Technical Data Sheet. Hilti Firestop Collar CFS-C P. European Technical Approval ETA N o 10/0404. Issue 08 / Hilti Firestop Collar CFS-C P
|
|
- Allison Dixon
- 5 years ago
- Views:
Transcription
1 Technical Data Sheet Hilti Firestop Collar CFS-C P Hilti Firestop Collar CFS-C P European Technical Approval ETA N o 10/0404 Issue 08 / 2015 Hilti Firestop Collar CFS-C P Issue 02/2015 page 1
2 General information Pipe end configurations Page 03 Pipe end configurations according to intended use Page 04 Insulation configurations Page 05 Hilti Firestop Collar CFS-C P Page 06 Installation instructions Page 07 Fire classification detail tables for walls Walls Construction and minimum distances Page 08 Flexible and rigid walls minimum wall thickness 100 mm Page 08 Pre-insulated pipes Page 10 Plastic pipes Page 11 Plastic pipes with foamed elastomeric insulation Page 14 Composite pipes with foamed elastomeric insulation Page 16 Rigid walls minimum wall thickness 150 mm Page 17 Plastic pipes Page 18 Fire classification detail tables for floors Floors Construction and minimum distances Page 19 Rigid floors minimum density of 2400 kg/m 3 Page 19 Pre-insulated pipes Page 21 Plastic pipes Page 22 Plastic pipes with foamed elastomeric insulation Page 26 Composite pipes Page 27 Composite pipes with foamed elastomeric insulation Page 28 Rigid floors minimum density of 550 kg/m 3 Page 29 Pre-insulated pipes Page 29 Plastic pipes Page 29 Plastic pipes with foamed elastomeric insulation Page 32 Composite pipes Page 33 Composite pipes with foamed elastomeric insulation Page 33 Hilti Firestop Acrylic Sealant CFS-S ACR Product data sheet Page 35 Installation instructions Page 36 Specification Additional attributes Page 37 page 2 Hilti Firestop Collar CFS-C P Issue 02/2015
3 Pipe end configurations All pipes tested according to EN have been tested with a specific pipe end configuration. In the fire classification, the first letter of the end configuration refers to the end conditions within the furnace (fire-side), the second letter to the end conditions outside the furnace (non-fire-side). EI 90 U / U Configuration outside furnace Configuration inside furnace Fire resistance classification in minutes, Test condition Pipe end configuration Inside furnace Outside furnace U / U Uncapped Uncapped C / U Capped Uncapped U / C Uncapped Capped C / C Capped Capped As the EN test standard EN states, it is important to ensure that sealing systems have been tested with appropriate pipe end conditions. The conditions the pipe and sealing system must endure in a fire situation depend on whether one or both ends of the pipe are sealed in practice, as pressures and the flow of hot gases will vary depending on whether the pipe is ventilated or not. There are rules that determine which tested end configurations are valid for additional pipe end situations. For metal pipes: Tested U / C C / U C / C Covered U / C Y N N C / U Y Y N C / C Y Y Y Y = acceptable, N = not acceptable For plastic pipes: Tested U / U C / U U / C C / C U / U Y N N N Covered C / U Y Y N N U / C Y Y Y N C / C Y Y Y Y Y = acceptable, N = not acceptable So, for example, a plastic pipe tested with the end configuration U / U will cover all possible end conditions. But a plastic pipe tested U / C will only cover the conditions U / C or C / C. Hilti Firestop Collar CFS-C P Issue 02/2015 page 3
4 Pipe end configurations according to intended use As previously stated, it is important to ensure that the tested pipe configuration corresponds to the intended use of the pipe. The table below outlines recommended end configurations for various intended pipe uses as per suggestions laid out in EN H In the event that a national regulation conflicts with this table, the national regulation takes precedence. Intended use of penetrations (list not exhaustive, other pipes uses possible) Application Penetration material Manufacturer, product (examples) Insulation Heating Al-Composite Geberit Mepla U / C CS Recommended pipe end classification KeKelit KELOX KM 110 CS Rehau Rautitan stabil PE-X Rehau Rautitan flex CS -R Aquatherm blue Aquatherm blue Faserverbundrohr Potable water Al-Composite Geberit Mepla U / C CS KeKelit KELOX KM 110 CS Rehau Rautitan stabil CS PE EN PE-HD 100 RC Wavin TS CS/LS PE-X Rehau Rautitan flex CS EN ISO 15874, DIN 8077/ 8078 (e.g. AquathermGreen, Aquatherm GreenFaserverbundrohr) CS/LS PCV-C Friatherm starr CS/LS Refrigeration ABS +GF+ COOL-FIT CS U/C Ventilated PE EN 1519, EN U / U Waste water Roof CI/CS Drainage PE-HD 1000 RC Wavin TS CS/LS PE-S2 Geberit Silent db20 EN Magnaplast Skolan db Pipelife Master 3 Poloplast Polo Kal NG Poloplast Polo Kal 3S Rehau Raupiano Plus Wavin AS/KeKelit Phonex AS Wavin SiTech PVC-C EN PVC-U EN ISO 1452, EN , EN Pneumatic Al-composite Geberit Mepla C/C DIN 8077/8078 Sprinkler -R Aquatherm red U/C Industry Al-Composite Various Varies depending upon application, PE EN ISO 15494, DIN 8074/8075 i.e. consider whether pipe is pressurized (U/C), DIN 8077/8078 ventilated (U/U) or unventilated PVC-U EN ISO 15493, DIN 8061/8062 (U/C) CS page 4 Hilti Firestop Collar CFS-C P Issue 02/2015
5 Insulation configurations When sealing pipes, the insulation configuration must be considered. The following configurations are possible: Insulation over the entire length of the pipe (i.e. thermal insulation) Continued sustained Continued interrupted Insulation only required in the area of the penetration seal Local insulation, sustained Local insulation, sustained See page 35 for specification of suitable insulation products. Hilti Firestop Collar CFS-C P Issue 02/2015 page 5
6 Hilti Firestop collar CFS-C P Firestopping for flammable pipes up to 250 mm in diameter with European Technical Approval. Applications n Sealing flammable pipes from 50 mm to 250 mm in diameter in penetrations through fire compartment walls and floors n Pipe materials: PVC, PVC-U, PE, PE-HD, PE-X,, ABS, Al-composite n Suitable for use in openings in concrete, aerated concrete, masonry, drywall, shaft wall and coated board. n Different backfilling and sealing materials are covered Advantages n Quick and easy closure without use of a tool n Adjustable position tabs for simple fastening n Sound decoupling strip based on PE (foam) can be used n Low profile for tight installations Technical data Minimal wall thickness Minimal ceiling thickness Storage and transportation temperature - range Close aperture with CFS-C P 100mm 150mm -5 C - 50 C Gypsum plaster, cementitious mortar, Hilti Firestop Acrylic Sealant CFS-S ACR Expansion temperature 210 C The European Technical Approval (ETA) and the technical data sheet can be obtained via your local Hilti contact. Nominal pipe diameter Number of hooks and fasteners Order designation Sales Quantity Item Number 50 mm 2 Firestop collar CFS-C P 50/1.5 1 pc mm 2 Firestop collar CFS-C P 63/2 1 pc mm 3 Firestop collar CFS-C P 75/2.5 1 pc mm 3 Firestop collar CFS-C P 90/3 1 pc mm 4 Firestop collar CFS-C P 110/4 1 pc mm 4 Firestop collar CFS-C P 125/5 1 pc mm 6 Firestop collar CFS-C P 160/6 1 pc mm 8 Firestop collar CFS-C P 180/7 1 pc mm 8 Firestop collar CFS-C P 200/8 1 pc mm 10 Firestop collar CFS-C P 225/9 1 pc mm 12 Firestop collar CFS-C P 250/10 1 pc page 6 Hilti Firestop Collar CFS-C P Issue 02/2015
7 Installation instructions Seal the opening: The aperture around the pipe is filled with gypsum plaster (flexible walls) or cementitious mortar (concrete walls/floors) over the full thickness of the wall/floor or alternatively sealed with minimum 25 mm thick Hilti Firestop Acrylic Sealant CFS-S ACR on both sides. Backfilling with stone wool may be omitted in case of small annular gaps and classifications EI 120. In case of missing sound decoupling means around the pipe it is recommended to use Hilti Firestop Acrylic Sealant CFS-S ACR as annular gap seal. If gypsum plaster or cementitious mortar is intended to be used it is recommended to install a PE foam strip around the pipe over the entire wall or floor thickness for sound de coupling of the pipe. Clean the plastic pipe. Remove all plaster/mortar or dust from the pipe in the area where the Firestop collar is to be installed. Close the Hilti Firestop Collar: Place the Hilti Firestop Collar around the plastic pipe and apply firm pressure by hand until it latches with a "click" sound. No tools, pins or screws are necessary. The Hilti Firestop Collar can be re-opened by pushing down the engaged "tongue" with a screwdriver while pulling the Hilti Firestop Collar apart. Attach fastening hooks/tabs: The fastening hooks can be attached to various points of the metal housing. The hooks must be positioned as symmetrically as possible. The required number of fastening hooks is indicated below and on the packaging. Fasten the Hilti Firestop Collar: a) Attach fastening hooks/tabs on the metal housing. b) Mark the fastening points on the wall/floor. c) Fasten the Hilti Firestop Collar, using recommended metal anchors/fasteners, e.g. Hilti HUS for rigid walls and floors or threaded rod, nuts, washers in flexible walls. These are defined in the respective test reports and approvals. d) If required by national prescriptions mark the penetration seal with an identification plate containing the required information. In such a case fasten the identification plate in a visible position next to the seal. For wall applications: Repeat installation on the other side of the wall. Collar sizes and number of hooks for suitable pipe diameters FS Collar P 50/1,5" 2 FS Collar P 63/2" 2 FS Collar P 160/6" 6 FS Collar P 250/10" 12 FS Collar P 75/2,5" 3 FS Collar P 90/3" 3 FS Collar P 180/7" 8 FS Collar P 200/8" 8 FS Collar P 110/4" 4 FS Collar P 125/5" 4 FS Collar P 225/9" 10 Hilti Firestop Collar CFS-C P Issue 02/2015 page 7
