1 LOD BREK SWITCHES & SWITCH FUSES Switch Fuses FSF FSF 250 FSF FSF 60 Load Break Switches FLS FLS 250 FLS FLS 60 CONTENTS General Information bout Load Break Switches & Switch Fuses Technical Characteristic and Pictures of Switch Fuses Technical Characteristic and Pictures of Load Break Switches Dimensions and Installation Diagram /1

2 GENERL INFORMTION BOUT LOD BREK SWITCHES & SWITCH FUSES General characteristics : The Federal Load Break Switches & Switch Fuses have been designed to provide a compact, instantly openingclosed with rolling or friction contact. They have a breaking feature from same phase and four different points and are high performance devices. Load break switches are manufactured with or without fuses according to the IEC- EN and VDE-0660 standards, CE certificate and C 2 class. Due to this feature they are used at C and DC systems and motor circuit. Various combinations and types with high amperes which are not shown in this catalogue are manufactured accordig to special orders. General features : High breaking capacity, High electrical and mechanical endurance, Rolling contact system (except for ) capable of selfcleaning, Double breaking on each phase, Modern technology and compact design, Quick making and breaking operation independent of manuel operation, Small dimension, Case made of thermoset material, non absorbing and flame-heat resistant, Capable of mounting to front or rear side of panel cover. Contacts : Load break switches & switch fuses consist of contact system with constant contact which placed moulded case. Breaking energy is divided between contacts with this system. Combustion in contact is kept minimum due to energy is dividing between contacts and arc extinguisher elements in the breaking chamber. Getting small combustion extends the life of contacts. switches are manufactured with friction and high value switches are manufactured with using rolling contact. Friction and rolling contact systems provide clear and precise touching at every opening and closing of switch. Passing resistance and loss of energy among the contacts are limited to minimum with respect as a special spring. Current is broken from same phase and at four different points in the switch (except ). This feature builds up current breaking capacity of switch and fuses separated from the circuit at two points. (Pic-1) Safety : - Off 0 position both fuse terminals will not be alive so the fuses can be changed, safely. - On I position the handle will be locked mechanically, so the panel cannot be opened while energized. - Off 0 position the handle can be blocked out with a padlock so that it may prevent any unauthorized personnel to energize the panel. - The isolation distance between the phases is rather wide to prevent arc jumping. - dditional fuse protection shields are used for better isolation and protection in the switch fuses. - rc separators are used for arc extinguishing between contacts which occur during closing or breaking process. Locking with padlock 0 position Rolling contact system (250,, 60) Pic-2 Pic-1 Opening-closing mechanism and control handle : Opening-closing mechanism has been provided to operate the poles altogether and very rapidly. Speed of opening and closing is independent from hand moving. Control handle is passing type. The handle extention is necessary for all cases supplied in the length, than it is cut by the customer at the desired length. The position of switch can be seen by means of indicating plate and control handle. Switching angle for ON/OFF operation is 90 degrees. /2

3 GENERL INFORMTION BOUT THE LOD BREK SWITCHES & SWITCH FUSES Inside construction : Current is broken from the four separate points in a rolling contact system. This way the breaking capacity is increased and when the circuit breaker is in open position, fuses are seperated from the circuit completely. - Opening closing position are not depending on hand actuated. - High speed opening-closing can be done thanks to the springs in mechanism. Frictional system is applied at type of. In this way this system provides clear and precise touching at every opening and closed. Especially contact destruction is prevented by rolling contact system. rc extinguishers are used for arc extinguishing between contacts which occur during making or breaking process. mechanical resistance in a compact design. Connection bars are plated with silver. Capable of mounting to front or rearside of panel cover. Operating principle : By means of a special sling rolling contact system, moving contacts are mechanically connected to the operating handle to ensure a positive ON/OFF action and a forced operation of contacts. ny damage to contact is prevented in the rolling contact. ccessories : Following accessories are available, -Cage type connection terminals - Terminal protective covers (Pic-4) - Neutral link available - uxiliary conctact block 1NO + 1 NC for remote indication of switch status. - Special interlock and padlock system. Note: Terminal cover prevent to contact of switch fuse cable connection terminal with hand. This feature provides safe the insulation according to CE certificate. Pic- Switch fuse with terminal cover Frame and cover : Frame and cover are molded from glass-polyester material, BMC (Bulk Moulding Compound) in literature that combines ruggedness and high dieletric stength, as well as high Order Codes : Pic-4 Terminal covers Number of poles FSF FSF 250 FSF FSF 60 FLS FLS 250 FLS Order codes 9BB-S BC-S BC-S BD-S BB-L BC-L BC-L110-0 FLS 60 9BD-L Note : pole number is written (like or 4) * Switch fuses can dispatch without NH fuse. Terminal Cover Order Codes : Upper Terminal Protection Cover Order Codes : FSF B-G FLS B-D FSF250-FSF BB-G FLS250-FLS BB-D FLS B-H FLS250-FLS BB-H /

4 SWITCH FUSES Switch Fuses FSF FSF 250 FSF FSF 60 Technical Characteristics FSF FSF 250 FSF FSF 60 Number of pole, 4, 4, 4, 4 Rated thermal current (lth) Rated insulation voltage (Ui) V Rated impulse withstand voltage - Uimp kv Rated frequency Hz Rated operating power 0V C2 500V Reactive power 690V 0V kvr Rated breaking capacity C Rated closed capacity C Rated fuses short circuit breaking capacity k Fuse type Mechanical life NH Electrical life Weight kg Min.connection conductor cross-section mm x Dimensions Rear Connection 4. Pole (Mounting foot for FSF 60) Tip B C D E F G H J K L M N P R S Ø FSF FSF 250 FSF FSF /4

