Circuit Breaker Selection was affected by Seventeenth Edition Amendment from the First of July 2015

Size: px
Start display at page:

Download "Circuit Breaker Selection was affected by Seventeenth Edition Amendment from the First of July 2015"

Transcription

1 Circuit Breaker Selection was affected by Seventeenth Edition Amendment from the First of July 2015 Abstract A new compensation factor, Cmin, has been included in the UK regulation for protection from electric shock. It is intended to ensure that circuits supplied by slightly lower voltages than normal will provide protection from electric shock. This takes account of the fact that the voltage of the electricity supply to an electrical installation varies depending on time and place, changing of transformer taps and other considerations. Eddie Donnelly Tim Campbell November, 2015

2 Contents Protection Against Electric Shock, Regulation Calculation of Maximum Allowable Earth Loop Impedance According to Requirements for Electrical Installations IET Wiring Regulations Seventeenth Edition. BS7671: Common reasons a design may not meet this requirement... 3 Solutions Offered by Terasaki... 4 Appendix 1: Circuit Breakers with Integral Residual Protection Appendix 2: Maximum Allowable Earth Loop Impedance Values for TemBreak 2 Lite Range, in accordance with BS 7671:2008+A3:2015 Appendix 3: Maximum Allowable Earth Loop Impedance Values for TemBreak 2 Lite Range, in accordance with BS 7671:2008+A3:2015 Ref. Number: 15-MARK.UK.11 2

3 Protection Against Electric Shock, Regulation The impedance of the protective circuit should be low enough that it allows sufficient fault current to cause the circuit breaker to trip. The regulation is intended to ensure that a protective device will trip within 0.4 seconds if fault current flows in the protective conductor. Calculation of Maximum Allowable Earth Loop Impedance According to Requirements for Electrical Installations IET Wiring Regulations Seventeenth Edition. BS7671:2008 Before Amendment 3: 2015 Zs * Ia Uo Where Zs is the earth fault loop impedance in ohms Ia is the current in amperes causing operation of the protective device within the time specified in table 41.1 of regulation Uo is the nominal a.c. r.m.s. line voltage to earth in volts After Amendment 3: 2015, effective 1 st July 2015 Zs * Ia Uo * Cmin Where Zs is the earth fault loop impedance in ohms Ia is the current in amperes causing operation of the protective device within the time specified in table 41.1 of regulation Uo is the nominal a.c. r.m.s. line voltage to earth in volts Cmin is the minimum voltage factor to take account of voltage variations depending on time and place, changing of transformer taps and other considerations. Common reasons a design may not meet this requirement Common reasons a design may not meet this requirement are: Protective conductors are too small and present a large impedance to the fault current Protective device instantaneous trip thresholds are too high Ref. Number: 15-MARK.UK.11 3

4 Solutions Offered by Terasaki The most common solutions are: Reduce the value of current, which will operate the protective device in 0.4 seconds either by selecting a different device or by making an adjustment to its settings. All Terasaki TemBreak 2 MCCBs, including thermal magnetic types and electronic types, have adjustable instantaneous trip thresholds. This makes it easy to comply with Regulation by changing the setting, not the device. MCCB with adjustable Thermal and Adjustable Magnetic Characteristics Include RCD protection set at no greater than 30mA in the circuit Terasaki offer a wide range of DIN modular RCDs and RCBOs. In addition we have the only CBR (circuit breaker with integral residual current protection) based on an MCCB in the UK market. Refer to Appendix 1 for details of our CBR solution. Terasaki CBR Ref. Number: 15-MARK.UK.11 4

5 Lower the earth-fault loop impedance by increasing the cross-sectional area of the protective conductor We have re-calculated the maximum allowable earthfault loop impedance for each of our Moulded Case Circuit Breakers at maximum and minimum settings taking the new Cmin factor into account. The results are presented in Appendixes 2 and 3. Maximum allowable earth-fault loop impedance for Miniature Circuit Breakers (MCBs) are published in Table 41.3 of the Wiring Regulations. Ref. Number: 15-MARK.UK.11 5

6 Appendix 1: Circuit Breakers with Integral Residual Protection

7 Appendix 2 Maximum Allowable Earth Loop Impedance Values for TemBreak 2 Lite Range, in accordance with BS 7671:2008+A3:2015 MCCB REFERENCE S/C Protection Zs 230 Volts Setting In 0.4sec 5 sec 160AF 1P FIXED MAGS E160-SF, 25 ka AF THERMAL MAGNETIC FIXED E160-SF, 16 ka S160-SCF, 25 ka S160-SF, 40 ka AF THERMAL MAGNETIC MIN ADJUSTABLE MAX MIN E160-SJ, 16 ka MAX MIN S160-SCJ, 25 ka MAX MIN S160-SJ, 40 ka MAX MIN MAX MIN MAX MIN MAX

8 250AF THERMAL MAGNETIC FIXED E250-SCF, 16 ka E250-SF, 25 ka S250-SF, 40 ka 250AF THERMAL MAGNETIC MIN ADJUSTABLE MAX MIN E250-SCJ, 16 ka MAX MIN E250-SJ, 25 ka MAX MIN S160-SJ, 40 ka MAX MIN MAX

9 Appendix 3 Maximum Allowable Earth Loop Impedance Values for TemBreak 2 Range, in accordance with BS 7671:2008+A3:2015 MCCB REFERENCE S/C Protection Zs 230 Volts Setting In 0.4sec 5 sec S125NJ, 36kA MIN S125GJ, 65kA MAX MIN MAX MIN MAX MIN MAX MIN MAX MIN MAX S160NJ, 36kA MIN S160GJ, 65kA MAX MIN MAX MIN MAX MIN MAX MIN MAX MIN MAX MIN MAX H160NJ, 125kA MIN L160NJ, 200kA MAX S250NJ, 36kA MIN S250GJ, 65kA MAX MIN MAX MIN MAX

