TEMPORARY ELECTRIC WIRING FOR CARNIVALS, CONVENTIONS, EXHIBITIONS, FAIRS AND SIMILAR USES

Size: px
Start display at page:

Download "TEMPORARY ELECTRIC WIRING FOR CARNIVALS, CONVENTIONS, EXHIBITIONS, FAIRS AND SIMILAR USES"

Transcription

1 INFORMATION BULLETIN / PUBLIC - ELECTRICAL CODE REFERENCE NO.: LAMC Effective: DOCUMENT NO. P/EC Revised: Previously Issued As: RGA #7-69 TEMPORARY ELECTRIC WIRING FOR CARNIVALS, CONVENTIONS, EXHIBITIONS, FAIRS AND SIMILAR USES A. Scope. The following shall apply to temporary wiring for carnivals, conventions, exhibitions, fairs and the like, that is energized or maintained in one location for 90 days or less. B. General. 1. Temporary wiring for carnivals, conventions, exhibitions, fairs and the like, energized or maintained in one location for more than 90 days shall be installed as specified in the City of Los Angeles Electrical Code for permanent wiring. 2. An electrical permit shall be required for all installation. EXCEPTION: Electrical permits will not be required for installations that do not exceed five transportable rides where those rides are of a type that can be relocated without disassembling their component parts, and provided: a. The rides are supplied by an engine-driven single phase two-wire generator with a rated capacity of not more than 7-1/2 KVA at a maximum voltage of 125 volts; and b. The generator is equipped with suitable externally operable circuit breakers and receptacles for the supply of each ride; and c. The rides are wired to comply with the applicable provisions for temporary wiring and equipment regulations; and d. Each ride is supplied by an individual branch circuit; and e. All equipment is properly grounded; and f. The equipment is permanently and legibly labeled to establish a means of identification for inspection purposes; and h. The rides are not used in one location for more than 72 hours. 3. Except as provided in the Exception to Paragraph B-2 above, all wiring shall be inspected Page 1 of 11

2 and approved by the Department before being energized or used. Note: To expedite inspections, a notice of intent to use shall be given, either verbally or in writing, at least three days prior to the first day of use. Whenever, upon request, an inspection is made outside of regular working hours, the provisions of Section for Emergency Inspections shall apply. 4. All wiring shall be maintained so that the hazards will be reduced as far as reasonably possible. Equipment exposed to the weather shall be of the weatherproof type, or shall be suitably protected against rain and water. Where the Department finds hazardous conditions such as disabled or improper protective devices, ungrounded equipment, bare live parts or conductors, open wire used as flexible cords, or similar dangerous conditions prevailing, the installation shall be classed as an extreme hazard and shall be immediately de-energized. All defective wiring and devices shall be removed or replaced before the system is energized. 5. Except where modified by these provisions, all wiring and equipment shall be installed to comply with the applicable provisions of the code. C. Portable Electrical Sub-Stations. 1. For the purpose of these provisions, a portable sub-station is defined as any transportable equipment under the jurisdiction of the Department of Building and Safety, not permanently connected to fixed wiring systems and which is used for generating, transforming or distributing power to temporary lighting and power installations for carnivals, conventions, exhibitions, fairs and the like. 2. Portable sub-stations shall not be located inside of any permanent building or structure, nor shall portable sub-stations supply any wiring or equipment located inside of any permanent building or structure except by special permission. 3. Portable sub-stations shall be located within noncombustible housings, partitions, screens, fences or any other suitable enclosure as determined by the Department or its authorized representative. Transportable housings shall be provided with a lockable door or gate which shall be kept locked while the station is unattended. 4. Portable sub-stations, related wiring and control devices shall comply with the following applicable provisions: a. High and low voltage sections shall be separated by a noncombustible partition, screen or fence; and Page 2 of 11

3 b. Sufficient working space shall be provided about all equipment so that the operator may work in safety, and so that other persons in the vicinity cannot accidentally contact or bring conducting objects into contact with energized current-carrying parts; and c. Transformers of the oil filled type shall be provided with leakproof pans of sufficient capacity to contain all the oil in the unit. Seals or vents shall be provided to prevent the oil from siphoning through the conductor insulation; and d. Service conductors shall be installed in approved rigid metal wiring enclosures. (A short length of flexible conduit may be installed at the base of the service conduit where it is necessary to lower the supporting rack for transit purposes. The flexible conduit shall be effectively bonded to insure ground continuity.) and e. All wiring inside of transportable sub-station housings shall be in approved wiring enclosures except where short lengths of unenclosed conductors are necessary for making connections to transformers, generators, motors and cable supply boxes. Open high voltage wiring may be installed on insulators where separated from low voltage equipment by a noncombustible partition, screen or fence; and f. High voltage service conductors supplying sub-stations in transportable housings shall be provided with fused isolating switches located on the service rack, and a single load interrupter switch located inside the housing. The load interrupter switch shall disconnect the service conductors with one operation of a single suitable operating means; and g. Ungrounded low voltage service or supply conductors and feeders from the load side of every generator shall be controlled by a single readily accessible fused switch or nontamperable trip-free circuit breaker with a single operating handle. The control device shall be located in sight of, and within 10 feet of, the supply equipment; and h. Switches and circuit breakers shall be clearly marked to indicate the equipment they control. Switches shall be so installed that gravity or a downward motion of the operating handle will not tend to close them; and i. Generators, transformers and conductors shall be protected against overcurrent in accordance with the applicable provisions of the Code; and j. The voltage on the load or secondary side of generators and transformers shall not exceed 300 volts between ungrounded terminals. Where the equipment is used to supply lighting and receptacle branch circuits, the voltage between any ungrounded terminal and ground shall not exceed 150 volts; and Page 3 of 11

4 k. An identified conductor of the following distribution systems shall be grounded in the first switch on the load side of the supply equipment: (i) (ii) (iii) Two-wire systems operating at less than 150 volts between conductors. Three-wire single phase systems operating at less than 300 volts between conductors (normally volt systems). Three phase, four-wire systems operating at less than 300 volts between conductors (normally volt wye - connected four-wire systems). D. Grounding. l. Delta connected, three phase, four-wire distribution systems shall not be used; and m. Metallic frames of transportable housings and noncurrent-carrying metal parts of equipment and wiring enclosures shall be effectively bonded and connected to a common grounding bus. The grounding bus shall be connected to the grounding electrode; and n. Cable supply terminal boxes shall comply with the applicable provisions for splice boxes; and o. Suitable, permanent warning signs shall be posted at doors, gates, service heads and cable supply boxes. 1. Except where modified by the provisions for lighting fixtures, signs and outline lighting, all noncurrent-carrying metal parts of electrical equipment enclosures around electrical equipment metal supports for wiring or equipment, metal supports of electrically-operated equipment and similar enclosures, frames or supports, shall be effectively grounded in accordance with the applicable provisions of the code. 2. A continuous metallic underground cold water piping system containing water under pressure shall always be used as the service and equipment grounding electrode when available. "Available" shall be considered as being on the same premises and within 100 feet of the service switch or equipment. 3. Where a cold water piping system is not available, the grounding electrode shall consist of one or more 1/2-inch copper clad steel ground rods or 3/4-inch trade size galvanized conduits spaced approximately three feet apart and driven into the earth for a distance of not less than eight feet. 4. Whenever the Department or its authorized representative determines that the resistance of any neutral conductor or equipment grounding conductor at any point exceeds 25 ohms Page 4 of 11

