OPERATING CHARACTERISTICS

Size: px
Start display at page:

Download "OPERATING CHARACTERISTICS"

Transcription

1 TEMBREAK 2 MOULDED CASE CIRCUIT BREAKERS 16A TO 630A 1. Welcome to TemBreak 2 2. Ratings and Specifications 3. Operating Characteristics Thermal Magnetic Protection 23 Thermal Magnetic Time / Current Characteristics 26 Electronic Protection 30 Electronic Time / Current Characteristics 34 Letthrough Peak Current Characteristics 37 Letthrough Energy Characteristics Application Data 5. Accessories 6. Installation 7. Dimensions TEMBREAK MOULDED CASE CIRCUIT BREAKERS 630A TO 1600A 8. TemBreak Moulded Case Circuit Breakers 9. Order Codes The Ultimate Safety Breaker page 22

2 THERMAL MAGNETIC PROTECTION TemBreak 2 MCCBs from 125A frame to 400A frame are available with thermal magnetic protection units. Refer to Section 9 for details of TemBreak thermal magnetic MCCBs up to 800A. Thermal Magnetic trip units are especially suited to the following applications: Installations where harmonic distortion of current waveforms is likely. They operate inherently on the root mean square (rms) heating effect of current. DC circuits. Refer to Section 4, The Application of MCCBs in DC Systems for more information. 3 Pole MCCB with Adjustable Thermal and Adjustable Magnetic Characteristics Single Pole MCCB with Fixed Characteristics Models with Adjustable Thermal and Adjustable Magnetic Characteristics All standard 3 pole and 4 pole TemBreak 2 thermal magnetic models have adjustable thermal and adjustable magnetic characteristics. Traditionally, thermal magnetic MCCBs have had adjustable thermal with fixed magnetic characteristics. The fixed magnetic element can limit the application of the MCCB. An adjustable magnetic characteristic allows shortcircuit protection to be matched to the load and supply characteristics, for example motor inrush currents or generator shortcircuit currents. Lowering the shortcircuit tripping threshold can allow a higher earthloop impedance in an installation and provide endofcable protection with the correct disconnection times. page 23 The Ultimate Safety Breaker

3 THERMAL MAGNETIC PROTECTION Adjustment Dials (xi n ) (xi n ) 1. I R is the thermal element adjustment dial and is used to set the rated current to match the conductor rating. I R can be set between 0.63 and 1.0 times I n. 2. I i is the magnetic element adjustment dial and is used to set the short circuit tripping threshold to suit the application. I i can be set between 6 and 12 times I n on 125A and 400A frame models. I i can be set between 6 and 13 times I n on 250A frame models with ratings of 160A, 200A and 250A. I i can be set between 6 and 12 times I n on 250A frame models with ratings of 125A and less. Models, Types and Rated Currents of Thermal Elements Model Type Current Rating I n (A) S125 NF 16, 20, 25, 32, 40, 50, 63, 80, 100, 125 E125 NJ 20, 32, 50, 63, 100, 125 S125 NJ 20, 32, 50, 63, 100, 125 S125 GJ 20, 32, 50, 63, 100, 125 H125 NJ 20, 32, 50, 63, 100, 125 L125 NJ 20, 32, 50, 63, 100, 125 S160 NF 16, 20, 25, 32, 40, 50, 63, 80, 100, 125, 160 S160 NJ 20, 32, 50, 63, 100, 125, 160 S160 GJ 50, 63, 100, 125, 160 H160 NJ 160 L160 NJ 160 E250 NJ 20, 32, 50, 63, 100, 125, 160, 200, 250 S250 NJ 160, 200, 250 S250 GJ 160, 200, 250 H250 NJ 160, 250 L250 NJ 160, 250 E400 NJ 250, 400 S400 CJ 250, 400 S400 NJ 250, 400 S400 GJ 250, 400 H400 NJ 250, 400 L400 NJ 250, 400 The Ultimate Safety Breaker page 24

4 THERMAL MAGNETIC PROTECTION Single Pole MCCBs Single pole models have fixed thermal and fixed magnetic characteristics. Generator Protection Generators may need specially modified protection characteristics, based on their shortcircuit capability. If a generator is capable of delivering shortcircuit current greater than six times its full load current, a standard TemBreak 2 thermal magnetic MCCB may be used, with I i set at less than the available shortcircuit current. (Note that MCCBs, with fixed magnetic characteristics may not be suitable for this application.) A thermal magnetic MCCB with low instantaneous protection may be used where the generator shortcircuit current is less than six times its full load current. These are modified versions of the standard MCCB. Refer to Section 10 for order codes for MCCBs with low instantaneous protection. Four pole MCCBs with low instantaneous protection have protection on the neutral pole as standard. The magnetic characteristic of MCCBs with low instantaneous protection is fixed at the following values: Model E125 S125 S160 E250 S250 E400 S400 Magnetic Trip Current 3xI n 3xI n 3xI n 3xI n 3xI n 3.5xI n 3.5xI n Neutral Pole Protection Neutral pole protection is available as an optional extra on four pole thermal magnetic MCCBs. The thermal and magnetic elements in the neutral pole are related to those in the phase poles as follows: Phase Trip Threshold Neutral Trip Threshold Thermal I r (adjustable) I N (adjustable)= I n Magnetic I i (adjustable) I i (adjustable) Please contact Terasaki for order codes of models with neutral pole protection. Motor Protection MCCBs feeding motors are often only required to provide protection from shortcircuits. Overload protection is provided by a dedicated thermal or electronic overload relay. Tembreak 2 MCCBs without thermal protection elements are available for this application. Refer to section 10 for order codes for MCCBs with Magnetic Trip Only. Four pole MCCBs with magnetic trip only have protection on the neutral pole as standard. page 25 The Ultimate Safety Breaker

5 THERMAL MAGNETIC CHARACTERISTICS Single Pole MCCBs The Ultimate Safety Breaker page 26

6 THERMAL MAGNETIC CHARACTERISTICS 125A Frame MCCBs page 27 The Ultimate Safety Breaker

7 THERMAL MAGNETIC CHARACTERISTICS 160A and 250A Frames FOR PLUGIN, 225A 2925±585A The Ultimate Safety Breaker page 28

8 THERMAL MAGNETIC CHARACTERISTICS 400A Frame page 29 The Ultimate Safety Breaker

9 ELECTRONIC PROTECTION TemBreak 2 MCCBs from 250A frame to 630A frame are available with electronic protection units. Current ratings, In, of 40A, 125A, 250A, 400A and 630A are available. These offer great flexibility as their characteristics can be set to suit a wide range of application conditions. Overload protection can be set between 0.4 and 1.0 times In. Terasaki offer one of the most adaptable protection units on the market: If you require a characteristic which is not available as a preset on our standard electronic protection unit, send us the details and we will program a customised characteristic to your specification.* Selecting a Preset Characteristic for a 400A TemBreak 2 MCCB with Electronic Protection Every TemBreak 2 electronic protection unit includes overload protection (L), delayed shortcircuit protection (S) and instantaneous protection (I) as standard. Electronic Protection Characteristic *Characteristic is programmable within certain limits. Contact us for details. The Ultimate Safety Breaker page 30

