "ipo installation terminals". 80 Siemens 10/2015

83 KA, KE up to 1000 A Introduction Technical specifications Standards IEC , IEC , VDE 0660 Part 107 Type KA50 KA51 KA52 1) KA5 1) KA55 1) KA57 1) KA58 1) Rated uninterrupted current I u A ) Conventional free air thermal current I 2) th A ) Rated insulation voltage U i V Rated impulse withstand voltage U imp kv Rated operational voltage U e 50/60 Hz AC V 690 DC V 440 ( conducting paths series-connected) V 220 (2 conducting paths series-connected) V 110 (1 conducting path) Rated short-circuit making capacity I cm ka with upstream fuses 4) At 50/60 Hz, 690 V AC, peak value Rated conditional short-circuit current ka with upstream fuses 4) At 50/60 Hz AC, 690 V, rms value Max. rated current I n of fuses A Permissible let-through current of the fuses ka ) 0 5) 40 5) Maximum permissible let-through I 2 t value ka 2 s Permissible let-through current of an upstream ka circuit breaker At 50/60 Hz, 690 V AC, peak value Rated short-circuit making capacity without fuses ka At AC 50 Hz/60 Hz 690 V, peak value Breaking capacity (infeed from the top or bottom) At 400 V AC Breaking current I c (at p.f. = 0.5, rms value) A Rated operational current I e at - AC-21A, AC-22A, AC-2A A ) Motor switching capacity AC-2A kw At 500 V AC Breaking current I c (at p.f. = 0.5, rms value) A Rated operational current I e at - AC-21A, AC-22A A AC-2A A Motor switching capacity AC-2A kw At 690 V AC Breaking current I c (at p.f. = 0.5, rms value) A Rated operational current I e at - AC-21A, AC-22A A AC-2A A Motor switching capacity AC-2A kw At 440 V DC ( conducting paths series-connected) 7) Breaking current I c (L/R = 15 ms) A ) Rated operational current I e at DC-2A A ) Rated short-time current I cw (1 s current, rms value) ka Permissible ambient temperature C for operation ) C during storage Mechanical endurance, operating cycles Degree of protection IP00/IP20 (from the operator side, with busbar and terminal covers) Power loss of the switch at I th W Main conductor connection Busbar systems, max. dimensions (W x T) mm 25 x 9 25 x 9 x 10 x x x x 15 Cable lug, max. conductor cross-section (stranded) mm x 150 or 1 2 x 240 x 240 Tightening torque Nm Terminal screws M6 M6 M6 M8 M10 M10 M10 Protective conductor connection Flat bars mm x x x 2.5 Cable lug, max. conductor cross-section (stranded) mm ) Technical specifications for approval on request. 2) Configuring note: Max. permissible operating temperature at connections 100 C. ) With KA58 for operation -25 C C, 570 A at 55 C. 4) Only available with fuses NA 8, NA 2 or ND1 8, ND1 2 (otherwise only 105 ka/50 ka). 5) ND1 switchgear protection fuse. 6) AC-2B. 7) 220 V DC (L1 and L series-connected) or 110 V DC (one conducting path) at DC-2A. 8) At 440 V L/R = 4 ms, at 220 V L/R = 15 ms. 9) At 440 V DC-22A, at 220 V DC-2A. Siemens 10/

84 KA, KE up to 1000 A Introduction Standards IEC , IEC , VDE 0660 Part 107 Type KE42 KE4 KE44 KE Rated uninterrupted current I u A Rated insulation voltage U i V 1000 AC, 1200 DC Rated impulse withstand voltage U imp kv Rated operational voltage U e 50/60 Hz AC V 690 DC V 440 ( conducting paths series-connected) V 220 (2 conducting paths series-connected) Rated short-circuit making capacity I cm ka At 50/60 Hz AC, 690 V (peak value) Rated short-circuit making capacity with upstream fuses ka At 50/60 Hz AC, 690 V (peak value) Rated conditional short-circuit current A with upstream fuses At 50/60 Hz AC, 690 V (rms value) Maximum permissible let-through I 2 t value ka 2 s Permissible let-through current of an upstream circuit breaker At 50/60 Hz AC, 690 V (peak value) ka Max. rated current I n of fuse A Permissible let-through current of the fuses (peak value) ka Breaking capacity (infeed from the top or bottom) At 400 V AC Breaking current I c (rms value at p.f. = 0.5) A Rated operational current I e at - AC-21A A AC-22A A AC-2A A at 500 V AC Breaking current I c (rms value at p.f. = 0.5) A Rated operational current I e at - AC-21A A AC-22A A AC-2A A At 690 V AC Breaking current I c (rms value at p.f. = 0.5) A Rated operational current I e at - AC-21A A AC-22A A AC-2A A ND1 switchgear protection fuse. Breaking current I c (L/R = 5 ms) A Rated operational current I e at - DC-21A A DC-22A A Rated short-time current I cw (1 s current, rms value) ka Permissible ambient temperature C for operation C during storage Mechanical endurance, operating cycles Degree of protection IP00 Power loss of the switch at I th W Main conductor connections Busbar systems, max. dimensions (W x T) mm 25 x x 10 2 x 40 x 10 2 x 40 x 10 Cable lug, max. conductor cross-section (stranded) mm 2 2 x x 150, 1 x x x Siemens 10/2015

85 KA, KE up to 1000 A Floor mounting Dimensional drawings KA50, 6 A, KA51, 80 A, -pole KA50 and KA51: Dimensional drawing for 4-pole version corresponds to KA52 Without shaft, without operating mechanism 4,5 4, KA50, 6 A, KA51, 80 A, -pole KA50 and KA51: Dimensional drawing for 4-pole version corresponds to KA52 With shaft and 8UC7 operating mechanism ,5 6, ,5 2,5 120 NSE0_0005a M 6x KA50, KA51 NSE0_ ,1 R2 Shaft (profile) Engaged length: min. 70 mm max. 150 mm a Shaft length Max ; unchanged shaft from 8UC71 Min ; shaft from 8UC71 short a -80 KA52, 125 A KA5, 160 A KA50, KA51, 4-pole Without shaft, without operating mechanism c g i KA52, 125 A KA5, 160 A KA50, KA51, 4-pole With shaft and 8UC7 operating mechanism h , Ø4,5 65 l e th pole KX52-0AA For KA5, KA52 NSE0_00279c 46 N N 16,5 h n d 14 Type c h n KA52 KA th pole KA52, KA5 a Shaft length NSE0_00281 Shaft (profile) Max ; unchanged shaft from 8UC72 R2 Engaged length: min. 70 mm Min ; shaft from 8UC72 short 8-0,1 max. 150 mm a -50 Type c d e g h i l n KA52 KA M6 20 M th pole 15 M l c KA55, 250 A, KA57, 400 A Without shaft, without operating mechanism a 26, b c KA55, 250 A, KA57, 400 A, KA58, 60 A With shaft and 8UC7 operating mechanism NSE0_ , Ø5,5 88 a Ø NSE0_0012a KA55, KA57, KA58 NSE0_0028 Shaft (profile) R2 Engaged length: min. 170 mm 10-0,1 max. 205 mm a Shaft length Max. 5 00; unchanged shaft from 8UC7 Min ; shaft from 8UC7 short a -5 Siemens 10/2015 8

86 f t t Siemens AG 2016 KA, KE up to 1000 A Floor mounting KA58, 60 A Without shaft, without operating mechanism 26, a b c KA58 4th pole KX55-0AA For KA55, KA57, KA58 55,5 NSE0_00285b NSE0_0014a Type a b c KA55, KA57 KA M10 0 M10 5 4th pole 80 4 M N N c KE4 FRONT OPERATING MECHANISM with handle 14,5 w ,5 2 x 90 46,5 e m KX2210-0H Coupling socket NSE0_ b d n g 12 NSE0_0018a k 8 c 187 p 1 h 4,5 z l y KE4 Rear rotary operating mechanism without handle Keep this Keep this space free m 1 space free b (arc exit) (arc exit) d 14,5 6,5 y x KX H 12 4, v c h 1 z l o p 1 w n 1 e g k f NSE0_0019b Caution! Must not be used as a drive s u Type b c d e f g h h 1 k l m m 1 n n 1 o p p 1 s t u v w w 1 x y z KE M M KE M M KE M M KE M M KE4. 0-0EA With shaft and 8UC7 operating mechanism 100 NSE0_0021 q 1,5...4 r ,5 to 65 Type r Shaft length q KE42, KE4 Max. 4 00; unchanged shaft from 8UC7 140 Min ; shortened shaft from 8UC r KE44, KE Max. 4 00; unchanged shaft from 8UC Min ; shortened shaft from 8UC r Siemens 10/2015

87 KX2210 changeover operating mechanism e 212 f 12 KA, KE up to 1000 A KX2250-1A operating linkage 12 Floor mounting , b c a NSE0_ NSE0_0022 d Version For type a b c d e f q Breakbeforemake Without interruption KE42, KE4 KE44 KE KE42, KE4 KE44 KE Circuit diagrams Internal circuit diagram for KA Internal circuit diagram for KE NSE0_ NSE0_00186 (for KA50 and KA51, only one auxiliary switch possible; 4th pole possible as main contact) Internal circuit diagram for KA and KE (Auxiliary switch not included in scope) Use for DC voltage at DC-2A 440 V) NSE0_01528 P 1 N 5 Circuit diagram for changeover switch with break-before-make feature I L1 L2 L NSE0_00188 L II L2 L I 0 II Siemens 10/

88 VT up to 1600 A General data Overview I202_02420a Switch disconnector Circular conductor terminal Front connection Rear connection Auxiliary conductor terminal Front connecting bus with increased pole spacing Insulating barriers Lateral rotary operating mechanism Shunt release Undervoltage release Adapter to install on 5 mm DIN rail Locking device type lever Signal switch Auxiliary switch Mechanical parallel switching Mechanical interlocking Front rotary operating mechanism Front rotary operating mechanism Lateral rotary operating mechanism (right) Lateral rotary operating mechanism (left) Non lockable knob Coupling driver Telescopic extension shaft Lockable knob Lockable knob Coupling driver Extension shaft 86 Siemens 10/2015

89 VT up to 1600 A General data Application VT switch disconnectors can be used as main control switches for sub-distribution boards, repair and transfer switches for cables, busbars or unit combinations. As three and four-pole versions, they ensure making and breaking of the specified rated current under load. At the same time, they constitute a safety isolating function and isolating distance in all low-voltage circuits. The position of the operating toggle lever always matches that of the contacts (positive operation). All VT switch disconnectors meet the requirements of IEC and IEC Technical specifications Standards A IEC , IEC Rated uninterrupted current I u A Number of poles and 4 and 4 and 4 Rated insulation voltage U i V 690 Utilization category 690 V AC AC-2A AC-2B 440 V DC DC-22A DC-2B Rated operational voltage U e 50/60 Hz AC V 690 DC 440 ( conducting paths series-connected) Rated short-time withstand current I cw ka rms 2/1s /5s 7.5/5s 15/1s 20/1s Rated impulse withstand voltage U imp kv 8 Rated short-circuit making capacity I cm At 415 V AC ka At 440 V DC ka Endurance Mechanical Operating cycles 20,000 0,000 20,000 10,000 10,000 Electrical at 415 V AC Operating cycles 6,000,000 5,000 4,000 4,000 Switching frequency Switching cycles/h Power loss per pole W Siemens 10/

90 TEST TEST Siemens AG 2016 VT up to 1600 A VT1 switch disconnectors up to 160 A Dimensional drawings -pole, fixed-mounted versions Fixed-mounted version, front-accessible connection Ø 6.4 ON OFF Fixed-mounted version, front-accessible connection (connection combination VT9100-4TF0) R NSO0_ x Ø ON OFF NSO0_ x Ø Siemens 10/2015

91 TEST TEST Siemens AG 2016 Fixed-mounted version, front-accessible connection with connection combination VT9100-4ED0 VT up to 1600 A VT1 switch disconnectors up to 160 A Ø ON 75 OFF NSO0_ x Ø Fixed-mounted version, rear-accessible connection with connection combination VT9100-4RC Ø Ø ON OFF Ø NSO0_ x Ø Siemens 10/

92 TEST TEST TEST Siemens AG 2016 VT up to 1600 A VT1 switch disconnectors up to 160 A Fixed-mounted version, rotary operating mechanism 75 1 NSO0_ VT1 2 VT9100-HA.0, -HB.0 VT9100-HE.0, HF Fixed-mounted version, rotary operating mechanism with adjustable handle 75 1 NSO0_ ,5 22, VT1 2 VT9100-HA.0, -HB.0 VT9100-HJ.0 4 VT9100-HE.0, -HF.0 5 VT9100-HG.0, -HH.0 6 Outside surface of cabinet door 6 27, (-HJ10) (-HJ20) Dimensions of door cutout min.50 ø7 ø6 2 2 Fixed-mounted version, lateral rotary operating mechanism right NSO0_0005a 1 VT1 2 VT9100-HD10 VT9100-HJ.0 4 VT9100-HE.0, -HF.0 5 VT9100-HG.0, -HH.0 6 Outside surface of cabinet door (HJ10) (HJ20) 90 Siemens 10/2015

93 TEST TEST Siemens AG 2016 VT up to 1600 A Fixed-mounted version, lateral rotary operating mechanism left VT1 switch disconnectors up to 160 A NSO0_ VT1 2 VT9100-HC10 VT9100-HJ.0 4 VT9100-HE.0, -HF.0 5 VT9100-HG.0, -HH.0 6 Outside surface of cabinet door (HJ10) (HJ20) Dimensions of door cutout ø7 2 ø6 2 Fixed-mounted version, mounting on standard mounting rail, width 5 mm 86 ON OFF 2.7 NSO0_ Fixed-mounted version and lateral motorized operating mechanism NSO0_00555 NSO0_00555 Siemens 10/

94 TEST TEST Siemens AG 2016 VT up to 1600 A VT1 switch disconnectors up to 160 A 4-pole, fixed-mounted version Fixed-mounted version, front-accessible connection Ø 6.4 ON OFF R NSO0_00014 M 15 Fixed-mounted version, front-accessible connection with connection combination VT9100-4FT Ø Ø ON OFF Ø NSO0_00016 M Fixed-mounted version, rear-accessible connection with connection combination VT9100-4RC ø ø ø6.4 5 M NSO0_00557 NSO0_ Siemens 10/2015

95 TEST Siemens AG 2016 VT up to 1600 A VT1 switch disconnectors up to 160 A Fixed-mounted version, front rotary operating mechanism NSO0_ VT1 2 VT9100-HA.0, -HB.0 VT9100-HE.0, HF ,5 22,5 52, Fixed-mounted version, front operating mechanism with adjustable handle NSO0_ VT1 2 VT9100-HA.0, -HB.0 VT9100-HJ.0 4 VT9100-HE.0, -HF VT9100-HG.0, -HH.0 6 Outside surface of cabinet door (-HJ10) (-HJ20) Dimensions of door cutout min.50 ø7 ø6 2 2 NSO0_0055 Siemens 10/2015 9

96 TEST TEST TEST Siemens AG 2016 VT up to 1600 A VT1 switch disconnectors up to 160 A Fixed-mounted version, lateral rotary operating mechanism right VT1 2 VT9100-HD10 VT9100-HJ.0 4 VT9100-HE.0, -HF.0 5 VT9100-HG.0, -HH.0 6 Outside surface of cabinet door NSO0_ (HJ10) (HJ20) Fixed-mounted version, lateral rotary operating mechanism left NSO0_000a 1 VT1 2 VT9100-HC10 VT9100-HJ.0 4 VT9100-HE.0, -HF.0 5 VT9100-HG.0, -HH.0 6 Outside surface of cabinet door (HJ10) (HJ20) Dimensions of door cutout ø7 2 ø6 2 NSO0_00554 Fixed-mounted version, mounting on standard mounting rail, width 5 mm 86 ON OFF 2.7 NSO0_ Siemens 10/2015

97 T TEST TEST Siemens AG 2016 VT up to 1600 A Arrangement of switch disconnectors with mechanical interlock VT9100-8LA00 VT1 switch disconnectors up to 160 A Arrangement of switch disconnectors with mechanical interlock for parallel switching VT9100-8LA00 NSO0_ NSO0_ Fixed-mounted version and lateral motorized operating mechanism NSO0_ Siemens 10/

98 VT up to 1600 A VT2 switch disconnectors up to 250 A Dimensional drawings -pole, fixed-mounted versions Fixed-mounted version, front-accessible connection > AC 415 V < AC 415 V Drilling plan 5 48 ON OFF x Ø TEST R NSO0_ Ø Fixed-mounted version, front-accessible connection with connection combination VT9224-4TD ON OFF TEST 0 NSO0_ Ø Siemens 10/2015

99 Fixed-mounted version, front-accessible connection with connection combination VT9215-4TF0 VT up to 1600 A VT2 switch disconnectors up to 250 A ON OFF TEST NSO0_00109 Ø 18 Ø Fixed-mounted version, front-accessible connection with connection combination VT920-4TF ON OFF TEST NSO0_ x Ø Siemens 10/

100 VT up to 1600 A VT2 switch disconnectors up to 250 A Fixed-mounted version, rear-accessible connection with connection combination VT9200-4RC TEST 105 ON OFF Drilling plan Fixed-mounted version, front-accessible connection with connection combination VT9200-4ED Ø NSO0_ x Ø R ON OFF TEST 6.5 NSO0_00121 Ø Siemens 10/2015

101 Fixed-mounted version, front-accessible connection with connection combination VT9200-4EE0 5 5 VT up to 1600 A VT2 switch disconnectors up to 250 A ON OFF TEST Ø Fixed-mounted version, with rotary operating mechanism NSO0_ NSO0_00118a VT2 2 VT9200-HA.0,-HB.0 VT900-HE.0,-HF.0 TEST Siemens 10/

102 VT up to 1600 A VT2 switch disconnectors up to 250 A Fixed-mounted version, rotary operating mechanism with adjustable handle NSO0_00126a VT2 2 VT9200-HA.0,-HB.0 VT900-HE.0,-HF.0 4 VT900-HG.0,-HH.0 5 VT900-HJ.0 6 Outside surface of cabinet door 50 TEST (-HJ10) (-HJ20) 6 Cabinet cutout min. 1 27,5 4 x Ø 6,5 Ø NSO0_ Hinge of cabinet door Fixed-mounted version, motorized operating mechanism VT9200-M..0 Opening dimensions in the switchgear door for an external operating cycle R R max 1 MANUAL AUTO Ø 4, max. TEST NSO0_ Siemens 10/2015

103 VT up to 1600 A -pole, plug-in technology Plug-in base assembly kit VT9200-4PA0 Drilling plan VT2 switch disconnectors up to 250 A L Ø 4+8 mm R x Ø NSO0_ x Ø Ø Plug-in base assembly kit, with terminal cover VT9200-8CB L R Ø 4+6 mm NSO0_ Siemens 10/

104 VT up to 1600 A VT2 switch disconnectors up to 250 A Plug-in design ON OFF 290 TEST NSO0_ Plug-in design Drilling plan ON TEST OFF Ø x Ø NSO0_ x Ø 5.5 R Siemens 10/2015

105 VT up to 1600 A Plug-in design, rotary operating mechanism VT2 switch disconnectors up to 250 A TEST NSO0_ Plug-in design, motorized operating mechanism VT9200-M..0 MANUAL AUTO Ø 4, max. TEST NSO0_ Siemens 10/

106 VT up to 1600 A VT2 switch disconnectors up to 250 A Dimensional drawings -pole, withdrawable version Withdrawable version VT9200-4WA0 Drilling plan x Ø x Ø 5.5 L Ø 4+8 mm Ø R NSO0_ Withdrawable version, VT9200-8CB0 terminal cover 180 L 1 5 R Ø 4+8 mm NSO0_ Siemens 10/2015

107 VT up to 1600 A VT2 switch disconnectors up to 250 A Withdrawable version Operating position Maintenance position ON OFF TEST NSO0_ Withdrawable version, rotary operating mechanism Operating position Maintenance position 0 NSO0_ TEST Siemens 10/

108 VT up to 1600 A VT2 switch disconnectors up to 250 A Withdrawable version, motorized operating mechanism VT9200-M..0 0 MANUAL AUTO Ø 4, max. TEST Withdrawable version, rear accessible connection (VT9200-4RC00 connection combination) Drilling plan NSO0_ ON TEST OFF Ø 8.5 NSO0_ x Ø Siemens 10/2015

109 Withdrawable version, rear-accessible connection (VT9200-4RC00 connection combination) VT up to 1600 A VT2 switch disconnectors up to 250 A Drilling plan > AC 415 V < AC 415 V 5 48 TEST ON OFF R x Ø NSO0_ Ø pole, fixed-mounted version Fixed-mounted version, front-accessible connection, connection combination VT9224-4TD0 + VT9224-4TD N ON OFF TEST N NSO0_00521 Siemens 10/

