Fire/combustion gas damper EKO-JBL

Size: px
Start display at page:

Download "Fire/combustion gas damper EKO-JBL"

Transcription

1 Fire/combustion Description The fire/combustion is a typeapproved damper intended for fire isolation or as protection against the spread of flame and fire gases in ventilation ducting. The damper is designed in accordance with the requirements of the Swedish standard VVS AMA 98, section QJC.2. The damper is for installation in fire isolation building cells constructed in accordance with fire technical classification EI60, consisting of approved partition walling or concrete constructions and in ventilation ducting prepared in accordance with the installation instructions. If the fire/combustion is used for direct air transfer and supervised by one of our control and monitoring systems, no duct termination is necessary. However, a wire mesh grille must always be fitted when the damper is not connected to the ducting. Type approval The fire/combustion has been tested by Sveriges Provnings- och Forskningsinstitut (the Swedish National Testing and Research Institute) and type-approved by SITAC (the leading Swedish construction approval agency), certificate no. 0098/02. The above-mentioned fire technical classifications apply on condition that the fire/combustion is connected to one of our control and monitoring systems, or equivalent equipment, to provide automatic functional testing at least once every 48 hours. This type of installation means that the ventilation duct can pass through fire cell separation construction areas without the need for any type of fire insulation or other additional measures to prevent the spread of flame and fire gases. In the case of smaller dampers, up to a maximum of 200 x 200 mm, installed in individual archive rooms or similar premises, the automatic functional checking system may be replaced by a manual system, with regular checks performed at least four times per year. Such checks must be logged in a register. In other respects the appropriate conditions must be maintained in accordance with the type approval. Design The fire/combustion is available with either guide or flange connections. The basic model is equipped with a factory-mounted electric damper motor with spring return and end position contacts. The damper can also be fitted with a thermal sensor. Since the damper has two inspection hatches it can be reversed and there is no need to select a particular motor side. However, on installation the damper blades must always be horizontal. The is a rectangular fire/combustion fitted with a housing and damper blades of non-combustible material and sides of hotdip galvanised sheet steel (2275) to environmental classi-fication M2. Alternatively the damper can be manufactured of stainless steel (2333) or acid-resistant steel (2343) for increased environmental requirements. Air tightness classification The fire/combustion is equipped with a sealing gasket that seals the air side to the equivalent of class 4 in accordance with the Swedish standard for air tightness, VVS AMA 98. There is also a sealing strip around the damper frame, that expands and seals if the damper is exposed to heat. Working pressure The working pressure of the damper is max Pa, pressure class B, differential pressure with closed blades.

2 Sizes The fire/combustion is manufactured in a large number of standard dimensions, from 200x200 to 650x650 mm. Damper motors The basic model is supplied with a 24V or 230V electric safety motor. A 24V motor is always used in conjunction with the EKO-KE control and monitoring system and a 230V motor for EKO-MKE and EKO-SKE. Alternatively the fire/combustion can be supplied with a pneumatic low or high pressure damper motor. Note that the fire/combustion must always be used with the supplied motor for type approval to be valid. Maintenance We recommend preventive maintenance of the damper as required by the plant in which it is installed. The damper blades and interior surfaces are cleaned with a brush, vacuum cleaner or by wiping down. NOTE! Water or other liquids must not be used. Other movement requirements apply, in accordance with the type approval. Accessories EKO-ANS Connection adapter for spiral ducting. EKO-FLS Extension adapter for walls or beams thicker than 220 mm or higher than 350 mm in combination with connection adapter EKO-ANS or wire mesh grilles EKO-N or EKO-NR. EKO-GIS Erection collar for damper mounting in plasterboard walls. Material for making good not included. EKO-KPB Junction box. EKO-RKB Control unit. EKO-RE Smoke detector (duct). EKO-RET Smoke detector (ceiling). EKO-KER Material for making good walls. EKO-KE Control and monitoring system. EKO-MKE Control and monitoring system. EKO-SKE Control and monitoring system. EKO-MFL Counter flange. EKO-INR Wall frame. EKO-N. EKO-NR. How to order Designation: Fire/combustion -A-B-C-D A B C D SIZE MATERIAL CONNECTION MOTOR (Width x Height) 1 = Galvanised 5 = Flange 8 = 24V electric motor 2 = Aluzinc (M3) 6 = Guide 9 = 230V electric motor 3 = Stainless steel SS = Spiro 10 = Pneumatic motor 4 = Stainless steel SS 2343 Example: 1 Fire/combustion -400x

3 Technical data Dimensions Max 100 Deln.n = 200 C 20 D 380 D B 35 Max 235 Max 165 Ställdon C Deln.n = 200 C Inspektionslucka Gejdanslutning Ø A Gäller normalutförande Standard sizes A or B C Number of D intervals n Weights of standard sizes B A Weight in kg, including actuator

4 Air tightness classification 1000 VVS-AMA98 Classification class Differential pressure, Pa Damper leakage factor l/(s. m 2 ) Pressure drop and sound power levels 100 Static pressure drop Pa L WA (db) Air velocity m/s Correction of sound power level L WACORR for different sizes. L WACORR = L WA + K 1 Damper area 0,04 0,09 0,18 0,3 0,6 1,2 K Correction of sound power level L WAOC in octave bands. L WAOC =L WACORR + K OC Octave band Opening angle K 2K 4K 8K K OK Sound power level measured in accordance with ISO 3741 and ISO 5135 by Sveriges Provnings- och Forskningsinstitut (the Swedish National Testing and Research Institute).

5 Mounting accessories Connections Anslutningsstos EKO-ANS Förlängningsstos EKO-FLS ØD ØD ØD ØD mm No extension adapter required ØD mm 2 extension adapters required Mounting plate EKO-MOP Plasterboard wall collar EKO-GIS Installation in internal wall Installation in chimney breast Duct dimension max 70 Included in the delivery.

