BS : C&G 2382 Outcomes 4

Size: px
Start display at page:

Download "BS : C&G 2382 Outcomes 4"

Transcription

1 BS : C&G 2382 Outcomes 4 Outcome 4 Protection for safety The candidate will be able to: 4.1 Identify the differences between basic and fault protection 4.2 State means of protection against electrical shock by a basic protection b fault protection c both basic and fault protection (excluding IT) d additional protection 4.3 Describe how the requirements for shock protection are affected by a value of the external loop Impedance (Ze) b compliance with Zs = Ze + R1 + R2 c compliance with tables 41.1, 41.2, 41.3, 41.4, 41.5 and 41.6 January 08 Legh Richardson 1

2 Protection Against Shock Methods of reducing the likelihood of electric shock 1. Limit the current flow to a person 2. Limit the current flow through a person 3. Limit the duration of shock

3 Protection Against Shock 1. Limit the current flow to a person (Basic Protection) Insulation (416) Class II equipment (412) Barriers and Enclosures (416.2) Non conducting location (418.1) restricted to trained personnel Obstacles and placing out of reach (417) Electrical Separation (413, 418.3) also (411.6) 2. Limit the current flow through a person Basic and Fault protection) SELV, PELV, FELV, RLV (414,411.8) Earth free protective earth bonding zone (418.2) 3. Limit the duration of shock (Fault Protection) Automatic Disconnection of Supply (RCDs, OPDs not shock protection) (411) RCDs in TT systems (411.5)

4 Protection for Safety Part 4 Protection from Electric Shock Basic Protection (Direct Contact) 1. Basic Insulation of Live Parts 2. Barriers or Enclosures Obstacles, Placing out of Reach 417.2, Class II Equipment January 08 Legh Richardson 4

5 Protection for Safety Part Basic Protection where supervised by a skilled or instructed person 1. Non-conducting Location (418.1) (No earth contact at sockets) 2. Earth Free local equipotential bonding (Faradays Cage) 3. Obstacles 4. Placing out of Reach 5. Electrical separation from more than one item of electrical equipment (common neutrals in IT systems)

6 Protection from Electric Shock Part Fault Protection (Indirect Contact) 1. Automatic Disconnection (ADS) 2. SELV, PELV, FELV The use of: 1. RCDs 2. Class II equipment Are additional measures added to ADS and ELV

7 Protection from Electric Shock Part 4 Additional Protection mA RCDs to be used on Socket outlets Where: 1. Socket outlets <20A 2. Mobile equipment < 32A Exceptions permitted to 1. above: 1. Under the supervision of a competent person (Industrial, commercial installation) 2. Identified and labelled for a specific item of equipment (freezers, fire alarm) January 08 Legh Richardson 7

8 Protection from Electric Shock Why RCD protection is provided for ordinary persons (Electricity is the same in the USA as in Europe!) January 08 Legh Richardson 8

9 Protection from Electric Shock January 08 Legh Richardson 9

10 Protection Against Shock January 08 Legh Richardson 10 Certain Conditions apply for Automatic protection (ADS) Under fault conditions the supply must be disconnected from a circuit within the time stated Table Have an Earth Fault Loop Impedance below or equal to Uo/Ia Tables 41.2, and 41.3 Zs U O Ia

11 BS : Protection from Electric Shock January 08 Legh Richardson 11 Fault Protection A low Earth Fault path controlling the duration of the fault Circuit Fuse Load Supply Origin of Installation Fault Earth-Fault Path Suppliers Earth Alternative Earth-Fault Path

12 Protection Against Shock 1. Stop the voltage potentials on exposed and extraneous conductive parts rising beyond the safety voltage - touch voltage in fault conditions AC systems : R 50V I DC Systems : R 120V a I a Where R is the resistance between two simultaneously touchable exposed/extraneous metalwork 1. Use an RCD for additional protection to detect earth fault currents at 50V Zs.I N (Where I N 30mA, t 40mS at 5I N, )

13 January 08 Legh Richardson 13 BS : Protection Fault Protection using SELV or/and local additional supplementary bonding by controlling the current flowing through the body

14 Protection against Shock January 08 Legh Richardson 14

15 Fault and short circuit protection January 08 Legh Richardson 15 Table 41.3 Max Zs for 0.4-5sec disconnection at 230V For the above devices : Type B Type C Type D 46/In 23/In 11.5/In

16 BS Update

17 Protection against Shock Prove that the following tables provides instantaneous disconnection for a BS EN Type B 32A MCB using tables 41.3, App 3, conforms to: Zs U O Ia Type B Type C Type D 48/In 24/In 12/In Type B Type C Type D 46/In 23/In 11.5/In 16 th Edition 17 th edition s = 1.5Ω = 1.5Ω = 5.In 48 32A 5 = 160A Zs = In = 1.44Ω = 1.44Ω multiplier for inst dist. Min.Amps.for inst.dist. (Appendix3) Max Zs (table41.2 Most manufacturer s data show 3-5 * In for instantaneous disconnection

18 MCB instantaneous tripping currents January 08 Legh Richardson 18 BS EN60898 and BS EN Instantaneous tripping currents Type Amperes 1 * > 2.7 I N * 4.0 I N 2* > 4.0 I N * 7.0 I N 3* > 7.0 I N * 10.0 I N 4* > 10 I N * 50.0 I N B > 3 I N 5.0 I N C > 5 I N 10.0 I N D > 10 I N 20.0 I N

19 Basic and Fault Protection Additional Protection for ADS in accordance with 415 Two methods are used: Protection by Residual Current Devices max value = 30mA, At 5 I N < 40ms Not recognized as a sole means of protection Supplementary Bonding Supplementary Bonding to localised and generalized zones To include local cross-bonding to all extraneous and exposed conductive parts with structural elements and metallic service pipes Where doubt exists to the effectiveness of supplementary bonding then it should be tested against R 50 / Ia for AC systems and R 120V / Ia for DC systems January 08 Legh Richardson 19

20 BS Update The use of Supplementary bonding ( ) Where doubt exists regarding the effectiveness of extraneous conductive parts having the same potential then: 50V 120V AC systems : R DC Systems : R I Where protection is given by a RCD then: a I a = 1.67kΩ Where protection is given by a 20A type B MCB then: R = 230 I a = = 100A or Appendix3 Fig3.4 = 100A 50 R'2' = = 0. 5Ω As long as the impedance of the circuit (exposed conductive part) is < 0.5Ω then the touch voltage on any simultaneously touchable metalwork for the time the fault is in operation will not rise above 50V 50 3

21 Protection Against Shock January 08 Legh Richardson 21 Protection provided by a Residual Current Device TN systems. Following condition applies: Regulation : Zs = Earth fault loop impedance in Ohms; Ian = rated residual operating current in Amps Protection in TT systems. The use of over current protective devices are not excluded although it is preferred to use a RCD with a disconnection time of not greater than 1 sec Regulation Zs I n 50V Ra Ia 50V RA = sum of all the resistances of earth electrode and protective conductors connected to the exposed conductive parts; Ia =the current causing automatic operation of the protective device with 1 sec

22 Protection against Shock Allowances from table TN systems disconnection time < 5sec for a distribution circuits TT systems disconnection time < 1sec for a distribution circuits Not covered by (>32A circuits) where disconnection times cannot be met then supplementary bonding must be applied January 08 Legh Richardson 22

