Memshield - ACB Ratings & Specifications

Size: px
Start display at page:

Download "Memshield - ACB Ratings & Specifications"

Transcription

1 Memshield Memshield - ACB Ratings & Specifications Rating and specifications Current rating, A List No Number of poles RATED CURRENT (A) [In] IEC, BS, VDE, AS Neutral pole ampere frame (A) RATED PRIMARY CURRENT OF OVERCURRENT TRIP DEVICES [ICT] (A) (For general feeder circuit use) RATED CURRENT OF OVERCURRENT TRIP DEVICES [Io] (A) (For generator protection use) [Io] is the generator rated current RATED IMPULSE WITHSTAND VOLTAGE [Uimp] (kv) AC RATED INSULATION VOLTAGE [Ui] (V) 0 RATED OPERATIONAL VOLTAGE [Ue] (V) 8 AC RATED BREAK. CAP. (ka r.m.s.)/make CAP. (ka peak) IEC 47- with Inst. 60V BS EN [Ics] =00% [Icu] 600V CEI EN V up to 45V 60V 600V up to 500V DC RATED BREAKING CAPACITY DC 3 50V DNV with Inst. 660V 600V 480V up to 480V LR with Inst. 660V 600V with Inst. 480V up to 480V AB with Inst. 660V 600V 480V up to 480V GL with Inst. 660V 600V 480V up to 480V BV with Inst. 660V 600V 500V up to 500V SHORT TIME WITHSTAND sec CURRENT [ICW] (ka) 3 sec Latching current [ka] UTILIZATION CATEGORY OPERATION TIMES Total breaking time (s) Spring charging time (s) max. Closing time (s) max. OUTLINE DIMENSIONS (mm) Fixed type a b b c a 0 c d d Draw-out type a b b c a 0 c d d Weight (kg) draw-out type MACB06 MACB MACB6 MACB0 MACB5 MACB3 MACB Io Io Io Io 30 5 Io Io Io <Io 60 30<Io <Io <Io <Io <Io <Io <Io <Io <Io <Io <Io Io Io <Io Io Io /46. 50/05 50/05 50/05 50/05 50/05 50/05 30/63 50/05 50/05 50/05 50/05 65/43 65/43 35/ /43 65/43 65/43 65/43 85/87 85/87 35/ /43 65/43 65/43 65/43 85/87 85/87 /46. 50/05 50/05 50/05 50/05 50/05 50/05 30/63 50/05 50/05 50/05 50/05 65/43 65/43 35/ /05 50/05 50/05 65/43 80/76 80/76 40/40 40/40 40/40 40/40 40/40 40/40 40/40 35/ /43 65/43 65/43 65/43 /5 85/87./ /8 35./8 45.3/ / / /6 50.6/6 50./6 66./68 37/0. 7.6/ / / /0.5 /5. 35/8. 50/4.6 50/4. 50/ /6 65/57. 35/77. 65/45 65/45 65/45 65/45 85/03 35/77. 50/ 50/ 50/ 50/ 65/45 /5.4 35/8 35/8 35/8 45/06 45/06 30/76 50/6 50/6 50/6 50/6 65/68 35/0. 65/0.5 65/0.5 65/0.5 65/0.5 65/0.5 35/ / / / / /0.6 35/ /.3 50/.5 50/6. 50/ / B B B B B B B NOTES: :Values in open air at 40 C (45 C for marine applications). 3 :DC rating is for special application. For further details, contact MEM Ltd. (500V) 5 :Approval pending. 6 :Full rated neutral pole available on request :For vertical terminals, d = mm. :Rated operational voltage depends on applied standard: 60V according to IEC47- :Only applied to 3 pole ACBs. :Rated insulation voltage depends on applied standard: 000VAC according to IEC47- :The application of I.T. systems at this voltage is not permissible RATINGS UPTO 6300A ARE AVAILABLE ON REQUEST - FOR FURTHER DETAILS CONTACT MEM LTD. (500V) 8

2 Memshield - ACB Ratings & Specifications Memshield Internal resistance, reactance, power consumption LIST NO: MACB06 MACB MACB6 MACB0 MACB5 MACB3 MACB40 DC Internal (mw) Draw-out type resistance (per pole) Fixed type Reactance (mw) Draw-out type (per pole) Fixed type AC Power(W) Draw-out type consumption Fixed Type Note: The power consumption shown above is measured on the basis of internal AC resistance for 3 poles De-rating BASED AMBIENT TEMP LIST NO: MACB06 MACB MACB6 MACB0 MACB5 MACB3 MACB40 STANDARDS ( C) IEC47-40 (Standard ambient temperature) BS EN VDE 0660 Part AS Dielectric withstand voltage Accessories CIRCUIT 50/60 HZ Main circuit Between terminals all terminals to earth AC3500V minute Auxiliary switch all terminals to earth AC500V minute Undervoltage trip AC Rating terminals - 0 to earth AC500V minute terminals - to earth AC500V minute DC Rating all terminals to earth AC500V minute Shunt trip all terminals to earth AC000V minute Overcurrent trip all terminals to earth AC000V minute Motor charging closing AC00-50V AC000V minute all terminals to earth control circuit DC00-0V DC4-48V all terminals to earth AC500V minute Other Accessories all terminals to earth AC000V minute Note: The values shown above are those measured on new parts and cannot be applied to components' terminals in the ACB.