110 VT up to 1600 A VT2 switch disconnectors up to 250 A Fixed-mounted version, front-accessible connection, connection combination VT9215-4TF0 + VT9215-4TF ON OFF TEST NSO0_00174 Ø 18 Ø Fixed-mounted version, front-accessible connection (connection combination VT9224-4TF0 + VT9224-4TF00) ON ON OFF OFF TEST TEST Siemens 10/2015

111 VT up to 1600 A VT2 switch disconnectors up to 250 A Fixed-mounted version, front-accessible connection (connection combination VT920-4TF0 + VT920-4TF00) ON OFF TEST NSO0_ x Ø Fixed-mounted version, front-accessible connection (connection combination VT9215-4TF0 + VT9215-4TF00) ON OFF TEST Ø 8.5 NSO0_ x Ø 5.5 R Fixed-mounted version, with rotary operating mechanism 77.5 N 1 5 NSO0_ VT2 2 VT9200-HA.0,-HB.0 VT900-HE.0,-HF.0 TEST N Siemens 10/

112 VT up to 1600 A VT2 switch disconnectors up to 250 A Fixed-mounted version, rotary operating mechanism with adjustable handle N NSO0_00185a 7 1 VT2 2 VT9200-HA.0,-HB.0 VT900-HE.0,-HF.0 4 VT900-HG.0,-HH.0 5 VT900-HJ.0 6 Outside surface of cabinet door 50 TEST 1 N (-HJ10) (-HJ20) 6 Cabinet cutout min. 1 27,5 4 x Ø 6,5 Ø NSO0_ Hinge of cabinet door Fixed-mounted version, VT9200-M..0 motorized operating mechanism Opening dimensions in the switchgear door for an external operating cycle R R max 1 TEST NSO0_ MANUAL AUTO 27 Ø 4, max Siemens 10/2015

113 VT up to 1600 A 4-pole, plug-in technology Plug-in base assembly kit VT9200-4PA40 Drilling plan VT2 switch disconnectors up to 250 A N L R Ø 4+8 mm 4 x Ø 5.5 N NSO0_ x Ø Ø Plug-in base assembly kit, with terminal cover VT9200-8CB40 N L R 400 Ø 4+8 mm N NSO0_ Siemens 10/

114 VT up to 1600 A VT2 switch disconnectors up to 250 A Plug-in design ON OFF 290 TEST NSO0_ Plug-in design, rear-accessible connection with connection combination VT9200-4RC0 + VT9200-4RC00 Drilling plan ON 140 TEST OFF Ø NSO0_ x Ø Siemens 10/2015

115 VT up to 1600 A Plug-in design, rotary operating mechanism VT2 switch disconnectors up to 250 A 290 TEST 140 NSO0_ Plug-in design, with motorized operating mechanism VT9200-M..0 MANUAL AUTO 290 Ø 4, max. TEST 140 NSO0_ Siemens 10/

116 VT up to 1600 A VT2 switch disconnectors up to 250 A Withdrawable version, VT9200-4WA40 Drilling plan N x Ø x Ø 5.5 L Ø 4+8 mm N Ø R NSO0_ Withdrawable version, terminal cover VT9200-8CB40 L N 1 5 R Ø 4+8 mm N NSO0_ Siemens 10/2015

117 Withdrawable version Operating position 21 Maintenance position VT up to 1600 A VT2 switch disconnectors up to 250 A 0 ON OFF TEST NSO0_ Withdrawable version, rear-accessible connection, connection combination VT9200-4RC0 + VT9200-4RC TEST ON OFF Ø NSO0_ x Ø Siemens 10/

118 VT up to 1600 A VT2 switch disconnectors up to 250 A Withdrawable version, rotary operating mechanism Operating position Maintenance position TEST NSO0_ Withdrawable version, with motorized operating mechanism VT9200-M MANUAL AUTO NSO0_ Ø 4, max. TEST Siemens 10/2015

119 VT up to 1600 A VT switch disconnectors up to 60 A Dimensional drawings -pole, fixed-mounted versions Fixed-mounted version, front-accessible connection < AC 415 V < AC 415 V ON OFF x Ø TEST R Ø Fixed-mounted version, front-accessible connection with connection combination VT924-4TF0, VT915-4TF NSO0_ ON OFF TEST NSO0_00261 Ø 22 Ø Ø 22 VT924-4TF0 Ø 18 VT915-4TF0 Siemens 10/

120 VT up to 1600 A VT switch disconnectors up to 60 A Fixed-mounted version, front-accessible connection with connection combination VT90-4TF ON OFF TEST NSO0_ x Ø Fixed-mounted version, rear-accessible connection with connection combination VT900-4RC x Ø 5 (M 5 x 25) ON OFF TEST 25 NSO0_ Ø 11 R Siemens 10/2015

121 Fixed-mounted version, front-accessible connection with connection combination VT900-4ED0 VT up to 1600 A VT switch disconnectors up to 60 A 1 6 ON OFF TEST Ø 1 NSO0_ Fixed-mounted version, front-accessible connection with connection combination VT900-4EE TEST ON OFF x Ø 11 NSO0_00269 Siemens 10/

122 VT up to 1600 A VT switch disconnectors up to 60 A Fixed-mounted version, rotary operating mechanism NSO0_00271a VT VT900-HA.0,-HB.0 VT900-HE.0,-HF.0 51 TEST Fixed-mounted version, rotary operating mechanism with adjustable handle NSO0_0027a VT 2 VT900-HA.0,-HB.0 VT900-HE.0,-HF.0 4 VT900-HG.0,-HH.0 5 VT900-HJ.0 6 Outside surface of cabinet door 51 TEST (-HJ10) (-HJ20) 6 Dimensions, cabinet cutout min x Ø 6.5 Ø NSO0_ Hinge of cabinet door 120 Siemens 10/2015

123 VT up to 1600 A Fixed-mounted version, with motorized operating mechanism VT900-M..0 VT switch disconnectors up to 60 A MANUAL AUTO 275 TEST NSO0_ Opening dimensions in the switchgear door for an external operating cycle R max 1 NSO0_ pole, plug-in technology Plug-in base assembly kit VT900-4PA0 Drilling plan x Ø x Ø 6.5 L 2 R Ø 4+8 mm NSO0_ Ø Siemens 10/

124 VT up to 1600 A VT switch disconnectors up to 60 A Plug-in design, with motorized operating mechanism and terminal cover VT900-8CB L R 518 Ø 4+8 mm NSO0_ Plug-in design ON 58 OFF TEST 140 NSO0_ Siemens 10/2015

125 Plug-in design, rear-accessible connection with connection combination VT900-4RC0 Drilling plan VT up to 1600 A VT switch disconnectors up to 60 A x Ø 6.5 ON OFF TEST Ø NSO0_ Plug-in design, with rotary operating mechanism TEST NSO0_ Siemens 10/

126 VT up to 1600 A VT switch disconnectors up to 60 A Plug-in design, with motorized operating mechanism VT900-M MANUAL AUTO Ø 4, max. TEST NSO0_ pole, withdrawable version Withdrawable version, base with terminal cover VT900-8CB0 Drilling plan x Ø x Ø 6.5 L 2 R Ø 4+8 mm NSO0_ Ø Siemens 10/2015

127 VT up to 1600 A Withdrawable version, base, with terminal cover VT900-8CB0 VT switch disconnectors up to 60 A 215 L 1 5 R Ø 4+8 mm NSO0_ Withdrawable version 21 Operating position Test position ON OFF TEST NSO0_ Siemens 10/

128 VT up to 1600 A VT switch disconnectors up to 60 A Withdrawable version, rear-accessible connection with connection combination VT900-4RC0 Operating position Test position xØ ON SP SV PS OFF PS PS PS PS TEST Ø NSO0_ Withdrawable version, with rotary operating mechanism Operating position Test position TEST NSO0_ Siemens 10/2015

129 VT up to 1600 A Withdrawable version, with motorized operating mechanism Operating position Test position VT switch disconnectors up to 60 A MANUAL AUTO Ø 4, max. TEST NSO0_ pole, fixed-mounted version Fixed-mounted version, front-accessible connection > AC 415 V < AC 415 V N ON OFF x Ø TEST R 94 N NSO0_ Ø Siemens 10/

130 VT up to 1600 A VT switch disconnectors up to 60 A Fixed-mounted version, front-accessible connection With connection combinations VT924-4TF0 + VT924-4TF00, VT915-4TF0 + VT915-4TF ON OFF TEST 2 NSO0_0022 Ø 22 Ø 22 (-HJ10) Ø 18 Ø 18 (-HJ20) 105 Fixed-mounted version, front-accessible connection with connection combinations VT90-4TF0 + VT90-4TF ON OFF TEST NSO0_ x Ø Siemens 10/2015

131 VT up to 1600 A VT switch disconnectors up to 60 A Fixed-mounted version, rear-accessible connection with connection combination VT900-4RC0 + VT900-4RC x Ø 6.5 ON OFF TEST 25 NSO0_ Ø 11 R Fixed-mounted version, with rotary operating mechanism N NSO0_ VT VT900-HA.0,-HB.0 VT900-HE.0,-HF TEST N Fixed-mounted version, with door-coupling rotary operating mechanism N NSO0_ TEST VT VT900-HA.0,-HB.0 VT900-HE.0,-HF.0 VT900-HG.0,-HH.0 VT900-HJ.0 Outside surface of cabinet door N (-HJ10) (-HJ20) 6 Siemens 10/

132 VT up to 1600 A VT switch disconnectors up to 60 A Cabinet cutout min x Ø 6.5 Ø 50 NSO0_ Hinge of cabinet door Fixed-mounted version, VT900-M..0 motorized operating mechanism MANUAL AUTO Ø 4, max. TEST 204 NSO0_ Opening dimensions in the switchgear door for an external operating cycle NSO0_ R max Siemens 10/2015

133 4-pole, plug-in technology VT900-4PA40 Drilling plan VT up to 1600 A VT switch disconnectors up to 60 A x Ø 6.5 N x Ø 6.5 L N 25 2 Ø Ø 4+8 mm 4 6 R NSO0_ Plug-in base assembly kit, with VT900-8CB40 N L R Ø 4+8 mm N NSO0_ Siemens 10/

134 VT up to 1600 A VT switch disconnectors up to 60 A Plug-in design ON 58 OFF TEST 185 NSO0_ Plug-in design, rear-accessible connection with connection combination VT900-4RC0 + VT900-4RC00 Drilling plan ON 185 OFF TEST Ø NSO0_008 4 x Ø Siemens 10/2015

135 VT up to 1600 A VT switch disconnectors up to 60 A Plug-in design with rotary operating mechanism 58 TEST 185 NSO0_ Plug-in design, with motorized operating mechanism VT900-M..0 N 1 5 MANUAL AUTO 58 Ø 4, max. TEST N NSO0_ Siemens 10/2015 1

136 VT up to 1600 A VT switch disconnectors up to 60 A 4-pole, withdrawable version VT900-4WA40 withdrawable version base 258 Drilling plan x Ø 6.5 N L N 25 R Ø 4+8 mm Ø NSO0_ Withdrawable version with terminal cover VT900-8CB40 L N 1 5 R Ø 4+8 mm N NSO0_ Siemens 10/2015

137 Withdrawable version 258 Operating position VT up to 1600 A VT switch disconnectors up to 60 A Test position 0 ON OFF TEST NSO0_ Withdrawable version, rear-accessible connection with connection combination VT900-4RC0 + VT900-4RC00 Operating position Test position ON OFF TEST Ø NSO0_00 4 x Ø Siemens 10/

138 VT up to 1600 A VT switch disconnectors up to 60 A Withdrawable version, with rotary operating mechanism Operating position 258 Test position TEST NSO0_0047 Withdrawable version, with VT900-M.. Motorized operating mechanism 258 Operating position Test position 0 MANUAL AUTO Ø 4, max. TEST NSO0_ Siemens 10/2015

139 VT up to 1600 A VT4 switch disconnectors up to 1000 A Dimensional drawings For dimensional drawings, see page 18 Siemens 10/

140 VT up to 1600 A VT5 switch disconnectors up to 1600 A Dimensional drawing Fixed-mounted versions Fixed-mounted version, front-accessible connection VT4 VT x M ON OFF NSO0_009 4 x Ø Drilling plan NSO0_ x Ø Fixed-mounted version, rear-accessible connection Connection combinations VT9500-4RC0, VT9400-4RC0 Openings for cable glands ON OFF BL1000S 8 50 BL1600S NSO0_ R Siemens 10/2015

141 VT up to 1600 A Fixed-mounted version, box terminal With connection combinations VT9524-4TG0 VT5 switch disconnectors up to 1600 A Two connection combinations VT9524-4TG0 can be used to connect four mm 2 cables. Not for switching unit VT4710-AA0-0AA ON OFF 18.5 NSO0_ Fixed-mounted version, box terminal With connection combinations VT9524-4TG0 and VT9524-4TF0 - not for switching unit VT4710-AA0-0AA0. Fixed-mounted version, terminals for circular conductor (VT952-4TF0) NSO0_0040 ON OFF 18.5 NSO0_00401 TEST ON OFF Ø 26 Siemens 10/

142 VT up to 1600 A VT5 switch disconnectors up to 1600 A Fixed-mounted version, terminals for circular conductor (VT95-4TF0) NSO0_ Fixed-mounted version, terminals for circular conductor With circular conductor terminals for four VT954-4TF0 cables NSO0_ TEST ON OFF TEST ON OFF Ø 26 Ø Ø 26 Ø Fixed-mounted version, front rotary operating mechanism Handle lockable VT9500-HE10, VT9500-HF NSO0_00409a R VT9500-HA10 2 VT9500-H Siemens 10/2015

143 Fixed-mounted version, front rotary operating mechanism Cabinet cutout VT up to 1600 A VT5 switch disconnectors up to 1600 A NSO0_00412a min Ø 40 4 x Ø VT4/VT5 2 VT9500-HA10 VT9500-HJ10 4 VT9500-HG.0 5 VT9500-H.10 6 Control cabinet door Hinge of control cabinet door min. 267 max Fixed-mounted version, motorized operating mechanism VT9500-M..0, lockable with up to three padlocks R88 NSO0_ Siemens 10/

144 VT up to 1600 A VT5 switch disconnectors up to 1600 A Withdrawable versions Withdrawable version, front-accessible connection, connection combination VT9500-4EF x M8.5 NSO0_ Withdrawable version Connection combination VT9500-4RC0 Rear terminals Drilling plan max x Ø NSO0_ Siemens 10/2015

145 VT up to 1600 A Withdrawable version, box terminal Connection combination VT9524-4TG0 250 VT5 switch disconnectors up to 1600 A Withdrawable version, box terminal Connection combination VT9524-4TG0 and VT9524-4TF NSO0_004 NSO0_ Withdrawable version Terminals for circular conductor (VT952-4TF0) Withdrawable version Terminals for circular conductor VT95-4TF0, for cables NSO0_ NSO0_ Ø Ø 26 Ø 26 Siemens 10/

146 VT up to 1600 A VT5 switch disconnectors up to 1600 A Withdrawable version Terminals for circular conductor VT954-4TF0, for 4 cables NSO0_ Withdrawable version Connected 100 Disconnected Ø 26 Ø ON OFF NSO0_ Siemens 10/2015

147 Withdrawable version Connected Disconnected Rotary operating mechanism VT up to 1600 A VT5 switch disconnectors up to 1600 A NSO0_ VT9500-MQ00 motorized operating mechanism Withdrawable version Connected Disconnected NSO0_ Siemens 10/2015 1

148 KL with Fuses up to 800 A Introduction Overview NSE0_01557f KL basic device 2 Fuses, optionally BS 88 or LV HRC fuses Terminal cover, IP20 (vertical to operator side) 4 Coupling driver 5 Extension shaft 6 Standard products from the Siemens SB1 range are used as auxiliary switches. All components from the switch to the actuator are provided with non-interchangeability features. Optional 7 Single-pole terminal cover from 6 A to 60 A, IP20 (vertical to operator side) 8 8UC9 knob for fixed mounting in standard version (black) or EMERGENCY-STOP version (red), or 9 8UC7 door-coupling rotary operating mechanism in standard version (ti-grey) or EMERGENCY-STOP version (red/yellow) 10 4th pole (optional) All switch disconnectors feature double contact interruption and an isolating distance. As a result, the fuses of the switch disconnectors are de-energized in the OFF position. Generally all K.5 switch disconnectors can be secured to the shaft with padlock against unauthorized reclosing. Application KL switch disconnectors with fuses protect against overload and short-circuits as main control and EMERGENCY-STOP switches of switchgear assemblies, distribution boards, power supply and motor outgoing feeders. In conjunction with Siemens SITOR semiconductor fuses, they are also used in UPS systems, frequency converters and capacitor control systems. Identical accessories for KA, KL and KM switch disconnectors with fuses simplify stock keeping. Please inquire about a special variant with reduced values that is particularly resistant to atmospheres high in sulfur, e.g. in the paper and cellulose processing industries. All K switch disconnectors are climate-proof and meet the requirements of IEC , IEC and VDE 0660 Part Siemens 10/2015

149 KL with Fuses up to 800 A Introduction Technical specifications Standards IEC , IEC , VDE 0660 Part 107 Type KL50 KL52 1) KL5 1) KL55 1) KL57 1) KL61 1) KL62 1) Rated uninterrupted current I u A For fuse links according to DIN 4620 Size 00 and and and 1 and 2 1 and 2 and 2 and 2 (when SITOR semiconductor fuses are used, 000 a reduction of rated current is necessary; see page 1, reference to technical information) 2) Conventional free air thermal current I th A Rated insulation voltage U i V Rated impulse withstand voltage U imp kv Rated operational voltage U e 50/60 Hz AC V 690 DC V 440 ( conducting paths series-connected) 220 (2 conducting paths series-connected) ) Rated short-circuit making capacity with fuses ka Peak value, at 50/60 Hz 690 V AC Rated conditional short-circuit current with fuses ka Rms value, at 50/60 Hz 690 V AC Max. rated current I n of fuses A ) 800 Max. permissible power loss of the installed fuse NH W BS W 8 (A2/A) 11.5 (A4) Permissible let-through current of the fuses ka ) 0 5) Maximum permissible let-through I 2 t value ka 2 s Breaking capacity (infeed from the top or bottom) At 400 V AC Breaking current I c (at p.f. = 0.5, rms value) A Rated operational current I e at AC-21A, AC-22A, AC-2A A ) 800 6) Motor switching capacity AC-2A kw At 500 V AC Breaking current I c (at p.f. = 0.5, rms value) A Rated operational current I e at AC-21A, AC-22A, AC-2A A ) 800 6) Motor switching capacity AC-2A kw At 690 V AC Breaking current I c (at p.f. = 0.5, rms value) A Rated operational current I e at AC-21A, AC-22A, AC-2A A ) 800 5) Motor switching capacity AC-2A kw At 440 V DC ( conducting paths series-connected) 7) Breaking current I c (L/R = 15 ms) A ) ) ) Rated operational current I e at DC-2A A ) ) 60 10) Rated short-time current I cw (1-s current, rms value) ka Permissible ambient temperature C for operation 4), C during storage Mechanical endurance, operating cycles Degree of protection IP00/IP20 (from the operator side, with fuse and terminal covers) Power loss of the switch at I th W (plus power loss of the fuses) Main conductor connections Busbar systems, max. dimensions (W x T) mm 25 x 9 x 10 x x x x x 17 Cable lug, max. conductor cross-section (stranded) mm x 150 or 2 x x x 240 Tightening torque Nm Terminal screws M6 M6 M8 M10 M10 M12 M12 Protective conductor connections Flat bars mm x x Cable lug, max. conductor cross-section (stranded) mm ) Technical specifications for approval on request. Permissible mounting position 2) Configuring note: Max. permissible operating temperature for fuse blades 15 C, for connections 100 C. 10 ) 110 V (one conducting path). With KL61 for operation -25 C C, at +55 C: I th = 570 A ) With ND1 switchgear protection fuse. 6) AC-2B. 7) 220 V DC (L1 and L series-connected) or 110 V DC (one conducting path) at DC-2A. 8) At 440 V L/R = 4 ms, at 220 V L/R = 15 ms. 9) Only DC-22A (L/R = 2.5 ms). 10) At 440 V DC-22A, at 220 V DC-2A. Mounting position for KL switch disconnectors Note: NSE0_00182 For the KL switch disconnectors, complete kits for standard and EMERGENCY-STOP application are available for installation in the side and rear panels of control cabinets. Siemens 10/

