APPENDIX E. Electrical System Single Line Diagram Overcurrent Protection Study Overcurrent Protection Device Specifications
|
|
- Shona Richardson
- 6 years ago
- Views:
Transcription
1 Student Resource Building University of California Santa Barbara Clement Fung Lighting Electrical Option APPENDIX E Electrical System Single Line Diagram Overcurrent Protection Study Overcurrent Protection Device Specifications
2
3 Overcurrent Protection and Coordination Main Switchboard (MS) Panel HAa Panel HA Panel HA Feeder to HA Breaker (A) 60 % of Rated Current Actual Current (A) Time(s) Actual Current (A) Time(s) Actual Current (A) Time(s) Actual Current (A) Time(s) Actual Current (A) Time(s) Breaker (A) Transformer TA (primary) Transformer TA (secondary) Feeder to Panel LAa % of Rated Current Actual Current (A) Time(s) Actual Current (A) Time(s) Actual Current (A) Time(s)
4 Time-Current Curves For Branch Circuit Protection "Path B-C-D-E" 0 00 Current (A) A A A 60A A Time (Seconds)
5 Time-Current Curves For Branch Circuit Protection "Path B--" 0 00 Current (A) A A A A Time (Seconds)
6 9-67N Page Types ND, CND, HND, CHND, NDC, CNDC Equipped With Type NES Digitrip RMS Trip Units With Adjustable Short Time Delay (Phase Protection) CURRENT IN MULTIPLES OF RATING PLUG AMPERES (I n ) ,000 MINUTE HOUR HOURS,000,000 Long Delay➀ Minimum Total Clearing Time Standard Plug X Long Delay➀ Maximum Total Clearing Time 4X 6X 7X 8X Short Delay Pick Up Settings (Tolerance ±%) Circuit Breaker Time/Current Curves (Phase Current) Series C N-Frame Circuit Breakers Equipped With Type NES Digitrip RMS Trip Units The NES Digitrip RMS Trip Units are AC only devices that employ microprocessor based technology that provides true RMS current sensing means for proper correlation with thermal characteristics of conductors and equipment. They are used with Circuit Breaker Types ND, CND, HND, CHND, NDC, and CNDC. Adjustable Short Time Delay Frame Amperes (Max.) Available Plugs Ampere Type (In) 6 4,,,,, 6, 0 6,, 0, Interrupting s /60 Hz RMS Sym. Amperes (ka) Breaker Type ND, CND HND, CHND NDC, CNDC Digitrip RMS Plug Push Cat. to /n Trip Y Engaged Remove Adj. Adj. Adj. UL/CSA 40V 480V V Catalog Number 8NEST 8NEST 8NES6T➃ 8NEST 8NEST 8NEST 8NES4T 8NEST A8NEST A8NEST➃ NEST NES0T NEST➃ NEST NEST NES6T➃ NEST ANEST Short Delay Pickup Range Amperes Notes Curve accuracy applies from - C to + C ambient. For possible ampere derating for ambient above 40 C, refer to Cutler-Hammer. Digitrip RMS trip units are suitable for functional field testing with test kit Cat. No. STK. For field testing using primary injection methods, follow NEMA publication AB For ground fault time-current curves see SC-77-9A. ➀ There is a memory effect that can act to shorten the long delay. The memory effect comes into play if a current above the long delay pick up value exists for a time and then is cleared by the tripping of a downstream device or the circuit breaker itself. A subsequent overload will cause the circuit breaker to trip in shorter time than normal. The amount of time delay reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately five minutes is required between overloads to completely reset the memory. ➁ For high fault current levels a fixed instantaneous override is provided at 0A (Tolerance ±%). ➂ The end of the curve is determined by the interrupting rating of the circuit breaker. See above tabulation. ➃ Not UL/CSA Listed. Typical Trip Unit Nameplate Short Delay Pickup x In 4 6 TEST Digitrip RMS 7 Trip Unit 8 40 C Ambient IEC V 80-4V ICS = ICU ICW = S Uimp = 8kV X X MS. MS MS I Instantaneous Overide➁ SECONDS Interrupting Determines End of Curve➂ CURRENT IN MULTIPLES OF RATING PLUG AMPERES (I n ).00,000,000,000 40,000,000 CURRENT IN AMPS 60,000 70,000 80,000 90,000,000,000 Curve No. SC-76-9A October 997
7 9-67N Page Types ND, CND, HND, CHND, NDC, CNDC Equipped With Type NES Digitrip RMS Trip Units With I t Ramp Short Time Delay (Phase Protection) CURRENT IN MULTIPLES OF RATING PLUG AMPERES (I n ) ,000 MINUTE HOUR HOURS,000,000 Long Delay➀ Minimum Total Clearing Time Standard Plug X Long Delay➀ Maximum Total Clearing Time X 4X Short Delay Pick Up Settings (Tolerance ± %) Circuit Breaker Time/Current Curves (Phase Current) Series C N-Frame Circuit Breakers Equipped With Type NES Digitrip RMS Trip Units The NES Digitrip RMS Trip Units are AC only devices that employ microprocessor based technology that provides true RMS current sensing means for proper correlation with thermal characteristics of conductors and equipment. They are used with Circuit Breaker Types ND, CND, HND, CHND, NDC, and CNDC. I t Ramp Short Time Delay Frame Amperes (Max.) Available Plugs Ampere (In) 6 4,,,,, 6, 0 6,, 0, Interrupting s /60 Hz RMS Sym. Amperes (ka) Breaker Type ND, CND HND, CHND NDC, CNDC Digitrip RMS Plug Push Cat. to /n Trip Y Engaged Remove Type Adj. Adj. Adj. Typical Trip Unit