10 S250NE, 36kA S250GE, 65kA MIN S250PE, 70kA H250NE, 125kA MAX MIN MAX MIN MAX H250NJ, 125 ka MIN L250NJ, 200 ka MAX MIN MAX E400NJ, 25 ka S400CJ, 36 ka MIN S400NJ, 50 ka S400GJ, 70 ka MAX MIN MAX S400NE, 50 ka S400GE, 70 ka MIN H400NE, 125 ka L400NE, 200 ka MAX MIN MAX E630NE, 36 ka S630CE, 50 ka MIN S630GE, 70 ka MAX S800CJ, 36kA S800NJ, 50kA MIN S800RJ, 70kA MAX MIN MAX S800NE, 50kA S800RE, 70kA MIN MAX MIN MAX S1000SE, 50kA S1000NE, 70kA MIN MAX S1250SE, 50kA S1250NE, 70kA MIN S1250GE, 85kA MAX S1600SE, 50Ka S1600NE, 85kA MIN MAX

11 Ref. Number: 15-MARK.UK.11 Copyright Terasaki Electric (Europe) ltd. 2015

OPERATING CHARACTERISTICS

OPERATING CHARACTERISTICS TEMBREAK 2 MOULDED CASE CIRCUIT BREAKERS 16A TO 630A 1. Welcome to TemBreak 2 2. Ratings and Specifications 3. Operating Characteristics Thermal Magnetic Protection 23 Thermal Magnetic Time / Current Characteristics

More information

OUR CUSTOMER CARE COMMITMENTS

OUR CUSTOMER CARE COMMITMENTS & TemBreak MCCBs from 12A to 3200A MCCBs for 1000V AC MCCBs for 1000V DC MCCBs with Integral RCD Switch Disconnectors Measurement and Data Communication OUR CUSTOMER CARE COMMITMENTS Quality is Guaranteed

More information

The Ultimate Safety Breaker

The Ultimate Safety Breaker The Ultimate Safety Breaker OUR CUSTOMER CARE COMMITMENTS Quality is Guaranteed All products supplied from this catalogue carry a guarantee against defects in materials and workmanship for a period of

More information

Power Distribution and Protection

Power Distribution and Protection Power Distribution and Protection Circuit Breakers ACB -2 MCCB - MCBs RCDs and RCBOs -76 Distribution Boards Loadcentre Assemblies -7 Panelboards -24 Arc and Surge Protection Arc Detecting Relays -58 Surge

More information

MCCB Connections, mounting and chassis systems

MCCB Connections, mounting and chassis systems MCCB Connections, mounting and chassis systems Section 6 Page MCCB Chassis NHP Chassis busbar systems overview 6-2 Quick reference table 6-2 MCCBs to suit each chassis type 6-3 XA 630 / 800 A chassis for

More information

MINIATURE CIRCUIT BREAKERS RCBO s & DIN RAIL MOUNTED FUSE HOLDERS

MINIATURE CIRCUIT BREAKERS RCBO s & DIN RAIL MOUNTED FUSE HOLDERS MINIATURE CIRCUIT BREAKERS RCBO s & DIN RAIL MOUNTED FUSE HOLDERS MANUFACTURED IN THE EU EUROPEAN QUALITY 1, 2 & 3 POLE MCB s TRIPPING CURVES C & D CURRENT RATINGS 1AMP TO 63AMPS 10KA BREAKING CAPACITY

More information

BS : C&G 2382 Outcomes 4

BS : C&G 2382 Outcomes 4 BS7671 2008: C&G 2382 Outcomes 4 Outcome 4 Protection for safety The candidate will be able to: 4.1 Identify the differences between basic and fault protection 4.2 State means of protection against electrical

More information

(Áp Dụng Từ Ngày 01/12/ 2012)

(Áp Dụng Từ Ngày 01/12/ 2012) HOANG TRANG ELECTRIC CO., LTD (HOTECO) Add : 15A Nguyễn Trung Trực; P.5; Q. Bình Thạnh; Tp.HCM Tel : (84.8) 351 5 8100/02-6297 7400/02 - Fax : (84.8) 3515 8101 Website: http//: www.hoangtrangco.com.vn

More information

Polestar Compact 250A MCB Distribution Boards

Polestar Compact 250A MCB Distribution Boards Polestar Compact 50A MCB Distribution Boards MCBS, RCBOs AND DISTRIBUTION BOARDS MCBs - 6A to 63A Type B, C and D Single, Double and Triple Pole 8mm modular width 6kA BS EN 60898 RCBOs - 6A to 50A Type

More information

On-Site Guide (BS 7671:2008 Wiring Regulations, incorporating Amendment No 1:2011)

On-Site Guide (BS 7671:2008 Wiring Regulations, incorporating Amendment No 1:2011) (BS 7671:2008 Wiring Regulations, incorporating Amendment No 1:2011) Author: IET Publications (edited by Mark Coles) Book details Author: IET Publications (edited by Mark Coles) Year: 2011 Format: Paperback,

More information

R.C.B.O. SP / 1 module

R.C.B.O. SP / 1 module 87045 LIMOGES Cedex - France Telephone : (+33) 5 55 06 87 87 Fax : (+33) 5 55 06 88 88 R.C.B.O. SP / 1 module 6064 04 6064 64 05 6064 10 6064 11 6064 12 CONTENTS PAGES 1. Description, use... 1 2. Range...