23 January 08 Legh Richardson 23 BS : Protection Fault protection using an RCD to BS EN 61008/9 by controlling the duration of current flowing through the body You do not need an earth with RCDs but you do need an imbalance of current between the Line and Neutral

24 Basic and Fault Protection January 08 Legh Richardson TT earthing systems Where disconnection times cannot be met, Zs is too high, then the Use of RCD protection is used for Earth Fault currents

25 Basic and Fault protection in TT systems Where RCDs are used in series, each RCD can be earthed via an earth electrode The method of achieving the disconnection times as stated in and table 41.1 can be achieved by the use of: 1. RCD 2. OPD The former being preferred

26 Basic and Fault protection January 08 Legh Richardson TT earthing systems

27 Protection against shock and Fire January 08 Legh Richardson 27 The TT earthing system in conjunction with RCD fault protection

28 Protection against shock and Fire The use of and terminology of IT systems are more prevalent in the 17 th edition ( ) What is an IT system? High impedance to earth or no connection January 08 Legh Richardson 28

29 Basic and fault protection in IT systems IT systems Insulation Monitoring Devices IMDs Supply Source Main Switch. Gear Limiting Impedance Dist. Board RCBOs IMD Supply Electrode Single fault condition must behave like a TN system and disconnect within the times stated in 41.1 Final Circuits IMD IMD IMD

30 Basic and fault protection in IT systems IT system of protection V1 R1 Resistance of the Phase conductors and Transformer windings Point of first fault V3 R3 Resistance Fault path V2 R2 Resistance of Earth. Voltage across body in contact with exposed conductive part V poc (V2) = V S (R2 / R1 + R2 + R3) Where R3 is fixed by the distributor around 50,000 Ohms R2 is the resistance of the earth path across a human body (1.0 kohms) and R1 is the resistance of the phase conductor (1.0 Ohm) = 4.5V The Max voltage across body to the source = ,000 (Voltage drop sits outside EQBZ) January 08 Legh Richardson 30

31 Basic and Fault protection Methods of protection IT systems High impedance to earth means that the majority of the volt drop under fault conditions is outside of the equipotential bonding zone of the installation (Earth to phase monitoring device < 50kΩ causes an alarm to sound IEC 60364) suitable protective devices Insulation Monitoring Devices (IMD) 2. Residual Current Monitoring Devices (RCM s) 3. Insulation Fault Location Systems 4. Overcurrent Protective Devices 5. Residual Current Devices (RCD s) January 08 Legh Richardson 31

32 PELV and IT systems IT systems and earth monitoring equipment The earth conductor is not separated with PELV but monitored

33 Basic and Fault Protection FELV Systems Designed where SELV and PELV are not fulfilled (414) Basic Protection Insulation 2. Barriers and/or enclosures Fault Protection Exposed conductive parts shall be connected to the primary earthing system to provide Automatic disconnection in the event of a fault Methods of reducing voltage for a FELV system do not include 1. Autotransformers 2. Semiconductor devices 3. Potentiometers January 08 Legh Richardson 33

34 Basic and Fault Protection Reduced Low Voltage Systems (RLV) (Voltage range < 110V ac 55V to earth single phase, 63.5V ac to earth three phase) Basic Protection Insulation Barriers and Enclosures Fault Protection Automatic Disconnection < 5secs by OPD or RCD For RCDs: 50V I N x Zs ( I N x Zs 50V) See Table 41.6 January 08 Legh Richardson 34

35 Basic and Fault Protection January 08 Legh Richardson 35 Zs requirements for reduced voltage systems

36 Protection against shock Examples: 1/ What is the maximum Zs for a BS EN OPD protecting a 230V ac 20A Type B A3 radial final circuit? 2/ What is the maximum Zs for a 110V AC final circuit protected by a 32A Type C BS EN OPD? 3/ What is the maximum Zs for a BS 88 type 2 100A HRC fuse protecting a 400V sub-main cable to a distribution board?

37 Protection Against Shock Requirements for Basic and Fault protection for Electrical Equipment Where the protective measure of double or reinforced insulation is used for the complete installation or part of the installation, electrical equipment shall comply with the following: 1. equipment type tested and marked to the relevant standard equipment with basic insulation only shall have supplementary insulation applied in the process of being erected equipment having no insulation around live parts shall have reinforced insulation applied in the process of being erected relates directly to enclosures which is applicable to (ii) and (iii) above

38 Protection Against Shock Symbols used for indicating protection by insulation and Insulating enclosures must be rated at IP2X or IPXXB And shall only be removed by the use of a tool or a key

39 Protection Against Shock Separated Extra Low Voltage (SELV) 50V ac phase to earth and 120V DC Positive and negative terminals Supplied to Double Insulated Appliances and Equipment Supplied from: Double wound isolating transformer 2. Generator 3. Battery 4. Certain types of electronic SELV equivalent Equipment The Primary Earthing functions separated from the secondary earthing No secondary earth path back to source Nominal ELV voltage 50V ac and 120V DC January 08 Legh Richardson 39

40 Protection Against Shock Conditions for SELV systems (i) insulated to the highest voltage present (ii) enclosed in a separate sheath or conduit additional to the basic insulation (iii) conductors of higher voltages to be separated by earthed metallic screen or sheath (iv) where installed in a multi-core cage or grouped together with higher voltage conductors the SELV conductors are insulated to the highest voltage present (v) Separation via earthed metallic screen (vi) Physical separation SELV/PELV circuits >25V ac or 60V DC or equipment immersed underwater require additional protection by Insulation Barriers or/and enclosures January 08 Legh Richardson 40

41 January 08 Legh Richardson 41 BS C&G 2382 Outcomes 4 continued 4.4 Describe means of protection against fire, burns and harmful thermal effects and identify precautions where particular risks of danger of fire exists 4.5 Identify the difference between overcurrent and fault current 4.6 Identify the differences between overload currents, earth fault currents, short circuit currents and shock currents 4.7 Describe methods of overcurrent protection and the need for co-ordination with conductors and equipment. 4.8 State the requirements for protection against a voltage disturbances I. overvoltage II. undervoltage b electromagnetic disturbances.

42 Protection against Thermal effects Chapter 42 now combines together chapters 42 and 48 from the 16 th edition Scope: I. Heat generated by electrical equipment II. Ignition, combustion or degradation of materials III.Propagated fire and smoke to other fire compartments IV. Protection of safety services being cut off by the failure of electrical equipment January 08 Legh Richardson 42

43 Protection against Thermal effects protection against hot surface temperatures I. Mounted on a surface of low thermal conductance II. Be screened by low thermal materials III.Positioned to allow dissipation of heat protection against arcs and sparks I. Totally enclosed in arc resistant material II. Screened by arc resistant material III.Mounted to allow safe extinguishing of sparks IV. In compliance with its standard January 08 Legh Richardson 43

44 Protection against Thermal effects and Lamps and luminares must be positioned away from combustible structures and materials 1. < 100W = 0.5m 2. > 100W < 300W = 0.8m 3. > 300W < 500W = 1.0m where MIMS, busbar, powertrack, are not used then: 1. TT,TN systems should be protected by <300mA RCD 2. Where overheating and fire are high use a <30mA RCD 3. IT systems use IMD January 08 Legh Richardson 44

