DIVISION 26 ELECTRICAL SECTION CIRCUIT BREAKERS
|
|
- Gwendolyn Curtis
- 5 years ago
- Views:
Transcription
1 DIVISION 26 ELECTRICAL SECTION PART 1 GENERAL 1.01 DESCRIPTION A. Furnish and install circuit breakers in switchboards, distribution panelboards, and separate enclosures for overcurrent protection for panelboards, transformers and equipment, as shown on the Drawings and specified herein. Provide all accessories as necessary. B. Short circuit ratings shall be as shown on the Drawings. C. Refer to Section , "Panelboards-Lighting and Appliance" for circuit breakers in panelboards. D. Provide frame size of circuit breaker with lug size as required to accommodate feeder size as shown on the Drawings. E. Provide frame size, plug size, and trip units as necessary to meet short circuit ratings, and to provide selective coordination (down to 0.01 seconds) on emergency power distribution systems. F. All circuit breakers shall be fully rated for short circuit levels indicated. Series ratings are not permitted QUALITY ASSURANCE A. All equipment shall be UL listed and labeled and in accordance with applicable NEMA and ANSI Standards SUBMITTALS A. For Review: 1. Product data sheets for all circuit breakers and components 2. Wiring diagrams B. To be included in Record and Information Manuals: 1. One (1) copy of each approved submittal 2. Test results 3. Manufacturer Representative's signed Certificate of Inspection and Approval 1.04 MANUFACTURERS A. Circuit Breakers 1. Square D Company 2. Siemens Energy & Automation, Inc. 3. Cutler-Hammer/Eaton Corporation 13-HC
2 PART 2 PRODUCTS 2.01 MOLDED CASE WITH THERMOMAGNETIC TRIP A. Molded case circuit breakers shall be bolt-on type operated by a toggle type handle and shall have quick-make/quick-break over-center switching mechanism that is mechanically trip free from the handle so that the contacts cannot be held closed against short circuits and abnormal currents. Tripping due to overload or short circuit shall be clearly indicated by the handle automatically assuming a position midway between the manual ON and OFF positions. B. Breakers must be completely enclosed in a molded case. Non-interchangeable trip breakers shall have their covers sealed; interchangeable trip breakers shall have the trip unit sealed to prevent tampering. Ampere ratings shall be clearly visible. Arc extinction must be accomplished by means of arc chutes. C. Molded case breakers shall be of the thermal magnetic standard type that provides inverse time delay overload and instantaneous short circuit protection by means of a thermal magnetic element. D. Single phase circuit breakers shall be balanced among the three (3) phases. E. All circuit breakers shall have an integral lock-out/tag-out means. F. High magnetic withstand circuit breaker type shall utilize higher trip levels of 18 to 20 times the breaker handle rating MOLDED CASE WITH SOLID STATE TRIP A. Circuit protective devices shall be molded case type circuit breakers UL Listed for 80% continuous current with full function trip system. Frame/Sensor ampere ratings shall be as shown on the Drawings. The ampere rating shall be clearly marked on the front of the circuit breaker. Circuit breakers shall be of fixed construction. B. Circuit breakers shall be constructed using glass-reinforced insulating material providing high dielectric strength. Current carrying components shall be completely isolated from the trip unit and accessory mounting area. Breakers shall have common tripping of all poles and shall be trip free. The breakers shall have quick-make/quick-break contacts with an over center toggle operating mechanism. All circuit breakers shall be equipped with electrical accessories as noted on the Drawings. C. The integral electronic trip system shall be independent of any external power source and shall contain electronic components to measure and time the output from internal current sensors and initiate automatic tripping action. The continuous ampere rating of the circuit breaker shall be determined by the combination of the ampere rating switch position, and the frame/sensor size of the circuit breaker. The resulting ampere rating shall be clearly marked on the face of the circuit breaker. Provide a means to seal the trip unit adjustments to discourage unauthorized tampering to meet the requirements of NEC Article HC1-033
3 D. Provide the following time/current curve shaping adjustment to maximize system selective coordination. Each adjustment shall have discrete settings and shall be independent from all other adjustments: 1. Adjustable Long Time Ampere Rating and Delay 2. Adjustable Short Time Pickup and Delay (delay includes I 2 t in and I 2 t out) 3. Fixed Instantaneous Trip 4. Ground fault trip (where shown on one line diagram) E. Provide local visual trip indication for overload, short circuit occurrences. The trip system shall include a memory circuit to detect intermittent overcurrent conditions. Each circuit breaker trip system shall be equipped with an externally accessible test port for use with a Universal Test Set. No disassembly of the circuit breaker is required for testing. Test set shall be capable of verifying the operation of all trip functions with or without tripping the circuit breaker. F. All circuit breakers shall have an integral lock-out/tag-out means INSULATED CASE WITH SOLID STATE TRIP A. Circuit protective devices shall be insulated case type circuit breakers UL lists for 