Nameplate Short Delay Pickup x I n 4 6 TEST Digitrip RMS 7 Trip Unit 8 40 C Ambient UL/CSA 40V 480V V Catalog Number 8NEST 8NEST 8NES6T➃ 8NEST 8NEST 8NEST 8NES4T 8NEST A8NEST A8NEST➃ NEST NES0T NEST➃ NEST NEST NES6T➃ NEST ANEST Short Delay Pickup Range Amperes IEC V 80-4V ICS = ICU ICW = S Uimp = 8kV Notes Curve accuracy applies from - C to + C ambient. For possible ampere derating for ambient above 40 C, refer to Cutler-Hammer. Digitrip RMS trip units are suitable for functional field testing with test kit Cat. No. STK. For field testing using primary injection methods, follow NEMA publication AB X 6X 8X For ground fault time-current curves see SC-77-9A. ➀ There is a memory effect that can act to shorten the long delay. The memory effect comes into play if a current above the long delay pick up value exists for a time and then is cleared by the tripping of a downstream device or the circuit breaker itself. A subsequent overload will cause the circuit breaker to trip in shorter time than normal. The amount of time delay reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately five minutes is required between overloads to completely reset the memory. ➁ For high fault current levels a fixed instantaneous override is provided at 0A (Tolerance ±%). ➂ The end of the curve is determined by the interrupting rating of the circuit breaker. See above tabulation. ➃ Not UL/CSA Listed. 7X. Instantaneous Overide➁ SECONDS Interrupting Determines End of Curve➂ CURRENT IN MULTIPLES OF RATING PLUG AMPERES (I n ).00,000,000,000 40,000,000 CURRENT IN AMPS 60,000 70,000 80,000 90,000,000,000 Curve No. SC-7-9A October 997
8 9-67L Page Types LDB, LD, HLD Equipped With Type LT Thermal-Magnetic Trip Unit CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING (I n ) MINUTE HOUR HOURS,000,000, Minimum 0 Maximum Single Pole Trip Times at C Maximum ,000 Circuit Breaker Time/Current Curves Series C L-Frame Circuit Breakers Equipped With Type LT Thermal-Magnetic Trip Unit Catalog Types LDB, LD, HLD Circuit Breakers,, and 4 Poles For application and coordination purposes only. Thermal calibration based on 40 C ambient, cold start. Connected with four (4) feet of rated wire (7 C) per terminal. Tested in open air with current in all poles. Instantaneous calibration based on single-pole tests. Maximum Voltage V., Ac (/60 Hz.) V., Dc Breaker Rated Amperes (I n ) Instantaneous Trip Amperes (See Figure Below),,,, Interrupting Breaker UL/CSA Type RMS Sym. ka, /60 Hz. LDB LD HLD LDB LD HLD,000,000 40,000,000 60, V. 480 V. V. V. IEC 947- RMS Sym. ka, /60 Hz. ka, Dc 40 V., (U e ) 80 V., (U e ) 4 V., (U e ) V., (U e ) Utilization Category A U IMP = 8 kv 70,000 80,000 90,000,000 to 0% of trip unit rating (Dc values are approximately 40% higher) ka, Dc I cu I cs I cu I cs I cu I cs I cu I cs ,000,000,000 HOURS HOUR MINUTE Note: For additional information on the trip unit, see IL 9C606. ➀ Single pole data at C based on NEMA Procedures (AB 4-99) for verifying performance of molded case circuit breakers. Typical Trip Unit Nameplate 7 Magnetic Multiples Of I n C Thermal Magnetic Trip Unit 7 Amps (In) Push to Trip Cat. 40 C No. 7 Individual Pole Adjustments ±% ±% X X Adjustable Magnetic Trip.. Maximum Interrupting Time Interrupting Determines End of Curve ,000,000,000 40,000,000 CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING (I n ) 60,000 70,000 80,000 90,000,000 Curve No. SC B October 997
9 Cutler-Hammer Types FD and HFD Amperes Technical Data Effective: May 999 Page Page 6a MINUTE HOUR HOURS,000,000,000 7-A ➀ Maximum Single Pole Trip Times at C ➁ CURRENT IN MULTIPLES OF I n Circuit Breaker Time/Current Curves Molded-Case Circuit Breakers Catalog Types FD/HFD Circuit Breakers, Two, Three and Four Poles For application and coordination purposes only. Based on 40 C ambient, cold start. Connected with four (4) feet of rated wire (7 C) per terminal. Tested in open air with current in all poles. Maximum AC Volts: 690 at /60 Hz Maximum DC Volts: Breaker In Amperes Instantaneous Pick-up, Amperes RMS 7 Breaker Type FD HFD Interrupting s Symmetrical RMS Amperes (ka), Icu 40 Vac 480 Vac Vac 0 8 Vac Notes: ➀ Inverse Time Overcurrent Release. ➁ Single Pole Test Data at C based on NEMA Procedures (AB 4-99) for verifying performances of Molded Case Circuit Breakers. ➂ Total Operation Time. ➃ Interrupting Determines End of Curve. In this interruption region: The curve is drawn for I n = A. For I n A, the end points in this region are displaced along the current-axis by a factor (A/I n ),000,000 HOURS HOUR MINUTE Maximum Trip Time Minimum Trip Time 7 A A. A. ➂ ➃ CURRENT IN MULTIPLES OF I n 0.00 Curve No. SC A AD 9-67F