45 Protection against Thermal effects January 08 Legh Richardson Protection against burns

46 Problem Currents Examples: 1. Fault 2. Fault current (434) 3. Overload currents (433) 4. Overcurrents (435) 5. Short Circuit Current (434) 6. Earth Fault currents (435) 7. Shock Currents 8. Prospective Fault Current 9. Protective device s Operating current January 08 Legh Richardson 46

47 Overcurrent Protective Devices Types of Protective Devices (In) 432.1, 433.3, 434.3, BS 3036 Rewireable fuse links BS1361 Cartridge Fuse links BS 88 pt 2 & pt6 HRC or HBC Fuses BS 3871 MCBs - Miniature Circuit Breakers (old type) No longer included in BS7671 BS EN New type MCBs BS-EN MCCBs 10kA+ BS EN RCBOs Residual Current Breaker with overload protection January 08 Legh Richardson 47

48 Overcurrent protective devices January 08 Legh Richardson 48 Fusing Factor ii Actual Fu sin g Current ( I2) Fu sin g Factor = Rated Fu sin g Current ( In) Typical Fusing Factors for: BS88 Pt2 & pt BS BS1361/ BS3871 / BS EN Appendix 3 Time current characteristics

49 Coordination of Protective Devices January 08 Legh Richardson 49 Coordination of Protective Devices and Current Carrying Capacities of Conductors for overload and short circuit , ( a ) ( b) I I I B I I N B N 2. I 1 45 I Z Z Overload conditions Note: It is the tabulated current after taking external factors into consideration Compliance with (i), (ii), (iii) HBC BS88pt2.1, pt6 BS1361 Cartridge Fuse I I Circuit Breaker to BS EN and BS EN RCBO to BS EN b N I I t Z

50 Coordination of Protective Devices January 08 Legh Richardson 50 To Comply with the regs using BS In order to satisfy the terms in (ii) then : I N I Z To satisfy the fact that rewirables have a fusing factor up to 2 times Fusing Current = Fusing Factor * Fuse Rating = 2 * In I 2 = I and 2. I N 2 N I I Z and The use of Semi-enclosed or re-wireable fuses to BS3036 is not recommended for untrained persons Z I I I Z Z

51 Coordination of Protective devices January 08 Legh Richardson 51 Energy Let through (434) All electromechanical devices have a maximum breaking capacity Maximum amount of energy that the component will allow through without exploding or disintegrating General Equation E = I 2 t where P = Joules Seconds Note: The Resistance of the conductor can be regarded as negligible (but not zero) for the short time period and very high fault currents E t

52 Coordination of Protective Devices January 08 Legh Richardson 52 Short Circuit Protection Regulation States that: The regulation is satisfied if the time for disconnection is equal to or less than: 2 2 S. k t = 2 I The fault current must be cleared before the time given in the above equation Note: for short circuits between live conductors and for earth fault currents

53 Coordination of Protective Devices January 08 Legh Richardson and states that for the time that the earth fault exists the cpc must be able to dissipate the heat generated without damage to the other cables 2 I. t S = k. S K t = 2 I So as long as : S. K I. t Then the thermal characteristics of the cable are protected from the energy let through of the protective device The size of the cpc usually works out to be much smaller than anticipated, regulation is applicable and then this must be sized up according to table 54.7

54 Applying Circuit Design 2 Operating Characteristics of Protective Devices Energy Let Through (Heat) I (r.m.s.) I (r.m.s.) Energy (I 2 t) let through by fuse t Energy (I 2 t) let through by one cycle of AC current Fuse Link Cut-off t 0 t1 t2 t1 Pre-arcing I 2 t melting area Fuse duration t2 Total I 2 t area January 08 Legh Richardson 54

55 Energy let-through for MEM 10kA MCBs January 08 Legh Richardson 55

56 MCB Breaking Capacities MCB to BS3871 Obsolete from 2001 (blue) Circuit Breakers BS EN BS EN Category of Duty Prospective current (A) ICN (once only) ka ICS (repeatable) ka M M M M M M January 08 Legh Richardson 56

57 Energy let-through video GEC BS 88 Fuse protection

58 Applying Circuit Design 2 Operating Characteristics of Protective Devices Electromagnetic Energy t Electromagnetic stress(i 2 ) let through by one cycle of AC current Fuse Link Cut-off Fuse duration I 2 (peak) Electromagnetic stress proportional to (I 2 ) peak current January 08 Legh Richardson 58

59 Discrimination of OPDs Discrimination of Protective Devices 10 6 A I2 characteristics of HBC fuses Rated Current plotted against Amperes squared 10 5 A Total (I 2 t) 10 4 A Pre-arcing (I 2 t) 10 3 A 30A 40A 50A 60A 80A 100A January 08 Legh Richardson 59

60 Ferraz Shawmut BS88 cartridge fuses I 2 t Characteristics Discrimination achieved when downstream fuse is ½ the size of the upstream OPD Ampere Fuse rating

61 Protection against Fault Currents Discrimination of Protective Devices to A X 300A 100A Y 80A? 40A 30A 30A 50A Z Discrimination of devices must take place to reduce danger and inconvenience If fuse Z blows then fuse Y should be of such size that it can withstand the energy let through without disconnecting January 08 Legh Richardson 61

62 Coordination of OPDs January 08 Legh Richardson 62 The example, shows the superimposed characteristics of a 5 A semi-enclosed fuse and a 10 A miniature circuit breaker which we shall assume are connected in series. If a fault current of 50 A flows, the fuse will operate in 0.56 s whilst the circuit breaker would take 24 s to open. Clearly the fuse will operate first and the devices have discriminated. However, if the fault current is 180 A, the circuit breaker will open in s, well before the fuse would operate, which would take 0.12 s. In this case, there has been no discrimination.

63 Coordination of OPDs January 08 Legh Richardson 63 Graph A shows discrimination from instantaneous disconnection of the 16A MCB from the 32A fuse at 180A Graph B shows poor discrimination only starting at 100A in an overload condition but none for short circuit

64 Protection against overcurrents Positioning of Device and 434 Where a conductors diameter reduces along the line of a cable run a method of protection is required for that part of the cable which has a reduced cross sectional area Examples of reduced cable conductors are: Fused spur on a ring final circuit Installation method changed (overhead to underground) Type of cable has changed (PVC in conduit to MIMS) Ambient change in temperature (Boiler house to outside) Rules for termination between reduction in current carrying capacity and Protective Device Not Exceed 3m in length 2. Be erected to minimise risk of fault current 3. Be erected to minimise fire and danger to persons January 08 Legh Richardson 64

65 Protection against Overcurrent Omission of protective devices for safety reasons Used where unexpected disconnection would cause a dangerous situation 1. The exciter circuit of a rotating machine 2. The supply circuit of a lifting magnet 3. The secondary circuit of a current transformer 4. A circuit supplying a fire extinguishing device 5. A circuit supplying a safety circuit (fire or gas alarm) 6. A circuit supplying medical equipment in IT systems January 08 Legh Richardson 65

66 January 08 Legh Richardson 66 Voltage and Electromagnetic disturbances 441 Overvoltages due to HV and LV faults Scope (See note) 1. HV faults to earth at the substation Loss of supply neutral on LV systems Line to Neutral Short Circuit in LV systems Accidental earthing of a line conductor to earth in IT systems Stress Voltages created by HV currents circulating around exposed conductive parts producing an electromagnetic effect thus producing a secondary fault voltage (stress voltage U1 and U2) rules for designers and installers of substations 1. Quality of system earth 2. Maximum level of earth fault current 3. Resistance of earthing arrangements

67 Voltage and Electromagnetic disturbances January 08 Legh Richardson 67

68 HV fault conditions affecting LV systems January 08 Legh Richardson 68

69 HV fault conditions affecting LV systems January 08 Legh Richardson 69

70 HV fault conditions affecting LV systems January 08 Legh Richardson 70

71 January 08 Legh Richardson 71 Voltage and Electromagnetic disturbances 443 Overvoltage requirements

72 Problem Voltages 445 Undervoltages Suitable precautions shall be taken to provide protection when the voltage dips or is reduced No automatic restarting of rotating machinery (Note: see external classifications appendix 5) January 08 Legh Richardson 72

3 o/c 2 An area or temporary structure used for display, marketing or sales is defined as a a booth b a stand c an exhibition d a show.

