Specifications. S&C Type XS Fuse Cutouts. Outdoor Distribution (4.16 kv through 25 kv)
|
|
- Ursula Mathews
- 6 years ago
- Views:
Transcription
1 Outdoor Distribution (4.16 through 25 ) Specifications Conditions of Sale STANDAD: Seller s standard conditions of sale set forth in Price Sheet 153 apply, except as modified under WAANTY QUALIFICATIONS below. SPECIAL TO THIS PODUCT: INCLUSIONS: S&C Type XS Fuse Cutouts are assigned single-value nominal voltage ratings (not dual, slant, or system voltage class ratings) and are applicable, without restriction, on all three-phase systems having system maximum operating voltage (line-to-line) less than or equal to the cutout maximum voltage. Type XS Cutout interrupting ratings have been substantiated by testing performed in accordance with IEEE C ecognizing that under certain fault conditions cutouts can be exposed to voltages in excess of system line-to-neutral voltage faults the cutouts should clear with no reliance on backup devices S&C has tested Type XS Cutouts at full system line-to-line voltage across a wide spectrum of available fault currents using transient-recovery voltages realistically representative of those the cutout will see in actual service. A choice of connector arrangements is available some at an extra charge as listed in the table Specify the connector arrangement desired by adding the appropriate suffix letter to the catalog number of the selected cutout. All S&C Type XS Fuse Cutouts and Disconnects listed are equipped with hooks for use with Loadbuster the S&C Loadbreak Tool. EXCLUSIONS: Overhead pole-top style cutouts do not include fuse links or mounting brackets. Mounting brackets for these cutouts are available, at an extra charge, as listed in the table WAANTY QUALIFICATIONS: The standard warranty contained in seller s standard conditions of sale (as set forth in Price Sheet 153) does not apply to S&C Type XS Fuse Cutouts Outdoor Distribution when installed in conjunction with fuse tubes or disconnect blades of other than S&C manufacture, nor does it apply to S&C fuse tubes and disconnect blades installed in cutouts of other than S&C manufacture. How to Order A Complete Type XS Fuse Cutout 1. Obtain the catalog number of the desired fuse cutout from the table on pages 2 and Select mounting bracket (if desired), connector arrangement (required), and other options (if desired) from the tables Add the indicated suffix letter(s) to the catalog number selected in Step 1, above. How to Order Handling Tools Obtain the catalog number(s) of recommended handling tool(s) from the table efer to Specification Bulletin S&C Type XS Fuse Cutouts are manufactured in accordance with a quality system certified to ISO 9001:2000. Single-shot Overhead Pole-Top Style Type XS Fuse Cutouts are sold in the United States, Canada, and all countries in the Caribbean (excluding countries located on the mainland of South America and Central America) by MacLean Power Systems, Also applicable on through systems for protection of single-phase-to-neutral circuits (lines or transformers) only and grounded-wye connected capacitor banks in solidly grounded-neutral (multigrounded-neutral) systems. For fuse cutouts to be used on a 36- system, contact your nearest S&C Sales Office. November 9, 2015 S&C Electric Company , all rights reserved Specification Bulletin
2 Complete Units Style and Illustration System Voltage, Extra-Heavy-Duty Overhead Pole-Top thru 14.4 Amperes, MS Interrupting, Asym. Leakage Distance to Ground Minimum, Inches (mm) and Connectors)1 Page eference for Dimensional Information ½ (216) 143/4 (375) P (279) (432) 19 (480) P thru (279) (432) 19 (480) P thru (432) 19 (480) P 7 Ultra-Heavy-Duty Overhead Pole-Top thru ½ (216) 143/4 (375) P ½ (216) 143/4 (375) P (279) (432) 19 (480) P (279) (279) thru (432) 19 (480) P (432) 19 (480) P (432) thru (432) 19 (480) P (432) thru (660) 357/16 (900) P 9 suffix letter(s) to catalog number. For example, BD. See table 2 Uses either nonremovable or removable buttonhead fuse links. 3 Uses removable buttonhead fuse links only. Applicable for protection of single-phase-to-neutral circuits (lines or transformers) only, and grounded-wye connected capacitor banks in solidly grounded-neutral (multigrounded-neutral) systems where the leakage distance to ground meets user s requirements. Applicable for protection of single-phase-to-neutral circuits (lines or transformers) only, and grounded-wye connected capacitor banks in solidly grounded-neutral (multigrounded-neutral) systems. For use on a 36- system, contact your nearest S&C Sales Office. One-shot rating, based on replacement of cutout tube only. Approximate fuse-tube length, top of fuse-tube cap to bottom of fuse tube: 14¾ inches (375 mm). Approximate fuse-tube length, top of fuse-tube cap to bottom of fuse tube: 18¼ inches (464 mm). Leakage distance to ground is 26 inches (660 mm) for catalog numbers and , 28.3 inches (720 mm) leakage distance also available, contact your nearest S&C Sales Office. Product discontinued. Meets 170- BIL rating requirement of IEC Publication TABLE CONTINUED 2 S&C Specification Bulletin