10 9-67F Page 6 Types FDB, FD and HFD Amperes ,000 MINUTE HOUR HOURS,000, A 0 Maximum Single Pole Trip Times at C Circuit Breaker Time/Current Curves Series C F-Frame Circuit Breakers Catalog Types EHD, FDB, FD and HFD Circuit Breakers, Two, Three and Four Poles For application and coordination purposes only. Based on 40 C ambient, cold start. Connected with four (4) feet of rated wire (60 C up to amps, 7 C above amps) per terminal. Tested in open air with current in all poles. Maximum AC Volts: at 60 Hz Maximum DC Volts: Breaker Continuous Amperes Instantaneous Trip Amperes Amps See Curve Interrupting (UL/CSA Listed) Breaker Symmetrical RMS Amperes (KA) Amps (KA) 40 V., 480 V., V., Ac V., Dc FDB FD HFD Single pole test data at C based on NEMA Procedures (AB 4-99) for verifying performance of molded case circuit breakers.,000,000 HOURS HOUR MINUTE Minimum Maximum.. Maximum Interrupting Time Interrupting Determines End of Curve (See Above) Curve No. SC B October 997
11 9-67F Page Types EHD, FDB, FD and HFD Amperes ,000 MINUTE HOUR HOURS,000,000 A Maximum Single Pole Trip Times at C Circuit Breaker Time/Current Curves Series C F-Frame Circuit Breakers Catalog Types EHD, FDB, FD and HFD Circuit Breakers, Two, Three and Four Poles For application and coordination purposes only. Based on 40 C ambient, cold start. Connected with four (4) feet of rated wire (60 C up to amps, 7 C above amps) per terminal. Tested in open air with current in all poles. Maximum AC Volts: at 60 Hz Maximum DC Volts: Breaker Continuous Amperes Instantaneous Trip Amperes Amps See Curve Interrupting (UL/CSA Listed) Breaker Symmetrical RMS Amperes (KA) Amps (KA) 40 V., 480 V., V., Ac V., Dc EHD FDB FD HFD Single pole test data at C based on NEMA Procedures (AB 4-99) for verifying performance of molded case circuit breakers.,000,000 HOURS HOUR MINUTE Minimum Maximum.. Maximum Interrupting Time Interrupting Determines End of Curve (See Above) Curve No. SC B October 997
12 9-67F Page 8 Types EHD, FDB, FD and HFD 60 Amperes ,000 MINUTE HOUR HOURS,000,000 60A Maximum Single Pole Trip Times at C 0 Interrupting (UL/CSA Listed) Breaker Symmetrical RMS Amperes (KA) Amps (KA) 40 V., 480 V., V., Ac V., Dc EHD FDB FD HFD Circuit Breaker Time/Current Curves Series C F-Frame Circuit Breakers Catalog Types EHD, FDB, FD and HFD Circuit Breakers, Two, Three and Four Poles For application and coordination purposes only. Based on 40 C ambient, cold start. Connected with four (4) feet of rated wire (60 C up to amps, 7 C above amps) per terminal. Tested in open air with current in all poles. Maximum AC Volts: at 60 Hz Maximum DC Volts: Breaker Continuous Amperes Instantaneous Trip Amperes 60 Amps See Curve Single pole test data at C based on NEMA Procedures (AB 4-99) for verifying performance of molded case circuit breakers.,000,000 HOURS HOUR MINUTE Minimum Maximum.. Maximum Interrupting Time Interrupting Determines End of Curve (See Above) Curve No. SC-44-87B October 997
13 9-67F Page 7 Types EHD, FDB, FD and HFD Amperes ,000 MINUTE HOUR HOURS,000,000 A Maximum Single Pole Trip Times at C 0 Interrupting (UL/CSA Listed) Breaker Symmetrical RMS Amperes (KA) Amps (KA) 40 V., 480 V., V., Ac V., Dc EHD FDB FD HFD Circuit Breaker Time/Current Curves Series C F-Frame Circuit Breakers Catalog Types EHD, FDB, FD and HFD Circuit Breakers, Two, Three and Four Poles For application and coordination purposes only. Based on 40 C ambient, cold start. Connected with four (4) feet of rated wire (60 C up to amps, 7 C above amps) per terminal. Tested in open air with current in all poles. Maximum AC Volts: at 60 Hz Maximum DC Volts: Breaker Continuous Amperes Instantaneous Trip Amperes Amps See Curve Single pole test data at C based on NEMA Procedures (AB 4-99) for verifying performance of molded case circuit breakers.,000,000 HOURS HOUR MINUTE Minimum Maximum.. Maximum Interrupting Time Interrupting Determines End of Curve (See Above) Curve No. SC-44-87B October 997
Cutler-Hammer. Molded Case Circuit Breakers Amperes January J-Frame
12-34 70 - Amperes Cutler-Hammer Vol. 12-2 Product Line Overview Vol. 1, Ref. No. [0468] 12 Product Line Description Cutler-Hammer Molded Case Circuit Breakers are designed to provide circuit protection
More informationCutler-Hammer. Molded Case Circuit Breakers Amperes. -" Product Selection M-Frame
Cutler-Hammer Vol. 1, Ref. No. [0537] 300-800 Amperes 12-71 -" Product Selection Table 12-114. Types MDL and HMDL Thermal-Magnetic Circuit Breakers with Interchangeable Trip Units Maximum Continuous Ampere
More informationDIVISION 26 ELECTRICAL SECTION CIRCUIT BREAKERS
DIVISION 26 ELECTRICAL SECTION 26 28 19 PART 1 GENERAL 1.01 DESCRIPTION A. Furnish and install circuit breakers in switchboards, distribution panelboards, and separate enclosures for overcurrent protection
More informationInstallation Instructions for NW, HNW, and NWC Circuit Breakers and N-frame Series C Molded Case Switches
Installation Instructions for NW, HNW, and NWC Circuit Breakers and N-frame Series C Molded Case Switches WARNING DO NOT ATTEMPT TO INSTALL OR PERFORM MAINTENANCE ON EQUIPMENT WHILE IT IS ENER- GIZED.