10 ELECTRONIC PROTECTION Optional Functions Three optional functions are available: Ground Fault Trip (G) This function trips the MCCB after time delay, tg, if the ground fault current exceeds the preset threshold, Ig. Ground fault protection can be enabled and disabled by operating a DIP switch on the electronic protection unit. An external current transformer is available if the ground fault trip function is required on a 3 pole MCCB, in a 3 phase, 4 wire system. Refer to Section 7 for dimensions and to Section 10 for order codes. Neutral Protection (N) Neutral protection trips the MCCB after time delay, t N, if current in the neutral conductor exceeds the rated current, In, of the MCCB. The time delay characteristic is identical to that of the overload characteristic (L). Preferential Trip Alarm (P) An LED and voltfree output contact are activated after a time delay, tp, if the load current exceeds the preset threshold, Ip. A power supply is required for operation of the preferential trip alarm. This is connected through a terminal block which is mounted as shown below, either on the side of the breaker (250A, 400A, 630A standard), or remotely (400A, 630A oly on request). Ratings, specifications and wiring arrangements are shown below. Dimensions of terminal blocks for preferential trip alarm can be found in Section 7. Note that the breaker mounted terminal block is not compatible with the Terminal Block for FrontConnected and RearConnected MCCBs described in Section 5, if the latter is mounted on the right side of the breaker. Control Power Supply Specifications Frame (A) /630 Voltage V AC V AC Rated Power 2VA 2VA Rated Current of Output Contact Frame (A) / V AC, resistive load 3A 3A 125V AC, inductive load 2A 2A 250V AC, resistive load 3A 3A 250V AC, inductive load 2A 2A 30V DC, resistive load 2A 2A 30V DC, inductive load 2A 2A page 31 The Ultimate Safety Breaker

11 ELECTRONIC PROTECTION A A. Connection Arrangement for Prefferential Trip Alarm with Breaker Mounted Terminal Block (Standard). MCCB Protection Relay Terminal Block for preferrentisl Trip Alarm, Breaker Mounted Control Power Supply Terminals Connections from Terminal Block to Protection Relay, PreWired Output Contact Cables, PreWired B B. Connection Arrangement for Prefferential Trip Alarm with Remotely Mounted Terminal Block (On Request). How to Specify Optional Functions Optional functions must be specified at the time of order. Descriptions for electronic MCCBs include a 14 digit alphabetic code after the type designation which details the combination of optional functions. For example: S400GE APG 3P 400A FC includes preferential trip and ground fault trip. The table below lists codes for all the optional functions currently available: Optional Function I n 250 Poles 3 Code AP Ground Fault (G) Neutral Protection (N) Preferential Trip Alarm (P) 4 AP AN APN AP AG APG 4 AP AN APN AGN APGN AP AG APG 4 AP AN APN AGN APGN Available Not Available The Ultimate Safety Breaker page 32

12 ELECTRONIC PROTECTION Adjustment Dials The left adjustment dial sets the rated current to match the conductor rating. The right adjustment dial selects one of seven preset characteristics on 250A and 400A models, and one of six preset characteristics on 630A models. The effects of the left adjustment dial (labelled I R(A)), and the right adjustment dial (labelled Characteristics) are detailed in the tables shown underneath each time / current graph. Tolerances of Characteristics Characteristics Long Time Delay Short Time Delay Tolerance t R ± 20% I sd ± 15% Instantaneous tsd Ii Total clearing time +50ms, resettable time 20ms ± 20% Preferential Trip Alarm I p ± 10% t p ± 10% Ground Fault Trip Neutral Protection Ig tg IN ± 15% Total clearing time +50ms, resettable time 20ms ± 15% page 33 The Ultimate Safety Breaker

13 ELECTRONIC CHARACTERISTICS S250NE, S250GE, S250PE, H250NE In = 250A; 125A; 40A Standard Option I R (A) LTD Pickup current I R xin LT ST INST PTA NP Characteristics t R Isd tsd Ii Ip tp IN tn No at 200% x I R at 600% x I R xi R xir 14(Max: 13 x I n) Note (1) xi R xin 1.0 Note (2) tn = tr Note (1) Ii max. = 13 x In. (2) Standard setting of IN is 100% of In. For any other setting please specify when ordering. Characteristic of neutral protection (t N vs. IN) is identical to characteristic of phase protection (tr vs. IR). The Ultimate Safety Breaker page 34

14 ELECTRONIC CHARACTERISTICS S400NE, S400GE, H400NE, L400NE In = 400A; 250A IR (A) LTD Pickup current IR xin Standard Option LT ST INST PTA GF* NP Characteristics t R I sd tsd Ii Ip tp Ig tg IN tn No at 200% x I R at 600% x IR xir xi R 14(Max: 13 x I n) Note (1) xir xi n xin Note(2) t N=tR page 35 Note (1) I i max. = 13 x I n. (2) Standard setting of I N is 100% of I n. For any other setting please specify when ordering. Characteristic of neutral protection (tn vs. IN) is identical to characteristic of phase protection (tr vs. IR). *Not available when In is 250A The Ultimate Safety Breaker

15 ELECTRONIC CHARACTERISTICS E630NE, S630CE, S630GE 3 Tripping Time second minute hour T I R I p t R t p I g I sd tsd t g I i I Percent rated current In Percent Rated Current I R In = 630A IR (A) LTD Pickup current IR xin Standard Option LT ST INST PTA GF NP Characteristics t R Isd tsd Ii Ip tp I g tg IN t N No at 200% x I R at 600% x IR xir xir 14(Max: 10 x I n) Note (1) xir xin xin Note(2) t N=tR Note (1) Ii max. = 10 x I n. (2) Standard setting of I N is 100% of I n. For any other setting please specify when ordering. Characteristic of neutral protection (t N vs. IN) is identical to characteristic of phase protection (tr vs. IR). The Ultimate Safety Breaker page 36

16 LETTHROUGH PEAK CURRENT CHARACTERISTICS S125NF. 240V AC S160NF. 240V AC. E125NJ, S125NJ, S125GJ. 440V AC. S125NJ, S125GJ. 690V AC. page 37 The Ultimate Safety Breaker

