S&C TripSaver II. Cutout-Mounted Recloser. For enhanced lateral circuit protection at 15 kv and 25 kv

Size: px
Start display at page:

Download "S&C TripSaver II. Cutout-Mounted Recloser. For enhanced lateral circuit protection at 15 kv and 25 kv"

Transcription

1 TripSaver II Cutout-Mounted Recloser For enhanced lateral circuit protection at 15 kv and 25 kv

2 Introducing s new TripSaver II Cutout-Mounted Recloser: A better solution for overhead lateral circuit protection at 15 kv and 25 kv Conventional lateral circuit protection requires some concessions Over 90% of temporary faults on overhead distribution circuits occur on laterals. Over the years, utilities have dealt with lateral protection a couple of ways. Some utilities employ a fuse blowing philosophy: The substation feeder breaker is properly coordinated with the lateral fuse, so that the fuse will clear any downstream fault within its rating... not the breaker. The problem: Service to customers on the lateral is permanently interrupted even for a temporary fault as shown in Figure 1. And the utility must deal with the high cost of service calls to replace lateral fuses. Feeder breaker Temporary or permanent fault Lateral fuse Feeder breaker Temporary fault Figure 1. Fuse blowing philosophy. Lateral fuse Other utilities employ a fuse saving philosophy: The first trip of the substation feeder breaker is intentionally miscoordinated so that the breaker operates faster than the lateral fuse to clear a fault downstream of the lateral fuse. The second trip of the breaker is slower so that if the fault is still present, the lateral fuse will operate to clear it. The problem: All customers on the feeder experience a momentary interruption for all faults as shown in Figure 2. Figure 2. Fuse saving philosophy. TripSaver II provides better lateral protection s new TripSaver II Cutout-Mounted Recloser eliminates these problems. It s ideally suited for protection of laterals that experience frequent temporary faults. This self-powered, electronically controlled, single-phase vacuum fault interrupter is available for installation in new or existing currentproduction ( -R10 or -R11 ) or MacLean Power Systems Type XS Fuse Cutout Mountings. A twoinsulator, branch-feeder style mounting is also available. TripSaver II eliminates the permanent outage which results when the lateral fuse operates in response to a temporary fault. Utilities using fuse blowing will see an improvement in SAIFI without sacrificing MAIFI. And TripSaver II eliminates the momentary interruption on the feeder in instances where the breaker is tripped to save the lateral fuse during a temporary fault. Utilities using fuse saving will see an improvement in MAIFI without sacrificing SAIFI. 2

3 TripSaver II has been tested to, and is in compliance with, IEEE Standards C and C and IEC Standard TripSaver II is manufactured in accordance with a quality system certified to ISO 9001:2000. As shown in the following table, TripSaver II offers a number of advantages over traditional lateral protective devices. Comparison of Lateral Protective Devices Feature/Benefit Single-Phase Hydraulic Recloser Dropout-Style Electronic Sectionalizer TripSaver II Easy to install Low initial price Low installation cost Fault-interrupting capability Easy to reset Electronic control No bypass switch required Light weight compared to oil reclosers No battery backup required Fits in cutout mounting No momentary outage on the main feeder for lateral faults 3

4 TripSaver II s operating sequence TripSaver II supports up to three reclosing operations (four tripping operations in total) before it drops open. A wide variety of time-current characteristic (TCC) curves are available. The open interval between tripping operations is five seconds. The vacuum interrupter resets two seconds after TripSaver II drops open. The operator can then reclose TripSaver II into the mounting. In instances in which a temporary fault is cleared before TripSaver II reaches the end of its operating sequence, TripSaver II will revert to its first TCC curve, i.e., reset after 15 seconds have elapsed since the last reclosing operation. How TripSaver II works for a temporary fault Consider a temporary fault downstream of TripSaver II, as shown in Figure 3. Feeder breaker Figure 4. TripSaver II opens. After five seconds, TripSaver II recloses, restoring power to customers served from the lateral downstream, as shown in Figure 5. Since the fault was temporary and has been cleared, further tripping operations aren t needed. TripSaver II reverts to its first TCC after 15 seconds. TripSaver II Temporary fault Figure 3. Temporary fault. Utilizing its fast TCC curve, TripSaver II opens, as shown in Figure 4. Only customers served from the lateral downstream of TripSaver II experience a momentary interruption. Figure 5. TripSaver II recloses. How TripSaver II works for a permanent fault Consider a permanent fault downstream of TripSaver II, as shown in Figure 6. 4

5 Feeder breaker TripSaver II Permanent fault Permanent fault Figure 6. Permanent fault. Figure 8. TripSaver II recloses. As before, utilizing its fast TCC curve, TripSaver II opens, as shown in Figure 7. Again, only customers served from the lateral downstream of TripSaver II experience a momentary interruption. Since the fault is permanent, TripSaver II performs further tripping operations per the specified TCC curves. For utilities employing fuse saving philosophy, TripSaver II drops open at the end of its operating sequence, in the same manner as a standard fuse cutout providing visual indication that the faulted lateral has been isolated, as shown in Figure 9. The vacuum interrupter resets two seconds after TripSaver II drops open. TripSaver II may then be reclosed by the operator once the fault has been repaired. Permanent fault Figure 7. TripSaver II opens. Figure 9. TripSaver II drops open. TripSaver II recloses, as shown in Figure 8. 5

6 Construction and Features A Birdproof-design insulator higher insulation characteristics than ANSI distribution-cutout standards. Porcelain insulator shown; composite-polymer silicone insulator also available. NEMA Type B and Extended Mounting Brackets are available B Parallel-groove connector tin-plated cast red brass. For ease of connection, accommodates two conductors, even of unlike size D B A C Attachment hooks for Loadbuster Tool it also guides TripSaver II during manual closing E D Upper contact silver-to-silver; stainless-steel spring provides high contact pressure C E F Bumper and Retainer spring-loaded retainer and bumper dampen impact on closing, reducing the possibility of bounce-back Vacuum fault interrupter it is contained inside the upper housing G Trunnion high-strength cast bronze, silver plated. Surfaces around trunnion bear on broad hinge surfaces to keep TripSaver II in alignment during closing. Its special shape facilitates easy removal and reduces vibration F G H H Lower contacts silver-to-silver; provide dual current path, independent of hinge pivot I Mode selector for selecting automatic reclosing or non-reclosing operation. In nonreclosing mode, TripSaver II will operate oneshot-to-lockout, suitable for use when crews are working downstream of TripSaver II I J Liquid-crystal display screen displays TripSaver II status. Six languages are supported J Ice-Breaking Capability TripSaver II is capable of dropping open under ¾-inch (20-mm) ice formation. Sectionalizing Option A sectionalizing option is available for TripSaver II models rated 4 ka. If specified, TripSaver II will operate as a sectionalizer for faults between 4 ka and 6.5 ka. TripSaver II will count the number of operations of the source-side circuit-breaker or recloser, and drop open after the specified number of counts. The counter resets if no sectionalizing event is registered for 120 seconds. 6

