CONFIGURATIONS TABLE OF CONTENTS PHASE LOCATIONS (PREFERRED LOCATIONS) STRUCTURAL ELEMENTS DESIGN LIMITS

Size: px
Start display at page:

Download "CONFIGURATIONS TABLE OF CONTENTS PHASE LOCATIONS (PREFERRED LOCATIONS) STRUCTURAL ELEMENTS DESIGN LIMITS"

Transcription

1 3 1 Sheet 1 of TLE OF CONTENTS NEUTRL LOCTIONS PHSE LOCTIONS PHSE LOCTIONS (PREFERRED LOCTIONS) STRUCTURL ELEMENTS DESIGN LIMITS NEUTRL ** NEUTRL TP CONNECTION TO SUTRNSMISSION STTIC WIRE 3 1 ** PRESSEMLED CLE SECONDRY RUN PRESSEMLED CLE SECONDRY L CORNER PRESSEMLED CLE SECONDRY DEDEND OPEN WIRE SECONDRY OPEN WIRE SECONDRY SECONDRY RUNS SECONDRY RUNS OPGW TNGENT OR CORNER < 3º OPGW TNGENT OR CORNER > 3º < 6º SINGLE PHSE 4KV OR 1KV SINGLE PHSE UNDERUILD 4KV OR 1KV RMLESS TWO OR THREE PHSE 4KV OR 1KV TWO OR THREE PHSE TNGENT OR NGLE ON WOOD CROSSRM 4KV OR 1KV 4KV or 1KV UNGUYED STRUCTURE WITH FIERGLSS RM TWO OR THREE PHSE FLOTING ND 9 DEGREE NGLES 4KV OR 1KV TWO OR THREE PHSE UCK RM 9 DEGREE NGLE 4KV OR 1KV TWO OR THREE PHSE DEDENDS 4KV OR 1KV TWO OR THREE PHSE LOOPOVER 4KV OR 1KV SINGLE PHSE TP FROM TWO OR THREE PHSE LINE 4KV OR 1KV ERIL MID SPN TP TWO OR THREE PHSE LINE TWO OR THREE PHSE TP 4KV OR 1KV TWO OR THREE PHSE VERTICL TP 4 OR 1KV ** ** ** 3 1 ** ** ** ** ** 3 1 ** ** ** ** ** ** ** ** 3 1 ** ** ** ** SINGLE CIRCUIT 4 15 KV SPCER CLE TNGENT STRUCTURE (< 1 ) REV. DTE: 1/1/

2 3 1 Sheet of SINGLE CIRCUIT 4 15 KV SPCER CLE NGLE STRUCTURE) SINGLE CIRCUIT 4 15 KV SPCER CLE NGLE STRUCTURE (61 9 ) SINGLE CIRCUIT 15KV&ELOW SPCER CLE TNGENT LLEY RM CONFIG SINGLE CIRCUIT 15KV&ELOW SPCER CLE DEDEND SINGLE CIRCUIT 15KV&ELOW SPCER CLE NGLE STRUCTURE (7 6 ) SINGLE CIRCUIT 15KV&ELOW SPCER CLE NGLE STRUCTURE (61 9 ) THREE CIRCUIT 15KV&ELOW SPCER CLE TO SPCER LOOPOVER THREE CIRCUIT 15KV&ELOW SPCER CLE TO OPEN WIRE LOOPOVER THREE CIRCUIT 15KV&ELOW SPCER CLE TP FROM OPEN WIRE THREE CIRCUIT 15KV&ELOW SPCER LTERL TP THREE CIRCUIT 15KV&ELOW SPCER CLE MID SPN TP SINGLE CIRCUIT 34 OR 69KV TNGENT STRUCTURE DOULE CIRCUIT 34 OR 69KV TNGENT STRUCTURE SINGLE CIRCUIT 34 OR 69KV FIXED NGLE STRUCTURE DOULE CIRCUIT 34 OR 69 KV FIXED NGLE STRUCTURE SINGLE CIRCUIT 34 OR 69KV FLOTING NGLE STRUCTURE DOULE CIRCUIT 34 OR 69KV FLOTING NGLE STRUCTURE SINGLE CIRCUIT 34 OR 69KV DEDEND CORNER STRUCTURE DOULE CIRCUIT 34 OR 69KV DEDEND CORNER STRUCTURE SINGLE CIRCUIT 34 OR 69KV DEDEND TNGENT STRUCTURE SINGLE CIRCUIT 34 OR 69KV DEDEND NGLE STRUCTURE SINGLE CIRCUIT 34 OR 69KV DEDEND ENDLINE STRUCTURE SINGLE CIRCUIT 34 OR 69KV TP STRUCTURE, NGLE DOULE CIRCUIT 34 OR 69KV TP STRUCTURE SINGLE CIRCUIT 34 OR 69KV TP STRUCTURE DEDEND SINGLE CIRCUIT H FRME 69KV UNGUYED COMPOSITE POLE, 34 OR 69KV TNGENT/NGLE STRUCTURE SINGLE CIRCUIT UNGUYED COMPOSIT POLE DOULE CIRCUIT DEDEND TNGENT 3 3** 3 4** 3 5** 3 1** 3 3** 3 4** 3 15** ** 3 69 ** ** ** ** ** ** ** ** ** ** 3 69 ** ** 3 69 ** ** ** ** REV. DTE: 1/1/18

3 Neutral Locations 3 1 Sheet 1 of 1 1. Historical Neutral Locations 1.1 CIPS Service Territory Since at least 1986, CIPS Distribution Standard DS1 has stated that the preferable location for the neutral is down 6 from the line arm on spans less than feet. Where span lengths exceeded feet, the 6 spacing was mandatory. However, it was permitted to place the neutral on the line arm or at 4 spacing to eliminate replacing otherwise adequate poles for increased height. 1. UE Service Territory Prior to this edition being published, UE Distribution Construction Standards called for neutrals on new line poles without any equipment mounted on the pole to be 4 down from the line arm. This was applicable to both 4 kv and 1 kv areas. Several Standards indicate spacing is permitted for existing construction on 4kV poles or on poles being converted from 4 Volt single phase to 7 Volt single phase.. Consolidated meren Standards The Standards in this book show neutral spacing on all new configurations to be 6 ft. The previous range was to accommodate present conditions of most of the existing poles at being at 4 and many of the existing poles at New Pole Installations New pole lines and relocated pole lines should use the 6 foot neutral spacing in general. Major advantage to the 6 foot spacing is that it permits a truck s basket to maneuver between the phase conductors and the neutral to reach the field side of the pole.. Working on Existing Poles or Replacing Existing Poles The rule of permitting 4 to avoid replacing otherwise acceptable poles shall continue. When replacing a pole in a lead, the existing spacing should generally be used on the new pole, except that a 4 minimum neutral spacing from the line arm is required. Increasing from a 4 spacing to a 6 spacing would change the conductor tensions considerably and likely cause future problems. ENG: MJ REV. NO: 1 REV. DTE: /1/1

4 Phase Locations Sheet 1 of 1 General The phase locations shown in this distribution standard shall be standard for the meren System. It is not intended to change all existing structures that do not conform to this standard. However, all new constructions, as well as reconstructed existing circuits, shall, to the extent it is practicable, be in accordance with this standard. Vertical Construction No standard phase locations are designated for vertical single circuit construction at corners or angles in a line. (Note Exception under 416 Volt Single Phase Construction Insulated for 7 Volt Operation). This will allow the most practicable positioning, based on the configuration of the adjacent poles. When possible, however, the phase locations should be selected so as to give the maximum distance between conductors. For example, for 4 kv and 1 kv when going from flat configuration (Fig. ) to vertical, the phase designation from the top of the pole shall be,, and C. The neutral conductor, when present on vertical corners, shall take a position below the primary phase conductor. 416 Volt Single Phase Construction Insulated for 7 Volt Operation Where a line is built for initial operation at 416 volt single phase but is insulated and spaced for future 7 volt operation, the conductor on the road side shall be considered the future phase wire and the field side conductor shall be the future multigrounded neutral. (See Figure 1 of this standard.) On private property the east, northeast, north and northwest sides shall be equivalent to the road side, while the west, southwest, south and southeast sides shall be equivalent to the field side. t vertical corners the road side conductor (future 7 volt phase wire) shall occupy the high position on the pole. There will be instances where it will be impracticable to follow these general rules (e.g. where adjacent poles are on opposite sides of a winding road to keep line angles at a minimum). Where it is necessary to deviate from the standard conductor locations on poles adjacent to vertical corner poles the estimator shall show on his construction plats the conductor that must take the high position on the corner pole. This will obviate the need for construction changes when the line is cutover for 7 volt operation. When the line is cutover to 7 volt operation all conductors in positions other than the standard shall be marked by fastening the proper identifying aluminum letter on the crossarm directly below the conductor. Marking ny deviations from the standard phase locations shall be plainly marked with letters,, C, or N attached to the crossarm below the respective conductor. These deviations may be due to transpositions or unusual construction. In addition to the marking of these deviations, all three phase switch locations, three phase capacitor installations, three phase recloser installations, three phase sectionalizer installations, and three phase terminal poles shall be plainly marked with the proper phase letter. These letters shall be attached to the crossarm or pole so that phases can be readily identified. On long feeders with considerable distances between three phase switches, additional locations as required may also be marked to facilitate phase identification. Normally, these additional phase identification points should be located on poles where single phase taps take off from the three phase feeder main. The phase locations on poles adjacent to vertical configurations shall be plainly marked to facilitate identification when making repairs. These letters shall be attached to the crossarm below the respective conductors. ENG: MJ REV. NO: 1 REV. DTE: 3/18/ REFFIRMED DTE: 1/14/11

5 Phase Locations (Preferred Locations) 3 1 Sheet 1 of 1 C C C C C TRINGULR CONSTRUCTION FLT CONSTRUCTION SINGLE CIRCUIT 34 KV 4 OR 1 kv RM TRINGULR VERTICL CONSTRUCTION FIG. 1 FIG. FIG. 3 FIG. 4 N C C NEUTRL IS USULLY CRRIED DOWN ON THE POLE, UT MY E HERE C C C C SIDERM CONSTRUCTION FIG. 5 C FUTURE DOULE CIRCUIT RM TRINGULR C FUTURE NEUTRL POSITION FOR 7 V OPERTION DOULE CIRCUIT RM TRINGULR DOULE CIRCUIT 3 RM VERTICL SEE NOTE FIG. 6 FIG. 7 FIG. 8 C C C C ROD SIDE EST, NORTHEST, NORTHWEST OR, NORTH SIDE ON PRIV. PROP. FIELD SIDE WEST SOUTHWEST, SOUTHEST, OR SOUTH SIDE ON PRIV. PROP. 34kV 416 V SINGLE PHSE DOULE CIRCUIT DOULE CIRCUIT INSULTED FOR FUTURE 3 RM VERTICL 7 V OPERTION OVERHED FIG. 9 FIG. 1 FIG. 11 DOULE CIRCUIT UNDERUILT FIG. 1 NOTE: Phase positions shown in Fig. 8 should be used only when this configuration is adjacent to poles with configuration shown in Fig. 6. When phases are in positions shown in Fig. 8, they shall be marked with identifying letters. ENG: JH REV. NO: 1 REV. DTE: 11/4/15

6 Structural Elements Design Limits 3 3 Sheet 1 of General This standard gives the design limits of the structural elements employed in building standard configurations. These limits are based on the allowable loading of crossarms and pins as shown in Dist. Std. 9 4, and also on required conductor separation to prevent midspan conductor contact.. ngle Limits Tables 1,, 3, 4 and 5 specify the maximum angle capable of being turned on pins, insulators, fiberglass standoffs, combination fiberglass and porcelain standoffs, and crossarms for various types of construction. This data is based on the transverse strength of the components of the structure and the load applied to it, due to the line angles. 3. Dead End Loadings Table 6 specifies the maximum balanced dead end loading for unguyed crossarms. It shows the number of conductors permitted to dead end on a structure, depending on the size of conductor and the type of dead end structure. The data is based on standard conductor tensions and allowable equivalent horizontal loadings on the crossarm. The purpose of this table is to provide the information necessary to get the most out of a dead end structure without having to resort to crossarm guying. TLE 1 Maximum Line ngles Capable of eing Turned on Pins and Crossarms SHORT SPN (STD ) Conductor Size WG or kcmil Pins (ll) (See Note 4) Single Crossarm # of Conductors (1# arm limit) Without Grid Plate # of Conductors (4#) DOULE CROSSRM With Grid Plate (5) # of Conductors (4#) Sgl Dbl # 1# #4 CSR / C CSR C T Penguin CSR Rail Notes: 1. Maximum number of pins for single crossarm is. Maximum number of pins for double crossarm without grid plate is 4; and maximum number of pins for double crossarm with grid plate is 6. The number of conductors that can be deadended back to back (not on pins) is only limited by the strength of the joint between the arm(s) and the pole.. bove table based on Grade N construction. ENG: DCG REV. NO: 7 REV. DTE: /1/1

7 Structural Elements Design Limits 3 3 Sheet of 11 Conductor Size WG or kcmil TLE 1 Maximum Line ngles Capable of eing Turned on Pins or Crossarms MEDIUM SPN (STD ) Pins (ll) (See Note 4) Single Crossarm # of Conductors (1# arm limit) Without Grid Plate # of Conductors (4#) DOULE CROSSRM ENG: DCG REV. NO: 7 REV. DTE: /1/1 With Grid Plate (5) # of Conductors (4#) Sgl Dbl # 1# #4 CSR / C CSR C T Penguin CSR Rail Notes: 1. Maximum number of pins for single crossarm is. Maximum number of pins for double crossarm without grid plate is 4; and maximum number of pins for double crossarm with grid plate is 6. The number of conductors that can be deadended back to back (not on pins) is only limited by the strength of the joint between the arm(s) and the pole.. bove table based on Grade N construction. TLE 1C Maximum Line ngles Capable of eing Turned on Pins or Crossarms LONG SPN (STD ) Conductor Size WG or kcmil Pins (ll) (See Note 4) Single Crossarm # of Conductors (1# arm limit) Without Grid Plate # of Conductors (4#) DOULE CROSSRM With Grid Plate (5) # of Conductors (4#) Sgl Dbl # 1# #4 CSR / C CSR C T Penguin (45/7) CSR Notes: 1. Maximum number of pins for single crossarm is. Maximum number of pins for double crossarm without grid plate is 4; and maximum number of pins for double crossarm with grid plate is 6. The number of conductors that can be deadended back to back (not on pins) is only limited by the strength of the joint between the arm(s) and the pole.. bove table based on Grade N construction.

