Spring Test 10 due 05/11/2013

Size: px
Start display at page:

Download "Spring Test 10 due 05/11/2013"

Transcription

1 Spring Test 10 due 05/11/2013 Multiple Choice Identify the letter of the choice that best completes the statement or answers the question. 1. When installed in an agricultural building that houses livestock the wiring material that is not permitted be installed is: 1) type MC cable. 2) hard usage cords when flexibility is necessary. 3) liquidtight flexible nonmetallic conduit. 4) type UF cable. 5) type AC cable. 2. A motor controller is installed in a Class II, Division 1 hazardous location and the enclosure for the controller is rated NEMA 9, dust-ignition-proof. A horizontal run of rigid metal conduit supplies power to the controller from a junction box that contains only conductor splices and the box is designed to prevent the entrance of dust, but does not have a dust-ignition-proof rating. Both the junction box and the controller have threaded hubs, and both are in the Class II, Division 1 area. This installation is permitted provided the horizontal run of conduit between the box and controller is not less than: 1) 18 in. (450 mm). 2) 3 ft (900 mm). 3) 5 ft (1.5 m). 4) 10 ft (3 m). 5) 12 ft (3.7 m). 3. CATV cable from a community antenna system is installed underground to a single-family dwelling. An additional grounding electrode is required to be installed when the grounding electrode conductor connecting the shield of the cable to the electrical system grounding electrode is longer than: 1) 6 ft. (1.8 m). 2) 10 ft. (3 m). 3) 20 ft. (6 m). 4) 25 ft. (7.5 m). 5) 50 ft. (15 m). 4. If Electrical Nonmetallic Tubing is to be used for a whip from a metal box to a fluorescent luminaire in a suspended ceiling, the: 1) space above the ceiling shall be used for environmental air. 2) ceiling shall have a 15-minute finish rating. 3) ceiling shall have a 1-hour finish rating. 4) ENT shall not be installed in lengths greater than 3 ft. 5) circuit rating shall not exceed 15 amperes. 5. A 25 kva transformer is installed on an ungrounded delta 240 volt 3-phase electrical system to supply a 100 ampere 120/240 volt single-phase electrical system, because there is no 120 volt power in the building. The conductor supplying the transformer is size 8 AWG copper protected on the supply end with a 50 ampere circuit breaker. The conductor leading away from the transformer is size 3 AWG copper ending at a single 100 ampere circuit breaker. The maximum distance permitted from the transformer to the 100 ampere circuit breaker is: 1) 10 ft (3 m). 2) 20 ft (6 m). 3) 25 ft (7.5 m). 4) 50 ft (15 m). 5) 75 ft (22.5 m).

2 6. Unless the equipment is marked otherwise, conductors for branch circuits rated 100 or less amperes and using 1 AWG or smaller conductors must be selected from the column of Table (B)(16). 1) 60 C (140 F) 2) 75 C (167 F) 3) 90 C (194 F) 4) any of these 7. The minimum size permitted for copper-clad aluminum conductors is. 1) 14 AWG 2) 12 AWG 3) 10 AWG 4) 8 AWG 8. For an existing dwelling unit, where no additional air-conditioning or electric space-heating equipment will be installed, the first 8 kva of load will be taken at 100% and the remainder of the load will be computed at of the load. 1) 75% 2) 60% 3) 40% 4) 25% 9. A transformer which is intended to be connected to a 3-phase 3-wire ungrounded electrical system for the purpose of creating a 3-phase 4-wire grounded electrical system is called a: 1) boost and buck transformer. 2) insulating transformer. 3) isolation transformer. 4) shielded transformer. 5) zig-zag transformer. 10. Rigid PVC Conduit is run from the metal forming shell of a wet-niche lighting fixture in a permanent swimming pool to the junction box installed in the concrete deck surface. A size 8 AWG copper bonding conductor run in Rigid Nonmetallic Conduit connects the metal forming shell to the surface junction box. The bonding conductor is: 1) required to be solid. 2) permitted to be bare. 3) not permitted to be bare but can be covered rather than insulated. 4) required to be stranded. 5) required to be insulated and permitted to be stranded. 11. A 3-phase transformer is connected for 480 volts on the primary and 208 volts on the secondary. If 200 amperes are flowing on the secondary conductors, the current in the primary conductors will be approximately: 1) 400 amperes. 2) 87 amperes. 3) 200 amperes. 4) 108 amperes. 5) 462 amperes. 12. One commercial building is supplied with 208/120 volt, 4-wire, three-phase power from another building on the same property and under the same management. The feeder is protected in the first building with a 200 ampere circuit breaker, and the conductors are copper Type THWN run underground in Rigid Nonmetallic Conduit. There are three ungrounded conductors, a neutral conductor, and an equipment grounding conductor. At the second building, the neutral and equipment grounding conductors are required to be: 1) kept separated, and the equipment grounding conductor is required to be connected to a grounding electrode.

3 2) bonded together, and not required to be connected to a grounding electrode. 3) kept separated, and grounding either conductor is optional. 4) kept separated, and the neutral is required to be connected to a grounding electrode. 5) connected to a grounding electrode. 13. A three-phase 69 KVA load will be connected to a circuit that is fed from a 3-pole breaker in a 120/240 volt 3Ø, 4-wire panel. This load will draw amps of current through each circuit conductor. 1) ) ) ) ) A multioutlet assembly is a raceway that contains receptacles and is either surface mounted, flush mounted, or free standing such as a power pole, and is permitted to be installed in: 1) concealed locations. 2) outside in damp locations. 3) inside or outside in damp locations. 4) locations subject to severe physical damage when constructed of steel with a minimum thickness of in.. 5) dry locations. 15. A common bonding grid for a permanent swimming pool is formed by connecting together with a bonding conductor all metal parts associated with the pool such as metallic parts of the pool structure, forming shells and mounting brackets of lighting fixtures, metal ladders and other metal fixtures attached to the pool, metal equipment associated with the water circulating system, pool covers and similar metal parts. The conductor used for this bonding is: 1) required to be solid copper not smaller than size 8 AWG. 2) permitted to be solid aluminum if insulated and not smaller than size 8 AWG. 3) required to be insulated copper, stranded, and not smaller than size 8 AWG. 4) permitted to be bare, insulated, or covered copper if not smaller than size 6 AWG. 5) required to be copper not smaller than size 2 AWG. 16. The sheath of nonmetallic cable must extend into a box not less than through a nonmetallic cable knockout opening. 1) 1/8 in. (3.18 mm) 2) 1/2 in. (12.7 mm) 3) 1/4 in. (6 mm) 4) 1/16 in. (1.6 mm) 17. The owner of a "Quick Lube" corporate franchise owns the building and the property it sits on. The owner has expressed a desire to wire the building. Which answer best describes what the owner may do. 1) Cannot wire the building 3) Can wire the building with employees 2) Can wire the building by himself 4) Hire an electrician to help him 18. Neon tubing and conductor must be supported not more than from the electrode connection. 1) 12 in. (300 mm) 2) 6 in. (150 mm) 3) 24 in. (600 mm) 4) none of the above 19. The secondary output conductors of an industrial arc welder consist of an electrode conductor and a workpiece conductor. The workpiece conductor: 1) is considered to be a separately derived system and is to be grounded accordingly. 2) is not required to be grounded to any premises electrical system grounding conductor or grounding electrode. 3) is required to be connected to a ground rod in the area of the welder. 4) shall be grounded to the metal frame of the building in the area of the welder. 5) shall be grounded to the equipment grounding conductor of the supply to the welder. 20. The conductor fill requirements for nonmetallic boxes is determined by:

