MULTICOMPARTMENT SMOKE CONTROL DAMPERS DKISMA

Size: px
Start display at page:

Download "MULTICOMPARTMENT SMOKE CONTROL DAMPERS DKISMA"

Transcription

1 MULTICOMPARTMENT SMOKE CONTROL DAMPERS DKISMA 96 - CPR - 0 ORIGINAL INSTALLATION, MAINTENANCE AND OPERATION MANUAL EVERY SMOKE DAMPER NEEDS TO BE INSTALLED IN ACCORDANCE WITH THIS MANUAL!

2 / PP-5_0604 DKISMA Fig. : RSW - Solid wall with a rectangular opening NOTE: Dimensions W, H are defined in the Tab. W Legend Concrete, masonry, cellular concrete H s (mm) Fire Wall Ceiling resistivity (min.) Concrete, Cellular Cellular Concrete Masonry Concrete Concrete ±0 0±0 0±0 5±0 0 50±0 50±0 50±0 50±0 Tab. : Thickness of standardized walls according to EN 66- S max. 65 Fig. : FSW - Flexible (plasterboard) wall with a rectangular opening NOTE: Dimensions W, H are defined in the Tab. 4 Legend H Vertical CW - profiles (profile width s CW according to fire resistivity, see Tab. ), maximum spacing in the opening area 65 mm. Mineral wool thickness / cubic weight see Tab. Horizontal CW - profiles (profile width s CW according to fire resistivity, see Tab. ), must be firmly embedded into the vertical profiles 4 Plasterboard fireproof plate, thickness,5 mm / layers W Insulation mineral wool Fire s s CW Cubic resistivity Thickness density (min.) (mm) (kg/m ) S Tab. : Thickness of standardized walls and layers according to EN 66-

3 DKISMA PP-5_0604 / Fig. : Wet installation of the DKISMA in the wall using a mixture of plaster or mortar or concrete 75 Legend H Bendable hanging Plaster / mortar / concrete filling Screw 5,5 DIN798 W Wall and opening type Dimensions of the openings W H (mm) Dimensions of the internal frame (mm) RSW W+0 H+0 - FSW W+0 H+0 W+0 H+0 Tab. : Wall opening NOTE: W, H see Fig. - N L NOTE Caution: Main power supply voltage! Parallel connection of several actuators possible Power consumption and switching tresholds must be observed! N L NOTE Supply via safety isolation transformer Parallel connection of several actuators possible Power consumption and switching tresholds must be observed! S S S S4 S5 S6 S S S S4 S5 S6 < <87 < <87 Fig. 4: Connection of the actuator BELIMO BLE 0 Fig. 5: Connection of the actuator BELIMO BE 0- Application with the SBSE-Control damper control and monitoring system Application with the SBSE-Control damper control and monitoring system Connecting lead with plugs for linking to the communication and power unit BKNE0-4 T ~ ~ Connecting lead with plugs for linking to the communication and power unit BKNE0-4 ~ ~ T S S S S4 S5 S6 S S S S4 S5 S6 < <87 < <87 Fig. 6: Connection of the actuator BELIMO B(L)E 4 Fig. 7: Connection of the actuator BELIMO B(L)E 4--ST

4 4 / PP-5_0604 DKISMA AC 0 V BKNE a b Nothing must be assigned to terminals to 5 -wire conductor to BKSE4-6 The device contains no parts which can be replaced or repaired by the user. M BE(G)4-ST, BE4--ST w09840 Displays LED Status Function yellow flashing light damper moving to OPEN steady light damper open green flashing light damper moving to CLOSED steady light damper closed yellow or green flashing and double frequency fault yellow + green dark power failure Fig. 8: Connection and display of the supply and communication unit BKNE0-4 NOTE Supply via isolation transformer Power consumption and switching tresholds must be observed! T - ~ 4 VAC or 4 VDC for BE4 + 0 VAC for BE0 S S S S4 S5 S6 S S S S4 S5 S6 < <87 < <87 Fig. 9: Parallel connection of two coupled actuators BELIMO BE4 or BE0 on one DKISMA blade axis

5 DKISMA PP-5_ / Smoke extraction damper Smoke extraction damper 6 M BE(G)4-ST BKNE0-4 a b Both actuators must be connected to the same BKSE4-6 unit. Both actuators must receive equal instructions in equal time M BE(G)4-ST BKNE0-4 a b AC 0 V The b-conductors must be linked in the equipment cubicle a... a6 b...b Fault BKSE4-6 Equipment cubicle Input Input AC 4 V - + ~ Service pushbutton SMOKE EXTRACTION AUTO CEASE SMOKE EXTRACTION Fire brigade control panel Fire alarm system SMOKE EXTRACTION AUTO CEASE SMOKE EXTRACTION Delay 0 s Delay 60 s OPEN CLOSED Fault A tip: The signal from the Delay 0 s output can be used as feedback for the SMOKE EXTRACTION / CEASE SMOKE EXTRACTION command. AC 4 V ~ Fig. 0: Parallel connection of two coupled actuators BELIMO BE4 on DKISMA blade axis through BKSE4-6

6 6 / PP-5_0604 DKISMA 75 * R 5 L=00 R 80 ø6, 8,8,8 W H (W+60) (H+60) Fig. 9: Dimensions of the DKISMA for nominal dimensions NOTES: Smoke dampers DKISMA have flanges width 0 mm. * Suspension plane W Warnings Some damper parts can have sharp edges therefore it is necessary to use gloves during damper installation and manipulation. In order to prevent an electric injury, fire or any other damage which could result from incorrect damper usage and operation, it is important to:. Install the damper in accordance with the installation manual and by a properly trained employee.. Execute the damper inspection in accordance with this installation, operation and maintenance manual.. Before you can install the smoke damper, it s functionality must be checked according to chapter Check of the functionality. This procedure prevents installation of a damper that has been damaged during transportation or handling. Do not install functionless smoke dampers! Introduction Instructions for installation, operation and control refers to products of Systemair, the rectangular multicompartment smoke control dampers (hereafter dampers) DKISMA aimed for: automatic activation, pressure level = differential pressure between inside and outside the duct for smoke extraction ductwork at ambient temperature up to -500 Pa, resistivity 0 minutes or less, wet installation in the wall meeting requirements for: -- modulating applications, -- systems for use with combined smoke control and general HVAC applications -- systems with smoke control dampers which are checked every day, -- systems where smoke control dampers are operated only in the case of emergency. Operating conditions Smoke dampers are part of the Smoke and Heat Exhaust Ventilation System (SHEVS). Functionality of the smoke damper is following. In case of fire: opens and removes the heat and smoke through a special fan from the fire compartment affected by fire or closes and prevents the spread of smoke and heat in the fire compartment unaffected by fire. The DKISMA smoke dampers are designed for wet installation according to Fig.. All smoke dampers have an electric driving mechanism as standard. They are intended for installation in places which are protected against weather disruptions in the SHEVS or in the combined HVAC ducts leading air without any mechanical or chemical contamination in the following operating conditions: Maximum air flow velocity m/s Temperature within the range -0 C up to +50 C This manual contains basic information and recommendations regarding the installation, use and inspections that need to be followed to ensure proper and smooth operation of the dampers. Resistance class EI0(v ew i o)s500c mod AAmulti is valid for all nominal dimensions of dampers DKISMA. Systemair smoke dampers are passive in terms of noise. There is increased noise only when closing or opening the damper in case of inspection or fire accident (and it takes less than 60 seconds). Installation The installation must be done as follows: Duct connected to the damper must be supported or suspended so that the damper do not bear its weight. The damper must not bear any part of the supporting construction. This could lead to damage and subsequent failure of the damper. Actuator can be on either side of the supporting construction, but it must be placed so that it is easy to access for inspection and repairs. Distance between dampers and building structures, distribution technology and ventilation equipment must be large enough for reliable performance of the installation, functional testing, inspection and repair. The distance between the dampers must be at least 00 mm according to EN The distance between dampers and the wall or ceiling must be at least 75 mm. The gap between the damper and the selfstanding grill (when installed) must be at least 00 mm according to EN Otherwise the damper must be tested together with the grill. The smoke dampers must be installed with horizontal blade axis.