More informationInterchangeable Built-in Fixed thermal Adjustable thermal Magnetic Fixed Adjustable Adjustable Electronic RMS 7 LS LSI
. Technical Data and Specifications Ratings Frames EG, JG and LG EG JG LG Maximum rated current (amperes) 15, 160 1 50 400, 630 Breaker type 3 B B E S S H H C E S H C U X E S H C U X of poles 1, 3, 4,
More informationProduct Line Overview. The Most Logically Designed Contact Assembly
Circuit Breakers & Supplementary Protectors 15 00 Amperes for UL, CSA & IEC Applications Product Line Overview -3 General Information Cutler-Hammer Series G Molded Case Circuit Breakers provide increased
More informationTable Type FD Thermal-Magnetic Circuit Breakers with Non-interchangeable Trip Units
-22 2 Amperes January 1 Vol. 1, Ref. No. [0488] Table -. FD Thermal-Magnetic Circuit Breakers with Non-interchangeable Trip Units Max. Cont. Ampere Rating @ 40 C 600V AC Maximum, 0V DC 277V AC Maximum,
More informationSection SWITCHBOARDS. Introduction. Part 1 - General. Related Work
Section 16435 - SWITCHBOARDS Introduction Part 1 - General Related Work Section 16070 Seismic Anchorage and Restraint Section 16075 Electrical Identification Section 16080 Power Distribution Acceptance
More informationTable Types LD, HLD and LDC Thermal-Magnetic Circuit Breakers with Interchangeable Trip Units
-1 1 Amperes July 07 Product Selection Table -191. s, H and C Thermal-Magnetic Circuit s with Interchangeable Trip Units Maximum Continuous Ampere at 40 C 2-Pole 0 0 3-Pole 0 0 4-Pole 0 0 Magnetic trip
More informationA. Submit manufacturer's literature and technical data before starting work.
SECTION 16425 SWITCHBOARD PART 1 GENERAL 1.01 SUMMARY A. Related Section: 1. 16450 - Grounding. 1.02 SUBMITTALS A. Submit manufacturer's literature and technical data before starting work. B. Submit Shop
More informationModular Metering - Trip Unit for >1200A Mains DEH41187 Application Guide
GE Industrial Solutions Modular Metering - Trip Unit for >1200A Mains DEH41187 Application Guide TABLE OF CONTENTS Description Page 1.0 General Information...... 1 1.1 Protection..... 1 2.0 UL Listed Devices...
More informationSECTION MICROPROCESSOR TRIP UNITS FOR LV CIRCUIT BREAKERS. This section is organized as indicated below. Select desired Paragraphs.
SECTION 16904 MICROPROCESSOR TRIP UNITS FOR LV CIRCUIT BREAKERS PART 2 PRODUCTS 01 MANUFACTURERS A. B. C. Eaton * * The listing of specific manufacturers above does not imply acceptance of their products
More informationCutler-Hammer. Molded Case Circuit Breakers Amperes F-Frame. January 2001
2-22 0-225 Amperes F-Frame Cutler-Hammer January 200 Vol.,Ref. 2-2 Product Line Overview January 200 Vol., Ref. No. [0468] 2 Product Line Description Cutler-Hammer Molded Case Circuit Breakers are designed
More informationAmperes. F-Frame. Price U.S. $ Catalog Number. Price U.S. $ EDH2100 EDH2125 EDH2150 EDH2175 EDH2200 EDH2225
January 1 Vol. 1, Ref. No. [0487] 2 Amperes - Product Selection Table -33. s,, and E Thermal-Magnetic Circuit Breakers with Non-interchangeable Trip Units Suitable for Reverse Feed Maximum Continuous Ampere
More informationData Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931
Data Bulletin 0931DB0101 July 2001 Cedar Rapids, IA, USA Ground-Censor Ground-Fault Protection System Type GC Class 931 09313063 GT Sensor Shunt Trip of Circuit Interrupter Window Area for Conductors GC
More informationCutler-Hammer. Installation Instructions for the Digitrip OPTIM Pole Trip Unit Installation and Operation with L-Frame Series C Circuit Breakers
Cutler-Hammer Installation Instructions for the Digitrip OPTIM 550 3-Pole Trip Unit Installation and Operation with L-Frame Series C Circuit Breakers Table of Contents Description Page 1.0 General Information......................1
More informationTable Line and Load Terminals. Terminal Body Material. Wire Type. Aluminum Copper Aluminum. English English English.
-174 Series C Molded Case Circuit s July 7 Molded Case Switches Refer to Eaton for UL listed, series tested Molded Case Switch application data. Table -278. Molded Case Switches Cont. Amp Rating at 40
More informationPVGard 600 and 1000 Vdc solar photovoltaic circuit breakers
Supersedes October 2013 photovoltaic circuit breakers Contents Description Page Product description........................ 1 PVGard 600 Vdc........................... 2 Technical data...........................
More informationCutler-Hammer Molded Case Circuit Breakers Amperes. January 2001 Vol. 1, Ref. No. [0477] G-Frame
Cutler-Hammer January 200 Vol., Ref. No. [077] s Molded Case s 5-00 Amperes 2- 2-2 Product Line Overview January 200 Vol., Ref. No. [068] 2 Product Line Description Cutler-Hammer Molded Case s are designed
More informationSwitchboards Instant Service
January 1 Vol. 1, Ref. No. [0845] Switchboards Instant Service - Accessories Table -57. Meter Compartment Doors (Meter Sockets Not Included) Door Size Dimensions Drilling Inches mm H x 32 W 381.0 H x 8.8
More informationMOLDED CASE CIRCUIT BREAKER BASICS. David Castor, P.E.
MOLDED CASE CIRCUIT BREAKER BASICS David Castor, P.E. History of MCCBs 1904 - Cutter Manufacturing Co., Philadelphia, produces circuit breakers. They called it the Inverse Time Element breaker, or I-T-E
More information25.4. Molded Case Circuit Breakers. For Immediate Delivery or Tech Support call KMParts.com at (866) Contents
.4 Molded Case Circuit Breakers Gi-, Fi, Ji-, Ki-, Li-Frames Molded Case Circuit Breaker Family Molded Case Circuit Breakers When higher interrupting ratings are not required. Product Overview Gi-, Fi,
More informationGJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector
GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector Catalog 0500CT9702R409 2009 Class 525/580 CONTENTS Description............................................. Page General Characteristics...................................
