Customer Requirements Clearance Requirements for Overhead Joint Utility Construction

Size: px
Start display at page:

Download "Customer Requirements Clearance Requirements for Overhead Joint Utility Construction"

Transcription

1 Application This standard establishes the clearances that are required on utility pole structures between electrical supply facilities owned and operated by Tacoma Power and communication facilities owned and operated by others. Terms Term Joint Utility Worker Safety Zone Supply Transmission Distribution Secondary Supply Neutral Common Position Definition For the purposes of this standard, any entity (utility, public agency, communications company, or other) other than the electrical supply utility that is attached to the structure. The space on joint-use structures where communication facilities are separated from the supply space by the communication Worker safety zone. This space is below the communication worker safety zone. That space as defined in National Electric Safety Code (NESC) Rule 235C4. This zone generally originates at the lowest point of the supply space. This space is intended to maintain a physical separation between supply and communication facilities. The minimum dimensions of this space shall at no time be violated. The space on joint-use structures where supply facilities are separated from the communication space by the communication worker safety zone. This space is above the communication worker safety zone. Tacoma Power supply voltages of 115 kv or 230 kv. Tacoma Power supply voltages of 7.2 kv to 15 kv. Tacoma Power supply voltages of 600 V or less. Multi-grounded conductor of the Distribution system. Nine feet (9 ft.) below the distribution. Transmission & Distribution Standards Page 1 of 13

2 Figure 1 Illustration of Allocation on Pole Supply Common Position Worker Safety Zone Required Ground Figure 2 Illustration of Worker Safety Zone Power Attachment Worker Safety Zone Per Figures 3,4,5,6, & 7 s Attachment Transmission & Distribution Standards Page 2 of 13

3 Clearance Requirements Clearances to Transmission Clearances from transmission to communication underbuild will be determined by the Tacoma Power Line Engineering Department. This standard does not list any clearances of communication cables to Tacoma Power transmission facilities. Clearances to Distribution, Secondary and Supply Neutral Clearances to distribution, secondary and supply neutral conductors will follow the most current version of the NESC unless otherwise noted. At no time will the minimum NESC clearances be compromised. Minimum clearance values listed for existing attachments do not allow for additional communication facilities to be installed at a later date. New Attachments For new communication attachments to existing structures that wish to be installed above existing communications facilities the minimum clearance values must be present. If this is not the case make ready work is likely to be required. Clearances at Supports The minimum clearances at supports between Tacoma Power electrical supply conductors, equipment, and hardware and communication conductors and hardware attached to the same supports are listed in the figures that follow: If and then refer to Figure 3 distribution/supply neutral conductors are mounted on a crossarm at the same level (either single or double arm construction) distribution/supply neutral conductors are mounted on a crossarm at the same level (either single or double arm construction) the supply neutral is located in the common position on the pole secondary conductor is located in the common position a secondary riser is located on the pole there are no additional Tacoma Power conductors or equipment below the crossarm electrical equipment enclosure is mounted beneath the crossarm with no additional Tacoma Power conductors or equipment beneath it there are no secondary conductors on the pole (The clearance is measured from the tie wire or conductor clamp on the insulator to the top of the communication space) Figure 4 Figure 5 Figure 6 Figure 7 Transmission & Distribution Standards Page 3 of 13

4 Figure 3 Clearance to Distribution/Supply Neutral Conductors on Pole with No Other Equipment or Conductors (e.g kv System or Supply Neutral on arm, etc.) Distribution Conductor Supply Neutral Worker Safety Zone 9 min. s Cable Pole Grounding Conductor Minimum Clearance* 9 feet Clearances are designed so that Tacoma Power manlift equipment can move from the road side of the structure to the field side of the structure. The clearances exceed the NESC minimum clearance of 40 in. Transmission & Distribution Standards Page 4 of 13

5 Figure 4 Clearance to Equipment Distribution/Supply Neutral Conductor Supply Grounded Equipment Case 30 Grounded Case 40 Ungrounded Case Worker Safety Zone Minimum Clearance Grounded Case Ungrounded Case 30 inches Transmission & Distribution Standards Page 5 of 13

6 Figure 5 Clearance to Supply Neutral in the Common Position Supply Optional Secondary Rack Supply Rigid Clevis Supply Neutral 40 Minimum Worker Safety Zone NOTE: s shall install as low as possible on the pole while maintaining clearances Minimum Clearance* The minimum clearance may be reduced to 30 inches on a per structure basis as reviewed and approved by the Tacoma Power Line Section. Transmission & Distribution Standards Page 6 of 13

7 Figure 6 Clearance to Secondary Conductor in the Common Position Rigid Clevis Secondary or Service Supply Conductors Supply Drip Loop 40" Minimum Worker Safety Zone NOTE: s shall install as low as possible on the pole while maintaining clearances Minimum Clearance Transmission & Distribution Standards Page 7 of 13

8 Figure 7 Clearance to Secondary Riser Termination (Top of the Conduit) Supply Top of Secondary Riser 40" Minimum Worker Safety Zone NOTE: Risers shall be installed at the same level or above the neutral Minimum Clearance Transmission & Distribution Standards Page 8 of 13

9 Clearances at Midspan between Supports The minimum clearances at midspan between Tacoma Power electrical supply conductors and communication conductors attached to the same supports are listed in the figures that follow: If and then refer to distribution/supply neutral conductors are mounted on a crossarm at the same level (either single or double arm construction) the supply neutral is located in the common position on the pole secondary conductor is located in the common position there are no additional Tacoma Power conductors or equipment below the crossarm there are no secondary conductors on the pole Figure 8 Figure 9 Figure 10 Figure 8 Midspan Clearance between Distribution Conductors and s Cables Distribution/Supply Neutral Conductor 63" min s Cable Minimum Clearance 63 inches Transmission & Distribution Standards Page 9 of 13