3 o/c 2 An area or temporary structure used for display, marketing or sales is defined as a a booth b a stand c an exhibition d a show. 1 PAPER 7 Sample Questions - C&G 2382 17th Edition paper C 1 o/c 1 - BS 7671 relates to permanent and temporary installations for equipment on: a marinas. b ships. c equipment on aircraft. d railway traction

More information

On_Disc. 2 o/c1 BS 7671 applies to a lift installations b highway equipment c equipment on board ships d electrical equipment of machines.

On_Disc. 2 o/c1 BS 7671 applies to a lift installations b highway equipment c equipment on board ships d electrical equipment of machines. 1 PAPER 4 Sample Questions - C&G 2382 17th Edition full paper D 1 o/c 1 - A recommendation for the interval to the first periodic inspection shall be made by: a the installation electrician. b the main

More information

IET Wiring Regulations (BS 7671:2008+A3:2015) - SECTION 717 MOBILE OR TRANSPORTABLE UNITS

IET Wiring Regulations (BS 7671:2008+A3:2015) - SECTION 717 MOBILE OR TRANSPORTABLE UNITS IET Wiring Regulations (BS 7671:2008+A3:2015) - SECTION 717 MOBILE OR TRANSPORTABLE UNITS 717.1 Scope The particular requirements of this section apply to a.c. and d.c. installations for mobile or transportable

More information

City & Guilds 2381 Test 2382 Level 3. Which one of these electrical installations does BS 7671:2008 not apply to:

City & Guilds 2381 Test 2382 Level 3. Which one of these electrical installations does BS 7671:2008 not apply to: City & Guilds 2381 Test 2382 Level 3 Q1 Which one of these electrical installations does BS 7671:2008 not apply to: Temporary Construction sites Distributor s Equipment Caravans Public Premises Q2 Which

More information

Power systems Protection course

Power systems Protection course Al-Balqa Applied University Power systems Protection course Department of Electrical Energy Engineering Dr.Audih 1 Part 3 Protective Devices Fuses & Circuit Breakers 2 Introduction: Fuse Is advice used

More information

SELECT MEMBERSHIP NUMBER Full Installation 75% new and 25% alteration to exsisting

SELECT MEMBERSHIP NUMBER Full Installation 75% new and 25% alteration to exsisting The Electrical Contractors Association SELECT MEMBERSHIP NUMBER 15019 ELECTRICAL INSTALLATION CERTIFICATE (REQUIREMENTS FOR ELECTRICAL INSTALLATIONS - BS 7671 [IET WIRING REGULATIONS]) EI Copyright The

More information

Electrical Protection

Electrical Protection Electrical Protection Excessive current in any electrical circuit is hazardous and not desired, and these maybe caused by the following; 1. Overloads, and 2. Short-circuits. Overload Currents: These are

More information

Effective discrimination of protective devices

Effective discrimination of protective devices Effective discrimination of protective devices In the event of a fault occurring on an electrical installation only the protective device nearest to the fault should operate,leaving other healthy circuits

More information

CLP POWER HONG KONG LIMITED. SUPPLY RULES March 2001

CLP POWER HONG KONG LIMITED. SUPPLY RULES March 2001 CLP POWER HONG KONG LIMITED SUPPLY March 2001 ADVISORY SERVICE Advice concerning matters relating to the supply of electricity may be obtained free of charge from the Company. OTHER COMPANY PUBLICATIONS

More information

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 2

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 2 The University of New South Wales School of Electrical Engineering and Telecommunications Industrial and Commercial Power Systems Topic 2 SWITCHBOARDS Overview Also called Switchgear and Controlgear Assembly

More information

ELECTRICAL INSPECTOR EXAMINATION 18 November 2017 QUESTION AND ANSWER BOOKLET Time Allowed: Three hours

ELECTRICAL INSPECTOR EXAMINATION 18 November 2017 QUESTION AND ANSWER BOOKLET Time Allowed: Three hours Candidate Code No. IT 36 For Board Use Only Result Date Int Result Date Int ELECTRICAL INSPECTOR EXAMINATION 18 November 2017 QUESTION AND ANSWER BOOKLET Time Allowed: Three hours INSTRUCTIONS READ CAREFULLY

More information

Earthing Principles. Symmetra PX 250/500 kw

Earthing Principles. Symmetra PX 250/500 kw Earthing Principles Symmetra PX 250/500 kw Table of Contents Earthing Principles... 1 Decoding the Earthing Types... 1 TN Systems... 2 Characteristics... 2 Reference to IEC/EN 60364-4-41 413.1.3... 2

More information

Characteristics of LV circuit breakers Releases, tripping curves, and limitation

Characteristics of LV circuit breakers Releases, tripping curves, and limitation Characteristics of LV circuit breakers Releases, tripping curves, and limitation Make, Withstand & Break Currents A circuit breaker is both a circuit-breaking device that can make, withstand and break

More information

Guidance for Low Voltage Electrical Installations

Guidance for Low Voltage Electrical Installations Guidance for Low Voltage Electrical Synopsis This document provides information in support of GI/RT7007 Low Voltage Electrical. Signatures removed from electronic version Submitted by Anne E Blakeney Standards

More information

Range 16A to 63A. Sensitivity 30mA, 100mA, 300mA, 500mA. Execution Double Pole, Four Pole. Specification IEC / IS : 2000

Range 16A to 63A. Sensitivity 30mA, 100mA, 300mA, 500mA. Execution Double Pole, Four Pole. Specification IEC / IS : 2000 The flow of current through electrical facilities always involves risks. Poorly insulated equipment, faulty wires and incorrect use of an electrical devise cause currents to flow through the wrong path

More information

EARTHING YOUR QUESTIONS ANSWERED

EARTHING YOUR QUESTIONS ANSWERED 18 EARTHING YOUR QUESTIONS ANSWERED By Geoff Cronshaw What are earthed and unearthed systems? What are the requirements of BS 7671? What are the advantages and disadvantages of the various types of earthing

More information

Miniature Circuit-Breakers (MCBs)

Miniature Circuit-Breakers (MCBs) Product Overview Miniature Circuit-Breakers (MCBs) Design Tripping characteristics Rated current I n Rated breaking capacity Power supply company product range 5SP3 E 16 - A Standard product range 5SQ2

More information

SLOVAK UNIVERSITY OF TECHNOLOGY Faculty of Material Science and Technology in Trnava ELECTRICAL ENGINEERING AND ELECTRONICS.