5 to ground, additional grounding electrodes shall be provided at those points. 5. The equipment grounding conductor shall not be smaller than No. 1 AWG except where contained with branch circuit BY conductors in a single assembly approved for the purpose. 6. Equipment grounding conductors shall be used in continuous unbroken lengths except where suitably joined or tapped in splice boxes or similar cable terminating enclosures. E. Flexible Cords and Cables. Flexible cords and cables may be used as feeder and branch circuit conductors with the following provisions: 1. Cords and cables shall be approved for extra hard usage. 2. If smaller than No. 1 AWG, branch circuit conductors of any one circuit and any related grounding conductor shall be contained in a single assembly approved for the purpose. 3. Cords and cables shall be used only in continuous lengths. Splices and taps shall be made in splice boxes or similar cable terminating enclosures. (Approved cable connectors may be used only where determined to be satisfactory by the Department or its authorized representative.) 4. Cords and cables shall be suitably protected from physical damage and shall be installed to reasonably prevent accidental contact with persons or conducting materials. 5. Where subject to vehicular or foot traffic, cords and cables shall be buried in the earth or covered with suitable protective material. Reasonable precaution shall be taken to prevent persons from stumbling over cable trenches and cable protection. 6. Cords and cables shall be securely fastened to boxes or other terminating points by means of approved cord grips or other suitable methods of strain relief. 7. Branch circuit cords and cables smaller than No. 1 AWG shall not be used. 8. Cords and cables shall not be used in circuits operating at more than 300 volts between any two ungrounded conductors. 9. Cords and cables shall have an ampacity of not less than the full connected load. 10. Feeders shall be controlled by an externally operable fused switch or circuit breaker and shall be protected against overcurrent at a rate not to exceed their rated ampacity or more than 400 amperes. 11. Overcurrent protection need not be provided for a tap between a feeder and the branch circuit overcurrent device when: Page 5 of 11

6 a. The feeder is protected against overcurrent at a rate not to exceed 200 amperes; and b. The tap has a rated ampacity adequate for the load; and c. The tap is not smaller than No. 6 AWG; and d. The tap does not exceed 25 feet in length. 12. Conductors larger than No. 10 AWG shall terminate to solder lugs or approved pressure connectors. 13. Conductors of size No. 10 AWG or smaller may be connected directly to any stud, binding screw, clamp or other terminal, provided the strands are soldered together before attachment. 14. Not more than one attachment plug cap (male plug) or similar device shall be attached to any one length of flexible cord or cable. More than one connector body (female plug) may be attached to the opposite end of the cord only if the devices are of the molded type, are installed at the time and place of manufacture and the outer jacket of the cord at the splice is molded or vulcanized to provide a covering at least equivalent to the original cable. F. Splice Boxes. 1. Splice boxes shall be substantially constructed and may be comprised of suitable wood not less than one inch in thickness, or of noncombustible material of equivalent mechanical strength. Note: Splice boxes, spiders or similar equipment of the type normally used in motion picture studios will not be approved by the Department. 2. The interior dimensions shall not exceed 12 inches in depth nor 30 inches in width or length. 3. Box covers shall be provided with a padlocking means, or shall be suitably secured in place by means of a tool-operated latch. 4. Covers shall be kept locked or fastened in place at all times when busses are energized. 5. Boxes shall be provided with suitable warning signs and shall be located in areas which are not normally accessible Boxes shall not be located where subject to physical damage. 6. When used in grounded systems, boxes shall contain an identified neutral bus. Page 6 of 11

7 7. Boxes shall contain a grounding bus identified by green coloring adjacent thereto. 8. An insulating barrier shall be installed between bus bars of unlike polarities. 9. Bus bars shall have a current-carrying capacity of not less than the sum total of the loads supplied, and shall be of sufficient length, width and thickness to insure good electrical connections. Not more than one lug shall be attached to any terminal, stud, screw or bolt. 10. Splice boxes shall contain adequate space for all conductors and shall not be used to enclose panels, switches, fuses, receptacles or other similar devices, except by special permission. G. Panelboards. 1. Panelboards shall be of an approved dead front type. 2. Panelboards containing receptacles or similar devices, or having such devices permanently attached thereto, shall be specifically approved as a unit by a recognized testing laboratory. 3. Panelboards shall be securely fastened in place to rigid supporting members, or shall be securely fastened to suitable portable stands. Where installed outside of buildings or structures in areas which are not normally accessible to the public, panelboards may be installed in suitable protective enclosures by special permission. 4. Panelboards rated at 200 amperes or less shall be supplied by feeders which are protected against overcurrent at not to exceed 200 amperes. Panelboards rated at over 200 amperes may be supplied by feeders which are protected against overcurrent at not to exceed the panel board rating. 5. Noncurrent-carrying metal parts of panelboards shall be effectively grounded. H. Motors and Motor-Driven Equipment. 1. Trolleys, collector rings, slip rings and similar exposed current-carrying parts shall be effectively guarded and located where not normally accessible 2. Motors exceeding 2 hp in rating shall be provided with an individual controller of adequate capacity for interrupting stalled rotor current. 3. Motor circuits and motor overcurrent protection shall comply with all applicable provisions of the code, except that running protection need not be provided for motors of 1 hp or less rating. Page 7 of 11

