1 Damper and Actuator Product Guide Damper Engineering Section Product Bulletin Issue Date 1297 Introduction to Johnson Controls Dampers For over 100 years, Johnson Controls has been the industry leader in automatic temperature control. We offer a complete line of Heating, Ventilating, and Air Conditioning (HVAC) controls, including top quality dampers for a wide range of applications, including: CD-1310 class III control damper CD-1320 class II control damper CD-1330 class I control damper BD-1300 balancing damper SD-1320 class II smoke damper SD-1330 class I smoke damper FD /2 hour fire-rated damper LD-1800 light duty damper RD-2000 round control damper To meet each customer s unique damper size and type requirements, we build dampers made-to-order. Dampers can be produced and shipped the next day after the order is received. Figure 1: Selection of Dampers Available Actuators and accessories are ordered with the damper, and can be factory installed or shipped separately, resulting in a damper which perfectly fits your application. All dampers and actuators have a three-year warranty on parts and workmanship Johnson Controls, Inc. 1 Code No. LIT , Rev. B

2 G eneral Dampers are an essential part of HVAC systems. They may control the pressure, temperature, or the amount of air entering, leaving, and flowing through a building. They may also be used to control the passage of smoke or restrict the passage of flame during fires. Johnson Controls dampers come in a variety of shapes and sizes to meet different application and environmental requirements. These include: volume (air) control applications, which regulate airflow temperature control applications, which regulate a constant temperature pressure control applications, which regulate a constant pressure smoke control to restrict the spread of smoke in HVAC systems that are designed to be automatically shut down in the event of a fire, or to control the movement of smoke within a building when the HVAC system is operational in engineered smoke control systems fire-rated, which interrupts airflow automatically through part of an air system so as to restrict the passage of flame, and installed in a fire-rated wall or floor to close automatically in the event of a fire to maintain the integrity of the fire-rated separation Each of these applications will be discussed later in this document in Damper Application Examples. The rectangular damper consists of five major components, identified in Figure 2 and described below: Frame--provides structural support Blades--provide the proper resistance to airflow Seals--prevent airflow when blades close Linkage--drives the blades to position Bearings--provide support and alignment for blade movement Frame Continuing the Johnson Controls effort to protect the environment, the frame is mechanically joined and uses no welding process. This manufacturing process improvement is standard for all of our damper product families. Rectangular Damper Construction Figure 3: 13-gauge Frame Assembly The frame shown in Figure 3 provides the structure and rigidity to the damper. A strong frame minimizes vibration and noise when the damper is exposed to high pressure and airflow. A rugged frame means less damage to the damper during shipping and installation. A square frame allows the blades to move freely, without twisting or binding. Figure 2: Rectangular Damper Components Individual panels can be quickly and easily coupled in the field to form multiple-section units with a modular frame. Blade stops provide sealing on top and bottom. 2 Introduction to Johnson Controls Dampers Product Bulletin

3 Blades Damper blades must withstand different levels of static pressure and velocities; some must provide low leakage rates, withstand high static pressures, or perform with minimal noise generation. The Johnson Controls family of dampers allows you to achieve these results by selecting 16-gauge, double-piece, or airfoil blades, as shown in Figures 4, 5, and 6. Seals Figure 4: 16-Gauge Blade Profile 16-gauge blades are made of 16-gauge rolled sheet metal. Figure 7: Replaceable Blade Seals Dampers with seals have lower leakage rates. This is important in applications where the flow of air must be fully shut off, such as outdoor air intakes and smoke dampers. Standard temperature seals are made of santoprene, which is a general purpose thermoplastic rubber. High-temperature seals are made of silicone. Figure 5: Double-Piece Blade Profile Double-piece blades are made from two layers of 22-gauge rolled sheet metal, mechanically joined. Figure 8: Frame Side Seal Rectangular dampers are provided with self- compensating stainless steel side seals, as shown in Figure 8. Figure 6: Airfoil Blade Profile Airfoil blades are made of extruded 1/16 inch thick aluminum. All dampers are available in 1 inch increments. Introduction to Johnson Controls Dampers Product Bulletin 3

4 Linkage The linkage connects the drive blade to the other blades, assuring simultaneous rotation of the blades. The linkage: features rugged, self-lubricating acetal (a polymer with up to 20% glass fiber) or bronze bearings for smooth, low-torque operation tested over 100,000 cycles is located in a side channel of the frame to reduce air noise, friction, and pressure drop requires no maintenance One blade in a multi-blade panel is always designated as the preferred drive blade and labeled accordingly, as shown in Figure 10. The actuator should be connected on the linkage side of this blade. This blade is recommended from experience to provide optimal performance and consistent mounting arrangements. For dampers with blades operating in parallel, any blade can be used as the drive blade. The ideal situation is to use a drive blade near the center of the damper height to distribute the torque evenly. For dampers with blades operating in opposed direction, the following blades should be used: Table 1: Single Drive Location Height, inches Blade 24 or less No. 1 or 3 Greater than 24 but less than 48 No. 3 or 5 Greater than 48 but 76 or less No. 5 or 7 For dampers using a single actuator, install the direct-mount actuator or associated actuator linkage to the linkage side of the recommended drive blade shown in Table 1. Use only odd-numbered blades for dampers with opposed blade rotation. Figure 9: Opposed and Parallel Operation The blades can operate parallel or opposed. In parallel operation, all the blades rotate in the same direction as shown in Figure 9 (right). In opposed operation, one blade rotates clockwise while the adjacent blade operates counterclockwise as shown in Figure 9 (left). The flow characteristics for the parallel and opposed operation differ significantly, but the pressure drop across the parallel and opposed dampers is identical. See Damper Application Examples for details. Table 2: Multiple Drive Location Height, inches Blade 30 Nos. 3 and 5 Greater than 30 but less than 48 Nos. 3 and 7 Greater than 48 but 76 or less Nos. 3 and 9 For dampers using multiple actuators, install the direct-mount actuator or associated actuator linkage to the linkage side of the recommended drive blades shown in Table 2. Note: Use only odd-numbered blades for dampers with opposed blade rotation. All other blades are connected to this blade by linkage. Additional linkage assemblies on multiple-section dampers should connect drive blade to drive blade for optimum performance. Figure 10: Drive Blade Identification 4 Introduction to Johnson Controls Dampers Product Bulletin

5 Bearings Johnson Controls offer two types of self-lubricating bearings: acetal and bronze. Selecting the proper bearing for your application is based on several factors: When cost is the only factor, acetal bearings would be the choice. In considering durability, bronze bearings are better where there are airborne contaminants that would attack the acetal bearing. For temperature limits, acetal bearings are rated to 250 F (121 C) and bronze bearings are rated to 350 F (177 C). Selecting the Correct Control Damper This section helps to determine appropriate applications for CD-1310, CD-1320, and CD-1330 Dampers. Dampers throttle or stop the flow of air through a duct or opening. The size and type of damper depends on the application and the environment. Listed below are some areas to consider when selecting a damper: What will be the maximum air velocity in the duct? What will be the maximum static pressure? What leakage rate will be acceptable? What will be the maximum and minimum operating temperature? Factors for selecting the appropriate model include the following: What is the control application (strategy)? Operating conditions including: - Velocity/pressure - Leakage - Temperature - Pressure drop - Closing Torque Figures 11 through 15 and Tables 3 through 5 provide the performance characteristics for the base models of control dampers. Table 3: Leakage Resistance Classes Class Static Pressure (inches water) I II III Leakage in cfm/sq ft Figure 11: CD-1310 Leakage Resistance Figure 12: CD-1320 Leakage Resistance Figure 13: CD-1330 Leakage Resistance Introduction to Johnson Controls Dampers Product Bulletin 5

