Poles - General Unguyed Single Phase Composite Poles Poles - General Unguyed Three Phase Composite Poles

Size: px
Start display at page:

Download "Poles - General Unguyed Single Phase Composite Poles Poles - General Unguyed Three Phase Composite Poles"

Transcription

1 Standard Description Poles - General Unguyed Single Phase Composite Poles Poles - General Unguyed Three Phase Composite Poles 3 3 Structural Elements - Design Limits Configurations - Neutral ** Configurations - Single Phase, 4 to 15kV ** Configurations - Two or Three Phase Tangent or Angle on Wood Crossarm, 4 to 15 kv ** Configurations - Two or Three Phase Floating and 9 o Angles, 4 to 15 kv ** Configurations Two or Three Phase Buck Arm - 9⁰ Angle, 4 to 15 kv ** configurations - Two or Three Phase Loopovers, 4 to 15 kv ** Configurations - Single Phase Tap from Two or Three Phase Line, 4 to 15 kv ** Configurations - Single Circuit 34kV or 69 kv, Tangent ** Configurations - Double Circuit 34kV or 69 kv, Tangent 4 2 ** Crossarms & Fittings - Single & Double Wood Arms With V Braces 4 24 ** Crossarms & Fittings - Single & Double Wood Arms With Heel Brace 4 35 Crossarms & Fittings - Grid Grain Plate On Double Wood Crossarm 4 41 ** Crossarms & Fittings - Fiberglass Assembly Wildlife Protection - 25 kv and below, Cutout Cover ** Wildlife Protection - 25kV and below, Conductor Cover Single Pin ** Wildlife Protection - 25kV and below, Conductor Cover Double Pin ** Wildlife Protection - 25kV and below, Conductor Cover Deadend 6 11 ** Insulators and Supports - Static Wire Attachment ** Insulators and Supports - Secondary Clevis, to 75 Volts ** Inuslators and Supports- Pin and Insulator, Single Pin, 12 kv and Static ** Insulators and Supports - Pole Top Mounting, 12 kv & Static Insulators and Suports - Training, Fiberglass, 12 kv ** Insulators and Supports - Deadends on Pole, 12 kv ** Insulators and Supports - Deadends on Pole-Double, 12 kv ** Insulators and Supports - Deadends on Wood Arm, 12 kv ** Inuslators and Supports- Horizontal Post Insulators, 69kV Primary Conductor and Fastending - Conductor Installation, Sagging Method ** Fuses and Switches - Single Phase Sectionalizing. 1-3 Amp, 4 or 12 kv ** Fuses & Switches - Three Phase Sectionallizing, 1-3 Amp, 4 or 12 kv ** Fuses and Switches - Three Phase Sectionalizing. 6 Amp, 4 or 12 kv ** Fuses & Switches - Single Phase Tap from Single Phase, 4 or 12 kv ** Fuses & Switches - Single Phase Tap from Three Phase, 4 or 12 kv ** Fuses & Switches - Two or Three Phase Tap, Crossarm Construction, 4 or 12 kv Guying - General Guying - Insulator Dimensional Requirements 11 4 ** Guying - Assmebly - Insulator, Guy ** Guying - Distribution Anchor Guy, Porcelain Insulator ** Guying - Sub Transmission Anchor Guy, Fiberglass Insulator 11 6 ** Guying - Screw Anchors, 6, Lb. Torque Capacity ** Guying - High Torque Screw Anchors (Alternate) Lightning Protection & Grounding - General

2 12 1 ** Lightning Protection & Grounding - Grounds ** Lightning Protection & Grounding - Lightning Arrester Installation, kv - Existing Circuit ** Lightning Protection & Grounding - Lightning Arrester Installation, Single Circuit - Existing 34 & 69 kv ** Lightning Protection & Grounding - Lightning Arrester Installation, Double Circuit - 34 kv Transformers - 15kV and below-grounded Wye, 1-167kVa, Single Phase ** Transformers - 15kV and below-grounded Wye, Three Single Phase Cluster Mounted ** Cable Terminals - 15kV and Below Single Phase, #2 through 4/ ** Cable Terminals - 15kV and Below Three Phase, #2 through 4/ Overhead Lines Instructions - Crossarm Units of Assembly - Loadings ** Cable Terminals - 15 kv #2-4/ XLP/EPR Cable, Indoor - Outdoor Revision Date

3 POLES General Unguyed Single Phase Composite Pole Sheet 1 of 1 The following tables are intended to apply for unguyed pole applications in good soil. Other unguyed or partial guyed pole applications will require communication with Standards Ruling Span under NESC Heavy Loading 1 1/ AAAC Conductor (Tension = 1,2 lbs./ cond.) & 1 1/ AAAC Neutral (Tension = 1,2 lbs./wire) Line Angle Tangent Fixed Floating Deadend Corner 1 >1 & 1 >1 & 2 >2 & 4 >4 & 6 >6 & 9 Description Span length 125 & <175 Pole Type Uniform Uniform Uniform Uniform Uniform Telescopic Pole Diameter(in) /12 Pole Height (ft) Stock # Configuration ** ** ** ** ** ** Auger Size (in) Pole Depth (ft) Approx. Rake (in) Backfill Stds Ruling Span under NESC Heavy Loading 1 1/ AAAC Conductor (Tension = 1,4 lbs/ cond.) & 1 1/ AAAC Neutral (Tension = 1,4 lbs./wire) Line Angle Tangent Fixed Floating Deadend Corner 1 >1 & 1 >1 & 2 >2 & 4 >4 & 6 >6 & 9 Description Span length 175 & <225 Pole Type Uniform Uniform Uniform Uniform Uniform Telescopic Pole Diameter(in) /12 Pole Height (ft) Stock # Configuration ** ** ** ** ** ** Auger Size (in) Pole Depth (ft) Approx. Rake (in) Backfill Stds ENG: MJ REV. NO: 1 REV. DATE: 1/17/12

4 POLES General Unguyed Three Phase Composite Pole Sheet 1 of 1 The following tables are intended to apply for unguyed pole applications in good soil. Other unguyed or partial guyed pole applications will require communication with Standards Ruling Span under NESC Heavy Loading AA Conductor (Tension = 3, lbs/ cond.) & 1 1/ AAAC Neutral (Tension = 1,2 lbs/ Wire) Line Angle Tangent Fixed Floating Deadend Corner 1 >1 & 1 >1 & 2 >2 & 4 >4 & 6 >6 & 9 Description Span length 125 & <175 Pole Type Uniform Uniform Uniform Telescopic Telescopic Telescopic Pole Diameter(in) /14 12/14 12/14 Pole Height (ft) /45 55/45 55/4 Stock # Configuration ** ** ** ** ** ** Auger Size (in) Pole Depth (ft) Approx. Rake (in) Backfill Stds Ruling Span under NESC Heavy Loading AA Conductor (Tension = 3,7 lbs/ cond.) & 1 1/ AAAC Neutral (Tension = 1,4 lbs/wire) Line Angle Tangent Fixed Floating Deadend Corner 1 >1 & 1 >1 & 2 >2 & 4 >4 & 6 >6 & 9 Description Span length 175 & <225 Pole Type Uniform Uniform Uniform Telescopic Telescopic Telescopic Pole Diameter(in) /14 12/14 12/14 Pole Height (ft) /45 55/45 5/4 Stock # Configuration ** ** ** ** ** ** Auger Size (in) Pole Depth (ft) Approx. Rake (in) Backfill Stds ENG: MJ REV. NO: 1 REV. DATE: 1/17/12

5 CONFIGURATIONS Structural Elements Design Limits 3 3 Sheet 1 of General This standard gives the design limits of the structural elements employed in building standard configurations. These limits are based on the allowable loading of crossarms and pins as shown in Dist. Std. 29 4, and also on required conductor separation to prevent midspan conductor contact. 2. Angle Limits Tables 1, 2, 3, 4 and 5 specify the maximum angle capable of being turned on pins, insulators, fiberglass standoffs, combination fiberglass and porcelain standoffs, and crossarms for various types of construction. This data is based on the transverse strength of the components of the structure and the load applied to it, due to the line angles. 3. Dead End Loadings Table 6 specifies the maximum balanced dead end loading for unguyed crossarms. It shows the number of conductors permitted to dead end on a structure, depending on the size of conductor and the type of dead end structure. The data is based on standard conductor tensions and allowable equivalent horizontal loadings on the crossarm. The purpose of this table is to provide the information necessary to get the most out of a dead end structure without having to resort to crossarm guying. TABLE 1A Maximum Line Angles Capable of Being Turned on Pins and Crossarms SHORT SPAN (STD ) Conductor Size AWG or kcmil Pins (All) (See Note 4) Single Crossarm # of Conductors (12# arm limit) Without Grid Plate # of Conductors (24#) DOUBLE CROSSARM With Grid Plate (5) # of Conductors (4#) Sgl Dbl # 12# #4 ACSR / AAAC ACSR AAC T2 Penguin ACSR Rail Notes: 1. Maximum number of pins for single crossarm is 2. Maximum number of pins for double crossarm without grid plate is 4; and maximum number of pins for double crossarm with grid plate is 6. The number of conductors that can be deadended back to back (not on pins) is only limited by the strength of the joint between the arm(s) and the pole. 2. Above table based on Grade N construction. ENG: DCG REV. NO: 7 REV. DATE: 2/21/12

6 CONFIGURATIONS Structural Elements Design Limits 3 3 Sheet 2 of 11 Conductor Size AWG or kcmil TABLE 1B Maximum Line Angles Capable of Being Turned on Pins or Crossarms MEDIUM SPAN (STD ) Pins (All) (See Note 4) Single Crossarm # of Conductors (12# arm limit) Without Grid Plate # of Conductors (24#) DOUBLE CROSSARM ENG: DCG REV. NO: 7 REV. DATE: 2/21/12 With Grid Plate (5) # of Conductors (4#) Sgl Dbl # 12# #4 ACSR / AAAC ACSR AAC T2 Penguin ACSR Rail Notes: 1. Maximum number of pins for single crossarm is 2. Maximum number of pins for double crossarm without grid plate is 4; and maximum number of pins for double crossarm with grid plate is 6. The number of conductors that can be deadended back to back (not on pins) is only limited by the strength of the joint between the arm(s) and the pole. 2. Above table based on Grade N construction. TABLE 1C Maximum Line Angles Capable of Being Turned on Pins or Crossarms LONG SPAN (STD ) Conductor Size AWG or kcmil Pins (All) (See Note 4) Single Crossarm # of Conductors (12# arm limit) Without Grid Plate # of Conductors (24#) DOUBLE CROSSARM With Grid Plate (5) # of Conductors (4#) Sgl Dbl # 12# #4 ACSR / AAAC ACSR AAC T2 Penguin (45/7) ACSR Notes: 1. Maximum number of pins for single crossarm is 2. Maximum number of pins for double crossarm without grid plate is 4; and maximum number of pins for double crossarm with grid plate is 6. The number of conductors that can be deadended back to back (not on pins) is only limited by the strength of the joint between the arm(s) and the pole. 2. Above table based on Grade N construction.

7 CONFIGURATIONS Structural Elements Design Limits 3 3 Sheet 3 of 11 Conductor Size AWG or kcmil TABLE 1D Maximum Line Angles Capable of Being Turned on Pins or Crossarms EXTRA LONG SPAN (STD ) Pins (All) (See Note 4) Single Crossarm # of Conductors (12# arm limit) Without Grid Plate # of Conductors (24#) DOUBLE CROSSARM With Grid Plate (5) # of Conductors (4#) Sgl Dbl # 12# 1/ AAAC ACSR AAC T2 Penguin ACSR Rail Notes: 1. Maximum number of pins for single crossarm is 2. Maximum number of pins for double crossarm without grid plate is 4; and maximum number of pins for double crossarm with grid plate is 6. The number of conductors that can be deadended back to back (not on pins) is only limited by the strength of the joint between the arm(s) and the pole. 2. Above table based on Grade N construction. Select The Required Crossarm Assembly Unit Using The Following As A Guide 1. The above table, based on maximum span length of applicable sag table, automatically takes care of vertical loadings. For shorter span lengths the crossarm may be strong enough; however, a strength calculation should be made. See Dist. Std for examples and allowable crossarm loads. 2. Inadequate vertical strength for the number and size of conductors shown. 3. Double arms and double dead end pole top construction shall always be used. a. At all railroad crossings. Note: If tensions do not exceed 2 lbs. per conductor during heavy loading; double pins and ties may be used. Double pole top pins mounted on the face of the pole may be used to meet this requirements. (Tensions for conductors sagged in accordance with Sag Table 1 does not exceed 2 lbs. under heavy loaded conditions except for kcmil A.A. and 795 kcmil A.A.). b. On grade B circuits where the line angle exceeds 2 o. c. On grade B circuits at communications crossings, if the supply conductors are not continuous and of uniform tension in the crossing span and each adjacent span. 4. Angles shown for single or double pins refer to crossarm pins and existing pole top pins mounted on the face of the pole. 5. Grid gain plates (Dist. Std. 4 35) shall be used only when required for the larger angles shown. Use caution to insure that pin angle limits are not exceeded (2 or 3 conductors). If pin limits are exceeded, use double dead ends. 6. Above table based on grade N construction. ENG: DCG REV. NO: 7 REV. DATE: 2/21/12

8 CONFIGURATIONS Structural Elements Design Limits 3 3 Sheet 4 of 11 Table 2 Maximum Line Angle Capability of Distribution Standards Side tie in tension or compression on pin insulator of full tension take off unit. Sag Table Conductor Angle o SHORT SPAN #4 (7/1) ACSR 78 1/ AAAC, bare or poly 46 1/ ACSR, bare (12/7) ACSR, bare (18/1) ACSR (19) AAC T2 Pigeon T2 Penguin (45/7) ACSR (19) T2 12 MEDIUM SPAN #4 (7/1) ACSR 62 1/ AAAC, bare or poly 38 1/ ACSR, bare (12/7) ACSR, bare (18/1) ACSR (19) AAC T2 Pigeon T2 Penguin (45/7) ACSR (19) T2 1 ENG: DCG REV. NO: 7 REV. DATE: 2/21/12

9 CONFIGURATIONS Structural Elements Design Limits 3 3 Sheet 5 of 11 Sag Table Conductor Angle o LONG SPAN #4 (7/1) ACSR 52 1/ AAAC, bare or poly 31 1/ ACSR, bare (12/7) ACSR, bare (18/1) ACSR (19) AAC T2 Pigeon T2 Penguin (45/7) ACSR (19) T2 9 ENG: DCG REV. NO: 7 REV. DATE: 2/21/12

10 CONFIGURATIONS Structural Elements Design Limits 3 3 Sheet 6 of 11 Table 3 Maximum Line Angle Capability of Distribution Standards Dist. Stds Pole Top Pins LOAD Pole Top Pin (1# Limit, Transverse) Sag Table Conductor Angle o SHORT SPAN MEDIUM SPAN #4 (7/1) ACSR 1/ AAAC, bare or poly 1/ ACSR, bare 11.8 (12/7) ACSR, bare (18/1) ACSR 556 (19) AAC T2 Pigeon T2 Penguin 954 (45/7) ACSR 556 (19) T2 #4 (7/1) ACSR 1/ AAAC, bare or poly 1/ ACSR, bare 11.8 (12/7) ACSR, bare (18/1) ACSR 556 (19) AAC T2 Pigeon T2 Penguin 954 (45/7) ACSR 556 (19) T LONG SPAN EXTRA LONG SPAN #4 (7/1) ACSR 1/ AAAC, bare or poly 1/ ACSR, bare 11.8 (12/7) ACSR, bare (18/1) ACSR 556 (19) AAC T2 Pigeon T2 Penguin 954 (45/7) ACSR 556 (19) T2 1/ AAAC, bare or poly 1/ ACSR, bare 11.8 (12/7) ACSR, bare (18/1) ACSR 556 (19) AAC T2 Pigeon T2 Penguin 954 (45/7) ACSR 556 (19) T ENG: DCG REV. NO: 7 REV. DATE: 2/21/12

11 CONFIGURATIONS Structural Elements Design Limits 3 3 Sheet 7 of 11 Table 4 Maximum Line Angle Capability of Distribution Standards Dist. Stds ** Vertical Line Post Insulator (Tie Top) F Neck N Neck LOAD Vertical Line Post (112# Limit, Cantilever) Sag Table Conductor F Neck Angle *** N Neck Angle* SHORT SPAN #4 (7/1) ACSR 1/ AAAC, bare or poly 1/ ACSR, bare 11.8 (12/7) ACSR, bare (18/1) ACSR 556 (19) AAC T2 Pigeon T2 Penguin 954 (45/7) ACSR 556 (19) T2 NL MEDIUM SPAN #4 (7/1) ACSR 1/ AAAC, bare or poly 1/ ACSR, bare 11.8 (12/7) ACSR, bare (18/1) ACSR 556 (19) AAC T2 Pigeon T2 Penguin 954 (45/7) ACSR 556 (19) T LONG SPAN #4 (7/1) ACSR 1/ AAAC, bare or poly 1/ ACSR, bare 11.8 (12/7) ACSR, bare (18/1) ACSR 556 (19) AAC T2 Pigeon T2 Penguin 954 (45/7) ACSR 556 (19) T EXTRA LONG SPAN 1/ AAAC, bare or poly 1/ ACSR, bare 11.8 (12/7) ACSR, bare (18/1) ACSR 556 (19) AAC T2 Pigeon T2 Penguin 954 (45/7) ACSR 556 (19) T * All 15 o line angles shown for N Neck insulators are based on top groove. *** Angles shown in above table are for single insulators only. For multiple conductors on a crossarm use grade N loads in DCS for the conductor, span and line angle being considered. Compare the total transverse load with the transverse crossarm intermittent load limits shown in Table 1 of DCS ENG: DCG REV. NO: 7 REV. DATE: 2/21/12

12 CONFIGURATIONS Structural Elements Design Limits 3 3 Sheet 8 of 11 Table 5 Maximum Line Angle Capability of Distribution Standards DCS ** and ** in Compression and Tension 34 and 69 kv Polymer Horizontal Line Post Insulator (Clamp Top Line Terminal) Stock Nos and (25 LB Limit in Compression and Tension) Sag Table Conductor Angle SHORT SPAN MEDIUM SPAN LONG SPAN EXTRA LONG SPAN #4 (7/1) ACSR 1/ AAAC, bare or poly 1/ ACSR, bare 11.8 (12/7) ACSR, bare (18/1) ACSR 556 (19) AAC T2 Pigeon T2 Penguin 954 (45/7) ACSR 556 (19) T2 954 (45/7) T2 #4 (7/1) ACSR 1/ AAAC, bare or poly 1/ ACSR, bare 11.8 (12/7) ACSR, bare (18/1) ACSR 556 (19) AAC T2 Pigeon T2 Penguin 954 (45/7) ACSR 556 (19) T2 954 (45/7) T2 #4 (7/1) ACSR 1/ AAAC, bare or poly 1/ ACSR, bare 11.8 (12/7) ACSR, bare (18/1) ACSR 556 (19) AAC T2 Pigeon T2 Penguin 954 (45/7) ACSR 556 (19) T2 954 (45/7) T2 #4 (7/1) ACSR 1/ AAAC, bare or poly 1/ ACSR, bare 11.8 (12/7) ACSR, bare (18/1) ACSR 556 (19) AAC T2 Pigeon T2 Penguin 954 (45/7) ACSR 556 (19) T2 954 (45/7) T2 NL* NL* NL* NL* NL* 47 NL* NL* NL* NL* NL* NL* NL* NL* NL* NL* 8 NL* ENG: DCG REV. NO: 7 REV. DATE: 2/21/12

13 CONFIGURATIONS Structural Elements Design Limits 3 3 Sheet 9 of 11 Table 5 Maximum Line Angle Capability of Distribution Standards 69 kv Polymer Horizontal Line Post Insulator (w/ 2 Hole Line Terminal Blade) Stock No (Maximum Transverse Working Load 5 Lbs. (Tension & Compression) Sag Table Conductor Angle SHORT SPAN MEDIUM SPAN LONG SPAN EXTRA LONG SPAN #4 (7/1) ACSR 1/ AAAC, bare or poly 1/ ACSR, bare 11.8 (12/7) ACSR, bare (18/1) ACSR 556 (19) AAC T2 Pigeon T2 Penguin 954 (45/7) ACSR 556 (19) T2 954 (45/7) T2 #4 (7/1) ACSR 1/ AAAC, bare or poly 1/ ACSR, bare 11.8 (12/7) ACSR, bare (18/1) ACSR 556 (19) AAC T2 Pigeon T2 Penguin 954 (45/7) ACSR 556 (19) T2 954 (45/7) T2 #4 (7/1) ACSR 1/ AAAC, bare or poly 1/ ACSR, bare 11.8 (12/7) ACSR, bare (18/1) ACSR 556 (19) AAC T2 Pigeon T2 Penguin 954 (45/7) ACSR 556 (19) T2 954 (45/7) T2 #4 (7/1) ACSR 1/ AAAC, bare or poly 1/ ACSR, bare 11.8 (12/7) ACSR, bare (18/1) ACSR 556 (19) AAC T2 Pigeon T2 Penguin 954 (45/7) ACSR 556 (19) T2 954 (45/7) T2 NL* NL* NL* NL* NL* NL* NL* NL* NL* NL* NL* NL* NL* 83 NL* NL* NL* NL* NL* NL* NL* 71 NL* NL* NL* NL* NL* NL* NL* 65 NL* NL* ENG: DCG REV. NO: 7 REV. DATE: 2/21/12

14 CONFIGURATIONS Structural Elements Design Limits 3 3 Sheet 1 of 11 TABLE 7 TABLE GIVING MAXIMUM NUMBER OF CONDUCTORS THAT CAN BE DEADENDED ON UNGUYED CROSSARMS (BASED ON STANDARD CONDUCTOR TENSIONS) Conductor Size # 4 ACSR 7/1 Bare 1/ AAAC (7 ) Bare 1/ ACSR (6/1) Bare ACSR (18/1) Bare ACSR T2 Pigeon AA (19) Bare ACSR T2 Penguin 954 ACSR (45/7) Bare Sag Table Span Short Medium Long Short Medium Long X Long Short Medium Long X Long Short Medium Long X Long Short Medium Long X Long Short Medium Long X Long Short Medium Long X Long Short Medium Long X Long Sgl Arm DE Dbl Arm DE Double Arm DE Fiberglass DE Arms 3 1/2 x 4 1/2 x 8Ft 3 3/4 x 4 3/4 x 1Ft 8 Ft. 1 Ft ENG: DCG REV. NO: 7 REV. DATE: 2/21/12

15 CONFIGURATIONS Structural Elements Design Limits 3 3 Sheet 11 of 11 Conductor Size 556 AAC T2 Dahlia Sag Table Span Short Medium Long X Long Sgl Arm DE Dbl Arm DE Double Arm DE Fiberglass DE Arms 3 1/2 x 4 1/2 x 8Ft 3 3/4 x 4 3/4 x 1Ft 8 Ft. 1 Ft ENG: DCG REV. NO: 7 REV. DATE: 2/21/12

16 CONFIGURATIONS Neutral ** Sheet 1 of THRU THRU W/EXT DEADEND DEG. ANGLE T CORNER LOOP AROUND THRU W/TAP THRU W/EXT. W/TAP THRU W/EXT. W/TAP ON BACK SIDE THRU X ARM THRU DBLE. X ARM DEADEND X ARM DEADEND TENSION > 15 LBS. ENG: EJB REV. NO: 8 REV. DATE: 5/19/216