150 KL with Fuses up to 800 A Floor mounting Dimensional drawings KL50, 6 A, -pole; Dimensional drawing for 4-pole version corresponds to dimensional drawing for KL52; without operating mechanism, with lyre-shaped contacts 4,5 Ø4, ,5 1) KL50, 6 A With shaft and 8UC7 operating mechanism NSE0_00275a a 1, Ø 4,5 65 4,5 Ø6, ,5 2,5 1) To be kept free of conductive parts. Not necessary when using lyre-shaped contacts or covers (accessories). KL50, 0, 6 A -pole; Dimensional drawing for 4-pole version corresponds to dimensional drawing for KL52; without operating mechanism, for BS fuses 4,5 Ø4, M 6x NSE0_00274 a Shaft length NSE0_00291 Max ; unchanged shaft from 8UC R2 Min ; shaft from 8UC71 short 175 < a < 80 a ,1 KL52, 125 A, KL5, 160 A With shaft and 8UC7 operating mechanism NSE0_ Shaft (profile) Engaged length: min. 70 mm max. 150 mm 0 1, Ø4, ,5 a 4,5 Ø 6,6 25 2,5 22, M 6x NSE0_00276a a Shaft length Max ; unchanged shaft from 8UC Min ; shaft from 8UC72 short 165 < a < 50 a -50 NSE0_ ,1 R2 Shaft (profile) Engaged length: min. 70 mm max. 150 mm KL52, 125 A, KL5, 160 A, KL50, 6 A, 4-pole Without operating mechanism, with lyre-shaped contacts n c h NSE0_00277a g i l 14 * ,5 KL52, 125 A, KL5, 160 A, KL50, 6 A, 4-pole Without operating mechanism, for BS fuses c g m i l 25 e * To be kept free of conductive parts. Not necessary when using lyre-shaped contacts or covers (accessories). Type c e g h n KL52 NH KL5 NH KL52 A2/A KL5 A th pole NSE0_00278a d 25 e Type c e g h n 149 KL52 NH KL5 NH KL52 A2/A KL5 A th pole IP20 cover for KL A B NSG0_0022 A_4 A_ A_8 A_7 Type for A B C D KX507-0CA02 KL KX527-0CA02 KL KX57-0CA02 KL KX557-0CA02 KL KX557-0CA02 KL C D 148 Siemens 10/2015

151 KL with Fuses up to 800 A Floor mounting KL55, 250 A, KL57, 400 A Without operating mechanism, with lyre-shaped contacts 26, a b c NSE0_00282a 195,5 (Gr.1) 20,5 (Gr.2) 209 Type a b c KM M 10 x 0 KM M 10 x 6 4th pole 80 4 M 10 x 0 KL55, 250 A, KL57, 400 A With shaft and 8UC7 operating mechanism NSE0_ , Ø5,5 88 a a Shaft length Max. 5 00; unchanged shaft from 8UC7 Min ; shaft from 8UC7 short 20 < a < 5 a -5 KL61, 60 A, KL62, 800 A Without operating mechanism, with lyre-shaped contacts, with phase barriers 9 20,5 15 NSE0_ th pole For KL NSE0_00905a , Total installation depth with handle: ,5 + 66,5 = M ,5 66, Ø12,5 1 Profile 12 x 12. Shaft length 110. Shaft can be turned by Circuit diagrams Internal circuit diagram for KL NSE0_ (For KL50 and KL51, only one auxiliary switch is possible, not included in scope, 4th pole possible as main contact) P N 5 6 NSE0_00187 (Auxiliary switch not included in scope). Use for DC voltage at DC-2A 440 V Siemens 10/

152 KL with Fuses up to 800 A Fuses Overview The KL switch disconnectors with fuses are suitable for all fuses in LV HRC design; see Catalog LV 10, "Fuse systems" SITOR semiconductor fuses in LV HRC design can also be used, although it must be noted that, compared to cable and line protection fuses, these get much hotter during operation. For this reason, the fuse must be operated below the rated current I n of the device (derating) when installed in a closed switching device. The following table shows the permissible load currents of the SITOR semiconductor fuses for installation in KL. The values were determined using the conductor cross-sections specified in the table. SITOR semiconductor fuses for KL fuse switch disconnectors: Assignment table SITOR semiconductor fuse data 1) 2) Type Rated current I n 150 Siemens 10/2015 Rated voltage ) Operational class Size Required conductor crosssection Cu Permissible load currents of fuse when installed in KL for floor mounting Type KL Alternative type KL Type Size Permissible load current 4) Type Size Permissible load current 4) A V AC mm² A A NC gr 70 KL61 1 KL NC gr 95 KL KL NC gr 120 KL KL NC gr 185 KL KL NC gr 240 KL61 0 KL62 NC ar 240 KL KL NC ar 2x (40x5) KL KL NC ar 2x (50x5) KL NC ar 2x (40x8) KL NC ar 2x (40x8) KL NC ar 2x (50x8) KL NC ar 2x (50x8) KL NC ar 2x (50x8) KL NC ar 2x95 KL KL62 00 NC ar 2x120 KL61 65 KL62 80 NC ar 2x150 KL KL62 0 NC ar 2x (40x5) KL KL NC ar 2x (40x8) KL NC gr 70 KL61 15 KL NC gr 95 KL KL NC gr 120 KL KL NC gr 240 KL61 00 KL62 15 NC gr 2x 150 KL KL62 0 NC ar 2x (60x6) KL KL61 60 NE gr KL KL NE gs 00 5 KL KL NE gr 00 5 KL KL NE gs KL KL NE gr KL KL NE gs 1 70 KL KL NE1224-2/ gr 1 70 KL KL NE gs 1 95 KL KL NE1225-2/ gr 1 95 KL KL NE gs KL KL NE1227-2/ gr KL KL NE gs 1 2x 70 KL NE120-2/ gr 1 2x 70 KL NE gs 2 2x 95 KL KL61 50 NE11-2/ gr 2 2x 95 KL KL61 50 NE gs 2 2x 95 KL KL NE12-2/ gr 2 2x 95 KL KL NE gs 2 2x 120 KL61 0 KL62 0 NE1-2/ gr 2 2x 120 KL61 0 KL62 0 NE gs 2 2x 120 KL KL NE14-2/ gr 2 2x 120 KL KL NE gs 2x 150 KL KL NE145-2/ gr 2x 150 KL KL NE gs 2x 185 KL61 60 KL62 60

153 KL with Fuses up to 800 A Fuses SITOR semiconductor fuse data 1) 2) Type Rated current I n Rated voltage ) Operational class Size Required conductor crosssection Cu NE146-2/ gr 2x 185 KL KL62 60 NE gs 2x (40x5) KL61 60 KL NE gr 2x (40x5) KL61 60 KL NE147-2/ gr 2x (40x5) KL61 60 KL NE gs 2x (50x5) KL61 60 KL NE gr 2x (50x5) KL61 60 KL NE148-2/ gr 2x (50x5) KL61 60 KL NE1447-2/ gr 2x (40x5) KL61 60 KL NE1448-2/ gr 2x (40x8) KL61 60 KL NE gs KL KL NE gs KL KL NE gs KL KL NE gs KL KL NE gs KL KL NE gs KL KL NE gs KL KL NE gs KL NE ar 1 5 KL KL NE ar 1 50 KL KL NE ar 1 70 KL KL NE ar 1 95 KL KL NE ar KL KL NE20-0B ar KL NE ar KL NE22-0B ar KL NE ar 1 2x 150 KL NE2-0B ar KL61 40 KL62 60 NE ar 2 2x 150 KL61 80 KL NE4-0B ar 2 2x 150 KL KL NE ar 2 2x 185 KL KL62 50 NE ar 2 2x 185 KL KL NE ar 2 2x (40x5) KL KL NE ar 2 2x 240 KL61 60 KL NE ar 2 2x (40x8) KL61 60 KL NE gr 0 6 KL NE gr 0 10 KL NE gr 0 10 KL NE ar 0 16 KL NE ar 0 25 KL NE ar 0 5 KL NE ar 0 50 KL NE ar 0 70 KL NE427-0B ar KL KL NE40-0B ar KL KL NE4-0B ar 2 2x (0x5) KL KL61 70 NE44-0B ar 2 2x (0x5) KL KL62 0 NE ar 2 2x (50x5) KL KL62 60 NE gr 00 4 KL KL NE gr 00 6 KL50 00 KL NE gr KL50 00 KL NE gr KL KL NE ar KL NE ar 00 5 KL NE ar KL NE ar KL ) ) Due to the mechanical stress on the relatively long fuse blades, SITOR NE41 semiconductor fuses should only be switched occasionally and only at zero current. 2) For permissible load currents for NE8-0MK, see Configuration Manual "Fuse Systems", or on request ) Fuses with a rated voltage >690 V may only be operated at max. 690 V (rated voltage of the KL) when installed in KL. Permissible load currents of fuse when installed in KL for floor mounting Type KL Alternative type KL Type Size Permissible load current 4) Type Size Permissible load current 4) A V AC mm² A A 4) In the case of cyclic loads, the currents may have to be further reduced (precise values on request). 5) The fuse can also be operated at a higher rated uninterrupted current than the 125 A current of the KL52. However, in this case, the KL52 must not be switched under load (utilization category AC-20). Siemens 10/

154 KM with Fuses and Isolating Plug Connector up to 400 A Introduction Overview 2 NSE0_0211b KM basic device 2 Plug-in contact strip for KM (part of basic device) Fuses, optionally BS 88 or LV HRC fuses 4 Terminal cover, IP20 (vertical to operator side) 5 Coupling driver 6 Extension shaft 7 Standard products from the Siemens SB1 range are used as auxiliary switches. All components from the switch to the actuator are provided with non-interchangeability features. Optional 8 Single-pole terminal cover from 6 A to 60 A, IP20 (vertical to operator side) 9 8UC9 knob for fixed mounting in standard version (black) or EMERGENCY-STOP version (red), or 10 8UC7 door-coupling rotary operating mechanism in standard version (ti-grey) or EMERGENCY-STOP version (red/yellow) All switch disconnectors feature double contact interruption and an isolating distance. As a result, the fuses are de-energized when the switch disconnectors are in the disconnected position. The KM switch disconnectors with fuses also feature an isolating plug connector. This facilitates mounting and contact establishment in motor control centers (MCCs) in conjunction with vertical busbars. Generally, all K.5 switch disconnectors can Application KM switch disconnectors with fuses protect against overload and short-circuits as main control and EMERGENCY-STOP switches of switchgear assemblies, distribution boards, power supply and motor outgoing feeders. In conjunction with Siemens SITOR semiconductor fuses, they are also used in UPS systems, frequency converters and capacitor control systems. be secured on the shaft with a padlock to prevent unauthorized reclosing. Identical accessories for KA switch disconnectors and KL and KM switch disconnectors with fuses simplify stock keeping. Please inquire about a special variant with reduced values that is particularly resistant to atmospheres high in sulfur, e.g. in the paper and cellulose processing industries. All K switch disconnectors are climate-proof and meet the requirements of IEC , IEC and VDE 0660 Part Siemens 10/2015

155 KM with Fuses and Isolating Plug Connector up to 400 A Introduction Technical specifications Standards IEC , IEC , VDE 0660 Part 107 Type KM50 KM52 KM5 KM55 KM57 Rated uninterrupted current I u A For fuse links according to DIN 4620, Size 00 and and and and 2 1 and 2 (when SITOR semiconductor fuses are used, a reduction of rated current is necessary; see page 1, reference to technical information) 1) Conventional free air thermal current I th A Rated insulation voltage U i V Rated impulse withstand voltage U imp kv Rated operational voltage U e 50/60 Hz AC V 690 DC V 440 ( conducting paths series-connected) V 220 (2 conducting paths series-connected) 2) Rated short-circuit making capacity with fuses ka (peak value, at 50/60 Hz 690 V AC) Rated conditional short-circuit current with fuses ka At 50/60 Hz 690 V AC (rms value) Max. rated current I n of fuses A Max. permissible power loss of the installed fuse NH W BS W 8 (A2/A) 11.5 (A4) Permissible let-through current of the fuses ka ) 0 ) Maximum permissible let-through I 2 t value ka 2 s Breaking capacity (infeed from the top or bottom) At 400 V AC Breaking current I c (at p.f. = 0.5, rms value) A Rated operational current I e at AC-21A, AC-22A, AC-2A A Motor switching capacity AC-2A kw At 500 V AC Breaking current I c (at p.f. = 0.5, rms value) A Rated operational current I e at AC-21A, AC-22A, AC-2A A Motor switching capacity AC-2A kw At 690 V AC Breaking current I c (at p.f. = 0.5, rms value) A Rated operational current I e at AC-21A, AC-22A, AC-2A A Motor switching capacity AC-2A kw At 440 V DC ( conducting paths series-connected) 4) Breaking current I c (L/R = 15 ms) A ) 1600 Rated operational current I e at DC-2A A ) 400 Rated short-time current (1 s current), rms value ka Permissible ambient temperature C for operation 6) C during storage Mechanical endurance, operating cycles Degree of protection IP00/IP20 (from the operator side, with fuse and terminal covers) Power loss of the switch at I th W (plus power loss of the fuses) Main conductor connections Busbar systems, max. dimensions (width thickness) mm Cable lug, max. conductor cross-section (stranded) mm or Busbar systems, max. dimensions (width thickness) mm Tightening torque Nm Terminal screws M6 M6 M8 M10 M10 Protective conductor connections Flat bars mm Cable lug, max. conductor cross-section (stranded) mm ) Configuring note: Max. permissible operating temperature for fuse blades 15 C, for connections 100 C. 110 V (one conducting path). 220 V DC (L1 and L series-connected) or 110 V DC (one conducting path) at DC-2A. At 440 V L/R = 4 ms, at 220 V L/R = 1 ms. 5) At 440 V DC-22A, at 220 V DC-2A. 6) ND1 switchgear protection fuse. Siemens 10/

156 KM with Fuses and Isolating Plug Connector up to 400 A For snapping onto busbar system Dimensional drawings KM50, 6 A With shaft and 8UC7 operating mechanism NSE0_00287a KM50, 6 A Without operating mechanism, with lyre-shaped contacts 120 1) 4,5 22,5 100 a 1, Ø4, l Siemens AG a Shaft length Max ; unchanged shaft from 8UC71 Min ; shaft from 8UC71 short 175 < a < 80 a , NSE0_00288a M 6x20 7,5 1) To be kept free of conductive parts. Not necessary when using lyre-shaped contacts or covers (accessories). KM50, 6 A Without operating mechanism, for BS fuses 120 4, , M 6x ,5 89 NSE0_00289a Drilling pattern and connector cutout NSE0_ , , , Shaft middle NSE0_ ,1 1) To be kept free of conductive parts. Not necessary when using lyre-shaped contacts (included in the scope of supply) or covers (accessory). R2 Shaft (profile) Engaged length: min. 70 mm max. 150 mm KM52, 125 A KM5, 160 A With shaft and 8UC7 operating mechanism NSE0_ , ,5 a , Shaft middle Shaft length Max ; unchanged shaft from 8UC72 Min ; shaft from 8UC72 short 165 < a < 50 a -50 KM52, 125 A KM5, 160 A Without operating mechanism, with lyre-shaped contacts (For additional dimensions, see from page 148 onwards, KL52 and KL5) e c 5-6,4 22,5 1) g i NSE0_0029b Type c e g i l KM Ø 6.6 KM Ø 9 1) To be kept free of conductive parts. Not necessary when using lyre-shaped contacts or covers (accessories). 154 Siemens 10/2015

157 l i Siemens AG 2016 KM with Fuses and Isolating Plug Connector up to 400 A For snapping onto busbar system KM52, 125 A KM5, 160 A Without operating mechanism, for BS fuses 96 Drilling pattern and cutout in the mounting plate for installation of KM Cutout in the mounting plate c e 5-6,4 25 g ,5 Shaft middle NSE0_00295a NSE0_00294b Type c e g i l KM Ø 6.6 KM Ø 9 NSE0_00296a 8-0,1 R2 Shaft (profile) Engaged length: min. 90 mm max. 14 mm KM55, 250 A KM57, 400 A With shaft and 8UC7 operating mechanism NSE0_00297a KM55, 250 A KM57, 400 A Without shaft, without operating mechanism, with lyre-shaped contacts (For additional dimensions, see from page 148 onwards, KL55) , ,5 88 a a Shaft length Max. 5 00; unchanged shaft from 8UC7 Min ; shaft from 8UC7 short 20 < a < 5 a ,4 209 NSE0_00298b y x 195,5 (Gr. 1) 20,5 (Gr. 2) z Type x y z KM M 10 x 0 KM M 10 x 6 Busbar supports KX508-0AA For 0 mm 5 mm busbars NSE0_0028 Shaft (profile) R2 Engaged length: min. 170 mm 10-0,1 max. 205 mm Drilling pattern and cutout in the mounting plate for installation of KM55 and KM57 Drilling pattern and cutout in the mounting plate for mounting KM55 and KM Cutout in the mounting plate 1 Shaft middle 1, , NSE0_0001a Siemens 10/

158 KM with Fuses and Isolating Plug Connector up to 400 A For snapping onto busbar system Cutouts for K.50, KA51 With rear manual operating mechanism KX ,8 56 Cutouts for K.52, K.5 With rear manual operating mechanism KX /KX ,8 22,5 4, ,5 4,8 5, NSE NSE0_000 Cutouts for K.55, K.57, K.58 With rear manual operating mechanism KX ,5 5,8 68 Circuit diagrams Internal circuit diagram for KM 1 5 Note: NSE0_ For KM50 and KM51, only one auxiliary switch possible 156 Siemens 10/2015

159 KM with Fuses and Isolating Plug Connector up to 400 A Overview The KL switch disconnectors with fuses are suitable for all fuses in LV HRC design; see Catalog LV 10, chapter "Fuse systems" SITOR semiconductor fuses in LV HRC design can also be used, although it must be noted that, compared to cable and line protection fuses, these get much hotter during operation. For this reason, the fuse must be operated below the rated current I n of the device (derating) when installed in a closed switching device. The following table shows the permissible load currents of the SITOR semiconductor fuses for installation in KM. The values were determined using the conductor cross-sections specified in the table. Note SITOR semiconductor fuses for KM fuse switch disconnectors: Assignment table Fuses If using smaller cross-sections, a considerably higher derating is required due to the lower heat dissipation. SITOR semiconductor fuse data Permissible load currents of fuse when installed in KM for busbar mounting Type KM Alternative type KM Type 1)2) Rated current I n Rated voltage ) Operational class Size Required conductor crosssection Cu Type Size Permissible load current 4) Type Size Permissible load current 4) A V AC mm² A A NE gr KM KM NE gs 00 5 KM KM NE gr 00 5 KM KM NE gs KM KM NE gr KM KM NE gs 1 70 KM KM NE1224-2/ gr 1 70 KM KM NE gs 1 95 KM KM NE1225-2/ gr 1 95 KM KM NE gs KM KM NE1227-2/ gr KM KM NE gs 1 2x 70 KM NE120-2/ gr 1 2x 70 KM NE gs 2 2x 95 KM NE11-2/ gr 2 2x 95 KM NE gs 2 2x 95 KM NE12-2/ gr 2 2x 95 KM NE gs 2 2x 120 KM NE1-2/ gr 2 2x 120 KM NE gs 2 2x 120 KM NE14-2/ gr 2 2x 120 KM NE gs KM KM NE gs KM KM NE gs KM KM NE gs KM KM NE gs KM KM NE gs KM KM NE gs KM KM NE gs KM NE ar 1 5 KM KM NE ar 1 50 KM KM NE ar 1 70 KM KM NE ar 1 95 KM KM NE ar KM KM NE20-0B ar KM NE ar KM NE22-0B ar KM NE ar 1 2x 150 KM NE2-0B ar KM NE ar 2 2x 150 KM NE4-0B ar 2 2x 150 KM NE ar 2 2x 185 KM Siemens 10/

160 KM with Fuses and Isolating Plug Connector up to 400 A Fuses SITOR semiconductor fuse data Type 1)2) Rated current I n Rated voltage ) Operational class Size Required conductor crosssection Cu Permissible load currents of fuse when installed in KM for busbar mounting Type KM Alternative type KM Type Size Permissible load current 4) Type Size Permissible load current 4) A V AC mm² A A NE ar 2 2x 185 KM NE ar 2 2x (40x5) KM NE ar 2 2x 240 KM NE ar 2 2x (40x8) KM NE gr 0 6 KM NE gr 0 10 KM NE gr 0 10 KM NE ar 0 16 KM NE ar 0 25 KM NE ar 0 5 KM NE ar 0 50 KM NE ar 0 70 KM NE427-0B ar KM NE40-0B ar KM NE4-0B ar 2 2x (0x5) KM NE44-0B ar 2 2x (0x5) KM NE ar 2 2x (50x5) KM NE gr 00 4 KM KM NE gr 00 6 KM50 00 KM NE gr KM50 00 KM NE gr KM KM NE ar KM NE ar 00 5 KM NE ar KM NE ar KM ) ) Due to the mechanical stress on the relatively long fuse blades, SITOR NE41 semiconductor fuses should only be switched occasionally and only at zero current. 2) For permissible load currents for NE8-0MK, see Configuration Manual "Fuse Systems", or on request ) Fuses with a rated voltage >690 V may only be operated at max. 690V (rated voltage of the KM) when installed in KM. 4) In the case of cyclic loads, the currents may have to be further reduced (precise values on request). 5) The fuse can also be operated at a higher rated uninterrupted current than the 125 A current of the KM52. However, in this case, the KM52 must not be switched under load (utilization category AC-20). 158 Siemens 10/2015

