Cascading & Discrimination
|
|
- Della Powers
- 5 years ago
- Views:
Transcription
1 Cascading & Discrimination
2 Typical LV System Level 1 ACBs A General LV Switchboard Level 2 ACB A MCCB 3200A Level 3 MCCB 1250A Fuses 630A Switchboard, Panelboard or MCC Level 4 MCBs - 100A Final Distribution Boards E62649
3 How do you determine the Fault level?
4 Terminology BSEN Overload >105% nominal current in an electrically sound circuit over a given period of time. ( Long Time Protection ) Short Circuit Electrical fault between Phases or to Earth usually >10x nominal current ( Instantaneous Protection ) Nominal Current = rating of the breaker
5 Terminology BSEN Icu Ultimate breaking capacity tested by O- CO O = opening or breaking operation C = closing or making operation. test for di-electric 2x rated voltage, but not less that 1000v, example: Icu = 70KA Ics Service Rating, tested by O-CO-CO test for di-electric 2 x rated voltage. temperature rise test at nominal operating current sometimes expressed as a % of Icu example Icu/Ics = 50% standard ratios 100%,75%,50% & 25%
6 Terminology BSEN Utilisation category Cat A a circuit breaker not specifically designed with an intentional time delay in respect of providing selectivity under short circuit conditions (eg. Lower rating MCCBs Compact NSX) Cat B a circuit breaker with an intentional time delay in respect of providing selectivity under short circuit conditions, such circuit breakers have a short time withstand current rating ( Icw ) (eg. Large MCCBs & ACBs Compact NS, Masterpact NT & NW)
7 Arc chute Magnet Double rotating contact Filter
8 Fundamental Features
9 Customer Benefits
10 Fundamental Features Improved double roto-active contact New contact material, new arc chamber Breaking units rationalized Reflex tripping For energy discrimination reflex tripping unit new raw material Polar breaking units to confine gas New filters for ratings above 400A, more exchange area Isolation function Positive break indication
11 Completely safe controls and settings "Mitop" integrated in the tripping device No electrical test required after fitting Settings shown in Amps Transparent sealed cover on the tripping device on the remote control The Micrologic 5/6 keyboard can be locked The settings and control can be locked in communication mode video_007
12 LV co-ordination techniques Optimising LV electrical distribution through 3 actions at the Protection Plan Level 1) discrimination to guarantee continuity of supply 2) limitation to reduce stresses 3) cascading to optimise performances
13 The IEC standard and co-ordination of protection devices Recognises the 2 co-ordination elements (appendix A) discrimination cascading Defines testing to guarantee this co-ordination Characterises the circuit-breakers capable of time discrimination utilisation category B E55229
14 What is discrimination? Total discrimination No discrimination CB1 CB1 CB1 and CB2 trip CB2 Only CB2 trips CB2 The power supply to the other feeders is still ensured The power supply to the other feeders is no longer ensured
15 Discrimination on different levels CB1 CB 2 CB3 CB 4 CB 5 CB 6 CB 7 Only CB7 trips
16 Co-ordination of protection devices 1) discrimination B A C Whatever the fault: overload short-circuit Ideally only the circuit-breaker located just upstream from the fault trips E types of discrimination current time energy logic
17 Discrimination in overload - rules Distribution Motor (circuit) Thermalmagnetic circuit breaker Electronic protection circuit breaker Electronic protection circuit breaker Thermal-magnetic or electronic protection circuit breaker Thermalmagnetic circuit breaker Electronic protection circuit breaker Thermalmagnetic circuit breaker Thermalmagnetic or electronic protection circuit breaker Ratio : Upstream setting Downstream setting
18 Discrimination in overload - rules NSX250N TMD NSX160N TMD NSX250N TMD NSX160N TMD NSX250N + TM250D NSX160N + TM160D 250/160 = 1.56 ratio Ratio should be > 1.6 Upstream Ir = 250A, Downstream = 160A Upstream/downstream ratio <1.6 therefore partial discrimination only Upstream Ir = 250A, Downstream = 144A ( 0.9xIn ) Therefore Upstream/downstream ratio >1.6 TM160D 160A/40 o C x160a x160a 250/144 = 1.73 ratio
19 Discrimination in short circuit - rules Distribution Motor (circuit) Thermalmagnetic circuit breaker Electronic protection circuit breaker Electronic protection circuit breaker Thermal-magnetic or electronic protection circuit breaker Thermalmagnetic circuit breaker Electronic protection circuit breaker Thermalmagnetic circuit breaker Thermalmagnetic or electronic protection circuit breaker Ratio : Upstream setting Downstream setting [TM upstream] 1.5 [Micrologic upstream]
20 Discrimination in short circuit - rules NSX250N + TM250D NSX250N TMD NSX160N TMD Upstream Im = 2500A (10xIn), Downstream = 1250A (fixed) Therefore Upstream/downstream ratio = 2 NSX160N + TM160D Steps to be taken: Provisionally select devices Consult catalogue for discrimination info. on particular combination of devices. Set devices to ensure ratios between upstream/downstream settings are adequate.