6 Figures 11 through 13 show resultant air leakage through the damper, corrected to standard temperature and pressure conditions, as determined using instrumentation and procedures in accordance with AMCA Standard for Test Methods for Louvers, Dampers, and Shutters No It is not always an accurate characterization to have specifications list percent leakage. The truth is that the dynamics of airflow are not simple. The factors affecting leakage are static pressure, actuator torque (affecting how much the seals are compressed), and damper size. These variables interact with each other in an indirect manner. When it is stated that dampers have a leakage of 1/2%, you need to know how that percentage was derived. For example: A damper that is 24 x 24 inches may have a leakage rate of 12 cfm at a velocity of 600 fpm and 1 inch static pressure (this is equal to 1/2%). The same damper may have a leakage rate of 40 cfm under conditions such as 1000 fpm at 2 inches of static; in this case the damper has a leakage of 1%. That is why Johnson Controls rates our CD-1300 damper leakage in cfm at specific levels of velocity and static pressure. Table 4: Temperature Rating Description CD-1310 with standard seals and acetal bearings BD-1310 without seals and with bronze bearings CD-1320 with standard seals and acetal bearings CD-1320 with silicone seals and bronze bearings CD-1330 with standard seals and acetal bearings Closing Torque Table 5: Required Closing Torque Temp. Rating -40 to 200 F (-40 to 93 C) -65 to 350 F (-54 to 177 C) -40 to 200 F (-40 to 93 C) -65 to 350 F (-54 to 177 C) -40 to 200 F (-40 to 93 C) Operating Torque in lb/sq ft (in. static, fpm velocity) CD-1310 CD-1320 CD , , , Another important issue to consider is the amount of actuator closing torque available. To size an actuator, divide the rated torque from the actuator by the required closing torque of the damper for the given conditions from Table 5. Pressure Drop Figure 14: Recommended Pressure/Velocity Limits Figure 14 indicates the recommended velocity and pressure limits at various damper widths. Note: Figure 15: Pressure Drop The pressure drop is the same for all models due to identical frame construction. 6 Introduction to Johnson Controls Dampers Product Bulletin

7 Free Area Ratio Table 6 provides the free area ratio of Johnson Controls damper product families. Free area is the nominal area x free area ratio where nominal area = W x H of the damper frame. Table 6: Free Area Ratio Height Width, in. (cm) in. (cm) 8 (20) 12 (30) 16 (41) 20 (51) 24 (61) 28 (71) 32 (81) 36 (91) 40 (102) 44 (112) 48 (122) 6 (15) (36) (56) (76) (97) (107) (127) (148) (168) (188) (193) Coupled Panels Panels can be coupled to create larger damper banks. Such damper banks require special consideration: Are reinforcements needed? Some form of reinforcement, cross-bracing, or structural support should be installed for dampers subjected to high pressures or high air velocities. Refer to the CD-1300 Installation Instructions Control Dampers Only Installation Bulletin (LIT , Rev A). It is recommended that Support Bars (DMPR-KC200) be used for extra support at the intersection of four dampers. Are the damper sections correctly aligned? Each section must be vertically and horizontally aligned. If necessary, install shims to bring each section into alignment. For versatility and ease of ordering, multiple-section dampers are available for sizes up to 192 inches wide and 228 inches high. Multiple-section dampers are available in 1 inch increments only. Vertical coupling kits (DMPR-KC100) will be provided for sections greater than 76 inches high. All dampers are shipped as individual panels for field coupling. Figure 16: Multiple-Section Dampers Introduction to Johnson Controls Dampers Product Bulletin 7

8 Balancing Dampers BD-1300 Dampers come in a variety of sizes to meet different balancing application and environmental requirements. These include: volume (air) control applications, which regulate airflow pressure control applications, which maintain a constant pressure can be used in manual or motorized applications The BD-1300 Balancing Damper is the same frame and blade as a CD-1310 but has no seals and is not leakage rated. These dampers have no seals which requires less torque and therefore a smaller actuator may be used. Smoke Dampers A smoke damper is: intended to restrict the spread of smoke in HVAC systems that are designed to be automatically shut down in the event of a fire, or intended to control the movement of smoke within a building when the HVAC system is operational in engineered smoke control systems a 2-position control only SD-1320 Smoke Dampers meet UL Class II (leakage less than 20 cfm/sq ft at 4 inch W.C.) at 250 F (121 C) with acetal bearings, and 350 F (177 C) with bronze bearings. SD-1330 Smoke Dampers meet UL Class I (leakage less than 8 cfm/sq ft at 4 inch W.C.) at 250 F (121 C) with acetal bearings, and 350 F (177 C) with bronze bearings. Standard mechanically joined frames, double-piece and airfoil blades, are used in the construction of smoke dampers. This provides more cost-effective construction and keeps system performance characteristics the same as our control dampers. Smoke&Control Dampers Figure 17: Smoke Damper with Electric Actuator The SD-1320 and SD-1330 Smoke Dampers are designed to restrict the flow of smoke in the ductwork. These UL/cUL leakage rated dampers are listed under UL-555S Standard, dated May 1995, and are California State Fire Marshal listed. Electric and pneumatic actuators, UL tested and approved with the damper as a matched set, are factory assembled. Single-section dampers up to 48 inches wide x 76 inches high (122 x 193 cm) are approved for vertical or horizontal mounting. Figure 18: Smoke&Control Damper with Pneumatic Actuator The SD-1320 and SD-1330 Smoke&Control Dampers are designed to restrict the flow of smoke in the ductwork and operate as volume control dampers. These UL/cUL leakage rated dampers are listed under UL-555S Standard, dated May 1995, and are California State Fire Marshal listed. 8 Introduction to Johnson Controls Dampers Product Bulletin

9 SD-1300 Series Smoke&Control Dampers are also suitable for volume control. Pneumatic actuators, UL tested and approved for 100,000 cycles with the damper as a matched set, are factory assembled. Single-section dampers up to 48 inches wide x 76 inches high (122 x 193 cm) are approved for vertical or horizontal mounting. A Smoke&Control Damper is: intended to restrict the spread of smoke in HVAC systems that are designed to be automatically shut down in the event of a fire, or intended to control the movement of smoke within a building when the HVAC system is operational in engineered smoke control systems also suitable for proportional temperature and pressure control applications SD-1320 Smoke Dampers meet UL Class II (leakage less than 20 cfm/sq ft at 4 inch W.C.) at 250 F (121 C) with acetal bearings, and 350 F (177 C) with bronze bearings. SD-1330 Smoke Dampers meet UL Class I (leakage less than 8 cfm/sq ft at 4 inch W.C.) at 250 F (121 C) with acetal bearings, and 350 F (177 C) with bronze bearings. Standard mechanically joined frames, double-piece and airfoil blades, are used in the construction of Smoke&Control Dampers. This provides more cost-effective construction and keeps system performance characteristics the same as Johnson Controls control dampers. Fire Dampers Figure 19: Fire Damper Components A fire damper interrupts airflow automatically through part of an air system to restrict the passage of flame. Installed in a fire-rated wall or floor, the fire damper closes automatically in the event of a fire in order to maintain the integrity of the fire-rated separation. The FD /2 Hour Fire-rated Damper is designed to limit fire migration and maintain the integrity of the fire wall it is installed in, and to restrict airflow (oxygen) in the ductwork in fire situations. These dynamically tested fire-rated dampers are UL/cUL Listed under UL-555 Standard, dated May 1995, and are California State Fire Marshal listed. The spring on the FD-1300 provides the torque required to close and hold the damper blades against an airstream velocity of 3500 fpm at 8 inches W.C. static pressure in either direction of airflow. The damper is not designed to reopen except through manual intervention once the fusible link melts. If the temperature in the system climbs above 165 F (74 C), the fusible link will melt allowing the high-torque spring to close and lock the damper blades. 212 F (100 C) fusible link is optional. Single-section fire dampers are approved for the following: vertical mounting in walls made of masonry or gypsum wallboard with metal or wood studs up to 32 inches wide x 48 inches high (81 x 122 cm) horizontal mounting in cement floors up to 32 inches wide x 36 inches high (81 x 91 cm) Introduction to Johnson Controls Dampers Product Bulletin 9