7 DKISMA PP-5_ / Before the installation of the smoke damper, it s functionality must be tested according to the chapter Check of the functionality. DO NOT INSTALL NONFUNCTIONAL SMOKE DAMPERS! Changes of smoke damper functionality, caused by transport or installation, aren t reclaimable after the installation (deformations, damages, mechanical damage of the sealing material, foreign objects which can constrain the blade, wrong handling of the activating mechanism etc.) Before connection of the smoke damper into the ductwork, smoke damper s functionality must be checked again (according to chapter Check of the functionality). During installation, it is necessary to protect the damper mechanism and its interior against dirt. The blade must be in the closed position. It is necessary to avoid deformation of the damper. Installation and setup of the dampers is always determined by SHEVS project plans that must comply with the applicable regulations. The smoke dampers DKISMA must be installed according to Fig.. After damper installing into the SHEVS duct it is necessary to connect electrical installation that must be done only by authorized persons connection has to be done according to Fig The actuators have two microswitches indicating the open and closed positions of the blade - see Fig Setup, install, repair, overhaul and inspections of the dampers must be done only by the manufacturer or by the personnel trained by the manufacturer. Before putting dampers into service after installation (and in subsequent periodic inspections) visual inspection and functional test must be conducted. After the visual inspection and functional test a record must be made into operational diary (page 6). WET INSTALLATION of a DKISMA smoke damper into a solid or flexible wall using plaster mixture, mortar or concrete (Fig. ). Prepare an opening with dimensions W+0mm and H+0mm (according to Fig. or and Tab. ), the opening surfaces must be even and cleaned off. The flexible wall opening must be reinforced according to the standards for plasterboard walls.. Insert the closed damper into the middle of the opening so that the damper blade is in the wall. Use the bendable hanging (; or hangings, if there is two of them) to secure the damper against the wall by a suitable screw (; recommended screw diameter 5,5 - for example DIN798).. Fill in the area between the wall and the damper with plaster mixture, mortar or concrete (), while paying attention to prevent fouling of the damper s functional parts, which could limit its correct functionality. The best way is to cover the functional parts during installation. 4. If needed, uncover and clean the damper after installation. 5. Check the damper functionality Setup, install, repair, overhaul and inspections of the dampers must be done only by the trained personnel. Before putting dampers into service after installation (and in subsequent periodic inspections) visual inspection and functional test must be conducted. After the visual inspection and functional test a record must be made into Operating diary (page 9). Operating and Maintenance. The damper operation Schemes for electrical connection are in Fig Several big dimensions up to mm have two coupled actuators on the blade axis. These must be connected according to Fig. 9 or 0. After installation, the damper must be set up into the operating position - closed. Switching power supply achieves entry into the operating position - closed.. Maintenance Systemair smoke dampers are maintenance free. Check of the functionality Switching the supply phase according to Figure 4-0 damper switch to the open : The blade must come to the fully open position and must remain there detented. After reaching the end position of the blade the appropriate signaling circuit must switch on - wires S and S must be connected. Switching the supply phase according to Figure 4-0 switch damper to the closed : The blade must come up to the fully closed position and remain there detented. After reaching the end position of the blade the appropriate signaling circuit must switch on - wires S4 and S6 must be connected. 4 Inspection of the damper Each damper should be inspected after installation and every months using following steps:. Identification of damper. Date of inspection. Check of the electrical connection of the activation mechanism 4. Check of the the electrical connection of the end switches 5. Check of the damper for cleanliness and eventually treatment (where necessary) 6. Removing of the cover of the inspection lid. 7. Check of the inspection lid, cover tightness and eventually correction and record (where applicable) 8. Check of the blade and sealings, and eventually correction and record (where applicable) 9. Check of the safety damper closure - details see Chap. 0. Check of the damper functionality (details see Chap. ) opening and closing by the control system, tracking the physical behavior of the damper and signalization of the end positions, and eventually correction and record (where applicable). Closing of the cover of the inspection lid.. Set up into the operating position - see Chap... Record into Operating diary (page 8) with name and signature of the checker. 4. The damper is part of the SHEVS. Therefore the system must be checked as specified in its operational and maintenance requirements this is task of the whole SHEVS installer.

8 8 / PP-5_0604 DKISMA 5 Warranty conditions:. IMOS-Systemair provides warranty for all its DKISMA smoke dampers. The warranty period is 4 months, starting on the date of product shipment, by an exceptional agreement this period can be up to 0 months, starting on the date of shipment.. The product is tested in the production factory before the shipment. The producer guarantees that the product features shall be in accordance with the related technical standards during the whole warranty period, assuming that the customer uses it in a way that complies with the Operation manual. If, in spite of this, any unpredictable production defects occur, the producer shall secure their removal without charge.. The customer may apply for the warranty service only in written form including serial number of the claimed damper. 4. The warranty does not apply to defects caused by unprofessional handling, incorrect mounting, mechanical damage or not following the instructions stated in the Operation manual. 5. The warranty period shall be prolonged for the same period of time which has elapsed between the date when the customer lodged the claim for warranty service and the date when the repair was carried out. 6. The repair shall be carried out at the customer s premises and the producer shall bear all the costs which are necessarily needed for the repair. 7. In case no defects applicable for warranty are identified, the costs associated with the arrival of the service technician will be handled by the customer who filed the warranty repair claim. 8. Before you can install the smoke damper, it s functionality must be tested according to the chapter Check of the functionality. DO NOT INSTALL NONFUNCTIONAL SMOKE DAMPERS! Changes of smoke damper functionality, caused by transport or installation, aren t reclaimable after the installation (deformations, damages, mechanical damage of the sealing material, foreign objects which can constrain the blade, wrong handling of the activating mechanism etc.) 9. Before you can connect the smoke damper into the ductwork, smoke damper s functionality must be checked again (according to chapter Check of the functionality). The dampers are transported in covered means of transport, on pallets or in boxes. When handling during transportation and storage, the dampers must be protected against damage and weather conditions and the damper blades must be in the closed position. These products must be stored in a closed and dry area where the temperature is kept within the range of -0 C to +50 C.