161 8UD1 Door-coupling Rotary Operating Mechanisms For KD switch disconnectors Overview 8UD1 rotary operating mechanisms in STANDARD version in gray (ti-gray, left) and EMERGENCY-STOP version in red/yellow (right) With door-coupling rotary operating mechanisms it is also possible to operate switch disconnectors from the outside with the control cabinet doors closed. The rotary operating mechanisms are available in "STANDARD" and "EMERGENCY-STOP" versions with the following differences: STANDARD version: Masking plates in light-gray with black inscription, handles in ti-gray EMERGENCY-STOP version: Masking plates in yellow with black inscription, handles in red Degree of protection Degree of protection when installed is IP65. Standards 8UD1 door-coupling rotary operating mechanisms are in line with the following standards, for example: Standard IEC , EN (VDE 011 Part 1) IEC , EN (VDE 0660 Part 500) IEC , EN (VDE 0660 Part 107) Title Safety of machinery; electrical equipment of machines Low-voltage switchgear and controlgear assemblies Low-voltage switchgear and controlgear: Switches, disconnectors, switch-disconnectors and fuse-combination units Lockability The retractable locking device integrated in the handles is suitable for padlocks with shackle diameters of 4.5 mm to 9.5 mm (locks according to DIN 7465). Up to three padlocks with a shackle diameter of 9.5 mm can be fitted simultaneously. Non-interchangeability To ensure that, when installing switching devices and door-coupling operating mechanisms, all components are assembled in the correct position with respect to one another, the components are provided with non-interchangeability features (rivet and lug). Stops Stops are used to prevent damage occurring as the result of excessive torque. These stops are supplied loose with the rotary operating mechanisms and can be fitted as required. Stops are fitted at the factory to size 1 and 2 rotary operating mechanisms with a 90 operating angle (exception: RV motor starter protectors/circuit breakers). Tolerance compensation 8UD1 rotary operating mechanisms are capable of taking up a radial eccentricity of max. 8 mm between the actuating shaft of the switching device and the door-coupling rotary operating mechanism. Supporting the extension shaft is recommended with greater tolerances. NSE0_009a Coupling drivers With tolerance compensation Without tolerance compensation a b Shaft length ±8 ±5 x +1.5 ±2.5 x+2.5 Permissible radial eccentricity and axial tolerance compensation in mm Pull-out strength The pull-out strength of interlocked operating mechanisms, e.g. pulling off the shaft or destruction of the operating mechanism, amounts to 800 N when the pulling force acts directly onto the operating mechanism in the direction of the shaft. Siemens 10/

162 8UD1 Door-coupling Rotary Operating Mechanisms For KD switch disconnectors Design Components The rotary operating mechanisms consist of a masking plate with handle, including seal and fixing screws for door installation, an extension shaft (00 mm) and a coupling driver to be mounted onto the switch shaft. Operating mechanisms for KD switch disconnectors do not have a shaft coupling since the extension shaft is fitted directly into the switch. Extension shafts with a length of 600 mm are also available. Switch position To ensure compliance with locking and interlocking conditions, the controls and operating mechanisms must be installed such that, with two-position switches, the "0" position lies at 9 o'clock and the "I" position at 12 o'clock NSE0_00022a NSE0_ o'clock position 2 9 o'clock position Positions for two-position switches with 90 operating angle Handle with masking frame Seal Door Fixing screws Coupling driver Extension shaft Adapter Operating shaft of switching device Switching device Tripped plate (can be glued on if required) Design, schematic representation More information For dimensional drawings of 8UD1 door-coupling rotary operating mechanisms, see from page 18 onwards 160 Siemens 10/2015

163 Overview 8UC7 rotary operating mechanism in STANDARD version (left) and EMERGENCY-STOP version (right) With door-coupling rotary operating mechanisms it is also possible to operate switch disconnectors from the outside with the control cabinet doors closed. The rotary operating mechanisms are available in "STANDARD" and "EMERGENCY-STOP" versions with the following differences: STANDARD version: Masking plates in light-gray with black inscription, handles in ti-gray EMERGENCY-STOP version: Masking plates in yellow with black inscription, handles in red Available sizes Rotary operating mechanism Size Rated Shaft profile Masking plate torque 1) Nm mm x mm mm x mm 8UC x 6 75 x 75 8UC x 8 75 x 75 8UC x 10 or 12 x x 100 8UC /55 2) 12 x x 100 1) Operating mechanisms tested with triple torque (according to EN ). They are therefore also suitable for applications in this area. 2) Operation with two hands. Degree of protection Degree of protection when installed is IP65. Standards 8UC7 door-coupling rotary operating mechanisms are in line with the following standards, for example: 8UC7 Door-coupling Rotary Operating Mechanisms For K switch disconnectors Benefits Lockability The retractable locking device integrated in the handles is suitable for padlocks with shackle diameters of 4.5 mm to 8.5 mm (locks according to DIN 7465). Up to three padlocks with a shackle diameter of 8.5 mm and up to five padlocks with a shackle diameter of 6 mm can be fitted simultaneously. Non-interchangeability To ensure that, when installing switching devices and door-coupling operating mechanisms, all components are assembled in the correct position with respect to one another, the components are provided with non-interchangeability features (rivet and lug). Stops Stops are used to prevent damage occurring as the result of excessive torque. These stops are supplied loose with the rotary operating mechanisms and can be fitted as required. Stops are fitted at the factory to size 1 and 2 rotary operating mechanisms with a 90 operating angle (exception: RV motor starter protectors/circuit breakers). Tolerance compensation 8UC7 rotary operating mechanisms are capable of taking up a radial eccentricity of max. mm between the actuating shaft of the switching device and the door-coupling rotary operating mechanism. Supporting the extension shaft is recommended with greater tolerances. NSE0_009a Coupling drivers With tolerance compensation Without tolerance compensation a b Shaft length + ±5 x +1.5 ±2.5 x+2.5 Permissible radial eccentricity and axial tolerance compensation in mm Pull-out strength The pull-out strength of interlocked operating mechanisms, e.g. pulling off the shaft or destruction of the operating mechanism, amounts to 800 N when the pulling force acts directly onto the operating mechanism in the direction of the shaft. Standard IEC , EN (VDE 011 Part 1) IEC , EN (VDE 0660 Part 500) IEC , EN (VDE 0660 Part 107) Title Safety of machinery; electrical equipment of machines Low-voltage switchgear and controlgear assemblies Low-voltage switchgear and controlgear: Switches, disconnectors, switch-disconnectors and fuse-combination units Siemens 10/

164 8UC7 Door-coupling Rotary Operating Mechanisms For K switch disconnectors Application Design 8UC7 door-coupling rotary operating mechanisms can be used in electrical controls, distribution boards and switchboards in cases Components where switches have to be mounted behind covers, end pla- tes and doors that must be opened and where they are to be operated manually from outside. Interlocking conditions The basic versions of the rotary operating mechanisms comply with the following interlocking conditions: Operating mechanism and switching device in "0" (OFF) position: The control cabinet door can be opened. With padlocks fitted, the control cabinet door remains locked however. Operating mechanism and switching device in "I" (ON) position: The control cabinet door cannot be opened in 7 this position. However, the interlock can be overridden 6 and the control cabinet door opened by trained personnel for performing checks. No padlocks can be fitted in "I" position. 4 5 Other interlocking conditions: 2 If no door interlock is required, the user can remove the door 10 interlocking plate of the rotary operating mechanism. It is easy for the user to fit padlocks to the rotary operating mechanisms 1 in the "I" position as well. In this case the door can- not be opened, the operating mechanism cannot be actuated and the door interlock cannot be overridden. Operating conditions and ambient conditions The temperature range for operation of the rotary operating mechanisms is between -25 C and +60 C. Thanks to the use of glass fiber-reinforced molded plastic for handles and masking plates as well as metal components 1 Handle with masking frame with surface protection, the rotary operating mechanisms are 2 Seal suitable for rough conditions, high air humidity and aggressive Door atmospheres. 4 Fixing screws 5 Coupling driver 6 Extension shaft 7 Adapter 8 Operating shaft of switching device 9 Switching device 10 Tripped plate (can be glued on if required) The rotary operating mechanisms consist of a masking plate with handle, including seal and fixing screws for door installation, an extension shaft (00 mm) and a coupling driver to be mounted onto the switch shaft. Operating mechanisms for KA/KL/KM switch disconnectors do not have a shaft coupling since the extension shaft is fitted directly into the switch. Extension shafts with a length of 600 mm are also available. NSE0_00022a 8 9 Design, schematic representation Switch position To ensure compliance with locking and interlocking conditions, the controls and operating mechanisms must be installed such that, with two-position switches, the "0" position lies at 9 o'clock and the "I" position at 12 o'clock NSE0_ o'clock position 2 9 o'clock position Positions for two-position switches with 90 operating angle 162 Siemens 10/2015

165 8UC7 Door-coupling Rotary Operating Mechanisms For K switch disconnectors Dimensional drawings 8UC71 and 8UC72 door-coupling rotary operating mechanisms, sizes 1 and AC ±1 4± P4x11,5 00 1) 5,5 ±1 29±1 1, with extension shaft 28 BD SectionSection A - B C - D NSE0_00490c ±1 ± ± P4x11,5 5,5±1 1, , NSE0_00491c with extension shaft without extension shaft Door cutout with fixing holes 8UC7 to 8UC74 door-coupling rotary operating mechanisms, sizes and A C ±1,5±1 1, ±1 ± ,5 P5x1,5 00 1) B D Section Section A - B C - D NSE0_00492c $ Handle or twin handle % Coupling driver 1) 7±1 22,5 ±1 ±1 P5x1,5,5 ±1 1, , NSE0_0049b & Masking plate ( Seal ) Door * Fixing screw, 4 units + Extension shaft, Shaft coupling - Actuating shaft of the control with extension shaft 1) Length of extension shaft can be cut to fit mounting depth. Extension shaft also available in 600 mm length. without extension shaft Door cutout with fixing holes Siemens 10/

166 8UC7 Door-coupling Rotary Operating Mechanisms Individual parts Dimensional drawings 8UC60 coupling driver 8UC92 5 shaft coupling NSE0_009a Coupling drivers With tolerance compensation a b Shaft length +5 ±5 x Without tolerance +1.5 ±2.5 x+2.5 compensation W 28 A 6,1 5,1 M5 12,1 NSE0_ ,5 W ,1 8 B 8UC71, size 1 NSE0_00495a ) ) Lock handle pulled out 8UC72, size 2 75 NSE0_ UC7, size NSE0_00496a ) 8UC74, size NSE0_ Handles with cover frame, sizes 1 to 4 1) Padlock feature of handle pulled out 164 Siemens 10/2015

167 8UC7 Door-coupling Rotary Operating Mechanisms Operating mechanisms for fixed mounting Dimensional drawings 8UC954, KX 516-1AA operating mechanisms for fixed mounting Size 1 8UC960 to 8UC96, KX 56-1AA operating mechanisms for fixed mounting Size 2 6 NSE0_ NSE0_ UC965 to 8UC975, KX 176-1E operating mechanisms for fixed mounting Sizes and 4 8UC981 to 8UC982, KX 616-1A operating mechanisms for fixed mounting Size 5 NSE0_ ,5 NSE0_00489a Ø54 25,5 a 65 a 65 Size Form a Size Baugröße Form Shape a Siemens 10/

168 NJ62 In-Line with Fuses up to 60 A Introduction Overview NJ62 switch disconnectors with fuses Overview of all components and accessory parts All key product features at a glance In-line design Type-tested according to IEC EN Voltage levels up to 690 V AC/440 V DC 160 A to 60 A for LV HRC and BS 88 fuse links, according to IEC /EN , - and 4-pole versions available 185 mm phase center distance of plug-in contacts Manually operated or with motorized operating mechanism Electronic fuse monitoring (EFM) Developed for switchgear in plug-in design Horizontal or vertical mounting position Front panel locked in ON position Degree of protection IP41 1 NJ62 switch disconnector basic device here in size 00, open, without front cover 2 Manual operating mechanism Motorized operating mechanism 4 Connection module 5 Blanking cover 6 Guide rails 7 Busbar cover 8 Contact extension 9 Current transformer 10 Current transformer bar Connection terminals Stud terminal Terminal cover Multifunction plug Holder for measuring device with electronic fuse monotoring (EFM 10) Holder for measuring device with electronic fuse monotoring (EFM 20/25) Holder for measuring device without EFM Bimetal current measuring device Moving-iron current measuring device BS fuse LV MRC fuse Auxiliary switch 166 Siemens 10/2015

169 NJ62 In-Line with Fuses up to 60 A Introduction Benefits Key advantages for switchboard manufacturers thanks to the following: Compact, modular design Simple and efficient mounting due to incoming plug-in contact High packing density in the field Cable connection with cable clamps or cable lugs Can be mounted in different control cabinet depths Comprehensive range of accessories The advantages for users are: Conversion, retrofitting and replacement without switching off the switchgear Dead-state fuse replacement Maintenance-free High personal safety Operating handle can be locked in OFF position Clear and unambiguous switch position indicator Design Compact and modular design All sizes fit busbar systems with a 185 mm center-to-center clearance, have the same width and depth, as well as a uniform 50 mm grid with regard to mounting height (50, 100 and 200 mm). This enables an in-line disconnector panel to be set up with any combinations of different sizes. Application The plug-in NJ6 switch disconnectors with fuses are installed in low-voltage distribution boards where a minimum amount of space is available for a maximum number of cable ducts to the power distribution. They can be easily fitted in all common control cabinets (minimum depth: 400 mm). The plug-in NJ62 switch disconnectors with fuses are available for rated uninterrupted currents from 160 A to 60 A. LV HRC fuse links according to IEC /EN (sizes 00 to ) or BS fuse links according to BS 88 provide overload and short-circuit protection up to 690 V AC. The switch disconnectors can be retrofitted at any time with auxiliary switches, an ammeter (48 mm x 48 mm) and current transformers, with no extra space required. For installation in control cabinets with a depth > 400 mm, the mounting depth of the disconnectors can be increased by 200 mm using a contact extension. Further installation accessories, such as guide rails and blanking covers, complete the product range. Subsequent replacement of in-line disconnectors of different sizes is easy. Furthermore, the user-friendly hinged handle is retractable in both the ON and the OFF states, so that the compact design is retained in both switch positions. Size 00, 160 A Size 2, 400 A, size, 60 A Siemens 10/

170 NJ62 In-Line with Fuses up to 60 A Introduction Current transformers and current transformer busbar kits Size with 1 current transformer 00 with current transformers 00 with 4 current transformers Current transformer busbar kits, 21 mm, Article No. Current transformer busbar kits, 14 mm, Article No. NJ69 20-DB00 NJ69 20-DE00 NJ69 20-DC00 NJ69 20-DF00 NJ69 20-DD00 NJ69 20-DG00 Size 1 1 with 1 current transformer 1 with current transformers 1 with 4 current transformers Current transformer busbar kits, 21 mm, Article No. NJ69 0-DB00 NJ69 0-DC00 NJ69 0-DD00 Size 2/ No current transformer busbar set required 2/ with 1 current transformer Connection methods All plug-in switch disconnectors supplied for cable lug connection as standard. Size Cable lug connection Terminal connection 00 1x(10mm mm 2 ) 1x(10mm mm 2 ) 2x(16mm mm 2 ) 1 1x(25mm mm 2 ) 1x(16mm mm 2 ) 2x(25mm mm 2 2/ 1x(25mm mm 2 ) 2x(16mm mm 2 ) 2x(25mm mm 2 Ammeters According to DIN 4718, an ammeter with dimensions 48 mm x 48 mm can be used to measure the current. It can be a moving-iron measuring instrument or a bi-metal measuring instrument. A holder for the ammeter must be ordered as a separate accessory part. 2/ with current transformers 2/ with 4 current transformers Holders for ammeters Ammeter (moving-iron measuring instrument, left) and (bi-metal measuring instrument, right) 168 Siemens 10/2015

171 NJ62 In-Line with Fuses up to 60 A General data Function Operating principle Operation The plug-in switch disconnectors are fitted with a snap-action mechanism and are switched by turning the handle approx.. Once actuated, the handle is folded against the front panel in the ON or OFF position for safety reasons. A unique switch position indication is output by the indicator in the inspection window of the in-line disconnector (ON "I" = red, OFF "O" = green). The switch position indicator is mechanically linked to the moving switching contacts. Voltage test In the event of a voltage test on the fuse links, the transparent insert in the front panel is opened. Switch position OFF Personnel safety The switch disconnectors are type tested according to IEC and have IP41 degree of protection in the operating state. The special interlocking mechanism on the handle ensures that the in-line disconnector must be switched off before it is possible to open the cover and remove the fuse. A switchgear key according to DIN 4668 is also required to open the cover. In the OFF position, the handle can also be padlocked to protect against unintentional restarting. Disconnection during the switching operation (snap-action mechanism) is implemented before and after the fuse link. This ensures that, if power is supplied over the busbars or via the cable connecting side, the fuse links are in a dead state when switched off. ON "OFF" position, display "ON" position, display "OFF" position, operating lever in changeable position "ON" position, operating lever in changeable position "OFF" position, operating lever in end position "ON" position, operating lever in end position Siemens 10/

172 NJ62 In-Line with Fuses up to 60 A General data Fuse monitoring Fuse monitoring is used to detect, indicate and report faults. The electronic fuse monitors are available in 2 versions. EFM10 electronic fuse monitor: For use up to 690 V AC Operational voltage < 20 V Display: Ready-to-run Individual fault display per phase 1 CO contact as centralized fault signaling unit EFM20/25 electronic fuse monitor and line monitor: EFM20 for use up to 690 V AC, EFM25 for use up to 440 V DC Operational voltage < 1 V (EFM20) < 20 V (EFM25) Test function Closed-circuit principle or open-circuit principle 2 CO contacts as centralized fault signaling unit incl. line monitoring functions with phase failure detection (EFM20), undervoltage/overvoltage detection EFM10 electronic fuse monitor EFM20/25 electronic fuse monitor 170 Siemens 10/2015

173 NJ62 In-Line with Fuses up to 60 A General data Configuration Installation data NJ62 switch disconnectors Rated current Size Height requirements of in-line disconnectors Type A mm NJ NJ NJ NJ Further built-in components Designation Height requirements Type mm NJ CB00 Blanking covers for empty compartments / connection module 50 NJ69 15-BA A connection module for device compartment (without front panel) 50 Rated currents Rated currents of device sizes = 0.8 x I N of the biggest fuse link For summation current of all feeders in the SIVACON cubicle 2000 A Device size Fuses I N A A Rated current =0.8xI N Configuration rules Configuration rules for ventilated SIVACON cubicles with NJ6 switch disconnectors with fuses For the fully equipped cubicle, the rated diversity factor according to IEC applies. Failure to comply with these instructions may lead to premature aging of fuses and uncontrolled tripping as a result of local overheating. All data refers to an ambient temperature of the switchgear of 5 C (24-hour average value). Rated diversity factor according to IEC Number of main circuits Rated diversity factor 2 and and to 9 inclusive and more 0.6 Siemens 10/

174 NJ62 In-Line with Fuses up to 60 A General data Conversion factors for other ambient temperatures Ambient temperature of the system C Conversion factor Rated current of the fuse links Summation current of all feeders in the cubicle 2000 A = 0.8 x I N of the fuse In-line disconnector arrangement Blanking covers With ventilation slots, 50 mm high Size in-line disconnectors (group formation not permissible) Permissible exceptions: Summation current of all feeders in cubicle 1500 A Size 00 to 2 = 0.90 x I N Size = 0.85 x I N Group formation is not permitted in this case. Every size 00 and 1 device must be assigned a 50 mm high blanking cover. Equipment in the cubicle, from top to bottom, decreasing from size to size 00 Size 2 in-line disconnectors > 280 A continuous load current As far as possible, size in-line disconnectors > 440 A continuous load current should be distributed over different cubicles. Permissible current Total covered height to be allocated Arrangement of in-line disconnectors + associated blanking covers (continuous load current at 5 C system ambient temperature) 440 A to 500 A of single device (for recommended arrangement of blanking covers, see right) 200 mm = 4 units per in-line disconnector I N = 60 A I N x0.8 = 500A = permissible continuous load current < 440 A of single device 150 mm = units per in-line disconnector e. g. I N = 500 A I N x 0.8 = 400 A = permissible continuous load current Size 2 in-line disconnectors (group formation not permissible) 20 A of single device 50 mm = 1 unit per in-line disconnector I N x 0.8 = 284 A e. g. I N = 55 A = permissible continuous load current Groups of in-line disconnectors Sizes 00 and A = summation current of fuse links group x mm = 2 units per group I Total N = 80 A I N x A I N = 125 A = permissible continuous load current I N = 125 A I N = 160 A Any sized groups of in-line disconnectors of size A of single device 100 mm = 2 units per group In combination with size 2 and in one cubicle, the rated currents are 280 A for size 2 and 440 A for size. Devices with size 2 and must be allocated blanking covers (see above). I N = 16 A I N = 20 A I N = 6 A I N = 80 A n n (Total 1 to I N )xα = permissible continuous load current α =rated diversity factor n=4 and 5α =0.8 n = 6 to 9α =0.7 n 10α = Siemens 10/2015