100% continuous current with full function trip system. Frame/Sensor ampere ratings shall be shown on the Drawings. Circuit breakers shall be of drawout construction. B. Provide selective override circuit on circuit breakers with defeatable instantaneous adjustment to allow the breaker (1) to remain closed for up to thirty (30) cycles during overcurrents below 50 ka RMS symmetrical, and (2) to trip instantaneously when current levels exceed thirty (30) cycle withstand rating. All circuit breakers shall be constructed in accordance with UL 489 and NEMA AB Circuit breakers shall be constructed using glass-reinforced insulating material providing high dielectric strength. Current carrying components shall be completely isolated from the trip unit and accessory mounting area. Breakers shall have common tripping of all poles and shall be trip free. The circuit breaker shall be UL listed for reverse connection without requiring special construction. C. Provide true two step stored energy mechanism for five (5) cycle closing. Energy required to close breaker shall be stored pending release to close action. All circuit breakers shall have multiple CHARGE/CLOSE provisions allowing the following sequence: CHARGE, CLOSE, RECHARGE, OPEN/CLOSE/OPEN. Visual indication of mechanism CHARGED and DISCHARGED position on the face of the breaker. Visual indicator shall show the face of the breaker. Visual indicator shall show CHARGED only when closing springs are completely charged. D. Provide interlocking capabilities for lockout of local manual closing buttons and padlocking main contacts in OPEN position. E. The integral trip system shall be independent of any external power source and shall contain electronic components to measure and time the output from internal current sensors and initiate automatic tripping action. The trip unit shall be factory installed and capable of being field interchangeable while retaining UL listing. 13-HC
4 F. The continuous ampere rating of the circuit breaker shall be determined by the combination of an interchangeable rating plug and the sensor size of the circuit breaker. The ampere rating resulting from the rating plug/sensor combination shall be clearly marked on the front of the circuit breaker. Provide a means to seal the rating plug and trip unit adjustments to discourage unauthorized tampering to meet the requirements of NEC Article G. Provide the following time/current curve shaping adjustments to maximize system selective coordination. Each adjustment shall have discrete settings and each function is independent from all other adjustments: 1. Adjustable Long Time Ampere Rating and Delay 2. Adjustable Short Time Pickup and Delay (delay includes I 2 t in and I 2 t out) 3. Adjustable Defeatable Instantaneous Pickup 4. Adjustable Ground-Fault Pickup and Delay (delay includes I 2 t in and I 2 t out) 5. Fixed Selective Override H. Provide local visual trip indication for overload, short circuit and ground-fault trip occurrences. Provide a long time pickup light to indicate when loading approaches or exceeds the continuous current carrying capacity of the circuit breaker. The trip system shall include a memory circuit to detect intermittent overcurrent conditions. Each circuit breaker trip system shall be equipped with an externally accessible test port for use with a Universal Test Set. No disassembly of the circuit breaker is required for testing. Test set shall be capable of verifying the operation of all trip functions with or without tripping the circuit breaker. I. Circuit breakers shall be provided with integral ground-fault protection. The circuit breaker shall be applicable on 3 phase, 3 wire circuits where the neutral is grounded, but not carried through the system or 3 phase, 4 wire systems. The ground-fault system shall be Zero Sequence. The ground-fault sensing system shall meet the on-site testing requirements of NEC Article (c). Provide a separate neutral current transformer for 3 phase, 4 wire systems ENCLOSURES A. Enclosures shall have padlocking provisions for locking circuit breakers in the "OFF" positions. B. Enclosure types shall be as follows: 1. NEMA 1 - Gray baked enamel on galvanized steel 2. NEMA 3R - Gray baked enamel on galvanized steel with drain holes, lockable door, securable in the open position 3. NEMA 4X - Stainless steel with gasketed cover C. Enclosures shall be flush mounted in gypsum board walls and surface mounted on concrete walls HC1-033
5 PART 3 EXECUTION 3.01 APPLICATION A. 15 Ampere through 175 Ampere circuit breakers shall be molded case with thermomagnetic trip sensor and mechanism. B. 200 Ampere and above through 1600 Ampere circuit breakers shall be molded case with solid state trip sensor and mechanism. C. Circuit breakers above 1600 Ampere shall be insulated case with solid state trip sensor and mechanism. D. Provide the following NEMA rated enclosure types for single circuit breakers in these locations: 1. Interior Exterior - 3R 3.02 INSTALLATION A. Install circuit breakers in switchboards, distribution panelboards or enclosures as shown on the Drawings and in accordance with Manufacturer's written instructions. B. Provide nameplates in accordance with Section , "Electrical Identification." 3.03 TESTING A. Perform a complete functional test of all features of circuit breakers in accordance with Manufacturer's recommendations. Submit written documentation in Record and Information Manuals. END OF SECTION 13-HC