More information

Circuit Breaker Prepared By :

Circuit Breaker Prepared By : Circuit Breaker Prepared By : Eng : Ayman Soliman Selmy Circuit Breaker Specification of circuit Breaker:- [1] Operating voltage of C.B [2] Rated current of C.B (Ir or In) Amp. [3] Instantaneous short

More information

Power systems Protection course

Power systems Protection course Al-Balqa Applied University Power systems Protection course Department of Electrical Energy Engineering Dr.Audih 1 Part 3 Protective Devices Fuses & Circuit Breakers 2 Introduction: Fuse Is advice used

More information

Intelligent Choice for Prestigious Buildings

Intelligent Choice for Prestigious Buildings Intelligent Choice for Prestigious Buildings Table of Contents I-LINE Moulded Case Circuit Breakers General Characteristics 16A to 160A 125A to 250A 250A to 600A 300A to 800A 630A to 1250A 2/3 4 5 6 6

More information

Protectors. Manual motor. Types MS116, MS132, MS45x, MS49x. MS Series. Manual motor protectors. Type MS116. Type MS132. Type MS45x.

Protectors. Manual motor. Types MS116, MS132, MS45x, MS49x. MS Series. Manual motor protectors. Type MS116. Type MS132. Type MS45x. Types MS116, MS132, MS5x, MS9x are electromechanical devices for motor and circuit protection. These devices offer local motor disconnect means, manual ON/OFF control, and protection against short circuit,

More information

ic60h (6kA) single module combined RCD/MCB units ic60h (10kA) single module combined RCD/MCB units ild residual current circuit breakers idpn N Vigi

ic60h (6kA) single module combined RCD/MCB units ic60h (10kA) single module combined RCD/MCB units ild residual current circuit breakers idpn N Vigi Contents Miniature circuit breakers ic60n miniature circuit breakers 6kA, C curve, 6-63A ic60h miniature circuit breakers 10kA, C curve, 6-63A ic60n miniature circuit breakers 6kA, B curve, 6-63A ic60h

More information

Protection, Monitoring and Control Components for Low Voltage Equipment SELECTION GUIDE: UK EDITION

Protection, Monitoring and Control Components for Low Voltage Equipment SELECTION GUIDE: UK EDITION Protection, Monitoring and Control Components for Low Voltage Equipment SELECTION GUIDE: UK EDITION [Telehouse Data Centre, London. 199 TemPower 2 ACBs, 423 TemBreak 2 MCCBs.] Terasaki supply circuit

More information

DX³ 4-pole RCBO 6000 A/10 ka

DX³ 4-pole RCBO 6000 A/10 ka 87045 LIMOGES Cedex Telephone number: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 DX³ 4-pole RCBO CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation - Connection...

More information

RCBOs - Residual current circuit breakers with integral overcurrent protection KZS

RCBOs - Residual current circuit breakers with integral overcurrent protection KZS RCBOs - Residual current circuit breakers with integral overcurrent protection KZS Advantages of residual current circuit breakers with integral overcurrent protection KZS - 1M Combining the features of

More information

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 6

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 6 The University of New South Wales School of Electrical Engineering and Telecommunications Industrial and Commercial Power Systems Topic 6 PROTECTIONS 1 FUNCTION OF ELECTRICAL PROTECTION SYSTEMS Problems:

More information

DSE201 Compact design with enhanced protection

DSE201 Compact design with enhanced protection DSE201 Compact design with enhanced protection The best of safety DSE201 6 ka: the highest level of reliability The 1P+N electronic residual current circuit-breakers with overcurrent protection (RCBOs)

More information

EAD10H80D EAD14H80D EAD17H80D

EAD10H80D EAD14H80D EAD17H80D 12.4 Technical data Consumer units and enclosures dimensions and data RCCB controlled surface mounting consumer units Eaton list Dimensions (mm) number w h d EAD2/3M63 154 223 101 EAD2/3M80 EAD4M63 235

More information

Innovators in Protection Technology. TemBreak. Total Protection, Complete Control. Catalogue No I20E

Innovators in Protection Technology. TemBreak. Total Protection, Complete Control. Catalogue No I20E Innovators in Protection Technology TemBreak Total Protection, Complete Control Catalogue No. 05 - I0E Terasaki (Europe) Ltd Terasaki Europe Ltd was established in 97 and is located near Glasgow, Scotland

More information

City & Guilds 2381 Test 2382 Level 3. Which one of these electrical installations does BS 7671:2008 not apply to:

City & Guilds 2381 Test 2382 Level 3. Which one of these electrical installations does BS 7671:2008 not apply to: City & Guilds 2381 Test 2382 Level 3 Q1 Which one of these electrical installations does BS 7671:2008 not apply to: Temporary Construction sites Distributor s Equipment Caravans Public Premises Q2 Which

More information

New DX 3 High rating & breaking capacity

New DX 3 High rating & breaking capacity New High rating & breaking capacity a new range OF MOduLar CirCuiT BrEakErs up TO 125 a T new dx³ MCBs AN ENHANCED range for HIgH-pErforMANCE INstALLAtIoNs DX³ : the new Legrand MCBs with dx³, Legrand

More information

Terasaki (Europe) Ltd

Terasaki (Europe) Ltd Terasaki (Europe) Ltd Terasaki Europe Ltd was established in 97 and is located near Glasgow, Scotland U.K. From head office at our 7,00 square metre facility, Terasaki Europe controls an International

More information

Type CDG 14 Extremely Inverse Time Overcurrent and Earth Fault Relay

Type CDG 14 Extremely Inverse Time Overcurrent and Earth Fault Relay Type DG 14 Extremely Inverse Time Overcurrent and Earth Fault Relay Type DG 14 Extremely Inverse Time Overcurrent and Earth Fault Relay DG 14 drawn out from the case The type DG 14 relay is a heavily damped

More information

Essential equipment for all your requirements

Essential equipment for all your requirements NEW CTX CONTACTORS Essential equipment for all your requirements 9 A TO 310 A THREE-POLE INDUSTRIAL CONTACTORS CTX three-pole industrial contactors, a sense of family The new range of CTX contactors provides

More information

3 o/c 2 An area or temporary structure used for display, marketing or sales is defined as a a booth b a stand c an exhibition d a show.

