(The actual state exam will be closer to 50 questions in 4 hours time) Master Electrician Practice Test

Size: px
Start display at page:

Download "(The actual state exam will be closer to 50 questions in 4 hours time) Master Electrician Practice Test"

Transcription

1 (The actual state exam will be closer to 50 questions in 4 hours time) Master Electrician Practice Test 1. Accessible as applied to wiring methods means capable of being removed or exposed without damaging the building structure or finish. a)t b)f 2. A building is a structure that stands alone or is that which is cut off from adjoining structures by firewalls with all openings protected by approved fire doors. a)t b)f 3. An equipment bonding jumper is the connection between the grounded circuit conductor and the equipment grounding conductor at the service. a)t b)f 4. A weatherproof fixture is constructed or protected so that moisture will not enter the enclosure under specified test conditions. a)t b)f 5. Wet locations include those which are underground or in concrete slabs or masonry in direct contact with earth. a)t b)f 6. Termination provisions for equipment for circuits rated over 100 amperes, or marked for conductors larger than #1 AWG shall be used only for conductors whose insulation rating is degrees centigrade. a) 30 b) 86 c) 75 d) 60

2 7. The working space depth of equipment with exposed live parts on one side and grounded parts on the other side, energized at less than 150 volts shall be feet. a) 3 b) 3 1/2 c) 10 d) 4 8. The minimum headroom of working spaces about service equipment, switchboards, panel boards, or motor control centers shall be feet. a) 7 b) 6 1/2 c) 6 d) none of the above 9. If a high discharge lamp is operating between 277 volts and 600 volts for tunnel lighting it must be mounted no less than feet high. a) 12 b) 14 c) 18 d) When replacing an outlet in a location that has no ground conductor which of the following is acceptable?: a)replace with the same type of non-grounded receptacle b)tear out the wallboard and pull a ground c)replace with a GFCI labeled "No Ground" d) a or c e)none of the above 11. If an electrician installs an outlet behind a freezer in an unfinished basement, it must be of the GFCI type: a)t b)f 12. For household ranges and cooking appliances the branch circuit supplying an 8 3/4 KW range shall have a minimum rating of. a) 8 KW b) 20 Amp c) 10 KW d) 40 Amp

3 13. Where fixed multi-outlet assemblies used in other than dwellings and where appliances are unlikely to be used simultaneously each 5 feet shall be considered to be VA. a) 90 b) 120 c) 180 d) In Wisconsin as far as the maximum number of service disconnects there shall be no more than in any one location. a) 6 b) 1 c) 2 d) For a one-family dwelling the feeder disconnect shall have a rating not less than. a) 60 amps b) 100 amps c) 10,000 watts d) 90 VA 16. Conductors are considered outside a building when they are buried under not less than of concrete. a) 2 inches b) 4 inches c) 6 inches d) 8 inches 17. The vertical clearance from ground level over a residential driveway for overhead service conductors not subject to truck traffic and are less than 300 volts to ground shall be ft. a) 10 b) 12 c) 15 d) The minimum size conductor for an underground lateral is. a)#4 copper / #6 aluminum b) #2 copper / #8 aluminum c)#8 copper / #6 aluminum d) #10 copper / #12 aluminum

4 19. Which of the following is used in calculating the minimum sized rating of a service entrance conductor? a) 100% of actual load b) sum of non-continuous load c) sum of the non-continuous load plus 125% of the continuous load d) sum of the inductive load times 2 pi 20. In a multiple-family dwelling shall have access to the service disconnecting means. a) owner / manager b) Superintendent c) each occupant d) utility electrician 21. Unless otherwise specified the current protection for a #14 AWG copper conductor shall not exceed amps. a) 10 b ) 1 5 c) 20 d) Type fuses shall fit Edison-base fuse holders. a) A b) M c) X d) S 23. Which of the following may be used to connect bonding and grounding equipment? a) Exothermic welding b) Sheet metal screws c) Solder d) Listed pressure connectors e) a and c only f) a and d only

5 24. Alternating current circuits less than 50 volts shall be grounded when the transformer supply exceeds volts. a) 50 b) 120 c) 150 d) Where parallel service entrance conductors are used they may be no less than AWG. a) 10 b) 1 c) 2 d) 1 / The main boding jumper shall be sized not less than % of the area of the largest phase conductor exceeding 1100 kcmil copper or 1750 kcmil aluminum. a) 12 1/2 b) 1 5 c) 30 d) If the service entrance conductors are 3/0, what size copper grounding electrode conductor is required. a) 2 AWG b) 4 AWG c) 6 AWG d) 8 AWG 28. What is the minimum size equipment grounding conductor allowable for a 200 amp service? a) # 8 cu b) # 6 al c) #6 cu d) #4 al e) a and b f) c and d

6 29. The grounding conductor for secondary circuits of instrument transformers shall not be smaller than AWG copper or AWG aluminum. a) 10, 12 b) 12, 10 c) 12, 14 d) 14, Bored holes for conductors through joists and wood members shall be bored so the edge of the hole is not less than from the nearest edge of the wood member. a) 1" b) 1 1/4' c) 1' d) 1 1/4" 31. Underground conductors, directly buried, shall be protected by enclosures or raceways extending to a point above ground and at least below ground. a) 6, 12" b) 8, 18" c) 10, 24" d) 12, 36" 32. What is the burial depth for conductors in PVC under a residential driveway? a) 6" b ) 4 " c) 12" d) 18" 33. Supports for vertical conductor runs size 2/0 aluminum can be no less than apart? a) 100 ft b) 50 ft c) 180 ft d) 140 ft 34. Temporary electrical power and lighting installations shall be permitted for a period not exceeding days for Christmas decorative lighting and similar purposes. a) 30 b) 60 c) 75 d) 90

7 35. Paralleled conductors in each phase, neutral, or grounded circuit conductor shall: a) Be the same length b) Be made of the same material c) Be the same circular mil area d) Have the same insulation type e) Be terminated in same manner f) All the above g) a / c only 36. When a conductor has a "-2" such as RHW-2 it means that that the conductor shall be permitted to be used at what highest continuous operating temperature? a) 30 C b) 60 C c) 90 C d) 86 F 37. If there are eight current carrying conductors in the same raceway by what percentage must they be derated in ampacity? a) 90% b) 80% c) 70% d) 60% 38. What minimum size aluminum conductors may be used for a 120 / 240 volt, 3-wire, single phase dwelling for a 150 amp service? a) 2/0 b) 3/0 c) 2 d) What is the maximum allowable amperage for a #1 AWG Copper THHN conductor? a) 110 b) 130 c) 150 d) 115

8 40. What is the maximum allowable amperage for the #1 AWG Copper conductor in Question 39 if it is ran behind a boiler with an ambient temperature of 131 F? a) 45.1 amps b) amps c) amps d) 97.6 amps 41. Intermediate metal conduit shall be supported at intervals not exceeding? a) 10 ft b) 12" c) 36" d) 5 ft 42. Rigid Metal Conduit shall be fastened from each outlet box but that distance can be extended to where structural members do not readily permit fastening. a) 3ft--5 ft b) 4 ft--8 ft c) 5 ft--10 ft d) 6 ft--8 ft 43. The sum of the cross sectional area of all contained conductors at any cross section of wireway shall not exceed % of the cross sectional area of the wireway. a) 10 b) 30 c) 20 d) What is the maximum number of #12 AWG conductors allowed inside a 4 x 11/2 square box? a) 8 b) 9 c) 17 d) As pertaining to box fill calculations what is the volume of a #10 AWG conductor? a) 2.5 cu in b) 2.25 cu in c) 2.00 cu in d) 1.75 cu in