8 Note: The majority of motors which operate carnival rides are classed as intermittent duty motors. Running protection is not required for motors of this type. 4. Motor controllers and motor disconnecting means shall be located or marked to clearly indicate the equipment they control. The disconnecting means shall be capable of being locked in the "off" position. 5. All noncurrent-carrying parts of motors, motor control equipment and motor-driven machinery shall be effectively grounded. I. Lighting Branch Circuits, Lighting Fixtures and Lampholders. 1. Lighting fixtures and lampholders shall be supplied from systems which have an identified grounded conductor. Voltage to ground shall not exceed 150 volts. Voltage between any two underground conductors shall not exceed 300 volts. 2. Branch circuit conductors shall have an ampacity of not less than their full connected load, and shall not be smaller than No. 12 AWG. 3. Branch circuits supplying electric discharge lighting fixtures or lampholders rated at not more than 300 watts shall be protected at not to exceed 20 amperes by nontamperable, trip-free circuit breakers. 4. Branch circuits supplying only mogul lampholders rated at more than 300 watts may be protected at more than 20 amperes, but not to exceed 50 amperes. The rating or setting of the branch circuit overcurrent device shall not exceed the rated capacity of the branch circuit conductors. 5. Exposed noncurrent-carrying metal parts of lighting fixtures shall be effectively grounded or shall be installed out of reach of the public and not less than eight feet vertically nor less than five feet horizontally from any grounded surface. 6. Lampholders, other than component parts of approved fixtures, shall be of molded composition or other approved material of the weatherproof type. Except where lampholders have terminals of a type which puncture the insulation to make contact with stranded conductors, lamphold terminal wires shall be soldered to the branch circuit conductors. Joints shall be staggered and insulated. 7. Brass lampholders, porcelain cleat receptacles, porcelain ring receptacles and lampholders with exposed terminals shall not be used. 8. Where run to a lampholder, the identified grounded conductor shall be connected to the screw shell terminal. Page 8 of 11

9 J. Receptacle Branch Circuit, Receptacles and Attachment to Plug Caps. 1. General use receptacles shall be supplied from systems which have an identified grounded conductor. Voltage to ground shall not exceed 150 volts. Voltage between ungrounded conductors shall not exceed 300 volts. 2. General use receptacle branch circuit conductors shall be minimum No. 14 AWG, when protected with 15 amperes circuit breakers or No. 12 AWG when protected with 20 ampere circuit breakers. 3. Receptacles and attachment plug caps shall have a rated capacity of not less than 15 amperes at 125 volts. 4. General use receptacles and attachment plug caps shall have two circuit contacts and an identified grounding contact. 5. Receptacle enclosures and outlet boxes shall be of an approved metal type. The enclosures and outlet boxes shall be provided with approved metal covers or face plates. 6. Receptacle enclosures containing switches, fuses, circuit breakers or similar devices shall be specifically approved for the purpose. 7. Not more than one flexible cord or cable entry shall be made into any receptacle enclosure or receptacle outlet box. Receptacle enclosures used for other than circuit termination shall be specifically approved for the purpose. Note: Where used inside of permanent buildings or structures, receptacle enclosures may have a maximum of two flexible cord or cable entries. The entries shall be made at opposite ends of the enclosure. 8. Receptacle enclosures and cord connector bodies shall have all exposed noncurrentcarrying metal parts effectively grounded. K. Signs and Outline Lighting (Gas Tube Systems). 1. Signs shall be approved by a recognized testing laboratory or shall be fabricated in accordance with those laboratory standards. 2. Gas tube transformers other than the approved portable type shall be installed in suitable enclosures as determined by the Department or its authorized representative. 3. Bushings or other suitable protection shall be provided at the points where wires enter or leave the transformer enclosures. Page 9 of 11

10 4. Electric discharge glass tubing shall be securely fastened to noncombustible nonabsorptive supports not less than 1/2-inch from any surface. 5. Where accessible to the public, connections to electrodes, high tension leads and jumpers shall be covered with suitable sleeving. 6. Signs, gas tube systems, transformers, glass tubing and high tension wiring shall be installed out of reach of the public where practical as determined by the Department or its authorized representative. Where installed less than eight feet vertically or five feet horizontally from any grounded surface normally accessible to the public all noncurrent-carrying metal parts of the equipment shall be effectively grounded. 7. Signs and outline lighting shall be supplied from systems which have an identified grounded conductor. Voltage to ground shall not exceed 150 volts. Voltage between any two ungrounded conductors shall not exceed 300 volts. 8. Sign circuit conductors shall not be smaller than No. 12 AWG and shall be protected with 20 ampere circuit breakers. Page 10 of 11

SINGLE PHASE WIRING SPECIFICATIONS

SINGLE PHASE WIRING SPECIFICATIONS SINGLE PHASE WIRING SPECIFICATIONS 1-866-MEC-ELEC (1-866-632-3532) Office Locations: Hondo Office 237 Hwy 173 N Hondo, TX 78661-0370 Fax 830.426.3335 Dilley Office 1718 W. FM 117 Dilley, TX 78017 Fax 830.965.1425

More information

SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS - ELECTRICAL

SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS - ELECTRICAL SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS - ELECTRICAL This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly.

More information

CHAPTER 10 ELECTRICAL. Notes:

CHAPTER 10 ELECTRICAL. Notes: CHAPTER 10 ELECTRICAL 1001.0 General Requirements. Electrical wiring and equipment shall comply with the requirements of NFPA 70, National Electrical Code (NEC), or local ordinances. 1002.0 Solar Photovoltaic

More information

THREE PHASE WIRING SPECIFICATIONS

THREE PHASE WIRING SPECIFICATIONS THREE PHASE WIRING SPECIFICATIONS 1-866-MEC-ELEC (1-866-632-3532) Office Locations: Hondo Office 237 Hwy 173 N Hondo, TX 78661-0370 Fax 830.426.3335 Dilley Office 1718 W. FM 117 Dilley, TX 78017 Fax 830.965.1425

More information

WIRING DESIGN & PROTECTION REQUIREMENTS CHECKLIST

WIRING DESIGN & PROTECTION REQUIREMENTS CHECKLIST WIRING DESIGN & PROTECTION REQUIREMENTS CHECKLIST Use & Identification of Grounded and Grounding Conductors YES NO N/A Grounded conductors are identifiable and distinguishable from all other conductors.

More information

SERVICE ATTACHMENT ON A BUILDING WITH BUS DUCT SERVICE ENTRANCE AND INDOOR METERING

SERVICE ATTACHMENT ON A BUILDING WITH BUS DUCT SERVICE ENTRANCE AND INDOOR METERING SERVICE ATTACHMENT ON A BUILDING WITH BUS DUCT SERVICE ENTRANCE AND INDOOR METERING Obtain acceptance and specific details from the local Company office. 1. Service entrance duct (see Note 1). Company

More information

2016 Photovoltaic Solar System Plan Review List

2016 Photovoltaic Solar System Plan Review List Building Division 555 Santa Clara Street Vallejo CA 94590 707.648.4374 2016 Photovoltaic Solar System Plan Review List GENERAL PROJECT INFORMATION PLAN CHECK NO DATE JOB ADDRESS CITY ZIP REVIEWED BY PHONE

More information

INDUSTRY WIDE LABOR-MANAGEMENT SAFETY COMMITTEE

INDUSTRY WIDE LABOR-MANAGEMENT SAFETY COMMITTEE INDUSTRY WIDE LABOR-MANAGEMENT SAFETY COMMITTEE SAFETY BULLETIN #23 GUIDELINES FOR WORKING WITH LIGHTING SYSTEMS AND OTHER ELECTRICAL EQUIPMENT All electrical systems and electrically energized equipment