More informationA. Provide a complete system of overcurrent protective devises as indicated on the drawings, and as specified herein.
16475 OVERCURRENT PROTECTIVE DEVICES ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 26 28 16 An optional
More information24.4. Miniature Circuit Breakers and Supplementary Protectors. For Immediate Delivery or Tech Support call KMParts.com at (866)
.4 Miniature Circuit Breakers and Supplementary Protectors SPHM Supplementary Protector SPHM Supplementary Protector Product Description The SPHM Supplementary Protector is a dual rated product for both
More informationSelective Coordination
Circuit Breaker Curves The following curve illustrates a typical thermal magnetic molded case circuit breaker curve with an overload region and an instantaneous trip region (two instantaneous trip settings
More informationS&C TripSaver II. Cutout-Mounted Recloser. For enhanced lateral circuit protection at 15 kv and 25 kv
TripSaver II Cutout-Mounted Recloser For enhanced lateral circuit protection at 15 kv and 25 kv Introducing s new TripSaver II Cutout-Mounted Recloser: A better solution for overhead lateral circuit protection
More informationN-frame Circuit Breaker
Bul. 140U N-Frame Circuti Breakers Instruction Leaflet for N-Frame Circuit Breakers WARNING DO NOT ATTEMPT TO INSTALL OR PERFORM MAIN- TENANCE ON EQUIPMENT WHILE ENERGIZED. DEATH, SEVERE PERSONAL INJURY,
More information1489-M Circuit Breakers
Dual terminals provide wiring/bus bar flexibility and clamp from both sides to improve connection reliability Terminal design helps prevent wiring misses Scratch- and solventresistant printing Suitable
More informationCircuit breakers and switch-disconnectors NT06 to NT16 and NW08 to NW63
Functions and characteristics Circuit breakers and switch-disconnectors NT06 to NT16 and NW08 to NW63 NT and NW selection criteria Masterpact NT Masterpact NW NT06, NT08, NT10, NT12, NT16 NT06, NT08, NT10
More informationAF40... AF96 3-pole contactors Technical data
Main pole - Utilization characteristics according to IEC Standards IEC 60947- / 60947-4- and EN 60947- / 60947-4- Rated operational voltage Ue max. 690 V Rated frequency (without derating) 50 / 60 Hz Conventional
More informationA. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein.
16425 SWITCHBOARD ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 26 24 13 An optional keynote to
More informationL-Frame. With Standard Line and. Standard Terminals Only. Catalog Number. Price U.S. $ LDB2300 LDB2350 LDB2400 LDB2450 LDB2500 LDB2600
January 01 Vol. 1, Ref. No. [05] 1 Amperes 12- Table 12-99. Type Thermal-Magnetic Circuit Breakers with Non-interchangeable Trip Units Maximum Continuous Ampere 2-Pole 0 0 3-Pole 0 0 V AC Rated, 0V DC
More informationPowerPact Q-Frame Molded Case Circuit Breakers and Switches (Types QB, QD, QG and QJ)
PowerPact Q-Frame Molded Case Circuit Breakers and Switches (Types QB, QD, QG and QJ) Catalog Class 734 0734CT0201R1/07 07 CONTENTS Description..............................................Page Description.............................................
More informationBulletin 1489 Circuit Breakers. Selection Guide
Bulletin 1489 s Selection Guide Bulletin 1489-A Overview/Description Bulletin 1489-A s Energy-limiting design protects downstream components better than conventional breakers during short circuits Field-mountable
More informationCutler-Hammer. January 2001
Vol. 12-2 Product Line Overview Vol. 1, Ref. No. [0468] 12 Product Line Description Cutler-Hammer Molded Case Circuit Breakers are designed to provide circuit protection for low voltage distribution systems.
More informationCharacteristics of LV circuit breakers Releases, tripping curves, and limitation
Characteristics of LV circuit breakers Releases, tripping curves, and limitation Make, Withstand & Break Currents A circuit breaker is both a circuit-breaking device that can make, withstand and break
More informationSafety, Reliability and Performance verified with the KEMA KEUR mark. Series G Moulded Case Circuit Breakers
Series G Moulded Case Circuit Breakers Product Focus Up to 690 Vac 18kA to 100kA Icu 16-2500 Amperes IEC 60947-2 Safety, Reliability and Performance verified with the KEMA KEUR mark Safety, Reliability
More informationLPSRK30SP 30A 600V TD Dual Elem Class RK1 Low Peak Fuse
LPSRK30SP 30A 600V TD Dual Elem Class RK Low Peak Fuse Catalog Number Manufacturer Description Weight per unit Product Category LPSRK30SP 30A 600V Class RK Low Peak Dual Element, Time Delay Fuse 600 (lbs/each)
More information6.1. Low Voltage Busway. Low Voltage Busway Pow-R-Way and 100V. Features, Benefits and Functions
.1 Features, Benefits and Functions Pow-R-Way III Offers a Full Line of to Meet the Needs of the Global Marketplace Eaton Corporation has combined the requirements of NEMA, UL, CSA and IEC into one design
More informationAmperes. F-Frame. Price U.S. $ Catalog Number. Price U.S. $ EDH2100 EDH2125 EDH2150 EDH2175 EDH2200 EDH2225
January 1 Vol. 1, Ref. No. [0487] 2 Amperes 12- Product Selection Table 12-33. s, H, and E Thermal-Magnetic Circuit Breakers with Non-interchangeable Trip Units Suitable for Reverse Feed Maximum Continuous
More informationUTS400 SELECTION GUIDE CATALOG NUMBERING [PRODUCT SELECTION] UTS400 NT ATU 400A 3P LL LSIS UL MCCB
PRODUCT CATALOG SELECTION GUIDE UTS400 CATALOG NUMBERING [PRODUCT SELECTION] UTS400 NT ATU 400A 3P LL UL SERIES & FRAME: Susol 400AF PERFORMANCE Rating 80% 0% ka N NT 65 SUFFIX UL : UL 240Vac H HT 0 L
More informationQ and M-Frame Circuit Breaker Instruction Leaflet for Installation and Operation for Thermal Magnetic Trip Units
Q and M-Frame Circuit Breaker Instruction Leaflet for Installation and Operation for Thermal Magnetic Trip Units Bul. 140U DO NOT ATTEMPT TO INSTALL OR PERFORM MAINTENANCE ON EQUIPMENT WHILE ITS IS ENERGIZED.