7 Ratings Complete Overhead Pole-Top Style TripSaver II For a new installation. Includes TripSaver II, mounting (less mounting bracket), and connectors 50/60-Hz Ratings1 With Porcelain Insulator With Polymer Insulator System Class kv Nom. Max BIL Cont. Amperes, RMS2 Interr., Sym. Leakage Distance to Ground Minimum, Inches (mm) Base Catalog Number Leakage Distance to Ground Minimum, Inches (mm) Base Catalog Number For 50-Hz applications, specify Microprocessor Control for Application on 50-Hz Systems, Catalog Number Suffix -F. 2 Minimum trip current is 5 amperes Z\x (216) M\, (378) P Z\x (216) M\, (378) P (279) (279) (432) a 19 (483) Pa (432) a 19 (483) Pa a Applicable for protection of single-phase-to-neutral circuits only in solidly-grounded-neutral (multi-grounded-neutral) 34.5-kV systems where leakage distance to ground meets user s requirement. Uses 25-kV 150-kV BIL mounting. Complete Branch-Feeder Style TripSaver II For a new installation. Includes TripSaver II, mounting (less backup member and mounting hardware), and connectors System Class 50/60-Hz Ratings1 With Porcelain Insulator With Cypoxy Insulator kv Amperes, RMS2 Leakage Distance to Ground Minimum, Interr., Nom. Max BIL Cont. Inches (mm) Sym For 50-Hz applications, specify Microprocessor Control for Application on 50-Hz Systems, Catalog Number Suffix -F. 2 Minimum trip current is 5 amperes. Base Catalog Number Leakage Distance to Ground Minimum, Inches (mm) Base Catalog Number (610) Z\v (616) E (610) Z\v (616) E (610) a 24 Z\v (616) Ea (610) a 24 Z\v (616) Ea a Applicable for protection of single-phase-to-neutral circuits only in solidly-grounded-neutral (multi-grounded-neutral) 34.5-kV systems where leakage distance to ground meets user s requirement. Uses 25-kV 150-kV BIL mounting. TripSaver II Only For retrofitting in an existing current-production ( -R10 or -R11 ) or MacLean Power Systems Type XS Fuse Cutout Mounting For Use with Type XS Fuse Cutout Mounting 50/60-Hz Ratings1 Basic Catalog Number 89811, 89021, 89031, 89071, SC15HG, 89221, , 89022, 89032, 89072, 89802, 89042, 89052, 89092, SC27SG, 89222, 89223, 99022, System Class 1 For 50-Hz applications, specify Microprocessor Control for Application on 50-Hz Systems, Catalog Number Suffix -F. kv Nom. Max BIL Cont or Minimum trip current is 5 amperes. Amperes, RMS2 Interr., Sym. Base Catalog Number

8 Mounting Bracket Options For Overhead Pole-Top Style TripSaver II Models Item Add Catalog Number Suffix Extended Mounting Bracket, for crossarm, pole, or wall mounting -B NEMA Type B Mounting Bracket, for crossarm mounting - C Backup Member and Mounting Hardware Options For Branch-Feeder Style TripSaver II Models Item Add Catalog Number Suffix Two 3/ /2 bolts -D1 Backup Member with galvanized steel carriage bolts (3 minimum thread), flat washers, lockwashers, and nuts Four 3/ /2 bolts -D2 Two 3/ bolts -D3 Four 3/ bolts -D4 Sectionalizer Mode Option For TripSaver II Models Rated 4 ka Only Item Sectionalizer Mode TripSaver II will operate as a recloser and interrupt fault currents up to 4 ka. For fault currents greater than 4 ka, up to 6.5 ka, TripSaver II will operate as a sectionalizer, and drop open after counting the specified number of source-side circuit breaker or recloser tripping operations. The counter resets if no sectionalizing event is registered for 120 seconds Add Catalog Number Suffix -Snl l Specify the number of source-side circuit breaker or recloser tripping operations, n (1 to 9), that TripSaver II counts up to before dropping open. Time-Current Characteristic Curves Instantaneous Instantaneous Fuse Link K Speed T Speed 6K 6T 10K 20K 30K 40K 50K 65K 80K 100K 10T 20T 30T 40T 50T 65T 80T 100T Cooper Forms 4, 5, 6, FX Type H 1 Discrete pickup currents (5 A through 200 A), and discrete time multipliers (0.1 through 0.9 and 1 through 9) can be selected. Recloser1 Cooper Hydraulic Recloser Type 4H, V4H Type L Type V4L (V4E) Type E Type 4E SEL 351R/651R A A A A A A Inverse (U2) B B B B B B Very Inverse (U3) C C C C C C D D D D Extremely Inverse (U4) Short-Time Inverse (U5) Inverse (C1) Very Inverse (C2) Extremely Inverse (C3) Short-Time Inverse (C5) 8

9 User Interface Indicator appears if TripSaver II trips and drops open on overload Vacuum interrupter status Operating mode Service Soon indicator appears when 10% vacuum interrupter life remains LCD screen and mode selector. Springs help guide mode selector lever to the desired position; colored labels provide visual confirmation. NR mode engaged as shown: upper label completely exposes and lower labels align. The Normal screen shows four operating parameters. Load Current Last Fault Current Operation Counter Vacuum Interrupter Life Remaining Internal Ambient Temperature Sectionalizing Feature Enabled, with Counts Setting The Display screen scrolls through six additional parameters. 9