9 46. The distance between raceway entries in an angle pull box enclosing the same conductor shall not be less than times the trade diameter of the largest raceway. a)2 b)3 c)4 d)6 47. In straight pulls, the length of the box shall not be less than times the diameter of the largest raceway. a) 24 b) 6 c) 36 d) The allowable ampacity of a #16 AWG fixture wire is amps. a) 2 b) 4 c) 6 d) When installed in a storage closet in a dwelling a recessed fluorescent luminaire must be located inches away from shelved or hanging clothing. a) 10 b) 12 c) 4 d) Outlet boxes or fittings installed as required by the code shall be permitted to support fixtures weighing lbs or less. a) 25 b ) 3 5 c) 50 d) 6

10 51. The branch circuit rating for an appliance that is continuously loaded, other than a motor operated appliance, shall not be less than % of its nameplate rating if listed for continuous loading. a) 50 b) 100 c) 80 d) Ceiling suspended paddle fans exceeding lbs shall be supported independently of the outlet box. a) 35 b) 40 c) 45 d) Branch circuit sizing for fixed resistance heating elements shall not be less than % of the total load of the motors and heaters. a) 80 b) 100 c) 115 d) Resistance type heating elements in electric space heating equipment shall be protected at not more than amps. Equipment rated at more than amps shall have its heating elements subdivided and each load shall not exceed 48 amps. a) 10, 30 b) 20, 60 c) 15, 45 d) 60, What color would designate 208 VAC as pertaining to space heating cables? a)red b) orange c) blue d) brown

11 56. As far as adjustable speed drive systems are concerned the disconnecting means shall be permitted to be in the incoming line to the conversion equipment and at a rating of not less than % of the rated input current of the conversion unit. a) 115 b) 125 c) 80 d) A locked rotor indicating code letter for a motor rated between kilo-volt amps at locked rotor would be? a)a b)k c)n d)t 58. The minimum wire bending space at the terminals of enclosed motor controllers for a size 1/0 conductor is inches. a) 2 b) 4 c) 5 d) The Ultimate Trip Current of a thermally protected motor shall not exceed % of the full load current given in Tables to as 9 amperes. a) 125 b) 115 c) 140 d) What is the full load current of a 208 Volt 3-phase 10 HP motor? a) 32.2 a b) 30.8 a c) 28.0 a d) 55.0 a

12 61. What is the maximum rating of motor branch circuit short circuit and ground fault protection when using an inverse time breaker to protect a 2 HP single phase 120 volt motor? a) 150% FLC b) 250% FLC c) 300% FLC d) 800% FLC 62. Where a flexible supply cord is used to supply a room air conditioner the length of cord shall not exceed ft for 120 VAC and ft for a 240 VAC rating. a) 10, 6 b) 8, 6 c) 8, 5 d) 10, Transformer vaults shall be located where they can be ventilated to the outside air without using flues or ducts whenever such an arrangement is possible. a) T b) F 64. The ampacity of capacitor circuit conductors shall not be less than % of the rated current of the capacitor. a) 110% b) 125% c) 115% d) 135% 65. Dust-Ignitionproof protection technique shall be permitted for Class II, Division 1and 2 locations. a) T b) F 66. If you saw T3 on a piece of industrial machinery, in a hazardous area what surface temperature would be designated? a) 450 F b) 300 C c) 215 F d) 200 C

13 67. A Class I Division 2 location is where combustible is not normally present in sufficient quantities to produce explosion. a) gas b) dust c) fibers d) paper 68. An explosion proof seal must be placed in each conduit entry into explosion proof enclosure where either the enclosure contains the apparatus, where high temperatures are considered to be an ignition source, or the entry is 2 inches or larger and the enclosure contains splices, terminals, o r t a p s i n a l o c a t i o n. a) Class I Division 1 b) Class II division 1 c) Class I Division 2 d) Class II Division 2 e) a and b only f) c and d only 69. When sealing Class II Division 1 and 2 locations it is permissible to use which of the following: a) A permanent seal b) A horizontal raceway not less than 10 ft long c) A vertical raceway not less than 5 ft downward d) all the above e) a and c f) none of the above 70. A location 15 ft away from a gas dispensing pump would be considered a location. a) Class I Division 1 b) Class I Division 2 c) Class II Division 1 d) Class II division The demand factor for feeders and service conductors at a mobile home park would be % for a park containing up to 40 units? a) 100% b) 44% c) 28% d) 24%

14 72. Each patient bed in a critical care area of a hospital shall be provided with a minimum of receptacles? a) 2 b) 4 c) 6 d) The demand factor for site feeders and service entrance conductors for an RV Park would be for a park with 25 sites? a) 38% b) 42% c) 88% d) 100% 74. Branch circuits that supply both outline lighting and signs containing incandescent and fluorescent forms of illumination shall not be rated more than amps. a)20 b)30 c)40 d) In a hoist way for an elevator it is permissible to use liquid tight flexible conduit in lengths over 6 feet. a)t b)f 76. Non-metallic raceways supplying swimming pool equipment must be buried at a minimum of inches. a) 6 b) 8 c) 18 d) A circuit breaker is best considered as: a)overload device b) over current device c)a switch d) a fuse

15 78. Another name for an overload device would be: a) heater b) fuse c) thermal reset d) breaker 79. The conductors found between the service panel and a sub-panel would be referred to as. a) feeder b) branch circuit c) service conductor d) hidden wiring 80. An outlet to a water heater would be best described as. a)dedicated b) individual c)protected d) 2 - phase 81. Cord and plug connected loads shall not exceed % of the branch circuit rating. a) 100 b) 80 c) 125 d) Branch circuits supplying more than one load are rated at 20, 30, 40, 50, and amperes only. a) 100 b) 60 c) 25 d) What is the maximum cord and plug load to receptacle rating for a 20 amp receptacle? a) 24 b) 16 c) 12 d) 10

16 84. What is the minimum size conductor allowed for a 15 amp branch circuit in a dwelling? a) 18 AWG b) 14 AWG c) 16 AWG d) 12 AWG 85. The total rating of an A/C unit fastened in place shall not exceed % of its branch circuit rating if lighting is also supplied? a) 100 b) 80 c) 125 d) In a dwelling the circuit conductors for a 15 amp branch circuit must have a minimum ampacity of amperes? a) 15 b) 20 c) 12 d) What would be the derating factor for 16 current carrying conductors in a 50 foot section of IMC conduit? a) 80% b) 70% c) 50% d) 45% 88. A continuous load is a load that is expected to stay energized for or more? a) 3 hours b) 6 hours c) 8 hours d) forever 89. If a branch circuit is wired with #12 THW the maximum OCD permitted when supplying eight 2 amp luminaires wired in place is amps? a) 30 b) 20 c) 15 d) 25