10 Figure 9 Midspan Clearance between Supply Neutral and s Cable Supply Neutral 30" min Upper s Cable Minimum Clearance 30 inches Figure 10 Midspan Clearance between Secondary Conductors and s Cable Supply Neutral Secondary Conductor 30" min Upper s Cable Minimum Clearance 30 inches Transmission & Distribution Standards Page 10 of 13

11 Clearances to Street Lights Clearances to street lights have been modified from the clearances to other electric supply facilities due to the nature of their installation. Clearances for Comm Cables Below Street Lights When communication cables are installed below a street light on a structure, all of the following minimum clearances shall be met (see Figure 11): Between the bottom of and the top of the The minimum clearance is street light communication space. Ungrounded Grounded 4 inches drip loop of street light supply wire communication space. Uncovered drip loop Covered drip loop 12 inches 3 inches Figure 11 Clearances for Street Light Above s Supply Bracket Arm 40" Minimum Worker Safety Zone Uncovered 12" Covered 3" Ungrounded 40" Grounded 4" Transmission & Distribution Standards Page 11 of 13

12 Clearances to Street Lights (continued) Clearances for Comm Cables/ Support arms Above Street Lights When communication cables/support arms are installed above a street light on a structure, all of the following minimum clearances shall be met (see Figures 12 and 13): Between the and the The minimum clearance is top of the street light lowest communication attachment Ungrounded Grounded 4 inches top of the street light bottom of the street light supply wire molding/conduit (where the wire is exposed at the drip loop) top of the street light supply wire molding/conduit (where the wire is exposed) bottom of any communication support arm. lowest communication attachment. highest communication attachment. Ungrounded Grounded 72 inches 24 inches Figure 12 Clearances for Street Light Below Cable Supply 40" Worker Safety Zone Protective Molding/Conduit s Cables Ungrounded 40" Grounded 4" 72 To Exposed Wires Transmission & Distribution Standards Page 12 of 13

13 Clearances to Street Lights (continued) Figure 13 Clearances for Street Light Below s Support Arm Supply 40" Worker Safety Zone Protective Molding/Conduit Ungrounded 40" Grounded 24" 72 To Exposed Wires Transmission & Distribution Standards Page 13 of 13

Appalachian Power Company Policy No. 2 Cover Up Procedures. Policy Summary:

Appalachian Power Company Policy No. 2 Cover Up Procedures. Policy Summary: Appalachian Power Company Policy No. 2 Cover Up Procedures Policy Summary: A. When a worker is in a position where the worker or a conductive object in the worker s hand can go or reach within the minimum

More information

Customer Requirements Pole Attachment Requirements for Telecommunications (non-rf)

Customer Requirements Pole Attachment Requirements for Telecommunications (non-rf) Application This standard establishes the attachment requirements to utility pole structures owned and operated by Tacoma Power and communication facilities owned and operated by others. This standard

More information

Engineering Service Specifications. Commercial Single-Phase Current Transformer Metering Schemes

Engineering Service Specifications. Commercial Single-Phase Current Transformer Metering Schemes Engineering Service Specifications Commercial Single-Phase Current Transformer Metering Schemes Specifications for Commercial Underground Current Transformer Metering Requirements for a Single-Phase Customer

More information

SOUTHWEST LOUISIANA ELECTRIC MEMBERSHIP COORPORATION COMMERCIAL SERVICE REQUIREMENTS

SOUTHWEST LOUISIANA ELECTRIC MEMBERSHIP COORPORATION COMMERCIAL SERVICE REQUIREMENTS SOUTHWEST LOUISIANA ELECTRIC MEMBERSHIP COORPORATION COMMERCIAL SERVICE REQUIREMENTS November 17, 2016 Engineering Service Specifications Table of Contents Commercial Service Requirements SLEMCO Commercial

More information

THE DAYTON POWER AND LIGHT COMPANY Original Sheet No. 15 DPL Building Courthouse Plaza Southwest Dayton, Ohio P.U.C.O. NO. 1

THE DAYTON POWER AND LIGHT COMPANY Original Sheet No. 15 DPL Building Courthouse Plaza Southwest Dayton, Ohio P.U.C.O. NO. 1 THE DAYTON POWER AND LIGHT COMPANY Original Sheet No. 15 SCHEDULE 1 Schedule of fees and charges used for determining sacrifice value, excess height and/or strength and sale costs of poles. Year % Set

More information

1150 CLEARANCES 11/28/2016

1150 CLEARANCES 11/28/2016 1150 CLEAANCES 11/28/2016 ~ CFG Construction Framing Guide N CO OH Clearance to oadways & Other Surfaces - ~ CTS OH Clearance to Structures N DC OH Clearance to oadways & Other Surfaces - Design Minimum

More information

Index Section 103 Joint Use. General Requirements for Installation of Attachments on Oncor Poles

Index Section 103 Joint Use. General Requirements for Installation of Attachments on Oncor Poles 103 09-17 103 Index Section 103 Joint Use Title Date Number General Requirements for Installation of Attachments on Oncor Poles... 103-100 Supply and Communication Space... 103-105 Communication Lines

More information

Service Requirements

Service Requirements Service Requirements General Contact Idaho Power before beginning work on any new service. All meter installations must meet current electrical code requirements and display the proper electrical permit.

More information

WPS SERVICE MANUAL. Section 7 Clearances. 7-1 Basic Electric Clearances - Services Miscellaneous Clearances Antenna Clearances...

