Spring Test 7 due 05/03/2013

Size: px
Start display at page:

Download "Spring Test 7 due 05/03/2013"

Transcription

1 Spring Test 7 due 05/03/2013 Multiple Choice Identify the choice that best completes the statement or answers the question. 1. A raceway contains two 3-phase, 3-wire circuits that supply 38 ampere continuous loads. The circuit conductors are copper with THHN insulation, and all circuit conductor terminations are 75 C rated. In route to supply the load, the circuits run through a room for a distance of 30 ft (9.14 m) that typically has an ambient temperature of 120 F (48.9 C). The minimum size conductors permitted for these circuits is: a. 8AWG. b. 6 AWG. c. 4 AWG. d. 3 AWG. e. 2 AWG. 2. Lighting outlets are not required in which dwelling unit? a. kitchens b. attics c. crawl spaces d. clothes closets 3. The conductor fill requirements for nonmetallic boxes is determined by: a. Table (A). b. Table (B). c. both of the above.. 4. The voltage drop at the controller line terminals shall not drop more than below normal (controller-rated voltage) under motor starting conditions. a. 10% b. 5% c. 15% 5. If a fuse is used for primary protection of a transformer not in a supervised location with a primary rated over 600 volts. it must be sized at a maximum of of the transformer full-load amperes. a. 300% b. 125% c. 250% 6. A crane is operating over an magneseum electrolytic cell line. The crane may be operated while the line is functioning. The controller installation is required to be. a. isolated and ungrounded c. isolated and ungrounded b. radio operated d. any of these 7. Receptacle outlets in floors shall not be counted as part of the required outlets unless located within of the wall. a. 18 in. (450 mm) b. 6 in. (150 mm) c. 12 in. (300 mm)

2 8. For motors with a service factor of 1.15, the overload relay may be set at of the motor full-load current. a. 125% b. 115 % c. 140% 9. Nine type THHN size 4 AWG copper conductors are to be run in Rigid Metal Conduit. The minimum trade size permitted is: a. 3/4 (21). b. 1 (27). c. 11/2 (41). d. 2 (53). e. 21/2 (63). 10. The supply voltage for electric vehicle charging equipment shall not be greater than: a. 120 volts. b. 240 volts. c. 480 volts A device box with cable clamps contains a 3-way switch and there is one Nonmetallic Sheathed Cable entering the box, Type NM-B 12/3 w.g. with three conductors and an equipment ground. The equivalent conductor count for the device box is: a. 3. b. 4. c. 5. d. 6. e A 50-kVA, 3-phase, 480/240-volt transformer has a full-load current of amperes on the secondary. a. 240 b. 360 c Taps to control transformers shall be considered as protected where the secondary circuit is protected by an overcurrent device rated or set at not more than of the rated secondary current of the transformer and not more than 200% of the ampacity of the control circuit conductors. a. 500% b. 300% c. 200% 14. An overhead feeder conductor supplies single-phase 120/240 volt power to a storage building from an office building at commercial property. If the feeder passes over a driveway used for truck traffic, the minimum clearance of the conductors over the drive is: a. 10 ft (3 m). b. 12 ft (3.7 m). c. 15 ft (4.5 m). d. 18 ft (5.5 m). e. 22 ft (6.7 m).

3 15. The continuous ampere rating of the runway conductor disconnecting means shall not be less than of the combined short-time ampere rating of the motors. a. 50% b. 75% c. 100% 16. A 480V/208Y/120V, 50-kVA transformer has a primary rated current of: a amperes. b amperes. c amperes Neon tubing and conductor must be supported not more than from the electrode connection. a. 12 in. (300 mm) b. 6 in. (150 mm) c. 24 in. (600 mm) 18. The conductor that is intentionally grounded is: a. service-entrance phase. b. transformer tap. c. neutral Individual partitions or groups of interconnected individual partitions shall not contain more than 15-ampere, 125-volt receptacle outlets. a. thirteen b. ten c. eight 20. The disconnecting means for a fire pump shall be a supervised connection. The disconnecting means shall be supervised in the closed position by: a. central station, proprietary, or remote signal device. b. local signaling device that causes sounding of an audible alarm signal at a constantly attended point. c. locking the disconnecting means in the closed position. d. any of the above. 21. The combined length of FMC, FMT, and LFMC in the same ground path must not exceed: a. 6 ft (1.8 m). b. 10 ft (3.0 m). c. 3 ft (900 mm). d. all of the above. 22. A 3-phase, alternating-current motor requires overload trip units in the motor controller. a. one b. two c. three

4 23. The electrical connection between freestanding-type partitions may be a extra-hard usage flexible cord with or larger conductors with an insulated grounding conductor. a. 14 AWG b. 12 AWG c. 16 AWG 24. An electrical system not required to be grounded is a: a. single-phase, 3-wire, 120/240 volt system. b. three-phase, 4-wire, 208/120 volt wye system. c. 240/120 volt, 4-wire, three-phase delta system. d. 480/277 volt, 4-wire, three-phase wye system serving 277 volt loads. e. 240 volt, three-phase, 3-wire delta system. 25. The motor full-load current of a 1/2-hP, single-phase, 230-volt alternating-current motor is: a. 4.9 amperes. b. 9.8 amperes. c. 5.4 amperes A 6 in. by 6 in. (150 mm by 150 mm) metal wireway has a 3 (78) trade size Electrical Metallic Tubing (EMT) entering from the bottom and a 2 (53) trade size EMT entering from the top and the two EMT entries are offset so the conductors make a 90 bend immediately upon entering the wireway. A set of size 2 AWG conductors pass directly from one EMT to the other. The two EMT entries are required to be separated from each other a distance of not less than: a. 6 in. (150 mm). b. 12 in. (300 mm). c. 14 in. (350 mm). d. 18 in. (450 mm). e. 2 ft. (600 mm). 27. A single-family dwelling has three bathrooms, each with a lighting fixture, a fan, and one receptacle outlet. Only in one bathroom, the lighting fixture, fan, and receptacle outlet are installed on a dedicated 20 ampere circuit. For this dwelling, the minimum number of 20 ampere circuits required to serve bathrooms is: a. two. b. three. c. four. d. five. e. not specified in the Code. 28. A 10-Hp motor with a marked service factor of 1.15 can develop horsepower without deterioration of the motor winding insulation. a. 11 b. 12 c A voltage meter with a voltage transformer having a 16 to 1 ratio, connected to a 480-volt line would read. a. 30 volts b. 50 volts c. 60 volts