17 LETTHROUGH PEAK CURRENT CHARACTERISTICS H125NJ, L125NJ. 440V AC. H125NJ, L125NJ. 690V AC S160NJ, S160GJ, E250NJ, S250NJ, S250GJ. 440V AC. S160NJ, S160GJ, S250NJ, S250GJ. 690V AC. The Ultimate Safety Breaker page 38

18 LETTHROUGH PEAK CURRENT CHARACTERISTICS H160NJ, L160NJ, S250NE, S250GE, S250PE, H250NJ, H250NE, L250NJ. 440V AC. H160NJ, L160NJ, S250NE, S250GE, S250PE, H250NJ, H250NE, L250NJ. 690V AC. c S250NE up to 36kA/380415V, 25kA/440V S250GE up to 65kA/380415V, 50kA/440V S250NE, S250GE up to 7.5kA E400NJ, S400CJ, S400NJ, S400NE, S400GJ, S400GE, 415V AC. S400CJ, S400NJ, S400NE, S400GJ, S400GE, 690V AC. page 39 The Ultimate Safety Breaker

19 LETTHROUGH PEAK CURRENT CHARACTERISTICS H400NJ, H400NE, L400NJ, L400NE. 415V AC. E630NE, S630CE, S630GE. 415V AC Max. Letthrough peak current(ka) E630NE, S630CE, S630GE. 690V AC Max. Letthrough peak current(ka) The Ultimate Safety Breaker page 40

20 LETTHROUGH ENERGY CHARACTERISTICS S125NF. 240V AC S160NF. 240V AC 1 240VAC E125NJ, S125NJ, S125GJ. 440V AC. S125NJ, S125GJ. 690V AC. page 41 The Ultimate Safety Breaker

21 LETTHROUGH ENERGY CHARACTERISTICS H125NJ, L125NJ. 440V AC. H125NJ, L125NJ. 690V AC S160NJ, S160GJ, E250NJ, S250NJ, S250GJ. 440V AC. S160NJ, S160GJ, S250NJ, S250GJ. 690V AC. The Ultimate Safety Breaker page 42

22 LETTHROUGH ENERGY CHARACTERISTICS H160NJ, L160NJ, S250NE, S250GE, S250PE, H250NE, H250NJ, L250NJ. 440V AC. H160NJ, L160NJ,S250NE, S250GE, S250PE, H250 NE, H250NJ, L250NJ. 690V AC. S250NE, S250GE upto 7.5kA S250NE up to 36kA/380415V, 25kA/440V S250GE up to 65kA/380415V, 50kA/440V E400NJ, S400CJ, S400NJ, S400NE, S400GJ, S400GE. 415V AC. S400CJ, S400NJ, S400NE, S400GJ, S400GE. 690V AC. page 43 The Ultimate Safety Breaker

23 LETTHROUGH ENERGY CHARACTERISTICS H400NJ, H400NE, L400NJ, L400NE. 415V AC. E630NE, S630CE, S630GE. 415V AC. E630NE, S630CE, S630GE. 690V AC. The Ultimate Safety Breaker page 44

24 SYMMETRICAL DOOR CUTOUT PATTERNS Door cutout patterns for external operating handles are symmetrical, even when breakers are mounted in opposite directions. Using TemBreak 2 Operating Handles Using other MCCB Operating Handles 3

The Ultimate Safety Breaker

The Ultimate Safety Breaker The Ultimate Safety Breaker OUR CUSTOMER CARE COMMITMENTS Quality is Guaranteed All products supplied from this catalogue carry a guarantee against defects in materials and workmanship for a period of

More information

Circuit Breaker Selection was affected by Seventeenth Edition Amendment from the First of July 2015

Circuit Breaker Selection was affected by Seventeenth Edition Amendment from the First of July 2015 Circuit Breaker Selection was affected by Seventeenth Edition Amendment from the First of July 2015 Abstract A new compensation factor, Cmin, has been included in the UK regulation for protection from

More information

5. OVERCURRENT RELEASE (OCR)

5. OVERCURRENT RELEASE (OCR) 5. OVERCURRENT RELEASE (OCR) Options available for the type AR ACBs include a highly reliable, multi-functional overcurrent release (OCR) with a built-in 8- bit microprocessor. This OCR is supplied with

More information

OUR CUSTOMER CARE COMMITMENTS

OUR CUSTOMER CARE COMMITMENTS & TemBreak MCCBs from 12A to 3200A MCCBs for 1000V AC MCCBs for 1000V DC MCCBs with Integral RCD Switch Disconnectors Measurement and Data Communication OUR CUSTOMER CARE COMMITMENTS Quality is Guaranteed

More information

Moulded case circuit breakers

Moulded case circuit breakers Moulded case circuit breakers CONTENT Range 4 Protection Releases 5 Salient Features 8 Accessories, 4 Technical data 2 Time Current Characteristics 5 Overall Dimensions 7 SN4 SN3 SN2 SN 3 RANGE Moulded

More information

Terasaki (Europe) Ltd

Terasaki (Europe) Ltd Terasaki (Europe) Ltd Terasaki Europe Ltd was established in 97 and is located near Glasgow, Scotland U.K. From head office at our 7,00 square metre facility, Terasaki Europe controls an International

More information

MOULDED CASE CIRCUIT BREAKERS 16A TO 630A

MOULDED CASE CIRCUIT BREAKERS 16A TO 630A TEMBREAK 2 MOULDED CASE CIRCUIT BREAKERS 16A TO 630A 1. Welcome to TemBreak 2 2. Ratings and Specifications 3. Operating Characteristics 4. Application Data 5. Accessories 6. Installation 7. Dimensions*

More information

5. OVERCURRENT RELEASE (OCR)

5. OVERCURRENT RELEASE (OCR) 5. OVERCURRENT RELEASE (OCR) Options available for the type AR ACBs include a highly reliable, multi-functional overcurrent release (OCR) with a built-in 8- bit microprocessor. This OCR is supplied with

More information

Low voltage moulded case circuit breaker EB2

Low voltage moulded case circuit breaker EB2 Low voltage moulded case circuit breaker EB2 Product series description unit condition Model-type Number of poles Nominal current ratings Electrical characteristics Rated operational voltage Rated insulation

More information

MCCB Connections, mounting and chassis systems

MCCB Connections, mounting and chassis systems MCCB Connections, mounting and chassis systems Section 6 Page MCCB Chassis NHP Chassis busbar systems overview 6-2 Quick reference table 6-2 MCCBs to suit each chassis type 6-3 XA 630 / 800 A chassis for

More information

Specification for 70mm pole pitch Air circuit breaker up to 1600 A

Specification for 70mm pole pitch Air circuit breaker up to 1600 A Specification for 70mm pole pitch Air circuit breaker up to 1600 A Protective device for low voltage electrical installation Last update :2011-07-08-1 - Table of contents: 1 General...3 2 Compliance with