10 Light Duty Dampers Table 7: LD-1800 Specifications Description 1 inch WG static pressure 4 inch WG static pressure Leakage (all sizes) 15 cfm 25 cfm Operational Torque 5 in lb 5 in lb Temperature Rating Approximate Weights (all sizes) -20 F to 200 F (-29 C to 93 C) 2.5 lb (1.13 kg) Table 8: LD-1800 Free Area Ratio Height, Width, inches inches Figure 20: LD-1800 Johnson Controls Light Duty Control Dampers are used in small ducts where maximum flow is required. Damper frames are constructed of formed, mechanically joined 18-gauge galvanized steel. Compressible spring stainless steel side seals are provided. Round Damper Construction Blade Shroud Damper blades are constructed with 16-gauge galvanized steel and have closed-cell polyurethane foam tape seals and a 5/16 inch round blade pin. Damper performance is designed for shutoff against a 6 inch pressure differential. Damper sealing force at 3 inches differential does not exceed 5 inch pounds per square foot. LD-1800 Dampers are ordered using the standard ordering system. LD-1800 Dampers are only available in 1 inch increments. Example: LOFNS-040 x 040 (4 inch W x 4 inch H) LOFNS-070 x 070 (7 inch W x 7 inch H) A 1/2 inch diameter shaft adapter is available. Seal Nylon Washer Shaft Figure 21: Round Damper Components The round damper consists of five major components: Shroud--provides structural support Blade--provides the proper resistance to airflow Shaft--drives the blade to position Washer--provides support for blade movement on diameters larger than 8 inches Seals--prevents airflow when blade is closed After rolling and forming, the shroud is mechanically joined for strength. 10 Introduction to Johnson Controls Dampers Product Bulletin

11 Damper Systems The manufacturer s published data is collected with the damper in a test environment, under controlled conditions. When dampers are affected by their surroundings, the published data will not always reflect the performance of the damper in an actual installation. The following factors affect the performance of dampers: Inlet and outlet conditions--certain conditions cause air currents which can adversely affect damper performance: - overhangs - projections - obstructions - adjacent walls - turbulence from a nearby discharge fan Damper location--the air entering the damper should be distributed evenly across the face of the damper, and the air leaving the damper should not be restricted. Take into consideration: - the nearness of duct elbows, both upstream and downstream from the damper - the location of the next damper Flow characteristics--the resistance offered by a parallel blade damper differs significantly from the resistance offered by an opposed blade damper. Damper authority--the impact of the damper on total system performance. See the Damper Engineering section of the Damper and Actuator Product Guide (FAN 268.1) for additional information. In-duct obstructions--some common in-duct obstructions include: - actuators - jackshaft assemblies - sensing devices - switching devices - structural supports - filters Installation quality--some common in-duct obstructions include: - squareness - proper installation per guidelines Damper Application Examples As stated earlier, dampers are used to control volume (air), pressure, or temperature. Volume Control Dampers Damper Regulates Air to Branch Figure 22: Volume Control Application A volume control damper regulates the flow of air, as shown in Figure 22. Common applications include: Isolating damper--this damper regulates the flow of air in branches of a duct system. This type of damper is either fully open or fully closed. The damper usually has seals to lower the leakage rate in the fully closed position. Modulation damper--unlike the isolating damper, the modulating damper must be able to hold the damper blades at a specified position to limit airflow. Fan inlet damper--either parallel or opposed blade dampers can be used to control the airflow rate to the fan--usually installed in an inlet box at the suction of the fan. Fan outlet damper--as with the fan inlet box damper, either parallel or opposed blade dampers can be used to provide proper control. Temperature Control Dampers Figure 23: Temperature Control Application Temperature control dampers operate as pairs, working together to maintain a predetermined temperature set point. The dampers simultaneously regulate two different airstreams, each having a different temperature. Introduction to Johnson Controls Dampers Product Bulletin 11

12 Temperature and Volume Control Dampers Figure 24: Pressure Control Application Control dampers can be used to control the temperature as well as maintain a constant volume of air. Figure 24 shows a typical mixed air control application. Dampers A and B work together to maintain a constant mixed-air temperature of air entering the coil. This is usually called the mixed air temperature. When these dampers are sized properly, they will also maintain a constant volume of air to the coil for all damper positions. Damper C will normally be controlled with Damper A with a common signal but in special cases, volume control can also be achieved by modulating Damper A with a control signal independent of Damper C. BD-1300: each panel is available in 1 inch increments from 8 to 48 inches in width and 6 to 76 inches in height. SD-1320: available in 1 inch increments from 10 to 48 inches in width and from 10 to 76 inches in height. SD-1330: available in 1 inch increments from 18 to 48 inches in width and from 10 to 70 inches in height. FD-1300: available in 1 inch increments from 10 to 32 inches in width and 10 to 48 inches in height for vertical mounting, and from 10 to 32 inches in width and 10 to 36 inches in height for horizontal mounting. LD-1800: available in 1 inch increments from 4 to 7 inches in width and 4 to 7 inches in height. RD-2000: available in 1 inch increments from 4 to 10 inches in diameter and 2 inch increments from 10 to 16 inches in diameter. Dimensional Information The damper is selected width x height, width dimension is listed first. All dimensions are from the outside of the frame. CD-1310: each panel is available in 1 inch increments from 8 to 48 inches in width and 6 to 76 inches in height. CD-1320: each panel is available in 1 inch increments from 8 to 48 inches in width and 6 to 76 inches in height. CD-1330: each panel is available in 1 inch increments from 8 to 48 inches in width and 7 to 76 inches in height. Note: Figure 25: Mounting Dimensions, inches Actual damper size will be less than width and height ordered. The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. Controls Group E. Michigan Street FAN P.O. Box 423 Damper and Actuator Product Guide Milwaukee, WI Printed in U.S.A. 12 Introduction to Johnson Controls Dampers Product Bulletin

SD-1250 and SD-1600 Series Smoke Dampers

SD-1250 and SD-1600 Series Smoke Dampers SD-1250 and SD-1600 Series Smoke Dampers Product Bulletin Code No. LIT-1201592 Issued January 30, 2014 Supersedes October 14, 2013 Johnson Controls provides a leakage-rated damper for life safety smoke

More information

RD-2000 Round Control Dampers

RD-2000 Round Control Dampers RD-000 Round Control Dampers Product Bulletin Code No. LIT-8105 Issued February 5, 010 Supersedes July, 009 Johnson Controls provides top-quality, low-leakage RD-000 Round Control Dampers for use in Heating,

More information

BD-1600 Balancing/Zone Control Damper

BD-1600 Balancing/Zone Control Damper BD-1600 Balancing/Zone Control Damper Product Bulletin Code No. LIT-12012355 Issued September 2016 Refer to the QuickLIT website for the most up-to-date version of this document. The BD-1600 Balancing/Zone