8 Structural Elements Design Limits 3 3 Sheet 3 of 11 Conductor Size WG or kcmil TLE 1D Maximum Line ngles Capable of eing Turned on Pins or Crossarms EXTR LONG SPN (STD ) Pins (ll) (See Note 4) Single Crossarm # of Conductors (1# arm limit) Without Grid Plate # of Conductors (4#) DOULE CROSSRM With Grid Plate (5) # of Conductors (4#) Sgl Dbl # 1# 1/ C CSR C T Penguin CSR Rail Notes: 1. Maximum number of pins for single crossarm is. Maximum number of pins for double crossarm without grid plate is 4; and maximum number of pins for double crossarm with grid plate is 6. The number of conductors that can be deadended back to back (not on pins) is only limited by the strength of the joint between the arm(s) and the pole.. bove table based on Grade N construction. Select The Required Crossarm ssembly Unit Using The Following s Guide 1. The above table, based on maximum span length of applicable sag table, automatically takes care of vertical loadings. For shorter span lengths the crossarm may be strong enough; however, a strength calculation should be made. See Dist. Std for examples and allowable crossarm loads.. Inadequate vertical strength for the number and size of conductors shown. 3. Double arms and double dead end pole top construction shall always be used. a. t all railroad crossings. Note: If tensions do not exceed lbs. per conductor during heavy loading; double pins and ties may be used. Double pole top pins mounted on the face of the pole may be used to meet this requirements. (Tensions for conductors sagged in accordance with Sag Table 1 does not exceed lbs. under heavy loaded conditions except for kcmil.. and 795 kcmil..). b. On grade circuits where the line angle exceeds o. c. On grade circuits at communications crossings, if the supply conductors are not continuous and of uniform tension in the crossing span and each adjacent span. 4. ngles shown for single or double pins refer to crossarm pins and existing pole top pins mounted on the face of the pole. 5. Grid gain plates (Dist. Std. 4 35) shall be used only when required for the larger angles shown. Use caution to insure that pin angle limits are not exceeded ( or 3 conductors). If pin limits are exceeded, use double dead ends. 6. bove table based on grade N construction. ENG: DCG REV. NO: 7 REV. DTE: /1/1

9 Structural Elements Design Limits 3 3 Sheet 4 of 11 Table Maximum Line ngle Capability of Distribution Standards Side tie in tension or compression on pin insulator of full tension take off unit. Sag Table Conductor ngle o SHORT SPN #4 (7/1) CSR 78 1/ C, bare or poly 46 1/ CSR, bare (1/7) CSR, bare (18/1) CSR (19) C T Pigeon T Penguin (45/7) CSR (19) T 1 MEDIUM SPN #4 (7/1) CSR 6 1/ C, bare or poly 38 1/ CSR, bare (1/7) CSR, bare (18/1) CSR (19) C T Pigeon T Penguin (45/7) CSR (19) T 1 ENG: DCG REV. NO: 7 REV. DTE: /1/1

10 Structural Elements Design Limits 3 3 Sheet 5 of 11 Sag Table Conductor ngle o LONG SPN #4 (7/1) CSR 5 1/ C, bare or poly 31 1/ CSR, bare (1/7) CSR, bare (18/1) CSR (19) C T Pigeon T Penguin 954 (45/7) CSR (19) T 9 ENG: DCG REV. NO: 7 REV. DTE: /1/1

11 Structural Elements Design Limits 3 3 Sheet 6 of 11 Table 3 Maximum Line ngle Capability of Distribution Standards Dist. Stds Pole Top Pins LOD Pole Top Pin (1# Limit, Transverse) Sag Table Conductor ngle o SHORT SPN MEDIUM SPN #4 (7/1) CSR 1/ C, bare or poly 1/ CSR, bare 11.8 (1/7) CSR, bare (18/1) CSR 556 (19) C T Pigeon 43. T Penguin 954 (45/7) CSR 556 (19) T #4 (7/1) CSR 1/ C, bare or poly 1/ CSR, bare 11.8 (1/7) CSR, bare (18/1) CSR 556 (19) C T Pigeon 43. T Penguin 954 (45/7) CSR 556 (19) T LONG SPN EXTR LONG SPN #4 (7/1) CSR 1/ C, bare or poly 1/ CSR, bare 11.8 (1/7) CSR, bare (18/1) CSR 556 (19) C T Pigeon 43. T Penguin 954 (45/7) CSR 556 (19) T 1/ C, bare or poly 1/ CSR, bare 11.8 (1/7) CSR, bare (18/1) CSR 556 (19) C T Pigeon 43. T Penguin 954 (45/7) CSR 556 (19) T ENG: DCG REV. NO: 7 REV. DTE: /1/1

12 Structural Elements Design Limits 3 3 Sheet 7 of 11 Table 4 Maximum Line ngle Capability of Distribution Standards Dist. Stds ** Vertical Line Post Insulator (Tie Top) F Neck N Neck LOD Vertical Line Post (11# Limit, Cantilever) Sag Table Conductor F Neck ngle *** N Neck ngle* SHORT SPN #4 (7/1) CSR 1/ C, bare or poly 1/ CSR, bare 11.8 (1/7) CSR, bare (18/1) CSR 556 (19) C T Pigeon 43. T Penguin 954 (45/7) CSR 556 (19) T NL MEDIUM SPN #4 (7/1) CSR 1/ C, bare or poly 1/ CSR, bare 11.8 (1/7) CSR, bare (18/1) CSR 556 (19) C T Pigeon 43. T Penguin 954 (45/7) CSR 556 (19) T LONG SPN #4 (7/1) CSR 1/ C, bare or poly 1/ CSR, bare 11.8 (1/7) CSR, bare (18/1) CSR 556 (19) C T Pigeon 43. T Penguin 954 (45/7) CSR 556 (19) T EXTR LONG SPN 1/ C, bare or poly 1/ CSR, bare 11.8 (1/7) CSR, bare (18/1) CSR 556 (19) C T Pigeon 43. T Penguin 954 (45/7) CSR 556 (19) T * ll 15 o line angles shown for N Neck insulators are based on top groove. *** ngles shown in above table are for single insulators only. For multiple conductors on a crossarm use grade N loads in DCS 11 4 for the conductor, span and line angle being considered. Compare the total transverse load with the transverse crossarm intermittent load limits shown in Table 1 of DCS ENG: DCG REV. NO: 7 REV. DTE: /1/1

13 Structural Elements Design Limits 3 3 Sheet 8 of 11 Table 5 Maximum Line ngle Capability of Distribution Standards DCS ** and ** in Compression and Tension 34 and 69 kv Polymer Horizontal Line Post Insulator (Clamp Top Line Terminal) Stock Nos and (5 L Limit in Compression and Tension) Sag Table Conductor ngle SHORT SPN MEDIUM SPN LONG SPN EXTR LONG SPN #4 (7/1) CSR 1/ C, bare or poly 1/ CSR, bare 11.8 (1/7) CSR, bare (18/1) CSR 556 (19) C T Pigeon 43. T Penguin 954 (45/7) CSR 556 (19) T 954 (45/7) T #4 (7/1) CSR 1/ C, bare or poly 1/ CSR, bare 11.8 (1/7) CSR, bare (18/1) CSR 556 (19) C T Pigeon 43. T Penguin 954 (45/7) CSR 556 (19) T 954 (45/7) T #4 (7/1) CSR 1/ C, bare or poly 1/ CSR, bare 11.8 (1/7) CSR, bare (18/1) CSR 556 (19) C T Pigeon 43. T Penguin 954 (45/7) CSR 556 (19) T 954 (45/7) T #4 (7/1) CSR 1/ C, bare or poly 1/ CSR, bare 11.8 (1/7) CSR, bare (18/1) CSR 556 (19) C T Pigeon 43. T Penguin 954 (45/7) CSR 556 (19) T 954 (45/7) T NL* NL* NL* NL* NL* 47 NL* NL* NL* NL* NL* NL* NL* NL* NL* NL* 8 NL* ENG: DCG REV. NO: 7 REV. DTE: /1/1

14 Structural Elements Design Limits 3 3 Sheet 9 of 11 Table 5 Maximum Line ngle Capability of Distribution Standards 69 kv Polymer Horizontal Line Post Insulator (w/ Hole Line Terminal lade) Stock No (Maximum Transverse Working Load 5 Lbs. (Tension & Compression) Sag Table Conductor ngle SHORT SPN MEDIUM SPN LONG SPN EXTR LONG SPN #4 (7/1) CSR 1/ C, bare or poly 1/ CSR, bare 11.8 (1/7) CSR, bare (18/1) CSR 556 (19) C T Pigeon 43. T Penguin 954 (45/7) CSR 556 (19) T 954 (45/7) T #4 (7/1) CSR 1/ C, bare or poly 1/ CSR, bare 11.8 (1/7) CSR, bare (18/1) CSR 556 (19) C T Pigeon 43. T Penguin 954 (45/7) CSR 556 (19) T 954 (45/7) T #4 (7/1) CSR 1/ C, bare or poly 1/ CSR, bare 11.8 (1/7) CSR, bare (18/1) CSR 556 (19) C T Pigeon 43. T Penguin 954 (45/7) CSR 556 (19) T 954 (45/7) T #4 (7/1) CSR 1/ C, bare or poly 1/ CSR, bare 11.8 (1/7) CSR, bare (18/1) CSR 556 (19) C T Pigeon 43. T Penguin 954 (45/7) CSR 556 (19) T 954 (45/7) T NL* NL* NL* NL* NL* NL* NL* NL* NL* NL* NL* NL* NL* 83 NL* NL* NL* NL* NL* NL* NL* 71 NL* NL* NL* NL* NL* NL* NL* 65 NL* NL* ENG: DCG REV. NO: 7 REV. DTE: /1/1

15 Structural Elements Design Limits 3 3 Sheet 1 of 11 TLE 7 TLE GIVING MXIMUM NUMER OF CONDUCTORS THT CN E DEDENDED ON UNGUYED CROSSRMS (SED ON STNDRD CONDUCTOR TENSIONS) Conductor Size # 4 CSR 7/1 are 1/ C (7 ) are 1/ CSR (6/1) are CSR (18/1) are CSR T Pigeon (19) are 43. CSR T Penguin 954 CSR (45/7) are Sag Table Span Short Medium Long Short Medium Long X Long Short Medium Long X Long Short Medium Long X Long Short Medium Long X Long Short Medium Long X Long Short Medium Long X Long Short Medium Long X Long Sgl rm DE Dbl rm DE Double rm DE Fiberglass DE rms 3 1/ x 4 1/ x 8Ft 3 3/4 x 4 3/4 x 1Ft 8 Ft. 1 Ft ENG: DCG REV. NO: 7 REV. DTE: /1/1

16 Structural Elements Design Limits 3 3 Sheet 11 of 11 Conductor Size 556 C T Dahlia Sag Table Span Short Medium Long X Long Sgl rm DE Dbl rm DE Double rm DE Fiberglass DE rms 3 1/ x 4 1/ x 8Ft 3 3/4 x 4 3/4 x 1Ft 8 Ft. 1 Ft. ENG: DCG REV. NO: 7 REV. DTE: /1/1

17 Neutral ** Sheet 1 of THRU THRU W/EXT DEDEND DEG. NGLE T CORNER LOOP ROUND THRU W/TP THRU W/EXT. W/TP THRU W/EXT. W/TP ON CK SIDE THRU X RM THRU DLE. X RM DEDEND X RM DEDEND TENSION > 15 LS. ENG: EJ REV. NO: 8 REV. DTE: 5/19/16

18 Neutral ** Sheet of Stnd./ Stk. No. Description ** Clevis, Secondary Single Clevis Extension C olt, Mach, ¾ x1 1 D Crossarm Pin and Insulator E SDE*W Deadend (See ) F PG* See Std G TT*W TopTie H DTT*W Double Top Tie I DE*W Deadend (See 7 11 ) 1 J Eyelet, ¾ 1 K Double Clevis 1 1 L Washer, Square, ¾ M 1 1** Grounding Unit 1 NOTE: If the deadend tension is greater than 15 lbs., use Dist. Std ENG: EJ REV. NO: 8 REV. DTE: 5/19/16

19 Distribution Neutral Tap Connection to Sub Transmission Static Wire 3 1 ** Sheet 1 of 1 C 1 Notes: 1. Connection from tap neutral to static/neutral wire must be at least the same ampacity as the tap neutral. For tap neutral, replace existing pole ground with # SD Cu. to a point 3 below tap neutral.. Install ground wire moulding in congested areas as required. 3. Install ground wire on quarter of pole that provides best clearance from center phase. Tap Neutral Std. 1/ CSR or C #4 CSR 3 1 E D Existing Pole Ground Std./Stk. No. Description 3 1 ** Clevis, Secondary Wire, Cu, # SD, Poly Covered C Clamp, PG 1 D Connector, Split olt 1 E Deadend, Preformed, 1/ CSR or C Deadend, Preformed, #4 CSR ENG: MJ REV. NO: REV. DTE: /1/1

20 Preassembled Cable Secondary Secondary Run ** Sheet 1 of 1 NOTES: 1. Terminate lashing ribbon with 5 close turns around entire cable and end on messenger with turns and a half hitch. Train leads neatly and eliminate excess slack.. For Service Construction Details, see Dist. Std For ease in making connections, cable may be opened up as far as required. Stnd. / Stk. No. Description ** Sgle. Clevis, Ext. rkt Dble. Sgle. Clevis rkt. 1 C Tie, Preformed, 1/ C 1 1 ENG: MJ REV. NO: REV. DTE: 1/5/95 REFFIRMED DTE: 1/14/11

21 Preassembled Cable Secondary L Corner ** Sheet 1 of 1 Without Service Takeoff With Service Takeoff C D E 6 1 NOTE: 1. Terminate lashing ribbon with 5 close turns around entire cable and end on messenger with two turns and a half hitch. Dist. Std. Or Stk. No. Description ** Sgle. Clevis, Ext. rkt Dble. Sgle. Clevis rkt. 1 C Deadend, 1/ C D Clamp, 1/ C 1 1 E Clamp, 4/ ENG: MJ REV. NO: 1 REV. DTE: 1/19/11 REFFIRMED: 1/19/11

22 Preassembled Cable Secondary Deadend ** Sheet 1 of 1 NOTES: 1. Open cable for distance of approximately 18 to allow room for making taps. Tape ends of conductors with rubber tape , followed by friction tape, , and lash cable to messenger on both sides of opening with 5 close turns around entire cable and end on messenger with turns and a half hitch.. unch same phase wires to form a cable and tape as necessary. Stnd. / Stk. No. Description ** Sgle. Clevis, Ext. rkt Dble. Sgle. Clevis rkt. 1 C Deadend 1/ C 1 1 ENG: MJ REV. NO: REV. DTE: 1/5/95 REFFIRMED DTE: 1/14/11

23 Open Wire Secondary 3 1 ** Sheet 1 of Thru 3 1 Thru w/ext W/O Ext Thru w/ext. w/service Ext Deadend Deadend Ext Deadend w/o Ext Deadend Ext. w/service Ext Neutral Thru Sec. Deadend Neutral Thru Sec. Deadend w/ext Neutral Thru Sec. Deadend w/ext. Service w/ext Wire Thru Notes: 1. When multiple secondary racks are installed on the same side of the poles, a 6 separation is required between the racks. ENG: MJ REV. NO: 3 REV. DTE: 3/18/ REFFIRMED DTE: 1/14/11

24 Open Wire Secondary 3 1 ** Sheet of Stnd. / Stk. No. Description 3 1 ** Secondary Clevis Ext. racket, 3 Clevis C Dble. Ext. rkt s. 3 & 1 Clevis D Secondary Ext. Guy 1 E DEP*W Preformed Deadend SDE*W Secondary Deadend F Spool Secondary Rack 1 1 G Spool Secondary Rack 1 ENG: MJ REV. NO: 3 REV. DTE: 3/18/ REFFIRMED DTE: 1/14/11