8 1. Flexible and rigid walls, minimum wall thickness 100 mm The intended use of the Hilti Firestop Collar CFS-C is to reinstate the fire resistance of: Flexible walls / drywalls (E) with a minimum thickness of 100 mm (t E ), with timber or steel studs lined on both faces with a minimum of two layers of 12.5 mm thick boards. For timber stud walls there must be a minimum distance of 100 mm between the seal and any stud, and the cavity must be filled with a minimum of 100 mm insulation of Class A1 or A2 in accordance with EN Penetration seal consists of a single penetration in the wall with Hilti Firestop Collar CFS-C P (A1) on both sides. Annular gap filled with Gypsum plaster (A3) over the entire thickness of the wall or Hilti Firestop Acrylic CFS-S ACR Sealant (A2) on both sides with a depth of minimum 25 mm from the surface of the wall. Rigid walls (E) consisting of comprise concrete, aerated concrete or masonry, minimum density of 450 kg/m 3, minimum thickness 100 mm. Penetration seal consists of a single penetration in the wall with Hilti Firestop Collar CFS-C P (A1) on both sides. Annular gap filled with Gypsum plaster (A3) or cementitious mortar over the entire thickness of the wall or Hilti Firestop Acrylic Sealant CFS-S ACR (A2) on both sides with a depth of minimum 15 mm from the surface of the wall. The sealant may be backfilled with mineral wool. Maximum opening diameter: the opening should not be larger than the collar outside diameter to allow safe fixing of the collar to the wall. Minimum distance between collars (s1): 0 mm. Firestop collar (A1) fastened by hooks (F) (minimum number of hooks: see installation instructions) in flexible wall / drywall and low density rigid wall with M8 threaded rods through the wall secured with nuts on both sides. In high density rigid walls, metal anchors may be used as an alternative (e.g. Hilti HUS). Sound decoupling strips (C1) based on PE foam, used in combination with gypsum plaster or mortar as gap filler. Sound decoupling installed around the pipe within the wall. For maximum thickness see tables below. page 8 Hilti Firestop Collar CFS-C P Issue 02/2015
9 Annular gap seal (drawings show non-insulated pipes as example) Gypsum plaster (A 3 ) Gypsum plaster (A 3 ) together with sound decoupling (C 1 ) Hilti Firestop Acrylic Sealant CFS-S ACR (A 2 ) Gypsum plaster or cementitious mortar (A 3 ) Gypsum plaster or cementitious mortar (A 3 ) together with sound decoupling (C 1 ) Hilti Firestop Acrylic Sealant CFS-S ACR (A 2 ) Pipe insulation (drawings show mortar as an example for the annular gap seal) Local/Sustained pipe insulation (LS) Continued/Sustained pipe insulation (CS) Hilti Firestop Collar CFS-C P Issue 02/2015 page 9
10 Flexible and rigid walls 100 mm 1.1. Pre-insulated pipes Minimum distance between pipe closure devices: 0 mm. Hilti Firestop Collar CFS-C P (A 3 ) installed on each side of the seal and fixed together with M8 threaded rods, washers and nuts. Metal anchors with minimum Ø 8 mm may be used (e.g HUS). Branded pipes Pipe material Pipe manufacturer Pipe diameter Inner pipe diameter Collar size Classification ABS/PUR insulation/ +GF+ COOL-FIT 90 mm 32 mm CFS-C P 90/3 EI 120-U/C PE-HD 110 mm 40 mm CFS-C P 110/4 EI 120-U/C 110 mm 50 mm CFS-C P 110/4 EI 120-U/C 160 mm 90 mm CFS-C P 160/6 EI 120-U/C 180 mm 110 mm CFS-C P 180/7 EI 120-U/C 225 mm 140 mm CFS-C P 225/9 EI 120-U/C 250 mm 160 mm CFS-C P 250/10 EI 60-U/C page 10 Hilti Firestop Collar CFS-C P Issue 02/2015
11 Flexible and rigid walls 100 mm 1.2. Plastic Pipes Minimum distance between pipe closure devices: 0 mm. Hilti Firestop Collar CFS-C P (A 3 ) installed on each side of the seal and fixed together with M8 threaded rods, washers and nuts. Metal anchors with minimum Ø 8 mm may be used (e.g HUS). Normed pipes Pipe end configuration U/U Pipe material Pipe manufacturer Pipe diameter Inner pipe diameter Collar size Classification PVC-U EN ISO , 50 mm mm CFS-C P 50/1.5 EI 120-U/U EN ISO 15493, DIN 8061/2, 63 mm mm CFS-C P 63/2 5 mm) EN , 75 mm mm CFS-C P 75/2.5 EN mm mm CFS-C P 90/3 110 mm mm CFS-C P 110/4 125 mm mm CFS-C P 125/5 160 mm mm CFS-C P 160/6 PE EN 1519, 50 mm 3.0 mm CFS-C P 50/1.5 EI 120-U/U EN , EN mm 3.0 mm CFS-C P 63/2 5 mm) 75 mm 3.0 mm CFS-C P 75/ mm 3.5 mm CFS-C P 90/3 110 mm 4.2 mm CFS-C P 110/4 125 mm 4.8 mm CFS-C P 125/5 160 mm 6.2 mm CFS-C P 160/6 EN ISO 15494, 50 mm mm CFS-C P 50/1.5 EI 120-U/U DIN 8074/5 63 mm mm CFS-C P 63/2 EI 90-U/U 63 mm mm CFS-C P 63/2 EI 120-U/U 75 mm mm CFS-C P 75/2.5 EI 120-U/U 90 mm mm CFS-C P 90/3 EI 120-U/U 110 mm mm CFS-C P 110/4 EI 120-U/U 125 mm mm CFS-C P 125/5 EI 120-U/U 160 mm mm CFS-C P 160/6 EI 120-U/U EN ISO mm mm CFS-C P 50/1.5 EI 90-U/U DIN 8077/ mm mm CFS-C P 63/2 EI 60-U/U 75 mm mm CFS-C P 75/2.5 EI 60-U/U 75 mm 6.8 mm CFS-C P 75/2.5 EI 120-U/U 90 mm mm CFS-C P 90/3 EI 120-U/U 110 mm 2.7 mm CFS-C P 110/4 EI 120-U/U EN mm 1,8 CFS-C P 50/1.5 EI 120-U/U DIN EN mm 1,8 CFS-C P 50/1.5 EI 120-U/U 50 mm 1,8 2,0 CFS-C P 50/1.5 EI 120-U/U 70 mm 4,5 CFS-C P 75/2.5 EI 120-U/U 75 mm CFS-C P 75/2.5 EI 120-U/U 90 mm CFS-C P 90/3 EI 120-U/U 110 mm CFS-C P 110/4 EI 120 U/U Hilti Firestop Collar CFS-C P Issue 02/2015 page 11
12 Normed pipes Pipe end configuration U/C Pipe material Pipe norm Pipe diameter Pipe wall thickness Collar size Classification EN ISO mm mm CFS-C P 50/1.5 EI 90-U/C DIN 8077/ mm mm CFS-C P 63/2 EI 60-U/C 63 mm 10.5 mm CFS-C P 63/2 EI 120-U/C 75 mm mm CFS-C P 75/2.5 EI 60-U/C 75 mm mm CFS-C P 75/2.5 EI 120-U/C Branded pipes Pipe end configuration U/U Pipe designation Pipe manufacturer Pipe diameter Pipe wall thickness Collar size Classification Geberit Silent-db20 Geberit 56 mm 3.2 mm CFS-C P 63/2 EI 120-U/U (PE-S2) 63 mm 3.2 mm CFS-C P 63/2 EI 120-U/U 75 mm 3.6 mm CFS-C P 75/2.5 EI 120-U/U 90 mm 5.6 mm CFS-C P 90/3 EI 120-U/U 110 mm 6.0 mm CFS-C P 110/4 EI 120-U/U Wavin TS (PE-HD Wavin 50 mm 4.6 mm CFS-C P 50/1.5 EI 90-U/U 100 RC) 75 mm 6.8 mm CFS-C P 75/2.5 EI 120-U/U 90 mm 8.2 mm CFS-C P 90/3 EI 120-U/U 110 mm 10.0 mm CFS-C P 110/4 EI 120-U/U Geberit Silent 32 mm 1,8 mm CFS-C P 50/1.5 EI 120-U/U Ostendorf Skolan-dB, Phonex AS, Pipelife 40 mm 1,8 mm CFS-C P 50/1.5 EI 120-U/U Master 3, POLO- 50 mm 1,8 2,0 mm CFS-C P 50/1.5 EI 120-U/U PLAST Polo Kal NG, 56 mm 4,0 mm CFS-C P 63/2 EI 90-U/C POLOPLAST Polo Kal 3S, Rehau Raupiano 70 mm 4,5 mm CFS-C P 75/2.5 EI 120-U/U Plus, Wavin AS / 75 mm 1,8 3,8 mm CFS-C P 75/2.5 EI 120-U/U KeKelit Phonex AS, Wavin SiTech, 90 mm 2,8 4,5 mm CFS-C P 90/3 EI 120-U/U Cloes Blue Power, 110 mm 2,7 5,3 mm CFS-C P 110/4 EI 120 U/U Cloes PhoNoFire, Valsire Triplus, Valsire Silere, Marley Silent Aquatherm blue, 50 mm 1,8 2,9 mm CFS-C P 50/1.5 EI 90-U/U Aquatherm blue Faserverbundrohr, 63 mm 1,8 5,8 mm CFS-C P 63/2 EI 60-U/U Aquatherm red, 75 mm 1,9 6,8 mm CFS-C P 75/2,5 EI 60-U/U 9 mm Aquatherm green, 75 mm 6,8 12,5 mm CFS-C P 75/2.5 EI 120 U/U Aquatherm green Faserverbundrohr, 90 mm 8,2 15,0 mm CFS-C P 90/3 EI 120 U/U +GF+ PROGEF Standard pipe, +GF+ Dekaprop Industry pipe)aquatherm green Faserverbundrohr, +GF+ PROGEF Standard pipe, +GF+ Dekaprop Industry pipe 110 mm 2,7 mm CFS-C P 110/4 EI 120 U/U page 12 Hilti Firestop Collar CFS-C P Issue 02/2015
13 Branded pipes Pipe end configuration U/C Pipe designation Pipe manufacturer Pipe diameter Pipe wall thickness Collar size Classification Aquatherm blue, 50 mm mm CFS-C P 50/1.5 EI 90-U/C Aquatherm blue Faserverbundrohr, 63 mm mm CFS-C P 63/2 EI 60-U/C Aquatherm red, 63 mm 10.5 mm CFS-C P 63/2 EI 120-U/C Aquatherm green, 75 mm mm CFS-C P 75/2.5 EI 60-U/C Aquatherm green Faserverbundrohr, 75 mm mm CFS-C P 75/2.5 EI 120-U/C +GF+ PROGEF 50 mm mm CFS-C P 50/1.5 EI 90-U/C Standard pipe, +GF+ Dekaprop Industry pipe)aquatherm green Faserverbundrohr, +GF+ PROGEF Standard pipe, +GF+ Dekaprop Industry pipe Branded pipes Pipe end configuration C/U Pipe designation Pipe manufacturer Pipe diameter Pipe wall thickness Collar size Classification Geberit Silent-db20 Geberit 135 mm 6.0 mm CFS-C P 160/6 EI 120-C/U (PE-S2) 160 mm 7.0 mm CFS-C P 160/6 EI 120-C/U Hilti Firestop Collar CFS-C P Issue 02/2015 page 13
14 Flexible and rigid walls 100 mm 1.3. Plastic pipes with foamed elastomeric insulation Minimum distance between pipe closure devices: 0 mm. Hilti Firestop Collar CFS-C P (A 3 ) installed on each side of the seal and fixed together with M8 threaded rods, washers and nuts. Metal anchors with minimum Ø 8 mm may be used (e.g HUS). Normed pipes Pipe material Pipe norm Pipe diameter PE EN 1519, EN , EN EN ISO DIN 8077/8078 Pipe wall thickness Insulation thickness Collar size Classification Insulation configuration 110 mm 4.2 mm 10 mm CFS-C P 125/5 EI 90-U/U Continued Interrupted 110 mm 4.2 mm 25 mm CFS-C P 160/6 EI 90-U/U Continued sustained 40 mm mm 9 mm CFS-C P 50/1.5 EI 120-U/C Continued 50 mm mm 9 mm CFS-C P 63/2 EI 120-U/C 75 mm mm 10 mm CFS-C P 90/3 EI 120-U/C length 250 mm 110 mm mm 10 mm CFS-C P 125/5 EI 120-U/C page 14 Hilti Firestop Collar CFS-C P Issue 02/2015
