Switches. Fused Switches ITCP for Semiconductor Fuses 32 to 800A CONTROL: FUSE CONNECTING: SWITCHING: MECHANISM: FIXING: CONSTRUCTION:

Size: px
Start display at page:

Download "Switches. Fused Switches ITCP for Semiconductor Fuses 32 to 800A CONTROL: FUSE CONNECTING: SWITCHING: MECHANISM: FIXING: CONSTRUCTION:"

Transcription

1 Fused CONTROL: Side control, padlockable in off position by three padlocks. Safe and reliable of contact position on handles. SWITCHING: Double isolation per phase. Complete isolation of fuse when circuit open. Onload opening and closing AC23 & DC 23. Interrupting rating 25 ka up to 100 ka. Insulation voltage 1000 V. FIXING: On DIN rail for ratings lower 250A or on board. FUSE CONNECTING: Forced tightening. MECHANISM: Snap action mechanism which ensures rapid disconnection regardjess of how fast the user turns the operation handle.` CONSTRUCTION: Complying with IEC 947 1and 3 and EN and 3 Standards Silverplated copper electrical contacts. Insulating partitions in UL 94 UO materials. Required blownfuse. PROTECTION AGAINST TOUCHING OF LIVE PARTS: IP 20 COMPLETE RANGE READYTO INSTALL SW40 12/04

2 Fused Protistor Fuse Switch disconnectors Easytoinstall and use For 10 x 38 fuses For 14 x 51 fuses For 22 x 58 fuses For 27 x 60 fuses For 00 x 000 fuses Complete protection against touching of live parts For 00P & 00TD80 fuses For endcontact fuses For bladestyle Protistor fuses DIN For American bladestyle Protistor fuses 12/04 SW41

3 Fused The ITCP switchdisconnector range is specially designed to satisfy the connection requirements of Protistor semiconductor fuses along with thermal stresses generated during their use. The combination of ITCP switches and Protistor fuses ensures a high degree of safety in the protection of both personnel and equipment, including power semiconductors and other fragile components. ITCP Main characteristics Safe switching or closing of circuit at any time, even on load Disconnection of circuit in order to safely service installations and downstream components off load Associated fuses enable protection of the even the most demanding semiconductors Complying with IEC 9473 BS 5419 VDE 0660 NFC Standards. Silverplated copper electrical contacts Interrupting rating as per IEC 9473, AC 23 Isolation of fuses downstream and upstream: when switch is open, fuses are off load Protection in all climate types Molded partitions in selfextinguishing fiber glassreinforced polyester Frontcontrolled ambient temperature <40 c Beyond this ambient, a derating factor must be applied to thermal rating: 110 θ where θ is ambient 70 in C User advice While the rating alone enables selection of the switchdisconnector for general purpose fuses, additional parameters must be taken into account for semiconductor fuses: RMS operating current Actual power loss through fuse must be lower than maximum dissipable power per fuse in fused switch. ITCP Selection example Assume that fuse determination, in accordance with our T59 application information document, results in selection of a PSC 660V size 31 with IN = 450A and 70W rated power. Operating conditions will be as follows: open air installation, ambient 30 C verticallyassembled fuses I rms = 340 A Calculated power loss through fuse: I rms = 340 ~ 0.76 IN 450 In Semiconductor Fuses section, curve P/PN = f(i/in) provides a 0.48 coefficient, thus power lost in fuse is: P = 0.48 x 70W = 33.6W Various possibilities: 1st case: fuse with end contacts TT 1 ITC P 400 III 30/32 TTF I rms = 340 A < 400 A P = 33,6 W < 45 W (Possible selection) 2nd case: fuse with LI blades 2 ITC P 400 III 30/32 LI I rms = 340 A < 400 A P = 33.6 W < 45 W (Possible selection) 3 ITC P 630 III 30/33 LI I rms = 340 A < 630 A P = 33.6 W < 60 W (Possible selection) Conclusion: Selection # 2 is recommended by Ferraz Shawmut easytoinstall fuse most costefficient solution Numerous accessories offer complete protection against casual touch of live parts for improved personnel safety. Designed for fusing with three Protistor fuse technologies: ferruletype fuses fuses PSC series 660V and 000V fuses. rating is given for an P P N 0,8 0,7 0,6 0,5 0,4 0,3 0,2 0,1 0 0,5 0,6 0,7 0,8 0,9 1 l l N SW42 12/04

4 Fused Selection Table: ITCP vs fuse type Reference number For PROTISTOR fuses ITCP Open air Ambient 40 C Max. Power loss in fuse Ferrule Solid Blades Brackets Endcontacts PSC 000/ 10 x x x x 60 00P 00D80 30TT 31TT 32TT 33TT 70TT 71TT 72TT 73TT 3 32 A 50 A 125 A 3,5 Ith 3,5 W@ Ithe 7,5 Ith 7,5 Ithe e B J C Y D L A (135)* 250 A (230)* 400 A 45 Ith (360)* 34 Ithe* 630 A (570)* 9 Ithe 32 Ith 23 Ithe 60 Ith 45 Ithe* E B F S G X M C H Y H Y N N N D D D S S S H H H J Z P E J Z P E P E S S S H H H A 65 Ith (720)* 55 Ithe* W W W W W W W W M M M M M M M M In bold letters: Switch plus accessories to be mounted (switch + connection kit + inside control + protection parts touching + protection against terminal touching + preisolating microswitch) + heightening cover. In Italics: Switch Accessories must be ordered Ith : value given at switch thermal Ithe : value given for a shrouded switch ( as when in cubicle) ITCP FOR FERRULE FUSES ITCP FOR BRACKETSTYLE 00 & 000 FUSES ITCP FOR ENDCONTACT FUSES SW44 12/04

5 Fused Reference number For PROTISTOR fuses ITCP Open air Ambient 40 C Max. Power loss in fuse German range PSC DIN 110 DIN 110 DIN 110 DIN American range PSC Long blades Short blades 30LI 31LLI 32LI 33LI 70KI 71KI 72KI 73KI 32 A 3,5 Ith 3,5 W@ Ithe 50 A 7,5 Ith 7,5 Ithe 125 A e 160 A (135)* 9 Ithe 250 A (230)* 32 Ith 23 Ithe K A K A L B L210414B L B L B A (360)* 45 Ith 34 Ithe* Q F Q F Q F R G R G R G R G R G R G A (570)* 800 A (720)* 60 Ith 45 Ithe* 65 Ith 55 Ithe* T L X Q T L X Q T L X Q X Q V K Y P V K Y P V K Y P Y P V K Y P V K Y P V K Y P Y P In bold letters: Switch plus accessories to be mounted (switch + connection kit + inside control + protection parts touching + protection against terminal touching + preisolating microswitch) + heightening cover. In Italics: Switch Accessories must be ordered Ith : value given at switch thermal Ithe : value given for a shrouded switch ( as when in cubicle) 4 5 ITCP FOR DINBLADE FUSES 12/04 SW45

6 Fused Selection Table: ITCP vs fuse type Catalog number For PROTISTOR fuses ITCP Open air Ambient 40 C Max. Power loss in fuse Ferrule Solid Blades Brackets 10 x x x x 60 00P 000/00D80 32 A 3,5 Ith 3,5 W@ Ithe ITCP32C3CP10 ITCP32S3CF 50 A 7,5 Ith 7,5 Ithe ITCP50C3CP14 ITC50S3CF 125 A e ITCP125C3CP22 ITC125S3CF 160 A (135)* 9 Ithe ITCP160K3CP27 ITCP160C3D08 ITC160S3CF 250 A (230)* 32 Ith 23 Ithe 400 A 45 Ith (360)* 34 Ithe* ITCP250C3TD08 ITCP250K3TD08 ITCP400C3TD08 ITCP400K3TD A (570)* 60 Ith 45 Ithe* 800 A 65 Ith (720)* 55 Ithe* In bold letters: Switch plus accessories to be mounted (switch + connection kit + inside control + protection parts touching + protection against terminal touching + preisolating microswitch) + heightening cover. In Italics: Switch Accessories must be ordered Ith : value given at switch thermal Ithe : value given for a shrouded switch ( as when in cubicle) 1 2 ITCP FOR FERRULE FUSES ITCP FOR BRACKETSTYLE 00 & 000 FUSES SW46 12/04