6 Mounting instructions Construction - wall - plasterboard or equivalent to fire technical classification EI60. type approval NO. 0098/02. Alternative 1, new construction Alternative 2, existing construction Damper mounted using mounting plate EKO-MOP flush with wall Damper mounted using mounting plate EKO-MOP flush with wall Minimum 15 mm slot Minimum 15 mm slot EKO-N, EKO-NR EKO-N, EKO-NR Sealed with EKO-KER or type-approved fire sealant Mounting plate Screws Sealed with EKO-KER or type-approved fire sealant 110 Important! These dampers must always be installed with the pivot shaft horizontal. Alternatives 1 and 2 1. Remove the horizontal wall studs, and where necessary also vertical studs, to obtain a suitable opening in the wall. 2. Attach the mounting plate EKO-MOP to the damper with screws so that the damper fits into the hole in the wall when offered up. 3. Centralise the damper in the opening and screw it to the wall studs with the mounting plate. 4. Make good the gap between the damper and the wall with fire sealant EKO-KER or other type-approved fire sealant. 5. Install the plasterboard or equivalent. 6. The securing materials for the damper and ducting shall meet the requirements for through aperture fire classification. To meet EI60, fire cell separation wall construction is required, for example using Gyproc. In cases where Fire/combustion gas dampers are installed as end plates or as air transmission ducts, i.e. not connected to a ducting system, wire mesh netting shall be fitted. For dampers measuring more than 350 mm in height, extension adapters are required to ensure free damper blade movement.

7 Mounting instructions Load-bearing construction - wall or joist - concrete, brick or air-entrained concrete to fire technical classification EI60. type approval NO. 0098/02. Alternative 1 Alternative 2 Damper mounted using mounting plate EKO-MOP flush with wall Wall frame and screwed fixing or expansion bolt in concrete surround Minimum 15 mm slot EKO-N, EKO-NR BxH EKO-N, EKO-NR If the wall thickness exceeds 220 mm the damper must be equipped with an FLS extension adapter Insulation in accordance with the same fire technical classification as the rest of the construction material Mounting plate EKO-MOP Sealed with EKO-KER or type-approved fire sealant Important! These dampers must always be installed with the pivot shaft horizontal. Alternative 1 1. The aperture measurement for the damper is the duct size mm. 2. Centralise the damper in the opening. Alternatively use a mounting plate EKO-MOP to secure the damper. 3. Make good the gap (15 mm) between the damper and the wall with fire sealant EKO-KER or other type-approved fire sealant. 4. The securing materials for the damper and ducting shall meet the requirements for through aperture fire classification. Alternative 2 1. An EKO-INR wall frame is cemented into place in the cement surround. 2. The damper is screwed into the wall frame. Alternatively expansion bolts can be screwed through the damper flange into the surround. 3. Insulate the damper frame from the aperture to the damper blade with material with the same fire technical classification as the rest of the construction material. 4. The securing materials for the damper and ducting shall meet the requirements for through aperture fire classification. In cases where Fire/combustion s are installed as end plates or as air transmission ducts, i.e. not connected to a ducting system, wire mesh netting shall be fitted. For dampers measuring more than 350 mm in height, extension adapters are required to ensure free damper blade movement.

8 Mounting instructions Constructions- wall - plasterboard or equivalent to fire technical classification EI60. type approval NO. 0098/02. Alternative1, studded wall Support details Alternative 2, chimney wall Support details Screw Minimum 15 mm slot EKO-N, EKO-NR Duct Wall collar EKO-GIS Sealed with EKO-KER or type-approved fire sealant Wall collar EKO-GIS Sealed with EKO-KER or type-approved fire sealant Self-tapping screw or steel pop rivet Self-tapping screw or steel pop rivet Important! These dampers must always be installed with the pivot shaft horizontal Alternative 1 and 2 1. Make an aperture in the construction, equivalent to the nominal size of the damper mm. 2. Install a plasterboard wall collar EKO-GIS, consisting of two insertion frames in the opening so that they can be slid together and pressed tight against the existing material. Joint the frames together with self-tapping screws or steel pop rivets. 3. Position the damper horizontal and centre it between the plates so that the damper blade is in the centre of the wall. 4. Make good the gap between the damper and the wall with fire sealant EKO-KER or other type-approved fire sealant. 5. The securing materials for the damper and ducting shall meet the requirements for through aperture fire classification. To meet EI60, fire cell separation wall construction is required, for example using Gyproc. In cases where Fire/combustion gas dampers are installed as end plates or as air transmission ducts, i.e. not connected to a ducting system, wire mesh netting shall be fitted. For dampers measuring more than 350 mm in height, extension adapters are required to ensure free damper blade movement.

9 Mounting and insulation instructions Load-bearing construction - wall or joist - concrete, brick or air-entrained concrete to fire technical classification EI60. Type approval NO. 0098/02. EKO-N, EKO-NR Duct Insulation in accordance with the same fire technical classification as the rest of the construction material Important! These dampers must always be installed with the pivot shaft horizontal. 1. The damper is installed in the ventilation duct. Entry into the ducting is performed in accordance with the applicable regulations. 2. The duct and damper are insulated, along with the damper blade, in accordance with the same fire technical classification as the rest of the construction material. In cases where Fire/combustion gas dampers are installed as end plates or as air transmission ducts, i.e. not connected to a ducting system, wire mesh netting shall be fitted. For dampers measuring more than 350 mm in height, extension adapters are required to ensure free damper blade movement. 3. The securing materials for the damper and ducting shall meet the requirements for through aperture fire classification.

Fire/combustion gas damper EKO-JBG

Fire/combustion gas damper EKO-JBG Fire/combustion EKO-JBG Description The EKO-JBG fire/combustion is a typeapproved damper intended for fire isolation or as protection against the spread of flame and fire gases in ventilation ducting.

More information

Combustion gas damper EKO-SRB

Combustion gas damper EKO-SRB Combustion EKO-SRB Description The EKO-SRB combustion is a Class E60 type-approved damper intended to prevent the spread of combustion gases in ventilation ducting that penetrates fire rated compartment

More information

Combustion gas damper EKO-JB

Combustion gas damper EKO-JB EKO-JB Description The EKO-JB combustion is a Class E6 type-approved damper intended to prevent the spread of combustion gases in ventilation ducting that penetrates fire rated compartment wall or floor

More information

Fire/smoke damper EKO-JBG2

Fire/smoke damper EKO-JBG2 Fire/smoke damper EKO-JBG2 Description The EKO-JBG2 fire/smoke damper is a CE-approved damper intended for fire compartmentation or protection against the spread of fire and smoke in ventilation installations.