10 TripSaver II Styles Base Catalog Numbers or Complete Overhead Pole-Top Style TripSaver II rated 15 kv nominal; 15.5 kv maximum; 110 kv BIL; 100 amperes continuous; or amperes interrupting, RMS, symmetrical; 8Z\x inches (216 mm) leakage distance to ground; porcelain mounting. Base Catalog Numbers or Complete Overhead Pole-Top Style TripSaver II rated 25 kv nominal; 29 kv maximum; 125 kv BIL; 100 amperes continuous; or amperes interrupting, RMS, symmetrical; 11 inches (279 mm) leakage distance to ground; porcelain mounting. Base Catalog Numbers or Complete Overhead Pole-Top Style TripSaver II rated 25 kv nominal; 29 kv maximum; 150 kv BIL; 100 amperes continuous; or amperes interrupting, RMS, symmetrical; 17 inches (432 mm) leakage distance to ground; porcelain mounting. Base Catalog Numbers E or E. Complete Branch-Feeder Style TripSaver II rated 15 kv nominal; 15.5 kv maximum; 150 kv BIL; 100 amperes continuous; or amperes interrupting, RMS, symmetrical; 24Z\v inches (616 mm) leakage distance to ground; Cypoxy insulators. 10

11 Handling TripSaver II Overhead Pole-Top Style Shown TripSaver II in dropped-open position Two seconds after TripSaver II drops open, the vacuum interrupter resets. Closing TripSaver II back into mounting TripSaver II can be readily closed back into the mounting using a standard hookstick equipped with an Talon Fuse Handling Fitting or a distribution prong. Opening TripSaver II with Loadbuster If the lateral circuit needs to be de-energized, TripSaver II can be opened using Loadbuster the Loadbreak Tool. 11

12 Specifications Voltage Ratings 15 kv Nominal Operating Voltage (kv) Maximum Design Voltage (kv) Basic Insulation Level (BIL) of mounting kv Nominal Operating Voltage (kv) Maximum Design Voltage (kv)...29 Basic Insulation Level (BIL) of mounting /150 Current Ratings Continuous Current (amperes) All models Symmetrical Interrupting Current (amperes) All models /6 300 Overload Capability 50 C) All models 125 amperes (125%) amperes (150%) Half-Second Current, Symmetrical (amperes) All models 100 amperes Duty Cycle Percent of Maximum Circuit Interrupting Rating Mechanical Life Minimum X/R Ratio Number of Unit Operations Total 68 Minimum Number of Operations Weight, lbs. (kg) 15-kV (110-kV BIL) (10.5) 25-kV (125-kV BIL or 150-kV BIL) (11.3) Printed in U.S.A. Descriptive Bulletin November 19, 2012 Offices Worldwide f

Improving distribution systems reliability with Cutoutmounted single phase Reclosers

Improving distribution systems reliability with Cutoutmounted single phase Reclosers Improving distribution systems reliability with Cutoutmounted single phase Reclosers AEDU Namibia Branch Meeting 16 March 2017, Swakopmund - Namibia 2013 461-3000 www.sandc.com Outline Review of lateral

More information

S&C Recloser Bypass Disconnects

S&C Recloser Bypass Disconnects S&C Recloser Bypass Disconnects Outdoor Distribution (14.4 kv through 34.5 kv) Application S&C Recloser Bypass Disconnects are station-type devices used to bypass and isolate automatic circuit reclosers

More information

S&C Fault Tamer Fuse Limiter. Outdoor Distribution (15 kv through 25 kv)

S&C Fault Tamer Fuse Limiter. Outdoor Distribution (15 kv through 25 kv) S&C Fault Tamer Fuse Limiter Outdoor Distribution (5 kv through 25 kv) Introducing S&C s new generation of pole-top transformer protection... Application Although the S&C Fault Tamer Fuse Limiter handles

More information

Outdoor Distribution (15 kv through 25 kv) S&C Fault Tamer Fuse Limiter

Outdoor Distribution (15 kv through 25 kv) S&C Fault Tamer Fuse Limiter Outdoor Distribution (5 kv through 25 kv) S&C Fault Tamer Fuse Limiter Introducing S&C s new generation of pole-top transformer protection... Application Although the S&C Fault Tamer Fuse Limiter handles

More information

S&C Loadbuster Disconnects

S&C Loadbuster Disconnects S&C Loadbuster Disconnects Outdoor Distribution ( kv through 34.5 kv) With these outstanding features... Up to -ampere continuous ratings, 40,000-ampere RMS asymmetrical momentary ratings Designed for

More information

S&C Loadbuster Disconnect Switches. Outdoor Distribution (14.4 kv through 34.5 kv)

S&C Loadbuster Disconnect Switches. Outdoor Distribution (14.4 kv through 34.5 kv) S&C Loadbuster Disconnect Switches Outdoor Distribution ( kv through 34.5 kv) S&C s Loadbuster Disconnect Switches, when used with S&C s Loadbuster tool, provide the ultimate in distribution live-switching

More information

Specifications. S&C Type XS Fuse Cutouts. Outdoor Distribution (4.16 kv through 25 kv)

Specifications. S&C Type XS Fuse Cutouts. Outdoor Distribution (4.16 kv through 25 kv) Outdoor Distribution (4.16 through 25 ) Specifications Conditions of Sale STANDAD: Seller s standard conditions of sale set forth in Price Sheet 153 apply, except as modified under WAANTY QUALIFICATIONS

More information

Specifications. S&C Power Fuses Types SM- 4, SM-5, SMD-20, and SMD-40 Outdoor Distribution (4.16 kv through 34.5 kv)

Specifications. S&C Power Fuses Types SM- 4, SM-5, SMD-20, and SMD-40 Outdoor Distribution (4.16 kv through 34.5 kv) S&C Power Fuses Types SM- 4, SM-5, SMD-0, and SMD-40 Outdoor Distribution (4.16 kv through kv) For use with SM Refill Units or SMU Fuse Units Specifications Conditions of Sale STANDARD: The seller s standard

More information

www. ElectricalPartManuals. com SPECIFICATIONS Page 1 of 24 March 24, 2003

www. ElectricalPartManuals. com SPECIFICATIONS Page 1 of 24 March 24, 2003 Types SM-4, SM-5, SMD-20, and SMD-40 Outdoor Distribution (4.16 kv through kv) Conditions of Sale STANDARD: Seller s standard conditions of sale set forth in Price Sheet apply, except as modified under

More information

S&C Type XS Fuse Cutouts

S&C Type XS Fuse Cutouts S&C Type XS Fuse Cutouts Outdoor Distribution 4.16 kv through 25 kv Application An Unexcelled Cutout S&C Type XS Fuse Cutouts, when fused with S&C Positrol Fuse Links provide full-fault-spectrum protection

More information

Solid Dielectric, Three Phase Reclosers CATALOG VS11

Solid Dielectric, Three Phase Reclosers CATALOG VS11 Solid Dielectric, Three Phase Reclosers Providing electronic, three phase overcurrent protection for systems rated through 38kV, 800A continuous current, 12.5kA symmetrical interrupting Reliable performance

More information

S&C Type XS Fuse Cutouts

S&C Type XS Fuse Cutouts S&C Type XS Fuse Cutouts Outdoor Distribution (4.16 kv through 25 kv) S&C ELECTRIC COMPANY Specialists in Electric Power Switching and Protection Descriptive Bulletin 351-30 August 25, 2003 Supersedes

More information

AutoLink Frequently Asked Questions

AutoLink Frequently Asked Questions Rev. 3 October 2013 Page 1 of 8 AutoLink Frequently Asked Questions October 2013 1 Rev. 3 October 2013 Page 2 of 8 Table of Contents 1 Background... 4 1.1 What is the AutoLink Single Phase Electronic Sectionalizer?...