17 CONFIGURATIONS Neutral ** Sheet 2 of 2 Stnd./ Stk. No. Description ** A Clevis, Secondary B Single Clevis Extension C Bolt, Mach, ¾ x1 1 D Crossarm Pin and Insulator 1 E SDEA*W Deadend (See ) F PG* See Std G TT*W TopTie H DTT*W Double Top Tie I DEA*W Deadend (See 7 11 ) 1 J Eyelet, ¾ 1 K Double Clevis 1 1 L Washer, Square, ¾ M 12 1** Grounding Unit 1 NOTE: If the deadend tension is greater than 15 lbs., use Dist. Std ENG: EJB REV. NO: 8 REV. DATE: 5/19/216

18 CONFIGURATIONS Single Phase 4 to 15 kv ** Sheet 1 of 4 C1 D1 E1 F1 G1 B1 H1 A1 FACE OF POLE Tangent, Single Pin Tangent, Double Pin A,D Angle, Single Pin Angle, Double Pin Guy Pole Top Pin 1. See DCS 3 3 for angle and span length limitations. 2. See DCS for unguyed composite pole application. 3. Composite pole has factory installed (internal) pole ground in quadrant B1, wood pole may require pole ground based on application. 4. See DCS ** for neutral configuration. 5. Use Pole eye plate Stk # on composite pole. 6. Double coil washer is not required on composite pole. Stnd. / Stk. No. Description ** A Insulator, Pole Top, Sgl Pin Insulator, Pole Top, Dbl Pin 1 1 D TT*W Single Top Tie ST*W Single Side Tie 1 DDT*W Double Top Tie 1 DST*W Doudle Side Tie 1 3.@ I Grounding Unit, Wood Pole Grounding Unit, Composite Pole @ J ** Guying Unit 1 1 K Neutral, Thru @ Neutral, Thru w/extension ENG: MJ REV. NO: 8 REV. DATE: 9/14/15

19 CONFIGURATIONS Single Phase 4 to 15 kv ** Sheet 2 of 4 C1 D1 E1 F1 G1 B1 H1 A1 FACE OF POLE 4 B J 5 F J 3 I Floating Angle 1 NOTES: 1. See DCS 7 16 for angle limitations. 2. See DCS for unguyed composite pole application. 3. Composite pole has factory installed (internal) pole ground in quadrant B1. Wood pole may require pole ground based on application. 4. See DCS ** for neutral configuration. 5. Use pole eye plate Stk # on composite pole. Stnd. / Stk. No. Description ** 4 B Insulator, Floating Angle F SC*W Clamp, Suspension 1 3.@ I Grounding Unit, Wood Pole Grounding Unit, Composite Pole 1 5.@ J ** Guying Unit 2 4.@ K Neutral, Thru Neutral, Thru w/extension 1 ENG: MJ REV. NO: 8 REV. DATE: 9/14/15

20 CONFIGURATIONS Single Phase 4 to 15 kv ** Sheet 3 of H C E G 8 C 6 Guy 6 Guy Guy W/FG Extension W/O FG Extension Deg. Angle W/FG Extension W/O FG Extension Deadend D D or H H G H 22 A 6 E 6 22 GUY 5 B G GUY I GUY 3 I W/FG Extension W/O FG Extension Loopover W/FG Extension W/O FG Extension Tap ENG: MJ REV. NO: 8 REV. DATE: 9/14/15

21 CONFIGURATIONS Single Phase 4 to 15 kv ** Sheet 4 of 4 NOTES: 1. Use FG extension if application requires. 2. See DCS for unguyed composite pole application. 3. Composite pole has factory installed (internal) pole ground in quadrant B1. Wood pole may require pole ground based on application. 4. See DCS ** for neutral configuration. 5. Use pole eye plate Stk # on composite pole. 6. Double coil washer is not required on composite pole. Stnd. / Stk. No. Description ** A Pole Top, Loopover w/fg Extension Pole Top, Loopover w/o FG Extension C Deadend w/fg Extension Deadend w/o FG Extension 1 2 D TT*W Top Tie E DEC*W Clamp, Deadend G PG* See DCS H PLW*W Wire, Poly Covered, (ft.) I Grounding Unit, Wood Pole Grounding Unit, Composite Pole J ** Guying Unit K Neutral, Thru Neutral, Deadend Neutral, Corner Neutral, Thru w/tap 1 1 ENG: MJ REV. NO: 8 REV. DATE: 9/14/15

22 CONFIGURATIONS Two or Three Phase Tangent Or Angle On Wood Crossarm 4 to 15 kv ** Sheet 1 of 3 C, D B 12 A 4 6 Guy 6 Tangent 8 Sgle. Arm Angle 8 Sgle. Arm Tangent 1 Sgle. Arm Angle 1 Sgle. Arm NOTES: 1. See DCS 3 3 for angle and span length limitations. 2. See DCS 4 2 ** for arm detail. 3. For 2 phase configuration, eliminate the center phase position. 4. See DCS for unguyed composite pole application. 5. Composite pole has factory installed pole ground; wood pole may require pole ground based on application. 6. See DCS ** for neutral configuration ft. crossarm available AmerenMO only. Stnd. / Stk. No. Description ** A Crossarm, 8 Sgl Crossarm, 1 Sgl B Insulator, Arm, Sgl C Insulator, Pole Top, Sgl D TT*W Sgl Top Tie ST*W Sgl Side Tie ENG: MJ REV. NO: 9 REV. DATE: 1/6/12

23 CONFIGURATIONS Two or Three Phase Tangent Or Angle On Wood Crossarm 4 to 15 kv ** Sheet 2 of 3 G GUY A 6 TANGENT 1 SGLE. ARM ANGLE 1 SGLE. ARM UNDERBUILD 3 2 NOTES: 1. See DCS 3 3 for angle and span length limitations. 2. Underbuild cover available AmerenIL only. Stnd. / Stk. No. Description ** A Crossarm, 1 Sgle C Insulator, Arm E TT*W Top Tie, Sgl Pin 3 2 ST*W Side Tie, Sgl Pin 3 2 2@ G Cover Single Pin 1 1 ENG: MJ REV. NO: 9 REV. DATE: 1/6/12

24 CONFIGURATIONS Two or Three Phase Tangent Or Angle On Wood Crossarm 4 to 15 kv ** Sheet 3 of 3 D C,F B Guy 6 TANGENT 8 SGLE. ARM ANGLE 8 SGLE. ARM ANGLE DBLE. ARM SIDE ARM NOTES: 1. See DCS 3 3 for angle and span length limitations ft. alley arm available AmerenMO only. 3. Cover available AmerenIL only. Stnd./ Stk. No. Description ** B Sidearm, 8 Sgle Sidearm, 8 Dble. 1 1 C Insulator, Arm D Insulator, Pole Top E TT*W Top Tie 3 2 ST*W Side Tie 3 2 DST*W Double Side Tie 3 2 3@ F Cover Single Pin 1 1 ENG: MJ REV. NO: 9 REV. DATE: 1/6/12

25 CONFIGURATIONS Two or Three Phase Floating and 9 o Angles 4kV to 15kV ** Sheet 1 of 2 B F W/O EXTENSION W/EXTENSION J GUY GUY J GUY 6 4 GUY GUY 36 6 GUY K I 3 2 Floating Angle Deadend w/fg Extension Deadend w/o FG Extension ENG: MJ REV. NO: 6 REV. DATE: 1/19/11

26 CONFIGURATIONS Two or Three Phase Floating and 9 o Angles 4kV to 15kV ** Sheet 2 of 2 NOTES: 1. Use pole eye plate Stk # on composite poles. 2. See DCS 3 3 for design limitations. 3. See DCS for unguyed composite pole application. 4. Composite pole has factory installed pole ground. Wood pole may require pole ground based on application. 5. See DCS ** for neutral configuration. 6. Guy attachment should be centered between phases and between phase and neutral. Stnd. / Stk. No. Description ** Ph 2 Ph A Insulator, Floating Angle 3 2 B Deadend w/fg Extension Deadend w/o FG Extension 2 D PG* See Std E DEC*W Deadend Clamp F SC*W Suspension Clamp 3 G PLW*W Wire, Poly covered, (Ft.) I Grounding Unit, Grounding Unit, Composite Pole J ** 5@ K Neutral, Corner Neutral, Tangent/Angle or 26 Install Connector or Jumper ENG: MJ REV. NO: 6 REV. DATE: 1/19/11

27 CONFIGURATIONS Two or Three Phase Buck Arm 9 o Angle 4 to 15kV ** Sheet 1 of 2 F F D GUY E,G J D 2 GUY 3 E,G J GUY GUY D C 4 F D F D W/O EXTENSION D 1 E W/EXTENSION 3 2 C J 1 D I H FG Arm, Pole w/o Ext FG Arm, Pole w/ext FG Arm, Pole w/o Ext FG Arm, Pole w/ext ENG: MJ REV. NO: 8 REV. DATE: 2/17/12

28 CONFIGURATIONS Two or Three Phase Buck Arm 9 o Angle 4 to 15kV ** Sheet 2 of 2 NOTES: 1. See DCS 4 41 for arm strength. 2. Attach guy to bracket of fiberglass arm. 3. Use 1 deadend arm with F/G extension on pole for underbuild application. 4. For 2 phase construction, eliminate the center phase position. 5. See DCS for unguyed composite pole application. 6. Composite pole has factory (internal) installed pole ground; wood pole may require pole ground based on application, and underbuild uses existing pole ground crossarm available AmerenMo only. 8. Deadend on pole w/o fiberglass extension available AmerenMo only. 9. See DCS ** for neutral configuration. Stnd. / Stk. No. Description ** A Deadend Assy., F/G, Deadend Assy., F/G, C Deadend w/fg Extension Deadend w/o FG Extension 1 2 D Deadend on Arm E Insulator on Arm F PG* See Std G TT*W Top Tie, Sgl Pin DEC*W Clamp, Deadend @ H Neutral Deadend I Neutral PG Clamp J PLW*W Lead Wire,Poly Covered, Ft @ K Grounding Unit, Grounding Unit, Composite Pole @ L ** Guying 252 or 26 Install Connector or Jumper ENG: MJ REV. NO: 8 REV. DATE: 2/17/12

29 CONFIGURATIONS Two or Three Phase Loopovers 4 to 15kV ** Sheet 1 of 5 POLE TOP F/G ARM F C 7 C P W/EXTENSION C W/O EXTENSION G D A 8 K GUY 2 Deadend 8 Arm, Pole w/ext. Deadend 8 Arm, Pole w/o Ext. Deadend 1 Arm, Pole w/ext. Deadend 1 Arm, Pole w/o Ext. 5 I NOTES: 1. See DCS 4 41 for arm strength. 2. Attach guy to center bracket of fiberglass arm for difference in tension. 3. For 2 phase construction, eliminate the center phase position 4. Contact Standards using unguyed composite pole for difference in conductor tension application. 5. Composite pole has factory (internal) installed pole ground; wood pole may require pole ground based on application crossarm available AmerenMO only. 7. Deadend on pole w/o fiberglass extension available AmerenMO only. 8. See DCS ** for neutral configuration. ENG: MJ REV. NO: 9 REV. DATE: 2/17/12

30 CONFIGURATIONS Two or Three Phase Loopovers 4 to 15kV ** Sheet 2 of 5 Dist. Std. Or Stk. No. Description ** A Deadend Assy. FG, Deadend Assy. FG, C Loopover w/fg Extension, Pole Top Loopover w/o FG Extension, Pole Top 1 1 D Loopover, Sgl Arm F DEC*W Clamp, Deadend G TT*W Top Tie, Sgl Pin I Grounding Unit, Wood Pole Grounding Unit, Composite Pole J PG* See Std @ K Neutral, Thru P PLW*W Lead Wire, Poly covered, Ft or 26 Install jumper ENG: MJ REV. NO: 9 REV. DATE: 2/17/12

31 CONFIGURATIONS Two or Three Phase Loopovers 4 to 15kV ** Sheet 3 of 5 P P J P P G G 8 8 C E 6 C E W/EXTENSION W/O EXTENSION Pole Top w/o Extension Pole Top w/extension Underbuild Dist. Std. Or Stk. No. Description ** C Pole Top Loopover w/extension Pole Top Loopover w/o Extension 1 1 E Looparound, Pole F DEC*W Clamp, Deadend G TT*W Top Tie, Sgl Pin J PG* See Std P PLW*W Lead Wire, Poly covered, Ft or 26 Install jumper ENG: MJ REV. NO: 9 REV. DATE: 2/17/12

32 CONFIGURATIONS Two or Three Phase Loopovers 4 to 15kV ** Sheet 4 of 5 P J C L J 1 D G D 2 K DE Assy. 1 Arm UNDERBUILD F/G ARM 8 Arm SIDEARM NOTES: 1. Wildlife cover required for AmerenIL only. ENG: MJ REV. NO: 9 REV. DATE: 2/17/12

33 CONFIGURATIONS Two or Three Phase Loopovers 4 to 15kV ** Sheet 5 of 5 Dist. Std. Or Stk. No. Description ** C Pole Top Loopover 1 1 D Loopover Arm E Looparound F DEC*W Deadend Clamp G TT*W Top Tie I Crossarm, DE Assy., 1 1 J PG* See Std P PLW*W Lead Wire, Poly covered, Ft K Sidearm, Double, @ L Wildlife Cover DE 252 or 26 Install jumper ENG: MJ REV. NO: 9 REV. DATE: 2/17/12

34 CONFIGURATIONS Single Phase Tap from Two or Three Phase Line 4 to 15kV ** Sheet 1 of 2 2 MAINTENANCE AND LIMITED USE ONLY G OR F E H G OR F 16 B C F 18 3 D I E H GUY 24 A F 74 1 GUY G OR F I E F G OR F J D A H I D E F E G OR F 3 A H D H C B GUY GUY F ARMLESS CONSTRUCTION Near Phase Top or Far Phase CROSSARM CONSTRUCTION Near Phase Top Phase Far Phase Notes 1. See Dist. Std. 3 1 for neutral spacing information. May be reduced to 4 if pole space is limited. 2. This standard to be used only for non fused single phase taps that do not pass through wooded areas and are of limited length (1 or 2 spans). ENG: MJ REV. NO: 5 REV. DATE: 2/17/12

35 CONFIGURATIONS Single Phase Tap from Two or Three Phase Line 4 to 15kV ** Sheet 2 of 2 Stnd. / Stk. No. Description ** A Assembly Standoff, 24 FG B Shackle Deadend 2 C Insulator Deadend, 12 kv 1 D Insulator Standoff, 18 LD Insulator Crossarm E PLW*W Lead Wire, Poly Covered Ft F PG* See Std G HLC*W Hot Line H DEC*W Deadend Clamp or 26 Install connector @ I TT*W Top Tie 1 J ST*W Side Tie 1 ENG: MJ REV. NO: 5 REV. DATE: 2/17/12

36 CONFIGURATIONS ** Single Circuit 34kV or 69kV Tangent Structure for Line Angle < 1 o Sheet 1 of 3 AA SHIELDED MIN. A AA 18º 135º 225º 9º 27º 45º 315º º WOOD FACE OF POLE SHIELDED 6 6 MIN. 1 RAKE 1 A BB BB 6 MIN. 6 MIN. B or C 4 F KV INS KV INS. BB SECTION AA AA º BB 6 MIN. 6 MIN. CL E 1 34KV INS KV INS MIN. º SECTION BB BB MIN. 1 F 3 B or C IL & MO 69 KV IL & MO 69 KV MO 34 KV MO 34 KV Stnd./Stk. No. Description ** A Static Support w/susp. Clamp B Insul., 34kV, Horz., Sgl Post w/clamp Top 3 C Insul., 69kV, Horz., Sgl Post w/clamp Top Insul., 69kV, Horz., Sgl Post w/susp. Clamp 3 E TC*W Clamp, Top, Tang/Ang, Cond SC*W Clamp, Susp, Tang/Ang, Cond. 3 F Grounding, Wood Pole Grounding, Composite Pole ENG: KR REV. NO: 3 REV. DATE: 1/22/216

37 CONFIGURATIONS ** Single Circuit 34kV or 69kV Tangent Structure for Line Angle < 1 o Sheet 2 of 3 6 AA 6 MIN. 6 6 MIN. BB 7 6 MIN. B 1 A AA C E 1 18º 135º 225º 9º 45º º 27º 315º WOOD FACE OF POLE BB SECTION AA AA º AA 6 6 MIN. D 6 MIN. BB 6 MIN. A 1 4 AA 1 BB C E 1 Ë ËËË Ë ËË MIN. º 3 SECTION BB BB 4 Stnd./Stk. No. Description ** 3 4 A Static Support w/susp. Clamp 1 B Insul., 69 kv, Horz. Sgl Post w/clamp Top Insul., 69 kv, Horz., Sgl Post w/susp. Clamp C Insul., 69 kv, Horz., Dbl Post w/clamp Top Insul., 69 kv, Horz., Dbl Post w/susp. Clamp 1 D TC*W Clamp, Top, Tang/Ang, Cond. 1 3 SC*W Clamp, Susp., Tang/Ang, Cond. 1 E Grounding, Wood Pole Grounding, Composite Pole 1 F Insul, 138 kv, Horz.,Dbl Post w/susp. Clamp ENG: KR REV. NO: 3 REV. DATE: 1/22/216

38 CONFIGURATIONS ** Single Circuit 34kV or 69kV Tangent Structure for Line Angle < 1 o Sheet 3 of 3 NOTES: 1. Install pole ground on wood pole as shown on configuration. Composite pole is pre assembled with #2 Str. Cu. Pole ground at 45 degree quadrant. See DCS or for grounding detail. 2. A taller pole shall be selected to replace existing 4 spacing and also to provide adequate ground clearance. If taller pole does not provide adequate ground clearances, consider utilizing Standard This standard is to be used where a future second circuit is anticipated or where constrained by horizontal clearance requirements or right of way issues. 4. Modify configuration 1 to 3 for additional clearance or use 138kV insulator to maintain additional horizontal separation if galloping is a concern. 5. If future circuits are anticipated reposition back to back insulator arrangement to upper position to 3 if strength requirements and shielding angle are met. 6. Use 7 6 spacing for tangent structure and 7 spacing for deadend structure. (use top bolt of fiberglass arm) 7. Install ground clamp above grade on wood and below grade on composite pole. See DCS 12 1**. 8. Use composite pole for storm structure as existing maintenance replacement or new line installation. See DCS for storm pole selection. ENG: KR REV. NO: 3 REV. DATE: 1/22/216

39 CONFIGURATIONS ** 34kV or 69kV Tangent Structure for Line Angle <1 o Sheet 1 of 2 LIMITED USE STANDARD 6 2 B BB 12 BB D,F BB 6 6 D,F BB 12 Ë Ë 7 6 MIN. 3 Ë ËËË Ë SECTION BB BB 7 6 MIN. 3 ËË Ë 69 KV KV KV Stnd./Stk. No. Description ** B Ins., 34 kv, Vert. Tie Top F Neck w/tie Ins., 69 kv, Vert. Tie Top N Neck w/tie D Insul., 69 kv, Horz., Dbl Post w/clamp Top Insul., 69 kv, Horz., Dbl Post w/susp. Clamp 1 3 F TC*W Clamp, Top, Tang/Ang, Cond SC*W Clamp, Susp., Tang/Ang, Cond. 2 6 G Grounding, Wood Pole Grounding, Composite Pole 1 1 H ** Arrester Assy. 1 1 L Insul, 138 kv, Horz., Dbl Post w/susp. Clamp ENG: KR REV. NO: 5 REV. DATE: 1/14/216

40 CONFIGURATIONS ** 34kV or 69kV Tangent Structure for Line Angle <1 o Sheet 2 of 2 NOTES: 1. A taller pole should be selected to replace existing 4 phase spacing and also to provide adequate ground clearance. 2. See Dist. Std for lighting arresters application and construction. 3. Use 7 6 distance to tangent and 7 to deadend crossarm (top bolt on FG arm) hole. 4. Use 138kV insulator to maintain horizontal separation if galloping is a concern. ENG: KR REV. NO: 5 REV. DATE: 1/14/216

41 CROSSARMS AND FITTINGS Single and Double Wood Arms With V Braces 4 2 ** Sheet 1 of 2 4 E,F G,H 18 1/ /2 18 1/2 N C,F,P M B A E,F G,H C,F,P N 18 M B 6 4 A 6 Sgle. 6 Dble Sgle. 8 Dble E,F 19 O 1 18 N C,F,P,A 6 G,H O D,F,P,A 1 E,F 19 G,H C,F,P A 6 N M 1 Sgle Dble kV 1 Dble M 1 Dble Verticaly Notes: 1 Field drill if required. ENG: WYW REV. NO: 15 REV. DATE: 3/11/16

42 CROSSARMS AND FITTINGS Single and Double Wood Arms With V Braces 4 2 ** Sheet 2 of 2 Stnd. / Stk. No. Description 4 2 ** A Arm Cross 3 1/2 x 4 1/2 x Arm Cross 3 1/2 x 4 1/2 x Arm Cross 3 1/2 x 4 1/2 x Arm Cross 3 3/4 x 4 3/4 x 1 2 B Brace, 37 V Brace, 6 x 18 V C Bolt Machine ¾ x D Bolt, Machine ¾ x E Bolt, Dble., Arm, 5/8 x F Washer, Square, ¾ G Bolt, Mach., 1/2 x I Washer, Square, ⅝ H Washer, Round, 1/ M Bolt, Mach., 5/8 x N Washer Lock, Galvanized 1/2 Dbl. Coil Type P Washer Lock, Galvanized ¾ Dbl. Coil Type O Bolt Dbl Aiming, ½ x 24 2 ENG: WYW REV. NO: 15 REV. DATE: 3/11/16

43 CROSSARMS AND FITTINGS Single and Double Side Wood Arms With Heel Brace 4 24 ** Sheet 1 of D, F, M E, F, M 2 M, G, F NOTES: Single Arm M, G, F 5 1/2 9 1/8 Dia. Pole Double Arm 9 1/8 14 3/4 Dia. Pole Heel brace step, Stock No is optional and is not shown in material list. 2. Field drill, if required. Stnd. / Stk. No. Description 4 24 ** A Arm, Cross 3 1/2 X 4 1/2 X Arm, Cross 3 1/2 x 4 1/2 x B Plate H.B., 8 3/4 13 3/ Plate H.B., 13 3/ C Brace Heel, D Bolt, D.A., 5/8 x E Bolt Mach., 5/8 x F Washer, Square, 5/ G Bolt Mach., 5/8 x H Bolt, Mach., 1/2 x J Washer Round, 1/2 1 1 K Bolt, Mach., 5/8 x L Bolt, Mach., 5/8 x M Washer 5/8 Dbl. Coil Spring N Bolt, Dbl. Arm, 5/8 x ENG: MJ REV. NO: 4 REV. DATE: 4/12/11

44 CROSSARMS AND FITTINGS Grid Gain Plate On Double Wood Crossarm 4 35 Sheet 1 of 1 NOTES: 1. Grid gain plates are to be used only when the line angle cannot be turned on normal double crossarm assemblies. For maximum line angles that may be turned with or without grid gain plates see DCS The grid gain plate should be mounted between the pole and the crossarm so that the curvature of the plate matches the curvature of the pole. Stnd. / Stk. No. Description 4 35 Req d A Plate, Gain, Grid, Crossarm 2 ENG: MJ REV. NO: 1 REV. DATE: 8/1/11

45 CROSSARMS AND FITTINGS Fiberglass Assembly 4 41 ** Sheet 1 of 3 TANGENT B 11/16 HOLE A 12 13/16 GUY EYE (2) 96 2 WIRE F/G TANGENT A A B 11/16 HOLE A O/ 13/16 O/ 1 5/ A O/ 13/16 C O/ 13/16 13/16 GUY EYE (2) 12 B B B B 2 WIRE F/G TANGENT ENG: WYW REV. NO: 12 REV. DATE: 3/1/16

