Miniature Circuit-Breakers (MCBs)

Size: px
Start display at page:

Download "Miniature Circuit-Breakers (MCBs)"

Transcription

1 Product Overview Miniature Circuit-Breakers (MCBs) Design Tripping characteristics Rated current I n Rated breaking capacity Power supply company product range 5SP3 E 16 - A Standard product range 5SQ2 B 6-40 A C A 5SQ3 C A 5SX2 A 1-40 A B 6-50 A C A D A 5SX4 B 6-50 A C A AC/DC product range 5SX5 B 6-32 A C A High current product range 5SX7 B A C A D 40 - A Energy limitation class T Definitions 1 MW =Modular width of 18 mm N-type =Device mounting depth of 55 mm Depth 70 mm= Device mounting depth 70 mm 2/2 Siemens I

2 Summary of Technical Data Tripping characteristics 5SX2 5SX4 5SX5 5SX7 A, B, C, D B, C B, C B, C, D No. of poles N 3 + N Rated voltage V AC 230/400 V DC - 220/440 - Operating voltage min. AC/DC V 24 max. DC V/pole 60 1) ) max. AC V 440 Rated breaking capacity acc. to DIN VDE 0641 AC ka DC ka Insulation coordination Rated insulation voltage AC V 250/440 Degree of pollution for overvoltage category III 2 3 Degree of protection IP 00 according to DIN , IP 40 when mounted in distribution boards Flammability Category IIb according to DIN VDE 0304 Part 3 Mounting 1) r Battery charging voltage 72 V. On a 35 mm mounting rail (DIN EN ); for 5SX7, also screw mounting Terminals Tunnel terminals on both ends; 5SX2, 5SX4, 5SX5 combined terminal below for simultaneous connection to busbars (fork-type) and feeder cables Conductor cross sections Solid and stranded, max. Upper terminal mm Lower terminal mm Finely stranded with end sleeves, max. Upper terminal mm Lower terminal mm Terminal tightening torque max. Nm Supply connection As required, observe the polarity for DC applications Mounting position As required Service life On the average operations at rated load Ambient temperature C -25 to +45, occasionally +55, max. 95 % humidity, storage temperature: -40 to +75 Resistance to climate According to IEC , 6 cycles Resistance to vibration m/s 2 60 at 10 Hz to 150 Hz according to IEC Siemens I /3

3 Applications MCBs of the N System primarily protect cables and conductors against overload and short circuit. Thus, they also protect electrical equipment against overheating according to DIN VDE 0 Part 430. Under certain conditions, MCBs also protect against shock currents caused by excessive touch voltage due to insulation failure according to DIN VDE 0 Part 410. Further, due to the fixed rated current settings of MCBs, it is also possible to protect motors in a limited form. For the respective application, there are four different tripping characteristics available which will be individually described. The standards EN , DIN VDE 0641 Part 11 and IEC form the basis for the design and approval of the MCBs. For applications in industry and in system and plant engineering where MCBs of the N System are used, add-on accessories are available, such as auxiliary contacts (AC), fault signal contacts (FC), shunt trips (ST), undervoltage releases (UR) and RCCB modules. Functional design, mode of operation MCBs of the N System operate using a delayed overload current/time-dependent thermal release (thermal bimetal) for low overcurrents and an instantaneous electromagnetic release for higher overload and shortcircuit currents. The special contact materials used assure a long service life and offer a high level of protection against contact welding. MCBs of the N System significantly limit the let-through current when a fault occurs due to the ultra-fast contact separation and the quick quenching of the arc in the arc-chamber. Thus, generally, they fall below the permissible limiting I 2 t values of energy limiting class 3, specified in DIN VDE 0641 Part 11 by 50%. This guarantees excellent selectivity with the upstream overcurrent protective devices. Features High rated breaking capacity up to A according to EN Excellent current limiting and selectivity Tripping characteristics A, B, C and D Add-on accessories, quick mounting on site using snapon mechanism Combined terminal allows busbar and feeder cable to be simultaneously connected Disconnector characteristics according to DIN VDE 0660 Part 107 (5SX7) Main switch characteristics according to EN (5SX7) Separate switch position indicator (5SX7) The terminals are safe from finger touch and safe from touch by the back of the hand acc. to DIN VDE 0106 Part Insertion guide for fast and easy access to the terminal Handle locking device effectively prevents unauthorized operation of the handle 2/4 Siemens I

4 Application examples Feeder cables from below with cross sections up to 25 mm 2 and 3-pole 5ST2 144 busbars can be simultaneously connected at the combined terminal of the MCB. Feeder cables from below with cross sections up to 35 mm 2 and double-pole 5ST2 143 busbars can be simultaneously connected using the terminal 5ST Cables connected from the top use the same principle. Feeder cables from above with cross sections up to 35 mm 2 can be connected to 5ST2 144 busbars through supplementary terminal 5ST Feeder cables with cross sections up to 25 mm 2 and 5ST2 165 busbars can be simultaneously connected at the combined terminal of the MCB using the auxiliary contacts mounted on-site. Siemens I /5

5 Cable protection The task of MCBs is to protect cables and conductors against thermal overload of the insulation due to overcurrents and short circuits. The tripping characteristics of the MCBs match the load curves of the cables and conductors. 1 st condition I b I n I z 2 nd condition I I z The following explanation describes the relative value of the cable/conductors and the MCBs. In the standards EN /1991 and IEC /1987, modified in 11/91, the new characteristics B, C and D were defined, and adopted in DIN VDE 0641 Part 11/8.92. Therefore, all three characteristics can be certified. Characteristic B replaces the earlier characteristic L. The characteristic G according to CEE 19, 1 st edition is still defined, but in practice it is going to be replaced by characteristic C. In the field, the new tripping characteristics with their common thermal release operating level I 2 = 1.45 x I n provide the advantage that the miniature circuit-breakers for the protection of cables and conductors can be more easily and clearly assigned in case of overload, and more specifically, according to the condition: I n I z. I b Operating current: current determined by the load at fault-free operation I z Permissible continuous current of a conductor for which the continuous limit temperature of the insulation is not exceeded 1.45 x I z Maximum permissible time-limited overload current at which the insulation properties are not reduced in a safety-relevant way if the continuous limit temperature is briefly exceeded I n Rated current: Current for which the circuit-breaker has been designed and to which other rated quantities are referred I 1 Low test current: A current, which does not lead to tripping under defined conditions I 2 High test current: A current, which trips the device within one hour (I n 63 A) under defined conditions I 3 Tolerance limits I 4 Holding current of the instantaneous release (short-circuit release) I 5 Tripping current of the instantaneous release (short-circuit release) Conductor cross sections Assignment of MCBs according to DIN VDE 0641 Part 11 to copper conductors with PVC insulation for installation type C 1) and R= 30 C: Rated cross section Rated current MCB I z (conductor) Continuous current in A acc. to DIN VDE 0298 T4 and DIN VDE 0 T430 Supplement sheet 1 2 conductors 3 conductors 2 conductors 3 conductors mm 2 A A A A ) Example: Rising, multi-core conductors on/in the wall. 2/6 Siemens I

6 Tripping characteristics according to EN , DIN VDE 0641 Part 11 Tripping characteristic A For limited semiconductor protection Protection of measuring circuits with transformers Protection of circuits with long cable lengths which will require tripping within 0.4 s according to DIN VDE 0 Part 410 Tripping characteristic B Cable and line protection mainly in residential buildings, proof regarding shock-hazard protection is not necessary Tripping characteristic C Cable and line protection, advantageous in case of higher inrush currents, e.g. lamps, motors Tripping characteristic D For applications involving equipment generating significant pulses, e.g. transformers, solenoid valves, capacitances Siemens I /7