5 30. What are minimum size service conductors for a computed load of kva on a 3-phase, 4-wire, 208Y/120-volt system? a. 1/0 AWG THW CU b. 350 kcmil THW CU c. 400 kcmil THW CU 31. Power sources for a Class 2 or a Class 3 circuit shall be a listed. a. auto transformer b. control transformer c. Class 2 or Class 3 transformer 32. Electrical equipment and wiring methods on rides or concessions must be provided with where such equipment or wiring is subject to physical damage. a. overcurrent protection b. mechanical protection c. double insulation d. all of the above 33. Where a transformer supplies an electric motor-driven fire pump, it must be rated at 125% of the fire pump motor and pressure maintenance pump motor load and of the associated fire pump accessory equipment supplied by the transformer. a. 100% b. 125% c. 115% 34. For transformers not in a supervised location over 600 volts with secondary voltage of 600 volts or below, the rating of a fuse or circuit breaker must not be more than of the transformer secondary rated current? a. 300% b. 2540% c. 125% 35. Where structural members do not readily permit fastening RMC within 3 ft (900 mm) of an outlet or junction box, fastening can be increased to a distance of. a. 5 ft (1.5 m) b. 10 ft (3.0 m) c. 8 ft (2.5 m) 36. If cord- and plug-connected equipment is used, the interrupting device of a listed personnel protection system shall be provided and shall be an integral part of the attachment plug or shall be located in the power supply cable not more than from the attachment plug. a. 12 in. (300 mm) b. 18 in. (450 mm c. 6 in. (150 mm) 37. The power source of a Class 1 remote-control or signaling circuit shall not be more than volts. a. 24 b. 600

6 c The distance of secondary circuit conductors, when installed in metal conduit, from the high voltage terminal of a transformer to the first neon tube electrode shall not exceed. a. 10 ft ( 7.5 m) b. 50 ft (15 m) c. 20 ft (6.0 m) 39. What is the demand factor percentage permitted to be used to size service-entrance conductors for 20 recreational vehicle sites? a. 60% b. 50% c. 45% 40. The sheath of nonmetallic cable must extend into a box not less than through a nonmetallic cable knockout opening. a. 1/8 in. (3.18 mm) b. 1/2 in. (12.7 mm) c. 1/4 in. (6 mm) d. 1/16 in. (1.6 mm) 41. A run of Intermediate Metal Conduit, IMC, contains three size 500 kcmil, THWN conductors and one size 3/0 AWG, THWN conductor. The minimum size IMC permitted for this installation is: a. 1 1/4 (35). b. 1 1/2 (41). c. 2 (53). d. 2 1/2 (63). e. 3 (78). 42. Amusement rides and amusement attractions must not be located under or within horizontally and extending vertically to grade of conductors operating in excess of 600 volts. a. 15 ft (4.5 m) b. 10 ft (3.0 m) c. 5 ft (1.5 m) 43. A commercial service entrance is rated at 200 amperes and the service entrance conductors are size 3/0 AWG copper with 75 C insulation and terminations. There is no metal underground water pipe entering the building, and the building does not have a metal frame. Two 8 ft (2.5 m) ground rods are driven into moist soil and bonded together to act as the grounding electrode for the building. The minimum size copper grounding electrode conductor permitted for this service is: a. 8 AWG. b. 6 AWG. c. 4 AWG. d. 3 AWG. e. 3/0 AWG. 44. Hallways measuring more than or more in length must have at least one receptacle outlet. a. 12 ft (3.7 m) b. 10 ft (3.0 m)

7 c. 8 ft (2.5 m) d. None of the above 45. The largest trade size flexible metal conduit permitted to be installed is: a. 1(27). b. 1 1/2 (41). c. 2 (53). d. 2 1/2 (63). e. 4 (103). 46. All circuit breakers having an interrupting rating other than amperes must be marked to show their interrupting rating. a. 100 b. 250 c. 10,000 d An unbroken length of kitchen counter along a wall in a dwelling is 10 ft (3.05 m) long. The counter extends from the edge of the sink for 4 ft (1.22 m), then makes a corner and continues for 6 ft (1.83 m) to the end of the counter at the refrigerator. The minimum number of receptacle outlets required on this length of wall space is: a. not specified and the number is up to the owner of the dwelling. b. one. c. two. d. three. e. four. 48. A receptacle outlet must be installed at each wall counter that is or wider. a. 36 in. (900 mm) b. 24 in. (600 mm) c. 12 in. (300 mm) d. 18 in. (450 mm) 49. A stand alone fuel cell system is connected to a premises wiring system. The output of the inverter is 120 volt and is connected to 120/240 volt, 3 wire distribution equipment. This output is allowed to supply_. a. multiwire branch circuits only c. 120 volt circuits only b. 240 volt circuits only d. all of these 50. For portable or mobile signs the ground-fault circuit-interrupter shall be an integral part of the attachment plug or be located in the power-supply cord within of the attachment plug. a. 12 in. (300 mm) b. 6 in. (150 mm) c. 24 in. (600 mm) 51. The conductor total cross-sectional area when the wires are run through a nipple is not permitted to exceed: a. 30% of the nipple cross-sectional area. b. 40% of the nipple cross-sectional area. c. 60% of the nipple cross-sectional area. d. 80% of the nipple cross-sectional area. e. 100% of the nipple cross-sectional area.

8 52. A transformer with an impedance of 2% would require a multiplier of to determine short-circuit current. a. 50 b. 35 c. 40

9 Spring Test 7 due 05/03/2013 Answer Section MULTIPLE CHOICE 1. ANS: B Adjustment factor of 0.8 for 6 wires in raceway - Table (B)(2)(b) Temperature correction factor of Table (B)(16) Ampacity of 6 AWG copper - 75 A - Table (B)(16) 75 A = 49.2 A 2. ANS: D (A) 3. ANS: B (A)(2) 4. ANS: C ANS: A Table 450.3(A) 6. ANS: D Article Special Requirements for Particular Locations,(C) Electrolytic Cell Lines, refers the to Cranes and Hoists. (B) Hazardous Electrical Conditions. Remote crane or hoist controls that could introduce hazardous electrical conditions into the cell line working zone shall employ one or more of the following systems: (1) Isolated and ungrounded control circuit in accordance with (A) (2) Nonconductive rope operator (3) Pendant pushbutton with nonconductive supporting means and having nonconductive surfaces or ungrounded exposed conductive surfaces (4) Radio 7. ANS: A (A)(3) 8. ANS: A 43032(A)(1)