More information

Disconnect & ByPass Switches

Disconnect & ByPass Switches Disconnect & ByPass Switches Disconnect & Oil Circuit Recloser Bypass Switches; Regulator & Current Transformer Bypass Switches Electrical Apparatus K-SEC 060 & 090 Contents Type D-73 Distribution Class

More information

Solid Dielectric, Single Phase Recloser

Solid Dielectric, Single Phase Recloser Solid Dielectric, Single Phase Recloser Catalog O-vsp17 Viper-SP Viper-SP solid dielectric, single phase recloser combines the time-proven reliability of electronically controlled, vacuum fault interrupters

More information

Type L Cutouts. UltraSIL Polymer-Insulated and Porcelain Type L Open Distribution Cutout. Description

Type L Cutouts. UltraSIL Polymer-Insulated and Porcelain Type L Open Distribution Cutout. Description Type L Cutouts UltraSIL Polymer-Insulated and Porcelain Type L Open Distribution Cutout Electrical Apparatus 327-30 Description Cooper Power Systems has set a new standard of excellence for polymer distribution

More information

T YPE MZ DISTRIBUTION S TANDARD CUTOUT

T YPE MZ DISTRIBUTION S TANDARD CUTOUT T YPE MZ DISTRIBUTION S TANDARD CUTOUT Page 1 of 7 The Fuse Cutout type MZ was developed to operate in overhead distribution systems rated at 15, 27 and 38 kv grounded systems with 100 or 200 A nominal

More information

Type M3 Hookstick Disconnect Switches Up to 38kV 600 or 900 Amp 40kA Momentary

Type M3 Hookstick Disconnect Switches Up to 38kV 600 or 900 Amp 40kA Momentary 14B-2 Type M3 Hookstick Disconnect Switches Up to 38kV 0 or 900 Amp 40kA Momentary Application The Chance Type M3 Disconnect Switch is a single-phase hookstick operated switch. It is for manual switching

More information

Specifications. S&C Power Fuses Types SM and SMLa. For use with SM Refill Units or SMU Fuse Units. Indoor Distribution (4.16 kv through 34.

Specifications. S&C Power Fuses Types SM and SMLa. For use with SM Refill Units or SMU Fuse Units. Indoor Distribution (4.16 kv through 34. S&C Power Fuses s SM and SMLa Indoor Distribution (4.16 through 34. ) For use with SM Refill Units or SMU Fuse Units Specifications Conditions of Sale STANDARD: Seller s standard conditions of sale set

More information

16kA Solid Dielectric, Triple Option Reclosers Catalog VLT12

16kA Solid Dielectric, Triple Option Reclosers Catalog VLT12 16kA Solid Dielectric, Triple Option Reclosers Providing electronic overcurrent protection for single or three phase operation on systems rated through 27kV, 630A continuous current, 16kA symmetrical interrupting

More information

Electronic Resettable Sectionalizer

Electronic Resettable Sectionalizer POWER SYSTEMS, INC. Protected by U.S. Patents No. 5,612,661; 4,935,715; DES. 278,331 and other patents pending Warranty - Material Hubbell Power Systems, Inc. warrants all products sold by it to be merchantable

More information

Solid Dielectric, Single Phase Reclosers

Solid Dielectric, Single Phase Reclosers Solid Dielectric, Single Phase Reclosers Providing electronic overcurrent protection for single phase operation on systems rated through 38kV, 800A continuous current,12.5ka symmetrical interrupting Reliable

More information

Solid Dielectric, Independent Pole Operated Reclosers Catalog O-vst16

Solid Dielectric, Independent Pole Operated Reclosers Catalog O-vst16 Solid Dielectric, Independent Pole Operated Reclosers Providing electronic overcurrent protection for single or three phase operation on systems rated through 38kV, 800A continuous current, 12.5kA symmetrical

More information

HUBBELL Type M3 Hookstick Disconnect Switches Up to 38kV 600 or 900 Amp 40kA Momentary

HUBBELL Type M3 Hookstick Disconnect Switches Up to 38kV 600 or 900 Amp 40kA Momentary Catalog 14B January 2015 HUBBELL Type M3 Hookstick Disconnect Switches Up to 38kV 600 or 900 Amp 40kA Momentary Application The Chance Type M3 Disconnect Switch is a single-phase hookstick operated switch.

More information

TYPE BLT DISCONNECT SWITCHES

TYPE BLT DISCONNECT SWITCHES TYPE BLT DISCONNECT SWITCHES OUTDOOR-HOOK OPERATED 8.3KV through 38KV A & A Current Furnished with hooks for loadbreak tool REA/RUS approved S M C O 1 BLT PARALLEL BLADE DISTRIBUTION CLASS DISCONNECT SWITCH

More information

UltraSIL polymer-insulated and porcelain loadbreak Type LB open distribution cutout

UltraSIL polymer-insulated and porcelain loadbreak Type LB open distribution cutout Fusing Equipment Catalog Data CA132035EN Supersedes November 2015 COOPER POWER SERIES UltraSIL polymer-insulated and porcelain loadbreak Type LB open distribution cutout Description Eaton has set a standard

More information

S&C Manual PME Pad-Mounted Gear

S&C Manual PME Pad-Mounted Gear S&C Manual PME Pad-Mounted Gear Outdoor Distribution,. kv and 5 kv S&C Manual PME Pad-Mounted Gear... Featuring Elbow-Connected Encased Components. S&C Manual PME Pad-Mounted Gear brings in-air insulation,

More information

SPECIFICATION BULLETIN

SPECIFICATION BULLETIN SPECIFICATIONS Conditions of Sale STANDARD: Seller s standard conditions of sale set forth in Price Sheet 150 apply, except as modified under WARRANTY QUALIFICATIONS on page 3. SPECIAL TO THIS PRODUCT:

More information

Specifications. S&C Alduti-Rupter Switches with Power Fuses Outdoor Distribution (14.4 kv through 46 kv)

Specifications. S&C Alduti-Rupter Switches with Power Fuses Outdoor Distribution (14.4 kv through 46 kv) Outdoor Distribution (4.4 kv through 46 kv) Specifications Conditions of Sale STANDARD: Seller s standard conditions of sale set forth in Price Sheet 50 apply, except as modified under WARRANTY QUALIFICATIONS

More information

SPECIFICATIONS. S&C Alduti-Rupter Switches with Power Fusesa SPECIFICATION BULLETIN Indoor Distribution (4.8 kv and 13.