3 o/c 2 An area or temporary structure used for display, marketing or sales is defined as a a booth b a stand c an exhibition d a show. 1 PAPER 7 Sample Questions - C&G 2382 17th Edition paper C 1 o/c 1 - BS 7671 relates to permanent and temporary installations for equipment on: a marinas. b ships. c equipment on aircraft. d railway traction

More information

Paramount HRC Cartridge

Paramount HRC Cartridge Paramount HRC Cartridge Eaton MEM HRC fuselinks are manufactured to exacting standards using precision assembly methods and undergo rigorous quality checking before dispatch including resistance testing

More information

020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB)

020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB) 020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB) CEYLON ELECTRICITY BOARD SRI LANKA Telephone: +94 11 232 0953 Fax: +94 11 232 3935 CONTENTS Page 1.0 Scope 3 2.0 System Parameters 3 3.0 Service

More information

Range 16A to 63A. Sensitivity 30mA, 100mA, 300mA, 500mA. Execution Double Pole, Four Pole. Specification IEC / IS : 2000

Range 16A to 63A. Sensitivity 30mA, 100mA, 300mA, 500mA. Execution Double Pole, Four Pole. Specification IEC / IS : 2000 The flow of current through electrical facilities always involves risks. Poorly insulated equipment, faulty wires and incorrect use of an electrical devise cause currents to flow through the wrong path

More information

ICG Switchgear Price List 2009

ICG Switchgear Price List 2009 ICG Switchgear Price List 2009 Section 1 Control Gear Page Contactors (AC,DC & Modular) 2,3 Overload Relays 4 Product Accessories 4,5 Starters-DOL, Star-Delta, Fan/Vibrators, Reversing/Twin 6,7 Section

More information

RESIDUAL CURRENT CIRCUIT BREAKER

RESIDUAL CURRENT CIRCUIT BREAKER Quality Features Mid Trip - Different knob position to indicate whether the device is Switched OFF by a fault or Switched OFF manually Inscription Window - Ensures circuit identification and hence reduces

More information

Safety, Reliability and Performance verified with the KEMA KEUR mark. Series G Moulded Case Circuit Breakers

Safety, Reliability and Performance verified with the KEMA KEUR mark. Series G Moulded Case Circuit Breakers Series G Moulded Case Circuit Breakers Product Focus Up to 690 Vac 18kA to 100kA Icu 16-2500 Amperes IEC 60947-2 Safety, Reliability and Performance verified with the KEMA KEUR mark Safety, Reliability

More information

DX 3 MCBs. Choice of DX 3 MCBs for capacitor banks. Technical data

DX 3 MCBs. Choice of DX 3 MCBs for capacitor banks. Technical data Specifications IS/IEC 60898-1 2002 Number of poles SP, SPN, DP, TP, TPN, FP Characteristics C & D Curve Breaking capacity 10 ka 0.5 A to 63 A as per IS/IEC 60898-1 2002 16 ka for 0.5 A to 25 A as per IEC

More information

Miniature & Moulded Case

Miniature & Moulded Case Miniature & Moulded Case MCB OPERATION MAGNETIC OPERATION The short time protection (typically less than 1 second after energising) of the MCB is defined as the magnetic operation. 1 2 3 THERMAL OPERATION

More information

File E47705 Project 97ME August 21, 1997 REPORT. MOTOR CONTROLLERS, MANUAL Amberg, FED REP Germany

File E47705 Project 97ME August 21, 1997 REPORT. MOTOR CONTROLLERS, MANUAL Amberg, FED REP Germany File E47705 Project 97ME18400 August 21, 1997 REPORT on MOTOR CONTROLLERS, MANUAL Amberg, FED REP Germany Copyright 1997 Underwriters Laboratories Inc. Underwriters Laboratories Inc. authorizes the above

More information

Consumer unit solutions to meet the requirements of the new 17th edition amendment 3 regulations

Consumer unit solutions to meet the requirements of the new 17th edition amendment 3 regulations MEMT Memera full metal consumer units and protective devices Consumer unit solutions to meet the requirements of the new 17th edition amendment 3 regulations Memera full metal consumer units and protective

More information

SELECT MEMBERSHIP NUMBER Full Installation 75% new and 25% alteration to exsisting

SELECT MEMBERSHIP NUMBER Full Installation 75% new and 25% alteration to exsisting The Electrical Contractors Association SELECT MEMBERSHIP NUMBER 15019 ELECTRICAL INSTALLATION CERTIFICATE (REQUIREMENTS FOR ELECTRICAL INSTALLATIONS - BS 7671 [IET WIRING REGULATIONS]) EI Copyright The

More information

Control Circuit Protection

Control Circuit Protection Contents 5SJ4 Branch Circuit Protectors 5SY4 Supplementary Protectors 5SY6 Supplementary Protectors 16/19 5SJ4 Page Selection and ordering data 1-pole up to 63A 16/4 1-pole, 2-pole, 16/5 3-pole, 240VAC

More information

ELECTRICAL INSTALLER EXAMINATION 18 November 2017 QUESTION AND ANSWER BOOKLET

ELECTRICAL INSTALLER EXAMINATION 18 November 2017 QUESTION AND ANSWER BOOKLET Candidate Code No. EIN15 For Board Use Only Result Date Int Result Date Int ELECTRICAL INSTALLER EXAMINATION 18 November 2017 QUESTION AND ANSWER BOOKLET INSTRUCTIONS READ CAREFULLY Time Allowed: Three