SLOVAK UNIVERSITY OF TECHNOLOGY Faculty of Material Science and Technology in Trnava ELECTRICAL ENGINEERING AND ELECTRONICS. SLOVAK UNIVERSITY OF TECHNOLOGY Faculty of Material Science and Technology in Trnava ELECTRICAL ENGINEERING AND ELECTRONICS Róbert Riedlmajer TRNAVA 2007 Unit 14 - Fundamentals of power system protection

More information

DX 3 MCBs. Choice of DX 3 MCBs for capacitor banks. Technical data

DX 3 MCBs. Choice of DX 3 MCBs for capacitor banks. Technical data Specifications IS/IEC 60898-1 2002 Number of poles SP, SPN, DP, TP, TPN, FP Characteristics C & D Curve Breaking capacity 10 ka 0.5 A to 63 A as per IS/IEC 60898-1 2002 16 ka for 0.5 A to 25 A as per IEC

More information

Initial and Periodic Inspection and Testing of Electrical Installations ( ) Sample Test

Initial and Periodic Inspection and Testing of Electrical Installations ( ) Sample Test Initial and Periodic Inspection and Testing of Electrical Installations (2391-052) Sample Test Version 1.1 January 2018 Please note this is not a complete sample theory exam, this document consists of

More information

DNX 3 MCB 4500 A / 6 ka Phase + Neutral, neutral on left side

DNX 3 MCB 4500 A / 6 ka Phase + Neutral, neutral on left side 87045 LIMOGES Cedex Telephone number: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 DNX 3 MCB 4500 A / 6 ka CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation

More information

Low Voltage Power Supplies in Electrified Areas

Low Voltage Power Supplies in Electrified Areas Low Voltage Power Supplies in Electrified Areas Synopsis This document mandates requirements for control of return and stray currents and the management of earthing for low voltage power supplies in electrified

More information

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 6

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 6 The University of New South Wales School of Electrical Engineering and Telecommunications Industrial and Commercial Power Systems Topic 6 PROTECTIONS 1 FUNCTION OF ELECTRICAL PROTECTION SYSTEMS Problems:

More information

1 This instrument must only be used by a competent and trained person and operated in strict accordance with the instructions.

1 This instrument must only be used by a competent and trained person and operated in strict accordance with the instructions. 1 This instrument must only be used by a competent and trained person and operated in strict accordance with the instructions. KYORITSU will not accept liability for any damage or injury caused by misuse

More information

Paramount HRC Cartridge

Paramount HRC Cartridge Paramount HRC Cartridge Eaton MEM HRC fuselinks are manufactured to exacting standards using precision assembly methods and undergo rigorous quality checking before dispatch including resistance testing

More information

Level 3 Award in the Requirements for Electrical Installations BS 7671:2018 ( )

Level 3 Award in the Requirements for Electrical Installations BS 7671:2018 ( ) Level 3 Award in the Requirements for Electrical Installations BS 7671:2018 (2382-18) March 2018 Version 1.0 FAQs 1 18 th Edition IET Wiring Regulations 2018 FAQs When will the 18 th Edition of BS 7671

More information

ELECTRICIANS REGULATIONS EXAMINATION 30 June 2012 QUESTION AND ANSWER BOOKLET

ELECTRICIANS REGULATIONS EXAMINATION 30 June 2012 QUESTION AND ANSWER BOOKLET ER47 Candidate Code No. For Board Use Only Result Date Result Date Int ELECTRICIANS REGULATIONS EXAMINATION 30 June 2012 QUESTION AND ANSWER BOOKLET INSTRUCTIONS READ CAREFULLY Int Time Allowed: Three

More information

DX³ 4-pole RCBO 6000 A/10 ka

DX³ 4-pole RCBO 6000 A/10 ka 87045 LIMOGES Cedex Telephone number: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 DX³ 4-pole RCBO CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation - Connection...

More information

Major changes within the New 18 th Edition Wiring Regulations announced by The IET

Major changes within the New 18 th Edition Wiring Regulations announced by The IET Major changes within the New 18 th Edition Wiring Regulations announced by The IET BS 7671:2018 Requirements for Electrical Installations will be issued on 2 nd July 2018 and is intended to come into effect

More information

The Impact of the 18 th edition (BS 7671:2018)

The Impact of the 18 th edition (BS 7671:2018) The Impact of the 18 th edition (BS 7671:2018) In this article, Geoff Cronshaw looks at some of the proposed changes in the DPC (draft for public comment) for electrical installations, focusing on Section

More information

Circuit Breaker Selection was affected by Seventeenth Edition Amendment from the First of July 2015

Circuit Breaker Selection was affected by Seventeenth Edition Amendment from the First of July 2015 Circuit Breaker Selection was affected by Seventeenth Edition Amendment from the First of July 2015 Abstract A new compensation factor, Cmin, has been included in the UK regulation for protection from

More information

IT 28 ELECTRICAL INSPECTOR EXAMINATION ANSWER SCHEDULE. Question 1 Marks Reference Marking notes. (1 mark) ESR 57(3)(e)(ii)

IT 28 ELECTRICAL INSPECTOR EXAMINATION ANSWER SCHEDULE. Question 1 Marks Reference Marking notes. (1 mark) ESR 57(3)(e)(ii) IT 28 ELECTRICAL INSPECTOR EXAMINATION ANSWER SCHEDULE Notes:1. means that the preceding statement/answer earns 1 mark. 2. This schedule sets out the expected answers to the examination questions. The

More information

ELECTRICIAN S THEORY EXAMINATION 11 September 2010 QUESTION AND ANSWER BOOKLET

ELECTRICIAN S THEORY EXAMINATION 11 September 2010 QUESTION AND ANSWER BOOKLET Candidate Code No. ET36 For Board Use Only Result Date Int Result Date Int ELECTRICIAN S THEORY EXAMINATION 11 September 2010 QUESTION AND ANSWER BOOKLET INSTRUCTIONS READ CAREFULLY Time Allowed: Three

More information

Phase + Neutral, neutral on left side

Phase + Neutral, neutral on left side 87045 LIMOGES Cedex Téléphone : 05 55 06 87 87 Télécopie : 05 55 06 88 88 DX 3 MCB 10000 A / 16 ka CONTENTS PAGE 1. Description, use...1 2. Range...1 3. Overall dimensions...1 4. Preparation - Connection...1

More information

Unified requirements for systems with voltages above 1 kv up to 15 kv

Unified requirements for systems with voltages above 1 kv up to 15 kv (1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) (Corr.1 June 2018) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements

More information

Renewable sources of electricity a brief overview

Renewable sources of electricity a brief overview Micro generation 11 Renewable sources of electricity a brief overview THE SCOPE of the 17th Edition is wider and contains many new requirements, including additional requirements to ensure the safe connection

More information

Electric Vehicle Charging Safety Guidelines Part 2: Selection and Installation Edition DRAFT

Electric Vehicle Charging Safety Guidelines Part 2: Selection and Installation Edition DRAFT Date of publication: 1 November 2016Not yet published Issued by: Mark Wogan, Manager Energy Safety WorkSafe New ZealandNot yet issued Electric Vehicle Charging Safety Guidelines Part 2: Selection and Installation

More information

DX³ RCBO 4500/6 ka Phase + Neutral, neutral on left

DX³ RCBO 4500/6 ka Phase + Neutral, neutral on left 87045 LIMOGES Cedex Telephone number: +33 5 55 06 87 87 Fax: +33 5 55 06 88 88 DX³ RCBO 4500/6 ka CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation Connection...