25 Open Wire Secondary 9 ngle ** Sheet 1 of Deg. ngle Deg. ngle w/3 Spool Rack Deg. ngle w/ Ext Deg. ngle w/ext. Service w/ext Sec. Deadend Neutral 9 Deg. ngle Sec. Deadend Neutral 9 Deg. ngle w/3 Spool Rack Sec. Deadend w/ext. Neutral 9 Deg. ngle Sec. Deadend w/ext. Neutral 9 Deg. ngle Service w/ext. Dist. Std. Or Stk. No. Description ** Secondary Clevis Extension rkt., 3 Clevis 1 1 C Dble. Ext. rkt s, 3 Clevis & 1 Clevis 1 D DEP*W Preformed Deadend SDE*W Secondary Deadend E Spool Secondary Rack 1 1 ENG: MJ REV. NO: REV. DTE: 3/18/ REFFIRMED DTE: 1/14/11

26 Secondary Runs ** Sheet 1 of Stnd. / Stk. No. Description Stnd. / Stk. No. Description Secondary Clevis Service Takeoff 3 X = 9 for Spans up to Ft. X = 1 for Ft. to 5 Ft. Spans X = 18 for 5 Ft. to 35 Ft. Spans X = 4 for 35 Ft. to 4 Ft. Spans NOTES: 1. This dimension may be reduced to 6 for spans up to 15 Ft. if necessary to meet joint use requirements.. Use secondary rack Stock No when available for spans up to 15 Ft. 3. For location of secondary clevises on rack with respect to primary circuits, see Dist. Std This construction is applicable to only those cases where climbing space can be obtained without use of secondary extension bracket. ENG: MJ REV. NO: REV. DTE: 1/5/95 REFFIRMED DTE: 1/14/11

27 Secondary Runs ** Sheet 1 of Sgle. rm Dble. rm Wire Secondary On One Side of Pole 1. This construction to be used only where existing facilities prohibit the use of secondary racks or clevises.. For location of secondary arms with respect to primary circuits, see Dist. Std Stnd. / Stk. No. Description ** Crossarm, Sgle., Crossarm, Dble., Insulator On rm 3 6 ENG: MJ REV. NO: 3 REV. DTE: 1/8/ REFFIRMED DTE: 1/14/11

28 3511 OPGW Tangent orcorner<3 º Sheet 1of 1 1 C D 3 E 6 -- minimum Highest phase conductor Notes: 1. Mark center ofclamplocationon OPGW cablewithink (nottape) whenaligningarmor rodsand clamp bodyon OPGW cable.. esureto finger tightenboltsonclampto ensure boltsarenotcompressed onto the OPGWcable,andalternate tightening. Tighten until break away bolt heads shear off. 3. Spiral VibrationDampers are usedon35 and abovespans only. Std./ Stk. No Description Static Supportracket¾ x¼ Wye Clevis 9º 1 C OPGW Suspension Clamp w/rmor Rods 1 D Clamp, ond OPGW Static Pole Ground 1 3@ E Spiral Vibration F 1 1** Grounding Unit 1 ENG: KR REV.NO:NEW REV. DTE:4//18

29 351 OPGW Tangent or Corner>3 º < 6 º Sheet1of1 D C 1 F 3 G 6 -- minimum E Highest phase conductor Notes: 1. Mark Center ofclamplocationonopgwwithink (not tape) when aligning armor rods and clampbody onopgw cable.. esureto finger tightenboltsonclampto ensure boltsarenotcompressed onto the OPGWcable,andalternate tightening. Tighten until break away bolt heads shear off. 3. Spiral vibration dampers are usedon35 and abovespans only. Std./ Stk. No Description Static Supportracket¾ x¼ Wye Clevis 9º 1 C Yoke Plate 1 D Clevis Eye E OPGW Suspension Clamp w/ rmor Rods 3@ F Spiral Vibration Damper G Clamp For onding OPGW Static to Pole Ground H 1 1 ** Grounding Unit 1 ENG: KR REV.NO:NEW REV. DTE: 4//18

30 Single Phase 4 to 15 kv ** Sheet 1 of 5 135º 18º 5º 9º 7º 45º º 315º FCE OF POLE Tangent, Single Pin Tangent, Double Pin 8,D ngle, Single Pin ngle, Double Pin J 5 K I 3 Pole Top Pin 1. See DCS 3 3 for angle and span length limitations.. See DCS 4 for unguyed composite pole application. 3. Composite pole has factory installed (internal) pole ground in the 45º quadrant. Wood pole may require pole ground depending on application. 4. Double coil washer is not required on composite pole. 5. See DCS 11 for typical guy insulator placement. Stnd. / Stk. No. Description ** Insulator, Pole Top, Sgl Pin Insulator, Pole Top, Dbl Pin 1 1 D TT*W Single Top Tie, See DCS 7 41 ST*W Single Side Tie, See DCS DTT*W Double Top Tie, See DCS DST*W Double Side Tie, See DCS 7 41 I 1 1 ** Grounding Unit, Grounding Unit, Composite Pole J 11 4* ** Guying Unit (Down, Span, or Sidewalk) 1 K ** Neutral ENG: KR REV. NO: 1 REV. DTE: 1/1/18

31 Single Phase 4 to 15 kv ** Sheet of 5 135º 18º 5º 9º 7º 45º º 315º FCE OF POLE L,M F J 6 K I Floating ngle 1 NOTES: 1. See DCS 7 16 for angle limitations.. See DCS 4 for unguyed composite pole application. 3. Composite pole has factory installed (internal) pole ground in the 45º quadrant. Wood pole may require pole ground depending on application. 4. If application is under built (not top attachment on the pole), use DCS For CSR, C, and C conductors where spans exceed 3 feet, see DCS for application of armor rods. 6. See DCS 11 for typical guy insulator placement. Stnd. / Stk. No. Description ** Insulator, Floating ngle F SC*W Clamp, Suspension See DCS 7 16 I 1 1 ** Grounding Unit, Wood Grounding Unit, Composite Pole J 11 4* ** Guying Unit (Down, Span, or Sidewalk) K ** Neutral 1 L olt, Mach., ⅝ x 1 (nti Split) 1 M Washer, Curved, ¾ ENG: KR REV. NO: 1 REV. DTE: 1/1/18

32 Single Phase 4 to 15 kv ** Sheet 3 of 5 135º 18º 5º 9º 7º 45º º 315º FCE OF POLE W/EXTENSION 1 W/EXTENSION 1 W/O EXTENSION 9 W/O EXTENSION 9 4 L,M 8 C L,M 5 1 C E G H J 8 I K 3 E J 8 W/FG Extension W/O FG Extension K Deadend 4 I 3 W/FG Extension W/O FG Extension Deg. ngle 9 ENG: KR REV. NO: 1 REV. DTE: 1/1/18

33 Single Phase 4 to 15 kv ** Sheet 4 of 5 FCE OF POLE 45º 9º 135º º 18º 315º 5º 7º 135º 18º 5º 9º 7º 45º º 315º FCE OF POLE W/EXTENSION 1 1 W/EXTENSION W/O EXTENSION 9 W/O EXTENSION H J E G D,G C 1 H E G 7 6 I 3 K J 8 K W/FG Extension W/O FG Extension LOOPOVER W/FG Extension W/O FG Extension TP I ENG: KR REV. NO: 1 REV. DTE: 1/1/18

34 Single Phase 4 to 15 kv ** Sheet 5 of 5 NOTES: 1. For meren Mo., use FG extension if other equipment is installed on this pole and additional working space is needed.. See DCS 4 for unguyed composite pole application. 3. Composite pole has factory installed (internal) pole ground in the 45º quadrant. Wood pole may require pole ground depending on application. 4. Double coil washer is not required on composite pole. 5. If application is under built (not top attachment on the pole), use DCS For jumper support application, hand tighten only and do not twist the eye off. 7. See DCS ** and ** for explanation of Operation Codes. 8. See DCS 11 for typical guy insulator placement. 9. Deadend on pole w/o fiberglass extension available meren Mo. Only. Stnd. / Stk. No. Description ** , Pole Top, Loopover w/fg Extension Pole Top, Loopover w/o FG Extension 1 1 C Deadend w/fg Extension Deadend w/o FG Extension 1 D TT*W Top Tie See DCS E DEC*W Clamp, Deadend See DCS G PG* See DCS 7 H PLW*W Wire, Poly Covered, (ft.) See DCS I 1 1 ** Grounding Unit, Grounding Unit, Composite Pole J 11 4* ** Guying Unit ( Down, Span, or Sidewalk) K ** Neutral L olt, Mach., ⅝ x 1 (nti Split) M Washer, Curved, ¾ 7 5, 55, or 6 Install Jumper ENG: KR REV. NO: 1 REV. DTE: 1/1/18

35 Single Phase -- Underbuild 4 to 15kV 3 1 ** Sheet 1 of 135º 18º 5º 135º 18º 5º 9º 7º 9º 7º C, J C,J 45º 315º º FCE OF POLE OR I º 315º º FCE OF POLE F P 7 D L RM TNGENT SGL PIN NGLE SGL PIN 3 1 NGLE DL PIN CROSSRM 18º 135º 5º 45º 315º º FCE OF POLE P 9º 7º 7 P P H 7 4 E 6 -- M 1 RM G P 18º 135º 5º 9º 7º 45º 315º º FCE OF POLE FLOTING NGLE P H 1 H E N K M 4 K P 7 P P 7 H P DEG. NGLE DEDEND 8 RM 1 RM ENG: KR REV. NO: 9 REV. DTE: 3/7/18

36 Single Phase -- Underbuild 4 to 15kV 3 1 ** Sheet of NOTES: 1. See DCS 3 3 for angle and span length limitations.. 8 crossarm available for use in meren Mo only. 3. See DCS 4 41 ** for maximum working loads for F/G deadend arms. 4. If neutral installed below arm, omit one pin insulator and see DCS ** for neutral materials. 5. For CSR, C, and C conductors where spans exceed 3 feet, see DCS for application of armor rods. 6. See DCS ** and ** for explanation of Operation Codes. 7. See DCS 11 for typical guy insulator placement Stnd. /Stk. No. Description 31 ** Crossarm, 8 Wood, Sgl Crossarm, 1 Wood, Sgl. 1 1, Crossarm, Deadend, FG, Crossarm, Deadend, FG, 1 1 C Insulator, rm, Sgl Pin Insulator, rm, Dbl Pin D Insulator, Floating ngle 1 E Deadend w/ FG Extension F Insulator, Guy Strain, FG, 6 1 G Deadend On rm 1 H ** Neutral I Crossarm, Tangent, F/G, Crossarm, Tangent, F/G, 1 J TT*W Sgl Top Tie (See DCS 7 41 ) ST*W Sgl Side Tie (See DCS 7 41 ) DST*W Dble. Side Tie (See DCS 7 41 K DEC*W Deadend, Clamp (See DCS 7 11 ) 1 L SC*W Suspension, Clamp (See 7 ) M PG*W See Std. (See DCS 7 5 N PLW*W Wire, Poly covered, (Ft.) (See DCS 7 8 ) P 11 4* ** Guying Unit (Down, Span, or Sidewalk) , 55, or 6 Install jumper 1 ENG: KR REV. NO: 9 REV. DTE: 3/7/18

37 rmless Two or Three Phase 4kV to 15kV ** Sheet 1 of 1 MINTENNCE ND LIMITED USE ONLY Pole Top Tangent ngle Tangent ngle Underbuild Stnd. / Stk. No. Description ** Pole Top Underbuild Insulator, Pole Top ssembly Standoff, 4 F.G C TT*W Top Tie 3 3 ST*W Side Tie 3 3 ENG: MJ REV. NO: 8 REV. DTE: 1/14/11

38 Two or Three Phase Tangent Or ngle On Wood Crossarm 4 to 15 kv ** Sheet 1 of 3 C, D Guy 6 Tangent 8 Sgle. rm ngle 8 Sgle. rm Tangent 1 Sgle. rm ngle 1 Sgle. rm NOTES: 1. See DCS 3 3 for angle and span length limitations.. See DCS 4 ** for arm detail. 3. For phase configuration, eliminate the center phase position. 4. See DCS 4 3 for unguyed composite pole application. 5. Composite pole has factory installed pole ground; wood pole may require pole ground based on application. 6. See DCS ** for neutral configuration ft. crossarm available merenmo only. Stnd. / Stk. No. Description ** Crossarm, 8 Sgl Crossarm, 1 Sgl Insulator, rm, Sgl C Insulator, Pole Top, Sgl D TT*W Sgl Top Tie 3 3 ST*W Sgl Side Tie 3 3 ENG: MJ REV. NO: 9 REV. DTE: 1/6/1

39 Two or Three Phase Tangent Or ngle On Wood Crossarm 4 to 15 kv ** Sheet of 3 G GUY 6 TNGENT 1 SGLE. RM NGLE 1 SGLE. RM UNDERUILD 3 NOTES: 1. See DCS 3 3 for angle and span length limitations.. Underbuild cover available merenil only. Stnd. / Stk. No. Description ** Crossarm, 1 Sgle C Insulator, rm 3 E TT*W Top Tie, Sgl Pin 3 ST*W Side Tie, Sgl Pin G Cover Single Pin 1 1 ENG: MJ REV. NO: 9 REV. DTE: 1/6/1

40 Two or Three Phase Tangent Or ngle On Wood Crossarm 4 to 15 kv ** Sheet 3 of 3 D C,F Guy 6 TNGENT 8 SGLE. RM NGLE 8 SGLE. RM NGLE DLE. RM SIDE RM NOTES: 1. See DCS 3 3 for angle and span length limitations.. 8 ft. alley arm available merenmo only. 3. Cover available merenil only. Stnd./ Stk. No. Description ** Sidearm, 8 Sgle Sidearm, 8 Dble. 1 1 C Insulator, rm D Insulator, Pole Top E TT*W Top Tie 3 ST*W Side Tie 3 DST*W Double Side Tie 3 3@ F Cover Single Pin 1 1 ENG: MJ REV. NO: 9 REV. DTE: 1/6/1

41 4to15kV Tangent Or ngle On Fiberglass Crossarm ** Sheet1of C,D K,D L 6 NOTES: 1 5 G SINGLE PIN 3Ø Ø Tangent8 Sglerm ngle8 Sglerm Tangent1 Sglerm ngle1 Sglerm SeeDCS33forangleandspanlengthlimitations.. SeeDCS441**forarmdetail. 3. For phase configuration, eliminate the center phase position. 4. SeeDCS43forunguyedcompositepoleapplication. 5. Composite pole has factory installed(internal) pole ground. Wood pole may require pole ground depending on application. 6. SeeDCS311**forneutralconfiguration ft. crossarm available meren Mo. only. Stnd. / Stk. No. Description 3 1 6** Crossarm, F/G, Crossarm, F/G, Insulator, rm, Sgl Pin C Insulator, Pole Top, Sgl Pin D TT*W TopTie,SglPinSeeDCS ST*W SideTie,SglPinSeeDCS @ G Grounding Unit, Grounding Unit, Composite Pole K 11 4*** Guying Unit(Down, Span, or Sidewalk) @ L Neutral, Tangent Neutral, Tangent w/ext Ø ENG: KR REV.NO: REV. DTE: 4/16/18 Ø