46 CROSSARMS AND FITTINGS Fiberglass Assembly 4 41 ** Sheet 2 of 3 DEADEND B 11/16 HOLE A C A 13/16 GUY EYE (2) 72 2 WIRE F/G DEADEND B 11/16 HOLE 2 13/16 15/16 HOLES 12 A A O/ 13/16 O/ 1 5/8 13/16 GUY EYE (2) O/ 13/16 2 WIRE F/G DEADEND O/ 13/16 11/16 HOLE B B C Max. Balanced Working Load per Phase 2 Wire , lbs. 6 Ft , lbs. 8 Ft , lbs. 1 Ft. 13/16 GUY EYE (2) 12 B B 2 WIRE F/G DEADEND ENG: WYW REV. NO: 12 REV. DATE: 3/1/16

47 CROSSARMS AND FITTINGS Fiberglass Assembly 4 41 ** Sheet 3 of 3 7 1/2 7 1/2 54 1/ / ALLEY ARM ALLEY ARM NOTES: 1. Unbalanced loads require arm guys. 2. All dimensions are for reference only and may vary slightly depending on manufacturer. Stnd. / Stk. No. Description 4 41 ** A Crossarm, Deadend, F/G, 8, 2 Pos Crossarm, Deadend, F/G, 1, 2 Pos Crossarm, Deadend, F/G, Crossarm, Tangent, F/G, Crossarm, Tangent, F/G, Crossarm, Alley, F/G, Crossarm, Alley, F/G, 1 1 B Bolt Mach., 3/4 x C Washer, Curved, SQ, ¾ D Lock Nut, ¾ ENG: WYW REV. NO: 12 REV. DATE: 3/1/16

48 WILDLIFE PROTECTION 25kV & Below Cutout Cover Sheet 1 of 1 The cutout live parts cover shown in this standard shall be used on the Ameren Distribution System to prevent circuit outage from wildlife contact. The cover is not intended for personal protection. CAUTION: AT TEMPERTURES BELOW O F THE CUTOUT COVERS BECOME RIGID AND LOSE THEIR FLEXIB- ILITY. INSTALLING THE COVERS WITH A HOTSTICK MAY CAUSE THE COVERS TO BREAK. NOTES: 1. Can be installed with live line tools. 2. Refer to Dist. Std ** for cutout installation. 3. The cover is intended for wildlife outage only. 4. Install the cutout cover from the front side. Push the cutout cover around the conductors. Pull the cover down until the interior fingers fully engage the sleet hood. Stnd. / Stk. No. Description ** 1 A Cover, Cutout 1 B 111 Cutout cover Installation 1 ENG:JWC REV. NO: 1 REV. DATE: 1/21/15

49 WILDLIFE PROTECTION 25kV & Below Conductor Cover Single Pin ** Sheet 1 of 1 The conductor and insulator cover shown in this standard shall be used on Ameren Distribution System to prevent avian outage from distribution facilities where horizontal conductor spacing is less than five feet. The cover is not intended for personal protection. B A 1 NOTES: 1. The cover is intended for wildlife outage only. 2. The cover can be installed with live line tools. 3. Cover fits #6 to 556 conductor on 55 5 pin, and 56 1 pin. 4. Install two covers on two interior positions when existing arm has four conductor configuration. 4 Stnd. / Stk. No. Description ** 1 2 A Cover, Single Pin Configuration 1 2 B Cover, Extension Arm 2 4 C 111 Wildlife cover Installation 1 2 ENG: MJ REV. NO: 1 REV. DATE: 9/29/11

50 WILDLIFE PROTECTION 25kV & Below Conductor Cover Double Pin ** Sheet 1 of 1 The wire and insulator cover shown in this standard shall be used on Ameren Distribution System to prevent avian outage from distribution facilities where horizontal conductor spacing is less than five feet. The cover is not intended for personal protection. B A 1 NOTES: 1. The cover is intended for wildlife outage only. 2. The cover can be installed with live line tools. 3. Install two covers on two interior position when existing arm has four conductor configuration. 3 Stnd. / Stk. No. Description ** 1 2 A Cover, Double pin configuration 1 2 B Cover, Extension arm 1 4 C 111 Wildlife Cover Installation 1 2 ENG: MJ REV. NO: 1 REV. DATE: 9/29/11

51 WILDLIFE PROTECTION 25kV & Below Deadend Cover ** Sheet 1 of 1 The conductor and insulator covers shown in this standard shall be used on the Ameren Distribution System to prevent wildlife outages on distribution facilities where horizontal conductor spacing is less than five feet. The cover is not intended for personal protection. C B A 1 1. The cover is intended for wildlife protection only. 2. Item A can be installed using live line tools if required. 3. If configuration has four cross arms, use standard Item B is required if the jumper is bare conductor. Stnd. / Stk. No. Description ** A Cover, DE 2 4 4@ B Cover, Loopover, up to.5 Cond. Diameter Cover, Loopover,.5 to.856 Cond. Diameter 1 2 C Tape, Insulating 1 1 D 111 Wildlife cover Installation 1 2 ENG: JC REV. NO: 2 REV. DATE: 3/7/17

52 INSULATORS AND SUPPORTS Static Wire Attachment 6 11 ** Sheet 1 of 3 H C F J D I D M G G kV & 69kV Tangent and Angle E G Max. O NOTE: 1. For pole top static, see stds , **. 2. Smallware must be assembled in order listed starting at pole face. Welded nut washer included with item H not used on 4 and wood poles. Stnd. / Stk. No. Description 6 11 ** 3 4 B Bolt, Machine 3/4 x 12 C Clamp, Guy Wire, 1/2 (used with 12/7 ACSR Static) Clamp, Parallel Groove (used with 1/ AAAC Static) 1 D Nut, Square, 3/4 2 E Eyelet, 3/4 Bolt 1 F Washer, Square, 3 x 3 w/ 3/4 Bolt Hole G SC*W Clamp, Suspension (armor over 3 span) 1 1 H Static Support, 3/4 x 14 1 I Clip, Bonding, 3/4 Bolt Dia. 1 J Washer, Lock 3/4 Dbl. Coil Type 1 M Nut, Lock, 3/4 HDG Steel, Square 1 ENG: DCG REV. NO: 7 REV. DATE: 1/19/12

53 INSULATORS AND SUPPORTS Static Wire Attachment 6 11 ** Sheet 2 of 3 E B C,D,I,D,M K C,N,D,M G G kV & 69kV Corner Deadend K B,E K C,D,I,D,M 3 C,N,D,M C,M G G G kV & 69kV Deadend Endline G F K E B K C,D,I,D,M E C,P G NOTES: 3. Assemble items in order listed to retain pole ground wire kV & 69kV 3 Way Deadend w/o Pole Ground kV & 69kV 3 Way Deadend w/ Pole Ground Stnd. / Stk. No. Description 6 11 ** B Bolt, Mach., 3/4 x C Washer, Curved, Square, 3 x 3 w/ 3/4 Bolt Hole D Nut, Square, 3/ E Eyelet, 3/4, Steel, HDG F Washer, Square, 2 1/4 x 2 1/4 w/ Hole for 3/4 Bolt G Clamp, Guy Wire, 1/2 inch (used with 12/7 ACSR Static) Clamp, Parallel Groove (used with 1/ AAAC Static) I Clip, Bonding, 3/4 Bolt Dia. 1 1 K DEC*W Clamp, Deadend M Nut, Lock, 3/4 HDG Steel, Square N Washer, Lock, 3/4, Dbl Coil Type P Eyenut, 3/4 Bolt 1 1 ENG: DCG REV. NO: 7 REV. DATE: 1/19/12

54 INSULATORS AND SUPPORTS Static Wire Attachment 6 11 ** Sheet 3 of 3 F B K F E L M,D,I,D,N kV & 69kV Deadend Tangent F B,M K E E K E M,D,I,D,N E kV & 69kV Deadend Angle F F F K B E L kV & 69kV Deadend Tangent NOTES: 4. Standard used on switch pole ground wire not installed. 4 Stnd. / Stk. No. Description 6 11 ** B Bolt, Mach., 3/4 x D Nut, Square, 3/4 1 1 E Eyelet, 3/4 Bolt 1 1 F Clamp, Guy Wire, 1/2 (used with 12/7 ACSR Static) Clamp, Parallel Groove (used with 1/ AAAC Static) I Clip, Bonding, 3/4 Bolt Dia. 1 K DEC*W Clamp, Deadend L Eyenut, 3/4 Bolt 1 1 M Washer, Square, Curved, 3 x 3 w/ 3/4 Bolt Hole N Nut, Lock, Square, Steel, HDG, 3/4 1 2 ENG: DCG REV. NO: 7 REV. DATE: 1/19/12

55 INSULATORS AND SUPPORTS Secondary Clevis to 75 Volts ** Sheet 1 of 1 C A E A E D C Secondary Clevis Double Secondary Clevis C B E C B D Single Clevis Extension Bracket Dble Single Clevis Extension Bracket Stnd. / Stk. No. Description ** A Clevis, Sec. Insulator 1 2 B Brkt., Ext., 1 Clevis 1 2 C Bolt, Mach., 5/8 x D Washer, Square, 5/8 1 2 E Insulator, Spool ENG: DCG REV. NO: 1 REV. DATE: 9/18/ REAFFIRMED DATE: 9/27/11

56 INSULATORS AND SUPPORTS Pin and Insulator 12kVandStatic 6121** Sheet1of1 A A A F C K F F F SglPinandInsulator -- WoodArm H G,H,K DblPinandInsulator -- FGArm K H Sgl Pin and Insulator--FG Arm A A A B B D,E,H D,E D,E,H D,E E SglPoleTopPin&Ins. E DblPoleTopPin&Ins. Notes: 1. The2 washerreceivedwiththepinshouldbeusedafterthe4 washertoeliminatethecoilwasherfromsliding inside the 4 washer. XA Pole Top Stnd./ Stk. No. Description ** A Insulator, Pin Type B Pin,PoleTop, C Plate, Dbl Pin 1 D Bolt,Mach.,5/8 x E Washer, Curved, 3/4 4 2 F Pin, Insulator, Long Shank Pin, Insulator, Short Shank 2 G Bolt,Mach.,5/8 x6 1 H Washer, Lock, Galvanized, 5/8 dbl coil type K Washer,Flat,Sq.,4 x4,w13/16 hole 1 2 ENG: KP REV.NO:12 REV. DATE: 9/11/217

57 INSULATORS AND SUPPORTS Pole Top Mounting 12 kv & Static ** Sheet 1 of 1 A A B B or or C,D D,E Pole Top & Insulator 3 Double Pole Top & Insulator NOTES: 1. This dimension will vary according to pole top drilling. Stnd. / Stk. No. Description ** 1 2 A Insulator, Pin Type 1 2 B Pin, Pole Top, C Bolt, Mach.,5/8 x D Washer Square 5/8 2 ENG: DCG REV. NO: 2 REV. DATE: 11/16/11 REAFFIRMED DATE: 9/15/11

58 INSULATORS AND SUPPORTS Arm Training, Fiberglass 15 kv Sheet 1 of 1 18 D, E B C Stnd. / Stk. No. Description B Bracket, FG, Standoff, LD, 18 1 C Insulator, Vise Top, 15kV 1 D Bolt, Mach., 5/8 x 12 1 E Washer, Square, 5/8 1 ENG: KSP REV. NO: 4 REV. DATE: 11/5/15

59 INSULATORS AND SUPPORTS Deadends on Pole 12 kv ** Sheet 1 of 2 D M C D C F,G F,G W/FG EXTENSION J WO/FG EXTENSION J STRAIGHT DEADEND D C F,G H FLOATING ANGLE K C M E D M F,G J DOUBLE DEADEND W/FG EXTENSIONS J E D C F,G J DOUBLE DEADEND WO/FG EXTENSIONS J ENG: WYW REV. NO: 7 REV. DATE: 9/4/14

60 INSULATORS AND SUPPORTS Deadends on Pole 12 kv ** Sheet 2 of 2 B A M E 8 4 D 8 M C F,G J W/FG Extension J A B E 8 4 D 8 C F,G J WO/FG Extension POLE TOP LOOPOVER J Stnd. / Stk. No. Description ** A Pin, Pole Top 1 1 B Ins., Pin Type 1 1 C Ins., Suspension, 15 kv D Eyelet, 3/ E Eyenut, 3/ F Bolt, Mach., 3/4 x G Washer, Square, ¾ H Shackle, Deadend J DEC*W Conductor Deadend clamp K SC*W Suspension Clamp 1 M Insulator, Guy Strain, F/G, 26, 15k UTS N Nut, Lock, Square, Galv, ¾ ENG: WYW REV. NO: 7 REV. DATE: 9/4/14

61 INSULATORS AND SUPPORTS Deadends on Pole Double 12 kv ** Sheet 1 of 1 A L F C L K H B G A LOOPAROUND A L F D G L A K H H DOUBLE DEADEND WITH EXTENSIONS Stnd. / Stk. No. Description ** 1 2 A Ins., Suspension, 15 kv 2 2 B Brkt, FG, Standoff, LD, 18, w Hor. Pin 1 C Ins., Pin Type, 12 kv 1 D Bolt, Mach., 5/8 x E Washer, Square, 5/8 2 2 F Eyelet, 5/8 1 1 G Eyenut, 5/8 1 1 H Ins, Guy Strain, F/G, 26, 15 K UTS 2 K DE C*W Clamp, Conductor, Deadend 2 2 L Link, Chain, Oval, 1 x2 1/4 2 2 ENG: DCG REV. NO: 8 REV. DATE: 9/2/11

62 INSULATORS AND SUPPORTS Deadends on Arms 12 kv ** Sheet 1 of 1 C B A J B A J D D DEADEND ON CROSSARMS DEADEND ON SINGLE CROSSARM J A 1 B or H F E B 1 A J D C or G Dble. Arm Sgl. Arm DOUBLE DEADEND LOOPOVER Notes: 1. Double deadend w/extension install Item (K) between Items A & B. 2. Working load of deadend insulator = 75 lb. Stnd. / Stk. No. Description ** A Ins., Suspension, 12 kv B Eyenut, 5/ C Bolt D.A. 5/8 x D Washer Square 2 1/ E Ins., Pin Type 1 1 F Pin, Insulator, X arm 1 1 G Bolt Machine 5/8 x H Eyelet, 5/8 1 1 J DEC*W Clamp, Deadend K Link, Extension, 6 Clevis Eye 2 ENG:KSP REV. NO 9 REV. DATE: 4/2/216

63 INSULATORS AND SUPPORTS Horizontal Post Insulators 69 kv ** Sheet 1 of 2 K,H,G,F C 25 3 A E 25 lbs. 5 o 1 or 12 C 1,25 lbs. working load K,H,G,F POLYMER INSULATOR W/TRUNNION CLAMP SINGLE DOUBLE K,H,G F K,H,G 25 3 B 5, lbs. 1 or 12 D L M D 1,25 lbs. working load K,H,G K,H,G POLYMER INSULATORS W/SUPENSION CLAMP SINGLE DOUBLE NOTES: 1. Reverse bolt position if guy wire is attached to bottom bolt. 2. Longer bolts are for use on larger diameter poles. ENG: MJ REV. NO. 4 REV. DATE: 9/1/13

64 INSULATORS AND SUPPORTS Horizontal Post Insulators 69 kv ** Sheet 2 of 2 Stnd. / Stk. No. Description ** A Insulator, Horiz. Post, 69 kv, Polymer, Trunnion Clamp 1 2 B Insulator, Horiz. Post, 69 kv, Polymer, Suspension Clamp 1 C Bolt, Mach., 3/4 x Bolt, Mach., 3/4 x 16 2 D Bolt, DA, 3/4 x Bolt, DA, 3/4 x 18 2 E TC*W Clamp, Trunnion 1 2 F Washer, Square, for 3/4 Bolt, 3 x3, Galvanized 2 2 G Washer, Lock, 3/4 Dbl Coil Type H Nut, Square, 3/4 x 1 TPI, Galvavized * * * * K Nut, Locking, 3/4, Galvanized L Wye Clevis Eye, 11/16 hole, 5/8 Thick, 3/4 Pin Dia. 1 M SC*W Clamp, Suspension 1 2 * Furnished with DA bolts (4) or machine bolts (1). ENG: MJ REV. NO. 4 REV. DATE: 9/1/13

65 PRIMARY CONDUCTOR AND FASTENINGS Conductor Installation Sagging Method Sheet 1 of 1. General ENG: REV. NO: REV. DATE:

66 PRIMARY CONDUCTOR AND FASTENINGS Conductor Installation Sagging Method Sheet 2 of ENG: REV. NO: REV. DATE:

67 PRIMARY CONDUCTOR AND FASTENINGS Conductor Installation Sagging Method Sheet 3 of ENG: REV. NO: REV. DATE:

68 PRIMARY CONDUCTOR AND FASTENINGS Conductor Installation Sagging Method Sheet 4 of ENG: REV. NO: REV. DATE:

69 PRIMARY CONDUCTOR AND FASTENINGS Conductor Installation Sagging Method Sheet 5 of ENG: REV. NO: REV. DATE:

70 PRIMARY CONDUCTOR AND FASTENINGS Conductor Installation Sagging Method Sheet 6 of ENG: REV. NO: REV. DATE:

71 PRIMARY CONDUCTOR AND FASTENINGS Conductor Installation Sagging Method Sheet 7 of ENG: REV. NO: REV. DATE:

72 PRIMARY CONDUCTOR AND FASTENINGS Conductor Installation Sagging Method Sheet 8 of ENG: REV. NO: REV. DATE:

73 PRIMARY CONDUCTOR AND FASTENINGS Conductor Installation Sagging Method Sheet 9 of 61 ENG: REV. NO: REV. DATE:

74 PRIMARY CONDUCTOR AND FASTENINGS Conductor Installation Sagging Method Sheet 1 of ENG: REV. NO: REV. DATE:

75 PRIMARY CONDUCTOR AND FASTENINGS Conductor Installation Sagging Method Sheet 11 of ENG: REV. NO: REV. DATE:

76 PRIMARY CONDUCTOR AND FASTENINGS Conductor Installation Sagging Method Sheet 12 of 61 ENG: REV. NO: REV. DATE:

77 PRIMARY CONDUCTOR AND FASTENINGS Conductor Installation Sagging Method Sheet 13 of ENG: REV. NO: REV. DATE:

78 PRIMARY CONDUCTOR AND FASTENINGS Conductor Installation Sagging Method Sheet 14 of ENG: REV. NO: REV. DATE:

79 PRIMARY CONDUCTOR AND FASTENINGS Conductor Installation Sagging Method Sheet 15 of ENG: REV. NO: REV. DATE:

80 PRIMARY CONDUCTOR AND FASTENINGS Conductor Installation Sagging Method Sheet 16 of ENG: REV. NO: REV. DATE:

81 PRIMARY CONDUCTOR AND FASTENINGS Conductor Installation Sagging Method Sheet 17 of ENG: REV. NO: REV. DATE:

82 PRIMARY CONDUCTOR AND FASTENINGS Conductor Installation Sagging Method Sheet 18 of ENG: REV. NO: REV. DATE:

83 PRIMARY CONDUCTOR AND FASTENINGS Conductor Installation Sagging Method Sheet 19 of ENG: REV. NO: REV. DATE:

84 PRIMARY CONDUCTOR AND FASTENINGS Conductor Installation Sagging Method Sheet 2 of ENG: REV. NO: REV. DATE:

85 PRIMARY CONDUCTOR AND FASTENINGS Conductor Installation Sagging Method Sheet 21 of ENG: REV. NO: REV. DATE:

86 PRIMARY CONDUCTOR AND FASTENINGS Conductor Installation Sagging Method Sheet 22 of ENG: REV. NO: REV. DATE:

87 PRIMARY CONDUCTOR AND FASTENINGS Conductor Installation Sagging Method Sheet 23 of ENG: REV. NO: REV. DATE:

88 PRIMARY CONDUCTOR AND FASTENINGS Conductor Installation Sagging Method Sheet 24 of ENG: REV. NO: REV. DATE:

89 PRIMARY CONDUCTOR AND FASTENINGS Conductor Installation Sagging Method Sheet 25 of ENG: REV. NO: REV. DATE:

90 PRIMARY CONDUCTOR AND FASTENINGS Conductor Installation Sagging Method Sheet 26 of ENG: REV. NO: REV. DATE:

91 PRIMARY CONDUCTOR AND FASTENINGS Conductor Installation Sagging Method Sheet 27 of ENG: REV. NO: REV. DATE:

92 PRIMARY CONDUCTOR AND FASTENINGS Conductor Installation Sagging Method Sheet 28 of ENG: REV. NO: REV. DATE:

93 PRIMARY CONDUCTOR AND FASTENINGS Conductor Installation Sagging Method Sheet 29 of ENG: REV. NO: REV. DATE:

94 PRIMARY CONDUCTOR AND FASTENINGS Conductor Installation Sagging Method Sheet 3 of ENG: REV. NO: REV. DATE:

95 PRIMARY CONDUCTOR AND FASTENINGS Conductor Installation Sagging Method Sheet 31 of 61 ENG: REV. NO: REV. DATE:

96 PRIMARY CONDUCTOR AND FASTENINGS Conductor Installation Sagging Method Sheet 32 of ENG: REV. NO: REV. DATE:

97 PRIMARY CONDUCTOR AND FASTENINGS Conductor Installation Sagging Method Sheet 33 of ENG: REV. NO: REV. DATE:

98 PRIMARY CONDUCTOR AND FASTENINGS Conductor Installation Sagging Method Sheet 34 of ENG: REV. NO: REV. DATE:

99 PRIMARY CONDUCTOR AND FASTENINGS Conductor Installation Sagging Method Sheet 35 of ENG: REV. NO: REV. DATE:

100 PRIMARY CONDUCTOR AND FASTENINGS Conductor Installation Sagging Method Sheet 36 of ENG: REV. NO: REV. DATE:

101 PRIMARY CONDUCTOR AND FASTENINGS Conductor Installation Sagging Method Sheet 37 of ENG: REV. NO: REV. DATE:

102 PRIMARY CONDUCTOR AND FASTENINGS Conductor Installation Sagging Method Sheet 38 of ENG: REV. NO: REV. DATE:

103 PRIMARY CONDUCTOR AND FASTENINGS Conductor Installation Sagging Method Sheet 39 of ENG: REV. NO: REV. DATE:

104 PRIMARY CONDUCTOR AND FASTENINGS Conductor Installation Sagging Method Sheet 4 of ENG: REV. NO: REV. DATE:

105 PRIMARY CONDUCTOR AND FASTENINGS Conductor Installation Sagging Method Sheet 41 of ENG: REV. NO: REV. DATE:

106 PRIMARY CONDUCTOR AND FASTENINGS Conductor Installation Sagging Method Sheet 42 of ENG: REV. NO: REV. DATE:

107 PRIMARY CONDUCTOR AND FASTENINGS Conductor Installation Sagging Method Sheet 43 of ENG: REV. NO: REV. DATE:

108 PRIMARY CONDUCTOR AND FASTENINGS Conductor Installation Sagging Method Sheet 44 of ENG: REV. NO: REV. DATE:

109 PRIMARY CONDUCTOR AND FASTENINGS Conductor Installation Sagging Method Sheet 45 of ENG: REV. NO: REV. DATE:

110 PRIMARY CONDUCTOR AND FASTENINGS Conductor Installation Sagging Method Sheet 46 of ENG: REV. NO: REV. DATE:

111 PRIMARY CONDUCTOR AND FASTENINGS Conductor Installation Sagging Method Sheet 47 of ENG: REV. NO: REV. DATE:

112 PRIMARY CONDUCTOR AND FASTENINGS Conductor Installation Sagging Method Sheet 48 of ENG: REV. NO: REV. DATE:

113 PRIMARY CONDUCTOR AND FASTENINGS Conductor Installation Sagging Method Sheet 49 of ENG: REV. NO: REV. DATE:

114 PRIMARY CONDUCTOR AND FASTENINGS Conductor Installation Sagging Method Sheet 5 of ENG: REV. NO: REV. DATE:

115 PRIMARY CONDUCTOR AND FASTENINGS Conductor Installation Sagging Method Sheet 51 of ENG: REV. NO: REV. DATE:

116 PRIMARY CONDUCTOR AND FASTENINGS Conductor Installation Sagging Method Sheet 52 of ENG: REV. NO: REV. DATE:

117 PRIMARY CONDUCTOR AND FASTENINGS Conductor Installation Sagging Method Sheet 53 of ENG: REV. NO: REV. DATE:

118 PRIMARY CONDUCTOR AND FASTENINGS Conductor Installation Sagging Method Sheet 54 of ENG: REV. NO: REV. DATE:

119 PRIMARY CONDUCTOR AND FASTENINGS Conductor Installation Sagging Method Sheet 55 of ENG: REV. NO: REV. DATE:

120 PRIMARY CONDUCTOR AND FASTENINGS Conductor Installation Sagging Method Sheet 56 of ENG: REV. NO: REV. DATE:

121 PRIMARY CONDUCTOR AND FASTENINGS Conductor Installation Sagging Method Sheet 57 of ENG: REV. NO: REV. DATE:

122 PRIMARY CONDUCTOR AND FASTENINGS Conductor Installation Sagging Method Sheet 58 of 61 ENG: REV. NO: REV. DATE:

123 PRIMARY CONDUCTOR AND FASTENINGS Conductor Installation Sagging Method Sheet 59 of ENG: REV. NO: REV. DATE:

124 PRIMARY CONDUCTOR AND FASTENINGS Conductor Installation Sagging Method Sheet 6 of ENG: REV. NO: REV. DATE:

125 PRIMARY CONDUCTOR AND FASTENINGS Conductor Installation Sagging Method Sheet 61 of ENG: REV. NO: REV. DATE:

126 FUSES AND SWITCHES Single Phase Sectionalizing All Construction 1 3 Amp 4 or 12 kv ** Sheet 1 of 2 1 AMP FUSED 2 AMP FUSED 3 AMP SOLID BLADE K M 2 C,D N L F F 8 12 A,P B 4 to 72 J NOTES: 1. Use DCS for ground coil application on new pole installation. 2. Double deadend on pole w/o FG extension available AmerenMO only. ENG: WYW REV. NO: 1 REV. DATE: 6/29/16

