320A Single Phase URD Meter Loop Installations

Size: px
Start display at page:

Download "320A Single Phase URD Meter Loop Installations"

Transcription

1 320A Single Phase URD Meter Loop Installations Location: The meter loop shall be mounted on the side of the pedestal facing the consumer's lot. (The side being one of the four flat surfaces of the pedestal which faces towards the consumer's lot.) Weatherproof fused or breaker protected main disconnect panel will have a main disconnect on the outside of the building regardless of the number of circuit breakers. Rack: 1. Shall be self supporting with a minimum of 2" schedule 40 galvanized rigid pipes and caps, cut to the required length, with two feet of the pipe set in the ground in concrete. 2. It shall be stood away from the pedestal a minimum of 18" and not more than 24" with a 3" schedule 40 galvanized rigid pipe nipple of required length. 3. Grounding bushings shall be installed on the 3" nipple inside the meter socket and pedestal with regular locknuts backing them up on the outside of the meter socket and meter pedestal. 4. The cross supports for the meter socket, panel, or panels shall be a minimum of 3/4" x 1 1/2" unistrut of the required length and shall not extend past the rigid pipe supports more than 2" and shall be bolted firmly to the rigid pipe. Wire Size: Shall be a minimum of 350 copper or equivalent aluminum with equal size neutral or one standard size smaller. (Parallel conductors of 2/0 copper and 4/0 aluminum for residences may be used.) Installation of the Wire: The wire shall run from the line side of the meter socket into the pedestal allowing 36" of tail to connect to the pedestal connectors and the same size wire or equivalent parallel conductors shall be run from the load side of the meter socket to the panel or panels. (If parallel conductors are used, double barrel lugs shall be used. Customer must purchase double barrel lugs if needed.) Pipe Nipples Between the Meter, s, and Gutters: 1. 3" Schedule 40 galvanized rigid or IMC nipples shall be used between the meter socket and 400A panel or gutter when used. 2. 2" Schedule 40 galvanized rigid or IMC nipples shall be used between the meter socket and or 125A panels or between or 125A panels and the gutter. Grounding Bushings: Shall be used on the inside of the meter socket, panel, or panels attached to the grounding bus bar with a #6 copper grounding conductor. Regular locknuts shall back them up on the outside of the meter socket, panel, or panels. drawn: REB approved MJB Page 1

2 320A Loops on Meter Pedestals Side by Side Combination Member will be responsible for the installation of underground cable from the breaker to the load. The underground cable used shall be an approved type for underground installation (USE or UF type). Conductor size will be based upon member load, location of meter, and National Electric Code for size of conduit. Minimum 2" rigid galvanized cap Meter Pedestal The rack should be separated a minimum of 18" or a maximum of 24" from the meter pedestal, use a 3" rigid nipple between the meter socket and meter pedestal 44" Minimum from top of pipe to grade 320A Meter or 125A Minimum of 2" rigid galvanized pipe Rigid pipe to be set in concrete 2' deep Unistrut support as needed Minimum 2" rigid nipples between panels Side Mount Combination 44" Minimum from top of pipe to grade 320A Meter or 125A drawn: REB approved MJB Page 2

3 Transformer Top View of 320A URD Meter Loop off a Meter Pedestal Pad or Pedestal Minimum of 2" rigid pipe Minimum of 18" to 24" Combination maximum between pedestal 3" Rigid galvanized Pad and rack nipple Minimum 2" rigid galvanized nipples between panels 320 Meter Loop Rack Must Face Towards the Lot to be Served Lot Line Meter Meter drawn: approved REB MJB Page 3

4 Side Mount with Trough Combination Member will be responsible for the installation of underground cable from the breaker to the load. The underground cable used shall be approved type for underground installation (USE or UF type). Conductor size will be based upon member load, location of meter, and National Electric Code for size of conduit. 44" Minimum from top of pipe to grade 320A Meter or 125A Service conductors only Trough to be sized according to NEC requirements 3" minimum rigid nipple between meter socket and trough Ground 2" nipples from panel to trough Ground Level 250A to 400A 44" Minimum from top of pipe to grade 320A Meter 250A or 400A 3" minimum rigid nipple between meter socket and main panel drawn: approved REB MJB Page 4

5 Typical URD 320A Loop on the Side of a House Any Loop Configuration Detailed Can Be Used 5' to 6' to center of meter socket 320A Meter or 125A 3" Schedule 80 URD lateral Note: The URD lateral from the pad mount transformer must be inspected by the underground inspector in accordance with existing requirements. Minimum of 2" nipples from meter socket to panels Ground rod 3/4" x 8' with #2 copper from meter to ground rod drawn: approved REB MJB Page 5

6 Typical URD 320A Free Standing Rack Any Loop Configuration Detailed Can Be Used Member will be responsible for the installation of underground cable from the breaker to the load. The underground cable used shall be an approved type for underground installation (USE or UF type). Conductor size will be based upon member load, location of meter, and National Electric Code for size of conduit. Please contact District Office prior to construction of this rack Unistrut support as needed Minimum 2" rigid galvanized cap 4' 320A Meter or 125A Minimum of 2" rigid galvanized pipe to be set in 2 feet of concrete 3/4" X 10' Ground Rod Minimum 2" rigid nipples between panels #2 Copper minimum drawn: approved JBS MJB Page 6

7

8 Typical 320A Single Phase Loop on a Meter Pole with Side by Side Mount Weatherhead to be within 12" from the top of the pole No member owned facilities on PEC poles other than meter loops. Member shall purchase meter socket. Member will be responsible for replacement and repair of meter loop, including meter socket. Minimum of 350 MCM copper or equivalent aluminum with 30" of tails out of the weatherhead. Neutral conductor must be electrically continuous through the meter socket to the main panel and must be attached to the meter socket. See note on page 7. 3" Schedule 40 rigid pipe, IMC, or EMT with weather tight connectors or electrical grade PVC 3-3" Two hole straps for the type of pipe being used Rigid cap sized for the pipe used Unistrut minimum 3/4" X 1 1/2"of required length 5' Minimum 6' Maximum 320A Meter or 125A 2" Minimum rigid galvanized pipe must be used to make the vertical supports Rigid posts must be set a minimum of 2' in the ground and cemented Ground Level #2 copper ground wire 3/4" x 8' copper ground rod drawn: approved REB MJB Page 8