5 LOD BREK SWITCHES Load Break Switches FLS FLS 250 FLS FLS 60 Technical Characteristics FLS FLS 250 FLS FLS 60 Number of pole Rated thermal current (lth) Rated insulation voltage (Ui) Rated impulse withstand voltage - Uimp Rated frequency 0V Rated operating power 500V C2 690V Reactive power 0V d. V kv Hz kvr Rated breaking capacity C 2 Rated closed capacity C 2 Rated fuses short circuit breaking capacity Short-circuit making capacity k kpeak Short-time withstand current k/1s 25 Mechanical life Electrical life Weight kg Min.connection conductor cross-section mm x Dimensions Rear Connection 4. Pole Ø (Mounting foot for FLS 60) Tip B C D E F G H J K L M N P R S Ø FLS FLS 250 FLS FLS /5

6 DIMENSIONS ND INSTLLTION DIGRM Control handle Shaft extension Door drilling template Upper terminal protection cover : Right and left terminal protective cover : for FLS and FSF type for FSF type for FLS type /6

SIRCO PV UL98B Load break switches for photovoltaic applications from 100 to 2000 A - up to 1500 VDC

SIRCO PV UL98B Load break switches for photovoltaic applications from 100 to 2000 A - up to 1500 VDC Load break switches sircopv_058_a cat SIRCO PV UL98 from 00 to 2000 up to 500 VDC sircopv_059_a cat Strong points > Patented switching technology. > Positive break indication. > Up to 000 VDC as per characteristics

More information

PUSHBUTTON SWITCHES. electrical controls 1/5 SPECIFICATIONS: TECHNICAL DATA CONTACT BLOCKS LIGHTING BLOCKS

PUSHBUTTON SWITCHES. electrical controls 1/5 SPECIFICATIONS: TECHNICAL DATA CONTACT BLOCKS LIGHTING BLOCKS SPECIFICATIONS: For panels with Ø22mm drilling and thickness up to 6mm Modern and functional design Robust and compact construction NF contact with positive rupture KEMA-KEUR certified contact s electrical

More information

Vistop TM isolating switches 63 to 160A

Vistop TM isolating switches 63 to 160A DX 3 - IS main switches 16 to 125A Vistop TM isolating switches 63 to 160A 225 15 225 18 4 064 00 4 064 59 Pack Cat. No. Main switches AC 22 A category as per EN607-3 Grey handle Accept 1 signalling auxiliary

More information

switch disconnectors switch disconnectors fuses

switch disconnectors switch disconnectors fuses SWITCHGER R switch disconnectors RB switch disconnectors fuses R switch disconnectors and RB switch disconnectors fuses are designed for distribution of electricity, making and breaking currents and protection

More information

RSC09 RSC16 RSC22 RSC38 RSC43 RSC63 RSC-AUX

RSC09 RSC16 RSC22 RSC38 RSC43 RSC63 RSC-AUX IEC-Contactor RSC 1 Features Rated operational current 9 63 (C-3) Coil voltages C 24, 230V 3 main contacts and auxiliary contact Extendable with auxiliary contact block Mounting position any 2 Description

More information

SIRCO PV Load break switches for photovoltaic applications for use up to 1500 VDC from 100 to 3200 A

SIRCO PV Load break switches for photovoltaic applications for use up to 1500 VDC from 100 to 3200 A Load break switches new SRCO-pv_023_a_1_cat The solution for > Residential buildings. > Buildings. > Solar parks. Strong points Function SRCO PV are manually operated multipolar load break switches. They

More information

SENTRON Switching and Protection Devices Switch Disconnectors

SENTRON Switching and Protection Devices Switch Disconnectors SENTRON Switching and Protection Devices Switch Disconnectors /2 Introduction 3K, 3KE, 3LD Switch Disconnectors 3K, 3KE Switch Disconnectors up to 1000 /4 General data /8 Floor mounting 3LD Main and EMERGENCY-STOP

More information

SIRCOVER and SIRCOVER BY-PASS. Changeover switches with fully visualised breaking from 125 to 3200 A. 274 General Catalogue SOCOMEC

SIRCOVER and SIRCOVER BY-PASS. Changeover switches with fully visualised breaking from 125 to 3200 A. 274 General Catalogue SOCOMEC and Manual Changeover Switches BY-PSS appli_114_a svr_099_b_1_cat svr_059_a_1_cat Changeover switches with fully visualised breaking from 125 to 3200 Function products are manually operated multipolar

More information

ADVANCE GRP Series 125A Switched Interlocked socket outlets

ADVANCE GRP Series 125A Switched Interlocked socket outlets DVNCE GRP Series 125 Switched Interlocked socket outlets DVNCE GRP Series 125 > SWITCHED INTERLOCKED SOCKET OUTLETS > REFERENCE STNDRDS EN 60309-1 Plugs, socket outlets and couples for industrial purposes.

More information

01 Spectra Plus - Introduction

01 Spectra Plus - Introduction 01 Spectra Plus - Introduction Standard features Conforming to IS13947-2/EN60947 2 Compact dimensions Available in 3P & 4P High performance microprocessor protection release Wide overload setting from

More information

RX 3 MCB 4500 A Phase + Neutral, neutral on left side

RX 3 MCB 4500 A Phase + Neutral, neutral on left side 87045 LIMOGES Cedex Téléphone : 05 55 06 87 87 Télécopie : 05 55 06 88 88 RX 3 MCB 4500 A CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation - Connection...