WPS SERVICE MANUAL. Section 7 Clearances. 7-1 Basic Electric Clearances - Services Miscellaneous Clearances Antenna Clearances... Revised 03/2016 Section 7 CLEARANCES Page 1 of 9 Section 7 Clearances 7-1 Basic Electric Clearances - Services... 2 7-2 Miscellaneous Clearances... 7 7-3 Antenna Clearances... 9 Revised 03/2016 Section

More information

Revised: April 2018 ¹ SERVICE TO WIRELESS DEVICE ANTENNA ATTACHMENTS ON CUSTOMER SERVICE POLES (SHEET 1) CUSTOMER: 1. An overcurrent protective device including a disconnect switch shall

More information

UNDERGROUND SERVICE ENTRANCE LOCATION. No meter base or entrance should be installed before an KREMC engineer has checked the proposed location.

UNDERGROUND SERVICE ENTRANCE LOCATION. No meter base or entrance should be installed before an KREMC engineer has checked the proposed location. UNDERGROUND SERVICE No meter base or entrance should be installed before an KREMC engineer has checked the proposed location. Entrance cabinet must be directly through wall or directly under meter in basement.

More information

MINIMUM DISTRIBUTION SYSTEM CONCEPTS AND APPLICATIONS. Larry Vogt. Manager, Rates

MINIMUM DISTRIBUTION SYSTEM CONCEPTS AND APPLICATIONS. Larry Vogt. Manager, Rates MINIMUM DISTRIBUTION SYSTEM CONCEPTS AND APPLICATIONS Larry Vogt Manager, Rates Minimum Distribution System What is MDS? MDS is an analysis module of the cost-of-service study in which distribution investment

More information

For Conduit Inspections

For Conduit Inspections Underground Conduit Standards - Table of Content 5/8/2017 Section S22 Underground Conduit Standard Index: Description: 00 Table of Content 01 General Notes 02 Definition of Terms 03 Primary Riser Conduit

More information

CAT-1 Series 3. Installation Guide. The Valley Group, Inc. 871 Ethan Allen Hwy. Suite 104 Ridgefield, CT 06877

CAT-1 Series 3. Installation Guide. The Valley Group, Inc. 871 Ethan Allen Hwy. Suite 104 Ridgefield, CT 06877 CAT-1 Series 3 Installation Guide The Valley Group, Inc. 871 Ethan Allen Hwy. Suite 104 Ridgefield, CT 06877 (203) 431-0262 (203) 431-0296 FAX tvg@cat-1.com Installation of Load Cells for CAT-1 Systems

More information

SERVICE ATTACHMENT ON A BUILDING WITH BUS DUCT SERVICE ENTRANCE AND INDOOR METERING

SERVICE ATTACHMENT ON A BUILDING WITH BUS DUCT SERVICE ENTRANCE AND INDOOR METERING SERVICE ATTACHMENT ON A BUILDING WITH BUS DUCT SERVICE ENTRANCE AND INDOOR METERING Obtain acceptance and specific details from the local Company office. 1. Service entrance duct (see Note 1). Company

More information

Pentahead bolts See note 2. Conduit run as specified. Company facility. Refer to drawing SS8.6-2 or SS8.6-3 STANDARD SERVICE INSTALLATION

Pentahead bolts See note 2. Conduit run as specified. Company facility. Refer to drawing SS8.6-2 or SS8.6-3 STANDARD SERVICE INSTALLATION PULL BOX F SECONDARY SYSTEM Typical grade Pentahead bolts See note 2 Conduit run as specified Plastic or fiberglass for grass areas or Polymer concrete for light duty areas (see notes 2, 3, & 4) Company

More information

Wisconsin Public Utility Institute. June 28, Minimum Distribution Charges. Larry Vogt. Director, Rates Mississippi Power

Wisconsin Public Utility Institute. June 28, Minimum Distribution Charges. Larry Vogt. Director, Rates Mississippi Power Wisconsin Public Utility Institute June 28, 2017 Minimum Distribution Charges Larry Vogt Director, Rates Mississippi Power 1 Costs of Service vs. Cost Recovery Residential Service Example Assuming that

More information

D9-3. No. WIRING DIAGRAM CONNECTIONS FOR UNDERGROUND SELF CONTAINED METERS JRH JED krich95 LINE LINE ABCN SOURCE SOURCE GROUND GROUND STUD STUD SOURCE

D9-3. No. WIRING DIAGRAM CONNECTIONS FOR UNDERGROUND SELF CONTAINED METERS JRH JED krich95 LINE LINE ABCN SOURCE SOURCE GROUND GROUND STUD STUD SOURCE SOURCE 20V 240V STUD (PER NEC) A customer supplied and installed teaser wire is required from the neutral lug to a 5th terminal mounted on the left side of the meter block between the line and load terminals.

More information

AGRICULTURAL UNDERGROUND SERVICE 500 HP OR LESS

AGRICULTURAL UNDERGROUND SERVICE 500 HP OR LESS Prepared by: ABB1 AGRICULTURAL UNDERGROUND SERVICE 500 HP OR LESS 05619 Asset Type: Electric Metering Function: Design and Construction Issued by: Lisseth Villareal (LDV2) Date: 07-31-15 Rev. #10: This

More information

The New 2017 National Electric Safety Code Overview and Significant Changes. Presented by. Mickey Gunter October 28, 2016

The New 2017 National Electric Safety Code Overview and Significant Changes. Presented by. Mickey Gunter October 28, 2016 The New 2017 National Electric Safety Code Overview and Significant Changes Presented by Mickey Gunter October 28, 2016 NESC Technical Subcommittees Subcommittee 1 Coordination, Definitions Subcommittee

More information

CONDUCTOR CONDUCTOR. Overhead Electric Distribution Standards INTRODUCTION

CONDUCTOR CONDUCTOR. Overhead Electric Distribution Standards INTRODUCTION INTRODUCTION 1. In order to ensure safety, certain minimum clearances shall be maintained between various circuits of an overhead distribution system. Proper clearances from joint-use utilities, railroads,

More information

UNDERGROUND SERVICE ENTRANCE LOCATION. No meter base or entrance should be installed before an KREMC engineer has checked the proposed location.