9 DKISMA PP-5_ / OPERATING DIARY Activation of the damper Date Description of found defects and date of the following inspection after deficiencies elimination Inspection technician s signature Periodic damper inspections - at least once in months Date Description of found defects and date of the following inspection after deficiencies elimination Inspection technician s signature

10 0 / PP-5_0604 DKISMA Periodic damper inspections - at least once in months Date Description of found defects and date of the following inspection after deficiencies elimination Inspection technician s signature

11 DKISMA PP-5_0604 / Periodic damper inspections - at least once in months Date Description of found defects and date of the following inspection after deficiencies elimination Inspection technician s signature

12 / PP-5_0604 DKISMA 5 96 Smoke damper identification IMOS-Systemair 9004 Kalinkovo 7, Slovakia 96-CPR-0 EN 0-8 Multicompartment smoke control dampers: DKISMA W H Construction site Fire resistance: EI0(v ew i o)s500c mod AA multi - maintenance of the cross section (under E) - integrity E - insulation I - smoke leakage S - mechanical stability (under E) - cross section (under E) Operational reliability: - cycling 0 00 cycles Durability of response delay: - open and closing cycle Pass Pass Placement Room No. ID No. Label Signalization Warranty service Date of claim submission Date of the repair Description of the repair Service officer (signature & stamp)

SMOKE CONTROL DAMPERS

SMOKE CONTROL DAMPERS SMOKE CONTROL DAMPERS 96 - CPD - 0058 Round DKIR and Rectangular DKIS ORIGINAL INSTALLATION, OPERATION AND MAINTENANCE MANUAL EVERY SMOKE DAMPER NEEDS TO BE INSTALLED IN ACCORDANCE WITH THIS MANUAL! /

More information

DKISMA. Systemair multicompartment rectangular smoke control dampers. Ordering codes. Description. Design. Fire safety products 1 / 8.

DKISMA. Systemair multicompartment rectangular smoke control dampers. Ordering codes. Description. Design. Fire safety products 1 / 8. Fire safety products 1 / 8 DKISMA Systemair multicompartment rectangular smoke control dampers Resistance class EI120(v ew i o) S1500C mod AAmulti 1396 - CPR - 0112 Ordering codes Nominal dimensions Type

More information

PKI-C Cartridge Fire Dampers

PKI-C Cartridge Fire Dampers Fire Safety Products / 7 PKI-C Cartridge Fire Dampers Fire resistance class EI60S, EI90S and EI0S 96 - CPD - 000 Ordering codes Fire resistance class PKI-C-EI - 60S, 90S and 0S Codes section. The thermal

More information

7/S6 FIRE DAMPER FDC40. v 2.9 (en)

7/S6 FIRE DAMPER FDC40. v 2.9 (en) 7/S6 v.9 (en) FIRE DAMPER FDC0 www.klimaoprema.hr 8 TABLE OF CONTENTS FIRE DAMPER FDC0 87 FIRE CLASSIFICATION 87 SELECTION DIAGRAM 88 ORDERING KEY 88 DAMPER MODELS 89 FDC0-M cylindrical fire damper with

More information

7/S1 FIRE DAMPER PPZEN. v 2.5 (en)

7/S1 FIRE DAMPER PPZEN. v 2.5 (en) 7/S1 v.5 (en) FIRE DAMPER PPZEN www.klimaoprema.hr 39 TABLE OF CONTENTS Product description... Range... Fire classification according to EN 13501-3... Operating mechanisms and dimensions... Operating manual...

More information

FDR - Fire Damper for Rectangular and Circular Ducts. Halton FDR. Fire Damper for Rectangular and Circular Ducts

FDR - Fire Damper for Rectangular and Circular Ducts. Halton FDR. Fire Damper for Rectangular and Circular Ducts Halton FDR Fire Damper for Rectangular and Circular Ducts Type-approved and compliant with the EN 1366-2 and EN 13501-3 standards. Design for installation in separating concrete and masonry walls and ceilings

More information

7/S5 FIRE DAMPER FD40. v 2.9 (en)

7/S5 FIRE DAMPER FD40. v 2.9 (en) 7/S v.9 (en) FIRE DAMPER FD0 www.klimaoprema.hr 69 FIRE DAMPER - FDC TABLE OF CONTENTS FIRE DAMPER FD0 7 FIRE CLASSIFICATION 7 SELECTION DIAGRAM 7 ORDERING KEY 7 DAMPER MODELS 7 FD0-M rectangular fire

More information

Fire Safety Products. Product Overview

Fire Safety Products. Product Overview Fans Air Handling Units Air Distribution Products Fire Safety Air Conditioning Air Curtains and Heating Products Tunnel Fans Fire Safety Products Product Overview SAFETY PRODUCTS prevent the spread of

More information

PKIR3G, PKIS, PKIS3G and PKIS3GA

PKIR3G, PKIS, PKIS3G and PKIS3GA PKIR3G, PKIS, PKIS3G and PKIS3GA Fire Dampers Fire resistance EI60S, EI90S and EI120S 1396 - CPR - 0076 1396 - CPR - 0077 1396 - CPD - 0062 Ordering codes Dimensions Type of activation PKIR3G 1) - ødn

More information

TPM 075/09. Valid from 1/2/2016 EN 15650: FIRE DAMPER FDMB

TPM 075/09. Valid from 1/2/2016 EN 15650: FIRE DAMPER FDMB Valid from //06 EN 5650:00-09 FIRE DAMPER FDMB These technical specifications state a row of manufactured sizes and models of fire dampers (further only dampers) FDMB. It is valid for production, designing,

More information

Systemair Fire Dampers

Systemair Fire Dampers Systemair Fire Dampers Fire resistance class EI60S; EI90S and EI120S www.systemair.com As standard, all fire dampers are designed and certified to comply with EI-S performance attributes. fire dampers

More information

Systemair Fire Dampers

Systemair Fire Dampers Fire safety products 1 / 7 Systemair Fire Dampers Fire resistance class EI60S; EI90S and EI120S 1396 - CPD - 0061 1396 - CPD - 0062 Ordering codes Ordering Codes for Circular FD: Fire resistance class