More information

MS25, MST25, MS20, MST20

MS25, MST25, MS20, MST20 Versions: - MS25 with thermal and magnetic releases - MST25 with a thermal release - MS20 - with thermal and magnetic releases for single-phase consumers - MST20 with a thermal for single phase consumers

More information

3NP1 Fuse Switch Disconnectors up to 630 A

3NP1 Fuse Switch Disconnectors up to 630 A Switch Disconnectors 3NP1 Fuse Switch Disconnectors up to 630 A Introduction Overview All key product features at a glance available for all sizes Connection of circular conductors and laminated conductors

More information

SWITCH FUSES 3KL71 from 32A to 800A Description

SWITCH FUSES 3KL71 from 32A to 800A Description from 32A to 800A Description SWITCH FUSES 3KL71 3KL71 is a range of load-break switches suitable for making and breaking on load and disconnetting low voltage electrical circuits. They are commonly used

More information

Changeover & Bypass Sw it ches

Changeover & Bypass Sw it ches Changeover & Bypass Switches St ate of the art Manufacturing Facilit ies Haridw ar, Noida Ph-I & Noida Ph-II Plant Changeover & Bypass Sw it ches Introduction On Load Changeover Switches (with & without

More information

NH (H.R.C) FUSES AND FUSE BASES

NH (H.R.C) FUSES AND FUSE BASES NH (H.R.C) FUSES AND FUSE BASES NH (H.R.C) Fuses NHC-FB (A...A) NH-FB (A...A) NH-FB (A...A) NH-FB (8A...4A) NH-FB (A...A) NH-FB (A...A) NH (H.R.C) Fuse Bases STEATIT NH-FA NH-FA NH-FA NH-FA NH-FA CONTENTS

More information

DPX Thermal magnetic and trip-free switches DPX 3 -I 250

DPX Thermal magnetic and trip-free switches DPX 3 -I 250 87045 LIMOGES Cedex Phone :+33 05 55 06 87 87 Fax :+33 05 55 06 88 88 DPX 3 250 Reference(s) : 420 205/ 207/ 208/209/ 215/ 217/ 218/ 219/ 235/ 237/ CONTENTS PAGES 1. USE 1 2. RANGE 1 3. DIMENSIONS 1 3.

More information

SIRCO MV PV Load break switches for photovoltaic applications for use up to 1000 VDC from 63 to 80 A

SIRCO MV PV Load break switches for photovoltaic applications for use up to 1000 VDC from 63 to 80 A Load break switches SIRCO MV PV sircm-pv_010_a_1_cat The solution for > Residential buildings > Buildings > Solar parks Strong points SIRCO MV PV 1000 V - 80 A direct operation > Modular device > Patented

More information

General Characteristics

General Characteristics from 63 to 31 lbs_037_a he solution for > ain switchboard > Distribution panel > Emergency switching > us tie Function he CEC ensures making and breaking on load and security breaking of any low voltage

More information

Rotary limit switches FCR FGR series

Rotary limit switches FCR FGR series Rotary limit switches FCR FGR series Rotary control switches with 00mm rods from up to positions. Control switches with rotary gear from up to 00 rpm with or micro switches. 0 Rotary limit switches FCR

More information

125 to 4000 A. Functions. Conformity to standards. Approvals and certifications (1) General characteristics. Available on request

125 to 4000 A. Functions. Conformity to standards. Approvals and certifications (1) General characteristics. Available on request 125 to 4000 A sirco_353_a_1_cat sirco_296_a_1_cat sirco_300_b switches are manually operated or motorised multipolar load break switches. They break on and off under load and provide safety isolation for

More information

15 16 MCCBs for Power Distribution Technical Specification Frame 100A 250A 250A 400A 400A 630A 800 / 1000 / 1250 Type C DN0-100 D DN1-250 N DN2-250 D N S H DN3B-400 DN3-400 D N D N S V DN3-630 DN4-1250

More information

SIRCO PV UL98B Load break switches for photovoltaic applications from 100 to 2000 A, up to 1500 VDC

SIRCO PV UL98B Load break switches for photovoltaic applications from 100 to 2000 A, up to 1500 VDC Load break switches sircopv_058_a cat SIRCO PV UL98 new sircopv_059_a cat The solution for > Combiner box > Recombiner box > Inverter Function SIRCO PV UL98 non fusible disconnect switches are heavy duty

More information

Contactor Types CI 61-98

Contactor Types CI 61-98 MKING MODERN LIVING POSSIBLE Data sheet Contactor s CI 6-98 Contactors CI 6, CI 73, CI 86 and CI 98 switch powers of up to 30 kw, 37 kw, 45 kw and 55 kw respectively under 3 380 V C-3 loads. ccessories

More information

MAKING MODERN LIVING POSSIBLE. Technical brochure. Minicontactors CI 5-

MAKING MODERN LIVING POSSIBLE. Technical brochure. Minicontactors CI 5- MKING MODERN LIVING POSSIBLE Technical brochure Minicontactors CI 5- www.danfoss.com 2 IC.PD.C10.F3.02-520B4167 Danfoss /S, C-SMC, mr, 07-2010 Contents Page Minicontactor CI 5- Introduction...............................................................................4

More information

Non-fusable disconnect switches standards UL and CSA from 16 to 100 A

Non-fusable disconnect switches standards UL and CSA from 16 to 100 A Non-fusible disconnect switches sircm_132_a sircm_133_a The solution for > Industrial control systems Rotary switch SIRCO M 3 x 80 A Toggle switch SIRCO M 3 x 80 A + 2 auxiliary contacts Competitive advantages

More information

Product brochure. ABB Fusegear EasyLine Fuse switch disconnector

Product brochure. ABB Fusegear EasyLine Fuse switch disconnector Product brochure ABB Fusegear EasyLine Fuse switch disconnector 2 EasyLine Fuse Switch Disconnector ABB Fusegear Content Fuse protection 4 Technical Data 5 General 6 Apparatus overview 7 Electronic Fuse

More information

Miniature Circuit Breaker

Miniature Circuit Breaker Introduction - Miniature Circuit Breaker (MCB) SALIENT FEATURES SALIENT FEATURES Standards MCBs conform to the latest standard IS 8828: 1996/IEC: 898 1995 Mid-Trip Position The Mid trip position of the

More information

SD Series Non-Fused Load Switches

SD Series Non-Fused Load Switches SD Series Non-Fused Load Switches The SD1 and SD2 series of non-fused load switches are listed as Manual Motor Controllers and are designed for use in local motor isolation. The SD series of modular load

More information

GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector

GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector Catalog 0500CT9702R409 2009 Class 525/580 CONTENTS Description............................................. Page General Characteristics...................................