4 1) Table (A). 2) Table (B). 3) both of the above. 4) none of the above. 21. Of the following, the one not permitted to serve as an equipment grounding conductor for a 30 ampere rated circuit is: 1) Electrical Metallic Tubing. 2) Rigid Metal Conduit. 3) Nonmetallic-Sheathed Cable Type NM-B with a size 10 AWG bare copper wire. 4) Metal Clad Cable Type MC with a size 10 AWG insulated green copper wire. 5) a 3 ft (900 mm) length of Flexible Metal Conduit terminating in fittings listed as suitable for grounding. 22. What percentage of the sum of the ratings can be used for a total of 43 receptacles in marinas and boatyards? 1) 50% 2) 40% 3) 30% 4) none of the above 23. Amusement rides and amusement attractions must not be located under or within horizontally of conductors operating in excess of 600 volts. 1) 15 ft (4.5 m) 2) 10 ft (3.0 m) 3) 5 ft (1.5 m) 4) none of the above 24. If type AC Cable is to be used for exposed wiring above a suspended ceiling in a facility classified as a place of assembly the cable shall: 1) be of the jacketed type. 2) not be smaller than size 12 AWG copper. 3) contain a bare equipment grounding conductor in contact with the metal sheath. 4) have an insulated equipment grounding conductor. 5) have an insulated equipment grounding conductor. 25. A 30 ampere, locking type grounding receptacle outlet is used to supply shore power to a boat at a marina. A disconnecting means shall be readily accessible and located so that the distance from the disconnect to the receptacle it controls is not more then: 1) 6 ft (1.8 m). 2) 10 ft (3 m). 3) 24 in. (600 mm). 4) 30 in. (750 mm). 5) 50 ft (15 m). 26. An overhead feeder conductor supplies single-phase 120/240 volt power to a storage building from an office building at commercial property. If the feeder passes over a driveway used for truck traffic, the minimum clearance of the conductors over the drive is: 1) 10 ft (3 m). 2) 12 ft (3.7 m). 3) 15 ft (4.5 m). 4) 18 ft (5.5 m). 5) 22 ft (6.7 m). 27. What is the demand factor percentage permitted to be used to size service-entrance conductors for 20 recreational vehicle sites? 1) 60%

5 2) 50% 3) 45% 4) none of the above 28. A 5 horsepower, 230 volt, 3-phase, design B, motor has a nameplate full-load current of 14 amperes and a service factor of The branch circuit conductors are copper with 75 C insulation and terminations. The minimum permitted conductor size is: 1) 14 AWG. 2) 12 AWG. 3) 10 AWG. 4) 8 AWG. 5) 6 AWG. 29. Each pedestrian entrance to a commercial building is required to have a receptacle outlet at an accessible location and is: 1) permitted to be supplied by a general use branch circuit. 2) required to be supplied by a 20 ampere branch circuit that supplies no other load. 3) required to be supplied by at least one 15 ampere branch circuit. 4) required to be ground-fault circuit interrupter protected. 5) required to be arc-fault circuit interrupter protected. 30. A stand alone fuel cell system is connected to a premises wiring system. The output of the inverter is 120 volt and is connected to 120/240 volt, 3 wire distribution equipment. This output is allowed to supply. 1) multiwire branch circuits only 3) 120 volt circuits only 2) 240 volt circuits only 4) all of these 31. An 80 gallon (300 L) storage type water heater has a full-load rating of 3500 watts at 240 volts. The minimum rating circuit breaker permitted to supply this water heater is: 1) 15 amperes. 2) 20 amperes. 3) 30 amperes. 4) 40 amperes. 5) 50 amperes. 32. Impedance in an alternating circuit is the result of: 1) resistance. 2) capacitive reactance. 3) inductive reactance. 4) all of the above. 33. A Type SJEO flexible cord is used to replace the damaged power cord on a 240 volt 1Ø appliance. The smallest size permitted is AWG where connected to a branch circuit that is protected by a 40 amp branch circuit breaker. 1) 12 2) 8 3) 10 4) 14 5) none of these 34. A gasoline dispenser at a service station is supplied with 120 volt power from a circuit breaker panelboard where the circuit breaker will act as the disconnecting means for the dispenser. The circuit breaker from the following list permitted to serve as the dispenser disconnect is the: 1) single-pole circuit breaker. 2) single-pole, ground-fault circuit interrupter breaker. 3) single-pole, arc-fault interrupter breaker. 4) two-pole circuit breaker. 5) switched neutral circuit breaker. 35. Electrical equipment and wiring methods on rides or concessions must be provided with where such equipment or wiring is subject to physical damage.

6 1) overcurrent protection 2) mechanical protection 3) double insulation 4) all of the above 36. A 25 kva single-phase transformer is connected 480 volts on the primary and 240 volts on the secondary. The primary full-load current of the transformer is: 1) 104 amperes. 2) 52 amperes. 3) 30 amperes. 4) 65 amperes. 5) 60 amperes. 37. Liquidtight flexible nonmetallic conduit cannot be used: 1) where subject to physical damage. 2) in lengths longer than 6 ft (1.8 m). 3) where the voltage of the contained conductors is in excess of 600 volts. 4) all of the above. 38. Electrical permits are required for 1) branch circuit extensions, security 3) Fire alarm testing, HVAC component cameras and doorbell installation replacement and RV wiring 2) minor label installations, garbage disposal 4) None of the above replacements 39. A particular piece of single-phase, 240 volt portable equipment is connected to a permanent wiring system with extra hard service Type SO copper flexible cord. The minimum conductor ampacity required for the equipment is 16 amperes. The minimum size flexible cord permitted to supply this equipment is: 1) 16 AWG. 2) 14 AWG. 3) 12 AWG. 4) 10 AWG. 5) 8 AWG. 40. Strut-type channel raceway: 1) is only permitted to contain conductors that supply fixtures supported by the raceway. 2) shall not have a conductor fill in excess of 20% of the cross-sectional area of the raceway. 3) is required to be supported at intervals not to exceed 8 ft. 4) shall not be permitted to penetrate partitions or walls. 5) shall not be installed where concealed. 41. Lighting outlets are not required in which dwelling unit? 1) kitchens 2) attics 3) crawl spaces 4) clothes closets 42. The attachment plug and receptacle are permitted to serve as the controller for a portable motor that has a rating not greater than: 1) 1/4 horsepower. 2) 1/3 horsepower. 3) 1/2 horsepower. 4) 3/4 horsepower. 5) 1 horsepower. 43. A standard 15- or 20-ampere, 125 volt receptacle that is used on normal building circuits is permitted to be supplied by a technical power system and installed in an audio equipment room if:

7 1) the room is restricted to use by qualified personnel. 2) the circuits are arc-fault circuit interrupter protected. 3) no other receptacles supplied by the normal power system with a grounded neutral conductor are present in the room. 4) only isolated ground type receptacles are used. 5) all lighting in the room is also supplied by the technical power receptacles. 44. A 37.5 kva, three-phase transformer is connected 480 volts on the primary and 208/120 volts on the secondary. The primary full-load current of the transformer is 45 amperes. The transformer supplies a panelboard, 25 ft (7.5 m) away that has a 100 ampere main circuit breaker. The conductor from the transformer to the panelboard is size 3 AWG copper. The primary of the transformer is protected with a 60 ampere circuit breaker. The minimum size copper conductors with 75 C insulation and terminations permitted to supply the primary of the transformer is: 1) 3 AWG. 2) 4 AWG. 3) 6 AWG. 4) 8 AWG. 5) 10 AWG. 45. If the rating of a branch circuit does not match the standard overcurrent protective device ratings specified in Section 240.6, the next higher standard OCPD rating can be used when. 1) the circuit is rated less than 800 amperes 2) it is not a multi-outlet branch circuit serving cord-and-plug connected loads 3) the circuit operates at less than 347/600 volts 4) both a and b 46. The total load of a room air conditioner supplied by an individual branch circuit shall not exceed percent of the branch-circuit rating. 1) 50 2) 75 3) 80 4) The combined length of FMC, FMT, and LFMC in the same ground path must not exceed: 1) 6 ft (1.8 m). 2) 10 ft (3.0 m). 3) 3 ft (900 mm). 4) all of the above. 48. When connecting conductors to receptacles at inserts in a cellular metal floor raceway, the conductors are: 1) permitted to be cut and connected to the receptacle terminal screws. 2) must be cut and pigtailed to each receptacle. 3) only permitted to be supply one receptacle. 4) not permitted to be installed as loop-wiring. 5) required to be attached to the receptacle terminals without cutting the conductors that feed on to other outlets. 49. Class 1 power-limited circuits are supplied from a source that has a rated output of not more than volts and volt-amperes. 1) 30; ) 600; volts and 1500 volt-amperes 3) 60; 150 4) none of the above 50. A building has underfloor raceway installed to supply power to office desk locations in an open room. If a floor outlet is removed, the conductors that were connected to the receptacle outlet:

8 1) are permitted to be taped and placed back into the underfloor raceway. 2) must be marked as an abandoned cable if left in the raceway. 3) shall have the bare conductor covered with a listed insulating material. 4) shall have the conductors cut and spliced with tape applied to exceed the original insulation value. 5) shall be removed from the raceway. 51. In critical care areas, patient bed receptacles may be: 1) single. 2) duplex. 3) quadruplex. 4) all of the above. 52. Power sources for a Class 2 or a Class 3 circuit shall be a listed. 1) auto transformer 2) control transformer 3) Class 2 or Class 3 transformer 4) none of the above

9 Spring Test 10 due 05/11/2013 Answer Section MULTIPLE CHOICE 1. ANS: (A) 2. ANS: (2) 3. ANS: (A)(4) Ex 4. ANS: (C) & (5) 5. ANS: (B)(3), (C)(6) 6. ANS: 1 7. ANS: 2 Table ANS: (A) 9. ANS: ANS: (B)(2)(b) 11. ANS: A (208 V / 480 V) = ANS: (B)

10 13. ANS: 5 I = [ ] = amps NAT: Obj ABank TOP: 3-ph: Current Calc 14. ANS: (A) 15. ANS: (B) 16. ANS: (C) 17. ANS: 1 OAR ANS: (C) 19. ANS: ANS: (A)(2) 21. ANS: ANS: 1 Table ANS: (B)(2) 24. ANS: (A)

11 25. ANS: (B) 26. ANS: (4) 27. ANS: 3 Table ANS: A 1.25 = 19 A 430.6(A), Table , (A), Table (B)(16) 29. ANS: (A) 30. ANS: Stand-Alone Systems. (C) Single 120-Volt Nominal Supply. The inverter output of a stand-alone fuel cell system shall be permitted to supply 120 volts, nominal, to single-phase, 3-wire 120/240-volt service equipment or distribution panels where there are no 240-volt loads and where there are no multiwire branch circuits. In all installations, the rating of the overcurrent device connected to the output of the fuel cell system(s) shall be less than the rating of the service equipment. This equipment shall be marked as follows: 31. ANS: 2 (3500 W / 240 V) 1.25 = 18.2 A ANS: 4 General knowledge 33. ANS: (A) 34. ANS: (A) NAT: Obj ABank 35. ANS:

12 36. ANS: 2 25 kva 1000 / 480 V = 52 A 37. ANS: ANS: 1 OAR ANS: 2 Table 400.5(A) 40. ANS: (1) 41. ANS: (A) 42. ANS: (B) 43. ANS: (A)(4) 44. ANS: (B) Table (B)(16) 45. ANS: (B) 46. ANS: (B) 47. ANS: (6)(d)

13 48. ANS: ANS: (A) 50. ANS: ANS: (B)(2) 52. ANS: (A)(1),(2), or (3)

Spring Test 7 due 05/03/2013

Spring Test 7 due 05/03/2013 Spring Test 7 due 05/03/2013 Multiple Choice Identify the choice that best completes the statement or answers the question. 1. A raceway contains two 3-phase, 3-wire circuits that supply 38 ampere continuous

More information

Chapter 2 Wiring and Protection Article 200 Use and Identification of Grounded Neutral Conductor Chapter 1 General...9

Chapter 2 Wiring and Protection Article 200 Use and Identification of Grounded Neutral Conductor Chapter 1 General...9 Article 90 Introduction...1 90.1 Purpose of the NEC...1 90.2 Scope of the NEC...2 90.3 Code Arrangement...4 90.4 Enforcement...5 90.5 Mandatory Requirements and Explanatory Material...6 90.6 Formal Interpretations...6

More information

CHAPTER V RESIDENTIAL WIRING

CHAPTER V RESIDENTIAL WIRING CHAPTER V RESIDENTIAL WIRING 5.1. THE SERVICE ENTRANCE Buildings and other structures receive the electrical energy through the service entrance. In residential wiring, the electric company supply this

More information

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 2/8/12 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 2/8/12 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions MECKLENBURG COUNTY Land Use and Environmental Service Agency Code Enforcement 2/8/12 ELECTRICAL CONSISTENCY MEETING Code Consistency Questions 1. I am inspecting a building addition. They have a 480V to

More information

SECTION 1: Field Inspection Guide for Rooftop Photovoltaic (PV) Systems

SECTION 1: Field Inspection Guide for Rooftop Photovoltaic (PV) Systems COUNTY OF SANTA CRUZ PLANNING DEPARTMENT 701 OCEAN STREET, 4 th FLOOR, SANTA CRUZ, CA 95060 (831) 454-2580 FAX: (831) 454-2131 TDD: (831) 454-2123 KATHLEEN MOLLOY PREVISICH, PLANNING DIRECTOR Photovoltaic

More information

WIRING DESIGN & PROTECTION REQUIREMENTS CHECKLIST

WIRING DESIGN & PROTECTION REQUIREMENTS CHECKLIST WIRING DESIGN & PROTECTION REQUIREMENTS CHECKLIST Use & Identification of Grounded and Grounding Conductors YES NO N/A Grounded conductors are identifiable and distinguishable from all other conductors.

