1 SUBCOURSE EN5141 EDITION B US ARMY ENGINEER SCHOOL INSTALL SERVICE- ENTRANCE SYSTEMS

2 INSTALL SERVICE- ENTRANCE SYSTEMS Subcourse Number EN5141 EDITION B United States Army Engineer School Fort Leonard Wood, Missouri Credit Hours Edition Date: June 1999 SUBCOURSE OVERVIEW This subcourse is part of Soldier Training Publication (STP) 5-51R12-SM-TG, Install Service Entrance Systems. It is designed to teach the knowledge and skills necessary to perform tasks related to installing service-entrance (SE) systems. The subcourse is presented in two lessons, each corresponding to a terminal learning objective as indicated below. There are no prerequisites for this subcourse. This subcourse reflects the doctrine which was current at the time the subcourse was prepared. In your own work situation, always refer to the latest official publications. Unless otherwise stated, the masculine gender of singular pronouns is used to refer to both men and women. TERMINAL LEARNING OBJECTIVE ACTION: CONDITION: You will learn the procedures used to install SE systems. You will be given the material in this subcourse and an Army Correspondence Course Program (ACCP) examination response sheet. STANDARD: To demonstrate competency of this task, you must achieve a minimum of 70 percent on this subcourse. i EN5141

3 TABLE OF CONTENTS Section Page Subcourse Overview...i Administrative Instructions...iii Grading and Certification Instructions...iii Lesson 1: Overhead Entrance Systems Practice Exercise Answer Key and Feedback Lesson 2: Underground Service Practice Exercise Answer Key and Feedback Examination...E -1 Appendix A: List of Common Acronyms... A-1 Appendix B: Recommended Reading List...B-1 Student Inquiry Sheets ii EN5141

4 LESSON 1 OVERHEAD ENTRANCE SYSTEMS Critical Task: OVERVIEW LESSON DESCRIPTION: In this lesson you will learn to describe an overhead entrance system. TERMINAL LEARNING OBJECTIVE: ACTION: CONDITION: STANDARDS: REFERENCES: You will learn the procedures used to install an overhead entrance system. You will be given subcourse booklet EN5141 and an ACCP examination response sheet. You will work at your own pace and in your own selected environment with no supervision. You will correctly answer practice exercise questions at the end of this lesson. The material contained in this lesson was derived from STP 5-51R12-SM-TG and FM INTRODUCTION Overhead entrance systems are the conductors and the equipment used for the control and protection of electrical circuits, equipment, and personnel. The SE is the end of the interior electrical system. This lesson will teach you how to describe an overhead entrance system. The conductors from the power pole to the building are called service drops as shown in Figure 1-1, page 1-2. The minimum height of a service drop above the ground and on the building is determined by its location. 1-1 EN5141

5 Figure 1-1. Clearances for a service drop Above foot-traffic areas, 10 feet of vertical clearance is necessary for service drops supported and wrapped on a ground messenger having 150 volts to ground between the current-carrying conductors (Figure 1-2). Remember, the 10-foot minimum clearance is measured from the lowest point of the SE cable. Figure 1-2. Service drop above a foot-traffic area 1-2 EN5141

6 Above residential property, driveways, and areas not subject to truck traffic, 12 feet of vertical clearance is maintained for conductors having 300 volts to ground (Figure 1-3). Figure 1-3. Service drop above residential property not subject to truck traffic (300 volts to ground) Above residential property, driveways, and commercial property not subject to truck traffic, 15 feet of vertical clearance is maintained for conductors having 600 volts to ground (Figure 1-4). Automobiles and small vehicles can clear an SE cable with a minimum clearance of 15 feet to ground. Figure 1-4. Service drop above residential property not subject to truck traffic (600 volts to ground) 1-3 EN5141

7 Above public streets and parking areas subject to truck traffic, 18 feet of vertical clearance is required in Figure 1-5. A 20-foot-high load did not clear the service drop. Figure 1-5. A high load damaging a service drop Above a peaked roof, having a 1:3 pitch or more, an 18-inch vertical clearance is necessary when the voltage between conductors is less than 300 volts and the SE is a mast within 48 inches of the roofs edge (Figure 1-6). Figure 1-6. Clearance between the roof and the service drop (300 volts) 1-4 EN5141

8 Conductors that carry more than 300 volts require an 8-foot vertical clearance (Figure 1-7). Figure 1-7. Clearance between the roof and the service drop (300 volts) Conductors that are installed at the side of a window or below it must have a 3-foot clearance (Figure 1-8). Figure 1-8. Conductor clearance from windows 1-5 EN5141

9 For fire escapes, porches, or platforms, conductors must have 3 feet of horizontal clearance from the object and 10 feet of vertical clearance from the ground (Figures 1-9 and 1-10). Figure 1-9. Fire escape/platform clearance Figure Clearance above ground level 1-6 EN5141

10 SE Requirements: Attachment of Service Drops Use back supports in walls that are not strong enough to support a service drop in adverse conditions (wind, snow, or ice) (Figure 1-11). A 2-inch by 4-foot back support gives added strength to the wall. Figure Back support installed in wall A single-cable system supports hot conductors and is hooked to the feed-through dead end (Figure 1-12). The cable that supports the service-drop conductors is clamped by the feed-through clamp and coupled to the ground conductors. The cable support is part of the ground system. Figure Grounded messenger cable providing support 1-7 EN5141

11 The bare neutral conductor is used as the messenger cable (Figure 1-13). By wrapping the hot conductors around the messenger cable, all the weight of the service drop is on the uninsulated neutral/messenger cable. Figure Hot conductors wrapped around a neutral/messenger cable. In a typical service-drop cable, the neutral conductor is used to attach the cable to the dead end (Figure 1-14). The feed-through clamp is built so that the pull of the conductors makes the clamp tighter on the neutral/messenger cable. Figure Feed-through clamp attached to the service spool 1-8 EN5141

12 Service drops are also dead-ended to a building by using secondary racks (Figure 1-15). When heavy service drops are installed on buildings, use secondary racks. Figure Service drop attached to a secondary rack When individual conductors are installed, many of the installations are dead-ended by using service spools made of porcelain (Figure 1-16). One service spool is screwed or bolted to the wall. Figure Service drop attached to service spools 1-9 EN5141

13 Service masts can dead-end individual conductors and an insulator bracket is used for this purpose (Figure 1-17). An insulator bracket can also be used when service conductors are wrapped around a messenger cable but feed-through clamp will be required. Figure Use of insulator brackets 1-10 EN5141

14 Most service masts use a single, dead-end bracket and a service cable (Figure 1-18). This makes a neat installation. Although time-consuming to install, a service mast is the best method for service installation. Figure Insulator bracket with feed-through clamp SE Requirements: Installation Procedures SE cable (Figure 1-19) has a flame-retardant, moisture-resistant covering. The neutral conductor (copper or aluminum) is twisted into a pigtail so that it can be clamped into the grounding system. Figure SE cable 1-11 EN5141