42 4to15kV Tangent Or ngle On Fiberglass Crossarm ** Sheetof 4 C,D ,D K L 6-5 G DOULE PIN 3Ø Ø Tangent8 Sglerm ngle8 Sglerm Tangent1 Sglerm ngle1 Sglerm NOTES: 1. SeeDCS33forangleandspanlengthlimitations.. SeeDCS441**forarmdetail. 3. For phase configuration, eliminate the center phase position. 4. SeeDCS43forunguyedcompositepoleapplication. 5. Composite pole has factory installed(internal) pole ground. Wood pole may require pole ground depending on application. 6. SeeDCS311**forneutralconfiguration ft. crossarm available meren Mo. only. Stnd. / Stk. No. Description 3 1 6** Crossarm, F/G, Crossarm, F/G, Insulator, rm, Dbl Pin C Insulator, Pole Top, Dbl Pin D DTT*W DoubleTopTie,DblPinSeeDCS DST*W DoubleSideTie,DblPinSeeDCS @ G Grounding Unit, Wood Pole Grounding Unit, Composite Pole K 11 4*** Guying Unit(Down, Span, or Sidewalk) @ L Neutral, Tangent Neutral, w/ext Ø ENG: KR REV.NO: REV. DTE: 4/16/18 Ø

43 TwoorThreePhaseFloatingand9 o ngles 4kVto15kV 317** Sheet1of FLOTING NGLES FCEOFPOLE 9 NGLES E D G E W/O EXTENSION D 3 W/O EXTENSION 3 6 E D W/EXTENSION G E D W/EXTENSION 8 4 L,M L,M ,F J J J J 8 C C K,F,F J J I 4 I K 4 3Ø Ø Floating ngle Deadendw/FGExtensioninTopPhase Deadendw/oFGExtensioninTopPhase ENG: KR REV.NO:7 REV. DTE: 4/17/18

44 TwoorThreePhaseFloatingand9 o ngles 4kVto15kV 317** Sheetof NOTES: 1. SeeDCS43forunguyedcompositepoleapplication.. Composite pole has factory installed(internal) pole ground in the 45º quadrant. Wood pole may require pole ground depending on application. 3. Use FG extension in top phase for climbing space if application is under--built(not top attachment on the pole). For317&6thisrequiresordering1additionalFGextension &8areforunder--buildconstructionandincludeFGextensionsforthetopphases. 5. Ifaspanguyorguysarerequiredortwothrough--boltsareusedtoattachtheguyhook(s),thelocationofoneor bothofthguyhookswillneedtobeadjustedupordowninches. 6. ForCSR,C,andCconductorswherespansexceed3feet,seeDCS781forapplicationof armor rods. 7. SeeDCS17315**and173151**forexplanationofOperationCodes. 8. SeeDCS11fortypicalguyinsulatorplacement. Stnd./ Stk. No. Description 3 1 7** Ø Ø Insulator, Floating ngle Deadend w/fg Extension Deadend w/o FG Extension 3 C Insulator, Guy Strain, FG, 6 D PG* SeeStd E DEC*W Deadend Clamp See DCS F SC*W Suspension Clamp See DCS 7 16 G PLW*W Wire, Poly covered,(ft.) See DCS I 1 1** Grounding Unit, Grounding Unit, Composite Pole J 11 4*** Guying Unit(Down, Span, or Sidewalk) K 3 1 1** Neutral L olt, Mach., ⅝ X 1 (nti Split) M Washer, Curved, ¾ 7 5, 55, or 6 Install Jumper 3 3 ENG: KR REV.NO:7 REV. DTE: 4/17/18

45 TwoorThreePhaseuckrm -- 9 ngle 4to15kV 319** Sheet1of 45º 9º 135º F G G,D F J F F C L J G,D 11 4 C F G,D G M,N,Q 1 L G,D J F º 18º 315º 5º 7º FCEOFPOLE M,N,Q 9 F G G,D F J F F C J G,D L 11 4 G,D C G M,N,Q J L 11 G,D F M,N,Q 9 TOP W/O EXTENSION O,P 1 M,N,Q 9 F TOP W/EXTENSION 3 -- F G J C J 5 M,N,Q 9 J Q F G,D 1 L I H K Ø Ø 4 8 FGrm,Polew/oExt FGrm,Polew/Ext FGrm,Polew/oExt FGrm,Polew/Ext ENG: KR REV.NO:9 REV. DTE: 4//18

46 TwoorThreePhaseuckrm -- 9 ngle 4to15kV 319** Sheetof NOTES: 1. SeeDCS 441**forarmstrength.. ttach guy to bracket of fiberglass arm. 3. Use 1 deadend arm with F/G extension on pole for underbuild application. 4. For phase construction, keep the arm spacing as shown but eliminate the center phase position. 5. SeeDCS43forunguyedcompositepoleapplication. 6. Composite pole has factory(internal) installed pole ground in the 45 quadrant. Wood pole may require pole ground depending on application. 7. The8 crossarmisavailableformerenmo.only. 8. Deadend on pole w/o fiberglass extension available meren Mo. only. 9. Forjumpersupportapplications,handtightenonlyanddonottwisttheeyeoff. 1. SeeDCS17315**and173151**forexplanationofOperationCodes. 11. SeeDCS11fortypicalguyinsulatorplacement. Stnd./Stk.No. Description 319** Ø Ø 3, Deadendssy.,F/G, Deadend ssy., F/G, 1 8 C Deadend w/fg Extension Deadend w/o FG Extension 1 1 D Deadendonrm F PG* SeeStd G DEC*W Clamp, Deadend See H I Neutral PG J PLW*W LeadWire,PolyCovered,Ft.See K Grounding Unit, Composite Pole L 11 4*** Guying Unit(Down, Span, or Sidewalk) M Pin, Insulator, Long Shank N Insulator, Vice--Top, 15kV O olt, Mach., ⅝ x 1 (nti--split) P Washer, Curved, ¾ Q Washer, Flat, Sq., 4 x4, w/ 13/16 hole , 55, or 6 Install Jumper ENG: KR REV.NO:9 REV. DTE: 4//18

47 Two or Three Phase Deadends 4 to 15kV ** Sheet 1 of 7 K GUY K GUY D 3 C 8 D C L 9 Std Std Std 8 rm 1 rm NOTES: 1. See DCS 4 41 for arm strength.. ttach guy to bracket of F.G. arm. 3. Use 1 deadend arm with F/G extension for underbuild application. 4. For phase construction, eliminate the center phase position. 5. See DCS 4 3 for unguyed composite pole application. 6. Composite pole has factory (internal) installed pole ground; wood pole may require pole ground based on application, and underbuild uses existing pole ground crossarm available meren MO only. 8. Deadend on pole w/o fiberglass extension available meren MO only. 9. See DCS ** for neutral configuration. ENG: MJ REV. NO: 8 REV. DTE: 11/1/11

48 Two or Three Phase Deadends 4 to 15kV ** Sheet of Stnd. / Stk. No. Description ** Deadend ssy, FG rm, Deadend ssy, FG rm, Deadend on Sgl rm 8 C Deadend on Pole w/fg Extension Deadend on Pole w/o FG Extension 1 D DEC*W Clamp, Deadend @ G Grounding Unit, Wood Pole Grounding Unit, Composite Pole @ K ** Guying Unit @ L Neutral, Deadend ENG: MJ REV. NO: 8 REV. DTE: 11/1/11

49 Two or Three Phase Loopovers 4 to 15kV ** Sheet 1 of 5 POLE TOP F/G RM F C 7 C P W/EXTENSION C W/O EXTENSION G D 8 K GUY Deadend 8 rm, Pole w/ext. Deadend 8 rm, Pole w/o Ext. Deadend 1 rm, Pole w/ext. Deadend 1 rm, Pole w/o Ext. 5 I NOTES: 1. See DCS 4 41 for arm strength.. ttach guy to center bracket of fiberglass arm for difference in tension. 3. For phase construction, eliminate the center phase position 4. Contact Standards using unguyed composite pole for difference in conductor tension application. 5. Composite pole has factory (internal) installed pole ground; wood pole may require pole ground based on application crossarm available merenmo only. 7. Deadend on pole w/o fiberglass extension available merenmo only. 8. See DCS ** for neutral configuration. ENG: MJ REV. NO: 9 REV. DTE: /17/1

50 Two or Three Phase Loopovers 4 to 15kV ** Sheet of 5 Dist. Std. Or Stk. No. Description ** Deadend ssy. FG, Deadend ssy. FG, C Loopover w/fg Extension, Pole Top Loopover w/o FG Extension, Pole Top 1 1 D Loopover, Sgl rm F DEC*W Clamp, Deadend G TT*W Top Tie, Sgl Pin I Grounding Unit, Wood Pole Grounding Unit, Composite Pole J PG* See Std @ K Neutral, Thru P PLW*W Lead Wire, Poly covered, Ft or 6 Install jumper ENG: MJ REV. NO: 9 REV. DTE: /17/1

51 Two or Three Phase Loopovers 4 to 15kV ** Sheet 3 of 5 P P J P P G G 8 8 C E 6 C E W/EXTENSION W/O EXTENSION Pole Top w/o Extension Pole Top w/extension Underbuild Dist. Std. Or Stk. No. Description ** C Pole Top Loopover w/extension Pole Top Loopover w/o Extension 1 1 E Looparound, Pole F DEC*W Clamp, Deadend G TT*W Top Tie, Sgl Pin 3 3 J PG* See Std P PLW*W Lead Wire, Poly covered, Ft or 6 Install jumper ENG: MJ REV. NO: 9 REV. DTE: /17/1

52 Two or Three Phase Loopovers 4 to 15kV ** Sheet 4 of 5 P J C L J 1 D G D K DE ssy. 1 rm UNDERUILD F/G RM 8 rm SIDERM NOTES: 1. Wildlife cover required for merenil only. ENG: MJ REV. NO: 9 REV. DTE: /17/1

53 Two or Three Phase Loopovers 4 to 15kV ** Sheet 5 of 5 Dist. Std. Or Stk. No. Description ** C Pole Top Loopover 1 1 D Loopover rm 3 1 E Looparound F DEC*W Deadend Clamp G TT*W Top Tie 3 3 I Crossarm, DE ssy., 1 1 J PG* See Std P PLW*W Lead Wire, Poly covered, Ft K Sidearm, Double, @ L Wildlife Cover 5 or 6 Install jumper 3 3 ENG: MJ REV. NO: 9 REV. DTE: /17/1

54 Single Phase Tap from Two or Three Phase Line 4 to 15kV 3 1 ** Sheet 1 of MINTENNCE ND LIMITED USE ONLY G OR F E H G OR F 16 C F 18 3 D I E H GUY 4 F 74 1 GUY G OR F I E F G OR F J D H I D E F E G OR F 3 H D H C GUY GUY F RMLESS CONSTRUCTION Near Phase Top or Far Phase CROSSRM CONSTRUCTION Near Phase Top Phase Far Phase Notes 1. See Dist. Std. 3 1 for neutral spacing information. May be reduced to 4 if pole space is limited.. This standard to be used only for non fused single phase taps that do not pass through wooded areas and are of limited length (1 or spans). ENG: MJ REV. NO: 5 REV. DTE: /17/1

55 Single Phase Tap from Two or Three Phase Line 4 to 15kV 3 1 ** Sheet of Stnd. / Stk. No. Description 3 1 ** ssembly Standoff, 4 FG Shackle Deadend C Insulator Deadend, 1 kv 1 D Insulator Standoff, 18 LD Insulator Crossarm E PLW*W Lead Wire, Poly Covered Ft F PG* See Std. 7 G HLC*W Hot Line H DEC*W Deadend Clamp or 6 Install connector @ I TT*W Top Tie 1 J ST*W Side Tie 1 ENG: MJ REV. NO: 5 REV. DTE: /17/1

56 erial Mid Span Tap 4 to 15kV ** Sheet 1 of STOCK NO. LINE SIZE COLOR CODE Main Tap Main Tap #4 CSR #4 CSR Orange Orange / C #4 CSR / C 1/ C Yellow Yellow / C Orange lack Orange Orange 1 95 Operations Code ENG: MJ REV. NO: 1 REV. DTE: 1/4/5 REFFIRMED DTE: /1/1

57 erial Mid Span Tap 4 to 15kV ** Sheet of Sag and Tension Table for Mid Span Taps TP SPN IN FEET Tap Tension Per LINE SIZE Conductor in Pounds Main Tap Tap Sag in Inches #4 CSR #4 CSR / C #4 CSR / C / C NOTES: 1. Mid span taps are permitted only under the following conditions: a. The location is easily accessible to a basket truck, and b. The run conductor(s) is full tension, and c. The tap will be made on the nearest phase, or from vertical construction in the case of two or three phase taps, and d. The tap can be made in accordance with the above sag and tension table, and e. The mid span tap will eliminate setting an additional pole.. Clearance shall be based on the run conductor s attachment height less three feet (3 ) less the sag indicated in the above table. Tap spans shall be as level as possible. 3. Switch(es) shall be installed at the first pole in the tap circuit. 4. Taps shall be limited to one per run conductor span. 5. Quantity specified in the material list is for tapping one conductor. 6. This Standard applicable for tangent construction. ngle construction satisfactory if angle complies with Dist. Std. 3 3 ** and tap(s) is within 1 ft. of insulator. Tap(s) 1 to 3 ft. from the insulator on angle construction require specific investigation. ENG: MJ REV. NO: 1 REV. DTE: 1/4/5 REFFIRMED DTE: /1/1

58 Two or Three Phase Line Two or Three Phase Tap 4 to 15kV ** Sheet 1 of 3 7 F 3 F H H E D, I C D, I C K 5 8 E F F D K 8 M E OVERHED UNDERUILD DE ssy 8 rm DE ssy 1 rm DEDEND TP NOTES: 1. See DCS 4 41 for arm strength.. ttach guy to center bracket of FG arm. ENG: MJ REV. NO: 7 REV. DTE: 1/1/1

59 Two or Three Phase Line Two or Three Phase Tap 4 to 15kV ** Sheet of 3 1. Use 1 deadend arm with F/G extension on pole for underbuild application.. For phase construction, eliminate the center phase position. 3. See DCS 4 3 for unguyed composite pole application. 4. Composite pole has factory (internal) installed pole ground; wood pole may require pole ground based on application, and underbuild uses existing pole ground crossarm available merenmo only. 6. See DCS ** for neutral configuration. Stnd. / Stk. No. Description ** Deadend ssy., FG, Deadend ssy., FG, Deadend on Pole w/ FG Extension 1 1 C Deadend on Sgl rm D Insulator and X rm Pin E PG* See Std F PLW*W Lead Wire, Poly covered G Grounding Unit, Grounding Unit, Composite Pole H STC*W Hot Tap w/stirrup 3 PG* See Std. 7 5 I TT*W Top Tie J DEC*W or DE*W Deadend Clamp 3 K ** Guying Unit M Neutral, Tangent w/tap or 6 Install connector or jumper ENG: MJ REV. NO: 7 REV. DTE: 1/1/1

60 Two or Three Phase Line Two or Three Phase Tap 4 to 15kV ** Sheet 3 of 3 F E MINTENNCE ND LIMITED USE ONLY G G E F 48 G 1 3 H D C E D New Construction 3 Tap Tap Tap Tap Existing Construction s Shown Opposite ( same side) (1 each side) 1. On existing circuits this spacing can be obtained by raising the top phase 8 and lowering the bottom phase 8. Tap spans may not exceed 175. Stnd. / Stk. No. Description ** Ph Ph ssembly Standoff, 4 F.G ssembly Standoff, 4 F.G Insulator Standoff, C Insulator Deadend, 1kV 3 3 D Shackle Deadend 3 E PLW*W Lead Wire, Poly covered F PG* See Std G HLC*W Hot Line Clamp w/stirrup PG* See Std H TT*W Top Tie 3 1 I DEC* or DE*W Deadend Clamp or 6 Install connector ENG: MJ REV. NO: 7 REV. DTE: 1/1/1