More information

GUIDELINES ON ELECTRICAL SAFETY AT WORKPLACES

GUIDELINES ON ELECTRICAL SAFETY AT WORKPLACES MINISTRY OF LABOUR, INDUSTRIAL RELATIONS AND EMPLOYMENT GUIDELINES ON ELECTRICAL SAFETY AT WORKPLACES Occupational Safety & Health Inspectorate These guidelines should be used with approved standards:

More information

Phase + Neutral, neutral on right side

Phase + Neutral, neutral on right side 87045 LIMOGES Cedex Telephone number: +33 5 55 06 87 87 Fax: +33 5 55 06 88 88 DX 3 MCB 6000 A / 10 ka Cat.. N (s): 4 074 67 / 68 / 69 / 70 / 71 / 72 / 73 / 74 / 75 / 76 / 77 / 78 / 79 ; 4 077 33 / 34

More information

FINAL-ER 42 Electrician Regulations Answer Schedule

FINAL-ER 42 Electrician Regulations Answer Schedule FINAL-ER 42 Electrician Regulations Answer Schedule Notes:1. (1 mark) means that the preceding statement/answer earns 1 mark. 2. This schedule sets out the expected answers to the examination questions.

More information

Cascading & Discrimination

Cascading & Discrimination Cascading & Discrimination Typical LV System Level 1 ACBs - 6300A General LV Switchboard Level 2 ACB - 3200A MCCB 3200A Level 3 MCCB 1250A Fuses 630A Switchboard, Panelboard or MCC Level 4 MCBs - 100A

More information

RE-PR3-E-86&105 3-Phase Panel Mount 86 and 105kW

RE-PR3-E-86&105 3-Phase Panel Mount 86 and 105kW Page 1 of 6 3-Phase Panel Mount 86 and 105kW Features: Benefits: 0-10Vdc, 0-5Vdc, 4-20mA or manual via potentiometer control input Over temperature protection with auto reset Enclosed panel mounting Efficient

More information

ELECTRICIAN S THEORY EXAMINATION 19 June 2010 QUESTION AND ANSWER BOOKLET

ELECTRICIAN S THEORY EXAMINATION 19 June 2010 QUESTION AND ANSWER BOOKLET Candidate Code No. ET34 For Board Use Only Result Date Int Result Date Int ELECTRICIAN S THEORY EXAMINATION 19 June 2010 QUESTION AND ANSWER BOOKLET INSTRUCTIONS READ CAREFULLY Time Allowed: Three hours

More information

Sentry Technical. Miniature Circuit Breakers (MCBs) Standards and approvals. Description. Technical specification

Sentry Technical. Miniature Circuit Breakers (MCBs) Standards and approvals. Description. Technical specification 543 technical hotline +44 ()1268 56372 Standards and approvals Sentry MCBs are designed to fully comply with the relevant requirements of BS EN 6898: 23. They all feature positive contact status indication

More information

WIRING MATTERS SEPTEMBER 2018

WIRING MATTERS SEPTEMBER 2018 WIRING MATTERS SEPTEMBER 2018 The 18 th Edition (BS 7671:2018) launch - revisited This is the second of two articles on the launch of the 18 th Edition (BS 7671:2018). The first article covered electric

More information

Miniature & Moulded Case

Miniature & Moulded Case Miniature & Moulded Case MCB OPERATION MAGNETIC OPERATION The short time protection (typically less than 1 second after energising) of the MCB is defined as the magnetic operation. 1 2 3 THERMAL OPERATION

More information

NH-Fuse system Low voltage

NH-Fuse system Low voltage 38103-FER NH-fuses A4-engl 22.10.2003 15:50 Uhr Seite 3 NH-Fuse system Low voltage 38103-FER NH-fuses A4-engl 22.10.2003 14:01 Uhr Seite 2 Utilization NH-fuses gg am gtr NH-fuses Utilization Categories

More information

Electric Vehicle Charging Safety Guidelines Part 2: Selection and Installation

Electric Vehicle Charging Safety Guidelines Part 2: Selection and Installation 86 Customhouse Quay PO Box 165, Wellington 6140 New Zealand Date of publication: 1 November 2016 Issued by: Mark Wogan, Manager Energy Safety WorkSafe New Zealand Electric Vehicle Charging Safety Guidelines

More information

Ordinary Level Physics SOLUTIONS: EFFECTS OF AN ELECTRIC CURRENT

Ordinary Level Physics SOLUTIONS: EFFECTS OF AN ELECTRIC CURRENT Ordinary Level Physics SOLUTIONS: EFFECTS OF AN ELECTRIC CURRENT Safety Features and kilowatt hours The unit of energy is called the kilowatt hour One kilowatt hour is the amount of energy used by a 1000

More information

ELECTRICAL INSPECTOR EXAMINATION 14 November 2015 QUESTION AND ANSWER BOOKLET Time Allowed: Three hours

ELECTRICAL INSPECTOR EXAMINATION 14 November 2015 QUESTION AND ANSWER BOOKLET Time Allowed: Three hours Candidate Code No. IT 32 For Board Use Only Result Date Int Result Date Int ELECTRICAL INSPECTOR EXAMINATION 14 November 2015 QUESTION AND ANSWER BOOKLET Time Allowed: Three hours INSTRUCTIONS READ CAREFULLY

More information

013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS

013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS 013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEYLON ELECTRICITY BOARD SRI LANKA Specification for MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEB Specification

More information

RESIDUAL CURRENT CIRCUIT BREAKER

RESIDUAL CURRENT CIRCUIT BREAKER Quality Features Mid Trip - Different knob position to indicate whether the device is Switched OFF by a fault or Switched OFF manually Inscription Window - Ensures circuit identification and hence reduces

More information

DX³ RCBO 6000 A Phase + Neutral, neutral right side

DX³ RCBO 6000 A Phase + Neutral, neutral right side 87045 LIMOGES Cedex Téléphone : 05 55 06 87 87 Télécopie : 05 55 06 88 88 DX³ RCBO 6000 A CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation Connection... 1

More information

Electrical. Earthing & Bonding. Installation Techniques. Learning Notes MODULE 2.2 UNIT PHASE:2

Electrical. Earthing & Bonding. Installation Techniques. Learning Notes MODULE 2.2 UNIT PHASE:2 Electrical Learning Notes MODULE 2.2 UNIT 2.2.6 Installation Techniques Earthing & Bonding PHASE:2 Table of Contents INTRODUCTION... 3 DEFINITIONS... 4 EARTHING... 5 TYPES OF SYSTEM EARTHING... 10 EQUIPOTENTIAL

More information

The impact of the 18 th Edition (BS 7671:2018) Sections 722, 753 and [new] 730

The impact of the 18 th Edition (BS 7671:2018) Sections 722, 753 and [new] 730 The impact of the 18 th Edition (BS 7671:2018) Sections 722, 753 and [new] 730 In this article, Geoff Cronshaw looks at the impact that some of the proposed changes in the DPC (draft for public comment)

More information

Key elements of the AS3000 Wiring standards and some of the recent changes.

Key elements of the AS3000 Wiring standards and some of the recent changes. Key elements of the AS3000 Wiring standards and some of the recent changes. Dean of Engineering Steve Mackay Worked for 30 years in Industrial Automation 30 years experience in mining, oil and gas, electrical

More information

R.C.B.O. SP / 1 module

R.C.B.O. SP / 1 module 87045 LIMOGES Cedex - France Telephone : (+33) 5 55 06 87 87 Fax : (+33) 5 55 06 88 88 R.C.B.O. SP / 1 module 6064 04 6064 64 05 6064 10 6064 11 6064 12 CONTENTS PAGES 1. Description, use... 1 2. Range...