127 FUSES AND SWITCHES Single Phase Sectionalizing All Construction 1 3 Amp 4 or 12 kv ** Sheet 2 of 2 Stnd. / Stk. No. Description ** A Switch, Fuse, 1A, 15kV Switch, Fuse, 2A, 15kV Switch, Solid Blade, 3A, 15kV 1 B Bracket, Fiberglass, Switch and Arrester C Bolt, Mach., 5/8 x D Washer, Square, 5/8 2 2 F PLW*P Wire, CU, Poly, SD, (ft.), DCS @ J Grounding Unit Ground Rod Grounding Unit Ground Coil 1 1 K PG* Clamp, Parallel Groove, DCS @ M Dbl Deadend on Pole w/ FG Extension Dbl Deadend on Pole w/o FG Extension 1 1 N DEC*W or DEA*W Clamp, Deadend, DCS O Link, Fuse ( Sized by Engineer ) P Cover, Cutout ENG: WYW REV. NO: 1 REV. DATE: 6/29/16

128 FUSES AND SWITCHES Three Phase Sectionalizing 1 3 Amp 4 or 12 kv ** Sheet 1 of 2 MISSOURI ONLY ÄÄ ÄÄ 1 AMP. FUSED 2 AMP. FUSED 3AMP. SOLID BLADE TURN SWITCHES TOWARD POLE A, P, O E 4 H K SOURCE LOAD F D 3 C A,N I L M MIN. D Q O B M G 2 ENG: WYW REV. NO: 6 REV. DATE: 6/3/16

129 FUSES AND SWITCHES Three Phase Sectionalizing 1 3 Amp 4 or 12 kv ** Sheet 2 of 2 NOTES: 1. This installation is permissible for existing installation in Missouri. For new installations, arresters are not required for normally closed switch installations. Where switches are normally open, install arresters on adjacent poles. Refer to DCS for arresters selection. 2. Use DCS for ground coil application on new pole installation. 3. Double deadend on pole w/o FG extension available AmerenMO only. 4. Underbuild construction requires deadend on pole w/fg extension. Stnd. / Stk. No. Description ** A Switch, Fuse, 1A., 15kV Switch, Fuse, 2A., 15kV Switch, Solid Blade, 3A., 15kV 3 1@ B Arrester, 1kV w/protective Cap Arrester, 3kV w/protective Cap 3 3 C Crossarm, Deadend, FG, Crossarm, Deadend, FG, D Crossarm, Sgl, Wood, 1 (use only 1/2 of V Brace) Crossarm, Sgl, Wood, 8 (use only 1/2 of V Brace) @ E Dbl Deadend on Pole w/ FG Extension Dbl Deadend on Pole w/o FG Extension F Double Deadend on Arm G Grounding Unit Ground Rod 1 1 H DEC*W or DEA*W Clamp, Deadend 6 6 I PLW*W Wire, Poly covered, S.D. (ft.) 3 3 J PG* Clamp, Parallel Groove ( See Std ) HLC*W Clamp, Hot Line 3 3 K PG* Clamp, Parallel Groove (See Std L Clamp, Hot Line M Wire, Poly Covered, #6 Cu., (Ft.) N Link, Fuse ( Sized by Designer ) 3 3 O Bracket, Mounting Switch, Arrester P Cover Cutout Q Connector, Split Bolt ENG: WYW REV. NO: 6 REV. DATE: 6/3/16

130 FUSES AND SWITCHES Three Phase Sectionalizing Crossarm Pole Top Construction 6 Amp 4 or 12 kv ** Sheet 1 of 3 MISSOURI ONLY ALTERNATIVE K F N K C A E J J 6 C 6 G ENG: WYW REV. NO: 8 REV. DATE: 6/3/16

131 FUSES AND SWITCHES Three Phase Sectionalizing Crossarm Pole Top Construction 6 Amp 4 or 12 kv ** Sheet 2 of 3 ALTERNATIVE MISSOURI ONLY K F N K C G A E J J L M 4 4 D C 6 D 6 D B 1 M 2 MIN G ENG: WYW REV. NO: 8 REV. DATE: 6/3/16

132 FUSES AND SWITCHES Three Phase Sectionalizing Crossarm Pole Top Construction 6 Amp 4 or 12 kv ** Sheet 3 of 3 NOTES: 1. Alternative 2 is permissible for existing installation in Missouri. For new installation, both Illinois and Missouri, arresters are not required for normally closed switch installations; where switches are normally open, install both sets of arresters on adjacent poles. Refer to DCS for arresters selection. 2. If insulators are not at least 2 from switch base using a single eye clevis, install one additional eye clevis in each deadend. On angle poles, a shackle may also be necessary to obtain clearances. 3. When required, switch number tag shall be installed here crossarm available AmerenMO only. 5. Double deadend on pole w/o FG extension available Missouri only. Stnd. / Stk. No. Description ** 1 2 A Switch, Dis., 6A, 15kV 3 3 1@ B Arrester, 1kV Arrester, 3kV 3 4@ C Crossarm, Dbl, Wood 1 ( use only 1/2 of V brace ) Crossarm, Dbl, Wood 8 ( use only 1/2 of V brace ) 1 1 4@ D Crossarm, Sgl, Wood 1 ( use only 1/2 of V brace ) Crossarm, Sgl, Wood 8 ( use only 1/2 of V brace ) 1 2 E Double Deadend on Arm 2 F DEC*W Clamp, Deadend, DCS G Grounding Unit on Existing Pole Ground Rod Grounding Unit on New Pole Ground Coil 1 J PLW*W Wire, Poly covered, (ft.), DCS K PG* Clamp, Parallel Groove, DCS L Clamp, Hot Line 3 M Wire, Poly, #6 Cu., Ft. 15 5@ N Dbl Deadend on Pole w/ FG Extension Dbl Deadend on Pole w/o FG Extension 1 1 ENG: WYW REV. NO: 8 REV. DATE: 6/3/16

133 FUSES AND SWITCHES Single Phase Tap From Single Phase All Construction 1 3 Amp. 4 or 12 kv ** Sheet 1 of 1 E H G H 1 AMP. FUSED 2 AMP. FUSED 3 AMP. SOLID BLADE G F O C,D B G A N M 4 to 72 F K Stnd. / Stk. No. Description ** A Switch, Fuse, 1A, 15 kv Switch, Fuse, 2A, 15kV Switch, Solid Blade, 3A, 15kV 1 B Bracket, Switch, Arr. and Deadend C Bolt, Mach., 5/8 x D Washer, Square, 5/ E Ins., Suspension, 12kV 1 1 F DEC*W or DEA*W Clamp, Deadend 1 1 G PLW*W Wire, Poly Covered (ft.), DCS H PG* Clamp, Parallel Groove DCS K Grounding Unit New Pole Ground Coil Grounding Unit Existing Pole Ground Rod 1 1 N Link, Fuse (Sized by Engineer) 1 1 O Cutout Cover ENG: WYW REV. NO: 12 REV. DATE: 12/15/15

134 FUSES AND SWITCHES Single Phase Tap From Three Phase All Construction 1 3 Amp. 4 & 12kV ** Sheet 1 of Amp Fused Amp Fused Amp Solid Blade H H H 2 P R H M,Q H ENG: WYW REV. NO: 11 REV. DATE: 3/21/17

135 FUSES AND SWITCHES Single Phase Tap From Three Phase All Construction 1 3 Amp. 4 & 12kV ** Sheet 2 of 2 Std. /Stk. No. Description ** A Switch, Fuse, 1A, 15 KV Switch, Fuse, 2A, 15 KV Switch, Solid Blade, 3A, 15 KV 1 B Bracket NEMA, Switch and Dead End C Bolt, Mach., ⅝ x D Washer, Square, ⅝ E Ins., Suspension, 15 KV 1 1 F DEC*W Clamp, Deadend DCS G PLW*W Wire, Poly Covered (ft.) DCS 7 8 & H PG* Clamp, Parallel Groove or Split Bolt or Two Bolt. See I Shackle, Deadend @ K Grounding Unit New Pole Ground Coil Grounding Unit Existing Pole Ground Rod M Washer, SQ, ¾ N Link, Fused, (sized by Engineer) O Cover, Cutout P Eyelet, ¾ 1 1 R SDEA*W Deadend, Automatic, Secondary. See Q Bolt, Machine ¾ x @ S 11 ** ** Guy Unit NOTES: 1. Use DCS for ground coil application on new pole installation. 2. This distance may be reduced to 4 inches if approved by engineering. Center the guy attachment between the primary and neutral if this distance is reduced. ENG: WYW REV. NO: 11 REV. DATE: 3/21/17

136 FUSES AND SWITCHES Two or Three Phase Tap Crossarm Construction 1 3 Amp 4 or 12kV ** Sheet 1 of 2 K K Near Phase Far Phase J 4 F C 4 R C D TURN SWITCHES TOWARD POLE A,P,B I H 2 PHASE 3 PHASE 1 AMP FUSED AMP FUSED AMP SOL. BL ENG: WYW REV. NO: 11 REV. DATE: 6/1/17

137 FUSES AND SWITCHES Two or Three Phase Tap Crossarm Construction 1 3 Amp 4 or 12kV ** Sheet 2 of 2 Notes: 1. Use DCS for ground coil application on new pole installation crossarm available AmerenMO only. Stnd / Stk. Description ** 2 PHASE 3 PHASE A Switch, Fused, 1A, 15 kv Switch, Fused, 2A, 15 kv Switch, Solid Blade, 3A, 15 kv 2 3 B Bracket NEMA, Switch @ C Crossarm, Deadend, F/G, Crossarm, Deadend, F/G, D Deadend on Pole w/fg Extension E Deadend on Single Arm F Insulator and X Arm Pin G DEC*W or DEA*W Clamp, Deadend @ H Grounding Unit Existing Pole Ground Rod Grounding Unit New Pole Ground Coil I Neutral Deadend J PLW*W Wire, Poly covered, S.D.(ft.) DCS K PG* Clamp, Parallel Groove DCS P Link, Fused (Sized By Designer) R Cover Cutout ENG: WYW REV. NO: 11 REV. DATE: 6/1/17

138 GUYING General Sheet 1 of 3 1. GENERAL Guys are used to sustain unbalanced forces imposed on a structure at corners, angles, deadends, large differences in span lengths, and changes of grade of construction. Guys shall be considered as taking the entire load in the direction in which they act, with the pole or structure acting as a strut only, resisting the vertical component of all forces. The strength requirements of guy and anchor systems are governed by the National Electric Safety Code which specifies criteria for calculating conductor tensions and imposes overload factors to be used under different circumstances. Guying is preferable to oversized self sustained poles. Where adequate guying cannot be obtained due to right of way or other difficulties, self sustained poles, within their limitations, may be used. Loadings and other details for self sustained poles are covered in Dist. Stds thru GUY WIRE & FITTINGS Three sizes and grades of galvanized steel guy wire are stocked for normal use. The maximum tension and associated fittings for each guy wire is given below in Table 1. The maximum tensions shown are 9 percent of the rated breaking strength, in accordance with the NESC. In Illinois, 1/4 guy wire is not used. GUY WIRE TABLE 1 PREFORMED GRIP AUTOMATIC DEADEND Stock No. Size & Grade Max. Tension (lbs) Stock No. Stock No /4 Galv. E.H.S 5, /8 Galv. E.H.S. 13, /16 Galv. E.H.S. 18, In general, all guy strand shall be secured to the pole fitting or to guy insulators with preformed guy grips. Automatic Deadends may only be used with galvanized guy wire at the anchor or guy pole. Due to increased cost, there is no need for more than one automatic installed per guy lead. 3. ANCHORS & ANCHOR RODS Three types of anchors are available for use in the distribution system; power installed screw anchors, expanding anchors and rock anchors. 3.1 Power installed screw anchors are the preferred anchors for use in all soils other than solid rock. Access with a power digger equipped with wrench assembly is required for installation. Two strengths of these anchors are stocked; a 6, ft lb series for use in sandy to hard pan soils, and a 1, ft lb series for use in rockier soils in which the 6, ft lb anchors cannot be installed. Only square shaft anchors shall be used in Illinois for down guys on Sub Transmission (34.5kV and 69kV). 3.2 Expanding anchors can be installed in most any soil in which an 8 to 12 diameter hole, depending on anchor size, can be augered. Because of the time needed to install these anchors, usage is generally limited to locations not accessible to power equipment. ENG: DG REV. NO: 8 REV. DATE: 8/12/15

139 GUYING General Sheet 2 of Rock anchors are an expanding type anchor which must be installed in at least 12 of solid rock. A 2 or 2 1/4 diameter hole is needed for installation. Rod lengths from 3 to 96 are available to meet site requirements. Standard sizes, holding strengths and methods of installation for each type of anchor are shown in Dist. Std ** thru **. 4. USE OF GUY INSULATORS Guy strain insulators are used to: (1) protect pedestrians and line workers if a guy accidentally contacts supply conductors, (2) minimize the possibility of plant damage which may result in unsafe conditions, and (3) increase the structure BIL and reduce lightning caused outages. All guys attached to poles supporting energized conductors or equipment shall have a minimum of one guy strain insulator inserted in each guy. EXCEPTION: Stub pole to anchor guys generally do not require an insulator unless the exposure between the energized pole and the stub pole cannot be isolated. One insulator typically cannot be located to satisfy all of the following requirements. Additional insulators shall be used as required. Where multiple guys are required, the insulators in each guy shall be located so that in case any guy sags down upon another, the insulators will not become ineffective (NESC Rule 215C5C). DCS demonstrates the general concepts of proper guy strain insulator placement described in this DCS. DCS gives more detailed guidance for guy strain insulator placement for many of Ameren s typical structure configurations. If necessary, a fiberglass (FG) guy strain insulator may be used to allow a guy to be located in closer proximity to a conductor than would otherwise be allowed. In no instance, however, shall any conductive portion of the guy or the insulator be located in closer proximity to a conductor than is specified in DCS To achieve the updated requirements from the 212 NESC as described in this DCS, it will often be necessary to link two or more FG guy strain insulators together. 4.1 Distribution In Missouri, FG or porcelain guy strain insulators may be used in guys associated with circuits 15 kv and below. In Illinois, only FG guy strain insulators shall be used. Insulators shall be installed to meet all of the following placement criteria that apply: a) A FG guy strain insulator shall be used at the pole attachment of all anchor or span guys. EXCEPTION: Stub pole to anchor guys do not require insulators if the span guys are effectively isolated and there are no energized conductors or communication attachments on the stub pole. b) On non joint use poles, an insulator (or at least 12 of a FG insulator) must be located between primary voltage and secondary voltage (including neutral) supply circuits. This insulator must be located so that: i. It prevents the possibility of voltage transfer between the primary and secondary circuits during normal operation of the guy, and ii. If the guy wire breaks below the insulator, it will fall below all primary voltage supply conductors and above any secondary conductors (including the neutral) as it rests against the pole. c) On non joint use poles, an insulator (or at least 12 of a FG insulator) must be located between the lowest supply conductor (primary, secondary, or neutral) and ground. The insulator must be located so that: i. It prevents the possibility of voltage transfer between the lowest supply conductor and ground during normal ii. operation of the guy, and If the guy wire breaks below the insulator, the insulator falls below the lowest supply conductor and the bottom of the insulator must fall a minimum of 8 ft. above the ground as it rests against the pole. d) On joint use poles, in addition to a) and b) above an insulator (or at least 12 of a FG insulator) must be located between the lowest supply conductor (primary, secondary, or neutral) and the highest communication cable. This insulator must be located so that: ENG: DG REV. NO: 8 REV. DATE: 8/12/15

140 GUYING General Sheet 3 of 3 i. Any guy passing within twelve inches (12 ) of a supply conductor and also passing within twelve inches (12 ) of a communication cable shall have an insulator located below the lowest supply conductor and above the highest communication cable (NESC Table 235 6, Note (1)). ii. It prevents the possibility of voltage transfer between the supply circuits and communication cable during normal operation of the guy, and iii. If the guy wire breaks below the insulator, it will fall below all supply conductors and above any communication cables as it rests against the pole. e) On joint use poles, an insulator (or at least 12 of a FG insulator) must be located between the lowest communication cable and ground. The insulator must be located so that: i. It prevents the possibility of voltage transfer between the lowest communication cable and ground during ii. normal operation of the guy, and If the guy wire breaks below the insulator, the insulator falls below the lowest communication cable and the bottom of the insulator must fall a minimum of 8 ft. above the ground as it rests against the pole. EXCEPTION: This insulator is not required if the communication cables are self supported fiber optic (with no metallic messenger). 4.2 Sub Transmission Guys associated with 34.5kV or 69kV circuits require a FG guy strain insulator be used in place of a porcelain insulator. In addition to the protective role, FG guy strain insulators serve to increase the BIL level of ungrounded structures associated with these circuits. FG guy strain insulators shall be installed to meet all of the following placement criteria that apply in addition to the criteria in section 4.1 of this DCS: a) A FG guy strain insulator shall be used at the pole attachment of all anchor or span guys. EXCEPTION: Stub pole to anchor guys do not require insulators if the span guys are effectively isolated and there are no energized conductors on the stub pole. b) If no underbuilt circuits are present, at least 24 of a FG insulator must be located between the lowest 34.5kV or 69 kv conductor and ground. The insulator must be located so that: i. It prevents the possibility of voltage transfer between the lowest supply conductor and ground during normal operation of the guy, and ii. If the guy wire breaks below the insulator, the insulator falls below the lowest supply conductor and the bottom of the insulator must fall a minimum of 8 ft. above the ground as it rests against the pole. c) If an underbuilt circuit is present, at least 24 of a FG insulator shall be located to effectively isolate the lowest 34.5kV or 69kV conductor and the highest distribution underbuilt conductor. 4.3 Span Guys All of the requirements of sections 4.1 and 4.2 of this DCS also apply to span guys. 5. GUY MARKERS Guy MARKERS shall be installed on the ground end of all anchor guys. Where two or more guys are attached to the same anchor, only one MARKER is required and shall be installed on the highest guy wire. ENG: DG REV. NO: 8 REV. DATE: 8/12/15

141 GUYING Insulator Dimensional Requirements Sheet 1 of 8 Single Phase 4 to 15kV ËËË Ë 8 8 GUY GUY COMM COMM Loopover Tap 3 GUY 4 GUY GUY COMM. 45 COMM Pole Top Pin Floating Angle ENG: DDG REV. NO: 2 REV. DATE: 3/1/216

142 GUYING Insulator Dimensional Requirements Sheet 2 of 8 GUY 8 4 Single Phase 4 to 15kV GUY GUY COMM COMM Degree Angle Deadend One, Two or Three Phase Angle on Wood Crossarm 4 to 15kV GUY GUY COMM. COMM. 45 TANGENT 3/ 2/ Preferred Avian Angle 1 Sgle. Arm Angle 8 Sgle. Arm UNDERBUILD 3 / 2 / 1/ Angle 8 Sgle. Arm Angle 8 Dble. Arm Angle 1 Sgle. Arm Angle 1 Dble. Arm ENG: DDG REV. NO: 2 REV. DATE: 3/1/216

143 GUYING Insulator Dimensional Requirements Sheet 3 of 8 One, Two or Three Phase Angle on Wood Crossarm 4 to 15kV GUY COMM. Deadend Arm Pole Top or Underbuild SIDEARM 66 GUY 88 3/ 2/ Tangent 8 Sgle. Arm Angle 8 Sgle. Arm Angle 8 Dble. Arm COMM / 2 / 1/ DE Assy 8 Arm DE Assy 1 Arm ENG: DDG REV. NO: 2 REV. DATE: 3/1/216

144 GUYING Insulator Dimensional Requirements Sheet 4 of 8 Two or Three Phase Floating and 9 Angle 4 to 15kV GUY GUY COMM VERTICAL FLOATING ANGLE / / COMM VERTICAL 9 DEGREE ANGLE With FG Ext. W/o FG Ext. 3 / / : ENG: DDG REV. NO: 2 REV. DATE: 3/1/216

145 GUYING Insulator Dimensional Requirements Sheet 5 of 8 Two or Three Phase Buck Arm 9 Angle 4 to 15kV o GUY GUY GUY 4 COMM / 3 / 2/ W/Ext. W/o Ext. (NOT SHOWN) 8 F.G. ARMS F.G. ARMS ENG: DDG REV. NO: 2 REV. DATE: 3/1/216

146 GUYING Insulator Dimensional Requirements Sheet 6 of 8 Two or Three Phase Vertical Tap 4 to 12 kv GUY GUY COMM ENG: DDG REV. NO: 2 REV. DATE: 3/1/216

147 GUYING Insulator Dimensional Requirements Sheet 7 of 8 3 to 1kVA Deadend or L Corner ÈÍ Ë ÈÍ Ê On L corners, where a guy can only be installed below the transformer, a Class 4 or heavier pole shall be used. A class 4 pole will provide adequate strength for deadending 1 1/ bare AAAC at 1,36 lbs. Max. Tension (non standard intermediate span urban construction). For conductor tension greater than this, contact Distribution Standards for determination of pole class ENG: DDG REV. NO: 2 REV. DATE: 3/1/216