15 Branded Pipes Pipe designation Wavin TS (PE-HD 100 RC) Friatherm starr (PVC-C) Rautitan flex (PE-Xa) Aquatherm Climatherm Faserverbundrohr () Aquatherm Firestop () PROGEF Standard pipe () Pipe manufacturer Aquatherm blue, Aquatherm blue Faserverbundrohr, Aquatherm red, Aquatherm green, Aquatherm green Faserverbundrohr, +GF+ PROGEF Standard pipe, +GF+ Dekaprop Industry pipe) Aquatherm green Faserverbundrohr, +GF+ PROGEF Standard pipe, +GF+ Dekaprop Industry pipe Aquatherm green Pipe diameter Pipe wall thickness Insulation thickness Collar size Classification Insulation configuration 40 mm mm 9 mm CFS-C P 50/1.5 EI 120-U/C Continued 50 mm mm 9 mm CFS-C P 63/2 EI 120-U/C 75 mm mm 10 mm CFS-C P 90/3 EI 120-U/C length 250 mm 90 mm mm 22.5 mm CFS-C P 125/5 EI 120-U/C 40 mm 3.7 mm 9 mm CFS-C P 50/1.5 EI 120-U/C Continued 50 mm 4.6 mm 9 mm CFS-C P 63/2 EI 120-U/C 75 mm 6.8 mm 10 mm CFS-C P 90/3 EI 120-U/C length 250 mm 110 mm 10.0 mm 10 mm CFS-C P 125/5 EI 120-U/C Aquatherm 40 mm 5.5 mm 9 mm CFS-C P 50/1.5 EI 120-U/C Continued green Faserverbundrohr 50 mm 6.9 mm 9 mm CFS-C P 63/2 EI 120-U/C 75 mm 10.3 mm 10 mm CFS-C P 90/3 EI 120-U/C length 250 mm 110 mm 15.1 mm 10 mm CFS-C P 125/5 EI 120-U/C Wavin 50 mm 4.6 mm 9 mm CFS-C P 63/2 EI 120-U/C Continued 63 mm 5.8 mm 10 mm CFS-C P 75/2.5 EI 120-U/C 75 mm 6.8 mm 10 mm CFS-C P 90/3 EI 120-U/C length 250 mm 90 mm 8.2 mm 10 mm CFS-C P 110/4 EI 120-U/C 110 mm 10.0 mm 10 mm CFS-C P 125/5 EI 120-U/C Friatec 32 mm 3.6 mm 9 mm CFS-C P 50/1.5 EI 120-U/C Continued 40 mm 4.5 mm 9 mm CFS-C P 63/2 EI 120-U/C 50 mm 5.6 mm 9 mm CFS-C P 75/2.5 EI 120-U/C length 200 mm 63 mm 7.1 mm 10 mm CFS-C P 90/3 EI 120-U/C Rehau 40 mm 5.5 mm 9 mm CFS-C P 63/2 EI 120-U/C Continued 50 mm 6.9 mm 9 mm CFS-C P 63/2 EI 120-U/C 63 mm 8.6 mm 10 mm CFS-C P 75/2.5 EI 120-U/C length 250 mm Aquatherm 40 mm 3.7 mm 9 mm CFS-C P 50/1.5 EI 120-U/C Continued 50 mm 4.6 mm 9 mm CFS-C P 63/2 EI 120-U/C 75 mm 6.8 mm 10 mm CFS-C P 90/3 EI 120-U/C length 250 mm 110 mm 10.0 mm 10 mm CFS-C P 125/5 EI 120-U/C Aquatherm 40 mm 5.5 mm 9 mm CFS-C P 50/1.5 EI 120-U/C Continued 50 mm 6.9 mm 9 mm CFS-C P 63/2 EI 120-U/C 75 mm 10.3 mm 10 mm CFS-C P 90/3 EI 120-U/C length 250 mm 110 mm 15.1 mm 10 mm CFS-C P 125/5 EI 120-U/C +GF+ 40 mm 3.7 mm 9 mm CFS-C P 50/1.5 EI 120-U/C Continued 50 mm 4.6 mm 9 mm CFS-C P 63/2 EI 120-U/C 75 mm 6.8 mm 10 mm CFS-C P 90/3 EI 120-U/C length 250 mm 110 mm 10.0 mm 10 mm CFS-C P 125/5 EI 120-U/C Hilti Firestop Collar CFS-C P Issue 02/2015 page 15
16 Flexible and rigid walls 100 mm 1.4. Composite pipes with foamed elastomeric insulation Minimum distance between pipe closure devices: 0 mm. Hilti Firestop Collar CFS-C P (A 3 ) installed on each side of the seal and fixed together with M8 threaded rods, washers and nuts. Metal anchors with minimum Ø 8 mm may be used (e.g HUS). Branded pipes Pipe designation and material Geberit Mepla (PE-Xb/Al/ PE-HD) Rautitan stabil (PE-Xa/Al/ PE-HD) KELOX KM 110 (PE-X/Al/ PE) Pipe manufacturer Pipe diameter Pipe wall thickness Insulation thickness Collar size Classification Insulation configuration Geberit 16 mm 2.0 mm 11.5 mm CFS-C P 50/1.5 EI 120-U/C Continued 32 mm 3.0 mm 13 mm CFS-C P 63/2 EI 120-U/C sustained 40 mm 3.5 mm 9 mm CFS-C P 63/2 EI 120-U/C 50 mm 4.0 mm 9 mm CFS-C P 63/2 EI 120-U/C 63 mm 4.5 mm 10 mm CFS-C P 75/2.5 EI 60-U/C 75 mm 4.7 mm 10 mm CFS-C P 90/3 EI 90-U/C Rehau 16 mm 2.6 mm 11.5 mm CFS-C P 50/1.5 EI 120-U/C Continued 32 mm 4.7 mm 13 mm CFS-C P 63/2 EI 120-U/C sustained 40 mm 6.0 mm 9 mm CFS-C P 63/2 EI 120-U/C Ke Kelit 16 mm 2.0 mm 11.5 mm CFS-C P 50/1.5 EI 120-U/C Continued 32 mm 3.0 mm 13 mm CFS-C P 63/2 EI 120-U/C sustained 32 mm 3.0 mm 9 mm CFS-C P 50/1.5 EI 90-U/C 40 mm 4.0 mm 9 mm CFS-C P 50/1.5 EI 90-U/C 50 mm 4.5 mm 9 mm CFS-C P 63/2 EI 90-U/C 63 mm 6.0 mm 10 mm CFS-C P 75/2.5 EI 90-U/C page 16 Hilti Firestop Collar CFS-C P Issue 02/2015
17 2. Rigid walls The intended use of the Hilti Firestop Collar CFS-C is to reinstate the fire resistance of: Rigid walls (E) consisting of comprise concrete, aerated concrete or masonry, minimum density of 650 kg/m 3, minimum thickness 150 mm. Penetration seal consists of a single penetration in the wall with Hilti Firestop Collar CFS-C P (A1) on both sides. Annular gap filled with Gypsum plaster (A3) or cementitious mortar over the entire thickness of the wall or Hilti Firestop Acrylic Sealant CFS-S ACR (A2) with a depth of minimum 15 mm from the surface of the wall. The sealant may be backfilled with mineral wool. Maximum opening diameter: the opening should not be larger than the collar outside diameter to allow safe fixing of the collar to the wall. Minimum distance between collars (s1): 0 mm. Firestop collar (A1) fastened by hooks (F) (minimum number of hooks: see installation instructions) in flexible wall / drywall and low density rigid wall with M8 threaded rods through the wall secured with nuts on both sides. In high density rigid walls, metal anchors may be used as an alternative (e.g. Hilti HUS). Sound decoupling strips (C1) based on PE foam, used in combination with gypsum plaster or mortar as gap filler. Sound decoupling installed around the pipe within the wall. For maximum thickness see tables below. Hilti Firestop Collar CFS-C P Issue 02/2015 page 17
18 Rigid walls 150 mm 2.1. Plastic Pipes Minimum distance between pipe closure devices: 0 mm. Hilti Firestop Collar CFS-C P (A 3 ) installed on each side of the seal and fixed together with M8 threaded rods, washers and nuts. Metal anchors with minimum Ø 8 mm may be used (e.g HUS). Normed pipes Pipe end configuration U/U Pipe material Pipe norm Pipe diameter Pipe wall thickness Collar size Classification PVC-U EN ISO , 180 mm mm CFS-C P 180/7 EI 180-U/U EN ISO 15493, DIN 8061/2, 200 mm mm CFS-C P 200/8 EI 180-U/U EN , 225 mm mm CFS-C P 225/9 EI 180-U/U EN mm mm CFS-C P 250/10 EI 180-U/U PE EN 1519, EN , 200 mm 6.2 mm CFS-C P 200/8 EI 120-U/U EN mm 7.8 mm CFS-C P 250/10 EI 120-U/U EN ISO 15494, 180 mm mm CFS-C P 180/7 EI 120-U/U 5 mm) DIN 8074/5 200 mm mm CFS-C P 200/8 EI 120-U/U 200 mm 11.4 mm CFS-C P 200/8 EI 180-U/U 225 mm mm CFS-C P 225/9 EI 180-U/U 250 mm mm CFS-C P 250/10 EI 180-U/U Normed pipes Pipe end configuration U/C Pipe material Pipe norm Pipe diameter Pipe wall thickness Collar size Classification PVC-U EN ISO , 50 mm 1.8 mm CFS-C P 50/1.5 EI 180-U/C EN ISO 15493, DIN 8061/2, 250 mm mm CFS-C P 250/10 EI 180-U/C EN , EN PE EN ISO 15494, 50 mm 2.9 mm CFS-C P 50/1.5 EI 180-U/C DIN 8074/5 250 mm 7.8 mm CFS-C P 250/10 EI 180-U/C 250 mm mm CFS-C P 250/10 EI 120-U/C 5 mm) Normed pipes Pipe end configuration C/U Pipe material Pipe norm Pipe diameter Pipe wall thickness Collar size Classification EN mm mm CFS-C P 200/8 EI 120-C/U DIN EN mm 8.6 mm CFS-C P 250/10 EI 120-C/U Branded pipes Pipe end configuration C/U Pipe material Pipe norm Pipe diameter Pipe wall thickness Collar size Classification Geberit Silent 200 mm mm CFS-C P 200/8 EI 120-C/U Ostendorf Skolan-dB, Phonex AS, Pipelife 250 mm 8.6 mm CFS-C P 250/10 EI 120-C/U Master 3, POLO- PLAST Polo Kal NG, POLOPLAST Polo Kal 3S, Rehau Raupiano Plus, Wavin "AS / KeKelit Phonex AS, Wavin SiTech, Cloes Blue Power, Cloes PhoNoFire, Valsire Triplus, Valsire Silere,Marley Silent page 18 Hilti Firestop Collar CFS-C P Issue 02/2015
19 3. Rigid floors, minimum density of 2400 kg/m 3 The intended use of the Hilti Firestop Collar CFS-C is to reinstate the fire resistance of: Rigid floors (E) consisting of concrete with a minimum density of 2400 kg/m 3, minimum thickness 150 mm. Penetration seal consists of a single penetration in the floor with Hilti Firestop Collar CFS-C P (A1) on the underside of the floor. Annular gap filled either with gypsum plaster or cementitious mortar (A3) over the entire thickness of the floor or with mineral wool of minimum density 60 kg/m 3 covered by Hilti Firestop Acrylic Sealant CFS-S ACR (A2) on top side (or on both sides) with a depth of minimum 10 mm. Classifications EI 120 and lower (opening diameter up to 300 mm), classification EI 180 (opening diameter up to 260 mm): The opening diameter should not be larger than the collar outside diameter to allow a safe fixing of the collar to the floor. Classification EI 180 (opening diameter > 260 mm): see in tables below. Minimum distance between collars/annular gap edge (s1): 0 mm. Firestop collar (A1) fastened by hooks (minimum number of hooks: see instructions for use) with metal anchors (e.g. Hilti HUS) on the underside of the floor (minimum 6 mm up to collar size 110/4" and 10 mm for higher collar sizes). Sound decoupling strips (C1) based on PE foam, used in combination with gypsum plaster or mortar as gap filler. Sound decoupling installed around the pipe within the floor. For maximum thickness see tables below. Hilti Firestop Collar CFS-C P Issue 02/2015 page 19
20 Annular gap seal (drawings show non-insulated pipes as example) Gypsum plaster or cementitious mortar (A 3 ) Cementitious mortar (A 3 ) together with sound decoupling (C 1 ) A3 C1 Hilti Firestop Acrylic Sealant CFS-S ACR (A 2 ) Pipe insulation (drawings show mortar as an example for the annular gap seal) Local/Sustained pipe insulation (LS) Continued/Sustained pipe insulation (CS) Hilti Firestop Acrylic Sealant CFS-S ACR (A 2 ) Gypsum plaster or cementitious mortar (A 3 ) page 20 Hilti Firestop Collar CFS-C P Issue 02/2015
21 Rigid Floors 2400 kg/m Pre-insulated Pipes Minimum distance between pipe closure devices: 0 mm. Hilti Firestop Collar CFS-C P (A 3 ) installed on each side of the seal and fixed together with M8 threaded rods, washers and nuts. Metal anchors with minimum Ø 8 mm may be used (e.g HUS). Branded Pipes Pipe material Pipe manufacturer Pipe diameter Inner pipe diameter Collar size Classification ABS/PUR insulation/ +GF+ COOL-FIT 90 mm 32 mm CFS-C P 90/3 EI 120-U/C PE-HD 110 mm 40 mm CFS-C P 110/4 EI 120-U/C 110 mm 50 mm CFS-C P 110/4 EI 120-U/C 160 mm 90 mm CFS-C P 160/6 EI 120-U/C 180 mm 110 mm CFS-C P 180/7 EI 60-U/C 225 mm 140 mm CFS-C P 225/9 EI 120-U/C 250 mm 160 mm CFS-C P 250/10 EI 120-U/C Hilti Firestop Collar CFS-C P Issue 02/2015 page 21