More information

Power Distribution and Protection

Power Distribution and Protection Power Distribution and Protection Circuit Breakers ACB -2 MCCB - MCBs RCDs and RCBOs -76 Distribution Boards Loadcentre Assemblies -7 Panelboards -24 Arc and Surge Protection Arc Detecting Relays -58 Surge

More information

WORKSHOP SPECIFICATIONS

WORKSHOP SPECIFICATIONS WORKSHOP SPECIFICATIONS DPX 3 160 & 250 MOULDED CASE CIRCUIT BREAKERS THE GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES DPX 3 RANGE Not only do DPX³ 160 and DPX 3 250 MCCBs provide

More information

C 1. SPECTRONIC SP - Air circuit breakers. Summary. C2. General characteristics. C3. Fixed circuit breaker. C4. Withdrawable circuit breakers

C 1. SPECTRONIC SP - Air circuit breakers. Summary. C2. General characteristics. C3. Fixed circuit breaker. C4. Withdrawable circuit breakers SPETRONI SP - Air circuit breakers Summary 2. General characteristics 3. Fixed circuit breaker 4. Withdrawable circuit breakers 5. haracteristics 6. RV23: protection and control unit 6. RV+ : protection

More information

6300A 15 Optibreak B1 & B2 Optibreak B1 & B2 50/60 Hz Ue Icu [v] [ka] 415 65 690 40 4h 4i 1. Open / close Indication 2. Charge and Discharge Indicator 3. Release the reset button 4. Laser Nameplate

More information

Low voltage. Masterpact NT and NW. LV power circuit breakers and switch-disconnectors Draw-out Type & Fixed Type. Catalogue

Low voltage. Masterpact NT and NW. LV power circuit breakers and switch-disconnectors Draw-out Type & Fixed Type. Catalogue Low voltage Masterpact NT and NW LV power circuit breakers and switch-disconnectors Draw-out Type & Fixed Type Catalogue 2015 Functions and characteristics Circuit breakers and switch-disconnectors NT06

More information

Rated Impulse withstand voltage U imp Main circuit Between terminals, AC3500V for 1 minute 12kV terminal group to earth Control circuits

Rated Impulse withstand voltage U imp Main circuit Between terminals, AC3500V for 1 minute 12kV terminal group to earth Control circuits 7 Technical Data Dielectric strength Circuit Withstand voltage (at 50/60 Hz) Rated Impulse withstand voltage U imp Main circuit Between terminals, AC3500V for 1 minute 12kV terminal group to earth Control

More information

Characteristics of LV circuit breakers Releases, tripping curves, and limitation

Characteristics of LV circuit breakers Releases, tripping curves, and limitation Characteristics of LV circuit breakers Releases, tripping curves, and limitation Make, Withstand & Break Currents A circuit breaker is both a circuit-breaking device that can make, withstand and break

More information

Innovators in Protection Technology. TemBreak. Total Protection, Complete Control. Catalogue No I20E

Innovators in Protection Technology. TemBreak. Total Protection, Complete Control. Catalogue No I20E Innovators in Protection Technology TemBreak Total Protection, Complete Control Catalogue No. 05 - I0E Terasaki (Europe) Ltd Terasaki Europe Ltd was established in 97 and is located near Glasgow, Scotland

More information

Modular Metering - Trip Unit for >1200A Mains DEH41187 Application Guide

Modular Metering - Trip Unit for >1200A Mains DEH41187 Application Guide GE Industrial Solutions Modular Metering - Trip Unit for >1200A Mains DEH41187 Application Guide TABLE OF CONTENTS Description Page 1.0 General Information...... 1 1.1 Protection..... 1 2.0 UL Listed Devices...

More information

DX 3 MCBs. Choice of DX 3 MCBs for capacitor banks. Technical data

DX 3 MCBs. Choice of DX 3 MCBs for capacitor banks. Technical data Specifications IS/IEC 60898-1 2002 Number of poles SP, SPN, DP, TP, TPN, FP Characteristics C & D Curve Breaking capacity 10 ka 0.5 A to 63 A as per IS/IEC 60898-1 2002 16 ka for 0.5 A to 25 A as per IEC

More information

Low voltage moulded case circuit breaker EB2

Low voltage moulded case circuit breaker EB2 Low voltage moulded case circuit breaker EB2 Product series description unit condition Model-type Number of poles Nominal current ratings Electrical characteristics Rated operational voltage Rated insulation

More information

Air Circuit Breakers DH series General information

Air Circuit Breakers DH series General information General information Air circuit breakers Description The newly designed air circuit breakers have excellent features as follows: The height and depth dimensions are identical in all sizes up to 3200AF

More information

L&T SWITCHGEAR S A F E & S U R E. Moulded Case Circuit Breakers

L&T SWITCHGEAR S A F E & S U R E. Moulded Case Circuit Breakers L&T SWITCHGER S F E & S U R E Moulded Case Circuit Breakers Introduction Larsen & Toubro infuses engineering with imagination. The Company offers a wide range of advanced solutions in the field of Engineering,

More information

DMX 3 -I 2500 switch disconnectors

DMX 3 -I 2500 switch disconnectors 8704 LIMOGES Cedex Telephone : 0 0 87 87 Fax : 0 0 88 88 DMX 3 200 circuit breakers DMX 3 -I 200 switch disconnectors References: 0 28 20 / 21 / 22 / 23 / 24 / 2 / 2 / 30 / 31/ 32/ 33/ 34 / 3 / 3 / 40

More information

DPX moulded case circuit breakers

DPX moulded case circuit breakers BREAKING AND PROTECTION DEVICES 10 / 2011 DPX moulded case circuit breakers DPX moulded case circuit breakers offer optimum solutions for the protection requirements of commercial and industrial installations.

More information

Moulded Case Circuit Breakers

Moulded Case Circuit Breakers L&T SWITCHGER S F E & S U R E imp: k U 8 V Ue V, 60Hz. :4 0/ Ic u : 70k, I :0%I C T: cs cu D2 S IS 3947-2 IEC 60947-2 E 60947-2 - Moulded Case Circuit Breakers bout us Larsen & Toubro is a technology-driven

More information

Innovators in Protection Technology. TemBreak. Total Protection, Complete Control. Catalogue No I20EJ

Innovators in Protection Technology. TemBreak. Total Protection, Complete Control. Catalogue No I20EJ Innovators in Protection Technology TemBreak Total Protection, Complete Control Catalogue No. 0 - IEJ Mission Statement. Terasaki aims to be the best supplier of circuit breakers and associated equipment

More information

PowerPact M-, P- and R-Frame, and Compact NS630b NS3200 Circuit Breakers

PowerPact M-, P- and R-Frame, and Compact NS630b NS3200 Circuit Breakers PowerPact M-, P- and R-Frame, and Compact NS630b NS3200 Circuit Breakers Catalog 0612CT0101 R02/14 2014 Class 0612 CONTENTS Description............................................. Page General Information..........................................