3 Complete Units Continued Style and Illustration System Voltage, Amperes, MS Mom., Asym. Leakage Distance to Ground Minimum, Inches (mm) and Connectors)1 Page eference for Dimensional Information Disconnect Overhead Pole- Top 4.16 thru ½ (216) 143/4 (375) P (279) thru (279) (432) thru (432) thru (660) 357/16 (900) P 13 suffix letter(s) to catalog number. For example, BD. See table Applicable where the leakage distance to ground meets user s requirements. For cutouts to be used on 36- system, contact your nearest S&C Sales Office inches (720 mm) leakage distance is also available; contact your nearest S&C Sales Office. Product discontinued. Meets 170- BIL rating requirement of IEC Publication S&C Specification Bulletin
4 Mounting Brackets and Connector Options Item Add Catalog Number Suffix S&C Extended Mounting Bracket for crossarm, pole, or wall mounting of overhead pole-top style cutouts -B NEMA Type B Mounting Bracket for crossarm mounting of overhead pole-top style cutouts -C Item Quantity Accommodating Conductors Size and Material Position Parallel-Groove Connectors Two No. 6 solid (13.3 mm 2 ) through No. 2 stranded (44.4 mm 2 ) copper or aluminum in one groove; No. 2 solid (33.6 mm 2 ) through 250 kc mil (168 mm 2 ) stranded copper or aluminum or 4/0 ACS (161 mm 2 ) in the other groove Standard Orientation -D Eye-Bolt Connectors One No. 8 solid (8.4 mm 2 ) through 250 kc mil (168 mm 2 ) stranded copper or aluminum, or 4/0 ACS (161 mm 2 ) Standard Orientation Lower Connector otated 90 -M -M90 Other Options Item Add Catalog Number Suffix Sea-Coast Design all galvanized steel components and hardware replaced with stainless steel to provide enhanced corrosion resistance in coastal or high contamination environments1 -S 1 Special order. Available only for porcelain insulators. ecommended Handling Tools For use with Type XS Fuse Cutouts Item Catalog Number Station Prong Distribution Prong 4416 Talon Handling Tool 4440 Universal Pole Select to match height of installation. efer to Specification Bulletin S&C Specification Bulletin
5 Mounting Bracket Details TO 4 MAX (68 TO 102 MAX) 3/8 (10) 413/16 (122) 41/8 TO 51/8 MAX (105 TO 130 MAX) 11/8 (29) 17/32 (13.5) SQUAE 43/8 (111) 71/2 41/2 (191) (114) 31/4 (83) 11/16 (17.5) DIA. HOLE 7/16 (11) SQUAE 11/8 (29) SEE DETAIL AT IGHT 11/8 (29) 2 (51) 1 (25) S&C Extended Mounting Bracket ( Suffix -B ) Adjustable from 3 4 to 4 5 ( to ) Crossarm TO 4 MAX (68 TO 102 MAX) 3/8 (10) 21/4 (57) 41/8 TO 51/8 MAX (105 TO 130 MAX) 17/32 (13.5) SQUAE 3/4 (19) 21/4 (57) 71/2 (191) 41/2 (114) 31/4 (83) 11/16 (17.5) DIA. HOLE 7/16 (11) SQUAE SEE DETAIL AT IGHT 7/8 (22) NEMA Type Mounting Bracket ( Suffix -C ) Adjustable from 3 4 to 4 5 ( to ) Crossarm 13/4 (44) S&C Specification Bulletin
6 Extra-Heavy-Duty Overhead Pole-Top Style OPTIONAL MOUNTING BACKET (CATALOG NUMBE SUFFIX -B O -C ). SEE PAGE 4. Q M S 17/32 (13.5) DIA. HOLE X 5/16 (8) T N OPTIONAL PAALLEL-GOOVE CONNECTO (CATALOG NUMBE SUFFIX -D ). SEE PAGE 4. W 20 s and Uses either nonremovable or removable buttonhead fuse links. Amperes, MS Interr., Asym Leakage Distance to Ground, Min., Inches (mm) and Connectors) /2 (216) /4 (375) P (279) suffix letter(s) to catalog number. For example, BD. See table 2 Dimension applies to cutout furnished with optional NEMA Type B Number Suffix -B ), dimension is 53/16 inches (132 mm). 3 Dimension applies to cutout furnished with optional parallel-groove connectors (cutout Suffix -D ). If cutout is furnished with optional eye-bolt connectors (cutout Suffix -M ), dimension is slightly smaller. Dimensions in Inches (mm) M N Q2 S3 T W X4 17 (432) 17 (432) 197/8 201/4 (514) 201/4 (514) 121/2 (318) 121/2 (318) 131/8 (333) 93/4 (248) 93/4 (248) 23/8 (60) 23/8 (60) Net Weight, Lbs. (kg) 13 (5.9) 81/2 (3.9) 151/2 (7.0) 4 Dimension applies to cutout furnished with optional NEMA Type B Mounting Bracket (cutout Suffix -C ). If cutout is furnished Number Suffix -B ), dimension is 11/8 inches (29 mm). 6 S&C Specification Bulletin
7 Extra-Heavy-Duty Overhead Pole-Top Style OPTIONAL MOUNTING BACKET (CATALOG NUMBE SUFFIX -B O -C ). SEE PAGE 4. S Q 17/32 (13.5) DIA. HOLE M X 5/16 (8) T N OPTIONAL PAALLEL-GOOVE CONNECTO (CATALOG NUMBE SUFFIX -D ). SEE PAGE 4. W Uses either nonremovable or removable buttonhead fuse links. Amperes, MS Interr., Asym Leakage Distance to Ground, Min., Inches (mm) and Connectors)1 suffix letter(s) to catalog number. For example, BD. See table 2 Dimension applies to cutout furnished with optional NEMA Type B Number Suffix -B ), dimension is 53/16 inches (132 mm). 3 Dimension applies to cutout furnished with optional parallel-groove connectors (cutout Suffix -D ). If cutout is furnished with optional eye-bolt connectors (cutout Suffix -M ), dimension is slightly smaller (432) Dimensions in Inches (mm) M N Q2 S3 T W X4 197/ (480) P 197/8 131/8 (333) 131/8 (333) Net Weight, Lbs. (kg) 201/2 (9.3) 10 (4.5) 4 Dimension applies to cutout furnished with optional NEMA Type B Number Suffix -B ), dimension is 11/8 inches (29 mm). Applicable for protection of single-phase-to-neutral circuits (lines or transformers) only, and grounded-wye connected capacitor banks in solidly-grounded-neutral (multigrounded-neutral) systems rated 26.4 through 34.5 where leakage distance to ground meets user s requirements. S&C Specification Bulletin