More information

Fire/smoke damper EKO-SRBG1

Fire/smoke damper EKO-SRBG1 Fire/smoke damper EKO- Description The EKO- fire/smoke damper is a CE-approved damper intended for fire compartmentation or protection against the spread of fire and smoke in ventilation installations.

More information

Smoke damper EKO-SRB1

Smoke damper EKO-SRB1 Smoke damper EKO-SRB1 Description The EKO-SRB1 smoke damper is a CE-approved damper in fire class E60 intended for fire compartmentation or protection against the spread of fire and smoke in ventilation

More information

Bevent Rasch BSK6. - Fire /04/2017

Bevent Rasch BSK6. - Fire /04/2017 Bevent Rasch - Fire - BSK6 11/04/2017 Fire resistance class EI60 / EI60S Sizes from 200 x 200 mm to 800 x 800 mm Prefitted safety actuator 24V or 230V Low weight Easy installation CE-marked building product

More information

Bevent Rasch BSK Fire /04/2017

Bevent Rasch BSK Fire /04/2017 Bevent Rasch - Fire - BSK120 10/04/2017 Rectangular Fire resistance class /S Sizes from 200 x 200 mm to 1200 x 1000 mm Prefitted safety actuator 24V or 230V Available in MagiCAD CE-marked building product

More information

FDR - Fire Damper for Rectangular and Circular Ducts. Halton FDR. Fire Damper for Rectangular and Circular Ducts

FDR - Fire Damper for Rectangular and Circular Ducts. Halton FDR. Fire Damper for Rectangular and Circular Ducts Halton FDR Fire Damper for Rectangular and Circular Ducts Type-approved and compliant with the EN 1366-2 and EN 13501-3 standards. Design for installation in separating concrete and masonry walls and ceilings

More information

(L=500) L=300 (L=500) PL /E... electric actuator version. Table standard dimensions, L = 300 mm.

(L=500) L=300 (L=500) PL /E... electric actuator version. Table standard dimensions, L = 300 mm. Fire damper pl-30 General characteristics Application Fire dampers prevent fire and smoke from spreading through ventilation ducts in buildings. The dampers are intended for use inside buildings and are

More information

CRP. Commissioning damper, Ductwork Leakage Class 0 QUICK FACTS. Perforated damper blade for better damper characteristic

CRP. Commissioning damper, Ductwork Leakage Class 0 QUICK FACTS. Perforated damper blade for better damper characteristic Commissioning damper, Ductwork Leakage Class 0 QUICK FACTS Perforated damper blade for better damper characteristic Manually adjustable blade (standard) Provision for motorised regulation Quick connection

More information

Fire damper FK120/FK90 TECHNICAL DATA

Fire damper FK120/FK90 TECHNICAL DATA Fire damper FK120/FK90 TECHNICAL DATA 2 Fire damper FK120/FK90 Figure 1 ER1 Figure 2 ER3 The rectangular fire damper FK120/FK90 is available both as motorized and with fuse. The damper casing is manufactured

More information

JVR CONTENTS. Page Introduction 2 Models and dimensions 3 Technical data. Selection tables 4 Technical data. Selection charts 5 Product codes 6

JVR CONTENTS. Page Introduction 2 Models and dimensions 3 Technical data. Selection tables 4 Technical data. Selection charts 5 Product codes 6 1 CONTENTS Page Introduction 2 Models and dimensions 3 Technical data. Selection tables 4 Technical data. Selection charts 5 Product codes 6 2 VAV regulator, model Description The variable air volume regulators

More information

Fire damper ETPR. Specifications. Product code example Fire damper ETPR

Fire damper ETPR. Specifications. Product code example Fire damper ETPR Fire damper ETPR ETPR fire damper is CE marked based on product standard EN 15650:2010 and tested according to the test standard EN 1366-2. ETPR meets the requirements of fire class EI 60 S / EI 90 S.

More information

Fire Dampers. Types FKA FRL FRK 4/1/EN/1

Fire Dampers. Types FKA FRL FRK 4/1/EN/1 Fire Dampers Types FKA FRL FRK /1/EN/1 Contents Description Description... Construction... Standard Sizes Installation Details... Functional Description Product Range... Accessories... Circuit Diagrams...

More information

FIRE DAMPERS, FIRE PROTECTION VALVES, SMOKE DAMPERS

FIRE DAMPERS, FIRE PROTECTION VALVES, SMOKE DAMPERS FIRE DAMPERS, FIRE PROTECTION VALVES, SMOKE DAMPERS Rectangular fire dampers FIRE DAMPERS PL-12 PL-15 PL-18-1, PL-18-2 Fire dampers are installed in rectangular or circular ventilation ducts, at passages

More information

ETPR-E-1 FIRE DAMPER» TECHNICAL CATALOGUE

ETPR-E-1 FIRE DAMPER» TECHNICAL CATALOGUE FIRE SAFETY AIR MANAGEMENT FIRE DAMPERS ETPR-E-1 FIRE DAMPER» TECHNICAL CATALOGUE 2 ETPR-E-1 Fire damper Technical catalogue Fire and smoke damper ETPR-E-1 is used as a closing device for preventing the

More information

Ceiling swirl diffusers

Ceiling swirl diffusers X X testregistrierung Ceiling swirl diffusers Type Horizontal swirling air discharge Adjustable blades Protective cage For high rooms, with adjustable air control blades Circular ceiling swirl diffusers,

More information

series RVV Variable flow rate controllers

series RVV Variable flow rate controllers series RVV Variable flow rate controllers www.koolair.com Series RVV 1 CONTENTS Variable flow rate controllers, type RVV Description 2 Dimensions and product code 3 Selection tables 4 Variable flow rate

More information

7/S5 FIRE DAMPER FD40. v 2.9 (en)

7/S5 FIRE DAMPER FD40. v 2.9 (en) 7/S v.9 (en) FIRE DAMPER FD0 www.klimaoprema.hr 69 FIRE DAMPER - FDC TABLE OF CONTENTS FIRE DAMPER FD0 7 FIRE CLASSIFICATION 7 SELECTION DIAGRAM 7 ORDERING KEY 7 DAMPER MODELS 7 FD0-M rectangular fire