More information

Electrical Tech Note 105 Agricultural Engineering Department Michigan State University

Electrical Tech Note 105 Agricultural Engineering Department Michigan State University Electrical Tech Note 105 Agricultural Engineering Department Michigan State University Journey Exam Study Guide and Sample Questions 1 Based on the 2002 NEC, Part 8 of PA 230, and the 2003 MRC The Journey

More information

SINGLE PHASE WIRING SPECIFICATIONS

SINGLE PHASE WIRING SPECIFICATIONS SINGLE PHASE WIRING SPECIFICATIONS 1-866-MEC-ELEC (1-866-632-3532) Office Locations: Hondo Office 237 Hwy 173 N Hondo, TX 78661-0370 Fax 830.426.3335 Dilley Office 1718 W. FM 117 Dilley, TX 78017 Fax 830.965.1425

More information

THREE PHASE WIRING SPECIFICATIONS

THREE PHASE WIRING SPECIFICATIONS THREE PHASE WIRING SPECIFICATIONS 1-866-MEC-ELEC (1-866-632-3532) Office Locations: Hondo Office 237 Hwy 173 N Hondo, TX 78661-0370 Fax 830.426.3335 Dilley Office 1718 W. FM 117 Dilley, TX 78017 Fax 830.965.1425

More information

Pretest Module 24 Three-phase Service Entrance

Pretest Module 24 Three-phase Service Entrance Pretest Module 24 Three-phase Service Entrance 1. What is the most widely used three-phase service entrance system? 2. What are the three most common voltage combinations for three-phase, four-wire systems?

More information

Western Section 101 st Annual Meeting Hot Springs, Arkansas September 21, 2005 Charlie Trout Code Breakfast

Western Section 101 st Annual Meeting Hot Springs, Arkansas September 21, 2005 Charlie Trout Code Breakfast Western Section 101 st Annual Meeting Hot Springs, Arkansas September 21, 2005 Charlie Trout Code Breakfast 1.Question: An add on unit for a hydromassage bathtub consists of a small 1-gallon water heater

More information

Volume 2 Charts, Formulas, and Other Useful Information

Volume 2 Charts, Formulas, and Other Useful Information Volume 2 Charts, Formulas, and Other Useful Information Aluminum Conductor Conductor Terminations 61 Compact Aluminum (Conduit Fill Tables) 68-79 Ampacity Dwelling Services 48 1-phase Loads on a 3-phase

More information

Overcurrent Protection (2014 NEC) (Homestudy)

Overcurrent Protection (2014 NEC) (Homestudy) Overcurrent Protection (2014 NEC) (Homestudy) Oregon Electrical License The key sections of Article 240 will be discussed. Overcurrent protection for panelboards, appliances, motors, motor compressors,

More information

SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS - ELECTRICAL

SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS - ELECTRICAL SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS - ELECTRICAL This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly.

More information

Chapter 1 Electrical Theory...1

Chapter 1 Electrical Theory...1 Electrical Formulas with Sample Calculations Table of Contents Chapter 1 Electrical Theory...1 Unit 1 Electrician s Math and Basic Electrical Formulas...3 Part A Electrician s Math...3 1 1 Fractions...3

More information

Electrical Tech Note 106

Electrical Tech Note 106 Electrical Tech Note 106 Biosystems & Agricultural Engineering Department Michigan State University Master Exam Study Guide and Sample Questions 1 Based on the 2014 NEC, Part 8 of PA 230, PA 407, and the

More information

Generator Fire Safety: Generator assemblies should be located outside the building.

Generator Fire Safety: Generator assemblies should be located outside the building. SECTION 33 70 00 - ELECTRICAL DISTRIBUTION PACKAGED GENERATOR ASSEMBLIES Generator Fire Safety: Generator assemblies should be located outside the building. All fuel piping from the outside of the building

More information

CHAPTER 10 ELECTRICAL. Notes:

CHAPTER 10 ELECTRICAL. Notes: CHAPTER 10 ELECTRICAL 1001.0 General Requirements. Electrical wiring and equipment shall comply with the requirements of NFPA 70, National Electrical Code (NEC), or local ordinances. 1002.0 Solar Photovoltaic

More information

2016 Photovoltaic Solar System Plan Review List

2016 Photovoltaic Solar System Plan Review List Building Division 555 Santa Clara Street Vallejo CA 94590 707.648.4374 2016 Photovoltaic Solar System Plan Review List GENERAL PROJECT INFORMATION PLAN CHECK NO DATE JOB ADDRESS CITY ZIP REVIEWED BY PHONE

More information

Western Section IAEI Code Panel Questions

Western Section IAEI Code Panel Questions Western Section IAEI 2013 Code Panel Questions 1. Do the factory wings that many fluorescent troffers have designed to fold out over the grid meet the requirements for securely fastened to the framing?

More information

Fee $20 Course: NEC Changes 1 This course is valid for these credentials: Credential Description Cred Code Credit Hours

Fee $20 Course: NEC Changes 1 This course is valid for these credentials: Credential Description Cred Code Credit Hours www.garyklinka.com Page 1 of 18 Instructions: Fee $20 1. Print these pages. 2. Circle the correct answers and transfer them to the answer sheet. 3. Page down to the last page for the verification forms

More information

2011 NEC Code Updates Part 3

2011 NEC Code Updates Part 3 www.garyklinka.com Page 1 of 22 Instructions: Fee $35 1. Print these pages. 2. Circle the correct answers and transfer them to the answer sheet. 3. Page down to the last page for the verification forms

More information

CHAPTER 10 ELECTRICAL

CHAPTER 10 ELECTRICAL 1001.0 General Requirements. 1001.1 Electrical Wiring and Equipment. Electrical wiring and equipment shall comply with the requirements of NFPA 70, National Electrical Code (NEC), or local ordinances.

More information

TEMPORARY ELECTRIC WIRING FOR CARNIVALS, CONVENTIONS, EXHIBITIONS, FAIRS AND SIMILAR USES

TEMPORARY ELECTRIC WIRING FOR CARNIVALS, CONVENTIONS, EXHIBITIONS, FAIRS AND SIMILAR USES INFORMATION BULLETIN / PUBLIC - ELECTRICAL CODE REFERENCE NO.: LAMC 93.0230 Effective: 3-24-69 DOCUMENT NO. P/EC 2002-006 Revised: 11-17-00 Previously Issued As: RGA #7-69 TEMPORARY ELECTRIC WIRING FOR

More information

PART A General Conductor Requirements

PART A General Conductor Requirements PART A General Conductor Requirements 6.1 Conductor Insulation Property Table 310.13 of the NEC provides information on conductor properties such as permitted use, maximum operating temperature, and other

More information

Photovoltaic Solar Plan Review

Photovoltaic Solar Plan Review PAIGE B. VAUGHAN, CBO Director of Building and Safety Phone (310) 605-5509 Fax Line (310) 605-5598 E-mail:lbutler@comptoncity.org Building & Safety Department Photovoltaic Solar Plan Review Plan Check

More information

The following are specific provisions of 1910(a)(2) that could be seen in the LBM sector

The following are specific provisions of 1910(a)(2) that could be seen in the LBM sector Know the Rules on Temporary Wiring OSHA Standard 1910.305, Wiring methods, components, and equipment for general use, addresses wiring methods, components, and equipment for general use as one of several

More information

This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly.