A. Provide a complete system of overcurrent protective devises as indicated on the drawings, and as specified herein.
16475 OVERCURRENT PROTECTIVE DEVICES ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 26 28 16 An optional
More informationA. Submit manufacturer's literature and technical data before starting work.
SECTION 16425 SWITCHBOARD PART 1 GENERAL 1.01 SUMMARY A. Related Section: 1. 16450 - Grounding. 1.02 SUBMITTALS A. Submit manufacturer's literature and technical data before starting work. B. Submit Shop
More informationSECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 29 21 ENCLOSED SWITCHES AND CIRCUIT BREAKERS SPEC WRITE NOTE: Delete between // // if not applicable to project. Also delete any other item or paragraph not
More informationSECTION PANELBOARDS
SECTION 16470 PANELBOARDS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. The general provisions of the contract including General and Special Conditions and General Requirements shall apply to all work under
More informationSection SWITCHBOARDS. Introduction. Part 1 - General. Related Work
Section 16435 - SWITCHBOARDS Introduction Part 1 - General Related Work Section 16070 Seismic Anchorage and Restraint Section 16075 Electrical Identification Section 16080 Power Distribution Acceptance
More informationSECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS
SECTION 26 28 16 ENCLOSED SWITCHES AND PART 1 - GENERAL 1.1 SUMMARY A. Section includes the following individually mounted, enclosed switches and circuit breakers rated 600V AC and less: 1. Fusible switches.
More informationA. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein.
16425 SWITCHBOARD ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 26 24 13 An optional keynote to
More information1. The term "withstand" means "the unit will remain in place without separation of any parts from the device when subjected to the seismic forces.
SECTION 262816 - ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Fusible switches. 2. Nonfusible switches. 3. Receptacle switches. 4. Shunt trip switches. 5.
More informationMichigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE
PAGE 261116-1 SECTION 261116 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationA. Work Included: Provide low voltage switchboard work as shown, scheduled, indicated, and as specified.
SECTION 26 24 13 LOW VOLTAGE SWITCHBOARDS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General
More information1. Division 26 Section "Elevator Shunt-Trip Fused Disconnect Switches".
SECTION 26 28 16 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification Sections,
More informationIN2 Enclosed Switches and Circuit Breakers
Illinois Math and Science Academy DigitalCommons@IMSA Project Manuals IN2 2015 IN2 Enclosed Switches and Circuit Breakers Illinois Mathematics and Science Academy Follow this and additional works at: http://digitalcommons.imsa.edu/facility_in2_manuals
More informationDESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5
DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5 1.1. APPLICABLE PUBLICATIONS 1.1.1. Publications listed below (including amendments, addenda, revisions, supplements, and errata), form a part of this
More informationWARREN COUNTY, N.Y. M/E REFERENCE
SECTION 262000 - ELECTRIC DISTRIBUTION PART 1 - GENERAL 1.1 DESCRIPTION A. Provide a complete secondary distribution system as indicated on the Contract Documents and as specified herein. 1.2 QUALITY ASSURANCE
More informationUniversity of Houston Master Construction Specifications Insert Project Name
SECTION 26 24 14 600 VOLT DRAWOUT SWITCHGEAR PART 1 - GENERAL 1.01 SECTION INCLUDES: A. Individually mounted rear-accessible low voltage switchgear ANSI rated switchgear and low voltage power circuit breakers
More information2018 Consultant s Handbook Division 26 Electrical 2413 Switchboards
1 General 1.1 Switchboards shall be U.L. listed and labeled. 1.2 Each switchboard shall have its own main disconnecting means unless it is located in the same room as its source of origin. In most cases
More informationUniversity of Houston Master Construction Specifications Insert Project Name
SECTION 26 13 13 MEDIUM VOLTAGE SWITCHGEAR PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General
More informationA. Products shall be designed, manufactured, tested, and installed in compliance with the following standards:
SECTION 26 29 13 ENCLOSED MOTOR CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General
More informationSECTION MOTOR CONTROL