7 Tripping characteristics Tripping performance at an ambient temperature of 30 C Tripping Standards Thermal release Electromagnetic release characteristics Test currents: Test currents: Low test High test Tripping time Hold Trips at the Tripping time current current 63 A I n 125 A latest at I 1 I 2 t I 4 I 5 t A 1.13 x I n > 1 h > 2 h 2 x I n 0.1 s 1.45 x I n < 1 h < 2 h 3 x I n < 0.1 s B IEC /EN x I n > 1 h > 2 h 3 x I n 0.1 s DIN VDE 0641 Part x I n < 1 h < 2 h 5 x I n < 0.1 s C 1.13 x I n > 1 h > 2 h 5 x I n 0.1 s 1.45 x I n < 1 h < 2 h 10 x I n < 0.1 s D 1.13 x I n > 1 h > 2 h 10 x I n 0.1 s 1.45 x I n < 1 h < 2 h 20 x I n < 0.1 s (IEC : 50 x I n) At other ambient temperatures, the currents of the delayed tripping change by approximately 5 % for each 10 K temperature difference. More specifically they increase for temperatures below 30 C and decrease for temperatures above 30 C. For DC, the limit currents of the instantaneous tripping increase by a factor of 1.2. If more than one circuit in a series of MCBs is loaded, this has an impact on the characteristic as a result of an increased ambient temperature. In this case, an additional correction factor must be applied, referred to the rated miniature circuit-breaker current. No > 7 K Rated breaking capacity For MCBs, there are special requirements with regard to the breaking capacity. The values are standardized and are determined according to the testing conditions of EN and DIN VDE 0641 Part 11. The most usual values are and For other reference voltages and other simpler test conditions, other values can be specified which lie above those of EN and DIN VDE 0641 Part 11. An example of another standard is EN or DIN VDE 0660 Part 101 for MCBs. Rated breaking capacity EN (IEC ) EN (IEC ) 1-pole 2, 3, 4-pole 1-pole 2, 3, 4-pole 230 V AC 230 V AC 400 V AC 230 V AC 230 V AC 400 V AC Rated current I n [A] I cn [ka] I cn [ka] I cn [ka] I cu [ka] I cu [ka] I cu [ka] 5SX SX SX E DIN VDE 0641 T 12 E DIN VDE 0641 T 12 1-pole 2-pole 1-pole 2-pole 230 V AC 400 V AC 220 V AC 440 V AC Rated current I n [A] I cn [ka] I cn [ka] I cn [ka] I cn [ka] 5SX ) 10 1) 1) Time constant 4 ms. 2/8 Siemens I

8 Selectivity, miniature circuit-breakers/fuses Generally, distribution networks Selectivity means, that in the are configured as radial networks. An overcurrent device protective device in the vicinity event of a fault, only the must be provided at each reduction of the conductor cross current paths can continue to of the fault trips. Thus, parallel section. This results in a cascade graded according to the For MCBs with upstream fuses, provide the necessary power. rated current, which should, the selectivity limit essentially where possible, provide selectivity. and tripping characteristics of depends on the current limits the MCB as well as on the pre-arcing I 2 t value of the fuse. Therefore, MCBs with different characteristics and rated breaking capacities also have different selectivity limits. The subsequent tables show the currents up to which selectivity is provided between MCBs and upstream fuses according to DIN VDE 0636 Part 21. The values specified in ka are limit values which have been determined under unfavourable test conditions. In practice, better values can be obtained, depending on the type of the upstream fuse. Limit values of the MCBs/fuses selectivity in ka Downstream MCBs Upstream fuses I n [A] 16 A 20 A 25 A 35 A 50 A 63 A 80 A A 5SX2 Characteristic A Characteristic B Characteristic C Characteristic D r Rated breaking capacity 5SX2 according to EN Siemens I /9

9 Selectivity MCBs/fuses In the event of a short circuit when using the MCBs 5SX4, 5SX7 and fuses according to DIN VDE 0636 Part 21 selectivity is provided up to the indicated values in ka. Limit values of the MCBs/fuses selectivity in ka Downstream MCBs Upstream fuses I n [A] 16 A 20 A 25 A 35 A 50 A 63 A 80 A A 125 A 5SX4 Characteristic B Characteristic C r Rated breaking capacity 5SX4 according to EN Limit values of the MCBs/fuses selectivity in ka Downstream MCB Upstream fuse I n [A] A 125 A 160 A 200 A 224 A 250 A 5SX7 Characteristic B Characteristic C Characteristic D r Rated breaking capacity 5SX7 according to EN /10 Siemens I

10 Selectivity MCBs/circuit-breakers Distribution networks can also In this case, the selectivity limit be configured without any depends on the level of the fuses. In these cases, a peak current Î of the miniature circuit-breaker acts like an circuit breaker and on the tripping current of the circuit-break- upstream protective device. er. Limit values of the MCBs/circuit-breakers selectivity in ka The following tables specify the short-circuit currents in ka up to which selectivity is provided between the MCBs and upstream circuit-breakers according to IEC and DIN VDE 0660, Part 101 at 230/400 V AC. Downstream MCBs Upstream circuit-breakers 3RV1.1 3RV1.2 I n [A] I >[A] I cn [ka] Selectivity limits [ka] 1) 5SX Characteristic A SX2/5SX Characteristic B / / / / / / / / / SX2/5SX Characteristic C / / / / / / / / / / / / / / / / SX Characteristic D ) In 240/415 V, 50 Hz networks, the selectivity limits must be reduced by 10 %. I > = Tripping current. Siemens I /11

11 Selectivity MCBs/circuit-breakers Under short-circuit conditions, in acc. with IEC and selectivity is provided between DIN VDE 0660 Part 101 up to the MCBs and circuit-breakers the specified values in ka. Limit values of the MCBs/circuit-breakers selectivity in ka Downstream MCBs Upstream circuit-breakers 3RV1.3 I n [A] I >[A] I cn [ka] Selectivity limits [ka] 1) 5SX Characteristic A SX2/5SX Characteristic B / / / / / / / / / SX2/5SX Characteristic C / / / / / / / / / / / / / / / / SX Characteristic D ) In 240/415 V, 50 Hz networks, the selectivity limits must be reduced by 10 %. I > = Tripping current. 2/12 Siemens I

12 Selectivity MCBs/circuit-breakers Under short-circuit conditions, in acc. with IEC and selectivity is provided between DIN VDE 0660 Part 101 up to the MCBs and circuit-breakers the specified values in ka. Limit values of the MCBs/circuit-breakers selectivity in ka Downstream MCBs Upstream circuit-breakers 3RV1.4 I n [A] I >[A] I cn [ka] Selectivity limits [ka] 1) 5SX Characteristic A SX2/5SX Characteristic B / / / / / / / / / SX2/5SX Characteristic C / /10 6/10 6/10 6/ / /10 6/10 6/10 6/ / /10 6/10 6/10 6/ / /10 6/10 6/10 6/ / / / / / / / / / / / / SX Characteristic D SX Characteristic C / / / SX Characteristic D / / / ) In 240/415 V, 50 Hz networks, the selectivity limits must be reduced by 10 %. I > = Tripping current. Siemens I /13

13 Selectivity MCBs/circuit-breakers Under short-circuit conditions, in acc. with IEC and selectivity is provided between DIN VDE 0660 Part 101 up to the MCBs and circuit-breakers the specified values in ka. Limit values of the MCBs/circuit-breakers selectivity in ka Downstream MCBs Upstream circuit-breakers 3VF3 3VF3 Adjustable Fixed setting I n [A] I >[A] I cn [ka] Selectivity limits [ka] 1) 5SX2/5SX4 Characteristic A Characteristic B / /10 6/10 6/10 6/10 6/ /10 6/9.7 6/10 6/10 6/ / /6.6 6/10 6/10 6/10 6/ / /6.2 6/6.5 6/ / /10 6/10 6/ / / /10 6/10 6/ / / /10 6/10 6/ / / / / / / / Characteristic C /10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/ /10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/ /10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/ /10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/ / /9.5 6/10 6/10 6/10 6/ /8.2 6/6.3 6/8.2 6/8.6 6/ / /9.5 6/10 6/10 6/10 6/ /8.2 6/6.3 6/8.2 6/8.6 6/ / /9.5 6/10 6/10 6/10 6/ /8.2 6/6.3 6/8.2 6/8.6 6/ / /7.9 6/10 6/10 6/ / / /7.9 6/10 6/10 6/ / / /10 6/10 6/ / / /10 6/10 6/ / / /10 6/10 6/ / / / / / / / Characteristic D SX7 Characteristic C Characteristic D ) In 240/415 V, 50 Hz networks, the selectivity limits must be reduced by 10 %. The selectivity limits are valid for adjustable releases for the maximum value, I n = rated current. I > = Tripping current. 2/14 Siemens I