9 Typical 320A Single Phase Loop on a Meter Pole with Side Mount s Weatherhead to be within 12" from the top of the pole No member owned facilities on PEC poles other than meter loops. Member shall purchase meter socket. Member will be responsible for replacement and repair of meter loop, including meter socket. Minimum of 350 MCM copper or equivalent aluminum with 30" of tails out of the weatherhead. Neutral conductor must be electrically continuous through the meter socket to the main panel and must be attached to the meter socket. See note on page 7. 3" Schedule 40 rigid pipe, IMC, or EMT with weather tight connectors or electrical grade PVC 3-3" Two hole straps for the type of pipe used Unistrut minimum of 3/4" x 1 1/2" of required length 5' Minimum 6' Maximum 320A Meter or 125A 2" Minimum rigid galvanized pipe must be used to make the vertical supports Rigid posts must be set a minimum of 2' in the ground and cemented Ground Level #2 copper ground wire 3/4" x 8' copper ground rod drawn: approved REB MJB Page 9

10

11

12

13

14

UNDERGROUND SERVICE ENTRANCE LOCATION. No meter base or entrance should be installed before an KREMC engineer has checked the proposed location.

UNDERGROUND SERVICE ENTRANCE LOCATION. No meter base or entrance should be installed before an KREMC engineer has checked the proposed location. UNDERGROUND SERVICE No meter base or entrance should be installed before an KREMC engineer has checked the proposed location. Entrance cabinet must be directly through wall or directly under meter in basement.

More information

UNDERGROUND SERVICE ENTRANCE LOCATION. No meter base or entrance should be installed before an KREMC engineer has checked the proposed location.

UNDERGROUND SERVICE ENTRANCE LOCATION. No meter base or entrance should be installed before an KREMC engineer has checked the proposed location. UNDERGROUND SERVICE No meter base or entrance should be installed before an KREMC engineer has checked the proposed location. Entrance cabinet must be directly through wall or directly under meter in basement.

More information

Engineering Service Specifications. Commercial Single-Phase Current Transformer Metering Schemes

Engineering Service Specifications. Commercial Single-Phase Current Transformer Metering Schemes Engineering Service Specifications Commercial Single-Phase Current Transformer Metering Schemes Specifications for Commercial Underground Current Transformer Metering Requirements for a Single-Phase Customer

More information

OVERHEAD SERVICE. Items to consider

OVERHEAD SERVICE. Items to consider OVERHEAD SERVICE Items to consider The maximum length of the service wire from the ComEd pole to the point of attachment on your residence is 150 feet, if practical. Your service wire installation must

More information

SERVICE ATTACHMENT ON A BUILDING WITH BUS DUCT SERVICE ENTRANCE AND INDOOR METERING

SERVICE ATTACHMENT ON A BUILDING WITH BUS DUCT SERVICE ENTRANCE AND INDOOR METERING SERVICE ATTACHMENT ON A BUILDING WITH BUS DUCT SERVICE ENTRANCE AND INDOOR METERING Obtain acceptance and specific details from the local Company office. 1. Service entrance duct (see Note 1). Company

More information

D9-3. No. WIRING DIAGRAM CONNECTIONS FOR UNDERGROUND SELF CONTAINED METERS JRH JED krich95 LINE LINE ABCN SOURCE SOURCE GROUND GROUND STUD STUD SOURCE

D9-3. No. WIRING DIAGRAM CONNECTIONS FOR UNDERGROUND SELF CONTAINED METERS JRH JED krich95 LINE LINE ABCN SOURCE SOURCE GROUND GROUND STUD STUD SOURCE SOURCE 20V 240V STUD (PER NEC) A customer supplied and installed teaser wire is required from the neutral lug to a 5th terminal mounted on the left side of the meter block between the line and load terminals.

More information

UNDERGROUND SERVICES - SECONDARY

UNDERGROUND SERVICES - SECONDARY UNDERGROUND SERVICES - SECONDARY Contents - Underground Services... U-1 General Requirements for Underground Service...U-2 Names of Parts for Underground Service... U-3 Service Termination in a Service

More information

Customer Requirements Meter Socket Configurations

Customer Requirements Meter Socket Configurations Application Information on meter socket configurations available from Tacoma Power. For enclosed meter pedestals, see standard C-MR-0020 Customer Requirements, Enclosed Meter Pedestal. General Requirements

More information

Pentahead bolts See note 2. Conduit run as specified. Company facility. Refer to drawing SS8.6-2 or SS8.6-3 STANDARD SERVICE INSTALLATION

Pentahead bolts See note 2. Conduit run as specified. Company facility. Refer to drawing SS8.6-2 or SS8.6-3 STANDARD SERVICE INSTALLATION PULL BOX F SECONDARY SYSTEM Typical grade Pentahead bolts See note 2 Conduit run as specified Plastic or fiberglass for grass areas or Polymer concrete for light duty areas (see notes 2, 3, & 4) Company

More information

COMMERCIAL QUICK REFERENCE

COMMERCIAL QUICK REFERENCE COMMERCIAL QUICK REFERENCE PROVO CITY POWER STANDARDS ELECTRICAL ENGINEERING UPDATED: 2016 SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTIFICATION. 18" MIN. OF TAIL. (NEUTRAL CONDUCTOR MUST BE WHITE OR