More information

Memshield - ACB Ratings & Specifications

Memshield - ACB Ratings & Specifications Memshield Memshield - ACB Ratings & Specifications Rating and specifications Current rating, A List No Number of poles RATED CURRENT (A) [In] IEC, BS, VDE, AS Neutral pole ampere frame (A) RATED PRIMARY

More information

DH series New OCR providing Higher Reliability

DH series New OCR providing Higher Reliability New OR providing Higher Reliability 8 EEH64b Variation Rated current [A] Rated Breaking capacity(ka sym.)/ Rated making current(ka peak) IE EN AS [Ics=Icu] Rated Voltage 69VA Rated Voltage 44VA 8A 5A 6A

More information

DPX 1600 Electronic release

DPX 1600 Electronic release 87045 LIMOGES Cedex Phone :+33 05 55 06 87 87 Fax :+33 05 55 06 88 88 DPX 1600 CONTENTS PAGES 1. USE 1 2. RANGE 1 3. DIMENSIONS 1 3. DIMENSIONS (NEXT) 2 4. OVERVIEW 2 5. CONNECTION 2 6. ELECTRICAL AND

More information

(Áp Dụng Từ Ngày 01/12/ 2012)

(Áp Dụng Từ Ngày 01/12/ 2012) HOANG TRANG ELECTRIC CO., LTD (HOTECO) Add : 15A Nguyễn Trung Trực; P.5; Q. Bình Thạnh; Tp.HCM Tel : (84.8) 351 5 8100/02-6297 7400/02 - Fax : (84.8) 3515 8101 Website: http//: www.hoangtrangco.com.vn

More information

Circuit breakers and switch-disconnectors NT06 to NT16 and NW08 to NW63

Circuit breakers and switch-disconnectors NT06 to NT16 and NW08 to NW63 Functions and characteristics Circuit breakers and switch-disconnectors NT06 to NT16 and NW08 to NW63 NT and NW selection criteria Masterpact NT Masterpact NW NT06, NT08, NT10, NT12, NT16 NT06, NT08, NT10

More information

INSTRUCTION MANUAL FOR AR-E AIR CIRCUIT BREAKERS (Fixed type and Type AGR-12B Overcurrent Protective Device)

INSTRUCTION MANUAL FOR AR-E AIR CIRCUIT BREAKERS (Fixed type and Type AGR-12B Overcurrent Protective Device) INSTRUCTION MANUAL FOR AR-E AIR CIRCUIT BREAKERS (Fixed type and Type AGR-12B Overcurrent Protective Device) Types: AR206E AR208E AR210E AR212E AR216E Notice Be sure to read this manual before installing,

More information

cor Long Run Experience

cor Long Run Experience Moulded Case Circuit Breakers Moulded Case Circuit Breakers 16-1250A cor Long Run Experience cor Breaking capacity (according to IEC 947-2 at 415V) Icu 100 D160L D250L D400L D630L 70 60 DH800 50 35 30

More information

3 - Protection components Motor circuit-breakers

3 - Protection components Motor circuit-breakers Contents 0 - Protection components Motor circuit-breakers protection components for the motor protection Thermal-magnetic motor circuit-breakers Selection guide..............................................page

More information

Prisma ipm Switchboard Air Circuit Breaker (ACB) Moulded-case Circuit Breaker (MCCB) Contactor Power meter

Prisma ipm Switchboard Air Circuit Breaker (ACB) Moulded-case Circuit Breaker (MCCB) Contactor Power meter 3 Prisma ipm Switchboard Air Circuit Breaker (ACB) Moulded-case Circuit Breaker (MCCB) Contactor Power meter The easy choice for quality, value, and peace of mind Schneider Electric makes it an easy choice

More information

01 Spectra Plus - Introduction

01 Spectra Plus - Introduction 01 Spectra Plus - Introduction Standard features Conforming to IS13947-2/EN60947 2 Compact dimensions Available in 3P & 4P High performance microprocessor protection release Wide overload setting from

More information

DNX 3 MCB 4500 A / 6 ka Phase + Neutral, neutral on left side

DNX 3 MCB 4500 A / 6 ka Phase + Neutral, neutral on left side 87045 LIMOGES Cedex Telephone number: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 DNX 3 MCB 4500 A / 6 ka CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation

More information

SECTION MICROPROCESSOR TRIP UNITS FOR LV CIRCUIT BREAKERS. This section is organized as indicated below. Select desired Paragraphs.

SECTION MICROPROCESSOR TRIP UNITS FOR LV CIRCUIT BREAKERS. This section is organized as indicated below. Select desired Paragraphs. SECTION 16904 MICROPROCESSOR TRIP UNITS FOR LV CIRCUIT BREAKERS PART 2 PRODUCTS 01 MANUFACTURERS A. B. C. Eaton * * The listing of specific manufacturers above does not imply acceptance of their products

More information

Data Sheet Molded Case Circuit Breakers Molded Case Motor Circuit Protectors Molded Case Switches Ex9 Series - M

Data Sheet Molded Case Circuit Breakers Molded Case Motor Circuit Protectors Molded Case Switches Ex9 Series - M Data Sheet Molded Case Circuit Breakers Molded Case Motor Circuit Protectors Molded Case Switches Ex9 Series - M MS50T3L M2N200T3L na.noark-electric.com NOARK Ex9 Series - M Features Molded Case Circuit

More information

Electronic circuit breaker EBU10-T

Electronic circuit breaker EBU10-T Description The electronic circuit protector type EBU10-T (Electronic Breaker Unit) provides selective overcurrent protection in AC 230 V UPS systems. It consists of an MCB approved for short circuit interruptions

More information

New DMX 3. Efficient protection up to A AIR CIRCUIT BREAKERS PRODUCT GUIDE

New DMX 3. Efficient protection up to A AIR CIRCUIT BREAKERS PRODUCT GUIDE New DMX 3 Efficient protection up to 4 000 A AIR CIRCUIT BREAKERS PRODUCT GUIDE NEW DMX 3 ACBs UP TO 4 000 A EFFICIENT PROTECTION AND CONTROL FOR ALL TYPE OF BUILDINGS 02 Electrical panel equipped with

More information

File E47705 Vol. 7 Sec. 9 Page 1 Issued: and Report Revised:

File E47705 Vol. 7 Sec. 9 Page 1 Issued: and Report Revised: File E47705 Vol. 7 Sec. 9 Page 1 Issued: 1997-08-29 and Report Revised: 2005-06-30 DESCRIPTION PRODUCT COVERED: USL, CNL - Type Nos. 3RV1021, 3RV1121, 3RV1321 or 3RV1421, followed by combination of 0,

More information

Compact Merlin Gerin 80 to 3200 A

Compact Merlin Gerin 80 to 3200 A LV power air circuit breakers and switch-disconnectors Catalogue Compact Merlin Gerin 80 to 3200 A 2005 Industries SA 5, rue Nadar 92506 Rueil-Malmaison Cedex France Tel : +33 (0)1 41 29 82 00 Fax : +33

More information

ACW. Molded-Case Circuit Breaker UL 489 Listed. ACW Catalog Number Sequence

ACW. Molded-Case Circuit Breaker UL 489 Listed. ACW Catalog Number Sequence rotection rotectors Contactors Overloads Relays ushbuttons Molded-Case Breaker UL 489 Listed The EG Series of Molded Case Breakers are designed to provide overload and short-circuit protection for industrial

More information

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931 Data Bulletin 0931DB0101 July 2001 Cedar Rapids, IA, USA Ground-Censor Ground-Fault Protection System Type GC Class 931 09313063 GT Sensor Shunt Trip of Circuit Interrupter Window Area for Conductors GC

More information

3VU13, 3VU16 Circuit-Breakers

3VU13, 3VU16 Circuit-Breakers 3VU3, 3VU6 Circuit-Breakers Description The 3VU3, 3VU6 circuit-breakers are compact circuit-breakers for currents up to 80 A which operate according to the current limiting principle. The devices are used

More information

APPENDIX E. Electrical System Single Line Diagram Overcurrent Protection Study Overcurrent Protection Device Specifications

APPENDIX E. Electrical System Single Line Diagram Overcurrent Protection Study Overcurrent Protection Device Specifications Student Resource Building University of California Santa Barbara Clement Fung Lighting Electrical Option APPENDIX E Electrical System Single Line Diagram Overcurrent Protection Study Overcurrent Protection

More information

Phase + Neutral, neutral on left side

Phase + Neutral, neutral on left side 87045 LIMOGES Cedex Téléphone : 05 55 06 87 87 Télécopie : 05 55 06 88 88 DX 3 MCB 10000 A / 16 ka CONTENTS PAGE 1. Description, use...1 2. Range...1 3. Overall dimensions...1 4. Preparation - Connection...1

More information

1. The term "withstand" means "the unit will remain in place without separation of any parts from the device when subjected to the seismic forces.

1. The term withstand means the unit will remain in place without separation of any parts from the device when subjected to the seismic forces. SECTION 262816 - ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Fusible switches. 2. Nonfusible switches. 3. Receptacle switches. 4. Shunt trip switches. 5.

More information

DPX 630 Electronic release

DPX 630 Electronic release 87045 LIMOGES Cedex Phone :+33 05 55 06 87 87 Fax :+33 05 55 06 88 88 DPX 630 CONTENTS PAGES 1. USE 1 2. RANGE 1 3. DIMENSIONS 1 4. OVERVIEW 2 5. CONNECTION 2 6. ELECTRICAL AND MECHANICAL CHARACTERISTICS

More information

Phase + Neutral, neutral on right side

Phase + Neutral, neutral on right side 87045 LIMOGES Cedex Telephone number: +33 5 55 06 87 87 Fax: +33 5 55 06 88 88 DX 3 MCB 6000 A / 10 ka Cat.. N (s): 4 074 67 / 68 / 69 / 70 / 71 / 72 / 73 / 74 / 75 / 76 / 77 / 78 / 79 ; 4 077 33 / 34

More information

2.2. Molded Case Circuit Breakers. Contents. NG-Frame ( Amperes) Series G

2.2. Molded Case Circuit Breakers. Contents. NG-Frame ( Amperes) Series G . NG-Frame (00 ) NG-Frame (30 00 s) Product All Eaton NG-Frame circuit breakers are suitable for reverse feed use All NG-Frame circuit breakers are HACR rated Contents Page EG-Frame (5 5 s)..................

More information

MULTI 9 System Catalog IEC Rated C60N/H/L Circuit Breakers

MULTI 9 System Catalog IEC Rated C60N/H/L Circuit Breakers IEC Rated C60N/H/L Circuit Breakers Standard Features Fast Closing Allows increased withstand to the high inrush currents of some loads Trip-free mechanism: Contacts cannot be held in the on position when

More information

ACW Molded-Case Circuit Breaker UL 489 Listed

ACW Molded-Case Circuit Breaker UL 489 Listed Motors Automation Energy Transmission & Distribution Coatings Molded-Case Circuit Breaker UL 489 Listed Overview Introducing the WEG Series of Molded Case Circuit Breakers now available with UL489 certification.

More information

Motor Protection Circuit Breakers 3VU13 and 3VU16

Motor Protection Circuit Breakers 3VU13 and 3VU16 Motor Protection Circuit Breakers 3VU13 and 3VU16 3VU13/3VU16 is suitable for use in fuseless motor feeders upto 11KW/22KW (25A/63A) respectively. 3VU motor protection circuit breakers are used for protection

More information

ACB l COMET AIR CIRCUIT BREAKER

ACB l COMET AIR CIRCUIT BREAKER ACB l COMET AIR CIRCUIT BREAKER MASCHINENBAU HALBERSTADT GmbH, building on its 60 year legacy in power generation, introduces COMET Air Circuit Breaker designed to meet the standards and the requirements

More information

UMBW-UL489 and UL1077 Listed

UMBW-UL489 and UL1077 Listed -UL489 and UL77 Listed Introducing the New WEG Series Thermal-Magnetic Miniature Breakers. This new offering includes both UL489 and UL77 approvals to provide a solution for circuit & equipment protection

More information

ACB l COMET AIR CIRCUIT BREAKER

ACB l COMET AIR CIRCUIT BREAKER ACB l COMET AIR CIRCUIT BREAKER MASCHINENBAU HALBERSTADT GROUP, building on its 60 years legacy in power generation, introduces COMET Air Circuit Breaker designed to meet the standards and the requirements

More information

PDR circuit breaker - Ground fault Datasheet

PDR circuit breaker - Ground fault Datasheet - Ground fault Datasheet protection device Features Blue housing 1-3 poles plus neutral 7-100mA Preciese, temperature independent operation Choise of time delays, terminals and actuator colours Application

More information

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 6

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 6 The University of New South Wales School of Electrical Engineering and Telecommunications Industrial and Commercial Power Systems Topic 6 PROTECTIONS 1 FUNCTION OF ELECTRICAL PROTECTION SYSTEMS Problems:

More information

Section Contents. 1. Introduction 2-5. Salient features, internal & general appearance of Drawout ACB