21 Energy based Discrimination according to IEC Energy let through curve of the downstream device Non-tripping energy curve of the upstream device. EN defines the method for calculating discrimination by comparing the operational curves based on the energy provided: i2 dt i2 dt downstream device I upstream device I
22 Discrimination with Compact NSX NSX160F/N/H/L TM125D Non-tripping curve NSX160 (TM125D) ic60 ic60 (63A) ic60 (10A) Total discrimination
23 Discrimination table ic60n B,C,D curves ic60n C curve All figures in ka
24 Logic Discrimination Principle: E41329 Breaker 2 detects the fault and sends a signal to Breaker 1 250mS Delay CB1 Twisted pair cable Breaker 1 receives 2 s signal & remains closed 2 eliminates the fault CB2 1 remains closed
25 Co-ordination of protection devices 2) limitation Technique that allows for the harmful effects of short-circuit currents to be reduced Limitation reduces following effects: electromagnetic: reduction in EMC disturbances mechanical: reduction of deformities and breaks thermal: increase the life span of busbars and cables Isc  100 % Isc presumed transient peak Isc presumed steady peak I 2 sc A % Presumed energy 100 % Isc limited peak E % tsc t 1 % Limited energy < 1 % t E62651
26 Co-ordination of protection devices 3) cascading The limiting upstream circuit-breaker helps the downstream circuit-breakers to open This technique allows the cost of LV electrical distribution to be optimised E62667
27 Cascading tested combination example Re-inforced breaking capacity of downstream device NSX250L 220A E Allows the installation of lower fault rating breakers downstream ( cost saving) NSX100F 63A - Discrimination study still needs to be carried out ic60h 25A
28 Cascading and enhanced discrimination Gives all the benefits of cascading without loss of discrimination Achievable with: Compact NSX - ic60h Compact NSX - Compact NSX Cascading and enhanced discrimination
29 Acti9 E41343 ic60n ic60h 30/30 = 30kA Discrimination level, 30kA back-up protection
30 Schneider solutions Customer needs Continuity of electrical energy supply Cost of the electrical installation Totally co-ordonated Schneider protection devices Discrimination as a standard in the circuit-breaker ranges Stress Limitation Economical association of circuit-breakers through Cascading
31 Design Aids - Curve Direct V3.4
32 On-Line Electrical Calculation Tools
33 Complementary Technical Information
Cascading. Complementary technical information
Cascading What is cascading? Cascading is the use of the current limiting capacity of circuit breakers at a given point to permit installation of lower-rated and therefore lower-cost circuit breakers downstream.
More informationCharacteristics of LV circuit breakers Releases, tripping curves, and limitation
Characteristics of LV circuit breakers Releases, tripping curves, and limitation Make, Withstand & Break Currents A circuit breaker is both a circuit-breaking device that can make, withstand and break
More informationCircuit breakers and switch-disconnectors NT06 to NT16 and NW08 to NW63
Functions and characteristics Circuit breakers and switch-disconnectors NT06 to NT16 and NW08 to NW63 NT and NW selection criteria Masterpact NT Masterpact NW NT06, NT08, NT10, NT12, NT16 NT06, NT08, NT10
More informationPrisma ipm Switchboard Air Circuit Breaker (ACB) Moulded-case Circuit Breaker (MCCB) Contactor Power meter
3 Prisma ipm Switchboard Air Circuit Breaker (ACB) Moulded-case Circuit Breaker (MCCB) Contactor Power meter The easy choice for quality, value, and peace of mind Schneider Electric makes it an easy choice
More informationLow voltage Direct Current Network. Compact NSX DC PV. Circuit breakers and switch disconnectors for solar application.