More information

SOUTHWEST LOUISIANA ELECTRIC MEMBERSHIP COORPORATION COMMERCIAL SERVICE REQUIREMENTS

SOUTHWEST LOUISIANA ELECTRIC MEMBERSHIP COORPORATION COMMERCIAL SERVICE REQUIREMENTS SOUTHWEST LOUISIANA ELECTRIC MEMBERSHIP COORPORATION COMMERCIAL SERVICE REQUIREMENTS November 17, 2016 Engineering Service Specifications Table of Contents Commercial Service Requirements SLEMCO Commercial

More information

SECTION 300 OVERHEAD SERVICE

SECTION 300 OVERHEAD SERVICE SECTION 300 OVERHEAD SERVICE 300.01 General Company provides, installs, and maintains service drop to point of delivery approved by Company. Customer provides point of attachment which is acceptable to

More information

AMENDMENT ELECTRIC SERVICE MANUAL 2014

AMENDMENT ELECTRIC SERVICE MANUAL 2014 AMENDMENT (Pages 20,43,50,72,74,,76,78,83,86,99) ELECTRIC SERVICE MANUAL 2014 Effective April 1, 2015 18-7 6.0 SERVICE AND SERVICE ENTRANCES (General), Continued Conductor Sizing It is recommended that

More information

New Service. From... BARRON. Spooner Office: P.O. Box 261 Spooner, WI Barron Office: P.O. Box 40 Barron, WI

New Service. From... BARRON. Spooner Office: P.O. Box 261 Spooner, WI Barron Office: P.O. Box 40 Barron, WI New Service Guidelines and Diagrams From... BARRON www.barronelectric.com email: janderson@barronelectric.com Barron Office: P.O. Box 40 Barron, WI 54812-0040 Spooner Office: P.O. Box 261 Spooner, WI 54801-0261

More information

UNDERGROUND SERVICE. Items to consider. There will be charges from ComEd if you convert from overhead to underground service.

UNDERGROUND SERVICE. Items to consider. There will be charges from ComEd if you convert from overhead to underground service. UNDERGROUND SERVCE tems to consider f your trenching route has to be dug by hand, or if a cable must be installed under a paved surface, additional charges apply. f your service cable has to be moved later

More information

ELECTRIC SERVICE RULES DISTRIBUTED GENERATION Issued Jan 2016

ELECTRIC SERVICE RULES DISTRIBUTED GENERATION Issued Jan 2016 DISTRIBUTED GENERATION CHAPTER 5 500. SCOPE This chapter includes distributed or customer-owned generation connected in parallel and operating with Alliant Energy s electric distribution system. For all

More information

Revised: April 2018 ¹ SERVICE TO WIRELESS DEVICE ANTENNA ATTACHMENTS ON CUSTOMER SERVICE POLES (SHEET 1) CUSTOMER: 1. An overcurrent protective device including a disconnect switch shall

More information

Approved Contractor Construction e-guide Residential Commercial

Approved Contractor Construction e-guide Residential Commercial Approved Contractor Construction e-guide Residential Commercial Clark Public Utilities PO Box 8900 Vancouver, WA 98668 (PAGE 2) TABLE OF CONTENTS PAGE Trenching 3 Wire 8 Single-Phase Transformer Set 13

More information

7. Residential Single-Family and Duplex Buildings (Dwellings)

7. Residential Single-Family and Duplex Buildings (Dwellings) Sin g le -F a mily a n d Du p le x Bu ild in g s 2016 Electric Service Requirements, 2 nd Edition Section 7 Section 7 Residential Single-Family and Duplex Buildings (Dwellings) Directory Page 7.1 General

More information

10 Commercial, Industrial, Agricultural Services

10 Commercial, Industrial, Agricultural Services 10 Commercial, Industrial, Agricultural Services This section describes the Power Company requirements for commercial, industrial, and agricultural services. This section covers single phase and three

More information

7 Single Family Service

7 Single Family Service 7 Single Family Service 7. General The location of the service entrance on the Customer s premises is an important consideration. For clearance and location information see section 5 (Clearances). Consult

More information

For Conduit Inspections

For Conduit Inspections Underground Conduit Standards - Table of Content 5/8/2017 Section S22 Underground Conduit Standard Index: Description: 00 Table of Content 01 General Notes 02 Definition of Terms 03 Primary Riser Conduit

More information

9. Non-Residential Services (Commercial, Industrial, and Agricultural)

9. Non-Residential Services (Commercial, Industrial, and Agricultural) Section 9 2016 Electric Service Requirements, 3rd Edition Section 9 Non-Residential Services Directory Page 9.1 General Requirements 68 9.2 Direct-Connect Metering, Single Installations 69 9.3 Direct-Connect

More information

SINGLE PHASE WIRING SPECIFICATIONS

SINGLE PHASE WIRING SPECIFICATIONS SINGLE PHASE WIRING SPECIFICATIONS 1-866-MEC-ELEC (1-866-632-3532) Office Locations: Hondo Office 237 Hwy 173 N Hondo, TX 78661-0370 Fax 830.426.3335 Dilley Office 1718 W. FM 117 Dilley, TX 78017 Fax 830.965.1425

More information

ELECTRIC SERVICE RULES UTILITY/CATV SERVICES Issued Jan 2016

ELECTRIC SERVICE RULES UTILITY/CATV SERVICES Issued Jan 2016 UTILITY/CATV SERVICES CHAPTER 9 900. GENERAL A. Alliant Energy receives many requests for electric service from other utilities; telephone, telecommunications companies, cable television, the Department

More information

U-18. Company furnishes and installs: 10. Service lateral and connectors. 11. Conduit package, Amperes.