14 Selectivity MCBs/circuit-breakers Under short-circuit conditions, in acc. with IEC and selectivity is provided between DIN VDE 0660 Part 101 up to the MCBs and circuit-breakers the specified values in ka. Limit values of the MCBs/circuit-breakers selectivity in ka Downstream MCBs Upstream circuit-breakers 3VF4 3VF5 3VF6 3VF7 3VF8 3WN1 3WN6 I n [A] I >[A] I cn [ka] Selectivity limits [ka] 1) 5SX2/5SX4 Characteristic A Characteristic B /10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/ /10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/ /10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/ /10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/ /10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/ /10 6/9.6 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/ /10 6/9.6 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/ / /10 6/10 6/10 6/10 6/10 6/10 6/10 6/ / /10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 Characteristic C /10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/ /10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/ /10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/ /10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/ /10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/ /10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/ /10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/ /10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/ /10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/ /10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/ /10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/ /10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/ /10 6/8 6/9.1 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/ /10 6/8 6/9.1 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/ / /6.5 6/6.5 6/6.5 6/6.5 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/ / /6.2 6/6.2 6/6.2 6/6.3 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 Characteristic D SX7 Characteristic C Characteristic D /70/ 45/70/ 45/70/ 45/70/ 45/70/ 45/70/ 50/70/ 70/ 65/80/ 65/75 1) In 240/415 V, 50 Hz networks, the selectivity limits must be reduced by 10 %. The selectivity limits are valid for adjustable releases for the maximum value, I n = rated current. I > = Tripping current. Siemens I /15

15 Selectivity MCBs/MCBs In distribution networks without any fuses, MCBs provide selectivity between themselves within close limits. Limit values of the MCBs/MCBs selectivity in ka This depends on the peak current Î of the downstream MCB and on the tripping current of the upstream MCB. The following table specifies the short-circuit currents in ka up to which selectivity is provided between MCBs connected in series at 230 V AC. Downstream MCBs Upstream MCBs 5SX4 7 Characteristic C 5SX7 7 Characteristic C 5SX7 8 Characteristic D I n [A] I >[A] I cn [ka] Selectivity limits [ka] 1) 5SX2/5SX4 Characteristic B / / / / / / / / / Characteristic C / /10 6/ / /10 6/ / /10 6/ / /10 6/ / / / / / / / / / / / / /16 Siemens I

16 Back-up protection, MCBs/fuses If the level of the maximum short-circuit current flowing at the MCB location is unkown, or if the specified rated breaking capacity is exceeded, an additional protective device must be connected upstream as backup protection. This prevents Limit values of the MCBs/fuses back-up protection in ka excessive stressing of the MCB. Generally, a fuse is used for this purpose. The following table specifies the short-circuit currents in ka up to which back-up protection is guaranteed if fuses are used acc. to DIN VDE 0636 Part 21. Downstream MCBs Upstream fuses I n [A] 50 A 63 A 80 A A 125 A 160 A 5SX2/5SX4 Characteristic C No back-up protection required up to 50 ka Characteristic B/C Characteristic C Characteristic B/C Characteristic C Test circuit data: Test cycle: U p = 250 V 0 (60 ) - t - 0 (60 ), t = 3 min cos ϕ = 0.27 to 0.49 (2 trips at 60 electrical) Siemens I /17

17 Back-up protection, MCBs/circuit-breakers If MCBs are used in fuseless back-up protection in accordance with EN and distribution boards, circuitbreakers are to be provided as DIN VDE 0660 Part 101. Limit values of the MCBs/circuit-breakers back-up protection in ka The following table shows the short-circuit currents in ka up to which back-up protection is guaranteed if circuit-breakers are used. Downstream MCBs 5SX2/5SX4 Characteristic A, Characteristic B, Characteristic C, Characteristic D, Upstream circuit-breakers 3VF3 Adjustable 3VF3 Fixed setting I n [A] I >[A] I cn [ka] Back-up protection up to ka /10 No back-up protection required up to 50 ka 6 6/ / / / / / / / / / SQ2 Characteristic B, Characteristic C /18 Siemens I

18 Back-up protection, MCBs/circuit-breakers When a short circuit develops, and the upstream circuit-breakers up to the values specified in back-up protection is provided between the downstream MCB ka. Limit value of the MCBs/circuit-breakers back-up protection in ka Downstream MCBs 5SX2/5SX4 Characteristic A, Characteristic B, Characteristic C, Characteristic D 5SQ2 Characteristic B, Characteristic C Upstream circuit-breakers 3VF4 3VF5 3VF6 3VF7 3VF8 3WN1/ 3WS1 I n [A] I >[A] I cn [ka] 45/70/ 45/70/ 45/70/ 45/70/ 45/70/ 50/70/ 70/ 65- Back-up protection up to [ka] /10 No back-up protection required up to 50 ka 6 6/ / / / / / / / / / Siemens I /19

19 e Internal resistances and power losses Data is per phase (with load I n ) I n [A] Type A Type B Type C Type D 5SX2, 5SX4, 5SX5 5SX7 5SQ2 R 1 P v R 1 P v R 1 P v R 1 P v mω W mω W mω W mω W Correction factors for power losses DC and AC up to 60 Hz x 1.0 AC 200 Hz x Hz x Hz x 1.3 2/20 Siemens I

20 Personnel protection using MCBs According to DIN VDE 0 device must ensure that a fault Part 410, to provide protection with negligible impedance (i.e. against hazardous shock currents in TN supply networks, the position between an external a short circuit) at an arbitrary dimensioning of the cross sections of conductors and/or their connected exposed conductive and a protective conductor or a lengths after the protective part causes an automatic disconnection within the specified times of 0.4 s or 5 s. This requirement is met by the following condition: Z s x I a U o Z s I a U o r Impedance of the entire fault loop circuit r Current, which causes the disconnection within the specified times r Voltage to ground Maximum permissible impedance Z, of the fault loop at U o = 230 V AC to comply with the disconnection condition according to DIN VDE 0 Part 410. I n [A] Characteristic A Characteristic B Characteristic C Characteristic D 5SX, 5SQ t a 0.4 s 5 s t a 0.4 s 5 s t a 5 s 5 s t a 0.4 s 5 s Ω Ω Ω Ω Ω Ω Ω Ω For U o = 240 V AC, Z s x For U o = 127 V AC, Z s x Siemens I /21

21 Protecting luminaire circuits Maximum permissible lamp load for a 5SQ3, 5SX2, 5SX4, 5SX5 miniature circuit-breaker Max. number of fluorescent lamps when feeding fluorescent lamps L 18 W, L 36 W, L 38 W, L 58 W. I n [A] Lamp Conventional control gear Electronic control gear Single lamp Full circuit Group circuit uncomp. Parallel Single lamp Two lamps Single lamp Two lamps comp. Characteristic all all B C D B C D all all 10 L 18 W L 36 W L 38 W L 58 W L 18 W L 36 W L 38 W L 58 W L 18 W L 36 W L 38 W L 58 W L 18 W L 36 W L 38 W L 58 W L 18 W L 36 W L 38 W L 58 W L 18 W L 36 W L 38 W L 58 W Comment: MCB design: Circuit impedance: DC operation: Maximum number of low-voltage halogen lamps 12 V The specified lamp load values are valid for single-pole MCBs. When using multipole MCBs, the permissible number of lamps is reduced by 20 %. The specified lamp load values are valid, taking into account a cable impedance of 800 mω. For 400 mω the permissible values are reduced by 10 %, for 200 mω by 20 %. The values in the table are also valid for DC operation for 5SX5 MCBs in conjunction with electronic control gear. I n [A] Lamp 20 W Lamp 50 W transf. 5NZ NZ NZ NZ SX2, 5SX4 Characteristic B Characteristic C Reduction factors for MCBs for a simultaneous switch-on of an incandescent lamp load referred to the rated current of the MCB and the total operating current of the lamps Reduction factor Switching using MCBs Switching using a separate switch 5SQ3, 5SX2, 5SX4, 5SX5 Characteristic A Characteristic B Characteristic C 1 1 Characteristic D 1 1 2/22 Siemens I