10 9. ANS: C , Chapter 9 Note 1, Table C8 10. ANS: D ANS: E Wires 3 Grounds 1 Device 2 Clamps (A), Table (A) 12. ANS: C 50, ( ) = 120 amperes Ugly s/ferm s 13. ANS: C (A) 14. ANS: D ANS: A ANS: A 50,000 (50.0 kva) 830 ( ) = ANS: B (C) 18. ANS: D ANS: A 605.8(C)

11 20. ANS: D 695.4(B)(5) 21. ANS: A (6)(c) 22. ANS: C ANS: B ANS: E (B) 25. ANS: A Table ANS: D 6 3 in = 18 in 6 78 mm = 468 mm , (A)(2) 27. ANS: A One circuit for the bathroom where the light and fan are combined with the receptacle, and one circuit for the receptacle in the other two bathrooms (C)(3) 28. ANS: C Ugly s/ferm s 29. ANS: A Ugly s/ferm s 30. ANS: C 120,000 (120.0 kva) 360 ( ) = 333 amperes (Table (B)(16) 31. ANS: C

12 725.41(A)(1) 32. ANS: B ANS: A 695.5(A) 34. ANS: C Table 450.3(A) 35. ANS: A (A) 36. ANS: A ANS: B (B) 38. ANS: C (J)(1) 39. ANS: A Table ANS: C (C) 41. ANS: E 500 kcmil THWN in 2 = in 2 3/0 AWG THWN in 2 = in in kcmil THWN mm 2 = 1369 mm 2 3/0 AWG THWN mm 2 = _173 mm 2 Look up size in 40% fill column of Table 4 Chapter 9 Table 1, Table 5, Table mm 2

13 42. ANS: A 525.5(B)(2) 43. ANS: B (A) 44. ANS: B (H) 45. ANS: E (B) or Chapter 9, Table ANS: D (C) 47. ANS: D (C)(1) 48. ANS: C (C)(1) 49. ANS: C Stand-Alone Systems. (C) Single 120-Volt Nominal Supply. The inverter output of a stand-alone fuel cell system shall be permitted to supply 120 volts, nominal, to single-phase, 3-wire 120/240-volt service equipment or distribution panels where there are no 240-volt loads and where there are no multiwire branch circuits. In all installations, the rating of the overcurrent device connected to the output of the fuel cell system(s) shall be less than the rating of the service equipment. This equipment shall be marked as follows: 50. ANS: A (C)(2) REF: (C) 51. ANS: C Chapter 9, Note ANS: A Ugly s/ferm s

Spring Test 10 due 05/11/2013

Spring Test 10 due 05/11/2013 Spring Test 10 due 05/11/2013 Multiple Choice Identify the letter of the choice that best completes the statement or answers the question. 1. When installed in an agricultural building that houses livestock

More information

CHAPTER V RESIDENTIAL WIRING

CHAPTER V RESIDENTIAL WIRING CHAPTER V RESIDENTIAL WIRING 5.1. THE SERVICE ENTRANCE Buildings and other structures receive the electrical energy through the service entrance. In residential wiring, the electric company supply this

More information

Chapter 2 Wiring and Protection Article 200 Use and Identification of Grounded Neutral Conductor Chapter 1 General...9

Chapter 2 Wiring and Protection Article 200 Use and Identification of Grounded Neutral Conductor Chapter 1 General...9 Article 90 Introduction...1 90.1 Purpose of the NEC...1 90.2 Scope of the NEC...2 90.3 Code Arrangement...4 90.4 Enforcement...5 90.5 Mandatory Requirements and Explanatory Material...6 90.6 Formal Interpretations...6

More information

WIRING DESIGN & PROTECTION REQUIREMENTS CHECKLIST

WIRING DESIGN & PROTECTION REQUIREMENTS CHECKLIST WIRING DESIGN & PROTECTION REQUIREMENTS CHECKLIST Use & Identification of Grounded and Grounding Conductors YES NO N/A Grounded conductors are identifiable and distinguishable from all other conductors.

More information

Overcurrent Protection (2014 NEC) (Homestudy)

Overcurrent Protection (2014 NEC) (Homestudy) Overcurrent Protection (2014 NEC) (Homestudy) Oregon Electrical License The key sections of Article 240 will be discussed. Overcurrent protection for panelboards, appliances, motors, motor compressors,

More information

Electrical Tech Note 105 Agricultural Engineering Department Michigan State University

Electrical Tech Note 105 Agricultural Engineering Department Michigan State University Electrical Tech Note 105 Agricultural Engineering Department Michigan State University Journey Exam Study Guide and Sample Questions 1 Based on the 2002 NEC, Part 8 of PA 230, and the 2003 MRC The Journey

More information

CHAPTER 10 ELECTRICAL. Notes:

CHAPTER 10 ELECTRICAL. Notes: CHAPTER 10 ELECTRICAL 1001.0 General Requirements. Electrical wiring and equipment shall comply with the requirements of NFPA 70, National Electrical Code (NEC), or local ordinances. 1002.0 Solar Photovoltaic

More information

Western Section 101 st Annual Meeting Hot Springs, Arkansas September 21, 2005 Charlie Trout Code Breakfast

Western Section 101 st Annual Meeting Hot Springs, Arkansas September 21, 2005 Charlie Trout Code Breakfast Western Section 101 st Annual Meeting Hot Springs, Arkansas September 21, 2005 Charlie Trout Code Breakfast 1.Question: An add on unit for a hydromassage bathtub consists of a small 1-gallon water heater

More information

SINGLE PHASE WIRING SPECIFICATIONS

SINGLE PHASE WIRING SPECIFICATIONS SINGLE PHASE WIRING SPECIFICATIONS 1-866-MEC-ELEC (1-866-632-3532) Office Locations: Hondo Office 237 Hwy 173 N Hondo, TX 78661-0370 Fax 830.426.3335 Dilley Office 1718 W. FM 117 Dilley, TX 78017 Fax 830.965.1425

More information

PART A General Conductor Requirements

PART A General Conductor Requirements PART A General Conductor Requirements 6.1 Conductor Insulation Property Table 310.13 of the NEC provides information on conductor properties such as permitted use, maximum operating temperature, and other

More information

THREE PHASE WIRING SPECIFICATIONS

THREE PHASE WIRING SPECIFICATIONS THREE PHASE WIRING SPECIFICATIONS 1-866-MEC-ELEC (1-866-632-3532) Office Locations: Hondo Office 237 Hwy 173 N Hondo, TX 78661-0370 Fax 830.426.3335 Dilley Office 1718 W. FM 117 Dilley, TX 78017 Fax 830.965.1425

More information

Chapter 1 Electrical Theory...1

Chapter 1 Electrical Theory...1 Electrical Formulas with Sample Calculations Table of Contents Chapter 1 Electrical Theory...1 Unit 1 Electrician s Math and Basic Electrical Formulas...3 Part A Electrician s Math...3 1 1 Fractions...3

More information

SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS - ELECTRICAL

SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS - ELECTRICAL SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS - ELECTRICAL This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly.