17 90. Which of the following are not considered to be continuous general lighting loads according to the National Electrical Code? a)show window lighting b) dwellings c)motel room lighting d) bank lobby lighting e)a and d only f) b and c only 91. An 8000 sq. ft. Barber shop would require how many 20 amp lighting circuits? a) 6 b) 10 c) 13 d) The main purpose of Table is: {Table (B) } a)determine the maximum ampacity of a conductor b)adjust ampacity by ambient temperature c)prevent electrical fires started by insulation melt down d)determine the minimum allowable size conductor e)a and b f) c and d g) all the above 93. You must count the neutral in a balanced 3-phase Wye system when derating current carrying conductors in a single raceway. a)t b)f 94. A #12 TW copper conductor has an ampacity of 20 amps. In an ambient temperature of 110 F the adjusted ampacity would be? a) 14.2 A b) 16.4 A c) 17.4 A d) 18.2 A

18 95. THHN conductors have a 90 C rating but only for derating purposes. When using THHN for installations in circuits rated over 100A would come out of the column? a) 30 C b) 60 C c) 75 C d) 106 C 96. When connecting THHN conductors that have a 90 C insulation rating to unmarked equipment terminations you must use the column of table ? a) 30 C b) 60 C c) 90 C d) 86 F amp service disconnect conductors may be loaded to 's column? a) 30 C b) 60 C c) 75 C d) 90 C 98. What is the ampacity of a #10 TW conductor in a conduit with 6 other current carrying conductors in an ambient temperature of 30 C? a) 30a b) 21a c) 24a d) 15a 99. Thirteen #14 THHN conductors are routed through an 18 inch long conduit and must be derated by? a) 65% b) 80% c) 90% d) 0% 100. A 26 inch nipple contains seven #10 THW current-carrying conductors in an ambient temperature of 30 C. What is the adjusted ampacity percentage? a) not required b) 30% c) 70% d) 80%

19 Answers and Code sections for the Master Practice Exam 1.A, Art. 100 Definitions 2.A, Art. 100 Definitions 3.B, Art. 100 Definitions 4.B, Art. 100 Definitions 5.A, Art. 100 Definitions 6.C, ( C)(1)(b) 7.A, Table (A)(1) condition 1 8.B, (E) 9.C, 210.6(D)(1)b 10. D, 406.3(D)(3)a----b; NEC 11. A, 210.8(A)(5) 12. D, (A)(3) 13. C, (H)1 14. A, (A) 15. B, (C) 16. A, 230.6(1) 17. B, (B)(2) 18. C, Art. 230 Part-III 19. C, Art 230 Part IV 20. B,240.4(D) 21. B, 240.4(D)

20 22. D, F, C, (A)(1) 25. D, (A)(8)b; (A)(3)(b) 2011 NEC 26. A, (D) 27. B, Table F, Table B, B, 300.4(A)(1) 31. B, 300.5(D)(1) 32. D, Table C, Table (A) 34. D, 590.3(B) 35. F, 310.4(1)---(6); 310.4(H)(2) 2011 NEC 36. C Table footnote C Table (B)(2)a; (B)(2)(a) 38. A Table (B)(6); (B)(7) 2011 NEC 39. A, Table ( C)(1)b(2); (B) NEC 40. A, A, 342.(B)(1) 42. A (A) 43. C,

21 44. B, Table (A) 45. A, Table (B) 46. D, (A)(2) 47. D, (A)(1) 48. D, Table D, 410.8(D)(3); ( C) NEC 50. C, (B) 51. D, (A) 52. A ; (D) 53. D,424.3(B) 54. D, (B) 55. C, (2) 56. A, Fig 430-1; 430 Part IX; D, Table 430.7(B) 58. C Table (B) 59. D, (A)(2) 60. B, Table B, Table A A, D 460.8(A) 65. A, 500.7(B) 66. D, Table 500.8(B); Table 500.8( C) 2011 NEC

22 67. A, 500.5(B)(2); 500.5(C)(2) 2011 NEC 68. A, (A)(1) 69. D, B, Fig 514.3; Table 514(B)(1) 71. D, Table C, (B)(1): NEC; NEC 73. B, Table A, 600.5(B)(1) 75. B, (A)(1)d 76. C, Table B, General 78. A, General 79. A, General 80. B, Definition 81. B, (A)(1) 82. D, (B)(3) 83. B, Table (B)(2) 84. B, Table D, (A)(2) 86. A, Table C, Table (B)(2)(a); Table (B)(3)(a)

23 88. A, 100 Definitions 89. B, 240.4(D) 90. F, (J) 91. C, [8000 x 3VA = 24000VA/(20A x 120V x80%) = 12.5] 92. G, Art. 90 Purpose; Table ; Table (B) NEC 93. B; balanced Wye = 0 neutral current 94. A,Table (A) (.71 x 20A) = 14.2A 95. C Table ; ( C); Table 31-15(B) NEC 96. B assume 60 C for unmarked terminals 97. B, Table ; C Table (.70 x 30A ) = 21A; Table (B)(3)(a) 2011 NEC 99. D, Chapter 9; notes to tables (4)

24 100. C, See Ques. 98 asked in a different wa y

CHAPTER V RESIDENTIAL WIRING

CHAPTER V RESIDENTIAL WIRING CHAPTER V RESIDENTIAL WIRING 5.1. THE SERVICE ENTRANCE Buildings and other structures receive the electrical energy through the service entrance. In residential wiring, the electric company supply this

More information

Spring Test 7 due 05/03/2013

Spring Test 7 due 05/03/2013 Spring Test 7 due 05/03/2013 Multiple Choice Identify the choice that best completes the statement or answers the question. 1. A raceway contains two 3-phase, 3-wire circuits that supply 38 ampere continuous

More information

Pretest Module 24 Three-phase Service Entrance

Pretest Module 24 Three-phase Service Entrance Pretest Module 24 Three-phase Service Entrance 1. What is the most widely used three-phase service entrance system? 2. What are the three most common voltage combinations for three-phase, four-wire systems?