Low voltage Direct Current Network Compact NSX DC PV Circuit breakers and switch disconnectors for solar application Catalogue 2012 Compact NSX DC PV A complete DC offer for solar application from 80
More informationDX 3 MCBs. Choice of DX 3 MCBs for capacitor banks. Technical data
Specifications IS/IEC 60898-1 2002 Number of poles SP, SPN, DP, TP, TPN, FP Characteristics C & D Curve Breaking capacity 10 ka 0.5 A to 63 A as per IS/IEC 60898-1 2002 16 ka for 0.5 A to 25 A as per IEC
More information4. CIRCUIT BREAKERS (Continued)
4. CIRCUIT BREAKERS (Continued) 4.3 Other Characteristics of a circuit breaker: Familiarity with the following less-important characteristics of LV circuit breakers is, however, often necessary when making
More informationTerasaki (Europe) Ltd
Terasaki (Europe) Ltd Terasaki Europe Ltd was established in 97 and is located near Glasgow, Scotland U.K. From head office at our 7,00 square metre facility, Terasaki Europe controls an International
More informationSpecification for 70mm pole pitch Air circuit breaker up to 1600 A
Specification for 70mm pole pitch Air circuit breaker up to 1600 A Protective device for low voltage electrical installation Last update :2011-07-08-1 - Table of contents: 1 General...3 2 Compliance with
More informationDPX moulded case circuit breakers
BREAKING AND PROTECTION DEVICES 10 / 2011 DPX moulded case circuit breakers DPX moulded case circuit breakers offer optimum solutions for the protection requirements of commercial and industrial installations.
More informationC60H-DC. C curve IEC Direct current (DC) Breaking capacity (Icu) according to IEC Type 1P 110 V 220 V 250 V 440 V 500 V
DC circuit supplementary protectors for feeders / distribution systems C60H-DC C curve DB123430 DB123525 DB405571 IEC 60947-2 PB107193-34.eps PB107194-34.eps The C60H-DC supplementary protectors are used
More informationCircuit protection and control devices 0.5 to 6300 A
Electrical distribution Circuit protection and control devices 0.5 to 6300 A LV product characteristics 2009 m TOOLS schneider-electric.com The technical guide This international site allows you to access
More informationPhase + Neutral, neutral on left side
87045 LIMOGES Cedex Téléphone : 05 55 06 87 87 Télécopie : 05 55 06 88 88 DX 3 MCB 10000 A / 16 ka CONTENTS PAGE 1. Description, use...1 2. Range...1 3. Overall dimensions...1 4. Preparation - Connection...1
More informationDNX 3 MCB 4500 A / 6 ka Phase + Neutral, neutral on left side
87045 LIMOGES Cedex Telephone number: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 DNX 3 MCB 4500 A / 6 ka CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation
More informationNew DMX 3. Efficient protection up to A AIR CIRCUIT BREAKERS PRODUCT GUIDE
New DMX 3 Efficient protection up to 4 000 A AIR CIRCUIT BREAKERS PRODUCT GUIDE NEW DMX 3 ACBs UP TO 4 000 A EFFICIENT PROTECTION AND CONTROL FOR ALL TYPE OF BUILDINGS 02 Electrical panel equipped with
More informationBreaking and protection devices
Power guide: A complete set of technical documentation Breaking and protection devices 01 Sustainable development 08 Protection against external disturbances 02 Power balance and choice of power supply
More informationDATA SHEET FOR 1 TYPE COMPARTMENTALISED / NON - COMPARTMENTALISED. ( a ) CIRCUIT BREAKER FEEDERS FULLY DRAWOUT / NON DRAWOUT
44LK-500/E.04/002A/A4 PROJECT NO 44LK-500 CHKD. BY VDV VDV A CLIMATIC CONDITIONS THIS DATA SHEET IS APPLICABLE FOR IN UTILITY BOILER PACKAGE DESIGN AMBIENT TEMPERATURE 45 C 2 ALTITUDE ( ABOVE MSL ) 6.7
More informationcor Long Run Experience
Moulded Case Circuit Breakers Moulded Case Circuit Breakers 16-1250A cor Long Run Experience cor Breaking capacity (according to IEC 947-2 at 415V) Icu 100 D160L D250L D400L D630L 70 60 DH800 50 35 30
More informationPower protection solutions
Power protection solutions DMX A.C.Bs UP TO 4000 A In high power installations, the role of the main enclosure is to: - House protection devices and provide for their connection - Provide management and
More informationLow Voltage. EasyPact CVS. Moulded-case circuit breakers from 16 to 100 A
Low Voltage EasyPact CVS Moulded-case circuit breakers from 16 to 100 A Catalogue 2013 EasyPact CVS Contents Functions and characteristics A-1 Installation recommendations B-1 Dimensions and connection
More information3 - Protection components Motor circuit-breakers
Contents 0 - Protection components Motor circuit-breakers protection components for the motor protection Thermal-magnetic motor circuit-breakers Selection guide..............................................page
More informationPhase + Neutral, neutral on right side
87045 LIMOGES Cedex Telephone number: +33 5 55 06 87 87 Fax: +33 5 55 06 88 88 DX 3 MCB 6000 A / 10 ka Cat.. N (s): 4 074 67 / 68 / 69 / 70 / 71 / 72 / 73 / 74 / 75 / 76 / 77 / 78 / 79 ; 4 077 33 / 34
More informationFUSE: SAFE & RELIABLE
FUSE: SAFE & RELIABLE VS. CIRCUIT BREAKER Tech Topics: Selective Coordination Note 2, Issue 1 Franck Charlier Technical Support Engineer Points of interest: Power fuse needs no repair only to be replaced
More informationNEW SERIES OF ETIBREAK EB2 IN VIEW OF SELECTIVITY
NEW SERIES OF ETIBREAK EB2 IN VIEW OF SELECTIVITY WHAT IS SELECTIVITY? Selectivity in mean of protective devices is also called by other terms as discrimination or coordination of protective devices. To
More informationDX³ 4-pole RCBO 6000 A/10 ka
87045 LIMOGES Cedex Telephone number: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 DX³ 4-pole RCBO CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation - Connection...