More information

DCX-M. changeover switches ->CATALOGUE PAGES INSIDE THE GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES

DCX-M. changeover switches ->CATALOGUE PAGES INSIDE THE GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES DCX-M changeover switches ->CATALOGUE PAGES INSIDE THE GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES FOR COMMERCIAL BUILDINGS AND DCX-M In = 63 A Quality & design CONFORM TO EN/IEC

More information

SENTRON 3NP1 Fuse Switch Disconnectors up to 630 A

SENTRON 3NP1 Fuse Switch Disconnectors up to 630 A Introduction Overview All key product features at a glance available for all sizes Connection of circular conductors and laminated conductors Fuse monitoring possible throughout Busbar supports can be

More information

DRX 125 Circuit breaker (not adjustable)

DRX 125 Circuit breaker (not adjustable) 87045 LIMOGES Cedex Téléphone : 05 55 06 87 87 Télécopie : 05 55 06 88 88 272 20/21/22/23/24/25/26/27/55/56/57/58/59/60 INDEX PAGES 1. USE 1 2. RANGE 1 3. DIMENSIONS 1 3. DIMENSIONS (continuation) 2 4.

More information

DPX Thermal magnetic and trip-free switches DPX 3 -I 160

DPX Thermal magnetic and trip-free switches DPX 3 -I 160 87045 LIMOGES Cedex Phone :+33 05 55 06 87 87 Fax :+33 05 55 06 88 88 DPX 3 160 CONTENTS PAGES 1. USE 1 2. RANGE 1 3. DIMENSIONS 1 4. OVERVIEW 2 5. ELECTRICAL AND MECHANICAL CHARACTERISTICS 3 6. CONFORMITY

More information

cor Long Run Experience

cor Long Run Experience Moulded Case Circuit Breakers Moulded Case Circuit Breakers 16-1250A cor Long Run Experience cor Breaking capacity (according to IEC 947-2 at 415V) Icu 100 D160L D250L D400L D630L 70 60 DH800 50 35 30

More information

Power systems Protection course

Power systems Protection course Al-Balqa Applied University Power systems Protection course Department of Electrical Energy Engineering Dr.Audih 1 Part 3 Protective Devices Fuses & Circuit Breakers 2 Introduction: Fuse Is advice used

More information

DPX Magnetic only

DPX Magnetic only 87045 LIMOGES Cedex Phone :+33 5 55 06 87 87 Fax :+33 5 55 06 88 88 CONTENTS PAGES 1. USE 1 2. RANGE 1 3. DIMENSIONS 1 3. DIMENSIONS (NEXT) 2 4. ELECTRICAL AND MECHANICAL CHARACTERISTICS 3 5. CONFORMITY

More information

new NH fuse-links (HRC) rated rated breaking type current voltage capacity size description price

new NH fuse-links (HRC) rated rated breaking type current voltage capacity size description price NH fuse-links (HRC) rated rated breaking type current voltage capacity size description price gg fuselinks 500V (IEC60269 - VDE0636 - DIN43620) with fuse blown indication NH Fuse links gg class with high

More information

What you need to know. Â Conformity to standards

What you need to know.  Conformity to standards SIRCO PV Load break switches for solar applications sirco_343_a_1_cat  What you need to know A solar electrical installation is an application that requires switching devices fully meet the needs of operational

More information

SIRCOVER. Manual Transfer Switching Equipment from 125 to 3200 A. Transfer switches. Function. Advantages. The solution for.

SIRCOVER. Manual Transfer Switching Equipment from 125 to 3200 A. Transfer switches. Function. Advantages. The solution for. Transfer switches svr_151_a The solution for > Manufacturing > Power distribution SIRCOVER 250 Strong points svr_214_a > Complete range > Easy to connect > Stable positions > On-load switching Conformity

More information

Selection Guide Motor Control Device Solutions

Selection Guide Motor Control Device Solutions Selection Guide Motor Control Device Solutions Expect more and get it from c3controls. Our portfolio of Motor Control Devices consists of worldclass products designed and manufactured to meet your requirements

More information

Switch Disconnectors. SENTRON 3NP5 Fuse Switch Disconnectors up to 630 A. Introduction. 7/106 Siemens LV

Switch Disconnectors. SENTRON 3NP5 Fuse Switch Disconnectors up to 630 A. Introduction. 7/106 Siemens LV Switch Disconnectors Introduction Siemens AG 2010 Overview 3NP5 0 3NP5 2 3NP5 fuse disconnector range 3NP5 4 SENTRON 3NP5 fuse disconnectors are controls for the occasional manual ing/isolating of loads

More information

Solenoid interlocks AZM 170 range. 98 Schmersal 22 8,2 60. ø4,2. ø Pg 11

Solenoid interlocks AZM 170 range. 98 Schmersal 22 8,2 60. ø4,2. ø Pg 11 2.4 AZM 170 range Features Thermoplastic enclosure Compact design Manual release Long life Double insulated X High holding force 1,000 N N latching force Cut clamp termination Actuation on de-energisation