This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly. SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS (ELEC) This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly.

More information

Table of Contents. Unit 3 Magnetism Unit 1 Matter Unit 4 Electricity Unit 2 Electron Theory Unit 5 Electromagnetism...

Table of Contents. Unit 3 Magnetism Unit 1 Matter Unit 4 Electricity Unit 2 Electron Theory Unit 5 Electromagnetism... Introduction...x How to Use This Textbook...xi About the Author...xii About the Graphic Illustrator...xiii Mike Holt Enterprises Team...xiv Chapter 1 Electrical Fundamentals... 1 Unit 1 Matter... 3 Introduction...

More information

Chapter 8 Interior Wiring and Lighting

Chapter 8 Interior Wiring and Lighting Chapter 8 Interior Wiring and Lighting Review Questions 1. What tool if any, is used to remove a fuse that is to be replaced? 1. Pliers 2. Screwdriver 3. Fuse puller 4. None 2. OSHA has established specific

More information

TABLE OF CONTENTS CHAPTER 1 ELECTRICAL THEORY About This Textbook...xi. Passing Your Exam...xiv. How to Use the National Electrical Code...

TABLE OF CONTENTS CHAPTER 1 ELECTRICAL THEORY About This Textbook...xi. Passing Your Exam...xiv. How to Use the National Electrical Code... TABLE OF CONTENTS About This Textbook...xi Passing Your Exam...xiv How to Use the National Electrical Code... 1 CHAPTER 1 ELECTRICAL THEORY... 7 Unit 1 Electrician s Math and Basic Electrical Formulas...

More information

NEC 2014 Code Changes

NEC 2014 Code Changes NEC 2014 Code Changes Articles 310 310.120 CHANGES FROM 2011 TO 2014 CODE ARE IN RED ARTICLE 310 Conductors for General Wiring I. General 310.2 Definitions Electrical Ducts Electrical conduits, or other

More information

UNIT 1 ELECTRICIAN S MATH AND BASIC ELECTRICAL FORMULAS...1 Introduction...1. UNIT 2 ELECTRICAL CIRCUITS...49 Introduction...49

UNIT 1 ELECTRICIAN S MATH AND BASIC ELECTRICAL FORMULAS...1 Introduction...1. UNIT 2 ELECTRICAL CIRCUITS...49 Introduction...49 UNIT 1 ELECTRICIAN S MATH AND BASIC ELECTRICAL FORMULAS...1 Introduction...1 PART A ELECTRICIAN S MATH...1 Introduction...1 1.1 Whole Numbers...1 1.2 Decimal...1 1.3 Fractions...1 1.4 Percentages...2 1.5

More information

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 9/14/11 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 9/14/11 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions MECKLENBURG COUNTY Land Use and Environmental Service Agency Code Enforcement 9/14/11 ELECTRICAL CONSISTENCY MEETING Code Consistency Questions 1. I recently installed a 45-KVA transformer, 480-volt primary

More information

NEC 2011 Code Changes

NEC 2011 Code Changes NEC 2011 Code Changes Articles 280.21-300.50 CHANGES FROM 2008 TO 2011 CODE ARE IN RED Chapter 2 - Wiring and Protection ARTICLE 280 Surge Arresters, Over 1kV III. Connecting Surge Arresters 280.21 Connection

More information

9/16/2010. Chapter , The McGraw-Hill Companies, Inc. TRANSMISSION SYSTEMS. 2010, The McGraw-Hill Companies, Inc.

9/16/2010. Chapter , The McGraw-Hill Companies, Inc. TRANSMISSION SYSTEMS. 2010, The McGraw-Hill Companies, Inc. Chapter 3 TRANSMISSION SYSTEMS 1 Transmitting large amounts of electric energy over long distances is accomplished most efficiently by using high-voltages. Without transformers the widespread distribution

More information

(The actual state exam will be closer to 50 questions in 4 hours time) Master Electrician Practice Test

(The actual state exam will be closer to 50 questions in 4 hours time) Master Electrician Practice Test (The actual state exam will be closer to 50 questions in 4 hours time) Master Electrician Practice Test 1. Accessible as applied to wiring methods means capable of being removed or exposed without damaging

More information

Electrical Tech Note 111 Biosystems & Agricultural Engineering Department Michigan State University

Electrical Tech Note 111 Biosystems & Agricultural Engineering Department Michigan State University Electrical Tech Note 111 Biosystems & Agricultural Engineering Department Michigan State University Electrical Code Changes in Michigan 1 (Based on Part 8, P.A. 230, the 2005 NEC and the 2003 MRC) This

More information

Table of Contents. CHAPTER 1 ElECTRiCAl THEoRY Mike Holt enterprises, inc neC.Code ( )

Table of Contents. CHAPTER 1 ElECTRiCAl THEoRY Mike Holt enterprises, inc neC.Code ( ) CHAPTER 1 ElECTRiCAl THEoRY... 1 UniT 1 electrician s MaTH and BasiC electrical formulas... 3 Introduction to Unit 1... 3 Part A Electrician s Math... 3 Introduction... 3 1.1 Whole Numbers... 3 1.2 Decimals...

More information

2011 NEC Changes Part 2 (Homestudy) (Homestudy)

2011 NEC Changes Part 2 (Homestudy) (Homestudy) 2011 NEC Changes Part 2 (Homestudy) (Homestudy) North Carolina Electrical License This course will review the second half of the most important National Electrical Code changes from the 2011 NEC. Changes

More information

Definitions of and have been revised. a. automatic b. nonautomatic c. none of the above d. both a and b

Definitions of and have been revised. a. automatic b. nonautomatic c. none of the above d. both a and b www.garyklinka.com Page 1 of 12 Instructions: Fee $25 1. Print these pages. 2. Circle the correct answers and transfer them to the answer sheet. 3. Page down to the last page for the verification forms

More information

Overcurrent Protection According to the 2011 NEC

Overcurrent Protection According to the 2011 NEC Overcurrent Protection According to the 2011 NEC Utah Electrical License This course will cover overcurrent protection according to the 2011 NEC. The key sections of Article 240 will be discussed. Overcurrent

More information

Chapter 5. Imagine That Engineering Inc. Assured Equipment Grounding Conductor Program (AEGCP) Ground Fault Circuit Interrupter (GFCI)

Chapter 5. Imagine That Engineering Inc. Assured Equipment Grounding Conductor Program (AEGCP) Ground Fault Circuit Interrupter (GFCI) Chapter 5 Imagine That Engineering Inc. Assured Equipment Grounding Conductor Program (AEGCP) Ground Fault Circuit Interrupter (GFCI) Imagine That Engineering Inc. has adopted this program for equipment

More information

9/7/2010. Objectives. Article 90. Introduction NEC Significant Changes. Review significant revisions in the 2011 NEC

9/7/2010. Objectives. Article 90. Introduction NEC Significant Changes. Review significant revisions in the 2011 NEC 2011 NEC Significant Changes Courtesy of NJATC Courtesy of NFPA Presented By: Michael J. Johnston Executive Director of Standards and Safety, NECA Objectives Review significant revisions in the 2011 NEC

More information

SECTION LOW VOLTAGE DISTRIBUTION EQUIPMENT

SECTION LOW VOLTAGE DISTRIBUTION EQUIPMENT SECTION 16400 LOW VOLTAGE DISTRIBUTION EQUIPMENT A. General 1. The University does not accept Series-Rated equipment for power distribution switchboards, distribution panels and branch circuit panelboards.