15 SE cable must be supported within 12 inches of the service head and all boxes, and then supported every 4 1/2 feet thereafter. When a service head is unavailable an expedient service head can be made. The SE cable is bent into a gooseneck and secured with tape (Figure 1-20). Service heads are located above the service drop to prevent water from entering the cable run. Figure Expedient head When installed as a service mast, an SE using rigid conduit provides protection for the conductors and a strong contact point for the service drop. A service-mast system is used when greater overhead roof clearance is needed (Figure 1-21). Figure Service mast using rigid conduct 1-12 EN5141

16 To provide adequate strength of the service mast, supports must be attached to the structure at critical points. A typical arrangement for supports is shown in Figure Figure Mast supports 1-13 EN5141

17 The conductors are pulled through the rigid conduit to provide total protection of the SE from the service head into the power panel (Figure 1-23). A well-built service mast will hold up under all types of weather. Figure Service mast Power-panel (Figure 1-24) and service-drop amperages must match. A smaller amperage power panel cannot be used as a main disconnect for a larger amperage service drop. A 210-ampere cable must be used to feed a 200-ampere power panel. Figure Power panel 1-14 EN5141

18 Conductors carrying current within a building are disconnected at the main power panel (Figure 1-25). When the main switch or circuit breaker is in the OFF position, all branch circuits will be disconnected. Figure Main switch inside a power panel A building can have no more than six switches or circuit breakers mounted in a single enclosure that disconnects all power from the building (Figure 1-26). In an emergency situation, all power from this service to the building can be disconnected by using no more than six operations of the hand. When a main switch (breaker) is provided inside the same panel, 42 branch circuit breakers can be installed. Figure Switches in a power panel 1-15 EN5141

19 Two- or three-pole breakers that can be joined together with a tie handle or a master handle can be counted as a single switch if all conductors are disconnected with a single pull or push of a set of switches. By adding tie handles, the power panel in Figure 1-27 follows the six-switch-maximum NEC rule. Label each breaker to indicate the load serviced. Figure Breakers joined with a tie handle The NEC contains important exceptions to the maximum-switch rule (Figure 1-28). The rule can be exceeded for a fire pump or an emergency service such as a hospital, but the switch should be located away from the other disconnects and the power panel should be labeled. Figure Labeled power panel 1-16 EN5141

20 The code also states that up to 42 overcurrent devices can be put into one panel; however, the power must be disconnected from all circuits with six hand operations. For the 42-device role, a two-pole circuit breaker is counted as two circuit breakers (Figure 1-29). One main disconnect removes the power from all circuits in 'this panel. Not counting the main, there are ten circuit breakers in this panel and four of them are tied together. Figure overcurrent devices in a power panel No circuit should be loaded greater than 80 percent of the breakers amperage capacity. In Figure 1-30, the breaker is rated at 20 amperes. Therefore, the ampere load to be applied cannot be greater than 16 amperes. Each heater uses 8 amperes. This circuit has the maximum allowable load. Figure Maximum ampere load 1-17 EN5141

21 Power panels must be accessible. This is accomplished by mounting the panel so that the top of the panel is no higher than 6 1/2 feet and the middle no lower than 4 12 feet (see Figure 1-31). Figure Panel mounting location 1-18 EN5141

22 THIS PAGE IS INTENTIONALLY LEFT BLANK EN5141

23 LESSON 1 PRACTICE EXERCISE The following items will test your grasp of the material covered in this lesson. There is only one correct answer for each item. When you complete the exercise, check your answer with the answer key that follows. If you answer any item incorrectly, study again that part of the lesson which contains the portion involved. 1. A service drop, limited to 300 volts to ground, is run over a sidewalk and goes to a house. What is the minimum distance, in feet, from the finished grade up to the lowest point of the SE drop? A. 10 B. 12 C. 14 D When a service drop is run over a public street that is not subject to truck traffic, what is the minimum distance, in feet, between the conductors and the finished surface? A. 9 B. 12 C. 15 D When the voltage exceeds 300 volts to ground, what is the minimum distance, in feet, from the roof to the service conductors? A. 2 B. 4 C. 6 D When installing a service drop beside a window, what is the minimum distance, in feet, from the side of the window to the point of attachment of the service drop? A. 2 B. 3 C. 6 D EN5141

24 5. How many feet can a service drop be mounted from the side of a porch? A. 2 B. 3 C. 6 D In which of the following situations can the maximum-switch rule be exceeded? A. Outside lighting B. Elevator C. Fire pump D. Telephone power 7. When installing a service drop using a feed-through dead end, the grounding conductor must be insulated from the cable support. A. True B. False 8. A service mast is not a good SE installation. A. True B. False 9. When installing a service, the SE cable can be rated at a lower amperage than the power panel. A. True B. False 1-21 EN5141

25 LESSON 1 PRACTICE EXERCISE ANSWER KEY AND FEEDBACK Item Correct Answer and Feedback 1. B. 12 Above residential property (page 1-3) 2. C. 15 An automobile can clear (page 1-3) 3. D. 8 Conductors that carry (page 1-5) 4. B. 3 conductors must have (page 1-6) 5. B. 3 For fire escapes, porches, or (page 1-6) 6. C. Fire Pumps The rule can be exceeded (page 1-16) 7. B. False A single cable system (page 1-16) 8. B. False Most service masts use (page 1-11) 9. B. False A 210-ampere cable must (page 1-14) 1-22 EN5141

26 LESSON 2 UNDERGROUND SERVICES Critical Task: OVERVIEW LESSON DESCRIPTION: In this lesson you will learn to describe an underground electrical service. TERMINAL LEARNING OBJECTIVE: ACTION: CONDITION: STANDARD: REFERENCES: You will learn the procedures used to install an underground electrical service. You will be given subcourse booklet EN5102 and an ACCP examination response sheet. You will work at your own pace and in your own selected environment with no supervision. You will correctly answer practice exercise questions at the end of this lesson. The material contained in this lesson was derived from STP 5-51R12-SM-TG and FM INTRODUCTION Underground electrical services are not subject to as much mechanical damage from equipment, personnel, and weather as overhead systems. Cable can be buried in the ground or pulled through conduit systems. To avoid a drop in voltage, underground systems usually run no more than 360 feet after the last transformer in the system. The underground service uses sizes of No. 8 copper or No. 6 aluminum conductors. This lesson will teach you how to describe an underground electrical service. The ground-cover requirements for underground conductors or conduit vary according to the site. In nontraffic areas, SE cable should be buried at least 18 inches and covered with a 2-inch-thick concrete pad (Figure 2-1). If rigid or intermediate conduit is installed, the depth can be reduced to 6 inches. 2-1 EN5141