More information

This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly.

This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly. SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS (ELEC) This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly.

More information

Have You Been Grounded Lately

Have You Been Grounded Lately Have You Been Grounded Lately Thurs, Oct. 26, 2017 9:15-10:15 Phil Simmons Author, Electrical Grounding and Bonding Author Cengage Learning Phil Simmons Have You Been Grounded Lately 2017 NEC Changes Relative

More information

Overcurrent Protection According to the 2011 NEC

Overcurrent Protection According to the 2011 NEC Overcurrent Protection According to the 2011 NEC Utah Electrical License This course will cover overcurrent protection according to the 2011 NEC. The key sections of Article 240 will be discussed. Overcurrent

More information

Electrical Tech Note 106

Electrical Tech Note 106 Electrical Tech Note 106 Biosystems & Agricultural Engineering Department Michigan State University Master Exam Study Guide and Sample Questions 1 Based on the 2014 NEC, Part 8 of PA 230, PA 407, and the

More information

TEMPORARY ELECTRIC WIRING FOR CARNIVALS, CONVENTIONS, EXHIBITIONS, FAIRS AND SIMILAR USES

TEMPORARY ELECTRIC WIRING FOR CARNIVALS, CONVENTIONS, EXHIBITIONS, FAIRS AND SIMILAR USES INFORMATION BULLETIN / PUBLIC - ELECTRICAL CODE REFERENCE NO.: LAMC 93.0230 Effective: 3-24-69 DOCUMENT NO. P/EC 2002-006 Revised: 11-17-00 Previously Issued As: RGA #7-69 TEMPORARY ELECTRIC WIRING FOR

More information

ADVANCED CALCULATIONS

ADVANCED CALCULATIONS ADVANCED CALCULATIONS 101. Why is it permissible in some cases to fuse a #14 AWG motor conductor with a 60 amp breaker when normally a #14 AWG should only be fused at 15 amps? a) the motor can't start

More information

2016 Photovoltaic Solar System Plan Review List

2016 Photovoltaic Solar System Plan Review List Building Division 555 Santa Clara Street Vallejo CA 94590 707.648.4374 2016 Photovoltaic Solar System Plan Review List GENERAL PROJECT INFORMATION PLAN CHECK NO DATE JOB ADDRESS CITY ZIP REVIEWED BY PHONE

More information

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 2/8/12 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 2/8/12 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions MECKLENBURG COUNTY Land Use and Environmental Service Agency Code Enforcement 2/8/12 ELECTRICAL CONSISTENCY MEETING Code Consistency Questions 1. I am inspecting a building addition. They have a 480V to

More information

Photovoltaic Solar Plan Review

Photovoltaic Solar Plan Review PAIGE B. VAUGHAN, CBO Director of Building and Safety Phone (310) 605-5509 Fax Line (310) 605-5598 E-mail:lbutler@comptoncity.org Building & Safety Department Photovoltaic Solar Plan Review Plan Check

More information

Pretest Module 24 Three-phase Service Entrance

Pretest Module 24 Three-phase Service Entrance Pretest Module 24 Three-phase Service Entrance 1. What is the most widely used three-phase service entrance system? 2. What are the three most common voltage combinations for three-phase, four-wire systems?

More information

Mecklenburg County Common Code Defects

Mecklenburg County Common Code Defects Electrical Code Defects Improper Over Current Protection Code Description 310.15 Ampacities for s Rated 0 2000 Volts. (A) General. (1) Tables or Engineering Supervision. Ampacities for conductors shall

More information

90.2 Scope. The installation of electrical conductors, equipment and raceways for:

90.2 Scope. The installation of electrical conductors, equipment and raceways for: NEC Generator Primer Rules on the installation of generators and transfer switches 1 90.2 Scope The installation of electrical conductors, equipment and raceways for: public and private premises Conductors

More information

TABLE OF CONTENTS CHAPTER 1 ELECTRICAL THEORY About This Textbook...xi. Passing Your Exam...xiv. How to Use the National Electrical Code...

TABLE OF CONTENTS CHAPTER 1 ELECTRICAL THEORY About This Textbook...xi. Passing Your Exam...xiv. How to Use the National Electrical Code... TABLE OF CONTENTS About This Textbook...xi Passing Your Exam...xiv How to Use the National Electrical Code... 1 CHAPTER 1 ELECTRICAL THEORY... 7 Unit 1 Electrician s Math and Basic Electrical Formulas...

More information

UNIT 1 ELECTRICIAN S MATH AND BASIC ELECTRICAL FORMULAS...1 Introduction...1. UNIT 2 ELECTRICAL CIRCUITS...49 Introduction...49

UNIT 1 ELECTRICIAN S MATH AND BASIC ELECTRICAL FORMULAS...1 Introduction...1. UNIT 2 ELECTRICAL CIRCUITS...49 Introduction...49 UNIT 1 ELECTRICIAN S MATH AND BASIC ELECTRICAL FORMULAS...1 Introduction...1 PART A ELECTRICIAN S MATH...1 Introduction...1 1.1 Whole Numbers...1 1.2 Decimal...1 1.3 Fractions...1 1.4 Percentages...2 1.5

More information

(The actual state exam will be closer to 50 questions in 4 hours time) Master Electrician Practice Test

(The actual state exam will be closer to 50 questions in 4 hours time) Master Electrician Practice Test (The actual state exam will be closer to 50 questions in 4 hours time) Master Electrician Practice Test 1. Accessible as applied to wiring methods means capable of being removed or exposed without damaging

More information

NEC 2014 Code Changes

NEC 2014 Code Changes NEC 2014 Code Changes Articles 310 310.120 CHANGES FROM 2011 TO 2014 CODE ARE IN RED ARTICLE 310 Conductors for General Wiring I. General 310.2 Definitions Electrical Ducts Electrical conduits, or other

More information

Table of Contents. Unit 3 Magnetism Unit 1 Matter Unit 4 Electricity Unit 2 Electron Theory Unit 5 Electromagnetism...

Table of Contents. Unit 3 Magnetism Unit 1 Matter Unit 4 Electricity Unit 2 Electron Theory Unit 5 Electromagnetism... Introduction...x How to Use This Textbook...xi About the Author...xii About the Graphic Illustrator...xiii Mike Holt Enterprises Team...xiv Chapter 1 Electrical Fundamentals... 1 Unit 1 Matter... 3 Introduction...