22 Load capacity of MCBs with compensated and non-compensated HQ, HQI and NAV lamps (Number) Lamp rating [W] Lamp current [A] Comp. lamp current [A] Inrush [A] I n [A] Lamp rating [W] SQ3, 5SX2, 5SX4 Characteristic B Characteristic C Characteristic D SX7 Characteristic B Characteristic C / /3 4/ / /7 8/ /8 5 Characteristic D 40 79/56 44/28 22/15 13/9 11/8 4/3 5/2 3/ /70 53/35 26/19 16/11 13/10 5/3 6/3 3/ /88 69/44 34/24 20/14 17/12 7/4 8/4 4/ /112 80/56 40/31 24/18 20/16 9/6 10/5 5/3 186/ /70 51/39 31/23 26/20 11/7 12/6 7/ / /87 51/48 31/29 26/25 14/9 15/8 8/5 The different values are valid for compensated/non-compensated lamps. Siemens I /23

23 Voltage-independent, selective main miniature circuit-breakers (SHU) According to DIN VDE 0645 Further, the selective main Selective main miniature circuitbreakers are essentially based vides back-up protection up to miniature circuit-breaker pro- on the mode of operation of 25 ka for all downstream MCBs. conventional MCBs and have a In the past, sealed fuses were delayed thermal release for generally used at the metering overload protection and an location to prevent power theft. electromagnetic fast release with an impact armature for As a result of various modes of short-circuit protection. operation and therefore Further, a selectivity device is different characteristics only a included which identifies limited short-circuit selectivity whether the downstream MCB can be achieved in a cascade in the load circuit can handle of upstream fuses and downstream MCBs. This selectivity the short circuit by itself or not. For situations where the MCB depends on the difference of cannot handle the short circuit, the particular rated currents. If a the selective main miniature circuit-breaker trips. meter fuse was blown due to an overcurrent or a short circuit, the power supply company Independent of its rated service department had to be current, the selective main called-in to replace the sealed miniature circuit-breaker guarantees a selectivity with regard done by a non-specialist. fuse because this could not be to the downstream MCBs acc. to EN and DIN VDE 0641 The selective main miniature circuit-breaker, however, can be Part 11 up to their rated break- reclosed by non-specialists. ing capacity The new selective main miniature circuit-breaker offers the following advantages for the system/plant user: Improved current limiting by supporting the downstream MCB using the selective main miniature circuit-breaker System-compatibility, as, with the exception of the downstream MCB, the operating characteristics of other devices are not influenced High and reliable selectivity between the sub-distribution and meter panel Safe, fast and economical reclosure by non-specialists Reclosure is not possible as long as the cause of the short circuit has not been removed A tariff monitoring function ensures that power taken from the line is registered Isolator characteristics with contact position indication according to EN Application example Selectivity with regard to downstream MCBs up to the rated breaking capacity Selectivity with regard to upstream fuses up to A Summary of the technical data Selective main circuit-breaker Standards DIN VDE 0645 Tripping characteristic E Rated voltage V AC 230/400 Rated breaking capacity ka 25 Size acc. to DIN when mounted on mounting rails acc. to DIN EN when mounting on busbars using an adapter Insulation coordination Rated insulation voltage V AC 690 Degree of pollution 3 for overvoltage class IV Connection Individual connection or group connection using busbars Terminals Saddle terminals on both ends Cross sections On both ends Stranded, max. mm 2 70 Finely stranded, max. mm 2 50 Tripping characteristic E 2/24 Siemens I

24 DC, AC/DC In DC networks up to 60 V or 120 V, all MCBs of the N System, are suitable for single-pole and 2-pole application. The 5SX5 design is required for higher voltages. Contrary to the standard product range, the 5SX5 are equipped with additional permanent magnets in the quenching chamber to support arc suppression. For this reason, the polarity of the MCB is clearly marked and must be observed when connecting the cables and conductors. Up to max. 220 V DC battery voltage Up to max. 220 V DC battery voltage (for centergrounded battery, up to max. 440 V DC) Up to max. 440 V DC battery voltage Siemens I /25

25 Power Supply Company Program Selective Main Miniature Circuit-Breakers (SHU) 5SP3, 25 ka Features Applications Advantages U n :230/400 V, Hz can be used in supply networks up to 250/440 V AC Standards: DIN VDE 0645 Mounting depth: 91 mm As main miniature circuitbreaker in meter panels. As group miniature circuitbreaker in distribution boards. Characteristic E: Adapted to the special application conditions encountered in cascade circuit configurations between fuses and MCBs. Protects insulated cables against overcurrents Isolates loads Power drawn from the supply is registered Non-specialists can reclose the circuit Meets defined selectivity requirements with respect to upstream and downstream overcurrent protective devides Can be screwed to mounting panels Can be clipped onto busbars using an adapter Can be snapped onto mounting rails in accordance with DIN EN using the mounting plate. 2/26 Siemens I

Miniature Circuit-Breakers (MCBs)

Miniature Circuit-Breakers (MCBs) Product overview Miniature Circuit-Breakers (MCBs) Design Tripping characteristic Rated currents I n Rated breaking capacity Power supply company product range 5SP3 E 16 - A Standard product range 5SX2

More information

Control Circuit Protection

Control Circuit Protection Contents 5SJ4 Branch Circuit Protectors 5SY4 Supplementary Protectors 5SY6 Supplementary Protectors 16/19 5SJ4 Page Selection and ordering data 1-pole up to 63A 16/4 1-pole, 2-pole, 16/5 3-pole, 240VAC

More information

Technical data. Miniature Circuit Breakers. System pro M. System pro M

Technical data. Miniature Circuit Breakers. System pro M. System pro M Technical data System pro M System pro M 1 Prior to connection of aluminium conductors ensure that their contact points are cleaned, brushed and coated with grease. The contact terminals must be tighten

More information

Jtec 10kA Miniature Circuit Breaker

Jtec 10kA Miniature Circuit Breaker EN 60898 Jtec 10kA Miniature Circuit Breaker Techna s JTEC range has been enthusiastically adopted by a diverse range of customers seeking a cost effective 10kA performance. Jtec MCBs are available in

More information

Residual Current Protective Devices / Arc Fault Detection Devices (AFDDs)

Residual Current Protective Devices / Arc Fault Detection Devices (AFDDs) Introduction Overview Devices Page Application Standards Used in / Personnel, material and fire protection, as well as protection against direct contact. SIGRES with active condensation protection for

More information

Page. Circuit-Breakers M4 2 for motor protection. Auxiliary contacts 3 Signalling switch Auxiliary releases

Page. Circuit-Breakers M4 2 for motor protection. Auxiliary contacts 3 Signalling switch Auxiliary releases Circuit Breakers M4 Page Circuit-Breakers M4 2 for motor protection Auxiliary contacts 3 Signalling switch Auxiliary releases Insulated 3-pole busbar system 4 Terminal block DIN-rail adapters 5 Busbar

More information

Selective main circuit breakers S 750 series Technical Data

Selective main circuit breakers S 750 series Technical Data Selective main circuit breakers S 750 series Technical Data When connecting aluminium conductors ( 4 mm 2 ) ensure that the contact surfaces of the conductors are cleaned, brushed and treated with grease.

More information

3NP1 Fuse Switch Disconnectors up to 630 A

3NP1 Fuse Switch Disconnectors up to 630 A Switch Disconnectors 3NP1 Fuse Switch Disconnectors up to 630 A Introduction Overview All key product features at a glance available for all sizes Connection of circular conductors and laminated conductors

More information

Switch Disconnectors. SENTRON 3NP5 Fuse Switch Disconnectors up to 630 A. Introduction. 7/106 Siemens LV

Switch Disconnectors. SENTRON 3NP5 Fuse Switch Disconnectors up to 630 A. Introduction. 7/106 Siemens LV Switch Disconnectors Introduction Siemens AG 2010 Overview 3NP5 0 3NP5 2 3NP5 fuse disconnector range 3NP5 4 SENTRON 3NP5 fuse disconnectors are controls for the occasional manual ing/isolating of loads

More information

Protective Devices: Circuit-Breakers 1 )

Protective Devices: Circuit-Breakers 1 ) Protective Devices: Circuit-Breakers 1 ) /2 Introduction SIRIUS circuit-breakers 1 ) up to 100 A / General data /20 For motor protection /22 For motor protection with overload relay function /23 For starter

More information

All round protection guaranteed

All round protection guaranteed s With SLR ll round protection guaranteed Betagard MCB 5SL Inspiring Safety nswers for infrastructure. Overview s a culture Siemens has always endeavoured to introduce innovative products worldwide. The