SECTION 26 24 19 MOTOR CONTROL PART 1 - GENERAL 1.1 SECTION INCLUDES A. Manual motor starters B. Magnetic motor starters C. Combination magnetic motor starters D. Solid-state reduced voltage motor starters
More informationAPPENDIX E. Electrical System Single Line Diagram Overcurrent Protection Study Overcurrent Protection Device Specifications
Student Resource Building University of California Santa Barbara Clement Fung Lighting Electrical Option APPENDIX E Electrical System Single Line Diagram Overcurrent Protection Study Overcurrent Protection
More informationA. This Section includes ac, enclosed controllers rated 600 V and less, of the following types:
SECTION 262913 600 VOLT ENCLOSED CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 0 Specification
More informationSECTION ELECTRIC DISTRIBUTION
SECTION 16400 - ELECTRIC DISTRIBUTION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary General Conditions and other Division
More informationSECTION ENCLOSED CONTROLLERS
SECTION 16420 ENCLOSED CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationFused Coordination Panelboard
Fused Coordination Panelboard SOLUTIONS GUIDE SOLUTIONS GUIDE Branch Circuit Protection Introducing Mersen s Fused Coordination Panelboard Selective Coordination is required in several locations as defined
More informationMedium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION
Medium Voltage Standby non-paralleling Control 1. GENERAL GUIDE FORM SPECIFICATION A. The requirements of the contract, Division 1, and part 16 apply to work in this section. 1.01 SECTIONS INCLUDE A. Medium
More informationSECTION LOW VOLTAGE DISTRIBUTION EQUIPMENT
SECTION 16400 LOW VOLTAGE DISTRIBUTION EQUIPMENT A. General 1. The University does not accept Series-Rated equipment for power distribution switchboards, distribution panels and branch circuit panelboards.
More informationSECTION DISTRIBUTION AND GROUNDING
SECTION 16400 DISTRIBUTION AND GROUNDING PART 1 GENERAL 1.01 SECTION INCLUDES A. Furnishing and installation of a complete electrical distribution and grounding system. B. Furnish and install motor control
More informationSpecification Guide. for RMAX. Direct Replacement. AC Low Voltage. Power Circuit Breakers
Specification Guide for RMAX Direct Replacement AC Low Voltage Power Circuit Breakers Table of Contents 1.0 General Work Scope...3 2.0 Standards... 3 3.0 Supplier Qualifications... 3 4.0 Mechanical and
More informationQuik-Spec Coordination Panelboard Specifications
Quik-Spec Coordination Panelboard Specifications 30A - 400A Fusible Panelboards SECTION 26 24 XX (This Specification references CSI MasterFormat 2004) FUSIBLE BRANCH CIRCUIT PANELBOARDS PART 1 1.01 SUMMARY
More informationGuide Specification. Three-Phase Solid Dielectric Trident-SR with SafeVu Integral Visible Break
Part 1-GENERAL 1.1 DESCRIPTION Guide Specification Three-Phase Solid Dielectric Trident-SR with SafeVu Integral Visible Break The switchgear shall consist of magnetically actuated solid dielectric insulated
More informationApplications. Trim are flat gauge steel per code. Standard painted finish ANSI 61 gray. Directory card with plastic cover on front of trim
Applications The CDP panels provide protection for lightning and power distribution circuits in the commercial and industrial establishments. The circuit breakers thermomagnetic trip allows for momentary
More information17.1. Low Voltage Switchgear. For Immediate Delivery or Tech Support call KMParts.com at (866) Contents
.1 Low Voltage Switchgear Magnum DS Metal-Enclosed Magnum DS Switchgear with Molded Case Circuit Breaker Feeder Section Cross-Reference Eaton s Electrical Sector has an organization dedicated to the support
More information.1 Low Voltage Switchgear Magnum DS Switchgear with Molded Case Circuit Breaker Feeder Section Cross-Reference Eaton s Electrical Sector has an organi
Low Voltage Switchgear Magnum DS Switchgear.1 Cross-Reference................................................ 102 Product Description............................................. 102 Application Description...........................................
More informationHorizontal Circuit Switchers
> Transformer Protection > CIRCUIT SWITCHERS C A T A L O G B U L L E T I N General Application Southern States Types CSH and CSH-B Horizontal Circuit Switchers provide an economical, versatile, space saving
More informationSECTION MICROPROCESSOR TRIP UNITS FOR LV CIRCUIT BREAKERS. This section is organized as indicated below. Select desired Paragraphs.