More information

VD-1600 Series Volume Control Dampers

VD-1600 Series Volume Control Dampers VD-1600 Series Volume Control Dampers Product Bulletin VD-1600 Code No. LIT-1201735 Issued April 2017 Refer to the QuickLIT website for the most up-to-date version of this document. Since 1885, Johnson

More information

RM-1200 Slim Round Control Damper

RM-1200 Slim Round Control Damper RM-1200 Slim Round Control Damper Product Bulletin Code No. LIT-12011358 Issued June 16, 2008 Since 1905, Johnson Controls has developed and refined air control products by providing the highest quality

More information

ID-141x 12-Gauge Hat Channel Industrial Damper

ID-141x 12-Gauge Hat Channel Industrial Damper ID-141x 12-Gauge Hat Channel Industrial Damper Product Bulletin Code No. LIT-12011355 Issued June 12, 2013 Supersedes March 13, 2012 Since 1905, Johnson Controls has developed and refined air control products

More information

RA-2000 Airflow Measuring System

RA-2000 Airflow Measuring System RA-2000 Airflow Measuring System Product Bulletin Code No. LIT-1201677 Issued May 2016 Refer to the QuickLIT website for the most up-to-date version of this document. Since 1905, Johnson Controls has provided

More information

PC-125x Counter-Balanced Backdraft Damper

PC-125x Counter-Balanced Backdraft Damper PC-15x Counter-Balanced Backdraft Damper Product Bulletin Code No. LIT-101180 Issued April 7, 015 Refer to the QuickLIT Web site for the most up-to-date version of this document. Since 1885, Johnson Controls

More information

AD-1250 Airflow Measuring Station

AD-1250 Airflow Measuring Station AD-1250 Airflow Measuring Station Product Bulletin Code No. LIT-12011472 Issued March 2016 Refer to the QuickLIT website for the most up-to-date version of this document. The AD-1250 Airflow Measuring

More information

B. Fabricate in accordance with ASHRAE handbooks and SMACNA duct manuals. A. Submit in accordance with Division-1 and Section

B. Fabricate in accordance with ASHRAE handbooks and SMACNA duct manuals. A. Submit in accordance with Division-1 and Section SECTION 15910 DUCT ACCESSORIES PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of Contract including General and Supplementary Conditions, Division-1 Specification Sections,

More information

Insulated Control Damper. 1/2 in. (13mm) 1/2 in. (13mm) 12 x 12 (305 x 305) 8 x 12 (203 x in. W x 120 in. H (3658mm x 3048mm) 5 in.

Insulated Control Damper. 1/2 in. (13mm) 1/2 in. (13mm) 12 x 12 (305 x 305) 8 x 12 (203 x in. W x 120 in. H (3658mm x 3048mm) 5 in. R Application and Design The is a low leakage thermally insulated damper with extruded airfoil blades. features thermally broken frame and blade to eliminate the transfer of heat or cold penetration and

More information

Insulated Control Damper. 12 x 7 (305 x 178) 8 x 7 (203 x 178)

Insulated Control Damper. 12 x 7 (305 x 178) 8 x 7 (203 x 178) R Application and Design The is a low leakage thermally insulated damper with extruded airfoil blades. features thermally broken blade to eliminate the transfer of heat or cold penetration and reduced

More information

HCD-135. Industrial Control Damper. Application and Design. Ratings (see page 2 and 3 for specific limitations) Standard Construction.

HCD-135. Industrial Control Damper. Application and Design. Ratings (see page 2 and 3 for specific limitations) Standard Construction. Application and Design Model is a heavy duty industrial control damper with a flanged frame. It is designed to control airflow and provide shut off in HVAC or industrial process control systems. A variety

More information

B. Base occupied space sound level estimates on ARI 885. C. Terminal heating coils shall conform to ARI 410.

B. Base occupied space sound level estimates on ARI 885. C. Terminal heating coils shall conform to ARI 410. PART 1 - GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

HCD-230 Industrial Control Damper

HCD-230 Industrial Control Damper Application and Design Model is a heavy duty industrial control damper with a flanged frame. It is designed to control airflow and provide shut off in HVAC or industrial process control systems. A variety

More information

AD-1251 Probe with Differential Pressure Transducer

AD-1251 Probe with Differential Pressure Transducer AD-1251 Probe with Differential Pressure Transducer Product Bulletin Code No. LIT-12011473 Issued October 31, 2011 Supersedes September 6, 2011 The AD-1251 Probe with Differential Pressure Transducer (DPT)

More information

Positive Seal Damper Blades with Vinyl Gaskets 2.5" SERIES 3000 SIDE MOUNT - NO FLANGE ORDERING METHOD FOR BACKDRAFT & MOTORIZED BACKDRAFT DAMPERS

Positive Seal Damper Blades with Vinyl Gaskets 2.5 SERIES 3000 SIDE MOUNT - NO FLANGE ORDERING METHOD FOR BACKDRAFT & MOTORIZED BACKDRAFT DAMPERS BACKDRAFT DAMPERS BLADE OPTION: SR: 0.016-0.020 roll formed aluminum with vinyl gasket - used with fan motors under 1 HP SE: 0.05 extruded aluminum with vinyl gasket - used with fan motors over 1 HP Positive

More information

FSD60, FSD60LP CoMBINAtIoN FIRe AND SMoKe DAMPeR

FSD60, FSD60LP CoMBINAtIoN FIRe AND SMoKe DAMPeR 3900 Dr. Greaves Rd. Kansas City, MO 64030 (816) 761-7476 FAX (816) 765-8955 FSD60, FSD60LP CoMINAtIoN FIRe AND SMoKe DAMPeR 1 1 /2 HoUR UL555 RAteD, UL555S LeAKAge CLASS 1 APPLICAtIoN Ruskin FSD60 Series

More information

Thermal Isolation. Break

Thermal Isolation. Break Application and Design The is a low leakage thermally insulated damper with extruded airfoil blades. features thermally broken frame and blade will minimize the transfer of thermal energy and reduces condensation.it

More information

Insulated Control Damper. 1/2 in. (13mm) 1/2 in. (13mm) 12 x 12 (305 x 305) 8 x 12 (203 x 305) 5 in. (127mm) Parallel

Insulated Control Damper. 1/2 in. (13mm) 1/2 in. (13mm) 12 x 12 (305 x 305) 8 x 12 (203 x 305) 5 in. (127mm) Parallel Application and Design The is a low leakage thermally insulated damper with extruded airfoil blades. features thermally broken frame and blade to eliminate the transfer of heat or cold penetration and

More information

Baked Enamel, Epoxy, Hi Pro Polyester, Industrial Epoxy, Kynar/Hylar (70%) Permatector. Single or Reverse Flange 8 x 6 (203 x 178)

Baked Enamel, Epoxy, Hi Pro Polyester, Industrial Epoxy, Kynar/Hylar (70%) Permatector. Single or Reverse Flange 8 x 6 (203 x 178) Application and Design The is an extremely low leakage damper designed to meet the highest standards established for commercial control dampers. The is intended for application in medium to high pressure

More information

DAMPERS FOR COMMERCIAL & INDUSTRIAL APPLICATIONS IN HEATING, VENTILATING & AIR CONDITIONING

DAMPERS FOR COMMERCIAL & INDUSTRIAL APPLICATIONS IN HEATING, VENTILATING & AIR CONDITIONING PUB. NO. 732-3 DAMPERS FOR COMMERCIAL & INDUSTRIAL APPLICATIONS IN HEATING, VENTILATING & AIR CONDITIONING The most widely used dampers in commercial HVAC applications Control Dampers - Extruded Aluminum