More information

, , PREPARATION - CONNECTION. Mounting:. On symmetrical EN rail or DIN 35 rail

, , PREPARATION - CONNECTION. Mounting:. On symmetrical EN rail or DIN 35 rail 87045 LIMOGES Cedex Telephone number: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 DX 3 4500 A / 6 ka CONTENTS PAGES 1. Description, use...1 2. Range...1 3. Overall dimensions...1 4. Preparation - Connection...1

More information

DPX earth leakage DPX 3 -I earth leakage

DPX earth leakage DPX 3 -I earth leakage 87045 LIMOGES Cedex Phone :+33 05 55 06 87 87 Fax :+33 05 55 06 88 88 DPX 3 250 + earth leakage Reference(s) : 420 225/ 227/ 228/229/ 255/ 257/ 258/ 259/ 285/ 287/ CONTENTS PAGES 1. USE 1 2. RANGE 1 3.

More information

Motorized switch-disconnectors OTM 40 to 125 Amperes

Motorized switch-disconnectors OTM 40 to 125 Amperes Motorized switch-disconnectors OTM to 125 mperes With the new range of motorized-switch disconnectors, BB offers now a full range from to 2500 mperes. Thanks to the design, OTM...125 are a good solution

More information

Phase + Neutral, neutral on left side

Phase + Neutral, neutral on left side 87045 LIMOGES Cedex Téléphone : 05 55 06 87 87 Télécopie : 05 55 06 88 88 DX 3 MCB 10000 A / 16 ka CONTENTS PAGE 1. Description, use...1 2. Range...1 3. Overall dimensions...1 4. Preparation - Connection...1

More information

CTX 3 Control relays Cat. N (s) : /06/09..14/16/19..24/26/29

CTX 3 Control relays Cat. N (s) : /06/09..14/16/19..24/26/29 87045 LIMOGES Cedex Telephone: +33 5 55 06 87 87 FAX: +33 5 55 06 88 88 CTX 3 Control relays Cat. N (s) : 4 168 00..04/06/09..14/16/19..24/26/29 CONTENTS PAGES 1. Description - Use... 1 2. Range... 1 3.

More information

DC MILL DUTY CONTACTORS

DC MILL DUTY CONTACTORS DC MILL DUTY CONTCTORS DC Mill Duty Contactors 900 Range (Rating 15, 25, 50, 150, 300 & 600) BCH DC type 900 Mill Duty Contactors have been designed keeping in view the arduous environment and duty conditions

More information

3RT14 Contactors with 3 Main Contacts

3RT14 Contactors with 3 Main Contacts 3RT14 Contactors with 3 Main Contacts for Switching Resistive Loads Contactor Size 3RT14 46 Mechanical endurance Oper. 10 million Electrical endurance Oper. 0.5 million C-1 utilization category at I e

More information

General information about motor protection

General information about motor protection Application guide General information about motor protection Typical construction of a motor starter Disconnect Switch UL 98 - UL489 CSA C22.2 # 4 CSA C22.2 # 5 Fuses SIRCO Non-Fusible Disconnect Switch

More information

SIDERMAT Load break switches for power distribution from 250 to 1800 A with tripping function

SIDERMAT Load break switches for power distribution from 250 to 1800 A with tripping function The solution for Load break switches sdmat_066_a cat > Main switchboard > Distribution panel > Motor load break unction SIDERMT 4 x 630 External front operation SIDERMT are manually operated 3 or 4 pole

More information

DNX 3 MCB 4500 A / 6 ka Phase + Neutral, neutral on left side

DNX 3 MCB 4500 A / 6 ka Phase + Neutral, neutral on left side 87045 LIMOGES Cedex Telephone number: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 DNX 3 MCB 4500 A / 6 ka CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation

More information

F E - Electromagnetic Safety Switch With Separated Actuator. 1 Code Construction. Casing: P: Plastic casing

F E - Electromagnetic Safety Switch With Separated Actuator. 1 Code Construction. Casing: P: Plastic casing Electromagnetic Safety Switch With Separated 1 Code Construction F E - Casing: P: Plastic casing Cable inlet: 5: 3 x (M20x1) Type of FEP: E: Electrical block ( b with excited ) M: Mechanical block ( b

More information

Switches disconnectors with fuse-holders. XNF series TF series

Switches disconnectors with fuse-holders. XNF series TF series Switches disconnectors with fuse-holders XNF series TF series Quick Reference Switch-disconnectors with fuse-holders XNF series TF series XNF Series page 155 16 32A with fuse holders 3 4 Pole Auxiliary

More information

Phase + Neutral, neutral on right side

Phase + Neutral, neutral on right side 87045 LIMOGES Cedex Telephone number: +33 5 55 06 87 87 Fax: +33 5 55 06 88 88 DX 3 MCB 6000 A / 10 ka Cat.. N (s): 4 074 67 / 68 / 69 / 70 / 71 / 72 / 73 / 74 / 75 / 76 / 77 / 78 / 79 ; 4 077 33 / 34

More information

Enclosed DC rated switch-disconnectors OTDCP from 16 to 32 Amperes

Enclosed DC rated switch-disconnectors OTDCP from 16 to 32 Amperes Protection and Connection Enclosed DC rated switchdisconnectors OTDCP from 16 to 32 Amperes Enclosed OTDC switches from 16 to 32 Amperes meet the demanding requirements of photovoltaic applications. Enclosed

More information

SIRCO PV IEC Load break switches for photovoltaic applications from 100 to 3200 A, up to 1500 VDC

SIRCO PV IEC Load break switches for photovoltaic applications from 100 to 3200 A, up to 1500 VDC Load break switches SIRCO PV IEC 609473 new The solution for > Combiner box > Recombiner box > Inverter sircopv_058_a_1_cat sircopv_059_a_1_cat Strong points Function SIRCO PV are manually operated multipolar

More information

RX 3 M.C.B A up to 63 A

RX 3 M.C.B A up to 63 A 87045 LIMOGES Cedex Telephone: +33 5 55 06 87 87 FAX: +33 5 55 06 88 88 RX 3 M.C.B. 6000 A up to 63 A CONTENTS PAGES 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation - Connection...