U-18. Company furnishes and installs: 10. Service lateral and connectors. 11. Conduit package, Amperes. SERVICE TERMINATION IN A TERMINATION COMPARTMENT DIRECT BURIED OR CONCRETE ENCASED LATERAL ALL 1-PHASE VOLTAGES, 400-800 AMPERES ALL 3-PHASE VOLTAGES, 400-3000 AMPERES ONLY Obtain acceptance for 1-phase

More information

THREE PHASE WIRING SPECIFICATIONS

THREE PHASE WIRING SPECIFICATIONS THREE PHASE WIRING SPECIFICATIONS 1-866-MEC-ELEC (1-866-632-3532) Office Locations: Hondo Office 237 Hwy 173 N Hondo, TX 78661-0370 Fax 830.426.3335 Dilley Office 1718 W. FM 117 Dilley, TX 78017 Fax 830.965.1425

More information

Installing or Rebuilding Your Electric Service

Installing or Rebuilding Your Electric Service Installing or Rebuilding Your Electric Service 2 3 Contents Policies for New and Rebuilt Electric Service 2-4 Paperwork and fees...2 Five-year policy...3 Proposed route location and conditions...3 Construction

More information

NEW SERVICE HANDBOOK COMMERCIAL & IRRIGATION SUPPLEMENT

NEW SERVICE HANDBOOK COMMERCIAL & IRRIGATION SUPPLEMENT NEW SERVICE HANDBOOK COMMERCIAL & IRRIGATION SUPPLEMENT Meter Installations There are three basic ways to measure electricity consumption: Small and medium services are metered directly using direct connect

More information

RESIDENTIAL SUBDIVISION SERVICE REQUIREMENTS SECTION VI RESIDENTIAL SUBDIVISION SERVICE REQUIREMENTS

RESIDENTIAL SUBDIVISION SERVICE REQUIREMENTS SECTION VI RESIDENTIAL SUBDIVISION SERVICE REQUIREMENTS SECTION VI SERVICE REQUIREMENTS This section discusses the requirements for establishing electric service to new residential subdivisions in Palo Alto. Subdivisions are normally constructed on dedicated

More information

Section 6 Electric Metering: Residential

Section 6 Electric Metering: Residential Section 6 Electric Metering: Residential 6.1. Scope This section provides specific information for residential metering that is not covered by the basic requirements in Section 5, Electric Metering: General.

More information

SPRINGVILLE CITY ELECTRICAL REQUIREMENTS & STANDARDS MANUAL

SPRINGVILLE CITY ELECTRICAL REQUIREMENTS & STANDARDS MANUAL POWER DEPARTMENT EFFECTIVE AS OF FEBRUARY 1, 2008, REVISED JULY 1, 2013 STANDARDS ARE SUBJECT TO REVIEW TABLE OF CONTENTS Section 1 General Requirements Purpose...1.1 Codes and Ordinances...1.1 Changes

More information

JACKSON ELECTRIC COOP METER LOOP CONSTRUCTION SPECIFICATIONS JUNE 2018

JACKSON ELECTRIC COOP METER LOOP CONSTRUCTION SPECIFICATIONS JUNE 2018 JACKSON ELECTRIC COOP METER LOOP CONSTRUCTION SPECIFICATIONS JUNE 2018 GANADO OFFICE PHYSICAL ADDRESS: 8925 State Highway 111 E Ganado, TX 77962 Phone: (361)771-4400 BAY CITY OFFICE PHYSICAL ADDRESS: 100

More information

34.00 METERING GENERAL LABELING MULTIPLE METER ENCLOSURES ON A SINGLE PREMISE

34.00 METERING GENERAL LABELING MULTIPLE METER ENCLOSURES ON A SINGLE PREMISE 4. METERING GENERAL LABELING MULTIPLE METER ENCLOSURES ON A SINGLE PREMISE 4.-4 4. SELF-CONTAINED METERING, SINGE-PHASE INSTALLATION DETAILS /4 VOLT SINGLE-PHASE UNDERGROUND RESIDENTIAL SERVICE AND METER

More information

New Panelboard for Lot H, EV Charger Energization, Las Positas College. Scope of Work and Technical Specifications

New Panelboard for Lot H, EV Charger Energization, Las Positas College. Scope of Work and Technical Specifications CHABOT-LAS POSITAS COMMUNITY COLLEGE DISTRICT New Panelboard for Lot H, EV Charger Energization, Las Positas College Scope of Work and Technical Specifications Chabot-Las Positas Community College District

More information

SECTION 400 UNDERGROUND SERVICE

SECTION 400 UNDERGROUND SERVICE SECTION 400 UNDERGROUND SERVICE 400.01 General Underground service is rovided to Customer who meets Comany requirements set out herein and ays to Comany any amount due. Cash ayments or other arrangements

More information

CHAPTER V RESIDENTIAL WIRING

CHAPTER V RESIDENTIAL WIRING CHAPTER V RESIDENTIAL WIRING 5.1. THE SERVICE ENTRANCE Buildings and other structures receive the electrical energy through the service entrance. In residential wiring, the electric company supply this

More information

Electric Service Standards

Electric Service Standards VI - 1 of 17 VI. METERING EQUIPMENT A. Equipment Furnished and Installed by FPL FPL provides and installs, at its expense, adequate metering instruments to measure the electric service used by the Customer.