More information

Fire, Smoke, and Combination Fire Smoke Dampers

Fire, Smoke, and Combination Fire Smoke Dampers Fire, Smoke, and Combination Fire Smoke Dampers Installation/Configuration Fire Dampers Smoke Dampers Agenda Combination Fire/Smoke Dampers Operational Test/Inspection Periodic Test/Maintenance Damper

More information

Thermal Isolation Break. Frame Type Channel Quick Connect Single or Reverse Flange Blade Action Parallel Opposed Parallel Opposed Parallel Opposed

Thermal Isolation Break. Frame Type Channel Quick Connect Single or Reverse Flange Blade Action Parallel Opposed Parallel Opposed Parallel Opposed Application The is a low leakage thermally insulated damper with extruded airfoil blades. features broken blade which minimized the transfer of thermal energy and reduce condensation. It s also IECC (International

More information

FSD36, FSD36LP COMBINATION FIRE AND SMOKE DAMPER 1 1 /2 HOUR UL555 RATED, UL555S LEAKAGE CLASS 2

FSD36, FSD36LP COMBINATION FIRE AND SMOKE DAMPER 1 1 /2 HOUR UL555 RATED, UL555S LEAKAGE CLASS 2 3900 Dr. Greaves Rd. Kansas City, MO 64030 (816) 761-7476 FAX (816) 765-8955 FSD36, FSD36LP COMINATION FIRE AND SMOKE DAMPER 1 1 /2 HOUR UL555 RATED, UL555S LEAKAGE CLASS 2 APPLICATION Ruskin FSD36 Series

More information

Model VCD-18. Ratings. Blade Operation. Size Limitations. Features & Options

Model VCD-18. Ratings. Blade Operation. Size Limitations. Features & Options Application and Design The series is a general purpose, low leakage control damper intended for application in low pressure and velocity systems. atings Pressure: 2 in. wg (.5 kpa) - pressure differential.

More information

AMCA MEMBER. American Warming and Ventilating. A Mestek Company. Quality Air Control Dampers

AMCA MEMBER. American Warming and Ventilating. A Mestek Company. Quality Air Control Dampers AMCA MEMBER American Warming and Ventilating A Mestek Company Quality Air Control Dampers Over a century of dedication to quality products and customer satisfaction has enabled American Warming and Ventilating

More information

Model DFD-230 Multi-Blade Fire Damper Steel 3V Blades UL555 3 Hour Fire Resistance Rating

Model DFD-230 Multi-Blade Fire Damper Steel 3V Blades UL555 3 Hour Fire Resistance Rating Application Model is a multi-blade fire damper with 3V style blades. The has been qualified to 4000 fpm (20.3 m/s) and 10 in. wg (2.5 kpa) for dynamic closure in emergency fire situations. Model may be

More information

Model SMD-302M. Modulating Smoke Damper. Application. Steel Airfoil Blades UL 555S Leakage Class II. Ratings. Size Limitations.

Model SMD-302M. Modulating Smoke Damper. Application. Steel Airfoil Blades UL 555S Leakage Class II. Ratings. Size Limitations. Model Application The is a leakage rated modulating smoke damper with airfoil blades for operational closure in emergency smoke control situations. This model serves the function of both a control damper

More information

VCD-23. Flange Options. Size Limitations

VCD-23. Flange Options. Size Limitations Application and Design The series is a ruggedly built low leakage control damper intended for application in low to medium pressure and velocity systems. A wide range of electric and pneumatic actuators

More information

Model CFSD-211. Corridor Ceiling FIRE SMOKE DAMPER Steel 3V Blades UL 555S Leakage Class I

Model CFSD-211. Corridor Ceiling FIRE SMOKE DAMPER Steel 3V Blades UL 555S Leakage Class I Application and Design Model is a combination fire smoke damper that is UL classified to protect corridor ceiling penetrations as required by the Uniform Building Code. This model s operational ratings

More information

Damper Accessory Kits

Damper Accessory Kits _daskits p; 1923185 9thcc:n/a Dampers Accessories Rev: 08/20/98 logo: standard Damper Accessory Kits left ft: undefnd right ft: standard Sect# = 0 seq# = 13 Control Dampers It is recommended that each

More information

CONTROL DAMPERS. Models 1810 & Model Model Model 1370

CONTROL DAMPERS. Models 1810 & Model Model Model 1370 CONTROL DAMPERS CONTROL DAMPERS MODELS 1810 & 1820 MANUAL ALANCING DAMPERS STEEL Models 1810 and 1820 have been engineering and designed for manual balancing applications in low to medium pressure and

More information

Centrifugal Cabinet Fans Model BCF. Belt Drive Low-Profile

Centrifugal Cabinet Fans Model BCF. Belt Drive Low-Profile Centrifugal Cabinet s BCF Belt Drive Low-Profile November 204 BCF Centrifugal Cabinet Contents Standard Construction Features... 3 Options and Accessories... 4 Filter and Mixing Box Data... 5 Typical Installations...

More information

FBV-43. Vertical Face & Bypass Control Damper Ultra Low Leakage Aluminum Frame Construction. Application and Design. Size Limitations.

FBV-43. Vertical Face & Bypass Control Damper Ultra Low Leakage Aluminum Frame Construction. Application and Design. Size Limitations. Application and Design The is a vertical style face and bypass low leakage damper. This model is intended for application in medium to high pressure and velocity systems. Smooth profile extruded aluminum

More information

Model FSD-211. Application. Combination Fire Smoke Damper Steel 3V Blades UL 555S Leakage Class I UL /2 Hour Fire Resistance Rating.

Model FSD-211. Application. Combination Fire Smoke Damper Steel 3V Blades UL 555S Leakage Class I UL /2 Hour Fire Resistance Rating. Application Model is a combination fire smoke damper with 3V style blades. This model is designed for operation and dynamic closure in emergency fire smoke situations. It is rated for airflow and leakage

More information

XeteX, Inc. All Rights Reserved.

XeteX, Inc. All Rights Reserved. Model XC Indoor or outdoor mounted, simple, in-case aluminum flat plate exchanger with options for frost control. Ideal for inline installations: in duct-work systems, in built-up units, or in modular

More information

Model FSD-331. Combination Fire Smoke Dampers. Application. Ratings. Features

Model FSD-331. Combination Fire Smoke Dampers. Application. Ratings. Features Application Model is a high performance combination fire smoke damper with Class I leakage. High strength airfoil blades ensure the lowest resistance to airflow in HVAC systems with velocities to 4000

More information

Air Measuring Products AMD AMS IAQ

Air Measuring Products AMD AMS IAQ Air Measuring Products AMD AMS IAQ January 1 2012 Air Measuring Products Why is outside air measurement important? There are many significant benefits to monitoring outside air volumes. By measuring the

More information

Model FSD-331 Combination Fire Smoke Dampers

Model FSD-331 Combination Fire Smoke Dampers R APPLICATION Model is a high performance combination fire smoke damper with class I leakage. High strength airfoil blades ensure the lowest resistance to airflow in HVAC systems with velocities to 4000

More information

D-4070 Two Stage Pneumatic Actuator

D-4070 Two Stage Pneumatic Actuator FANs 268.1, 1628.3 Product/Techncial Bulletin D4070 Issue Date 1095 D-4070 Two Stage Pneumatic Actuator The D-4070 Two Stage Pneumatic Actuator is a multipurpose positioning device used to accurately position

More information

AMD-42-TD. Thermal Dispersion Air Measuring Station with VCD-42 Control Damper. Application and Design. Ratings. Features and Control Options

AMD-42-TD. Thermal Dispersion Air Measuring Station with VCD-42 Control Damper. Application and Design. Ratings. Features and Control Options Application and Design Thermal Dispersion Air Measuring Station with VCD-42 Control Damper The combines the functionality of a highly accurate thermal dispersion airflow measuring station and a low leakage

More information

Centrifugal Cabinet Fans Model BCF Belt Drive Low-Profile

Centrifugal Cabinet Fans Model BCF Belt Drive Low-Profile Centrifugal Cabinet s BCF Belt Drive Low-Profile May 2007 BCF Belt Drive Cabinet s Greenheck belt drive low-profile cabinet fans, BCF, are designed for efficiency and reliability in supply, exhaust or

More information

Model VCD-40. Extruded Airfoil Blade Control Damper Narrowline Frame Construction. Application. Ratings. Flange Options.