More information

Btdin RCBO 6000A up to 63A (2P)

Btdin RCBO 6000A up to 63A (2P) Index Pages 1. Descripton... 2 2. Product range... 2 3. Overall dimensions... 2 4. Fixing Connection... 3 5. Generl characteristics.... 4-29 6. Compliance - Approvals... 30 7. Curves... 30-34 8.Auxiliaries-

More information

l Suitable for most residential, commercial and light industrial applications

l Suitable for most residential, commercial and light industrial applications 538 Consumer Units and Enclosures Standards and approvals All Sentry consumer units are designed to fully comply with the requirements of BS EN 60439-3. Weatherproof enclosures are designed to fully comply

More information

DX³ RCBO 6000 A Phase + Neutral, neutral right side

DX³ RCBO 6000 A Phase + Neutral, neutral right side 87045 LIMOGES Cedex Téléphone : 05 55 06 87 87 Télécopie : 05 55 06 88 88 DX³ RCBO 6000 A CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation Connection... 1

More information

87045 LIMOGES Cedex. 2. PRODUCT RANGE (continued) 1. DESCRIPTION - USE. Breaking capacity : Symbol : Technology : 3. OVERALL DIMENSIONS

87045 LIMOGES Cedex. 2. PRODUCT RANGE (continued) 1. DESCRIPTION - USE. Breaking capacity : Symbol : Technology : 3. OVERALL DIMENSIONS 87045 LIMOGES Cedex Phone : + 33 5 55 06 87 87 Fax : + 33 5 55 06 88 88 R.C.B.O. DX 6000 A Phase + Neutral,, neutral on right side Cat. n (s) : 077 31 077 44-077 77 077 84 078 79 079 01-083 95 084 06 084

More information

1 Phase electronic contactor (SC 1)

1 Phase electronic contactor (SC 1) 1 Phase electronic contactor (SC 1) - Rated operational voltage up to 600VAC 50/60 Hz - Rated operational current up to 15/30A/50/63A AC-1 - Control voltage from or - Compact modular design 22.5, 45, or

More information

Btdin-RS RCBO 2p Phase + Neutral, neutral on right

Btdin-RS RCBO 2p Phase + Neutral, neutral on right Viale Borri 231, 21100 Varese - Italy RCBO 2p CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation Connection... 1 5. General characteristics... 2 6. Compliance

More information

The young energy ensures more safety

The young energy ensures more safety The young energy ensures more safety Domestic Products Catalogue 2017 CORPORATE OFFICE ABOUT STANDARD STANDARD is a brand of India s leading FMEG company, Havells India Ltd., that offers a wide range of

More information

Air-insulated switchgear UniGear type ZS1

Air-insulated switchgear UniGear type ZS1 Air-insulated switchgear UniGear type ZS1 ABB Power Technologies / 1-7074 D 12-03-2003 - Air-insulated switchgear UniGear type ZS1 ABB Power Technologies / 2-7075 D 1 2-03-2003 - Rated voltage kv 12 17.5

More information

Characteristics of LV circuit breakers Releases, tripping curves, and limitation

Characteristics of LV circuit breakers Releases, tripping curves, and limitation Characteristics of LV circuit breakers Releases, tripping curves, and limitation Make, Withstand & Break Currents A circuit breaker is both a circuit-breaking device that can make, withstand and break

More information

WORKSHOP SPECIFICATIONS

WORKSHOP SPECIFICATIONS WORKSHOP SPECIFICATIONS DPX 3 160 & 250 MOULDED CASE CIRCUIT BREAKERS THE GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES DPX 3 RANGE Not only do DPX³ 160 and DPX 3 250 MCCBs provide

More information

DX³ RCBO 4500/6 ka Phase + Neutral, neutral on left

DX³ RCBO 4500/6 ka Phase + Neutral, neutral on left 87045 LIMOGES Cedex Telephone number: +33 5 55 06 87 87 Fax: +33 5 55 06 88 88 DX³ RCBO 4500/6 ka CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation Connection...

More information

MINIATURE CIRCUIT BREAKER

MINIATURE CIRCUIT BREAKER Technical Article MINIATURE CIRCUIT BREAKER T 146 PURCHASE he Spaceage MCB protects wires and cables automatically against overload and short-circuits in domestic, commercial and industrial installations.

More information

Low voltage moulded case circuit breaker EB2

Low voltage moulded case circuit breaker EB2 Low voltage moulded case circuit breaker EB2 Product series description unit condition Model-type Number of poles Nominal current ratings Electrical characteristics Rated operational voltage Rated insulation

More information

Major changes within the New 18 th Edition Wiring Regulations announced by The IET

Major changes within the New 18 th Edition Wiring Regulations announced by The IET Major changes within the New 18 th Edition Wiring Regulations announced by The IET BS 7671:2018 Requirements for Electrical Installations will be issued on 2 nd July 2018 and is intended to come into effect

More information

COMPLETE SOLUTIONS FOR POWER PROTECTION

COMPLETE SOLUTIONS FOR POWER PROTECTION COMPLETE SOLUTIONS FOR POWER PROTECTION GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES Modular protection P. 8 RX 3 MCBs 63 A 4500 & 6000 P. 18 DX 3 -IS isolating switches P. 9 RX

More information

Technical News. High Efficiency Motors & Type 2 Coordination Motor Starting. Industrial Electrical and Automation Products, Systems and Solutions

Technical News. High Efficiency Motors & Type 2 Coordination Motor Starting. Industrial Electrical and Automation Products, Systems and Solutions Issue #74 - Autumn 2016 Technical News Industrial Electrical and Automation Products, Systems and Solutions High Efficiency Motors & Type 2 Coordination Motor Starting Written by Steve Young, Application