More information

Spring Test 10 due 05/11/2013

Spring Test 10 due 05/11/2013 Spring Test 10 due 05/11/2013 Multiple Choice Identify the letter of the choice that best completes the statement or answers the question. 1. When installed in an agricultural building that houses livestock

More information

Electrical Tech Note 105 Agricultural Engineering Department Michigan State University

Electrical Tech Note 105 Agricultural Engineering Department Michigan State University Electrical Tech Note 105 Agricultural Engineering Department Michigan State University Journey Exam Study Guide and Sample Questions 1 Based on the 2002 NEC, Part 8 of PA 230, and the 2003 MRC The Journey

More information

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 2/8/12 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 2/8/12 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions MECKLENBURG COUNTY Land Use and Environmental Service Agency Code Enforcement 2/8/12 ELECTRICAL CONSISTENCY MEETING Code Consistency Questions 1. I am inspecting a building addition. They have a 480V to

More information

Electrical Tech Note 106

Electrical Tech Note 106 Electrical Tech Note 106 Biosystems & Agricultural Engineering Department Michigan State University Master Exam Study Guide and Sample Questions 1 Based on the 2014 NEC, Part 8 of PA 230, PA 407, and the

More information

Chapter 2 Wiring and Protection Article 200 Use and Identification of Grounded Neutral Conductor Chapter 1 General...9

Chapter 2 Wiring and Protection Article 200 Use and Identification of Grounded Neutral Conductor Chapter 1 General...9 Article 90 Introduction...1 90.1 Purpose of the NEC...1 90.2 Scope of the NEC...2 90.3 Code Arrangement...4 90.4 Enforcement...5 90.5 Mandatory Requirements and Explanatory Material...6 90.6 Formal Interpretations...6

More information

ADVANCED CALCULATIONS

ADVANCED CALCULATIONS ADVANCED CALCULATIONS 101. Why is it permissible in some cases to fuse a #14 AWG motor conductor with a 60 amp breaker when normally a #14 AWG should only be fused at 15 amps? a) the motor can't start

More information

TEMPORARY ELECTRIC WIRING FOR CARNIVALS, CONVENTIONS, EXHIBITIONS, FAIRS AND SIMILAR USES

TEMPORARY ELECTRIC WIRING FOR CARNIVALS, CONVENTIONS, EXHIBITIONS, FAIRS AND SIMILAR USES INFORMATION BULLETIN / PUBLIC - ELECTRICAL CODE REFERENCE NO.: LAMC 93.0230 Effective: 3-24-69 DOCUMENT NO. P/EC 2002-006 Revised: 11-17-00 Previously Issued As: RGA #7-69 TEMPORARY ELECTRIC WIRING FOR

More information

SINGLE PHASE WIRING SPECIFICATIONS

SINGLE PHASE WIRING SPECIFICATIONS SINGLE PHASE WIRING SPECIFICATIONS 1-866-MEC-ELEC (1-866-632-3532) Office Locations: Hondo Office 237 Hwy 173 N Hondo, TX 78661-0370 Fax 830.426.3335 Dilley Office 1718 W. FM 117 Dilley, TX 78017 Fax 830.965.1425

More information

THREE PHASE WIRING SPECIFICATIONS

THREE PHASE WIRING SPECIFICATIONS THREE PHASE WIRING SPECIFICATIONS 1-866-MEC-ELEC (1-866-632-3532) Office Locations: Hondo Office 237 Hwy 173 N Hondo, TX 78661-0370 Fax 830.426.3335 Dilley Office 1718 W. FM 117 Dilley, TX 78017 Fax 830.965.1425

More information

Mecklenburg County Common Code Defects

Mecklenburg County Common Code Defects Electrical Code Defects Improper Over Current Protection Code Description 310.15 Ampacities for s Rated 0 2000 Volts. (A) General. (1) Tables or Engineering Supervision. Ampacities for conductors shall

More information

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 9/14/11 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 9/14/11 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions MECKLENBURG COUNTY Land Use and Environmental Service Agency Code Enforcement 9/14/11 ELECTRICAL CONSISTENCY MEETING Code Consistency Questions 1. I recently installed a 45-KVA transformer, 480-volt primary

More information

Fee $20 Course: NEC Changes 1 This course is valid for these credentials: Credential Description Cred Code Credit Hours

Fee $20 Course: NEC Changes 1 This course is valid for these credentials: Credential Description Cred Code Credit Hours www.garyklinka.com Page 1 of 18 Instructions: Fee $20 1. Print these pages. 2. Circle the correct answers and transfer them to the answer sheet. 3. Page down to the last page for the verification forms

More information

NEC 2014 Code Changes

NEC 2014 Code Changes NEC 2014 Code Changes Articles 310 310.120 CHANGES FROM 2011 TO 2014 CODE ARE IN RED ARTICLE 310 Conductors for General Wiring I. General 310.2 Definitions Electrical Ducts Electrical conduits, or other

More information

Volume 2 Charts, Formulas, and Other Useful Information

Volume 2 Charts, Formulas, and Other Useful Information Volume 2 Charts, Formulas, and Other Useful Information Aluminum Conductor Conductor Terminations 61 Compact Aluminum (Conduit Fill Tables) 68-79 Ampacity Dwelling Services 48 1-phase Loads on a 3-phase

More information

The Reliable Choice. Field Pocket Guide

The Reliable Choice. Field Pocket Guide The Reliable Choice Field Pocket Guide Allowable Ampacities of STABILOY Brand XHHW-2 and Copper 75 C (167 F) 90 C (194 F) 75 C (167 F) 90 C (194 F) Conductor Size (AWG or kcmil) Types RHW, THHW, THW, THWN,

More information

grounded in service wired to innovate STABILOY Type XHHW-2 and USE-2/RHH/RHW-2

grounded in service wired to innovate STABILOY Type XHHW-2 and USE-2/RHH/RHW-2 grounded in service wired to innovate STABILOY Type XHHW-2 and USE-2/RHH/RHW-2 grounded in service wired to innovate www.cable.alcan.com Type XHHW-2 and Type USE-2/RHH/RHW-2 Alcan manufactures XHHW-2 and

More information

Electrical Design/Build Guide

Electrical Design/Build Guide 2017 Electrical Design/Build Guide Based on the 2017 National Electrical Code Copyright Durand & Associates 1986-2016 60 C Copper Ampacity 4 - Wire Fill - (Non-Current Carrying Neutral) 4 or 5 - Parallel

More information

TABLE OF CONTENTS CHAPTER 1 ELECTRICAL THEORY About This Textbook...xi. Passing Your Exam...xiv. How to Use the National Electrical Code...

TABLE OF CONTENTS CHAPTER 1 ELECTRICAL THEORY About This Textbook...xi. Passing Your Exam...xiv. How to Use the National Electrical Code... TABLE OF CONTENTS About This Textbook...xi Passing Your Exam...xiv How to Use the National Electrical Code... 1 CHAPTER 1 ELECTRICAL THEORY... 7 Unit 1 Electrician s Math and Basic Electrical Formulas...

More information

Customer Requirements Downtown Secondary Network Service

Customer Requirements Downtown Secondary Network Service Application This standard describes the limitations and requirements for receiving service from the Tacoma Power secondary network system within the City of Tacoma downtown core area. In This Standard

More information

90.2 Scope. The installation of electrical conductors, equipment and raceways for:

90.2 Scope. The installation of electrical conductors, equipment and raceways for: NEC Generator Primer Rules on the installation of generators and transfer switches 1 90.2 Scope The installation of electrical conductors, equipment and raceways for: public and private premises Conductors

More information

ECET Circuit Design Motor Loads. Branch Circuits. Article 210

ECET Circuit Design Motor Loads. Branch Circuits. Article 210 ECET 4520 Industrial Distribution Systems, Illumination, and the NEC Circuit Design Motor Loads Branch Circuits Article 210 210.1 Scope This article covers branch circuits except for those that supply

More information

AGRICULTURAL UNDERGROUND SERVICE 500 HP OR LESS

AGRICULTURAL UNDERGROUND SERVICE 500 HP OR LESS Prepared by: ABB1 AGRICULTURAL UNDERGROUND SERVICE 500 HP OR LESS 05619 Asset Type: Electric Metering Function: Design and Construction Issued by: Lisseth Villareal (LDV2) Date: 07-31-15 Rev. #10: This

More information

Generator Fire Safety: Generator assemblies should be located outside the building.