7 Fused Catalog number For PROTISTOR fuses ITCP Open air Ambient 40 C Max. Power loss in fuse Endcontacts PSC 30TT 31TT 32TT 33TT 70TT 71TT 72TT 73TT 3 32 A 3,5 Ith 3,5 W@ Ithe 50 A 7,5 Ith 7,5 Ithe 125 A e 160 A (135)* 9 Ithe 250 A (230)* 32 Ith 23 Ithe ITCP250C3TTF3 ITCP250K3TTF3 ITCP250C3TTF3 ITCP250K3TTF3 ITCP250C3TTF7 ITCP250K3TTF7 ITCP250C3TTF7 ITCP250K3TTF7 400 A (360)* 45 Ith 34 Ithe* ITCP400C3TTF3 ITCP400K3TTF3 ITCP400C3TTF3 ITCP400K3TTF3 ITCP400C3TTF3 ITCP400K3TTF3 ITCP400C3TTF7 ITCP400K3TTF7 ITCP400C3TTF7 ITCP400K3TTF7 ITCP400C3TTF7 ITCP400K3TTF7 630 A (570)* 60 Ith 45 Ithe* ITCP630C3TTF ITCP630K3TTF ITCP630C3TTF ITCP630K3TTF ITCP630C3TTF ITCP630K3TTF ITCP630C3TTF ITCP630K3TTF ITCP630C3TTF ITCP630K3TTF ITCP630C3TTF ITCP630K3TTF 800 A (720)* 65 Ith 55 Ithe* ITCP800C3TTF ITCP800K3TTF ITCP800C3TTF ITCP800K3TTF ITCP800C3TTF ITCP800K3TTF ITCP800C3TTF ITCP800K3TTF ITCP800C3TTF ITCP800K3TTF ITCP800C3TTF ITCP800K3TTF ITCP800C3TTF ITCP800K3TTF ITCP800C3TTF ITCP800 K3TTF In bold letters: Switch plus accessories to be mounted (switch + connection kit + inside control + protection parts touching + protection against terminal touching + preisolating microswitch) + heightening cover. In Italics: Switch Accessories must be ordered Ith : value given at switch thermal Ithe : value given for a shrouded switch ( as when in cubicle) ITCP FOR ENDCONTACT FUSES ITCP FOR DINBLADE FUSES 12/04 SW47

8 Fused Selection Table: ITCP vs fuse type Catalog number For PROTISTOR fuses ITCP Open air Ambient 40 C Max. Power loss in fuse German range PSC DIN DIN DIN DIN A 3,5 Ith 3,5 W@ Ithe 50 A 7,5 Ith 7,5 Ithe 125 A e 160 A (135)* 9 Ithe 250 A (230)* 32 Ith 23 Ithe ITCP250C3D11 ITCP250K3D11 ITCP250C3D11 ITCP250K3D A 45 Ith (360)* 34 Ithe* ITCP400C3D11 ITCP400K3D11 ITCP400C3D11 ITCP400K3D11 ITCP400C3D11 ITCP400K3D A (570)* 60 Ith 45 Ithe* ITCP630C3D08/14 ITCP630K3D11/14 ITCP630C3D08/14 ITCP630K3D11/14 ITCP630C3D08/14 ITCP630K3D11/ A 65 Ith (720)* 55 Ithe* ITCP800C3D08/14 ITCP800K3D08/14 ITCP800C3D08/14 ITCP800K3D08/14 ITCP800C3D08/14 ITCP800K3D08/14 ITCP800C3D08/14 ITCP800K3D08/14 In bold letters: Switch plus accessories to be mounted (switch + connection kit + inside control + protection parts touching + protection against terminal touching + preisolating microswitch) + heightening cover. In Italics: Switch Accessories must be ordered Ith : value given at switch thermal Ithe : value given for a shrouded switch ( as when in cubicle) ITCP FOR ENDCONTACT FUSES ITCP FOR DINBLADE FUSES SW48 12/04

9 Fused Catalog number For PROTISTOR fuses ITCP Open air Ambient 40 C Max. Power loss in fuse Long blades American range PSC 5 Short blades 30LI 31LLI 32LI 33LI 70KI 71KI 72KI 73KI 32 A 3,5 Ith 3,5 W@ Ithe 50 A 7,5 Ith 7,5 Ithe 125 A e 160 A (135)* 9 Ithe 250 A (230)* 32 Ith 23 Ithe ITCP250C3US ITCP250K3US ITCP250C3US ITCP250K3US ITCP250C3US ITCP250K3US ITCP250C3US ITCP250K3US 400 A (360)* 45 Ith 34 Ithe* ITCP400C3US ITCP400K3US ITCP400C3US ITCP400K3US ITCP400C3US ITCP400K3US ITCP400C3US ITCP400K3US ITCP400C3US ITCP400K3US ITCP400C3US ITCP400K3US 630 A (570)* 60 Ith 45 Ithe* ITCP630C3US ITCP630K3US ITCP630C3US ITCP630K3US ITCP630C3US ITCP630K3US ITCP630C3US ITCP630K3US ITCP630C3US ITCP630K3US ITCP630C3US ITCP630K3US 800 A (720)* 65 Ith 55 Ithe* ITCP800C3US ITCP800K3US ITCP800C3US ITCP800K3US ITCP800C3US ITCP800K3US ITCP800C3US ITCP800K3US ITCP800C3US ITCP800K3US ITCP800C3US ITCP800K3US ITCP800C3US ITCP800K3US ITCP800C3US ITCP800K3US In bold letters: Switch plus accessories to be mounted (switch + connection kit + inside control + protection parts touching + protection against terminal touching + preisolating microswitch) + heightening cover. In Italics: Switch Accessories must be ordered Ith : value given at switch thermal Ithe : value given for a shrouded switch ( as when in cubicle) ITCP FOR ENDCONTACT FUSES ITCP FOR DINBLADE FUSES 12/04 SW49

10 Fused Reference number lth ( A) Fuse Type Readytoinstall complete switch** Complete switch Reference Number Designation Switch supplied with black & red handle, 2 auxiliary preisolating contacts NO & NC, blown fuse for ferrule fuses, protection parts touching, protection against terminal touching and heightening cover. Separate switch with kit for connecting fuses Separate Switch Reference Number Connection kit Reference Number Switch plus mounted connection kit Ref. Number 32 10x38 B ITCP 32 III 10x38 COMPLETE J x51 C ITCP 50 III 14x51 COMPLETE Y x58 D ITCP 125 III 22x58 COMPLETE L x60 E ITCP 160 III 27x60 COMPLETE B P F ITCP 160 III 00 COMPLETE S /00DIN80 G ITCP 250 III 00/000 TD08 COMPLETE M X to 31 TTF H ITCP 250 III 3031 TTF COMPLETE K Y to 71 TTF J ITCP 250 III 7071 TTF COMPLETE C L Z to 31 LI 70 to 71 KI L ITCP 250 III 3031 LI/7071 KI COMPLETE N B /00DIN80 M ITCP 400 III 00/000 TD08 COMPLETE M C to 32 TTF N ITCP 400 III 3032 TTF COMPLETE K D to 72 TTF P ITCP 400 III 7072 TTF COMPLETE D L E to 32 DIN to 72 DIN to 32 LI 70 to 72 KI 30 to 33 TTF 70 to 72 TTF 30 to 33 DIN to 73 DIN to 33 LI 70 to 73 KI 30 to 33 TTF 70 to 73 TTF 30 to 33 DIN to 73 DIN to 33 LI 70 to 73 KI Q # ITCP 400 III 3032/7072 D11 # COMPLETE H F # R ITCP 400 III 3032 LI/7072 KI COMPLETE N G S ITCP 630 III 3033/7073 TTF COMPLETE Q H T # ITCP 630 III 3033/7073 D08 à 14 COMPLETE E P L # V ITCP 630 III 3033 LI/7073 KI COMPLETE S K W ITCP 800 III 3033/7073 TTF COMPLETE Q M X # ITCP 800 III 3033/7073 D08 à 14 # COMPLETE F P Q # Y ITCP 800 III 3033 LI/7073 KI COMPLETE S P ** Connection parts are not mounted on TTF fuses due to a distance between connection axes depending on height of fuse body variation which is +/ 1mm # Infactory adjustments for DIN 110 blade fuses SW50 12/04

11 Fused Reference number Accessories lth ( A) 32 10x x x x P Fuse Type Inside handle Black & Red (Internal control) N E Outside handle ➀ Black & Red 2 Red & Yellow (Internal control)u ➊ V ❷ C ➊ M ❷ N mm shaft Shaft extension for outside handle if needed H mm shaft B mm shaft Preisolating auxiliary contact (MC) ➀23➃➄➅ 3 P ou G ➀ L H ➀ L contacts maximum 2 H Blown fuse auxiliary contact (DPMM) ➀23➃ 3 Q Z (1 NO & 1 NC) A (1 NO & 1 NC) For 2 NO or 2 NC order L H No Protection parts touching (CPT)* Builtin Builtin Builtin Terminal cover (CB) * 1 CB per terminal Builtin Builtin N /00 DIN80 30 to 31 TTF to 71 TTF 30 to 31 LI 70 to 71 KI 000/00 DIN80 30 to 32 TTF to 72 TTF to 32 DIN to 72 DIN to 32 LI 70 to 72 KI 30 to 33 TTF 70 to 72 TTF 30 to 33 DIN to 73 DIN to 33 LI 70 to 73 KI 30 to 33 TTF 70 to 73 TTF 30 to 33 DIN to 73 DIN to 33 LI 70 to 73 KI Q To be ordered ➊ Q with a protection ❷ R screen 250 mm shaft part touching Q To be ordered with a protection screen part touching Q To be ordered with a protection screen part touching Q To be ordered with a protection screen part touching ➊ Q ❷ R mm shaft ➊ Q ❷ R mm shaft ➊ Q ❷ R mm shaft L mm shaft L mm shaft L mm shaft L mm shaft ➃ S ➄ L ➅ J ➃ S ➄ L ➅ J ➃ S ➄ L ➅ J ➃ S ➄ L ➅ J Function of fuse type See Semiconductor Fuse section Function of fuse type See Semiconductor Fuse section Function of fuse type See Semiconductor Fuse section Function of fuse type See Semiconductor Fuse section without blown fuse G With blown fuse G Y without blown fuse J With blown fuse J Y Without blown fuse L With blown fuse L Y Without blown fuse Z With blown fuse Z Y * M * M * S * S * With outside control, a locking mechanism of cover can be used. When switch is ON, this mechanism locks the cover (e.g. test of fuse live part touching protection, servicing of circuit when cubicle open) TYPES OF AUXILIARY CONTACTS ➀ Single microswitch 1 NO 2 Single microswitch 1 NC 3 Reversing microswitch 1 NO/NC ➃ Microswitch 1 NO & 1 NC ➄ Twin microswitch 2 NO & 2 NC ➅ Microswitch 1 NO & 1 NC low level 12/04 SW51