More information

Pentahead bolts See note 2. Conduit run as specified. Company facility. Refer to drawing SS8.6-2 or SS8.6-3 STANDARD SERVICE INSTALLATION

Pentahead bolts See note 2. Conduit run as specified. Company facility. Refer to drawing SS8.6-2 or SS8.6-3 STANDARD SERVICE INSTALLATION PULL BOX F SECONDARY SYSTEM Typical grade Pentahead bolts See note 2 Conduit run as specified Plastic or fiberglass for grass areas or Polymer concrete for light duty areas (see notes 2, 3, & 4) Company

More information

PHOTOVOLTAIC ELECTRICAL POWER SYSTEMS INSPECTOR/INSTALLER CHECKLIST

PHOTOVOLTAIC ELECTRICAL POWER SYSTEMS INSPECTOR/INSTALLER CHECKLIST PHOTOVOLTAIC ELECTRICAL POWER SYSTEMS INSPECTOR/INSTALLER CHECKLIST The following checklist is an outline of the general requirements found in the 2005 National Electrical Code (NEC) Article 690 for Photovoltaic

More information

Have You Been Grounded Lately

Have You Been Grounded Lately Have You Been Grounded Lately Thurs, Oct. 26, 2017 9:15-10:15 Phil Simmons Author, Electrical Grounding and Bonding Author Cengage Learning Phil Simmons Have You Been Grounded Lately 2017 NEC Changes Relative

More information

EV Charging Station Submittal Requirements

EV Charging Station Submittal Requirements EV Charging Station Submittal Requirements To obtain a permit for an Electric Vehicle Charging Station, please provide the following: Plan and details of the charging system installation o Print applicable

More information

Contents. Obtaining Electric Service from Your Cooperative...1. Bonding Frames of Major Appliances...4. Voltage Drop...8. Drawings...

Contents. Obtaining Electric Service from Your Cooperative...1. Bonding Frames of Major Appliances...4. Voltage Drop...8. Drawings... Contents Obtaining Electric Service from Your Cooperative...1 Bonding Frames of Major Appliances...4 Voltage Drop...8 Drawings...14 Agricultural Buildings...23 Optional Standby Systems...42 Grounding &

More information

2014 NEC Changes Part 4

2014 NEC Changes Part 4 www.garyklinka.com Page 1 of 14 Instructions: Fee $25 1. Print these pages. 2. Circle the correct answers and transfer them to the answer sheet. 3. Page down to the last page for the verification forms

More information

Western Section IAEI Code Panel Questions

Western Section IAEI Code Panel Questions Western Section IAEI 2013 Code Panel Questions 1. Do the factory wings that many fluorescent troffers have designed to fold out over the grid meet the requirements for securely fastened to the framing?

More information

See Part 3 for the Introduction for Article 314

See Part 3 for the Introduction for Article 314 See Part 3 for the Introduction for Article 314 76 314.25 Covers and Canopies When the installation is complete, each outlet box must be provided with a cover or faceplate, unless covered by a fixture

More information

Arc Fault Circuit Interrupter (AFCI) FACT SHEET

Arc Fault Circuit Interrupter (AFCI) FACT SHEET Arc Fault Circuit Interrupter (AFCI) FACT SHEET THE AFCI The AFCI is an arc fault circuit interrupter. AFCIs are newly-developed electrical devices designed to protect against fires caused by arcing faults

More information

ADVANCED CALCULATIONS

ADVANCED CALCULATIONS ADVANCED CALCULATIONS 101. Why is it permissible in some cases to fuse a #14 AWG motor conductor with a 60 amp breaker when normally a #14 AWG should only be fused at 15 amps? a) the motor can't start

More information

Table of Contents. CHAPTER 1 BASIC ELECTRICAL THEORY (Essential for Journeyman and Master s Licensing Exams)... 1

Table of Contents. CHAPTER 1 BASIC ELECTRICAL THEORY (Essential for Journeyman and Master s Licensing Exams)... 1 Introduction... x About This Textbook...xi Passing Your Exam...xiv How to Use the National Electrical Code... xviii About the Author...xxi About the Graphic Illustrator...xxii Mike Holt Enterprises Team...

More information

TABLE OF CONTENTS. About the Mike Holt Enterprises Team... xviii CHAPTER 1 ELECTRICAL THEORY... 1

TABLE OF CONTENTS. About the Mike Holt Enterprises Team... xviii CHAPTER 1 ELECTRICAL THEORY... 1 TABLE OF CONTENTS Introduction...xv About the Mike Holt Enterprises Team... xviii CHAPTER 1 ELECTRICAL THEORY... 1 Unit 1 Electrician s Math and Basic Electrical Formulas... 1 Part A Electrician s Math...

More information

Continued from Part 2 Rules

Continued from Part 2 Rules Continued from Part 2 Rules 26 50. 51 250.94 Grounding (Bonding) of Communications Systems An accessible bonding point must be provided at service equipment or the disconnecting means of separate buildings

More information

Preface...x Chapter 1 Electrical Fundamentals

Preface...x Chapter 1 Electrical Fundamentals Preface...x Chapter 1 Electrical Fundamentals Unit 1 Matter...3 Introduction...3 1.1 Matter...3 1.2 Atomic Theory...3 1.3 Law of Electrical Charges...4 1.4 Law of Atomic Charges...5 Negative Atomic Charge...5

More information

TRANSMISSION SYSTEMS

TRANSMISSION SYSTEMS TRANSMISSION SYSTEMS Transmitting large amounts of electric energy over long distances is accomplished most efficiently by using high-voltages. Without transformers the widespread distribution of electric

More information

D9-3. No. WIRING DIAGRAM CONNECTIONS FOR UNDERGROUND SELF CONTAINED METERS JRH JED krich95 LINE LINE ABCN SOURCE SOURCE GROUND GROUND STUD STUD SOURCE

D9-3. No. WIRING DIAGRAM CONNECTIONS FOR UNDERGROUND SELF CONTAINED METERS JRH JED krich95 LINE LINE ABCN SOURCE SOURCE GROUND GROUND STUD STUD SOURCE SOURCE 20V 240V STUD (PER NEC) A customer supplied and installed teaser wire is required from the neutral lug to a 5th terminal mounted on the left side of the meter block between the line and load terminals.