More information

3VU13, 3VU16 Circuit-Breakers

3VU13, 3VU16 Circuit-Breakers 3VU3, 3VU6 Circuit-Breakers Description The 3VU3, 3VU6 circuit-breakers are compact circuit-breakers for currents up to 80 A which operate according to the current limiting principle. The devices are used

More information

Circuit-Breakers M4 166 for motor protection. Auxiliary contacts 167 Signalling switch Auxiliary releases

Circuit-Breakers M4 166 for motor protection. Auxiliary contacts 167 Signalling switch Auxiliary releases Index Page Circuit-Breakers M4 166 for motor protection Auxiliary contacts 167 Signalling switch Auxiliary releases Insulated 3-pole busbar system 168 Terminal block DIN-rail adapters 169 Busbar adapters

More information

Data sheet. CI-TI TM Contactors and Motor Starters Circuit Breakers CTI B1427

Data sheet. CI-TI TM Contactors and Motor Starters Circuit Breakers CTI B1427 Data sheet CI-TI TM Contactors and Motor Starters Circuit Breakers November 2002 DKACT.PD.C00.L2.02 520B1427 Introduction Circuit breakers/manual motor starters cover the power ranges 0.09-12.5 kw This

More information

SIRIUS 3RU2 Thermal Overload Relays

SIRIUS 3RU2 Thermal Overload Relays Overview 1 2 3 4 6 1 2 NSB0_0207a Connection for mounting onto contactors: Optimally adapted in electrical, mechanical and design terms to the contactors. The overload relay can be connected directly to

More information

Miniature Circuit Breaker

Miniature Circuit Breaker Introduction - Miniature Circuit Breaker (MCB) SALIENT FEATURES SALIENT FEATURES Standards MCBs conform to the latest standard IS 8828: 1996/IEC: 898 1995 Mid-Trip Position The Mid trip position of the

More information

max pole for t=15 ms

max pole for t=15 ms Types RI 61 RI 61N RI 61J RI 62 RI 62J RI 63 RI 63N RI 64 single-pole single-pole + neutral pole single-pole (for DC circuits) two-pole two-pole (for DC circuits) three-pole three-pole + neutral pole three-pole

More information

System pro M compact Miniature Circuit Breaker SU200 M for branch circuit protection acc. to UL 489

System pro M compact Miniature Circuit Breaker SU200 M for branch circuit protection acc. to UL 489 Data Sheet System pro M compact for branch circuit protection acc. to UL 489 2CDC021004S0014 2CDC021046S0014 The miniature circuit breaker SU200 M is BB s solution for UL 489 branch circuit protection

More information

BETA Switching Switches and Light Indicators

BETA Switching Switches and Light Indicators Siemens AG 2008 BETA Switching /2 Product overview /3 5TE8 control switches / 5TE4 pushbuttons /2 5TE5 light indicators /5 5TE8 ON/OFF switches /22 5TE9 busbars /24 5TE switch disconnectors Siemens ET

More information

Low Voltage A GE Power Controls Company. General catalogue

Low Voltage A GE Power Controls Company. General catalogue Low Voltage A GE Power Controls Company General catalogue this is a blanc page Miniature circuit breakers A Miniature circuit breakers AC miniature circuit breakers Benefits of the new MCB s A 3 The AEG

More information

MINIATURE CIRCUIT BREAKER

MINIATURE CIRCUIT BREAKER Technical Article MINIATURE CIRCUIT BREAKER T 146 PURCHASE he Spaceage MCB protects wires and cables automatically against overload and short-circuits in domestic, commercial and industrial installations.

More information

System pro M compact Miniature Circuit Breaker SU200M for branch circuit protection acc. to UL 489

System pro M compact Miniature Circuit Breaker SU200M for branch circuit protection acc. to UL 489 System pro M compact Miniature Circuit Breaker SU200M for branch circuit protection acc. to UL 489 2CDC021004S0014 2CDC021046S0014 The miniature circuit breaker SU 200 M is ABB s solution for UL 489 branch

More information

Protection Equipment

Protection Equipment Protection Equipment Price Groups 101, 102, 121, 131, 143 /2 Introduction Motor Starter Protectors/ Circuit Breakers SIRIUS 3RV2 Motor Starter Protectors up to 40 A new /7 General data /13 For motor protection

More information

and other modular devices for low voltage installation

and other modular devices for low voltage installation Technical catalogue System and other modular devices for low voltage installation 2CSC400002D0204 SUMMARY Introduction Miniature Circuit-Breakers Residual Current Devices Auxiliary elements and accessories

More information

Modular contactor for installation into distribution boards

Modular contactor for installation into distribution boards Modular contactor for installation into distribution boards Description Modular contactors are used for installation in consumer units in dwellings, business premises, hotels, hospitals, shopping centres,

More information

Sentry Technical. Miniature Circuit Breakers (MCBs) Standards and approvals. Description. Technical specification

Sentry Technical. Miniature Circuit Breakers (MCBs) Standards and approvals. Description. Technical specification 543 technical hotline +44 ()1268 56372 Standards and approvals Sentry MCBs are designed to fully comply with the relevant requirements of BS EN 6898: 23. They all feature positive contact status indication

More information

LEXIC Curv LIMOGES Cedex. Cats N (s) : /68/87/88, /48, /84/85, /76/77/95/96/97, /71/72 1.

LEXIC Curv LIMOGES Cedex. Cats N (s) : /68/87/88, /48, /84/85, /76/77/95/96/97, /71/72 1. 87045 LIMOGES Cedex Téléphone : 05 55 06 87 87 Télécopie : 05 55 06 88 88 LEXIC MCB s DX-H 80A, 100A, 125A Curv urves B and C CONTENTS PAGES 1. Description, use...1 2. Range...1 3. Overall dimensions...1

More information

020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB)

020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB) 020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB) CEYLON ELECTRICITY BOARD SRI LANKA Telephone: +94 11 232 0953 Fax: +94 11 232 3935 CONTENTS Page 1.0 Scope 3 2.0 System Parameters 3 3.0 Service

More information

3RT14 Contactors with 3 Main Contacts

3RT14 Contactors with 3 Main Contacts 3RT14 Contactors with 3 Main Contacts for Switching Resistive Loads Contactor Size 3RT14 46 Mechanical endurance Oper. 10 million Electrical endurance Oper. 0.5 million C-1 utilization category at I e

More information

S200 UL 489 Series. Miniature Circuit Breakers. Description. Features

S200 UL 489 Series. Miniature Circuit Breakers. Description. Features S200 UL 489 Series Miniature S200 UL 489 Series Miniature Circuit Breakers Description The S200 Series miniature circuit breaker offers a compact solution for protection requirements. The S200U AND S200UP

More information

Electronic Circuit Breaker ESS20-0..

Electronic Circuit Breaker ESS20-0.. Electronic Circuit Breaker ES-0.. Description Electronic circuit breaker type ES-0.. is designed to ensure selective disconnection of individual loads in systems which are powered by a DC 4 V switch-mode

More information

, , PREPARATION - CONNECTION. Mounting:. On symmetrical EN rail or DIN 35 rail

, , PREPARATION - CONNECTION. Mounting:. On symmetrical EN rail or DIN 35 rail 87045 LIMOGES Cedex Telephone number: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 DX 3 4500 A / 6 ka CONTENTS PAGES 1. Description, use...1 2. Range...1 3. Overall dimensions...1 4. Preparation - Connection...1

More information

Characteristics of LV circuit breakers Releases, tripping curves, and limitation

Characteristics of LV circuit breakers Releases, tripping curves, and limitation Characteristics of LV circuit breakers Releases, tripping curves, and limitation Make, Withstand & Break Currents A circuit breaker is both a circuit-breaking device that can make, withstand and break

More information

Phase + Neutral, neutral on left side

Phase + Neutral, neutral on left side 87045 LIMOGES Cedex Téléphone : 05 55 06 87 87 Télécopie : 05 55 06 88 88 DX 3 MCB 10000 A / 16 ka CONTENTS PAGE 1. Description, use...1 2. Range...1 3. Overall dimensions...1 4. Preparation - Connection...1

More information

SU200M Datasheet. Branch protection acc. to CSA C22.2 No.5 / UL 489

SU200M Datasheet. Branch protection acc. to CSA C22.2 No.5 / UL 489 MINIATURE CIRCUIT BREAKERS SU200M Datasheet Branch protection acc. to CSA C22.2 No.5 / UL 489 The miniature circuit breaker SU200 M is ABB s solution for UL 489 branch circuit protection up to 480 Y/277

More information

87045 LIMOGES Cedex. 2. PRODUCT RANGE (continued) 1. DESCRIPTION - USE. Breaking capacity : Symbol : Technology : 3. OVERALL DIMENSIONS

87045 LIMOGES Cedex. 2. PRODUCT RANGE (continued) 1. DESCRIPTION - USE. Breaking capacity : Symbol : Technology : 3. OVERALL DIMENSIONS 87045 LIMOGES Cedex Phone : + 33 5 55 06 87 87 Fax : + 33 5 55 06 88 88 R.C.B.O. DX 6000 A Phase + Neutral,, neutral on right side Cat. n (s) : 077 31 077 44-077 77 077 84 078 79 079 01-083 95 084 06 084

More information

Index. Manual Motor Starters 1. Auxiliary Contact Blocks 1. Trip Alarm Auxiliary 1. Switch. Shunt Release 1. Under-voltage Release 2.