More information

Phase + Neutral, neutral on right side

Phase + Neutral, neutral on right side 87045 LIMOGES Cedex Telephone number: +33 5 55 06 87 87 Fax: +33 5 55 06 88 88 DX 3 MCB 6000 A / 10 ka Cat.. N (s): 4 074 67 / 68 / 69 / 70 / 71 / 72 / 73 / 74 / 75 / 76 / 77 / 78 / 79 ; 4 077 33 / 34

More information

Innovators in Protection Technology. TemBreak. Total Protection, Complete Control. Catalogue No I20EJ

Innovators in Protection Technology. TemBreak. Total Protection, Complete Control. Catalogue No I20EJ Innovators in Protection Technology TemBreak Total Protection, Complete Control Catalogue No. 0 - IEJ Mission Statement. Terasaki aims to be the best supplier of circuit breakers and associated equipment

More information

Technical Journal September 2012

Technical Journal September 2012 Technical Journal September 2012 Earth leakage protection in polluted low voltage network In present day irrespective of the application be it in process industry or in IT industry, Pollution of electrical

More information

DX³ RCBO 6000A Phase + Neutral, neutral on left

DX³ RCBO 6000A Phase + Neutral, neutral on left 87045 LIMOGES Cedex Telephone number: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 DX³ RCBO 6000A CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation Connection...

More information

OPERATING AND MAINTENANCE MANUAL. Primary Current Injection Test Set. 750ADM-H mk2

OPERATING AND MAINTENANCE MANUAL. Primary Current Injection Test Set. 750ADM-H mk2 OPERATING AND MAINTENANCE MANUAL Product: Type: Primary Current Injection Test Set 750ADM mk2 750ADM-H mk2 DESIGNED AND MANUFACTURED BY: T & R Test Equipment Limited 15-16 Woodbridge Meadows, Guildford,

More information

XT IEC Power Control Manual Motor Protectors

XT IEC Power Control Manual Motor Protectors May 07 Product Selection Table 7. Rotary with Screw Terminals Global Ratings and North American Ratings Type and Type 2 Coordination Motor Protective Device with Thermal and Magnetic Trip Rated Uninterrupted

More information

File E47705 Vol. 7 Sec. 9 Page 1 Issued: and Report Revised:

File E47705 Vol. 7 Sec. 9 Page 1 Issued: and Report Revised: File E47705 Vol. 7 Sec. 9 Page 1 Issued: 1997-08-29 and Report Revised: 2005-06-30 DESCRIPTION PRODUCT COVERED: USL, CNL - Type Nos. 3RV1021, 3RV1121, 3RV1321 or 3RV1421, followed by combination of 0,

More information

INTRODUCTION. The plug-in connection on the cables and lightning arrestors, allows for easy installation and replacement.

INTRODUCTION. The plug-in connection on the cables and lightning arrestors, allows for easy installation and replacement. INTRODUCTION The Power Systems 44 kv MiniSub TM is the most compact system at this voltage available. Utilizing a deadfront termination and lightning arrestor setup, it eliminates the line top or side

More information

DX³ RCBO 6000 / 10 ka Phase + Neutral, neutral on left

DX³ RCBO 6000 / 10 ka Phase + Neutral, neutral on left 87045 LIMOGES Cedex Téléphone : 05 55 06 87 87 Télécopie : 05 55 06 88 88 DX³ RCBO 6000 / 10 ka CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation Connection...

More information

DPX earth leakage DPX 3 -I earth leakage

DPX earth leakage DPX 3 -I earth leakage 87045 LIMOGES Cedex Phone :+33 05 55 06 87 87 Fax :+33 05 55 06 88 88 DPX 3 250 + earth leakage Reference(s) : 420 225/ 227/ 228/229/ 255/ 257/ 258/ 259/ 285/ 287/ CONTENTS PAGES 1. USE 1 2. RANGE 1 3.

More information

On_Disc. 2 o/c1 BS 7671 applies to a lift installations b highway equipment c equipment on board ships d electrical equipment of machines.

On_Disc. 2 o/c1 BS 7671 applies to a lift installations b highway equipment c equipment on board ships d electrical equipment of machines. 1 PAPER 4 Sample Questions - C&G 2382 17th Edition full paper D 1 o/c 1 - A recommendation for the interval to the first periodic inspection shall be made by: a the installation electrician. b the main

More information

LG Moulded Case Circuit Breakers - 3P

LG Moulded Case Circuit Breakers - 3P Model Description ka at 415V GBN103/16 100AF/16AT 3P MCCB GBN103/20 100AF/20AT 3P MCCB GBN103/25 100AF/25AT 3P MCCB GBN103/32 100AF/32AT 3P MCCB GBN103/40 100AF/40AT 3P MCCB GBN103/50 100AF/50AT 3P MCCB

More information

DPX moulded case circuit breakers

DPX moulded case circuit breakers BREAKING AND PROTECTION DEVICES 10 / 2011 DPX moulded case circuit breakers DPX moulded case circuit breakers offer optimum solutions for the protection requirements of commercial and industrial installations.