UNDERGROUND SERVICE ENTRANCE LOCATION. No meter base or entrance should be installed before an KREMC engineer has checked the proposed location. UNDERGROUND SERVICE No meter base or entrance should be installed before an KREMC engineer has checked the proposed location. Entrance cabinet must be directly through wall or directly under meter in basement.

More information

Service Requirements

Service Requirements Service Requirements General Contact Idaho Power before beginning work on any new service. All meter installations must meet current electrical code requirements and display the proper electrical permit.

More information

ELECTRIC SERVICE RULES UTILITY/CATV SERVICES Issued Jan 2016

ELECTRIC SERVICE RULES UTILITY/CATV SERVICES Issued Jan 2016 UTILITY/CATV SERVICES CHAPTER 9 900. GENERAL A. Alliant Energy receives many requests for electric service from other utilities; telephone, telecommunications companies, cable television, the Department

More information

Approved Meter Sockets and Cabinets

Approved Meter Sockets and Cabinets Single Unit Residential Guide 1 PHASE, 120/240 VOLT SERVICES SERVICE CAPACITY OWNED METERING (Metering sockets and cabinets are supplied by Customer). Outdoor meter mounting height is 1730 mm ( 5 8 ) to

More information

SINGLE PHASE WIRING SPECIFICATIONS

SINGLE PHASE WIRING SPECIFICATIONS SINGLE PHASE WIRING SPECIFICATIONS 1-866-MEC-ELEC (1-866-632-3532) Office Locations: Hondo Office 237 Hwy 173 N Hondo, TX 78661-0370 Fax 830.426.3335 Dilley Office 1718 W. FM 117 Dilley, TX 78017 Fax 830.965.1425

More information

THREE PHASE WIRING SPECIFICATIONS

THREE PHASE WIRING SPECIFICATIONS THREE PHASE WIRING SPECIFICATIONS 1-866-MEC-ELEC (1-866-632-3532) Office Locations: Hondo Office 237 Hwy 173 N Hondo, TX 78661-0370 Fax 830.426.3335 Dilley Office 1718 W. FM 117 Dilley, TX 78017 Fax 830.965.1425

More information

OVERHEAD SERVICE. Items to consider

OVERHEAD SERVICE. Items to consider OVERHEAD SERVICE Items to consider The maximum length of the service wire from the ComEd pole to the point of attachment on your residence is 150 feet, if practical. Your service wire installation must

More information

SECTION 300 OVERHEAD SERVICE

SECTION 300 OVERHEAD SERVICE SECTION 300 OVERHEAD SERVICE 300.01 General Company provides, installs, and maintains service drop to point of delivery approved by Company. Customer provides point of attachment which is acceptable to

More information

9. Non-Residential Services (Commercial, Industrial, and Agricultural)

9. Non-Residential Services (Commercial, Industrial, and Agricultural) Section 9 2016 Electric Service Requirements, 3rd Edition Section 9 Non-Residential Services Directory Page 9.1 General Requirements 68 9.2 Direct-Connect Metering, Single Installations 69 9.3 Direct-Connect

More information

INTERCONNECTION REQUIREMENTS INVERTER-BASED DISTRIBUTED GENERATION SOURCES FOR SINGLE-PHASE CUSTOMER SERVICES

INTERCONNECTION REQUIREMENTS INVERTER-BASED DISTRIBUTED GENERATION SOURCES FOR SINGLE-PHASE CUSTOMER SERVICES INTERCONNECTION REQUIREMENTS INVERTER-BASED DISTRIBUTED GENERATION SOURCES FOR SINGLE-PHASE CUSTOMER SERVICES 3. Definitions ( cont'd) Parallel System: A generating facility that is electrically interconnected

More information

7. Residential Single-Family and Duplex Buildings (Dwellings)

7. Residential Single-Family and Duplex Buildings (Dwellings) Sin g le -F a mily a n d Du p le x Bu ild in g s 2016 Electric Service Requirements, 2 nd Edition Section 7 Section 7 Residential Single-Family and Duplex Buildings (Dwellings) Directory Page 7.1 General

More information

Installing or Rebuilding Your Electric Service

Installing or Rebuilding Your Electric Service Installing or Rebuilding Your Electric Service 2 3 Contents Policies for New and Rebuilt Electric Service 2-4 Paperwork and fees...2 Five-year policy...3 Proposed route location and conditions...3 Construction

More information

Table of Contents. Electrical Service Requirements. 1. General Requirements

Table of Contents. Electrical Service Requirements. 1. General Requirements Table of Contents 1. General Requirements 1.1 General Definition.................................................... 1 1 1.2 Booklet Purpose and Organization....................................... 1-1

More information

SmartPole Meter for Service to Pole-Mounted Communication Equipment

SmartPole Meter for Service to Pole-Mounted Communication Equipment SUMMARY This bulletin introduces a new PG&E meter, called a SmartPole meter, approved for use with overhead services connected to communication equipment mounted on wood poles. The SmartPole meter and

More information

ELECTRIC POLICY INTRODUCTION CHAPTER I GENERAL

ELECTRIC POLICY INTRODUCTION CHAPTER I GENERAL INTRODUCTION This policy has been adopted by the Board of Public Works as a guide to obtaining electric service and to set forth the services available, conditions for service, and standards for materials

More information

Poles - General Unguyed Single Phase Composite Poles Poles - General Unguyed Three Phase Composite Poles

Poles - General Unguyed Single Phase Composite Poles Poles - General Unguyed Three Phase Composite Poles Standard Description 2 4 2 Poles - General Unguyed Single Phase Composite Poles 2 4 3 Poles - General Unguyed Three Phase Composite Poles 3 3 Structural Elements - Design Limits 3 1 1 Configurations -