27 Figure 2-1. Buried SE cable (nontraffic area) When SE cable is subject to vehicle traffic, at least 24 inches of ground cover is required (Figure 2-2). The 24-inch-depth requirement will allow the service to withstand the weight of vehicles passing over it. The depth requirement is the same when conduit is used. Figure 2-2. Buried SE cable (traffic area) 2-2 EN5141

28 SE cable buried in solid-rock areas can be installed down to the surface of the rock if the cable is covered with at least 2 inches of concrete that extends to the rock surface (Figure 2-3). The same requirement exists for conduit. Figure 2-3. Buried cable in solid rock area Conductors coming out of the ground should be protected by enclosures, raceways, or conduit from below grade to 8 feet above the ground (Figure 2-4). Figure 2-4. Conductor protection When backfilling a trench where there are cables or conductors, do not backfill with- Large rocks. Paving materials. Cinders. Sharp substances. Corrosive materials. 2-3 EN5141

29 Placement of SEs. Underground services can be installed using either underground service entrance (USE) cable, direct-burial conductors, or conduit (Figure 2-5). Conductors should not be spliced unless they are placed in a properly installed splice box. Figure 2-5. Types of installation When direct-burial conductors or USE cables are above grade they must be protected in the plastic or metallic conduit at both ends (Figure 2-6). Figure 2-6. Protection at ends of SE cable 2-4 EN5141

30 The installation of a USE to the power panel varies according to the site and the equipment. (Figure 2-7) shows a typical setup that is subject to change to fit the installation. NOTE: surface. A 1/4-inch air space is required when mounting a power panel to a damp wall or Figure 2-7. Typical USE power-panel setup 2-5 EN5141

31 LESSON 2 PRACTICE EXERCISE The following items will test your grasp of the material covered in this lesson. There is only one correct answer for each item. When you complete the exercise, check your answer with the answer key that follows. If you answer any item incorrectly, study again that part of the lesson which contains the portion involved. 1. When using SE cable in nontraffic areas, what is the minimum depth, in inches, for a service having a 2-inch-thick concrete pad over its length? A. 2 B. 6 C. 18 D How deep, in inches, should a service subject to vehicle traffic be buried? A. 2 B. 6 C. 12 D When cable is installed in solid-rock areas, how many inches thick is the concrete pad covering the cable? A. 2 B. 6 C. 12 D How many feet above finished grade should USE cable be protected? A. 6 B. 8 C. 10 D Which of the following materials can be used to backfill a cable trench? A. Sand B. Large rocks C. Cinders D. Paving materials 2-6 EN5141

32 6. A direct-burial conductor can be spliced anywhere along its length if plastic, self-sealing tape is used to replace the insulation. A. True B. False 7. Rigid conduit cannot be used for underground services. A. True B. False 2-7 EN5141

33 LESSON 2 PRACTICE EXERCISE ANSWER KEY AND FEEDBACK Item Correct Answer and Feedback 1. C. 18 In nontraffic areas SE (page 2-2) 2. D. 24 When SE cable (page 2-2) 3. A. 2 SE cable buried in solid rock (page 2-3) 4. B. 8 Conductors coming out of the ground (page 2-3) 5. A. Sand When backfilling (page 2-3) 6. B. False Protection of SE (page 2-4) 7. B. False Placement of SE (page 2-4) 2-8 EN5141

EN5144 US ARMY ENGINEER SCHOOL INSTALL SYSTEM, EQUIPMENT AND COMPONENT GROUNDS

EN5144 US ARMY ENGINEER SCHOOL INSTALL SYSTEM, EQUIPMENT AND COMPONENT GROUNDS SUBCOURSE EN5144 EDITION B US ARMY ENGINEER SCHOOL INSTALL SYSTEM, EQUIPMENT AND COMPONENT GROUNDS INSTALL SYSTEM, EQUIPMENT, AND COMPONENT GROUNDS Subcourse Number EN 5144 EDITION B United States Army

More information

INSTALL CIRCUIT PROTECTIVE DEVICES

INSTALL CIRCUIT PROTECTIVE DEVICES SUBCOURSE EN5146 EDITION B US ARMY ENGINEER CENTER AND SCHOOL INSTALL CIRCUIT PROTECTIVE DEVICES INSTALL CIRCUIT PROTECTIVE DEVICES Subcourse Number EN5146 EDITION B United States Army Engineer School

More information

SINGLE PHASE WIRING SPECIFICATIONS

SINGLE PHASE WIRING SPECIFICATIONS SINGLE PHASE WIRING SPECIFICATIONS 1-866-MEC-ELEC (1-866-632-3532) Office Locations: Hondo Office 237 Hwy 173 N Hondo, TX 78661-0370 Fax 830.426.3335 Dilley Office 1718 W. FM 117 Dilley, TX 78017 Fax 830.965.1425

More information

THREE PHASE WIRING SPECIFICATIONS

THREE PHASE WIRING SPECIFICATIONS THREE PHASE WIRING SPECIFICATIONS 1-866-MEC-ELEC (1-866-632-3532) Office Locations: Hondo Office 237 Hwy 173 N Hondo, TX 78661-0370 Fax 830.426.3335 Dilley Office 1718 W. FM 117 Dilley, TX 78017 Fax 830.965.1425

More information

D9-3. No. WIRING DIAGRAM CONNECTIONS FOR UNDERGROUND SELF CONTAINED METERS JRH JED krich95 LINE LINE ABCN SOURCE SOURCE GROUND GROUND STUD STUD SOURCE

D9-3. No. WIRING DIAGRAM CONNECTIONS FOR UNDERGROUND SELF CONTAINED METERS JRH JED krich95 LINE LINE ABCN SOURCE SOURCE GROUND GROUND STUD STUD SOURCE SOURCE 20V 240V STUD (PER NEC) A customer supplied and installed teaser wire is required from the neutral lug to a 5th terminal mounted on the left side of the meter block between the line and load terminals.

More information

CHAPTER V RESIDENTIAL WIRING

CHAPTER V RESIDENTIAL WIRING CHAPTER V RESIDENTIAL WIRING 5.1. THE SERVICE ENTRANCE Buildings and other structures receive the electrical energy through the service entrance. In residential wiring, the electric company supply this

More information

Pentahead bolts See note 2. Conduit run as specified. Company facility. Refer to drawing SS8.6-2 or SS8.6-3 STANDARD SERVICE INSTALLATION

Pentahead bolts See note 2. Conduit run as specified. Company facility. Refer to drawing SS8.6-2 or SS8.6-3 STANDARD SERVICE INSTALLATION PULL BOX F SECONDARY SYSTEM Typical grade Pentahead bolts See note 2 Conduit run as specified Plastic or fiberglass for grass areas or Polymer concrete for light duty areas (see notes 2, 3, & 4) Company

More information

OVERHEAD SERVICE. Items to consider

OVERHEAD SERVICE. Items to consider OVERHEAD SERVICE Items to consider The maximum length of the service wire from the ComEd pole to the point of attachment on your residence is 150 feet, if practical. Your service wire installation must

More information

ENTRANCE EQUIPMENT ER D PAGE 1 OF 5

ENTRANCE EQUIPMENT ER D PAGE 1 OF 5 PAGE 1 OF 5 USE: Requirements for entrance equipment. PREVIOUS REVISION 07-01-98 ORIGINATED 03-94 PREVIOUS NUMBER ER 100 (12-01-81) LATEST REVISION: Updated meter socket labeling specification and instrument

More information

Pretest Module 24 Three-phase Service Entrance

Pretest Module 24 Three-phase Service Entrance Pretest Module 24 Three-phase Service Entrance 1. What is the most widely used three-phase service entrance system? 2. What are the three most common voltage combinations for three-phase, four-wire systems?