SECTION 16904 MICROPROCESSOR TRIP UNITS FOR LV CIRCUIT BREAKERS PART 2 PRODUCTS 01 MANUFACTURERS A. B. C. Eaton * * The listing of specific manufacturers above does not imply acceptance of their products
More informationService Entrance Methods
Service Section Typical switchboards consist of a service section, also referred to as the main section, and one or more distribution sections. The service section can be fed directly from the utility
More informationSECTION MOTOR CONTROLLERS
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 29 11 MOTOR CONTROLLERS SPEC WRITER NOTE: Delete between // ---- // if not applicable to project. Also, delete any other item or paragraph not applicable to
More informationPower Break II Switchboard
Power Break II Switchboard Now available with PowerBreak II Circuit Breakers through 4000A GE s Power Break II Switchboard is now available with the new Power Break II Insulated Case Circuit Breaker (800A
More informationIce Rink Renovation & New Clubhouse
SECTION 262913 - ENCLOSED CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationSECTION MOTOR CONTROLLERS
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 29 11 SPEC WRITER NOTE: Use this section only for NCA projects. Delete between // ---- // if not applicable to project. Also, delete any other item or paragraph
More informationSwitchgear. Low Voltage
January 2001 Vol. 1, Ref. No. [0923] -1 Low Voltage Switchgear Contents Description Page Magnum DS Metal-Enclosed Product Description........................................... -2 Application Description........................................
More informationHorizontal Circuit Switchers
> Transformer Protection > CIRCUIT SWITCHERS C A T A L O G B U L L E T I N General Application Southern States Types CSH and CSH-B Horizontal Circuit Switchers provide an economical, versatile, space saving
More informationBRANCH CIRCUIT PROTECTION FUSED COORDINATION PANELBOARD
BRANCH CIRCUIT PROTECTION FUSED COORDINATION BOARD MERSEN S FUSED COORDINATION BOARD Selective Coordination is required in several locations as defined in the National Electrical Code (NEC). Mersen s Fused
More informationBUSWAY Low Voltage (Pow-R-Flex)
BUSWAY LOW VOLTAGE (POW-R-FLEX) PART 1 GENERAL 1.01 1.02 SCOPE The Contractor shall furnish and install the busway system including all necessary fittings, hangers and accessories as specified herein and
More informationLow Voltage Switchgear
Low Voltage Switchgear Magnum DS Switchgear.1 Cross-Reference......................................... Product Description....................................... Application Description....................................
More information020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB)
020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB) CEYLON ELECTRICITY BOARD SRI LANKA Telephone: +94 11 232 0953 Fax: +94 11 232 3935 CONTENTS Page 1.0 Scope 3 2.0 System Parameters 3 3.0 Service
More informationUNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation
Basis of Design This section applies to the design relating to low voltage switchboards. Design Criteria UW Class N1 facilities main switchboards shall be rear accessible. The main, tie and feeder breakers
More informationCONTROLLIX CORPORATION CONTROLLIX.COM LOW VOLTAGE AUTOMATIC SWITCH CAPACITOR BANK SPECIFICATIONS
LOW VOLTAGE AUTOMATIC SWITCH CAPACITOR BANK SPECIFICATIONS I. SCOPE a. This specification describes the necessary requirements for the design, fabrication, and operation of automatically switched, low
More informationCritical Power Switchboards. Selection and Application Guide
Selection and Application Guide Siemens RCIII (rear connected) switchboards utilizing Siemens Type SB Encased Breakers are a perfect solution for your critical power distribution needs. Whether your installation
More informationIndividual breakers in separate enclosures can be applied in low voltage distribution systems through 600 volts Ac, 50/60 Hertz.