More informationMolded Case Circuit Breakers Amperes LSIA. LSIG Catalog Number 3-Pole Standard Interrupting Capacity 600V AC Rated V AC 13,950.
Vol. 1, Ref. No. [0559] - Amperes M-Frame 12-93 % Rated Digitrip OPTSM s with interchangeable Rating Plugs Order as individual components: Frame (which includes Trip Unit), Rating Plug, Terminals. Table
More informationDPX earth leakage DPX 3 -I earth leakage
87045 LIMOGES Cedex Phone :+33 05 55 06 87 87 Fax :+33 05 55 06 88 88 DPX 3 250 + earth leakage Reference(s) : 420 225/ 227/ 228/229/ 255/ 257/ 258/ 259/ 285/ 287/ CONTENTS PAGES 1. USE 1 2. RANGE 1 3.
More informationDPX Thermal magnetic and trip-free switches DPX 3 -I 250
87045 LIMOGES Cedex Phone :+33 05 55 06 87 87 Fax :+33 05 55 06 88 88 DPX 3 250 Reference(s) : 420 205/ 207/ 208/209/ 215/ 217/ 218/ 219/ 235/ 237/ CONTENTS PAGES 1. USE 1 2. RANGE 1 3. DIMENSIONS 1 3.
More informationTechnical Information
-100 Controller IEC Performance Data (CSA C22.2, UL 508 No. 14 in connection with a short-circuit protection device Catalog No. -100... 25A 40A 63A 90A Maximum Short-Circuit Current 480V [ka] 65 65 42
More informationUtilization of Electric Power Laboratory 3 rd Year G2: Testing & Characteristic of MCCB Used in Commercial and Industrial Applications
G2: Testing & Characteristic of MCCB Used in Commercial and Industrial Applications Contents 1. Laboratory Objective... 4 2. MECHANICAL OPERATION TESTS... 4 2.1 Purpose... 4 2.2 Procedure... 4 2.3 Results...
More informationMoulded case circuit breakers
Moulded case circuit breakers CONTENT Range 4 Protection Releases 5 Salient Features 8 Accessories, 4 Technical data 2 Time Current Characteristics 5 Overall Dimensions 7 SN4 SN3 SN2 SN 3 RANGE Moulded
More informationProtective Device Coordination ETAP Star
Protective Device Coordination ETAP Star Agenda Concepts & Applications Star Overview Features & Capabilities Protective Device Type TCC Curves STAR Short-circuit PD Sequence of Operation Normalized TCC
More informationElectronic circuit breaker EBU10-T
Description The electronic circuit protector type EBU10-T (Electronic Breaker Unit) provides selective overcurrent protection in AC 230 V UPS systems. It consists of an MCB approved for short circuit interruptions
More informationCH120CAFPN 1P 20A 120 Combo Arc Fault PN Breaker
3804 South Street 75964-7263, TX Nacogdoches Phone: 936-569-794 Fax: 936-560-4685 CH20CAFPN P 20A 20 Combo Arc Fault PN Breaker Eaton Corp Catalog Number Manufacturer Description Weight per unit Product
More informationLow voltage moulded case circuit breaker EB2
Low voltage moulded case circuit breaker EB2 Product series description unit condition Model-type Number of poles Nominal current ratings Electrical characteristics Rated operational voltage Rated insulation
More informationMolded Case. Circuit Breakers. Molded Case Circuit Breakers Contents
January 2001 Vol. 1, Ref. No. [0467] -1 Molded Case Circuit Breakers Contents Description Page Product Line Overview........................................... -2 Product Line Description.......................................
More informationCutler-Hammer. January 2001
Cutler-Hammer Vol. -2 Product Line Overview Vol. 1, Ref. No. [0468] Product Line Description Cutler-Hammer Molded Case s are designed to provide circuit protection for low voltage distribution systems.
More informationThermal-magnetic Miniature Circuit Breaker 4230-T...
Thermal-magnetic Miniature Circuit Breaker 420-T... Description Single pole and multipole thermal-magnetic miniature circuit breakers (MCBs) in accordance with EN 60947-2, UL 077 and UL 489 for DIN rail
More informationType MP-T Type MP-HT Type MP-MT
CIRCUIT BREAKERS 2 Circuit Breakers Full Size (1 per Pole) with INSTA-WIRE 1-Pole Plug-In (120V AC) Type MP-T Type MP-HT Type MP-MT Continuous 10,000A IR 22,000A IR 65,000A IR Current Rating Catalog List
More informationProduct index. 4 - Manual motor protectors. Manual motor protectors. Manual motor protectors Low Voltage Products & Systems 4.