Index. Manual Motor Starters 1. Auxiliary Contact Blocks 1. Trip Alarm Auxiliary 1. Switch. Shunt Release 1. Under-voltage Release 2. Index Index Page Manual Motor Starters 1 Auxiliary Contact Blocks 1 Trip Alarm Auxiliary 1 Switch Shunt Release 1 Under-voltage Release 2 Accessories 2 Busbar Connectors 2 Enclosures 2 Leistung, kw C mv

More information

DX 3 MCBs. Choice of DX 3 MCBs for capacitor banks. Technical data

DX 3 MCBs. Choice of DX 3 MCBs for capacitor banks. Technical data Specifications IS/IEC 60898-1 2002 Number of poles SP, SPN, DP, TP, TPN, FP Characteristics C & D Curve Breaking capacity 10 ka 0.5 A to 63 A as per IS/IEC 60898-1 2002 16 ka for 0.5 A to 25 A as per IEC

More information

Phase + Neutral, neutral on right side

Phase + Neutral, neutral on right side 87045 LIMOGES Cedex Telephone number: +33 5 55 06 87 87 Fax: +33 5 55 06 88 88 DX 3 MCB 6000 A / 10 ka Cat.. N (s): 4 074 67 / 68 / 69 / 70 / 71 / 72 / 73 / 74 / 75 / 76 / 77 / 78 / 79 ; 4 077 33 / 34

More information

DNX 3 MCB 4500 A / 6 ka Phase + Neutral, neutral on left side

DNX 3 MCB 4500 A / 6 ka Phase + Neutral, neutral on left side 87045 LIMOGES Cedex Telephone number: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 DNX 3 MCB 4500 A / 6 ka CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation

More information

(1,5 modules per pole)

(1,5 modules per pole) 87045 LIMOGES Cedex Telephone: +33 5 55 06 87 87 FAX: +33 5 55 06 88 88 DX 3 MCB 36kA, 80A CONTENTS PAGES 1. Description - Use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation - Connection...

More information

Latch for Contactors 4-pole see page 36. Ratings Rated Aux. Contacts Type Coil voltage 2) AC2 Current Built-in Additional 24 24V= DC 5

Latch for Contactors 4-pole see page 36. Ratings Rated Aux. Contacts Type Coil voltage 2) AC2 Current Built-in Additional 24 24V= DC 5 3-pole DC Operated Ratings Rated Aux. Contacts Type Coil voltage 1) AC2 Current Built-in Additional 24 24V= DC 5 AC3 see 48 60V= DC 6 380V AC1 page 34 110 110V= DC 7 400V 660V 220 220V= DC 8 415V 690V

More information

Siemens AG Price groups PG 14O, 41B, 41E, 41F, 41G, 41H, 41J, 42F, 42J

Siemens AG Price groups PG 14O, 41B, 41E, 41F, 41G, 41H, 41J, 42F, 42J Protection Equipment Siemens AG 2015 Click on the Article No. in the catalog PDF to access it in the Industry Mall and get all related information. Article-No. 3RA1943-2C 3RA1943-2B 3RA1953-2B 3RA1953-2N

More information

1489-M Circuit Breakers

1489-M Circuit Breakers Dual terminals provide wiring/bus bar flexibility and clamp from both sides to improve connection reliability Terminal design helps prevent wiring misses Scratch- and solventresistant printing Suitable

More information

Other Devices. Installation Contactors Z-SCH. Connection diagrams Z-SCH NO 3 NO / 1 NC. Permitted Installation Positions

Other Devices. Installation Contactors Z-SCH. Connection diagrams Z-SCH NO 3 NO / 1 NC. Permitted Installation Positions Installation Contactors Z-SCH These switching devices have been designed and rated particularly for modular installation in modular distribution boxes for electrical installation or cabinets with device

More information

S200 UL 489 Series. Miniature circuit breakers S200. Features. Description

S200 UL 489 Series. Miniature circuit breakers S200. Features. Description UL 489 Series UL 489 Series Description The Series miniature circuit breaker offers a compact solution for protection requirements. The U AND UP devices are UL 489 tested limiting and DIN rail mounted.

More information

S200 UL 1077 Series S200. Supplementary protective devices. UL 1077 Series. Miniature. circuit breakers. S200 Supplementary protective devices

S200 UL 1077 Series S200. Supplementary protective devices. UL 1077 Series. Miniature. circuit breakers. S200 Supplementary protective devices UL 077 Series Supplementary protective devices The UL 077 Series miniature supplementary protector offers a compact solution for protection requirements. The devices are DIN rail mounted. The is available

More information

Thermal-Magnetic Circuit Breaker 2210-S291-P9M A

Thermal-Magnetic Circuit Breaker 2210-S291-P9M A Thermal-Magnetic Circuit Breaker 0-S9-P9M-40033-...A Description Single pole thermal-magnetic circuit breaker with trip-free mechanism and toggle actuation. Two-chamber construction with cascade contact

More information

Thermal-magnetic Miniature Circuit Breaker 4230-T...

Thermal-magnetic Miniature Circuit Breaker 4230-T... Thermal-magnetic Miniature Circuit Breaker 420-T... Description Single pole and multipole thermal-magnetic miniature circuit breakers (MCBs) in accordance with EN 60947-2, UL 077 and UL 489 for DIN rail

More information

RESIDUAL CURRENT CIRCUIT BREAKERS WITH OVERCURRENT PROTECTION OLE

RESIDUAL CURRENT CIRCUIT BREAKERS WITH OVERCURRENT PROTECTION OLE OLE Residual current circuit breakers RESIDUAL CURRENT CIRCUIT BREAKERS WITH OVERCURRENT PROTECTION OLE OLE-10B-1N-030AC The device is a combination of residual current circuit breaker and circuit breaker.

More information

Magnetic Overcurrent Circuit Breaker

Magnetic Overcurrent Circuit Breaker Magnetic Overcurrent Circuit Breaker 808-... Description ngle pole miniaturised magnetic circuit breakers with unique highspeed operating mechanism and push/pull on/off manual actuation. Fitted with electrically

More information

Technical Data. Miniature circuit-breakers for branch circuit protection according to UL 489, CSA C 22.2 No. 5

Technical Data. Miniature circuit-breakers for branch circuit protection according to UL 489, CSA C 22.2 No. 5 Technical Data Miniature circuit-breakers for branch circuit protection according to UL 489, CSA C 22.2 No. 5 When connecting aluminum conductors, ensure that the contact surfaces of the conductors are

More information

Bulletin 1489 Circuit Breakers. Selection Guide

Bulletin 1489 Circuit Breakers. Selection Guide Bulletin 1489 s Selection Guide Bulletin 1489-A Overview/Description Bulletin 1489-A s Energy-limiting design protects downstream components better than conventional breakers during short circuits Field-mountable

More information

NB1 Miniature Circuit Breaker

NB1 Miniature Circuit Breaker P-00 Modular DIN Rail Products MCB NB Miniature Circuit Breaker Color coded contact position indicator provides visual indication of the device status and insulation function Magnetic trip elements provide

More information

MINIATURE CIRCUIT BREAKERS RCBO s & DIN RAIL MOUNTED FUSE HOLDERS

MINIATURE CIRCUIT BREAKERS RCBO s & DIN RAIL MOUNTED FUSE HOLDERS MINIATURE CIRCUIT BREAKERS RCBO s & DIN RAIL MOUNTED FUSE HOLDERS MANUFACTURED IN THE EU EUROPEAN QUALITY 1, 2 & 3 POLE MCB s TRIPPING CURVES C & D CURRENT RATINGS 1AMP TO 63AMPS 10KA BREAKING CAPACITY