22 Rigid Floors 2400 kg/m Plastic Pipes Minimum distance between pipe closure devices: 0 mm. Hilti Firestop Collar CFS-C P (A 3 ) installed on each side of the seal and fixed together with M8 threaded rods, washers and nuts. Metal anchors with minimum Ø 8 mm may be used (e.g HUS). Normed pipes Pipe end configuration U/U Pipe material Pipe norm Pipe diameter Pipe wall thickness Collar size Classification PVC-U EN ISO , 20 mm mm CFS-C P 50/1.5 EI 120-U/U EN ISO 15493, DIN 8061/2, 50 mm mm CFS-C P 50/1.5 EN , 63 mm mm CFS-C P 63/2 5 mm) EN mm mm CFS-C P 75/ mm mm CFS-C P 90/3 110 mm mm CFS-C P 110/4 125 mm mm CFS-C P 125/5 160 mm mm CFS-C P 160/6 180 mm mm CFS-C P 180/7 200 mm mm CFS-C P 200/8 225 mm mm CFS-C P 225/9 250 mm mm CFS-C P 250/10 PVC-C EN mm mm CFS-C P 50/1.5 EI 120-U/U 50 mm mm CFS-C P 50/ mm mm CFS-C P 63/2 5 mm) 75 mm mm CFS-C P 75/ mm mm CFS-C P 90/3 110 mm mm CFS-C P 110/4 125 mm mm CFS-C P 125/5 160 mm mm CFS-C P 160/6 180 mm mm CFS-C P 180/7 200 mm mm CFS-C P 200/8 225 mm mm CFS-C P 225/9 250 mm mm CFS-C P 250/10 PE EN 1519, 50 mm 3.0 mm CFS-C P 50/1.5 EI 120-U/U EN , EN mm 3.0 mm CFS-C P 63/2 75 mm 3.0 mm CFS-C P 75/2.5 5 mm) 90 mm 3.5 mm CFS-C P 90/3 110 mm 4.2 mm CFS-C P 110/4 125 mm 4.8 mm CFS-C P 125/5 160 mm 6.2 mm CFS-C P 160/6 200 mm 6.2 mm CFS-C P 200/8 250 mm 7.7 mm CFS-C P 250/10 EN ISO 15494, 20 mm mm CFS-C P 50/1.5 EI 90-U/U DIN 8074/5 50 mm mm CFS-C P 50/1.5 EI 120-U/U 63 mm mm CFS-C P 63/2 EI 120-U/U 75 mm mm CFS-C P 75/2.5 EI 120-U/U 90 mm mm CFS-C P 90/3 EI 120-U/U 110 mm mm CFS-C P 110/4 EI 120-U/U 125 mm mm CFS-C P 125/5 EI 120-U/U 160 mm mm CFS-C P 160/6 EI 120-U/U page 22 Hilti Firestop Collar CFS-C P Issue 02/2015
23 Normed pipes Pipe end configuration U/U Pipe material Pipe norm Pipe diameter Pipe wall thickness Collar size Classification PE EN ISO 15494, mm 1.9 mm CFS-C P 50/1.5 EI 90-U/U DIN 8074/5 2 Pipes in 1 Collar mm 2.8 mm CFS-C P 50/1.5 EN ISO mm mm CFS-C P 50/1.5 EI 120-U/U DIN 8077/ mm mm CFS-C P 50/1.5 EI 120-U/U 63 mm mm CFS-C P 63/2 EI 180-U/U 75 mm mm CFS-C P 75/2.5 EI 180-U/U 90 mm mm CFS-C P 90/3 EI 180-U/U 110 mm 2.7 mm CFS-C P 110/4 EI 180-U/U 125 mm 3.1 mm CFS-C P 125/5 EI 180-U/U EN mm 1,2 1,8 mm CFS-C P 50/1.5 EI 90-U/U 40 mm 1,8 mm CFS-C P 50/ mm 1,8 2,0 mm CFS-C P 50/ mm 4,0 mm CFS-C P 63/2 75 mm 1,9 4,5 mm CFS-C P 75/ mm 4,5 mm CFS-C P 75/ mm 2,8 4,5 mm CFS-C P 90/3 110 mm 2,7 5,3 mm CFS-C P 110/4 125 mm 3,9 5,3 mm CFS-C P 125/5 135 mm 5,3 mm CFS-C P 160/6 160 mm 4,9 5,3 mm CFS-C P 160/6 Normed pipes Pipe end configuration U/C Pipe material Pipe norm Pipe diameter Pipe wall thickness Collar size Classification PVC-U EN ISO , 50 mm 1.8 mm CFS-C P 50/1.5 EI 180-U/C EN ISO 15493, DIN 8061/2, 250 mm mm CFS-C P 250/10 5 mm) EN , EN PE 5 mm) EN ISO 15494, DIN 8074/5 EN ISO DIN 8077/ mm 2.9 mm CFS-C P 50/1.5 EI 180-U/C 180 mm mm CFS-C P 180/7 EI 120-U/C 200 mm mm CFS-C P 200/8 EI 120-U/C 225 m mm CFS-C P 225/9 EI 120-U/C 250 mm mm CFS-C P 250/10 EI 120-U/C 250 mm 7.8 mm CFS-C P 250/10 EI 180-U/C 40 mm mm CFS-C P 50/1.5 EI 120-U/C 50 mm mm CFS-C P 50/1.5 EI 180-U/C 63 mm mm CFS-C P 63/2 EI 180-U/C 75 mm 6.8 mm CFS-C P 75/2.5 EI 180-U/C 75 mm mm CFS-C P 75/2.5 EI 120-U/C 90 mm 8.2 mm CFS-C P 90/3 EI 180-U/C 90 mm mm CFS-C P 90/3 EI 120-U/C 110 mm mm CFS-C P 110/4 EI 120-U/C Hilti Firestop Collar CFS-C P Issue 02/2015 page 23
24 Branded pipes Pipe end configuration U/U Pipe designation Pipe manufacturer Pipe diameter Pipe wall thickness Collar size Classification Geberit Silent-db20 Geberit 75 mm 3.6 mm CFS-C P 75/2.5 EI 180-U/U (PE-S2) 90 mm 5.6 mm CFS-C P 90/3 EI 180-U/U 110 mm 6.0 mm CFS-C P 110/4 EI 180-U/U 135 mm 6.0 mm CFS-C P 160/6 EI 120-U/U 160 mm 7.0 mm CFS-C P 160/6 EI 180-U/U Wavin TS Wavin 50 mm 4.6 mm CFS-C P 50/1.5 EI 90-U/U (PE-HD 100 RC) 63 mm 5.8 mm CFS-C P 63/2 EI 120-U/U 75 mm 6.8 mm CFS-C P 75/2.5 EI 120-U/U 90 mm 8.2 mm CFS-C P 90/3 EI 120-U/U 110 mm 10.0 mm CFS-C P 110/4 EI 120-U/U Geberit Silent 32 mm 1,2 1,8 mm CFS-C P 50/1.5 EI 180-U/U Ostendorf Skolan-dB, Phonex AS, Pipelife 40 mm 1,8 mm CFS-C P 50/1.5 EI 180-U/U Master 3, POLO- 50 mm 1,8 2,0 mm CFS-C P 50/1.5 EI 180-U/U PLAST Polo Kal NG, 58 mm 4,0 mm CFS-C P 63/2 EI 180-U/U POLOPLAST Polo Kal 3S, Rehau Raupiano 75 mm 1,9 4,5 mm CFS-C P 75/2.5 EI 180-U/U Plus, Wavin AS / 78 mm 4,5 mm CFS-C P 75/2.5 EI 180-U/U KeKelit Phonex AS, Wavin SiTech, 90 mm 2,8 4,5 mm CFS-C P 90/3 EI 90-U/U Cloes Blue Power, 110 mm 2,7 5,3 mm CFS-C P 110/4 EI 180-U/U Cloes PhoNoFire, Valsire Triplus, 125 mm 3,9 5,3 mm CFS-C P 125/5 EI 180-U/U Valsire Silere, Marley 135 mm 5,3 mm CFS-C P 160/6 EI 180-U/U Silent 160 mm 4,9 5,3 mm CFS-C P 160/6 EI 90-U/U Magnaplast Magnaplast 58 mm 4,0 mm CFS-C P 90/3 EI 180-U/U Skolan-dB pipes 78 mm 4,5 mm CFS-C P 75/ mm 4,5 mm CFS-C P 90/3 110 mm 5,3 mm CFS-C P 110/4 135 mm 5,3 mm CFS-C P 160/6 160 mm 5,3 mm CFS-C P 160/6 Rehau Raupiano Rehau 50 mm 1,8 mm CFS-C P 50/1.5 EI 180-U/U Plus pipes (/-MV/) 75 mm 1,9 mm CFS-C P 75/2.5 EI 180-U/U 110 mm 2,7 mm CFS-C P 110/4 EI 180-U/U Wavin AS / KeKelit Wavin 70 mm 4,5 mm CFS-C P 75/2.5 EI 180-U/U Phonex AS pipes 90 mm 4,5 mm CFS-C P 90/3 EI 180-U/U 125 mm 5,3 mm CFS-C P 125/5 EI 180-U/U 160 mm 5,3 mm CFS-C P 160/6 EI 180-U/U Wavin SiTech pipes Wavin 75 mm 2,3 mm CFS-C P 75/2.5 EI 180-U/U 90 mm 2,8 mm CFS-C P 90/3 EI 180-U/U 125 mm 3,9 mm CFS-C P 125/5 EI 180-U/U 160 mm 4,9mm CFS-C P 160/6 EI 180-U/U Aquatherm blue, Aquatherm 20 mm mm CFS-C P 50/1.5 EI 120-U/U blue Faserver- bundrohr, Aquatherm 50 mm mm CFS-C P 50/1.5 EI 180-U/U red, Aquatherm green, 63 mm mm CFS-C P 63/2 EI 180-U/U Aquatherm green 75 mm mm CFS-C P 75/2.5 EI 180-U/U Faser verbundrohr, +GF+ PROGEF 90 mm mm CFS-C P 90/3 EI 180-U/U Standard pipe, +GF+ 110 mm 2.7 mm CFS-C P 110/4 EI 180-U/U Dekaprop Industry pipe) Aquatherm green Faserverbundrohr, +GF+ PROGEF Standard pipe, +GF+ Dekaprop 125 mm 3.1 mm CFS-C P 125/5 EI 180-U/U page 24 Industry pipe Hilti Firestop Collar CFS-C P Issue 02/2015
25 Branded pipes Pipe end configuration U/C Pipe designation Pipe manufacturer Pipe diameter Pipe wall thickness Collar size Classification Aquatherm blue, 40 mm mm CFS-C P 50/1.5 EI 120-U/C Aquatherm blue Faserverbundrohr, 50 mm mm CFS-C P 50/1.5 EI 180-U/C Aquatherm red, 63 mm mm CFS-C P 63/2 EI 180-U/C Aquatherm green, 75 mm 6.8 mm CFS-C P 75/2.5 EI 180-U/C Aquatherm green Faserverbundrohr, 75 mm mm CFS-C P 75/2.5 EI 120-U/C +GF+ PROGEF 90 mm 8.2 mm CFS-C P 90/3 EI 180-U/C Standard pipe, +GF+ Dekaprop Industry 90 mm mm CFS-C P 90/3 EI 120-U/C pipe)aquatherm green Faserverbundrohr, +GF+ PROGEF Standard pipe, +GF+ Dekaprop Industry pipe 110 mm mm CFS-C P 110/4 EI 120-U/C Hilti Firestop Collar CFS-C P Issue 02/2015 page 25
26 Rigid Floors 2400 kg/m Plastic pipes with foamed elastomeric insulation Minimum distance between pipe closure devices: 0 mm. Hilti Firestop Collar CFS-C P (A 3 ) installed on each side of the seal and fixed together with M8 threaded rods, washers and nuts. Metal anchors with minimum Ø 8 mm may be used (e.g HUS). Normed pipes Pipe material Pipe norm Pipe diameter EN ISO DIN 8077/8078 Branded pipes Pipe designation Wavin TS (PE- HD-100 RC) Friatherm starr (PVC-C) Rautitan flex (PE-Xa) Pipe manufacturer Pipe wall thickness Insulation thickness Collar size Classification Insulation configuration 40 mm mm 9 mm CFS-C P 63/2 EI 180-U/C Continued 50 mm mm 9 mm CFS-C P 75/2.5 EI 180-U/C 75 mm mm 10 mm CFS-C P 90/3 EI 180-U/C length 250 mm 90 mm 12.3 mm 22.5 mm CFS-C P 160/6 EI 120-U/C 110 mm mm 10 mm CFS-C P 125/5 EI 180-U/C Pipe diameter Pipe wall thickness Insulation thickness Collar size Classification Insulation configuration Wavin 50 mm 4.6 mm 9 mm CFS-C P 63/2 EI 180-U/C Continued Supllier 63 mm 5.8 mm 10 mm CFS-C P 75/ mm 6.8 mm 10 mm CFS-C P 90/3 length 250 mm 90 mm 8.2 mm 9.5 mm CFS-C P 110/4 110 mm 10.0 mm 9.5 mm CFS-C P 125/5 Friatec 32 mm 3.6 mm 9 mm CFS-C P 50/1.5 EI 180-U/C Continued 40 mm 4.5 mm 9 mm CFS-C P 63/2 50 mm 5.6 mm 9 mm CFS-C P 75/2.5 length 200 mm 63 mm 7.1 mm 10 mm CFS-C P 90/3 Rehau 40 mm 6.0 mm 9 mm CFS-C P 63/2 EI 180-U/C Continued 50 mm 6.9 mm 9 mm CFS-C P 75/2.5 EI 180-U/C 63 mm 8.6 mm 9 mm CFS-C P 90/3 EI 180-U/C length 250 mm 40 mm 6.0 mm mm CFS-C P 63/2 EI 120-U/C 75/ mm 6.9 mm 9 21 mm CFS-C P 75/2.5 EI 120-U/C 90/3 63 mm 8.6 mm mm CFS-C P 90/3 EI 120-U/C 110/4 Aquatherm blue, 40 mm mm 9 mm CFS-C P 63/2 EI 180-U/C Continued Aquatherm 50 mm mm 9 mm CFS-C P 75/2.5 EI 180-U/C blue Faserverbundrohr, 75 mm mm 10 mm CFS-C P 90/3 EI 180-U/C length 250 mm Aquatherm red, 90 mm 12.3 mm 22.5 mm CFS-C P 160/6 EI 120-U/C Aquatherm green, mm 10 mm CFS-C P 125/5 EI 180-U/C Aquatherm green Faserverbundrohr, +GF+ PROGEF Standard pipe, +GF+ Dekaprop Industry pipe) Aquatherm green Faserverbundrohr, +GF+ PROGEF Standard pipe, +GF+ Dekaprop Industry pipe page 26 Hilti Firestop Collar CFS-C P Issue 02/2015
27 Rigid Floors 2400 kg/m Composite pipes Minimum distance between pipe closure devices: 0 mm. Hilti Firestop Collar CFS-C P (A 3 ) installed on each side of the seal and fixed together with M8 threaded rods, washers and nuts. Metal anchors with minimum Ø 8 mm may be used (e.g HUS). Branded pipes Pipe designation Pipe manufacturer Pipe diameter Pipe wall thickness Collar size Classification Geberit Mepla Geberit 40 mm 3.5 mm CFS-C P 50/1.5 EI 90-U/C (PE-Xb/Al/PE-HD) 50 mm 4.0 mm CFS-C P 50/1.5 EI 120-U/C 63 mm 4.5 mm CFS-C P 63/2 EI 60-U/C 75 mm 4.7 mm CFS-C P 75/2.5 EI 30-U/C 110 mm 6.0 mm CFS-C P 110/4 EI 180-U/U Hilti Firestop Collar CFS-C P Issue 02/2015 page 27