More information

CRP. Commissioning damper, Ductwork Leakage Class 0

CRP. Commissioning damper, Ductwork Leakage Class 0 Commissioning damper, Ductwork Leakage Class 0 Quick facts Perforated damper blade for better damper characteristic Manually adjustable blade (standard) Motorised regulation Provision for motorised regulation

More information

SINGLE DUCT TERMINAL UNITS

SINGLE DUCT TERMINAL UNITS www.igcaire.com SINGLE DUCT TERMINAL UNITS Direct Digital Control, Pressure Independent FEATURES 22 Gauge Galvanized Steel Casing Construction with a 20 Gauge Casing Option that Provides Strength and Product

More information

Type KA-EU FOR THE EXTRACT AIR OF COMMERCIAL KITCHENS. Homepage > Products > Fire and Smoke Protection > Fire dampers > Type KA-EU

Type KA-EU FOR THE EXTRACT AIR OF COMMERCIAL KITCHENS. Homepage > Products > Fire and Smoke Protection > Fire dampers > Type KA-EU Homepage > Products > Fire and Smoke Protection > Fire dampers > Type KA-EU Type KA-EU FOR THE EXTRACT AIR OF COMMERCIAL KITCHENS Rectangular fire damper for use in extract air and exhaust air ducts of

More information

VOLUME CONTROL / REGULATING DAMPERS

VOLUME CONTROL / REGULATING DAMPERS VOLUME CONTROL / REGULATING S PRODUCT RANGE Model Range Includes A - Multi-Leaf. (Flanged - Rectangular Duct) B - Multi-Leaf. (Slip joint / Spigot - Rectangular Duct) C - Multi-Leaf. (Slip joint / Spigot

More information

1/3/EN/4. Ventilation Grilles Types TRS-K TRS-R TRSE-R

1/3/EN/4. Ventilation Grilles Types TRS-K TRS-R TRSE-R 1/3/EN/4 Ventilation Grilles Types TRS-K TRS-R TRSE-R Contents Description Description 2 Constructions Dimensions TRS-K 3 Constructions Dimensions TRS-R 4 Constructions Dimensions TRSE-R 5 Installation

More information

CAV controllers. Type EN-Ex. For the precise control of normal and high constant volume flows in potentially explosive atmospheres (ATEX)

CAV controllers. Type EN-Ex. For the precise control of normal and high constant volume flows in potentially explosive atmospheres (ATEX) X X testregistrierung CAV controllers Type Adjustment scale For the precise control of normal and high constant volume flows in potentially explosive atmospheres (ATEX) Rectangular, mechanical self-powered

More information

7/S6 FIRE DAMPER FDC40. v 2.9 (en)

7/S6 FIRE DAMPER FDC40. v 2.9 (en) 7/S6 v.9 (en) FIRE DAMPER FDC0 www.klimaoprema.hr 8 TABLE OF CONTENTS FIRE DAMPER FDC0 87 FIRE CLASSIFICATION 87 SELECTION DIAGRAM 88 ORDERING KEY 88 DAMPER MODELS 89 FDC0-M cylindrical fire damper with

More information

EAGLE Wall. Wall air diffusers with discs for supply air and flush mounting QUICK FACTS

EAGLE Wall. Wall air diffusers with discs for supply air and flush mounting QUICK FACTS Wall air diffusers with discs for supply air and flush mounting QUICK FACTS Rotatable discs % flexible distribution pattern Cleanable Adjustable slot for enhanced capacity Simple adjustment Used together

More information

Ceiling swirl diffusers

Ceiling swirl diffusers X X testregistrierung Ceiling swirl diffusers Type Horizontal swirling air discharge Vertical air discharge Protective cage For high rooms, with adjustable air control blades Square ceiling swirl diffusers,

More information

DCV-CF DCV-CF. DCV-CF Pressure control with airflow measuring CFL Version B03. Pressure controlwith airflow measuring. Product description

DCV-CF DCV-CF. DCV-CF Pressure control with airflow measuring CFL Version B03. Pressure controlwith airflow measuring. Product description DCV-CF Pressure controlwith airflow measuring 24VAC + Communication Pressure control with airflow measuring DCV-CF DIN 24VAC + Communication AIN AOUT SMART DAMPERS & MEASURING UNITS PRESSURE & FLOW DCV-CF

More information

FlowBar High Capacity Slot Diffuser

FlowBar High Capacity Slot Diffuser October 2016 FlowBar High Capacity Diffuser Model HT (High Throw) Model JT (Jet Throw) Features HT & JT 25mm, 38mm, 51mm, 63mm & 76mm s Ceiling or Sidewall Applications Modular or Continuous s Curved Sections

More information

ESAS Smoke control damper

ESAS Smoke control damper ESAS Smoke control damper 1 Rectangular smoke control damper ESAS is specially designed to use in single fire compartment applications as a closing or as an opening damper for smoke extract purposes. ESAS

More information

WGA Long throw nozzle grille

WGA Long throw nozzle grille Technical documentation WGA Long throw nozzle grille Contents Function and use... 2 Models... 2 Processing... 3 Accessories... 3 Models and dimensions... 4 Quick selection... 12 Installation situation...

More information

CAV controllers. Type RN-Ex. For the precise control of constant volume flows in potentially explosive atmospheres (ATEX) PD RN-Ex 1

CAV controllers. Type RN-Ex. For the precise control of constant volume flows in potentially explosive atmospheres (ATEX) PD RN-Ex 1 X X testregistrierung CAV controllers Type Adjustment scale ATEX-Zertifizierung For the precise control of constant volume flows in potentially explosive atmospheres (ATEX) Circular, mechanical self-powered

More information

Type VDL FOR HIGH ROOMS, WITH ADJUSTABLE AIR CONTROL BLADES. Homepage > Products > Air Diffusers > Swirl diffusers > Type VDL

Type VDL FOR HIGH ROOMS, WITH ADJUSTABLE AIR CONTROL BLADES. Homepage > Products > Air Diffusers > Swirl diffusers > Type VDL Homepage > Products > Air Diffusers > Swirl diffusers > Type VDL Type VDL FOR HIGH ROOMS, WITH ADJUSTABLE AIR CONTROL BLADES Circular ceiling swirl diffusers, with manual or motorised adjustment of the