12 Fused Catalog number Readytoinstall complete switch** Separate switch with kit for connecting fuses lth ( A) Fuse Type Complete switch catalog Number Designation Switch supplied with black & red handle, 2 auxiliary preisolating contacts NO & NC, blown fuse for ferrule fuses, protection parts touching, protection against terminal touching and heightening cover. Separate Switch Catalog Number Connection kit Catalog Number Switch plus mounted connection kit Cat. Number 32 10x38 ITCP32C3CP10 ITCP 32 III 10x38 COMPLETE ITC32S3CF 50 14x51 ITCP50C3CP14 ITCP 50 III 14x51 COMPLETE ITC50S3CF x58 ITCP125C3CP22 ITCP 125 III 22x58 COMPLETE ITC125S3CF x60 ITCP 160 III 27x60 COMPLETE ITCP160K3CP P ITCP160C3D08 ITCP 160 III 00 COMPLETE ITC160S3CF 000/00DIN80 ITCP250C3TD08 ITCP 250 III 00/000 TD08 COMPLETE KITCP250/400TD8 ITCP250K3TD08 30 to 31 TTF ITCP250C3TTF3 ITCP 250 III 3031 TTF COMPLETE to 71 TTF ITCP250C3TTF7 ITCP 250 III 7071 TTF COMPLETE ITCP250S3 KITCP250/400TF3 KITCP250/400TF7 ITCP250K3TTF3 ITCP250K3TTF7 30 to 31 LI 70 to 71 KI ITCP250C3US ITCP 250 III 3031 LI/7071 KI COMPLETE KITCP250/400US ITCP250K3US 000/00DIN80 ITCP400C3TD08 ITCP 400 III 00/000 TD08 COMPLETE KITCP250/400TD8 ITCP400K3TD08 30 to 32 TTF ITCP400C3TTF3 ITCP 400 III 3032 TTF COMPLETE KITCP250/400TF3 ITCP400K3TTF to 72 TTF ITCP400C3TTF7 ITCP 400 III 7072 TTF COMPLETE ITCP400S3 KITCP250/400TF7 ITCP400K3TTF7 30 to 32 DIN to 72 DIN 110 ITCP400C3D11 ITCP 400 III 3032/7072 D11 # COMPLETE KITCP250/400D11 ITCP400K3D to 32 LI 70 to 72 KI 30 to 33 TTF 70 to 72 TTF 30 to 33 DIN to 73 DIN to 33 LI 70 to 73 KI 30 to 33 TTF 70 to 73 TTF ITCP400C3US ITCP630C3TTF ITCP630C3D08/14 ITCP630C3US ITCP800C3TTF ITCP 400 III 3032 LI/7072 KI ITCP 630 III 3033/7073 TTF ITCP 630 III 3033/7073 D08 à 14 ITCP 630 III 3033 LI/7073 KI ITCP 800 III 3033/7073 TTF COMPLETE COMPLETE COMPLETE COMPLETE COMPLETE ITCP630S3 KITCP250/400US KITCP630/800TTF KITCP630/800D KITCP630/800US KITCP630/800TTF ITCP400K3US ITCP630K3TTF ITCP630K3D11/14 ITCP630K3US ITCP800K3TTF to 33 DIN to 73 DIN 110 ITCP800C3D08/14 ITCP 800 III 3033/7073 D08 à 14 # COMPLETE ITCP800S3 KITCP630/800D ITCP800K3D08/14 30 to 33 LI 70 to 73 KI ITCP800C3US ITCP 800 III 3033 LI/7073 KI COMPLETE KITCP630/800US ITCP800K3US ** Connection parts are not mounted on TTF fuses due to a distance between connection axes depending on height of fuse body variation which is +/ 1mm # Infactory adjustments for DIN 110 blade fuses SW52 12/04

13 Fused Catalog number Accessories lth ( A) 32 10x x x x P Fuse Type Inside handle Black & Red (Internal control) Outside handle ➀ Black & Red 2 Red & Yellow (Internal control)u ➊ ❷ ➊ ❷ 150 mm shaft Shaft extension for outside handle if needed 265 mm shaft 290 mm shaft Preisolating auxiliary contact (MC) ➀23➃➄➅ 3 ou ➀ 2 ➀ 8 contacts maximum 2 Blown fuse auxiliary contact (DPMM) ➀23➃ 3 (1 NO & 1 NC) (1 NO & 1 NC) For 2 NO or 2 NC order L No Protection parts touching (CPT)* Builtin Builtin Builtin Terminal cover (CB) * 1 CB per terminal Builtin Builtin 000/00 DIN80 30 to 31 TTF to 71 TTF 30 to 31 LI 70 to 71 KI To be ordered with a protection screen part touching ➊ ❷ 250 mm shaft 395 mm shaft ➃ ➄ ➅ Function of fuse type See Semiconductor Fuse section without blown fuse With blown fuse 000/00 DIN80 30 to 32 TTF to 72 TTF 30 to 32 DIN to 72 DIN to 32 LI 70 to 72 KI To be ordered with a protection screen part touching ➊ ❷ 250 mm shaft 395 mm shaft ➃ ➄ ➅ Function of fuse type See Semiconductor Fuse section without blown fuse With blown fuse to 33 TTF 70 to 72 TTF 30 to 33 DIN to 73 DIN to 33 LI 70 to 73 KI 30 to 33 TTF 70 to 73 TTF 30 to 33 DIN to 73 DIN to 33 LI 70 to 73 KI To be ordered with a protection screen part touching To be ordered with a protection screen part touching ➊ ❷ 250 mm shaft ➊ ❷ 250 mm shaft 395 mm shaft 395 mm shaft ➃ ➄ ➅ ➃ ➄ ➅ Function of fuse type See Semiconductor Fuse section Function of fuse type See Semiconductor Fuse section Without blown fuse With blown fuse Without blown fuse With blown fuse * With outside control, a locking mechanism of cover can be used. When switch is ON, this mechanism locks the cover (e.g. test of fuse live part touching protection, servicing of circuit when cubicle open) TYPES OF AUXILIARY CONTACTS ➀ Single microswitch 1 NO 2 Single microswitch 1 NC 3 Reversing microswitch 1 NO/NC ➃ Microswitch 1 NO & 1 NC ➄ Twin microswitch 2 NO & 2 NC ➅ Microswitch 1 NO & 1 NC low level 12/04 SW53

14 Fused ITCP Fused Switchdisconnectors Electrical characteristics ITCP 32 ITCP 50 ITCP 125 ITCP 160 rating (1) open air Ith: in cubicle Ithe: Ith (A) Ithe Rated voltage Rated insulation voltage Rated impulse withstand voltage AC20 DC20 (V) Ui (V) (kv) Ferrule 10x38 14x51 22x58 27x P PROTISTOR fuse type Endcontacts PSC American PSC DIN PSC Maximum power losses per fuse # (w) Ith Ithe Ith Ithe Ith Ithe Ith Ithe RMS shortcircuit rated current with fuses (ka) Interrupting rating (AC23) Ic (A) Operating rated voltage: AC23 Operating rated current Ie (1) Power class Operating rated power P (kw) with a 1500 rpm asynchronous 3phase motor (Ue: operating rated voltage) Ue Ie en (A) Ue P en (W) Ue 400 V DC23 Operating rated current / poles in series** Ie (A) (Ue: operating rated voltage) Mechanical endurance: number of operating cycles V Ue 440V V 32/2 32/4 125/3 100/4* 160/3 100/4* Electrical endurance: number of operating cycles at Ith and cosj 0, (I=100A) 1000 Power losses per pole (without fusible) (W) Permissible shortduration current 1s ** Poles in series: to be completed by user (ka) pole in series 3pole in series 4pole in series 5 (1) For ambient 50 C = x0.9, 60 C : x0.8. Pour fusible horizontal: x0.9. * Use in class B ** To be completed by user # Value given at thermal rating, for a switch in open air (Ith) and for a shrouded switch (Ithe) e.g. as in cubicle. SW54 12/04