More information

2. DEFINITIONS. 2.3 APPROVED Acceptable to the authority enforcing the National Electric Code

2. DEFINITIONS. 2.3 APPROVED Acceptable to the authority enforcing the National Electric Code 2. DEFINITIONS 2.1 ACCEPTABLE Acceptable to the Company. 2.2 ADVANCED METER A meter that is capable of remote reading, and is capable of storing electric consumption data at specified time intervals of

More information

City of Walnut Creek Development Review Services 1666 N. Main Street, Walnut Creek, CA (925) phone (925) fax

City of Walnut Creek Development Review Services 1666 N. Main Street, Walnut Creek, CA (925) phone (925) fax City of Walnut Creek Development Review Services 1666 N. Main Street, Walnut Creek, CA 94596 (925) 943-5834 phone (925) 256-3500 fax Issued September 30, 2017 Policy Bulletin No. PB-72 Background Residential

More information

Electrical Design/Build Guide

Electrical Design/Build Guide 2017 Electrical Design/Build Guide Based on the 2017 National Electrical Code Copyright Durand & Associates 1986-2016 60 C Copper Ampacity 4 - Wire Fill - (Non-Current Carrying Neutral) 4 or 5 - Parallel

More information

An average of one worker is electrocuted on the job every day There are four main types of electrical injuries:

An average of one worker is electrocuted on the job every day There are four main types of electrical injuries: Electrical Safety Introduction An average of one worker is electrocuted on the job every day There are four main types of electrical injuries: Electrocution (death due to electrical shock) Electrical shock

More information

90.2 Scope. The installation of electrical conductors, equipment and raceways for:

90.2 Scope. The installation of electrical conductors, equipment and raceways for: NEC Generator Primer Rules on the installation of generators and transfer switches 1 90.2 Scope The installation of electrical conductors, equipment and raceways for: public and private premises Conductors

More information

Mecklenburg County Common Code Defects

Mecklenburg County Common Code Defects Electrical Code Defects Improper Over Current Protection Code Description 310.15 Ampacities for s Rated 0 2000 Volts. (A) General. (1) Tables or Engineering Supervision. Ampacities for conductors shall

More information

2014 NEC Update RV

2014 NEC Update RV PLEASE DO NOT BOOKMARK ANY ANYTIMECE WEBPAGES! Our system will remember the last page you viewed when logging out and back in but please DO NOT exit out when taking a test. Your place will NOT be saved.

More information

A Look at the 2017 NEC Significant Changes

A Look at the 2017 NEC Significant Changes A Look at the 2017 NEC Significant Changes A Look at the 2017 NEC Significant Changes Michael J. Johnston NECA James T. Dollard Local 98 Philadelphia Electrical JATC This session is eligible for 1 Continuing

More information

Solar PV Standard Plan Simplified Central/String Inverter Systems for One- and Two-Family Dwellings

Solar PV Standard Plan Simplified Central/String Inverter Systems for One- and Two-Family Dwellings Your City logo here Solar PV Standard Plan Simplified Central/String Inverter Systems for One- and Two-Family Dwellings SCOPE: Use this plan ONLY for utility-interactive central/string inverter systems

More information

Solar PV Standard Plan Simplified Central/String Inverter Systems for One- and Two-Family Dwellings

Solar PV Standard Plan Simplified Central/String Inverter Systems for One- and Two-Family Dwellings PV TOOLKIT DOCUMENT #3 Solar PV Standard Plan Simplified Central/String Inverter Systems for One- and Two-Family Dwellings SCOPE: Use this plan ONLY for utility-interactive central/string inverter systems

More information

WISCONSIN ELECTRICIANS

WISCONSIN ELECTRICIANS Wisconsin Contractors Institute 2017 PART 2 3 CONTINUING EDUCATION FOR WISCONSIN ELECTRICIANS 2017 NEC Code Change Part 2 8 Hours WISCONSIN CONTRACTORS INSTITUTE N16 W23217 Stone Ridge Drive, Suite 290

More information

SOLAR PHOTOVOLTAIC SYSTEMS INSPECTOR CHECKLIST

SOLAR PHOTOVOLTAIC SYSTEMS INSPECTOR CHECKLIST SOLAR PHOTOVOLTAIC SYSTEMS INSPECTOR CHECKLIST The following checklist is an outline of the general requirements found in the 1999 National Electrical Code (NEC) Article 690 for Photovoltaic (PV) Power

More information

CONTINUING EDUCATION FOR OREGON ELECTRICIANS NEC Code Change Part 2 Course # Hours

CONTINUING EDUCATION FOR OREGON ELECTRICIANS NEC Code Change Part 2 Course # Hours AMERICAN ELECTRICAL INSTITUTE 2017 PART 2 3 CONTINUING EDUCATION FOR OREGON ELECTRICIANS 2017 NEC Code Change Part 2 Course #90817 8 Hours AMERICAN ELECTRICAL INSTITUTE N16 W23217 Stone Ridge Drive, Suite

More information

Electrical Safety. Electrical Safety Webinar. Electrical. Printing Industries Alliance Printing Industries Alliance 1

Electrical Safety. Electrical Safety Webinar. Electrical. Printing Industries Alliance Printing Industries Alliance 1 Webinar 1 Electrical 2 1 Webinar Introduction An average of one worker is electrocuted on the job every day There are four main types of electrical injuries: Electrocution (death due to electrical shock)

More information

The Reliable Choice. Field Pocket Guide

The Reliable Choice. Field Pocket Guide The Reliable Choice Field Pocket Guide Allowable Ampacities of STABILOY Brand XHHW-2 and Copper 75 C (167 F) 90 C (194 F) 75 C (167 F) 90 C (194 F) Conductor Size (AWG or kcmil) Types RHW, THHW, THW, THWN,

More information

SERVICE ATTACHMENT ON A BUILDING WITH BUS DUCT SERVICE ENTRANCE AND INDOOR METERING

SERVICE ATTACHMENT ON A BUILDING WITH BUS DUCT SERVICE ENTRANCE AND INDOOR METERING SERVICE ATTACHMENT ON A BUILDING WITH BUS DUCT SERVICE ENTRANCE AND INDOOR METERING Obtain acceptance and specific details from the local Company office. 1. Service entrance duct (see Note 1). Company

More information

2014 NEC Changes (Homestudy)

2014 NEC Changes (Homestudy) 2014 NEC Changes (Homestudy) Idaho Electrical License This course will review the most important National Electrical Code changes from the 2014 NEC. Changes in Articles 100 - Chapter 9 will be covered.

More information

DEWALT Electrical Licensing Exam Guide CONTENTS

DEWALT Electrical Licensing Exam Guide CONTENTS DEWALT Electrical Licensing Exam Guide v ONTENTS How to Prepare for the Exam................................................ 2 How to Study.............................................................