More information

TYPE EK-EU SMOKE CONTROL DAMPER

TYPE EK-EU SMOKE CONTROL DAMPER Homepage > PRODUCTS > Fire and Smoke Protection > Smoke Control Damper > Type EK-EU TYPE EK-EU SMOKE CONTROL DAMPER WITH TROXNETCOM AS AN OPTION CE COMPLIANT ACCORDING TO EUROPEAN REGULATIONS EK-EU WITH

More information

VARYCONTROL VAV Dual Duct Terminal Boxes

VARYCONTROL VAV Dual Duct Terminal Boxes 5/2/B/3 VARYCONTROL VAV Dual Duct Terminal Boxes for variable volume systems Type TVM Trox (U.K.) Ltd Caxton Way GB-Thetford Norfolk IP24 3SQ Telephone +44 (0)1842 754545 Telefax +44 (0)1842 7051 www.troxuk.co.uk

More information

TPM 075/09. Valid from 1/2/2016 EN 15650: FIRE DAMPER FDMB

TPM 075/09. Valid from 1/2/2016 EN 15650: FIRE DAMPER FDMB Valid from //06 EN 5650:00-09 FIRE DAMPER FDMB These technical specifications state a row of manufactured sizes and models of fire dampers (further only dampers) FDMB. It is valid for production, designing,

More information

TRB - Conical Ceiling Diffuser. Halton TRB. Conical Ceiling Diffuser

TRB - Conical Ceiling Diffuser. Halton TRB. Conical Ceiling Diffuser Halton TRB Conical Ceiling Diffuser Horizontal or vertical air supply, suitable for both heating and cooling applications Supply air jet velocity is effectively reduced due to high mixing effect Installation

More information

UTK/UTT - Multi-blade Damper. Halton UTK, UTT. Multi-blade Damper

UTK/UTT - Multi-blade Damper. Halton UTK, UTT. Multi-blade Damper Halton UTK, UTT Multi-blade Damper Temperature operation range up to +100 C, optionally up to +200 C Galvanised steel design Classification of casing leakage EN 1751 class B UTK: Shut-off, adjustment,

More information

Registers for spiral ducts

Registers for spiral ducts Registers for spiral ducts RGS-3 5 The RGS-3 is a supply/return register with adjustable double deflection blades and a volume damper designed specifically for direct mounting on a spiral duct. The use

More information

Rectangular fire damper TFER 30. pag. C-10

Rectangular fire damper TFER 30. pag. C-10 pag. C-10 Description Rectangular fire damper with CE label in conformity to UNI-EN 15650, certified according to EN 1366-2, classified EI 120 S in accordance to EN 13501-3. Removable shifted kinematic

More information

Fire Dampers Catalogue

Fire Dampers Catalogue Fire s Catalogue DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.) CRFD - Type A, B, CR & CO Rectangular, Round & Flat Oval UL 555 Classified 2013 For Use in Static & Dynamic Systems 3 Hour Rating Made in

More information

CAV controllers. Type EN. For the precise control of normal and high constant volume flows. 01/2017 DE/en PD EN 1

CAV controllers. Type EN. For the precise control of normal and high constant volume flows. 01/2017 DE/en PD EN 1 X X testregistrierung CAV controllers Type For the precise control of normal and high constant volume flows Rectangular self-powered volume flow controllers for the control of supply air or extract air

More information

Regulation and shut-off damper SPB and SPC

Regulation and shut-off damper SPB and SPC SPB / SP -type multi leaf damper is a robust and reliable regulation and shut-off device to be used for different purposes in air handling systems. SPB SP.01.13 Area of application Multi leaf dampers are

More information

Ceiling diffusers. Type VDR. For large temperature differences in heating mode, high penetration of air, with adjustable air control blades

Ceiling diffusers. Type VDR. For large temperature differences in heating mode, high penetration of air, with adjustable air control blades X X testregistrierung Type Vertical air discharge Horizontal air discharge For large temperature differences in heating mode, high penetration of air, with adjustable air control blades Circular ceiling

More information

Circular silencers. Type CA. For the reduction of noise in circular ducts, galvanised sheet steel construction. 02/2017 DE/en PD CA 1

Circular silencers. Type CA. For the reduction of noise in circular ducts, galvanised sheet steel construction. 02/2017 DE/en PD CA 1 X X testregistrierung Circular silencers Type For the reduction of noise in circular ducts, galvanised sheet steel construction Circular silencers Type for the reduction of noise in the circular ducts

More information

CAV controllers. Type VFL. Volume flow limiter for insertion into ducting PD VFL 1

CAV controllers. Type VFL. Volume flow limiter for insertion into ducting PD VFL 1 X X testregistrierung CAV controllers Type Aerodynamic damper blade Sticker showing volume flow rates Set the volume flow rate Insert Volume flow limiter for insertion into ducting Circular, mechanical

More information

THL - Conical Ceiling Diffuser. Halton THL. Conical Ceiling Diffuser

THL - Conical Ceiling Diffuser. Halton THL. Conical Ceiling Diffuser Halton THL Conical Ceiling Diffuser Horizontal or vertical air supply, suitable for both heating and cooling applications Adjustable throw pattern and pressure drop Installation flush to the ceiling, or

More information

Shut-off dampers. Type AKK. For contaminated air PD AKK 1

Shut-off dampers. Type AKK. For contaminated air PD AKK 1 X X testregistrierung Shut-off dampers Type Variant with circular spigot For contaminated air Plastic circular shut-off dampers for shutting off aggressive media volume flows in air conditioning systems

More information

PKIR3G, PKIS, PKIS3G and PKIS3GA

PKIR3G, PKIS, PKIS3G and PKIS3GA PKIR3G, PKIS, PKIS3G and PKIS3GA Fire Dampers Fire resistance EI60S, EI90S and EI120S 1396 - CPR - 0076 1396 - CPR - 0077 1396 - CPD - 0062 Ordering codes Dimensions Type of activation PKIR3G 1) - ødn

More information

THB - Perforated Ceiling Diffuser. Halton THB. Perforated Ceiling Diffuser

THB - Perforated Ceiling Diffuser. Halton THB. Perforated Ceiling Diffuser Halton THB Perforated Ceiling Diffuser Horizontal air supply, suitable also for exhaust Installation either directly to ductwork or balancing plenum Detachable front panel enables the cleaning of the diffuser

More information

CAV controllers. Type RN. For the precise control of constant volume flow rates PD RN 1