15 Fused ITCP Fused Switchdisconnectors Electrical characteristics rating (1) open air Ith: in cubicle Ithe: Rated voltage Rated insulation voltage Rated impulse withstand voltage PROTISTOR fuse type Maximum power losses per fuse # (w) Ith (A) Ithe AC20 DC20 (V) Ui (V) (kv) Ferrule Endcontacts PSC American PSC DIN PSC ITCP 250 ITC /00/D80 000/00/D TT 7071 TT 3031TT 7071TT 30LI 31LLI 30LI 31LLI 32LI 70KI 71KI 70KI 71KI 72KI 3031 & & 7071 DIN DIN110 Ith Ith Ithe Ithe RMS shortcircuit rated current with fuses (ka) Interrupting rating (AC23) Ic (A) Operating rated voltage: AC23 Operating rated current Ie (1) Power class Operating rated power P (kw) with a 1500 rpm asynchronous 3phase motor (Ue: operating rated voltage) Ue Ie en (A) Ue P en (W) Ue 400 V DC23 Operating rated current / poles in series** Ie (A) (Ue: operating rated voltage) Mechanical endurance: number of operating cycles Electrical endurance: number of operating cycles at Ith and cosj 0,65 Power losses per pole (without fusible) Permissible shortduration current 1s V Ue 440V V (W) (ka) 250 /2 400 /2 250 /2 400 /2 200 /3 400 / ** Poles in series: to be completed by user 2pole in series 3pole in series 4pole in series (1) For ambient 50 C = x0.9, 60 C : x0.8. Pour fusible horizontal: x0.9. * Use in class B ** To be completed by user # Value given at thermal rating, for a switch in open air (Ith) and for a shrouded switch (Ithe) e.g. as in cubicle. 12/04 SW55

16 Fused ITCP Fused Switchdisconnectors Electrical characteristics rating (1) open air Ith: in cubicle Ithe: Ith (A) Ithe ITCP 630 ITCP Rated voltage Rated insulation voltage Rated impulse withstand voltage PROTISTOR fuse type Maximum power losses per fuse # (w) AC20 DC20 (V) Ui (V) (kv) Ferrule Endcontacts PSC American PSC DIN PSC TT 72TT 32TT 33TT 72TT 73TT 30LI 31LLI 32 LI 30LI 31LLI 32LI 33LI 70KI 71KI 72KI 70KI 71KI 72KI 73KI & & DIN DIN110 Ith Ithe Ithe RMS shortcircuit rated current with fuses (ka) Interrupting rating (AC23) Ic (A) Operating rated voltage: AC23 Operating rated current Ie (1) Power class Operating rated power P (kw) with a 1500 rpm asynchronous 3phase motor (Ue: operating rated voltage) Ue Ie en (A) Ue P en (W) Ue 400 V DC23 Operating rated current / poles in series** Ie (A) (Ue: operating rated voltage) Mechanical endurance: number of operating cycles Electrical endurance: number of operating cycles at Ith and cosj 0,65 Power losses per pole (without fusible) Permissible shortduration current 1s V Ue 440V V (W) (ka) 630 /2 800 /2 630 /2 800 /2 630 /3 800 / (cosj = 0.6) ** Poles in series: to be completed by user 2pole in series 3pole in series 4pole in series (1) For ambient 50 C = x0.9, 60 C : x0.8. Pour fusible horizontal: x0.9. * Use in class B ** To be completed by user # Value given at thermal rating, for a switch in open air (Ith) and for a shrouded switch (Ithe) e.g. as in cubicle. SW56 12/04

17 Fused Dimensions and weight ITC Protistor ITCP 32 III 10 x 38 Weight: 0.7 kg Terminal tightening torque: Mini.: 1.6 N.m Maxi. 2.4 N.m Section of copper cables: 0.5 to 10 mm Weight: 1.6 kg. Terminal tightening torque: Mini.: 4 N.m Maxi. 6 N.m Section of copper cables: 2.5 to 25 mm ITCP 50 III 14 x 51 1 ITCP 125 III 22 x 58 ITCP 160 III 27 x 60 ITCP 160 III 00 2 Weight: 1.8 kg. Terminal tightening torque: Mini.: 5 N.m Maxi.: 7 N.m Connection: torque 20 mm with M8 bolt 12/04 SW57

18 Fused TCP 250 III D80 ITCP 250 III 30 LI 31 LLI ITCP 250 III 3031 TTF ITCP 250 III 7071 TTF ITCP 250 III 3031 DIN 110 / 7071 DIN 110 Weight: 7 kg. 3 4 Terminal tightening torque: Mini.: 30 N.m Maxi. : 44 N.m Connecting: torque 25 mm per terminal with M10 bolt TCP 400 III D80 ITCP 400 III 3032 LI 31LLI 7072 KI ITCP 400 III 3031 TTF ITCP 400 III 7071 TTF ITCP 400 III 3032 DIN 110 / 7072 DIN 110 Weight: 8 kg. Terminal tightening torque: Mini.: 30 N.m Maxi. : 44 N.m Connecting: torque 25 mm per terminal with M10 bolt Weight: 15 kg. Terminal tightening torque: Mini.: 50 N.m Maxi.: 75 N.m Connecting: torque 40 mm per terminal with M12 bolt A B C D E F G* H *With booster ITCP 250 D III G + 41 ITCP 400 D III G + 41 * With protection cover against live part touching, and if blown fuse auxiliary contacts are used, lenghthening of G is necessary. ITCP 630 III 3033 / 7073 TTF ITCP 630 III 3033 / 7073 DIN 80 to 140 ITCP 630 III 3033 LI 31LLI 7073 KI 5 6 Weight: 19 kg. ITCP 800 III 3033 / 7073 TTF ITCP 800 III 3033 / 7073 DIN 80 to 140 ITCP 800 III 3033 LI 31LLI 7073 KI Terminal tightening torque: Mini: 50 N.m Maxi. : 75 N.m Connecting: torque 40 mm per terminal with M12 bolt Drilling diagram for outside control 7 A B C D G* With booser ITCP 630 D III ITCP 800 D III * With protection cover against live part touching, and if blown fuse auxiliary contacts are used, lenghthening of G is necessary. SW58 12/04

onlinecomponents.com

onlinecomponents.com 66 grb 66 V AC grb - from up to 3 A Size: x38 The fuse preselection table below indicates: Fuse preselection Rated current Pre-arcing I²t Total I²t at 66VAC I N (A) I²t p (A²s) I²t (A²s) - rated current

More information

Semiconductor Fuses European Fuses

Semiconductor Fuses European Fuses 66 grb 66 V AC grb - from up to 3 A Size: x38 The fuse preselection table below indicates: Fuse preselection - rated current (or ) I N - pre-arcing I²t (I²t p ) at ms - total ope I²t (I²tt) at 66 V, cos

More information

Semiconductor (AC) fuses

Semiconductor (AC) fuses Main characteristics 450 TO 700VAC / 63 TO 2800A Recognized Exceptionally low I 2 T, Watt losses. Non-magnetic construction, Highly reliable low voltage Trip-indicator system, conformity to UL, IEC, DIN

More information

Semiconductor Fuses Microswitches & Studs

Semiconductor Fuses Microswitches & Studs MICROSWITCH SYSTEMS ADAPTED TO THE FOLLOWING FUSES: - PSC sizes 0,,, / 70, 7, 7, 7 - Blade-type PSC (PA) sizes 0-, - / 70, 7, 7, 7 - PSC sizes 000 / 00 New MS L -5 B6 MS PA -5 HIGHLY RESISTANT STUDS OFFERING

More information

Fusegear for Semiconductor Fuse

Fusegear for Semiconductor Fuse Fusegear for Semiconductor Fuse IP 20.SI Bases for PSC ranges: SI TT, SI 000/00, SI DIN SI TT for stud-type fuses SI 00 for bracket-type fuses STANDARD VERSION SI FUSEHOLDERS FOR STUD-TYPE FUSES, FOR BLADE-TYPE

More information

Vistop TM isolating switches 63 to 160A

Vistop TM isolating switches 63 to 160A DX 3 - IS main switches 16 to 125A Vistop TM isolating switches 63 to 160A 225 15 225 18 4 064 00 4 064 59 Pack Cat. No. Main switches AC 22 A category as per EN607-3 Grey handle Accept 1 signalling auxiliary

More information

NH Solid Blades 690 VAC sizes 000 to 3

NH Solid Blades 690 VAC sizes 000 to 3 NH Solid Blades 6 VAC sizes 000 to gs-class Protistor NH 6 VAC fuse-links provide maximum flexibility in equipment design and ultimate protection for today s power conversion equipment. This range is a

More information

RX 3 MCB 4500 A Phase + Neutral, neutral on left side

RX 3 MCB 4500 A Phase + Neutral, neutral on left side 87045 LIMOGES Cedex Téléphone : 05 55 06 87 87 Télécopie : 05 55 06 88 88 RX 3 MCB 4500 A CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation - Connection...