More information

FUSOMAT Visible breaking and tripping fuse switches from 250 to 1250 A

FUSOMAT Visible breaking and tripping fuse switches from 250 to 1250 A Fuse protection The solution for > Motor load break > Protection of industrial cabinet > Electrical distribution fusom_063_b_1_cat Strong points > Tripping upon overload > High breaking capacity > Improved

More information

D509E. Manual Motor - Starters

D509E. Manual Motor - Starters D509E Manual Motor - Starters Index Page Manual Motors Starters 182 Auxilliary Contact Blocks 182 Trip Alarm Aux. Switch 182 Shunt Release 182 Under-voltage Release 183 Accessories 183 Busbar Connectors

More information

RX 3 M.C.B A up to 63 A

RX 3 M.C.B A up to 63 A 87045 LIMOGES Cedex Telephone: +33 5 55 06 87 87 FAX: +33 5 55 06 88 88 RX 3 M.C.B. 6000 A up to 63 A Cat. N (s): 4 197 49 to 4 199 23 CONTENTS PAGES 1. Description, use... 1 2. Range... 1 3. Overall dimensions...

More information

DPX 160 Thermal magnetic and trip-free switches DPX-I 160

DPX 160 Thermal magnetic and trip-free switches DPX-I 160 87045 LIMOGES Cedex Phone : +33 05 55 06 87 87 FAX : +33 05 55 06 88 88 DPX 160 CONTENTS PAGES 1. USE 1 2. RANGE 1 3. DIMENSIONS 1 3. DIMENSIONS (NEXT) 2 4. OVERVIEW 2 5. CONNECTION 2 6. ELECTRICAL AND

More information

Switch Disconnectors

Switch Disconnectors Switch Disconnectors Reversible terminals allow the same switch body to be used in both front & rear mount applications 25A - 32A - 50A - 63A - 80A - A versions available Neutral pole, additional poles

More information

Modular contactors and relays

Modular contactors and relays pages /4 to / pages /8 and /9 pages /10 and /11 pages /12 and /13 Presentation and standards Presentation Designed for use in modular panels and enclosures, these contactors feature : i Easy installation

More information

FL series position switches

FL series position switches FL series position switches Selection diagram 0 08 0 9 0 0 0 Ball Ø. External rubber Ball Ø 8 mm, mm, stainless Glass fibre rod gasket stainless steel steel Adjustable lever Adjustable safety lever Bistable

More information

DX³ 4-pole RCBO 6000 A/10 ka

DX³ 4-pole RCBO 6000 A/10 ka 87045 LIMOGES Cedex Telephone number: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 DX³ 4-pole RCBO CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation - Connection...

More information

Control Equipment. ATHEX bvba Tel: +32 (0) Fax: +32 (0) Alpenroosbaan 2, 2900 Schoten, België

Control Equipment. ATHEX bvba Tel: +32 (0) Fax: +32 (0) Alpenroosbaan 2, 2900 Schoten, België Control Equipment 01616E00 Position switches are used to monitor the position of moving parts of machines and plant. Can be used in safety circuits, as the device satisfies EN 60 947-5-1/DIN VDE 0660 part

More information

DRX 250 B/N/H Circuit breaker (not adjustable)

DRX 250 B/N/H Circuit breaker (not adjustable) 87045 LIMOGES Cedex Téléphone : 05 55 06 87 87 Télécopie : 05 55 06 88 88 References rences: /18/19/20/21/22/23/24/25/26/27/28/29/ 32/33 INDEX PAGES 1. USE 1 2. RANGE 1 3. DIMENSIONS 1 4. MOUNTING 2 5.

More information

Varius SUMMARY OF MODELS

Varius SUMMARY OF MODELS SUMMARY OF MODELS FH000 FH00 FH FH2 FH LTL4a Rated operating current I e 60 A 60 A 250 A 400 A 60 A 600 A Rated operating voltage AC/DC U e 690 V 690 V 690 V 690 V 690 V 690 V Size 000 00 2 4a Fuse-link

More information

Safety rope switches with reset for emergency stop

Safety rope switches with reset for emergency stop Safety rope switches with reset for emergency stop Selection diagram 8 8 83 ACTUATORS ACTUATORS CONTACT BLOCKS 18 9 21 1NO+ FP FD FL FC 22 33 34 LED signalling light CONDUIT ENTRIES For other available

More information

Varius SUMMARY OF MODELS

Varius SUMMARY OF MODELS Varius SUMMARY OF MODELS Type FH00 FH1 FH2 FH3 LTL4a Rated operating current I e 160 A 160 A 250 A 400 A 630 A 1 600 A Rated operating voltage AC/DC U e 690 V 690 V 690 V 690 V 690 V 690 V Size 000 00

More information

TAE pole Contactors

TAE pole Contactors TAE9...26 3-pole Contactors d.c. operated with double-winding coil SB8033C3 Utilisation TAE9 to TAE26 contactors are a compliment to the DC control contactor range. The coils have large voltage ranges