175 NJ62 In-Line with Fuses up to 60 A Assignment of blanking covers with 50 mm high ventilation slots Group Single device Size 00 Size 1 Size 2 Size Summation current of group 500 A I N = 80 A I N = 125 A I N = 125 A I N = 160 A Permissible continuous load current 400 A Summation current of group 490 A x 0.8 = 92 A 2 blanking covers/group Summation current of group = 500 A I N = 250 A I N = 250 A Permissible continuous load current 40 A Summation current of group 500 A x 0.8 = 400 A 2 blanking covers/group Permissible continuous load current of single device 20 A 0.8 x I N = 280 A e. g. I N = 55 A e. g. I N = 500 A 1 blanking cover/device General data Permissible continuous load current of single device 440 A 0.8 x I N = 400 A blanking covers/device I N = 60 A 440 A >I 500 A = 500 A 4 blanking covers/device Group Permissible continuous load current of single device 64 A Group Example: Size 00 Sizes 00 and 1 Group size 00 and sizes 2 and Size 00 with I N 80 A I N = 20 A I N = 2 A I N = 2 A I N = 40 A I N = 40 A I N = 50 A I N = 50 A I N = 80 A I N = 80 A I N = 80 A I N = 80 A I N = 80 A Any group size, up to in-line disconnectors/ panel 16 A 26 A 26 A 2 A 2 A 40 A 40 A 64 A 64 A 64 A 64 A 64 A 2 blanking covers/group I N = 40 A I N = 100 A I N = 100 A I N = 250 A Summation current of group 490 A x 0.8 = 92 A 2 blanking covers/group I N = 20 A I N = 2 A I N = 2 A I N = 40 A I N = 40 A I N = 50 A I N = 50 A I N = 80 A I N = 80 A I N = 80 A I N = 80 A I N = 80 A Size 2 I N = 400 A When combining size 00 I N 80 A with other sizes, in the case of sizes 2 to, the rated currents must be reduced to 0.7 x I N : The assignment of blanking covers for devices of sizes 1 to must be observed (see adjacent example of an incomplete cubicle). Rated current: 280 A Size I N = 60 A Rated current: 440 A Siemens 10/

176 NJ62 In-Line with Fuses up to 60 A General data Technical specifications Main devices of sizes 00 and 1 Size 00 1 Switch disconnectors with fuses Type NJ62... NH BS Breaking capacity H H H S H H S H Rated insulation voltage U i V 1000 Rated impulse withstand voltage U imp V 8000 Rated operational current I e A For LV HRC fuse links and according to IEC For BS fuse links according to BS 88 A A 00T 1) B2 Rated operational voltage U e At 50/60Hz rated frequency V At DC V Utilization category AC2B DC2B DC21B AC22B AC2B DC2B DC21B AC22B AC2B Rated conditional short-circuit current Short-circuit strength (rms value) ka Short-circuit making capacity ka (rms value) Rated making capacity P.f. = 0.65 A P.f. = 0. A P.f. = 0.5 A Rated breaking capacity P.f. = 0.65 A P.f. = 0. A P.f. = 0.5 A Endurance Operating cycles total Electrical (690 V, p.f. = 0.65) Power losses W (without fuse links) Permissible ambient temperature C Permissible mounting position Horizontal and vertical with bottom connection Degree of protection IP41 (in operating state) Connection type Main conductor connections Cable lug connection Conductor cross-section (Al/Cu, solid or stranded) according to DIN 4625 (Cu) and DIN 4629 (Al) mm 2 1x x x x Screw size M8 M12 Torque Nm 15 0 Terminal connection Conductor cross-section (Al/Cu), rm mm 2 1x x Conductor cross-section (Al/Cu), re mm 2 1x x Conductor cross-section (Al/Cu), sm mm 2 1x x Conductor cross-section (Al/Cu), se mm 2 1x x 5-00 Required torque Nm ) The fuse is available from Lawson fuses (UK) and does not correspond to BS Siemens 10/2015

177 NJ62 In-Line with Fuses up to 60 A Main devices of sizes 2 and General data Size 2 Switch disconnectors with fuses Type NJ62... NH BS Screw size 2x M12 2x M12 Torque Nm 0 0 Terminal connection Conductor cross-section (Al/Cu), rm mm 2 2x x Conductor cross-section (Al/Cu), re mm 2 2x x Conductor cross-section (Al/Cu), sm mm 2 2x x Conductor cross-section (Al/Cu), se mm 2 2x x 5-00 Required torque Nm ) The fuse is available from Lawson fuses (UK) and does not correspond to BS Breaking capacity H S H H S H Rated insulation voltage U i V 1000 Rated impulse withstand voltage U imp V 8000 Rated operational current I e For fuse links according to A IEC 60269/BS88 For fuse links 2 and 1 and 2 according to IEC For BS fuse links according to BS 88 B4 T 1) Rated operational voltage U e At 50/60Hz rated frequency V At DC V Utilization category DC2B DC21B AC22B AC2B DC2B DC21B AC22B AC2B Rated conditional short-circuit current Short-circuit strength (rms value) ka Short-circuit making capacity ka (rms value) Rated making capacity P.f. = 0.65 A P.f. = 0. A P.f. = 0.5 A Rated breaking capacity P.f. = 0.65 A P.f. = 0. A P.f. = 0.5 A Endurance Operating cycles total Electrical (690 V, p.f. = 0.65) Power losses W (without fuse links) Permissible ambient temperature C Permissible mounting position Horizontal and vertical with bottom connection Degree of protection IP41 (in operating state) Connection type Main conductor connections Cable lug connection Conductor cross-section Al/Cu, solid or stranded according to DIN 4625 (Cu) and DIN 4629 (Al) mm 2 1x x x x Siemens 10/

178 NJ62 In-Line with Fuses up to 60 A General data Auxiliary switches Acc. to IEC Rated insulation voltage U i V 690 Rated impulse withstand voltage U imp V 8000 Rated operational current I e At AC 15, U e = 120 V A 8 At AC 15, U e = 20 V A 6 At AC 15, U e = 400 V A 4 At AC 15, U e = 690 V A 2 Electronic fuse monitor, AC version (EFM 10) Size / Apparent power consumption S VA Approx. 2.5 Internal resist. of measurement circuit MΩ R in > 6 Storage temperature C Operating temperature C Operating temperature (500 V or 500 A) C Protection rating in closed IP40 in-line disconnector Rated operating voltage of the main control switching devices V AC Hz 50/60 Voltage limits % ±15 Signaling relay acc. to IEC A I th = 1.5 kv U imp = 4 V U i = 250 Load capacity of the signaling relay U e V DC - 1; I e A AC- 15; I e A 1.5 Short-circuit protection Max. fuse protection DIAZED 2 A glgg Electronic fuse monitor, AC version (EFM 20) Size / Apparent power consumption S VA Approx. 2.5 Internal resist. of measurement circuit MΩ R in > 6 Storage temperature C Operating temperature C Operating temperature (500 V or 500 A) C Protection rating in closed IP40 in-line disconnector Rated operating voltage of the main control switching devices V AC Hz 50/60 Voltage limits % ±15 Undervoltage V 75 Overvoltage V 425 Voltage drop for faulty fuses V > 1 Delay time s 0.1 Relay 2 Same as relay 1 (fuse monitor) Storage function Off Open/closed-circuit principle Closed-circuit principle Mode Run mode Menu option Display of voltage values/messages Signaling relay acc. to IEC A I th = 1.5 kv U imp = 4 V U i = 250 Signaling relay 1 1 changeover contact for fuse monitoring only Signaling relay 2 1 changeover contact as output for central fault OR as signaling relay 1 (presetting) Load capacity of the signaling relay U e V DC - 1; I e A AC- 15; I e A 1.5 Short-circuit protection Max. fuse protection DIAZED 2 A glgg Electronic fuse monitor, DC version (EFM 25) Size / Apparent power consumption S VA Approx. 2.5 Internal resist. of measurement circuit MΩ R in > 6 Storage temperature C Operating temperature C Operating temperature (500 V or 500 A) C Protection rating in closed IP40 in-line disconnector Rated operating voltage of the main V DC control switching devices Voltage limits % ±15 Undervoltage V 200 Overvoltage V 240 Voltage drop for faulty V > 20 fuses Delay time s 0.1 Relay 2 Same as relay 1 (fuse monitor) Storage function Off Open/closed-circuit principle Closed-circuit principle Mode Run mode Menu option Display of voltage values/ messages Signaling relay acc. to IEC A I th = 1.5 kv U imp = 4 V U i = 250 Signaling relay 1 1 changeover contact for fuse monitoring only Signaling relay 2 1 changeover contact as output for central fault OR as signaling relay 1 (presetting) Load capacity of the signaling relay U e V DC - 1; I e A AC- 15; I e A 1.5 Short-circuit protection Max. fuse protection DIAZED 2 A glgg Ammeters Inputs x /1 A or x /5 A Overload Moving-iron measuring instruments 1.2 times Bi-metal measuring instruments 2 times Slave pointer Moving-iron measuring instruments min -- Bi-metal measuring instruments min 15 Power consumption Moving-iron measuring instruments VA 0.6 Bi-metal measuring instruments VA 1 Motorized operating mechanism Size / Supply voltage V DC 24 ± 2 Power consumption A Endurance (no limitation of switch disconnector according to IEC ) Operating cycles total 1600 Switch cycles under load 200 Signal duration s Min. 0.5 or continuous signal 176 Siemens 10/2015

179 NJ62 In-Line with Fuses up to 60 A General data Dimensional drawings -pole NJ62 switch disconnector, top view NSE0_ NJ62 0, size , NSE0_01875 NSE0_00259b NJ62 1, size 1 Plug-in contact Guide pin NSE0_ NSE0_00261b NJ62 and NJ62 4, sizes 2 and NSE0_ NSE0_0026b 21 NSE0_00264b Clearance between phases Alternating voltage versions, -pole 12,5 77, L1 L2 L NSE0_01878 Siemens 10/

180 NJ62 In-Line with Fuses up to 60 A General data Ammeters Moving-iron measuring instrument Bi-metal measuring instrument 48, ,1-0, 48 NSE0_01098 NSE0_ Snap-on mounting Snap-on mounting Left: View from the front Right: View from the right Current transformers Current transformer for NJ62 switch disconnectors, sizes NH00 and NH1 with feed-through opening Æ 21 mm Left: View from the front Right: View from the right Current transformer for NJ62 switch disconnectors, sizes 2 and NSE0_ NSE0_ ,5 85,5 10,5 16 0,5 40,5 64,5 65 6, Top: View from the top Bottom left: View from the front Bottom right: View from the right Current transformer for NJ62 switch disconnectors, sizes 00 and 1 with feed-through opening 14 mm Top: View from the top Bottom left: View from the front Bottom right: View from the right 0 NSE0_ , Siemens 10/2015

181 NJ62 In-Line with Fuses up to 60 A General data Circuit diagrams Typical circuit diagrams L1 L2 L L1 L2 L NSE0_02126 F1 F2 F T1 K L Typical circuit diagram with 1 current transformer wired on 1 ammeter, with 1 NO and 1 NC Typical circuit diagram with current transformers wired to multi-function plug, with 1 NO contact and 1 NC contact NSE0_02127 NSE0_02124 F1 F2 F T1 K L T2 K L T K L A L1 L2 L L1 L2 L NSE0_02125 F1 F2 F F1 F2 F T1 K L T1 K L A Typical circuit diagram with 1 current transformer wired to 1 ammeter and multi-function plug, with 1 NO contact and 1 NC contact Typical circuit diagram with 1 current transformer wired on 1 ammeter, with 1 NO and 1 NC Siemens 10/

182 NJ62 In-Line with Fuses up to 60 A General data L1 L2 L NSE0_02124 F1 F2 F T1 K L T2 K L T K L A Typical circuit diagram with current transformers wired on 1 ammeter and multi-function plug, with 1 NO and 1 NC 180 Siemens 10/2015

183 NJ62 In-Line with Fuses up to 60 A Position of the terminals and current transformers General data L1 L2 L L1 L2 L L1 L2 L NSE0_01926 L L2 L1 Position of the terminals for NJ62 switch disconnectors, size 00 Left: View from the top; Right: View from the right L1 L2 L L2 L1 L1 L2 L L L2 L L1 NSE0_01927 Position of the terminals for NJ62 switch disconnectors, size 1 Left: View from the top; Right: View from the right L1 L2 L L1 L2 L L1 L2 L NSE0_01928 L1 L2 L Positions of the terminals in the case of NJ62 switch disconnectors, sizes 2/ Left: View from the top; Right: View from the right Siemens 10/

184 Siemens AG 2016 NP1 Fuse up to 60 A Introduction Overview All key product features at a glance Box terminals available for all sizes Connection of circular conductors and laminated conductors Fuse monitoring possible throughout Busbar supports can be built over Conversion of 5/10 mm thick busbars without parts which can be lost or broken off Convertibility of cable feeder at top/bottom without intervention in the internal conducting paths Optimum integration in various system environments through cover levels and on busbar systems with/without base Touch protection also with rear incoming feeder Fuses are removed using a release shaft without the fuses being touched All units can be sealed and locked NP1 fuse switch disconnectors Overview of all components and accessory parts [ _ Z ` \ X ] Y ^ XW XX Z NSG0_0025 [ YW XZ XY X\ X` X[ X] 182 XX Box terminal XY Auxiliary conductor connection for box terminal Reach-around protection for Siemens busbar system XZ Flat connector [ Reach-around protection for Rittal busbar system X[ Auxiliary conductor connection for flat connector \ Locking device X\ Deep-drawn connection module ] Auxiliary switch with actuator X] Prism terminal ^ Molded-plastic masking frame X^ Auxiliary conductor connection for prism terminal _ Fuse carrier with MFM electromechanical fuse monitoring X_ Saddle terminal ` Fuse carrier with EFM 10 electronic fuse monitoring X` Cable connection cover XW Fuse carrier with EFM 20/25 electronic fuse monitoring YW Cable connection cover with rear reach-around protection X NP1 fuse switch disconnector Y Cover masking frame support Z Siemens 10/2015 X_ X^

185 NP1 Fuse up to 60 A Introduction Benefits Advantages during planning and configuration Low level of equipment variation due to easy convertibility of cable feeder at top/bottom (delivered from factory with cable feeder at bottom) Only one device variant for applications in industry and infrastructure thanks to touch and reach-around protection as a standard feature Uniform grid sizes for easy configuration Advantages during operation and service The optional rear covers for the cable connections ensure optimum touch protection even for switchgear assemblies with rear access Innovative design enables the highest safety for equipment and personnel Fuses can be released and removed using a release shaft Lockable and sealable design enables safe working and prevents unauthorized access Application Possible uses NP1 fuse switch disconnectors can be used for protecting and switching the most diverse electrical loads: Motor starter combinations In conjunction with SITOR semiconductor fuses for the protection of frequency converters and soft starters Fusing of compensation modules Cable feeders Group fusing of small loads The devices are optimized for operation in all kinds of system environments: Low-voltage switchgear assemblies for power distribution and MCCs (e.g. main and sub-distribution boards) Distribution systems with cover levels of 2 and 70 mm or and 70 mm Mechanical engineering Railway applications Fuse monitoring Fuse monitors are used to detect, indicate and report faults: MFM electromechanical fuse monitoring for AC/DC networks EFM 10 electronic fuse monitoring for AC networks EFM 20 electronic fuse monitoring with line monitoring for AC networks EFM 25 electronic fuse monitoring with line monitoring for DC networks Standards and specifications The NP1 fuse switch disconnectors are compliant with: IEC , EN IEC , EN Advantages during installation Only one device version is required for cable feeders at top/bottom and there is no need to intervene in the internal conducting paths One device version with very high short-circuit values dispenses with having to order and install arc splitters to increase the electrical values On all sizes it is possible to install two CO contacts for indicating the switching position All devices feature all-round touch protection Box terminals are available for all sizes and shorten the mounting time appreciably Snapping on the sizes NH000 and NH00 shortens the mounting time greatly compared to fixing with screws The screw-fixing method on sizes NH1, NH2 and NH provides for easy positioning and at the same time secure contacting of the larger and heavier device versions Small space requirement through compact devices and busbar supports which can be built over Device versions for busbar mounting can be converted to 5 mm or 10 mm thick busbars without parts which can be lost or broken off Mounting Floor mounting Sizes 000, 00 System cover (alternative) 70 Mounting plate Sizes 1, 2, NP1 fuse switch disconnector for floor mounting Busbar mounting Mounting on Siemens 8US busbar systems with 2/70 mm cover level 70 2 Mounting plate Base Busbar support Busbar support NP1 fuse switch disconnector for busbar mounting NSG0_0026 Mounting on Rittal Riline 60 busbar systems with base NSG0_0027 Siemens 10/

186 NP1 Fuse up to 60 A Introduction Technical specifications Standards IEC / EN , IEC / EN , VDE 0660 Part 7 Type NP NP11... NP NP NP Rated uninterrupted current I u A 160 1) For fuse links acc. to IEC Size and and 0 2 and 1 and 2 Conventional free air thermal current I th A Rated operational voltage U e At 50 Hz/60 Hz AC V With DC ( conducting paths series-connected) V With DC (2 conducting paths series-connected) V 220/ / / / /240 With utilization category AC-20 or DC-20 Max. V ) Rated insulation voltage U i V Rated impulse withstand voltage U imp kv Rated cond. short-circuit current with fuses (by fast switch on) Size/A 000/160 00/160 1/250 2/400 /60 Rated current at 500 V/690 V AC ka 80/50 80/50 80/50 80/50 80/50 Permissible let-through current of the fuses, peak value ka Short-circuit strength with fuses (with closed disconnector) Size/A 000/160 00/160 1/250 2/400 /60 Rated current at 500 V/690 V, rms value ka 120/ / / / /100 Let-through I 2 t value ka 2 s Permissible let-through current of the fuses, peak value ka Rated making capacity ka with isolating blades at 500 V AC Rated making and breaking capacity At AC-21B, 22B, 2B 400 V AC A At AC-21B 500 V AC A At AC-22B 500 V AC A At AC-2B 500 V AC A At AC-21 B 690 V AC A At AC-22B 690 V AC A At AC-2B 690 V AC A With DC-21B (2 cond. paths series-connected) 240 V DC A With DC-22B (2 cond. paths series-connected) 240 V DC A With DC-2B (2 cond. paths series-connected) 240 V DC A With DC-21B ( cond. paths series-connected) 440 V DC A With DC-22B ( cond. paths series-connected) 440 V DC A With DC-2B ( cond. paths series-connected) 440 V DC A Capacitor switching capacity At 400 V AC Capacitor rating kvar Rated current I n A At 525 V AC Capacitor rating kvar Rated current I n A Permissible ambient temperature ) C for operation, during storage Mechanical endurance, operating cycles Degree of protection (operator side) Without molded-plastic masking frame/cable lug cover IP0 (switch closed) / IP20 (switch open) With molded-plastic masking frame/cable lug cover IP40 (switch closed) / IP20 (switch open) Power loss of the switch at I th (plus fuses) W Maximum power loss of the usable fuses (per fuse) 4) W 7.5 5) Max. conductor cross-section of main conductor connection Flat terminals mm 2 Up to 95 (M8) Up to 150 (M10) Permissible mounting position 1) 160 A available in combination with feeder terminal NP1 92-1BD00, otherwise max. 100 A. 2) Up to pollution degree 2, above this U i = 690 V ) Only with isolating links; otherwise, please observe specifications of fuse manufacturer. Up to 240 (M10) Up to 00 (M10) Box terminals mm Prism terminal mm Saddle terminals mm Laminated conductors in box terminal mm 8x8 9x8 10 x x 2 20 x 2 Rated operational current of auxiliary switch (at max. 250 V AC) NP FA00 auxiliary switch A 0.25 (I th =5A) NP FB00 auxiliary switch (solid-state compatible) A 0.1 (I th =0.1A) Vertical and horizontal (no derating) 4) Values are valid when using LV HRC (NH) fuse systems with characteristic gg. If using fuses for semiconductor protection, please refer to the assignment table, see page ) For operation up to 160 A, max. 9W. 184 Siemens 10/2015