8 Ultra-Heavy-Duty Overhead Pole-Top Style OPTIONAL MOUNTING BACKET (CATALOG NUMBE SUFFIX -B O -C ). SEE PAGE 4. Q M S 17/32 (13.5) DIA. HOLE X 5/16 (8) T N OPTIONAL PAALLEL-GOOVE CONNECTO (CATALOG NUMBE SUFFIX -D ). SEE PAGE 4. W 20 s and Uses removable buttonhead fuse links only. Amperes, MS Interr., Asym Leakage Distance to Ground, Min., Inches (mm) and Connectors) /2 (216) /4 (375) P (279) suffix letter(s) to catalog number. For example, CM. See table 2 Dimension applies to cutout furnished with optional NEMA Type B Number Suffix -B ), dimension is 53/16 inches (132 mm). 3 Dimension applies to cutout furnished with optional parallel-groove connectors (cutout Suffix -D ). If cutout is furnished with optional eye-bolt connectors (cutout Suffix -M ), dimension is slightly smaller. Dimensions in Inches (mm) M N Q2 S3 T W X4 17 (432) 17 (432) 197/8 201/4 (514) 201/4 (514) 121/2 (318) 121/2 (318) 131/8 (333) 93/4 (248) 93/4 (248) 23/8 (60) 23/8 (60) Net Weight, Lbs. (kg) 13 (5.9) 81/2 (3.9) 151/2 (7.0) 4 Dimension applies to cutout furnished with optional NEMA Type B Number Suffix -B ), dimension is 11/8 inches (29 mm). 8 S&C Specification Bulletin
9 Ultra-Heavy-Duty Overhead Pole-Top Style OPTIONAL MOUNTING BACKET (CATALOG NUMBE SUFFIX -B O -C ). SEE PAGE 4. Q M S 17/32 (13.5) DIA. HOLE X 5/16 (8) T N OPTIONAL PAALLEL-GOOVE CONNECTO (CATALOG NUMBE SUFFIX -D ). SEE PAGE 4. W 20 s and Uses removable buttonhead fuse links only. Amperes, MS Interr., Asym Leakage Distance to Ground, Min., Inches (mm) and Connectors) (432) (480) P (660) suffix letter(s) to catalog number. For example, CM. See table 2 Dimension applies to cutout furnished with optional NEMA Type B Number Suffix -B ), dimension is 53/16 inches (132 mm). 3 Dimension applies to cutout furnished with optional parallel-groove connectors (cutout Suffix -D ). If cutout is furnished with optional eye-bolt connectors (cutout Suffix -M ), dimension is slightly smaller. 4 Dimension applies to cutout furnished with optional NEMA Type B Number Suffix -B ), dimension is 11/8 inches (29 mm). Dimensions in Inches (mm) M N Q2 S3 T W X4 197/8 197/8 223/4 (578) /16 (900) P 223/4 (578) 313/8 (797) 313/8 (797) 133/4 (349) 133/4 (349) 133/4 (349) 133/4 (349) 91/2 (241) 91/2 (241) 13 (330) 13 (330) Meets 170 BIL rating requirement of IEC Publication Net Weight, Lbs. (kg) 201/2 (9.3) 10 (4.5) 23 (10.4) 12 (5.5) Approximate fuse-tube length, top of fuse-tube cap to bottom of fuse tube: 143/4 inches (375 mm). Approximate fuse-tube length, top of fuse-tube cap to bottom of fuse tube: 181/4 inches (464 mm). Applicable for protection of single-phase-to-neutral circuits (lines or transformers) only, and grounded-wye connected capacitor banks in solidly-grounded-neutral (multigrounded-neutral) systems rated 26.4 through 34.5 where leakage distance to ground meets user s requirements. S&C Specification Bulletin
10 Ultra-Heavy-Duty Overhead Pole-Top Style Q OPTIONAL MOUNTING BACKET (CATALOG NUMBE SUFFIX -B O -C ). SEE PAGE 4. S M 17/32 (13.5) DIA. HOLE X 5/16 (8) T N OPTIONAL PAALLEL-GOOVE CONNECTO (CATALOG NUMBE SUFFIX -D ). SEE PAGE 4. W 20 s and Uses removable buttonhead fuse links only. Amperes, MS Interr., Asym Leakage Distance to Ground, Min., Inches (mm) and Connectors)1 Dimensions in Inches (mm) Net Weight, Lbs. (kg) /2 (216) /4 (375) P (279) suffix letter(s) to catalog number. For example, CD. See table 2 Dimension applies to cutout furnished with optional NEMA Type B Number Suffix -B ), dimension is 53/16 inches (132 mm). M N Q2 S3 T W X4 17 (432) 17 (432) 197/8 201/4 (514) 201/4 (514) 121/2 (318) 121/2 (318) 131/8 (333) 93/4 (248) 93/4 (248) 23/8 (60) 23/8 (60) 14 (5.9) 91/2 (4.3) 161/2 (7.5) 3 Dimension applies to cutout furnished with optional parallel-groove connectors (cutout Suffix -D ). If cutout is furnished with optional eye-bolt connectors (cutout Suffix -M ), dimension is slightly smaller. 4 Dimension applies to cutout furnished with optional NEMA Type B Number Suffix -B ), dimension is 11/8 inches (29 mm). 10 S&C Specification Bulletin
11 Ultra-Heavy-Duty Overhead Pole-Top Style OPTIONAL MOUNTING BACKET (CATALOG NUMBE SUFFIX -B O -C ). SEE PAGE 4. Q 17/32 (13.5) DIA. HOLE M S X 5/16 (8) T N OPTIONAL PAALLEL-GOOVE CONNECTO (CATALOG NUMBE SUFFIX -D ). SEE PAGE 4. W Uses removable buttonhead fuse links only. Amperes, MS Interr., Asym Leakage Distance to Ground, Min., Inches (mm) suffix letter(s) to catalog number. For example, CD. See table 2 Dimension applies to cutout furnished with optional NEMA Type B Number Suffix -B ), dimension is 53/16 inches (132 mm). and Connectors)1 Dimensions in Inches (mm) Net Weight, Lbs. (kg) (432) M N Q2 S3 T W X4 197/ (480) P 197/8 131/8 (333) 131/8 (333) 2 (9.8) 11 (5.0) 3 Dimension applies to cutout furnished with optional parallel-groove connectors (cutout Suffix -D ). If cutout is furnished with optional eye-bolt connectors (cutout Suffix -M ), dimension is slightly smaller. 4 Dimension applies to cutout furnished with optional NEMA Type B Number Suffix -B ), dimension is 11/8 inches (29 mm). S&C Specification Bulletin