More information

Technical Section: Miniature Circuit Breakers

Technical Section: Miniature Circuit Breakers MCBs and Accessories Data. Calibration With CBI Hydraulic- Magnetic Miniature Circuit Breakers, there is no effect on the fixed trip point at ambient temperature ranges from -5 C to +60 C. 2. Products

More information

01 Spectra Plus - Introduction

01 Spectra Plus - Introduction 01 Spectra Plus - Introduction Standard features Conforming to IS13947-2/EN60947 2 Compact dimensions Available in 3P & 4P High performance microprocessor protection release Wide overload setting from

More information

Miniature circuit 3.2 breakers 6kA type B SP. Miniature circuit 3.3 breakers curve B,C&D 10kA and 15kA. Protection Devices

Miniature circuit 3.2 breakers 6kA type B SP. Miniature circuit 3.3 breakers curve B,C&D 10kA and 15kA. Protection Devices Miniature circuit 3.2 breakers 6kA type B SP Miniature circuit 3.3 breakers curve B,C&D 10kA and 15kA Auxiliaries and 3.5 accessories Protection Devices RCCB add-on blocks 3.6 Miniature cicruit 3.8 breakers

More information

Jtec 10kA Miniature Circuit Breaker

Jtec 10kA Miniature Circuit Breaker EN 60898 Jtec 10kA Miniature Circuit Breaker Techna s JTEC range has been enthusiastically adopted by a diverse range of customers seeking a cost effective 10kA performance. Jtec MCBs are available in

More information

LEXIC Curv LIMOGES Cedex. Cats N (s) : /68/87/88, /48, /84/85, /76/77/95/96/97, /71/72 1.

LEXIC Curv LIMOGES Cedex. Cats N (s) : /68/87/88, /48, /84/85, /76/77/95/96/97, /71/72 1. 87045 LIMOGES Cedex Téléphone : 05 55 06 87 87 Télécopie : 05 55 06 88 88 LEXIC MCB s DX-H 80A, 100A, 125A Curv urves B and C CONTENTS PAGES 1. Description, use...1 2. Range...1 3. Overall dimensions...1

More information

A DIVISION OF TGC INTERNATIONAL LTD HIRE EQUIPMENT CATALOGUE

A DIVISION OF TGC INTERNATIONAL LTD HIRE EQUIPMENT CATALOGUE A DIVISION OF TGC INTERNATIONAL LTD HIRE EQUIPMENT CATALOGUE GENERATOR HIRE FUEL TANK HIRE LOADBANK HIRE CABLE HIRE DISTRIBUTION HIRE Rev 1: January 2015 Powerhire operating globally from our base in the

More information

CHAPTER 4 PROTECTION REQUIREMENTS

CHAPTER 4 PROTECTION REQUIREMENTS CHAPTER 4 PROTECTION REQUIREMENTS CHAPTER 4 PROTECTION REQUIREMENTS 4.1 General Means of protection for automatic disconnection against phase and earth faults shall be provided on the customer main switch.

More information

Level 3 Award in the Requirements for Electrical Installations BS 7671:2018 ( )

Level 3 Award in the Requirements for Electrical Installations BS 7671:2018 ( ) Level 3 Award in the Requirements for Electrical Installations BS 7671:2018 (2382-18) March 2018 Version 1.0 FAQs 1 18 th Edition IET Wiring Regulations 2018 FAQs When will the 18 th Edition of BS 7671

More information

NEPAL ELECTRICITY AUTHORITY (A Government of Nepal Undertaking)

NEPAL ELECTRICITY AUTHORITY (A Government of Nepal Undertaking) NEPAL ELECTRICITY AUTHORITY (A Government of Nepal Undertaking) Generation Directorate Medium Generation Operation and Maintenance Department SUNDARIJAL HYDROPOWER PLANT REHABILITATION PROJECT Electricity

More information

ELECTRICAL INSPECTOR EXAMINATION 14 November 2015 QUESTION AND ANSWER BOOKLET Time Allowed: Three hours

ELECTRICAL INSPECTOR EXAMINATION 14 November 2015 QUESTION AND ANSWER BOOKLET Time Allowed: Three hours Candidate Code No. IT 32 For Board Use Only Result Date Int Result Date Int ELECTRICAL INSPECTOR EXAMINATION 14 November 2015 QUESTION AND ANSWER BOOKLET Time Allowed: Three hours INSTRUCTIONS READ CAREFULLY

More information

DNX 3 MCB 4500 A / 6 ka Phase + Neutral, neutral on left side

DNX 3 MCB 4500 A / 6 ka Phase + Neutral, neutral on left side 87045 LIMOGES Cedex Telephone number: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 DNX 3 MCB 4500 A / 6 ka CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation

More information

ELECTRICIAN S THEORY EXAMINATION 11 September 2010 QUESTION AND ANSWER BOOKLET

ELECTRICIAN S THEORY EXAMINATION 11 September 2010 QUESTION AND ANSWER BOOKLET Candidate Code No. ET36 For Board Use Only Result Date Int Result Date Int ELECTRICIAN S THEORY EXAMINATION 11 September 2010 QUESTION AND ANSWER BOOKLET INSTRUCTIONS READ CAREFULLY Time Allowed: Three

More information

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931 Data Bulletin 0931DB0101 July 2001 Cedar Rapids, IA, USA Ground-Censor Ground-Fault Protection System Type GC Class 931 09313063 GT Sensor Shunt Trip of Circuit Interrupter Window Area for Conductors GC

More information

xboard safety, reliability effectively combining and performance safety, reliability and performance in commercial and industrial applications

xboard safety, reliability effectively combining and performance safety, reliability and performance in commercial and industrial applications xboard commercial and industrial panelboards xboard effectively combining safety, reliability and performance safety, reliability and performance in commercial and industrial applications NEW xboard (xdb)

More information

Innovators in Protection Technology Moulded Case Circuit Breaker Instruction Manual

Innovators in Protection Technology Moulded Case Circuit Breaker Instruction Manual Innovators in Protection Technology Moulded Case Circuit Breaker Instruction Manual 11-M61E TABLE OF CONTENTS HANDLING & MAINTENANCE Storage 1 Transport 1 STANDARD ENVIRONMENT 1 INSTALLATION AND CONNECTION

More information

School of Electrical and Information Engineering. ELEC High Voltage. University of Sydney. Dr Keith Mitchell. Engineering

School of Electrical and Information Engineering. ELEC High Voltage. University of Sydney. Dr Keith Mitchell. Engineering University of Sydney School of Electrical and Information Engineering Dr Keith Mitchell ELEC 5205 - High Voltage Engineering ELEC 5205 - High Voltage Engineering 3. Switchgear Types of Power System Switchgear

More information

GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector

GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector Catalog 0500CT9702R409 2009 Class 525/580 CONTENTS Description............................................. Page General Characteristics...................................