Model VCD-40. Extruded Airfoil Blade Control Damper Narrowline Frame Construction. Application. Ratings. Flange Options. Model Application The is a low leakage high performance control damper with extruded aluminum airfoil blades. Blades are completely contained within the frame allowing the damper to be directly mounted

More information

SECTION CONTROL DAMPERS

SECTION CONTROL DAMPERS SECTION 23 09 13.43 - CONTROL DAMPERS PART I - GENERAL 1.1 SECTION INCLUDES A. Airfoil Dampers, Heavy Duty Galvanized Steel B. Thermally Insulated Dampers, Heavy Duty Galvanized Steel C. Airfoil Dampers,

More information

Series HCD Airfoil Control Damper

Series HCD Airfoil Control Damper Series HCD Airfoil Control Damper Model: HCD-1 The Holyoake HCD-1 is a precisely made volume and pressure control device with extremely low leakage when closed, (in the range of 0.003m 3 /s at 100 Pa).

More information

AMD-42V Air Measuring Station with VCD-42V Control Damper

AMD-42V Air Measuring Station with VCD-42V Control Damper Application and Design Construction Standard Optional Frame Material Galvanized Steel - Frame Material Thickness 16 ga. (1.5mm) 12 ga. (2.7mm) 14 ga. (2mm) Frame Type 5 in. x 1 in. hat channel - Blade

More information

AMD-42 Air Measuring Station with VCD-42 Control Damper

AMD-42 Air Measuring Station with VCD-42 Control Damper Application and Design W x H Construction Standard Optional Frame Material Galvanized Steel - Frame Material Thickness External Minimum Size 16 ga. (1.5mm) Internal Single Section Maximum Size Multiple

More information

WD-300 Series. Backdraft Damper Vertical Mount - Horizontal Airflow. Application and Design. Ratings. Frame Styles. Size Limitations.

WD-300 Series. Backdraft Damper Vertical Mount - Horizontal Airflow. Application and Design. Ratings. Frame Styles. Size Limitations. Application and Design The WD300 series dampers are designed to prevent reverse airflow in horizontal exhaust applications. The WD300 features a pressure sensitive blade design that opens and remains open

More information

FOR USE IN SOLUTION AIR HANDLING UNITS

FOR USE IN SOLUTION AIR HANDLING UNITS AMS-60 AIRFLOW MONITORING DEVICE APPLICATION GUIDE Supersedes: NOTHING Form 102.20-AG1 (303) FOR USE IN SOLUTION AIR HANDLING UNITS GENERAL The YORK AMS-60 is an airflow monitoring device which combines

More information

Control Dampers and Fire Dampers. Volume 1 - March Insulated Control Dampers. Non-Insulated Control Dampers. Framing. Accessories.

Control Dampers and Fire Dampers. Volume 1 - March Insulated Control Dampers. Non-Insulated Control Dampers. Framing. Accessories. Insulated Control Dampers 2 Volume 1 - March 2010 6 Non-Insulated Control Dampers 8 Framing Accessories 9 Jack Shaft Steel Control Dampers Fire Dampers 10 11 Control Dampers and Fire Dampers 3900 Insulated

More information

Section Va: Valve Actuators

Section Va: Valve Actuators Valve and Actuator Manual 977 Actuator Basics and Sizing Information Section Engineering Data Book Va Issue Date 0592 Section Va: Valve Actuators Pneumatic Actuators Page 3 Electric Actuators 5 Maximum

More information

SMD-201M. Application. Modulating Smoke Dampers Steel 3V Blades UL 555S Leakage Class I. Ratings. Operational Rating. Size Limitations.

SMD-201M. Application. Modulating Smoke Dampers Steel 3V Blades UL 555S Leakage Class I. Ratings. Operational Rating. Size Limitations. Application Model is a leakage rated modulating smoke damper with 3V style blades. The has been qualified to 2,000 fpm (10.2 m/s) and 6 in. wg (1.5 kpa) for operational closure in emergency smoke control

More information

Model VCD-20. Control Damper. Application. 3V Blade. Ratings. Flange Options. Size Limitations. Blade Operation. Features and Options

Model VCD-20. Control Damper. Application. 3V Blade. Ratings. Flange Options. Size Limitations. Blade Operation. Features and Options Application The series is a general purpose control damper for applications as an automatic control or manual balancing damper with low to medium pressure and velocity systems. A wide range of electric

More information

Model VCD-43 Extruded Airfoil Blade Control Damper

Model VCD-43 Extruded Airfoil Blade Control Damper Application and Design The is an extremely low leakage damper designed to meet the highest standards established for commercial control dampers. The is intended for application in medium to high pressure

More information

ARROW INDUSTRIAL PRODUCTS

ARROW INDUSTRIAL PRODUCTS IP-2R ARROW INDUSTRIAL PRODUCTS For Applications in Industrial, Power Plant & Commercial Projects ARROW UNITED INDUSTRIES ARROW UNITED INDUSTRIES has specialized in the manufacturing of air control products

More information

DRUM LOUVERS DRUM LOUVERS 45DL SERIES. Models: 45DL1 Single Vanes 45DL2 Split Vanes G151 HIGH CAPACITY LONG THROW ALUMINUM CONSTRUCTION

DRUM LOUVERS DRUM LOUVERS 45DL SERIES. Models: 45DL1 Single Vanes 45DL2 Split Vanes G151 HIGH CAPACITY LONG THROW ALUMINUM CONSTRUCTION DRUM LOUVERS 45DL SERIES HIH CAPACITY LON THROW ALUMINUM CONSTRUCTION Models: Single Vanes 45DL2 Split Vanes Suffix '-O' adds a steel opposed blade damper Models -O and 45DL2 Model Series 45DL Drum Louvers

More information

Model FSD-211. Combination FIRE SMOKE DAMPERS Steel 3-V Blades UL 555S Leakage Class I UL Hour Fire Resistance Rating

Model FSD-211. Combination FIRE SMOKE DAMPERS Steel 3-V Blades UL 555S Leakage Class I UL Hour Fire Resistance Rating R APPLICATION Model FSD-211 is a combination fire smoke damper with 3V style blades. The FSD-211 has been qualified to 2000 fpm (10.2 m/s) and 6 in. wg (1.5 kpa) for operation and dynamic closure in emergency

More information

Model SSFSD-211. Combination Fire Smoke Damper 304 Stainless Steel 3V Blades UL 555S Leakage Class I UL Hour Fire Resistance Rating

Model SSFSD-211. Combination Fire Smoke Damper 304 Stainless Steel 3V Blades UL 555S Leakage Class I UL Hour Fire Resistance Rating R Model Application Model is a 304SS combination fire smoke damper with 3V style blades. The is qualified to 2,000 fpm (10.2 m/s) and 6 in. wg (1.5 kpa). This damper may be installed vertically (with blades