148 GUYING Insulator Dimensional Requirements Sheet 8 of 8 Transformer, 1PH, T Corner 8 GUY ENG: DDG REV. NO: 2 REV. DATE: 3/1/216 :

149 GUYING Assembly Insulator, Guy 11 4 ** Sheet 1 of 2 B C A 2 Porcelain Strain Ins. 45 Fiberglass Ins. 88 Fiberglass Ins. 1/4 Guy Wire /8 Guy Wire /16 Guy Wire NOTE: 1. If installing insulator in existing guy, Operation Code 918 must be added. 2. Porcelain insulators to be used in Missouri only. Stnd. / Stk. No. Description 11 4 ** kV Insl. Fiberglass Insl Insulator 15kV, 1/4 1 2 A Insulator 15kV, 3/8 or 7/ Insulator Fiberglass, Insulator Fiberglass, Grip Guy, 1/ B Grip Guy, 3/ Grip Guy, 7/ C Roller Guy @ D 918 Install Guy ENG: DDG REV. NO: 3 REV. DATE: 3/21/16

150 GUYING Assembly Insulator, Guy 11 4 ** Sheet 2 of 2 3/8 Guy Wire /16 Guy Wire A B C A A C B 3/8 Guy Wire /16 Guy Wire A C 3/8 Guy Wire /16 Guy Wire B A Stnd. /Stk. No. Description 11 4 ** A Insulator Fiberglass, Insulator Fiberglass, B Grip Guy 3/ Grip Guy 7/ C Link Figure D 918 Install Guy ENG: DDG REV. NO: 3 REV. DATE: 3/21/16

151 GUYING Stub Pole Guy ** Sheet 1 of 1 D or E NOTE: 1. This DCS may only be used on guy stub poles where the span guy is insulated and there are no other energized conductor or communication attachments on the pole. 2. DCS for 1/4 guy is not to be used in Illinois. A B D Stnd. / Description ** Stk. No. 1/4 3/8 7/ Wire Guy, 1/ Wire Guy, 3/ Wire Guy, 7/ Hook Guy, Light Duty Hook Guy, Heavy Duty Grip Guy, 1/ Grip Guy, 3/ Grip Guy, 7/16 3 E Deadend Auto 1/ Deadend Auto 3/ Deadend Auto 7/ ** Anchor Screw F ** Anchor Screw, Hi Torque G Protector Guy 1 1 I 11 4 ** Assembly Insulator, Guy Install Guy ENG:DDG REV. NO: 1 REV. DATE: 11/13/15

152 GUYING Sub Transmission Anchor Guy Fiberglass Insulator ** Sheet 1 of 1 B C A E I 1 H F 6 G NOTES: 1. Omit insulator if not required. Insert additional insulators if needed. See DCS 11 1 ** for insulator location and requirements FG insulator (Stk. No ) may be used in place of the 45 FG insulator where required. 3. For anchors with three guys attached, use DCS or Stnd. / Stk. No. Description ** /8 7/16 3/8 7/16 A Wire Guy, 3/ Wire Guy, 7/16 4 B Hook Guy, Heavy Duty Hook Guy, Heavy Duty @ C Insulator Guy, FG Insulator Guy, FG E Grip Guy, 3/ Grip Guy, 7/ F Deadend Auto, 3/ Deadend Auto, 7/ Deadend Auto, 3/8, Long Bail Deadend Auto, 7/16, Long Bail G 11 6 ** Anchor Screw ** Anchor Screw, Hi Torque H Marker Guy @ I 11 4 ** Assembly Insulator, Guy Install Guy ENG: DG REV. NO: 9 REV. DATE: 2/8/16

153 GUYING Screw Anchors 6, Lb. Torque Capacity 11 6 ** Sheet 1 of 1 6 MIN. to 9 MAX. GROUND LINE 5 B ( ) 5 TWIN EYE GUY ADAPTER 14 HELIX 18 B 2 A 7 12 HELIX A 1 HELIX ROUND ROD SINGLE HELIX HELIX SQUARE SHAFT MULTI HELIX 1, 12 & ATTACHED TO EXTENSION ROD AT GROUND LINE Size Holding Power Lbs. Standard Sand Clay Clay Pan 1 12, 15, 16, , 22, 25, , 12, & 14 35, 4, 6, NOTES: 1. Expanding anchors, Dist. Std ** may be used if power installation equipment is unavailable or if soil condition, particularly rocks makes use of screw anchor or high torque screw anchor impractical sectional rods (Stk. No ) may also be used in poor soil to obtain greater setting depth of the anchor. 3. High torque screw anchors, Dist. Std ** should be used only where power installation equipment is available and soil conditions are such that regular screw anchors would twist off at the helix. 4. Guy eye nut/adapter is provided with the rod. If it is necessary to order separately, the stock numbers are; Twin eye nut for round rod Triple eye adapter for square shaft The top helix must be a minimum 6 deep. Therefore, extension rod ( ) must be used in all cases. Continue to install until there is approximately one quarter (1/4) turn per foot in the square shaft. 6. Drive wrench for square shaft anchors is Stock No Multiple anchors must be spaced a minimum 5 apart. Stnd. / Stk. No. Description 11 6 ** A Anchor 1 Helix, 1 3/8 Hub Anchor 14 Helix, 1 3/8 Hub Anchor 1, 12, & 14 Helix, w/twin Eye Guy Adaptor 1 B Rod Anchor, 7, with Twin Eye Nut Rod Anchor Extension, 5 1 ENG: DDG REV. NO: 6 REV. DATE: 8/31/15

154 GUYING High Torque Screw Anchors Alternate ** Sheet 1 of 1 Anchor Size Holding Power Lbs. Clay Claypan Hardpan Laminated Rock Standard No. Single Section Rod 8 Note 3 12,5 2, 24, Note 3 16,5 25, 28, NOTES: 1. Expanding anchors, Dist. Std ** may be used if power installation equipment is unavilable or if soil condition, particularly rocks, makes use of high torque screw anchors impossible rods must be used with some installation equipment. 3. Screw anchors, Dist. Std ** must be used in this type soil. They should also be used where soil conditions permit because of the increased expense of these high torque screw anchors over regular screw anchors. Stnd. / Stk. No. Description ** 1 3 A Anchor 8 Helix Anchor 1 Helix 1 B Rod Anchor, 7, with Twin Eye Nut 1 1 ENG: DDG REV. NO: 1 REV. DATE: 5/14/99 REAFFIRMED DATE: 7/1/1

155 LIGHTNING PROTECTION AND GROUNDING General Sheet 1 of 8 1. General This section outlines standard ratings of lightning protective equipment, methods of installation, equipment to be grounded, and methods of grounding. 2. Lightning Protection Two types of lightning protective equipment are used to protect OH lines and associated equipment. These are Overhead Static Wire and Lightning Arresters. 2.1 Overhead Static Wire This is a grounded overhead wire installed above the circuit to be protected to shield it from lightning. It is located at an elevation such that a line passing through the static wire and the outermost conductor below it is at a 3 O maximum angle with a vertical line. This continuous overhead static wire is grounded by means of a formed copper wire grounding electrode at each pole Installation of Static Wire The preferred method of lightning protection of overhead sub transmission circuits is through use of an overhead static wire. The static wire shall be grounded at every pole except manually operated group air break switch poles. The best protection is afforded by low pole ground resistance (less than 15 ohms). Existing circuits which qualify for improved lightning protection shall be protected in this manner. Additional pole height may be required to add a static wire. A fiberglass pole top extension or a wood bayonet can be used for added height. 2.2 Lightning Arresters Metal Oxide Varistor (MOV) arresters are normally used for protection of overhead distribution circuits or equipment where conditions warrant (e.g. high ground resistance or retrofitting shielded circuits with a poor history of lightning performance). These arresters (mostly zinc oxide) are solid state and are direct connected from line to ground. MOV arresters are sensitive to temporary system overvoltage such as may occur due to ferroresonance or to single phase switching of ungrounded wye delta transformer banks. In such instances contact Standards engineering for recommendations. Higher voltage arresters may be required. There are many silicon carbide internally and externally gaped arresters still on the system. These allow a higher discharge voltage than MOV arresters, reducing the surge protective margin. When these are found during work on a pole they should be replaced with a polymer housed metal oxide (MOV) arrester (especially at riser poles) Installation of Lightning Arresters When installed to protect equipment, arresters shall be installed as near as practical to the equipment to be protected. See Table 2 for equipment to be protected. ENG:WYW REV. NO: 21 REV. DATE: 11/18/16

156 LIGHTNING PROTECTION AND GROUNDING General Sheet 2 of 8 Arresters are also installed on sub transmission for general line protection. In this application, arresters should be installed on the top phase of every pole where a 3 O shield angle exists. Skipping spans severely reduces the ability of the arresters to protect against direct stroke flashovers. Where lines run through wooded areas or close (within 1 1/2 pole heights) to any type of structure at least as tall as the top phase, induce flashovers may be experienced. If outages are experienced in this circumstance, arresters should be installed on the remaining phases of the circuit(s) at roughly 6 intervals. Where a shield angle greater than 3 O exists, arresters should be placed on all three phases of every pole in open territory. Where the line runs through areas shielded by trees of other structures, arresters should be installed on all three phases at roughly 6 intervals. Distribution underbuild, particularly when built with all three phases on one crossarm, will many times experience flashovers from the ground lead of either static construction or arresters on the sub transmission circuit(s). If experience indicates this to be the case, arresters should be installed on the B phase (closest to the pole). In all cases the primary connection lead as well as the ground lead should be as short as possible and free of any sharp bends. Under no circumstances should pigtail coils be made in the arrester connecting leads. Installation notes: 1. Connect the arrester ground lead before connecting the arrester to the line. 2. Install wildlife guards on line terminals of all line arresters and cover (stk # ) over transformer sidewall bracket arrester attachment bolt. 3. Do not reconnect arresters with a blown ground lead disonnector. 4. Arresters removed for any reason shall not be re installed. ENG:WYW REV. NO: 21 REV. DATE: 11/18/16

157 LIGHTNING PROTECTION AND GROUNDING General Sheet 3 of 8 TABLE 1. Standard Lightning Arrester Ratings (See NOTES As Below) App Type Circuit Rating *MCOV Stock Number 24 V Delta 3 kv 2.55 kv Gnd Y/24 V 3 kv 2.55 kv Gnd Y/24 V Trf. Mnt 3 kv 2.55 kv Gnd Y/24 V Terminal Pole 3 kv 2.55 kv /24 V with Isolated Neut 3 kv 2.55 kv V without Neutral Extended 6 kv 5.1 kv V Delta 6 kv 5.1 kv OH OH 1247 Gnd Y/72 V 1 kv 8.4 kv Gnd Y/72 V Trf Mnt 1 kv 8.4 kv Gnd Y/72 V Terminal Pole 9 kv 7.65 kv Gnd Y/72 V Terminal Pole 1 kv 8.4 kv (3) 1247 Delta or 14,4 Un Grounded, Gapped 15 kv 12.7 kv Gnd Y/762 V 1 kv 8.4 kv Gnd Y/797 V 12 kv 1.2 kv V Un Grounded 15 kv 12.7 kv or 144 Delta 18 kv 15.3 kv Gnd Y/797 V Terminal Pole 1 kv 8.4 kv Gnd Y/144 V (Solidly Grounded) 18 kv 15.3 kv Gnd Y/19.9kV (Solidly Grounded (Transformer) 27kV 22kV Gnd Y/1992 V (solidly Grounded) 3 kv 24.4 kv (1)(4) 345 Gnd Y/1992 V (solidly Grounded) 3 kv 24.4 kv (2)(4) 345 Gnd Y/1992 V Terminal Pole 27 kv 22 kv Gnd Y/1992 V Terminal Pole, Gapped 27 kv 22 kv (5) 345 Gnd Y/1992 V Suspended with Side Post Insulator 3 kv 24.4 kv (4) 345 V Un grounded Delta /Suspended with Side Post Insulator(13) 36 kv 29 kv (5) 345 Gnd Y/1992 V Suspended with DE Insulator 3 kv 24.4 kv V Un grounded Delta /Suspended with DE Insulator (13) 36 kv 29 kv Gnd Y/1992 V (Solidly Grounded) Intermediate Class 3 kv 24.4 kv (6) 345 Gnd Y/1992 V (Solidly Grounded) Intermediate Class 3 kv 24.4 kv (7) 345 V Un grounded Delta Intermediate Class (13) 36 kv 29 kv (9) 345 V Un grounded Delta Intermediate Class (13) 36 kv 29 kv (8) 69 V Gnd Y Intermediate Class 6 kv 48 kv (1) 69 V Gnd Y Suspended with Side Post Insulator 6 kv 48 kv V Gnd Y Suspended with DE Insulator 6 kv 48 kv V URD 1 kv 8.4 kv UG 1247 V URD (Parking Stand Arrester) 1 kv 8.4 kv V URD (Small Interface) (11) 27 kv 22 kv V URD (Large Interface)(12) 27 kv 22 kv V URD (Small Interface)(11)(13) 36 kv 29 kv V URD (Large Interface)(12)(13) 36 kv 29 kv SEC 1 Phase 12 or 12/24 V 175 V *Maximum Continuous Operating Voltage (MOV) ENG:WYW REV. NO: 21 REV. DATE: 11/18/16

158 LIGHTNING PROTECTION AND GROUNDING General Sheet 4 of 8 NOTES: THIS TABLE DOES NOT APPLY TO ANY ARRESTERS ANYWHERE IN SUBSTATIONS. (1) Direct pole mounting (2) Crossarm mounting (3) Use only when problems are experienced with 9kV ( ) operating frequently or failing due to higher operation voltages (proximity to substation, etc.). (4) The suspended arrester is to replace stock # and stock # (5) Use on un grounded delta system. (6) Base mount for use on primary metering structure. (7) Crossarm mount for use on primary metering structure. (8) Base mount for use on un grounded delta primary metering structure. (9) Crossarm mount for use on un grounded delta primary metering structure. (1) Base mount for use on primary metering structure. (11) Small Interface is to mount on radial feed. (12) Large Interface is to mount on loop feed. (13) For un-grounded delta 34kV system. TABLE 2. Equipment To Be Protected by Lightning Arresters Equipment Arrester Location Distribution Transformers Primary Side Voltage Regulators Pole Installations Primary & Secondary Sides Constant Current Regulators Pole Installations Primary & Secondary Sides On terminal pole and on same phase on structures each side of riser poles. Terminal Poles Lead and Non Lead Cables Line Switches Normally Closed Arresters not required Install both sets of arresters on adjacent pole for Illinois; for Missouri, install arresters on a separate bracket arm below the switch, and install additional set of arrester on adjacent pole Line Switches Normally Open of unprotected side, or install both arresters on adjacent pole if space is limited. Install both sets of arresters across the deadend insulators on the switch pole shown DCS 1 Airbreak Switches Normally Open 35 & 69kV 34** and 1 69**. Capacitors On capacitor rack Time Switches On switch Meters (only on approval of Engineering) On service entrance equipment On crossarm, pole face or primary apparatus. Minimum of 4 arresters per phase per mile Unshielded Distribution Lines (counting apparatus arresters if separated by 6 ft or more). Deadend Poles (Unshielded Circuits) Top Phase (Vert): All Phases (Flat) 3. Grounding Practices 3.1 General ENG:WYW REV. NO: 21 REV. DATE: 11/18/16

159 LIGHTNING PROTECTION AND GROUNDING General Sheet 5 of 8 Per NESC code, multiple ground leads on the same pole shall be bonded together. Ground rods will continue to be used for grounding pad mounted equipment and existing pole ground installations. For new pole ground installations a formed #2 soft drawn copper electrode shall be used. This electrode is to be placed at the bottom of the pole and covered with at least six inches of native soil. The vertical lead of the electrode should be trained to the side of the pole hole so that it will not be covered by the crushed rock backfill. If the desired resistance is not obtained additional ground rods can be driven in parallel with the formed electrode but a minimum separation distance of six feet shall be maintained. 3.2 The Common Neutral System Either a 24/416 Y volt or a 72/1247 Y volt common neutral distribution system is normally used at Ameren. These systems use a continuous metallic conductor which serves as both the primary and secondary neutral conductor. This neutral conductor must be attached to grounds at various points throughout its length to insure adequate grounding of the circuit. These grounds (Table 3) will consist of customers grounds, lightning arrester grounds, and static wire grounds and occasionally a ground installed solely to provide adequate grounding of the common neutral. Where a common neutral is present, all grounds installed for any purpose shall be bonded to it. 3.3 Number of Grounds Common Neutral At least four grounds are required, (counting equipment grounds but not counting customers grounds), in each mile of common neutral circuit for both overhead and underground circuits (maximum 132 feet spacing). In cases of random lay underground with other utilities, at least 8 grounds per mile are required. Where it is necessary to install additional grounds because of this requirement, approximately uniform spacing shall be used. See Table Size of Ground Wire The size of ground wire will vary according to the type of equipment being grounded and shall conform to Table 3. In areas of frequent damage/vandalism, 7#1 copperweld should be substituted for the #6 soft drawn copper pole ground wire. ENG:WYW REV. NO: 21 REV. DATE: 11/18/16

160 LIGHTNING PROTECTION AND GROUNDING General Sheet 6 of Equipment To Be Grounded (*) TABLE 3. Equipment To Be Grounded and Size Of Ground Wire Case Equipment or Circuit To Be Min. Size of Other Requirements No. Grounded Ground Wire 1 Lightning Arrester #6 See Note 2 for Sec Lightning Arresters 2 Cable Sheath Grounds #2 Wipe ground leads to cable sheath at base of potheads and also to standpipe on pole. Interconnect solidly with arrester ground leads. 3 Twist together and route close to arrester and on Concentric Neutral on Terminal Pole #2 to the neutral using #2. Tie short #6 SD cu to arrester ground terminal. 4 Capacitors #6 Hangers are cases to be bonded together and 5 Regulator Cases #6 Secondary Neutral or Grounded Conductor connected solidly to arrester ground lead. Connect solidly to arrester ground lead. Keep leads short. 6 7#1 CW Connect solidly to pole ground. 7 Common Neutral 7#1 CW A minimum of four grounds per mile, in addition to customers' grounds, is required. 8 Metal Cable Risers #6 Separate grounds shall be installed for risers carrying non lead sheath cables. All airbreak switch handles shall be grounded 9 Airbreak Switch #2 through a separate ground lead and rod. Interconnection shall be made with arrester ground lead or to the OH static wire. All transformer cases shall be grounded. Ground 1 Transformer Cases #4 lead from transformer case shall be closely and solidly connected to arrester ground lead. 11 Transformer Windings See DCS 13 6 and 13 7 for connection #6 pole mounted diagrams. 12 Transformer Windings #2 pad mounted See DCS Section Metal Lamp Posts & Metal Metal lamp posts and metal line or guying posts #6 Poles shall be effectively grounded. 14 Reclosers/Sectionalizers #6 Connect arrester ground lead solidly to equipment tank. 15 S&C Intellirupter/G&W #2 Connect the recloser bracket to pole ground. Wiper Recloser 16 Static wire 7#1 CW 17 Customer Service #6 18 Instrument Transformers #12 Meter Sockets, Troughs & 19 Enclosures 2 Long Runs of UG Cable May Require an External Ground Connection Connect to pole ground on every pole unless otherwise noted on construction standards. Connect to metallic water pipe system. Otherwise to driven ground rod. Cases of instrument transformers shall be grounded. Grounding of secondary windings shall be per Engineering instructions. #12 Meter sockets, troughs and enclosure shall be grounded. #2 See DCS ** for an example of an external ground connection on a splice. ENG:WYW REV. NO: 21 REV. DATE: 11/18/16

161 LIGHTNING PROTECTION AND GROUNDING General Sheet 7 of 8 NOTES: 1 Pole line hardware (including cluster bracket and streetlight brackets) must not be grounded except with engineering approval. 2 Where a lightning arrester is installed on a secondary or service the arrester ground lead shall be solidly connected to any one or combination of the following grounds: a The neutral or grounded service wire. b Customer s common grounding conductor. c Customer s equipment grounding conductor. da. A separate grounding conductor such as a driven rod. 3.6 Ground Wire Attachment and Covering The ground wire shall be run in a straight line or a smooth curve and shall clear hardware by at least 2 inches. The static ground wire from 34kV circuits shall be routed on the opposite side of the pole away from the closest phase of any underbuilt circuit. Avoid making sharp bends in ground wires. Take care when driving staples onto ground wires to avoid damaging the wire. Where the ground wire passes over a messenger or guy wire, a loop shall be formed to clear the messenger or guy wire. If necessary a bridge shall be made from a 6 length of plastic molding, placing the half round of the molding against the pole and taping the ground wire in place in the groove. Where guarding is not required, grounds shall be protected by being substantially attached closely to the surface of the pole or other structure in areas of exposure to mechanical damage and, where practical, on the portion of the structure having least exposure. A 4 section of molding may be placed over the ground wire in the working area on badly congested poles. The purpose of the molding is to keep linemen s climbers from damaging the ground wire when working on primary circuits. Ground wire molding is required for installations with no common neutral and separate arrester/equipment tank and secondary neutral grounds. These separate grounds shall be made with 6 volt insulated conductor (use stk # ) and shall be covered with plastic molding for a distance of 8 feet from the ground. The arrester/tank ground and secondary ground can be connected using an isolation arrester (stk #1 1 19). One ground wire can be connected to a driven ground or coiled ground electrode at the base of the pole but the other ground wire shall be carried (buried) to a driven ground rod at least 2 feet from the base of the pole and connected with #2 SD bare copper conductor. 3.7 Static Wire at Substation 1/ AAC or 12/7 ACSR static wire shall be electrically continuous and tied into the bulk substation ground grid. Where the connection into the substation cannot be made overhead, direct bury a 4/ bare copper conductor from the last pole with static termination to the substation ground grid. The 4/ size conductor allows ENG:WYW REV. NO: 21 REV. DATE: 11/18/16

162 LIGHTNING PROTECTION AND GROUNDING General Sheet 8 of 8 some safety margin for corrosion. The downlead from the static wire to the 4/ conductor shall be #2 copper. 3.8 Static Wire Personal Protective Grounds a Wire Common Neutral 1/ AAC or 11.8 (12/7) ACSR (or other shield wires having current capacity of 25 amps or greater) may be used for direct connection of protective grounds on 35 and 69 kv circuits if there is a common neutral and 7#1 CW pole grounds (or other pole grounds with current capacity of at least 5 amps) connected to the shield wire for at least two poles in each direction. The common neutral must also be connected to the down leads at each pole. b Without Common Neutral 1/ AAC or 11.8 (12/7) ACSR (or other shield wires having current capacity of 25 amps or greater) may be used for direct connection of protective grounds on 35 and 69 kv circuits with no common neutral present if #2 copper down leads are grounded at every 4 th pole (no more than 12 feet apart); a supplementary grounded rod must be driven at least 6 feet from the closest ground rod. This extra ground rod shall be connected with #2 copper to the #2 copper down lead.. Alumoweld Static Wire Alumoweld static wires have been installed in the past. Do not connect protective grounds to Alumoweld. It may fuse if a fault occurs. To improve protective grounding on 35 kv lines with Alumoweld static and poor ground resistance, #2 copper downleads may be installed at intervals of 4 spans (no more than 12 feet). Protective grounds can then be connected to the #2 Cu. A supplemental ground is required from #2 copper downlead to a second driven ground. 3.9 Static Wire/Common Neutral System 1/ AAC or 11.8 (12/7) ACSR (or other static wires having current capacity of 25 amps or greater)may be used as the common neutral for lower voltage underbuilt circuits where the run is 3 feet or more. In such cases the static wire must be continuous and connected to the source transformer neutral with #2 SD poly covered wire. The static wire shall not be used in place of the secondary neutral. Where secondary is present the secondary neutral shall be paralleled with the static wire neutral and interconnected at every static wire ground down lead. However, where this would result in short discontinuous sections of neutral a continuous neutral shall be installed from the source transformer. To equalize ground potential static wire ground leads, arrester ground leads, neutral ground leads and equipment case ground leads shall be bonded together with the only exceptions noted in the transformer section of these standards. ENG:WYW REV. NO: 21 REV. DATE: 11/18/16