Page 2 Introduction The Westinghouse Systems Pow-R Breaker, the worlds first encased power breaker, is not just an extension of existing technology. It represents the biggest breakthrough in circuit protection
More informationFused Coordination Panelboard
Fused Coordination Panelboard SOLUTIONS GUIDE SOLUTIONS GUIDE Branch Circuit Protection Introducing Mersen s Fused Coordination Panelboard Selective Coordination is required in several locations as defined
More informationEast Central College
SECTION 262726 - WIRING DEVICES PART 1 - GENERAL 1.1 WORK INCLUDES A. Base and Alternate Bids: 1. Contractor Provide: a. Wall switches. b. Receptacles c. Device plates and decorative box covers. 1.2 RELATED
More informationSpecification Number: Product Name: GROUP MOUNTED MAIN FUSIBLE SWITCH, GROUP MOUNTED BRANCH FUSIBLE SWITCH (LONG) SECTION
Specification Number: 26 24 13.20 Product Name: GROUP MOUNTED MAIN FUSIBLE SWITCH, GROUP MOUNTED BRANCH FUSIBLE SWITCH (LONG) SECTION 26 24 13.20 SWITCHBOARDS (Long) Main Disconnect Group Mounted Fusible
More informationNEHB Circuit Breaker Panelboards. For 480Y /277V. ac Systems
NEHB Circuit Breaker Panelboards For 480Y /277V. ac Systems www. ElectricalPartManuals ElectricalPartManuals. com com NEHB Panelboards EHB (bolt-on) Circuit Breakers MONO-FLAT front features completely
More informationLow Voltage Switchgear Type WL Low Voltage Metal-Enclosed Switchgear
13 Low Voltage Switchgear Siemens Type WL low voltage metal-enclosed switchgear is designed, constructed and tested to provide superior power distribution, power monitoring and control. At the heart of
More informationSECTION LOW VOLTAGE SWITCHBOARDS - Spectra Bolt-On
PART 1 GENERAL A. The requirements of the Contract, Division 1, and Division 16 apply to work in this Section. 1.01 SECTION INCLUDES A. Low Voltage, Front-Accessible and Front/Rear-Accessible switchboards
More informationC1000 Series Automatic Cap Bank
C1000 Series Automatic Cap Bank Metal Enclosed - Medium Voltage Capacitors Assemblies Fixed / Auto Medium Voltage 5, 15, 25 and 35 kv Class Customized to your specifications The Reactive Power Solution
More informationAre the New 2005 NEC Selective Coordination Requirements Causing an Increase in Arc Flash Energies and Reducing Distribution System Reliability?
Are the New 2005 NEC Selective Coordination Requirements Causing an Increase in Arc Flash Energies and Reducing Distribution System Reliability? The 2005 NEC has new sections that require people transporting
More informationUniversity of Houston Master Construction Specifications Insert Project Name SECTION ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL
SECTION 23 04 10 ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section
More informationSECTION LOW VOLTAGE SWITCHBOARDS - SPECTRA. A. The requirements of the Contract, Division 1, and Division 16 apply to work in this Section.
PART 1 GENERAL A. The requirements of the Contract, Division 1, and Division 16 apply to work in this Section. 1.01 SECTION INCLUDES A. Low Voltage, Front-Accessible and Front/Rear-Accessible switchboards
More informationDesign Standard. Purpose: Design Standard:
Design Standard Purpose: This design standard has the purpose of creating a consistent application of motor-control centers throughout the East Side Union High School District, therefore achieving a standard
More informationMetal-Enclosed Switches. Medium Voltage. Medium Voltage Metal-Enclosed Switches Contents
January 2003 Vol. 1, Ref. No. [1011] -1 Medium Voltage Metal-Enclosed Switches Contents Description Page MVS................................... -2 and Breaker MSB........................ -3 Metal-Enclosed
More informationDescriptive bulletin. Medium voltage load interrupter switchgear Reliable, low maintenance and economical for distribution applications
Descriptive bulletin Medium voltage load interrupter switchgear Reliable, low maintenance and economical for distribution applications General overview Reliable, low maintenance and economical Load Interrupter
More information25.4. Molded Case Circuit Breakers. For Immediate Delivery or Tech Support call KMParts.com at (866) Contents
.4 Molded Case Circuit Breakers Gi-, Fi, Ji-, Ki-, Li-Frames Molded Case Circuit Breaker Family Molded Case Circuit Breakers When higher interrupting ratings are not required. Product Overview Gi-, Fi,
More informationPowerPact Q-Frame Molded Case Circuit Breakers and Switches (Types QB, QD, QG and QJ)
PowerPact Q-Frame Molded Case Circuit Breakers and Switches (Types QB, QD, QG and QJ) Catalog Class 734 0734CT0201R1/07 07 CONTENTS Description..............................................Page Description.............................................