More information

IT 0335 US ARMY INTELLIGENCE CENTER INTRODUCTION TO CELLS AND BATTERIES

IT 0335 US ARMY INTELLIGENCE CENTER INTRODUCTION TO CELLS AND BATTERIES SUBCOURSE IT 0335 EDITION B US ARMY INTELLIGENCE CENTER INTRODUCTION TO CELLS AND BATTERIES INTRODUCTION TO CELLS AND BATTERIES Subcourse Number IT0335 EDITION B US ARMY INTELLIGENCE CENTER FORT HUACHUCA,

More information

IT 0335 US ARMY INTELLIGENCE CENTER INTRODUCTION TO CELLS AND BATTERIES

IT 0335 US ARMY INTELLIGENCE CENTER INTRODUCTION TO CELLS AND BATTERIES SUBCOURSE IT 0335 EDITION B US ARMY INTELLIGENCE CENTER INTRODUCTION TO CELLS AND BATTERIES INTRODUCTION TO CELLS AND BATTERIES Subcourse Number IT0335 EDITION B US ARMY INTELLIGENCE CENTER FORT HUACHUCA,

More information

SECTION 300 OVERHEAD SERVICE

SECTION 300 OVERHEAD SERVICE SECTION 300 OVERHEAD SERVICE 300.01 General Company provides, installs, and maintains service drop to point of delivery approved by Company. Customer provides point of attachment which is acceptable to

More information

Engineering Service Specifications. Commercial Single-Phase Current Transformer Metering Schemes

Engineering Service Specifications. Commercial Single-Phase Current Transformer Metering Schemes Engineering Service Specifications Commercial Single-Phase Current Transformer Metering Schemes Specifications for Commercial Underground Current Transformer Metering Requirements for a Single-Phase Customer

More information

AMENDMENT ELECTRIC SERVICE MANUAL 2014

AMENDMENT ELECTRIC SERVICE MANUAL 2014 AMENDMENT (Pages 20,43,50,72,74,,76,78,83,86,99) ELECTRIC SERVICE MANUAL 2014 Effective April 1, 2015 18-7 6.0 SERVICE AND SERVICE ENTRANCES (General), Continued Conductor Sizing It is recommended that

More information

SOUTHWEST LOUISIANA ELECTRIC MEMBERSHIP COORPORATION COMMERCIAL SERVICE REQUIREMENTS

SOUTHWEST LOUISIANA ELECTRIC MEMBERSHIP COORPORATION COMMERCIAL SERVICE REQUIREMENTS SOUTHWEST LOUISIANA ELECTRIC MEMBERSHIP COORPORATION COMMERCIAL SERVICE REQUIREMENTS November 17, 2016 Engineering Service Specifications Table of Contents Commercial Service Requirements SLEMCO Commercial

More information

9. Non-Residential Services (Commercial, Industrial, and Agricultural)

9. Non-Residential Services (Commercial, Industrial, and Agricultural) Section 9 2016 Electric Service Requirements, 3rd Edition Section 9 Non-Residential Services Directory Page 9.1 General Requirements 68 9.2 Direct-Connect Metering, Single Installations 69 9.3 Direct-Connect

More information

SERVICE ATTACHMENT ON A BUILDING WITH BUS DUCT SERVICE ENTRANCE AND INDOOR METERING

SERVICE ATTACHMENT ON A BUILDING WITH BUS DUCT SERVICE ENTRANCE AND INDOOR METERING SERVICE ATTACHMENT ON A BUILDING WITH BUS DUCT SERVICE ENTRANCE AND INDOOR METERING Obtain acceptance and specific details from the local Company office. 1. Service entrance duct (see Note 1). Company

More information

RESIDENTIAL SUBDIVISION SERVICE REQUIREMENTS SECTION VI RESIDENTIAL SUBDIVISION SERVICE REQUIREMENTS

RESIDENTIAL SUBDIVISION SERVICE REQUIREMENTS SECTION VI RESIDENTIAL SUBDIVISION SERVICE REQUIREMENTS SECTION VI SERVICE REQUIREMENTS This section discusses the requirements for establishing electric service to new residential subdivisions in Palo Alto. Subdivisions are normally constructed on dedicated

More information

7. Residential Single-Family and Duplex Buildings (Dwellings)

7. Residential Single-Family and Duplex Buildings (Dwellings) Sin g le -F a mily a n d Du p le x Bu ild in g s 2016 Electric Service Requirements, 2 nd Edition Section 7 Section 7 Residential Single-Family and Duplex Buildings (Dwellings) Directory Page 7.1 General

More information

UNDERGROUND SERVICE ENTRANCE LOCATION. No meter base or entrance should be installed before an KREMC engineer has checked the proposed location.

UNDERGROUND SERVICE ENTRANCE LOCATION. No meter base or entrance should be installed before an KREMC engineer has checked the proposed location. UNDERGROUND SERVICE No meter base or entrance should be installed before an KREMC engineer has checked the proposed location. Entrance cabinet must be directly through wall or directly under meter in basement.

More information

NEC 2011 Code Changes

NEC 2011 Code Changes NEC 2011 Code Changes Articles 280.21-300.50 CHANGES FROM 2008 TO 2011 CODE ARE IN RED Chapter 2 - Wiring and Protection ARTICLE 280 Surge Arresters, Over 1kV III. Connecting Surge Arresters 280.21 Connection

More information

COMMERCIAL QUICK REFERENCE

COMMERCIAL QUICK REFERENCE COMMERCIAL QUICK REFERENCE PROVO CITY POWER STANDARDS ELECTRICAL ENGINEERING UPDATED: 2016 SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTIFICATION. 18" MIN. OF TAIL. (NEUTRAL CONDUCTOR MUST BE WHITE OR

More information

Associated equipment As related to metering equipment: such as the current transformers, CT wiring and test switches.