61 TwoOrThreePhase -- VerticalTap 4or1kV ** Sheet1of E C,F K K C,F C,F C,F E E E D D,F D D,F E E TOP PHSE W/EXTENSION 4 M,N TOP PHSE W/O EXTENSION M,N K K K K K K L 3 3 G G L Top Phase Deadend on Pole w/fg Extension Top Phase Deadend on Pole w/o FG Extension ENG: KR REV.NO:7 REV. DTE: 4/3/18

62 TwoOrThreePhase -- VerticalTap 4or1kV ** Sheetof NOTES: 1. Top bolt of guy attachments should be centered between phase positions and between phase and neutral position.. SeeDCS43forunguyedcompositepoleapplication. 3. Composite pole has factory(internal) installed pole ground in the 45 quadrant. Wood pole may require pole ground depending on application. 4. Deadend on pole w/o fiberglass extension available meren Mo only. 5. SeeDCS17315**and173151**forexplanationofOperationCodes. 6. SeeDCS11fortypicalguyinsulatorplacement. Stnd. /Stk. No. Description 3 13** Ø Ø Deadend on Pole w/fg Extension DeadendonPolew/oFGExtension C Dbl Deadend on Pole w/extension D PLW*W Dbl Deadend on Pole w/o Extensions Lead Wire, Poly Covered See E PG* See F DEC*W Clamp, Deadend See G Grounding Unit, Composite Pole K 11 4*** Guying Unit(Down, Span, or Sidewalk) L 3 1 1** Neutral M olt, Mach., ⅝ x 1 (nti--split) N Washer, Curved, ¾ 5 5, 55, or 6 Install Jumper ENG: KR REV.NO:7 REV. DTE: 4/3/18

63 15 KV & elow Spacer Cable Single Circuit Tangent Structure Sheet 1 of Stnd. / Stk. No. Description racket, Messenger Stirrup, Spacer Support 1 C Spacer, High Density Polyethylene 1 D ar, nti Sway 1 E Screw, Lag, Fetter Type, ½ x 4 1 F olt, Machine, ⅝ x 1 (w/nut) 3 G Washer, Square ¼ x ¼ x 3/16 Thick 3 H Connector, PG, Pole Ground to Messenger 1 I #1 Grounding Unit # Cu. Poly Grounding Unit 1 NOTES 1. This distance can be reduced to a minimum of 6ft if needed when replacing a pole in an existing line.. pole ground is required on every spacer cable pole. Install a covered 7#1 pole ground if no equipment is being installed or install a covered # pole ground if the equipment being installed requires it such as a riser, recloser, etc. 3. Secondary location if present. Connect secondary neutral to pole ground. 4. See DCS for spacer installation between poles. ENG: KR REV. NO: 3 REV. DTE: 7//18

64 15kV & elow Spacer Cable Double Circuit Tangent Structure 3 ** Sheet 1 of ENG: KR REV. NO: REV. DTE: NEW

65 15kV & elow Spacer Cable Double Circuit Tangent Structure 3 ** Sheet of Stnd. / Stk. No. Description 3 ** racket, Messenger Stirrup, Spacer Support C Spacer, High Density Polyethylene D ar, nti Sway E Screw, Lag, Fetter Type, 1/ x 4 F olt, Machine, 5/8 x 1 (w/ nut) 1 5 G Washer, Square 1/4 x 1/4 x 3/16 Thick 6 H olt, Machine, 5/8 x 14 (w/ nut) I Clamp, Parallel Groove, luminum Messenger to pole J Grounding Unit, 7#1 Copperweld Grounding Unit, # Cu. Poly 1 K ** Neutral Configuration NOTES 1. The distance can be reduced to a minimum of 6ft if needed when replacing a pole in an existing line.. pole ground is required on every spacer cable pole. Install a covered 7#1 pole ground if no equipment is being installed or install a covered # pole ground if the equipment being installed requires it such as a riser, recloser, etc. 3. Secondary location if present. Connect secondary neutral to pole ground. 4. See DCS for spacer installation between poles. 5. The distance can be reduced to a minimum of 5 ft. If approved by Engineering. ENG: KR REV. NO: REV. DTE: NEW

66 4--15 kv Spacer Cable nglestructure7 6 33** Sheet1of ENG: KR REV.NO: REV. DTE: 7//18

67 4--15 kv Spacer Cable nglestructure7 6 33** Sheetof Stnd./ Stk. No. Description 3 3** olt,machine,5/8 x14 (w/nut) Washer, Square, --1/4 x --1/4 x 3/ C Eyelet, NM, STD, 3/4 1 D Shackle, nchor, 9/16 1 E Clamp, Suspension 1 F Connector, PG, Pole Ground to Messenger G 114** GuyingUnitw/FGStrainInsulator&HDGuyHook 1 H Insulator, Pin, 15 kv, Vise--Top 3 6 I Pin, Insulator, 1 Thread, Short Shank, 5/8 3 6 J racket, ngle, Insulator Support K 1 1** Grounding Unit, 7#1 Copperweld 1 L 3 1 1** Neutral Configuration NOTES 1. Thedistancecanbereducedtoaminimumof6ftifneededwhenreplacingapoleinanexistingline.. polegroundisrequiredoneveryspacercablepole.installacovered7#1polegroundifnoequipmentisbeing installed or install a covered# pole ground if the equipment being installed requires it such as a riser, recloser, etc. 3. Secondary location if present. Connect secondary neutral to pole ground. 4. Thedistancecanbereducedtoaminimumof5ft.ifapprovedbyEngineering. ENG: KR REV.NO: REV. DTE: 7//18

68 4--15 kv Spacer Cable nglestructure61 and±9 34** Sheet1of ENG: KR REV.NO: REV. DTE: 7//18

69 4--15 kv Spacer Cable nglestructure61 and±9 34** Sheetof Stnd./ Stk. No. Description 3 4** olt,machine,5/8 x14 (w/nut) Washer, Square, --1/4 x --1/4 x 3/ C Eyelet, NM, STD, 3/4 4 D Clevis, NM, Thimble, Galvanized Steel 4 E Grip, Messenger/ Neutral, Preformed 7# W 4 F Connector, PG, Pole Ground to Messenger G 114** GuyingUnitw/FiberglassInsulator&HDGuyHook 4 H racket, ngle, Insulator Support 1 I Plate, Mounting, Dbl Pin Insulator 3 6 J Insulator, Pin, 15kV, Vise--Top 6 1 K Pin, Insulator, 1 Thread, Short Shank, 5/8 6 L 1 1** Grounding Unit, 7#1 Copperweld 1 M 3 1 1** Neutral Configuration NOTES 1. Thedistancecanbereducedtoaminimumof6ftifneededwhenreplacingapoleinanexistingline. polegroundisrequiredoneveryspacercablepole.installacovered7#1polegroundifnoequipmentisbeing installed or install a covered# pole ground if the equipment being installed requires it such as a riser, recloser, etc. 3. Secondary location if present. Connect secondary neutral to pole ground. 4. Thedistancecanbereducedtoaminimumof5ft.ifapprovedbyEngineering. ENG: KR REV.NO: REV. DTE: 7//18

70 15kV & elow Spacer Cable Single Circuit Tangent Structure lley rm Configuration 3 5 ** Sheet 1 of 1 Stnd. / Stk. No. Description 3 5 ** FG lley rm ssembly Eyelet, NM, 5/8 1 1 C olt, Mach., 5/8 x D Nut, Lock, 5/8 1 1 E Washer, Square, Galv. 4 x 4 x 3/16 w/ 13/16 hole F Clamp, Suspension (conductor Range:.31.6 ) 1 1 G Clip, Electrical, Grd. 1 H 1 1 ** Grounding Unit, 7#1 Copperweld 1 1 I Connector, PG, Pole Ground to Messenger 1 1 NOTES 1. Install spacers 3 from crossarm in each direction. See DCS for spacer installation between poles.. Vertical load limited to 15 lbs. Max spans are: 1/ span = 58, 477 span = 167, and 795 span = 13. ENG: KR REV. NO: 1 REV. DTE: 6/18/18

71 15 kv & elow Spacer Cable Single Circuit Dead End Structure 3 1 ** Sheet 1 of 4 ENG: KR REV. NO: 1 REV. DTE: 6/18/18

72 15 kv & elow Spacer Cable Single Circuit Dead End Structure 3 1 ** Sheet of 4 ENG: KR REV. NO: 1 REV. DTE: 6/18/18

73 15 kv & elow Spacer Cable Single Circuit Dead End Structure 3 1 ** Sheet 3 of 4 ENG: KR REV. NO: 1 REV. DTE: 6/18/18

74 15 kv & elow Spacer Cable Single Circuit Dead End Structure 3 1 ** Sheet 4 of 4 Stnd. / Stk. No. Description 3 1 ** Deadend ssy., FG rm, Spacer Cable Dead End racket 1 C 4 3 Crossarm, Sgl., Wood, 1 (use only 1/ of V race) 1 D racket, Mounting, rrester 1 1 E Eyelet, NM, STD 3/ F olt, Mach., 5/8 x G Washer, Square, 1/4 x 1/4 x 3/ H Grip, Messenger/ Neutral, Preformed 7#6 5W I Clevis, NM, Thimble, Galvanized Steel J Line Duc Cover (Messenger Cover), lack, 8 Long (Each) K Insulator, Suspension, 15kV, Poly 3 3 L Insulator, Guy Strain, Fiberglass, 6, 15kV 1 1 M Shackle nchor, 9/ N Clevis, Thimble, 7/8 Opening, Galvanized Steel O Deadend on Pole with FG Ext. P Grip, Conductor Deadend, 15kV, 477 Spacer Cable Size Grip per Existing Spacer Cable Conductor (See 7 11 ) 3 3 Q rrester, 1kV w/ Protective Cap rrester, 3kV w/ Protective Cap R racket, Switch/ rrester Mounting 3 S Wire, Poly #6 Cu., (FT.) T Clamp, Hot Line, 1/ Through 477 Spacer Cable Clamp, Hot Line, 795 Spacer Cable 3 3 U Connector, PG, Pole Ground to Messenger V Lag, Square Head, Galvanized, 1/ x ,3@ W 1 1 ** Grounding Unit, 7#1 Copperweld 1 1 X 11 4 ** Guying Unit with FG Strain Insulator & HD Guy Y ** Neutral Configuration Z PG Clamp Cover 3 NOTES: 1. Install the first spacer ( ) about 4 feet from the pole as to not stress the cable. Normal spacing is 5 to 33. See DCS for space installation between poles.. Install the center phase of the spacer cable with Fiberglass Strain Insulator into the top hole on the DE arm. 3. Use DCS ground coil application on new pole installation. Use DCS 1 1 for ground rod application on existing pole installation. 4. Secondary location if present. Connect secondary neutral to pole ground. 5. Only use 3 1 when extending the line with open wire is unlikely or when required by clearance restrictions. 6. Distance may be reduced to 4 if approved by Engineering. 7. For installations on a composite pole, substitute a fiberglass crossarm, Stock # , in place of the wood arm. Use electrical ground clips, stock # , to attach the ground wire to the bottom of the fiberglass crossarm. ENG: KR REV. NO: 1 REV. DTE: 6/18/18

75 15 kv & elow Spacer Cable Three Phase Loopover Spacer Cable to Spacer Cable 3 15 ** Sheet 1 of 3 ENG: KR REV. NO: 1 REV. DTE: 6/18/18

76 15 kv & elow Spacer Cable Three Phase Loopover Spacer Cable to Spacer Cable 3 15 ** Sheet of 3 ENG: KR REV. NO: 1 REV. DTE: 6/18/18

77 15 kv & elow Spacer Cable Three Phase Loopover Spacer Cable to Spacer Cable 3 15 ** Sheet 3 of 3 Stnd. / Stk. No. Description 3 15 ** racket, Messenger olt, Machine, 5/8 x 1 (w/ nut) 3 1 C Washer, Square, 1/4 x 1/4 x 3/16 Thick 4 D Eyenut, 3/4, Galvanized Steel 1 E Line Duc (Messenger Cover), lack, 8 Long (Each) F Connector, PG, Pole Ground to Messenger 1 1 G Crossarm, Deadend, F/G, H Insulator, Suspension, 15kV, Poly 6 6 I Insulator, Strain, Fiberglass, 6, 15kV J Insulator, Pin, 15kV, Vise Top 3 3 K Pin, Insulator, Long Shank 3 3 L Washer, Flat, Sq., 4 x 4, w/ 13/16 hole 3 3 M Clevis, Thimble, ⅞ opening, Galvanized Steel 6 6 N Shackle nchor, 9/16 6 O Grip, Conductor Deadend, 15kV, New 477 Spacer Cable (See 7 11 ) 6 6 Size Grip per Existing Spacer Cable Conductor 6 P PG*W Clamp, Parallel Groove (See 7 5 ) 3 3 Q Cover, Large, Vice Type Connectors 3 R 1 1 ** Grounding Unit, 7#1 Copperweld 1 S ** Neutral Configuration T Eyelet, 3/4, Galvanized Steel 1 U olt, 3/4 x 1 1 V Grip Messenger/Neutral, Preformed 5 W W Clevis, NM, Thimble, Galvanized Steel NOTES 1. Install the first spacer ( ) about 4 feet from the pole as to not stress the cable. Normal spacing is 5 to 33. See DCS for spacing installation between poles.. Install the center phase of the spacer cable with fiberglass strain insulator into the top hole on the DE arm. This leaves the bottom hole for guying if needed. 3. Use DCS ground coil application on new pole installation. Use DCS 1 1 for ground rod application on existing pole installation. 4. Secondary location if present. Connect secondary neutral to pole ground. 5. This distance can be reduced to 4 inches if approved by engineering. ENG: KR REV. NO: 1 REV. DTE: 6/18/18

78 15 kv & elow Spacer Cable Three Phase Loopover Spacer Cable to Open Wire 3 1 Sheet 1 of 3 ENG: KR REV. NO: 1 REV. DTE: 6/18/18

79 15 kv & elow Spacer Cable Three Phase Loopover Spacer Cable to Open Wire 3 1 Sheet of 3 Stnd. / Stk. No. Description olt, 5/8 x Washer, Square, 1/4 C Deadend on Pole w/ FG Extension 1 D Line Duc (Messenger Cover), lack. 8 Long (Each) 1 E Grip, Messenger/Neutral, Preformed for 5 W 1 F Clevis, NM, Thimble, Galvanized Steel 1 G Eyelet, NM, Thimble, 3/4, Galvanized Steel 1 H Clamp, PG Messenger to Open Wire Neutral I Clevis, Thimble, 7/8 opening, Galvanized Steel 3 J Shackle nchor, 9/16 3 K Insulator, Suspension, 15kV, Poly 5 L Insulator, Strain, Fiberglass, 6 1 M Insulator, Pin, 15kV, Vise Top N Grip, Conductor Deadend, 15kV, New 477 Spacer Cable 3 Size Grip per existing Spacer Cable Conductor (See 7 11 ) 3 O Crossarm, Deadend, F/G, 1 1 P 4 3 Crossarm, Sgl., Wood, 1, (use only 1/ of V race) 1 ENG: KR REV. NO: 1 REV. DTE: 6/18/18