More informationPrice List. Low Voltage Distribution Products. With effect from March 12, schneider-electric.co.in
Price List Low Voltage Distribution Products With effect from March 12, 2018 schneider-electric.co.in Price List Contents Smart Panels Introduction to Smart Panels............................... 5 Moulded
More informationPower systems Protection course
Al-Balqa Applied University Power systems Protection course Department of Electrical Energy Engineering Dr.Audih 1 Part 3 Protective Devices Fuses & Circuit Breakers 2 Introduction: Fuse Is advice used
More information87045 LIMOGES Cedex. 2. PRODUCT RANGE (continued) 1. DESCRIPTION - USE. Breaking capacity : Symbol : Technology : 3. OVERALL DIMENSIONS
87045 LIMOGES Cedex Phone : + 33 5 55 06 87 87 Fax : + 33 5 55 06 88 88 R.C.B.O. DX 6000 A Phase + Neutral,, neutral on right side Cat. n (s) : 077 31 077 44-077 77 077 84 078 79 079 01-083 95 084 06 084
More informationNew DX 3 High rating & breaking capacity
New High rating & breaking capacity a new range OF MOduLar CirCuiT BrEakErs up TO 125 a T new dx³ MCBs AN ENHANCED range for HIgH-pErforMANCE INstALLAtIoNs DX³ : the new Legrand MCBs with dx³, Legrand
More information013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS
013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEYLON ELECTRICITY BOARD SRI LANKA Specification for MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEB Specification
More informationLEXIC Curv LIMOGES Cedex. Cats N (s) : /68/87/88, /48, /84/85, /76/77/95/96/97, /71/72 1.
87045 LIMOGES Cedex Téléphone : 05 55 06 87 87 Télécopie : 05 55 06 88 88 LEXIC MCB s DX-H 80A, 100A, 125A Curv urves B and C CONTENTS PAGES 1. Description, use...1 2. Range...1 3. Overall dimensions...1
More informationPrice List. Low Voltage Distribution Products. With effect from December 29, schneider-electric.co.in
Price List Low Voltage Distribution Products With effect from December 29, 2016 schneider-electric.co.in Price List Contents Smart Panels Introduction to Smart Panels............................... 5
More informationLow voltage. Masterpact NT and NW. LV power circuit breakers and switch-disconnectors Draw-out Type & Fixed Type. Catalogue
Low voltage Masterpact NT and NW LV power circuit breakers and switch-disconnectors Draw-out Type & Fixed Type Catalogue 2015 Functions and characteristics Circuit breakers and switch-disconnectors NT06
More informationIntelligent Choice for Prestigious Buildings
Intelligent Choice for Prestigious Buildings Table of Contents I-LINE Moulded Case Circuit Breakers General Characteristics 16A to 160A 125A to 250A 250A to 600A 300A to 800A 630A to 1250A 2/3 4 5 6 6
More informationMOLDED CASE CIRCUIT BREAKER BASICS. David Castor, P.E.