More information

NEW SERVICE HANDBOOK COMMERCIAL & IRRIGATION SUPPLEMENT

NEW SERVICE HANDBOOK COMMERCIAL & IRRIGATION SUPPLEMENT NEW SERVICE HANDBOOK COMMERCIAL & IRRIGATION SUPPLEMENT Meter Installations There are three basic ways to measure electricity consumption: Small and medium services are metered directly using direct connect

More information

ELECTRIC INCIDENT INVESTIGATION WORKSHOP

ELECTRIC INCIDENT INVESTIGATION WORKSHOP ELECTRIC INCIDENT INVESTIGATION WORKSHOP Schedule Start Hour Finish Hour Day 1 Breakfast 8:00 A.M. 8:30 A.M. Workshop in session Introduction Electrical Theory Physiological Effects of Electricity 8:30

More information

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 9/14/11 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 9/14/11 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions MECKLENBURG COUNTY Land Use and Environmental Service Agency Code Enforcement 9/14/11 ELECTRICAL CONSISTENCY MEETING Code Consistency Questions 1. I recently installed a 45-KVA transformer, 480-volt primary

More information

Customer Requirements Meter Socket Configurations

Customer Requirements Meter Socket Configurations Application Information on meter socket configurations available from Tacoma Power. For enclosed meter pedestals, see standard C-MR-0020 Customer Requirements, Enclosed Meter Pedestal. General Requirements

More information

STOUGHTON UTILITIES ELECTRIC SERVICE RULES AND INFORMATION

STOUGHTON UTILITIES ELECTRIC SERVICE RULES AND INFORMATION CHAPTER 1 - GENERAL INFORMATION 100. Purpose 101. Codes and rules 102. Continuity of service 103. Frequency, Voltage, and Amperage Limitations 104. High voltages 105. Unusual capacity requirements 106.

More information

320A Single Phase URD Meter Loop Installations

320A Single Phase URD Meter Loop Installations 320A Single Phase URD Meter Loop Installations Location: The meter loop shall be mounted on the side of the pedestal facing the consumer's lot. (The side being one of the four flat surfaces of the pedestal

More information

SECTION LOW VOLTAGE DISTRIBUTION EQUIPMENT

SECTION LOW VOLTAGE DISTRIBUTION EQUIPMENT SECTION 16400 LOW VOLTAGE DISTRIBUTION EQUIPMENT A. General 1. The University does not accept Series-Rated equipment for power distribution switchboards, distribution panels and branch circuit panelboards.

More information

Technical Specification for Pole Mounted Capacitor Rack

Technical Specification for Pole Mounted Capacitor Rack Technical Specification for Pole Mounted Rack Page 1 1. Scope and Function a) Pole mounted capacitor racks shall be installed on a distribution feed as an economical means of applying capacitor units to

More information

NEC 2011 Code Changes

NEC 2011 Code Changes NEC 2011 Code Changes Articles 280.21-300.50 CHANGES FROM 2008 TO 2011 CODE ARE IN RED Chapter 2 - Wiring and Protection ARTICLE 280 Surge Arresters, Over 1kV III. Connecting Surge Arresters 280.21 Connection

More information

JACKSON ELECTRIC COOP METER LOOP CONSTRUCTION SPECIFICATIONS JUNE 2018

JACKSON ELECTRIC COOP METER LOOP CONSTRUCTION SPECIFICATIONS JUNE 2018 JACKSON ELECTRIC COOP METER LOOP CONSTRUCTION SPECIFICATIONS JUNE 2018 GANADO OFFICE PHYSICAL ADDRESS: 8925 State Highway 111 E Ganado, TX 77962 Phone: (361)771-4400 BAY CITY OFFICE PHYSICAL ADDRESS: 100

More information

WILDLIFE PROTECTION

WILDLIFE PROTECTION 05 00 00 01 TABLE OF CONTENTS GENERAL INFORMATION INSTALLATION OF CRITTER LINE GUARDS INSTALLATION OF TANK MOUNTED LIGHTNING ARRESTER BRACKET GUARDS 25KV & BELOW EXISTING STRUCTURE MODIFICATION 05 00 00

More information

Meter Installation. -and- Padmount Transformer Guide

Meter Installation. -and- Padmount Transformer Guide Meter Installation -and- Padmount Transformer Guide Feb. 2016 METERING REQUIREMENTS The following information shall be used as a guide for installing metering equipment. A self-contained meter has all

More information

RESIDENTIAL ELECTRIC PERMIT (REP) Village of Montpelier 211 N. Jonesville Street, PO Box 148 Montpelier, OH P:

RESIDENTIAL ELECTRIC PERMIT (REP) Village of Montpelier 211 N. Jonesville Street, PO Box 148 Montpelier, OH P: Address: Date: Legal Owner: Address (if different than above): Electrical Contractor: Address: Phone: Size of New Service (amps): Location of New Service: RESIDENTIAL ELECTRIC PERMIT (REP) Village of Montpelier

More information

Customer Guide to Electric Service Requirements

Customer Guide to Electric Service Requirements Customer Guide to Electric Service Requirements Tillamook People s Utility District Power Services Group 1115 Pacific Avenue Tillamook, Oregon 97141 OFFICE: 503.815.8629 FAX: 503.815.8648 TOLL FREE: 800.422.2535

More information

NEW SERVICE HANDBOOK

NEW SERVICE HANDBOOK NEW SERVICE HANDBOOK LOCATING UNDERGROUND UTILITIES CHECK SHEET cut here Will you be working within ten feet of any overhead power lines? Yes No Type of work Work being done for County Nearest City Address

More information

Commercial Electric Policy

Commercial Electric Policy Commercial Electric Policy 7/19/16 1 Table of Contents General Information..3 Construction.3 Ownership.4 Multi-Unit/Multi-Service Buildings....4 Secondary Termination Enclosures.4 Meter Bases.5 Temporary

More information

UNDERGROUND SERVICE. Items to consider. There will be charges from ComEd if you convert from overhead to underground service.