187 NP1 Fuse up to 60 A Fuses Overview The NP1 fuse switch disconnectors are suitable for all fuses in LV HRC design; see Catalog LV 10, chapter "Fuse Systems". SITOR semiconductor fuses in LV HRC design can also be used, although it must be noted that, compared to cable and line protection fuses, these get much hotter during operation. For this reason, the fuse must be operated below the rated current I n of the device (derating) when installed in a closed switching device. The following table shows the permissible load currents of the SITOR semiconductor fuses for installation in NP1. The values were determined using the conductor cross-sections specified in the table. Note If using smaller cross-sections, a considerably higher derating is required due to the lower heat dissipation. SITOR semiconductor fuses for NP1 fuse switch disconnectors: Assignment table SITOR semiconductor fuse data Permissible load currents of fuse when installed in: NP1 for floor mounting NP1 for busbar mounting Type 1)2) Rated current I n Rated voltage ) Operational class Size Required conductor crosssection Cu Type Size Permissible load current 4) Type Size Permissible load current 4) 5) A V AC mm² A A NC gr 70 NP NP NC gr 95 NP NP NC gr 120 NP NP NC gr 185 NP NP NC gr 240 NP NP116 2 NC ar 240 NP NP NC ar 2x (40x5) NP NP NC ar 2x95 NP NP NC ar 2x120 NP NP NC ar 2x150 NP NP NC ar 2x (40x5) NP NP NC gr 70 NP NP NC gr 95 NP NP NC gr 120 NP NP NC gr 240 NP NP NC gr 2x 150 NP NP NE gr NP NP NE gs 00 5 NP NP NE gr 00 5 NP NP NE gs NP NP NE gr NP NP NE gs 1 70 NP NP NP NP NE1224-2/ gr 1 70 NP NP NP NP NE1224-2/ gr 1 70 NP NP NP NP NE1225-2/ gr 1 95 NP NP NP NP NE gs NP NP NP NP NE1227-2/ gr NP NP NP NP NE gs 1 2x 70 NP NP NE120-2/ gr 1 2x 70 NP NP NP NP NE gs 2 2x 95 NP NP NP NP NE11-2/ gr 2 2x 95 NP NP NP116 0 NP NE gs 2 2x 95 NP NP NE12-2/ gr 2 2x 95 NP NP NP NP NE gs 2 2x 120 NP116 0 NP NE1-2/ gr 2 2x 120 NP NP NE gs 2 2x 120 NP NP116 0 NE14-2/ gr 2 2x 120 NP NP116 0 Siemens 10/

188 NP1 Fuse up to 60 A Fuses SITOR semiconductor fuse data Type 1)2) Rated current I n Rated voltage ) Operational class Size Required conductor crosssection Cu Permissible load currents of fuse when installed in: NP1 for floor mounting NP1 for busbar mounting Type Size Permissible Type Size Permissible load load current 4) 4) 5) current A V AC mm² A A NE gs 2x 150 NP NP NE145-2/ gr 2x 150 NP NP NE gs 2x 185 NP NP NE146-2/ gr 2x 185 NP NP NE gs 2x (40x5) NP NE gr 2x (40x5) NP NE147-2/ gr 2x (40x5) NP NE gs 2x (50x5) NP NE gr 2x (50x5) NP NE148-2/ gr 2x (50x5) NP NE1447-2/ gr 2x (40x5) NP NE1448-2/ gr 2x (40x8) NP NE gs NP NP NP NP NE gs NP NP NP NP NE gs NP NP NP NP NE gs NP NP NP NP NE gs NP NP NP NP NE gs NP NP NP NP NE gs NP NP NP NP NE gs NP NP NP NP NE ar 1 5 NP NP NP NP NE ar 1 50 NP NP NP NP NE ar 1 70 NP NP NP NP NE ar 1 95 NP NP NP NP NE ar NP NP NP NP NE20-0B ar NP NP NE ar NP NP NE22-0B ar NP NP NE ar 1 2x 150 NP NP NE2-0B ar NP NP NP NE ar 2 2x 150 NP NP NE4-0B ar 2 2x 150 NP NP NE ar 2 2x 185 NP NP NE ar 2 2x 185 NP NP NE ar 2 2x (40x5) NP NP NE ar 2 2x 240 NP NP NE ar 2 2x (40x8) NP NP NE gr 0 6 NP NP NE gr 0 10 NP NP NE gr 0 10 NP NP NE ar 0 16 NP NP NE ar 0 25 NP NP NE ar 0 5 NP NP NE ar 0 50 NP NP NE ar 0 70 NP NP NE427-0B ar NP NP NP NP NE40-0B ar NP NP NP NE4-0B ar 2 2x (0x5) NP NP Siemens 10/2015

189 SITOR semiconductor fuse data Type 1)2) Rated current I n Rated voltage ) Operational class Size Required conductor crosssection Cu NP1 Fuse up to 60 A A V AC mm² A A NE44-0B ar 2 2x (0x5) NP NP NE ar 2 2x (50x5) NP NP NE gr 00 4 NP NP NE gr 00 6 NP NP NE gr NP NP NE gr NP NP NE ar NP NP NE ar 00 5 NP NP NE ar NP NP NE ar NP NP ) Due to the mechanical stress on the relatively long fuse blades, SITOR NE41 semiconductor fuses should only be switched occasionally and only at zero current. 2) For permissible load currents for NE8-0MK, see Configuration Manual "Fuse Systems", or on request. ) NP1 fuse switch disconnectors may be operated at up to 1000 V AC/DC with the following restrictions: - Pollution degree 2 (instead of ) - AC20/DC20 - i. e. must not be switched under load 4) In the case of cyclic loads, the currents may have to be further reduced (precise values on request). 5) Values apply if used with 0 x 10 mm rails; for size 00: 12 x 5 mm and top busbar connection values for other configurations available on request. Fuses Permissible load currents of fuse when installed in: NP1 for floor mounting NP1 for busbar mounting Type Size Permissible Type Size Permissible load load current 4) 4) 5) current Siemens 10/

190 NP1 Fuse up to 60 A Dimensions, hole drilling templates, circuit diagrams Dimensional drawings Handle positions K M L N F G H I A C E J B A, B C D I201_18926 Dimensions (mm) NP112-1CA20 Handle positions, size 000 A B C D E F G H I J K L M N 76,6 60,6 71,6 88,8 141,7 110,4 188 Siemens 10/2015

191 NP1 Fuse up to 60 A Dimensions, hole drilling templates, circuit diagrams H I Siemens AG 2016 K M L N F G B A C D E J A, B C D I201_18927 Dimensions (mm) NP11-1CA10 NP11-1CA20 NP11-1BB.0 A B C D E F G H I J K L M N 86,5 6,7 87,7 105, ,5 6,7 87,7 105, ,5 6,7 87,7 105,8 210, Handle positions, size 00 Siemens 10/

192 NP1 Fuse up to 60 A Dimensions, hole drilling templates, circuit diagrams 70 2 I E G J A B C D F H A, B C D Dimensions (mm) NP114-1DA.0 NP115-1DA.0 NP116-1DA.0 I201_18928 A B C D E F G H I J ,7 275,6 129, , , , Handle positions, sizes 1, 2 and 190 Siemens 10/2015

193 NP1 Fuse up to 60 A Standard rail mounting Dimensions, hole drilling templates, circuit diagrams Floor mounting 88, I201_ ,8 76,9 I201_1891 Standard rail mounting, size 000 Floor mounting in distribution boards Busbar mounting A I201_18929 C Z B Busbar mounting, sizes 000 and 00 on the left, sizes 1, 2, and on the right I201_ Abmessungen (mm) NP11-1CA10 NP11-1CA10 NP11-1CA20 NP11-1CA20 NP114-1CA.. NP114-1CA.. Z A B C , ,8 8,5 8, , ,8 7,5 7, , ,7 105,5 75,5 Standard rail mounting, size 00 Siemens 10/

194 NP1 Fuse up to 60 A Dimensions, hole drilling templates, circuit diagrams Hole drilling templates I201_1895 I201_189 76,8 50 D E 141,7 A C F 5 B G Hole drilling template, size ,8 I201_1894 Dimensions (mm) NP114-1CA.0 NP115-1CA.0 NP116-1CA.0 Hole drilling template, sizess 1, 2 and A B C D E F G ,5 12,5 Mounting position I201_ ,8 Hole drilling template, size 00 Mounting position, size Siemens 10/2015

195 NP1 Fuse up to 60 A Dimensions, hole drilling templates, circuit diagrams Circuit diagrams AC applications L1 L2 L I201_1897 Circuit diagram for AC applications DC applications L+ I201_1898 L- Circuit diagram for 220 V/240 V DC applications L+ I201_1899 L- Circuit diagram for 440 V DC applications (floor mounting only) Siemens 10/

196 NP5 Fuse up to 60 A Introduction Overview NP5 0 NP5 2 NP5 4 NP5 fuse switch disconnector range NP5 fuse switch disconnectors are controls for the occasional manual switching/isolating of loads and distribution boards. They are able to switch on, control and switch off the specified rated current (including a specific overload). With the NP5 fuse switch disconnectors, all poles of downstream electric loads can be safely disconnected from the system under load. Application The NP5 fuse switch disconnectors are ideally suited for surface mounting and installation in distribution boards (e.g. ALPHA, SIKUS), meter cabinets (e.g. ALPHA 400-ZS), and molded-plastic distribution systems such as 8HP. The ability to mount them on a range of different busbar systems allows their very diverse implementation in switchgear cabinet and control engineering. The NP5 fuse switch disconnectors are ideal for operation in combination with other switching devices, for example in capacitor modules for reactive-power compensation. In conjunction with semiconductor protection fuses (e.g. SITOR), these are used for the effective protection of frequency converters and soft starters. The NP5 fuse switch disconnectors are suitable for use in any climate and comply with standards IEC , IEC and DIN VDE 0660 Part 107. In addition, the NP5 series of fuse switch disconnectors complies with the requirements of BS 5419 and is also approved for operation in marine applications. All NP5 fuse switch disconnectors can be sealed as standard or using accessories. Permissible mounting position NSE0_00182 NP5 194 Siemens 10/2015

197 NP5 Fuse up to 60 A Introduction Technical specifications Standards IEC , IEC , VDE 0660 Part 107 Type NP50 NP52 NP5 NP54 Rated uninterrupted current I u A For fuse links acc. to IEC Size 00 1 and 0 2 and 1 and 2 Conventional free air thermal current I th A Rated operational voltage U e 50/60 Hz AC V 690 DC V 440 ( conducting paths series-connected), 220 (2 conducting paths in series, fuse monitoring by RV) Rated insulation voltage U i V 690 1) 690 1) 690 1) 690 1) Rated impulse withstand voltage U imp kv Rated conditional short-circuit current with fuses (by fast switch on) Rated current Size/A 00/160 1/250 2/400 /60 At 500 V AC (rms value) ka Permissible let-through current of the fuses (peak value) ka Short-circuit strength with fuses (with closed disconnector) Rated current Size/A 00/160 1/250 2/400 /60 At 500 V AC (rms value) ka Maximum permissible let-through I 2 t value ka 2 s Permissible let-through current of the fuses (peak value) ka Rated short-circuit making capacity with isolating blades 2) Size At 500 V AC (peak value) ka Rated making and breaking capacity 2) (infeed from top or bottom) ) Size Breaking current I c At p.f. = 0.5, rms value at 500 V A At p.f. = 0.5, rms value at 690 V A At p.f. = 0.5 and 400 V AC, with fuse links, rms value A Rated operational current I e At AC-21B, AC-22B, AC-2B at 400 V AC, with fuse links A At AC-21B, AC-22B, AC-2B at 500 V AC, with fuse links A At AC-21B, AC-22B at AC 690 V A At AC-2B at AC 690 V A At 220 (440) V DC, with 2 () conducting paths series-connected and fuse links: Breaking current I c (L/R = 15 ms) A Rated operational current I e at DC-2B A Capacitor switching capacity Capacitor rating at 400 V AC kvar Rated current I n at 525 V AC A Capacitor rating kvar Rated current I n A Permissible ambient temperature C for operation 4), during storage Mechanical endurance, operating cycles 1600 Degree of protection Without molded-plastic masking frame IP00, for NP52 with terminal clamp connection degree of protection IP10 With molded-plastic masking frame with closed fuse carrier on the operator side IP0 With molded-plastic masking frame with open fuse carrier IP10 Power loss of the switch at I th (without power loss of the fuse links) Without busbar adapter W 7.8 (16.) 5) Maximum power loss of the usable fuses (per fuse) 6) W Main conductor connections Flat terminal for connection of Crimped cable lugs acc. to DIN 4624 (conductor cross-section, stranded) mm Pressed cable lugs acc. to DIN 4625 (conductor cross-section, stranded) mm Busbars (usable busbar width) mm Clamp terminals mm ) Auxiliary switch 1 NO + 1 NC (accessories) The same voltage potential must be applied to the NO and NC contacts At 50 Hz/60 Hz to 400 V AC, rated operational current I e at AC-12/AC-15 A A 16/6 Flat plug-in terminals (DIN 46244) A Permissible mounting position Vertical or horizontal (switching capacity may be reduced with horizontal installation) Signaling contact for solid-state fuse monitoring 2NO + 1NC Rated operational current I e at 250 V, DC-1 A 0.27 Rated operational current I e at 240 V, AC-15 A 1.5 Thermal free-air rated current I th A 5 1) When observing degree of pollution 2 (instead of ) operation is also possible up to U i = 1000 V. 2) Rated making and breaking current according to IEC : Rated making current I = 10 I e (AC-2); I e (AC-22); 1.5 I e (AC-21); Rated breaking current I e = 8 I e (AC-2); I e (AC-22); 1.5 I e (AC-21). ) When electronic fuse monitors are used, infeed must be from the top. 4) When using isolating blades. If using fuse links, please observe the fuse manufacturer s specifications. 5) With busbar adapter. 6) Values are valid when using LV HRC (NH) fuse systems with characteristic gg. If using fuses for semiconductor protection, please refer to the assignment table, see page ) When connecting one conductor. For 2 conductors max. 1 x 50 mm 2 and 1 x 5mm 2. Siemens 10/

198 NP5 Fuse up to 60 A Introduction Dimensional drawings NP5660, 160 A For surface mounting ,5 70 Ø5, NSE0_00226a NP5060, 160 A With molded-plastic masking frame for any type of installation NSE0_0021a M8 22 a Auxiliary switches 228 Type a b c d NY NY NY NY NY c b d 12 Molded-plastic masking frame NY1107 NSE0_00227b NP5660, 160 A With fuse monitoring by RV1 circuit breaker, with connector 161, NSE0_00228b For plastic frame Cutout for NP5660, with and without auxiliary switch NSE0_00229a 70 5, Cutout for NY1208 mounting kit NSE0_0020a 126, , For metal frame Cutouts for NP5 228 B h NSE0_00906b H Type Molded-plastic masking Panel cut-out min. frames Molded-plastic masking frame behind panel Type B H B H h 1) NP566 NY1105 2) NP566 NY1125 NP526 NY NP56 NY NP546 NY Molded-plastic masking frame in the front of the panel Type B H B H h 1) NP566 NY NP566 NY NP526 NY NP56 NY NP546 NY ) h = Distance from upper edge of panel cut-out to center of disconnector mounting. 2) With standard molded-plastic masking frame behind panel and corresponding panel cutout, the standard switching capacity is reduced to the following AC 2B values: At 400 V I e 160 A, at 500 V from I e 160 A to 125 A and At 690 V from I e 100 A to 50 A Circuit diagrams 196 Siemens 10/2015

199 NP5 Fuse up to 60 A Introduction Function for auxiliary contacts main contact elements with NP5 Off On Off 1-4 (1 NO) 1-14 (1 NO) 1-2 (1 NC) (1 NC) NP40 1, ( NO) NP50 60 ( NO) NP (1 NO) (1 NC) NP52 60 ( NO) NP5 60 ( NO) NP54 60 ( NO) Auxiliary switch For NP40 1, and NP4. 7 Contact closed Contact open For NP5 NSE_00174e NP5 fuse switch disconnector with fuse monitoring (with RV1 motor starter protector, with auxiliary switch 1 NO + 1 NC) Circuit diagram of main circuit Circuit diagram of auxiliary circuit!! 0 8 * 7 *!! #! " " $ " 5 - % # >.! * 9 0 Q1 = Fuse switch disconnector Q2 = Circuit breaker K1 = Contactor S1 = ON button S0 = OFF button F1 = Overload relay F2 = Control cable fuse NP5 fuse switch disconnector with electronic fuse monitoring Block diagram L1 L2 L LED indication Operation Fault F1 Fault F2 Voltages Fault F F1 F2 F Resistor network Microcontroller Switching stage Parameterization Synchronization signals Power supply unit L1' L2' L' NSE0_00177a Version "A" (open-circuit principle): Auxiliary switches pick up only if fuse defective and voltage is applied. Version "R" (closed-circuit principle): Auxiliary contact elements pick up only provided voltage is present and fuses are intact. X1 Signal leads BN BK BU GY WH RD 1 Siemens 10/

200 NP5 Fuse up to 60 A Fuses Overview NP5 fuse switch disconnectors are suitable for all fuses in LV HRC design, see Catalog LV10, chapter "Fuse Systems". SITOR semiconductor fuses in LV HRC design can also be used, although it must be noted that, compared to cable and line protection fuses, these get much hotter during operation. For this reason, the fuse must be operated below the rated current I n of the device (derating) when installed in a closed switching device. The following table shows the permissible load currents of the SITOR semiconductor fuses for installation in NP5. The values were determined using the conductor cross-sections specified in the table. Note If using smaller cross-sections, a considerably higher derating is required due to the lower heat dissipation. SITOR semiconductor fuses for NP5 fuse switch disconnectors: Assignment table SITOR semiconductor fuse data Permissible load currents of fuse when installed in NP5 for floor mounting Type NP5 Alternative type NP5 Type 1)2) Rated current I n Rated voltage ) Operational class Size Required conductor crosssection Cu Type Size Permissible load current 4) Type Size Permissible load current 4) A V AC mm² A A NC gr 70 NP NC gr 95 NP NC gr 120 NP NC gr 185 NP NC gr 240 NP NC ar 240 NP NC ar 2x (40x5) NP NC ar 2x (50x5) NP NC ar 2x (40x8) NP NC ar 2x (40x8) NP ) NC ar 2x (50x8) NP ) NC ar 2x (50x8) NP ) NC ar 2x (50x8) NP ) NC ar 2x95 NP NC ar 2x120 NP NC ar 2x150 NP NC ar 2x (40x5) NP NC ar 2x (40x8) NP NC gr 70 NP NC gr 95 NP NC gr 120 NP NC gr 240 NP NC gr 2x 150 NP NC8444-C ar 2x (60x6) NP ) NE gr NP NE gs 00 5 NP NE gr 00 5 NP NE gs NP NE gr NP NE gs 1 70 NP NP NE1224-2/ gr 1 70 NP NP NE gs 1 95 NP NP NE gr 1 95 NP NP NE gr 1 95 NP NP NE gs NP NP NE gr NP NP NE gr NP NP NE gs 1 2x 70 NP NE120-2/ gr 1 2x 70 NP NE gs 2 2x 95 NP NP54 50 NE11-2/ gr 2 2x 95 NP NP54 50 NE gs 2 2x 95 NP NP NE12-2/ gr 2 2x 95 NP NP Siemens 10/2015

201 NP5 Fuse up to 60 A Fuses SITOR semiconductor fuse data Type 1)2) Rated current I n Rated voltage ) Operational class Size Required conductor crosssection Cu Permissible load currents of fuse when installed in NP5 for floor mounting Type NP5 Alternative type NP5 Type Size Permissible load current 4) Type Size Permissible load current 4) A V AC mm² A A NE gs 2 2x 120 NP NE1-2/ gr 2 2x 120 NP NE gs 2 2x 120 NP NE14-2/ gr 2 2x 120 NP NE gs 2x 150 NP NE145-2/ gr 2x 150 NP NE gs 2x 185 NP NE146-2/ gr 2x 185 NP NE gs 2x (40x5) NP ) NE gr 2x (40x5) NP ) NE147-2/ gr 2x (40x5) NP ) NE gs 2x (50x5) NP ) NE gr 2x (50x5) NP ) NE148-2/ gr 2x (50x5) NP ) NE1447-2/ gr 2x (40x5) NP ) NE1448-2/ gr 2x (40x8) NP ) NE gs NP NE gs NP NE gs NP NE gs NP NE gs NP NE gs NP NE gs NP NE gs NP NE ar 1 5 NP NP NE ar 1 50 NP NP NE ar 1 70 NP NP NE ar 1 95 NP NP NE ar NP NP NE20-0B ar NP NE ar NP NE22-0B ar NP NE ar 1 2x 150 NP NE2-0B ar NP NE ar 2 2x 150 NP NE4-0B ar 2 2x 150 NP NE ar 2 2x 185 NP NE ar 2 2x 185 NP NE ar 2 2x (40x5) NP NE ar 2 2x 240 NP NE ar 2 2x (40x8) NP NE gr 0 6 NP NE gr 0 10 NP NE gr 0 10 NP NE ar 0 16 NP NE ar 0 25 NP NE ar 0 5 NP NE ar 0 50 NP NE ar 0 70 NP NE427-0B ar NP NP NE40-0B ar NP NP NE4-0B ar 2 2x (0x5) NP NP Siemens 10/