CAV controllers. Type RN. For the precise control of constant volume flow rates PD RN 1 X X testregistrierung CAV controllers Type For the precise control of constant volume flow rates Circular self-powered volume flow controllers for the control of supply air or extract air in constant air

More information

TPM 075/09-DK VALID FROM: 15/1/2012 FIRE DAMPER AND FIRE DAMPER-SMOKE FDMB, FDMB-SRD

TPM 075/09-DK VALID FROM: 15/1/2012 FIRE DAMPER AND FIRE DAMPER-SMOKE FDMB, FDMB-SRD FIRE DAMPER AND FIRE DAMPER-SMOKE FDMB, FDMB-SRD TPM 075/09-DK VALID FROM: 15/1/2012 I. CONTENT These technical specifications state a row of manufactured sizes and models of fire dampers and fire dampers

More information

Fan - Powered Terminal Unit Series Flow

Fan - Powered Terminal Unit Series Flow 5/22/M/1 Fan - Powered Terminal Unit Series Flow Type TFP Trox (Malaysia) Sdn Bhd 20 Persiaran Bunga Tanjung 1 Senawang Land Industrial Park 70400 Seremban Negeri Sembilan Darul Khusus Malaysia Telephone

More information

DCV-RC DCV-RC. DCV-RC Room climate control unit. Room climate control SMART DAMPERS & MEASURING UNITS. Product description.

DCV-RC DCV-RC. DCV-RC Room climate control unit. Room climate control SMART DAMPERS & MEASURING UNITS. Product description. DCV-RC Room climate control SMART DAMPERS & MEASURING UNITS DCV-RC Office landscape with DCV-RC. 1(18) Contents Page DCV-RC Introduction... 3 Functional chart... 4 Dimensions, Ordering format... 5 Accessories,

More information

Krantz. Floor displacement outlet Q-B-DN 200. Air distribution systems

Krantz. Floor displacement outlet Q-B-DN 200. Air distribution systems Krantz Floor displacement outlet Q-B-DN 0 Air distribution systems DS 62 E 05. Construction design Preliminary remarks Floor displacement outlets are usually used where wall or plinth displacement outlets

More information

series FSD-FLD Fire and smoke dampers UL Approval

series FSD-FLD Fire and smoke dampers UL Approval series FSD-FLD Fire and smoke dampers UL Approval www.koolair.com Series FSD-FLD 1 Fire and smoke dampers UL Approval FSD-B-U / FSD-A-U and FLD-S-U / FLD-S-UD CONTENTS Description FSD-B-U / FSD-A-U 2 Construction

More information

B. Base occupied space sound level estimates on ARI 885. C. Terminal heating coils shall conform to ARI 410.

B. Base occupied space sound level estimates on ARI 885. C. Terminal heating coils shall conform to ARI 410. PART 1 - GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

For installation into ductwork

For installation into ductwork X X testregistrierung Non-return dampers Type For installation into ductwork Non-return dampers prevent unwanted airflows against the intended airflow direction when the system is not in operation Maximum

More information

KAT. DOUBLE INLET CENTRIFUGAL FAN with Forward Wheels

KAT. DOUBLE INLET CENTRIFUGAL FAN with Forward Wheels KAT DOUBLE INLET ENTRIFUGAL FAN with Forward Wheels KAT Series DOUBLE INLET ENTRIFUGAL FAN with Forward Wheels Kruger Ventilation Industries certifies that the KAT series : version S and - model 9-7 to

More information

DAMPERS LSS - R. N-6230 SYKKYLVEN, NORWAY TEL FAX

DAMPERS LSS - R. N-6230 SYKKYLVEN, NORWAY TEL FAX DAMPERS LSS - R LSS / SOD circular single blade shut off damper SSVent rectangular multiblade shut off damper S.Ventil R1OVL circular single blade weather tight damper/valve RD circular regulating damper

More information

DKR - Multi-nozzle Ceiling Diffuser. Halton DKR. Multi-nozzle Ceiling Diffuser

DKR - Multi-nozzle Ceiling Diffuser. Halton DKR. Multi-nozzle Ceiling Diffuser Halton DKR Multi-nozzle Ceiling Diffuser Horizontal air supply, vertical air patterns are also possible Supply air pattern can freely be directed in up to four directions or alternatively radially as swirl

More information

Ventilation grilles for installation into walls, sills or rectangular

Ventilation grilles for installation into walls, sills or rectangular X X testregistrierung Ventilation grilles for installation into walls, sills or rectangular ducts Type Ventilation grilles, made of sheet steel, with individually adjustable, horizontal blades Ventilation

More information

Pressure control damper ERPA

Pressure control damper ERPA Key features Constant pressure Real-time pressure monitoring with FW compact controller Can be connected to Modbus Available in IPSUM compatible version ERPA is a rectangular pressure control damper for

More information

Circular Silencer. Rigid and flexible construction Type CA CB CF CS. TROX GmbH Telephone +49/28 45/ Telefax +49/28 45/

Circular Silencer. Rigid and flexible construction Type CA CB CF CS. TROX GmbH Telephone +49/28 45/ Telefax +49/28 45/ 6/5/EN/6 Circular Silencer Rigid and flexible construction Type CA CB CF CS TROX GmbH Telephone +49/28 45/2 02-0 Telefax +49/28 45/2 02-2 65 Heinrich-Trox-Platz e-mail trox@trox.de D-47504 Neukirchen-Vluyn

More information

CAV controllers. Type VFL. Volume flow limiter for insertion into ducting K

CAV controllers. Type VFL. Volume flow limiter for insertion into ducting K .1 X X testregistrierung CAV controllers Type Aerodynamic damper blade Sticker showing volume flow rates Set the volume flow rate Insert Volume flow limiter for insertion into ducting Circular, mechanical

More information

Type DCS FOR HORIZONTAL SWIRLING SUPPLY AIR DISCHARGE CREATING HIGH INDUCTION LEVELS, WITH FIXED AIR CONTROL BLADES

Type DCS FOR HORIZONTAL SWIRLING SUPPLY AIR DISCHARGE CREATING HIGH INDUCTION LEVELS, WITH FIXED AIR CONTROL BLADES Homepage > Products > Grilles and Diffusers > Ceiling diffusers > Ceiling swirl diffusers with perforated face plate > Type DCS Type DCS FOR HORIZONTAL SWIRLING SUPPLY AIR DISCHARGE CREATING HIGH INDUCTION