Generator Fire Safety: Generator assemblies should be located outside the building. SECTION 33 70 00 - ELECTRICAL DISTRIBUTION PACKAGED GENERATOR ASSEMBLIES Generator Fire Safety: Generator assemblies should be located outside the building. All fuel piping from the outside of the building

More information

TABLE OF CONTENTS. About the Mike Holt Enterprises Team... xviii CHAPTER 1 ELECTRICAL THEORY... 1

TABLE OF CONTENTS. About the Mike Holt Enterprises Team... xviii CHAPTER 1 ELECTRICAL THEORY... 1 TABLE OF CONTENTS Introduction...xv About the Mike Holt Enterprises Team... xviii CHAPTER 1 ELECTRICAL THEORY... 1 Unit 1 Electrician s Math and Basic Electrical Formulas... 1 Part A Electrician s Math...

More information

PART A General Conductor Requirements

PART A General Conductor Requirements PART A General Conductor Requirements 6.1 Conductor Insulation Property Table 310.13 of the NEC provides information on conductor properties such as permitted use, maximum operating temperature, and other

More information

Photovoltaic Solar Plan Review

Photovoltaic Solar Plan Review PAIGE B. VAUGHAN, CBO Director of Building and Safety Phone (310) 605-5509 Fax Line (310) 605-5598 E-mail:lbutler@comptoncity.org Building & Safety Department Photovoltaic Solar Plan Review Plan Check

More information

UNDERGROUND SERVICES - SECONDARY

UNDERGROUND SERVICES - SECONDARY UNDERGROUND SERVICES - SECONDARY Contents - Underground Services... U-1 General Requirements for Underground Service...U-2 Names of Parts for Underground Service... U-3 Service Termination in a Service

More information

Electrical Tech Note 111 Biosystems & Agricultural Engineering Department Michigan State University

Electrical Tech Note 111 Biosystems & Agricultural Engineering Department Michigan State University Electrical Tech Note 111 Biosystems & Agricultural Engineering Department Michigan State University Electrical Code Changes in Michigan 1 (Based on Part 8, P.A. 230, the 2005 NEC and the 2003 MRC) This

More information

Have You Been Grounded Lately

Have You Been Grounded Lately Have You Been Grounded Lately Thurs, Oct. 26, 2017 9:15-10:15 Phil Simmons Author, Electrical Grounding and Bonding Author Cengage Learning Phil Simmons Have You Been Grounded Lately 2017 NEC Changes Relative

More information

Chapter 1 Electrical Theory...1

Chapter 1 Electrical Theory...1 Electrical Formulas with Sample Calculations Table of Contents Chapter 1 Electrical Theory...1 Unit 1 Electrician s Math and Basic Electrical Formulas...3 Part A Electrician s Math...3 1 1 Fractions...3

More information

2016 Photovoltaic Solar System Plan Review List

2016 Photovoltaic Solar System Plan Review List Building Division 555 Santa Clara Street Vallejo CA 94590 707.648.4374 2016 Photovoltaic Solar System Plan Review List GENERAL PROJECT INFORMATION PLAN CHECK NO DATE JOB ADDRESS CITY ZIP REVIEWED BY PHONE

More information

2011 NEC Code Updates Part 3

2011 NEC Code Updates Part 3 www.garyklinka.com Page 1 of 22 Instructions: Fee $35 1. Print these pages. 2. Circle the correct answers and transfer them to the answer sheet. 3. Page down to the last page for the verification forms

More information

Western Section 101 st Annual Meeting Hot Springs, Arkansas September 21, 2005 Charlie Trout Code Breakfast

Western Section 101 st Annual Meeting Hot Springs, Arkansas September 21, 2005 Charlie Trout Code Breakfast Western Section 101 st Annual Meeting Hot Springs, Arkansas September 21, 2005 Charlie Trout Code Breakfast 1.Question: An add on unit for a hydromassage bathtub consists of a small 1-gallon water heater

More information

Corrections most seen on plan review October 18, 2017 David Rankin Seattle Department of Construction and Inspections

Corrections most seen on plan review October 18, 2017 David Rankin Seattle Department of Construction and Inspections Corrections most seen on plan review October 18, 2017 David Rankin Seattle Department of Construction and Inspections One-Line / Riser Diagrams Drawings are not reviewed prior to submission. Because of

More information

Section 6 Electric Metering: Residential

Section 6 Electric Metering: Residential Section 6 Electric Metering: Residential 6.1. Scope This section provides specific information for residential metering that is not covered by the basic requirements in Section 5, Electric Metering: General.

More information

Chapter 8 Interior Wiring and Lighting

Chapter 8 Interior Wiring and Lighting Chapter 8 Interior Wiring and Lighting Review Questions 1. What tool if any, is used to remove a fuse that is to be replaced? 1. Pliers 2. Screwdriver 3. Fuse puller 4. None 2. OSHA has established specific

More information

See Part 3 for the Introduction for Article 314

See Part 3 for the Introduction for Article 314 See Part 3 for the Introduction for Article 314 76 314.25 Covers and Canopies When the installation is complete, each outlet box must be provided with a cover or faceplate, unless covered by a fixture

More information

Data Bulletin. Wire Temperature Ratings and Terminations INTRODUCTION WHY ARE TEMPERATURE RATINGS IMPORTANT?

Data Bulletin. Wire Temperature Ratings and Terminations INTRODUCTION WHY ARE TEMPERATURE RATINGS IMPORTANT? Data Bulletin March 2002 Lexington, KY, USA Wire Temperature Ratings and Terminations INTRODUCTION WHY ARE TEMPERATURE RATINGS IMPORTANT? Table 1: Insulation Type Figure 1: Figure 2: Ampacity of a 1/0

More information

Western Section IAEI Code Panel Questions

Western Section IAEI Code Panel Questions Western Section IAEI 2013 Code Panel Questions 1. Do the factory wings that many fluorescent troffers have designed to fold out over the grid meet the requirements for securely fastened to the framing?

More information

NEC 2011 Code Changes

NEC 2011 Code Changes NEC 2011 Code Changes Articles 280.21-300.50 CHANGES FROM 2008 TO 2011 CODE ARE IN RED Chapter 2 - Wiring and Protection ARTICLE 280 Surge Arresters, Over 1kV III. Connecting Surge Arresters 280.21 Connection

More information

Table of Contents. CHAPTER 1 ElECTRiCAl THEoRY Mike Holt enterprises, inc neC.Code ( )

Table of Contents. CHAPTER 1 ElECTRiCAl THEoRY Mike Holt enterprises, inc neC.Code ( ) CHAPTER 1 ElECTRiCAl THEoRY... 1 UniT 1 electrician s MaTH and BasiC electrical formulas... 3 Introduction to Unit 1... 3 Part A Electrician s Math... 3 Introduction... 3 1.1 Whole Numbers... 3 1.2 Decimals...