More information

Centrifugal Roof Supply Fans Models RSF and RSFP. Forward Curved

Centrifugal Roof Supply Fans Models RSF and RSFP. Forward Curved Centrifugal Roof Supply Fans Models and Forward Curved April 2008 Centrifugal Filtered Roof Supply Fan When you buy a Greenheck model or, you receive a fan with the industry s best performance and durability

More information

Model SMD-301. Smoke Damper Steel Airfoil Blades UL 555S Leakage Class I. Application. Ratings. Size Limitations. Features

Model SMD-301. Smoke Damper Steel Airfoil Blades UL 555S Leakage Class I. Application. Ratings. Size Limitations. Features Model Application The is a leakage rated smoke damper with airfoil blades for operational closure in emergency smoke control situations. This model serves the function of both a control damper and smoke

More information

SECTION DUCTWORK ACCESSORIES

SECTION DUCTWORK ACCESSORIES SECTION 15910 DUCTWORK ACCESSORIES PART 1- GENERAL SCOPE This sections includes accessories used in the installation of duct systems. Included are the following topics: PART 1- GENERAL Related Work Reference

More information

VCD-43V. Vertical Airfoil Blade Control Damper. Application and Design. Ratings. Size Limitations. Features and Options: Pressure:

VCD-43V. Vertical Airfoil Blade Control Damper. Application and Design. Ratings. Size Limitations. Features and Options: Pressure: Application and Design is a low leakage damper with vertical blade orientation designed to meet the highest standards established for commercial control dampers. The is intended for application in medium

More information

For installation into ductwork

For installation into ductwork X X testregistrierung Non-return dampers Type For installation into ductwork Non-return dampers prevent unwanted airflows against the intended airflow direction when the system is not in operation Maximum

More information

Centrifugal Roof Supply Fans Models RSF and RSFP. Forward Curved

Centrifugal Roof Supply Fans Models RSF and RSFP. Forward Curved Centrifugal Roof Supply Fans Models and Forward Curved B U I L D I N G V A L U E I N A I R. April 2008 Centrifugal Filtered Roof Supply Fan When you buy a Greenheck model or, you receive a fan with the

More information

VCD-23 Low Leakage CONTROL DAMPER

VCD-23 Low Leakage CONTROL DAMPER Application and Design The series is a ruggedly built low leakage control damper intended for application in low to medium pressure and velocity systems. A wide range of electric actuators are available.

More information

Propeller Hooded Roof Fans

Propeller Hooded Roof Fans Propeller Hooded Roof Fans Series A - Model AE and AS Exhaust and Supply Fans August 8 Model AE and AS Propeller Fans Greenheck s models AE (axial exhaust) and AS (axial supply) spun aluminum direct drive

More information

ARROW UNITED INDUSTRIES

ARROW UNITED INDUSTRIES IP-3R ARROW UNITED INDUSTRIES Building Tomorrow s Ventilation Today Heavy Duty Dampers Industrial, Power Plant & Commercial Applications ARROW UNITED INDUSTRIES has specialized in the design and manufacturing

More information

MODEL TUB TUBEAXIAL UPBLAST PROPELLER ROOF EXHAUSTER

MODEL TUB TUBEAXIAL UPBLAST PROPELLER ROOF EXHAUSTER MODEL TUB MODEL FEATURES Exhaust air up to 60,116 CFM in static pressure applications up to 1 w.g. Straight-through air flow design results in maximum exhaust efficiency Motor and drives are located outside

More information

Model FSD-212. Combination FIRE SMOKE DAMPERS

Model FSD-212. Combination FIRE SMOKE DAMPERS R APPLICATION Model is a combination fire smoke damper with 3V style blades. The has been qualified to 2000 fpm (10.2 m/s) and 6 in. wg (1.5 kpa) for operation and dynamic closure in emergency fire smoke

More information

CENTRIFUGAL UPBLAST ROOF EXHAUSTERS Model VRBK

CENTRIFUGAL UPBLAST ROOF EXHAUSTERS Model VRBK CENTRIFUGAL UPBLAST ROOF EXHAUSTERS Model VRBK CENTRIFUGAL UPBLAST ROOF EXHAUSTERS COMMERCIAL KITCHEN APPLICATIONS Belt Driven Model VRBK DESIGNED AND ENGINEERED TO MEET INDUSTRY NEEDS The Carnes Company

More information

Model VCD-34. Low Leakage Insulated Airfoil CONTROL DAMPER. Ratings (See page 3 for specific limitations) Flange Options.

Model VCD-34. Low Leakage Insulated Airfoil CONTROL DAMPER. Ratings (See page 3 for specific limitations) Flange Options. Application and Design The Series is a ruggedly built low leakage control damper with thermally insulated blades. The is intended for application in medium pressure and velocity systems. This model also

More information

SafidDampers SPK Description. Standard Construction SPK ( Flange Type )

SafidDampers SPK Description. Standard Construction SPK ( Flange Type ) ( Flange Type ) SPK 30-300 Description SPK 30 - Series The single and multi-leaf s with extruded aluminum airfoil blades are designed for quite, efficient and reliable air volume control in air conditioning

More information

VCD-23. Low Leakage CONTROL DAMPER

VCD-23. Low Leakage CONTROL DAMPER Application and Design The series is a ruggedly built low leakage control damper intended for application in low to medium pressure and velocity systems. A wide range of electric and pneumatic actuators

More information

MODEL TXD DIRECT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER

MODEL TXD DIRECT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER MEL TXD Model Features Exhaust air up to 3,400 CFM in high static pressure applications up to 1-1/4 w.g. Attractive spun aluminum exterior Direct drive units have low sound levels and quiet operation Non-overloading

More information

The IAQ50 Air Damper/Monitor Installation and Maintenance Manual

The IAQ50 Air Damper/Monitor Installation and Maintenance Manual The IAQ50 Air Damper/Monitor Installation and Maintenance Manual RUSKIN MANUFACTURING 3900 Dr. Greaves Road Kansas City, Missouri 64030-1183 U.S.A. ! WARNING DO NOT TAMPER WITH (REMOVE, REPLACE, RELOCATE

More information

SMOKE DAMPERS SMOKE DAMPERS SMOKE DAMPERS

SMOKE DAMPERS SMOKE DAMPERS SMOKE DAMPERS SMOKE DAMPERS 96 97 SD SERIES SD for Use in Dynamic Systems Types Galvanized Steel Construction as Standard.. Sleeve Type, Model: SD - 0-00. Circular Type, Model: SD - 50-00. Oval Type, Model: SD - 60-00

More information

Metasys Zoning Package Overview

Metasys Zoning Package Overview Technical Bulletin Issue Date August 26, 2002 Metasys Zoning Package Overview Metasys Zoning Package Overview...2 Introduction... 2 Key Concepts... 3 Related Information... 3 Metasys Zoning Package Components...