202 NP5 Fuse up to 60 A Fuses SITOR semiconductor fuse data Type 1)2) Rated current I n Rated voltage ) Operational class Size Required conductor crosssection Cu Permissible load currents of fuse when installed in NP5 for floor mounting Type NP5 Alternative type NP5 Type Size Permissible load current 4) Type Size Permissible load current 4) A V AC mm² A A NE44-0B ar 2 2x (0x5) NP NE ar 2 2x (50x5) NP NE gr 00 4 NP NE gr 00 6 NP NE gr NP NE gr NP NE ar NP NE ar 00 5 NP NE ar NP NE ar NP ) Due to the mechanical stress on the relatively long fuse blades, SITOR NE41 semiconductor fuses should only be switched occasionally and only at zero current. 2) For permissible load currents for NE8-0MK, see Configuration Manual "Fuse Systems", or on request ) NP1 fuse switch disconnectors may be operated at up to 1000 V AC/DC with the following restrictions: - Pollution degree 2 (instead of ) - AC20/DC20 - i. e. must not be switched under load 4) In the case of cyclic loads, the currents may have to be further reduced (precise values on request). 5) The fuse can also be operated at a higher rated uninterrupted current than the 60 A current of the NP54. However, in this case, the NP54 must not be switched under load (utilization category AC-20). 200 Siemens 10/2015

203 NJ4, NJ5 In-Line Fuse up to 2000 A Introduction Overview All key product features at a glance Compliant with IEC/EN , IEC/EN Voltage levels up to 690 V AC Rated operational current from 160 A to 2000 A Fuse links according to IEC Part 1 can be used nickel-plated fuse blades are not permissible due to the high transfer resistance In open position safe from touch by the back of the hand (exception NJ56: IP00) Parking position for maintenance 1-pole or -pole switchable Vertical and horizontal mounting position Climate-proof Degree of protection IP0 with closed fuse carriers, IP10 with open fuse carriers (exception NJ56: IP00) NJ4/NJ5 fuse switch disconnectors Overview of all components and accessory parts: NJ4/NJ5 in size Cover 2 Terminal strip Busbar terminal 4 Adapter for screw fixing on busbar systems 9 Prism terminal 10 Box terminal 11 Cover 12 NJ4/5 fuse switch disconnector Basic device size Current transformer 1 Auxiliary switch mounting kit 6 Distance compensation 7 Flat connector 8 Saddle terminal Siemens 10/

SENTRON Switching and Protection Devices Switch Disconnectors

SENTRON Switching and Protection Devices Switch Disconnectors SENTRON Switching and Protection Devices Switch Disconnectors /2 Introduction 3K, 3KE, 3LD Switch Disconnectors 3K, 3KE Switch Disconnectors up to 1000 /4 General data /8 Floor mounting 3LD Main and EMERGENCY-STOP

More information

BETA Switching Switches and Light Indicators

BETA Switching Switches and Light Indicators Siemens AG 2008 BETA Switching /2 Product overview /3 5TE8 control switches / 5TE4 pushbuttons /2 5TE5 light indicators /5 5TE8 ON/OFF switches /22 5TE9 busbars /24 5TE switch disconnectors Siemens ET

More information

3NP1 Fuse Switch Disconnectors up to 630 A

3NP1 Fuse Switch Disconnectors up to 630 A Switch Disconnectors 3NP1 Fuse Switch Disconnectors up to 630 A Introduction Overview All key product features at a glance available for all sizes Connection of circular conductors and laminated conductors

More information

Switch Disconnectors. SENTRON 3NP5 Fuse Switch Disconnectors up to 630 A. Introduction. 7/106 Siemens LV

Switch Disconnectors. SENTRON 3NP5 Fuse Switch Disconnectors up to 630 A. Introduction. 7/106 Siemens LV Switch Disconnectors Introduction Siemens AG 2010 Overview 3NP5 0 3NP5 2 3NP5 fuse disconnector range 3NP5 4 SENTRON 3NP5 fuse disconnectors are controls for the occasional manual ing/isolating of loads

More information

Circuit-Breakers M4 166 for motor protection. Auxiliary contacts 167 Signalling switch Auxiliary releases

Circuit-Breakers M4 166 for motor protection. Auxiliary contacts 167 Signalling switch Auxiliary releases Index Page Circuit-Breakers M4 166 for motor protection Auxiliary contacts 167 Signalling switch Auxiliary releases Insulated 3-pole busbar system 168 Terminal block DIN-rail adapters 169 Busbar adapters

More information

Page. Circuit-Breakers M4 2 for motor protection. Auxiliary contacts 3 Signalling switch Auxiliary releases

Page. Circuit-Breakers M4 2 for motor protection. Auxiliary contacts 3 Signalling switch Auxiliary releases Circuit Breakers M4 Page Circuit-Breakers M4 2 for motor protection Auxiliary contacts 3 Signalling switch Auxiliary releases Insulated 3-pole busbar system 4 Terminal block DIN-rail adapters 5 Busbar

More information

8WH2 Spring-Loaded Terminals

8WH2 Spring-Loaded Terminals 8WH2 Spring-Loaded Terminals /2 Introduction /3 General data on 8WH /7 8WH through-type terminals 1) /18 8WH hybrid through-type terminals 1) /21 8WH fuse terminals /23 8WH isolating blade terminals /25

More information

Protection Equipment

Protection Equipment Protection Equipment Price Groups 101, 102, 121, 131, 143 /2 Introduction Motor Starter Protectors/ Circuit Breakers SIRIUS 3RV2 Motor Starter Protectors up to 40 A new /7 General data /13 For motor protection

More information

Control Circuit Protection

Control Circuit Protection Contents 5SJ4 Branch Circuit Protectors 5SY4 Supplementary Protectors 5SY6 Supplementary Protectors 16/19 5SJ4 Page Selection and ordering data 1-pole up to 63A 16/4 1-pole, 2-pole, 16/5 3-pole, 240VAC

More information

SENTRON 3NP1 Fuse Switch Disconnectors up to 630 A

SENTRON 3NP1 Fuse Switch Disconnectors up to 630 A Introduction Overview All key product features at a glance available for all sizes Connection of circular conductors and laminated conductors Fuse monitoring possible throughout Busbar supports can be

More information

SIRIUS 3RV2 Motor Starter Protectors/Circuit Breakers up to 40 A Accessories Enclosures and front plates

SIRIUS 3RV2 Motor Starter Protectors/Circuit Breakers up to 40 A Accessories Enclosures and front plates Motor Starter Protectors/Circuit Breakers SIRIUS 3RV2 Motor Starter Protectors/Circuit Breakers up to 40 A Accessories Enclosures and front plates Overview Enclosures For stand-alone installation of 3RV20

More information

Product index. 4 - Manual motor protectors. Phone: Fax: Web: -

Product index. 4 - Manual motor protectors. Phone: Fax: Web:  - Product index -....1.3 Features and benefits...1 General information Suitable applications...2 -.3 Motor ratings... Pilot duty ratings and overload trip classes...5 Ordering details Type MS116...6 Type

More information

Approvals UL 508; CSA-C22.2 No ; IEC/EN ; CE marking

Approvals UL 508; CSA-C22.2 No ; IEC/EN ; CE marking MainswitchRearmounting Partno. T0-2-1/V/SVB-SW Articleno. 045992 Front IP65 Deliveryprogramme Product range Switch-disconnectors Basic function Main switches Maintenance switches Manual override switches

More information

Product index. 4 - Manual motor protectors. Manual motor protectors. Manual motor protectors Low Voltage Products & Systems 4.

Product index. 4 - Manual motor protectors. Manual motor protectors. Manual motor protectors Low Voltage Products & Systems 4. Product index -....1.3 Features and benefits...1 General information Suitable applications...2 -.3 Motor ratings... Pilot duty ratings and overload trip classes...5 Ordering details Type MS116...6 Type

More information

MULTIBLOC 3.ST8 Size 3, 630A, 690VAC, Design for Bottom Fitting, 3-,4-pole

MULTIBLOC 3.ST8 Size 3, 630A, 690VAC, Design for Bottom Fitting, 3-,4-pole MULTIBLOC 3.ST8 IEC FUSE SWITCH DISCONNECTORS NH FUSE SWITCH DISCONNECTOR The production programme of MULTIBLOC series 3.ST8 comprises NH fuse switch disconnectors for 630A. They are designed for bottom

More information

Protection Equipment. 5/2 Introduction

Protection Equipment. 5/2 Introduction Protection Equipment /2 Introduction SIRIUS 3RV2 Motor Starter Protectors/ Circuit Breakers up to 40 A /6 General data /12 For motor protection /14 For motor protection with overload relay function /1

More information

8WH2 Spring-Loaded Terminals

8WH2 Spring-Loaded Terminals 8WH2 Spring-Loaded Terminals /2 Introduction /3 General data on 8WH /7 8WH through-type terminals 1) /18 8WH hybrid through-type terminals 1) /21 8WH fuse terminals /23 8WH isolating blade terminals /25

More information

3VU13, 3VU16 Circuit-Breakers

3VU13, 3VU16 Circuit-Breakers 3VU3, 3VU6 Circuit-Breakers Description The 3VU3, 3VU6 circuit-breakers are compact circuit-breakers for currents up to 80 A which operate according to the current limiting principle. The devices are used

More information

Terminal Blocks Product Catalog Terminal Block Supplement. Introduction. 8WH6 ipo Plug-In Terminals. 8WH6 ipo Installation Terminals

Terminal Blocks Product Catalog Terminal Block Supplement. Introduction. 8WH6 ipo Plug-In Terminals. 8WH6 ipo Installation Terminals Terminal Blocks 2013 Product Catalog Terminal Block Supplement Introduction 8WH6 ipo Plug-In Terminals 8WH6 ipo Installation Terminals 8WH2 Spring-Loaded Terminals 1 2 3 4 8WH 8WH5 Combination Plug-In

More information

MULTIBLOC 2.RST8 Size 2, 400A, 690VAC, Design for bus bar installation, Triple Pole

MULTIBLOC 2.RST8 Size 2, 400A, 690VAC, Design for bus bar installation, Triple Pole MULTIBLOC 2.RST8 IEC FUSE SWITCH DISCONNECTORS NH FUSE SWITCH DISCONNECTOR The production programme of MULTIBLOC 2.RST8 comprises NH fuse switch disconnectors for 400A. Products are designed in triple

More information

MULTIBLOC 1.RST8 Size 1, 250A, 690VAC, Design for bus bar installation, Triple Pole

MULTIBLOC 1.RST8 Size 1, 250A, 690VAC, Design for bus bar installation, Triple Pole MULTIBLOC 1.RST8 IEC FUSE SWITCH DISCONNECTORS NH FUSE SWITCH DISCONNECTOR The production programme of MULTIBLOC 1.RST8 comprises NH fuse switch disconnectors for 250A. Products are designed in triple

More information

Phone: Fax: Web: -

Phone: Fax: Web:  - HK1-11 HKF1-11 HK-11 HKS-20 uxiliary contacts Mounting uxiliary contacts position Pilot duty rating Instantaneous Lagging / leading / max. 116 132 5x 9x quantity ac dc NO NC NO NC 2 - - - HK1-20 Right

More information

Emergency stop without emergency switching off/emergency stop function. Locking facility Lockable in the 0 (Off) position N/O 0 B 0

Emergency stop without emergency switching off/emergency stop function. Locking facility Lockable in the 0 (Off) position N/O 0 B 0 MainswitchSurfacemounting Partno. T0-2-1/I1/SVB-SW Articleno. 207148 IP65 Deliveryprogramme Product range Switch-disconnectors Basic function Main switches Maintenance switches Manual override switches

More information

Approvals UL 508; CSA-C22.2 No ; CSA-C22.2 No. 94; IEC/EN ; CE marking

Approvals UL 508; CSA-C22.2 No ; CSA-C22.2 No. 94; IEC/EN ; CE marking MainswitchSurfacemounting Partno. P1-25/I2/SVB-SW Articleno. 207294 IP65 Deliveryprogramme Product range Switch-disconnectors Basic function Main switches Maintenance switches Manual override switches

More information

Siemens AG Price groups PG 14O, 41B, 41E, 41F, 41G, 41H, 41J, 42F, 42J

Siemens AG Price groups PG 14O, 41B, 41E, 41F, 41G, 41H, 41J, 42F, 42J Protection Equipment Siemens AG 2015 Click on the Article No. in the catalog PDF to access it in the Industry Mall and get all related information. Article-No. 3RA1943-2C 3RA1943-2B 3RA1953-2B 3RA1953-2N

More information

MULTIBLOC 1.ST8 Size 1, 250A, 690VAC, Design for Bottom Fitting, 1-,2-,3-,4-pole

MULTIBLOC 1.ST8 Size 1, 250A, 690VAC, Design for Bottom Fitting, 1-,2-,3-,4-pole MULTIBLOC 1.ST8 IEC FUSE SWITCH DISCONNECTORS NH FUSE SWITCH DISCONNECTOR The production programme of MULTIBLOC series 1.ST8 comprises NH fuse switch disconnectors for 250A. They are designed for bottom

More information

Emergency stop As an emergency switching off/emergency stop device. Standards According to IEC/EN , VDE 0113 Part 1

Emergency stop As an emergency switching off/emergency stop device. Standards According to IEC/EN , VDE 0113 Part 1 MainswitchSurfacemounting Partno. T0-2-8900/I1/SVB Articleno. 207151 CatalogNo. CT02-8900-I1CRQ Deliveryprogramme Product range Switch-disconnectors Basic function Main switches Maintenance switches Manual

More information

MS /27/2015. ABB contact for United States of America. General Information Extended Product Type: Categories

MS /27/2015. ABB contact for United States of America. General Information Extended Product Type: Categories Page 1 of 5 MS132-10 ABB contact for United States of America General Information Extended Product Type: Product ID: EAN: Catalog Description: Long Description: MS132-10 1SAM350000R1010 4013614400100 MS132-10

More information

Breakers and Switches. Switches Switch-disconnectors OT and OTM

Breakers and Switches. Switches Switch-disconnectors OT and OTM Breakers and Switches Switches Switch-disconnectors OT and OTM Switch-disconnectors OT16...4000 and OTM40...2500 Features Product overview 4 High performance, compact solution 6 Technical data Switch-disconnectors,

More information

Index. Manual Motor Starters 1. Auxiliary Contact Blocks 1. Trip Alarm Auxiliary 1. Switch. Shunt Release 1. Under-voltage Release 2.

Index. Manual Motor Starters 1. Auxiliary Contact Blocks 1. Trip Alarm Auxiliary 1. Switch. Shunt Release 1. Under-voltage Release 2. Index Index Page Manual Motor Starters 1 Auxiliary Contact Blocks 1 Trip Alarm Auxiliary 1 Switch Shunt Release 1 Under-voltage Release 2 Accessories 2 Busbar Connectors 2 Enclosures 2 Leistung, kw C mv

More information

General technical data: CONTACTOR, AC-3, 5.5KW/400V, 1NC, AC110V 50HZ, 120V 60HZ 3-POLE, SZ S00 SCREW TERMINAL. product brand name

General technical data: CONTACTOR, AC-3, 5.5KW/400V, 1NC, AC110V 50HZ, 120V 60HZ 3-POLE, SZ S00 SCREW TERMINAL. product brand name Data sheet CONTACTOR, AC-3, 5.5KW/400V, 1NC, AC110V 50HZ, 120V 60HZ 3-POLE, SZ S00 SCREW TERMINAL product brand name Product designation SIRIUS 3RT2 contactor General technical data: Size of contactor

More information

AF40... AF96 3-pole contactors Technical data

AF40... AF96 3-pole contactors Technical data Main pole - Utilization characteristics according to IEC Standards IEC 60947- / 60947-4- and EN 60947- / 60947-4- Rated operational voltage Ue max. 690 V Rated frequency (without derating) 50 / 60 Hz Conventional

More information

MS General Information Extended Product Type: MS

MS General Information Extended Product Type: MS MS132-1.6 General Information Extended Product Type: MS132-1.6 Product ID: 1SAM350000R1006 EAN: 4013614400063 Catalog Description: MS132-1.6 Manual Motor Starter Long Description: The MS132-1.6 manual

More information

3/2 Introduction. Unequipped Distribution Boards (Flat Pack) 3/6 8GK1 surface-mounting distribution boards

3/2 Introduction. Unequipped Distribution Boards (Flat Pack) 3/6 8GK1 surface-mounting distribution boards ALPHA 400 - DIN Wall-Mounted Distribution Boards /2 Introduction Unequipped Distribution Boards (Flat Pack) /6 8GK1 surface-mounting distribution boards Pre-Assembled Unequipped Distribution Boards /7

More information

PANEL PANEL MOUNTING COMPONENTS

PANEL PANEL MOUNTING COMPONENTS PANEL PANEL MOUNTING COMPONENTS For conventional wiring, Wöhner offers a comprehensive range of panel components for fastening to a DIN rail or mounting plate. The fuses and associated connection technology

More information

MULTIBLOC 2.ST8 Size 2, 400A, 690VAC, Design for Bottom Fitting, 3-,4-pole

MULTIBLOC 2.ST8 Size 2, 400A, 690VAC, Design for Bottom Fitting, 3-,4-pole MULTIBLOC 2.ST8 IEC FUSE SWITCH DISCONNECTORS NH FUSE SWITCH DISCONNECTOR The production programme of MULTIBLOC series 2.ST8 comprises NH fuse switch disconnectors for 400A. They are designed for bottom

More information

General technical data: CONTACTOR, AC-3, 4KW/400V, 2NO+2NC, DC 24V, 3-POLE, SZ S0 SCREW TERMINAL REMOVABLE AUX. SWITCH. product brand name

General technical data: CONTACTOR, AC-3, 4KW/400V, 2NO+2NC, DC 24V, 3-POLE, SZ S0 SCREW TERMINAL REMOVABLE AUX. SWITCH. product brand name Data sheet CONTACTOR, AC-3, 4KW/400V, 2NO+2NC, DC 24V, 3-POLE, SZ S0 SCREW TERMINAL REMOVABLE AUX. SWITCH product brand name Product designation SIRIUS 3RT2 contactor General technical data: Size of contactor

More information

SIRIUS 3RU2 Thermal Overload Relays

SIRIUS 3RU2 Thermal Overload Relays Overview 1 2 3 4 6 1 2 NSB0_0207a Connection for mounting onto contactors: Optimally adapted in electrical, mechanical and design terms to the contactors. The overload relay can be connected directly to

More information

Air Circuit Breakers

Air Circuit Breakers Siemens AG 204 /2 Introduction 3WL air circuit breakers/ non-automatic air circuit breakers up to 6300 A (AC), IEC /8 Introduction /9 3-pole, fixed-mounted versions /6 3-pole, withdrawable versions /23

More information

SIRCO M UL 508 Non-fusible disconnect switches standards UL and CSA from 16 to 100 A

SIRCO M UL 508 Non-fusible disconnect switches standards UL and CSA from 16 to 100 A Non-fusible disconnect switches SRCO M UL 58 sircm_132_a sircm_133_a The solution for > ndustrial control systems Rotary switch SRCO M 3 x 8 A Toggle switch SRCO M 3 x 8 A + 2 auxiliary contacts Strong

More information

Molded-Plastic Distribution Systems

Molded-Plastic Distribution Systems Molded-Plastic Distribution Systems / Introduction ALPHA 8HP molded-plastic distribution systems /8 Empty enclosures / Modular installation devices /4 DIAZED/NEOZED fuse systems /7 NP fuse switch disconnectors

More information

System pro M compact Miniature Circuit Breaker SU200M for branch circuit protection acc. to UL 489

System pro M compact Miniature Circuit Breaker SU200M for branch circuit protection acc. to UL 489 System pro M compact Miniature Circuit Breaker SU200M for branch circuit protection acc. to UL 489 2CDC021004S0014 2CDC021046S0014 The miniature circuit breaker SU 200 M is ABB s solution for UL 489 branch

More information

General technical data: CONTACTOR, AC-3, 11KW/400V, 1NO+1NC, AC110V 50HZ, 120V 60HZ 3-POLE, SZ S0 SCREW TERMINAL. product brand name

General technical data: CONTACTOR, AC-3, 11KW/400V, 1NO+1NC, AC110V 50HZ, 120V 60HZ 3-POLE, SZ S0 SCREW TERMINAL. product brand name Data sheet CONTACTOR, AC-3, 11KW/400V, 1NO+1NC, AC110V 50HZ, 120V 60HZ 3-POLE, SZ S0 SCREW TERMINAL product brand name Product designation SIRIUS 3RT2 contactor General technical data: Size of contactor

More information

An innovative technology

An innovative technology The range An innovative technology Description The new are load break switches that combine attractive style and optimised features due to their innovative design. This range, dedicated to industrial applications,

More information

Non-fusable disconnect switches standards UL and CSA from 16 to 100 A

Non-fusable disconnect switches standards UL and CSA from 16 to 100 A Non-fusible disconnect switches sircm_132_a sircm_133_a The solution for > Industrial control systems Rotary switch SIRCO M 3 x 80 A Toggle switch SIRCO M 3 x 80 A + 2 auxiliary contacts Competitive advantages

More information

D509E. Manual Motor - Starters

D509E. Manual Motor - Starters D509E Manual Motor - Starters Index Page Manual Motors Starters 182 Auxilliary Contact Blocks 182 Trip Alarm Aux. Switch 182 Shunt Release 182 Under-voltage Release 183 Accessories 183 Busbar Connectors

More information

Short form catalogue. Motor protection & control

Short form catalogue. Motor protection & control Short form catalogue Star Series Motor protection & control Motor Protection and Control up to 25 HP / 600 VAC Overview...2 Contactors and Overload Relays...11 4-pole Contactors...41 Control Relays...59

More information

System pro M compact Miniature Circuit Breaker SU200 M for branch circuit protection acc. to UL 489

System pro M compact Miniature Circuit Breaker SU200 M for branch circuit protection acc. to UL 489 Data Sheet System pro M compact for branch circuit protection acc. to UL 489 2CDC021004S0014 2CDC021046S0014 The miniature circuit breaker SU200 M is BB s solution for UL 489 branch circuit protection

More information

Air Circuit Breakers

Air Circuit Breakers Siemens AG 203 /2 Introduction 3WL air circuit breakers/ non-automatic air circuit breakers up to 6300 A (AC), IEC /8 Introduction /9 3-pole, fixed-mounted versions /6 3-pole, withdrawable versions /23

More information

MSW. MSW Catalog Number Sequence. Standard Features MSW 25 B- 3

MSW. MSW Catalog Number Sequence. Standard Features MSW 25 B- 3 Introducing the New WEG Series. The was developed according to IEC 60947-3 & UL508. The compact, reliable design of the allows the operator to safely disconnect power and isolate the circuit within the

More information

AF09... AF38 4-pole Contactors AC / DC Operated - with Screw Terminals

AF09... AF38 4-pole Contactors AC / DC Operated - with Screw Terminals AF09... AF38 4-pole Contactors AC / DC Operated - with Screw Terminals 25 to 55 A culus CE Application AF09... AF38 4-pole contactors are used for controlling power circuits up to 600 V AC and 240 V DC.