More information

9/16/2010. Chapter , The McGraw-Hill Companies, Inc. TRANSMISSION SYSTEMS. 2010, The McGraw-Hill Companies, Inc.

9/16/2010. Chapter , The McGraw-Hill Companies, Inc. TRANSMISSION SYSTEMS. 2010, The McGraw-Hill Companies, Inc. Chapter 3 TRANSMISSION SYSTEMS 1 Transmitting large amounts of electric energy over long distances is accomplished most efficiently by using high-voltages. Without transformers the widespread distribution

More information

UNIT 1 ELECTRICIAN S MATH AND BASIC ELECTRICAL FORMULAS...1 Introduction...1. UNIT 2 ELECTRICAL CIRCUITS...49 Introduction...49

UNIT 1 ELECTRICIAN S MATH AND BASIC ELECTRICAL FORMULAS...1 Introduction...1. UNIT 2 ELECTRICAL CIRCUITS...49 Introduction...49 UNIT 1 ELECTRICIAN S MATH AND BASIC ELECTRICAL FORMULAS...1 Introduction...1 PART A ELECTRICIAN S MATH...1 Introduction...1 1.1 Whole Numbers...1 1.2 Decimal...1 1.3 Fractions...1 1.4 Percentages...2 1.5

More information

SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS - ELECTRICAL

SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS - ELECTRICAL SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS - ELECTRICAL This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly.

More information

Pentahead bolts See note 2. Conduit run as specified. Company facility. Refer to drawing SS8.6-2 or SS8.6-3 STANDARD SERVICE INSTALLATION

Pentahead bolts See note 2. Conduit run as specified. Company facility. Refer to drawing SS8.6-2 or SS8.6-3 STANDARD SERVICE INSTALLATION PULL BOX F SECONDARY SYSTEM Typical grade Pentahead bolts See note 2 Conduit run as specified Plastic or fiberglass for grass areas or Polymer concrete for light duty areas (see notes 2, 3, & 4) Company

More information

WIRING DESIGN & PROTECTION REQUIREMENTS CHECKLIST

WIRING DESIGN & PROTECTION REQUIREMENTS CHECKLIST WIRING DESIGN & PROTECTION REQUIREMENTS CHECKLIST Use & Identification of Grounded and Grounding Conductors YES NO N/A Grounded conductors are identifiable and distinguishable from all other conductors.

More information

SECTION 300 OVERHEAD SERVICE

SECTION 300 OVERHEAD SERVICE SECTION 300 OVERHEAD SERVICE 300.01 General Company provides, installs, and maintains service drop to point of delivery approved by Company. Customer provides point of attachment which is acceptable to

More information

10 Commercial, Industrial, Agricultural Services

10 Commercial, Industrial, Agricultural Services 10 Commercial, Industrial, Agricultural Services This section describes the Power Company requirements for commercial, industrial, and agricultural services. This section covers single phase and three

More information

Preface...x Chapter 1 Electrical Fundamentals

Preface...x Chapter 1 Electrical Fundamentals Preface...x Chapter 1 Electrical Fundamentals Unit 1 Matter...3 Introduction...3 1.1 Matter...3 1.2 Atomic Theory...3 1.3 Law of Electrical Charges...4 1.4 Law of Atomic Charges...5 Negative Atomic Charge...5

More information

SECTION VII METERING INSTALLATIONS

SECTION VII METERING INSTALLATIONS SECTION VII METERING INSTALLATIONS 1. GENERAL Outdoor metering is required for all new service installations to one, two, and three family detached, semi-detached and row houses. 2. COMPANY FURNISHES AND

More information

Metering and Service Installation:

Metering and Service Installation: Table of Contents 1. Metering Installation Requirements, General... 1 2. Type of Service... 2 3. Definitions... 2 4. Who Provides Metering Equipment?... 2 5. Establishment of Service... 2 6. Meter Access...

More information

Metering and Control Standards OFF-PEAK & DUAL FUEL WIRING DIAGRAMS

Metering and Control Standards OFF-PEAK & DUAL FUEL WIRING DIAGRAMS Metering and Control Standards OFF-PEAK & DUAL FUEL WIRING DIAGRAMS REVISED FEBRUARY 2017 TABLE OF CONTENTS Metering Equipment & Installation Standards... 1 Metering Equipment & Installation Standards

More information

A. Submit manufacturer's literature and technical data before starting work.

A. Submit manufacturer's literature and technical data before starting work. SECTION 16425 SWITCHBOARD PART 1 GENERAL 1.01 SUMMARY A. Related Section: 1. 16450 - Grounding. 1.02 SUBMITTALS A. Submit manufacturer's literature and technical data before starting work. B. Submit Shop

More information

Table of Contents. CHAPTER 1 BASIC ELECTRICAL THEORY (Essential for Journeyman and Master s Licensing Exams)... 1

Table of Contents. CHAPTER 1 BASIC ELECTRICAL THEORY (Essential for Journeyman and Master s Licensing Exams)... 1 Introduction... x About This Textbook...xi Passing Your Exam...xiv How to Use the National Electrical Code... xviii About the Author...xxi About the Graphic Illustrator...xxii Mike Holt Enterprises Team...

More information

PHOTOVOLTAIC ELECTRICAL POWER SYSTEMS INSPECTOR/INSTALLER CHECKLIST

PHOTOVOLTAIC ELECTRICAL POWER SYSTEMS INSPECTOR/INSTALLER CHECKLIST PHOTOVOLTAIC ELECTRICAL POWER SYSTEMS INSPECTOR/INSTALLER CHECKLIST The following checklist is an outline of the general requirements found in the 2005 National Electrical Code (NEC) Article 690 for Photovoltaic

More information

10. METERING General Requirements

10. METERING General Requirements 10. METERING 10.1 General Requirements A. The Company will not supply service to a Customer whose wiring is designed for resale of electricity through submetering except for recreational campgrounds, marinas,

More information

Table of Contents. Unit 3 Magnetism Unit 1 Matter Unit 4 Electricity Unit 2 Electron Theory Unit 5 Electromagnetism...

Table of Contents. Unit 3 Magnetism Unit 1 Matter Unit 4 Electricity Unit 2 Electron Theory Unit 5 Electromagnetism... Introduction...x How to Use This Textbook...xi About the Author...xii About the Graphic Illustrator...xiii Mike Holt Enterprises Team...xiv Chapter 1 Electrical Fundamentals... 1 Unit 1 Matter... 3 Introduction...

More information

Overcurrent Protection According to the 2011 NEC

Overcurrent Protection According to the 2011 NEC Overcurrent Protection According to the 2011 NEC Utah Electrical License This course will cover overcurrent protection according to the 2011 NEC. The key sections of Article 240 will be discussed. Overcurrent

More information

9. Non-Residential Services (Commercial, Industrial, and Agricultural)

9. Non-Residential Services (Commercial, Industrial, and Agricultural) Section 9 2016 Electric Service Requirements, 3rd Edition Section 9 Non-Residential Services Directory Page 9.1 General Requirements 68 9.2 Direct-Connect Metering, Single Installations 69 9.3 Direct-Connect

More information

SERVICE ATTACHMENT ON A BUILDING WITH BUS DUCT SERVICE ENTRANCE AND INDOOR METERING

SERVICE ATTACHMENT ON A BUILDING WITH BUS DUCT SERVICE ENTRANCE AND INDOOR METERING SERVICE ATTACHMENT ON A BUILDING WITH BUS DUCT SERVICE ENTRANCE AND INDOOR METERING Obtain acceptance and specific details from the local Company office. 1. Service entrance duct (see Note 1). Company

More information

This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly.