12 Disconnect Overhead Pole-Top Style OPTIONAL MOUNTING BACKET (CATALOG NUMBE SUFFIX -B O -C ). SEE PAGE 4. Q M S 17/32 (13.5) DIA. HOLE X 5/16 (8) T N OPTIONAL PAALLEL-GOOVE CONNECTO (CATALOG NUMBE SUFFIX -D ). SEE PAGE 4. W 20 s and Amperes, MS Short Time Mom., Asym 15-Cycle (Sym.) Leakage Distance to Ground, Min., Inches (mm) and Connectors) /2 (216) /4 (375) P (279) suffix letter(s) to catalog number. For example, BD. See table 2 Dimension applies to cutout furnished with optional NEMA Type B Number Suffix -B ), dimension is 53/16 inches (132 mm). Dimensions in Inches (mm) M N Q2 S3 T W X4 17 (432) 17 (432) /4 (514) 201/4 (514) 121/2 (318) 121/2 (318) 131/8 (333) 93/4 (248) 93/4 (248) 23 8 (60) 23 8 (60) Net Weight, Lbs. (kg) 13 (5.9) 81/2 (5.9) 151/2 (7.0) 3 Dimension applies to cutout furnished with optional parallel-groove connectors (cutout Suffix -D ). If cutout is furnished with optional eye-bolt connectors (cutout Suffix -M ), dimension is slightly smaller. 4 Dimension applies to cutout furnished with optional NEMA Type B Number Suffix -B ), dimension is 11/8 inches (29 mm). 12 S&C Specification Bulletin
13 Disconnect Overhead Pole-Top Style OPTIONAL MOUNTING BACKET (CATALOG NUMBE SUFFIX -B O -C ). SEE PAGE 4. S Q 17/32 (13.5) DIA. HOLE M X 5/16 (8) T N 20 OPTIONAL PAALLEL- GOOVE CONNECTO (CATALOG NUMBE SUFFIX -D ). SEE PAGE 4. W Amperes, MS Short Time Mom., Asym 15-Cycle (Sym.) Leakage Distance to Ground, Min., Inches (mm) and Connectors)1 suffix letter(s) to catalog number. For example, BD. See table 2 Dimension applies to cutout furnished with optional NEMA Type B Number Suffix -B ), dimension is 53/16 inches (132 mm) (660) Dimensions in Inches (mm) M N Q2 S3 T W X4 223/4 (578) /16 (900) P 223/4 (578) 313/8 (797) 313/8 (797) 133/4 (349) 133/4 (349) 91/2 (241) 91/2 (241) 13 (330) 13 (330) 3 Dimension applies to cutout furnished with optional parallel-groove connectors (cutout Suffix -D ). If cutout is furnished with optional eye-bolt connectors (cutout Suffix -M ), dimension is slightly smaller. 4 Dimension applies to cutout furnished with optional NEMA Type B Number Suffix -B ), dimension is 11/8 inches (29 mm). Meets 170- BIL rating requirement of IEC Publication Net Weight, Lbs. (kg) 23 (10.4) 12 (5.5) S&C Specification Bulletin
14 Parts for Type XS Cutout Item Basic Catalog Number Presently ated,, Nom.1 Previously ated,, Nom.2 Leakage Distance to Ground, Minimum, Inches (mm) Approx. Fuse Tube Length,3 Inches (mm) Amperes, Cont. and Connectors)4 Overhead Pole- Top Cutout, less Fuse Tube Extra-Heavy- Duty Fuse Tube, including cap Ultra-Heavy- Duty Fuse Tube, including cap and arc-shortening rod Spare Disconnect Blade , 7.2/ , 14.4/ , 14.4/25 81/2 (216) 143/4 (375) 111/4 (286) P 11 (279) 143/4(375) (432) 19 (480) 143/4 (375) P (432) 181/4 (464) (660) 357/16 (900) 181/4 (464) P / /2 (216) 14¾ (375) 111/4 (286) (279) 17 (432) 19 (480) 143/4 (375) / /2 (216) 14¾ (375) 111/4 (286) / (279) 17 (432) 17 (432) 26 (660) 19 (480) (900) 143/4 (375) /4 (464) /2 (216) 14¾ (375) 111/4 (286) (279) 17 (432) 19 (480) 143/4 (375) / /2 (216) 14¾ (375) 111/4 (286) /25 11 (279) 143/4 (375) (432) 26 (660) 1 Cutouts having catalog number supplement -11, -10, -9, 8, or -7. For example, BD. 2 Cutouts having catalog number supplement -6 or lower. For example, BD. 3 From top of fuse-tube cap to bottom of fuse tube (900) 181/4 (464) Specify mounting bracket, if desired, and connector option by adding suffix letter(s) to catalog number. For example, BD. See table Product discontinued. 14 S&C Specification Bulletin
15
16
Specifications. S&C Power Fuses Types SM- 4, SM-5, SMD-20, and SMD-40 Outdoor Distribution (4.16 kv through 34.5 kv)
S&C Power Fuses Types SM- 4, SM-5, SMD-0, and SMD-40 Outdoor Distribution (4.16 kv through kv) For use with SM Refill Units or SMU Fuse Units Specifications Conditions of Sale STANDARD: The seller s standard
More informationwww. ElectricalPartManuals. com SPECIFICATIONS Page 1 of 24 March 24, 2003
Types SM-4, SM-5, SMD-20, and SMD-40 Outdoor Distribution (4.16 kv through kv) Conditions of Sale STANDARD: Seller s standard conditions of sale set forth in Price Sheet apply, except as modified under
More informationSpecifications. S&C Alduti-Rupter Switchesa Indoor Distribution (4.8 kv through 34.5 kv) Conditions of Sale SPECIAL TO THIS PRODUCT: How to Order
S&C Alduti-Rupter Switchesa Indoor Distribution ( kv through kv) Specifications Conditions of Sale STANDARD: Seller s standard conditions of sale set forth in Price Sheet 0 apply. SPECIAL TO THIS PRODUCT:
More informationSpecif ications. Minimum Surge Arrester Rating, kv
&C Fault amer Fuse Limiter Outdoor Distribution ( kv through kv) For Overhead Pole-op ransformers pecif ications Conditions of ale ADAD: eller s standard conditions of sale set forth in Price heet 0 apply.
More informationSpecifications. S&C Alduti-Rupter Switches with Power Fuses Outdoor Distribution (14.4 kv through 46 kv)
Outdoor Distribution (4.4 kv through 46 kv) Specifications Conditions of Sale STANDARD: Seller s standard conditions of sale set forth in Price Sheet 50 apply, except as modified under WARRANTY QUALIFICATIONS
More informationSPECIFICATIONS. S&C Alduti-Rupter Switches with Power Fusesa SPECIFICATION BULLETIN Indoor Distribution (4.8 kv and 13.
S&C Alduti-Rupter Switches with Power Fusesa SPECIFICATIONS Conditions of Sale STANDARD: Seller s standard conditions of sale set forth in Price Sheet 150 apply, except as modified under WARRANTY QUALIFICATIONS
More informationT YPE MZ DISTRIBUTION S TANDARD CUTOUT
T YPE MZ DISTRIBUTION S TANDARD CUTOUT Page 1 of 7 The Fuse Cutout type MZ was developed to operate in overhead distribution systems rated at 15, 27 and 38 kv grounded systems with 100 or 200 A nominal
More informationSpecifications. S&C Power Fuses Types SM and SMLa. For use with SM Refill Units or SMU Fuse Units. Indoor Distribution (4.16 kv through 34.