163 LIGHTNING PROTECTION AND GROUNDING Grounds 121** Sheet1of5 Connectors positioned above ground with a staple above and below the connector I BELOW GRADE - NEW CONSTRUCTION 1 EXCAVATED EARTH 6 EXISTING Connectors positioned above ground with a staple above and below the connector I K 6 SOIL ROCK APPROX.1 - Connectors positioned above ground with a staple above and below the connector I 6 1 EXCAVATED EARTH AA AA APPROX. 6 AUGER SIZE 6 1 EXCAVATED EARTH EXISTING SOIL ROCK BACKFILL EXISTING SOIL K EARTH AUGER SIZE K FOAM AA AUGER SIZE AA APPROX. 6 EXCAVATED EARTH BACKFILL AA AA APPROX. * * 6 AUGER SIZE **12 - MIN.COIL SECTION AA-AA #1 CW Pole Ground/Ground Coil 15kV&Below 1214-#2CuPoleGround/GroundCoil15kV&Below #1CWPoleGround/GroundCoil34&69kV CompositePole12kV CompositePole34&69kV FOAM BACKFILL NOTES: 1. Trainbelowgradegroundwireapproximately8 abovegroundlinetolineupwithpolegroundwireabovegrade. Avoid making sharp bends. 2. See DCS 2 for pole setting depth, reinforcement, and backfill detail. ENG:JMW REV.NO:2 REV. DATE: 9/2/17

164 LIGHTNING PROTECTION AND GROUNDING Grounds 121** Sheet2of5 BELOW GRADE - EXISTING CONSTRUCTION Non-Tension Sleeve Reducer - connect pole ground wirewith#2solidcubareto7#1cwandposition above ground against pole with a staple above and below the connector I K F E 1 6 Min. 6 Min #1CWPoleGround/GroundRod12kV&Below #1CWPoleGround/GroundRod34&69kV 1213-#2CuPoleGround/GroundRod NOTES: 1. Groundresistancewillnormallybelessthan25ohmswithonecoiloronerod. Inrockyorsandysoilwhereexperience indicates ground resistance may exceed 25 ohms, install additional coil or rods spaced not less than 6 apart. Doublingthenumberofrodsorcoilsordoublingthelengthoftherodreducesgroundresistanceby4%. If additional grounding is needed: a) terminalpoles -- a#2barecucounterpoisewire longmaybeplacedinthecabletrenchand connected to the ground lead. b) inrockysoilwheredrivingarodisdifficult -- acounterpoise,asstatedina),maybeplacedinatrenchatleast 18 deep. ENG:JMW REV.NO:2 REV. DATE: 9/2/17

165 LIGHTNING PROTECTION AND GROUNDING Grounds 121** Sheet3of5 ABOVEGRADE - WOODPOLE 5 A NEUTRAL G G 7 B 3-2 APPROX. 1-3 B 4 C kV 1211&4 -Newinstallation &3 - Existing Pole Installation AddStaples AddGroundMolding/Staples 34kV&69kV New-7#1CW Pole Ground/Field Formed Coil-34&69kV Existing-7#1CW Pole Ground/Ground Rod 34&69kV Replacement-Add Staples NOTES: 1. Thegroundwireshallberuninasstraightalinedownthepolewithoutmakingsharpbendsinsuchamanneras to clear hardware by at least 2 inches. Avoid damaging ground wire when installing staples. 2. According to an NESC subcommittee s interpretation, metal brackets and straps used to support non--conductive conduits do not need to be grounded. However, conductive material conduits that enclose electrical supply lines or are exposed to contact with open supply conductors must be effectively grounded. 3. Refer to DCS Section 3 for proper grounding position on different structure configuration. 4. Staplesaretobespaced3 onpolegroundwireand1 --6 fromtopofthepoleon34kvand69kvline. 5. SeeDCS611**forstaticsupportassemblyandDCS12341**and12342**forlightningarresterconnection. 6. Reconnectexistinggroundwirewith7#1CWifpolegroundwireismissingusingDCS Installplasticmoldingonanexistingbarewirepolegroundwhenre--framinganexistingpoleusingDCS ENG:JMW REV.NO:2 REV. DATE: 9/2/17

166 LIGHTNING PROTECTION AND GROUNDING Grounds 121** Sheet4of5 ABOVE GRADE- COMPOSITE POLE A G G 6 NEUTRAL kV CompositePole 34kV&69kV CompositePole Notes: 1. Factory installed#2 Cu pole ground. ENG:JMW REV.NO:2 REV. DATE: 9/2/17

167 LIGHTNING PROTECTION AND GROUNDING Grounds 121** Sheet5of5 Stnd./Stk. No Description 12 1** A Wire, 7#1, CW Poly Covered(ft.) @ Wire,#2Cu.Polycovered (ft.) B Molding -- Grd.Wire,3/4 x8 Long 1 C Staple,GroundWire,Serrated,CuClad D Staple, for 3/4 Plastic Molding, Zn Plated Stl E Rod,Ground,5/8 x8 CuBond F Clamp,Grd.Rod,5/8 for#8 -- 1/ G Clamp, PG.#6 -- 1/ I Non--Tension Sleeve Reducer, Compression -- #2Cu,Solto7#1CWor#2Cu,Str K Wire,#2BareCu,Sol(ft.) @ L Non--Tension Sleeve, Compression, 7#1 CW OP 31 Install Below Grade Ground Coil OP 32 Install Above Grade Pole Ground OP 41 Install Pole Ground/Ground Rod Note: 1. Use the appropriate connector for the ground wire size being replaced. Non--tension sleeve stock# can beusedfor7#1cwconnections,reducingnon--tensionsleevestock#176749canbeusedfor#2solidcuto 7#1CWor#2strandedCuconnections,andsplit--boltstock# canbeusedformostotherconnections. 2. When an underbuild circuit is added, the conductor from the static neutral to the distribution neutral and ground mustbe#2cupolyorlarger. ENG:JMW REV.NO:2 REV. DATE: 9/2/17

168 LIGHTNING PROTECTION AND GROUNDING Lightning Arrester Installation 4 15 kv Existing Circuit ** Sheet 1 of 5 D C 1 B,E D C B H J,K,L H E D E D A A H D AMEREN MO AMEREN MO C C H H E B D J,K,L 36 H A J,K,L A D H D AMEREN IL AMEREN IL & MO 21 ENG: WYW REV. NO: 11 REV. DATE: 6/15/15

169 LIGHTNING PROTECTION AND GROUNDING Lightning Arrester Installation 4 15 kv Existing Circuit ** Sheet 2 of D 24 3 F D H D D H AMEREN MO H AMEREN IL & MO C B 1 24 D 1 ARM 3 D H D B D H B 1 ARM A A AMEREN IL & MO AMEREN MO 22 ENG: WYW REV. NO: 11 REV. DATE: 6/15/15

170 LIGHTNING PROTECTION AND GROUNDING Lightning Arrester Installation 4 15 kv Existing Circuit ** Sheet 3 of 5 C D E 3 B H D A D D H 24 H FT CROSSARM AMEREN IL&MO FT CROSSARM AMEREN MO 23 ENG: WYW REV. NO: 11 REV. DATE: 6/15/15

171 LIGHTNING PROTECTION AND GROUNDING Lightning Arrester Installation 4 15 kv Existing Circuit ** Sheet 4 of 5 NOTES: 1. Route the ground wires in a straight line or a smooth curve. Avoid making sharp bends in ground wires. 2. Take care when driving the staples onto the ground wires to avoid damaging the wire. 3. For IL, arresters must be installed on separate arm 1 ft, For MO, if space allows, arresters on separate arm allows installation with 2 man crew instead of 3 in some areas. 4. Arresters Selection, Refer to DCS Table 1. Stnd. / Stk. No. Description ** Ph 1 Ph 1 Ph 1 Ph A 12 1 ** Grounding Unit B Arrester, 3kV, MCOV Arrester, 8.4kV MCOV Arrester, 12.7kV MCOV Arrester, 1.2kV MCOV C HLC*W Clamp, Hot Line DCS 7 21 D Wire, Copper, #6 SD Poly Covered (ft) E Bracket, Crossarm, Arr. 1 2 G Bracket, Fiberglass, Switch and Arrester F Crossarm, 6 I Crossarm, H Connector, Elect., Split bolt J Bolt, Machine, 3/4 x 1 w/sq Nut K Washer, Square, 3/4 Bolt L Nut, Lock, Square, Galv, ¾ M PG** Clamp, Parallel Groove DCS ENG: WYW REV. NO: 11 REV. DATE: 6/15/15

172 LIGHTNING PROTECTION AND GROUNDING Lightning Arrester Installation 4 15 kv Existing Circuit ** Sheet 5 of 5 Stnd. / Stk. No. Description ** Ph 3 Ph 3 Ph 3 Ph 3 A 12 1 ** Grounding Unit B Arrester, 2.55kV MCOV Arrester, 8.4kV MCOV Arrester, 12.7kV MCOV Arrester, 1.2kV MCOV C HLC*W Clamp, Hot Line DCS D Wire, Copper, #6 SD Poly Covered (ft) E Bracket, Crossarm, Arr G Bracket, Fiberglass, Switch and Arrester F Crossarm, 6 1 I Crossarm, H Connector, Elect., Split bolt J Bolt, Machine, 3/4 x 1 w/sq Nut K Washer, Square, 3/4 Bolt L Nut, Lock, Square, Galv, ¾ M PG** Clamp, Parallel Groove DCS ENG: WYW REV. NO: 11 REV. DATE: 6/15/15

173 LIGHTNING PROTECTION AND GROUNDING Lightning Arrester Installation Single Circuit Existing 34 & 69 kv (Not for New Construction) ** Sheet 1 of 3 G C, N,S E D kv kv TOP PHASE G E C, N,S G G 14 E P D C,S,N,K kv kv THREE PHASE ENG: WYW REV. NO: 14 REV. DATE: 12/16/16

174 LIGHTNING PROTECTION AND GROUNDING Lightning Arrester Installation Single Circuit Existing 34 & 69 kv (Not for New Construction) ** Sheet 2 of 3 E H I G Shield Angle MIN. E R,S DIMENSION VARIES I H 3 P D kV all Three Phases NOTES: 1. If the shield formed by the pole top insulator and the outside crossarm insulator is less than 3 deg., arrester on the top phase only. If the angle exceeds 3 deg., arresters on all three phases. 2. Arresters should be installed on every pole in open ground, every third pole if shielded by trees or buildings. 3. Not for use in new construction. This Standard is only for lightning protection of existing subtransmission configurations. 4. Use double staples to hold ground wire in the event the ground lead isolator blows off. Distance from the double staples to the ground lead isolator should be 6 minimum. 5. Route the ground wires in a straight line or a smooth curve. Avoid making sharp bends in ground wires. 6. Take care when driving the staples onto the ground wires to avoid damaging the wire. 7. Stock # and Stock # are not for new installation. 8. Stock # and stock # are for New installation. ENG: WYW REV. NO: 14 REV. DATE: 12/16/16

175 LIGHTNING PROTECTION AND GROUNDING Lightning Arrester Installation Single Circuit Existing 34 & 69 kv (Not for New Construction) ** Sheet 3 of 3 Stnd. / Stk. No. Description C Bolt, Mach., 3/4 x D 12 1 ** Grounding Unit E Arrester, 3kV, 24.4kV MCOV Crossarm Mt Arrester, 3kV, 24.4kV MCOV Pole Mt Arrester, 6kV, 48kV MCOV W/Clevis, Susp Arrester, 3kV, 24.4kV MCOV, W/Clevis, Susp 3 F HLC*W Hot Line Clamp DCS 7 21 G STC*W Clamp, Stirrup DCS H Wire, Copper, Poly Covered, #6 S.D. 2 I Bracket, Crossarm, Arrester Bracket, fiberglass, Switch and Arrester 1 K Eyelet, ¾ Bolt 2 2 L Eyenut, ¾ Bolt 1 1 N Washer, Square, Curved 3 x 3 3/ P P.G. Clamp, P.G. ( see Std ) R Bolt, Dbl., Arm, 3/4 x 14 2 S Nut, Lock, Square, Galv, ¾ ENG: WYW REV. NO: 14 REV. DATE: 12/16/16

176 LIGHTNING PROTECTION AND GROUNDING Lightning Arrester Installation Single/Double Circuit 34 kv ** Sheet 1 of B 14 6 E 14 A A F,E,H,I,C G NOTES: 1. Arresters should be installed on every pole. 2. Items A includes base mounted clevis, tinned copper ground and line terminal leads, disconnector, and hot line clamps. Stirrup clamp on end of line terminal lead need to be ordered separately. 3. Use care when driving staples onto covered pole ground wire to avoid damaging the wire. Stnd. / Stk. No. Description ** A Arrester, 3kV, 24.4kV MCOV Suspended 1 B STC*W Clamp, Stirrup DCS C Bolt, DA, 3/4 x 18, HDG w/4 Sq Nuts D 12 1 ** Grounding Unit 1 1 E Eyenut, 3/4 1 F Washer, Square ¾, Galvanized 2 G PG** Clamp, PG, Bronze DCS H Eyelet, ¾ Bolt 1 1 I Nut, Lock, Square, Galv, ¾ 1 2 J Bolt, Mach, ¾: x 12 1 ENG:WYW REV. NO: 7 REV. DATE: 9/8/14

177 LIGHTNING PROTECTION AND GROUNDING Lightning Arrester Installation Single/Double Circuit 34 kv ** Sheet 2 of C 12 4 B THREE PHASES A E 3 NOTE: ARRESTERS SHOULD BE INSTALLED ONLY ON THE PHASES LOCATED ON THE UPPERMOST OF THE THREE CROSSARMS. (TOP CROSSARM ONLY IS SHOWN.) kV C 6 A B E NOTES: D kV 1. Arresters should be installed on every pole 2. Use double staples to hold ground wire in case the ground lead isolator blows off. Distance from the doubles staples to the ground lead isolator should be 6 maximum. 3. Arrange arrester brackets to position arresters low on the cross but not low enough to place the top of the arrester below the phase wire. 4. Route the ground wires in a straight line or a smooth curve. Avoid making sharp bends in ground wires. 5. Use care when driving staples onto covered pole ground wire to avoid damaging the wire. Stnd. / Stk. No. Description ** 1 2 A Arrester, 3 kv 24.4kV MCOV, Crossarm Mount 2 B HLC*W Clamp, Hot Line 2 4 C Wire, Copper, Poly Covered, #6 S.D. 15 D 12 1 ** Grounding Unit 1 1 E Bracket, Crossarm, Arrester 2 4 ENG:WYW REV. NO: 7 REV. DATE: 9/8/14

178 TRANSFORMERS 15 kv and Below Grounded Wye Primary System KVA Single Phase Protected Sheet 1 of 3 FOR CSP TRANSFORMER INSTALLATION SEE NOTE 7 FOR TRANSFORMER WITHOUT TANK MOUNTED ARRESTER SEE NOTE B TURN SWITCH TOWARD POLE. K N, D J 3 11 SEE ARRESTER MOUNTING DETAIL 9 8 S 3 5 A A PRIMARY NEUTRAL H 1 L,M F T C,D 12 5kVA & Smaller or kVA SEE DCS FOR 12/24 OR 24/48 V 3 WIRE SEE DCS FOR 12 OR 24 VOLT 2 WIRE G A 6 1 NOTE: TRANSFORMERS MAY BE RECEIVED WITH THE LA MOUNTED BESIDE EITHER THE H1 OR H2 BUSHING. BOTH POSITIONS ARE ACCEPTABLE. POSITION THE SWITCH FOR EASY CONNECTION TO THE BUSHING HAVING THE LA ATTACHED. 13 R #2 Cu H.D. FOR LA CONNECTION S 16 P Q TO LINE R 16 S MAY BE ROTATED FOR SECONDARY CLEARANCE SECTION AA WITH CUTOUT COVER SWITCH DETAIL 8 O SEE SWITCH DETAIL TO GROUND TO TRANSFORMER ARRESTER MOUNTING DETAIL FOR TRANSFORMER WITHOUT TANK MOUNTED ARRESTER ENG: DG REV. NO: 12 REV. DATE: 11/17/15

179 TRANSFORMERS 15 kv and Below Grounded Wye Primary System KVA Single Phase Protected Sheet 2 of 3 Stnd. / Stk. No. Description A 12 1 ** Grounding Unit B HLC*W Hot Line Clamp 1 T C Bolt, Mach., 5/8 x 12 (5 kva & smaller) OR Bolt, Mach., 3/4 x 12 ( kva) 2 T D Washer, Square, 5/8 (5 kva & smaller) OR Washer, Curved, 3/4 ( kva) 2 T F Secondary Leads (Ft.) (See ) 12 T G PG* See 7 25 H Transformer (see ) 1 T9 J Wire, Trans. Riser, #4, S.D. Poly covered (FT.) 12 K Bracket, Cutout 1 5, 7 L Switch, Fused, Open Type M Link, Fuse 1 N Bolt,, Mach, 5/8 x 12 O Bracket, 3 Position, Equipment Mount P Arrester, Lightning (see ) Q Wire, #6Cu, S.D. R Clamp, Hotline, #6 to 2/ 1 NOTES: S Cover Cutout 1 T T Wire, #4 Cu, S.D., Covered 1 1. Arrester may be shifted to most convenient side of tank on two bushing transformers. 2. Deadend construction Deadend primary one span past transformer pole if there is another pole in the lead. If not, see DCS Measure distance between mounting slots and drill so that transformer rests evenly on both bolts. 4. See DCS for fuse selections. 5. Switch may be mounted on either side of pole or on the crossarm. If the switch is mounted on the crossarm, it should be positioned 12 from the pin insulator or from the pole. The transformer may be raised 12 to 24 when the switch is located on the crossarm. Omit items K and N. 6. See DCS ** for secondary support and DCS ** for secondary configurations. 7. If installing a CSP transformer, a fused switch shall be installed as shown. Exception: If existing pole space does not allow for installation of a fused switch and the number of customers affected by transformer failure is deemed acceptable, then items K, L, M, N, and S may be omitted and connect the transformer primary lead to the overhead conductor. 8. If installing a transformer that does not have a tank mounted lightning arrester use items O, P, Q, and R and install the appropriate lightning arrester on the bracket beside the switch. Keep arrester leads as short as possible. See note 16 for avian protection requirements /416Y transformer may have side wall or cover mounted HV bushings. If side wall mounted bushings: a. Build according to this DCS except use 2.5kV primary lead wire stock # , or b. If pole is congested, 2.5kV primary lead wire stock # in conduit similar to DCS may be used. 1. Use DCS for ground coil application on new pole installation. Use DCS for ground rod application on existing pole installation. ENG: DG REV. NO: 12 REV. DATE: 11/17/15

180 TRANSFORMERS 15 kv and Below Grounded Wye Primary System KVA Single Phase Protected Sheet 3 of This dimension is to top bolt position if FG crossarm is used. 12. Use DCS for existing structure modification or DCS for pin cover in area with eagle population. 13. If pole is NOT truck accessible, make secondary connections on the climbing side of the pole. 14. Use DCS ** for new pole installation. 15. On single phase pole lines where future addition of crossarm for adding additional phases is not reasonably expected, this dimension can be reduced to 6 (i.e., total of 36 from the pole top to the top bolt of the cutout bracket). 16. For all of Illinois and locations in Missouri where additional avian protection is needed, omit the piece of #2 copper wire and hotline clamp R. Connect the #6 copper poly covered arrester wire Q directly to the fused switch connector. ENG: DG REV. NO: 12 REV. DATE: 11/17/15

181 TRANSFORMERS Three Single Phase Cluster Mounted 15 kv and Below Grounded Wye Primary Systems ** Sheet 1 of 2 GROUNDED WYE PRIMARY CONNECTION TO FUSED CUTOUTS AND COMMON NEUTRAL R,S HIGH VOLTAGE NEUTRAL CONNECT TO SYSTEM NEUTRAL TO LINE E TO TRANSFORMER #2 Cu H.D. FOR LA CONNECTION P 8 SWITCH DETAIL TO GROUND 9 Q TO LINE TO TRANSFORMER LIMITED USE SEE SWITCH DETAIL ARRESTER ON ARM E 18 E 4 D A B TURN SWITCHES TOWARD POLE. 9 P D Q 7 B TO SYSTEM NEUTRAL D R,S 4 ÉÉ G 1 6 L ÉÉ SEE DCS SEE DCS L 5 kva & Smaller kva kVA kva & Smaller kva ENG: DG REV. NO: 7 REV. DATE: 9/2/15

182 TRANSFORMERS Three Single Phase Cluster Mounted 15 kv and Below Grounded Wye Primary Systems ** Sheet 2 of 2 NOTES: Stnd. / Stk. No. Description ** A Crossarm 1 w/ 6 V Brace B Switch, Fused, 1A, 15kV T1 D Primary Leads (ft.) (See ) E HLC*W Hot Line Clamp F Mounting Unit 3 Pos. Light ( Up To Three 5 KVA Trans. ) Mounting Unit 3 Pos. Heavy (Three KVA Trans. ) Mounting Unit 3 Pos. Xtra Hvy (Three KVA) G Transformer H Secondary Leads (Ft.) (See ) T K PG* See L 12 1 ** Grounding Unit N Link, Fuse O Tag, Banked Transformer P Bracket, Crossarm, Heavy Duty Q Cover Cutout R Bolt, Mach., 3/4 x S Washer, Curved, 3/ See DCS ** for secondary support and DCS ** for secondary configurations. 2. Use only one V Brace. Keep the extra brace for future use. 3. See DCS for fuse selection. 4. Use tag, Stock # to identify transformers that have been rewired internally for 12/28Y service. The tag should be attached to the secondary bushing that is no longer connected internally. See DCS These dimensions may be reduced to 24 and 48 for installation on existing pole. 6. Use DCS for ground coil application on new pole installation. Use DCS for ground rod application on existing pole installation. 7. For transformer banks greater than 5 KVA on 4KV circuits, substitute 2A fused switches stock # For all of Illinois and locations in Missouri where additional avian protection is required, omit #2 CU HD wire and hot line clamps and connect #6 CU poly covered arrester lead wire directly to the fused switch connector. 9. ONLY FOR INSTALLATION WHERE ARRESTERS CANNOT BE MOUNTED ON THE TRANSFORMER TANKS, substitute crossarm bracket with stock # and mount arresters on crossarm back to back with the fused switches. See note 8 for avian protection /416Y transformers may have side wall or cover mounted HV bushings. If side wall mounted bushings: a. Build according to this DCS except use 2.5 KV primary lead wire per Table 2.2 of DCS , or b. If pole is congested, 2.5KV primary lead wire in conduit similar to DCS ENG: DG REV. NO: 7 REV. DATE: 9/2/15