This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly. SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS (ELEC) This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly.

More information

Arc Fault Circuit Interrupter (AFCI) FACT SHEET

Arc Fault Circuit Interrupter (AFCI) FACT SHEET Arc Fault Circuit Interrupter (AFCI) FACT SHEET THE AFCI The AFCI is an arc fault circuit interrupter. AFCIs are newly-developed electrical devices designed to protect against fires caused by arcing faults

More information

2014 NEC Changes Part 4

2014 NEC Changes Part 4 www.garyklinka.com Page 1 of 14 Instructions: Fee $25 1. Print these pages. 2. Circle the correct answers and transfer them to the answer sheet. 3. Page down to the last page for the verification forms

More information

Approved Contractor Construction e-guide Residential Commercial

Approved Contractor Construction e-guide Residential Commercial Approved Contractor Construction e-guide Residential Commercial Clark Public Utilities PO Box 8900 Vancouver, WA 98668 (PAGE 2) TABLE OF CONTENTS PAGE Trenching 3 Wire 8 Single-Phase Transformer Set 13

More information

RESIDENTIAL SUBDIVISION SERVICE REQUIREMENTS SECTION VI RESIDENTIAL SUBDIVISION SERVICE REQUIREMENTS

RESIDENTIAL SUBDIVISION SERVICE REQUIREMENTS SECTION VI RESIDENTIAL SUBDIVISION SERVICE REQUIREMENTS SECTION VI SERVICE REQUIREMENTS This section discusses the requirements for establishing electric service to new residential subdivisions in Palo Alto. Subdivisions are normally constructed on dedicated

More information

ELECTRIC SERVICE RULES UTILITY/CATV SERVICES Issued Jan 2016

ELECTRIC SERVICE RULES UTILITY/CATV SERVICES Issued Jan 2016 UTILITY/CATV SERVICES CHAPTER 9 900. GENERAL A. Alliant Energy receives many requests for electric service from other utilities; telephone, telecommunications companies, cable television, the Department

More information

5. What is the maximum number of#18 TEW control conductors permitted to be installed into a 6 inch rigid metal conduit? a. 196 b. 138 c. 259 d.

5. What is the maximum number of#18 TEW control conductors permitted to be installed into a 6 inch rigid metal conduit? a. 196 b. 138 c. 259 d. I Practice Exam Questions :loo(p c:.e.c... 1. A construction drawing has a scale of 1:200. If a line on the drawing measured 11.5mm, what would be the actual measured length on the project? a. 2300cm b.

More information

Overcurrent Protection (2014 NEC) (Homestudy)

Overcurrent Protection (2014 NEC) (Homestudy) Overcurrent Protection (2014 NEC) (Homestudy) Oregon Electrical License The key sections of Article 240 will be discussed. Overcurrent protection for panelboards, appliances, motors, motor compressors,

More information

ENTRANCE EQUIPMENT ER D PAGE 1 OF 5

ENTRANCE EQUIPMENT ER D PAGE 1 OF 5 PAGE 1 OF 5 USE: Requirements for entrance equipment. PREVIOUS REVISION 07-01-98 ORIGINATED 03-94 PREVIOUS NUMBER ER 100 (12-01-81) LATEST REVISION: Updated meter socket labeling specification and instrument

More information

DEWALT Electrical Licensing Exam Guide CONTENTS

DEWALT Electrical Licensing Exam Guide CONTENTS DEWALT Electrical Licensing Exam Guide v ONTENTS How to Prepare for the Exam................................................ 2 How to Study.............................................................

More information

WISCONSIN ELECTRICIANS

WISCONSIN ELECTRICIANS Wisconsin Contractors Institute 2017 PART 2 3 CONTINUING EDUCATION FOR WISCONSIN ELECTRICIANS 2017 NEC Code Change Part 2 8 Hours WISCONSIN CONTRACTORS INSTITUTE N16 W23217 Stone Ridge Drive, Suite 290

More information

ELECTRICIANS REGULATIONS EXAMINATION 23 November 2013 QUESTION AND ANSWER BOOKLET

ELECTRICIANS REGULATIONS EXAMINATION 23 November 2013 QUESTION AND ANSWER BOOKLET ER54 Candidate Code No. For Board Use Only Result Date Result Date Int ELECTRICIANS REGULATIONS EXAMINATION 23 November 2013 QUESTION AND ANSWER BOOKLET Time Allowed: Three hours INSTRUCTIONS READ CAREFULLY

More information

Code Calculations. for an Off-Grid PV System

Code Calculations. for an Off-Grid PV System Code Calculations for an Off-Grid PV System John Wiles Sponsored by the Photovoltaic Systems Assistance Center, Sandia National Laboratories Judy LaPointe s home is on its way to becoming a finished, off-grid

More information

SECTION 1: Field Inspection Guide for Rooftop Photovoltaic (PV) Systems

SECTION 1: Field Inspection Guide for Rooftop Photovoltaic (PV) Systems COUNTY OF SANTA CRUZ PLANNING DEPARTMENT 701 OCEAN STREET, 4 th FLOOR, SANTA CRUZ, CA 95060 (831) 454-2580 FAX: (831) 454-2131 TDD: (831) 454-2123 KATHLEEN MOLLOY PREVISICH, PLANNING DIRECTOR Photovoltaic

More information

Chapter 5. Imagine That Engineering Inc. Assured Equipment Grounding Conductor Program (AEGCP) Ground Fault Circuit Interrupter (GFCI)

Chapter 5. Imagine That Engineering Inc. Assured Equipment Grounding Conductor Program (AEGCP) Ground Fault Circuit Interrupter (GFCI) Chapter 5 Imagine That Engineering Inc. Assured Equipment Grounding Conductor Program (AEGCP) Ground Fault Circuit Interrupter (GFCI) Imagine That Engineering Inc. has adopted this program for equipment

More information

Solar PV Standard Electrical Plan

Solar PV Standard Electrical Plan *** Provide this document to the inspector along with ALL system installation instructions *** Project Address: Permit Number: SCOPE: Standard plan for installation of solar PV systems utilizing 2 wire

More information

2011 NEC Changes Part 2 (Homestudy) (Homestudy)

2011 NEC Changes Part 2 (Homestudy) (Homestudy) 2011 NEC Changes Part 2 (Homestudy) (Homestudy) North Carolina Electrical License This course will review the second half of the most important National Electrical Code changes from the 2011 NEC. Changes

More information

CHAPTER 10 ELECTRICAL. Notes:

CHAPTER 10 ELECTRICAL. Notes: CHAPTER 10 ELECTRICAL 1001.0 General Requirements. Electrical wiring and equipment shall comply with the requirements of NFPA 70, National Electrical Code (NEC), or local ordinances. 1002.0 Solar Photovoltaic

More information

Contents. Obtaining Electric Service from Your Cooperative...1. Bonding Frames of Major Appliances...4. Voltage Drop...8. Drawings...