More information

The following are specific provisions of 1910(a)(2) that could be seen in the LBM sector

The following are specific provisions of 1910(a)(2) that could be seen in the LBM sector Know the Rules on Temporary Wiring OSHA Standard 1910.305, Wiring methods, components, and equipment for general use, addresses wiring methods, components, and equipment for general use as one of several

More information

Spring Test 7 due 05/03/2013

Spring Test 7 due 05/03/2013 Spring Test 7 due 05/03/2013 Multiple Choice Identify the choice that best completes the statement or answers the question. 1. A raceway contains two 3-phase, 3-wire circuits that supply 38 ampere continuous

More information

AGRICULTURAL UNDERGROUND SERVICE 500 HP OR LESS

AGRICULTURAL UNDERGROUND SERVICE 500 HP OR LESS Prepared by: ABB1 AGRICULTURAL UNDERGROUND SERVICE 500 HP OR LESS 05619 Asset Type: Electric Metering Function: Design and Construction Issued by: Lisseth Villareal (LDV2) Date: 07-31-15 Rev. #10: This

More information

ICOMIA Global Conformity Guideline for ISO/ABYC Standards and Canadian TP 1332 requirements. Guideline Number 3 Electrical

ICOMIA Global Conformity Guideline for ISO/ABYC Standards and Canadian TP 1332 requirements. Guideline Number 3 Electrical ICOMIA Global Conformity Guideline for ISO/ABYC Standards and Canadian TP 1332 requirements 1. PURPOSE sponsored by ABYC, BMF, ICOMIA, IMCI, and NMMA Author: Wieger de Wit Guideline Number 3 Electrical

More information

Generator Fire Safety: Generator assemblies should be located outside the building.

Generator Fire Safety: Generator assemblies should be located outside the building. SECTION 33 70 00 - ELECTRICAL DISTRIBUTION PACKAGED GENERATOR ASSEMBLIES Generator Fire Safety: Generator assemblies should be located outside the building. All fuel piping from the outside of the building

More information

Pretest Module 24 Three-phase Service Entrance

Pretest Module 24 Three-phase Service Entrance Pretest Module 24 Three-phase Service Entrance 1. What is the most widely used three-phase service entrance system? 2. What are the three most common voltage combinations for three-phase, four-wire systems?

More information

ENTRANCE EQUIPMENT ER D PAGE 1 OF 5

ENTRANCE EQUIPMENT ER D PAGE 1 OF 5 PAGE 1 OF 5 USE: Requirements for entrance equipment. PREVIOUS REVISION 07-01-98 ORIGINATED 03-94 PREVIOUS NUMBER ER 100 (12-01-81) LATEST REVISION: Updated meter socket labeling specification and instrument

More information

Spring Test 10 due 05/11/2013

Spring Test 10 due 05/11/2013 Spring Test 10 due 05/11/2013 Multiple Choice Identify the letter of the choice that best completes the statement or answers the question. 1. When installed in an agricultural building that houses livestock

More information

This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly.

This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly. SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS (ELEC) This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly.

More information

Installing a Downstream Distribution Panelboard

Installing a Downstream Distribution Panelboard Job Sheet 5 Installing a Downstream Distribution Panelboard OBJECTIVE To install a downstream distribution panelboard (DDP) on the Mobile Workstation. To mechanically and electrically connect the DDP to

More information

AMENDMENT ELECTRIC SERVICE MANUAL 2014

AMENDMENT ELECTRIC SERVICE MANUAL 2014 AMENDMENT (Pages 20,43,50,72,74,,76,78,83,86,99) ELECTRIC SERVICE MANUAL 2014 Effective April 1, 2015 18-7 6.0 SERVICE AND SERVICE ENTRANCES (General), Continued Conductor Sizing It is recommended that

More information

Chapter 5. Imagine That Engineering Inc. Assured Equipment Grounding Conductor Program (AEGCP) Ground Fault Circuit Interrupter (GFCI)

Chapter 5. Imagine That Engineering Inc. Assured Equipment Grounding Conductor Program (AEGCP) Ground Fault Circuit Interrupter (GFCI) Chapter 5 Imagine That Engineering Inc. Assured Equipment Grounding Conductor Program (AEGCP) Ground Fault Circuit Interrupter (GFCI) Imagine That Engineering Inc. has adopted this program for equipment

More information

CHAPTER V RESIDENTIAL WIRING

CHAPTER V RESIDENTIAL WIRING CHAPTER V RESIDENTIAL WIRING 5.1. THE SERVICE ENTRANCE Buildings and other structures receive the electrical energy through the service entrance. In residential wiring, the electric company supply this

More information

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 2/8/12 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 2/8/12 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions MECKLENBURG COUNTY Land Use and Environmental Service Agency Code Enforcement 2/8/12 ELECTRICAL CONSISTENCY MEETING Code Consistency Questions 1. I am inspecting a building addition. They have a 480V to

More information

10 Commercial, Industrial, Agricultural Services

10 Commercial, Industrial, Agricultural Services 10 Commercial, Industrial, Agricultural Services This section describes the Power Company requirements for commercial, industrial, and agricultural services. This section covers single phase and three

More information

90.2 Scope. The installation of electrical conductors, equipment and raceways for:

90.2 Scope. The installation of electrical conductors, equipment and raceways for: NEC Generator Primer Rules on the installation of generators and transfer switches 1 90.2 Scope The installation of electrical conductors, equipment and raceways for: public and private premises Conductors

More information

9. Non-Residential Services (Commercial, Industrial, and Agricultural)

9. Non-Residential Services (Commercial, Industrial, and Agricultural) Section 9 2016 Electric Service Requirements, 3rd Edition Section 9 Non-Residential Services Directory Page 9.1 General Requirements 68 9.2 Direct-Connect Metering, Single Installations 69 9.3 Direct-Connect

More information

CHAPTER 10 ELECTRICAL

CHAPTER 10 ELECTRICAL 1001.0 General Requirements. 1001.1 Electrical Wiring and Equipment. Electrical wiring and equipment shall comply with the requirements of NFPA 70, National Electrical Code (NEC), or local ordinances.

More information

An average of one worker is electrocuted on the job every day There are four main types of electrical injuries:

An average of one worker is electrocuted on the job every day There are four main types of electrical injuries: Electrical Safety Introduction An average of one worker is electrocuted on the job every day There are four main types of electrical injuries: Electrocution (death due to electrical shock) Electrical shock

More information

9/16/2010. Chapter , The McGraw-Hill Companies, Inc. TRANSMISSION SYSTEMS. 2010, The McGraw-Hill Companies, Inc.