More information

Eaton Corp. - Marina Power and Lighting, Inc. General Specifications for Lighthouse Power Pedestal

Eaton Corp. - Marina Power and Lighting, Inc. General Specifications for Lighthouse Power Pedestal DRILL \ PUNCH OUT TO SIZE REQUIRED DRILL \ PUNCH OUT TO SIZE REQUIRED Lighthouse Power Pedestal - Specifications Lighthouse Power Pedestal Dimensions Height: 44.00" (1117.60 mm) Width: 13.67" (347.22 mm)

More information

FROM B.C. HYDRO ENCLOSURE (SEE NOTE 4) RIGID CONDUITS (SEE NOTE 8) ALTERNATIVE TO LOAD BARRIER (SEE NOTE 7) SERVICE ENTRANCE ENCLOSURE

FROM B.C. HYDRO ENCLOSURE (SEE NOTE 4) RIGID CONDUITS (SEE NOTE 8) ALTERNATIVE TO LOAD BARRIER (SEE NOTE 7) SERVICE ENTRANCE ENCLOSURE FROM B.C. HYDRO FOR OVERHEAD INSTALLATION ONLY DUCT SEAL (SEE NOTE 8) PULL BOX (SEE NOTE 5) PULL BOX (SEE NOTE 5) FROM B.C. HYDRO 7- REVISED NOTES & TABLES ON PAGES,3,4,5,.MARCH AJ - GENERAL REV.MA 08

More information

SALEM CITY POWER ELECTRICAL REQUIREMENTS & STANDARDS MANUAL

SALEM CITY POWER ELECTRICAL REQUIREMENTS & STANDARDS MANUAL SALEM CITY POWER DEPARTMENT TABLE OF CONTENTS Section 1 General Requirements Purpose...1.1 Codes and Ordinances...1.1 Changes or Conflicts in Requirements and Guidelines...1.1 Application for Service...1.2

More information

2. DEFINITIONS. 2.3 APPROVED Acceptable to the authority enforcing the National Electric Code

2. DEFINITIONS. 2.3 APPROVED Acceptable to the authority enforcing the National Electric Code 2. DEFINITIONS 2.1 ACCEPTABLE Acceptable to the Company. 2.2 ADVANCED METER A meter that is capable of remote reading, and is capable of storing electric consumption data at specified time intervals of

More information

2016 METER SERVICES SPECIFICATION GUIDE

2016 METER SERVICES SPECIFICATION GUIDE 2016 METER SERVICES SPECIFICATION GUIDE 802.01.ST (10-16) CONTENTS Introduction 2 Disclaimers 2 LES contacts 3 Definitions 4 LES Meter Services department requirements for approval of connection to LES

More information

Outdoor Power Transmission & Distribution

Outdoor Power Transmission & Distribution Description: The purpose of the section is to highlight the current applicable UMCP Design Standards and requirements for Outdoor Power Transmission and Distribution, including but not limited to the following:

More information

Cable Supports. Requirements for Cable Supports in the National Electrical Code reads as follows:

Cable Supports. Requirements for Cable Supports in the National Electrical Code reads as follows: QA1 General Information are used to support cables in vertical raceways or risers. Cable supports relieve the strain that would be placed on terminations, the interior of panels, or other devices to which

More information

Commercial & Industrial

Commercial & Industrial The Empire District Electric Company Requirements For Electric Service And Meter Installations Commercial & Industrial (800) 206 2300 The latest revision of this book can be found at www.empiredistrict.com

More information

TEMPORARY ELECTRIC WIRING FOR CARNIVALS, CONVENTIONS, EXHIBITIONS, FAIRS AND SIMILAR USES

TEMPORARY ELECTRIC WIRING FOR CARNIVALS, CONVENTIONS, EXHIBITIONS, FAIRS AND SIMILAR USES INFORMATION BULLETIN / PUBLIC - ELECTRICAL CODE REFERENCE NO.: LAMC 93.0230 Effective: 3-24-69 DOCUMENT NO. P/EC 2002-006 Revised: 11-17-00 Previously Issued As: RGA #7-69 TEMPORARY ELECTRIC WIRING FOR

More information

ELECTRIC POLICY INTRODUCTION CHAPTER I GENERAL

ELECTRIC POLICY INTRODUCTION CHAPTER I GENERAL INTRODUCTION This policy has been adopted by the Board of Public Works as a guide to obtaining electric service and to set forth the services available, conditions for service, and standards for materials

More information

Eaton Corp. - Marina Power and Lighting, Inc. General Specifications for Lighthouse-SS Power Pedestals

Eaton Corp. - Marina Power and Lighting, Inc. General Specifications for Lighthouse-SS Power Pedestals Lighthouse-SS Power Pedestal Dimensions Height: 44.00" (1117.60 mm) Width: 9.565" (242.95 mm) Depth: 9.875" (250.83 mm) Lighthouse-SS Base Diagram Ø0.50" MOUNTING HOLE (TYP.) 9.5625" 8.0625" 7.3125" C:\Documents

More information

General Specifications for Lighthouse Power Pedestal

General Specifications for Lighthouse Power Pedestal Dimensions Height: 44.00 11 (1117.60 mm) Width: 13.67" (347.22 mm) Depth: 13.75" (349.25 mm) Lighthou98 Base Diagram ---13,75 1 --- Approximate Weight: 30 lbs. (13.6 kg) Multiply base dimensions by 25.4

More information

General Cable Support Information

General Cable Support Information General Cable Support Information Applications Used to support cables in vertical raceways or risers. Relieves the strain that would be placed on terminations, the interior of panels, or other devices

More information

Recreational Vehicle Park Electrical Products & Accessories

Recreational Vehicle Park Electrical Products & Accessories Recreational Vehicle Park Electrical Products & Accessories 2 MILBANK OVERVIEW Milbank Overview Energy At Work since 1927 Milbank designs and manufactures electrical solutions that move and manage power

More information

AGRICULTURAL UNDERGROUND SERVICE 500 HP OR LESS

AGRICULTURAL UNDERGROUND SERVICE 500 HP OR LESS Prepared by: ABB1 AGRICULTURAL UNDERGROUND SERVICE 500 HP OR LESS 05619 Asset Type: Electric Metering Function: Design and Construction Issued by: Lisseth Villareal (LDV2) Date: 07-31-15 Rev. #10: This

More information

Electric Service Requirements & Guidelines

Electric Service Requirements & Guidelines Electric Service Requirements & Guidelines Montana Service Area September 2011 NORTHWESTERN ENERGY Montana Service Area ELECTRIC SERVICE REQUIREMENTS AND GUIDELINES CONTENTS I. GENERAL INFORMATION 1.01