SPECIFICATIONS. S&C Alduti-Rupter Switches with Power Fusesa SPECIFICATION BULLETIN Indoor Distribution (4.8 kv and 13. S&C Alduti-Rupter Switches with Power Fusesa SPECIFICATIONS Conditions of Sale STANDARD: Seller s standard conditions of sale set forth in Price Sheet 150 apply, except as modified under WARRANTY QUALIFICATIONS

More information

APPENDIX E. Electrical System Single Line Diagram Overcurrent Protection Study Overcurrent Protection Device Specifications

APPENDIX E. Electrical System Single Line Diagram Overcurrent Protection Study Overcurrent Protection Device Specifications Student Resource Building University of California Santa Barbara Clement Fung Lighting Electrical Option APPENDIX E Electrical System Single Line Diagram Overcurrent Protection Study Overcurrent Protection

More information

T HREE-SHOT TYPE MZR F USE CUTOUT

T HREE-SHOT TYPE MZR F USE CUTOUT T HREE-SHOT TYPE MZR F USE CUTOUT Page 1 of 7 D ESCRIPTION It is known that about 90% of the defects that occur in an air distribution system, are of a transient origin, i.e., are transient faults which

More information

Figure 1. HX cutout fuseholders.

Figure 1. HX cutout fuseholders. Fusing Equipment Kearney Open Distribution Cutout - Type HX Electrical Apparatus K-SEC 010 GENERAL Application Versatility Cooper Power Systems Kearney HX cutouts can be quickly and economically adapted

More information

M-Force three-phase switch

M-Force three-phase switch Supersedes K-SEC 926 December 2012 M-Force three-phase switch Description The M-Force switch from Eaton's Cooper Power Systems is a distribution-class, gangoperated, factory unitized three-phase overhead

More information

Solid Dielectric, Triple Option Reclosers Catalog O-vlt14

Solid Dielectric, Triple Option Reclosers Catalog O-vlt14 Solid Dielectric, Triple Option Reclosers Providing electronic overcurrent protection for single or three phase operation on systems rated through 27kV, 630A or 800A continuous current, 12.5 or 16kA symmetrical

More information

M-Force three-phase switch

M-Force three-phase switch Switches and Disconnects CA008004EN Supersedes May 2015 COOPER POWER SERIES M-Force three-phase switch Description Eaton's Cooper Power series M-Force switch is a distribution-class, gang-operated, factory

More information

KFE10002-E. Reclosers. Type KFE and KFVE Electronically Controlled Vacuum Recloser Installation Instructions. Service Information

KFE10002-E. Reclosers. Type KFE and KFVE Electronically Controlled Vacuum Recloser Installation Instructions. Service Information Reclosers Type KFE and KFVE Electronically Controlled Vacuum Recloser Installation Instructions Service Information KFE10002-E CONTENTS Shipment and Acceptance... 2 Handling and Storage... 2 Description...

More information

Figure 1. HX cutout fuseholders. Positive Interruption

Figure 1. HX cutout fuseholders. Positive Interruption Fusing Equipment Kearney Open Distribution Cutout - Type HX Electrical Apparatus 327-10 general Application Versatility Cooper Power Systems Kearney HX cutouts can be quickly and economically adapted to

More information

RUS accepted Catalog O-vst18

RUS accepted Catalog O-vst18 Solid-Dielectric, Independent Pole Option Recloser Providing electronic overcurrent protection for single or three phase operation on systems rated through 38kV, 800A continuous current, 12.5kA or 16kA

More information

Fusing Equipment. Kearney Fuse Links. general. Internal Construction. tin element

Fusing Equipment. Kearney Fuse Links. general. Internal Construction. tin element Fusing Equipment Kearney Fuse Links Electrical Apparatus 327-40 general Cooper Power Systems Kearney fuse links can be applied to a variety of applications requiring overcurrent protection of distribution

More information

Specifications. S&C Alduti-Rupter Switchesa Indoor Distribution (4.8 kv through 34.5 kv) Conditions of Sale SPECIAL TO THIS PRODUCT: How to Order

Specifications. S&C Alduti-Rupter Switchesa Indoor Distribution (4.8 kv through 34.5 kv) Conditions of Sale SPECIAL TO THIS PRODUCT: How to Order S&C Alduti-Rupter Switchesa Indoor Distribution ( kv through kv) Specifications Conditions of Sale STANDARD: Seller s standard conditions of sale set forth in Price Sheet 0 apply. SPECIAL TO THIS PRODUCT:

More information

solutions RUS accepted

solutions RUS accepted Solid Dielectric, Triple Option Reclosers Providing electronic overcurrent protection for single or three phase operation on systems rated through 38kV, 800A continuous current, 12.5kA symmetrical interrupting

More information

Solid Dielectric, Triple Option Reclosers Catalog O-vlt14

Solid Dielectric, Triple Option Reclosers Catalog O-vlt14 Solid Dielectric, Triple Option Reclosers Providing electronic overcurrent protection for single or three phase operation on systems rated through 27kV, 630A or 800A continuous current, 12.5 or 16kA symmetrical

More information

Specif ications. Minimum Surge Arrester Rating, kv

Specif ications. Minimum Surge Arrester Rating, kv &C Fault amer Fuse Limiter Outdoor Distribution ( kv through kv) For Overhead Pole-op ransformers pecif ications Conditions of ale ADAD: eller s standard conditions of sale set forth in Price heet 0 apply.