More information

AMD-33 Air Measuring Station with VCD-33 Control Damper

AMD-33 Air Measuring Station with VCD-33 Control Damper Application and Design Construction Standard Optional Frame Material Galvanized Steel - Frame Material Thickness 16 ga. (1.5mm) 12 ga. (2.7mm) Frame Type 5 in. x 1 in. hat channel - Blade Material Galvanized

More information

VA-8020 Floating Valve Actuator

VA-8020 Floating Valve Actuator FANs 977, 1628.3 Product/Technical Bulletin VA-8020 Issue Date 0300 VA-8020 Floating Valve Actuator The VA-8020 synchronous motor-driven actuator provides floating (three wire) control of valves with up

More information

R-317 Air Flow Controller

R-317 Air Flow Controller 24-4660- 1, Rev. B Product Bulletin R-317 Issue Date February 2016 R-317 Air Flow Controller The R-317 Air Flow Controller is a proportional, direct acting, low volume output signal instrument designed

More information

CONTROL DAMPERS. Model Model 1370CB. Model 1380CB. Model 1390CB B7

CONTROL DAMPERS. Model Model 1370CB. Model 1380CB. Model 1390CB B7 CONTROL DAMPERS MODEL 1380 HIGH PERFORMANCE ACKDRAFT DAMPER EXTRUDED ALUMINUM HEAVY DUTY Model 1380 is a high performance extruded aluminum gravity operated backdraft damper for use in medium to heavy

More information

SINGLE DUCT TERMINAL UNITS

SINGLE DUCT TERMINAL UNITS www.igcaire.com SINGLE DUCT TERMINAL UNITS Direct Digital Control, Pressure Independent FEATURES 22 Gauge Galvanized Steel Casing Construction with a 20 Gauge Casing Option that Provides Strength and Product

More information

BULLETIN 456. July 1997 VANEAXIAL FANS. Type W Direct Drive/Belt Driven. Model VW Direct Drive. Model VWBD Belt Driven

BULLETIN 456. July 1997 VANEAXIAL FANS. Type W Direct Drive/Belt Driven. Model VW Direct Drive. Model VWBD Belt Driven BULLETIN 456 July 1997 VANEAXIAL FANS Type W Direct Drive/Belt Driven Model VW Direct Drive Model VWBD Belt Driven Aerovent certifies that the Type W Vaneaxial Fans shown herein are licensed to bear the

More information

Motorized Fire Dampers

Motorized Fire Dampers Model : OMFD-611 (Fusible link and spring return actuator) GI steel sheet construction In accordance with UL555 & UL555S suitable for installation in walls and partitions having rating 2 Hrs. Static and

More information

Document number AMS & AMD Damper Series for Honeywell Spyder Controller Installation, Operation, and Maintenance Instructions

Document number AMS & AMD Damper Series for Honeywell Spyder Controller Installation, Operation, and Maintenance Instructions Document number 480938 AMS & AMD Damper Series for Honeywell Spyder Controller Installation, Operation, and Maintenance Instructions Use this manual when AMS and AMD series dampers were purchased prior

More information

SMD-201. Application. Smoke Dampers Steel 3V Blades UL 555S Leakage Class I. Ratings. Operational Rating. Size Limitations.

SMD-201. Application. Smoke Dampers Steel 3V Blades UL 555S Leakage Class I. Ratings. Operational Rating. Size Limitations. Application Model is a leakage rated smoke damper with 3V style blades. The has been qualified to 2,000 fpm (10.2 m/s) and 6 in. wg (1.5 kpa) for operational closure in emergency smoke control situations.

More information

Model VCD-20V. 3V Vertical Control Damper. Application and Design. Ratings (See page 4 for specific limitations) Flange Options.

Model VCD-20V. 3V Vertical Control Damper. Application and Design. Ratings (See page 4 for specific limitations) Flange Options. Application and Design The series is a vertical blade general purpose damper for application as an automatic control or manual balancing damper. This model is intended for application in low to medium

More information

CENTRIFUGAL UPBLAST ROOF EXHAUSTERS Models VUDK and VUBK

CENTRIFUGAL UPBLAST ROOF EXHAUSTERS Models VUDK and VUBK CENTRIFUGAL UPBLAST ROOF EXHAUSTERS Models VUDK and VUBK CENTRIFUGAL UPBLAST ROOF EXHAUSTERS Direct and Belt Driven Models VUDK and VUBK DESIGNED AND ENGINEERED TO MEET INDUSTRY NEEDS The Carnes Company

More information

WD-200 Series. Model WD-220 Flange Opposite Motor. Model WD-210 Flange on Motor Side. Model WD-200 No Flange. Motorized Backdraft Damper.

WD-200 Series. Model WD-220 Flange Opposite Motor. Model WD-210 Flange on Motor Side. Model WD-200 No Flange. Motorized Backdraft Damper. Application The WD200 series are electrically motorized backdraft dampers that open when energized and spring return close when deenergized. The WD200 series are for horizontal or vertical mounting. Primary

More information

MODEL TXD DIRECT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER

MODEL TXD DIRECT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER MEL TXD MEL FEATURES Exhaust air up to 3,400 CFM in high static pressure applications up to 1-1/4 w.g. Attractive spun aluminum exterior Direct drive units have low sound levels and quiet operation Non-overloading

More information

M Remote Mounting Kit

M Remote Mounting Kit M9203-250 Remote Mounting Kit Installation Instructions M9203-250 Part No. 34-636-2324, Rev. Issued July 6, 2011 Applications The M9203-250 Remote Mounting Kit enables the M9203 Series Electric Spring

More information

VANEAXIAL & TUBEAXIAL FANS

VANEAXIAL & TUBEAXIAL FANS BULLETIN 482 July 2008 VANEAXIAL & TUBEAXIAL FANS Type "S" Belt Driven Featuring Welded Steel Propellers Models VSBD & TSBD Model TSBD Belt Driven Tubeaxial Type "S" Vaneaxial & Tubeaxial Fans For applications

More information

Model VCD-33. Low Leakage Airfoil CONTROL DAMPER. Flange Options. Blade Operation. Size Limitations

Model VCD-33. Low Leakage Airfoil CONTROL DAMPER. Flange Options. Blade Operation. Size Limitations Application and Design The series is an ultra low leakage damper with rugged steel airfoil blades designed to meet the highest standards established for commercial control dampers. The airfoil shape reduces

More information

VOLUME CONTROL & SHUT OFF DAMPERS SERIES 400

VOLUME CONTROL & SHUT OFF DAMPERS SERIES 400 SERIES 400 Series 900 Volume Control And Shut Off Dampers: Series 900 balancing and shut off dampers have been designed, engineered and tested, with smooth efficient operation as an important consideration.

More information

BAC, BAF, BAH Central Station Air Handlers

BAC, BAF, BAH Central Station Air Handlers PRODUCT DATA & INSTALLATION Bulletin B80-BA-PDI-5 Part # 1097717 PRODUCT SUPPORT web: b-rp.ca/bah email: ahu@b-rp.ca call: 1-844-893-3222 x527 scan: BAC, BAF, BAH Central Station Air Handlers Indoor and

More information

SECTION AIR TERMINAL UNITS

SECTION AIR TERMINAL UNITS SECTION 23 36 00 AIR TERMINAL UNITS PART 1 - GENERAL 1.1 SUMMARY A. Section includes constant volume terminal units, variable volume terminal units, dual duct terminal units, fan powered terminal units,

More information

AMD-33. Air Measuring Station with VCD-33 Control Damper. Application and Design. Features & Control Options

AMD-33. Air Measuring Station with VCD-33 Control Damper. Application and Design. Features & Control Options Application and Design The combines the functionality of an accurate airflow measuring station and a low leakage control damper into one compact assembly that both measures and regulates airflow volumes

More information

Laboratory Exhaust Systems

Laboratory Exhaust Systems Laboratory Exhaust Systems Vektor -MH and Vektor -MD Mixed Flow High Plume and High Plume Dilution Blower August 2013 Vektor-MH High Plume and High Plume Dilution Blower Greenheck s Vektor-MH high plume

More information

TSS Single-Duct VAV Terminals

TSS Single-Duct VAV Terminals TSS Single-Duct VAV Terminals Model TSS construction features Standard Construction Mechanical-lock construction ensures lowest possible casing leakage Roll-formed inlet collar with integral stiffening

More information