More information

2011 NEC Code Updates Part 3

2011 NEC Code Updates Part 3 www.garyklinka.com Page 1 of 22 Instructions: Fee $35 1. Print these pages. 2. Circle the correct answers and transfer them to the answer sheet. 3. Page down to the last page for the verification forms

More information

SECTION 1: Field Inspection Guide for Rooftop Photovoltaic (PV) Systems

SECTION 1: Field Inspection Guide for Rooftop Photovoltaic (PV) Systems COUNTY OF SANTA CRUZ PLANNING DEPARTMENT 701 OCEAN STREET, 4 th FLOOR, SANTA CRUZ, CA 95060 (831) 454-2580 FAX: (831) 454-2131 TDD: (831) 454-2123 KATHLEEN MOLLOY PREVISICH, PLANNING DIRECTOR Photovoltaic

More information

TABLE OF CONTENTS. About the Mike Holt Enterprises Team... xviii CHAPTER 1 ELECTRICAL THEORY... 1

TABLE OF CONTENTS. About the Mike Holt Enterprises Team... xviii CHAPTER 1 ELECTRICAL THEORY... 1 TABLE OF CONTENTS Introduction...xv About the Mike Holt Enterprises Team... xviii CHAPTER 1 ELECTRICAL THEORY... 1 Unit 1 Electrician s Math and Basic Electrical Formulas... 1 Part A Electrician s Math...

More information

ARKANSAS ELECTRICIANS

ARKANSAS ELECTRICIANS CONTINUING EDUCATION FOR ARKANSAS ELECTRICIANS 2014 NEC Code Change 8 Hours AMERICAN ELECTRICAL INSTITUTE N16 W23217 Stone Ridge Drive, Suite 290 Waukesha, WI 53188 855-780-5046 www.aeitraining.com DISCLAIMER

More information

Electrical Tech Note 111 Biosystems & Agricultural Engineering Department Michigan State University

Electrical Tech Note 111 Biosystems & Agricultural Engineering Department Michigan State University Electrical Tech Note 111 Biosystems & Agricultural Engineering Department Michigan State University Electrical Code Changes in Michigan 1 (Based on Part 8, P.A. 230, the 2005 NEC and the 2003 MRC) This

More information

Preface...x Chapter 1 Electrical Fundamentals

Preface...x Chapter 1 Electrical Fundamentals Preface...x Chapter 1 Electrical Fundamentals Unit 1 Matter...3 Introduction...3 1.1 Matter...3 1.2 Atomic Theory...3 1.3 Law of Electrical Charges...4 1.4 Law of Atomic Charges...5 Negative Atomic Charge...5

More information

Electrical Design/Build Guide

Electrical Design/Build Guide 2017 Electrical Design/Build Guide Based on the 2017 National Electrical Code Copyright Durand & Associates 1986-2016 60 C Copper Ampacity 4 - Wire Fill - (Non-Current Carrying Neutral) 4 or 5 - Parallel

More information

CHAPTER 10 ELECTRICAL

CHAPTER 10 ELECTRICAL 1001.0 General Requirements. 1001.1 Electrical Wiring and Equipment. Electrical wiring and equipment shall comply with the requirements of NFPA 70, National Electrical Code (NEC), or local ordinances.

More information

Definitions of and have been revised. a. automatic b. nonautomatic c. none of the above d. both a and b

Definitions of and have been revised. a. automatic b. nonautomatic c. none of the above d. both a and b www.garyklinka.com Page 1 of 12 Instructions: Fee $25 1. Print these pages. 2. Circle the correct answers and transfer them to the answer sheet. 3. Page down to the last page for the verification forms

More information

Western Section IAEI Code Panel Questions

Western Section IAEI Code Panel Questions Western Section IAEI 2013 Code Panel Questions 1. Do the factory wings that many fluorescent troffers have designed to fold out over the grid meet the requirements for securely fastened to the framing?

More information

PHOTOVOLTAIC ELECTRICAL POWER SYSTEMS INSPECTOR/INSTALLER CHECKLIST

PHOTOVOLTAIC ELECTRICAL POWER SYSTEMS INSPECTOR/INSTALLER CHECKLIST PHOTOVOLTAIC ELECTRICAL POWER SYSTEMS INSPECTOR/INSTALLER CHECKLIST The following checklist is an outline of the general requirements found in the 2005 National Electrical Code (NEC) Article 690 for Photovoltaic

More information

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 9/14/11 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 9/14/11 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions MECKLENBURG COUNTY Land Use and Environmental Service Agency Code Enforcement 9/14/11 ELECTRICAL CONSISTENCY MEETING Code Consistency Questions 1. I recently installed a 45-KVA transformer, 480-volt primary

More information

The Reliable Choice. Field Pocket Guide

The Reliable Choice. Field Pocket Guide The Reliable Choice Field Pocket Guide Allowable Ampacities of STABILOY Brand XHHW-2 and Copper 75 C (167 F) 90 C (194 F) 75 C (167 F) 90 C (194 F) Conductor Size (AWG or kcmil) Types RHW, THHW, THW, THWN,

More information

Table of Contents. CHAPTER 1 BASIC ELECTRICAL THEORY (Essential for Journeyman and Master s Licensing Exams)... 1

Table of Contents. CHAPTER 1 BASIC ELECTRICAL THEORY (Essential for Journeyman and Master s Licensing Exams)... 1 Introduction... x About This Textbook...xi Passing Your Exam...xiv How to Use the National Electrical Code... xviii About the Author...xxi About the Graphic Illustrator...xxii Mike Holt Enterprises Team...