More information

Phase + Neutral, neutral on left side

Phase + Neutral, neutral on left side 87045 LIMOGES Cedex Téléphone : 05 55 06 87 87 Télécopie : 05 55 06 88 88 DX 3 MCB 10000 A / 16 ka CONTENTS PAGE 1. Description, use...1 2. Range...1 3. Overall dimensions...1 4. Preparation - Connection...1

More information

AF40... AF96 3-pole contactors Technical data

AF40... AF96 3-pole contactors Technical data Main pole - Utilization characteristics according to IEC Standards IEC 60947- / 60947-4- and EN 60947- / 60947-4- Rated operational voltage Ue max. 690 V Rated frequency (without derating) 50 / 60 Hz Conventional

More information

3 - Protection components Motor circuit-breakers

3 - Protection components Motor circuit-breakers Contents 0 - Protection components Motor circuit-breakers protection components for the motor protection Thermal-magnetic motor circuit-breakers Selection guide..............................................page

More information

Semiconductor (AC) fuses

Semiconductor (AC) fuses x38 grb - 69VAC 69V AC grb - from up to 3 A Size: x38 The fuse preselection table below indicates: - rated current (or rating) I N - pre-arcing I 2 t (I 2 t p ) at ms - total operating I 2 t (I 2 tt) at

More information

DNX 3 MCB 4500 A / 6 ka Phase + Neutral, neutral on left side

DNX 3 MCB 4500 A / 6 ka Phase + Neutral, neutral on left side 87045 LIMOGES Cedex Téléphone : 05 55 06 87 87 Télécopie : 05 55 06 88 88 DNX 3 MCB 4500 A / 6 ka CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation - Connection...

More information

GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector

GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector Catalog 0500CT9702R409 2009 Class 525/580 CONTENTS Description............................................. Page General Characteristics...................................

More information

, , PREPARATION - CONNECTION. Mounting:. On symmetrical EN rail or DIN 35 rail

, , PREPARATION - CONNECTION. Mounting:. On symmetrical EN rail or DIN 35 rail 87045 LIMOGES Cedex Telephone number: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 DX 3 4500 A / 6 ka CONTENTS PAGES 1. Description, use...1 2. Range...1 3. Overall dimensions...1 4. Preparation - Connection...1

More information

Varius SUMMARY OF MODELS

Varius SUMMARY OF MODELS SUMMARY OF MODELS FH000 FH00 FH FH2 FH LTL4a Rated operating current I e 60 A 60 A 250 A 400 A 60 A 600 A Rated operating voltage AC/DC U e 690 V 690 V 690 V 690 V 690 V 690 V Size 000 00 2 4a Fuse-link

More information

TeSys contactors. Use in category DC-1 (resistive loads; time constant L/R y 1 ms) Rated operational current Ie. to be wired in series

TeSys contactors. Use in category DC-1 (resistive loads; time constant L/R y 1 ms) Rated operational current Ie. to be wired in series Selection 3-pole shockproof contactors FG d.c. supply Selection guide for utilisation categories DC-1 to DC-5 Use in category DC-1 (resistive loads; time constant L/R y 1 ms) Rated operational current

More information

Varius SUMMARY OF MODELS

Varius SUMMARY OF MODELS Varius SUMMARY OF MODELS Type FH00 FH1 FH2 FH3 LTL4a Rated operating current I e 160 A 160 A 250 A 400 A 630 A 1 600 A Rated operating voltage AC/DC U e 690 V 690 V 690 V 690 V 690 V 690 V Size 000 00

More information

87045 LIMOGES Cedex. 2. PRODUCT RANGE (continued) 1. DESCRIPTION - USE. Breaking capacity : Symbol : Technology : 3. OVERALL DIMENSIONS

87045 LIMOGES Cedex. 2. PRODUCT RANGE (continued) 1. DESCRIPTION - USE. Breaking capacity : Symbol : Technology : 3. OVERALL DIMENSIONS 87045 LIMOGES Cedex Phone : + 33 5 55 06 87 87 Fax : + 33 5 55 06 88 88 R.C.B.O. DX 6000 A Phase + Neutral,, neutral on right side Cat. n (s) : 077 31 077 44-077 77 077 84 078 79 079 01-083 95 084 06 084

More information

Phase + Neutral, neutral on right side

Phase + Neutral, neutral on right side 87045 LIMOGES Cedex Telephone number: +33 5 55 06 87 87 Fax: +33 5 55 06 88 88 DX 3 MCB 6000 A / 10 ka Cat.. N (s): 4 074 67 / 68 / 69 / 70 / 71 / 72 / 73 / 74 / 75 / 76 / 77 / 78 / 79 ; 4 077 33 / 34

More information

SIRCO UL98 Non-fusible switches standards UL and CSA 100 to 1200 A

SIRCO UL98 Non-fusible switches standards UL and CSA 100 to 1200 A Non-fusible disconnect switches SIRCO UL98 Non-fusible switches standards UL and CSA sirco-ul_022_b_1_cat The solution for > Power distribution sirco_093_b_1_cat SIRCO 3 x 200 A Strong points > Reliability

More information

Non-fusable disconnect switches standards UL and CSA from 16 to 100 A

Non-fusable disconnect switches standards UL and CSA from 16 to 100 A Non-fusible disconnect switches sircm_132_a sircm_133_a The solution for > Industrial control systems Rotary switch SIRCO M 3 x 80 A Toggle switch SIRCO M 3 x 80 A + 2 auxiliary contacts Competitive advantages

More information

15 16 MCCBs for Power Distribution Technical Specification Frame 100A 250A 250A 400A 400A 630A 800 / 1000 / 1250 Type C DN0-100 D DN1-250 N DN2-250 D N S H DN3B-400 DN3-400 D N D N S V DN3-630 DN4-1250

More information

3NP1 Fuse Switch Disconnectors up to 630 A

3NP1 Fuse Switch Disconnectors up to 630 A Switch Disconnectors 3NP1 Fuse Switch Disconnectors up to 630 A Introduction Overview All key product features at a glance available for all sizes Connection of circular conductors and laminated conductors

More information

Protistor size 70 gr 690VAC (IEC)

Protistor size 70 gr 690VAC (IEC) Protistor size 70 gr SEMICONDUCTOR PROTECTION FUSES SQUARE BODY HIGH-SPEED FUSE-LINKS AC PROTECTION FEATURES & BENEFITS Excellent cycling capability Multiple body sizes and terminals or blades combination

More information

MANUALLY OPERATED CHANGEOVER SWITCHES

MANUALLY OPERATED CHANGEOVER SWITCHES are manually operated multipolar changeover switches. They changeover between two low voltage power circuits under load and provide safety disconnection. Application: NORMA/EMERGENCY Application: UPS,

More information

L O W V O L T A G E DISCONNECT SWITCHES G LO B A L L I N E OF PREMIUM C O M PA C T LOW VOLTAGE SWITCHGEAR

L O W V O L T A G E DISCONNECT SWITCHES G LO B A L L I N E OF PREMIUM C O M PA C T LOW VOLTAGE SWITCHGEAR L O W V O L T A G E DISCONNECT SWITCHES G LO B A L L I N E OF PREMIUM C O M PA C T LOW VOLTAGE SWITCHGEAR The safest way to switch power on and off in your industrial control panels. Your problem: You

More information

AF40... AF96 3-pole contactors 30 to 60 hp at 480 V AC AC / DC operated with 1 N.O. + 1 N.C. auxiliary contacts

AF40... AF96 3-pole contactors 30 to 60 hp at 480 V AC AC / DC operated with 1 N.O. + 1 N.C. auxiliary contacts AF4... AF96 -pole contactors to 6 hp at 48 V AC AC / DC operated with N.O. N.C. auxiliary contacts Description AF4... AF96 contactors are mainly used for controlling -phase motors and power circuits up

More information

DNX 3 MCB 4500 A / 6 ka Phase + Neutral, neutral on left side

DNX 3 MCB 4500 A / 6 ka Phase + Neutral, neutral on left side 87045 LIMOGES Cedex Telephone number: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 DNX 3 MCB 4500 A / 6 ka CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation

More information

SENTRON Switching and Protection Devices Switch Disconnectors

SENTRON Switching and Protection Devices Switch Disconnectors SENTRON Switching and Protection Devices Switch Disconnectors /2 Introduction 3K, 3KE, 3LD Switch Disconnectors 3K, 3KE Switch Disconnectors up to 1000 /4 General data /8 Floor mounting 3LD Main and EMERGENCY-STOP

More information

FUSOMAT Visible breaking and tripping fuse switches from 250 to 1250 A

FUSOMAT Visible breaking and tripping fuse switches from 250 to 1250 A Fuse protection The solution for > Motor load break > Protection of industrial cabinet > Electrical distribution fusom_063_b_1_cat Strong points > Tripping upon overload > High breaking capacity > Improved