More information

ELECTRICAL INSTALLER EXAMINATION 18 November 2017 QUESTION AND ANSWER BOOKLET

ELECTRICAL INSTALLER EXAMINATION 18 November 2017 QUESTION AND ANSWER BOOKLET Candidate Code No. EIN15 For Board Use Only Result Date Int Result Date Int ELECTRICAL INSTALLER EXAMINATION 18 November 2017 QUESTION AND ANSWER BOOKLET INSTRUCTIONS READ CAREFULLY Time Allowed: Three

More information

MAGNETIC MOTOR STARTERS

MAGNETIC MOTOR STARTERS Chapter 6 MAGNETIC MOTOR STARTERS 1 The basic use for the magnetic contactor is for switching power in resistance heating elements, lighting, magnetic brakes, or heavy industrial solenoids. Contactors

More information

Step 1: Collection of required data

Step 1: Collection of required data Step 1: Collection of required data If the relevant parameters of the interfaces are known, it is possible to dimension ASSEMBLIES 3 Installation and environmental conditions 4 Operating and servicing

More information

Fundamentals and Earthing

Fundamentals and Earthing Ανάλυση και Εφαρμογή κανονισμών BS 7671 για ηλεκτρολογικές εγκαταστάσεις (17 η έκδοση, 3 η τροποποίηση)» Μονοεπιχειρησιακό πρόγραμμα εγκεκριμένο από την ΑνΑΔ Fundamentals and Earthing Ιούνιος 2017 Εισηγητής

More information

Technical information No. 01. IT systems. The basis for reliable power supply

Technical information No. 01. IT systems. The basis for reliable power supply IT systems The basis for reliable power supply FA01en/01.2004 IT systems The basis for reliable power supply in critical areas The advantages of sophisticated industrial systems can only be of use, if

More information

SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS - ELECTRICAL

SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS - ELECTRICAL SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS - ELECTRICAL This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly.

More information

Electrical Awareness and Considerations

Electrical Awareness and Considerations Electrical Awareness and Considerations By David Taylor FIHE MIET IEng Objectives Awareness of specifications. Awareness of Distribution Network Operators (DNO) earthing arrangements. Awareness of basic

More information

Element C8.3 Installation, Use and Inspection of Electrical Systems

Element C8.3 Installation, Use and Inspection of Electrical Systems .3 Installation, Use and Inspection of Electrical Systems Duty Holders Electricity at Work Regs 1989 EWR Employers and Self Employed Comply with regs as far as they are under their control Managers of

More information

On-Site Guide (BS 7671:2008 Wiring Regulations, incorporating Amendment No 1:2011)

On-Site Guide (BS 7671:2008 Wiring Regulations, incorporating Amendment No 1:2011) (BS 7671:2008 Wiring Regulations, incorporating Amendment No 1:2011) Author: IET Publications (edited by Mark Coles) Book details Author: IET Publications (edited by Mark Coles) Year: 2011 Format: Paperback,

More information

Btdin-RS RCBO 2p Phase + Neutral, neutral on right

Btdin-RS RCBO 2p Phase + Neutral, neutral on right Viale Borri 231, 21100 Varese - Italy RCBO 2p CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation Connection... 1 5. General characteristics... 2 6. Compliance

More information

ES5 Security Theory/Regulations Answer Schedule

ES5 Security Theory/Regulations Answer Schedule ES5 Security Theory/Regulations Answer Schedule Notes:1. means that the preceding statement/answer earns 1 mark. 2. This schedule sets out the expected answers to the examination questions. The marker

More information

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931 Data Bulletin 0931DB0101 July 2001 Cedar Rapids, IA, USA Ground-Censor Ground-Fault Protection System Type GC Class 931 09313063 GT Sensor Shunt Trip of Circuit Interrupter Window Area for Conductors GC

More information

LEXIC Curv LIMOGES Cedex. Cats N (s) : /68/87/88, /48, /84/85, /76/77/95/96/97, /71/72 1.

LEXIC Curv LIMOGES Cedex. Cats N (s) : /68/87/88, /48, /84/85, /76/77/95/96/97, /71/72 1. 87045 LIMOGES Cedex Téléphone : 05 55 06 87 87 Télécopie : 05 55 06 88 88 LEXIC MCB s DX-H 80A, 100A, 125A Curv urves B and C CONTENTS PAGES 1. Description, use...1 2. Range...1 3. Overall dimensions...1

More information

ELECTRICIAN S THEORY EXAMINATION 20 June 2015 QUESTION AND ANSWER BOOKLET

ELECTRICIAN S THEORY EXAMINATION 20 June 2015 QUESTION AND ANSWER BOOKLET Candidate Code No. ET54 For Board Use Only Result Date Int Result Date Int ELECTRICIAN S THEORY EXAMINATION 20 June 2015 QUESTION AND ANSWER BOOKLET INSTRUCTIONS READ CAREFULLY Time Allowed: Three hours

More information

This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly.

This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly. SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS (ELEC) This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly.

More information

SWITCHBOARDS (LV and MV)

SWITCHBOARDS (LV and MV) ELEC9713 Industrial and Commercial Power Systems SWITCHBOARDS (LV and MV) 1. Introduction Depending on the size of the building or factory site and whether the supply is high voltage or low voltage, there

More information

Btdin RCBO 6000A up to 63A (2P)

Btdin RCBO 6000A up to 63A (2P) Index Pages 1. Descripton... 2 2. Product range... 2 3. Overall dimensions... 2 4. Fixing Connection... 3 5. Generl characteristics.... 4-29 6. Compliance - Approvals... 30 7. Curves... 30-34 8.Auxiliaries-

More information

ELECTRICAL APPLIANCE SERVICEPERSON (QUALIFIED) EXAMINATION

ELECTRICAL APPLIANCE SERVICEPERSON (QUALIFIED) EXAMINATION 23 June 2018 Time Allowed: 2 Hours ELECTRICAL APPLIANCE SERVICEPERSON (QUALIFIED) EXAMINATION Check the label on the back of this paper to ensure you have your paper. INSTRUCTIONS READ CAREFULLY You have

More information

Class X Chapter 09 Electrical Power and Household circuits Physics

Class X Chapter 09 Electrical Power and Household circuits Physics EXERCISE- 9 (A) Question 1: Write an expression for the electrical energy spent in flow of current through an electrical appliance in terms of current, resistance and time. Solution 1: Electrical energy,

More information

, , PREPARATION - CONNECTION. Mounting:. On symmetrical EN rail or DIN 35 rail

, , PREPARATION - CONNECTION. Mounting:. On symmetrical EN rail or DIN 35 rail 87045 LIMOGES Cedex Telephone number: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 DX 3 4500 A / 6 ka CONTENTS PAGES 1. Description, use...1 2. Range...1 3. Overall dimensions...1 4. Preparation - Connection...1

More information

ELECTRICIANS REGULATIONS EXAMINATION 23 November 2013 QUESTION AND ANSWER BOOKLET

ELECTRICIANS REGULATIONS EXAMINATION 23 November 2013 QUESTION AND ANSWER BOOKLET ER54 Candidate Code No. For Board Use Only Result Date Result Date Int ELECTRICIANS REGULATIONS EXAMINATION 23 November 2013 QUESTION AND ANSWER BOOKLET Time Allowed: Three hours INSTRUCTIONS READ CAREFULLY