183 CABLE TERMINALS 15 kv & Below Single Phase #2 Through 4/ ** Sheet 1 of 3 1 #2 Direct Buried or In 2 Conduit/Duct 2 4/ Direct Buried or In 2 Conduit/Duct 3 #2 Direct Buried or In 3 Conduit/Duct 4 4/ Direct Buried or In 3 Conduit/Duct TO LINE Z 3 #2 Cu H.D. FOR LA CONNECTION MOUNTING LIMITED TO 3 A B DO NOT GROUND BRACKET Use #4 Cu Line Lead w/ 1A Barrel Use #1/ Cu Line Lead w/ 2A Barrel Use #1/ Cu Line Lead w/ 3A Barrel 3 BRACKET DETAIL #2 Cu H.D. FOR GROUNDING CONNECTION TO TERMINATOR SWITCH DETAIL Ë Ë 6 12 Ë Ë ËËË ËË ËË U,W ËË 1 G V ËËË ËË TOP BOLT CONDUIT MUST EXTEND A MINIMUM OF 4 ABOVE THE HIGHEST COMMUNICATION ATTACHMENT AND TO THE NEUTRAL. TO LINE 11 BB TO LA F Q BB T C 11 E X 1 Z S Ë Ë Ë Y D DD SEE BRACKET DETAIL 8 J,K,L,M,P H 4 MINIMUM 8 TO LOWEST BRACKET 6 CC SWITCH DETAIL W/COVER SWEEP INSTALLED AS A PART OF CONDUIT INSTALLATION AA 7 DIRECT BURIED ENG:HLH REV. NO:21 REV. DATE: 12/16/15

184 CABLE TERMINALS 15 kv & Below Single Phase #2 Through 4/ ** Sheet 2 of 3 Stnd. / Stk. No. Description ** B Bracket,Fiberglass, 3 Position Mounting C Switch, Fused, 1A, 15kV @ D Arrester, Lightning, 9kV Arrester, Lightning, 3kV Arrester, Lightning, 1kV E Grounding Unit F Wire, Cu., #4 S.D. Covered Wire, Cu., 1/ S.D. Covered 1 1 G Conduit, Plastic, 2, SCH Conduit, Plastic, 3, SCH H Conduit, 2 SCH Conduit, 3 SCH @ J Bracket, Standoff Bracket, Standoff K Bolt, Double Arming 5/8 x M Strap. Conduit Strap. Conduit N Clamp, PG, 1/ 35 kcmil P Nut, Jam 5/ Q PG* See HLC*W Clamp, Hot line S Clamp, PG, 1/ # T Fuse Sized By Engineer U Bolt, Mach., 5/8 x V Cable, 15kV, # Cable, 15kV, 4/ W Washer, Square, 5/ X Termination, 15kV, #2 Al Termination, 15kV, 4/ 1 1 Y Wire, #6 Cu, S.D. Covered Z Clamp, Hotline, #6 to 2/ AA Shield, Duct, Cable BB Cover Cutout, 1A Fused CC Stirrup Grounding, ½ x DD Cover Conduit OP278 Install Cable Up Pole ENG:HLH REV. NO:21 REV. DATE: 12/16/15

185 CABLE TERMINALS 15 kv & Below Single Phase #2 Through 4/ ** Sheet 3 of 3 NOTES: 1. Keep arrester ground lead as short as possible. 2. On 13 kv terminal poles use 1 kv lightning arrester, Stock # Insert a piece of #2 H.D. Cu for LA and grounding attachments. See note 11 for avian protection requirements. 4. See DCS 1413 for standoff bracket placement and grounding requirements. 5. Some standoff brackets require that one of the nuts on the double arming bolt be replaced with a jam nut. The jam nut should then be inserted into the 5/8 slot on the standoff bracket. If the nut on the double arming bolt will fit into the 5/8 slot on the bracket Do Not Use the jam nut. 6. On the front of the 2 standoff bracket, the following conduits may be mounted: 4 2 conduits, 3 2 1/2 conduits, 3 3 conduits, 3 4 conduits, 2 5 conduits. Various combinations of conduits may also be mounted. On the front of the 12 standoff bracket, the following conduits may be mounted: 2 2 conduits, 2 2 1/2 conduits, 1 3 & 1 2 conduits, 1 3 and 1 2 1/2 conduit, 1 4 conduit, and 1 5 conduit. 7. To prevent damage to direct buried cables, install a cable shield (Stk# ) at the conduit entry and increase the quantity of cable shields shown in the Materials List by Install a conduit cover at the top end of the conduit to prevent cable damage. 9. Use DCS for ground coil application on new pole installation. 1. Always connect the metallic shields of the riser cables to the system neutral with at least a #2 stranded copper wire. Be aware that the bare and/or covered 7 strand #1 copperweld ground wire may look like stranded #2 copper wire. Never substitute the copperweld ground wire for the #2 stranded copper wire when constructing the primary neutral buss. 11. For all of Illinois and locations in Missouri where additional avian protection is needed, omit the piece of #2 bare copper wire and hot line clamp Z. Connect the #6 copper poly covered arrester wire Y directly to the fused switch connector. 12. More than one single phase riser can be ona pole. Generally, installing three to four single phase risers on a pole will require the use of a crossarm. Refer to DCS ** for proper spacing of cutouts. ENG:HLH REV. NO:21 REV. DATE: 12/16/15

186 CABLE TERMINALS 15kV & Below Three Phase #2 Through 4/ ** Sheet 1 of 3 #2 3C #2 1C / 3C /1 1C TO LINE THROUGH POLE OR DEADEND Z 3 11 #2 Cu H.D. FOR LA CONNECTION MOUNTING LIMITED TO 3 AMPS FF To Line To LA 11 AA Use #4 Cu w/ 1A Barrel Use #1/ Cu w/ 2A Barrel Use #1/ Cu w/ 3A Barrel #2 Cu H.D. 3 FOR GROUNDING CONNECTION SWITCH DETAIL W/COVER TO TERMINATOR SWITCH DETAIL C P G Y 2 B A X FF 6 SEE SWITCH DETAIL DO NOT GROUND MOUNTING HARDWARE W 1 GG 12 S F,H,T,D CONDUIT MUST EXTEND A MINIMUM OF 4 ABOVE THE HIGHEST COMMUNICATION ATTACHMENT AND UP TO THE NEUTRAL N RISER TO BE LOCATED ON PROPERTY SIDE OF POLE 8 J 6 6 U SWEEP INSTALLED AS A PART OF CONDUIT INSTALLATION ENG: HLH REV. NO: 17 REV. DATE: 11/24/15 U DIRECT BURIED

Guying - Insulator Dimensional Requirements ** Lightning Protection & Grounding - Grounds

Guying - Insulator Dimensional Requirements ** Lightning Protection & Grounding - Grounds Standard Description 03 12 01 ** Configurations - Single Phase, 4 to 15kV 03 12 05 ** Configurations - Two or Three Phase Tangent or Angle on Wood Crossarm, 4 to 15 kv 03 12 07 ** Configurations - Two

More information

CONFIGURATIONS TABLE OF CONTENTS PHASE LOCATIONS (PREFERRED LOCATIONS) STRUCTURAL ELEMENTS DESIGN LIMITS

CONFIGURATIONS TABLE OF CONTENTS PHASE LOCATIONS (PREFERRED LOCATIONS) STRUCTURAL ELEMENTS DESIGN LIMITS 3 1 Sheet 1 of TLE OF CONTENTS NEUTRL LOCTIONS PHSE LOCTIONS PHSE LOCTIONS (PREFERRED LOCTIONS) STRUCTURL ELEMENTS DESIGN LIMITS NEUTRL 3 1 3 1 1 3 1 3 3 3 1 1 ** NEUTRL TP CONNECTION TO SUTRNSMISSION

More information

CABLE TERMINALS

CABLE TERMINALS 14 00 00 01 Sheet 1 of 1 TABLE OF CONTENTS LOCATION & PLACEMENT OF RISERS ON JOINT USE POLES STANDOFF BRACKET PLACEMENT AND GROUNDING ONE RISER WITH U GUARD, 2, 3, 4, & 5 SPLIT CONDUIT OR SCHEDULE 40 0

More information

WILDLIFE PROTECTION

WILDLIFE PROTECTION 05 00 00 01 TABLE OF CONTENTS GENERAL INFORMATION INSTALLATION OF CRITTER LINE GUARDS INSTALLATION OF TANK MOUNTED LIGHTNING ARRESTER BRACKET GUARDS 25KV & BELOW EXISTING STRUCTURE MODIFICATION 05 00 00

More information

LABOR OPERATIONS

LABOR OPERATIONS 17 00 00 01 TABLE OF CONTENTS RECONDUCTORING 4KV LOOPOVER AND SWITCH POLE RECONDUCTORING CROSSARM OR ARMLESS 1, 2, AND 3 PHASE RECONDUCTORING ANGLE OR DEADEND RECONDUCTORING FLOATING ANGLE RECONDUCTORING

More information

TABLE OF CONTENTS GUY PLACEMENT PERPENDICULAR TO LINE PARALLEL TO LINE GUYING INSULATOR DIMENSIONAL REQUIREMENTS MINIMUM CLEARANCES GUY TO CONDUCTOR

TABLE OF CONTENTS GUY PLACEMENT PERPENDICULAR TO LINE PARALLEL TO LINE GUYING INSULATOR DIMENSIONAL REQUIREMENTS MINIMUM CLEARANCES GUY TO CONDUCTOR 11 00 00 01 TALE OF ONTENTS Sheet 1 of 1 GENERAL GUY PLAEMENT PERPENDIULAR TO LINE PARALLEL TO LINE GUYING INSULATOR DIMENSIONAL REQUIREMENTS MINIMUM LEARANES GUY TO ONDUTOR HART FOR SELETION OF GUY STRAND

More information

METER INSTALLATIONS

METER INSTALLATIONS 25 00 00 01 TALE OF CONTENTS Sheet 1 of 2 SECTION INDEX 25 00 00 01 OUTDOOR POLE MOUNTED PRIAMRY METERING STRUCTURE 25 00 01 01 CUSTOMER OWNED UNMETERED D/D LIGHT INSTALLATION 25 01 05 00 PRIMARY METERING

More information

SECTION 3 - PRIMARY CONSTRUCTION OVERHEAD TABLE OF CONTENTS

SECTION 3 - PRIMARY CONSTRUCTION OVERHEAD TABLE OF CONTENTS 03.00 GENERAL CONSTRUCTION NOTES PRIMARY CONSTRUCTION PRIMARY CONSTRUCTION PIN INSULATOR INSTALLATION 03.00-02 03.00-04 03.00-20 03.02 CONNECTORS AUTOMATIC SPLICE INSTALLATION 03.02-01 INSTALLATION GUIDE

More information

When power interruptions happen.

When power interruptions happen. When power interruptions happen. We know it s never a good time to have your power go out, so we work all year pruning trees and investing in our system to cut down on problems before they start. Outage

More information

AMENDMENT ELECTRIC SERVICE MANUAL 2014

AMENDMENT ELECTRIC SERVICE MANUAL 2014 AMENDMENT (Pages 20,43,50,72,74,,76,78,83,86,99) ELECTRIC SERVICE MANUAL 2014 Effective April 1, 2015 18-7 6.0 SERVICE AND SERVICE ENTRANCES (General), Continued Conductor Sizing It is recommended that

More information

SECTION 8 - SWITCHES AND PROTECTIVE DEVICES TABLE OF CONTENTS

SECTION 8 - SWITCHES AND PROTECTIVE DEVICES TABLE OF CONTENTS 08.00 GENERAL DISTRIBUTION SURGE ARRESTERS 08.00-0 CUTOUTS AND ARRESTERS GENERAL 08.00-03 08.0 CUTOUTS AND ARRESTERS METAL OXIDE ARRESTERS WITH POLYMER HOUSINGS 08.0-0 APPLICATION OF DIRECT CONNECTED ARRESTERS

More information

Item Code Description Unit Qty Total

Item Code Description Unit Qty Total UNDP ELECTRICITY SECTOR NORTHERN GOVERNORATES Phase XI Item Code Description Unit Qty Total 04-02-00001 Service Pole - 6m, 75mm dia GS Pipe 11250 04-02-00002 9m Tubular Steel Poles complete with all Accessories

More information

Customer Requirements Clearance Requirements for Overhead Joint Utility Construction

Customer Requirements Clearance Requirements for Overhead Joint Utility Construction Application This standard establishes the clearances that are required on utility pole structures between electrical supply facilities owned and operated by Tacoma Power and communication facilities owned

More information

SYSTEM PROTECTION - PLATING

SYSTEM PROTECTION - PLATING INTRODUCTION 1. Plates F1 thru F10 supply only the material required for one-phase. Therefore, for threephase construction, you will be required to call for the specified plate three times at that station.

More information

SOUTHWEST LOUISIANA ELECTRIC MEMBERSHIP COORPORATION COMMERCIAL SERVICE REQUIREMENTS

SOUTHWEST LOUISIANA ELECTRIC MEMBERSHIP COORPORATION COMMERCIAL SERVICE REQUIREMENTS SOUTHWEST LOUISIANA ELECTRIC MEMBERSHIP COORPORATION COMMERCIAL SERVICE REQUIREMENTS November 17, 2016 Engineering Service Specifications Table of Contents Commercial Service Requirements SLEMCO Commercial

More information

Index Section 103 Joint Use. General Requirements for Installation of Attachments on Oncor Poles

Index Section 103 Joint Use. General Requirements for Installation of Attachments on Oncor Poles 103 09-17 103 Index Section 103 Joint Use Title Date Number General Requirements for Installation of Attachments on Oncor Poles... 103-100 Supply and Communication Space... 103-105 Communication Lines

More information

SERVICE ATTACHMENT ON A BUILDING WITH BUS DUCT SERVICE ENTRANCE AND INDOOR METERING

SERVICE ATTACHMENT ON A BUILDING WITH BUS DUCT SERVICE ENTRANCE AND INDOOR METERING SERVICE ATTACHMENT ON A BUILDING WITH BUS DUCT SERVICE ENTRANCE AND INDOOR METERING Obtain acceptance and specific details from the local Company office. 1. Service entrance duct (see Note 1). Company

More information

MINIMUM DISTRIBUTION SYSTEM CONCEPTS AND APPLICATIONS. Larry Vogt. Manager, Rates

MINIMUM DISTRIBUTION SYSTEM CONCEPTS AND APPLICATIONS. Larry Vogt. Manager, Rates MINIMUM DISTRIBUTION SYSTEM CONCEPTS AND APPLICATIONS Larry Vogt Manager, Rates Minimum Distribution System What is MDS? MDS is an analysis module of the cost-of-service study in which distribution investment

More information

OUTDOOR LIGHTING

OUTDOOR LIGHTING 15 00 00 01 Sheet 1 of 1 TABLE OF CONTENTS GENERAL INFORMATION HID LAMPS PHOTOCONTROLS LUMINAIRE COMPONENTS HID NEMA HEAD LUMINAIRE COMPONENTS HID HORIZONTAL LUMINAIRE COMPONENTS LED BRACKET MOUNT LUMINAIRES

More information

PART NUMBER POLE DIAMETER RANGE CARTON QTY " to 5" " to 6 3 4" " to 7 3 4" " to 8 3 4" 10

PART NUMBER POLE DIAMETER RANGE CARTON QTY  to 5  to 6 3 4  to 7 3 4  to 8 3 4 10 PH1 Offset Pole Band Bands Single Double Offset Pole Bands are used for dead-ending, guying, and mounting secondary racks on metal poles, pipe masts, or conduit. Each Pole Band Assembly contains two 1

More information

List of materials for 1Km. Of L.T line 1-Ph., 2-Wire AB cable (1 X 25+1X16) sq.mm using 8M X 200 KG. PSC Pole

List of materials for 1Km. Of L.T line 1-Ph., 2-Wire AB cable (1 X 25+1X16) sq.mm using 8M X 200 KG. PSC Pole List of materials for 1Km. Of L.T line 1-Ph., 2-Wire AB cable (1 X 25+1X16) sq.mm using 8M X 200 KG. PSC Pole 1 L.T Stay set Complete Set 5 2 7/12 GI stay wire kg 50 3 Concreting of stay NO 5 4 Stay clamp

More information

Engineering Service Specifications. Commercial Single-Phase Current Transformer Metering Schemes

Engineering Service Specifications. Commercial Single-Phase Current Transformer Metering Schemes Engineering Service Specifications Commercial Single-Phase Current Transformer Metering Schemes Specifications for Commercial Underground Current Transformer Metering Requirements for a Single-Phase Customer

More information

/1-141 ///_=///E ///_=//47/1_=//

/1-141 ///_=///E ///_=//47/1_=// NOTES: 1. Ground wire to be located on same side as neutral conductor and in quadrant opposite climbing space or pole top pin. 2. Staples on ground wire shall be 2'.-0 apart except for a distance of 8'

More information

THE DAYTON POWER AND LIGHT COMPANY Original Sheet No. 15 DPL Building Courthouse Plaza Southwest Dayton, Ohio P.U.C.O. NO. 1

THE DAYTON POWER AND LIGHT COMPANY Original Sheet No. 15 DPL Building Courthouse Plaza Southwest Dayton, Ohio P.U.C.O. NO. 1 THE DAYTON POWER AND LIGHT COMPANY Original Sheet No. 15 SCHEDULE 1 Schedule of fees and charges used for determining sacrifice value, excess height and/or strength and sale costs of poles. Year % Set

More information

GAINESVILLE REGIONAL UTILITIES APPROVED ELECTRIC SYSTEM MATERIALS MANUAL Page 1 ACTIVE MATERIAL INDEXED ALFHABETICALLY. Rev.

GAINESVILLE REGIONAL UTILITIES APPROVED ELECTRIC SYSTEM MATERIALS MANUAL Page 1 ACTIVE MATERIAL INDEXED ALFHABETICALLY. Rev. Page 1 ACTIVE MATERIAL INDEXED ALFHABETICALLY ANCHOR, DROP-IN FOR 1/2" BOLT 18564-7 A-11.00 11/2/2016 ANCHOR, DROP-IN FOR 3/9" BOLT 18549-3 A-11.00 11/2/2016 ANCHOR, NO-WRENCH: 10" X 96" 01558-6 A-5.00

More information

UG FEEDING OH UG FEEDING OH. Electric Distribution Standards I. INTRODUCTION

UG FEEDING OH UG FEEDING OH. Electric Distribution Standards I. INTRODUCTION I. INTRODUCTION Electric Distribution Standards Design, Construction & Material Standards formed a special committee to establish some basic design guidelines for construction alternatives to be used for

More information

Single phase pole mounted. 11kV. Electrical Engineer KEU ID#:

Single phase pole mounted. 11kV. Electrical Engineer KEU ID#: Single phase pole mounted Distribution Transformers 11kV Prepared by: ARY SAIDAHMED SHEKSAEED Electrical Engineer KEU ID#: 4252 Email: ary.sayd@hotmail.com 1 S # Contents Page # 1 Introduction 3 2 Type

More information

For mounting. cutouts, power fuses, arresters, capacitors, terminations, conduit EQUIPMENT MOUNTS

For mounting. cutouts, power fuses, arresters, capacitors, terminations, conduit EQUIPMENT MOUNTS For mounting cutouts, power fuses, arresters, capacitors, terminations, conduit EQUIPMENT Index Introduction.... 1 Typical Installation.... 2 Aluminum Three Phase Cutout & Arrester Mounts.... 3 Aluminum

More information

Standard Compression Dead End for ACSR and ACSS Conductor CAUTION: ACSR Dead Ends Cannot Be Used on ACSS HT Conductor

Standard Compression Dead End for ACSR and ACSS Conductor CAUTION: ACSR Dead Ends Cannot Be Used on ACSS HT Conductor INS-ACA089 Installation Instructions Standard Compression Dead End for ACSR and ACSS Conductor CAUTION: ACSR Dead Ends Cannot Be Used on ACSS HT Conductor 1. Mark the conductor a distance of 3 /4 the length

More information

Easy-On II Terminations

Easy-On II Terminations Features Class 1 (outdoor) termination as defined in IEEE 48 standard. For use on all extruded dielectric cables, concentric neutral, metal tape shielded or wire shielded cables without need for additional

More information

Jumpers & Load Pickup Tools

Jumpers & Load Pickup Tools Jumpers & Load Pickup Tools Catalog 2300 May 2016 Jumpers & Load Pickup Tools 2300 May 2016 Page 2301 All Chance Insulated Jumpers meet ASTM F 2321 Standard Specification. G4758 15kV 5 5 / 8 " G4765 25kV

More information

Customer Substation Manual

Customer Substation Manual Customer Substation Manual Table of Contents Section Page 2 of 81 Description 0 Preface 010.00 General 010.10 Information Required for the Review of New Customer Substations 010.20 New Customer Substation

More information

WPS SERVICE MANUAL. Section Amp and Smaller - Common

WPS SERVICE MANUAL. Section Amp and Smaller - Common Revised 01/2017 Section 2 200 AMP AND SMALLER - COMMON Page 1 of 17 Section 2 200 Amp and Smaller - Common 2-0 General Metering Requirements... 2 2-1 Basic Calculations... 4 2-2 100-200 Amp Single-Phase

More information

Wildlife Power Outage Protection Products

Wildlife Power Outage Protection Products Wildlife Power Outage Protection Products BirdguarD Line www.kaddas.com KADDAS Enterprises Inc. Avian Protection Plan (APP) Your Total Wildlife Outage Protection Solution An Avian Protection Plan is a

More information

Wisconsin Public Utility Institute. June 28, Minimum Distribution Charges. Larry Vogt. Director, Rates Mississippi Power

Wisconsin Public Utility Institute. June 28, Minimum Distribution Charges. Larry Vogt. Director, Rates Mississippi Power Wisconsin Public Utility Institute June 28, 2017 Minimum Distribution Charges Larry Vogt Director, Rates Mississippi Power 1 Costs of Service vs. Cost Recovery Residential Service Example Assuming that

More information

Index. Aluma Form, ALUMA-FORMEQUIPMENT MOUNTS Inc. WORLD S MOST COMPLETE LINE

Index. Aluma Form, ALUMA-FORMEQUIPMENT MOUNTS Inc. WORLD S MOST COMPLETE LINE Aluma Form, Index ALUMA-FORMEQUIPMENT MOUNTS Inc. Introduction.............................. 3 Typical Installation......................... 4 Aluminum Three Phase Cutout & Arrester Mounts..........................