More information

TYPE EK-EU SMOKE CONTROL DAMPER

TYPE EK-EU SMOKE CONTROL DAMPER Homepage > PRODUCTS > Fire and Smoke Protection > Smoke Control Damper > Type EK-EU TYPE EK-EU SMOKE CONTROL DAMPER WITH TROXNETCOM AS AN OPTION CE COMPLIANT ACCORDING TO EUROPEAN REGULATIONS EK-EU WITH

More information

Type KA-EU FOR THE EXTRACT AIR OF COMMERCIAL KITCHENS. Homepage > Products > Fire and Smoke Protection > Fire dampers > Type KA-EU

Type KA-EU FOR THE EXTRACT AIR OF COMMERCIAL KITCHENS. Homepage > Products > Fire and Smoke Protection > Fire dampers > Type KA-EU Homepage > Products > Fire and Smoke Protection > Fire dampers > Type KA-EU Type KA-EU FOR THE EXTRACT AIR OF COMMERCIAL KITCHENS Rectangular fire damper for use in extract air and exhaust air ducts of

More information

FIRE DAMPERS, FIRE PROTECTION VALVES, SMOKE DAMPERS

FIRE DAMPERS, FIRE PROTECTION VALVES, SMOKE DAMPERS FIRE DAMPERS, FIRE PROTECTION VALVES, SMOKE DAMPERS Rectangular fire dampers FIRE DAMPERS PL-12 PL-15 PL-18-1, PL-18-2 Fire dampers are installed in rectangular or circular ventilation ducts, at passages

More information

TPM 075/09-DK VALID FROM: 15/1/2012 FIRE DAMPER AND FIRE DAMPER-SMOKE FDMB, FDMB-SRD

TPM 075/09-DK VALID FROM: 15/1/2012 FIRE DAMPER AND FIRE DAMPER-SMOKE FDMB, FDMB-SRD FIRE DAMPER AND FIRE DAMPER-SMOKE FDMB, FDMB-SRD TPM 075/09-DK VALID FROM: 15/1/2012 I. CONTENT These technical specifications state a row of manufactured sizes and models of fire dampers and fire dampers

More information

TECHNICAL-OPERATIONAL DOCUMENTATION. FIRE SAFETY VALVES type V370 and RK370

TECHNICAL-OPERATIONAL DOCUMENTATION. FIRE SAFETY VALVES type V370 and RK370 TECHNICAL-OPERATIONAL DOCUMENTATION FIRE SAFETY VALVES type V370 and RK370 MANUFACTURER: FRAPOL Spółka z o.o. 30-832 Kraków, ul. Mierzeja Wiślana 8 Phone: (012) 653-27-66, 653-27-67, 653-26-92 fax (012)

More information

Installation, Operation and Maintenance Manual

Installation, Operation and Maintenance Manual Installation, Operation and Maintenance Manual Document 483514 SMOKE DAMPERS SMD-XXX and SMDR-XXX Series Leakage Rated Smoke Dampers Vertical and Horizontal Mount Please read and save these instructions

More information

TECHNICAL AND OPERATIONAL DOCUMENTATION

TECHNICAL AND OPERATIONAL DOCUMENTATION Ver. PL1 10.04.08 ul. Grzegorza z Sanoka 2 80 408 Gdańsk tel. +48 58 341 42 45 TECHNICAL AND OPERATIONAL DOCUMENTATION Overpressure-bleed damper of mcr PL1 type FIRE VENTILATION SYSTEMS DEPARTMENT GDAŃSK

More information

PK-I-Ex. Fire resistance class Circular: EI60S, EI90S, EI120S Square: EI90S, EI120S. Systemair Fire Dampers for Explosive Areas.

PK-I-Ex. Fire resistance class Circular: EI60S, EI90S, EI120S Square: EI90S, EI120S. Systemair Fire Dampers for Explosive Areas. Systemair Fire Dampers for Explosive Areas Fire resistance class Circular: EI60S, EI90S, EI120S Square: EI90S, EI120S www.systemair.com Description Fire damper (hereafter referred to as damper) is a fire

More information

Installation, Operation and Maintenance Manual

Installation, Operation and Maintenance Manual Document 461338 SMOKE DAMPERS SMD-XXX, SMD-XXXEF, SMD-XXXM, SMD-XXXV, SESMD-XXX, SSSMD-XXX, SMDR-XXX, SESMDR-XXX, and SSSMDR-XXX Series Leakage Rated Smoke Dampers Vertical and Horizontal Mount Installation,

More information

ETPR-E-1 FIRE DAMPER» TECHNICAL CATALOGUE

ETPR-E-1 FIRE DAMPER» TECHNICAL CATALOGUE FIRE SAFETY AIR MANAGEMENT FIRE DAMPERS ETPR-E-1 FIRE DAMPER» TECHNICAL CATALOGUE 2 ETPR-E-1 Fire damper Technical catalogue Fire and smoke damper ETPR-E-1 is used as a closing device for preventing the

More information

M A D E L. FOK-EIS-180 Fire dampers CE

M A D E L. FOK-EIS-180 Fire dampers CE M A D E L EN 60: FOK-EIS-80 Fire dampers CE The fire dampers FOK-EIS-80 work as a separator between two sectors of fire and ensure the same fire resistance that the structural elements of compartmentalisation,

More information

Document number AMS & AMD Damper Series for Honeywell Spyder Controller Installation, Operation, and Maintenance Instructions

Document number AMS & AMD Damper Series for Honeywell Spyder Controller Installation, Operation, and Maintenance Instructions Document number 480938 AMS & AMD Damper Series for Honeywell Spyder Controller Installation, Operation, and Maintenance Instructions Use this manual when AMS and AMD series dampers were purchased prior

More information

3. Dimensions and weights Placement and installation Pressure lost Material... 14

3. Dimensions and weights Placement and installation Pressure lost Material... 14 These technical conditions define the scope of produced dimensions and versions of "ALUMINIUM REGULATION DAMPER RKALM ("damper"). These technical conditions apply to the manufacture, design, ordering,

More information

Rectangular fire damper TFER 30. pag. C-10

Rectangular fire damper TFER 30. pag. C-10 pag. C-10 Description Rectangular fire damper with CE label in conformity to UNI-EN 15650, certified according to EN 1366-2, classified EI 120 S in accordance to EN 13501-3. Removable shifted kinematic

More information

ESAS Smoke control damper

ESAS Smoke control damper ESAS Smoke control damper 1 Rectangular smoke control damper ESAS is specially designed to use in single fire compartment applications as a closing or as an opening damper for smoke extract purposes. ESAS

More information

ETPS-EI Fire Damper EI 60 S / EI 120 S Instructions for Installation, Operation and Maintenance

ETPS-EI Fire Damper EI 60 S / EI 120 S Instructions for Installation, Operation and Maintenance ETPS-EI Fire Damper EI 60 S / EI 120 S Instructions for Installation, Operation and Maintenance 07/2013 Fläkt Woods FIFLO EN 2013.07 2 ZU CLOSED AUF OPEN Fire damper ETPS-EI Contents Operation and Maintenance