28 Rigid floors 2400 kg/m Composite pipes with foamed elastomeric insulation Minimum distance between pipe closure devices: 0 mm. Hilti Firestop Collar CFS-C P (A 3 ) installed on each side of the seal and fixed together with M8 threaded rods, washers and nuts. Metal anchors with minimum Ø 8 mm may be used (e.g HUS). Branded Pipes Pipe designation Geberit Mepla (PE-Xb/Al/ PE-HD) Geberit Mepla (PE-Xb/Al/ PE-HD) KELOX KM 110 (PE-X/Al/ PE-X) KELOX KM 110 (PE-X/Al/ PE-X) KELOX KM 110 (PE-X/Al/ PE-X) Rautitan stabil (PE-Xa//Al/ PE-HD) Pipe manufacturer Pipe diameter Pipe wall thickness Insulation thickness Collar size Classification Insulation configuration Geberit 40 mm 3.5 mm 9 mm CFS-C P 63/2 EI 180-U/C Continued 50 mm 4.0 mm 9 mm CFS-C P 63/2 63 mm 4.5 mm 9 mm CFS-C P 75/2.5 length 250 mm 75 mm 4.7 mm 10 mm CFS-C P 90/3 Geberit 40 mm 3.5 mm mm CFS-C P 63/2 EI 120-U/C 75/ mm 4.0 mm 9 21 mm CFS-C P 63/2 90/3 63 mm 4.5 mm mm CFS-C P 75/ /4 75 mm 4.7 mm mm CFS-C P 90/3 125/5 KeKelit 32 mm 3.0 mm 9 mm CFS-C P 50/1.5 EI 180-U/C Continuated 40 mm 4.0 mm 9 mm CFS-C P 50/1.5 EI 180-U/C Sustained 50 mm 4.5 mm 9 mm CFS-C P 63/1.5 EI 180-U/C 63 mm 6.0 mm 10 mm CFS-C P 75/2.5 EI 120-U/C KeKelit 32 mm 3.0 mm mm CFS-C P 50/1.5 EI 120-U/C Continuated 75/2.5 Sustained 40 mm 4.0 mm mm CFS-C P 50/1.5 75/ mm 4.5 mm 9 21 mm CFS-C P 63/2 90/3 63 mm 6.0 mm mm CFS-C P 75/ /4 KeKelit 32 mm 3.0 mm 19.5 mm CFS-C P 75/2.5 EI 120-U/C Continued 40 mm 4.0 mm 20.5 mm CFS-C P 75/ mm 4.5 mm 21 mm CFS-C P 90/3 length 250 mm 63 mm 6.0 mm 21.5 mm CFS-C P 110/4 Rehau 40 mm 6.0 mm 9 mm CFS-C P 63/2 EI 180-U/C Continued 40 mm 6.0 mm mm CFS-C P 63/2 EI 120-U/C 75/2.5 length 250 mm page 28 Hilti Firestop Collar CFS-C P Issue 02/2015
29 4. Rigid floors, minimum density of 550 kg/m 3 The floor must have a minimum thickness of 150 mm and comprise concrete or aerated concrete with a minimum density of 550 kg/m 3. For details of the penetration seal design see 3. Pipes shall be supported at maximum 250 mm away from the upper face of the floor construction. Rigid Floors 550 kg/m Pre-insulated Pipes Minimum distance between pipe closure devices: 0 mm. Hilti Firestop Collar CFS-C P (A 3 ) installed on each side of the seal and fixed together with M8 threaded rods, washers and nuts. Metal anchors with minimum Ø 8 mm may be used (e.g HUS). Branded pipes Pipe material Pipe manufacturer Pipe diameter Inner pipe diameter Collar size Classification ABS/PUR insulation/ +GF+ COOL-FIT 90 mm 32 mm CFS-C P 90/3 EI 120-U/C PE-HD 110 mm 40 mm CFS-C P 110/4 EI 120-U/C 110 mm 50 mm CFS-C P 110/4 EI 120-U/C 160 mm 90 mm CFS-C P 160/6 EI 120-U/C 180 mm 110 mm CFS-C P 180/7 EI 60-U/C 225 mm 140 mm CFS-C P 225/9 EI 120-U/C 250 mm 160 mm CFS-C P 250/10 EI 120-U/C Rigid Floors 550 kg/m Plastic Pipes Minimum distance between pipe closure devices: 0 mm. Hilti Firestop Collar CFS-C P (A 3 ) installed on each side of the seal and fixed together with M8 threaded rods, washers and nuts. Metal anchors with minimum Ø 8 mm may be used (e.g HUS). Normed pipes Pipe end configuration U/U Pipe material Pipe norm Pipe diameter Pipe wall thickness Collar size Classification PVC-U EN ISO , 20 mm mm CFS-C P 50/1.5 EI 120-U/U EN ISO 15493, DIN 8061/2, EN , EN Pipe End Configuration U/U 50 mm mm CFS-C P 50/1.5 EI 120-U/U PE EN ISO 15494, DIN 8074/5 Pipe End Configuration U/U EN ISO 15494, DIN 8074/5 2 Pipes in 1 Collar EN ISO DIN 8077/ mm mm CFS-C P 50/1.5 EI 90-U/U 50 mm mm CFS-C P 50/1.5 EI 90-U/U mm 1.9 mm CFS-C P 50/1.5 EI 90-U/U mm 2.8 mm CFS-C P 50/1.5 EI 90-U/U 20 mm mm CFS-C P 50/1.5 EI 120-U/U Hilti Firestop Collar CFS-C P Issue 02/2015 page 29
30 Normed pipes Pipe end configuration U/C Pipe material Pipe norm Pipe diameter Pipe wall thickness Collar size Classification EN ISO mm mm CFS-C P 50/1.5 EI 120-U/C DIN 8077/ mm mm CFS-C P 50/ mm 6.8 mm CFS-C P 75/ mm 12.3 mm CFS-C P 90/3 110 mm mm CFS-C P 110/4 Branded pipes Pipe end configuration U/U Pipe designation Pipe manufacturer Pipe diameter Pipe wall thickness Collar size Classification Geberit Silent-db20 (PE-S2) CFS-C P 63/2 75/2.5 EI 180-U/U Wavin TS (PE-HD-100 RC) Master 3 (-CO/-MV/- CO) Polo Kal 3S (/-MV/) Polo Kal NG (-CO/-MV/- CO) CFS-C P 63/2 75/ CFS-C P 110/4 Wavin 50 mm 4.6 mm CFS-C P 50/1.5 EI 90-U/U 63 mm 5.8 mm CFS-C P 63/2 EI 120-U/U 75/ mm 6.8 mm CFS-C P 75/2.5 EI 120-U/U 90 mm 8.2 mm CFS-C P 90/3 EI 120-U/U 110 mm 10.0 mm CFS-C P 110/4 EI 120-U/U Pipelife 32 mm 1.2 mm CFS-C P 50/1.5 EI 90-U/U 40 mm 1.8 mm CFS-C P 50/ mm 1.8 mm CFS-C P 50/ mm 1.8 mm CFS-C P 75/ mm 1.8 mm CFS-C P 110/4 POLOPLAST 75 mm 3.8 mm CFS-C P 75/2.5 EI 90-U/U 90 mm 4.5 mm CFS-C P 90/3 110 mm 4.8 mm CFS-C P 110/4 POLOPLAST 32 mm 1.8 mm CFS-C P 50/1.5 EI 90-U/U 40 mm 1.8 mm CFS-C P 50/ mm 2.0 mm CFS-C P 50/ mm 2.6 mm CFS-C P 75/ mm 3.0 mm CFS-C P 90/3 110 mm 3.6 mm CFS-C P 110/4 Aquatherm blue, 20 mm mm CFS-C P 50/1.5 EI 120-U/U Aquatherm blue Faserverbundrohr, Aquatherm red, Aquatherm green, Aquatherm green Faserverbundrohr, +GF+ PROGEF Standard pipe, +GF+ Dekaprop Industry pipe)aquatherm green Faserverbundrohr, +GF+ PROGEF Standard pipe, +GF+ Dekaprop Industry pipe page 30 Hilti Firestop Collar CFS-C P Issue 02/2015
31 Branded pipes Pipe end configuration U/C Pipe designation Pipe manufacturer Pipe diameter Pipe wall thickness Collar size Classification Aquatherm blue, 40 mm mm CFS-C P 50/1.5 EI 120-U/C Aquatherm blue Faserverbundrohr, 50 mm mm CFS-C P 50/1.5 Aquatherm red, 75 mm 6.8 mm CFS-C P 75/2.5 9 mm Aquatherm green, 90 mm 12.3 mm CFS-C P 90/3 Aquatherm green Faserverbundrohr, 110 mm mm CFS-C P 110/4 +GF+ PROGEF Standard pipe, +GF+ Dekaprop Industry pipe)aquatherm green Faserverbundrohr, +GF+ PROGEF Standard pipe, +GF+ Dekaprop Industry pipe Branded pipes Pipe end configuration U/C Pipe designation Pipe manufacturer Pipe diameter Pipe wall thickness Collar size Classification Polo Kal NG (-CO/ -MV/-CO) POLOPLAST 200 mm 6.8 mm CFS-C P 200/8 EI 180-U/C 250 mm 8.6 mm CFS-C P 250/10 EI 180-U/C Hilti Firestop Collar CFS-C P Issue 02/2015 page 31
32 Rigid Floors 550 kg/m Plastic Pipes with foamed elastomeric insulation Minimum distance between pipe closure devices: 0 mm. Hilti Firestop Collar CFS-C P (A 3 ) installed on each side of the seal and fixed together with M8 threaded rods, washers and nuts. Metal anchors with minimum Ø 8 mm may be used (e.g HUS). Normed pipes Pipe end configuration U/C Pipe material Pipe norm Pipe diameter EN ISO DIN 8077/8078 Branded pipes Pipe end configuration U/C Pipe designation Rautitan flex (PE-Xa) Aquatherm Climatherm Faserverbundrohr Aquatherm Fusiotherm Faserverbundrohr Aquatherm Firestop Pipe manufacturer Pipe wall thickness Insulation thickness Collar size Classification Insulation configuration 90 mm 110 mm 12.3 mm 15.1 mm 22.5 mm 10 mm CFS-C P 160/6 CFS-C P 125/5 EI 120-U/C EI 120-U/C Continued length 250 mm Pipe diameter Pipe wall thickness Insulation thickness Collar size Rehau 40 mm 6.0 mm 20.5 mm CFS-C P 63/2 75/ mm 6.9 mm 21 mm CFS-C P 75/2.5 90/3 Classification EI 120-U/C EI 120-U/C 63 mm 8.6 mm 21.5 mm CFS-C P 110/4 EI 120-U/C Aquatherm 90 mm 12.3 mm 22.5 mm CFS-C P 160/6 EI 120-U/C 110 mm 15.1 mm 10 mm CFS-C P 125/5 EI 120-U/C Aquatherm 90 mm 12.3 mm 22.5 mm CFS-C P 160/6 EI 120-U/C 110 mm 15.1 mm 10 mm CFS-C P 125/5 EI 120-U/C Aquatherm 90 mm 12.3 mm 22.5 mm CFS-C P 160/6 EI 120-U/C 110 mm 15.1 mm 10 mm CFS-C P 125/5 EI 120-U/C Insulation configuration Continued length 250 mm page 32 Hilti Firestop Collar CFS-C P Issue 02/2015
33 Rigid Floors 550 kg/m Composite pipes Minimum distance between pipe closure devices: 0 mm. Hilti Firestop Collar CFS-C P (A 3 ) installed on each side of the seal and fixed together with M8 threaded rods, washers and nuts. Metal anchors with minimum Ø 8 mm may be used (e.g HUS). Branded pipes Pipe end configuration U/C Pipe designation Pipe manufacturer Pipe diameter Pipe wall thickness Collar size Classification Geberit Mepla Geberit 40 mm 3.5 mm CFS-C P 50/1.5 EI 90-U/C (PE-Xb/Al/PE-HD) 50 mm 4.0 mm CFS-C P 50/1.5 EI 120-U/C 63 mm 4.5 mm CFS-C P 63/2 EI 60-U/C 75 mm 4.7 mm CFS-C P 75/2.5 EI 30-U/C Rigid Floors 550 kg/m Composite pipes with foamed elastomeric insulation Minimum distance between pipe closure devices: 0 mm. Hilti Firestop Collar CFS-C P (A 3 ) installed on each side of the seal and fixed together with M8 threaded rods, washers and nuts. Metal anchors with minimum Ø 8 mm may be used (e.g HUS). Branded pipes Pipe end configuration U/C Pipe designation Geberit Mepla (PE-Xb/Al/ PE-HD) KELOX KM 110 (PE-X/Al/ PE-X) Rautitan stabil (PE-Xa/Al/ PE-HD) Pipe manufacturer Pipe diameter Pipe wall thickness Insulation thickness Collar size Geberit 40 mm 3.5 mm 20.5 mm CFS-C P 63/2 75/ mm 4.0 mm 21 mm CFS-C P 63/2 90/3 63 mm 4.5 mm 21.5 mm CFS-C P 75/ /4 75 mm 4.7 mm 22 mm CFS-C P 90/3 125/5 Classification EI 120-U/C EI 120-U/C EI 120-U/C EI 120-U/C Insulation configuration Continued length 250 mm KeKelit 32 mm 3.0 mm 19.5 mm CFS-C P 75/2.5 EI 120-U/C Continued 40 mm 4.0 mm 20.5 mm CFS-C P 75/2.5 EI 120-U/C 50 mm 4.5 mm 21 mm CFS-C P 90/3 EI 120-U/C length 250 mm 63 mm 6.0 mm 21.5 mm CFS-C P 110/4 EI 120-U/C Rehau 40 mm 6.0 mm 20.5 mm CFS-C P 63/2 EI 120-U/C Continued 75/2.5 length 250 mm Hilti Firestop Collar CFS-C P Issue 02/2015 page 33