9/16/2010. Chapter , The McGraw-Hill Companies, Inc. TRANSMISSION SYSTEMS. 2010, The McGraw-Hill Companies, Inc. Chapter 3 TRANSMISSION SYSTEMS 1 Transmitting large amounts of electric energy over long distances is accomplished most efficiently by using high-voltages. Without transformers the widespread distribution

More information

3.8 KVA IsoG2. INSTALLATION INSTRUCTIONS & OWNER S MANUAL Model 93-ISOG2/8-A LT-ISOG28-1. Issue 1 Print 3 SHORELINE ISOLATION TRANSFORMER

3.8 KVA IsoG2. INSTALLATION INSTRUCTIONS & OWNER S MANUAL Model 93-ISOG2/8-A LT-ISOG28-1. Issue 1 Print 3 SHORELINE ISOLATION TRANSFORMER Issue 1 Print 3 3.8 KVA IsoG2 SHORELINE ISOLATION TRANSFORMER LT-ISOG28-1 INSTALLATION INSTRUCTIONS & OWNER S MANUAL Model 93-ISOG2/8-A Charles Industries, Ltd. All rights reserved. Printed in the United

More information

D9-3. No. WIRING DIAGRAM CONNECTIONS FOR UNDERGROUND SELF CONTAINED METERS JRH JED krich95 LINE LINE ABCN SOURCE SOURCE GROUND GROUND STUD STUD SOURCE

D9-3. No. WIRING DIAGRAM CONNECTIONS FOR UNDERGROUND SELF CONTAINED METERS JRH JED krich95 LINE LINE ABCN SOURCE SOURCE GROUND GROUND STUD STUD SOURCE SOURCE 20V 240V STUD (PER NEC) A customer supplied and installed teaser wire is required from the neutral lug to a 5th terminal mounted on the left side of the meter block between the line and load terminals.

More information

GUIDELINES ON ELECTRICAL SAFETY AT WORKPLACES

GUIDELINES ON ELECTRICAL SAFETY AT WORKPLACES MINISTRY OF LABOUR, INDUSTRIAL RELATIONS AND EMPLOYMENT GUIDELINES ON ELECTRICAL SAFETY AT WORKPLACES Occupational Safety & Health Inspectorate These guidelines should be used with approved standards:

More information

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 9/14/11 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 9/14/11 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions MECKLENBURG COUNTY Land Use and Environmental Service Agency Code Enforcement 9/14/11 ELECTRICAL CONSISTENCY MEETING Code Consistency Questions 1. I recently installed a 45-KVA transformer, 480-volt primary

More information

3.6 KVA IsoGuard. INSTALLATION INSTRUCTIONS & OWNER S MANUAL Model 93 IXFMR3/6N A LT IXFMR36N 1. Issue 1 Print 1 SHORELINE ISOLATION TRANSFORMER

3.6 KVA IsoGuard. INSTALLATION INSTRUCTIONS & OWNER S MANUAL Model 93 IXFMR3/6N A LT IXFMR36N 1. Issue 1 Print 1 SHORELINE ISOLATION TRANSFORMER Issue 1 Print 1 3.6 KVA IsoGuard SHORELINE ISOLATION TRANSFORMER LT IXFMR36N 1 INSTALLATION INSTRUCTIONS & OWNER S MANUAL Model 93 IXFMR3/6N A Charles Industries, Ltd. All rights reserved. Printed in the

More information

Chapter 8 Interior Wiring and Lighting

Chapter 8 Interior Wiring and Lighting Chapter 8 Interior Wiring and Lighting Review Questions 1. What tool if any, is used to remove a fuse that is to be replaced? 1. Pliers 2. Screwdriver 3. Fuse puller 4. None 2. OSHA has established specific

More information

24 KVA International Universal IsoTransformer

24 KVA International Universal IsoTransformer 24 KVA International Universal IsoTransformer SHORELINE ISOLATION TRANSFORMER INSTALLATION INSTRUCTIONS & OWNER S MANUAL Model 93 IXFMR24I A Marine Group 1 Issue 1 Print 4 Contents INTRODUCING...THE 24

More information

2. DEFINITIONS. 2.3 APPROVED Acceptable to the authority enforcing the National Electric Code

2. DEFINITIONS. 2.3 APPROVED Acceptable to the authority enforcing the National Electric Code 2. DEFINITIONS 2.1 ACCEPTABLE Acceptable to the Company. 2.2 ADVANCED METER A meter that is capable of remote reading, and is capable of storing electric consumption data at specified time intervals of

More information

Permit for Charging Equipment Installation Electric Vehicle Supply Equipment (EVSE)

Permit for Charging Equipment Installation Electric Vehicle Supply Equipment (EVSE) Permit for Charging Equipment Installation Electric Vehicle Supply Equipment (EVSE) Town of Lake George, New York Compliance with the following permit will allow the installation and operation of electric

More information

INSPECTION REQUIREMENTS: PHOTOVOLTAIC (PV) RESIDENTIAL

INSPECTION REQUIREMENTS: PHOTOVOLTAIC (PV) RESIDENTIAL Photovoltaic (PV) Residential Page 1 of 10 Revision Date: 07/18/2018 INSPECTION REQUIREMENTS: PHOTOVOLTAIC (PV) RESIDENTIAL INSPECTION CODE: 703 SCOPE: RESIDENTIAL APPLICABLE CODES: 2016 CBC, CRC, CPC,

More information

3.6 KVA IsoG2. INSTALLATION INSTRUCTIONS & OWNER S MANUAL Model 93-ISOG26-A LT ISOG26 1. Issue 1 Print 3 SHORELINE ISOLATION TRANSFORMER

3.6 KVA IsoG2. INSTALLATION INSTRUCTIONS & OWNER S MANUAL Model 93-ISOG26-A LT ISOG26 1. Issue 1 Print 3 SHORELINE ISOLATION TRANSFORMER 3.6 KVA IsoG2 SHORELINE ISOLATION TRANSFORMER INSTALLATION INSTRUCTIONS & OWNER S MANUAL Model 93-ISOG26-A 1 Issue 1 Print 3 Contents INTRODUCING... THE 3.6 KVA IsoG2............................................................