UNDERGROUND SERVICE. Items to consider. There will be charges from ComEd if you convert from overhead to underground service. UNDERGROUND SERVCE tems to consider f your trenching route has to be dug by hand, or if a cable must be installed under a paved surface, additional charges apply. f your service cable has to be moved later

More information

TABLE OF CONTENTS. Important Notices Underground Plant Protection Information. Commercial/Industrial Information Sheet

TABLE OF CONTENTS. Important Notices Underground Plant Protection Information. Commercial/Industrial Information Sheet DRAWING NUMBER INTRODUCTORY INFORMATION Important Notices Underground Plant Protection Information Code Clearances Commercial/Industrial Information Sheet Work Management Customer Projects Engineering

More information

10 Commercial, Industrial, Agricultural Services

10 Commercial, Industrial, Agricultural Services 10 Commercial, Industrial, Agricultural Services This section describes the Power Company requirements for commercial, industrial, and agricultural services. This section covers single phase and three

More information

Temporarily Approved Solar Photovoltaic System Electrical Schematics

Temporarily Approved Solar Photovoltaic System Electrical Schematics March 20, 2019 Page 1 of 10 Temporarily Approved Solar Photovoltaic System Electrical Schematics This document is intended as a temporary interpretation of approved solar photovoltaic electrical schematics

More information

AMENDMENT ELECTRIC SERVICE MANUAL 2014

AMENDMENT ELECTRIC SERVICE MANUAL 2014 AMENDMENT (Pages 20,43,50,72,74,,76,78,83,86,99) ELECTRIC SERVICE MANUAL 2014 Effective April 1, 2015 18-7 6.0 SERVICE AND SERVICE ENTRANCES (General), Continued Conductor Sizing It is recommended that

More information

CONTENTS BY CHAPTER. Chapter 2: COMPANY EQUIPMENT ON CUSTOMER PREMISES

CONTENTS BY CHAPTER. Chapter 2: COMPANY EQUIPMENT ON CUSTOMER PREMISES CONTENTS BY CHAPTER Chapter 1: GENERAL INFORMATION Chapter 2: COMPANY EQUIPMENT ON CUSTOMER PREMISES Chapter 3: SERVICE ENTRANCES Chapter 4: METERING INSTALLATION Chapter 5: CUSTOMER-INSTALLED SERVICE

More information

Single-Sided Storage Rack Assembly Instructions

Single-Sided Storage Rack Assembly Instructions Single-Sided Storage Rack Assembly Instructions H D I G J K M L F I D B C A E PART NAME QTY A. BASE BAR (50 ) 2 B. BASE BAR HULL GUARD (34 ) 2 C. BASE BAR END CAP 2 D. SAFETY END CAP 4 E. FOOT 4 F. UPRIGHT

More information

INSTALL SERVICE- ENTRANCE SYSTEMS

INSTALL SERVICE- ENTRANCE SYSTEMS SUBCOURSE EN5141 EDITION B US ARMY ENGINEER SCHOOL INSTALL SERVICE- ENTRANCE SYSTEMS INSTALL SERVICE- ENTRANCE SYSTEMS Subcourse Number EN5141 EDITION B United States Army Engineer School Fort Leonard

More information

DISCONNECT SWITCH REQUIREMENTS FOR DISTRIBUTED GENERATION CUSTOMERS

DISCONNECT SWITCH REQUIREMENTS FOR DISTRIBUTED GENERATION CUSTOMERS Prepared by: SXZO DISCONNECT SWITCH REQUIREENTS FOR DISTRIBUTED GENERATION CUSTOERS 060559 Department: Electric Distribution Section: Design and Construction Approved by: D.Jantz (DWJ7) Date: 8/15/17 Rev.

More information

JACKSON ENERGY AUTHORITY ELECTRIC SERVICE POLICY EFFECTIVE SEPTEMBER 26 th, 2005 *REVISED JULY 12 th, 2017

JACKSON ENERGY AUTHORITY ELECTRIC SERVICE POLICY EFFECTIVE SEPTEMBER 26 th, 2005 *REVISED JULY 12 th, 2017 JACKSON ENERGY AUTHORITY ELECTRIC SERVICE POLICY EFFECTIVE SEPTEMBER 26 th, 2005 *REVISED JULY 12 th, 2017 JEA SHALL MAKE ALL METER SPOTS BEFORE ELECTRICAL WORK BEGINS AS TO DETERMINE THE POINT OF ATTACHMENT

More information

Demonstrate knowledge of electrical theory for Electrical Service Technician B

Demonstrate knowledge of electrical theory for Electrical Service Technician B Demonstrate knowledge of electrical theory for Electrical Service Technician B 10937 version 4 Page 1 of 5 Level 3 Credits 3 Purpose 'Electrical Service Technician B' (EST B) refers to a class of electrical

More information

COMMERCIAL QUICK REFERENCE

COMMERCIAL QUICK REFERENCE COMMERCIAL QUICK REFERENCE PROVO CITY POWER STANDARDS ELECTRICAL ENGINEERING UPDATED: 2016 SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTIFICATION. 18" MIN. OF TAIL. (NEUTRAL CONDUCTOR MUST BE WHITE OR

More information

Pretest Module 29 High Voltage Unit 1

Pretest Module 29 High Voltage Unit 1 Pretest Module 29 High Voltage Unit 1 1. Is a person qualified to work on high-voltage installations when this module is completed? 2. What is the code definition of high-voltage? 3. What is the IEEE definition

More information

Associated equipment As related to metering equipment: such as the current transformers, CT wiring and test switches.