Section Contents. 1. Introduction 2-5. Salient features, internal & general appearance of Drawout ACB 1 Section Contents PAGES 1. Introduction 2-5 Salient features, internal & general appearance of Drawout ACB 2. Ratings & Specifications 6-9 Free air & enclosed thermal current ratings for AC & DC applications

More information

with Electronic Trip Units

with Electronic Trip Units Instruction Leaflet IL0001 ffective ugust 011 Supersedes February 011 Instruction Leaflet for LG-Frame Circuit Breakers with lectronic Trip Units Warning 1 O NOT TTMPT TO LL OR PRFORM MINTNNC ON QUIPMNT

More information

File E47705 Project 97ME August 21, 1997 REPORT. MOTOR CONTROLLERS, MANUAL Amberg, FED REP Germany

File E47705 Project 97ME August 21, 1997 REPORT. MOTOR CONTROLLERS, MANUAL Amberg, FED REP Germany File E47705 Project 97ME18400 August 21, 1997 REPORT on MOTOR CONTROLLERS, MANUAL Amberg, FED REP Germany Copyright 1997 Underwriters Laboratories Inc. Underwriters Laboratories Inc. authorizes the above

More information

Dycon D2430 EN54-4 Fire Alarm Power Supply Series

Dycon D2430 EN54-4 Fire Alarm Power Supply Series Dycon D2430 EN54-4 Fire Alarm Power Supply Series Technical Description Installation and Operating Manual Construction Product Regulation 0359-CPR-00434 Page 1 of 14 Contents 1. General... 3 1.1 Product

More information

24.4. Miniature Circuit Breakers and Supplementary Protectors. For Immediate Delivery or Tech Support call KMParts.com at (866)

24.4. Miniature Circuit Breakers and Supplementary Protectors. For Immediate Delivery or Tech Support call KMParts.com at (866) .4 Miniature Circuit Breakers and Supplementary Protectors SPHM Supplementary Protector SPHM Supplementary Protector Product Description The SPHM Supplementary Protector is a dual rated product for both

More information

Recommended Procedures

Recommended Procedures Selective Coordination Study Recommended Procedures The following steps are recommended when conducting a selective coordination study.. One-Line Diagram Obtain the electrical system one-line diagram that

More information

, , PREPARATION - CONNECTION. Mounting:. On symmetrical EN rail or DIN 35 rail

, , PREPARATION - CONNECTION. Mounting:. On symmetrical EN rail or DIN 35 rail 87045 LIMOGES Cedex Telephone number: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 DX 3 4500 A / 6 ka CONTENTS PAGES 1. Description, use...1 2. Range...1 3. Overall dimensions...1 4. Preparation - Connection...1

More information

Low Voltage. EasyPact CVS. Moulded-case circuit breakers from 16 to 100 A

Low Voltage. EasyPact CVS. Moulded-case circuit breakers from 16 to 100 A Low Voltage EasyPact CVS Moulded-case circuit breakers from 16 to 100 A Catalogue 2013 EasyPact CVS Contents Functions and characteristics A-1 Installation recommendations B-1 Dimensions and connection

More information

Magnum IEC Low Voltage Air Circuit Breakers

Magnum IEC Low Voltage Air Circuit Breakers Magnum IEC Low Voltage Air Circuit Breakers Product Focus Up to 690 Vac 42 ka to 100 ka Icu 800 to 6300 Amperes EN 60947-2 A Global Source for Innovative Electrical Power Distribution Solutions Proven

More information

DX³ 4-pole RCBO 6000 A/10 ka

DX³ 4-pole RCBO 6000 A/10 ka 87045 LIMOGES Cedex Telephone number: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 DX³ 4-pole RCBO CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation - Connection...

More information

Control Circuit Protection

Control Circuit Protection Contents 5SJ4 Branch Circuit Protectors 5SY4 Supplementary Protectors 5SY6 Supplementary Protectors 16/19 5SJ4 Page Selection and ordering data 1-pole up to 63A 16/4 1-pole, 2-pole, 16/5 3-pole, 240VAC

More information

Protectors. Manual motor. Types MS116, MS132, MS45x, MS49x. MS Series. Manual motor protectors. Type MS116. Type MS132. Type MS45x.

Protectors. Manual motor. Types MS116, MS132, MS45x, MS49x. MS Series. Manual motor protectors. Type MS116. Type MS132. Type MS45x. Types MS116, MS132, MS5x, MS9x are electromechanical devices for motor and circuit protection. These devices offer local motor disconnect means, manual ON/OFF control, and protection against short circuit,

More information

SD Series Non-Fused Load Switches

SD Series Non-Fused Load Switches SD Series Non-Fused Load Switches The SD1 and SD2 series of non-fused load switches are listed as Manual Motor Controllers and are designed for use in local motor isolation. The SD series of modular load

More information

013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS

013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS 013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEYLON ELECTRICITY BOARD SRI LANKA Specification for MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEB Specification

More information

Miniature circuit breaker Application guide

Miniature circuit breaker Application guide Miniature circuit breaker Application guide Miniature Miniature circuit circuit breakers breakers Application S200 guide Introduction The circuit breaker plays an important role in providing over-current

More information

Index. Manual Motor Starters 1. Auxiliary Contact Blocks 1. Trip Alarm Auxiliary 1. Switch. Shunt Release 1. Under-voltage Release 2.

Index. Manual Motor Starters 1. Auxiliary Contact Blocks 1. Trip Alarm Auxiliary 1. Switch. Shunt Release 1. Under-voltage Release 2. Index Index Page Manual Motor Starters 1 Auxiliary Contact Blocks 1 Trip Alarm Auxiliary 1 Switch Shunt Release 1 Under-voltage Release 2 Accessories 2 Busbar Connectors 2 Enclosures 2 Leistung, kw C mv

More information

Breaking and protection devices

Breaking and protection devices Power guide: A complete set of technical documentation Breaking and protection devices 01 Sustainable development 08 Protection against external disturbances 02 Power balance and choice of power supply

More information

IN2 Enclosed Switches and Circuit Breakers

IN2 Enclosed Switches and Circuit Breakers Illinois Math and Science Academy DigitalCommons@IMSA Project Manuals IN2 2015 IN2 Enclosed Switches and Circuit Breakers Illinois Mathematics and Science Academy Follow this and additional works at: http://digitalcommons.imsa.edu/facility_in2_manuals

More information

C E R T I F I C A T E O F C O M P L I A N C E

C E R T I F I C A T E O F C O M P L I A N C E 1512 E47705 Report Reference E4770519970821 15OCTOBER12 Issued to: SIEMENS AG DF CP R&D V 3 WERNERVONSIEMENSSTRASSE 48 9 AMBERG GERMANY This is to certify that representative samples of MOTOR CONTROLLERS,

More information

DEVICE STATE/BYPASSED FAILURE OVERLOAD

DEVICE STATE/BYPASSED FAILURE OVERLOAD Technical specifications Type 5. 7. Control electronics Rated values Terminal Rated control supply voltage A1A2 V AC 115 230 115 230 Tolerance % -15+10-15+10 Rated control supply STANDBY ma 15 15 Rated

More information

DNX 3 MCB 4500 A / 6 ka Phase + Neutral, neutral on left side

DNX 3 MCB 4500 A / 6 ka Phase + Neutral, neutral on left side 87045 LIMOGES Cedex Téléphone : 05 55 06 87 87 Télécopie : 05 55 06 88 88 DNX 3 MCB 4500 A / 6 ka CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation - Connection...