More information

Chapter 8 Interior Wiring and Lighting

Chapter 8 Interior Wiring and Lighting Chapter 8 Interior Wiring and Lighting Review Questions 1. What tool if any, is used to remove a fuse that is to be replaced? 1. Pliers 2. Screwdriver 3. Fuse puller 4. None 2. OSHA has established specific

More information

NEC 2011 Code Changes

NEC 2011 Code Changes NEC 2011 Code Changes Articles 280.21-300.50 CHANGES FROM 2008 TO 2011 CODE ARE IN RED Chapter 2 - Wiring and Protection ARTICLE 280 Surge Arresters, Over 1kV III. Connecting Surge Arresters 280.21 Connection

More information

2. DEFINITIONS. 2.3 APPROVED Acceptable to the authority enforcing the National Electric Code

2. DEFINITIONS. 2.3 APPROVED Acceptable to the authority enforcing the National Electric Code 2. DEFINITIONS 2.1 ACCEPTABLE Acceptable to the Company. 2.2 ADVANCED METER A meter that is capable of remote reading, and is capable of storing electric consumption data at specified time intervals of

More information

SERVICE ATTACHMENT ON A BUILDING WITH BUS DUCT SERVICE ENTRANCE AND INDOOR METERING

SERVICE ATTACHMENT ON A BUILDING WITH BUS DUCT SERVICE ENTRANCE AND INDOOR METERING SERVICE ATTACHMENT ON A BUILDING WITH BUS DUCT SERVICE ENTRANCE AND INDOOR METERING Obtain acceptance and specific details from the local Company office. 1. Service entrance duct (see Note 1). Company

More information

Table of Contents. CHAPTER 1 ElECTRiCAl THEoRY Mike Holt enterprises, inc neC.Code ( )

Table of Contents. CHAPTER 1 ElECTRiCAl THEoRY Mike Holt enterprises, inc neC.Code ( ) CHAPTER 1 ElECTRiCAl THEoRY... 1 UniT 1 electrician s MaTH and BasiC electrical formulas... 3 Introduction to Unit 1... 3 Part A Electrician s Math... 3 Introduction... 3 1.1 Whole Numbers... 3 1.2 Decimals...

More information

Western Section IAEI Code Panel Questions

Western Section IAEI Code Panel Questions Western Section IAEI 2013 Code Panel Questions 1. Do the factory wings that many fluorescent troffers have designed to fold out over the grid meet the requirements for securely fastened to the framing?

More information

Chapter 5. Imagine That Engineering Inc. Assured Equipment Grounding Conductor Program (AEGCP) Ground Fault Circuit Interrupter (GFCI)

Chapter 5. Imagine That Engineering Inc. Assured Equipment Grounding Conductor Program (AEGCP) Ground Fault Circuit Interrupter (GFCI) Chapter 5 Imagine That Engineering Inc. Assured Equipment Grounding Conductor Program (AEGCP) Ground Fault Circuit Interrupter (GFCI) Imagine That Engineering Inc. has adopted this program for equipment

More information

Generator Fire Safety: Generator assemblies should be located outside the building.

Generator Fire Safety: Generator assemblies should be located outside the building. SECTION 33 70 00 - ELECTRICAL DISTRIBUTION PACKAGED GENERATOR ASSEMBLIES Generator Fire Safety: Generator assemblies should be located outside the building. All fuel piping from the outside of the building

More information

SECTION 300 OVERHEAD SERVICE

SECTION 300 OVERHEAD SERVICE SECTION 300 OVERHEAD SERVICE 300.01 General Company provides, installs, and maintains service drop to point of delivery approved by Company. Customer provides point of attachment which is acceptable to

More information

SOLAR PHOTOVOLTAIC SYSTEMS INSPECTOR CHECKLIST

SOLAR PHOTOVOLTAIC SYSTEMS INSPECTOR CHECKLIST SOLAR PHOTOVOLTAIC SYSTEMS INSPECTOR CHECKLIST The following checklist is an outline of the general requirements found in the 1999 National Electrical Code (NEC) Article 690 for Photovoltaic (PV) Power

More information

Corrections most seen on plan review October 18, 2017 David Rankin Seattle Department of Construction and Inspections

Corrections most seen on plan review October 18, 2017 David Rankin Seattle Department of Construction and Inspections Corrections most seen on plan review October 18, 2017 David Rankin Seattle Department of Construction and Inspections One-Line / Riser Diagrams Drawings are not reviewed prior to submission. Because of

More information

grounded in service wired to innovate STABILOY Type XHHW-2 and USE-2/RHH/RHW-2

grounded in service wired to innovate STABILOY Type XHHW-2 and USE-2/RHH/RHW-2 grounded in service wired to innovate STABILOY Type XHHW-2 and USE-2/RHH/RHW-2 grounded in service wired to innovate www.cable.alcan.com Type XHHW-2 and Type USE-2/RHH/RHW-2 Alcan manufactures XHHW-2 and

More information

SECTION LOW VOLTAGE DISTRIBUTION EQUIPMENT

SECTION LOW VOLTAGE DISTRIBUTION EQUIPMENT SECTION 16400 LOW VOLTAGE DISTRIBUTION EQUIPMENT A. General 1. The University does not accept Series-Rated equipment for power distribution switchboards, distribution panels and branch circuit panelboards.

More information

ROCKY MOUNTAIN CHAPTER IAEI MARCH 15-16, 2012

ROCKY MOUNTAIN CHAPTER IAEI MARCH 15-16, 2012 ROCKY MOUNTAIN CHAPTER IAEI MARCH 15-16, 2012 1) Can a switched outlet be on a small appliance branch circuit for dining room lighting? No, a switched outlet on a general purpose branch circuit may be

More information

2014 NEC Changes Part 4

2014 NEC Changes Part 4 www.garyklinka.com Page 1 of 14 Instructions: Fee $25 1. Print these pages. 2. Circle the correct answers and transfer them to the answer sheet. 3. Page down to the last page for the verification forms

More information

9/16/2010. Chapter , The McGraw-Hill Companies, Inc. TRANSMISSION SYSTEMS. 2010, The McGraw-Hill Companies, Inc.

9/16/2010. Chapter , The McGraw-Hill Companies, Inc. TRANSMISSION SYSTEMS. 2010, The McGraw-Hill Companies, Inc. Chapter 3 TRANSMISSION SYSTEMS 1 Transmitting large amounts of electric energy over long distances is accomplished most efficiently by using high-voltages. Without transformers the widespread distribution

More information

Solar PV Standard Electrical Plan

Solar PV Standard Electrical Plan *** Provide this document to the inspector along with ALL system installation instructions *** Project Address: Permit Number: SCOPE: Standard plan for installation of solar PV systems utilizing 2 wire

More information

Volume 2 Charts, Formulas, and Other Useful Information

Volume 2 Charts, Formulas, and Other Useful Information Volume 2 Charts, Formulas, and Other Useful Information Aluminum Conductor Conductor Terminations 61 Compact Aluminum (Conduit Fill Tables) 68-79 Ampacity Dwelling Services 48 1-phase Loads on a 3-phase

More information

EV Charging Station Submittal Requirements

EV Charging Station Submittal Requirements EV Charging Station Submittal Requirements To obtain a permit for an Electric Vehicle Charging Station, please provide the following: Plan and details of the charging system installation o Print applicable

More information

Fee $20 Course: NEC Changes 1 This course is valid for these credentials: Credential Description Cred Code Credit Hours

Fee $20 Course: NEC Changes 1 This course is valid for these credentials: Credential Description Cred Code Credit Hours www.garyklinka.com Page 1 of 18 Instructions: Fee $20 1. Print these pages. 2. Circle the correct answers and transfer them to the answer sheet. 3. Page down to the last page for the verification forms

More information

201 S. Anaheim Blvd. Page No Anaheim, CA RULE NO. 2 DESCRIPTION OF SERVICE

201 S. Anaheim Blvd. Page No Anaheim, CA RULE NO. 2 DESCRIPTION OF SERVICE 201 S. Anaheim Blvd. Page No. 3.2.1 A. GENERAL 1. The character of electric service available at any particular location should be ascertained by inquiry at the City's Electrical Engineering Division office.