More information

Table of Contents. Electrical Service Requirements. 1. General Requirements

Table of Contents. Electrical Service Requirements. 1. General Requirements Table of Contents 1. General Requirements 1.1 General Definition.................................................... 1 1 1.2 Booklet Purpose and Organization....................................... 1-1

More information

ROADWAY LIGHTING SYSTEMS (2545)

ROADWAY LIGHTING SYSTEMS (2545) GENERAL LIGHTING MATERIAL REQUIREMENTS General material requirements must be in accordance with MnDOT 2545.2. SERVICE CABINETS 3850 Lighting service cabinets Type L1, Type L2, Type A, Type B, and Type

More information

Number Tube I.P.S. Rod Size or O.D. Range Cable H J W

Number Tube I.P.S. Rod Size or O.D. Range Cable H J W TYPE GAR D-28 FENCE POST GROUNDING CONNECTOR For Parallel or 90 Copper Cable Connection To Rod or Pipe with the Same Connector High copper alloy ground connector for joining a range of cable, parallel

More information

SERVICE ENTRANCE - UNDERGROUND Single & Three Phase 200, & 320/400 Amp

SERVICE ENTRANCE - UNDERGROUND Single & Three Phase 200, & 320/400 Amp Printed from NIPSCO.com 04-01-17 PAGE 1 OF 6 USE: Arrangement of service equipment to supply electric energy to an underground, outdoor self contained meter installation. LATEST REVISION: PREVIOUS REVISION

More information

Transmission & Distribution Glossary of Electrical Terms

Transmission & Distribution Glossary of Electrical Terms Transmission & Distribution Glossary of Electrical s Breaker Panel Bushing Circuit Circuit Breaker Conductor Conduit Consumption Current Distribution Electricity (Static vs. Current) Electron Feeder The

More information

PUBLIC UTILITY DISTRICT NO. 1 OF LEWIS COUNTY METERING SPECIFICATIONS

PUBLIC UTILITY DISTRICT NO. 1 OF LEWIS COUNTY METERING SPECIFICATIONS PUBLIC UTILITY DISTRICT NO. 1 OF LEWIS COUNTY METERING SPECIFICATIONS 1. General Metering Requirements a. Interpretation The District s metering requirements shall not be interpreted to conflict with the

More information

Meter Installation. -and- Padmount Transformer Guide

Meter Installation. -and- Padmount Transformer Guide Meter Installation -and- Padmount Transformer Guide Feb. 2016 METERING REQUIREMENTS The following information shall be used as a guide for installing metering equipment. A self-contained meter has all

More information

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 2/8/12 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 2/8/12 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions MECKLENBURG COUNTY Land Use and Environmental Service Agency Code Enforcement 2/8/12 ELECTRICAL CONSISTENCY MEETING Code Consistency Questions 1. I am inspecting a building addition. They have a 480V to

More information

Metering and Service Installation:

Metering and Service Installation: Table of Contents 1. Metering Installation Requirements, General... 1 2. Type of Service... 2 3. Definitions... 2 4. Who Provides Metering Equipment?... 2 5. Establishment of Service... 2 6. Meter Access...

More information

FM9 Aluminum Unilet Conduit Outlet Bodies, Covers and Gaskets For use with Rigid Steel, Rigid Aluminum and IMC.

FM9 Aluminum Unilet Conduit Outlet Bodies, Covers and Gaskets For use with Rigid Steel, Rigid Aluminum and IMC. FM9 Aluminum Unilet Conduit Outlet Bodies, Covers and Gaskets For use with Rigid Steel, Rigid Aluminum and IMC. : Conduit Bodies Applications Serve as pulling fittings. Make bends in conduit system. Provide

More information

METERING REQUIREMENTS

METERING REQUIREMENTS METERING REQUIREMENTS KUA will not accept a non-securable service trough entrance. That is, all enclosed conductors prior to the meter (line side) will be securable by and accessible to KUA personnel only.

More information

Marshfield Utilities Rules for Electric Service Installations. Table of Contents

Marshfield Utilities Rules for Electric Service Installations. Table of Contents ELECTRIC SERVICE MANUAL 2018 Marshfield Utilities Rules for Electric Service Installations Table of Contents Section Topic Page Table of Contents... I Mission and Vision Statements... VII Introduction

More information

Approved Meter Sockets and Cabinets

Approved Meter Sockets and Cabinets Single Unit Residential Guide 1 PHASE, 120/240 VOLT SERVICES SERVICE CAPACITY OWNED METERING (Metering sockets and cabinets are supplied by Customer). Outdoor meter mounting height is 1730 mm ( 5 8 ) to

More information

SPRINGVILLE CITY ELECTRICAL REQUIREMENTS & STANDARDS MANUAL

SPRINGVILLE CITY ELECTRICAL REQUIREMENTS & STANDARDS MANUAL 1 POWER DEPARTMENT EFFECTIVE AS OF FEBRUARY 1, 2008, REVISED JULY 1, 2013 STANDARDS ARE SUBJECT TO REVIEW Table of Contents 2 TABLE OF CONTENTS Section 1 General Requirements Purpose...1.1 Codes and Ordinances...1.1

More information

Engineering Rules and Regulations for Electric Service Platte-Clay Electric Cooperative, Inc.