S&C Power Fuses s SM and SMLa Indoor Distribution (4.16 through 34. ) For use with SM Refill Units or SMU Fuse Units Specifications Conditions of Sale STANDARD: Seller s standard conditions of sale set
More informationS&C Type XS Fuse Cutouts
S&C Type XS Fuse Cutouts Outdoor Distribution (4.16 kv through 25 kv) S&C ELECTRIC COMPANY Specialists in Electric Power Switching and Protection Descriptive Bulletin 351-30 August 25, 2003 Supersedes
More informationS&C Type XS Fuse Cutouts
S&C Type XS Fuse Cutouts Outdoor Distribution 4.16 kv through 25 kv Application An Unexcelled Cutout S&C Type XS Fuse Cutouts, when fused with S&C Positrol Fuse Links provide full-fault-spectrum protection
More informationS&C TripSaver II. Cutout-Mounted Recloser. For enhanced lateral circuit protection at 15 kv and 25 kv
TripSaver II Cutout-Mounted Recloser For enhanced lateral circuit protection at 15 kv and 25 kv Introducing s new TripSaver II Cutout-Mounted Recloser: A better solution for overhead lateral circuit protection
More informationS&C Loadbuster Disconnect Switches. Outdoor Distribution (14.4 kv through 34.5 kv)
S&C Loadbuster Disconnect Switches Outdoor Distribution ( kv through 34.5 kv) S&C s Loadbuster Disconnect Switches, when used with S&C s Loadbuster tool, provide the ultimate in distribution live-switching
More informationS&C Recloser Bypass Disconnects
S&C Recloser Bypass Disconnects Outdoor Distribution (14.4 kv through 34.5 kv) Application S&C Recloser Bypass Disconnects are station-type devices used to bypass and isolate automatic circuit reclosers
More informationT HREE-SHOT TYPE MZR F USE CUTOUT
T HREE-SHOT TYPE MZR F USE CUTOUT Page 1 of 7 D ESCRIPTION It is known that about 90% of the defects that occur in an air distribution system, are of a transient origin, i.e., are transient faults which
More informationS&C Loadbuster Disconnects
S&C Loadbuster Disconnects Outdoor Distribution ( kv through 34.5 kv) With these outstanding features... Up to -ampere continuous ratings, 40,000-ampere RMS asymmetrical momentary ratings Designed for
More informationSPECIFICATION BULLETIN
SPECIFICATIONS Conditions of Sale STANDARD: Seller s standard conditions of sale set forth in Price Sheet 150 apply, except as modified under WARRANTY QUALIFICATIONS on page 3. SPECIAL TO THIS PRODUCT:
More informationSpecifications. S&C Omni-Rupter Switches Outdoor Distribution (14.4 kv and 25 kv) Conditions of Sale
S&C Omni-Rupter Switches Outdoor istribution (14.4 kv and 5 kv) Specifications Conditions of Sale STNR: Seller s standard conditions of sale as set forth in Price Sheet apply. SPECIL TO THIS PROUCT: INCLUSIONS:
More informationDisconnect & ByPass Switches
Disconnect & ByPass Switches Disconnect & Oil Circuit Recloser Bypass Switches; Regulator & Current Transformer Bypass Switches Electrical Apparatus K-SEC 060 & 090 Contents Type D-73 Distribution Class
More informationCutouts (Standard, Linkbreak, Loadbreak) and Cutout-Arrester Combinations. Catalog 10A January 2014
10A Type C PORCELAIN Cutouts (Standard, Linkbreak, Loadbreak) and Cutout-Arrester Combinations Catalog 10A Page 1 Type C Cutouts LINKBREAK cutout, pages 8-10 LOADBREAK cutout with Arc-Chute interrupter,
More informationUltraSIL polymer-insulated and porcelain loadbreak Type LB open distribution cutout
Fusing Equipment Catalog Data CA132035EN Supersedes November 2015 COOPER POWER SERIES UltraSIL polymer-insulated and porcelain loadbreak Type LB open distribution cutout Description Eaton has set a standard
More informationType L Cutouts. UltraSIL Polymer-Insulated and Porcelain Type L Open Distribution Cutout. Description
Type L Cutouts UltraSIL Polymer-Insulated and Porcelain Type L Open Distribution Cutout Electrical Apparatus 327-30 Description Cooper Power Systems has set a new standard of excellence for polymer distribution
More informationCutouts (Standard, Linkbreak, Loadbreak) and Cutout-Arrester Combinations. Catalog 10AA March 2013
10AA Type C-Polymer Cutouts (Standard, Linkbreak, Loadbreak) and Cutout-Arrester Combinations Catalog 10AA Page 10AA-1 Quality Construction Efficient Current Transfer The Type C-Polymer cutout has an all
More informationSpecifications. S&C Mini-Rupter Switches Indoor Distribution (4.16 kv through 25 kv) Manually Operated Styles
Indoor Distribution (4.16 kv through 25 kv) Manually Operated Styles Specifications Conditions of Sale STANDARD: Seller s standard conditions of sale set forth in Price Sheet 150 apply, except as modified
More informationCutouts (Standard, Linkbreak, Loadbreak) and Cutout-Arrester Combinations. Catalog 10A October 2015
10A Type C PORCELAIN Cutouts (Standard, Linkbreak, Loadbreak) and Cutout-Arrester Combinations Catalog 10A Page 1 Type C Cutouts LINKBREAK cutout, pages 8-10 LOADBREAK cutout with Arc-Chute interrupter,
More informationWestinghouse Electric Corporation Distribution Apparatus Division Bloomington, Indiana 47401
February 26, 1976 Supersedes PL 38-640 dated October 15,1974 Pages 1-8 Prices effective April 29, 1974 Subject to change without notice Selling Policy 38-000 Mailed to E, D, C/1991, 2430/ PL Standard Bill
More informationCutouts (Standard, Linkbreak, Loadbreak) and Cutout-Arrester Combinations. Catalog 10AA August 2015
10AA Type C-POLYMER Cutouts (Standard, Linkbreak, Loadbreak) and Cutout-Arrester Combinations Catalog 10AA Page 10AA-1 Quality Construction Efficient Current Transfer The Type C-Polymer cutout has an all
More informationS&C Fault Tamer Fuse Limiter. Outdoor Distribution (15 kv through 25 kv)
S&C Fault Tamer Fuse Limiter Outdoor Distribution (5 kv through 25 kv) Introducing S&C s new generation of pole-top transformer protection... Application Although the S&C Fault Tamer Fuse Limiter handles
More informationOutdoor Distribution (15 kv through 25 kv) S&C Fault Tamer Fuse Limiter
Outdoor Distribution (5 kv through 25 kv) S&C Fault Tamer Fuse Limiter Introducing S&C s new generation of pole-top transformer protection... Application Although the S&C Fault Tamer Fuse Limiter handles
More informationType M3 Hookstick Disconnect Switches Up to 38kV 600 or 900 Amp 40kA Momentary
14B-2 Type M3 Hookstick Disconnect Switches Up to 38kV 0 or 900 Amp 40kA Momentary Application The Chance Type M3 Disconnect Switch is a single-phase hookstick operated switch. It is for manual switching
More informationCutouts (Standard, Linkbreak & Loadbreak) and Cutout-Arrester Combinations U.S. Patent 4,546,341; 6,392,526
Cutouts (Standard, Linkbreak & Loadbreak) and Cutout-Arrester Combinations U.S. Patent 4,546,341; 6,392,526 Section 10A 10A-1 Warranty - Material Hubbell Power Systems, Inc. warrants all products sold
More informationTYPE BLT DISCONNECT SWITCHES
TYPE BLT DISCONNECT SWITCHES OUTDOOR-HOOK OPERATED 8.3KV through 38KV A & A Current Furnished with hooks for loadbreak tool REA/RUS approved S M C O 1 BLT PARALLEL BLADE DISTRIBUTION CLASS DISCONNECT SWITCH
More informationPSC Terminations. Features Class 1 (outdoor) termination as defined in IEEE 48 standard. For use on all extruded dielectric cables.
Features Class 1 (outdoor) termination as defined in IEEE 48 standard. For use on all extruded dielectric cables. Sizes are available for all shielded cables in voltage classes from 15kV through 46kV.
More informationPRECISE HIGH VOLTAGE DISTRIBUTION FUSE CUTOUT
PRECISE HIGH VOLTAGE DISTRIBUTION FUSE CUTOUT COS 38kV 100A 8kA asym. Type PGC Parallel groove terminal bronze with tin plated NEMA Bracket type B Upper contact copper with silver plated Cap - Cast bronze
More informationHUBBELL Type M3 Hookstick Disconnect Switches Up to 38kV 600 or 900 Amp 40kA Momentary
Catalog 14B January 2015 HUBBELL Type M3 Hookstick Disconnect Switches Up to 38kV 600 or 900 Amp 40kA Momentary Application The Chance Type M3 Disconnect Switch is a single-phase hookstick operated switch.