More information

FUSERBLOC Fuse combination switches with rear connection for industrial fuses up to 400 A

FUSERBLOC Fuse combination switches with rear connection for industrial fuses up to 400 A Fuse protection fuser_737_a_1_cat.eps fuser_738_a_1_cat.eps The solution for > Motor load break > Protection of industrial processes FUSERBLOC REAR / FRONT connections 3 x 250 A fuser_739_a_1_cat.eps Strong

More information

GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Standard Features

GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Standard Features Standard Features Table : Standard Features GV2ME GV2P GV3P GV7RE/GV7RS 0. to 32 A Up to 20 hp @ 460 V 0 SCCR @ 480 V Push Button Operator 0. to 30 A Up to 5 hp @ 460 V 50 SCCR @ 480 V Rotary Handle Operator

More information

Protection components

Protection components Presentation, characteristics Presentation 1 2 3 motor circuit-breakers are 3-pole thermal-magnetic circuit-breakers standards IEC 60947-2 and IEC 60947-4-1. Connection These circuit-breakers are designed

More information

Protistor size 31 ar 690VAC (IEC) / 700VAC (UL)

Protistor size 31 ar 690VAC (IEC) / 700VAC (UL) Protistor size 31 ar SEMICONDUCTOR PROTECTION FUSES SQUARE BODY HIGH-SPEED FUSE-LINKS AC PROTECTION FEATURES & BENEFITS Multiple body sizes and terminals or blades combination ar Class according to IEC

More information

Fuse switch-disconnectors

Fuse switch-disconnectors Fuse switch-disconnector FH000 is intended for fuse-links with blade contacts size 000. It enables safe disconnection not only of rated current, but also overcurrent up to octuple rated current. A version

More information

Switch Disconnectors. SENTRON 3NP5 Fuse Switch Disconnectors up to 630 A. Introduction. 7/106 Siemens LV

Switch Disconnectors. SENTRON 3NP5 Fuse Switch Disconnectors up to 630 A. Introduction. 7/106 Siemens LV Switch Disconnectors Introduction Siemens AG 2010 Overview 3NP5 0 3NP5 2 3NP5 fuse disconnector range 3NP5 4 SENTRON 3NP5 fuse disconnectors are controls for the occasional manual ing/isolating of loads

More information

DX³ RCBO 6000A Phase + Neutral, neutral on left

DX³ RCBO 6000A Phase + Neutral, neutral on left 87045 LIMOGES Cedex Telephone number: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 DX³ RCBO 6000A CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation Connection...

More information

Gears & Fuse Gears. Medium Voltage Fuses Clips. Clip lock design for CL-14 series. Mounting Details for Clip Lock Cat. No.

Gears & Fuse Gears. Medium Voltage Fuses Clips. Clip lock design for CL-14 series. Mounting Details for Clip Lock Cat. No. Clip lock design for CL-14 series Cat. No. 228-700-520 Cat. No. 228-700-530 (Pair at bottom) (Single at top) The Clip Lock design provides a reliable, high-pressure contact. Ferraz Shawmut CL-14 fuses

More information

Load break switches. Load break switches for all your applications... Why choose a load break switch designed for photovoltaic applications?...

Load break switches. Load break switches for all your applications... Why choose a load break switch designed for photovoltaic applications?... Load break switches Load break switches for all your applications.................................... Why choose a load break switch designed for photovoltaic applications?............. Load break switch

More information

TeSys contactors 5. Characteristics 5. Mini-contactors TeSys LC1 SK and LP1 SK. Environment Rated insulation voltage (Ui) 5/30

TeSys contactors 5. Characteristics 5. Mini-contactors TeSys LC1 SK and LP1 SK. Environment Rated insulation voltage (Ui) 5/30 Characteristics TeSys contactors Mini-contactors TeSys LC SK and LP SK Environment Rated insulation voltage (Ui) Conforming to 0, VDE 00 gr C,BS, CSA - n, UL 0 V 0 Conforming to standards IEC 0, NF C -0,

More information

cor Long Run Experience

cor Long Run Experience Moulded Case Circuit Breakers Moulded Case Circuit Breakers 16-1250A cor Long Run Experience cor Breaking capacity (according to IEC 947-2 at 415V) Icu 100 D160L D250L D400L D630L 70 60 DH800 50 35 30

More information

Switches disconnectors with fuse-holders. XNF series TF series

Switches disconnectors with fuse-holders. XNF series TF series Switches disconnectors with fuse-holders XNF series TF series Quick Reference Switch-disconnectors with fuse-holders XNF series TF series XNF Series page 155 16 32A with fuse holders 3 4 Pole Auxiliary

More information

DX³ RCBO 4500/6 ka Phase + Neutral, neutral on left

DX³ RCBO 4500/6 ka Phase + Neutral, neutral on left 87045 LIMOGES Cedex Telephone number: +33 5 55 06 87 87 Fax: +33 5 55 06 88 88 DX³ RCBO 4500/6 ka CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation Connection...

More information

Changeover & Bypass Sw it ches

Changeover & Bypass Sw it ches Changeover & Bypass Switches St ate of the art Manufacturing Facilit ies Haridw ar, Noida Ph-I & Noida Ph-II Plant Changeover & Bypass Sw it ches Introduction On Load Changeover Switches (with & without

More information

Emergency stop without emergency switching off/emergency stop function. Locking facility Lockable in the 0 (Off) position N/O 0 B 0

Emergency stop without emergency switching off/emergency stop function. Locking facility Lockable in the 0 (Off) position N/O 0 B 0 MainswitchSurfacemounting Partno. T0-2-1/I1/SVB-SW Articleno. 207148 IP65 Deliveryprogramme Product range Switch-disconnectors Basic function Main switches Maintenance switches Manual override switches

More information

Modular contactors and relays

Modular contactors and relays pages /4 to / pages /8 and /9 pages /10 and /11 pages /12 and /13 Presentation and standards Presentation Designed for use in modular panels and enclosures, these contactors feature : i Easy installation

More information

LV switch-disconnectors. Interpact Merlin Gerin 40 to 2500 A. Catalogue. We do more with electricity

LV switch-disconnectors. Interpact Merlin Gerin 40 to 2500 A. Catalogue. We do more with electricity LV switch-disconnectors Catalogue Merlin Gerin 40 to 2500 A We do more with electricity LV switch-disconnectors The various low-voltage applications 2 from 40 to 2500 A 4 Compact from 80 to 1250 A 5 Masterpact

More information

PowerLine OS Switch Fuses A, 690V

PowerLine OS Switch Fuses A, 690V Technical Brochure PowerLine OS Switch Fuses 20...160 A, 690V Brochure OS 10 GB 99-04 9902CD04 ABB Control New Switch Fuse Range 2 3 Total user safety Total user safety Fuse carriers fully IP20 protected

More information

FUSERBLOC Fuse combination switches for industrial fuses up to 1250 A

FUSERBLOC Fuse combination switches for industrial fuses up to 1250 A Fuse protection fuser_548_a cat The solution for > Motor load break. > Protection of industrial cabinet. FUSERBLOC 6 to 25 A Strong points fuser_52_a cat Function FUSERBLOC 2 to 4 A FUSERBLOC are manually

More information

DX³ 4-pole RCBO 6000 A/10 ka

DX³ 4-pole RCBO 6000 A/10 ka 87045 LIMOGES Cedex Telephone number: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 DX³ 4-pole RCBO CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation - Connection...

More information

Modulostar. Motor Branch 400V AC - 690V AC up to 11 kw

Modulostar. Motor Branch 400V AC - 690V AC up to 11 kw Modulostar Motor Branch 400V AC - 690V AC up to 11 kw Innovations in MODULOSTAR to control energy in motor starters Already active in the field of motor starters with rated current over 32A per phase,

More information

Siemens AG Switch Disconnectors SENTRON. Configuration. Edition 10/2015. Manual. siemens.com/lowvoltage

Siemens AG Switch Disconnectors SENTRON. Configuration. Edition 10/2015. Manual. siemens.com/lowvoltage SENTRON Configuration Manual Edition 10/2015 siemens.com/lowvoltage 2 Introduction LD main control and EMERGENCY-STOP switches up to 250 A 4 Introduction 7 Front mounting 10 Floor mounting 11 Distribution

More information

SIRCO M UL 508 Non-fusible disconnect switches standards UL and CSA from 16 to 100 A

SIRCO M UL 508 Non-fusible disconnect switches standards UL and CSA from 16 to 100 A Non-fusible disconnect switches SRCO M UL 58 sircm_132_a sircm_133_a The solution for > ndustrial control systems Rotary switch SRCO M 3 x 8 A Toggle switch SRCO M 3 x 8 A + 2 auxiliary contacts Strong

More information

DRX 125 Circuit breaker (not adjustable)

DRX 125 Circuit breaker (not adjustable) 87045 LIMOGES Cedex Téléphone : 05 55 06 87 87 Télécopie : 05 55 06 88 88 272 20/21/22/23/24/25/26/27/55/56/57/58/59/60 INDEX PAGES 1. USE 1 2. RANGE 1 3. DIMENSIONS 1 3. DIMENSIONS (continuation) 2 4.