34 Loose mineral wool products suitable for being used as backfilling material of CFS-S ACR Firestop Acrylic Sealant: Product Heralan LS Isover loose wool SL Isover Universal-Stopfwolle Rockwool RL Paroc Pro Loose Wool Manufacturer Knauf Insulation Saint-Gobain Isover Saint-Gobain Isover Rockwool Paroc OY AB Suitable insulation products; Combustible insulation (closed cell flexible elastomeric foam, e.g. AF/Armaflex). Reaction to fire minimum B-s3, d0 (acc. to EN ) Combustible insulation for sound decoupling ( elastomeric foam, e.g. PE). Reaction to fire minimum E (acc. to EN ) page 34 Hilti Firestop Collar CFS-C P Issue 02/2015
35 Hilti Firestop acrylic sealant CFS-S ACR An acrylic based firestop sealant that provides movement capability in fire rated linear joint seals and penetration seals Applications n Within or between flexible wall constructions n Vertical joints in / between wall constructions n Horizontal joints in a wall abutting a floor, ceiling or roof n Joints in floor construction n Penetration seals (steel and copper pipes) Advantages n Easy to dispense, apply and tool n Strong adhesion to various base materials n Low shrinkage after curing n Excellent airborne sound insulation property n Broad application temperature range Technical data CFS-S ACR Chemical basis Water-based acrylic dispersion Volume shrinkage < 20 % Movement 12.5 % (ISO 11600) Cure Time (at 23 C / 50 % r.h.) ~ 3 mm / 72 h Application temperature range 5 C 40 C Storage and transportation 5 C 25 C temperature - range Shelf life (@73 F / 23 C and 24 month(s) 50 % relative humidity) Reaction to fire class D-s1d0 (EN ) Approvals* ETA 10 / 0292, ETA 10 / 0389 * The European Technical Approval (ETA) can be obtained via your local Hilti contact or Packaging Volume Color Order designation Sales Quantity Item Number Cartridge 310 ml White Firestop acrylic sealant CFS-S ACR 1 pc Cartridge 310 ml White Firestop acrylic sealant CFS-S ACR 1 pc Cartridge 310 ml Grey Firestop acrylic sealant CFS-S ACR 1 pc Foil pack 580 ml White Firestop acrylic sealant CFS-S ACR 20 pc Pail 5 l White Firestop acrylic sealant CFS-S ACR 1 pc Pail 10 l White Firestop acrylic sealant CFS-S ACR 1 pc Hilti Firestop Collar CFS-C P Issue 02/2015 page 35
TPM 075/09. Valid from 1/2/2016 EN 15650: FIRE DAMPER FDMB
Valid from //06 EN 5650:00-09 FIRE DAMPER FDMB These technical specifications state a row of manufactured sizes and models of fire dampers (further only dampers) FDMB. It is valid for production, designing,
More informationTPM 075/09-DK VALID FROM: 15/1/2012 FIRE DAMPER AND FIRE DAMPER-SMOKE FDMB, FDMB-SRD
FIRE DAMPER AND FIRE DAMPER-SMOKE FDMB, FDMB-SRD TPM 075/09-DK VALID FROM: 15/1/2012 I. CONTENT These technical specifications state a row of manufactured sizes and models of fire dampers and fire dampers
More information7/S1 FIRE DAMPER PPZEN. v 2.5 (en)
7/S1 v.5 (en) FIRE DAMPER PPZEN www.klimaoprema.hr 39 TABLE OF CONTENTS Product description... Range... Fire classification according to EN 13501-3... Operating mechanisms and dimensions... Operating manual...
More information7/S6 FIRE DAMPER FDC40. v 2.9 (en)
7/S6 v.9 (en) FIRE DAMPER FDC0 www.klimaoprema.hr 8 TABLE OF CONTENTS FIRE DAMPER FDC0 87 FIRE CLASSIFICATION 87 SELECTION DIAGRAM 88 ORDERING KEY 88 DAMPER MODELS 89 FDC0-M cylindrical fire damper with
More information7/S5 FIRE DAMPER FD40. v 2.9 (en)
7/S v.9 (en) FIRE DAMPER FD0 www.klimaoprema.hr 69 FIRE DAMPER - FDC TABLE OF CONTENTS FIRE DAMPER FD0 7 FIRE CLASSIFICATION 7 SELECTION DIAGRAM 7 ORDERING KEY 7 DAMPER MODELS 7 FD0-M rectangular fire
More informationReport Number BTC 12261F
Report Number BTC 6F A FIRE RESISTANCE TEST ON A 5m HIGH X m WIDE GYPROC SHAFTWALL SYSTEM INCORPORATING A 6mm METAL STUD FRAMEWORK CLAD WITH A DOUBLE LAYER OF 5mm GYPROC FIRELINE, EXPOSED TO THE FIRE FROM
More informationyour and attach spreadsheet of 23 December 2003; and
s Science and Engineering 14 Julius Avenue, Riverside Corporate Park North Ryde NSW 2113 PO Box 310, North Ryde NSW 2113, Australia Telephone: (02) 9490 5444 Facsimile: (02) 9490 5555 ABN 41 687 119 230
More informationReport Number BTC 12024F
Report Number BTC F A FIRE RESISTANCE TEST ON A GYPROC GYPWALL PARTITION INCORPORATING A DOUBLE LAYER OF mm SOUNDBLOC EACH SIDE OF S STUDS, CONDUCTED IN ACCORDANCE WITH BS EN 4:999. Test Date: 9 th June
More informationFire/combustion gas damper EKO-JBL
Fire/combustion Description The fire/combustion is a typeapproved damper intended for fire isolation or as protection against the spread of flame and fire gases in ventilation ducting. The damper is designed
More informationFire/smoke damper EKO-JBG2
Fire/smoke damper EKO-JBG2 Description The EKO-JBG2 fire/smoke damper is a CE-approved damper intended for fire compartmentation or protection against the spread of fire and smoke in ventilation installations.
More informationTable of Contents COOLMANT. 2.0 Table of Contents
CLM 2.0 Table of Contents 2.0 Table of Contents 2.1 System description 2.100 System description (general) 2.105 System description (data) 2.115 COOLMANT range, Ø 125 - Ø 315 / SDR 11/SDR 17 (bars) 2.2
More informationFire/combustion gas damper EKO-JBG
Fire/combustion EKO-JBG Description The EKO-JBG fire/combustion is a typeapproved damper intended for fire isolation or as protection against the spread of flame and fire gases in ventilation ducting.
More informationCombustion gas damper EKO-SRB
Combustion EKO-SRB Description The EKO-SRB combustion is a Class E60 type-approved damper intended to prevent the spread of combustion gases in ventilation ducting that penetrates fire rated compartment
More informationETPR-E-1 FIRE DAMPER» TECHNICAL CATALOGUE
FIRE SAFETY AIR MANAGEMENT FIRE DAMPERS ETPR-E-1 FIRE DAMPER» TECHNICAL CATALOGUE 2 ETPR-E-1 Fire damper Technical catalogue Fire and smoke damper ETPR-E-1 is used as a closing device for preventing the
More informationBracket U Value at 1.5M Centres. 265mm 275mm 295mm 300mm 315mm 335mm 355mm mm.
Bracket Typically @ 1200 ELITE SYSTEMS 402 Top Sheet set out typically for straight sheets * Varies - See Table 39 75 Varies - See Table 32 Bracket Height 100mm 150mm 160mm 180mm 185mm 200mm 220mm Halter
More informationFire/smoke damper EKO-SRBG1
Fire/smoke damper EKO- Description The EKO- fire/smoke damper is a CE-approved damper intended for fire compartmentation or protection against the spread of fire and smoke in ventilation installations.
More informationTable of Contents. EIGERFLEX -Clima. 2.0 Table of Contents
2.0 Table of Contents 2.0 Table of Contents 2.1 System description 2.100 System description (general) 2.105 System description (data) 2.115 -Clima range, DN 20 - DN 125 / SDR 11 (coils) 2.120 -Clima range,
More informationAMCA International. Guide for Commissioning and Periodic Performance Testing of Fire, Smoke and Other Life Safety Related Dampers
AMCA International Guide for Commissioning and Periodic Performance Testing of Fire, Smoke and Other Life Safety Related Dampers AIR MOVEMENT AND CONTROL ASSOCIATION INTERNATIONAL, INC. The International
More informationCombustion gas damper EKO-JB
EKO-JB Description The EKO-JB combustion is a Class E6 type-approved damper intended to prevent the spread of combustion gases in ventilation ducting that penetrates fire rated compartment wall or floor
More informationTable of Contents 2.0 COOLFLEX CLX. 2.0 Table of Contents
Table of Contents CLX 2.0 2.0 Table of Contents 2.1 System description 2.100 System description (general) 2.105 System description (data) 2.115 range, DN 20 - DN 125 / SDR 11 (coils) 2.2 Planning, design
More informationK-FLEX NAME PRODUCT June 2016 K-FLEX. Rail Application. K-FLEX thermal and acoustic insulation solutions for rolling stock market
K-FLEX NAME PRODUCT June 2016 K-FLEX Rail Application K-FLEX thermal and acoustic insulation solutions for rolling stock market K-FLEX RAIL APPLICATION 2 K-FLEX RAIL APPLICATION People s lives are soon
More informationFIRE DAMPERS, FIRE PROTECTION VALVES, SMOKE DAMPERS
FIRE DAMPERS, FIRE PROTECTION VALVES, SMOKE DAMPERS Rectangular fire dampers FIRE DAMPERS PL-12 PL-15 PL-18-1, PL-18-2 Fire dampers are installed in rectangular or circular ventilation ducts, at passages
More informationInstallation Instructions
Installation Instructions Models: SLP Venting System These venting system components have been tested for use with approved HHT Direct Vent appliances. Check with your local building code agency before
More informationWaste water drainage PRODUCT GUIDE. Wavin SiTech+ for low-noise soil & waste drainage
Waste water drainage PRODUCT GUIDE for low-noise soil & waste drainage System description is a mineral reinforced polypropylene (PP) soil and waste system. The system offers increased robustness, low-noise
More informationHeights up to 1000 mm Fire resistance period up to 120 minutes
Maintenance-free FK90 fire dampers - series FK120 - Heights up to 1000 mm Fire resistance period up to 120 minutes Fire classification: EI 30/60/90/120 (ve - ho, i o) S C10ooo Hygiene certificate Environmental
More informationINDOOR CLIMATE SOLUTIONS PRODUCT CATALOG Uponor Radiant Heating/Cooling
INDOOR CLIMATE SOLUTIONS PRODUCT CATALOG 2012 Uponor Radiant Heating/Cooling Uponor Radiant Heating/Cooling > List of content List of content Abbreviations 4 Uponor Renovationsystem Minitec Uponor Minitec
More informationMÜPRO. One-piece pipe clamps. Sprinkler pipe clamps. Refrigerant pipe clamps. Two-piece pipe clamps. Heavy-duty pipe support/din pipe clamps
0. MÜPRO 1. Vibration control 2. Fire protection 3. Pipe clamps 4. Support channels 5. Accessories 6. Anchor points/expansion points 7. Heavy-duty pipe support 8. MPT-Support system 9. Ventilation 10.