Contents. Obtaining Electric Service from Your Cooperative...1. Bonding Frames of Major Appliances...4. Voltage Drop...8. Drawings... Contents Obtaining Electric Service from Your Cooperative...1 Bonding Frames of Major Appliances...4 Voltage Drop...8 Drawings...14 Agricultural Buildings...23 Optional Standby Systems...42 Grounding &

More information

ELECTRICIANS REGULATIONS EXAMINATION 25 June 2011

ELECTRICIANS REGULATIONS EXAMINATION 25 June 2011 ER42 Candidate Code No. For Board Use Only Result Date Result Date Int ELECTRICIANS REGULATIONS EXAMINATION 25 June 2011 Int QUESTION AND ANSWER BOOKLET INSTRUCTIONS READ CAREFULLY Time Allowed: Three

More information

D9-3. No. WIRING DIAGRAM CONNECTIONS FOR UNDERGROUND SELF CONTAINED METERS JRH JED krich95 LINE LINE ABCN SOURCE SOURCE GROUND GROUND STUD STUD SOURCE

D9-3. No. WIRING DIAGRAM CONNECTIONS FOR UNDERGROUND SELF CONTAINED METERS JRH JED krich95 LINE LINE ABCN SOURCE SOURCE GROUND GROUND STUD STUD SOURCE SOURCE 20V 240V STUD (PER NEC) A customer supplied and installed teaser wire is required from the neutral lug to a 5th terminal mounted on the left side of the meter block between the line and load terminals.

More information

Commercial & Industrial Wiring (2014 NEC) (Homestudy)

Commercial & Industrial Wiring (2014 NEC) (Homestudy) Commercial & Industrial Wiring (2014 NEC) (Homestudy) Montana Electrical License This course will review the 2014 National Electrical Code requirements for installing commercial and industrial wiring systems

More information

TRANSMISSION SYSTEMS

TRANSMISSION SYSTEMS TRANSMISSION SYSTEMS Transmitting large amounts of electric energy over long distances is accomplished most efficiently by using high-voltages. Without transformers the widespread distribution of electric

More information

STOUGHTON UTILITIES ELECTRIC SERVICE RULES AND INFORMATION

STOUGHTON UTILITIES ELECTRIC SERVICE RULES AND INFORMATION CHAPTER 1 - GENERAL INFORMATION 100. Purpose 101. Codes and rules 102. Continuity of service 103. Frequency, Voltage, and Amperage Limitations 104. High voltages 105. Unusual capacity requirements 106.

More information

CHAPTER 10 ELECTRICAL

CHAPTER 10 ELECTRICAL 1001.0 General Requirements. 1001.1 Electrical Wiring and Equipment. Electrical wiring and equipment shall comply with the requirements of NFPA 70, National Electrical Code (NEC), or local ordinances.

More information

SURFACE TRACK (120/250V) SPECIFICATIONS

SURFACE TRACK (120/250V) SPECIFICATIONS SURFACE TRACK (120/250V) SPECIFICATIONS GENERAL Lighting Track shall allow fixtures to be located anywhere along the track length. Fixtures shall be easily focused, switched, dimmed, accessorized and removed

More information

9/7/2010. Objectives. Article 90. Introduction NEC Significant Changes. Review significant revisions in the 2011 NEC

9/7/2010. Objectives. Article 90. Introduction NEC Significant Changes. Review significant revisions in the 2011 NEC 2011 NEC Significant Changes Courtesy of NJATC Courtesy of NFPA Presented By: Michael J. Johnston Executive Director of Standards and Safety, NECA Objectives Review significant revisions in the 2011 NEC

More information

2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE

2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE 2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE PAGE 1 OF 5 This Reference provides a very comprehensive list of aspects of a solar PV installation that could be reviewed, clarifying

More information

CONTINUING EDUCATION FOR OREGON ELECTRICIANS NEC Code Change Part 2 Course # Hours

CONTINUING EDUCATION FOR OREGON ELECTRICIANS NEC Code Change Part 2 Course # Hours AMERICAN ELECTRICAL INSTITUTE 2017 PART 2 3 CONTINUING EDUCATION FOR OREGON ELECTRICIANS 2017 NEC Code Change Part 2 Course #90817 8 Hours AMERICAN ELECTRICAL INSTITUTE N16 W23217 Stone Ridge Drive, Suite

More information

NEW SERVICE HANDBOOK COMMERCIAL & IRRIGATION SUPPLEMENT

NEW SERVICE HANDBOOK COMMERCIAL & IRRIGATION SUPPLEMENT NEW SERVICE HANDBOOK COMMERCIAL & IRRIGATION SUPPLEMENT Meter Installations There are three basic ways to measure electricity consumption: Small and medium services are metered directly using direct connect

More information

Electric Drive Vehicle Infrastructure Training. Instructor s Manual. National Alternative Fuels Training Consortium

Electric Drive Vehicle Infrastructure Training. Instructor s Manual. National Alternative Fuels Training Consortium Electric Drive Vehicle Infrastructure Training Instructor s Manual National Alternative Fuels Training Consortium Part 4: : Service Panel to Receptacle Overview of Service Panel The role of the service

More information

A. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein.

A. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein. 16425 SWITCHBOARD ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 26 24 13 An optional keynote to

More information

COMMERCIAL QUICK REFERENCE

COMMERCIAL QUICK REFERENCE COMMERCIAL QUICK REFERENCE PROVO CITY POWER STANDARDS ELECTRICAL ENGINEERING UPDATED: 2016 SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTIFICATION. 18" MIN. OF TAIL. (NEUTRAL CONDUCTOR MUST BE WHITE OR

More information

ARKANSAS ELECTRICIANS

ARKANSAS ELECTRICIANS CONTINUING EDUCATION FOR ARKANSAS ELECTRICIANS 2014 NEC Code Change 8 Hours AMERICAN ELECTRICAL INSTITUTE N16 W23217 Stone Ridge Drive, Suite 290 Waukesha, WI 53188 855-780-5046 www.aeitraining.com DISCLAIMER

More information

Continued from Part 2 Rules

Continued from Part 2 Rules Continued from Part 2 Rules 26 50. 51 250.94 Grounding (Bonding) of Communications Systems An accessible bonding point must be provided at service equipment or the disconnecting means of separate buildings

More information

2. DEFINITIONS. 2.3 APPROVED Acceptable to the authority enforcing the National Electric Code

2. DEFINITIONS. 2.3 APPROVED Acceptable to the authority enforcing the National Electric Code 2. DEFINITIONS 2.1 ACCEPTABLE Acceptable to the Company. 2.2 ADVANCED METER A meter that is capable of remote reading, and is capable of storing electric consumption data at specified time intervals of

More information

Multi-Pak Group Control

Multi-Pak Group Control Multi-Pak Grouping.1 Product....................................... Application.................................... Features Enclosures........................................... V-T-2 V-T-2 V-T-2 Feeder

More information