More information

Motorized Fire Dampers

Motorized Fire Dampers Model : OMFD-611 (Fusible link and spring return actuator) GI steel sheet construction In accordance with UL555 & UL555S suitable for installation in walls and partitions having rating 2 Hrs. Static and

More information

Ceiling swirl diffusers with perforated face plate

Ceiling swirl diffusers with perforated face plate X X testregistrierung Ceiling swirl diffusers with perforated face plate Type Horizontal swirling air discharge Diffuser face plate with perforated circular face style and exposed discharge nozzle Diffuser

More information

FIREGARD GILBERTS. Curtain Fire Dampers FEATURES DAMPERS 4 SFB (57.9) X UDC AUGUST 2006

FIREGARD GILBERTS. Curtain Fire Dampers FEATURES DAMPERS 4 SFB (57.9) X UDC AUGUST 2006 FIREGARD Curtain Fire Dampers DAMPERS SFB (.) X UDC. AUGUST 00 FEATURES Galvanised or Stainless Steel Interlocking Blades in Airtight Casing. Stainless Steel Side Seals. Constant Tension Stainless Steel

More information

TBV - Terminal Unit. Halton TBV. Terminal Unit

TBV - Terminal Unit. Halton TBV. Terminal Unit Halton TBV Terminal Unit Horizontal air supply, suitable also for exhaust Integrated rectangular balancing plenum with measurement and adjustment functions Effective sound attenuation Circular duct connection

More information

Systemair Fire Dampers

Systemair Fire Dampers Systemair Fire Dampers Fire resistance class EI60S; EI90S and EI120S www.systemair.com As standard, all fire dampers are designed and certified to comply with EI-S performance attributes. fire dampers

More information

Catalogue. FlowBar. High Capacity Slot Diffuser.

Catalogue. FlowBar. High Capacity Slot Diffuser. Catalogue FlowBar High Capacity Slot Diffuser www.air-diffusion.co.uk sales@air-diffusion.co.uk Content Introduction... 4 Diffuser Specification... 5 Air Patterns... 6 Flange Styles... 7 Curved Sections...

More information

FALCON Ceiling. Circular ceiling air diffuser for supply air QUICK FACTS

FALCON Ceiling. Circular ceiling air diffuser for supply air QUICK FACTS Circular ceiling air diffuser for supply air QUICK FACTS Manages large supply airflows Horizontal or vertical distribution pattern Provision for motorised adjustment of the distribution pattern Suitable

More information

Ventilation grilles for installation into walls, sills or rectangular

Ventilation grilles for installation into walls, sills or rectangular X X testregistrierung Ventilation grilles for installation into walls, sills or rectangular ducts Type Grille cores made of aluminium, with fixed horizontal blades Grille cores with special profiled blades

More information

Wall air diffusers with discs for supply air and flush mounting. Quick guide COLIBRI WALL

Wall air diffusers with discs for supply air and flush mounting. Quick guide COLIBRI WALL Wall air diffusers with discs for supply air and flush mounting General Rectangular supply air diffusers with rotatable discs. The disc technique enables supply of air above or below room temperature as

More information

CONSTANTFLOW Volume Flow Controllers

CONSTANTFLOW Volume Flow Controllers 5/9.1/EN/8 CONSTANTFLOW Volume Flow Controllers for constant volume systems Type EN The art of handling air Contents Description Description 2 Application 3 Construction Dimensions Accessories 4 Dimensions

More information

DFB - Conical Ceiling Diffuser. Halton DFB. Conical Ceiling Diffuser

DFB - Conical Ceiling Diffuser. Halton DFB. Conical Ceiling Diffuser Halton DFB Conical Ceiling Diffuser Horizontal air supply, suitable also for exhaust Installation flush to the ceiling, light-weight aluminium design Circular duct connection with rubber gasket All sizes

More information

Slot diffusers, Round duct diffusers. IMP Klima

Slot diffusers, Round duct diffusers. IMP Klima , Round duct diffusers 04 Round duct diffusers 176 , Round duct diffusers SLOT DIFFUSERS, ROUND DUCT DIFFUSERS SWIRL DIFFUSERS, VARIABLE SWIRL DIFFUSERS CIRCULAR DIFFUSERS, SQUARE DIFFUSERS VENTILATING

More information

PKI-C Cartridge Fire Dampers

PKI-C Cartridge Fire Dampers Fire Safety Products / 7 PKI-C Cartridge Fire Dampers Fire resistance class EI60S, EI90S and EI0S 96 - CPD - 000 Ordering codes Fire resistance class PKI-C-EI - 60S, 90S and 0S Codes section. The thermal

More information

7/S1 FIRE DAMPER PPZEN. v 2.5 (en)

7/S1 FIRE DAMPER PPZEN. v 2.5 (en) 7/S1 v.5 (en) FIRE DAMPER PPZEN www.klimaoprema.hr 39 TABLE OF CONTENTS Product description... Range... Fire classification according to EN 13501-3... Operating mechanisms and dimensions... Operating manual...

More information

Fire dampers ETCE and ETCS TECHNICAL DATA

Fire dampers ETCE and ETCS TECHNICAL DATA Fire dampers ETCE and ETCS TECHNICAL DATA 2 Fire dampers ETCE and ETCS Veloduct ETCE fire damper is CE marked based on product standard EN 15650:2010 and tested according to the test standard EN 13662.