More information

Cobra-S. Catalog Cobra-S

Cobra-S. Catalog Cobra-S Cobra-S Solid Dielectric, Three Phase Reclosers Providing electronic three phase overcurrent protection for systems rated through 38kV, 800A continuous current, 12.5/16kA symmetrical interrupting Control

More information

Solid Dielectric, Three Phase Reclosers Catalog O-vs18

Solid Dielectric, Three Phase Reclosers Catalog O-vs18 Solid Dielectric, Three Phase Reclosers Providing electronic three phase overcurrent protection for systems rated through 38kV, 800A continuous current, 12.5kA symmetrical interrupting Reliable performance

More information

10DD 10DD-1. Section CAUTION:

10DD 10DD-1. Section CAUTION: POLYMER Electronic Resettable Sectionalizer Protected by U.S. Patents No. 6,593,842; 5,854,582; 5,612,661; 4,935,715; 4,795,996; and other patents pending Section 10DD-1 10DD Warranty - Material Hubbell

More information

Solid Dielectric, Triple Option Reclosers Catalog O-vst14

Solid Dielectric, Triple Option Reclosers Catalog O-vst14 Solid Dielectric, Triple Option Reclosers Providing electronic overcurrent protection for single or three phase operation on systems rated through 38kV, 800A continuous current, 12.5kA symmetrical interrupting

More information

Kearney fuse links. Technical Data General. Effective December 2013 Supersedes November 2009

Kearney fuse links. Technical Data General. Effective December 2013 Supersedes November 2009 Kearney fuse links Supersedes November 2009 General Eaton's Cooper Power Systems Kearney fuse links can be applied to a variety of applications requiring overcurrent protection of distribution systems

More information

PRECISE HIGH VOLTAGE DISTRIBUTION FUSE CUTOUT

PRECISE HIGH VOLTAGE DISTRIBUTION FUSE CUTOUT PRECISE HIGH VOLTAGE DISTRIBUTION FUSE CUTOUT COS 38kV 100A 8kA asym. Type PGC Parallel groove terminal bronze with tin plated NEMA Bracket type B Upper contact copper with silver plated Cap - Cast bronze

More information

TYPE V CENTER BREAK SWITCH

TYPE V CENTER BREAK SWITCH TYPE V CENTER BREAK SWITCH 3-PHASE, GROUP-OPERATED (SUBSTATION AND TRANSMISSION APPLICATIONS) *Available in Copper Horizontal upright, vertical or underhung mounting 15KV through 230KV 600A through 4000A

More information

Figure 1. Non-removable buttonhead Edison Links. TABLE 1 Edison Link Fuse Designs. System Fuse Ampere Rating Type Rating

Figure 1. Non-removable buttonhead Edison Links. TABLE 1 Edison Link Fuse Designs. System Fuse Ampere Rating Type Rating Fusing Equipment Edison Links Electrical Apparatus K-SEC 100 GENERAL Cooper Power Systems Kearney line of fuse links, Edison Links, can be applied to a variety of applications requiring overcurrent protection

More information

Source-Side Fuse/Load-Side Recloser Coordination

Source-Side Fuse/Load-Side Recloser Coordination How to Coordinate ransformer Primary-Side Fuses with Feeder Reclosers Using Coordinaide M he S&C Protection and Coordination Assistant Part I: Conservative Method his is the first in a series of articles

More information

S&C SMD -20 Power Fuses

S&C SMD -20 Power Fuses S&C SMD -20 Power Fuses Outdoor Distribution (14.4 kv through 34.5 kv) SMD-20 Power Fuses offer full-fault-spectrum protection. They detect and interrupt all faults large, medium, and small even down to

More information

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work Section 16435 - SWITCHBOARDS Introduction Part 1 - General Related Work Section 16070 Seismic Anchorage and Restraint Section 16075 Electrical Identification Section 16080 Power Distribution Acceptance

More information

A system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment.

A system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment. General Unit substations shall be 500 kva minimum, 1500 kva maximum unless approved otherwise by the University. For the required configuration of University substations see Standard Electrical Detail

More information

Kearney fuse links. Technical Data General. Effective March 2014 Supersedes December 2013

Kearney fuse links. Technical Data General. Effective March 2014 Supersedes December 2013 Kearney fuse links Supersedes December 2013 General Eaton's Cooper Power Systems Kearney fuse links can be applied to a variety of applications requiring overcurrent protection of distribution systems

More information

Cutouts (Standard, Linkbreak, Loadbreak) and Cutout-Arrester Combinations. Catalog 10A January 2014

Cutouts (Standard, Linkbreak, Loadbreak) and Cutout-Arrester Combinations. Catalog 10A January 2014 10A Type C PORCELAIN Cutouts (Standard, Linkbreak, Loadbreak) and Cutout-Arrester Combinations Catalog 10A Page 1 Type C Cutouts LINKBREAK cutout, pages 8-10 LOADBREAK cutout with Arc-Chute interrupter,

More information

Horizontal Circuit Switchers

Horizontal Circuit Switchers > Transformer Protection > CIRCUIT SWITCHERS C A T A L O G B U L L E T I N General Application Southern States Types CSH and CSH-B Horizontal Circuit Switchers provide an economical, versatile, space saving

More information

Types VSA12, VSA12B, VSA16, VSA20, and VSA20A; three-phase; air-insulated; electronically controlled recloser

Types VSA12, VSA12B, VSA16, VSA20, and VSA20A; three-phase; air-insulated; electronically controlled recloser Reclosers Catalog Data CA280008EN Supersedes 280-45 July 2014 COOPER POWER SERIES Types VSA12, VSA12B, VSA16, VSA20, and ; three-phase; air-insulated; electronically controlled recloser VSA16 recloser

More information

EE 741 Over-voltage and Overcurrent. Spring 2014

EE 741 Over-voltage and Overcurrent. Spring 2014 EE 741 Over-voltage and Overcurrent Protection Spring 2014 Causes of Over-voltages Lightning Capacitor switching Faults (where interruption occurs prior to zero current crossing) Accidental contact with

More information

Specifications. S&C Omni-Rupter Switches Outdoor Distribution (14.4 kv and 25 kv) Conditions of Sale

Specifications. S&C Omni-Rupter Switches Outdoor Distribution (14.4 kv and 25 kv) Conditions of Sale S&C Omni-Rupter Switches Outdoor istribution (14.4 kv and 5 kv) Specifications Conditions of Sale STNR: Seller s standard conditions of sale as set forth in Price Sheet apply. SPECIL TO THIS PROUCT: INCLUSIONS:

More information

SUBSTATION VACUUM CIRCUIT BREAKER (38KV)