MOLDED CASE CIRCUIT BREAKER BASICS David Castor, P.E. History of MCCBs 1904 - Cutter Manufacturing Co., Philadelphia, produces circuit breakers. They called it the Inverse Time Element breaker, or I-T-E
More informationMCBs and RCDs LR TM 6000
MCBs and RCDs LR TM 6000 thermal magnetic MCBs from 6 A to 63 A B and C curves residual current devices from 25 A to 63 A AC and A types ± ± ± ± MCBs Single pole 230/400 V± Single pole neutral 230 V± (1)
More informationCompact Merlin Gerin 80 to 3200 A
LV power air circuit breakers and switch-disconnectors Catalogue Compact Merlin Gerin 80 to 3200 A 2005 Industries SA 5, rue Nadar 92506 Rueil-Malmaison Cedex France Tel : +33 (0)1 41 29 82 00 Fax : +33
More informationFUSERBLOC CD. The universal Fuse Combination Switch FROM 20 TO 1250 A. Industrial Switching & Protection Systems
FUSERBLOC CD The universal Fuse Combination Switch FROM 20 TO 1250 A SOCOMEC GROUP SWITCHING PROTECTION & UPS Industrial Switching & Protection Systems SWITCHING FUSERBLOC CD THE UNIVERSAL FUSE COMBINATION
More informationC60H-DC C curve. Catalogue numbers
distriution systems PB104013-34 The supplementary protectors are used in direct current circuits (Industrial control and automations, transport, renewale energy...). They comine the following functions
More informationDPX 1600 Electronic release
87045 LIMOGES Cedex Phone :+33 05 55 06 87 87 Fax :+33 05 55 06 88 88 DPX 1600 CONTENTS PAGES 1. USE 1 2. RANGE 1 3. DIMENSIONS 1 3. DIMENSIONS (NEXT) 2 4. OVERVIEW 2 5. CONNECTION 2 6. ELECTRICAL AND
More informationLow voltage distribution products
Price List Low voltage distribution products With effect from June 03, 2013 Price List Contents Prisma ipm: A range of Kit based LV panels.............. 1 EasyPact EZC: Range Overview...................................
More informationWall mounted switchgear
Contents Safepact 2... pages /2 to / Enclosed MCCBs 6 to 60A... page /2 Enclosed switch disconnectors 100 to 60A... page / Earth leakage.... page /4 Auxiliaries and accessories... page /5 Enclosed Interpact...page
More informationControl Circuit Protection
Contents 5SJ4 Branch Circuit Protectors 5SY4 Supplementary Protectors 5SY6 Supplementary Protectors 16/19 5SJ4 Page Selection and ordering data 1-pole up to 63A 16/4 1-pole, 2-pole, 16/5 3-pole, 240VAC
More information15 16 MCCBs for Power Distribution Technical Specification Frame 100A 250A 250A 400A 400A 630A 800 / 1000 / 1250 Type C DN0-100 D DN1-250 N DN2-250 D N S H DN3B-400 DN3-400 D N D N S V DN3-630 DN4-1250
More information, , PREPARATION - CONNECTION. Mounting:. On symmetrical EN rail or DIN 35 rail
87045 LIMOGES Cedex Telephone number: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 DX 3 4500 A / 6 ka CONTENTS PAGES 1. Description, use...1 2. Range...1 3. Overall dimensions...1 4. Preparation - Connection...1
More informationDX³ RCBO 6000 A Phase + Neutral, neutral right side
87045 LIMOGES Cedex Téléphone : 05 55 06 87 87 Télécopie : 05 55 06 88 88 DX³ RCBO 6000 A CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation Connection... 1
More informationCompact NSX100 to 630
Low Voltage Compact NSX00 to 30 Circuit reakers and switch-disconnectors Sustitution guide - Technical characteristics 200 Sustitution guide Technical characteristics Performance levels and trip units
More informationCOMPLETE SOLUTIONS FOR POWER PROTECTION
COMPLETE SOLUTIONS FOR POWER PROTECTION GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES Modular protection P. 8 RX 3 MCBs 63 A 4500 & 6000 P. 18 DX 3 -IS isolating switches P. 9 RX
More informationMiniature circuit breaker Application guide
Miniature circuit breaker Application guide Miniature Miniature circuit circuit breakers breakers Application S200 guide Introduction The circuit breaker plays an important role in providing over-current
More informationDNX 3 MCB 4500 A / 6 ka Phase + Neutral, neutral on left side
87045 LIMOGES Cedex Téléphone : 05 55 06 87 87 Télécopie : 05 55 06 88 88 DNX 3 MCB 4500 A / 6 ka CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation - Connection...
More informationACW Molded-Case Circuit Breaker UL 489 Listed
Motors Automation Energy Transmission & Distribution Coatings Molded-Case Circuit Breaker UL 489 Listed Overview Introducing the WEG Series of Molded Case Circuit Breakers now available with UL489 certification.