80 15 kv & elow Spacer Cable Three Phase Loopover Spacer Cable to Open Wire 3 1 Sheet 3 of Q rrester, 1kV w/ Protective Cap rrester, 3kV w/ Protective Cap 3 R racket, Switch/ rrester Mounting 3 S Wire, Poly #6 Cu., (Ft.) T PG* Clamp, Parallel Groove (See 7 5 ) U DEC*W Clamp, Deadend V HLC*W Hot Line Clamp 3 W Wire, # Cu. Poly Covered (Ft.) 15 X 1 1 ** Grounding Unit, 7#1 Copperweld Y 11 4 ** Guying Unit with FG Strain Insulator & HD Guy Z ** Neutral Configuration Pin, Insulator, Long Shank Washer, Flat, Sq., 4 x 4 w/ 13/16 hole 3 NOTES 1. Install the first spacer ( ) about 4 feet from the pole as to not stress the cable. Normal spacing is 5 to 33. See DCS for spacing installation between poles.. Install the center phase of the space cable with fiberglass Strain Insulator into the top hole on the DE arm. This leaves the bottom hole for guying if needed. 3. Use DCS ground coil application on new pole installation. Use DCS 1 1 for ground rod application on existing pole installation. 4. Secondary location if present. Connect secondary neutral to pole ground. 5. Extend # poly covered ground wire ( ) from open wire neutral to the messenger. 6. For installations on a composite pole, substitute a fiberglass crossarm, Stock # , in place of the wood arm. Use electrical ground clips, stock # , to attach the ground wire to the bottom of the fiberglass crossarm. ENG: KR REV. NO: 1 REV. DTE: 6/18/18

81 15 kv & elow Spacer Cable Three Phase Tap From Open Wire Sheet 1 of ENG: KR REV. NO: 1 REV. DTE: 6/18/18

82 15 kv & elow Spacer Cable Three Phase Tap From Open Wire Sheet of Stnd./Stk. No. Description Deadend ssy, FG rm, Crossarm, Sgl, Wood, 1 (use only 1/ of V race) 1 C Connector, PG, Pole Ground to Messenger 1 D Eyelet, NM, STD, 3/4 1 E Grip, Messenger/Neutral, Preformed for 7#6 5W 1 F Clevis, NM, Thimble, Galvanized Steel 1 G Line Duc Cover (Messenger Cover), lack. 8 Long (Each) 1 H Insulator, Suspension, 15kV, Poly 3 I Insulator, Guy Strain, Fiberglass 6, 15kV 1 J Insulator, Pin, 15kV, Vice Top 1 K Pin, Insulator, Long Shank 1 L Shackle nchor, 9/16 3 M Clevis, Thimble, 7/8 Opening, Galvanized Steel N Grip, Conductor Deadend, 15kV, 477 Spacer Cable 3 Size Grip per existing Spacer Cable Conductor (See 7 11 ) 3 R LW*W Wire, Poly Covered, S.D. (ft.) (See 7 8 ) S rrester, 1kV w/ Protective Cap rrester, 3kV w/ Protective Cap 3 T racket, Switch/rrester Mounting 3 U Wire, Poly #6 CU., (FT.) V PG*W Clamp, Parallel Groove (See 7 5 ) W HLC*W Hot Line Clamp 3 X Cover, Large, Vice Type Connectors Y 1 1 ** Grounding Unit, 7#1 Copperweld Z 11 4 ** Guying Unit with FG Strain Insulator & HD Guy Hook Wire, # Cu. Poly Covered (Ft.) Washer, Flat, Sq., 4 x 4 w/ 13/16 hole 1 NOTES: 1. Install the first spacer ( ) about 4 feet from the pole as to not stress the cable. Normal spacing is 5 to 33. See DCS for spacer installation between poles.. Install the center phase of the spacer cable with fiberglass strain insulator into the top hole on the DE arm. This leaves the bottom hole for guying if needed. 3. Use DCS ground coil application on new pole installation. Use DCS 1 1 for ground rod application on existing pole installation. 4. Secondary location if present. Connect secondary neutral to pole ground. 5. Extend # poly covered ground wire ( ) from open wire neutral to the messenger. 6. For installations on a composite pole, substitute a fiberglass crossarm, Stock # , in place of the wood arm. Use electrical ground clips, stock # , to attach the ground wire to the bottom of the fiberglass crossarm. ENG: KR REV. NO: 1 REV. DTE: 6/18/18

83 15kV&elow -- SpacerCable Three Phase Lateral Tap 351 Sheet1of ENG: KR REV.NO:1 REV. DTE: 6/18/18

Poles - General Unguyed Single Phase Composite Poles Poles - General Unguyed Three Phase Composite Poles

Poles - General Unguyed Single Phase Composite Poles Poles - General Unguyed Three Phase Composite Poles Standard Description 2 4 2 Poles - General Unguyed Single Phase Composite Poles 2 4 3 Poles - General Unguyed Three Phase Composite Poles 3 3 Structural Elements - Design Limits 3 1 1 Configurations -

More information

Guying - Insulator Dimensional Requirements ** Lightning Protection & Grounding - Grounds

Guying - Insulator Dimensional Requirements ** Lightning Protection & Grounding - Grounds Standard Description 03 12 01 ** Configurations - Single Phase, 4 to 15kV 03 12 05 ** Configurations - Two or Three Phase Tangent or Angle on Wood Crossarm, 4 to 15 kv 03 12 07 ** Configurations - Two

More information

CABLE TERMINALS

CABLE TERMINALS 14 00 00 01 Sheet 1 of 1 TABLE OF CONTENTS LOCATION & PLACEMENT OF RISERS ON JOINT USE POLES STANDOFF BRACKET PLACEMENT AND GROUNDING ONE RISER WITH U GUARD, 2, 3, 4, & 5 SPLIT CONDUIT OR SCHEDULE 40 0

More information

LABOR OPERATIONS

LABOR OPERATIONS 17 00 00 01 TABLE OF CONTENTS RECONDUCTORING 4KV LOOPOVER AND SWITCH POLE RECONDUCTORING CROSSARM OR ARMLESS 1, 2, AND 3 PHASE RECONDUCTORING ANGLE OR DEADEND RECONDUCTORING FLOATING ANGLE RECONDUCTORING

More information

WILDLIFE PROTECTION

WILDLIFE PROTECTION 05 00 00 01 TABLE OF CONTENTS GENERAL INFORMATION INSTALLATION OF CRITTER LINE GUARDS INSTALLATION OF TANK MOUNTED LIGHTNING ARRESTER BRACKET GUARDS 25KV & BELOW EXISTING STRUCTURE MODIFICATION 05 00 00

More information

TABLE OF CONTENTS GUY PLACEMENT PERPENDICULAR TO LINE PARALLEL TO LINE GUYING INSULATOR DIMENSIONAL REQUIREMENTS MINIMUM CLEARANCES GUY TO CONDUCTOR

TABLE OF CONTENTS GUY PLACEMENT PERPENDICULAR TO LINE PARALLEL TO LINE GUYING INSULATOR DIMENSIONAL REQUIREMENTS MINIMUM CLEARANCES GUY TO CONDUCTOR 11 00 00 01 TALE OF ONTENTS Sheet 1 of 1 GENERAL GUY PLAEMENT PERPENDIULAR TO LINE PARALLEL TO LINE GUYING INSULATOR DIMENSIONAL REQUIREMENTS MINIMUM LEARANES GUY TO ONDUTOR HART FOR SELETION OF GUY STRAND

More information

METER INSTALLATIONS

METER INSTALLATIONS 25 00 00 01 TALE OF CONTENTS Sheet 1 of 2 SECTION INDEX 25 00 00 01 OUTDOOR POLE MOUNTED PRIAMRY METERING STRUCTURE 25 00 01 01 CUSTOMER OWNED UNMETERED D/D LIGHT INSTALLATION 25 01 05 00 PRIMARY METERING

More information

SECTION 3 - PRIMARY CONSTRUCTION OVERHEAD TABLE OF CONTENTS

SECTION 3 - PRIMARY CONSTRUCTION OVERHEAD TABLE OF CONTENTS 03.00 GENERAL CONSTRUCTION NOTES PRIMARY CONSTRUCTION PRIMARY CONSTRUCTION PIN INSULATOR INSTALLATION 03.00-02 03.00-04 03.00-20 03.02 CONNECTORS AUTOMATIC SPLICE INSTALLATION 03.02-01 INSTALLATION GUIDE

More information

Index Section 103 Joint Use. General Requirements for Installation of Attachments on Oncor Poles

Index Section 103 Joint Use. General Requirements for Installation of Attachments on Oncor Poles 103 09-17 103 Index Section 103 Joint Use Title Date Number General Requirements for Installation of Attachments on Oncor Poles... 103-100 Supply and Communication Space... 103-105 Communication Lines

More information

PART NUMBER POLE DIAMETER RANGE CARTON QTY " to 5" " to 6 3 4" " to 7 3 4" " to 8 3 4" 10

PART NUMBER POLE DIAMETER RANGE CARTON QTY  to 5  to 6 3 4  to 7 3 4  to 8 3 4 10 PH1 Offset Pole Band Bands Single Double Offset Pole Bands are used for dead-ending, guying, and mounting secondary racks on metal poles, pipe masts, or conduit. Each Pole Band Assembly contains two 1

More information

MATERIAL FOR FIBRE OPTIC LINES. General C-bracket HSU trunnion type, forged, for aluminium based OPGW conductors...

MATERIAL FOR FIBRE OPTIC LINES. General C-bracket HSU trunnion type, forged, for aluminium based OPGW conductors... 153 Contents General.................................................................................................. 154 C-bracket.................................................................................................

More information

TYPE BILT DISCONNECT SWITCHES

TYPE BILT DISCONNECT SWITCHES TYPE BILT DISCONNECT SWITCHES OUTDOOR HOOKSTICK OPERTED (DISTRIBUTION CLSS) For sectionalizing and tap applications 7.5KV through 38KV 900 -- 40,000 momentary Furnished with hooks for loadbreak tool Used

More information

Standard Compression Dead End for ACSR and ACSS Conductor CAUTION: ACSR Dead Ends Cannot Be Used on ACSS HT Conductor

Standard Compression Dead End for ACSR and ACSS Conductor CAUTION: ACSR Dead Ends Cannot Be Used on ACSS HT Conductor INS-ACA089 Installation Instructions Standard Compression Dead End for ACSR and ACSS Conductor CAUTION: ACSR Dead Ends Cannot Be Used on ACSS HT Conductor 1. Mark the conductor a distance of 3 /4 the length

More information

OUTDOOR LIGHTING

OUTDOOR LIGHTING 15 00 00 01 Sheet 1 of 1 TLE OF CONTENTS GENERL INFORMTION HID LMPS PHOTOCONTROLS LUMINIRE COMPONENTS NEM HED LUMINIRE COMPONENTS HORIZONTL LUMINIRE COMPONENTS LED RCKET MOUNT LUMINIRES LUMINIRE COMPONENTS

More information

Customer Requirements Clearance Requirements for Overhead Joint Utility Construction

Customer Requirements Clearance Requirements for Overhead Joint Utility Construction Application This standard establishes the clearances that are required on utility pole structures between electrical supply facilities owned and operated by Tacoma Power and communication facilities owned

More information

THE DAYTON POWER AND LIGHT COMPANY Original Sheet No. 15 DPL Building Courthouse Plaza Southwest Dayton, Ohio P.U.C.O. NO. 1

THE DAYTON POWER AND LIGHT COMPANY Original Sheet No. 15 DPL Building Courthouse Plaza Southwest Dayton, Ohio P.U.C.O. NO. 1 THE DAYTON POWER AND LIGHT COMPANY Original Sheet No. 15 SCHEDULE 1 Schedule of fees and charges used for determining sacrifice value, excess height and/or strength and sale costs of poles. Year % Set

More information

AMENDMENT ELECTRIC SERVICE MANUAL 2014

AMENDMENT ELECTRIC SERVICE MANUAL 2014 AMENDMENT (Pages 20,43,50,72,74,,76,78,83,86,99) ELECTRIC SERVICE MANUAL 2014 Effective April 1, 2015 18-7 6.0 SERVICE AND SERVICE ENTRANCES (General), Continued Conductor Sizing It is recommended that

More information

MINIMUM DISTRIBUTION SYSTEM CONCEPTS AND APPLICATIONS. Larry Vogt. Manager, Rates

MINIMUM DISTRIBUTION SYSTEM CONCEPTS AND APPLICATIONS. Larry Vogt. Manager, Rates MINIMUM DISTRIBUTION SYSTEM CONCEPTS AND APPLICATIONS Larry Vogt Manager, Rates Minimum Distribution System What is MDS? MDS is an analysis module of the cost-of-service study in which distribution investment

More information

When power interruptions happen.

When power interruptions happen. When power interruptions happen. We know it s never a good time to have your power go out, so we work all year pruning trees and investing in our system to cut down on problems before they start. Outage

More information

SUSPENSION 04 CLAMPS

SUSPENSION 04 CLAMPS SUSPENSION CLAMPS 04 4 SUSPENSION CLAMPS 57 Contents General... 58 Suspension clamp trunnion type, forged,... 63 Suspension clamp trunnion type, forged, with bigger angle of deflection, for aluminium based

More information

Armor Rods. Armor Rods NOMENCLATURE GENERAL RECOMMENDATIONS

Armor Rods. Armor Rods NOMENCLATURE GENERAL RECOMMENDATIONS Transmission: Section 1 NOMENCLATURE Single Support and Double Support : Identified by S and D appearing in the length column on the catalog page. Should the maximum distance between tied supports exceed

More information

Slack Span Dead-end GENERAL RECOMMENDATIONS NOMENCLATURE (440)

Slack Span Dead-end GENERAL RECOMMENDATIONS NOMENCLATURE (440) NOMENCLATURE Material Helical Leg Section: Aluminum covered steel. An aluminum alloy version is available for corrosive environment. Contact PLP. Crossover Marks: Indicates starting point for application

More information

STRAIN LINK STICK ROLLER LINK STICK ADJUSTABLE STRAIN POLES SPIRAL LINK STICK TRANSMISSION TOOLS

STRAIN LINK STICK ROLLER LINK STICK ADJUSTABLE STRAIN POLES SPIRAL LINK STICK TRANSMISSION TOOLS 172 Phone: 800-323-6606 Fax: 847-488-1285 www.hilineco.com STRAIN LINK STICK Used as insulation between rope blocks and a hot line wire grip For deadend structures and running corners Attached to conductor

More information

Wisconsin Public Utility Institute. June 28, Minimum Distribution Charges. Larry Vogt. Director, Rates Mississippi Power

Wisconsin Public Utility Institute. June 28, Minimum Distribution Charges. Larry Vogt. Director, Rates Mississippi Power Wisconsin Public Utility Institute June 28, 2017 Minimum Distribution Charges Larry Vogt Director, Rates Mississippi Power 1 Costs of Service vs. Cost Recovery Residential Service Example Assuming that

More information

CONDUCTOR CONDUCTOR. Overhead Electric Distribution Standards INTRODUCTION

CONDUCTOR CONDUCTOR. Overhead Electric Distribution Standards INTRODUCTION INTRODUCTION 1. In order to ensure safety, certain minimum clearances shall be maintained between various circuits of an overhead distribution system. Proper clearances from joint-use utilities, railroads,

More information

SERVICE ATTACHMENT ON A BUILDING WITH BUS DUCT SERVICE ENTRANCE AND INDOOR METERING

SERVICE ATTACHMENT ON A BUILDING WITH BUS DUCT SERVICE ENTRANCE AND INDOOR METERING SERVICE ATTACHMENT ON A BUILDING WITH BUS DUCT SERVICE ENTRANCE AND INDOOR METERING Obtain acceptance and specific details from the local Company office. 1. Service entrance duct (see Note 1). Company