More informationData Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931
Data Bulletin 0931DB0101 July 2001 Cedar Rapids, IA, USA Ground-Censor Ground-Fault Protection System Type GC Class 931 09313063 GT Sensor Shunt Trip of Circuit Interrupter Window Area for Conductors GC
More informationSPECIAL SPECIFICATION 5066 Packaged Engine Generator System
2004 Specifications CSJ 2121-04-072 SPECIAL SPECIFICATION 5066 Packaged Engine Generator System 1. Description. Furnish and install packaged engine generator system complete with transfer switch and service
More information6/4/2017. Advances in technology to address safety. Thomas A. Domitrovich, P.E., LEED AP VP, Technical Sales Eaton
Advances in technology to address safety Thomas A. Domitrovich, P.E., LEED AP VP, Technical Sales Eaton 1 Advances in technology could mean use existing technology & back to basics Advances in safety are
More informationCutler-Hammer Molded Case Circuit Breakers Amperes. January 2001 Vol. 1, Ref. No. [0477] G-Frame
Cutler-Hammer January 200 Vol., Ref. No. [077] s Molded Case s 5-00 Amperes 2- 2-2 Product Line Overview January 200 Vol., Ref. No. [068] 2 Product Line Description Cutler-Hammer Molded Case s are designed
More informationTable Type FD Thermal-Magnetic Circuit Breakers with Non-interchangeable Trip Units
-22 2 Amperes January 1 Vol. 1, Ref. No. [0488] Table -. FD Thermal-Magnetic Circuit Breakers with Non-interchangeable Trip Units Max. Cont. Ampere Rating @ 40 C 600V AC Maximum, 0V DC 277V AC Maximum,
More informationCutler-Hammer. January 2001
Cutler-Hammer Vol. -2 Product Line Overview Vol. 1, Ref. No. [0468] Product Line Description Cutler-Hammer Molded Case s are designed to provide circuit protection for low voltage distribution systems.
More informationA. Provide variable frequency drives to operate variable torque loads as shown on the Drawings and as specified herein.
DIVISION 23 HEATING, VENTILATING, AND AIR CONDITIONING (HVAC) SECTION 23 90 71 PART 1 GENERAL 1.01 DESCRIPTION A. Provide variable frequency drives to operate variable torque loads as shown on the Drawings
More informationBussmann series Quik-Spec Coordination Panelboard
Quik-Spec electrical gear 12 Contents Bussmann series Quik-Spec Coordination Panelboard Section page Description Quik-Spec Coordination Panelboards Up to 400 A 2 600 to 1200 A 3 Quik-Spec elevator disconnects
More informationTypical Specification
Engineered to Order Built to Last Typical Specification VAULT VRPFI, TWO POSITION, ROTARY PUFFER SWITCHGEAR PART 1- GENERAL 1.1 DESCRIPTION A. The switch shall consist of manually operated load interrupting,
More informationSUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)
SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products for utilities
More informationWestinghouse Electric Corporation Distribution and Control Business Unit Assemblies Division Bloomington, Indiana
Supersedes Descriptive Bulletin, pages 1-8, dated January, 1976 Mailed to: E, D, C/38-000F Westinghouse Electric Corporation Distribution and Control Business Unit Assemblies Division Bloomington, Indiana
More informationSUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)
SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products
More informationSUBSTATION VACUUM CIRCUIT BREAKER (38KV)
SUBSTATION VACUUM CIRCUIT BREAKER (38KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products for utilities
More informationMOLDED CASE CIRCUIT BREAKER BASICS. David Castor, P.E.
MOLDED CASE CIRCUIT BREAKER BASICS David Castor, P.E. History of MCCBs 1904 - Cutter Manufacturing Co., Philadelphia, produces circuit breakers. They called it the Inverse Time Element breaker, or I-T-E
More informationPowerPact M-, P- and R-Frame, and Compact NS630b NS3200 Circuit Breakers
PowerPact M-, P- and R-Frame, and Compact NS630b NS3200 Circuit Breakers Catalog 0612CT0101 R02/14 2014 Class 0612 CONTENTS Description............................................. Page General Information..........................................