More informationMiniature & Moulded Case
Miniature & Moulded Case MCB OPERATION MAGNETIC OPERATION The short time protection (typically less than 1 second after energising) of the MCB is defined as the magnetic operation. 1 2 3 THERMAL OPERATION
More information6300A 15 Optibreak B1 & B2 Optibreak B1 & B2 50/60 Hz Ue Icu [v] [ka] 415 65 690 40 4h 4i 1. Open / close Indication 2. Charge and Discharge Indicator 3. Release the reset button 4. Laser Nameplate
More information37-SDMS-04 SPECIFICATIONS FOR INTERFACE LOW VOLTAGE MAIN CIRCUIT BREAKERS
SPECIFICATIONS FOR INTERFACE LOW VOLTAGE MAIN CIRCUIT BREAKERS This specification is property of SEC and subject to change or modification without any notice CONTENTS Clause Page 1.0 SCOPE 3 2.0 CROSS
More informationDX³ RCBO 6000A Phase + Neutral, neutral on left
87045 LIMOGES Cedex Telephone number: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 DX³ RCBO 6000A CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation Connection...
More informationLow Voltage A GE Power Controls Company. General catalogue
Low Voltage A GE Power Controls Company General catalogue this is a blanc page Miniature circuit breakers A Miniature circuit breakers AC miniature circuit breakers Benefits of the new MCB s A 3 The AEG
More informationConsumer Switchboards and Circuit Protection Flexible range designed for domestic and commercial installations
Consumer Switchboards and Circuit Protection Flexible range designed for domestic and commercial installations POWER DISTRIBUTION AND PROTECTION NHP Electrical Engineering Products Pty Ltd AUS NZ 1300
More informationDX³ RCBO 4500/6 ka Phase + Neutral, neutral on left
87045 LIMOGES Cedex Telephone number: +33 5 55 06 87 87 Fax: +33 5 55 06 88 88 DX³ RCBO 4500/6 ka CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation Connection...
More informationDX³ RCBO 6000 / 10 ka Phase + Neutral, neutral on left
87045 LIMOGES Cedex Téléphone : 05 55 06 87 87 Télécopie : 05 55 06 88 88 DX³ RCBO 6000 / 10 ka CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation Connection...
More informationMiniature Circuit Breaker UL / CSA Range
PRODUCT CATALOG CANADA Miniature Circuit Breaker UL / CSA Range UL489 / CSA C22.2 No.5 devices UL1077 / CSA C22.2 No. 235 devices Electronic Protection Devices Technical data Miniature Circuit Breakers
More informationEnhancing Short Circuit Selective Coordination with Low Voltage Circuit Breakers
Data Bulletin 0100DB0403R5/05 05/2005 Cedar Rapids, Iowa, USA Enhancing Short Coordination with Low Voltage s Retain for future use. INTRODUCTION DEFINITIONS ASSUMPTIONS CIRCUIT BREAKER BASICS The purpose
More informationNEW TX³ RANGE PROTECTION YOU CAN RELY ON
TX³ NEW RANGE TRUSTED PROTECTION FOR YOUR INSTALLATIONS GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES NEW TX³ RANGE PROTECTION YOU CAN RELY ON Designed to meet the requirements of
More informationNS Feeder pillar up to 3200A
NS Feeder pillar up to 3200A Advanced technology for low voltage, outdoor distribution Merlin Gerin Modicon Telemecanique Outdoor electrical distribution with advanced technology Merlin Gerin low voltage,
More informationThe University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 6
The University of New South Wales School of Electrical Engineering and Telecommunications Industrial and Commercial Power Systems Topic 6 PROTECTIONS 1 FUNCTION OF ELECTRICAL PROTECTION SYSTEMS Problems:
More informationMiniature Circuit-Breakers (MCBs)
Product Overview Miniature Circuit-Breakers (MCBs) Design Tripping characteristics Rated current I n Rated breaking capacity Power supply company product range 5SP3 E 16 - A Standard product range 5SQ2
More informationDPX 630 Electronic release
87045 LIMOGES Cedex Phone :+33 05 55 06 87 87 Fax :+33 05 55 06 88 88 DPX 630 CONTENTS PAGES 1. USE 1 2. RANGE 1 3. DIMENSIONS 1 4. OVERVIEW 2 5. CONNECTION 2 6. ELECTRICAL AND MECHANICAL CHARACTERISTICS
More informationMolded Case Circuit Breaker
Molded Case Circuit Breaker + + + Building + + + a better + + future + + + + We, Hyundai Heavy Industries Co., Ltd., are challenging + + + + for better + future with + continuous + investment + in R&D
More informationAPPENDIX E. Electrical System Single Line Diagram Overcurrent Protection Study Overcurrent Protection Device Specifications
Student Resource Building University of California Santa Barbara Clement Fung Lighting Electrical Option APPENDIX E Electrical System Single Line Diagram Overcurrent Protection Study Overcurrent Protection
More informationschneider-electric.com/sg K60 Circuit Breakers The affordable way to stay safe from electrocution and electrical overloads schneider-electric.