More information

10 Commercial, Industrial, Agricultural Services

10 Commercial, Industrial, Agricultural Services 10 Commercial, Industrial, Agricultural Services This section describes the Power Company requirements for commercial, industrial, and agricultural services. This section covers single phase and three

More information

9/7/2010. Objectives. Article 90. Introduction NEC Significant Changes. Review significant revisions in the 2011 NEC

9/7/2010. Objectives. Article 90. Introduction NEC Significant Changes. Review significant revisions in the 2011 NEC 2011 NEC Significant Changes Courtesy of NJATC Courtesy of NFPA Presented By: Michael J. Johnston Executive Director of Standards and Safety, NECA Objectives Review significant revisions in the 2011 NEC

More information

An average of one worker is electrocuted on the job every day There are four main types of electrical injuries:

An average of one worker is electrocuted on the job every day There are four main types of electrical injuries: Electrical Safety Introduction An average of one worker is electrocuted on the job every day There are four main types of electrical injuries: Electrocution (death due to electrical shock) Electrical shock

More information

City of Walnut Creek Development Review Services 1666 N. Main Street, Walnut Creek, CA (925) phone (925) fax

City of Walnut Creek Development Review Services 1666 N. Main Street, Walnut Creek, CA (925) phone (925) fax City of Walnut Creek Development Review Services 1666 N. Main Street, Walnut Creek, CA 94596 (925) 943-5834 phone (925) 256-3500 fax Issued September 30, 2017 Policy Bulletin No. PB-72 Background Residential

More information

Section 6 Electric Metering: Residential

Section 6 Electric Metering: Residential Section 6 Electric Metering: Residential 6.1. Scope This section provides specific information for residential metering that is not covered by the basic requirements in Section 5, Electric Metering: General.

More information

SOLAR PV STANDARD PLAN - COMPREHENSIVE Central/String Inverter Systems for One and Two Family Dwellings

SOLAR PV STANDARD PLAN - COMPREHENSIVE Central/String Inverter Systems for One and Two Family Dwellings SCOPE: Use this plan ONLY for utility-interactive central/string inverter systems not exceeding a total combined system ac inverter output rating of 10kW on the roof of a one- or two-family dwelling or

More information

2000 Cooper Bussmann, Inc. Page 1 of 9 10/04/00

2000 Cooper Bussmann, Inc. Page 1 of 9 10/04/00 DO YOU KNOW THE FACTS ABOUT SINGLE-POLE INTERRUPTING RATINGS? YOU MAY BE IN TROUBLE! Typical plant electrical systems use three-phase distribution schemes. As an industry practice, short-circuit calculations

More information

2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE

2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE 2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE PAGE 1 OF 5 This Reference provides a very comprehensive list of aspects of a solar PV installation that could be reviewed, clarifying

More information

Code Calculations. for an Off-Grid PV System

Code Calculations. for an Off-Grid PV System Code Calculations for an Off-Grid PV System John Wiles Sponsored by the Photovoltaic Systems Assistance Center, Sandia National Laboratories Judy LaPointe s home is on its way to becoming a finished, off-grid

More information

2014 NEC Update RV

2014 NEC Update RV PLEASE DO NOT BOOKMARK ANY ANYTIMECE WEBPAGES! Our system will remember the last page you viewed when logging out and back in but please DO NOT exit out when taking a test. Your place will NOT be saved.

More information

Continued from Part 2 Rules

Continued from Part 2 Rules Continued from Part 2 Rules 26 50. 51 250.94 Grounding (Bonding) of Communications Systems An accessible bonding point must be provided at service equipment or the disconnecting means of separate buildings

More information

2011 NEC Changes Part 2 (Homestudy) (Homestudy)

2011 NEC Changes Part 2 (Homestudy) (Homestudy) 2011 NEC Changes Part 2 (Homestudy) (Homestudy) North Carolina Electrical License This course will review the second half of the most important National Electrical Code changes from the 2011 NEC. Changes

More information

2014 NEC Changes Part 1 (Homestudy)

2014 NEC Changes Part 1 (Homestudy) 2014 NEC Changes Part 1 (Homestudy) Wisconsin Electrical License This course will review the first half of the most important National Electrical Code changes from the 2014 NEC. Changes in Articles 100-404.2

More information

Electrical Safety. Electrical Safety Webinar. Electrical. Printing Industries Alliance Printing Industries Alliance 1

Electrical Safety. Electrical Safety Webinar. Electrical. Printing Industries Alliance Printing Industries Alliance 1 Webinar 1 Electrical 2 1 Webinar Introduction An average of one worker is electrocuted on the job every day There are four main types of electrical injuries: Electrocution (death due to electrical shock)

More information

INSPECTION REQUIREMENTS: PHOTOVOLTAIC (PV) RESIDENTIAL

INSPECTION REQUIREMENTS: PHOTOVOLTAIC (PV) RESIDENTIAL Photovoltaic (PV) Residential Page 1 of 10 Revision Date: 07/18/2018 INSPECTION REQUIREMENTS: PHOTOVOLTAIC (PV) RESIDENTIAL INSPECTION CODE: 703 SCOPE: RESIDENTIAL APPLICABLE CODES: 2016 CBC, CRC, CPC,

More information

City of Perris Development Services Building & Safety

City of Perris Development Services Building & Safety Western Riverside County Code Uniformity Program City of Perris Development Services Building & Safety Residential Electric Vehicle (EV) Charger Guidelines PHONE NUMBER 951-943-5003 Inspection Request

More information

Pentahead bolts See note 2. Conduit run as specified. Company facility. Refer to drawing SS8.6-2 or SS8.6-3 STANDARD SERVICE INSTALLATION

Pentahead bolts See note 2. Conduit run as specified. Company facility. Refer to drawing SS8.6-2 or SS8.6-3 STANDARD SERVICE INSTALLATION PULL BOX F SECONDARY SYSTEM Typical grade Pentahead bolts See note 2 Conduit run as specified Plastic or fiberglass for grass areas or Polymer concrete for light duty areas (see notes 2, 3, & 4) Company