Associated equipment As related to metering equipment: such as the current transformers, CT wiring and test switches. APPENDIX Glossary Approval Acceptable to the authority having jurisdiction. Assessor s Parcel Number (APN) Identifying number assigned by the county assessor s office to each taxable building lot in the

More information

Clark Public Utilities Commercial Electric Service Handbook. This page left blank intentionally.

Clark Public Utilities Commercial Electric Service Handbook. This page left blank intentionally. This page left blank intentionally. 38 Chapter 4: Commercial Metering / January 2011 APPENDIX Glossary Approval Acceptable to the authority having jurisdiction. Associated equipment As related to metering

More information

7 Single Family Service

7 Single Family Service 7 Single Family Service 7. General The location of the service entrance on the Customer s premises is an important consideration. For clearance and location information see section 5 (Clearances). Consult

More information

ELECTRIC POLICY INTRODUCTION CHAPTER I GENERAL

ELECTRIC POLICY INTRODUCTION CHAPTER I GENERAL INTRODUCTION This policy has been adopted by the Board of Public Works as a guide to obtaining electric service and to set forth the services available, conditions for service, and standards for materials

More information

SECTION 1: Field Inspection Guide for Rooftop Photovoltaic (PV) Systems

SECTION 1: Field Inspection Guide for Rooftop Photovoltaic (PV) Systems COUNTY OF SANTA CRUZ PLANNING DEPARTMENT 701 OCEAN STREET, 4 th FLOOR, SANTA CRUZ, CA 95060 (831) 454-2580 FAX: (831) 454-2131 TDD: (831) 454-2123 KATHLEEN MOLLOY PREVISICH, PLANNING DIRECTOR Photovoltaic

More information

For Conduit Inspections

For Conduit Inspections Underground Conduit Standards - Table of Content 5/8/2017 Section S22 Underground Conduit Standard Index: Description: 00 Table of Content 01 General Notes 02 Definition of Terms 03 Primary Riser Conduit

More information

Mecklenburg County Common Code Defects

Mecklenburg County Common Code Defects Electrical Code Defects Improper Over Current Protection Code Description 310.15 Ampacities for s Rated 0 2000 Volts. (A) General. (1) Tables or Engineering Supervision. Ampacities for conductors shall

More information

UNDERGROUND SERVICE ENTRANCE LOCATION. No meter base or entrance should be installed before an KREMC engineer has checked the proposed location.

UNDERGROUND SERVICE ENTRANCE LOCATION. No meter base or entrance should be installed before an KREMC engineer has checked the proposed location. UNDERGROUND SERVICE No meter base or entrance should be installed before an KREMC engineer has checked the proposed location. Entrance cabinet must be directly through wall or directly under meter in basement.

More information

UNDERGROUND SERVICE. Items to consider. There will be charges from ComEd if you convert from overhead to underground service.

UNDERGROUND SERVICE. Items to consider. There will be charges from ComEd if you convert from overhead to underground service. UNDERGROUND SERVCE tems to consider f your trenching route has to be dug by hand, or if a cable must be installed under a paved surface, additional charges apply. f your service cable has to be moved later

More information

NEW SERVICE HANDBOOK COMMERCIAL & IRRIGATION SUPPLEMENT

NEW SERVICE HANDBOOK COMMERCIAL & IRRIGATION SUPPLEMENT NEW SERVICE HANDBOOK COMMERCIAL & IRRIGATION SUPPLEMENT Meter Installations There are three basic ways to measure electricity consumption: Small and medium services are metered directly using direct connect

More information

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 03/05/09 TSEWG TP-11: UFC N BEST PRACTICES

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 03/05/09 TSEWG TP-11: UFC N BEST PRACTICES TSEWG TP-11: UFC 3-500-10N BEST PRACTICES UFC 3-500-10N was developed by NAVFAC and was used as the starting point for the tri-services development of UFC 3-500-10, Design: Electrical Engineering. UFC

More information

RESIDENTIAL UNDERGROUND AND OVERHEAD SERVICE REQUIREMENTS SECTION II RESIDENTIAL UNDERGROUND AND OVERHEAD SERVICE REQUIREMENTS

RESIDENTIAL UNDERGROUND AND OVERHEAD SERVICE REQUIREMENTS SECTION II RESIDENTIAL UNDERGROUND AND OVERHEAD SERVICE REQUIREMENTS SECTION II This section discusses the City of Palo Alto's requirements for establishing electric service to new or upgraded residential installations. The same requirements apply to both underground and

More information

Have You Been Grounded Lately

Have You Been Grounded Lately Have You Been Grounded Lately Thurs, Oct. 26, 2017 9:15-10:15 Phil Simmons Author, Electrical Grounding and Bonding Author Cengage Learning Phil Simmons Have You Been Grounded Lately 2017 NEC Changes Relative

More information

SOLAR PHOTOVOLTAIC SYSTEMS INSPECTOR CHECKLIST

SOLAR PHOTOVOLTAIC SYSTEMS INSPECTOR CHECKLIST SOLAR PHOTOVOLTAIC SYSTEMS INSPECTOR CHECKLIST The following checklist is an outline of the general requirements found in the 1999 National Electrical Code (NEC) Article 690 for Photovoltaic (PV) Power

More information

A. Submit manufacturer's literature and technical data before starting work.

A. Submit manufacturer's literature and technical data before starting work. SECTION 16425 SWITCHBOARD PART 1 GENERAL 1.01 SUMMARY A. Related Section: 1. 16450 - Grounding. 1.02 SUBMITTALS A. Submit manufacturer's literature and technical data before starting work. B. Submit Shop

More information

Table of Contents. Electrical Service Requirements. 1. General Requirements

Table of Contents. Electrical Service Requirements. 1. General Requirements Table of Contents 1. General Requirements 1.1 General Definition.................................................... 1 1 1.2 Booklet Purpose and Organization....................................... 1-1

More information

WPS SERVICE MANUAL. Section 7 Clearances. 7-1 Basic Electric Clearances - Services Miscellaneous Clearances Antenna Clearances...