More information

FACT SHEET Standard: Electrical Safety

FACT SHEET Standard: Electrical Safety What is a Ground Fault Circuit Interrupter? FACT SHEET The ground-fault circuit interrupter, or GFCI, is a fast-acting circuit breaker designed to shut off electric power in the event of a ground-fault

More information

AGRICULTURAL UNDERGROUND SERVICE 500 HP OR LESS

AGRICULTURAL UNDERGROUND SERVICE 500 HP OR LESS Prepared by: ABB1 AGRICULTURAL UNDERGROUND SERVICE 500 HP OR LESS 05619 Asset Type: Electric Metering Function: Design and Construction Issued by: Lisseth Villareal (LDV2) Date: 07-31-15 Rev. #10: This

More information

2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE

2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE 2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE PAGE 1 OF 5 This Reference provides a very comprehensive list of aspects of a solar PV installation that could be reviewed, clarifying

More information

The 84 th NC Electrical Institute Code Questions April 9 th & 10 th 2013 North Raleigh Hilton Raleigh, NC

The 84 th NC Electrical Institute Code Questions April 9 th & 10 th 2013 North Raleigh Hilton Raleigh, NC The 84 th NC Electrical Institute Code Questions April 9 th & 10 th 2013 North Raleigh Hilton Raleigh, NC www.ncdoi.com www.ncbeec.org NC DEPARTMENT OF INSURANCE NC STATE BOARD OF EXAMINERS OF ELECTRICAL

More information

CAL/OSHA ELECTRICAL LOW VOLTAGE

CAL/OSHA ELECTRICAL LOW VOLTAGE Preparation: Safety Mgr Authority: CEO Issuing Dept: Safety Page: Page 1 of 7 Purpose The purpose of this program is to prevent injuries due to electrical exposure to low voltage (less than or equal to

More information

Learning Module 10: Loadcenters. 101 Basic Series

Learning Module 10: Loadcenters. 101 Basic Series Learning Module 10: Loadcenters 101 Basic Series What You Will Learn We ll step through each of these topics in detail: What Does a Loadcenter Do? 4 Applications 4 Basic Circuitry and Wiring 5 Residential

More information

5. What is the maximum number of#18 TEW control conductors permitted to be installed into a 6 inch rigid metal conduit? a. 196 b. 138 c. 259 d.

5. What is the maximum number of#18 TEW control conductors permitted to be installed into a 6 inch rigid metal conduit? a. 196 b. 138 c. 259 d. I Practice Exam Questions :loo(p c:.e.c... 1. A construction drawing has a scale of 1:200. If a line on the drawing measured 11.5mm, what would be the actual measured length on the project? a. 2300cm b.

More information

SOLAR PV STANDARD PLAN - COMPREHENSIVE Central/String Inverter Systems for One and Two Family Dwellings

SOLAR PV STANDARD PLAN - COMPREHENSIVE Central/String Inverter Systems for One and Two Family Dwellings SCOPE: Use this plan ONLY for utility-interactive central/string inverter systems not exceeding a total combined system ac inverter output rating of 10kW on the roof of a one- or two-family dwelling or

More information

Solar PV Standard Electric Plan

Solar PV Standard Electric Plan *** Provide this document to the inspector along with ALL system installation instructions *** SCOPE: Standard plan for the installation of microinverter solar PV systems, not exceeding a total AC output

More information

Installing a Downstream Distribution Panelboard

Installing a Downstream Distribution Panelboard Job Sheet 5 Installing a Downstream Distribution Panelboard OBJECTIVE To install a downstream distribution panelboard (DDP) on the Mobile Workstation. To mechanically and electrically connect the DDP to

More information

AMENDMENT ELECTRIC SERVICE MANUAL 2014

AMENDMENT ELECTRIC SERVICE MANUAL 2014 AMENDMENT (Pages 20,43,50,72,74,,76,78,83,86,99) ELECTRIC SERVICE MANUAL 2014 Effective April 1, 2015 18-7 6.0 SERVICE AND SERVICE ENTRANCES (General), Continued Conductor Sizing It is recommended that

More information

ARKANSAS ELECTRICIANS

ARKANSAS ELECTRICIANS CONTINUING EDUCATION FOR ARKANSAS ELECTRICIANS 2014 NEC Code Change 8 Hours AMERICAN ELECTRICAL INSTITUTE N16 W23217 Stone Ridge Drive, Suite 290 Waukesha, WI 53188 855-780-5046 www.aeitraining.com DISCLAIMER

More information

ROCKY MOUNTAIN CHAPTER IAEI MARCH 15-16, 2012

ROCKY MOUNTAIN CHAPTER IAEI MARCH 15-16, 2012 ROCKY MOUNTAIN CHAPTER IAEI MARCH 15-16, 2012 1) Can a switched outlet be on a small appliance branch circuit for dining room lighting? No, a switched outlet on a general purpose branch circuit may be

More information

2010 National Electric Code

2010 National Electric Code PDHonline Course E361 (4 PDH) 2010 National Electric Code Instructor: Thomas Mason, P.E. 2012 PDH Online PDH Center 5272 Meadow Estates Drive Fairfax, VA 22030-6658 Phone & Fax: 703-988-0088 www.pdhonline.org

More information

City of Manhattan Beach Community Development

City of Manhattan Beach Community Development City of Manhattan Beach Community Development Phone: (310) 802-5500 FAX: (310) 802-5501 TDD: (310) 546-3501 Photovoltaic Solar Panel Plan Check Guidelines Updated: 10-01-15 ORDINANCE NO. 15-0022 MBMC 9.06

More information

Service Requirements

Service Requirements Service Requirements General Contact Idaho Power before beginning work on any new service. All meter installations must meet current electrical code requirements and display the proper electrical permit.

More information

ELECTRICAL. 60 Minutes

ELECTRICAL. 60 Minutes ELECTRICAL 60 Minutes AGENDA Electrical definitions Electrical shocks, burns and secondary injuries Electrical hazards in the workplace Safety devices and prevention steps Do s and Don ts INTRODUCTORY

More information

Commercial & Industrial Wiring (2014 NEC) (Homestudy)

Commercial & Industrial Wiring (2014 NEC) (Homestudy) Commercial & Industrial Wiring (2014 NEC) (Homestudy) Montana Electrical License This course will review the 2014 National Electrical Code requirements for installing commercial and industrial wiring systems

More information

FOR ALL STAKEHOLDERS TO

FOR ALL STAKEHOLDERS TO Our Goal is FOR ALL STAKEHOLDERS TO HAVE A SUCCESSFUL PROJECT with us and that together we keep people and structures safe and buildings economically viable to serve the needs of our community. We strive

More information

Corrections most seen on plan review October 18, 2017 David Rankin Seattle Department of Construction and Inspections

Corrections most seen on plan review October 18, 2017 David Rankin Seattle Department of Construction and Inspections Corrections most seen on plan review October 18, 2017 David Rankin Seattle Department of Construction and Inspections One-Line / Riser Diagrams Drawings are not reviewed prior to submission. Because of

More information

City of Perris Development Services Building & Safety

City of Perris Development Services Building & Safety Western Riverside County Code Uniformity Program City of Perris Development Services Building & Safety Residential Electric Vehicle (EV) Charger Guidelines PHONE NUMBER 951-943-5003 Inspection Request

More information