More information

NEO. Fire Damper. air handling intelligence FIRE SAFETY FUNCTION

NEO. Fire Damper. air handling intelligence FIRE SAFETY FUNCTION air handling intelligence FIRE SFETY Fire Damper in libraries of EI 10 (v e -i o) S EN 13501-3+1:01 EN 15650:0 Certificate of Conformity 1488-CPD-081/W EUROPEN PTENT PPLICTION EP 01158318 GOLD MEDL MTP

More information

Slot diffusers for ceiling installation

Slot diffusers for ceiling installation X X testregistrierung Slot diffusers for ceiling installation Type lenum box with damper blade (optional) Alternating horizontal air discharge Concealed screw fixing With wide diffuser face for larger

More information

BX-1H. Fire Valve FIRE SAFETY FUNCTION APPLICATION DESCRIPTION. in libraries of

BX-1H. Fire Valve FIRE SAFETY FUNCTION APPLICATION DESCRIPTION. in libraries of FIRE SAFETY Fire Valve in libraries of EI 60 (v e -o i) S EN 131-3+A1:10 EN 156:10 Certificate of Conformity 1488-CPD-02 82/W FUNCTION The fire valves are designed for buildings where in the event of a

More information

DCV-LC DCV-LC. DCV-LC Lab climate control unit. Lab climate control SMART DAMPERS & MEASURING UNITS. Product description. Occupancy AIN AOUT DCV-LC

DCV-LC DCV-LC. DCV-LC Lab climate control unit. Lab climate control SMART DAMPERS & MEASURING UNITS. Product description. Occupancy AIN AOUT DCV-LC DCV-LC Lab climate control External occupancy detector Lab climate control unit 24VAC + Communication Occupancy DCV-LC 24VAC + Communication AIN Adjustable function AOUT Adjustable function SMART DAMPERS

More information

Accessories. Front vane panel Coupling sleeve with gasket Galvanised steel Gasket of rubber compound

Accessories. Front vane panel Coupling sleeve with gasket Galvanised steel Gasket of rubber compound Halton TSR/TSS Swirl Diffuser Radial horizontal air supply Air velocity is effectively reduced due to high mixing effect Circular duct connection with gasket All sizes available as an adapted version for

More information

500-YH SINGLE DUCT AIR TERMINAL UNIT FORM EG1 (1101)

500-YH SINGLE DUCT AIR TERMINAL UNIT FORM EG1 (1101) 500-YH SINGLE DUCT AIR TERMINAL UNIT FORM 130.12-EG1 (1101) Table of Contents General Description.......................................................................3 500-YH Features........................................................................4-5

More information

COLIBRI Ceiling QUICK FACTS. Square ceiling diffuser with discs for supply air

COLIBRI Ceiling QUICK FACTS. Square ceiling diffuser with discs for supply air Square ceiling diffuser with discs for supply air QUICK FACTS Adjustable discs flexible spread pattern Can be used for vertical air diffusion Swirl function Also available in the Extract air version Designed

More information

ETPS-EI Fire Damper EI 60 S / EI 120 S Instructions for Installation, Operation and Maintenance

ETPS-EI Fire Damper EI 60 S / EI 120 S Instructions for Installation, Operation and Maintenance ETPS-EI Fire Damper EI 60 S / EI 120 S Instructions for Installation, Operation and Maintenance 07/2013 Fläkt Woods FIFLO EN 2013.07 2 ZU CLOSED AUF OPEN Fire damper ETPS-EI Contents Operation and Maintenance

More information

DKS - Multi-nozzle Ceiling Diffuser. Halton DKS. Multi-nozzle Ceiling Diffuser

DKS - Multi-nozzle Ceiling Diffuser. Halton DKS. Multi-nozzle Ceiling Diffuser Halton DKS Multi-nozzle Ceiling Diffuser Horizontal air supply, vertical air patterns also possible Supply air pattern can freely be directed in up to four directions or alternatively radially as swirl

More information

Mechanical mixing box MBM

Mechanical mixing box MBM Mechanical mixing box MBM Ferdinand Schad KG Steigstraße 25-27 D-78600 Kolbingen Telefon 0 74 63-980 - 0 Fax 0 74 63-980 - 200 info@schako.de www.schako.de Contents Description...3 Construction... 3 Model...

More information

technical data air conditioning systems Round Flow Cassette FXFQ-P9VEB

technical data air conditioning systems Round Flow Cassette FXFQ-P9VEB technical data Round Flow Cassette FXFQ-P9VEB air conditioning systems technical data Round Flow Cassette FXFQ-P9VEB air conditioning systems TABLE OF CONTENTS FXFQ-P9VEB 1 Specifications.......................................................

More information

Standard Installation Combination Fire/Smoke Damper Models: FS1(SS), FS2(SS) Fire Damper Models: MD19(SS)

Standard Installation Combination Fire/Smoke Damper Models: FS1(SS), FS2(SS) Fire Damper Models: MD19(SS) Standard Installation Combination Fire/Smoke Damper Models: FS1(SS), FS2(SS) Fire Damper Models: MD19(SS) Page 1 of 6 APPLICATION These dynamically rated fire/smoke and fire s are intended to restrict

More information

M A D E L. FOK-EIS-180 Fire dampers CE

M A D E L. FOK-EIS-180 Fire dampers CE M A D E L EN 60: FOK-EIS-80 Fire dampers CE The fire dampers FOK-EIS-80 work as a separator between two sectors of fire and ensure the same fire resistance that the structural elements of compartmentalisation,

More information

Ceiling swirl diffusers with perforated face plate

Ceiling swirl diffusers with perforated face plate X X testregistrierung Ceiling swirl diffusers with perforated face plate Type Horizontal swirling air discharge For horizontal swirling supply air discharge creating high induction levels, with fixed air

More information

VAV terminal units. Type TVM. For dual duct systems PD TVM 1

VAV terminal units. Type TVM. For dual duct systems PD TVM 1 X X testregistrierung VAV terminal units Type Variant -S Rectangular connection on the room end For dual duct systems VAV dual duct terminal units for dual duct systems with variable volume flows in buildings

More information

Ceiling Slot Diffuser DSC

Ceiling Slot Diffuser DSC Ceiling Slot Diffuser DSC Ferdinand Schad KG Steigstraße 25-27 D-78600 Kolbingen Telephone +49 (0) 74 63-980 - 0 Fax +49 (0) 74 63-980 - 200 info@schako.de www.schako.de Contents Description...3 Construction...

More information

MULTICOMPARTMENT SMOKE CONTROL DAMPERS DKISMA

MULTICOMPARTMENT SMOKE CONTROL DAMPERS DKISMA MULTICOMPARTMENT SMOKE CONTROL DAMPERS DKISMA 96 - CPR - 0 ORIGINAL INSTALLATION, MAINTENANCE AND OPERATION MANUAL EVERY SMOKE DAMPER NEEDS TO BE INSTALLED IN ACCORDANCE WITH THIS MANUAL! / PP-5_0604 DKISMA

More information