More information

Protection Equipment. 5/2 Introduction

Protection Equipment. 5/2 Introduction Protection Equipment /2 Introduction SIRIUS 3RV2 Motor Starter Protectors/ Circuit Breakers up to 40 A /6 General data /12 For motor protection /14 For motor protection with overload relay function /1

More information

Technical Information

Technical Information -100 Controller IEC Performance Data (CSA C22.2, UL 508 No. 14 in connection with a short-circuit protection device Catalog No. -100... 25A 40A 63A 90A Maximum Short-Circuit Current 480V [ka] 65 65 42

More information

Magnetic and Hydraulic-Magnetic Circuit Breaker

Magnetic and Hydraulic-Magnetic Circuit Breaker Magnetic and Hydraulic-Magnetic Circuit Breaker 845-... Description Single or multipole hydraulic-magnetic circuit breakers with trip-freemechanism and toggle actuation. A choice of switching characteristics

More information

Basic function. Rated current. Appropriate for three-phase motors of output 2) [kw] I n. = 400 V a.c. 2) Appropriate for three-phase motors

Basic function. Rated current. Appropriate for three-phase motors of output 2) [kw] I n. = 400 V a.c. 2) Appropriate for three-phase motors MOTOR STARTERS SM Basic function Switching and protection of motors up to A Protection against short-circuit and protection against overload The device responds to phase failure The device is provided

More information

Motor Protection Circuit Breakers 3VU13 and 3VU16

Motor Protection Circuit Breakers 3VU13 and 3VU16 Motor Protection Circuit Breakers 3VU13 and 3VU16 3VU13/3VU16 is suitable for use in fuseless motor feeders upto 11KW/22KW (25A/63A) respectively. 3VU motor protection circuit breakers are used for protection

More information

Siemens AG Switch Disconnectors SENTRON. Configuration. Edition 10/2015. Manual. siemens.com/lowvoltage

Siemens AG Switch Disconnectors SENTRON. Configuration. Edition 10/2015. Manual. siemens.com/lowvoltage SENTRON Configuration Manual Edition 10/2015 siemens.com/lowvoltage 2 Introduction LD main control and EMERGENCY-STOP switches up to 250 A 4 Introduction 7 Front mounting 10 Floor mounting 11 Distribution

More information

SIRIUS 3RV2 Motor Starter Protectors/Circuit Breakers up to 40 A Accessories Enclosures and front plates

SIRIUS 3RV2 Motor Starter Protectors/Circuit Breakers up to 40 A Accessories Enclosures and front plates Motor Starter Protectors/Circuit Breakers SIRIUS 3RV2 Motor Starter Protectors/Circuit Breakers up to 40 A Accessories Enclosures and front plates Overview Enclosures For stand-alone installation of 3RV20

More information

MCBs and accessories are certified under CSA C22.2 No. 235 per File LR Tripping characteristics

MCBs and accessories are certified under CSA C22.2 No. 235 per File LR Tripping characteristics Miniature circuit breakers General information General information Miniature circuit breakers (MCBs) are used throughout the world in all types of electrical installations. ABB MCBs are recognized for

More information

DX³ 4-pole RCBO 6000 A/10 ka

DX³ 4-pole RCBO 6000 A/10 ka 87045 LIMOGES Cedex Telephone number: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 DX³ 4-pole RCBO CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation - Connection...

More information

Electronic Circuit Breaker ESS20

Electronic Circuit Breaker ESS20 Electronic Circuit Breaker ESS20 Description Electronic circuit breaker type ESS20 is designed to ensure selective disconnection of individual loads in systems which are powered by a DC 24 V switch-mode

More information

RX 3 M.C.B A up to 63 A

RX 3 M.C.B A up to 63 A 87045 LIMOGES Cedex Telephone: +33 5 55 06 87 87 FAX: +33 5 55 06 88 88 RX 3 M.C.B. 6000 A up to 63 A CONTENTS PAGES 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation - Connection...

More information

PKZ 2 System For Optimum Motor and System Protection

PKZ 2 System For Optimum Motor and System Protection www.moeller.net PKZ 2 System For Optimum Motor and System Protection The complete range of contactors, efficient motorstarters and controlled drives for the motor circuit. New simple to install solutions

More information

Approved Standards. Ordering Information. Mini Motor Contactor J7KNA. Model Number Legend. Main contactor. Accessories. Mini Motor Contactor J7KNA 1

Approved Standards. Ordering Information. Mini Motor Contactor J7KNA. Model Number Legend. Main contactor. Accessories. Mini Motor Contactor J7KNA 1 Mini Motor Contactor J7KNA ) Main contactor AC & DC operated Integrated auxiliary contacts Screw fixing and snap fitting (35 mm DIN-rail) Range from 4 to 5.5 (AC 3, 380/415V) 4 -main pole version (4 AC

More information

Cat. N (s) : /65/66/83/84, /94/95/96/99, /01/02/06/07/11/12/13/14. Pollution degree : C / + 40 C. .

Cat. N (s) : /65/66/83/84, /94/95/96/99, /01/02/06/07/11/12/13/14. Pollution degree : C / + 40 C. . 87045 LIMOGES Cedex Telephone : (+33) 05 55 06 87 87 Fax : (+ 33) 05 55 06 88 88 R.C.C.B. s 0090 00/01/02/06/07/11/12/13/14 0/01/02/06/07/11/12/13/14/18/19/23/24/25/26/ /18/19/23/24/25/26/45/46 45/46 0090

More information

LINOCUR Size D02 63A 230VAC/440VAC

LINOCUR Size D02 63A 230VAC/440VAC IEC FUSE SWITCH DISCONNECTORS D0 FUSE COMBINATION UNITS The D0 Linocur is a combination of switch disconnector fuse and Neozed 63A fuse-link, equiped with significant safety characeristics and sophisticated

More information

SENTRON Switching and Protection Devices Switch Disconnectors

SENTRON Switching and Protection Devices Switch Disconnectors SENTRON Switching and Protection Devices Switch Disconnectors /2 Introduction 3K, 3KE, 3LD Switch Disconnectors 3K, 3KE Switch Disconnectors up to 1000 /4 General data /8 Floor mounting 3LD Main and EMERGENCY-STOP

More information

DATASHEET - DILMC9-10(24VDC) Technical data General. Contactor, 3p+1N/O, 4kW/400V/AC3. Catalog No Eaton Catalog No. XTCEC009B10TD.

DATASHEET - DILMC9-10(24VDC) Technical data General. Contactor, 3p+1N/O, 4kW/400V/AC3. Catalog No Eaton Catalog No. XTCEC009B10TD. DATASHEET - DILMC9-10(24VDC) Technical data General Contactor, 3p+1N/O, 4kW/400V/AC3 Part no. DILMC9-10(24VDC) Catalog No. 277468 Eaton Catalog No. XTCEC009B10TD EL-Nummer 4110305 (Norway) Standards IEC/EN

More information

Short-circuit current limiter S800-SCL-SR

Short-circuit current limiter S800-SCL-SR Short-circuit current limiter S800-SCL-SR 2 ABB Short-circuit current limiter S800-SCL-SR Self-resetting current limiting module S800-SCL-SR is ABB s innovative self-resetting current limiting module which

More information

DEVICE STATE/BYPASSED FAILURE OVERLOAD

DEVICE STATE/BYPASSED FAILURE OVERLOAD Technical specifications Type 5. 7. Control electronics Rated values Terminal Rated control supply voltage A1A2 V AC 115 230 115 230 Tolerance % -15+10-15+10 Rated control supply STANDBY ma 15 15 Rated

More information

The breakers offer thermal-magnetic trip protection according to Z and K characteristics.