More information

MCCB Accessories to suit AF

MCCB Accessories to suit AF MCCB s MCCB Accessories to suit 125-630AF Accessory fitting combinations INTERNAL General purpose types Micro-switch types Auxiliary Heavy duty types Bridge -contact types Auxiliary Shunt UVT Internal

More information

Shunt Capacitor Bank Protection in UHV Pilot Project. Qing Tian

Shunt Capacitor Bank Protection in UHV Pilot Project. Qing Tian Shunt Capacitor Bank Protection in UHV Pilot Project Qing Tian 2012-5 INTRODUCTION State Grid Corp. of China, the largest electric power provider in the country, has first build a 1000 kv transmission

More information

Btdin RCBO 6000A up to 63A (2P)

Btdin RCBO 6000A up to 63A (2P) Index Pages 1. Descripton... 2 2. Product range... 2 3. Overall dimensions... 2 4. Fixing Connection... 3 5. Generl characteristics.... 4-29 6. Compliance - Approvals... 30 7. Curves... 30-34 8.Auxiliaries-

More information

INSTALLATION INSTRUCTIONS FOR SYMCOM'S MODEL 777-HVR-SP ELECTRONIC OVERLOAD RELAY

INSTALLATION INSTRUCTIONS FOR SYMCOM'S MODEL 777-HVR-SP ELECTRONIC OVERLOAD RELAY CONNECTIONS INSTALLATION INSTRUCTIONS FOR SYMCOM'S MODEL 777-HVR-SP ELECTRONIC OVERLOAD RELAY BE SURE POWER IS DISCONNECTED PRIOR TO INSTALLATION!! FOLLOW NATIONAL, STATE AND LOCAL CODES! READ THESE INSTRUCTIONS

More information

Jtec 10kA Miniature Circuit Breaker

Jtec 10kA Miniature Circuit Breaker EN 60898 Jtec 10kA Miniature Circuit Breaker Techna s JTEC range has been enthusiastically adopted by a diverse range of customers seeking a cost effective 10kA performance. Jtec MCBs are available in

More information

S200 UL 489 Series. Miniature Circuit Breakers. Description. Features

S200 UL 489 Series. Miniature Circuit Breakers. Description. Features S200 UL 489 Series Miniature S200 UL 489 Series Miniature Circuit Breakers Description The S200 Series miniature circuit breaker offers a compact solution for protection requirements. The S200U AND S200UP

More information

R.C.B.O. SP / 1 module

R.C.B.O. SP / 1 module 87045 LIMOGES Cedex - France Telephone : (+33) 5 55 06 87 87 Fax : (+33) 5 55 06 88 88 R.C.B.O. SP / 1 module 6064 04 6064 64 05 6064 10 6064 11 6064 12 CONTENTS PAGES 1. Description, use... 1 2. Range...

More information

Molded Case Circuit Breakers Solid-state trip types

Molded Case Circuit Breakers Solid-state trip types Solidstate trip types Solidstate trip types, SA00E, 0E, 00E Features Equipped with a load current pretrip alarm Constantly monitors the load current, and outputs an alarm when the set current is exceeded.

More information

Interchangeable Built-in Fixed thermal Adjustable thermal Magnetic Fixed Adjustable Adjustable Electronic RMS 7 LS LSI

Interchangeable Built-in Fixed thermal Adjustable thermal Magnetic Fixed Adjustable Adjustable Electronic RMS 7 LS LSI . Technical Data and Specifications Ratings Frames EG, JG and LG EG JG LG Maximum rated current (amperes) 15, 160 1 50 400, 630 Breaker type 3 B B E S S H H C E S H C U X E S H C U X of poles 1, 3, 4,

More information

G-Series. Circuit Breaker.

G-Series. Circuit Breaker. -Series Circuit Breaker Carling Technologies -Series hydraulic/magnetic circuit breakers offer the highest quality solution to your circuit protection requirements. The -Series is designed to sense over-current

More information

Basic function. Rated current. Appropriate for three-phase motors of output 2) [kw] I n. = 400 V a.c. 2) Appropriate for three-phase motors

Basic function. Rated current. Appropriate for three-phase motors of output 2) [kw] I n. = 400 V a.c. 2) Appropriate for three-phase motors MOTOR STARTERS SM Basic function Switching and protection of motors up to A Protection against short-circuit and protection against overload The device responds to phase failure The device is provided

More information

Selective Coordination

Selective Coordination Circuit Breaker Curves The following curve illustrates a typical thermal magnetic molded case circuit breaker curve with an overload region and an instantaneous trip region (two instantaneous trip settings

More information

Alphapower HTU UPS. Some key features include:

Alphapower HTU UPS. Some key features include: The is a durable, high operating temperature UPS, ideal for outdoor applications. It is a combination of an inverter, battery charger and AC transfer switch in one complete system with a peak conversion

More information

LSIS UL MCCB & Accessory

LSIS UL MCCB & Accessory LSIS UL MCCB & Accessory UL MCCB 100/150/250/400/600/800/1200AF UL MCCB Accessory 100/150/250/400/600/800/1200AF No. Specification 100AF 150AF 250AF 400AF 600AF 800AF 1200AF 1 2 3 4 5 6 7 8 9 10 11 12

More information

Innovators in Protection Technology Moulded Case Circuit Breaker Instruction Manual

Innovators in Protection Technology Moulded Case Circuit Breaker Instruction Manual Innovators in Protection Technology Moulded Case Circuit Breaker Instruction Manual 11-M61E TABLE OF CONTENTS HANDLING & MAINTENANCE Storage 1 Transport 1 STANDARD ENVIRONMENT 1 INSTALLATION AND CONNECTION

More information

Engineering Dependable Protection

Engineering Dependable Protection Electrical Distribution System Engineering Dependable Protection Engineering Dependable Protection - Part II "Selective Coordination of Overcurrent Protective Devices" Table of Contents Page Basic Considerations

More information