More information

SMOKE DAMPERS SMOKE DAMPERS SMOKE DAMPERS

SMOKE DAMPERS SMOKE DAMPERS SMOKE DAMPERS SMOKE DAMPERS 96 97 SD SERIES SD for Use in Dynamic Systems Types Galvanized Steel Construction as Standard.. Sleeve Type, Model: SD - 0-00. Circular Type, Model: SD - 50-00. Oval Type, Model: SD - 60-00

More information

Motorized Fire Dampers

Motorized Fire Dampers Model : OMFD-611 (Fusible link and spring return actuator) GI steel sheet construction In accordance with UL555 & UL555S suitable for installation in walls and partitions having rating 2 Hrs. Static and

More information

USER S MANUAL VENTS OV/ OVK/ OV1/ OV1 R/ OVK1/ VKF/ VKOM / OVP

USER S MANUAL VENTS OV/ OVK/ OV1/ OV1 R/ OVK1/ VKF/ VKOM / OVP USER S MANUAL Industrial electric axial fans VENTS OV/ OVK/ OV1/ OV1 R/ OVK1/ / VKOM / OVP 2 CONTENTS Safety requirements 3 Introduction 5 Purpose 5 Delivery set 5 Designation key 5 Technical data 6 Design

More information

Combustion gas damper EKO-JB

Combustion gas damper EKO-JB EKO-JB Description The EKO-JB combustion is a Class E6 type-approved damper intended to prevent the spread of combustion gases in ventilation ducting that penetrates fire rated compartment wall or floor

More information

TECHNICAL-OPERATIONAL DOCUMENTATION RK370M FIRE SAFETY VALVES

TECHNICAL-OPERATIONAL DOCUMENTATION RK370M FIRE SAFETY VALVES TECHNICAL-OPERATIONAL DOCUMENTATION RK370M FIRE SAFETY VALVES MANUFACTURER: FRAPOL Spółka z o.o. 30-832 Kraków, ul. Mierzeja Wiślana 8 Phone: (012) 653-27-66, 653-27-67, 653-26-92 fax (012) 653-27-89 MARCH

More information

MODELS TSX AND TSX-S SINGLE DUCT ROUND AIR TERMINALS

MODELS TSX AND TSX-S SINGLE DUCT ROUND AIR TERMINALS MODELS TSX AND TSX-S SINGLE DUCT ROUND AIR TERMINALS INSTALLATION OPERATION & MAINTENANCE New Release Form 130.13-NOM4 (908) In conjunction with the use of these instructions, obtain and refer to the construction,

More information

MODELS SGX AND SSX SINGLE DUCT ROUND AIR TERMINALS

MODELS SGX AND SSX SINGLE DUCT ROUND AIR TERMINALS BY JOHNSON CONTROLS INSTALLATION OPERATION & MAINTENANCE MODELS SGX AND SSX SINGLE DUCT ROUND AIR TERMINALS New Release Form ET130.13-NOM4 (908) In conjunction with the use of these instructions, obtain

More information

Fire damper BKA-EN. with general technical approval Z tested according to DIN EN

Fire damper BKA-EN. with general technical approval Z tested according to DIN EN Fire damper BKA-EN with general technical approval Z-41.3-667 tested according to DIN EN 1366-2 Ferdinand Schad KG Steigstraße 25-27 D-78600 Kolbingen Phone +49 (0) 74 63-980 - 0 Fax +49 (0) 74 63-980

More information

FLÄKTGROUP PM-MOTOR WITH INTEGRATED FC 106 FREQUENCY CONVERTER

FLÄKTGROUP PM-MOTOR WITH INTEGRATED FC 106 FREQUENCY CONVERTER FLÄKTGROUP PM-MOTOR WITH INTEGRATED FC 106 FREQUENCY CONVERTER INSTALLATION AND MAINTENANCE INSTRUCTIONS Risk of electric shock: Motor terminals may still be live if the impeller is rotating, even when

More information

Fire/combustion gas damper EKO-JBL

Fire/combustion gas damper EKO-JBL Fire/combustion Description The fire/combustion is a typeapproved damper intended for fire isolation or as protection against the spread of flame and fire gases in ventilation ducting. The damper is designed

More information

Installation, Operation and Maintenance Manual

Installation, Operation and Maintenance Manual Document 474916 HBS Series Installation, Operation and Maintenance Manual Please read and save these instructions for future reference. Read carefully before attempting to assemble, install, operate or

More information

Mechanical mixing box MBM

Mechanical mixing box MBM Mechanical mixing box MBM Ferdinand Schad KG Steigstraße 25-27 D-78600 Kolbingen Telefon 0 74 63-980 - 0 Fax 0 74 63-980 - 200 info@schako.de www.schako.de Contents Description...3 Construction... 3 Model...

More information

FSAF24(-S) US, FSAF120(-S) US

FSAF24(-S) US, FSAF120(-S) US FSAF4(-S) US, FSAF10(-S) US On/Off, Spring Return, Meets 50 F [11 C] for Half Hour, 75 Seconds Torque min. 133 in-lb, for control of air dampers Technical Data FSAF4(-S) US, FSAF10(-S) US Power supply

More information

BSK-EN Fire damper INSTALLATION, MOUNTING AND OPERATING INSTRUCTIONS

BSK-EN Fire damper INSTALLATION, MOUNTING AND OPERATING INSTRUCTIONS INSTALLATION, MOUNTING AND OPERATING BSK-EN Fire damper Contents Description... 2 Models and dimensions... 3 Mounting information... 5 Installation information... 6 Technical data... 7 Accessories... 9

More information

Fire damper. Type FKA-3.8. GB/en. Installation and operating manual. according to Declaration of Performance. DoP / FKA-3.

Fire damper. Type FKA-3.8. GB/en. Installation and operating manual. according to Declaration of Performance. DoP / FKA-3. Installation and operating manual GB/en Fire damper Type FKA-3.8 according to Declaration of Performance DoP / FKA-3.8 / DE / 002 Read the instructions prior to performing any task! TROX GmbH Heinrich-Trox-Platz

More information

CFSD Series. Product Description

CFSD Series. Product Description COMBINATION FIRE AND SMOKE DAMPER 1-1/2 HR LEAKAGE RESISTANCE CLASS II 250 O F FILE NO: R22165 Product Description Combination Fire / Smoke dampers provide an automatic means of localizing areas of smoke

More information

Fire Dampers. Types FKA FRL FRK 4/1/EN/1

Fire Dampers. Types FKA FRL FRK 4/1/EN/1 Fire Dampers Types FKA FRL FRK /1/EN/1 Contents Description Description... Construction... Standard Sizes Installation Details... Functional Description Product Range... Accessories... Circuit Diagrams...

More information

Installation, Operation, and Maintenance Instructions

Installation, Operation, and Maintenance Instructions Document Number 463384 VCD, FBH & FBV MODELS Vertical and Horizontal Mount Installation, Operation, and Maintenance Instructions This manual is the property of the owner, and is required for future maintenance.