More information

EARTH WIRE FITTINGS 08

EARTH WIRE FITTINGS 08 EARTH WIRE FITTINGS 08 8 EARTH WIRE FITTINGS 119 Contents General... 120 C-bracket... 123 Suspension clamp with bolt, with straps, for steel and copper conductors... 123 Suspension clamp with bolt, with

More information

CAT-1 Series 3. Installation Guide. The Valley Group, Inc. 871 Ethan Allen Hwy. Suite 104 Ridgefield, CT 06877

CAT-1 Series 3. Installation Guide. The Valley Group, Inc. 871 Ethan Allen Hwy. Suite 104 Ridgefield, CT 06877 CAT-1 Series 3 Installation Guide The Valley Group, Inc. 871 Ethan Allen Hwy. Suite 104 Ridgefield, CT 06877 (203) 431-0262 (203) 431-0296 FAX tvg@cat-1.com Installation of Load Cells for CAT-1 Systems

More information

S. K. Industrial Corporation

S. K. Industrial Corporation +91-8048763042 S. K. Industrial Corporation https://www.indiamart.com/skindlcorpn/ We are an ISO 9001 : 2008 certified company. We are manufacturing, exporting and supplying HT and LT transmission line,

More information

Polymer Insulators A Better Solution

Polymer Insulators A Better Solution Polymer Insulators A Better Solution October 2016 LET S CONNECT POLYMER INSULATORS Design derived from PLP s many years of worldwide experience and tested to adhere to ANSI C29.5 and ANSI 29.6 insulator

More information

TEMPORARY ELECTRIC WIRING FOR CARNIVALS, CONVENTIONS, EXHIBITIONS, FAIRS AND SIMILAR USES

TEMPORARY ELECTRIC WIRING FOR CARNIVALS, CONVENTIONS, EXHIBITIONS, FAIRS AND SIMILAR USES INFORMATION BULLETIN / PUBLIC - ELECTRICAL CODE REFERENCE NO.: LAMC 93.0230 Effective: 3-24-69 DOCUMENT NO. P/EC 2002-006 Revised: 11-17-00 Previously Issued As: RGA #7-69 TEMPORARY ELECTRIC WIRING FOR

More information

SYSTEM PROTECTION - PLATING

SYSTEM PROTECTION - PLATING INTRODUCTION 1. Plates F1 thru F10 supply only the material required for one-phase. Therefore, for threephase construction, you will be required to call for the specified plate three times at that station.

More information

OVERHEAD DESIGN MANUAL

OVERHEAD DESIGN MANUAL OVERHEAD DESIGN MANUAL Section 4 Poletop Constructions Approved by: F ZAINI ENERGEX 2018 MANUAL 00302 CONSTRUCTION SELECTION General Notes 1. Constructions should be selected according to: spanning and

More information

SECTION 8 - SWITCHES AND PROTECTIVE DEVICES TABLE OF CONTENTS

SECTION 8 - SWITCHES AND PROTECTIVE DEVICES TABLE OF CONTENTS 08.00 GENERAL DISTRIBUTION SURGE ARRESTERS 08.00-0 CUTOUTS AND ARRESTERS GENERAL 08.00-03 08.0 CUTOUTS AND ARRESTERS METAL OXIDE ARRESTERS WITH POLYMER HOUSINGS 08.0-0 APPLICATION OF DIRECT CONNECTED ARRESTERS

More information

SPIRAL VIBRATION DAMPERS FOR AAC, AAAC, ACSR, COPPER, SC/AC & SC/GZ CONDUCTORS. Part Number

SPIRAL VIBRATION DAMPERS FOR AAC, AAAC, ACSR, COPPER, SC/AC & SC/GZ CONDUCTORS. Part Number SPIRAL VIBRATION DAMPERS FOR AAC, AAAC, ACSR, COPPER, SC/AC & SC/GZ CONDUCTORS Made from high impact, UV resistant, polyvinyl chloride (PVC), they are non-corrosive and do not abrade the conductor or require

More information

Customer Requirements Pole Attachment Requirements for Telecommunications (non-rf)

Customer Requirements Pole Attachment Requirements for Telecommunications (non-rf) Application This standard establishes the attachment requirements to utility pole structures owned and operated by Tacoma Power and communication facilities owned and operated by others. This standard

More information

OUTDOOR LIGHTING

OUTDOOR LIGHTING 15 00 00 01 Sheet 1 of 1 TABLE OF CONTENTS GENERAL INFORMATION HID LAMPS PHOTOCONTROLS LUMINAIRE COMPONENTS HID NEMA HEAD LUMINAIRE COMPONENTS HID HORIZONTAL LUMINAIRE COMPONENTS LED BRACKET MOUNT LUMINAIRES

More information

Fiberglass Construction Products

Fiberglass Construction Products 12 Fiberglass Construction Products Catalog 12 Page 12-1 Fiberglass Construction Products Standoff Brackets With over 50 years of experience in manufacturing Chance Fiberglass Rod polymer insulation products,

More information

STATE OF NEW HAMPSHIRE Inter-Department Communication

STATE OF NEW HAMPSHIRE Inter-Department Communication STATE OF NEW HAMPSHIRE Inter-Department Communication DATE: February 11, 2010 AT (OFFICE): NHPUC FROM: Torn Frantz Director, Electric Division SUBJECT: DE 09-277: Petition by Public Service Company of

More information

SINGLE PHASE WIRING SPECIFICATIONS

SINGLE PHASE WIRING SPECIFICATIONS SINGLE PHASE WIRING SPECIFICATIONS 1-866-MEC-ELEC (1-866-632-3532) Office Locations: Hondo Office 237 Hwy 173 N Hondo, TX 78661-0370 Fax 830.426.3335 Dilley Office 1718 W. FM 117 Dilley, TX 78017 Fax 830.965.1425

More information

Mechanical Suspensions Single and Double

Mechanical Suspensions Single and Double Mechanical Suspensions Single and Double Supporting spans of Optical Ground Wire cable through a wide range of line angle changes, the unique design of the lightweight AFL Mechanical Suspension installs

More information

CONSTRUCTION STANDARD ELECTRIC OPERATIONS ORGANIZATION

CONSTRUCTION STANDARD ELECTRIC OPERATIONS ORGANIZATION Page 1 of 11 R1 ****This Standard Supercedes CE Macros MPR1S, MUR1S, MPR3S & MUR3S and portions of BECo Standards CS2.7-1.1, CS2.7-1.5 & CS2.7-1.7**** PRIMARY URD RISER CONSTRUCTION TABLE OF CONTENTS Page

More information

ELECTRICAL ACCESSORIES FOR 1 5 8" (41 MM) WIDTH SERIES CHANNEL

ELECTRICAL ACCESSORIES FOR 1 5 8 (41 MM) WIDTH SERIES CHANNEL ELECTRICL CCESSORIES FOR 5 8" (4 MM) WIDTH SERIES CHNNEL Page Electrical Fittings Receptacles Fixture Hangers ccessories and Connectors Junction Boxes In-Channel Joiners Swivel Hangers Cable Entrance Tubing

More information

230 kv Aluminum Bolted Bus Supports TYPE 16300, 16500, Ordering Information. or

230 kv Aluminum Bolted Bus Supports TYPE 16300, 16500, Ordering Information.   or 230 kv luminum 230 kv luminum TYPE 16300, 16500, 16700 Cable Support The 16300, 16500 and 16700 series supports are designed for mounting stranded aluminum or CSR conductors. New cable support reduces

More information

INSTALL SERVICE- ENTRANCE SYSTEMS

INSTALL SERVICE- ENTRANCE SYSTEMS SUBCOURSE EN5141 EDITION B US ARMY ENGINEER SCHOOL INSTALL SERVICE- ENTRANCE SYSTEMS INSTALL SERVICE- ENTRANCE SYSTEMS Subcourse Number EN5141 EDITION B United States Army Engineer School Fort Leonard

More information

/1-141 ///_=///E ///_=//47/1_=//

/1-141 ///_=///E ///_=//47/1_=// NOTES: 1. Ground wire to be located on same side as neutral conductor and in quadrant opposite climbing space or pole top pin. 2. Staples on ground wire shall be 2'.-0 apart except for a distance of 8'

More information

THREE PHASE WIRING SPECIFICATIONS

THREE PHASE WIRING SPECIFICATIONS THREE PHASE WIRING SPECIFICATIONS 1-866-MEC-ELEC (1-866-632-3532) Office Locations: Hondo Office 237 Hwy 173 N Hondo, TX 78661-0370 Fax 830.426.3335 Dilley Office 1718 W. FM 117 Dilley, TX 78017 Fax 830.965.1425

More information

00083FAB-DC DRAWN BY DATE CHK SCALE SIZE

00083FAB-DC DRAWN BY DATE CHK SCALE SIZE D0D/6 THIS COPY IS PROVIDED ON RESTRICTED SIS ND IS NOT TO E USED IN NY WY DETRIMENTL TO THE INTERESTS OF PNDUIT CORP. 0 5/4/8 SPLIT SIDE PNEL JGC TOP CP CURVED PERFORTED SINGLE HINGE DOOR SPLIT SIDE PNEL

More information

OVERHEAD DISTRIBUTION SWITCHES

OVERHEAD DISTRIBUTION SWITCHES HIGH VOLTAGE SWITCHGEAR & AUTOMATION EQUIPMENT SECTION 2 Overhead Distribution Switches CAT. NO: 040930G May, 2008 INERTIA Engineering & Machine Works, INC. Fax: (209) 931-8186 6665 Hardaway Road, Stockton,

More information

34.00 METERING GENERAL LABELING MULTIPLE METER ENCLOSURES ON A SINGLE PREMISE

34.00 METERING GENERAL LABELING MULTIPLE METER ENCLOSURES ON A SINGLE PREMISE 4. METERING GENERAL LABELING MULTIPLE METER ENCLOSURES ON A SINGLE PREMISE 4.-4 4. SELF-CONTAINED METERING, SINGE-PHASE INSTALLATION DETAILS /4 VOLT SINGLE-PHASE UNDERGROUND RESIDENTIAL SERVICE AND METER

More information

ELECTRIC SERVICE RULES UTILITY/CATV SERVICES Issued Jan 2016

ELECTRIC SERVICE RULES UTILITY/CATV SERVICES Issued Jan 2016 UTILITY/CATV SERVICES CHAPTER 9 900. GENERAL A. Alliant Energy receives many requests for electric service from other utilities; telephone, telecommunications companies, cable television, the Department

More information

Breathable Wall Light Traps

Breathable Wall Light Traps reathable Wall Light Traps 2017 Growers Supply ll Rights Reserved. Reproduction is prohibited without permission. Maintain controlled airflow without sacrificing blackout environments. RETHLE WLL LIGHT

More information

VORTX Vibration Damper

VORTX Vibration Damper Product Identification 1 2 3 5 4 NOMENLTURE 1. lamp & Keeper: The lamp has an extruded hook shaped profile to hang onto the cable or conductor while tightening the keeper. Together, the aluminum keeper

More information

1150 CLEARANCES 11/28/2016

1150 CLEARANCES 11/28/2016 1150 CLEAANCES 11/28/2016 ~ CFG Construction Framing Guide N CO OH Clearance to oadways & Other Surfaces - ~ CTS OH Clearance to Structures N DC OH Clearance to oadways & Other Surfaces - Design Minimum

More information

NET-ACCESS S TYPE VED READY CABINET 600mm WIDE X 1200mm DEEP FAMILY 12V343ST-DC VED TOP CAP FRONT PERFORATED SINGLE HINGE DOOR SPLIT SIDE PANEL

NET-ACCESS S TYPE VED READY CABINET 600mm WIDE X 1200mm DEEP FAMILY 12V343ST-DC VED TOP CAP FRONT PERFORATED SINGLE HINGE DOOR SPLIT SIDE PANEL THIS COPY IS PROVIDED ON RESTRICTED SIS ND IS NOT TO E USED IN NY WY DETRIMENTL TO THE INTERESTS OF PNDUIT CORP. PNEL VED TOP CP PERFORTED SINGLE HINGE PNEL SOLID RER NET-CCESS S TYPE VED REDY CINET 600mm

More information

Conductor Protection. results

Conductor Protection. results Conductor Protection results Conductor Protection Index Dampers 607... Vibration Damper 4R Stockbridge...1 Armor Rods AP8... Aluminum Armor Rods...6 APS... alvanized Steel Armor Rods...8 APAS... AluminumClad

More information

SECTION 500 METERING AND ASSOCIATED EQUIPMENT

SECTION 500 METERING AND ASSOCIATED EQUIPMENT SECTION 500 METERING AND ASSOCIATED EQUIPMENT 500.0 General Meter sockets shall be provided, installed and maintained by Customer. When the ratings of meter sockets are exceeded, transockets shall be used.

More information

Table of Contents. 1 General. 2 General Safety Precautions and Guidelines. 3 Clearances

Table of Contents. 1 General. 2 General Safety Precautions and Guidelines. 3 Clearances Issue 5, September 2011 Blue Book - Manual of Construction Procedures 1 General 1.1 Reasons for SR1421 Reissue(s)........................... 1 1 1.1.1 Reasons for SR-1421, Issue 5..........................

More information

THIS COPY IS PROVIDED ON A RESTRICTED BASIS AND IS NOT TO BE USED IN ANY WAY DETRIMENTAL TO THE INTERESTS OF PANDUIT CORP.

THIS COPY IS PROVIDED ON A RESTRICTED BASIS AND IS NOT TO BE USED IN ANY WAY DETRIMENTAL TO THE INTERESTS OF PANDUIT CORP. THIS COPY IS PROVIDED ON RESTRICTED SIS ND IS NOT TO E USED IN NY WY DETRIMENTL TO THE INTERESTS OF PNDUIT CORP. SIDE PNEL 2 TOP CP PERFORTED SINGLE HINGE KNOCK-OUTS FOR PDU POWER CORD SIDE PNEL RER PERFORTED

More information

BRACKETS, MOUNTS & HARDWARE

BRACKETS, MOUNTS & HARDWARE HIGH VOLTAGE SWITCHGEAR & AUTOMATION EQUIPMENT SECTION 6 Brackets, Mounts & Misc. Hardware CAT. NO: 040930G May, 2008 INERTIA Engineering & Machine Works, INC. Fax: (209) 931-8186 6665 Hardaway Road, Stockton,

More information

+91-8048571184 UB Exim Private Limited http://www.ubexim.in/ We are amongst the leading exporters, manufacturers, suppliers and traders, of this highly commendable and diverse range of Electrical Spares

More information

1000 SERIES SURFACE MOUNTED CLOSERS

1000 SERIES SURFACE MOUNTED CLOSERS 1000 SERIES SURFCE MOUNTED CLOSERS PPLICTIONS n For aluminum, hollow metal, or wood swinging doors and frames. n Can be used with hinge or pivot mounted door. n Mounts on 1-3/ transom without adapter plates.