SUBSTATION VACUUM CIRCUIT BREAKER (38KV) SUBSTATION VACUUM CIRCUIT BREAKER (38KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products for utilities

More information

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV) SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products

More information

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV) SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products for utilities

More information

Cutouts (Standard, Linkbreak, Loadbreak) and Cutout-Arrester Combinations. Catalog 10A October 2015

Cutouts (Standard, Linkbreak, Loadbreak) and Cutout-Arrester Combinations. Catalog 10A October 2015 10A Type C PORCELAIN Cutouts (Standard, Linkbreak, Loadbreak) and Cutout-Arrester Combinations Catalog 10A Page 1 Type C Cutouts LINKBREAK cutout, pages 8-10 LOADBREAK cutout with Arc-Chute interrupter,

More information

ECET Distribution System Protection. Overcurrent Protection

ECET Distribution System Protection. Overcurrent Protection ECET 4520 Industrial Distribution Systems, Illumination, and the NEC Distribution System Protection Overcurrent Protection One of the most important aspects of distribution system design is system protection.

More information

Cutouts (Standard, Linkbreak, Loadbreak) and Cutout-Arrester Combinations. Catalog 10AA March 2013

Cutouts (Standard, Linkbreak, Loadbreak) and Cutout-Arrester Combinations. Catalog 10AA March 2013 10AA Type C-Polymer Cutouts (Standard, Linkbreak, Loadbreak) and Cutout-Arrester Combinations Catalog 10AA Page 10AA-1 Quality Construction Efficient Current Transfer The Type C-Polymer cutout has an all

More information

Molded Vacuum Reclosers The recloser you want, all in one package. Single- and Three-Phase Molded Vacuum Reclosers, 15 38kV

Molded Vacuum Reclosers The recloser you want, all in one package. Single- and Three-Phase Molded Vacuum Reclosers, 15 38kV The recloser you want, all in one package. Single- and Three-Phase, 15 38kV The need for automated reclosers has never been greater, but many of today s reclosers come with penalties. They weigh too much,

More information

Jumpers & Load Pickup Tools

Jumpers & Load Pickup Tools Jumpers & Load Pickup Tools Catalog 2300 May 2016 Jumpers & Load Pickup Tools 2300 May 2016 Page 2301 All Chance Insulated Jumpers meet ASTM F 2321 Standard Specification. G4758 15kV 5 5 / 8 " G4765 25kV

More information

Sectionalizing. Rick Seeling. Pete Malamen. Introduction Philosophy. Three Phase Reclosers High-Side Protection Specific Applications

Sectionalizing. Rick Seeling. Pete Malamen. Introduction Philosophy. Three Phase Reclosers High-Side Protection Specific Applications Sectionalizing Rick Seeling Introduction Philosophy Pete Malamen Three Phase Reclosers High-Side Protection Specific Applications History Early 1970 s Small Substation Transformers

More information

Joslyn Hi-Voltage. Overhead Reclosers & Switches. In this section...

Joslyn Hi-Voltage. Overhead Reclosers & Switches. In this section... In this section... Joslyn Hi-Voltage Overhead Reclosers & Switches Joslyn Hi-Voltage Overhead Reclosers & Switches TRIMOD Reclosers... H-190 H-210 Disconnect Switches... H-211 H-219 Load Interrupter Attachments...

More information

Metal-Enclosed Switches. Medium Voltage. Medium Voltage Metal-Enclosed Switches Contents

Metal-Enclosed Switches. Medium Voltage. Medium Voltage Metal-Enclosed Switches Contents January 2003 Vol. 1, Ref. No. [1011] -1 Medium Voltage Metal-Enclosed Switches Contents Description Page MVS................................... -2 and Breaker MSB........................ -3 Metal-Enclosed

More information

Horizontal Circuit Switchers

Horizontal Circuit Switchers > Transformer Protection > CIRCUIT SWITCHERS C A T A L O G B U L L E T I N General Application Southern States Types CSH and CSH-B Horizontal Circuit Switchers provide an economical, versatile, space saving

More information

D-73P disconnect and bypass switches

D-73P disconnect and bypass switches Switches atalog Data 008005EN Supersedes pril 2016 OOPER POWER SERIES D-73P disconnect and bypass switches ontents Description Page D-73P disconnect switch....2 D-73P3 bypass switch....5 D-73P-D cutout

More information

Catalog 14A January 2013

Catalog 14A January 2013 Catalog 14A January 2013 Page 1 January 2013 Type AR (Automation-Ready) Switch 14.4kV, 25kV or 34.5kV 900 Amperes Continuous/Interrupt Description The Hubbell unitized Type AR switch is a distribution-level,

More information

Padmount Solid Dielectric Switchgear Catalog

Padmount Solid Dielectric Switchgear Catalog Padmount Solid Dielectric Switchgear Catalog p G&W headquarters in Bolingbrook, IL USA Company Profile Since 1905, G&W Electric has helped energize the world with innovative power system solutions. With

More information

Tolerance-Based Time-Current Coordination

Tolerance-Based Time-Current Coordination S&C IntelliRupter PulseCloser Fault Interrupter Outdoor Distribution (15.5 kv, 27 kv, and 38 kv) Tolerance-Based Time-Current Coordination Table of Contents Section Page Section Page Overview Background....

More information

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 03/05/09 TSEWG TP-11: UFC N BEST PRACTICES

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 03/05/09 TSEWG TP-11: UFC N BEST PRACTICES TSEWG TP-11: UFC 3-500-10N BEST PRACTICES UFC 3-500-10N was developed by NAVFAC and was used as the starting point for the tri-services development of UFC 3-500-10, Design: Electrical Engineering. UFC

More information

Cutouts (Standard, Linkbreak, Loadbreak) and Cutout-Arrester Combinations. Catalog 10AA August 2015

Cutouts (Standard, Linkbreak, Loadbreak) and Cutout-Arrester Combinations. Catalog 10AA August 2015 10AA Type C-POLYMER Cutouts (Standard, Linkbreak, Loadbreak) and Cutout-Arrester Combinations Catalog 10AA Page 10AA-1 Quality Construction Efficient Current Transfer The Type C-Polymer cutout has an all

More information

CATALOG. Joslyn Hi-Voltage Overhead reclosers & switches

CATALOG. Joslyn Hi-Voltage Overhead reclosers & switches CATALOG Joslyn Hi-Voltage Overhead reclosers & switches Thomas & Betts is now ABB Installation Products, but our long legacy of quality products and innovation remains the same. From connectors that help