More information

Cat. N (s) : /65/66/83/84, /94/95/96/99, /01/02/06/07/11/12/13/14. Pollution degree : C / + 40 C. .

Cat. N (s) : /65/66/83/84, /94/95/96/99, /01/02/06/07/11/12/13/14. Pollution degree : C / + 40 C. . 87045 LIMOGES Cedex Telephone : (+33) 05 55 06 87 87 Fax : (+ 33) 05 55 06 88 88 R.C.C.B. s 0090 00/01/02/06/07/11/12/13/14 0/01/02/06/07/11/12/13/14/18/19/23/24/25/26/ /18/19/23/24/25/26/45/46 45/46 0090

More information

Industrial Contactors CTX 3 3P 185A - 800A

Industrial Contactors CTX 3 3P 185A - 800A 87045 LIMOGES Cedex Telephone: +33 5 55 06 87 87 FAX: +33 5 55 06 88 88 Industrial Contactors CONTENTS PAGES 1. Description - Use... 1 2. Range... 1 3. Overall dimensions... 1 4. Installation - Connection...

More information

Btdin-RS RCBO 2p Phase + Neutral, neutral on right

Btdin-RS RCBO 2p Phase + Neutral, neutral on right Viale Borri 231, 21100 Varese - Italy RCBO 2p CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation Connection... 1 5. General characteristics... 2 6. Compliance

More information

SFS-UFS Single Foot Switches

SFS-UFS Single Foot Switches SFS-UFS Single Foot Switches Technopolymer housing, shock proof Protection degree IP53 or IP65 13 contact blocks available Various auxiliary devices available UFS Series SFS Series Options & Ordering Codes

More information

Page. Circuit-Breakers M4 2 for motor protection. Auxiliary contacts 3 Signalling switch Auxiliary releases

Page. Circuit-Breakers M4 2 for motor protection. Auxiliary contacts 3 Signalling switch Auxiliary releases Circuit Breakers M4 Page Circuit-Breakers M4 2 for motor protection Auxiliary contacts 3 Signalling switch Auxiliary releases Insulated 3-pole busbar system 4 Terminal block DIN-rail adapters 5 Busbar

More information

Protistor size 120 gr 750VDC (IEC)

Protistor size 120 gr 750VDC (IEC) Protistor size 12 gr SEMICONDUCTOR PROTECTION FUSES SQUARE BODY HIGH-SPEED FUSE-LINKS DC PROTECTION FEATURES & BENEFITS Multiple body sizes and terminals or blades combination Very low I²t Extremely fast

More information

gi-gl-gg, am gi-gl-gg gi-gl-gg NH DIMENSION KNIFE-BLADE FUSE-LINKS EURO/IEC Fuses & Accessories

gi-gl-gg, am gi-gl-gg gi-gl-gg NH DIMENSION KNIFE-BLADE FUSE-LINKS EURO/IEC Fuses & Accessories ,, FUSE BASES, AND ACCESSORIES Ferraz Shawmut NH Fuse-links, sizes 00, 0, 1, 2, 3 and 4 are rated 500 or 690 Volts AC with breaking capacities of 80kA or 120kA. All fuse-links include an indicator or striker

More information

LEXIC Curv LIMOGES Cedex. Cats N (s) : /68/87/88, /48, /84/85, /76/77/95/96/97, /71/72 1.

LEXIC Curv LIMOGES Cedex. Cats N (s) : /68/87/88, /48, /84/85, /76/77/95/96/97, /71/72 1. 87045 LIMOGES Cedex Téléphone : 05 55 06 87 87 Télécopie : 05 55 06 88 88 LEXIC MCB s DX-H 80A, 100A, 125A Curv urves B and C CONTENTS PAGES 1. Description, use...1 2. Range...1 3. Overall dimensions...1

More information

SIRCO UL98 Load break switches standards UL and CSA 100 to 1200 A

SIRCO UL98 Load break switches standards UL and CSA 100 to 1200 A The solution for Load break switches sirco-ul_022_b_1_cat > Power distribution. Strong points sirco_093_b_1_cat SIRCO 3 x 200 A > Reliability. > Safety of property and personnel. > Simplicity. > Easy assembling.

More information

Introduction. Standard Features. GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Introduction

Introduction. Standard Features. GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Introduction Introduction Introduction Schneider Electric offers a complete line of products for the manual control and protection of motors. This catalog covers those devices designed to meet IEC standards for protection

More information

Emergency stop As an emergency switching off/emergency stop device. Standards According to IEC/EN , VDE 0113 Part 1

Emergency stop As an emergency switching off/emergency stop device. Standards According to IEC/EN , VDE 0113 Part 1 MainswitchSurfacemounting Partno. T0-2-8900/I1/SVB Articleno. 207151 CatalogNo. CT02-8900-I1CRQ Deliveryprogramme Product range Switch-disconnectors Basic function Main switches Maintenance switches Manual

More information

R.C.B.O. SP / 1 module

R.C.B.O. SP / 1 module 87045 LIMOGES Cedex - France Telephone : (+33) 5 55 06 87 87 Fax : (+33) 5 55 06 88 88 R.C.B.O. SP / 1 module 6064 04 6064 64 05 6064 10 6064 11 6064 12 CONTENTS PAGES 1. Description, use... 1 2. Range...

More information

Contact gap 7 mm (norm >5.5 mm) ÿ IN ENCLOSURE. ÿ WITH CLUTCH DRIVE

Contact gap 7 mm (norm >5.5 mm) ÿ IN ENCLOSURE. ÿ WITH CLUTCH DRIVE Switch disconnectors A modular and flexible range Contact gap 7 mm (norm 5.5 mm) Reversible terminal feature ÿ IN ENCLOSURE - Degree of protection: up to IP 66 - For 25A to 100A size switches (see Ithe

More information

SWITCH FUSES 3KL71 from 32A to 800A Description

SWITCH FUSES 3KL71 from 32A to 800A Description from 32A to 800A Description SWITCH FUSES 3KL71 3KL71 is a range of load-break switches suitable for making and breaking on load and disconnetting low voltage electrical circuits. They are commonly used

More information

TX³ RCCBs 2P up to 100 A

TX³ RCCBs 2P up to 100 A 87045 LIMOGES Cedex Telephone number: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 TX³ RCCBs CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation - Connection...

More information

DPX Thermal magnetic and trip-free switches DPX 3 -I 160

DPX Thermal magnetic and trip-free switches DPX 3 -I 160 87045 LIMOGES Cedex Phone :+33 05 55 06 87 87 Fax :+33 05 55 06 88 88 DPX 3 160 CONTENTS PAGES 1. USE 1 2. RANGE 1 3. DIMENSIONS 1 4. OVERVIEW 2 5. ELECTRICAL AND MECHANICAL CHARACTERISTICS 3 6. CONFORMITY

More information

DPX Thermal magnetic and trip-free switches DPX 3 -I 630

DPX Thermal magnetic and trip-free switches DPX 3 -I 630 87045 LIMOGES Cedex Phone :+33 05 55 06 87 87 Fax :+33 05 55 06 88 88 DPX 3 630 CONTENTS PAGES 1. USE 1 2. RANGE 1 3. DIMENSIONS 1 4. OVERVIEW 2 5. ELECTRICAL AND MECHANICAL CHARACTERISTICS 2 6. CONFORMITY

More information

MSW. MSW Catalog Number Sequence. Standard Features MSW 25 B- 3

MSW. MSW Catalog Number Sequence. Standard Features MSW 25 B- 3 Introducing the New WEG Series. The was developed according to IEC 60947-3 & UL508. The compact, reliable design of the allows the operator to safely disconnect power and isolate the circuit within the

More information

Approvals UL 508; CSA-C22.2 No ; IEC/EN ; CE marking

Approvals UL 508; CSA-C22.2 No ; IEC/EN ; CE marking MainswitchRearmounting Partno. T0-2-1/V/SVB-SW Articleno. 045992 Front IP65 Deliveryprogramme Product range Switch-disconnectors Basic function Main switches Maintenance switches Manual override switches

More information

DX³ RCBO 6000 A Phase + Neutral, neutral right side

DX³ RCBO 6000 A Phase + Neutral, neutral right side 87045 LIMOGES Cedex Téléphone : 05 55 06 87 87 Télécopie : 05 55 06 88 88 DX³ RCBO 6000 A CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation Connection... 1

More information

AF09... AF30 3-pole Contactors up to 25 HP / 600 VAC

AF09... AF30 3-pole Contactors up to 25 HP / 600 VAC AF09... AF0 -pole Contactors up to 25 HP / 600 VAC Contactors and Overload Relays Overview.../0 AF09... AF0 -pole Contactors.../2 Main Technical Data.../8 Main Accessory Fitting Details.../2 Main Accessory.../24

More information

DX³ RCCBs - ID 4P up to 100 A

DX³ RCCBs - ID 4P up to 100 A 87045 LIMOGES Cedex Telephone number: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 DX³ s - ID CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation - Connection...