WPS SERVICE MANUAL. Section 7 Clearances. 7-1 Basic Electric Clearances - Services Miscellaneous Clearances Antenna Clearances... Revised 03/2016 Section 7 CLEARANCES Page 1 of 9 Section 7 Clearances 7-1 Basic Electric Clearances - Services... 2 7-2 Miscellaneous Clearances... 7 7-3 Antenna Clearances... 9 Revised 03/2016 Section

More information

Definitions of and have been revised. a. automatic b. nonautomatic c. none of the above d. both a and b

Definitions of and have been revised. a. automatic b. nonautomatic c. none of the above d. both a and b www.garyklinka.com Page 1 of 12 Instructions: Fee $25 1. Print these pages. 2. Circle the correct answers and transfer them to the answer sheet. 3. Page down to the last page for the verification forms

More information

The Reliable Choice. Field Pocket Guide

The Reliable Choice. Field Pocket Guide The Reliable Choice Field Pocket Guide Allowable Ampacities of STABILOY Brand XHHW-2 and Copper 75 C (167 F) 90 C (194 F) 75 C (167 F) 90 C (194 F) Conductor Size (AWG or kcmil) Types RHW, THHW, THW, THWN,

More information

Code Calculations. for an Off-Grid PV System

Code Calculations. for an Off-Grid PV System Code Calculations for an Off-Grid PV System John Wiles Sponsored by the Photovoltaic Systems Assistance Center, Sandia National Laboratories Judy LaPointe s home is on its way to becoming a finished, off-grid

More information

UNDERGROUND SERVICES - SECONDARY

UNDERGROUND SERVICES - SECONDARY UNDERGROUND SERVICES - SECONDARY Contents - Underground Services... U-1 General Requirements for Underground Service...U-2 Names of Parts for Underground Service... U-3 Service Termination in a Service

More information

Circuit Concepts (Residential)

Circuit Concepts (Residential) Youth Explore Trades Skills Circuit Concepts (Residential) Description This Activity Plan will allow students to understand how electrical circuits work in a home. Students will also gain knowledge of

More information

Chapter 8 Interior Wiring and Lighting

Chapter 8 Interior Wiring and Lighting Chapter 8 Interior Wiring and Lighting Review Questions 1. What tool if any, is used to remove a fuse that is to be replaced? 1. Pliers 2. Screwdriver 3. Fuse puller 4. None 2. OSHA has established specific

More information

Spring Test 10 due 05/11/2013

Spring Test 10 due 05/11/2013 Spring Test 10 due 05/11/2013 Multiple Choice Identify the letter of the choice that best completes the statement or answers the question. 1. When installed in an agricultural building that houses livestock

More information

AGRICULTURAL UNDERGROUND SERVICE 500 HP OR LESS

AGRICULTURAL UNDERGROUND SERVICE 500 HP OR LESS Prepared by: ABB1 AGRICULTURAL UNDERGROUND SERVICE 500 HP OR LESS 05619 Asset Type: Electric Metering Function: Design and Construction Issued by: Lisseth Villareal (LDV2) Date: 07-31-15 Rev. #10: This

More information

SPECIFICATIONS FOR RESIDENTIAL CONSTRUCTION

SPECIFICATIONS FOR RESIDENTIAL CONSTRUCTION Roseville Electric SPECIFICATIONS FOR RESIDENTIAL CONSTRUCTION REVISED 04/25/18 Specifications for Residential Construction Revision List REVISION Date Page No. Description 03/20/00 6.1-6.2 Added Armorcast

More information

Approved Contractor Construction e-guide Residential Commercial

Approved Contractor Construction e-guide Residential Commercial Approved Contractor Construction e-guide Residential Commercial Clark Public Utilities PO Box 8900 Vancouver, WA 98668 (PAGE 2) TABLE OF CONTENTS PAGE Trenching 3 Wire 8 Single-Phase Transformer Set 13

More information

TEMPORARY ELECTRIC WIRING FOR CARNIVALS, CONVENTIONS, EXHIBITIONS, FAIRS AND SIMILAR USES

TEMPORARY ELECTRIC WIRING FOR CARNIVALS, CONVENTIONS, EXHIBITIONS, FAIRS AND SIMILAR USES INFORMATION BULLETIN / PUBLIC - ELECTRICAL CODE REFERENCE NO.: LAMC 93.0230 Effective: 3-24-69 DOCUMENT NO. P/EC 2002-006 Revised: 11-17-00 Previously Issued As: RGA #7-69 TEMPORARY ELECTRIC WIRING FOR

More information

Electrical Tech Note 105 Agricultural Engineering Department Michigan State University

Electrical Tech Note 105 Agricultural Engineering Department Michigan State University Electrical Tech Note 105 Agricultural Engineering Department Michigan State University Journey Exam Study Guide and Sample Questions 1 Based on the 2002 NEC, Part 8 of PA 230, and the 2003 MRC The Journey

More information

ELECTRIC SERVICE MANUAL

ELECTRIC SERVICE MANUAL ELECTRIC SERVICE MANUAL Issued: November 2018 For the most current version of the Jo-Carroll Energy electric service manual please visit www.jocarroll.com TABLE OF CONTENTS Chapter 1. General Information...1

More information

320A Single Phase URD Meter Loop Installations

320A Single Phase URD Meter Loop Installations 320A Single Phase URD Meter Loop Installations Location: The meter loop shall be mounted on the side of the pedestal facing the consumer's lot. (The side being one of the four flat surfaces of the pedestal

More information

ELECTRICAL - GENERAL REQUIREMENTS SELF INSPECTION CHECKLIST

ELECTRICAL - GENERAL REQUIREMENTS SELF INSPECTION CHECKLIST Name of School: OPTIONAL INFORMATION Date of Inspection: Vocational Program/Course/Room: Signature of Inspector: ELECTRICAL - GENERAL REQUIREMENTS SELF INSPECTION CHECKLIST Guidelines: This checklist covers

More information

2018 Consultant s Handbook Division 26 Electrical 2413 Switchboards

2018 Consultant s Handbook Division 26 Electrical 2413 Switchboards 1 General 1.1 Switchboards shall be U.L. listed and labeled. 1.2 Each switchboard shall have its own main disconnecting means unless it is located in the same room as its source of origin. In most cases

More information

SALEM CITY POWER ELECTRICAL REQUIREMENTS & STANDARDS MANUAL

SALEM CITY POWER ELECTRICAL REQUIREMENTS & STANDARDS MANUAL SALEM CITY POWER DEPARTMENT TABLE OF CONTENTS Section 1 General Requirements Purpose...1.1 Codes and Ordinances...1.1 Changes or Conflicts in Requirements and Guidelines...1.1 Application for Service...1.2

More information

TEMPORARY ELECTRICAL SERVICE

TEMPORARY ELECTRICAL SERVICE ENERGY SERVICES ENGINEERING 840 Northgate Drive Telephone (509) 942-7403 Fax (509) 942-7405 P.O. Box 190 Richland, WA 99352 www.ci.richland.wa.us/energyservices TEMPORARY ELECTRICAL SERVICE A. INTRODUCTION

More information

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS SECTION 26 28 16 ENCLOSED SWITCHES AND PART 1 - GENERAL 1.1 SUMMARY A. Section includes the following individually mounted, enclosed switches and circuit breakers rated 600V AC and less: 1. Fusible switches.

More information

Installing or Rebuilding Your Electric Service

Installing or Rebuilding Your Electric Service Installing or Rebuilding Your Electric Service 2 3 Contents Policies for New and Rebuilt Electric Service 2-4 Paperwork and fees...2 Five-year policy...3 Proposed route location and conditions...3 Construction

More information

A. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein.

A. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein. 16425 SWITCHBOARD ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 26 24 13 An optional keynote to

More information

WPS SERVICE MANUAL. Section Amp and Smaller - Common

WPS SERVICE MANUAL. Section Amp and Smaller - Common Revised 01/2017 Section 2 200 AMP AND SMALLER - COMMON Page 1 of 17 Section 2 200 Amp and Smaller - Common 2-0 General Metering Requirements... 2 2-1 Basic Calculations... 4 2-2 100-200 Amp Single-Phase

More information

10 Commercial, Industrial, Agricultural Services

10 Commercial, Industrial, Agricultural Services 10 Commercial, Industrial, Agricultural Services This section describes the Power Company requirements for commercial, industrial, and agricultural services. This section covers single phase and three

More information

Section 02: Pre-Installation Procedures

Section 02: Pre-Installation Procedures Section 02: Pre-Installation Procedures Foundation! WARNING The MUST be placed on a surface that will support the combined weight of the, options, fixtures, and tooling, etc. (refer to the Specifications

More information

SPRINGVILLE CITY ELECTRICAL REQUIREMENTS & STANDARDS MANUAL

SPRINGVILLE CITY ELECTRICAL REQUIREMENTS & STANDARDS MANUAL POWER DEPARTMENT EFFECTIVE AS OF FEBRUARY 1, 2008, REVISED JULY 1, 2013 STANDARDS ARE SUBJECT TO REVIEW TABLE OF CONTENTS Section 1 General Requirements Purpose...1.1 Codes and Ordinances...1.1 Changes

More information

Fee $20 Course: NEC Changes 1 This course is valid for these credentials: Credential Description Cred Code Credit Hours

Fee $20 Course: NEC Changes 1 This course is valid for these credentials: Credential Description Cred Code Credit Hours www.garyklinka.com Page 1 of 18 Instructions: Fee $20 1. Print these pages. 2. Circle the correct answers and transfer them to the answer sheet. 3. Page down to the last page for the verification forms

More information

Service Requirements

Service Requirements Service Requirements General Contact Idaho Power before beginning work on any new service. All meter installations must meet current electrical code requirements and display the proper electrical permit.

More information

Service Installation

Service Installation Service Installation S T U D E N T M A N U A L March 31, 2005 2 STUDENT TRAINING MANUAL Prerequisites: None Objectives: Given the Construction Standards Manual, you will be able to explain and/or demonstrate

More information

Published 2018 RULES AND REGULATIONS FOR ELECTRIC SERVICE

Published 2018 RULES AND REGULATIONS FOR ELECTRIC SERVICE Published 2018 RULES AND REGULATIONS FOR ELECTRIC SERVICE TABLE OF CONTENTS Page No. SECTION I INTRODUCTION 1 A. PURPOSE 1 B. SCOPE 1 C. CORPORATION 1 D. CODES 1 E. RESPONSIBILITY 1 F. INSPECTION 2 G.

More information

WIRING DESIGN & PROTECTION REQUIREMENTS CHECKLIST

WIRING DESIGN & PROTECTION REQUIREMENTS CHECKLIST WIRING DESIGN & PROTECTION REQUIREMENTS CHECKLIST Use & Identification of Grounded and Grounding Conductors YES NO N/A Grounded conductors are identifiable and distinguishable from all other conductors.

More information

Section 6 Electric Metering: Residential

Section 6 Electric Metering: Residential Section 6 Electric Metering: Residential 6.1. Scope This section provides specific information for residential metering that is not covered by the basic requirements in Section 5, Electric Metering: General.

More information

Electric & Gas Service Requirements (Greenbook) Overview

Electric & Gas Service Requirements (Greenbook) Overview INTRODUCTION The Greenbook contents and standard documents are updated regularly to provide users with the most current information possible. In conjunction with this effort, the 2016 Greenbook was reviewed

More information

Volume 2 Charts, Formulas, and Other Useful Information

Volume 2 Charts, Formulas, and Other Useful Information Volume 2 Charts, Formulas, and Other Useful Information Aluminum Conductor Conductor Terminations 61 Compact Aluminum (Conduit Fill Tables) 68-79 Ampacity Dwelling Services 48 1-phase Loads on a 3-phase

More information

ELECTRIC SERVICE RULES UTILITY/CATV SERVICES Issued Jan 2016

ELECTRIC SERVICE RULES UTILITY/CATV SERVICES Issued Jan 2016 UTILITY/CATV SERVICES CHAPTER 9 900. GENERAL A. Alliant Energy receives many requests for electric service from other utilities; telephone, telecommunications companies, cable television, the Department

More information

JACKSON ENERGY AUTHORITY ELECTRIC SERVICE POLICY EFFECTIVE SEPTEMBER 26 th, 2005 *REVISED JULY 12 th, 2017

JACKSON ENERGY AUTHORITY ELECTRIC SERVICE POLICY EFFECTIVE SEPTEMBER 26 th, 2005 *REVISED JULY 12 th, 2017 JACKSON ENERGY AUTHORITY ELECTRIC SERVICE POLICY EFFECTIVE SEPTEMBER 26 th, 2005 *REVISED JULY 12 th, 2017 JEA SHALL MAKE ALL METER SPOTS BEFORE ELECTRICAL WORK BEGINS AS TO DETERMINE THE POINT OF ATTACHMENT

More information

Design Standard. Purpose: Design Standard:

Design Standard. Purpose: Design Standard: Design Standard Purpose: This design standard has the purpose of creating a consistent application of motor-control centers throughout the East Side Union High School District, therefore achieving a standard

More information

Indianapolis Power & Light Company

Indianapolis Power & Light Company Indianapolis Power & Light Company Electric Service and Meter Manual The Electric Service & Meter Manual is not copyrighted and permission is hereby given to reproduce this document. However, the Indianapolis

More information

Electrical. Earthing & Bonding. Installation Techniques. Learning Notes MODULE 2.2 UNIT PHASE:2

Electrical. Earthing & Bonding. Installation Techniques. Learning Notes MODULE 2.2 UNIT PHASE:2 Electrical Learning Notes MODULE 2.2 UNIT 2.2.6 Installation Techniques Earthing & Bonding PHASE:2 Table of Contents INTRODUCTION... 3 DEFINITIONS... 4 EARTHING... 5 TYPES OF SYSTEM EARTHING... 10 EQUIPOTENTIAL

More information

Surface Regulations and Policies

Surface Regulations and Policies Surface Regulations and Policies COAL FATALITIES 1970-2002 350 300 250 200 150 100 50 0 1970 1973 1976 1979 1982 1985 1988 1991 1994 1997 2000 From January 1, 1970 through today, a total of 240 coal miners

More information

Sentinel Field Satellite Controller Metal Pedestal, Plastic Pedestal and Wall Mount Models Installation Instructions

Sentinel Field Satellite Controller Metal Pedestal, Plastic Pedestal and Wall Mount Models Installation Instructions WARNING HIGH VOLTAGE 115V 4 M AP Sentinel Field Satellite Controller Metal Pedestal, Plastic Pedestal and Wall Mount Models Installation Instructions Important: For your protection and the safety of the