More informationFigure 1. HX cutout fuseholders.
Fusing Equipment Kearney Open Distribution Cutout - Type HX Electrical Apparatus K-SEC 010 GENERAL Application Versatility Cooper Power Systems Kearney HX cutouts can be quickly and economically adapted
More informationNOTE: Because Hubbell has a policy of continuous product improvement, we reserve the right to change design and specifications without notice.
CUTOUTS (Standard, Linkbreak & Loadbreak) and CUTOUT-ARRESTER COMBINATIONS Warranty - Material Hubbell Power Systems, Inc. warrants all products sold by it to be merchantable (as such term is defined in
More informationFigure 1. HX cutout fuseholders. Positive Interruption
Fusing Equipment Kearney Open Distribution Cutout - Type HX Electrical Apparatus 327-10 general Application Versatility Cooper Power Systems Kearney HX cutouts can be quickly and economically adapted to
More informationInstallation and Operation
S&C Three-Shot Type XS Fuse Cutout Outdoor Distribution (4.16 kv through 15 kv) Installation and Operation Table of Contents Section Page Section Page Introduction Qualified Persons... 2 Read this Instruction
More informationSpecif ications. S&C Positrol Fuse Links. Outdoor Distribution
S&C Positrol Fuse Links Outdoor Distribution Specif ications Conditions of Sale STANDARD: Seller s standard conditions of sale set forth in Price Sheet 150 apply. SPECIAL TO THIS PRODUCT: SPECIFICATION
More informationTechnical Specification for Pole Mounted Capacitor Rack
Technical Specification for Pole Mounted Rack Page 1 1. Scope and Function a) Pole mounted capacitor racks shall be installed on a distribution feed as an economical means of applying capacitor units to
More informationSpecifications. S&C Manual PMH Pad-Mounted Gear Outdoor Distribution (14.4 kv and 25 kv)
Outdoor Distribution ( kv and kv) Specifications Conditions of Sale STANDARD: Seller s standard conditions of sale set forth in Price Sheet 150 apply, except as modified under WAR- RANTY QUALIFICATIONS
More informationS&C Mini-Rupter Switches Application The Standard Mounting Arrangement Scheme for S&C Mini-Rupter Switches Typical ED, reduced from full 11 size.
S&C Mini-Rupter es Indoor Distribution (4.16 kv through 25 kv) Selecting Standard Mounting Arrangements for Manually Operated Styles Application The Standard Mounting Arrangement Scheme for S&C Mini-Rupter
More informationType ICX Outdoor open type cutout
Distribution cutouts Type IC Outdoor open type cutout Product features 7.8 kv, 15 kv, 15/27 kv, 27 kv, or 38 kv on 100 A 7.8 kv, 15 kv, and 15/27 kv only on 200 A 110, 125, 150, 170, or 180 kv BIL 180
More informationS&C Manual PME Pad-Mounted Gear
S&C Manual PME Pad-Mounted Gear Outdoor Distribution,. kv and 5 kv S&C Manual PME Pad-Mounted Gear... Featuring Elbow-Connected Encased Components. S&C Manual PME Pad-Mounted Gear brings in-air insulation,
More informationTYPE V CENTER BREAK SWITCH
TYPE V CENTER BREAK SWITCH 3-PHASE, GROUP-OPERATED (SUBSTATION AND TRANSMISSION APPLICATIONS) *Available in Copper Horizontal upright, vertical or underhung mounting 15KV through 230KV 600A through 4000A
More informationPOWER SYSTEMS, INC. CUTOUTS (Standard, Linkbreak & Loadbreak) and CUTOUT-ARRESTER COMBINATIONS
CUTOUTS (Standard, Linkbreak & Loadbreak) and CUTOUT-ARRESTER COMBITIONS Warranty - Material Chance warrants all products sold by it to be merchantable (as such term is defined in the Uniform Coercial
More informationCatalog 14A January 2013
Catalog 14A January 2013 Page 1 January 2013 Type AR (Automation-Ready) Switch 14.4kV, 25kV or 34.5kV 900 Amperes Continuous/Interrupt Description The Hubbell unitized Type AR switch is a distribution-level,
More informationInstallation. Loadbuster The S&C Loadbreak Tool Outdoor Distribution (14.4 kv through 34.5 kv) Table of Contents. Instruction Sheet
Loadbuster The S&C Loadbreak Tool Outdoor Distribution (14.4 kv through 34.5 kv) Installation Table of Contents Section Page Section Page Introduction Qualified Persons... 2 Read this Instruction Sheet....
More informationSURGE DURABILITY AND IMPROVED TRANSFORMER PROTECTION
Fusing Equipment Tandem ELF Current-Limiting Dropout Fuse Electrical pparatus 240-67 GENERL The Cooper Power Systems Tandem ELF current-limiting fuse is designed for transformer protection. The Tandem
More informationTechnical Specification For Outdoor Substation Harmonic Filter Banks
Technical Specification For Outdoor Substation Harmonic Filter Banks One of Three 5th, 11th & 23rd, 34.5 kv, Rated Harmonic Filter Assemblies Provided for a Central Venezuela Heavy Oil Production Field
More informationTYPE PSI/II PADMOUNT SWITCHGEAR 15KV 25KV
Cutler Hammer SECTION PB-1A-110 PAGE 1 Replaces April, 1996 TYPE PSI/II PADMOUNT SWITCHGEAR 15KV 25KV The PSI/II Padmount is the second generation of switchgear in the PSI switchgear family. The PSI/II
More informationElectronic Resettable Sectionalizer
POWER SYSTEMS, INC. Protected by U.S. Patents No. 5,612,661; 4,935,715; DES. 278,331 and other patents pending Warranty - Material Hubbell Power Systems, Inc. warrants all products sold by it to be merchantable
More informationK-Limiter high ampere Companion II fuse
Fusing Equipment Catalog Data CA132059EN Supersedes February 2016 COOPER POWER SERIES K-Limiter high ampere Companion II fuse General Eaton designs its Cooper Power series K-Limiter fuse to be conveniently
More informationشركة كهرباء محافظة القدس المساهمة المحدودة
Our Ref: Date: Messrs. Dear Sir, Tender 22/2017 (re-bidding) 11& 33Kv Fuse Cutouts and Links You are kindly requested to bid for supply and delivery (DDP) for the medium voltage overhead line accessories
More informationQ pole Pole Mounted Capacitor System
Q pole Pole Mounted Capacitor System Introduction The ABB Qpole pole mount capacitor system is an economical solution for shunt reactive compensation on overhead distribution networks. The Qpole is suitable
More informationSpecifications. S&C Source-Transfer PMH Pad-Mounted Gear Outdoor Distribution (14.4 kv and 25 kv) With Micro-AT Control. Conditions of Sale
Outdoor Distribution ( kv and kv) With Micro-AT Control Specifications Conditions of Sale STANDARD: Seller s standard conditions of sale set forth in Price Sheet 150 apply, except as modified under WAR-
More informationOVERHEAD SERVICE. Items to consider
OVERHEAD SERVICE Items to consider The maximum length of the service wire from the ComEd pole to the point of attachment on your residence is 150 feet, if practical. Your service wire installation must
More informationVersaRupter 5-38 kv Load Interrupter Switch. Technical Guide
VersaRupter 5-38 kv Load Interrupter Switch Technical Guide NOTICE Components in this catalog are intended for use by switchgear assemblers engaged in original equipment manufacturing. All sales are subject
More informationJUMPERS & SWITCHING TOOLS
INSULATED JUMPER SETS 368 INSULATED JUMPER SETS FOR 15 KV, 25KV AND 35 KV Used for bypassing work areas when upgrading lines and when making temporary or emergency repairs Continuous-current ratings for
More information15-kV Wall-Mount Switchgear Three-Phase Indoor/Outdoor 600 Amp S&C Mini-Rupter Switch
Page 1 2015 Kinked roof prevents standing moisture Glass reinforced barriers meet NEMA GPO-3 Standards 0.625" diameter copper ground bar Elliott air-insulated bushings accept IEEE Standard inserts and
More informationUnderground Distribution Switchgear
Underground Distribution Switchgear Functional Specification Guide Functional Specification for 15 kv, 25 kv, or 35 kv Underground Distribution Switchgear 1. Scope 1.1. This specification applies to three-phase,
More informationA. Three-phase, oil filled self-cooled, padmounted transformers are installed outdoors on pads in the EWEB distribution system.