More information

Technical Specification for Pole Mounted Capacitor Rack

Technical Specification for Pole Mounted Capacitor Rack Technical Specification for Pole Mounted Rack Page 1 1. Scope and Function a) Pole mounted capacitor racks shall be installed on a distribution feed as an economical means of applying capacitor units to

More information

SURGE DURABILITY AND IMPROVED TRANSFORMER PROTECTION

SURGE DURABILITY AND IMPROVED TRANSFORMER PROTECTION Fusing Equipment Tandem ELF Current-Limiting Dropout Fuse Electrical pparatus 240-67 GENERL The Cooper Power Systems Tandem ELF current-limiting fuse is designed for transformer protection. The Tandem

More information

Product Specifications for Aluminum Vertical Break Switches

Product Specifications for Aluminum Vertical Break Switches 1. General a) This specification covers the design, manufacture, and shipment of aluminum vertical break switches, both air-break and load-break configurations, for substation and transmission switching

More information

Installation and Operation

Installation and Operation S&C Three-Shot Type XS Fuse Cutout Outdoor Distribution (4.16 kv through 15 kv) Installation and Operation Table of Contents Section Page Section Page Introduction Qualified Persons... 2 Read this Instruction

More information

JUMPERS & SWITCHING TOOLS

JUMPERS & SWITCHING TOOLS INSULATED JUMPER SETS 368 INSULATED JUMPER SETS FOR 15 KV, 25KV AND 35 KV Used for bypassing work areas when upgrading lines and when making temporary or emergency repairs Continuous-current ratings for

More information

OVERHEAD DISTRIBUTION SWITCHES

OVERHEAD DISTRIBUTION SWITCHES OVERHEAD DISTRIBUTION SWITCHES 0800 442 182 www.transnet.co.nz CONTENTS LineBOSS 15kV - 35kV Sidebreak GOAB Switch - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4 LineBOSS Selection

More information

Copper Vertical Break Switch kv A.

Copper Vertical Break Switch kv A. Bulletin DB-106C05 Type V2-C Copper Vertical Break Switch 7.2-69 kv 600-2000 A. Designed for Simplicity V2-C APPLICATION The Cleaveland/Price V2-C is a three pole, group operated, copper vertical break

More information

Typical Specification

Typical Specification Engineered to Order Built to Last Typical Specification VAULT VRPFI, TWO POSITION, ROTARY PUFFER SWITCHGEAR PART 1- GENERAL 1.1 DESCRIPTION A. The switch shall consist of manually operated load interrupting,

More information

ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position

ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position LET S BE PACIFIC November 0 Volume Number 5 ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position Federal Pacific has the capability to engineer, fabricate and assemble

More information

Specification Guide. for RMAX. Direct Replacement. AC Low Voltage. Power Circuit Breakers

Specification Guide. for RMAX. Direct Replacement. AC Low Voltage. Power Circuit Breakers Specification Guide for RMAX Direct Replacement AC Low Voltage Power Circuit Breakers Table of Contents 1.0 General Work Scope...3 2.0 Standards... 3 3.0 Supplier Qualifications... 3 4.0 Mechanical and

More information

Aluminum Vertical Break Switch kv A.

Aluminum Vertical Break Switch kv A. Bulletin DB-C106AA05 Type V2-CA Aluminum Vertical Break Switch 7.2-69 kv 600-2000 A. Designed for Simplicity V2-CA APPLICATION The Cleaveland/Price V2-CA is a three pole, group operated, aluminum vertical

More information

Figure 1. Two and Three-phase MagneX.

Figure 1. Two and Three-phase MagneX. Fusing Equipment Two- & Three-Phase MagneX Interrupter Electrical Apparatus 240-33 GENERAL The Cooper Power Systems MagneX Interrupter is an overcurrent protective device that protects distribution transformers

More information

Copper Double Break Switch

Copper Double Break Switch Bulletin DB-104DB09 Type DB-C Copper Double Break Switch 7.2 kv - 69 kv 600 A. - 2000 A. 14000 Rt. 993, Trafford, PA 15085 (724) 864-4177 FAX (724) 864-9040 E-mail: sales@cleavelandprice.com Type DB-C

More information

Medium Voltage Metal-Enclosed Switches

Medium Voltage Metal-Enclosed Switches Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Medium Voltage Switch MVS Product Description............................................. 2 Application Description..........................................

More information

Power & High Voltage Joslyn Hi-Voltage Overhead Reclosers & Switches H-220. Series HVI Hi-Velocity Interrupter Attachment

Power & High Voltage Joslyn Hi-Voltage Overhead Reclosers & Switches H-220. Series HVI Hi-Velocity Interrupter Attachment Use load interrupter attachments to enable loop sectionalizing, line dropping, load breaking and transformer-magnetizing current interruption. Increase the capability of your disconnect switches by adding

More information

شركة كهرباء محافظة القدس المساهمة المحدودة

شركة كهرباء محافظة القدس المساهمة المحدودة Our Ref: Date: Messrs. Dear Sir, Tender 22/2017 (re-bidding) 11& 33Kv Fuse Cutouts and Links You are kindly requested to bid for supply and delivery (DDP) for the medium voltage overhead line accessories

More information

GROUP D. Switch & Protective device.

GROUP D. Switch & Protective device. GROUP D Switch & Protective device PYUNGIL Bldg., 147-10, Gwanyang 2-dong, Dongan-gu, Anyang-si, Gyeonggi-do, 431-808, Korea Tel : 82-31-420-0~3 FAX : 82-31-424-7300 www.pyungil.com Pole-mounted SF Insulated

More information

Elastimold. Cable Accessories. Underground Distribution Switchgear. Molded Vacuum Switches and Fault Interrupters

Elastimold. Cable Accessories. Underground Distribution Switchgear. Molded Vacuum Switches and Fault Interrupters Underground Distribution Switchgear Molded Vacuum Switches and Fault Interrupters MVS Molded Vaccum Switches Spring-energy, load-switching devices that make, carry and interrupt load currents through 600

More information

Eaton s Cooper Power Systems catalog Medium-voltage vacuum circuit breakers

Eaton s Cooper Power Systems catalog Medium-voltage vacuum circuit breakers Eaton s Cooper Power Systems catalog Medium-voltage vacuum circuit breakers Medium-voltage vacuum circuit breakers Catalog information Medium-voltage vacuum circuit breakers catalog Technical Data Effective

More information