Product index -....1.3 Features and benefits...1 General information Suitable applications...2 -.3 Motor ratings... Pilot duty ratings and overload trip classes...5 Ordering details Type MS116...6 Type
More informationSECTION MOTOR CONTROL
SECTION 26 24 19 MOTOR CONTROL PART 1 - GENERAL 1.1 SECTION INCLUDES A. Manual motor starters B. Magnetic motor starters C. Combination magnetic motor starters D. Solid-state reduced voltage motor starters
More informationPD-Series Ground Fault Circuit Protection
PD-Series Ground Fault Circuit Protection SmartGuard is an equipment ground fault protection device that functions as a standard high-quality Carling hydraulic/ magnetic circuit breaker, offering customized
More informationEOEM panelboard and switchboard (OPS) Program
Instructional Leaflet IL02009EN EOEM panelboard and switchboard (OPS) Program OPS Program overview The OPS Program enables EOEMs to purchase panelboard/switchboard chassis, boxes, trims, molded-case circuit
More informationMAGNETIC MOTOR STARTERS
Chapter 6 MAGNETIC MOTOR STARTERS 1 The basic use for the magnetic contactor is for switching power in resistance heating elements, lighting, magnetic brakes, or heavy industrial solenoids. Contactors
More information22.000A IR. Catalog Number. Price $
Full Size (" per Pole) with INSTA-WIRE -Pole Plug-In (V AC) Type MP-T Type MP-HT Type MP-MT Continuous Current Rating @ C 5 25 35 5 0.000A IR Catalog Number MP5 MP MP25 MP MP35B MP MP5B MP MPB MPB List
More informationSynergy EN product information
Synergy EN60947-4-2 product information Rated operational voltages U e 200Vac to 480Vac Rated operational currents I e See Rating Table Rating index See Sizing Guide Rated frequency/frequencies 50-60Hz
More informationSECTION PANELBOARDS
SECTION 16470 PANELBOARDS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. The general provisions of the contract including General and Special Conditions and General Requirements shall apply to all work under
More informationCutler-Hammer. Molded Case Circuit Breakers Amperes. Product Selection January 2001 Vol. 1, Ref. No ) J-Frame
Vol. 1, Ref. No. 10499) Product Selection Table 12-56. Types 12-33 12-2 Product Line Overview Vol. 1, Ref. No. [0468] 12 Product Line Description Cutler-Hammer Molded Case Circuit Breakers are designed
More informationPowerPact M-, P- and R-Frame, and Compact NS630b NS3200 Circuit Breakers
PowerPact M-, P- and R-Frame, and Compact NS630b NS3200 Circuit Breakers Catalog 0612CT0101 R02/14 2014 Class 0612 CONTENTS Description............................................. Page General Information..........................................
More information2.3. Molded Case Circuit Breakers. Contents
.3 Molded Case Circuit Breaker Product Family Product Overview Eaton s molded case circuit breakers are designed to provide circuit protection for low voltage distribution systems. They are described by
More informationSECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS
SECTION 26 28 16 ENCLOSED SWITCHES AND PART 1 - GENERAL 1.1 SUMMARY A. Section includes the following individually mounted, enclosed switches and circuit breakers rated 600V AC and less: 1. Fusible switches.
More informationMagnum IEC Low Voltage Air Circuit Breakers
Magnum IEC Low Voltage Air Circuit Breakers Product Focus Up to 690 Vac 42 ka to 100 ka Icu 800 to 6300 Amperes EN 60947-2 A Global Source for Innovative Electrical Power Distribution Solutions Proven
More informationA system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment.
General Unit substations shall be 500 kva minimum, 1500 kva maximum unless approved otherwise by the University. For the required configuration of University substations see Standard Electrical Detail
More informationVL Circuit Breaker DG 150A frame
VL Circuit Breaker DG 150A frame Breaker type Defined by the 3rd character of the catalog number G Global (UL, CSA, IEC, CE, CCC), interchangeable K Global, non-interchangeable W Global, 100% rated, non-interchangeable,
More informationRecommended Procedures
Selective Coordination Study Recommended Procedures The following steps are recommended when conducting a selective coordination study.. One-Line Diagram Obtain the electrical system one-line diagram that
More informationVL Circuit Breaker FG 250A frame Breaker type Defined by the 3rd character of the catalog number K Global, Non-interchangeable
VL Circuit Breaker FG 250A frame Breaker type Defined by the 3rd character of the catalog number K Global, Non-interchangeable Trip unit type Defined by the 5th character of the catalog number B Thermal-magnetic,
More informationACS motor protection circuit breakers KT 7 Introduction
Introduction Automatic Type 2 coordination The right circuit breaker for all applications The KT 7 circuit breaker family consists of two basic frame sizes of mm and 5 mm in three variations with different
More informationKT4 Manual Motor Starter
KT4 Manual Motor Starter Ideal for use as a manual starter The KT4 is a manual motor starter that employs the features of power switching, thermal overload protection and control circuit signaling in one
More informationEvaluating Selective Coordination Between
Evaluating Selective Coordination Between Current-Limiting Fuses And Non Current- Limiting Circuit Breakers selective coordination note 1 By Steve Hansen Sr. Field Engineer and Robert Lyons Jr. Product
More informationSeries C, F-frame molded case circuit breaker, 15A, Two-pole, Thermal Magnetic Trip, FD Breaker
FD2015 2 Pole 15A FD Eaton Corp Catalog Number Manufacturer Description Weight per unit Product Category Features amperage rating 15 Frame Size F-frame interrupt rating 35 kaic at 480V Poles 2 Trip Type
More informationL-Frame LD F. Circuit Breaker/ Frame Ampere Rating. Trip Unit Rating/ Plug Ampere Rating LD T5 7 W
July 07 5 Amperes -111 Product Selection This information is presented only as an aid to understanding catalog numbers. It is not to be used to build catalog numbers for circuit breakers or trip units.