1. APPLICATION A. Three-phase, oil filled self-cooled, padmounted transformers are installed outdoors on pads in the EWEB distribution system. 2. REFERENCE STANDARDS A. The transformers supplied shall
More information3.0OVERHEAD TRANSMISSION SWITCHES
HIGH VOLTAGE SWITCHGEAR & AUTOMATION EQUIPMENT SECTION 3 Overhead Transmission Switches CAT. NO: 040930G May, 2008 INERTIA Engineering & Machine Works, INC. Fax: (209) 931-8186 6665 Hardaway Road, Stockton,
More informationM-Force three-phase switch
Supersedes K-SEC 926 December 2012 M-Force three-phase switch Description The M-Force switch from Eaton's Cooper Power Systems is a distribution-class, gangoperated, factory unitized three-phase overhead
More informationM-Force three-phase switch
Switches and Disconnects CA008004EN Supersedes May 2015 COOPER POWER SERIES M-Force three-phase switch Description Eaton's Cooper Power series M-Force switch is a distribution-class, gang-operated, factory
More information34-SDMS-01 SPECIFICATIONS FOR
SPECIFICATIONS FOR M V DROPOUT FUSE CUT OUTS This specification is property of SEC and subject to change or modification without any notice CONTENTS C l a u s e s: Page No. 1- SCOPE 3 2- CROSS REFERENCES
More information43-SDMS-01 SPECIFICATIONS FOR
SPECIFICATIONS FOR MV SHUNT POWER CAPACITOR BANK UP TO 36 KV This specification is property of SEC and subject to change or modification without any notice CONTENTS Clause Description Page 1.0 SCOPE 3
More information35-kV Safefront 200 Amp SuperWell Primary Capacitor Station Pad-Mounted Outdoor
Page 1 2016 EPM-PCS-35-320P-R2/ESW-GCM6-2S-SA Three Phase Two Ways per Phase 200 Amp 35 kv Class Eaton's CPS LRTPs 35 kv Elliott Air-Insulated SuperWell Bushings 21.1/36.6 kv Grounded Wye Max Design, 150
More informationTHE DAYTON POWER AND LIGHT COMPANY Original Sheet No. 15 DPL Building Courthouse Plaza Southwest Dayton, Ohio P.U.C.O. NO. 1
THE DAYTON POWER AND LIGHT COMPANY Original Sheet No. 15 SCHEDULE 1 Schedule of fees and charges used for determining sacrifice value, excess height and/or strength and sale costs of poles. Year % Set
More informationSERVICE ATTACHMENT ON A BUILDING WITH BUS DUCT SERVICE ENTRANCE AND INDOOR METERING
SERVICE ATTACHMENT ON A BUILDING WITH BUS DUCT SERVICE ENTRANCE AND INDOOR METERING Obtain acceptance and specific details from the local Company office. 1. Service entrance duct (see Note 1). Company
More informationSpecifications. S&C Switch Operators Types AS-1A and AS-10a. Conditions of Sale
a Specifications Conditions of Sale STANDARD: Seller s standard conditions of sale set forth in Price Sheet 150 apply. SPECIAL TO THIS PRODUCT: INCLUSIONS: S&C Switch Operators Types AS-1A and AS-10 are
More informationCOOPER POWER SERIES. UltraSIL polymer-insulated D-73P disconnect switches installation instructions. Switches MN008004EN
Switches MN008004EN Effective April 2016 Supersedes S328-10-1 June 2013 COOPER POWER SERIES UltraSIL polymer-insulated D-73P disconnect switches installation instructions DISCLAIMER OF WARRANTIES AND LIMITATION
More information43-SDMS-04 REV. 00 SPECIFICATIONS FOR
43-SDMS-04 REV. 00 SPECIFICATIONS FOR SHUNT CAPACITOR BANK 13.8 kv THROUGH 69 kv FOR PRIMARY DISTRIBUTION SUBSTATIONS This specification is property of SEC and subject to change or modification without
More informationD-73P disconnect and bypass switches
Switches atalog Data 008005EN Supersedes pril 2016 OOPER POWER SERIES D-73P disconnect and bypass switches ontents Description Page D-73P disconnect switch....2 D-73P3 bypass switch....5 D-73P-D cutout
More informationEasy-On II Terminations
Features Class 1 (outdoor) termination as defined in IEEE 48 standard. For use on all extruded dielectric cables, concentric neutral, metal tape shielded or wire shielded cables without need for additional
More informationSurge Arresters. Surge Arrester/Type L Fuse Cutout Combination. Description. Construction. Connectors/Brackets
Surge Arresters Surge Arrester/Type L use ombination Electrical Apparatus 235-26 escription ooper Power Systems surge arrester/type L interchangeable fuse cutout combinations are available in a wide variety
More informationOptima Distribution Class (PDV) and Riser Pole (PVR) Surge Arresters
Section 1-1 1 Optima Distribution Class (PDV) and Riser Pole (PVR) Surge Arresters NOTE: Because Hubbell has a policy of continuous product improvement, we reserve the right to change design and specifications
More informationType ICX Interchangeable Cutout kv Outdoor Distribution Cutout Product Bulletin 1VAG DB
Type ICX Interchangeable Cutout 15-38 kv Outdoor Distribution Cutout Product Bulletin 1VAG271201-DB Product Features 15, 27, or 38 kv 110, 125, 150, 180, or 200 kv BIL 100 A, 200 A Fused 300 A Disconnect
More informationOVERHEAD DISTRIBUTION SWITCHES
OVERHEAD DISTRIBUTION SWITCHES 0800 442 182 www.transnet.co.nz CONTENTS LineBOSS 15kV - 35kV Sidebreak GOAB Switch - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4 LineBOSS Selection
More informationCopper Double Break Switch
Bulletin DB-104DB09 Type DB-C Copper Double Break Switch 7.2 kv - 69 kv 600 A. - 2000 A. 14000 Rt. 993, Trafford, PA 15085 (724) 864-4177 FAX (724) 864-9040 E-mail: sales@cleavelandprice.com Type DB-C
More information15-kV Safefront 200 Amp Primary Capacitor Station Pad-Mounted Outdoor