More information

Temporarily Approved Solar Photovoltaic System Electrical Schematics

Temporarily Approved Solar Photovoltaic System Electrical Schematics March 20, 2019 Page 1 of 10 Temporarily Approved Solar Photovoltaic System Electrical Schematics This document is intended as a temporary interpretation of approved solar photovoltaic electrical schematics

More information

ELECTRIC SERVICE RULES DISTRIBUTED GENERATION Issued Jan 2016

ELECTRIC SERVICE RULES DISTRIBUTED GENERATION Issued Jan 2016 DISTRIBUTED GENERATION CHAPTER 5 500. SCOPE This chapter includes distributed or customer-owned generation connected in parallel and operating with Alliant Energy s electric distribution system. For all

More information

Service Entrance Methods

Service Entrance Methods Service Section Typical switchboards consist of a service section, also referred to as the main section, and one or more distribution sections. The service section can be fed directly from the utility

More information

FACT SHEET Standard: Electrical Safety

FACT SHEET Standard: Electrical Safety What is a Ground Fault Circuit Interrupter? FACT SHEET The ground-fault circuit interrupter, or GFCI, is a fast-acting circuit breaker designed to shut off electric power in the event of a ground-fault

More information

7. SERVICES OVER 600 VOLTS

7. SERVICES OVER 600 VOLTS 7. SERVICES OVER 600 VOLTS 7.1 GENERAL The Company shall always be consulted to obtain required design criteria where service is contemplated.preliminary plans of the Customer shall be submitted for review

More information

SECTION 1: Field Inspection Guide for Rooftop Photovoltaic (PV) Systems

SECTION 1: Field Inspection Guide for Rooftop Photovoltaic (PV) Systems COUNTY OF SANTA CRUZ PLANNING DEPARTMENT 701 OCEAN STREET, 4 th FLOOR, SANTA CRUZ, CA 95060 (831) 454-2580 FAX: (831) 454-2131 TDD: (831) 454-2123 KATHLEEN MOLLOY PREVISICH, PLANNING DIRECTOR Photovoltaic

More information

Transmission & Distribution Glossary of Electrical Terms

Transmission & Distribution Glossary of Electrical Terms Transmission & Distribution Glossary of Electrical s Breaker Panel Bushing Circuit Circuit Breaker Conductor Conduit Consumption Current Distribution Electricity (Static vs. Current) Electron Feeder The

More information

A. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein.

A. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein. 16425 SWITCHBOARD ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 26 24 13 An optional keynote to

More information

12T KVA IsoTransformer SHORELINE ISOLATION TRANSFORMER

12T KVA IsoTransformer SHORELINE ISOLATION TRANSFORMER Issue 1 Print 3 LT IXFMR12T 1 12T KVA IsoTransformer SHORELINE ISOLATION TRANSFORMER INSTALLATION INSTRUCTIONS & OWNER S MANUAL Model 93 IXFMR12T A Charles Industries, Ltd. All rights reserved. Printed

More information

Grounding Systems. Equipment Grounding & Grounded Conductors

Grounding Systems. Equipment Grounding & Grounded Conductors Grounding Systems Equipment Grounding & Grounded Conductors Definitions A Grounded or Earthed system is one that is connected to the earth Grounded Conductor is a conductor that normally carries current

More information

Photovoltaic Solar Plan Review

Photovoltaic Solar Plan Review PAIGE B. VAUGHAN, CBO Director of Building and Safety Phone (310) 605-5509 Fax Line (310) 605-5598 E-mail:lbutler@comptoncity.org Building & Safety Department Photovoltaic Solar Plan Review Plan Check

More information

Electrical Safety. Electrical Safety Webinar. Electrical. Printing Industries Alliance Printing Industries Alliance 1

Electrical Safety. Electrical Safety Webinar. Electrical. Printing Industries Alliance Printing Industries Alliance 1 Webinar 1 Electrical 2 1 Webinar Introduction An average of one worker is electrocuted on the job every day There are four main types of electrical injuries: Electrocution (death due to electrical shock)

More information

UNDERGROUND SERVICES - SECONDARY

UNDERGROUND SERVICES - SECONDARY UNDERGROUND SERVICES - SECONDARY Contents - Underground Services... U-1 General Requirements for Underground Service...U-2 Names of Parts for Underground Service... U-3 Service Termination in a Service

More information

Solar PV Standard Electric Plan

Solar PV Standard Electric Plan *** Provide this document to the inspector along with ALL system installation instructions *** SCOPE: Standard plan for the installation of microinverter solar PV systems, not exceeding a total AC output

More information

ELECTRICAL. 60 Minutes

ELECTRICAL. 60 Minutes ELECTRICAL 60 Minutes AGENDA Electrical definitions Electrical shocks, burns and secondary injuries Electrical hazards in the workplace Safety devices and prevention steps Do s and Don ts INTRODUCTORY

More information

Bulletin Wiring methods for Solar Photovoltaic Systems Rules and , Tables 11 and 19

Bulletin Wiring methods for Solar Photovoltaic Systems Rules and , Tables 11 and 19 Bulletin 50-4-1 Wiring methods for Solar Photovoltaic Systems Rules 50-018 and 50-020, Tables 11 and 19 Issued December 2012 Supersedes Bulletin 50-4-0 (1) (2) (3) (4) (5) Scope Introduction New cable

More information

Chapter 2 Wiring and Protection Article 200 Use and Identification of Grounded Neutral Conductor Chapter 1 General...9

Chapter 2 Wiring and Protection Article 200 Use and Identification of Grounded Neutral Conductor Chapter 1 General...9 Article 90 Introduction...1 90.1 Purpose of the NEC...1 90.2 Scope of the NEC...2 90.3 Code Arrangement...4 90.4 Enforcement...5 90.5 Mandatory Requirements and Explanatory Material...6 90.6 Formal Interpretations...6

More information

COMMERCIAL QUICK REFERENCE

COMMERCIAL QUICK REFERENCE COMMERCIAL QUICK REFERENCE PROVO CITY POWER STANDARDS ELECTRICAL ENGINEERING UPDATED: 2016 SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTIFICATION. 18" MIN. OF TAIL. (NEUTRAL CONDUCTOR MUST BE WHITE OR

More information

Electrical Hazards in Construction

Electrical Hazards in Construction Electrical Hazards in Construction WELCOME Tim Dawson Presentation developed by Dawson Safety Services - 2013 Dangers of Electrical Shock Currents above 10 ma* can paralyze or freeze muscles. Currents

More information

Section 6 Electric Metering: Residential

Section 6 Electric Metering: Residential Section 6 Electric Metering: Residential 6.1. Scope This section provides specific information for residential metering that is not covered by the basic requirements in Section 5, Electric Metering: General.

More information

STOUGHTON UTILITIES ELECTRIC SERVICE RULES AND INFORMATION

STOUGHTON UTILITIES ELECTRIC SERVICE RULES AND INFORMATION CHAPTER 1 - GENERAL INFORMATION 100. Purpose 101. Codes and rules 102. Continuity of service 103. Frequency, Voltage, and Amperage Limitations 104. High voltages 105. Unusual capacity requirements 106.