More informationPIPE LOG BOOK. Project no:... Project:... Construction section:... On behalf of:... Commissioned by:... Order no:... Date:... Construction period:...
FW-FERNWÄRME-TECHNIK GmbH Grafftring 2-6 D-29227 Celle Tel.: + 49 5141 888 88-0 Fax: + 49 5141 888 88-22 E-Mail: info@fw-gmbh.de Internet: www.fw-gmbh.de PIPE LOG BOOK... Project:... Construction section:...
More informationHeradesign fine Product Data & Certificates
Product ata & Certificates Product ata 1-layer magnesite bonded wood wool acoustic panel (fibre width 2 mm). Characteristic surface structure, building biology recommended. Colour variations The natural,
More informationBevent Rasch BSK6. - Fire /04/2017
Bevent Rasch - Fire - BSK6 11/04/2017 Fire resistance class EI60 / EI60S Sizes from 200 x 200 mm to 800 x 800 mm Prefitted safety actuator 24V or 230V Low weight Easy installation CE-marked building product
More informationTable of contents. Chapter 1: Fusiotherm. Chapter 4: climasystem Produktgruppe 20. Chapter 5: aquatherm. Chapter 2: aquatherm SHT.
Table of contents Chapter 1: Fusiotherm 01 Fusiotherm -pipe 04 climatherm-pipe & aquatherm-lilac 07 Accessories 09 Fittings 15 Weld-in saddle 19 Threaded connections and accessories 22 Transition pieces
More informationPSI CASING END SEALS FOR CASING PIPE CLOSURE FOR PROTECTION AGAINST MOISTURE AND DIRT ALSO FOR RETROFITTING INDIVIDUAL CUSTOMIZED SOLUTIONS
PSI CASING END SEALS FOR CASING PIPE CLOSURE FOR PROTECTION AGAINST MOISTURE AND DIRT ALSO FOR RETROFITTING INDIVIDUAL CUSTOMIZED SOLUTIONS WWW.PSI-PRODUCTS.COM 111 PSI Casing End Seals Pipes carrying
More information4 pole insulated conductor rails UNILIFT-ULA 35A, 50A, 80A, 100A
2 Table of contents General information... 4 Elements of the conductor rail supply line... 4 Innovative connection method... 5 Technical properties... 6 Construction of the line section... 6 Line section...
More informationToppTube PA11 (Polyamide) page 4. ToppTube PA12 (Polyamide) page 5. ToppTube PA12HIPHL (Polyamide) page 6. ToppTube PUR 98A (Polyurethane) page 7
ToppTube PA11 (Polyamide) page 4 ToppTube PA12 (Polyamide) page 5 ToppTube PA12HIPHL (Polyamide) page 6 ToppTube PUR 98A (Polyurethane) page 7 ToppTube PE-LD (Polyethylene) page 8 ToppTube PE-LLD (Polyethylene)
More informationPKI-C Cartridge Fire Dampers
Fire Safety Products / 7 PKI-C Cartridge Fire Dampers Fire resistance class EI60S, EI90S and EI0S 96 - CPD - 000 Ordering codes Fire resistance class PKI-C-EI - 60S, 90S and 0S Codes section. The thermal
More informationFireFree ScandiBoard 850 Passive Fire Protection of Steel Constructions R30 - R180
FireFree ScandiBoard 850 Passive Fire Protection of Steel Constructions R30 - R180 www.scandisupply.dk 2531-CPR-CXO10102 Scandi Supply a/s Energivej 2 5492 Vissenbjerg Tlf.: 45 7624 4800 E-mail: info@scandisupply.dk
More informationFROTH-PAK INDEX. General. FROTH-PAK mini kit
FROTH-PAK INDEX GENERAL FROTH-PAK mini kit FROTH-PAK 180 FROTH-PAK 600 FROTH-PAK 1900 GUN HOSE ASSEMBLY [GHA] NOZZLES General FROTH-PAK is a portable two component polyurethane spray foam kit which enables
More informationFire protection accessories for the glazing industry
Fire protection accessories for the glazing industry Fire protection for europe Made in germany Content General Definition The Rolf Kuhn GmbH Fire classification rating 4 7 4 4 5 5 6 7 Product overview
More informationCordless Systems. Cordless Systems. Hilti. Outperform. Outlast. Cordless. Systems
Hilti. Outperform. Outlast. 49 Introduction Introduction Page 51-52 Drill drivers compact drill driver SFC 22-A Page 53 hammer drill driver SFH 22-A Page 54 Accessories for drill drivers Page 57 Impact
More informationCordless Systems. Cordless Systems. Hilti. Outperform. Outlast.
Cordless Systems Hilti. Outperform. Outlast. 52 Introduction Introduction Page 54-55 Drill drivers Cordless compact drill driver SFC 22-A Page 56 Cordless hammer drill driver SFH 22-A Page 57 Accessories
More informationSteel Spline Joint Bulkheads Junction: B-0 Class FIPRO MS 16 mm steel spline No x3 mm Construction: free-standing Sound reduction: 29 db (estima
Bulkheads 1.1 Steel Spline Joint 1.2 OMEGA-Profile Joints 1.3 Details of Corners, T-Corners, Top and Bottom Connections 2.1 Double Shell Partitions 2.2 Details of Double Shell Corner, T-Corner, Top and
More informationSmoke damper EKO-SRB1
Smoke damper EKO-SRB1 Description The EKO-SRB1 smoke damper is a CE-approved damper in fire class E60 intended for fire compartmentation or protection against the spread of fire and smoke in ventilation
More informationMULTICOMPARTMENT SMOKE CONTROL DAMPERS DKISMA
MULTICOMPARTMENT SMOKE CONTROL DAMPERS DKISMA 96 - CPR - 0 ORIGINAL INSTALLATION, MAINTENANCE AND OPERATION MANUAL EVERY SMOKE DAMPER NEEDS TO BE INSTALLED IN ACCORDANCE WITH THIS MANUAL! / PP-5_0604 DKISMA
More informationBevent Rasch BSK Fire /04/2017
Bevent Rasch - Fire - BSK120 10/04/2017 Rectangular Fire resistance class /S Sizes from 200 x 200 mm to 1200 x 1000 mm Prefitted safety actuator 24V or 230V Available in MagiCAD CE-marked building product
More informationWGA Long throw nozzle grille
Technical documentation WGA Long throw nozzle grille Contents Function and use... 2 Models... 2 Processing... 3 Accessories... 3 Models and dimensions... 4 Quick selection... 12 Installation situation...
More informationRound or Square Type Low-Profile Housing with Toroidal Transformer for Flangeless Trims E3_LF-HDSM-WR_ 1.0
Installation Instructions for 90EHMH-LNIC Round or Square Type Low-Profile Housing with Toroidal Transformer for Flangeless Trims E_LF-HDSM-WR_.0 HALOGEN MR - ROUND/SQUARE FLANGELESS GENERAL PRODUCT INFORMATION:
More informationCU-LT. Optimised rectangular fire damper up to C3-EN-J-06/2018
CU-LT Optimised rectangular fire damper up to 120 en 0749 Rf-Technologies nv Lange Ambachtstraat 40 9860 Oosterzele Belgium Tel +32 9 362 31 71 Fax +32 9 362 33 07 info@rft.be www.rft.be C3-EN-J-06/2018
More informationPRICE/ LISTE PRICELIST. My favorite: Curaflam Konfix pro. The sealing of flexible e pipes? No problem by using the Curaflex Nova Senso!
My favorite: Curaflam Konfix pro. (see page 42) NEW The sealing of flexible e pipes? No problem by using the Curaflex Nova Senso! (see page 14) PRICE/ LISTE PRICELIST valid gültig from ab 01.01.2014 014
More informationETPS-EI Fire Damper EI 60 S / EI 120 S Instructions for Installation, Operation and Maintenance
ETPS-EI Fire Damper EI 60 S / EI 120 S Instructions for Installation, Operation and Maintenance 07/2013 Fläkt Woods FIFLO EN 2013.07 2 ZU CLOSED AUF OPEN Fire damper ETPS-EI Contents Operation and Maintenance
More informationCatalogue of Accessories
Catalogue of Accessories Room Controller with CO 2 Sensor 3 CO 2 Sensor 4 F7 Filter 400 x 220 x 48 mm 5 Carbon Filter 6 Design valve circle 7 (for pipes Ø 100, 125 and 160) Design valve square 8 (for pipes
More informationSECTION METAL LOCKERS
SECTION 10 5113 METAL LOCKERS This section includes editing notes to assist the user in editing the section to suit project requirements. These notes are included as hidden text, and can be revealed or
More informationBX-1H. Fire Valve FIRE SAFETY FUNCTION APPLICATION DESCRIPTION. in libraries of
FIRE SAFETY Fire Valve in libraries of EI 60 (v e -o i) S EN 131-3+A1:10 EN 156:10 Certificate of Conformity 1488-CPD-02 82/W FUNCTION The fire valves are designed for buildings where in the event of a
More informationPSI Compakt-Seals. Pipeline Accessories. Compakt-Standard Compakt-Special Compakt-Varia. General Information. Selection Guide. Order Submittal Sheet
2 General Information Selection Guide Order Submittal Sheet Installation Instruction PSI Compakt-Seals Compakt-Standard Compakt-Special Compakt-Varia Pipeline Accessories 21 General Information The Sealing
More informationInstallation Trunking
P83865 Description INKA aluminium installation system is intended for mounting directly onto the wall or on brackets, on fl oor or desk level; some sizes also for fl ush mounting. The range includes with
More informationVALSIR SUPPLY SYSTEMS MIXAL
TECHNICAL DATA SHEET VALSIR SUPPLY SYSTEMS MIXAL The product Mixal is an extremely flexible multilayer pipe and is therefore ideal for the creation of floor, wall and ceiling radiant heating and cooling
More informationGmbH Lufttechnik Dresden USER INFORMATION ROOF FANS SERIES VRV. vertical outlet. Issue 07/02
GmbH Lufttechnik Dresden USER INFORMATION ROOF FANS SERIES VRV vertical outlet Issue 07/02 Roof fans made of plastic materials Series VRV with vertical outlet Usable in ventilation engineering of all branches
More informationaccqpulse Velocity Profiler Sensor Installation Guide
accqpulse Velocity Profiler Sensor Installation Guide Instruction Sheet #69-7403-012 Released May 2016 Overview This instruction guide is for the installation of the accqpulse shallow water and deep water
More informationTECHNICAL-OPERATIONAL DOCUMENTATION RK370M FIRE SAFETY VALVES
TECHNICAL-OPERATIONAL DOCUMENTATION RK370M FIRE SAFETY VALVES MANUFACTURER: FRAPOL Spółka z o.o. 30-832 Kraków, ul. Mierzeja Wiślana 8 Phone: (012) 653-27-66, 653-27-67, 653-26-92 fax (012) 653-27-89 MARCH
More informationU Thermo datasheets May Manufactured in Springs according to ISO 9001 : 2008 South Africa
ULTIMATE Mineral Wool U Thermo datasheets May 2010 Manufactured in Springs according to ISO 9001 : 2008 South Africa 1 ULTIMATE : A new generation mineral wool Developed by ISOVER for high temperature
More informationConnecting ignition tool
B8.1 Pre-treatment B8.1.1 Pyrotechnics Connecting ignition tool Driver's side Ignition cable A directly to the 2-pole plug for the contact unit (below the steering column). Place the ignition device in
More informationSound insulated doors
Sound insulated doors Standard program overview Sound-insulated steel doors Sound-insulated single and double-leaf steel doors Dimensions Leaf thickness, sheet thickness * Tested as a sound insulated door
More informationCATALOGUE SEWAGE MANHOLES
CATALOGUE SC SEWAGE MANHOLES Table of contents TABLE OF CONTENTS Introduction 4 Inspection chamber, type 315 7 Inspection chamber, type 400 10 Inspection chamber, type 425 14 Assembly instruction 19 Catch
More informationFRP Ball Valves INSTALLATION & MAINTENANCE MANUAL
FRP Ball Valves INSTALLATION & MAINTENANCE MANUAL FRP BALL VALVES TABLE OF CONTENTS MAINTENANCE AND INSTALLATION INSTRUCTIONS 1. 2. 2.1 2.2 2.3 2.4 GENERAL...Page 1 HANDLING...1 Receiving and Storing...1
More informationPlaster In Grilles 1/1.5/B/1. AHP Plaster-in Linear Bar Grille ADMP Plaster-in Linear Diffuser ALSP Plaster-in Linear Slot Diffuser
1/1.5/B/1 Plaster In Grilles AHP Plaster-in Linear Bar Grille ADMP Plaster-in Linear Diffuser ALSP Plaster-in Linear Slot Diffuser TROX UK Ltd Caxton Way Thetford Norfolk IP24 3SQ Telephone +44 (0) 1842
More informationChannel without outlet box for concrete, in-situ or tiled floor
Type 670. Product code definition 670 X X XXX-XX X X Channel without outlet box for concrete, in-situ or tiled floor The channel is made in the following standard widths: 147, 197, 297 and 397 mm internal
More informationSEMI RIGID THE PROFESSIONALS CHOICE
SEMI RIGID THE PROFESSIONALS CHOICE for efficient, high performance MVHR ductwork installations. SAP APPENDIX Q LISTED brookvent.co.uk FITTING OUTLINE THE PROFESSIONALS CHOICE for efficient, high performance
More informationpiece of straight pipe with a minimum length of 25 cm. (see figure 13) For this purpose the 45 long bend is included in the Wavin AS program.