Engineering Rules and Regulations for Electric Service Platte-Clay Electric Cooperative, Inc. Engineering Rules and Regulations for Electric Service Platte-Clay Electric Cooperative, Inc. December 2016 (Expires 9/30/18) Kearney Cooperate Headquarters 1000 W. 92 Highway Kearney, MO Platte City District

More information

RESIDENTIAL UNDERGROUND AND OVERHEAD SERVICE REQUIREMENTS SECTION II RESIDENTIAL UNDERGROUND AND OVERHEAD SERVICE REQUIREMENTS

RESIDENTIAL UNDERGROUND AND OVERHEAD SERVICE REQUIREMENTS SECTION II RESIDENTIAL UNDERGROUND AND OVERHEAD SERVICE REQUIREMENTS SECTION II This section discusses the City of Palo Alto's requirements for establishing electric service to new or upgraded residential installations. The same requirements apply to both underground and

More information

Current Transformer, Termination & Disconnect Cabinets WE Energies Approved

Current Transformer, Termination & Disconnect Cabinets WE Energies Approved Current Transformer, Termination & Disconnect Cabinets WE Energies Approved 2 TABLE OF CONTENTS Table of Contents Current Transformer Cabinets Overhead Entry... 4 Underground Entry and Underground Exit...

More information

Pretest Module 24 Three-phase Service Entrance

Pretest Module 24 Three-phase Service Entrance Pretest Module 24 Three-phase Service Entrance 1. What is the most widely used three-phase service entrance system? 2. What are the three most common voltage combinations for three-phase, four-wire systems?

More information

A. Submit manufacturer's literature and technical data before starting work.

A. Submit manufacturer's literature and technical data before starting work. SECTION 16425 SWITCHBOARD PART 1 GENERAL 1.01 SUMMARY A. Related Section: 1. 16450 - Grounding. 1.02 SUBMITTALS A. Submit manufacturer's literature and technical data before starting work. B. Submit Shop

More information

Electric Service Policy Kerrville Public Utility Board

Electric Service Policy Kerrville Public Utility Board Electric Service Policy Kerrville Public Utility Board 1 SCOPE AND PURPOSE... 1 2 DEFINITIONS... 1 2.1 Agreement for Electric Service... 1 2.2 City of Kerrville... 1 2.3 Connected Load...1 2.4 Contribution

More information

Specification Grade Insulated Bushings...DA1 Specification Grade Insulated Grounding Bushings...DA2-DA4. Insulating Bushings & Couplings...

Specification Grade Insulated Bushings...DA1 Specification Grade Insulated Grounding Bushings...DA2-DA4. Insulating Bushings & Couplings... SECTION D INDEX Product Description Page Number Specification Grade Insulated Bushings.....................DA Specification Grade Insulated Grounding Bushings........DA2-DA4 Insulating Bushings & Couplings.......................DA-DA6

More information

Options: PART NUMBER MAIN BREAKER PHASE VOLTAGE

Options: PART NUMBER MAIN BREAKER PHASE VOLTAGE BC Hydro Metering Kiosk BCH Metering and distribution kiosk built to BC Hydro distribution standards. Used for applications where secondary services are installed in weatherproof kiosks outside of a main

More information

INSTALL SERVICE- ENTRANCE SYSTEMS

INSTALL SERVICE- ENTRANCE SYSTEMS SUBCOURSE EN5141 EDITION B US ARMY ENGINEER SCHOOL INSTALL SERVICE- ENTRANCE SYSTEMS INSTALL SERVICE- ENTRANCE SYSTEMS Subcourse Number EN5141 EDITION B United States Army Engineer School Fort Leonard

More information

Conduit Bushings for Rigid Metal Conduit and IMC

Conduit Bushings for Rigid Metal Conduit and IMC Applications Used with a locknut to terminate rigid metal conduit or IMC conduit to a box or enclosure. Features Provides a smooth pulling surface. Material/Finish BU: malleable iron/zinc electroplated

More information

CONTENTS BY CHAPTER. Chapter 2: COMPANY EQUIPMENT ON CUSTOMER PREMISES

CONTENTS BY CHAPTER. Chapter 2: COMPANY EQUIPMENT ON CUSTOMER PREMISES CONTENTS BY CHAPTER Chapter 1: GENERAL INFORMATION Chapter 2: COMPANY EQUIPMENT ON CUSTOMER PREMISES Chapter 3: SERVICE ENTRANCES Chapter 4: METERING INSTALLATION Chapter 5: CUSTOMER-INSTALLED SERVICE

More information

SECTION 500 METERING AND ASSOCIATED EQUIPMENT

SECTION 500 METERING AND ASSOCIATED EQUIPMENT SECTION 500 METERING AND ASSOCIATED EQUIPMENT 500.0 General Meter sockets shall be provided, installed and maintained by Customer. When the ratings of meter sockets are exceeded, transockets shall be used.

More information

KIUC Service Installation Manual

KIUC Service Installation Manual KIUC Service Installation Manual Second Edition (November 2016) This manual provides the general requirements for electric service and metering for Kauaʻi Island Utility Cooperative ("KIUC") and is meant

More information

PEU reserves the right to determine all meter locations. Only authorized PEU personnel will determine this location.

PEU reserves the right to determine all meter locations. Only authorized PEU personnel will determine this location. I N T R O D U C T I O N - M-1 RIGHTS: PEU reserves the right to determine all meter locations. Only authorized PEU personnel will determine this location. NOTIFICATION: Customers planning to install or

More information

STOUGHTON UTILITIES ELECTRIC SERVICE RULES AND INFORMATION

STOUGHTON UTILITIES ELECTRIC SERVICE RULES AND INFORMATION CHAPTER 1 - GENERAL INFORMATION 100. Purpose 101. Codes and rules 102. Continuity of service 103. Frequency, Voltage, and Amperage Limitations 104. High voltages 105. Unusual capacity requirements 106.