More information

JUMPERS & SWITCHING TOOLS

JUMPERS & SWITCHING TOOLS INSULATED JUMPER SETS 368 INSULATED JUMPER SETS FOR 15 KV, 25KV AND 35 KV Used for bypassing work areas when upgrading lines and when making temporary or emergency repairs Continuous-current ratings for

More information

1100 OVERHEAD TRANSFORMERS

1100 OVERHEAD TRANSFORMERS 00 OVEHEAD TANSFOMES //00 ~ F Pole Type - Transformer Fuse Schedule ~ T Transformer Field Stenciling Code ~ TA Transformer Coding for Material Mgmt System C T,TH Pole Mounted Transformer and Cutout on

More information

BRACKETS, MOUNTS & HARDWARE

BRACKETS, MOUNTS & HARDWARE HIGH VOLTAGE SWITCHGEAR & AUTOMATION EQUIPMENT SECTION 6 Brackets, Mounts & Misc. Hardware CAT. NO: 040930G May, 2008 INERTIA Engineering & Machine Works, INC. Fax: (209) 931-8186 6665 Hardaway Road, Stockton,

More information

AGRICULTURAL UNDERGROUND SERVICE 500 HP OR LESS

AGRICULTURAL UNDERGROUND SERVICE 500 HP OR LESS Prepared by: ABB1 AGRICULTURAL UNDERGROUND SERVICE 500 HP OR LESS 05619 Asset Type: Electric Metering Function: Design and Construction Issued by: Lisseth Villareal (LDV2) Date: 07-31-15 Rev. #10: This

More information

Customer Requirements Pole Attachment Requirements for Telecommunications (non-rf)

Customer Requirements Pole Attachment Requirements for Telecommunications (non-rf) Application This standard establishes the attachment requirements to utility pole structures owned and operated by Tacoma Power and communication facilities owned and operated by others. This standard

More information

Disconnect & ByPass Switches

Disconnect & ByPass Switches Disconnect & ByPass Switches Disconnect & Oil Circuit Recloser Bypass Switches; Regulator & Current Transformer Bypass Switches Electrical Apparatus K-SEC 060 & 090 Contents Type D-73 Distribution Class

More information

S&C Loadbuster Disconnects

S&C Loadbuster Disconnects S&C Loadbuster Disconnects Outdoor Distribution ( kv through 34.5 kv) With these outstanding features... Up to -ampere continuous ratings, 40,000-ampere RMS asymmetrical momentary ratings Designed for

More information

Urgent Support to the Agriculture and Electricity Sector in the Gaza Strip

Urgent Support to the Agriculture and Electricity Sector in the Gaza Strip Project Number: PAL -10-00063805 Project Name: Urgent Support to the Agriculture and Electricity Sector in the Gaza Strip Bill of Quantities Package # 2 LOT 2: Supply of Electrical Materials The contract

More information

CHAPTER V RESIDENTIAL WIRING

CHAPTER V RESIDENTIAL WIRING CHAPTER V RESIDENTIAL WIRING 5.1. THE SERVICE ENTRANCE Buildings and other structures receive the electrical energy through the service entrance. In residential wiring, the electric company supply this

More information

10 Commercial, Industrial, Agricultural Services

10 Commercial, Industrial, Agricultural Services 10 Commercial, Industrial, Agricultural Services This section describes the Power Company requirements for commercial, industrial, and agricultural services. This section covers single phase and three

More information

TEMPORARY ELECTRIC WIRING FOR CARNIVALS, CONVENTIONS, EXHIBITIONS, FAIRS AND SIMILAR USES

TEMPORARY ELECTRIC WIRING FOR CARNIVALS, CONVENTIONS, EXHIBITIONS, FAIRS AND SIMILAR USES INFORMATION BULLETIN / PUBLIC - ELECTRICAL CODE REFERENCE NO.: LAMC 93.0230 Effective: 3-24-69 DOCUMENT NO. P/EC 2002-006 Revised: 11-17-00 Previously Issued As: RGA #7-69 TEMPORARY ELECTRIC WIRING FOR

More information

Polymer Insulators A Better Solution

Polymer Insulators A Better Solution Polymer Insulators A Better Solution October 2016 LET S CONNECT POLYMER INSULATORS Design derived from PLP s many years of worldwide experience and tested to adhere to ANSI C29.5 and ANSI 29.6 insulator

More information

STRAIN LINK STICK ROLLER LINK STICK ADJUSTABLE STRAIN POLES SPIRAL LINK STICK TRANSMISSION TOOLS

STRAIN LINK STICK ROLLER LINK STICK ADJUSTABLE STRAIN POLES SPIRAL LINK STICK TRANSMISSION TOOLS 172 Phone: 800-323-6606 Fax: 847-488-1285 www.hilineco.com STRAIN LINK STICK Used as insulation between rope blocks and a hot line wire grip For deadend structures and running corners Attached to conductor

More information

CONSTRUCTION STANDARD ELECTRIC OPERATIONS ORGANIZATION

CONSTRUCTION STANDARD ELECTRIC OPERATIONS ORGANIZATION Page 1 of 11 R1 ****This Standard Supercedes CE Macros MPR1S, MUR1S, MPR3S & MUR3S and portions of BECo Standards CS2.7-1.1, CS2.7-1.5 & CS2.7-1.7**** PRIMARY URD RISER CONSTRUCTION TABLE OF CONTENTS Page

More information

OVERHEAD SERVICE. Items to consider

OVERHEAD SERVICE. Items to consider OVERHEAD SERVICE Items to consider The maximum length of the service wire from the ComEd pole to the point of attachment on your residence is 150 feet, if practical. Your service wire installation must

More information

Product Specifications for Phase Over Phase GOABS(r)

Product Specifications for Phase Over Phase GOABS(r) 1. General a) This specification covers the design, manufacture, and shipment of phase-over-phase, 1-way, 2-way, 3-way, and 4-way, gang-operated disconnecting switches, both air-break and load-break, for

More information

GAINESVILLE REGIONAL UTILITIES APPROVED ELECTRIC SYSTEM MATERIALS MANUAL Page 1 ACTIVE MATERIAL INDEXED ALFHABETICALLY. Rev.

GAINESVILLE REGIONAL UTILITIES APPROVED ELECTRIC SYSTEM MATERIALS MANUAL Page 1 ACTIVE MATERIAL INDEXED ALFHABETICALLY. Rev. Page 1 ACTIVE MATERIAL INDEXED ALFHABETICALLY ANCHOR, DROP-IN FOR 1/2" BOLT 18564-7 A-11.00 9/12/2011 ANCHOR, DROP-IN FOR 3/9" BOLT 18549-3 A-11.00 9/12/2011 ANCHOR, NO-WRENCH: 10" X 96" 01558-6 A-5.00

More information

RISER POLES RISER POLES. Overhead Electric Distribution Standards INTRODUCTION

RISER POLES RISER POLES. Overhead Electric Distribution Standards INTRODUCTION INTRODUCTION. For proper fuse coordination, refer to the SYSTEM PROTECTION section to select the appropriate fuse for underground risers.. Terminators or Potheads and their mounting brackets are included

More information

Fiberglass Construction Products

Fiberglass Construction Products 12 Fiberglass Construction Products Catalog 12 Page 12-1 Fiberglass Construction Products Standoff Brackets With over 50 years of experience in manufacturing Chance Fiberglass Rod polymer insulation products,

More information

CAT-1 Series 3. Installation Guide. The Valley Group, Inc. 871 Ethan Allen Hwy. Suite 104 Ridgefield, CT 06877

CAT-1 Series 3. Installation Guide. The Valley Group, Inc. 871 Ethan Allen Hwy. Suite 104 Ridgefield, CT 06877 CAT-1 Series 3 Installation Guide The Valley Group, Inc. 871 Ethan Allen Hwy. Suite 104 Ridgefield, CT 06877 (203) 431-0262 (203) 431-0296 FAX tvg@cat-1.com Installation of Load Cells for CAT-1 Systems

More information

URD Mini Pillar Installation Guide. UDS Universal Pillar Installation Guide. Cable to LV Isolators, Crossarm and Cable Detail

URD Mini Pillar Installation Guide. UDS Universal Pillar Installation Guide. Cable to LV Isolators, Crossarm and Cable Detail Part 5 LV Underground Drawing Register Number U8 U9 Description URD Mini Pillar Installation Guide UDS Universal Pillar Installation Guide U10-1 UDS Universal Pillar Double Link Unit Drilling Detail U10-2

More information

JOSLYN. Underground Cable Accessories. Table of Contents. JPT/JIPT Polymer Terminations. ShrinkTite Sealing Kits. Easy-On II Terminations

JOSLYN. Underground Cable Accessories. Table of Contents. JPT/JIPT Polymer Terminations. ShrinkTite Sealing Kits. Easy-On II Terminations Underground Cable Accessories JOSLYN Table of Contents JPT/JIPT Polymer Terminations 15kV, 25kV & 35kV ShrinkTite Sealing Kits 1kV In-Line Splice Sealing Kit Cable Jacket Sealing Kit Easy-On II Terminations

More information

Slack Span Dead-end GENERAL RECOMMENDATIONS NOMENCLATURE (440)

Slack Span Dead-end GENERAL RECOMMENDATIONS NOMENCLATURE (440) NOMENCLATURE Material Helical Leg Section: Aluminum covered steel. An aluminum alloy version is available for corrosive environment. Contact PLP. Crossover Marks: Indicates starting point for application

More information

M-Force three-phase switch

M-Force three-phase switch Switches and Disconnects CA008004EN Supersedes May 2015 COOPER POWER SERIES M-Force three-phase switch Description Eaton's Cooper Power series M-Force switch is a distribution-class, gang-operated, factory

More information

Electrical Components

Electrical Components Table of Contents ELECTRICAL COMPONENTS Electrical Components 3 ELECTRICAL COMPONENTS 1 Electrical Cables.... 3-1 - 3-2 Hitch Ball & Grounding Jumpers.... 3-3 Fuses... 3-4 - 3-6 Fuse Packages... 3-7 Cord

More information

34.00 METERING GENERAL LABELING MULTIPLE METER ENCLOSURES ON A SINGLE PREMISE

34.00 METERING GENERAL LABELING MULTIPLE METER ENCLOSURES ON A SINGLE PREMISE 4. METERING GENERAL LABELING MULTIPLE METER ENCLOSURES ON A SINGLE PREMISE 4.-4 4. SELF-CONTAINED METERING, SINGE-PHASE INSTALLATION DETAILS /4 VOLT SINGLE-PHASE UNDERGROUND RESIDENTIAL SERVICE AND METER

More information

Conductor Protection. results

Conductor Protection. results Conductor Protection results Conductor Protection Index Dampers 607... Vibration Damper 4R Stockbridge...1 Armor Rods AP8... Aluminum Armor Rods...6 APS... alvanized Steel Armor Rods...8 APAS... AluminumClad

More information

OVERHEAD DESIGN MANUAL

OVERHEAD DESIGN MANUAL OVERHEAD DESIGN MANUAL Section 4 Poletop Constructions Approved by: F ZAINI ENERGEX 2018 MANUAL 00302 CONSTRUCTION SELECTION General Notes 1. Constructions should be selected according to: spanning and

More information

SECTION 27 - PAD-MOUNTED TRANSFORMERS TABLE OF CONTENTS

SECTION 27 - PAD-MOUNTED TRANSFORMERS TABLE OF CONTENTS CABLE AND CONDUIT ENTRANCE SINGLE-PHASE PAD-MOUNTED TRANSFORMER INSTALLATION 100 KVA AND LARGER (CONCRETE PADS ONLY) 27.05-01 CABLE AND CONDUIT ENTRANCE SINGLE-PHASE PAD-MOUNTED TRANSFORMER INSTALLATION

More information

OVERHEAD DISTRIBUTION SWITCHES

OVERHEAD DISTRIBUTION SWITCHES HIGH VOLTAGE SWITCHGEAR & AUTOMATION EQUIPMENT SECTION 2 Overhead Distribution Switches CAT. NO: 040930G May, 2008 INERTIA Engineering & Machine Works, INC. Fax: (209) 931-8186 6665 Hardaway Road, Stockton,

More information

PSC Terminations. Features Class 1 (outdoor) termination as defined in IEEE 48 standard. For use on all extruded dielectric cables.

PSC Terminations. Features Class 1 (outdoor) termination as defined in IEEE 48 standard. For use on all extruded dielectric cables. Features Class 1 (outdoor) termination as defined in IEEE 48 standard. For use on all extruded dielectric cables. Sizes are available for all shielded cables in voltage classes from 15kV through 46kV.

More information

DISCONNECT SWITCH REQUIREMENTS FOR DISTRIBUTED GENERATION CUSTOMERS

DISCONNECT SWITCH REQUIREMENTS FOR DISTRIBUTED GENERATION CUSTOMERS Prepared by: SXZO DISCONNECT SWITCH REQUIREENTS FOR DISTRIBUTED GENERATION CUSTOERS 060559 Department: Electric Distribution Section: Design and Construction Approved by: D.Jantz (DWJ7) Date: 8/15/17 Rev.

More information

11. CABLE SPECIFICATIONS 5kV, 15kV, AND 35kV RUBBER OR PLASTIC INSULATED CABLE

11. CABLE SPECIFICATIONS 5kV, 15kV, AND 35kV RUBBER OR PLASTIC INSULATED CABLE 11. CABLE SPECIFICATIONS 5kV, 15kV, AND 35kV RUBBER OR PLASTIC INSULATED CABLE 11.1 GENERAL Only single conductor cables as described in this section are acceptable for connection to PECO Energy Company

More information

Appalachian Power Company Policy No. 2 Cover Up Procedures. Policy Summary:

Appalachian Power Company Policy No. 2 Cover Up Procedures. Policy Summary: Appalachian Power Company Policy No. 2 Cover Up Procedures Policy Summary: A. When a worker is in a position where the worker or a conductive object in the worker s hand can go or reach within the minimum

More information

S&C Loadbuster Disconnect Switches. Outdoor Distribution (14.4 kv through 34.5 kv)

S&C Loadbuster Disconnect Switches. Outdoor Distribution (14.4 kv through 34.5 kv) S&C Loadbuster Disconnect Switches Outdoor Distribution ( kv through 34.5 kv) S&C s Loadbuster Disconnect Switches, when used with S&C s Loadbuster tool, provide the ultimate in distribution live-switching

More information

Catalog 14A January 2013

Catalog 14A January 2013 Catalog 14A January 2013 Page 1 January 2013 Type AR (Automation-Ready) Switch 14.4kV, 25kV or 34.5kV 900 Amperes Continuous/Interrupt Description The Hubbell unitized Type AR switch is a distribution-level,

More information

Bulletin 1494V Variable Depth Disconnect Switch Installation Instructions (Cat 1494V-DS400; -DSX400 - Series D)

Bulletin 1494V Variable Depth Disconnect Switch Installation Instructions (Cat 1494V-DS400; -DSX400 - Series D) Bulletin 494V Variable Depth Disconnect Switch Installation Instructions (Cat 494V-DS400; -DSX400 - Series D) ATTENTION: To prevent electrical shock, disconnect from power source before installing or servicing.

More information

Technical Specification for Pole Mounted Capacitor Rack

Technical Specification for Pole Mounted Capacitor Rack Technical Specification for Pole Mounted Rack Page 1 1. Scope and Function a) Pole mounted capacitor racks shall be installed on a distribution feed as an economical means of applying capacitor units to

More information

ELECTRIC SERVICE RULES UTILITY/CATV SERVICES Issued Jan 2016

ELECTRIC SERVICE RULES UTILITY/CATV SERVICES Issued Jan 2016 UTILITY/CATV SERVICES CHAPTER 9 900. GENERAL A. Alliant Energy receives many requests for electric service from other utilities; telephone, telecommunications companies, cable television, the Department

More information

TYPE BLT DISCONNECT SWITCHES

TYPE BLT DISCONNECT SWITCHES TYPE BLT DISCONNECT SWITCHES OUTDOOR-HOOK OPERATED 8.3KV through 38KV A & A Current Furnished with hooks for loadbreak tool REA/RUS approved S M C O 1 BLT PARALLEL BLADE DISTRIBUTION CLASS DISCONNECT SWITCH

More information

ENTRANCE EQUIPMENT ER D PAGE 1 OF 5

ENTRANCE EQUIPMENT ER D PAGE 1 OF 5 PAGE 1 OF 5 USE: Requirements for entrance equipment. PREVIOUS REVISION 07-01-98 ORIGINATED 03-94 PREVIOUS NUMBER ER 100 (12-01-81) LATEST REVISION: Updated meter socket labeling specification and instrument

More information

WPS SERVICE MANUAL. Section 7 Clearances. 7-1 Basic Electric Clearances - Services Miscellaneous Clearances Antenna Clearances...

WPS SERVICE MANUAL. Section 7 Clearances. 7-1 Basic Electric Clearances - Services Miscellaneous Clearances Antenna Clearances... Revised 03/2016 Section 7 CLEARANCES Page 1 of 9 Section 7 Clearances 7-1 Basic Electric Clearances - Services... 2 7-2 Miscellaneous Clearances... 7 7-3 Antenna Clearances... 9 Revised 03/2016 Section

More information

OVERHEAD DISTRIBUTION SWITCHES

OVERHEAD DISTRIBUTION SWITCHES OVERHEAD DISTRIBUTION SWITCHES 0800 442 182 www.transnet.co.nz CONTENTS LineBOSS 15kV - 35kV Sidebreak GOAB Switch - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4 LineBOSS Selection

More information

NATIONAL POWER INDUSTRIES

NATIONAL POWER INDUSTRIES NSIC - CRISIL RATTING : SE 3 B NSIC - ICRA RATTING : SE 3 B C E MARKED PRODUCT Regd. Office : Administration Office Factory (1) Factory (2) Tele/Fax Mobile E-mail Website (Vyas Group Of Companies) Load

More information

Specification for 11kV and 33kV Overhead Lines of Unearthed Construction on Single and H Type Wood Poles

Specification for 11kV and 33kV Overhead Lines of Unearthed Construction on Single and H Type Wood Poles 1. SCOPE Specification for 11kV and 33kV overhead power lines of unearthed construction employing AAAC conductors, supported on single and H type wood pole supports. 2. ISSUE RECORD This is a Reference

More information

12. ILLUSTRATIONS 12.1 GENERAL

12. ILLUSTRATIONS 12.1 GENERAL 12. ILLUSTRATIONS 12.1 GENERAL Illustrations of typical service equipment and installations are shown in this section as an aid to interpretation of these Electric Service Requirements. The illustrations

More information

BLACKBIRD INSTALLATION SUPPLEMENT

BLACKBIRD INSTALLATION SUPPLEMENT BLACKBIRD INSTALLATION SUPPLEMENT FOR 2003-7 FORD 6.0 LITER DIESEL F-SERIES DUAL ALTERNATOR VERSION 10/07 Blackbird Installation Supplement for Ford 6.0. Liter Dual Alternator Parts included in the 6.0

More information

EXCLUSIVE AUSTRALIAN DISTRIBUTORS

EXCLUSIVE AUSTRALIAN DISTRIBUTORS Helical Fittings EXCLUSIVE AUSTRALIAN DISTRIBUTORS B4/1 Introduction in helical fittings Helical fittings are composed of single helical rods which -according to the respective application - are separate

More information

Type M3 Hookstick Disconnect Switches Up to 38kV 600 or 900 Amp 40kA Momentary

Type M3 Hookstick Disconnect Switches Up to 38kV 600 or 900 Amp 40kA Momentary 14B-2 Type M3 Hookstick Disconnect Switches Up to 38kV 0 or 900 Amp 40kA Momentary Application The Chance Type M3 Disconnect Switch is a single-phase hookstick operated switch. It is for manual switching

More information

Power System Analysis I TRANSMISSION LINE PARAMETERS

Power System Analysis I TRANSMISSION LINE PARAMETERS Power System Analysis I TRANSMISSION LINE PARAMETERS Components of Overhead Lines Transmission Line Parameters An overhead transmission line consists of conductors, insulators, support structures, and,

More information

OVERHEAD CONSTRUCTION MANUAL

OVERHEAD CONSTRUCTION MANUAL OVERHEAD CONSTRUCTION MANUAL Section Materials Quick Reference Approved by: A Smith-de Pere Energex Limited 214 ABN 4 78 849 55 DOCUMENT NUMBER: 492-A4 LAST UPDATE: 27/2/214 APPLE 6/113. 8372 APPLE 6/113.

More information

Mechanical Suspensions Single and Double

Mechanical Suspensions Single and Double Mechanical Suspensions Single and Double Supporting spans of Optical Ground Wire cable through a wide range of line angle changes, the unique design of the lightweight AFL Mechanical Suspension installs

More information

M-Force three-phase switch

M-Force three-phase switch Supersedes K-SEC 926 December 2012 M-Force three-phase switch Description The M-Force switch from Eaton's Cooper Power Systems is a distribution-class, gangoperated, factory unitized three-phase overhead

More information

35-kV Safefront SuperWell Mini-Switch Source Isolated Pad-Mounted Switchgear 50 Amp (Max) Clip-Mounted Current Limiting Fuses

35-kV Safefront SuperWell Mini-Switch Source Isolated Pad-Mounted Switchgear 50 Amp (Max) Clip-Mounted Current Limiting Fuses Page 1 2016 EPMR-35-311S-R2/ESW-CM9 Three Phase Two Ways per Phase 200 Amp 35 kv Class Eaton s CPS LRTPs 50 Amp (Max) 27 kv Clip-Mounted NX Fuse Provisions 21.1/36.6 kv Grounded Wye Max Design, 150 kv

More information

Type L Cutouts. UltraSIL Polymer-Insulated and Porcelain Type L Open Distribution Cutout. Description

Type L Cutouts. UltraSIL Polymer-Insulated and Porcelain Type L Open Distribution Cutout. Description Type L Cutouts UltraSIL Polymer-Insulated and Porcelain Type L Open Distribution Cutout Electrical Apparatus 327-30 Description Cooper Power Systems has set a new standard of excellence for polymer distribution

More information

Armor Rods. Armor Rods NOMENCLATURE GENERAL RECOMMENDATIONS

Armor Rods. Armor Rods NOMENCLATURE GENERAL RECOMMENDATIONS Transmission: Section 1 NOMENCLATURE Single Support and Double Support : Identified by S and D appearing in the length column on the catalog page. Should the maximum distance between tied supports exceed

More information

7 Single Family Service

7 Single Family Service 7 Single Family Service 7. General The location of the service entrance on the Customer s premises is an important consideration. For clearance and location information see section 5 (Clearances). Consult

More information

11. CABLE SPECIFICATIONS 5kV, 15kV, AND 35kV RUBBER OR PLASTIC INSULATED CABLE

11. CABLE SPECIFICATIONS 5kV, 15kV, AND 35kV RUBBER OR PLASTIC INSULATED CABLE 11. CABLE SPECIFICATIONS 5kV, 15kV, AND 35kV RUBBER OR PLASTIC INSULATED CABLE 11.1 GENERAL Only single conductor cables as described in this section are acceptable for connection to PECO Energy Company

More information

HUBBELL Type M3 Hookstick Disconnect Switches Up to 38kV 600 or 900 Amp 40kA Momentary

HUBBELL Type M3 Hookstick Disconnect Switches Up to 38kV 600 or 900 Amp 40kA Momentary Catalog 14B January 2015 HUBBELL Type M3 Hookstick Disconnect Switches Up to 38kV 600 or 900 Amp 40kA Momentary Application The Chance Type M3 Disconnect Switch is a single-phase hookstick operated switch.

More information

Transmission Tools. Catalog 2250 May Transmission Tools Phone: Web: hubbellpowersystems.

Transmission Tools. Catalog 2250 May Transmission Tools Phone: Web: hubbellpowersystems. Transmission Tools Catalog 2250 May 2016 Transmission Tools 2250 May 2016 Page 2251 STRAIN LINK STICK Tested per OSHA & ASTM F711 Used as insulation between rope blocks and a hot line wire grip For deadend

More information

The New 2017 National Electric Safety Code Overview and Significant Changes. Presented by. Mickey Gunter October 28, 2016

The New 2017 National Electric Safety Code Overview and Significant Changes. Presented by. Mickey Gunter October 28, 2016 The New 2017 National Electric Safety Code Overview and Significant Changes Presented by Mickey Gunter October 28, 2016 NESC Technical Subcommittees Subcommittee 1 Coordination, Definitions Subcommittee

More information

Commercial Electric Policy

Commercial Electric Policy Commercial Electric Policy 7/19/16 1 Table of Contents General Information..3 Construction.3 Ownership.4 Multi-Unit/Multi-Service Buildings....4 Secondary Termination Enclosures.4 Meter Bases.5 Temporary

More information

SUBSTATION DESIGN TRAINING

SUBSTATION DESIGN TRAINING 2017 SUBSTATION DESIGN TRAINING ADVANCE ELECTRICAL DESIGN & ENGINEERING INSITUTE (Registered under MSME& An ISO 9001:2008 CERTIFIED) Training Centre: Advance Group of Institutions C-1, Second Floor Near

More information

Specifications. S&C Type XS Fuse Cutouts. Outdoor Distribution (4.16 kv through 25 kv)

Specifications. S&C Type XS Fuse Cutouts. Outdoor Distribution (4.16 kv through 25 kv) Outdoor Distribution (4.16 through 25 ) Specifications Conditions of Sale STANDAD: Seller s standard conditions of sale set forth in Price Sheet 153 apply, except as modified under WAANTY QUALIFICATIONS

More information