More information

Distribution of Supplies in Buildings

Distribution of Supplies in Buildings Chapter 5 Distribution of Supplies in Buildings This chapter describes some of the points a designer will need to consider when planning an electrical installation. 5.1 INCOMING SUPPLY In the United Kingdom

More information

FUSES. Safety through quality

FUSES. Safety through quality Safety through quality HH HIGH VOLTAGE Over many decades SIBA has developed a global product line of High Voltage Fuses that are comprehensive for any and all applications. Superior engineering, advanced

More information

Distributor. Kewtech Corporation Limited 76 St. Catherine s Grove Lincoln LN5 8NA KEWTECH

Distributor. Kewtech Corporation Limited 76 St. Catherine s Grove Lincoln LN5 8NA  KEWTECH Distributor Kewtech Corporation Limited 76 St. Catherine s Grove Lincoln LN5 8NA www.kewtechcorp.com KEWTECH 92-1618 04-03 KEWTECH KT61 digital multi function tester Instruction manual Contents 1 Safe

More information

NPS/003/010 - Technical Specification for 400V Assemblies (LVAC Boards) utilised in Major Substations

NPS/003/010 - Technical Specification for 400V Assemblies (LVAC Boards) utilised in Major Substations Version:- 3.0 Date of Issue:- Dec 2013 Page 1 of 13 NPS/003/010 - Technical Specification for 400V Assemblies (LVAC Boards) utilised in Major Substations 1. Purpose This document is the technical specification

More information

OPERATING AND MAINTENANCE MANUAL. Primary Current Injection Test Set. 750ADM-H mk2

OPERATING AND MAINTENANCE MANUAL. Primary Current Injection Test Set. 750ADM-H mk2 OPERATING AND MAINTENANCE MANUAL Product: Type: Primary Current Injection Test Set 750ADM mk2 750ADM-H mk2 DESIGNED AND MANUFACTURED BY: T & R Test Equipment Limited 15-16 Woodbridge Meadows, Guildford,

More information

Miniature circuit breaker Application guide

Miniature circuit breaker Application guide Miniature circuit breaker Application guide Miniature Miniature circuit circuit breakers breakers Application S200 guide Introduction The circuit breaker plays an important role in providing over-current

More information

CHAPTER 2: ELECTRICAL SAFETY

CHAPTER 2: ELECTRICAL SAFETY CHAPTER 2: ELECTRICAL SAFETY 2.1 Physiological Effect of Electricity 2.2 Macroshock and Microshock Macroshock Microshock 2.3 Approaches toward Protection against Shock 2.4 Medical Safety Test Electrical

More information

Photovoltaic Solar Plan Review

Photovoltaic Solar Plan Review PAIGE B. VAUGHAN, CBO Director of Building and Safety Phone (310) 605-5509 Fax Line (310) 605-5598 E-mail:lbutler@comptoncity.org Building & Safety Department Photovoltaic Solar Plan Review Plan Check

More information

RE-PR1-F 1-Phase Din-Rail Mount 1.5, 3 & 6kW

RE-PR1-F 1-Phase Din-Rail Mount 1.5, 3 & 6kW Page 1 of 5 RE-PR1-F 1-Phase Din-Rail Mount 1.5, 3 & Features: Benefits: 0-10Vdc or 0-5Vdc control input Over temperature protection with auto reset Din-rail mounting Efficient electronic switching No

More information

Calculation of the Cross-sectional Areas of Circuit Live Conductors

Calculation of the Cross-sectional Areas of Circuit Live Conductors Calculation of the Cross-sectional Areas of Circuit Live Conductors MOTOR CIRCUITS SUBJECT TO FREQUENT STOPPING AND STARTING Regulations requires that where a motor is intended for intermittent duty and

More information

FUSE: SAFE & RELIABLE

FUSE: SAFE & RELIABLE FUSE: SAFE & RELIABLE VS. CIRCUIT BREAKER Tech Topics: Selective Coordination Note 2, Issue 1 Franck Charlier Technical Support Engineer Points of interest: Power fuse needs no repair only to be replaced

More information

OUTPUT SHORT-CIRCUIT CURRENT BEARABLE BY THE UPS

OUTPUT SHORT-CIRCUIT CURRENT BEARABLE BY THE UPS OUTPUT SHORT-CIRCUIT CURRENT BEARABLE BY THE UPS Abstract According to the standards, an overcurrent is a current which exceeds its rated value. Overcurrents can arise in different modalities, depending

More information

Miniature Circuit-Breakers (MCBs)

Miniature Circuit-Breakers (MCBs) Product overview Miniature Circuit-Breakers (MCBs) Design Tripping characteristic Rated currents I n Rated breaking capacity Power supply company product range 5SP3 E 16 - A Standard product range 5SX2

More information

Chapter P Residential and other special locations

Chapter P Residential and other special locations Chapter P Residential and other special locations 1 2 3 Contents Residential and similar premises 1.1 General P1 1.2 Distribution boards components P1 1.3 Protection of people P4 1.4 Circuits P6 1.5 Protection

More information

Electrical Workplace Safety

Electrical Workplace Safety Electrical Workplace Safety Alan Kelly 23 rd September 2015 Objectives To provide an understanding of Electrical terms and the concepts of electricity To introduce Electrical Protective Devices and provide

More information

EST Electrical Service Technician Answer Schedule

EST Electrical Service Technician Answer Schedule EST 2075 - Electrical Service Technician Answer Schedule Notes:1. means that the preceding statement/answer earns 1 mark. 2. This schedule sets out the accepted answers to the examination questions. A

More information

& HIGH CURRENT DC POWER SUPPLIES INSTRUCTION MANUAL

& HIGH CURRENT DC POWER SUPPLIES INSTRUCTION MANUAL 72-6850 & 72-6852 HIGH CURRENT DC POWER SUPPLIES INSTRUCTION MANUAL Table of Contents Introduction 2 Specification 2 Safety 4 EMC 5 Installation 6 Connections 6 Operation 7 Maintenance and Repair 8 www.tenma.com

More information

New DX 3 High rating & breaking capacity

New DX 3 High rating & breaking capacity New High rating & breaking capacity a new range OF MOduLar CirCuiT BrEakErs up TO 125 a T new dx³ MCBs AN ENHANCED range for HIgH-pErforMANCE INstALLAtIoNs DX³ : the new Legrand MCBs with dx³, Legrand

More information

Breaking and protection devices

Breaking and protection devices Power guide: A complete set of technical documentation Breaking and protection devices 01 Sustainable development 08 Protection against external disturbances 02 Power balance and choice of power supply

More information

Guide to the IET Wiring Regulations

Guide to the IET Wiring Regulations Guide to the IET Wiring Regulations Guide to the IET Wiring Regulations 17 th Edition IET Wiring Regulations (BS 7671:2008 incorporating Amendment No. 1:2011) Electrical Contractors Association Extracts

More information

DX³ RCBO 6000 / 10 ka Phase + Neutral, neutral on left

DX³ RCBO 6000 / 10 ka Phase + Neutral, neutral on left 87045 LIMOGES Cedex Téléphone : 05 55 06 87 87 Télécopie : 05 55 06 88 88 DX³ RCBO 6000 / 10 ka CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation Connection...

More information