More information

ENTRANCE EQUIPMENT ER D PAGE 1 OF 5

ENTRANCE EQUIPMENT ER D PAGE 1 OF 5 PAGE 1 OF 5 USE: Requirements for entrance equipment. PREVIOUS REVISION 07-01-98 ORIGINATED 03-94 PREVIOUS NUMBER ER 100 (12-01-81) LATEST REVISION: Updated meter socket labeling specification and instrument

More information

TABLE OF CONTENTS. Important Notices Underground Plant Protection Information. Commercial/Industrial Information Sheet

TABLE OF CONTENTS. Important Notices Underground Plant Protection Information. Commercial/Industrial Information Sheet DRAWING NUMBER INTRODUCTORY INFORMATION Important Notices Underground Plant Protection Information Code Clearances Commercial/Industrial Information Sheet Work Management Customer Projects Engineering

More information

MINIMUM DISTRIBUTION SYSTEM CONCEPTS AND APPLICATIONS. Larry Vogt. Manager, Rates

MINIMUM DISTRIBUTION SYSTEM CONCEPTS AND APPLICATIONS. Larry Vogt. Manager, Rates MINIMUM DISTRIBUTION SYSTEM CONCEPTS AND APPLICATIONS Larry Vogt Manager, Rates Minimum Distribution System What is MDS? MDS is an analysis module of the cost-of-service study in which distribution investment

More information

WPS SERVICE MANUAL. Section Amp and Smaller - Common

WPS SERVICE MANUAL. Section Amp and Smaller - Common Revised 01/2017 Section 2 200 AMP AND SMALLER - COMMON Page 1 of 17 Section 2 200 Amp and Smaller - Common 2-0 General Metering Requirements... 2 2-1 Basic Calculations... 4 2-2 100-200 Amp Single-Phase

More information

Customer Requirements Downtown Secondary Network Service

Customer Requirements Downtown Secondary Network Service Application This standard describes the limitations and requirements for receiving service from the Tacoma Power secondary network system within the City of Tacoma downtown core area. In This Standard

More information

LIFT STATION 11 ONE-LINE DIAGRAM

LIFT STATION 11 ONE-LINE DIAGRAM LAC JOB : 118-086 OSG-D-ELEC06.DWG LIFT STATION 11 ONE-LINE DIAGRAM DWG : SHEET : E15 33 47 NEW NEW GENERATOR PAD BOLLARD BOLLARD WETWELL ACCESS HATCH WETWELL OUTLINE HANDHOLE SEWER MANHOLE LIFT STATION

More information

Lighthouse Power Pedestals,

Lighthouse Power Pedestals, Lighthouse Power Pedestal One of our most popular units, the all-purpose Lighthouse pedestal has a wide range of features. With units in service around the world, this stylish power pedestal is recognized

More information

Switchgear Skid, C1192

Switchgear Skid, C1192 CUSTOM SOLUTIONS 15kV Modular Stairs stored on floor in front of battery bay Ground grid stored on front tongue of trailer Stairs deployed for unit access Storage box for fencing materials and other parts

More information

Have You Been Grounded Lately

Have You Been Grounded Lately Have You Been Grounded Lately Thurs, Oct. 26, 2017 9:15-10:15 Phil Simmons Author, Electrical Grounding and Bonding Author Cengage Learning Phil Simmons Have You Been Grounded Lately 2017 NEC Changes Relative

More information

SOLAR PHOTOVOLTAIC SYSTEMS INSPECTOR CHECKLIST

SOLAR PHOTOVOLTAIC SYSTEMS INSPECTOR CHECKLIST SOLAR PHOTOVOLTAIC SYSTEMS INSPECTOR CHECKLIST The following checklist is an outline of the general requirements found in the 1999 National Electrical Code (NEC) Article 690 for Photovoltaic (PV) Power

More information

Item Code Description Unit Qty Total

Item Code Description Unit Qty Total UNDP ELECTRICITY SECTOR NORTHERN GOVERNORATES Phase XI Item Code Description Unit Qty Total 04-02-00001 Service Pole - 6m, 75mm dia GS Pipe 11250 04-02-00002 9m Tubular Steel Poles complete with all Accessories

More information

Cable Connectors & Conduit Sealing Bushings

Cable Connectors & Conduit Sealing Bushings RA1 Cable Terminators General Information Purpose: Cable Terminators and Sealing Fittings are used on conduit ends and cable ends to effectively seal the cable and conduit. Where Installed: Wherever the

More information

ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position

ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position LET S BE PACIFIC November 0 Volume Number 5 ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position Federal Pacific has the capability to engineer, fabricate and assemble

More information

TEMPORARY ELECTRICAL SERVICE

TEMPORARY ELECTRICAL SERVICE ENERGY SERVICES ENGINEERING 840 Northgate Drive Telephone (509) 942-7403 Fax (509) 942-7405 P.O. Box 190 Richland, WA 99352 www.ci.richland.wa.us/energyservices TEMPORARY ELECTRICAL SERVICE A. INTRODUCTION

More information

Liquid Tight. Liquid Tight Connectors Reusable Fittings. Straight Connectors. Straight Connectors with Insulated Throat

Liquid Tight. Liquid Tight Connectors Reusable Fittings. Straight Connectors. Straight Connectors with Insulated Throat Liquid Tight Connectors Reusable Fittings Industrial specification grade, screw machined steel, zinc plated UL Rated Liquid Tight Includes sealing washer Bonds conduit to box or enclosure Corrosion resistant

More information

The Green Meter Adapter (GMA) program will become effective on January 15, Customers may start applying for a GMA on January 15, 2018.

The Green Meter Adapter (GMA) program will become effective on January 15, Customers may start applying for a GMA on January 15, 2018. SUMMARY This bulletin introduces a new PG&E program that allows the installation of an electric meter socket adapter that will accept a wired connection directly from a residential customer s Photo Voltaic

More information

Metering and Control Standards OFF-PEAK & DUAL FUEL WIRING DIAGRAMS

Metering and Control Standards OFF-PEAK & DUAL FUEL WIRING DIAGRAMS Metering and Control Standards OFF-PEAK & DUAL FUEL WIRING DIAGRAMS REVISED FEBRUARY 2017 TABLE OF CONTENTS Metering Equipment & Installation Standards... 1 Metering Equipment & Installation Standards

More information