K0 Circuit Breakers The affordable way to stay safe from electrocution and electrical overloads Overview K0 Circuit Breaker Technical Specification MCB RCCB K0 Circuit Breaker K0N K0H ID K Number of poles
More informationTechnical Section: Miniature Circuit Breakers
MCBs and Accessories Data. Calibration With CBI Hydraulic- Magnetic Miniature Circuit Breakers, there is no effect on the fixed trip point at ambient temperature ranges from -5 C to +60 C. 2. Products
More informationBtdin-RS RCBO 2p Phase + Neutral, neutral on right
Viale Borri 231, 21100 Varese - Italy RCBO 2p CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation Connection... 1 5. General characteristics... 2 6. Compliance
More informationDX³ RCBO 6000A Phase + Neutral, neutral on right
87045 LIMOGES Cedex Telephone number: +33 5 55 06 87 87 Fax: +33 5 55 06 88 88 DX³ RCBO 6000A CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation Connection...
More informationParamount HRC Cartridge
Paramount HRC Cartridge Eaton MEM HRC fuselinks are manufactured to exacting standards using precision assembly methods and undergo rigorous quality checking before dispatch including resistance testing
More information01 Spectra Plus - Introduction
01 Spectra Plus - Introduction Standard features Conforming to IS13947-2/EN60947 2 Compact dimensions Available in 3P & 4P High performance microprocessor protection release Wide overload setting from
More informationRX 3 MCB 4500 A Phase + Neutral, neutral on left side
87045 LIMOGES Cedex Téléphone : 05 55 06 87 87 Télécopie : 05 55 06 88 88 RX 3 MCB 4500 A CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation - Connection...
More informationAn electrical panel capable of evolving
An electrical panel capable of evolving Prisma TT Low voltage factory built assemblies Buildings Commercial & Industrial Make the most of your energy General For a dependable electrical installation Total
More informationSentry Technical. Miniature Circuit Breakers (MCBs) Standards and approvals. Description. Technical specification
543 technical hotline +44 ()1268 56372 Standards and approvals Sentry MCBs are designed to fully comply with the relevant requirements of BS EN 6898: 23. They all feature positive contact status indication
More informationSelective Coordination
Circuit Breaker Curves The following curve illustrates a typical thermal magnetic molded case circuit breaker curve with an overload region and an instantaneous trip region (two instantaneous trip settings
More informationJtec 10kA Miniature Circuit Breaker
EN 60898 Jtec 10kA Miniature Circuit Breaker Techna s JTEC range has been enthusiastically adopted by a diverse range of customers seeking a cost effective 10kA performance. Jtec MCBs are available in
More informationLPSRK30SP 30A 600V TD Dual Elem Class RK1 Low Peak Fuse
LPSRK30SP 30A 600V TD Dual Elem Class RK Low Peak Fuse Catalog Number Manufacturer Description Weight per unit Product Category LPSRK30SP 30A 600V Class RK Low Peak Dual Element, Time Delay Fuse 600 (lbs/each)
More informationWORKSHOP SPECIFICATIONS
WORKSHOP SPECIFICATIONS DPX 3 160 & 250 MOULDED CASE CIRCUIT BREAKERS THE GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES DPX 3 RANGE Not only do DPX³ 160 and DPX 3 250 MCCBs provide
More information(p. 47) (p. 155) (p. 155)
0 286 56 + 0 288 02 (p. 47) 0 286 74 + 0 288 02 (p. 155) 0 287 56 + 0 288 02 (p. 155) Dimensions see e-catalogue Elecical characteristics p. 162 Automatic air circuit breakers must be equipped with eleconic
More informationSPOT-INDIA GROUP WHATSAPP ARCHANA With effect from December 29, 2016
Price List Panel Builder With effect from December 29, 2016 schneider-electric.co.in mailspotindia@gmail.com SPOT-INDIA GROUP WHATSAPP +91 9821696132 ARCHANA mailspotindia@gmail.com SPOT-INDIA GROUP WHATSAPP
More informationLow Voltage. Interpact. Switch-disconnectors INS/INV40 to 2500 A. Catalogue 2011
Low Voltage Interpact Switch-disconnectors INS/INV40 to 2500 A Catalogue 2011 Interpact INS/INV Contents Presentation 2 Functions and characteristics A-1 Installation recommendations B-1 Dimensions and
More informationCompact NR630. NR100F to NR630F
Low voltage switchgear Compact NR NR100F NR630F The Compact NS range has revolutionised the world of moulded-case circuit breakers. For installations not requiring the high performance levels of the NS