The breakers offer thermal-magnetic trip protection according to Z and K characteristics. Series High Performance Circuit Breakers Description The high performance MCB offers a compact solution to circuit protection. The devices are DIN rail mounted. The is available with application-specific

More information

CI-TI Contactors and motor starters Types CI 61 - CI 98

CI-TI Contactors and motor starters Types CI 61 - CI 98 Data sheet CI-TI Contactors and motor starters s CI 6 - CI 98 Contactors CI 6, CI 7, CI 86 and CI 98 switch powers of up to 0 kw, 7 kw, 45 kw and 55 kw respectively under 80 V - loads. Accessories include

More information

3 - Protection components Motor circuit-breakers

3 - Protection components Motor circuit-breakers Contents 0 - Protection components Motor circuit-breakers protection components for the motor protection Thermal-magnetic motor circuit-breakers Selection guide..............................................page

More information

SENTRON 3NP1 Fuse Switch Disconnectors up to 630 A

SENTRON 3NP1 Fuse Switch Disconnectors up to 630 A Introduction Overview All key product features at a glance available for all sizes Connection of circular conductors and laminated conductors Fuse monitoring possible throughout Busbar supports can be

More information

BETA Fuses and Fuse Systems

BETA Fuses and Fuse Systems Introduction Overview Application LV HRC fuses are used for installation systems in non-residential, commercial and industrial buildings as well as in the switchboards of power supply companies. Fuses

More information

Miniature circuit breaker Application guide

Miniature circuit breaker Application guide Miniature circuit breaker Application guide Miniature Miniature circuit circuit breakers breakers Application S200 guide Introduction The circuit breaker plays an important role in providing over-current

More information

System pro M compact Miniature Circuit Breaker S 200 M UC for DC and AC applications

System pro M compact Miniature Circuit Breaker S 200 M UC for DC and AC applications Data Sheet System pro M compact Miniature Circuit Breaker S 200 M UC for DC and AC applications 2CDC021031S0011 2CDC021033S0011 The miniature circuit breaker S 200 M UC extends the established ABB System

More information

Technical data for manual motor starters Type MS325

Technical data for manual motor starters Type MS325 for manual mor starters Type MS325 General data Rated voltage 600 V Rated current 25 A (14 setting ranges, 0.1 25A) Rated frequency 50-60 Hz Electrical and mechanical life endurance 100,000 operations

More information

Main catalogue. Distribution Innovation

Main catalogue. Distribution Innovation Main catalogue Distribution Innovation Contents The family... 2 3 Miniature circuit-breakers - General, technical data... 6 9 - Order data... 10 19 Residual current operated circuit-breakers - Residual

More information

Modular contactors and relays

Modular contactors and relays pages /4 to / pages /8 and /9 pages /10 and /11 pages /12 and /13 Presentation and standards Presentation Designed for use in modular panels and enclosures, these contactors feature : i Easy installation

More information

RX 3 M.C.B A up to 63 A

RX 3 M.C.B A up to 63 A 87045 LIMOGES Cedex Telephone: +33 5 55 06 87 87 FAX: +33 5 55 06 88 88 RX 3 M.C.B. 6000 A up to 63 A Cat. N (s): 4 197 49 to 4 199 23 CONTENTS PAGES 1. Description, use... 1 2. Range... 1 3. Overall dimensions...

More information

IEC Low Voltage General Purpose Protection

IEC Low Voltage General Purpose Protection , 6A, 0/400VAC (/440VAC) Complying with DIN VDE 0660 Part 07 EN / IEC 60947- DIN VDE 066 Part IEC 6069- DIN VDE 068 DIN VDE 4880 The D0-LINOCUR is a combination of switch-disconnector-fuse and NEOZED 6

More information

Model Number Legend. Motor Contactor J7KN. Motor Contactor J7KN 1

Model Number Legend. Motor Contactor J7KN. Motor Contactor J7KN 1 Motor Contactor J7KN Range from 4 to 500 kw (AC 3, 380/415 V) AC and DC operated Integrated auxiliary contacts; integrated aux. contact of J7KN contactors up to 11kW suitable for electronic circuits Screw

More information

SENTRON Switching and Protection Devices Molded Case Circuit Breakers

SENTRON Switching and Protection Devices Molded Case Circuit Breakers SENTRON Switching and Protection Devices Molded Case Circuit Breakers /2 Introduction 3VL Molded Case Circuit Breakers up to 00 A General data /4 - Design /12 - Function /15 - Integration / - Configuration

More information

W DATASHEET: MINIATURE CIRCUIT BREAKER (MCB), SERIES AMPARO

W DATASHEET: MINIATURE CIRCUIT BREAKER (MCB), SERIES AMPARO W DATASHEET: MINIATURE CIRCUIT BREAKER (MCB), SERIES AMPARO W SCHRACK-INFO Lift and clamp terminals on both sides Terminal guide for secure connection Terminal cross-section: 1-25mm² Snap-on mounting for

More information

IP20 degree of protection; IP40 degree of protection after installation in a distribution box

IP20 degree of protection; IP40 degree of protection after installation in a distribution box RI 50 RI 50 is used for the protection of installations and devices (overload and short circuit), and as a disconnector in case of electric shock Simple and quick fixing to a 35 mm mounting rail in accordance

More information

Thermal-Magnetic Circuit Breaker 201/-WA

Thermal-Magnetic Circuit Breaker 201/-WA Thermal-Magnetic Circuit Breaker 0/-WA Description Single pole thermal-magnetic circuit breaker with tease-free, trip-free, snap action mechanism and two button operation (M-type TM CBE to EN 60934). Featuring

More information

Approved Standards. Motor Contactor. Main contactor. Accessoires. 21 Motor Contactor J7KN

Approved Standards. Motor Contactor. Main contactor. Accessoires. 21 Motor Contactor J7KN Motor Contactor Main contactor AC & DC operated Integrated auxiliary contacts Screw fixing and snap fitting (35 mm DIN rail) up to 45 kw Range from 4 to 110 kw (AC 3, 380/415V) Finger proof ( VBG 4) Accessoires

More information

Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-G V

Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-G V Description Single and two pole magnetic circuit breakers with trip-free mechanism and push/pull on/off manual actuation. A choice of fast magnetic only or hydraulically delayed switching characteristics

More information

W Datasheet: Residual current circuit breaker, series PRIORI, 10kA, Typ B

W Datasheet: Residual current circuit breaker, series PRIORI, 10kA, Typ B W Datasheet: Residual current circuit breaker, series PRIORI, 10kA, Typ B W SCHRACK-INFO All-current sensitive RCCB ( type B, B+ and Bfq) B+ types also meet the requirements of superior fire-protection

More information

AF series contactors (9 2650)

AF series contactors (9 2650) R E32527 R E39322 contactors General purpose and motor applications AF series contactors (9 2650) 3- & 4-pole contactors General purpose up to 2700 A Motor applications up to 50 hp, 900 kw NEMA Sizes 00

More information

Thermal-magnetic Miniature Circuit Breaker 4230-T...

Thermal-magnetic Miniature Circuit Breaker 4230-T... Thermal-magnetic Miniature Circuit Breaker 40-T... Description Single pole and multipole thermal-magnetic miniature circuit breakers (MCBs) in accordance with EN 60947-, UL 1077 and UL 489 for DIN rail

More information

Miniature Circuit Breaker UL / CSA Range

Miniature Circuit Breaker UL / CSA Range PRODUCT CATALOG CANADA Miniature Circuit Breaker UL / CSA Range UL489 / CSA C22.2 No.5 devices UL1077 / CSA C22.2 No. 235 devices Electronic Protection Devices Technical data Miniature Circuit Breakers

More information

FUSE: SAFE & RELIABLE

FUSE: SAFE & RELIABLE FUSE: SAFE & RELIABLE VS. CIRCUIT BREAKER Tech Topics: Selective Coordination Note 2, Issue 1 Franck Charlier Technical Support Engineer Points of interest: Power fuse needs no repair only to be replaced

More information

Residual current circuit breakers with conditional shortcircuit

Residual current circuit breakers with conditional shortcircuit LFE Residual current circuit breakers RESIDUAL CURRENT CIRCUIT BREAKERS LFE Residual current circuit breakers with conditional shortcircuit current 6 ka. They react to sine-wave residual current (type

More information

Approved Standards. Ordering Information. Thermal Overload Relay J7TKN. Model Number Legend. Thermal Overload Relay. Accessories

Approved Standards. Ordering Information. Thermal Overload Relay J7TKN. Model Number Legend. Thermal Overload Relay. Accessories Thermal Overload Relay J7TKN ) Thermal Overload Relay Direct and separate mounting Single phasing sensivity according to IEC 60947-4-1 Finger proof (BGV A2) Accessories Set for single mounting Approved

More information