More information

INSTALLATION and MAINTENANCE INSTRUCTIONS SHO SERIES ELECTRIC CABLE REELS

INSTALLATION and MAINTENANCE INSTRUCTIONS SHO SERIES ELECTRIC CABLE REELS INSTALLATION and MAINTENANCE INSTRUCTIONS SHO SERIES ELECTRIC CABLE REELS All units are provided with right hand rotation unless otherwise specified. This means that cable is pulled off spool top left

More information

Convertible - Rated 3 4-Ton /2-Ton Nylon Strap Hoists Refer to any questions about the use, application, repair or testing of this hoist to:

Convertible - Rated 3 4-Ton /2-Ton Nylon Strap Hoists Refer to any questions about the use, application, repair or testing of this hoist to: Operating and Servicing Instructions for Convertible - Rated 3 4-Ton - 1 1 /2-Ton Nylon Strap Hoists Refer to any questions about the use, application, repair or testing of this hoist to: Hubbell / Chance

More information

Center Point. Triple Axle Equalizer by Trailair. Triple Axle Equalizer. Installation and Owner s Manual. Table of Contents

Center Point. Triple Axle Equalizer by Trailair. Triple Axle Equalizer. Installation and Owner s Manual. Table of Contents Triple xle Equalizer (For ftermarket pplications) Center Point Triple xle Equalizer by Trailair Installation and Owner s Manual (For ftermarket pplications) Table of Contents Introduction... 2 Quick Facts...

More information

AMP AIR SUSPENSION KITS. HP10193: Ford F-250/350 4WD* Ford F-450* HP10194: Ford F-250/350 2WD* Ford F-450*

AMP AIR SUSPENSION KITS. HP10193: Ford F-250/350 4WD* Ford F-450* HP10194: Ford F-250/350 2WD* Ford F-450* MP IR SUSPENSION KITS HP10193: Ford F-250/350 4WD* Ford F-450* HP10194: Ford F-250/350 2WD* Ford F-450* LL KITS FOR TRUCKS INCLUDING IN-ED HITCHES; NOT FOR USE WITH CHSSIS C TRUCKS * See application guide

More information

LIGHTING CONSTRUCTION MANUAL PE CELL CONVERSION

LIGHTING CONSTRUCTION MANUAL PE CELL CONVERSION CONSTRUCTION MNUL Back to MIN INDEX Go to SECTION INDEX TYPE DESCRIPTION PGE TYPE DESCRIPTION PGE Construction type guide - PE Cell conversion - Ergon Energy Minor road overhead mains supply Minor road

More information

OPTOFIT CATALOGUE. FITTINGS FOR METALFREE (ADSS CABLES) and METAL ARMOURED (OPGW & OPPW) AERIAL CABLES WITH INTEGRATED OPTICAL FIBRES.

OPTOFIT CATALOGUE. FITTINGS FOR METALFREE (ADSS CABLES) and METAL ARMOURED (OPGW & OPPW) AERIAL CABLES WITH INTEGRATED OPTICAL FIBRES. OPTOFIT CATALOGUE FITTINGS FOR METALFREE (ADSS CABLES) and METAL ARMOURED (OPGW & OPPW) AERIAL CABLES WITH INTEGRATED OPTICAL FIBRES. EXCLUSIVE AUSTRALIAN DISTRIBUTORS B8/8 Introduction Metalfree (ADSS

More information

Section 5 Fiber Optics: FIBERLIGN Hardware for OPGW

Section 5 Fiber Optics: FIBERLIGN Hardware for OPGW FIBERLIGN Hardware for OPGW: Section Section Fiber Optics: FIBERLIGN Hardware for OPGW Table of Contents Page Fiber Optic Product Layout for OPGW...-2 FIBERLIGN ead-end for OPGW...-3 FIBERLIGN Formed Wire

More information

Company Profile. ZTT Cable was established in 1992, and now becomes a public high-tech enterprise with 33 subsidiaries, and about 7,000 employees.

Company Profile. ZTT Cable was established in 1992, and now becomes a public high-tech enterprise with 33 subsidiaries, and about 7,000 employees. Company Profile ZTT Cable was established in 1992, and now becomes a public high-tech enterprise with 33 subsidiaries, and about 7,000 employees. We provide products such as electrical fittings, optical

More information

1000 Series surface mounted closers

1000 Series surface mounted closers 1000 surface mounted closers PPLICTIONS n For aluminum, hollow metal, or wood swinging doors and frames. n Can be used with hinge or pivot mounted door. n Mounts on 1-3/4 transom without adapter plates.

More information

TOP CAP KNOCK-OUTS FOR

TOP CAP KNOCK-OUTS FOR 2 THIS COPY IS PROVIDED ON RESTRICTED SIS ND IS NOT TO E USED IN NY WY DETRIMENTL TO THE INTERESTS OF PNDUIT CORP.. VISIT OUR ON-LINE CTLOG T WWW.PNDUIT.COM FOR LIST OF CURRENT PRTS PPLICLE FOR TOP CP

More information

ENGINEERING SPECIFICATION

ENGINEERING SPECIFICATION December 206 ENGINEERING SPECIFICATION No. of 6 DATE: 2-9-6 CATEGORY SUBJECT TABLE OF CONTENTS. Overview... 2 2. General Requirements for Service... 3 3. Definitions... 3 4. Abbreviations... 5 5. References

More information

TEKNISK RIKTLINJE TR05-10E

TEKNISK RIKTLINJE TR05-10E Notes Change notes Date 1 (A) Revision of standards and new template 09 / 07 2010 2 Template changed.clause. 10.5.1.4 support clamp inserted. Clause 10.5.4.2 creepage text revised. Clause 10.6.7 Dry inserted

More information

INSULIGN Guy Strain Insulators Fiberglass

INSULIGN Guy Strain Insulators Fiberglass NOMENLTURE GENERL INFORMTION Preformed Line Products INSULIGN Guy Strain Insulator series is intended for use with down guys or pole-to-pole guys on overhead lines. The insulative fiberglass rod electrically

More information

VORTXô VIBRATION DAMPER

VORTXô VIBRATION DAMPER VORTXô VIRTION DMPER ontoured lamp Technical Support - when you need it! PLP Motion ontrol Products VORTXô Vibration Damper From the Recognized Leader in onductor Protection Much of PLP s business has

More information

Customer Requirements Downtown Secondary Network Service

Customer Requirements Downtown Secondary Network Service Application This standard describes the limitations and requirements for receiving service from the Tacoma Power secondary network system within the City of Tacoma downtown core area. In This Standard

More information

OEM INSTALLATION MANUAL

OEM INSTALLATION MANUAL G C 3.0 4 P 6 P OEM INSTLLTION MNUL Rev: 03.13.2015 Page 1 Ground Control 3.0 OEM Installation Manual System and Safety Information TLE OF CONTENTS System and Safety Information 2 Preparation 2 Criteria

More information

The reinforcing rods are incorporated in this assembly to ensure the optical fibres within the OPGW Range

The reinforcing rods are incorporated in this assembly to ensure the optical fibres within the OPGW Range OPGW Suspension Assemblies Optical Fibre Cable Same lay as OPGW outer stranding H Reinforcing rods opposite lay to OPGW outer stranding S L Application Heliformed suspension assemblies designed for use

More information

Series 900H Hydraulic Crane 27 Ton Load Ratings

Series 900H Hydraulic Crane 27 Ton Load Ratings Series 0H Hydraulic Crane 27 Ton Load Ratings DNGER N UNTRINED OPERTOR SUBJECTS HIMSELF ND OTHERS TO DETH OR SERIOUS INJURY YOU MUST NOT OPERTE THIS CRNE UNLESS You have been trained in the safe operation

More information

Directional Control Valves. General Description. Features. Specifications

Directional Control Valves. General Description. Features. Specifications echnicl Informtion Generl Description directionl control vlves re high performnce, 5-chmer, direct operted, wet rmture, solenoid controlled, 3 or 4-wy vlves. hey re ville in 2 or 3-position nd conform

More information

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 03/05/09 TSEWG TP-11: UFC N BEST PRACTICES

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 03/05/09 TSEWG TP-11: UFC N BEST PRACTICES TSEWG TP-11: UFC 3-500-10N BEST PRACTICES UFC 3-500-10N was developed by NAVFAC and was used as the starting point for the tri-services development of UFC 3-500-10, Design: Electrical Engineering. UFC

More information

THERMOLIGN Products for 3M Aluminum Conductor Composite Reinforced (3M ACCR)

THERMOLIGN Products for 3M Aluminum Conductor Composite Reinforced (3M ACCR) Products for 3M Aluminum Conductor Composite Reinforced (3M ACCR) July 2015 History of Hardware at PLP Preformed Line Products has been involved with the design, testing and production of hardware and

More information

Transmission Tools. Catalog 2250 May Transmission Tools Phone: Web: hubbellpowersystems.

Transmission Tools. Catalog 2250 May Transmission Tools Phone: Web: hubbellpowersystems. Transmission Tools Catalog 2250 May 2016 Transmission Tools 2250 May 2016 Page 2251 STRAIN LINK STICK Tested per OSHA & ASTM F711 Used as insulation between rope blocks and a hot line wire grip For deadend

More information

OEM INSTALLATION MANUAL

OEM INSTALLATION MANUAL Ground Control 3.0 (5th Wheel) 4 Point and 6 Point OEM INSTLLTION MNUL Rev: 06.15.2016 Page 1 Ground Control 3.0 5th Wheel OEM Installation Manual TLE OF CONTENTS System and Safety Information 2 Preparation

More information

MODIFICATIONS/ACCESSORIES

MODIFICATIONS/ACCESSORIES tigear_2_mod_access Page 90 Friday, October 15, 2004 1:30 PM TORQUE-RM II TORQUE-RM MXUM oncentric Reducer TIGER-2 MODIFITIONS/ESSORIES TIGER-2 MOTOR DPTER KIT TIGER-2 motor adapter kits are available

More information

SMARTBOX MOUNTING BRACKET INSTALLATION INSTRUCTIONS John Deere 1790 (24/20 ), 1770NT, and DB CCS Planters Ladder & Rear Row Mount

SMARTBOX MOUNTING BRACKET INSTALLATION INSTRUCTIONS John Deere 1790 (24/20 ), 1770NT, and DB CCS Planters Ladder & Rear Row Mount World Class Industries 3 E. Prairie Street Crystal Lake, IL 6001 Phone: -SMRTOX (opt. 1) -62-26 (opt. 1) Fax: 1-9-99 SMRTOX MOUNTING RCKET INSTLLTION INSTRUCTIONS John Deere 190 (2/20 ), 10NT, and D CCS

More information

List of materials for 1Km. Of L.T line 1-Ph., 2-Wire AB cable (1 X 25+1X16) sq.mm using 8M X 200 KG. PSC Pole

List of materials for 1Km. Of L.T line 1-Ph., 2-Wire AB cable (1 X 25+1X16) sq.mm using 8M X 200 KG. PSC Pole List of materials for 1Km. Of L.T line 1-Ph., 2-Wire AB cable (1 X 25+1X16) sq.mm using 8M X 200 KG. PSC Pole 1 L.T Stay set Complete Set 5 2 7/12 GI stay wire kg 50 3 Concreting of stay NO 5 4 Stay clamp

More information

Specifications. S&C Omni-Rupter Switches Outdoor Distribution (14.4 kv and 25 kv) Conditions of Sale

Specifications. S&C Omni-Rupter Switches Outdoor Distribution (14.4 kv and 25 kv) Conditions of Sale S&C Omni-Rupter Switches Outdoor istribution (14.4 kv and 5 kv) Specifications Conditions of Sale STNR: Seller s standard conditions of sale as set forth in Price Sheet apply. SPECIL TO THIS PROUCT: INCLUSIONS:

More information

Series 1 Steel - Straight Sections

Series 1 Steel - Straight Sections - Straight Sections H-1 -Line series able Systems - ccessories & Fittings How The Service dvisor Works We know that your time is important! That s why the color-coding system in this catalog is designed

More information

MISCELLANEOUS INDEX PAGE DATE SERIES DESCRIPTION

MISCELLANEOUS INDEX PAGE DATE SERIES DESCRIPTION MISCELLNEOUS INDEX 08/01/11 PGE DTE SERIES DESCRIPTION M-1 08/01/11 Miscellaneous Index M-2 04/16/96 M01 Tooling all M-3 04/16/96 M02 Scrap Chute Hook and Retainer racket M-4 01/03/95 M03 Scrap Chute Chain

More information

Suspension Clamps. performance

Suspension Clamps. performance Suspension Clamps performance Suspension Clamps Index olted/aluminum CFS... Corona Free Clamp for Use With Armor Rods...-3 CFS (ONG)... Corona Free Clamp for Use Without Armor Rods...-4 CFSHT... Corona

More information

EMLock Magnetic Locks

EMLock Magnetic Locks EMLock EMLock Lifetime Warranty NSI/HM 156.23 Grade 1 CSFM 3774-0324:100 ME City of New York 768-80-S GWXT uxiliary Locks CVXJ urglary Resistant Electrically Operated Door Lock UL10C Positive Pressure

More information

Vertical Housing EMLock Discount Code GK LIST. Retrofit Kit for Discontinued Locknetics 390+ PLUS

Vertical Housing EMLock Discount Code GK LIST. Retrofit Kit for Discontinued Locknetics 390+ PLUS EMLock Vertical Housing EMLock LIST Vertical Housings - Side jamb mount, aprovides 2,400 or 3,300 lbs. of holding force. 1572VV82 Vertical Housing for 1572 EMLock, 8 length, for 84" opening - INCLUDES

More information

HUBBELL Type M3 Hookstick Disconnect Switches Up to 38kV 600 or 900 Amp 40kA Momentary

HUBBELL Type M3 Hookstick Disconnect Switches Up to 38kV 600 or 900 Amp 40kA Momentary Catalog 14B January 2015 HUBBELL Type M3 Hookstick Disconnect Switches Up to 38kV 600 or 900 Amp 40kA Momentary Application The Chance Type M3 Disconnect Switch is a single-phase hookstick operated switch.

More information

CAUTION - PUT SAFETY FIRST

CAUTION - PUT SAFETY FIRST www.shoremaster.com DVS Vertical Lift (Double V Side): Frame ssembly Instructions. Models: 00DVS 0ft Wide Pontoon, 000 Capacity Part #: 0 0(with Pontoon Guide/Cradles) 00DVS 0ft Wide, 000lb Capacity Part

More information

Engineering Service Specifications. Commercial Single-Phase Current Transformer Metering Schemes

Engineering Service Specifications. Commercial Single-Phase Current Transformer Metering Schemes Engineering Service Specifications Commercial Single-Phase Current Transformer Metering Schemes Specifications for Commercial Underground Current Transformer Metering Requirements for a Single-Phase Customer

More information

Volume-III : Section-I 370 Technical Specifications

Volume-III : Section-I 370 Technical Specifications Volume-III : Section-I 370 TECHNICAL SPECIFICATION-PIERCING INSULATOR 5.1 Insulation Piercing Connectors (IPC) 5.1.1 Insulation Piercing Connectors (IPC) are used for making Tee/Tap-off/Service connectors

More information

Table of Contents. Optical Ground Wire Hardware. Tools. Assemblies. ADSS Mini-Span Hardware. ADSS Hardware. Installation Instructions

Table of Contents. Optical Ground Wire Hardware. Tools. Assemblies. ADSS Mini-Span Hardware. ADSS Hardware. Installation Instructions Table of Contents Optical Ground Wire Hardware Bolted Dead End..................................... 3 Dead End Link Plate.... 6 Comealong......................................... 7 HIBUS OPGW Suspension...

More information

STABILOY BRAND FeeDeR SOLuTIONS

STABILOY BRAND FeeDeR SOLuTIONS STABILOY BRAND Feeder Solutions DATA CENTER Introduction General Cable understands that data centers depend heavily on a steady, reliable and scalable source of power. That is why our STABILOY Brand aluminum

More information