More information

Fire/combustion gas damper EKO-JBG

Fire/combustion gas damper EKO-JBG Fire/combustion EKO-JBG Description The EKO-JBG fire/combustion is a typeapproved damper intended for fire isolation or as protection against the spread of flame and fire gases in ventilation ducting.

More information

lindab we simplify construction LindabSmoke control system single compartment Duct and fittings, Smoke control dampers Mounting instruction

lindab we simplify construction LindabSmoke control system single compartment Duct and fittings, Smoke control dampers Mounting instruction lindab we simplify construction LindabSmoke control system single compartment Duct and fittings, Smoke control dampers Mounting instruction Duct and fittings Content Duct and fittings Introduction...3

More information

Instructions for installation, operation and maintenance of: GATE VALVE

Instructions for installation, operation and maintenance of: GATE VALVE Instructions for installation, operation and maintenance of: GATE VALVE GEN GAC GAF/GENF TERMOVENT SC Temerin Republic of Serbia Instruction for installation, operation and maintenance: Table of Contents

More information

SD-1250 and SD-1600 Series Smoke Dampers

SD-1250 and SD-1600 Series Smoke Dampers SD-1250 and SD-1600 Series Smoke Dampers Product Bulletin Code No. LIT-1201592 Issued January 30, 2014 Supersedes October 14, 2013 Johnson Controls provides a leakage-rated damper for life safety smoke

More information

Combustion gas damper EKO-SRB

Combustion gas damper EKO-SRB Combustion EKO-SRB Description The EKO-SRB combustion is a Class E60 type-approved damper intended to prevent the spread of combustion gases in ventilation ducting that penetrates fire rated compartment

More information

B. Base occupied space sound level estimates on ARI 885. C. Terminal heating coils shall conform to ARI 410.

B. Base occupied space sound level estimates on ARI 885. C. Terminal heating coils shall conform to ARI 410. PART 1 - GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

(L=500) L=300 (L=500) PL /E... electric actuator version. Table standard dimensions, L = 300 mm.

(L=500) L=300 (L=500) PL /E... electric actuator version. Table standard dimensions, L = 300 mm. Fire damper pl-30 General characteristics Application Fire dampers prevent fire and smoke from spreading through ventilation ducts in buildings. The dampers are intended for use inside buildings and are

More information

Air terminal devices

Air terminal devices Installation manual GB/en Air terminal devices Slot Diffusers Type PureLine18 TROX GmbH Heinrich-Trox-Platz 47504 Neukirchen-Vluyn Germany Phone: +49 (0) 2845 2020 Fax: +49 (0) 2845 202265 E-mail: trox@trox.de

More information

For installation into ductwork

For installation into ductwork X X testregistrierung Non-return dampers Type For installation into ductwork Non-return dampers prevent unwanted airflows against the intended airflow direction when the system is not in operation Maximum

More information

Installation, Operation and Maintenance Manual

Installation, Operation and Maintenance Manual Document 483509 VCD, FBH & FBV Models Vertical and Horizontal Mount Installation, Operation and Maintenance Manual Please read and save these instructions for future reference. Read carefully before attempting

More information

Type TA-Silenzio FOR EXTRACT AIR SYSTEMS WITH DEMANDING ACOUSTIC REQUIREMENTS AND LOW AIRFLOW VELOCITIES

Type TA-Silenzio FOR EXTRACT AIR SYSTEMS WITH DEMANDING ACOUSTIC REQUIREMENTS AND LOW AIRFLOW VELOCITIES Type TA-Silenzio FOR EXTRACT AIR SYSTEMS WITH DEMANDING ACOUSTIC REQUIREMENTS AND LOW AIRFLOW VELOCITIES Rectangular VAV terminal units for the extract air control in buildings with variable air volume

More information

Fire/smoke damper EKO-SRBG1

Fire/smoke damper EKO-SRBG1 Fire/smoke damper EKO- Description The EKO- fire/smoke damper is a CE-approved damper intended for fire compartmentation or protection against the spread of fire and smoke in ventilation installations.

More information

Smoke control damper RKI-90 Test certificate Z

Smoke control damper RKI-90 Test certificate Z Resistance class EK90 within smoke extraction ducts that have a fire resistance time of 90 min Ordering example / dimensions smoke control damper consisting of the housing with cut-off damper designed

More information

Model CFSD-211. Corridor Ceiling FIRE SMOKE DAMPER Steel 3V Blades UL 555S Leakage Class I

Model CFSD-211. Corridor Ceiling FIRE SMOKE DAMPER Steel 3V Blades UL 555S Leakage Class I Application and Design Model is a combination fire smoke damper that is UL classified to protect corridor ceiling penetrations as required by the Uniform Building Code. This model s operational ratings

More information

.3 Section Concrete Forms and Accessories: Installation of Anchor Devices, Setting Templates

.3 Section Concrete Forms and Accessories: Installation of Anchor Devices, Setting Templates Issued 2005/06/01 Section 16239 Power Generation to 30 kw Page 1 of 7 PART 1 GENERAL 1.1 RELATED WORK.1 Section 01355 Waste Management and Disposal..2 Section 01810 Commissioning..3 Section 03100 Concrete

More information

MANUAL INSTALLATION. Venturi FX. VFX Series. v100 Issue Date: 11/22/ Price Industries Limited. All rights reserved.

MANUAL INSTALLATION. Venturi FX. VFX Series. v100 Issue Date: 11/22/ Price Industries Limited. All rights reserved. MANUAL INSTALLATION Venturi FX VFX Series v100 Issue Date: 11/22/16 2016 Price Industries Limited. All rights reserved. TABLE OF CONTENTS Product Overview Safety Precautions... 1 Caution to Contractors...1

More information

NEO. Fire Damper. air handling intelligence FIRE SAFETY FUNCTION

NEO. Fire Damper. air handling intelligence FIRE SAFETY FUNCTION air handling intelligence FIRE SFETY Fire Damper in libraries of EI 10 (v e -i o) S EN 13501-3+1:01 EN 15650:0 Certificate of Conformity 1488-CPD-081/W EUROPEN PTENT PPLICTION EP 01158318 GOLD MEDL MTP

More information

Inlet Controller TC5-ITA USER'S MANUAL. M rev. 02 K rev. 00

Inlet Controller TC5-ITA USER'S MANUAL. M rev. 02 K rev. 00 Inlet Controller TC5-ITA USER'S MANUAL M 890-00047 rev. 02 K 895-00458 rev. 00 TABLE OF CONTENTS PRECAUTIONS... 3 FEATURES... 4 LOCATION OF THE CONTROLS... 5 Status Leds...5 Internal Switches...6 INSTALLATION