More information

Selection Guide. Control Circuit and Load Protection

Selection Guide. Control Circuit and Load Protection Selection Guide Control Circuit and Load Protection Circuit Protection Portfolio 1489-M Circuit Breakers Approved for branch circuit protection in the United States and Canada, and certified as Miniature

More information

Greater protection UNDERSTANDING THE 17TH EDITION CONSUMER UNITS / PRODUCT GUIDE

Greater protection UNDERSTANDING THE 17TH EDITION CONSUMER UNITS / PRODUCT GUIDE Greater protection UNDERSTANDING THE 17TH EDITION CONSUMER UNITS / PRODUCT GUIDE Summary of changes Simplifying the 17 th Edition Understanding new regulations is never easy... that s why we ve tried to

More information

013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS

013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS 013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEYLON ELECTRICITY BOARD SRI LANKA Specification for MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEB Specification

More information

Model 340i / 680i / 1220i DC drive product manual HG iss 8 1

Model 340i / 680i / 1220i DC drive product manual HG iss 8 1 Model 340i / 680i / 1220i DC drive product manual HG102938 iss 8 1 Sprint Electric Limited, Arundel, UK Tel. +44 (0)1903 730000 Fax. +44 (0)1903 730893 Email. info@sprint-electric.com www.sprint-electric.com

More information

Protection, Monitoring and Control Components for Low Voltage Equipment SELECTION GUIDE: INTERNATIONAL EDITION

Protection, Monitoring and Control Components for Low Voltage Equipment SELECTION GUIDE: INTERNATIONAL EDITION Protection, Monitoring and Control Components for Low Voltage Equipment SELECTION GUIDE: INTERNATIONAL EDITION [Terasaki is the world leader for circuit breakers in switchgear in the marine market] Terasaki

More information

Get detailed information on many digital or printed supports, or contact your Area Commercial Manager

Get detailed information on many digital or printed supports, or contact your Area Commercial Manager The RX 3 and DX-E ranges provide essential functions for the protection requirements of people and property in residential and small commercial buildings Two breaking capacities, 4500 and 6000 (IEC 60898-1)

More information

Utilization of Electric Power Laboratory 3 rd Year G2: Testing & Characteristic of MCCB Used in Commercial and Industrial Applications

Utilization of Electric Power Laboratory 3 rd Year G2: Testing & Characteristic of MCCB Used in Commercial and Industrial Applications G2: Testing & Characteristic of MCCB Used in Commercial and Industrial Applications Contents 1. Laboratory Objective... 4 2. MECHANICAL OPERATION TESTS... 4 2.1 Purpose... 4 2.2 Procedure... 4 2.3 Results...

More information

Rated Impulse withstand voltage U imp Main circuit Between terminals, AC3500V for 1 minute 12kV terminal group to earth Control circuits

Rated Impulse withstand voltage U imp Main circuit Between terminals, AC3500V for 1 minute 12kV terminal group to earth Control circuits 7 Technical Data Dielectric strength Circuit Withstand voltage (at 50/60 Hz) Rated Impulse withstand voltage U imp Main circuit Between terminals, AC3500V for 1 minute 12kV terminal group to earth Control

More information

ELECTRICAL INSPECTOR EXAMINATION 18 November 2017 QUESTION AND ANSWER BOOKLET Time Allowed: Three hours

ELECTRICAL INSPECTOR EXAMINATION 18 November 2017 QUESTION AND ANSWER BOOKLET Time Allowed: Three hours Candidate Code No. IT 36 For Board Use Only Result Date Int Result Date Int ELECTRICAL INSPECTOR EXAMINATION 18 November 2017 QUESTION AND ANSWER BOOKLET Time Allowed: Three hours INSTRUCTIONS READ CAREFULLY

More information

2000 Cooper Bussmann, Inc. Page 1 of 9 10/04/00

2000 Cooper Bussmann, Inc. Page 1 of 9 10/04/00 DO YOU KNOW THE FACTS ABOUT SINGLE-POLE INTERRUPTING RATINGS? YOU MAY BE IN TROUBLE! Typical plant electrical systems use three-phase distribution schemes. As an industry practice, short-circuit calculations

More information

Phase + Neutral, neutral on left side

Phase + Neutral, neutral on left side 87045 LIMOGES Cedex Téléphone : 05 55 06 87 87 Télécopie : 05 55 06 88 88 DX 3 MCB 10000 A / 16 ka CONTENTS PAGE 1. Description, use...1 2. Range...1 3. Overall dimensions...1 4. Preparation - Connection...1

More information

IT 28 ELECTRICAL INSPECTOR EXAMINATION ANSWER SCHEDULE. Question 1 Marks Reference Marking notes. (1 mark) ESR 57(3)(e)(ii)

IT 28 ELECTRICAL INSPECTOR EXAMINATION ANSWER SCHEDULE. Question 1 Marks Reference Marking notes. (1 mark) ESR 57(3)(e)(ii) IT 28 ELECTRICAL INSPECTOR EXAMINATION ANSWER SCHEDULE Notes:1. means that the preceding statement/answer earns 1 mark. 2. This schedule sets out the expected answers to the examination questions. The

More information