Associated equipment As related to metering equipment: such as the current transformers, CT wiring and test switches. APPENDIX Glossary Approval Acceptable to the authority having jurisdiction. Assessor s Parcel Number (APN) Identifying number assigned by the county assessor s office to each taxable building lot in the

More information

ELECTRICAL - GENERAL REQUIREMENTS SELF INSPECTION CHECKLIST

ELECTRICAL - GENERAL REQUIREMENTS SELF INSPECTION CHECKLIST Name of School: OPTIONAL INFORMATION Date of Inspection: Vocational Program/Course/Room: Signature of Inspector: ELECTRICAL - GENERAL REQUIREMENTS SELF INSPECTION CHECKLIST Guidelines: This checklist covers

More information

SOLAR PHOTOVOLTAIC SYSTEMS INSPECTOR CHECKLIST

SOLAR PHOTOVOLTAIC SYSTEMS INSPECTOR CHECKLIST SOLAR PHOTOVOLTAIC SYSTEMS INSPECTOR CHECKLIST The following checklist is an outline of the general requirements found in the 1999 National Electrical Code (NEC) Article 690 for Photovoltaic (PV) Power

More information

Pretest Module 24 Three-phase Service Entrance

Pretest Module 24 Three-phase Service Entrance Pretest Module 24 Three-phase Service Entrance 1. What is the most widely used three-phase service entrance system? 2. What are the three most common voltage combinations for three-phase, four-wire systems?

More information

Commercial & Industrial

Commercial & Industrial The Empire District Electric Company Requirements For Electric Service And Meter Installations Commercial & Industrial (800) 206 2300 The latest revision of this book can be found at www.empiredistrict.com

More information

7 Single Family Service

7 Single Family Service 7 Single Family Service 7. General The location of the service entrance on the Customer s premises is an important consideration. For clearance and location information see section 5 (Clearances). Consult

More information

The Green Meter Adapter (GMA) program will become effective on January 15, Customers may start applying for a GMA on January 15, 2018.

The Green Meter Adapter (GMA) program will become effective on January 15, Customers may start applying for a GMA on January 15, 2018. SUMMARY This bulletin introduces a new PG&E program that allows the installation of an electric meter socket adapter that will accept a wired connection directly from a residential customer s Photo Voltaic

More information

WPS SERVICE MANUAL. Section Amp and Smaller - Common

WPS SERVICE MANUAL. Section Amp and Smaller - Common Revised 01/2017 Section 2 200 AMP AND SMALLER - COMMON Page 1 of 17 Section 2 200 Amp and Smaller - Common 2-0 General Metering Requirements... 2 2-1 Basic Calculations... 4 2-2 100-200 Amp Single-Phase

More information

Guying - Insulator Dimensional Requirements ** Lightning Protection & Grounding - Grounds

Guying - Insulator Dimensional Requirements ** Lightning Protection & Grounding - Grounds Standard Description 03 12 01 ** Configurations - Single Phase, 4 to 15kV 03 12 05 ** Configurations - Two or Three Phase Tangent or Angle on Wood Crossarm, 4 to 15 kv 03 12 07 ** Configurations - Two

More information

34.00 METERING GENERAL LABELING MULTIPLE METER ENCLOSURES ON A SINGLE PREMISE

34.00 METERING GENERAL LABELING MULTIPLE METER ENCLOSURES ON A SINGLE PREMISE 4. METERING GENERAL LABELING MULTIPLE METER ENCLOSURES ON A SINGLE PREMISE 4.-4 4. SELF-CONTAINED METERING, SINGE-PHASE INSTALLATION DETAILS /4 VOLT SINGLE-PHASE UNDERGROUND RESIDENTIAL SERVICE AND METER

More information

SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS - ELECTRICAL

SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS - ELECTRICAL SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS - ELECTRICAL This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly.

More information

WIRING DESIGN & PROTECTION REQUIREMENTS CHECKLIST

WIRING DESIGN & PROTECTION REQUIREMENTS CHECKLIST WIRING DESIGN & PROTECTION REQUIREMENTS CHECKLIST Use & Identification of Grounded and Grounding Conductors YES NO N/A Grounded conductors are identifiable and distinguishable from all other conductors.

More information

Photovoltaic Solar Plan Review

Photovoltaic Solar Plan Review PAIGE B. VAUGHAN, CBO Director of Building and Safety Phone (310) 605-5509 Fax Line (310) 605-5598 E-mail:lbutler@comptoncity.org Building & Safety Department Photovoltaic Solar Plan Review Plan Check

More information

ENGINEERING SPECIFICATION

ENGINEERING SPECIFICATION December 206 ENGINEERING SPECIFICATION No. of 6 DATE: 2-9-6 CATEGORY SUBJECT TABLE OF CONTENTS. Overview... 2 2. General Requirements for Service... 3 3. Definitions... 3 4. Abbreviations... 5 5. References

More information

Contents. Obtaining Electric Service from Your Cooperative...1. Bonding Frames of Major Appliances...4. Voltage Drop...8. Drawings...

Contents. Obtaining Electric Service from Your Cooperative...1. Bonding Frames of Major Appliances...4. Voltage Drop...8. Drawings... Contents Obtaining Electric Service from Your Cooperative...1 Bonding Frames of Major Appliances...4 Voltage Drop...8 Drawings...14 Agricultural Buildings...23 Optional Standby Systems...42 Grounding &

More information

2016 METER SERVICES SPECIFICATION GUIDE

2016 METER SERVICES SPECIFICATION GUIDE 2016 METER SERVICES SPECIFICATION GUIDE 802.01.ST (10-16) CONTENTS Introduction 2 Disclaimers 2 LES contacts 3 Definitions 4 LES Meter Services department requirements for approval of connection to LES

More information

Electric Service and Meter Installations Manual SCANA Corporation 2018

Electric Service and Meter Installations Manual SCANA Corporation 2018 Electric Service and Meter Installations Manual SCANA Corporation 2018 Revised: January 2018 On file with South Carolina Public Service Commission Table of Contents Section 1: Introduction Customer Call