Recommendations 3.9 Sound insulation recommendations National / Local building regulations should be observed where applicable. In order to achieve optimal sound insulation it is highly recommended to
More informationContents Technical characteristics Han A Technical characteristics Han 3 A with HARAX Termination
Contents Page... 01.02 3 with HRX Termination... 01.04 3, 3 with HRX Termination... 01.05 4... 01.06 10... 01.07 16... 01.08 32... 01.09 01 Features Metal and plastic version available 3 hoods/housings
More information10. Universal Clips. 254 Product overview 2013 We reserve the right to change designs and technical specifications of our products.
10. Universal lips Whether you need ceiling, wall or floor mounted clips, Flamco has the solution. We offer a wide range of universal mounting clips with a variety of closures, connections and finishes.
More informationCR120. Optimised circular fire damper up to 120' C11-EN-L 06/2018
CR120 Optimised circular fire damper up to 120' en 0749 Rf-Technologies nv Lange Ambachtstraat 40 9860 Oosterzele Belgium Tel +32 9 362 31 71 Fax +32 9 362 33 07 info@rft.be www.rft.be C11-EN-L 06/2018
More informationCircular Silencer. Rigid and flexible construction Type CA CB CF CS. TROX GmbH Telephone +49/28 45/ Telefax +49/28 45/
6/5/EN/6 Circular Silencer Rigid and flexible construction Type CA CB CF CS TROX GmbH Telephone +49/28 45/2 02-0 Telefax +49/28 45/2 02-2 65 Heinrich-Trox-Platz e-mail trox@trox.de D-47504 Neukirchen-Vluyn
More informationAluminium Productive Fence System 40 PRODUCT CATALOGUE
11 2017 (e) Aluminium Productive Fence System 40 PRODUCT CATALOGUE solutions by F.EE Elektrotech Engineering Automation Robotik Informatik + Systeme Energietechnik F.EE GmbH In der Seugn 10 and 20 D-92431
More informationINSTALLATION & OWNER S MANUAL
Rev. E p. of 3 INSTALLATION & OWNER S MANUAL V446 Front Cab Kit and V446 Rear Cab Kit for RTV 40 INSTALLATION & OWNER S MANUAL The contents of this envelope are the property of the owner. Be sure to leave
More informationTechnical and Dimensional Data. Double Wall One Inch Air Space AL 29-4C Stainless Steel Special Gas Vent
$5 Technical and Dimensional Data Saf-T Vent CI Plus Double Wall One Inch Air Space AL 29-4C Stainless Steel Special Gas Vent For Venting Commercial & Industrial Appliances Condensing Appliances Category
More informationFire damper BKA-EN. with general technical approval Z tested according to DIN EN
Fire damper BKA-EN with general technical approval Z-41.3-667 tested according to DIN EN 1366-2 Ferdinand Schad KG Steigstraße 25-27 D-78600 Kolbingen Phone +49 (0) 74 63-980 - 0 Fax +49 (0) 74 63-980
More informationUNDERSTANDING FIREBLOCK
UNDERSTANDING FIREBLOCK INDUSTRY TRENDS Polyurethane foam has been used for decades in many residential construction sealing applications INDUSTRY TRENDS In recent years, Fireblocking has been prescribed
More informationShelving systems Stable construction, simple assembly
Shelving systems Stable construction, simple assembly Shelving systems in classical unit widths of 1000 or 1300 are suitable for every application, for every inventory type and for every kind of storage
More informationTest certificate General construction inspection test certificate Nr. 3666/4421 -a - Fe/Wi 1. Issue ( )
Test certificate Nr. 3666/4421-a -Fe/Wi- page 1 TESTING LABORATORY FOR CIVIL ENGINEERING MATERIALS INSTITUTE FOR REASEARCH OF CIVIL ENGINEERING MATERIALS, STONE- AND CONCRETE CONSTRUCTION AND FIRE INTEGRITY
More informationContents Technical characteristics Han A Technical characteristics Han 3 A with HARAX Termination
Contents Page... 01.02 3 with HRX Termination... 01.04 3, 3 with HRX Termination... 01.05 4... 01.06 10... 01.07 16... 01.08 32... 01.09 01 Features Metal and plastic version available 3 hoods/housings
More informationSecurity steel door dw 62-1 Teckentrup
Teckentrup RC 2 Text example Compile and tender according to requirements. Please refer to technical data below for respective details. Updated 1 st June 2015 Position No. of pieces Item Security steel
More informationNEC 2011 Code Changes
NEC 2011 Code Changes Articles 280.21-300.50 CHANGES FROM 2008 TO 2011 CODE ARE IN RED Chapter 2 - Wiring and Protection ARTICLE 280 Surge Arresters, Over 1kV III. Connecting Surge Arresters 280.21 Connection
More informationAccessories and extra equipment fit for SCHRAMM-switchgear cabinets and SCHRAMM-protection boxes
Accessories Accessories and extra equipment fit for SCHRAMM-switchgear cabinets and SCHRAMM-protection boxes describtion assignment page Closures Locks, closures, handles... Switchgear cabinets... 9.01
More informationM A D E L. FOK-EIS-180 Fire dampers CE
M A D E L EN 60: FOK-EIS-80 Fire dampers CE The fire dampers FOK-EIS-80 work as a separator between two sectors of fire and ensure the same fire resistance that the structural elements of compartmentalisation,
More informationINDUSTRIAL HOSES 1
INDUSTRIAL HOSES 1 WATER HOSES LONG-SU 6 BAR Gardening and general water discharge services. Temperature range: -25 C / +70 C. Tube: NBR/SBR / Natural and synthetic rubber. Cover: SBR, weather and abrasion
More informationCR120. Optimized circular fire damper up to 120' C11-I 07/2015
Organisme Certificateur AFNOR Certification - www.marque-nf.com CR120 Optimized circular fire damper up to 120' en Clapets coupe-feu et Volets de désenfumage D.A.S. Rf-Technologies nv Lange Ambachtstraat
More informationDIVISION: METALS SECTION: COLD-FORMED METAL FRAMING REPORT HOLDER: WARE INDUSTRIES D/B/A MARINO\WARE
0 Most Widely Accepted and Trusted ICC-ES Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-3578 Reissued 0/206 This report is subject to renewal 0/208. DIVISION: 05 00 00 METALS SECTION:
More informationType 567. Wafer Style Butterfly Valve
Wafer Style Butterfly Valve Type 5 General Size: 2 12 Outer Body: Glass-filled PP Material: PVC, CPVC, PROGEF Standard PP, ABS, SYGEF Standard PVDF Seals: EPDM, FPM, PTFE/FPM Stem: 31 stainless steel Operation:
More informationFire damper ETPR. Specifications. Product code example Fire damper ETPR
Fire damper ETPR ETPR fire damper is CE marked based on product standard EN 15650:2010 and tested according to the test standard EN 1366-2. ETPR meets the requirements of fire class EI 60 S / EI 90 S.
More informationVentilation system Design and installation guide
Ventilation system Design and installation guide Contents Uponor ventilation systems...4 Technical specifications for the ducting material...4 Technical characteristics of the ducting...4 Technical specifications
More informationSpaceloft Insulation TECHNICAL GUIDE
(Click below to jump to sections.) Contents Introduction 3 Non-Combustibility and Fire Performance 4 EN 13501-1 Reaction to Fire Classification (Bodycote, Warrington Fire) ASTM E 84 Surface Burning Characteristics
More informationLK Shunt Cabinet VS2, Shunt Cabinet VS2 Prefab
LK Shunt Cabinet VS2, Shunt Cabinet VS2 Prefab Design LK Shunt Cabinet VS2 The LK Shunt Cabinet VS2 is designed to be used when you wish to hide the LK Manifold RF and LK Manifold Shunt VS2. The cabinet
More informationPRODUCT INFORMATION
PRODUCT INFORMATION A NEW CONCEPT PLASTER PANELS ALL INORGANIC COMPONENTS (1200 mm) 47 1/4 PATENTED SHIPLAP EDGE SYSTEM 23 5/8 (600 mm) OFFSET PLASTER PLASTER FILLER PLASTER PATENTED SYSTEM HANDLING &
More informationINSTALLATION & OWNER S MANUAL
Rev. B, p. 1 of 25 INSTALLATION & OWNER S MANUAL POLARIS RANGER RCS (for models XP or HD) (for model years 2009-) cab without doors kit (p/n 1POLRCWD) cab with doors kit (p/n 1POLRC) doors only kit (p/n
More informationFire Dampers. Types FKA FRL FRK 4/1/EN/1
Fire Dampers Types FKA FRL FRK /1/EN/1 Contents Description Description... Construction... Standard Sizes Installation Details... Functional Description Product Range... Accessories... Circuit Diagrams...
More information(L=500) L=300 (L=500) PL /E... electric actuator version. Table standard dimensions, L = 300 mm.
Fire damper pl-30 General characteristics Application Fire dampers prevent fire and smoke from spreading through ventilation ducts in buildings. The dampers are intended for use inside buildings and are
More informationraugeo ground-source systems innovative heating & cooling solutions parts list /11 EN ENERGY EFFICIENCY Building Solutions Automotive Industry
raugeo ground-source systems innovative heating & cooling solutions parts list 827300/11 EN ENERGY EFFICIENCY www.rehau.co.uk/groundsource Valid from May 2013 Subject to Technical Alterations Building
More informationSCION xb 2004 SATELLITE RADIO TUNER Section I Installation Preparation
Section I Installation Preparation Part Number: PT546 52040 Section I Installation Preparation Kit Contents Item # Quantity Reqd. Description 1 1 Satellite Tuner 2 1 Ground Cable 3 1 Tuner Cable 4 2 Tuner
More informationMANUAL. Firescreen Temperature T1, T2, T3, T4
Product Type: Subtitle Firescreen Temperature T1, T2, T3, T4 Installation instruction Firescreen Temperature, on the supporting construction, tubular motor, gravity fail safe, insulated headbox Version:
More informationPSI Anti-Corrosion Tape
General information Technical specifications Requirement evaluation Application instructions Certificates PSI Anti-Corrosion Tape 8 Pipeline Accessories 85 The Systems PSI anti-corrosion tapes have been
More information