More information

Solar PV Standard Electric Plan

Solar PV Standard Electric Plan *** Provide this document to the inspector along with ALL system installation instructions *** SCOPE: Standard plan for the installation of microinverter solar PV systems, not exceeding a total AC output

More information

2011 NEC Significant Changes Part 1 The following course will summarize many of the important changes to the NEC code.

2011 NEC Significant Changes Part 1 The following course will summarize many of the important changes to the NEC code. 2 PART 1 American Electrical Institute 2013 2011 NEC Significant Changes Part 1 The following course will summarize many of the important changes to the NEC code. The 2011 Code has added 3 new articles:

More information

DEWALT Electrical Licensing Exam Guide CONTENTS

DEWALT Electrical Licensing Exam Guide CONTENTS DEWALT Electrical Licensing Exam Guide v ONTENTS How to Prepare for the Exam................................................ 2 How to Study.............................................................

More information

ECET Circuit Design Motor Loads. Branch Circuits. Article 210

ECET Circuit Design Motor Loads. Branch Circuits. Article 210 ECET 4520 Industrial Distribution Systems, Illumination, and the NEC Circuit Design Motor Loads Branch Circuits Article 210 210.1 Scope This article covers branch circuits except for those that supply

More information

TRANSMISSION SYSTEMS

TRANSMISSION SYSTEMS TRANSMISSION SYSTEMS Transmitting large amounts of electric energy over long distances is accomplished most efficiently by using high-voltages. Without transformers the widespread distribution of electric

More information

ELECTRICAL. 60 Minutes

ELECTRICAL. 60 Minutes ELECTRICAL 60 Minutes AGENDA Electrical definitions Electrical shocks, burns and secondary injuries Electrical hazards in the workplace Safety devices and prevention steps Do s and Don ts INTRODUCTORY

More information

2014 NEC Changes (Homestudy)

2014 NEC Changes (Homestudy) 2014 NEC Changes (Homestudy) Idaho Electrical License This course will review the most important National Electrical Code changes from the 2014 NEC. Changes in Articles 100 - Chapter 9 will be covered.

More information

9. Non-Residential Services (Commercial, Industrial, and Agricultural)

9. Non-Residential Services (Commercial, Industrial, and Agricultural) Section 9 2016 Electric Service Requirements, 3rd Edition Section 9 Non-Residential Services Directory Page 9.1 General Requirements 68 9.2 Direct-Connect Metering, Single Installations 69 9.3 Direct-Connect

More information

Service Entrance Methods

Service Entrance Methods Service Section Typical switchboards consist of a service section, also referred to as the main section, and one or more distribution sections. The service section can be fed directly from the utility

More information

WISCONSIN ELECTRICIANS

WISCONSIN ELECTRICIANS Wisconsin Contractors Institute 2017 PART 2 3 CONTINUING EDUCATION FOR WISCONSIN ELECTRICIANS 2017 NEC Code Change Part 2 8 Hours WISCONSIN CONTRACTORS INSTITUTE N16 W23217 Stone Ridge Drive, Suite 290

More information

CONTINUING EDUCATION FOR OREGON ELECTRICIANS NEC Code Change Part 2 Course # Hours

CONTINUING EDUCATION FOR OREGON ELECTRICIANS NEC Code Change Part 2 Course # Hours AMERICAN ELECTRICAL INSTITUTE 2017 PART 2 3 CONTINUING EDUCATION FOR OREGON ELECTRICIANS 2017 NEC Code Change Part 2 Course #90817 8 Hours AMERICAN ELECTRICAL INSTITUTE N16 W23217 Stone Ridge Drive, Suite

More information

See Part 3 for the Introduction for Article 314

See Part 3 for the Introduction for Article 314 See Part 3 for the Introduction for Article 314 76 314.25 Covers and Canopies When the installation is complete, each outlet box must be provided with a cover or faceplate, unless covered by a fixture

More information

Installing a Downstream Distribution Panelboard

Installing a Downstream Distribution Panelboard Job Sheet 5 Installing a Downstream Distribution Panelboard OBJECTIVE To install a downstream distribution panelboard (DDP) on the Mobile Workstation. To mechanically and electrically connect the DDP to

More information

Permitting, Installation and Inspection Residential EV Chargers Be aware that there are different types of Electric Vehicle (EV) Chargers.

Permitting, Installation and Inspection Residential EV Chargers Be aware that there are different types of Electric Vehicle (EV) Chargers. Be aware that there are different types of Electric Vehicle (EV) Chargers. There are 2 basic types of EV chargers for home use (Level 1 and Level 2). Level 1 Chargers are smaller units that plug directly

More information

CONTINUING EDUCATION FOR OREGON ELECTRICIANS NEC Code Change Part 1 8 Hours

CONTINUING EDUCATION FOR OREGON ELECTRICIANS NEC Code Change Part 1 8 Hours AMERICAN ELECTRICAL INSTITUTE 2017 PART 1 3 CONTINUING EDUCATION FOR OREGON ELECTRICIANS 2017 NEC Code Change Part 1 8 Hours AMERICAN ELECTRICAL INSTITUTE PO Box 31131 Spokane, WA 99223 855-780-5046 www.aeitraining.com

More information

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 03/05/09 TSEWG TP-11: UFC N BEST PRACTICES

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 03/05/09 TSEWG TP-11: UFC N BEST PRACTICES TSEWG TP-11: UFC 3-500-10N BEST PRACTICES UFC 3-500-10N was developed by NAVFAC and was used as the starting point for the tri-services development of UFC 3-500-10, Design: Electrical Engineering. UFC

More information

COUNTY OF RIVERSIDE BUILDING AND SAFETY DEPARTMENT

COUNTY OF RIVERSIDE BUILDING AND SAFETY DEPARTMENT COUNTY OF RIVERSIDE BUILDING AND SAFETY DEPARTMENT RESIDENTIAL ELECTRIC VEHICLE (EV) CHARGER GUIDELINES Mike Lara Director The purpose of this guideline is to assist permit applicants in streamlining the

More information

COMMERCIAL QUICK REFERENCE

COMMERCIAL QUICK REFERENCE COMMERCIAL QUICK REFERENCE PROVO CITY POWER STANDARDS ELECTRICAL ENGINEERING UPDATED: 2016 SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTIFICATION. 18" MIN. OF TAIL. (NEUTRAL CONDUCTOR MUST BE WHITE OR

More information