More information

Electrical Equipment and Terminology

Electrical Equipment and Terminology Youth Explore Trades Skills Description Understanding the language of the electrical trade and knowing what electrical equipment is named and its purpose are very important. Anyone who is exposed to a

More information

2. DEFINITIONS. 2.3 APPROVED Acceptable to the authority enforcing the National Electric Code

2. DEFINITIONS. 2.3 APPROVED Acceptable to the authority enforcing the National Electric Code 2. DEFINITIONS 2.1 ACCEPTABLE Acceptable to the Company. 2.2 ADVANCED METER A meter that is capable of remote reading, and is capable of storing electric consumption data at specified time intervals of

More information

grounded in service wired to innovate STABILOY Type XHHW-2 and USE-2/RHH/RHW-2

grounded in service wired to innovate STABILOY Type XHHW-2 and USE-2/RHH/RHW-2 grounded in service wired to innovate STABILOY Type XHHW-2 and USE-2/RHH/RHW-2 grounded in service wired to innovate www.cable.alcan.com Type XHHW-2 and Type USE-2/RHH/RHW-2 Alcan manufactures XHHW-2 and

More information

Spring Test 7 due 05/03/2013

Spring Test 7 due 05/03/2013 Spring Test 7 due 05/03/2013 Multiple Choice Identify the choice that best completes the statement or answers the question. 1. A raceway contains two 3-phase, 3-wire circuits that supply 38 ampere continuous

More information

SPECIFICATIONS FOR RESIDENTIAL CONSTRUCTION

SPECIFICATIONS FOR RESIDENTIAL CONSTRUCTION Roseville Electric SPECIFICATIONS FOR RESIDENTIAL CONSTRUCTION REVISED 10/03/17 Specifications for Residential Construction Revision List REVISION Date Page No. Description 8/18/09 T.O.C., 8.1-8.1.5 &

More information

Service Requirements

Service Requirements Service Requirements General Contact Idaho Power before beginning work on any new service. All meter installations must meet current electrical code requirements and display the proper electrical permit.

More information

Approved Meter Sockets and Cabinets

Approved Meter Sockets and Cabinets Single Unit Residential Guide 1 PHASE, 120/240 VOLT SERVICES SERVICE CAPACITY OWNED METERING (Metering sockets and cabinets are supplied by Customer). Outdoor meter mounting height is 1730 mm ( 5 8 ) to

More information

9/16/2010. Chapter , The McGraw-Hill Companies, Inc. TRANSMISSION SYSTEMS. 2010, The McGraw-Hill Companies, Inc.

9/16/2010. Chapter , The McGraw-Hill Companies, Inc. TRANSMISSION SYSTEMS. 2010, The McGraw-Hill Companies, Inc. Chapter 3 TRANSMISSION SYSTEMS 1 Transmitting large amounts of electric energy over long distances is accomplished most efficiently by using high-voltages. Without transformers the widespread distribution

More information

SECTION PANELBOARDS

SECTION PANELBOARDS SECTION 16470 PANELBOARDS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. The general provisions of the contract including General and Special Conditions and General Requirements shall apply to all work under

More information

New Service. From... BARRON. Spooner Office: P.O. Box 261 Spooner, WI Barron Office: P.O. Box 40 Barron, WI

New Service. From... BARRON. Spooner Office: P.O. Box 261 Spooner, WI Barron Office: P.O. Box 40 Barron, WI New Service Guidelines and Diagrams From... BARRON www.barronelectric.com email: janderson@barronelectric.com Barron Office: P.O. Box 40 Barron, WI 54812-0040 Spooner Office: P.O. Box 261 Spooner, WI 54801-0261

More information

Generator Fire Safety: Generator assemblies should be located outside the building.

Generator Fire Safety: Generator assemblies should be located outside the building. SECTION 33 70 00 - ELECTRICAL DISTRIBUTION PACKAGED GENERATOR ASSEMBLIES Generator Fire Safety: Generator assemblies should be located outside the building. All fuel piping from the outside of the building

More information

DEWALT Electrical Licensing Exam Guide CONTENTS

DEWALT Electrical Licensing Exam Guide CONTENTS DEWALT Electrical Licensing Exam Guide v ONTENTS How to Prepare for the Exam................................................ 2 How to Study.............................................................

More information

Contents. Obtaining Electric Service from Your Cooperative...1. Bonding Frames of Major Appliances...4. Voltage Drop...8. Drawings...

Contents. Obtaining Electric Service from Your Cooperative...1. Bonding Frames of Major Appliances...4. Voltage Drop...8. Drawings... Contents Obtaining Electric Service from Your Cooperative...1 Bonding Frames of Major Appliances...4 Voltage Drop...8 Drawings...14 Agricultural Buildings...23 Optional Standby Systems...42 Grounding &

More information

See Part 3 for the Introduction for Article 314

See Part 3 for the Introduction for Article 314 See Part 3 for the Introduction for Article 314 76 314.25 Covers and Canopies When the installation is complete, each outlet box must be provided with a cover or faceplate, unless covered by a fixture

More information

STOUGHTON UTILITIES ELECTRIC SERVICE RULES AND INFORMATION

STOUGHTON UTILITIES ELECTRIC SERVICE RULES AND INFORMATION CHAPTER 1 - GENERAL INFORMATION 100. Purpose 101. Codes and rules 102. Continuity of service 103. Frequency, Voltage, and Amperage Limitations 104. High voltages 105. Unusual capacity requirements 106.

More information

Customer Guide to Electric Service Requirements

Customer Guide to Electric Service Requirements Customer Guide to Electric Service Requirements Tillamook People s Utility District Power Services Group 1115 Pacific Avenue Tillamook, Oregon 97141 OFFICE: 503.815.8629 FAX: 503.815.8648 TOLL FREE: 800.422.2535

More information

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 2/8/12 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 2/8/12 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions MECKLENBURG COUNTY Land Use and Environmental Service Agency Code Enforcement 2/8/12 ELECTRICAL CONSISTENCY MEETING Code Consistency Questions 1. I am inspecting a building addition. They have a 480V to

More information

CHAPTER 1 INTRODUCTION

CHAPTER 1 INTRODUCTION CHAPTER 1 INTRODUCTION Installing new electric service is a joint project between the customer and the power company. The power company is responsible for bringing power to the site, for installing the

More information

Busway Construction. Bus Bars

Busway Construction. Bus Bars Busway Construction Bus Bars A better understanding of what busway is can be gained by examining its construction. A typical Siemens Sentron busway section has three or four formed aluminum or copper bars

More information

Power Connection Kit installation instructions

Power Connection Kit installation instructions Operating instructions & Parts Manual ET00 Please read and save these instructions. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and

More information