More information

BX-1H. Fire Valve FIRE SAFETY FUNCTION APPLICATION DESCRIPTION. in libraries of

BX-1H. Fire Valve FIRE SAFETY FUNCTION APPLICATION DESCRIPTION. in libraries of FIRE SAFETY Fire Valve in libraries of EI 60 (v e -o i) S EN 131-3+A1:10 EN 156:10 Certificate of Conformity 1488-CPD-02 82/W FUNCTION The fire valves are designed for buildings where in the event of a

More information

INSTALLATION and OPERATING INSTRUCTIONS

INSTALLATION and OPERATING INSTRUCTIONS INSTALLATION and OPERATING INSTRUCTIONS UHV-LEAKVALVE ND 3 pneumatically operated NC, 2-positions cylinder. Valve F3CF1616-29 Valve F3CF3516-29 Valve F3VCR-29 Heating Cartridge HF3 Heater Controller HF3-S1

More information

Fire/smoke damper EKO-JBG2

Fire/smoke damper EKO-JBG2 Fire/smoke damper EKO-JBG2 Description The EKO-JBG2 fire/smoke damper is a CE-approved damper intended for fire compartmentation or protection against the spread of fire and smoke in ventilation installations.

More information

TRACTION BATTERY CHARGER SERVICE MANUAL

TRACTION BATTERY CHARGER SERVICE MANUAL AXIgo TRACTION BATTERY CHARGER SERVICE MANUAL AXIgo TRACTION BATTERY CHARGER Content 1 Basic Data... 2 1.1 Device Characteristics... 2 1.2 Usage... 2 1.3 The Marking System of the AXIgo-type chargers...

More information

Fire Dampers. Type FDF. Compliant to SABS (193:2004) SA/6/1/EN/3

Fire Dampers. Type FDF. Compliant to SABS (193:2004) SA/6/1/EN/3 SA/6/1/EN/3 Fire Dampers Type FDF Compliant to SABS (193:2004) TROX (South Africa) (Pty) Ltd. 10 Wigford Road Masons Mill Pietermaritzburg Tel. +27 (0)33 398 1006 Fax. +27 (0)33 398 1100 email : pmb@troxsa.co.za

More information

Bevent Rasch BSK6. - Fire /04/2017

Bevent Rasch BSK6. - Fire /04/2017 Bevent Rasch - Fire - BSK6 11/04/2017 Fire resistance class EI60 / EI60S Sizes from 200 x 200 mm to 800 x 800 mm Prefitted safety actuator 24V or 230V Low weight Easy installation CE-marked building product

More information

VU120. Rectangular smoke evacuation damper. V22-EN-G 08/2017

VU120. Rectangular smoke evacuation damper.  V22-EN-G 08/2017 Organisme Certificateur AFNOR Certification - www.marque-nf.com VU120 Rectangular smoke evacuation damper. en 0749 Clapets coupe-feu et Volets de désenfumage D.A.S. Rf-Technologies nv Lange Ambachtstraat

More information

VAV terminal units. Type TVM. For dual duct systems PD TVM 1

VAV terminal units. Type TVM. For dual duct systems PD TVM 1 X X testregistrierung VAV terminal units Type Variant -S Rectangular connection on the room end For dual duct systems VAV dual duct terminal units for dual duct systems with variable volume flows in buildings

More information

CAV controllers. Type EN. For the precise control of normal and high constant volume flows. 01/2017 DE/en PD EN 1

CAV controllers. Type EN. For the precise control of normal and high constant volume flows. 01/2017 DE/en PD EN 1 X X testregistrierung CAV controllers Type For the precise control of normal and high constant volume flows Rectangular self-powered volume flow controllers for the control of supply air or extract air

More information

Floor Swirls Models BZD and SZD

Floor Swirls Models BZD and SZD July 09 Floor Swirls Floor Swirls Models BZD and SZD Features Model BZD Circular Floor Swirl Model SZD Circular Step Diffuser Grilles Diffusers Louvres Chilled Beams Ruskin Air Management Limited www.ruskinuk.co.uk

More information

INSTALLATION & OPERATION MANUAL. Fan Powered Terminals VAV TERMINALS. Redefine your comfort zone.

INSTALLATION & OPERATION MANUAL. Fan Powered Terminals VAV TERMINALS. Redefine your comfort zone. INSTALLATION & OPERATION MANUAL Fan Powered Terminals VAV TERMINALS IOM FAN POWERED TERMINALS Receiving Inspection After unpacking the terminal, check it for shipping damage. If any shipping damage is

More information

Installation and operating instructions. Solar charge controller MPPT 10 A / 20 A Z Z

Installation and operating instructions. Solar charge controller MPPT 10 A / 20 A Z Z Installation and operating instructions Solar charge controller MPPT 10 A / 20 A EN 1 Contents 1. About these instructions... 3 1.1 Applicability... 3 1.2 Users... 3 1.3 Description of symbols... 3 2.

More information

SECTION AXIAL HVAC FANS

SECTION AXIAL HVAC FANS SECTION 233413 - AXIAL HVAC FANS 1. PART 1 GENERAL 1.1. RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

VAV terminal units. Type TVA. For extract air systems with demanding acoustic requi rements K

VAV terminal units. Type TVA. For extract air systems with demanding acoustic requi rements K . X X testregistrierung VAV terminal units Type Easy controller Compact controller Circular connection on the fan end For extract air systems with demanding acoustic requi rements VAV terminal units for

More information

Smoke damper EKO-SRB1

Smoke damper EKO-SRB1 Smoke damper EKO-SRB1 Description The EKO-SRB1 smoke damper is a CE-approved damper in fire class E60 intended for fire compartmentation or protection against the spread of fire and smoke in ventilation

More information

Type MZ15. Operating Instructions. Bedienungsanleitung Manuel d utilisation

Type MZ15. Operating Instructions. Bedienungsanleitung Manuel d utilisation Handheld calibration tool / Handheld cleaning tool Tragbares Kalibrierwerkzeug / Tragbares Reinigungswerkzeug Outil d'étalonnage portatif / Outil de nettoyage portatif Operating Instructions Bedienungsanleitung

More information

Fire damper ETPR. Specifications. Product code example Fire damper ETPR

Fire damper ETPR. Specifications. Product code example Fire damper ETPR Fire damper ETPR ETPR fire damper is CE marked based on product standard EN 15650:2010 and tested according to the test standard EN 1366-2. ETPR meets the requirements of fire class EI 60 S / EI 90 S.