More informationRated Impulse withstand voltage U imp Main circuit Between terminals, AC3500V for 1 minute 12kV terminal group to earth Control circuits
7 Technical Data Dielectric strength Circuit Withstand voltage (at 50/60 Hz) Rated Impulse withstand voltage U imp Main circuit Between terminals, AC3500V for 1 minute 12kV terminal group to earth Control
More informationPrice List. Panel Builder. With effect from July 01, 2017
Price List Panel Builder With effect from July 01, 2017 schneider-electric.co.in *Final Distribution prices w.e.f. June 01, 2017 Price List Contents Low Voltage Products Smart Panels Introduction to Smart
More informationDon t Discriminate: The importance of selective coordination in electrical installations
Don t Discriminate: The importance of selective coordination in electrical installations Prepared by: Design Engineer: Anthony Unsworth anthonyunsworth@sudlows.com What is Discrimination? Discrimination,
More informationR.C.B.O. SP / 1 module
87045 LIMOGES Cedex - France Telephone : (+33) 5 55 06 87 87 Fax : (+33) 5 55 06 88 88 R.C.B.O. SP / 1 module 6064 04 6064 64 05 6064 10 6064 11 6064 12 CONTENTS PAGES 1. Description, use... 1 2. Range...
More informationSwitch Disconnectors. SENTRON 3NP5 Fuse Switch Disconnectors up to 630 A. Introduction. 7/106 Siemens LV
Switch Disconnectors Introduction Siemens AG 2010 Overview 3NP5 0 3NP5 2 3NP5 fuse disconnector range 3NP5 4 SENTRON 3NP5 fuse disconnectors are controls for the occasional manual ing/isolating of loads
More informationMINIATURE CIRCUIT BREAKER
Technical Article MINIATURE CIRCUIT BREAKER T 146 PURCHASE he Spaceage MCB protects wires and cables automatically against overload and short-circuits in domestic, commercial and industrial installations.
More informationGJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector
GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector Catalog 0500CT9702R409 2009 Class 525/580 CONTENTS Description............................................. Page General Characteristics...................................
More informationProtectors. Manual motor. Types MS116, MS132, MS45x, MS49x. MS Series. Manual motor protectors. Type MS116. Type MS132. Type MS45x.
Types MS116, MS132, MS5x, MS9x are electromechanical devices for motor and circuit protection. These devices offer local motor disconnect means, manual ON/OFF control, and protection against short circuit,
More informationMoulded case circuit breakers
Moulded case circuit breakers CONTENT Range 4 Protection Releases 5 Salient Features 8 Accessories, 4 Technical data 2 Time Current Characteristics 5 Overall Dimensions 7 SN4 SN3 SN2 SN 3 RANGE Moulded
More informationCircuit Breaker Prepared By :
Circuit Breaker Prepared By : Eng : Ayman Soliman Selmy Circuit Breaker Specification of circuit Breaker:- [1] Operating voltage of C.B [2] Rated current of C.B (Ir or In) Amp. [3] Instantaneous short
More informationManual motor starters Overview and benefits
Manual motor starters Overview and benefits ABB offers a complete standard motor-protection concept for the world market IEC motor branch protection UL type E/F Motor applications with fuseless protection
More informationPowerPact Q-Frame Molded Case Circuit Breakers and Switches (Types QB, QD, QG and QJ)
PowerPact Q-Frame Molded Case Circuit Breakers and Switches (Types QB, QD, QG and QJ) Catalog Class 734 0734CT0201R1/07 07 CONTENTS Description..............................................Page Description.............................................
More information1. Design, function and types of circuit breakers 1.1
Content: 1. Design, function and types of circuit breakers 1.1 1.1. Summary 1.1 1.2. Types of switches 1.2 1.2.1. Manual motor starter and protector or circuit breaker with motor protective characteristics
More informationSchool of Electrical and Information Engineering. ELEC High Voltage. University of Sydney. Dr Keith Mitchell. Engineering
University of Sydney School of Electrical and Information Engineering Dr Keith Mitchell ELEC 5205 - High Voltage Engineering ELEC 5205 - High Voltage Engineering 3. Switchgear Types of Power System Switchgear
More informationACS motor protection circuit breakers KT 7 Introduction
Introduction Automatic Type 2 coordination The right circuit breaker for all applications The KT 7 circuit breaker family consists of two basic frame sizes of mm and 5 mm in three variations with different
More information