More information

AF09... AF30 3-pole Contactors up to 25 HP / 600 VAC

AF09... AF30 3-pole Contactors up to 25 HP / 600 VAC AF09... AF0 -pole Contactors up to 25 HP / 600 VAC Contactors and Overload Relays Overview.../0 AF09... AF0 -pole Contactors.../2 Main Technical Data.../8 Main Accessory Fitting Details.../2 Main Accessory.../24

More information

SWITCH FUSES 3KL71 from 32A to 800A Description

SWITCH FUSES 3KL71 from 32A to 800A Description from 32A to 800A Description SWITCH FUSES 3KL71 3KL71 is a range of load-break switches suitable for making and breaking on load and disconnetting low voltage electrical circuits. They are commonly used

More information

SD Series Non-Fused Load Switches

SD Series Non-Fused Load Switches SD Series Non-Fused Load Switches The SD1 and SD2 series of non-fused load switches are listed as Manual Motor Controllers and are designed for use in local motor isolation. The SD series of modular load

More information

IEC Low Voltage General Purpose Protection

IEC Low Voltage General Purpose Protection , 6A, 0/400VAC (/440VAC) Complying with DIN VDE 0660 Part 07 EN / IEC 60947- DIN VDE 066 Part IEC 6069- DIN VDE 068 DIN VDE 4880 The D0-LINOCUR is a combination of switch-disconnector-fuse and NEOZED 6

More information

Varius SUMMARY OF MODELS

Varius SUMMARY OF MODELS SUMMARY OF MODELS FH000 FH00 FH FH2 FH LTL4a Rated operating current I e 60 A 60 A 250 A 400 A 60 A 600 A Rated operating voltage AC/DC U e 690 V 690 V 690 V 690 V 690 V 690 V Size 000 00 2 4a Fuse-link

More information

Interchangeable Built-in Fixed thermal Adjustable thermal Magnetic Fixed Adjustable Adjustable Electronic RMS 7 LS LSI

Interchangeable Built-in Fixed thermal Adjustable thermal Magnetic Fixed Adjustable Adjustable Electronic RMS 7 LS LSI . Technical Data and Specifications Ratings Frames EG, JG and LG EG JG LG Maximum rated current (amperes) 15, 160 1 50 400, 630 Breaker type 3 B B E S S H H C E S H C U X E S H C U X of poles 1, 3, 4,

More information

MOULDED CASE CIRCUIT BREAKERS BC160N

MOULDED CASE CIRCUIT BREAKERS BC160N D MOULDED CASE CIRCUIT BREAKERS BC160N D BC160N COMMERCIAL INFORMATION Circuit breakers...d4 Switch-disconnectors...D5 Connecting sets......d6 Mounting sets......d6 Switches...D7 Shunt trips...d7 Undervoltage

More information

Motor Starter Protectors

Motor Starter Protectors Motor Starter Protectors Industrial Controls Product Catalog 207 Section contents Section Overview /2 - /3 Motor Starter Protectors 3RV20 MSP, Class 0/20 /4 - /5 Circuit Breakers 3RV27, 3RV28 Circuit Breaker

More information

Fuse Switch Disconnectors XNH. Fuse Switch Disconnectors XNH... For fuse links NH000 to NH3. Rated operating current of 160, 250, 400 and 630A

Fuse Switch Disconnectors XNH. Fuse Switch Disconnectors XNH... For fuse links NH000 to NH3. Rated operating current of 160, 250, 400 and 630A www.eaton.eu Panel Building Accessories PIFT Plug In Fused Terminal Fuse Disconnectors Thermostats Filters and Fans Terminals Electrical Cabinet Heating Catalogue 2016 Fuse Switch Disconnectors XNH Fuse

More information

1489-M Circuit Breakers

1489-M Circuit Breakers Dual terminals provide wiring/bus bar flexibility and clamp from both sides to improve connection reliability Terminal design helps prevent wiring misses Scratch- and solventresistant printing Suitable

More information

Control and Load Switch Specifications Bulletin Number 194E, 194L

Control and Load Switch Specifications Bulletin Number 194E, 194L Technical Data Control and Load Switch Specifications Bulletin Number 194E, 194L Topic Page Product Line Overview 2 194E General Specifications 3 194E Approximate Dimensions 5 194L Circuit Diagrams 13

More information

Product Specification Sheet #3LD2.1

Product Specification Sheet #3LD2.1 Product Specification Sheet #3LD2.1 Enclosed Non-Fusible Rotary Disconnect Switch 16 30 Amp, Type 12K Industrial and Type 4X Non-Metallic Enclosures General Information and Horsepower Ratings Shipping

More information

SIRCO UL98 Load break switches standards UL and CSA 100 to 1200 A

SIRCO UL98 Load break switches standards UL and CSA 100 to 1200 A The solution for Load break switches sirco-ul_022_b_1_cat > Power distribution. Strong points sirco_093_b_1_cat SIRCO 3 x 200 A > Reliability. > Safety of property and personnel. > Simplicity. > Easy assembling.

More information

Contents. Volume 5 Motor Control and Protection CA E December

Contents. Volume 5 Motor Control and Protection CA E December Rotary Disconnects.2 R5 Series Non-Fusible 16 80A Product Description R5 Series (UL 508 listed) products are manually operated modular switches. Load break switching and isolation provide safety solutions

More information

General technical data: CONTACTOR, AC-3, 18.5KW/400V, 1NO+1NC, DC 24V, 3-POLE, SZ S0 SCREW TERMINAL. product brand name

General technical data: CONTACTOR, AC-3, 18.5KW/400V, 1NO+1NC, DC 24V, 3-POLE, SZ S0 SCREW TERMINAL. product brand name Data sheet CONTACTOR, AC-3, 18.5KW/400V, 1NO+1NC, DC 24V, 3-POLE, SZ S0 SCREW TERMINAL product brand name Product designation SIRIUS 3RT2 contactor General technical data: Size of contactor S0 Product

More information

Load and Motor Switches, Load-Break Switches Series 8549

Load and Motor Switches, Load-Break Switches Series 8549 www.stahl.de > Innovative switch concept > State-of-the-art contact arrangement > Easy and clear connection technology > Wiring channel for auxiliary contacts > Retrofittable: Pick-off terminal block Auxiliary

More information

125 to 4000 A. Functions. Conformity to standards. Approvals and certifications (1) General characteristics. Available on request

125 to 4000 A. Functions. Conformity to standards. Approvals and certifications (1) General characteristics. Available on request 125 to 4000 A sirco_353_a_1_cat sirco_296_a_1_cat sirco_300_b switches are manually operated or motorised multipolar load break switches. They break on and off under load and provide safety isolation for

More information

DATASHEET - DILMC9-10(24VDC) Technical data General. Contactor, 3p+1N/O, 4kW/400V/AC3. Catalog No Eaton Catalog No. XTCEC009B10TD.

DATASHEET - DILMC9-10(24VDC) Technical data General. Contactor, 3p+1N/O, 4kW/400V/AC3. Catalog No Eaton Catalog No. XTCEC009B10TD. DATASHEET - DILMC9-10(24VDC) Technical data General Contactor, 3p+1N/O, 4kW/400V/AC3 Part no. DILMC9-10(24VDC) Catalog No. 277468 Eaton Catalog No. XTCEC009B10TD EL-Nummer 4110305 (Norway) Standards IEC/EN

More information

Application Mini Contactors for Motors and Resistive Loads

Application Mini Contactors for Motors and Resistive Loads Delivery program Contactor, 4p, 4kW/400V/AC3 Part no. DILEM4-G(24VDC) Catalog No. 012701 Eaton Catalog No. XTMF9A00TD Product range Contactors Application Mini Contactors for Motors and Resistive Loads

More information

Manual. Industrial Controls. Protection Devices. SIRIUS 3RV Motor Starter Protectors. Edition 12/2017. siemens.com

Manual. Industrial Controls. Protection Devices. SIRIUS 3RV Motor Starter Protectors. Edition 12/2017. siemens.com Manual Industrial Controls Protection Devices Edition 12/2017 siemens.com Introduction 1 Standards 2 Industrial Controls Protection devices SIRIUS 3RV Motor Starter Protectors Manual Product description

More information

Varius SUMMARY OF MODELS

Varius SUMMARY OF MODELS Varius SUMMARY OF MODELS Type FH00 FH1 FH2 FH3 LTL4a Rated operating current I e 160 A 160 A 250 A 400 A 630 A 1 600 A Rated operating voltage AC/DC U e 690 V 690 V 690 V 690 V 690 V 690 V Size 000 00

More information

Fuse switch-disconnectors

Fuse switch-disconnectors Fuse switch-disconnector FH000 is intended for fuse-links with blade contacts size 000. It enables safe disconnection not only of rated current, but also overcurrent up to octuple rated current. A version

More information

DCX-M. changeover switches ->CATALOGUE PAGES INSIDE THE GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES

DCX-M. changeover switches ->CATALOGUE PAGES INSIDE THE GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES DCX-M changeover switches ->CATALOGUE PAGES INSIDE THE GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES FOR COMMERCIAL BUILDINGS AND DCX-M In = 63 A Quality & design CONFORM TO EN/IEC

More information

Load Break Disconnect Switches FSLBS

Load Break Disconnect Switches FSLBS Load Break Disconnect Switches FSLBS UL 508 Non-Fused Load Break Switches The FSLBS Load Break Switch is a newly designed industrial-grade switch capable of making or breaking loads up to 600V. It is suitable

More information

Protective Devices: Circuit-Breakers 1 )

Protective Devices: Circuit-Breakers 1 ) Protective Devices: Circuit-Breakers 1 ) /2 Introduction SIRIUS circuit-breakers 1 ) up to 100 A / General data /20 For motor protection /22 For motor protection with overload relay function /23 For starter

More information

MS25, MST25, MS20, MST20

MS25, MST25, MS20, MST20 Versions: - MS25 with thermal and magnetic releases - MST25 with a thermal release - MS20 - with thermal and magnetic releases for single-phase consumers - MST20 with a thermal for single phase consumers

More information

Rotary Cam Switches. Rotary Cam Switches

Rotary Cam Switches. Rotary Cam Switches Rotary Cam es Series... 2 Handle Assemblies... 8 Accessories... 12 Circuit Diagrams, Technical Information & Dimensions (Online)... 13 Series R-Line Rotary Cam es... 24 Handles and Accessories... 27 Circuit

More information

8WH6 ipo Installation Terminals

8WH6 ipo Installation Terminals /2 Introduction /4 8WH through-type terminals /6 8WH through-type screw terminals /8 8WH N-conductor isolating terminals /10 8WH N-conductor isolating screw terminals /12 8WH installation terminals More

More information

Miniature Circuit-Breakers (MCBs)

Miniature Circuit-Breakers (MCBs) Product Overview Miniature Circuit-Breakers (MCBs) Design Tripping characteristics Rated current I n Rated breaking capacity Power supply company product range 5SP3 E 16 - A Standard product range 5SQ2

More information

Contact gap 7 mm (norm >5.5 mm) ÿ IN ENCLOSURE. ÿ WITH CLUTCH DRIVE

Contact gap 7 mm (norm >5.5 mm) ÿ IN ENCLOSURE. ÿ WITH CLUTCH DRIVE Switch disconnectors A modular and flexible range Contact gap 7 mm (norm 5.5 mm) Reversible terminal feature ÿ IN ENCLOSURE - Degree of protection: up to IP 66 - For 25A to 100A size switches (see Ithe

More information

GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector

GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector Catalog 0500CT9702R409 2009 Class 525/580 CONTENTS Description............................................. Page General Characteristics...................................

More information

3VT Kompaktleistungsschalter bis 630A

3VT Kompaktleistungsschalter bis 630A Katalog LV 36 AT Österreich - Auszug 2012 3VT Kompaktleistungsschalter bis 630A SENTRON Schutz-, Schalt- und Messtechnik www.siemens.com/lowvoltage 3VT1 Molded Case Circuit Breakers up to 160 A 1 Technical

More information

Product Line Overview. The Most Logically Designed Contact Assembly

Product Line Overview. The Most Logically Designed Contact Assembly Circuit Breakers & Supplementary Protectors 15 00 Amperes for UL, CSA & IEC Applications Product Line Overview -3 General Information Cutler-Hammer Series G Molded Case Circuit Breakers provide increased

More information

SU200M Datasheet. Branch protection acc. to CSA C22.2 No.5 / UL 489

SU200M Datasheet. Branch protection acc. to CSA C22.2 No.5 / UL 489 MINIATURE CIRCUIT BREAKERS SU200M Datasheet Branch protection acc. to CSA C22.2 No.5 / UL 489 The miniature circuit breaker SU200 M is ABB s solution for UL 489 branch circuit protection up to 480 Y/277

More information

PKZ and PKE motor-protective circuit-breakers

PKZ and PKE motor-protective circuit-breakers PKZ and PKE motor-protective circuit-breakers Machinery and installation downtimes should be kept as short as possible. The PKZ fuseless motor-protective circuit-breakers combine short-circuit and overload

More information

Protection Equipment. Overload Relays. Reference Manual 04/2011. Industrial Controls. Answers for industry.

Protection Equipment. Overload Relays. Reference Manual 04/2011. Industrial Controls. Answers for industry. Protection Equipment Overload Relays Reference Manual 04/2011 Industrial Controls Answers for industry. Protection Equipment 2 3 7 7 8 9 14 1 16 17 18 18 19 20 2 26 27 28 29 30 32 37 38 40 42 Introduction

More information

AF09... AF30 3-pole Contactors up to 20 HP / 480 VAC

AF09... AF30 3-pole Contactors up to 20 HP / 480 VAC AF0... AF0 -pole Contactors up to 20 HP / 480 VAC Contactors and Overload Relays Overview...2 AF0... AF0 -pole Contactors Ordering Details...4 Main Technical Data...20 DC Circuit switching...2 Main Accessory

More information

General_technical_data Series

General_technical_data Series Slow-make switching element Switching system The double-break, slow-make switching element is equipped with one or two independent contact systems, acting as normally open or normally closed contact. The

More information

MULTIVERT 250A Size 1, 690VAC

MULTIVERT 250A Size 1, 690VAC MULTIVERT 250A IEC FUSE SWITCH DISCONNECTORS NH VERTICAL FUSE SWITCH DISCONNECTOR FEATURES & BENEFITS MULTIVERT NH vertical fuse switch disconnectors meet all functions of NH fuse switch disconnectors.

More information

System pro M compact Supplementary protector S 200 PR for ring-tongue applications acc. to UL1077

System pro M compact Supplementary protector S 200 PR for ring-tongue applications acc. to UL1077 Data Sheet System pro M compact Supplementary protector S 200 PR for ring-tongue applications acc. to UL1077 2CDC021026S0011 2CDC021016S0012 The S 200 PR is a high-performance supplementary protector with

More information

Motor-protectivecircuit-breaker,3p,Ir=2.5-4A. Product range PKZM01 motor protective circuit-breakers up to 16 A with pushbutton actuation

Motor-protectivecircuit-breaker,3p,Ir=2.5-4A. Product range PKZM01 motor protective circuit-breakers up to 16 A with pushbutton actuation Motor-protectivecircuit-breaker,3p,Ir=2.5-4A Partno. PKZM01-4 Articleno. 278482 CatalogNo. XTPB004BC1 Deliveryprogramme Product range PKZM01 motor protective circuit-breakers up to 16 A with pushbutton

More information

Motor Starter Protectors

Motor Starter Protectors Motor Starter Protectors Industrial Controls Product Catalog 09 Section contents Section Overview / - /3 Motor Starter Protectors 3RV0 MSP, Class 0/0 /4 - / Circuit Breakers 3RV7, 3RV8 Circuit Breaker

More information

Approbationen IEC/EN ; UL 508; CSA-C22.2 No ; CE marking

Approbationen IEC/EN ; UL 508; CSA-C22.2 No ; CE marking Contactor,4kW/400V,DCoperated Partno. DILEM-10-G(24VDC) Articleno. 010213 Program Product range Contactors Subrange DILEM contactors Application Mini Contactors for Motors and Resistive Loads Description

More information

Miniature Circuit-Breakers (MCBs)

Miniature Circuit-Breakers (MCBs) Product overview Miniature Circuit-Breakers (MCBs) Design Tripping characteristic Rated currents I n Rated breaking capacity Power supply company product range 5SP3 E 16 - A Standard product range 5SX2

More information

SENTRON Switching and Protection Devices Molded Case Circuit Breakers

SENTRON Switching and Protection Devices Molded Case Circuit Breakers SENTRON Switching and Protection Devices Molded Case Circuit Breakers /2 Introduction 3VL Molded Case Circuit Breakers up to 00 A General data /4 - Design /12 - Function /15 - Integration / - Configuration

More information

15 16 MCCBs for Power Distribution Technical Specification Frame 100A 250A 250A 400A 400A 630A 800 / 1000 / 1250 Type C DN0-100 D DN1-250 N DN2-250 D N S H DN3B-400 DN3-400 D N D N S V DN3-630 DN4-1250

More information

Series L9 UL489 Miniature Circuit Breakers

Series L9 UL489 Miniature Circuit Breakers Series L9 UL489 iniature Circuit Breakers Industrial Circuit Breakers for Branch Circuit Protection up to 63 Amps L9 Series B Circuit Breakers Series B L9 UL489 circuit breakers offer new features, expanded

More information

SIRCO M and MV Universal load break switches from 16 to 160 A

SIRCO M and MV Universal load break switches from 16 to 160 A SRCO M and MV from 16 to 16 A The solution for Load break switches sircm_99_a > Main incoming load break > Distribution load break > Machine control > Local safety load break sircm_13_a 4 pole SRCO MV

More information

BETA Fuses and Fuse Systems

BETA Fuses and Fuse Systems Introduction Overview Application LV HRC fuses are used for installation systems in non-residential, commercial and industrial buildings as well as in the switchboards of power supply companies. Fuses

More information