More information

Customer Requirements Downtown Secondary Network Service

Customer Requirements Downtown Secondary Network Service Application This standard describes the limitations and requirements for receiving service from the Tacoma Power secondary network system within the City of Tacoma downtown core area. In This Standard

More information

Electrical Awareness and Considerations

Electrical Awareness and Considerations Electrical Awareness and Considerations By David Taylor FIHE MIET IEng Objectives Awareness of specifications. Awareness of Distribution Network Operators (DNO) earthing arrangements. Awareness of basic

More information

Chapter 6. Batteries. Types and Characteristics Functions and Features Specifications and Ratings Jim Dunlop Solar

Chapter 6. Batteries. Types and Characteristics Functions and Features Specifications and Ratings Jim Dunlop Solar Chapter 6 Batteries Types and Characteristics Functions and Features Specifications and Ratings 2012 Jim Dunlop Solar Overview Describing why batteries are used in PV systems. Identifying the basic components

More information

Customer Guide to Electric Service Requirements

Customer Guide to Electric Service Requirements Customer Guide to Electric Service Requirements Tillamook People s Utility District Power Services Group PO Box 433 1115 Pacific Avenue Tillamook, Oregon 97141 OFFICE: 503.815.8629 FAX: 503.815.8648 TOLL

More information

Spring Test 7 due 05/03/2013

Spring Test 7 due 05/03/2013 Spring Test 7 due 05/03/2013 Multiple Choice Identify the choice that best completes the statement or answers the question. 1. A raceway contains two 3-phase, 3-wire circuits that supply 38 ampere continuous

More information

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 2/8/12 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 2/8/12 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions MECKLENBURG COUNTY Land Use and Environmental Service Agency Code Enforcement 2/8/12 ELECTRICAL CONSISTENCY MEETING Code Consistency Questions 1. I am inspecting a building addition. They have a 480V to

More information

When power interruptions happen.

When power interruptions happen. When power interruptions happen. We know it s never a good time to have your power go out, so we work all year pruning trees and investing in our system to cut down on problems before they start. Outage

More information

Grounding Systems. Equipment Grounding & Grounded Conductors

Grounding Systems. Equipment Grounding & Grounded Conductors Grounding Systems Equipment Grounding & Grounded Conductors Definitions A Grounded or Earthed system is one that is connected to the earth Grounded Conductor is a conductor that normally carries current

More information

Electric Vehicle Pricing Plan Contractor Set-Up Guide

Electric Vehicle Pricing Plan Contractor Set-Up Guide Electric Vehicle Pricing Plan Contractor Set-Up Guide Contractor s Set-Up Guide: Overview Pricing Plan Summary Our special Pricing plan makes it easy for electric vehicle owners to save on charging costs.

More information

CABLE TERMINALS

CABLE TERMINALS 14 00 00 01 Sheet 1 of 1 TABLE OF CONTENTS LOCATION & PLACEMENT OF RISERS ON JOINT USE POLES STANDOFF BRACKET PLACEMENT AND GROUNDING ONE RISER WITH U GUARD, 2, 3, 4, & 5 SPLIT CONDUIT OR SCHEDULE 40 0

More information

Generator Fire Safety: Generator assemblies should be located outside the building.

Generator Fire Safety: Generator assemblies should be located outside the building. SECTION 33 70 00 - ELECTRICAL DISTRIBUTION PACKAGED GENERATOR ASSEMBLIES Generator Fire Safety: Generator assemblies should be located outside the building. All fuel piping from the outside of the building

More information

Clark Public Utilities Commercial Electric Service Handbook. This page left blank intentionally.

Clark Public Utilities Commercial Electric Service Handbook. This page left blank intentionally. This page left blank intentionally. 38 Chapter 4: Commercial Metering / January 2011 APPENDIX Glossary Approval Acceptable to the authority having jurisdiction. Associated equipment As related to metering

More information

Electrical. Earthing & Bonding. Installation Techniques. Learning Notes MODULE 2.2 UNIT PHASE:2

Electrical. Earthing & Bonding. Installation Techniques. Learning Notes MODULE 2.2 UNIT PHASE:2 Electrical Learning Notes MODULE 2.2 UNIT 2.2.6 Installation Techniques Earthing & Bonding PHASE:2 Table of Contents INTRODUCTION... 3 DEFINITIONS... 4 EARTHING... 5 TYPES OF SYSTEM EARTHING... 10 EQUIPOTENTIAL

More information

Surface Regulations and Policies

Surface Regulations and Policies Surface Regulations and Policies COAL FATALITIES 1970-2002 350 300 250 200 150 100 50 0 1970 1973 1976 1979 1982 1985 1988 1991 1994 1997 2000 From January 1, 1970 through today, a total of 240 coal miners

More information

TADP 548 Transmission Line Design- Electrical Aspects

TADP 548 Transmission Line Design- Electrical Aspects TADP 548 Transmission Line Design- Electrical Aspects Presentation 3.1 Electrical Design Clearances Part 4 Transmission & Distribution Program Parvez Rashid & Dr. Prasad Yenumula Electrical Design Clearances

More information

Electric Service Requirements

Electric Service Requirements Electric Service Requirements Section V Commercial Industrial July 2007 ENGINEERING SPECIFICATION 620 S Street, P.O. Box 5830, Sacramento, CA 95852-830 The Power To Do More ṢM SM A registered service mark

More information

2016 Photovoltaic Solar System Plan Review List

2016 Photovoltaic Solar System Plan Review List Building Division 555 Santa Clara Street Vallejo CA 94590 707.648.4374 2016 Photovoltaic Solar System Plan Review List GENERAL PROJECT INFORMATION PLAN CHECK NO DATE JOB ADDRESS CITY ZIP REVIEWED BY PHONE

More information