More information

CONTENT. EPE METALCLAD SWITCHGEARS AMS SERIES 12kV AMS METALCLAD SWITCHGEAR 24kV AMS METALCLAD SWITCHGEAR 40.5KV AMS METALCLAD SWITCHGEAR

CONTENT. EPE METALCLAD SWITCHGEARS AMS SERIES 12kV AMS METALCLAD SWITCHGEAR 24kV AMS METALCLAD SWITCHGEAR 40.5KV AMS METALCLAD SWITCHGEAR CONTENT EPE METLCLD SWITCHGERS SERIES EPE 1220 / - 12KV METLCLD SWITCHGER EPE 10D - 12KV METLCLD SWITCHGER EPE 24-24KV METLCLD SWITCHGER EPE 36-36KV METLCLD SWITCHGER EPE METLCLD SWITCHGERS MS SERIES 12

More information

Industrial Contactors CTX 3 3P 185A - 800A

Industrial Contactors CTX 3 3P 185A - 800A 87045 LIMOGES Cedex Telephone: +33 5 55 06 87 87 FAX: +33 5 55 06 88 88 Industrial Contactors CONTENTS PAGES 1. Description - Use... 1 2. Range... 1 3. Overall dimensions... 1 4. Installation - Connection...

More information

Siemens AG Switch Disconnectors SENTRON. Configuration. Edition 10/2015. Manual. siemens.com/lowvoltage

Siemens AG Switch Disconnectors SENTRON. Configuration. Edition 10/2015. Manual. siemens.com/lowvoltage SENTRON Configuration Manual Edition 10/2015 siemens.com/lowvoltage 2 Introduction LD main control and EMERGENCY-STOP switches up to 250 A 4 Introduction 7 Front mounting 10 Floor mounting 11 Distribution

More information

Micro Contactor MA Series

Micro Contactor MA Series Relay-sized contactor, making it the world s smallest >3mm contact clearance acc. to IEC 60335-1 for Safety Applications Reversing contactor with mechanical interlock 3 Pole and 1 Aux. Contact NO or NC

More information

1 Phase electronic contactor (SC 1)

1 Phase electronic contactor (SC 1) 1 Phase electronic contactor (SC 1) - Rated operational voltage up to 600VAC 50/60 Hz - Rated operational current up to 15/30A/50/63A AC-1 - Control voltage from or - Compact modular design 22.5, 45, or

More information

SIRCOVER. Manual transfer switches from 125 to 3200 A. Transfer switches. Function. Advantages. The solution for. Strong points

SIRCOVER. Manual transfer switches from 125 to 3200 A. Transfer switches. Function. Advantages. The solution for. Strong points Transfer switches svr_151_a The solution for > Manufacturing industry > Power distribution SRCOVER 2 Strong points > complete range > Easy connections > Stable positions svr_125_a_1_cat Bypass TS 0 Conformity

More information

DPX Thermal magnetic and trip-free switches DPX 3 -I 630

DPX Thermal magnetic and trip-free switches DPX 3 -I 630 87045 LIMOGES Cedex Phone :+33 05 55 06 87 87 Fax :+33 05 55 06 88 88 DPX 3 630 CONTENTS PAGES 1. USE 1 2. RANGE 1 3. DIMENSIONS 1 4. OVERVIEW 2 5. ELECTRICAL AND MECHANICAL CHARACTERISTICS 2 6. CONFORMITY

More information

TX³ RCCBs 2P up to 100 A

TX³ RCCBs 2P up to 100 A 87045 LIMOGES Cedex Telephone number: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 TX³ RCCBs CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation - Connection...

More information

DPX Electronic. Fiche technique : F01362EN/02 Mise à jour le : 15/12/2011 Créé le : 15/06/2011

DPX Electronic. Fiche technique : F01362EN/02 Mise à jour le : 15/12/2011 Créé le : 15/06/2011 87045 LIMOGES Cedex Phone :+33 5 55 06 87 87 Fax :+33 5 55 06 88 88 DPX 3 250 Electronic Reference(s): 420 302/305/307/309/312/315/317/319/332/335/ CONTENTS PAGES 1. USE 1 2. RANGE 1 3. DIMENSIONS 1 3.

More information

SIRCO UL98 Non-fusible switches standards UL and CSA 100 to 1200 A

SIRCO UL98 Non-fusible switches standards UL and CSA 100 to 1200 A Non-fusible disconnect switches SIRCO UL98 Non-fusible switches standards UL and CSA sirco-ul_022_b_1_cat The solution for > Power distribution sirco_093_b_1_cat SIRCO 3 x 200 A Strong points > Reliability

More information

Page. Circuit-Breakers M4 2 for motor protection. Auxiliary contacts 3 Signalling switch Auxiliary releases

Page. Circuit-Breakers M4 2 for motor protection. Auxiliary contacts 3 Signalling switch Auxiliary releases Circuit Breakers M4 Page Circuit-Breakers M4 2 for motor protection Auxiliary contacts 3 Signalling switch Auxiliary releases Insulated 3-pole busbar system 4 Terminal block DIN-rail adapters 5 Busbar

More information

MANUALLY OPERATED CHANGEOVER SWITCHES

MANUALLY OPERATED CHANGEOVER SWITCHES are manually operated multipolar changeover switches. They changeover between two low voltage power circuits under load and provide safety disconnection. Application: NORMA/EMERGENCY Application: UPS,

More information

DPX moulded case circuit breakers

DPX moulded case circuit breakers BREAKING AND PROTECTION DEVICES 10 / 2011 DPX moulded case circuit breakers DPX moulded case circuit breakers offer optimum solutions for the protection requirements of commercial and industrial installations.