More information

Type TVT FOR NORMAL AND HIGH VOLUME FLOW RATE RANGES AND LOW-LEAKAGE SHUT-OFF

Type TVT FOR NORMAL AND HIGH VOLUME FLOW RATE RANGES AND LOW-LEAKAGE SHUT-OFF Type TVT FOR NORMAL AND HIGH VOLUME FLOW RATE RANGES AND LOW-LEAKAGE SHUT-OFF Rectangular VAV terminal units for standard applications regarding the supply air or extract air control in variable air volume

More information

Electrical linear actuator with safety function MC100FSR/230

Electrical linear actuator with safety function MC100FSR/230 Issue 2013-05-24 Operating manual 3.10-TA.210-10-EN Electrical linear actuator with safety function Application Linear actuator with automatic coupling and safety function for fine stroke adjustment of

More information

VAV TERMINAL BOXES TYPE: BA BT

VAV TERMINAL BOXES TYPE: BA BT Installation dimensions View inlet side View outlet side C G F E ø D A 65 ø8 B 25 Side view Top view 40 150 150 L1 Application ø D 150 Size operating range q (m 3 /h) Min. Max. Nom. 125 90 150-440 500

More information

Shut-off dampers. Type AKK. For contaminated air PD AKK 1

Shut-off dampers. Type AKK. For contaminated air PD AKK 1 X X testregistrierung Shut-off dampers Type Variant with circular spigot For contaminated air Plastic circular shut-off dampers for shutting off aggressive media volume flows in air conditioning systems

More information

Elektric actuator MC50/24-C

Elektric actuator MC50/24-C Issue 2014-04-29 Operating manual 3.10-TA.150-15-EN Elektric actuator for KTM512, KTH512 DN15-50 Application Elektric actuator for 3-point or modulating controllers in heating systems. Positive connection

More information

M9106-AGx-2N0x Series Electric Non-spring Return Actuators

M9106-AGx-2N0x Series Electric Non-spring Return Actuators Installation Instructions M9106AGx-2N0x Issue Date 08/31/01 M9106-AGx-2N0x Series Electric Non-spring Return Actuators Installation IMPORTANT: The M9106-AGx-2N0x Series actuator is intended to control

More information

INSTRUCTIONS FOR INSTALLATION, OPERATION AND MAINTENANCE OF

INSTRUCTIONS FOR INSTALLATION, OPERATION AND MAINTENANCE OF INSTRUCTIONS FOR INSTALLATION, OPERATION AND MAINTENANCE OF Forged Strainers [SAP] Table of Contents 1.General safety information s 3 2. Product description 3 3. Transport and storage 5 4. Installation

More information

Danfoss Butterfly Valve

Danfoss Butterfly Valve Triple Eccentric Danfoss Butterfly Valve Operating, installation and maintenance instructions Edition 1 / January 2015. Table of Contents: 1 Overview... - 1-2 General... - 1-2.1 Safety notes... - 1-2.2

More information

Introduction to Johnson Controls Dampers

Introduction to Johnson Controls Dampers Damper and Actuator Product Guide 268.1 Damper Engineering Section Product Bulletin Issue Date 1297 Introduction to Johnson Controls Dampers For over 100 years, Johnson Controls has been the industry leader

More information

Mounting and operating instructions EB 5801 EN. Electric Actuators Type 5801 (Rotary Actuator) Type 5802 (Linear Actuator)

Mounting and operating instructions EB 5801 EN. Electric Actuators Type 5801 (Rotary Actuator) Type 5802 (Linear Actuator) Electric Actuators Type 5801 (Rotary Actuator) Type 5802 (Linear Actuator) Linear Actuator with Type 3260 Control Valve Rotary actuator with lever system Linear actuator with Type 3321 (V2001) Control

More information

Power consumption In operation At rest For wire sizing. Torque Inhibiting torque. 150 s / C Sound power level Motor

Power consumption In operation At rest For wire sizing. Torque Inhibiting torque. 150 s / C Sound power level Motor Technical data sheet GK24G- SuperCap rotary actuator with emergency setting function and extended functionalities in the IP66 protective housing for adjusting air dampers in ventilation and air-conditioning

More information

ROOF FAN ROOFMASTER STEC NON-INSULATED VERSION TECHNICAL CATALOGUE

ROOF FAN ROOFMASTER STEC NON-INSULATED VERSION TECHNICAL CATALOGUE ROOF FAN ROOFMASTER STEC NON-INSULATED VERSION TECHNICAL CATALOGUE Roofmaster STEC non-insulated version - Technical Catalogue 3 CONTENTS GENERAL DESCRIPTION Application/specification...4 Features...4

More information

Homepage > Products > External louvres - louvre blades > Mechanically self-powered dampers > Non-return dampers > Type KUL.

Homepage > Products > External louvres - louvre blades > Mechanically self-powered dampers > Non-return dampers > Type KUL. Homepage > Products > External louvres - louvre blades > Mechanically self-powered dampers > Non-return dampers > Type KUL Type KUL FOR INSTALLATION INTO DUCTWORK Non-return dampers prevent unwanted airflows

More information

Type TA-Silenzio FOR EXTRACT AIR SYSTEMS WITH DEMANDING ACOUSTIC REQUIREMENTS AND LOW AIRFLOW VELOCITIES

Type TA-Silenzio FOR EXTRACT AIR SYSTEMS WITH DEMANDING ACOUSTIC REQUIREMENTS AND LOW AIRFLOW VELOCITIES Type TA-Silenzio FOR EXTRACT AIR SYSTEMS WITH DEMANDING ACOUSTIC REQUIREMENTS AND LOW AIRFLOW VELOCITIES Rectangular VAV terminal units for the extract air control in buildings with variable air volume

More information

18VDC ESB6 Series Cordless Screwdrivers Operation Manual

18VDC ESB6 Series Cordless Screwdrivers Operation Manual 18VDC ESB6 Series Cordless Screwdrivers Screwdriver Models : ESB6-8, ESB6-12, ESB6-15, ESB6-22 CAUTION - Please read, understand, and follow all operating and safety instructions in this manual before

More information

SECTION CENTRIFUGAL HVAC FANS

SECTION CENTRIFUGAL HVAC FANS SECTION 233416 - CENTRIFUGAL HVAC FANS 1. PART 1 GENERAL 1.1. RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

Operating Instructions Type MPT 53

Operating Instructions  Type MPT 53 Operating Instructions www.turnstiles.us Type MPT 53 Contents 1. Delivery... 2 2. Safety...3-4 3 Description and operation... 5 4. Technical Data 6 5. oundation...6-9 6. Assembly and installation...10-13

More information

CONSTANTFLOW Volume Flow Controllers

CONSTANTFLOW Volume Flow Controllers 5/9.1/EN/8 CONSTANTFLOW Volume Flow Controllers for constant volume systems Type EN The art of handling air Contents Description Description 2 Application 3 Construction Dimensions Accessories 4 Dimensions

More information

series FSD-FLD Fire and smoke dampers UL Approval

series FSD-FLD Fire and smoke dampers UL Approval series FSD-FLD Fire and smoke dampers UL Approval www.koolair.com Series FSD-FLD 1 Fire and smoke dampers UL Approval FSD-B-U / FSD-A-U and FLD-S-U / FLD-S-UD CONTENTS Description FSD-B-U / FSD-A-U 2 Construction

More information