More informationSECTION DOMESTIC-WATER PACKAGED BOOSTER PUMPS
SECTION 221123.13 - DOMESTIC-WATER PACKAGED BOOSTER PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More information9/7/2010. Objectives. Article 90. Introduction NEC Significant Changes. Review significant revisions in the 2011 NEC
2011 NEC Significant Changes Courtesy of NJATC Courtesy of NFPA Presented By: Michael J. Johnston Executive Director of Standards and Safety, NECA Objectives Review significant revisions in the 2011 NEC
More informationSelective Coordination
Circuit Breaker Curves The following curve illustrates a typical thermal magnetic molded case circuit breaker curve with an overload region and an instantaneous trip region (two instantaneous trip settings
More informationSpecification for 70mm pole pitch Air circuit breaker up to 1600 A
Specification for 70mm pole pitch Air circuit breaker up to 1600 A Protective device for low voltage electrical installation Last update :2011-07-08-1 - Table of contents: 1 General...3 2 Compliance with
More informationMoulded case circuit breakers
Moulded case circuit breakers CONTENT Range 4 Protection Releases 5 Salient Features 8 Accessories, 4 Technical data 2 Time Current Characteristics 5 Overall Dimensions 7 SN4 SN3 SN2 SN 3 RANGE Moulded
More informationVL Circuit Breaker Features & Benefits. powerful ideas RELIABLE SOLUTIONS
VL Circuit Breaker Features & Benefits powerful ideas RELIABLE SOLUTIONS A Solutions Oriented Circuit Protection Family The Tangram An ancient Chinese game in which a few simple components provide endless
More information013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS
013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEYLON ELECTRICITY BOARD SRI LANKA Specification for MOULDED CASE CIRCUIT BREAKERS FOR OVERHEAD NETWOKS CEB Specification
More informationSECTION MOTORS AND VARIABLE FREQUENCY DRIVES
PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Related Sections: 1. Section 15050 - Basic Mechanical Requirements. 2. Section 15051 - Motors. 3. Section 15185 - Hydronic Pumps. 4. Section 15625 - Centrifugal
More informationMedium Voltage Metal-Enclosed Switches
Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Medium Voltage Switch MVS Product Description............................................. 2 Application Description..........................................
More informationA system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment.
General Unit substations shall be 500 kva minimum, 1500 kva maximum unless approved otherwise by the University. For the required configuration of University substations see Standard Electrical Detail
More informationSECTION SWITCHGEAR. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section.
PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes metal-enclosed,
More informationPublication No.: PSG
TABLE OF CONTENTS PAGE 1.0 SCOPE...2 2.0 STANDARDS...2 3.0 DESIGN REQUIREMENTS...2 3.01 Service Conditions... 2 3.02 Ratings... 3 3.03 Resistors... 3 3.04 Interrupter... 4 3.05 SF 6 Gas System... 4 3.06
More informationCutler-Hammer. Installation Instructions for the Digitrip OPTIM Pole Trip Unit Installation and Operation with L-Frame Series C Circuit Breakers
Cutler-Hammer Installation Instructions for the Digitrip OPTIM 550 3-Pole Trip Unit Installation and Operation with L-Frame Series C Circuit Breakers Table of Contents Description Page 1.0 General Information......................1
More informationD2P and EWP Factory Sealed Circuit Breaker Panelboards Explosionproof, Dust-Ignitionproof, Watertight, Corrosion-Resistant
Applications Protection and control of electrical equipment and circuits such as lighting and heat tracing in hazardous locations or in damp, wet or corrosive conditions. D2P Series designed for use in
More informationSECTION DOMESTIC-WATER PACKAGED BOOSTER PUMPS
SECTION 22 1123.13 DOMESTIC-WATER PACKAGED BOOSTER PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationA. This section includes unit capacitors for power factor correction.
PART 1: GENERAL 1.01 Wiring Devices A. This section of the standard includes design requirements for wiring connections, including receptacles and switches to equipment specified in other sections. 1.02
More informationSECTION MOTOR STARTERS (AMPGARD) MEDIUM VOLTAGE
MOTOR STARTERS (AMPGARD) MEDIUM VOLTAGE PART 1 GENERAL 1.01 1.02 1.03 1.04 SCOPE The Contractor shall furnish and install the medium voltage motor starters as specified herein and as shown on the contract
More information3RV1011-0DA15 CIRCUIT-BREAKER, SIZE S00,
Low-Voltage Controls and Distribution > Industrial Controls > Protection Equipment > Circuit Breakers/Motor Starter Protectors > Motor Starter Protectors SIRIUS RV up to 00 A RV0-0DA5 CIRCUIT-BREAKER,
More informationAmperes. F-Frame. Price U.S. $ Catalog Number. Price U.S. $ EDH2100 EDH2125 EDH2150 EDH2175 EDH2200 EDH2225
January 1 Vol. 1, Ref. No. [0487] 2 Amperes - Product Selection Table -33. s,, and E Thermal-Magnetic Circuit Breakers with Non-interchangeable Trip Units Suitable for Reverse Feed Maximum Continuous Ampere
More informationSECTION WIRING DEVICES
SECTION 16140 - WIRING DEVICES PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. General: Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More information