More information

IEC Low Voltage General Purpose Protection

IEC Low Voltage General Purpose Protection , 6A, 0/400VAC (/440VAC) Complying with DIN VDE 0660 Part 07 EN / IEC 60947- DIN VDE 066 Part IEC 6069- DIN VDE 068 DIN VDE 4880 The D0-LINOCUR is a combination of switch-disconnector-fuse and NEOZED 6

More information

MULTIBLOC 3.ST8 Size 3, 630A, 690VAC, Design for Bottom Fitting, 3-,4-pole

MULTIBLOC 3.ST8 Size 3, 630A, 690VAC, Design for Bottom Fitting, 3-,4-pole MULTIBLOC 3.ST8 IEC FUSE SWITCH DISCONNECTORS NH FUSE SWITCH DISCONNECTOR The production programme of MULTIBLOC series 3.ST8 comprises NH fuse switch disconnectors for 630A. They are designed for bottom

More information

DPX 630 Thermal magnetic and trip-free switches DPX-I 630

DPX 630 Thermal magnetic and trip-free switches DPX-I 630 87045 LIMOGES Cedex Phone :+33 05 55 06 87 87 Fax :+33 05 55 06 88 88 DPX 630 CONTENTS PAGES 1. USE 1 2. RANGE 1 3. DIMENSIONS 1 4. OVERVIEW 2 5. CONNECTION 2 6. ELECTRICAL AND MECHANICAL CHARACTERISTICS

More information

DPX Electronic + earth leakage

DPX Electronic + earth leakage 87045 LIMOGES Cedex Phone :+33 5 55 06 87 87 Fax :+33 5 55 06 88 88 DPX 3 250 Electronic + earth leakage CONTENTS PAGES 1. USE 1 2. RANGE 1 3. DIMENSIONS 1 3. DIMENSIONS (NEXT) 2 4. ELECTRICAL AND MECHANICAL

More information

Molded case circuit breakers

Molded case circuit breakers Molded case circuit breakers Metasol 30F to 250F Series Type Type and Pole Rated current, In Rated operational voltage, Ue Rated insulation voltage, Ui Rated impulse withstand voltage, Uimp Frame Size(F)

More information

Essential Loads also use stand by generator systems mostly in process industries as they relate to high restarting times or high down times.

Essential Loads also use stand by generator systems mostly in process industries as they relate to high restarting times or high down times. The need for continuous power supply and its reliability has increased rapidly over the years, especially in all those areas where uninterrupted power supply is a must. Modern systems are power dependent.

More information

SIRCO UL98 Load break switches standards UL and CSA 100 to 1200 A

SIRCO UL98 Load break switches standards UL and CSA 100 to 1200 A The solution for Load break switches sirco-ul_022_b_1_cat > Power distribution. Strong points sirco_093_b_1_cat SIRCO 3 x 200 A > Reliability. > Safety of property and personnel. > Simplicity. > Easy assembling.

More information

Protection components

Protection components Presentation, characteristics Presentation 1 2 3 motor circuit-breakers are 3-pole thermal-magnetic circuit-breakers standards IEC 60947-2 and IEC 60947-4-1. Connection These circuit-breakers are designed

More information

DRX 100 B/N/H Circuit breaker (not adjustable)

DRX 100 B/N/H Circuit breaker (not adjustable) 87045 LIMOGES Cedex Téléphone : 05 55 06 87 87 Télécopie : 05 55 06 88 88 INDEX PAGES 1. USE 1 2. RANGE 1 3. DIMENSIONS 1 3. DIMENSIONS (continuation) 2 4. MOUNTING 2 5. CABLING 3 6. ELECTRIC AND MECHANICAL

More information

SIRCO PV IEC Load break switches for photovoltaic applications from 100 to 3200 A, up to 1500 VDC

SIRCO PV IEC Load break switches for photovoltaic applications from 100 to 3200 A, up to 1500 VDC SIRCO PV IEC 609473 The solution for Load break switches > Combiner box > Recombiner box > Inverter sircopv_058_a_1_cat sircopv_059_a_1_cat Strong points Function SIRCO PV are manually operated multipolar

More information

K50H004UP cam changeover switch - 4-pole A - screw mounting

K50H004UP cam changeover switch - 4-pole A - screw mounting Characteristics cam changeover switch - 4-pole - 60-50 A - screw mounting Main Range of product Product or component type Component name [Ith] conventional free air thermal current Mounting location Fixing

More information

TeSys contactors. Use in category DC-1 (resistive loads; time constant L/R y 1 ms) Rated operational current Ie. to be wired in series

TeSys contactors. Use in category DC-1 (resistive loads; time constant L/R y 1 ms) Rated operational current Ie. to be wired in series Selection 3-pole shockproof contactors FG d.c. supply Selection guide for utilisation categories DC-1 to DC-5 Use in category DC-1 (resistive loads; time constant L/R y 1 ms) Rated operational current

More information

Low voltage Direct Current Network. Compact NSX DC PV. Circuit breakers and switch disconnectors for solar application.

Low voltage Direct Current Network. Compact NSX DC PV. Circuit breakers and switch disconnectors for solar application. Low voltage Direct Current Network Compact NSX DC PV Circuit breakers and switch disconnectors for solar application Catalogue 2012 Compact NSX DC PV A complete DC offer for solar application from 80

More information

Catalogue March InLine II - ZLBM/ZHBM Fuse Switch Disconnector

Catalogue March InLine II - ZLBM/ZHBM Fuse Switch Disconnector Catalogue March 2015 InLine II - ZLBM/ZHBM Fuse Switch Disconnector 2 1SEC312022B0202 ABB Catalogue Contents Introduction 1 Apparatus 2 Accessories 3 Technical Data 4 Cable terminations and cable shrouds

More information