More information

SECTION PANELBOARDS

SECTION PANELBOARDS SECTION 16470 PANELBOARDS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. The general provisions of the contract including General and Special Conditions and General Requirements shall apply to all work under

More information

TRANSMISSION SYSTEMS

TRANSMISSION SYSTEMS TRANSMISSION SYSTEMS Transmitting large amounts of electric energy over long distances is accomplished most efficiently by using high-voltages. Without transformers the widespread distribution of electric

More information

Approved Meter Sockets and Cabinets

Approved Meter Sockets and Cabinets Single Unit Residential Guide 1 PHASE, 120/240 VOLT SERVICES SERVICE CAPACITY OWNED METERING (Metering sockets and cabinets are supplied by Customer). Outdoor meter mounting height is 1730 mm ( 5 8 ) to

More information

Mecklenburg County Common Code Defects

Mecklenburg County Common Code Defects Electrical Code Defects Improper Over Current Protection Code Description 310.15 Ampacities for s Rated 0 2000 Volts. (A) General. (1) Tables or Engineering Supervision. Ampacities for conductors shall

More information

Design Standard. Purpose: Design Standard:

Design Standard. Purpose: Design Standard: Design Standard Purpose: This design standard has the purpose of creating a consistent application of motor-control centers throughout the East Side Union High School District, therefore achieving a standard

More information

PHOTOVOLTAIC ELECTRICAL POWER SYSTEMS INSPECTOR/INSTALLER CHECKLIST

PHOTOVOLTAIC ELECTRICAL POWER SYSTEMS INSPECTOR/INSTALLER CHECKLIST PHOTOVOLTAIC ELECTRICAL POWER SYSTEMS INSPECTOR/INSTALLER CHECKLIST The following checklist is an outline of the general requirements found in the 2005 National Electrical Code (NEC) Article 690 for Photovoltaic

More information

12 KVA International Universal IsoTransformer SHORELINE ISOLATION TRANSFORMER

12 KVA International Universal IsoTransformer SHORELINE ISOLATION TRANSFORMER Issue 1 Print 3 LT IXFMR12I 1 12 KVA International Universal IsoTransformer SHORELINE ISOLATION TRANSFORMER INSTALLATION INSTRUCTIONS & OWNER S MANUAL Model 93 IXFMR12I A Charles Industries, Ltd. All rights

More information

A. Submit manufacturer's literature and technical data before starting work.

A. Submit manufacturer's literature and technical data before starting work. SECTION 16425 SWITCHBOARD PART 1 GENERAL 1.01 SUMMARY A. Related Section: 1. 16450 - Grounding. 1.02 SUBMITTALS A. Submit manufacturer's literature and technical data before starting work. B. Submit Shop

More information

Electrical Wiring Practices

Electrical Wiring Practices Chapter 2 Electrical Wiring Practices and Diagrams MElec-Ch2-1 Overview Safety Standards Wiring Considerations Wire Terminations Coaxial Cable Wiring Installations Wiring Diagrams MElec-Ch2-2 Safety Lethal

More information

CAL/OSHA ELECTRICAL LOW VOLTAGE

CAL/OSHA ELECTRICAL LOW VOLTAGE Preparation: Safety Mgr Authority: CEO Issuing Dept: Safety Page: Page 1 of 7 Purpose The purpose of this program is to prevent injuries due to electrical exposure to low voltage (less than or equal to

More information

NEC 2011 Code Changes

NEC 2011 Code Changes NEC 2011 Code Changes Articles 280.21-300.50 CHANGES FROM 2008 TO 2011 CODE ARE IN RED Chapter 2 - Wiring and Protection ARTICLE 280 Surge Arresters, Over 1kV III. Connecting Surge Arresters 280.21 Connection

More information

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE PAGE 261116-1 SECTION 261116 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

PEU reserves the right to determine all meter locations. Only authorized PEU personnel will determine this location.

PEU reserves the right to determine all meter locations. Only authorized PEU personnel will determine this location. I N T R O D U C T I O N - M-1 RIGHTS: PEU reserves the right to determine all meter locations. Only authorized PEU personnel will determine this location. NOTIFICATION: Customers planning to install or

More information

OVERHEAD SERVICE. Items to consider

OVERHEAD SERVICE. Items to consider OVERHEAD SERVICE Items to consider The maximum length of the service wire from the ComEd pole to the point of attachment on your residence is 150 feet, if practical. Your service wire installation must

More information

Solar PV Standard Electrical Plan

Solar PV Standard Electrical Plan *** Provide this document to the inspector along with ALL system installation instructions *** Project Address: Permit Number: SCOPE: Standard plan for installation of solar PV systems utilizing 2 wire

More information

Arc Fault Circuit Interrupter (AFCI) FACT SHEET

Arc Fault Circuit Interrupter (AFCI) FACT SHEET Arc Fault Circuit Interrupter (AFCI) FACT SHEET THE AFCI The AFCI is an arc fault circuit interrupter. AFCIs are newly-developed electrical devices designed to protect against fires caused by arcing faults

More information

9/7/2010. Objectives. Article 90. Introduction NEC Significant Changes. Review significant revisions in the 2011 NEC

9/7/2010. Objectives. Article 90. Introduction NEC Significant Changes. Review significant revisions in the 2011 NEC 2011 NEC Significant Changes Courtesy of NJATC Courtesy of NFPA Presented By: Michael J. Johnston Executive Director of Standards and Safety, NECA Objectives Review significant revisions in the 2011 NEC

More information

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS SECTION 26 28 16 ENCLOSED SWITCHES AND PART 1 - GENERAL 1.1 SUMMARY A. Section includes the following individually mounted, enclosed switches and circuit breakers rated 600V AC and less: 1. Fusible switches.

More information

6T KVA IsoTransformer

6T KVA IsoTransformer Issue 1 Print 2 LT IXFMR6T 1 6T KVA IsoTransformer SHORELINE ISOLATION TRANSFORMER INSTALLATION INSTRUCTIONS & OWNER S MANUAL Model 93 IXFMR6T A Charles Industries, Ltd. Charles Industries, Ltd. All rights

More information

Surface Regulations and Policies

Surface Regulations and Policies Surface Regulations and Policies COAL FATALITIES 1970-2002 350 300 250 200 150 100 50 0 1970 1973 1976 1979 1982 1985 1988 1991 1994 1997 2000 From January 1, 1970 through today, a total of 240 coal miners

More information

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5 DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5 1.1. APPLICABLE PUBLICATIONS 1.1.1. Publications listed below (including amendments, addenda, revisions, supplements, and errata), form a part of this

More information

12 KVA International Universal Isotransformer

12 KVA International Universal Isotransformer Issue 1 Print 4 LT IXFMR12I 1 12 KVA International Universal Isotransformer SHORELINE ISOLATION TRANSFORMER INSTALLATION INSTRUCTIONS & OWNER S MANUAL Model 93 IXFMR12I A Charles Industries, Ltd. Charles