More informationInstructions for Type W Three Phase, Standalone Overload Relays, Size 1 through 6
Revision D Instructions for Type W Three Phase, Standalone Overload Relays, Size 1 through 6 Size 2 Size 3 Fig. 1 Type W Standalone Overload Relays Size 5 THE OVERLOAD RELAYS Advantage Type W three phase,
More informationIdeal for use as a manual starter
Manual Motor Starter Ideal for use as a manual starter The is a manual motor starter that employs the features of power switching, thermal overload protection and control circuit signaling in one compact
More informationSeries C, F-frame molded case circuit breaker, 125A, Three-pole, Thermal magnetic trip. Thermal magnetic
3804 South Street 75964-7263, TX Nacogdoches Phone: 936-569-7941 Fax: 936-560-4685 HFD3125 HFD3125 125A 3P CKT BRKR Eaton Corp Catalog Number Manufacturer Description Weight per unit Product Category Features
More informationMolded Case Circuit Breakers
Type SND6 Molded Case Circuit Breakers SND 1200A Frame Digital Solid State Sentron Sensitrip III Series Type SHND6 Current Limiting Type SCND6 Blue Label Black Label Red Label Catalog Current Price SND69800A
More informationLow-Peak 600V Class RK1
LPS-RK 600Vac/300Vdc, 1 10-60A, Dual Element, Time-Delay Fuses Dimensions - in 5" (± 0.31) 5.5" (± 0.31) Available with easyid open fuse indication 1/10 to 30A 0.81" (±0.008) 35 to 60A 1.06" (±0.008) Description:
More informationA. This Section includes ac, enclosed controllers rated 600 V and less, of the following types:
SECTION 262913 600 VOLT ENCLOSED CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 0 Specification
More informationAF09... AF30 3-pole Contactors up to 25 HP / 600 VAC
AF09... AF0 -pole Contactors up to 25 HP / 600 VAC Contactors and Overload Relays Overview.../0 AF09... AF0 -pole Contactors.../2 Main Technical Data.../8 Main Accessory Fitting Details.../2 Main Accessory.../24
More informationProtectors. Manual motor. Types MS116, MS132, MS45x, MS49x. MS Series. Manual motor protectors. Type MS116. Type MS132. Type MS45x.
Types MS116, MS132, MS5x, MS9x are electromechanical devices for motor and circuit protection. These devices offer local motor disconnect means, manual ON/OFF control, and protection against short circuit,
More informationLPSRK100SP 100A 600V TD Dual Elem Class RK1 Low Peak Fuse
LPSRK100SP 600V TD Dual Elem Class RK1 Low Peak Fuse Catalog Number Manufacturer Description Weight per unit Product Category LPSRK100SP 600V Class RK1 Low Peak Dual Element, Time Delay Fuse 0.4100 (lbs/each)
More informationMotor Protection. Presented By. Scott Peele PE
Motor Protection Presented By Scott Peele PE Motor Protection Overload on the motor load Fuses Heater Magnetic relay Short Circuit on motor circuit Fuses Breakers Single Phasing Overload Protection NEC
More informationPage. Circuit-Breakers M4 2 for motor protection. Auxiliary contacts 3 Signalling switch Auxiliary releases
Circuit Breakers M4 Page Circuit-Breakers M4 2 for motor protection Auxiliary contacts 3 Signalling switch Auxiliary releases Insulated 3-pole busbar system 4 Terminal block DIN-rail adapters 5 Busbar
More informationDISTRIBUTION EQUIPMENT: NEC/CEC HAZARDOUS LOCATION SWITCHES. Application
- and 3-Pole, Non-Interchangeable Trip. Bolted Enclosure Type. Class I, Division 1 and, Groups B, C, D Class II, Division 1 and, Groups E, F, G Application Explosionproof circuit breaker enclosures are
More informationTable of Contents. Review Answers...84 Final Exam...85 quickstep Online Courses...88
Table of Contents Introduction...2 Need for Circuit Protection...4 Types of Overcurrent Protective Devices...8 Circuit Breaker Design... 11 Types of Circuit Breakers...23 Circuit Breaker Ratings...27 Time-Current
More informationEnhancing Short Circuit Selective Coordination with Low Voltage Circuit Breakers
Data Bulletin 0100DB0403R5/05 05/2005 Cedar Rapids, Iowa, USA Enhancing Short Coordination with Low Voltage s Retain for future use. INTRODUCTION DEFINITIONS ASSUMPTIONS CIRCUIT BREAKER BASICS The purpose
More informationElectromagnetic Industries LLP
GROUND FAULT CURRENT DETECTION GFM Relay (Model 252 & 262) The GFM system is designed for electrical protection, not for personnel protection Application: These Class 1 (Model GFM) Ground Fault protection
More informationCerti cation Record INDUSTRIAL CONTROL EQUIPMENT Motor Controllers Magnetic
Certi cation Record Customer Schneider Electric USA, Inc. Square D Raleigh (Knightdale) Plant, 8001 Knightdale Blvd Knightdale NC USA 27545 Class 3211 04 INDUSTRIAL CONTROL EQUIPMENT Motor Controllers
More informationIN2 Enclosed Switches and Circuit Breakers
Illinois Math and Science Academy DigitalCommons@IMSA Project Manuals IN2 2015 IN2 Enclosed Switches and Circuit Breakers Illinois Mathematics and Science Academy Follow this and additional works at: http://digitalcommons.imsa.edu/facility_in2_manuals
More information16kA Solid Dielectric, Triple Option Reclosers Catalog VLT12
16kA Solid Dielectric, Triple Option Reclosers Providing electronic overcurrent protection for single or three phase operation on systems rated through 27kV, 630A continuous current, 16kA symmetrical interrupting
More informationcor Long Run Experience
Moulded Case Circuit Breakers Moulded Case Circuit Breakers 16-1250A cor Long Run Experience cor Breaking capacity (according to IEC 947-2 at 415V) Icu 100 D160L D250L D400L D630L 70 60 DH800 50 35 30
More informationA. Work Included: Provide low voltage switchboard work as shown, scheduled, indicated, and as specified.
SECTION 26 24 13 LOW VOLTAGE SWITCHBOARDS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General
More informationLENRK/LESRK CLASS RK1 DUAL ELEMENT TIME-DELAY FUSES
LENRK/LESRK CLASS RK Catalog Number LENRK (. - 0A) 50 Volts AC or Less Catalog Number LESRK (.5-0A) 0 Volts AC or Less S LENRK 50V 0..5 75 0..5 5 0..5 9 50 5 0.5 50 0.. 70 0 0..5 5 0 50 7.5 90 0..5 0 50.
More information