More information

UL/CSA Non-fused Disconnect Switches

UL/CSA Non-fused Disconnect Switches Product Selection UL/CSA Non-fused Disconnect Switches Cat. No. 194R-N30-1753 Cat. No. 194R-J100-1753 Note: Your order must include 1) Cat. No. of disconnect switch, 2) shaft, 3) handle, and 4) any accessories.

More information

DX 3 MCBs. Choice of DX 3 MCBs for capacitor banks. Technical data

DX 3 MCBs. Choice of DX 3 MCBs for capacitor banks. Technical data Specifications IS/IEC 60898-1 2002 Number of poles SP, SPN, DP, TP, TPN, FP Characteristics C & D Curve Breaking capacity 10 ka 0.5 A to 63 A as per IS/IEC 60898-1 2002 16 ka for 0.5 A to 25 A as per IEC

More information

DX³ RCBO 6000A Phase + Neutral, neutral on right

DX³ RCBO 6000A Phase + Neutral, neutral on right 87045 LIMOGES Cedex Telephone number: +33 5 55 06 87 87 Fax: +33 5 55 06 88 88 DX³ RCBO 6000A CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation Connection...

More information

HelioProtection HP15NH Photovoltaic fuse-links gpv 1500VDC

HelioProtection HP15NH Photovoltaic fuse-links gpv 1500VDC SPECIAL PURPOSE FUSES PHOTOVOLTAIC FUSES FEATURES & BENEFITS Mersen HP15NH photovoltaic (PV) fuse serie was engineered and designed specifically for the protection of photovoltaic systems. Helio-Protection

More information

Fuses for Semiconductor Protection - European Standard. Class: Voltage ratings: Current ratings: Standards: Approvals: Features and Benefits

Fuses for Semiconductor Protection - European Standard. Class: Voltage ratings: Current ratings: Standards: Approvals: Features and Benefits Fuses for Semiconductor Protection - European Standard Class: ar Voltage ratings: 660V AC to 1000V AC Current ratings: 16 A to 400 A Standards: UL 248-13 IEC 60269-1 & 4 DIN VDE 0636-40 DIN 43653 Approvals:

More information

BETA Switching Switches and Light Indicators

BETA Switching Switches and Light Indicators Siemens AG 2008 BETA Switching /2 Product overview /3 5TE8 control switches / 5TE4 pushbuttons /2 5TE5 light indicators /5 5TE8 ON/OFF switches /22 5TE9 busbars /24 5TE switch disconnectors Siemens ET

More information

25A 25A 32A 40A 40A 63A 63A 80A

25A 25A 32A 40A 40A 63A 63A 80A ISDC Compact Range 25A - 200A Control Panel Isolation Equipment Craig & Derricott has ranges of Switch-Disconnectors, Fuse Combination Units and Changeover Isolators for panel mounting ranging from 25A

More information

B115...B180 RF200 RFN200 B250...B400 RF400 RFN400

B115...B180 RF200 RFN200 B250...B400 RF400 RFN400 Page -2 Page -4 Page -6 FOR BG SERIES MINI-CONTACTORS Type RF9, phase failure sensitive, manual resetting Type RFA9, phase failure sensitive, automatic resetting Type RFN9, non-phase failure sensitive,

More information

C60H-DC. C curve IEC Direct current (DC) Breaking capacity (Icu) according to IEC Type 1P 110 V 220 V 250 V 440 V 500 V

C60H-DC. C curve IEC Direct current (DC) Breaking capacity (Icu) according to IEC Type 1P 110 V 220 V 250 V 440 V 500 V DC circuit supplementary protectors for feeders / distribution systems C60H-DC C curve DB123430 DB123525 DB405571 IEC 60947-2 PB107193-34.eps PB107194-34.eps The C60H-DC supplementary protectors are used

More information

Btdin RCBO 6000A up to 63A (2P)

Btdin RCBO 6000A up to 63A (2P) Index Pages 1. Descripton... 2 2. Product range... 2 3. Overall dimensions... 2 4. Fixing Connection... 3 5. Generl characteristics.... 4-29 6. Compliance - Approvals... 30 7. Curves... 30-34 8.Auxiliaries-

More information

Fuse switch-disconnectors

Fuse switch-disconnectors Fuse switch-disconnector FH00 is intended fuse-links with blade contacts size 000 and 00. It enables safe disconnection not only of rated current, but also overcurrent up to octuple rated current. A version

More information

TeSys GS & DF Fuse protection

TeSys GS & DF Fuse protection TeSys GS & DF Fuse protection Simple and effective protection TeSys GS Fuse disconnect switches Total isolation between poles Safe replacement of the fuses (double breaking system) Frontal and right side

More information

PSC SQUARE BODY 690/700 Volt SEMICONDUCTOR PROTECTION FUSES

PSC SQUARE BODY 690/700 Volt SEMICONDUCTOR PROTECTION FUSES PSC SQUARE BOY Ferraz Shawmut 690/700V PSC fuse-links provide maximum flexibility in equipment design and ultimate protection for today s power conversion equipment. These square body fuse-links are available

More information

schneider-electric.com/sg K60 Circuit Breakers The affordable way to stay safe from electrocution and electrical overloads schneider-electric.

schneider-electric.com/sg K60 Circuit Breakers The affordable way to stay safe from electrocution and electrical overloads schneider-electric. K0 Circuit Breakers The affordable way to stay safe from electrocution and electrical overloads Overview K0 Circuit Breaker Technical Specification MCB RCCB K0 Circuit Breaker K0N K0H ID K Number of poles

More information

NH fuse-links gg 690VAC top indicator/live gripping-lugs size 4 and 4a

NH fuse-links gg 690VAC top indicator/live gripping-lugs size 4 and 4a NH fuse-links gg 69VAC NH fuse-links gg 69VAC LOW VOLTAGE IEC FUSES IEC NH FUSE-LINKS FEATURES & BENEFITS Dimensions in accordance with DIN 43 62 Live tags Top indicator Lead free contact blades % cadmium

More information

THE SANTON FCS-TYPE SWITCH DISCONNECT. Superior Switch Solutions

THE SANTON FCS-TYPE SWITCH DISCONNECT. Superior Switch Solutions THE SANTON FCS-TYPE SWITCH DISCONNECT Superior Switch Solutions The technical information given in this table applies to and pole fuse combination switches. A B NOMINAL RATING 0A A FUSE COMBINATION SWITCHES

More information

Contactors. Mini-contactors type LC1-SKGC for use in modular panels. Conforming to standards IEC/EN , IEC/EN , NF C , VDE 0660

Contactors. Mini-contactors type LC1-SKGC for use in modular panels. Conforming to standards IEC/EN , IEC/EN , NF C , VDE 0660 Characteristics Environment Rated insulation voltage (Ui) Conforming to IEC/EN 60947-1, V 690 IEC/EN 60947-4-1, VDE 0110 gr C, CSA - n 14, UL 508.1 Conforming to standards IEC/EN 60947-1, IEC/EN 60947-4-1,

More information

DRX 100 B/N/H Circuit breaker (not adjustable)

DRX 100 B/N/H Circuit breaker (not adjustable) 87045 LIMOGES Cedex Téléphone : 05 55 06 87 87 Télécopie : 05 55 06 88 88 INDEX PAGES 1. USE 1 2. RANGE 1 3. DIMENSIONS 1 3. DIMENSIONS (continuation) 2 4. MOUNTING 2 5. CABLING 3 6. ELECTRIC AND MECHANICAL

More information

Safety Switches Series 8537

Safety Switches Series 8537 Safety Switches www.stahl.de > 3- and 6-pole switches 12 / 16, 25, 40, 63 / 80, 125 / 160, 250, 315, 400, 500 A > Motor switching capacity AC-3 and AC-23 acc. to IEC 60947-3, EN 60947, DIN VDE 0660 part

More information

General information about motor protection

General information about motor protection Application guide General information about motor protection Typical construction of a motor starter Disconnect Switch UL 98 - UL489 CSA C22.2 # 4 CSA C22.2 # 5 Fuses SIRCO Non-Fusible Disconnect Switch

More information

(1,5 modules per pole)

(1,5 modules per pole) 87045 LIMOGES Cedex Telephone: +33 5 55 06 87 87 FAX: +33 5 55 06 88 88 DX 3 MCB 36kA, 80A CONTENTS PAGES 1. Description - Use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation - Connection...

More information

G eneral Purpose Fuses

G eneral Purpose Fuses G eneral Purpose Fuses North American Power Fuses AMP-TRAP2000 AMP-TRAP2000 AJT Class J - Time Delay 1 to 600A - - Motor, motor controller, control transformer, and circuit back-up protection. Space saving

More information

Switch disconnectors

Switch disconnectors Selection Load break switch disconnectors type LK3, 40-120 A Selection guide for 3 and 4-pole switch disconnectors General The LK3 range of switch disconnectors (lth: 40 A to 120 A) is designed for use

More information