More information

Indianapolis Power & Light Company

Indianapolis Power & Light Company Indianapolis Power & Light Company Electric Service and Meter Manual The Electric Service & Meter Manual is not copyrighted and permission is hereby given to reproduce this document. However, the Indianapolis

More information

2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE

2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE 2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE PAGE 1 OF 5 This Reference provides a very comprehensive list of aspects of a solar PV installation that could be reviewed, clarifying

More information

PowerLogic High Density Metering System 4-Meter Enclosure Installation Guide

PowerLogic High Density Metering System 4-Meter Enclosure Installation Guide PowerLogic High Density Metering System 4-Meter Enclosure Installation Guide 7002-0289-00 Instruction Bulletin HAZARD CATEGORIES AND SPECIAL SYMBOLS Read these instructions carefully and look at the equipment

More information

SOLAR PHOTOVOLTAIC SYSTEMS INSPECTOR CHECKLIST

SOLAR PHOTOVOLTAIC SYSTEMS INSPECTOR CHECKLIST SOLAR PHOTOVOLTAIC SYSTEMS INSPECTOR CHECKLIST The following checklist is an outline of the general requirements found in the 1999 National Electrical Code (NEC) Article 690 for Photovoltaic (PV) Power

More information

Requirements for Secondary Voltage Revenue Metering (750 V and less)

Requirements for Secondary Voltage Revenue Metering (750 V and less) Requirements for Secondary Voltage Revenue Metering (750 V and less) To view the latest revision of this document go to: http://www.bchydro.com/ext/metering/ January 28, 2010 Copyright 2008 by BC Hydro.

More information

Customer Substation Manual

Customer Substation Manual Customer Substation Manual Table of Contents Section Page 2 of 81 Description 0 Preface 010.00 General 010.10 Information Required for the Review of New Customer Substations 010.20 New Customer Substation

More information

7.5T KVA Isotransformer INSTALLATION INSTRUCTIONS

7.5T KVA Isotransformer INSTALLATION INSTRUCTIONS Issue 1 Print 2 LT93-IXFMR75I-1 7.5T KVA Isotransformer INSTALLATION INSTRUCTIONS MARINE ISOLATION TRANSFORMER & OWNER S MANUAL Model 93-IXFMR7/5T-A Marine Group Charles Industries, Ltd. All rights reserved.

More information

2000 Cooper Bussmann, Inc. Page 1 of 9 10/04/00

2000 Cooper Bussmann, Inc. Page 1 of 9 10/04/00 DO YOU KNOW THE FACTS ABOUT SINGLE-POLE INTERRUPTING RATINGS? YOU MAY BE IN TROUBLE! Typical plant electrical systems use three-phase distribution schemes. As an industry practice, short-circuit calculations

More information

ELECTRICAL - GENERAL REQUIREMENTS SELF INSPECTION CHECKLIST

ELECTRICAL - GENERAL REQUIREMENTS SELF INSPECTION CHECKLIST Name of School: OPTIONAL INFORMATION Date of Inspection: Vocational Program/Course/Room: Signature of Inspector: ELECTRICAL - GENERAL REQUIREMENTS SELF INSPECTION CHECKLIST Guidelines: This checklist covers

More information

SOLAR PV STANDARD PLAN - COMPREHENSIVE Central/String Inverter Systems for One and Two Family Dwellings

SOLAR PV STANDARD PLAN - COMPREHENSIVE Central/String Inverter Systems for One and Two Family Dwellings SCOPE: Use this plan ONLY for utility-interactive central/string inverter systems not exceeding a total combined system ac inverter output rating of 10kW on the roof of a one- or two-family dwelling or

More information

Metering and Service Installation:

Metering and Service Installation: Table of Contents 1. Metering Installation Requirements, General... 1 2. Type of Service... 2 3. Definitions... 2 4. Who Provides Metering Equipment?... 2 5. Establishment of Service... 2 6. Meter Access...

More information

SECTION VII METERING INSTALLATIONS

SECTION VII METERING INSTALLATIONS SECTION VII METERING INSTALLATIONS 1. GENERAL Outdoor metering is required for all new service installations to one, two, and three family detached, semi-detached and row houses. 2. COMPANY FURNISHES AND

More information

SAFETY SOCKET BOX. Note 8 3" MIN. 3" Max. (200 A)

SAFETY SOCKET BOX. Note 8 3 MIN. 3 Max. (200 A) .&. SAFETY SOCKET BOX USE: 1 12/24V 1A & 2A 4 Terminal EUSERC Dwg. No's 34 & 35 (With Factory Installed Test-Bypass Facilities) Refer to SR-452 for the complete Front View Lower-Panel Removed Note 3 3"

More information

Definitions of and have been revised. a. automatic b. nonautomatic c. none of the above d. both a and b

Definitions of and have been revised. a. automatic b. nonautomatic c. none of the above d. both a and b www.garyklinka.com Page 1 of 12 Instructions: Fee $25 1. Print these pages. 2. Circle the correct answers and transfer them to the answer sheet. 3. Page down to the last page for the verification forms

More information

Bulletin Wiring methods for Solar Photovoltaic Systems Rules, 2-034, , and , Tables 11 and 19

Bulletin Wiring methods for Solar Photovoltaic Systems Rules, 2-034, , and , Tables 11 and 19 Bulletin 50-4-4 Wiring methods for Solar Photovoltaic Systems Rules, 2-034, 50-014, 50-018 and 50-020, Tables 11 and 19 Scope (1) Introduction (2) New cable types RPV & RPVU (3) Wiring methods within photovoltaic

More information

Bulletin Wiring methods for Solar Photovoltaic Systems Rule and , Tables 11 and 19

Bulletin Wiring methods for Solar Photovoltaic Systems Rule and , Tables 11 and 19 -4-0 Bulletin -4-0 Wiring methods for Solar Photovoltaic Systems Rule -018 and -020, Tables 11 and 19 Scope Issued May 2012 (1) Introduction (2) New cable types RPV & RPVU (3) Wiring methods within photovoltaic

More information

Chapter 14:08 Factories and Works (Electrical) Regulations, Chapter 14:08 Factories and Works (Electrical) Regulations, 1976

Chapter 14:08 Factories and Works (Electrical) Regulations, Chapter 14:08 Factories and Works (Electrical) Regulations, 1976 1 Title Chapter 14:08 Factories and Works (Electrical) Regulations, 1976 2 Interpretation of terms 3 Fencing and enclosure 4 Notices 5 Safety precautions 6 Switch-boards 7 Portable electric tools and lights

More information

Section 02: Pre-Installation Procedures

Section 02: Pre-Installation Procedures Section 02: Pre-Installation Procedures Foundation! WARNING The MUST be placed on a surface that will support the combined weight of the, options, fixtures, and tooling, etc. (refer to the Specifications

More information