Page 1 2015 Heavy-duty 11-gauge steel enclosure is all-welded construction for long life Clear polycarbonate removable safety barrier separates upper and lower compartment (supplied only with internally
More informationMolded Current-Limiting Fuse
Molded Current-Limiting provide fullrange fault current protection using specially designed fuse elements, rated through 23kV line to ground and 50kA interrupting current. Construction is modular with
More informationS&C Power Fuses Types SMD-1A, SMD-2B, SMD-2C, SMD-3, and SMD-50. Outdoor Transmission (34.5 kv through 138 kv)
S&C Power Fuses Types SMD-1A, SMD-2B, SMD-2C, SMD-3, and SMD-50 Outdoor Transmission ( kv through 138 kv) S&C SMD Power Fuses Set the Standard of Excellence for Transformer and Capacitor-Bank Protection
More informationCLEAVELAND / PRICE INC. Type RL-C Side Break Switch kv A. Bulletin DB-104E12
Bulletin DB-104E12 Type RL-C Side Break Switch 7.2-69 kv 600-2000 A. CLEAVELAND / PRICE INC. 14000 Rt. 993, Trafford, PA 15085 (724) 864-4177 FAX (724) 864-9040 Email: sales@cleavelandprice.com Type RL-C
More informationFigure 1. Non-removable buttonhead Edison Links. TABLE 1 Edison Link Fuse Designs. System Fuse Ampere Rating Type Rating
Fusing Equipment Edison Links Electrical Apparatus K-SEC 100 GENERAL Cooper Power Systems Kearney line of fuse links, Edison Links, can be applied to a variety of applications requiring overcurrent protection
More informationMedium Voltage Fuses
2,400-38,000 VAC General Information Current-limiting E and rated fuses are equipped with a mechanical indicator or striker pin that protrudes through the fuse cap upon operation of the fuse. This provides
More informationIndustrial Control Transformers
6 Industrial Control Transformers Section 6 Industrial Control Transformers provide a low and safe control voltage for the operation of electromagnetic devices, such as motor starters, contactors, solenoids
More informationPROTECTION AND CONTROL
B C Table 1 DIMENSIONAL Information for Trans-Guard OS Fuses Fuse Voltage Rating (kv) 1/4-20 threaded hole 1/2 deep (both ends) Current Rating (Amps) Fuse Catalog Number 35 HTDS232035 Overall Diameter
More informationGROUP D. Switch & Protective device.
GROUP D Switch & Protective device PYUNGIL Bldg., 147-10, Gwanyang 2-dong, Dongan-gu, Anyang-si, Gyeonggi-do, 431-808, Korea Tel : 82-31-420-0~3 FAX : 82-31-424-7300 www.pyungil.com Pole-mounted SF Insulated
More informationFIXED POWER FACTOR CORRECTION EQUIPMENT 5KV CLASS MEDIUM VOLTAGE SECTION Z
PART 1 GENERAL 1.01 1.02 1.03 1.04 1.05 SCOPE The Contractor shall furnish and install fixed power factor correction equipment as specified herein and as shown on the contract drawings. This specification
More information045 : 2000 CEB STANDARD
045 : 2000 CEB STANDARD LOW VOLTAGE FUSE SWITCH DISCONNECTOR CEYLON ELECTRICITY BOARD SRI LANKA Specification for LOW VOLTAGE FUSE SWITCH DISCONNECTOR CEB Standard 045 : 2000 CEYLON ELECTRICITY BOARD No.
More informationGuide Specification. Three-Phase Solid Dielectric Trident-SR with SafeVu Integral Visible Break
Part 1-GENERAL 1.1 DESCRIPTION Guide Specification Three-Phase Solid Dielectric Trident-SR with SafeVu Integral Visible Break The switchgear shall consist of magnetically actuated solid dielectric insulated
More informationGENERAL. CONSTRUCTION External
Surge Arresters VariSTAR Type AZG4 Surge Arresters for Systems through 400 kv IEC 20-kA; Line Discharge Class 4 Electrical Apparatus I235-84 GENERAL VariSTAR AZG4 Surge Arresters incorporate the latest
More informationDIN HV Distribution. DIN HV fuses are partial-range high voltage currentlimiting fuses for use in distribution circuits from kV.
DIN HV Distribution DIN HV fuses are partial-range high voltage currentlimiting fuses for use in distribution circuits from 2.3-38kV. Their compact dimensions and non-venting characteristics make them
More informationInstructions for Installation
S&C Vista Underground Distribution Switchgear Wind Turbine Style Instructions for Installation Table of Contents Section Page Section Page Introduction Qualified Persons... 2 Read this Instruction Sheet....
More informationMichigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE
PAGE 261116-1 SECTION 261116 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationJumpers & Load Pickup Tools
Jumpers & Load Pickup Tools Catalog 2300 May 2016 Jumpers & Load Pickup Tools 2300 May 2016 Page 2301 All Chance Insulated Jumpers meet ASTM F 2321 Standard Specification. G4758 15kV 5 5 / 8 " G4765 25kV
More informationCLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS
CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS Originated 1/85 Revised 6/95 Revised 6/02 Revised 11/05 Revised 4/08 Revised 11/09 Revised 1/12 Revised 11/12 Revised
More informationSurge Arresters. UltraSIL Housed VariSTAR Station Class Surge Arresters GENERAL CONSTRUCTION
Surge Arresters UltraSIL Housed VariSTAR Station Class Surge Arresters Electrical Apparatus 235-88 GENERAL Cooper Power Systems has set a new standard of excellence for polymerhoused station class surge
More informationTypical Specification
Engineered to Order Built to Last Typical Specification VAULT VRPFI, TWO POSITION, ROTARY PUFFER SWITCHGEAR PART 1- GENERAL 1.1 DESCRIPTION A. The switch shall consist of manually operated load interrupting,
More information