3 Memshield Memshield - ACB Types of Mounting Draw-out type Fixed type The draw-out type consists of a circuit breaker and a draw-out cradle. The circuit breaker can be removed from the cradle. There are four circuit breaker positions CONNECTED, TEST, ISOLATED and REMOVE. The switchboard panel door can be kept closed in CONNECTED, TEST and ISOLATED positions ( shut-in three positions ). Connected position Indication CONN. Control circuits Main circuits This consists only of the circuit breaker with fixings to allow it to be mounted permanently inside the switchboard. Main circuit terminals Standard terminal arrangements are either horizontal or vertical type. (Horizontal and vertical types are available for MACB06, MACB, MACB6 and MACB0). Front connections are also available. Please refer to the table below and specify the required connection method at time of ordering. Terminal Arrangement Breaker Type Of Horizontal Vertical Front List No Mounting Terminals Terminals Connections Both main and control circuits are connected for normal service. Test position Indication TEST The main circuit is isolated and the control circuits are connected. This position permits operation tests with the switchboard panel shut. 3 Isolated position Indication ISOLATED MACB06 MACB MACB6 MACB0 MACB5 MACB3 MACB40 Draw-out Fixed Draw-out Fixed Draw-out Fixed Draw-out Fixed Draw-out Fixed Draw-out Fixed Draw-out Fixed Both main and control circuits are isolated. The switchboard panel door can be shut. Earth circuit still connected. Note:- : Standard : Optional : No or not available 4 Remove position The ACB is completely removed from the cradle. Horizontal Terminals Vertical Terminals 0

4 Memshield - ACB Accessories Memshield Accessories are factory fitted and should be specified when ordering. An order form is shown on P48. Door interlock The door interlock prevents the switchboard door from being opened when the breaker is CLOSED. The door can be opened only when the breaker is OPEN. It is also fitted with a lock release. Installation of the door interlock requires simple drilling of the switchboard panel door. Hinge can only be fitted on the RIGHT HAND SIDE as shown in the opposite diagram ø0 (Front view) ø7 50 Panel door 70 Dust plate 50 (Plan view) Breaker mounting hole Hinge A (min.) Breaker A B (3P) B (4P) MACB-06,,6,0, MACB MACB-3, A B (min.) (min.) Panel door Door interlock 0 5 Lifting Truck Breaker mounting position *50 max ACB front panel Lifter List no D W H Weight (kg) AWT-B Dimensions (mm) AWT-B The loader is a variable size type to suit all frame sizes of Memshield ACBs (3 and 4 pole). Panel door Size change is readily done by adjusting the loader. Maximum safe working load (SWL) : 50kg Maximum lifting height : 850mm Minimum passage width : 800mm 300 mm Note: * If distance exceeds 50mm, contact MEM Ltd. (500V) D H W ARC GAS BARRIER The Arc Gas Barrier reduces the air gap requirement between the top of the ACB and other electrical equipment or earthed metal. See outline dimension drawings for details. The barrier can be installed with the cradle, for the draw-out type breaker. The arc gas barrier is a heat proof, flame-resistant insulating plate. CARRYING ROLLERS The carrying rollers are necessary when the lifting truck is used. The rollers can also be used for moving the breaker on the floor. METAL-CLAD TYPE The metal-clad type consists of a draw-out breaker, housed in a steel enclosure. A load centre is readily constructed by simply placing metal-clad units one upon another.

5 Memshield Memshield - ACB Accessories OPEN PADLOCK Permits the ACB to be padlocked in the OPEN position, this is fitted as standard. Max. 3 padlocks (hasp size ø6 to ø8mm) can be fitted (not supplied). CARRYING HANDLE For use with hooks, ropes etc when lifting the breaker. PUSH-BUTTON PADLOCK COVER Prevents unauthorised operation of the manual CLOSE and OPEN buttons. Padlock hasp size ø6 to ø8mm (not supplied). Dustplate Provides a dust proof seal between the ACB front panel and the cut-out on the switchboard panel when the breaker is located between the CONNECTED and ISOLATED position. Special environment specification Cold Climate Treatment Specify this treatment when the breaker is used in cold areas. Specification: 40 C storage temperature -5 C operating temperature (no condensation or freezing). Anti-Corrosion Treatment Anti-corrosion treatment permits the use of the breaker in a corrosive atmosphere. Contact MEM Ltd. (500V) for further information. Tropicalization (Fungus and Moisture Treatment) Specify this treatment when the breaker is used under high temperature and high humidity conditions: Up to 60 C ambient temperature and up to 5% relative humidity (no condensation). Door flange Earthing device Covers the panel cut-out on the switchboard. The panel cut-out should be greater than the standard size shown in the outline dimensions section of 50mm x 70mm. We would recommend to use a cut out of 60mm x 80mm. There is a growing demand in L.V. distribution for greater protection against electric shock particularly during periods when maintenance work is being carried out on the main busbars or cables. A safe and economical way to meet this requirement is to apply system earthing via the normal service breaker. Earthing devices (optional) on Memshield ACBs comprises; Permanent parts which are factory fitted and are mounted on the ACB chassis and body to enable the ACB to receive the portable parts. Portable parts are supplied in loose kit form and are fitted on to the ACB body by the customer's engineer. This converts the ACB from a normal service device to an earthing device. For further information contact MEM Ltd. (500V) for details.

6 Memshield - ACB Accessories Memshield Key interlock The key interlock is a system of interlocking between breakers, each fitted with a lock-inopen type key lock *The key must be inserted to release the lock before the breaker can be closed * The breaker must be opened and locked in the open position before the key can be removed Utilising the lock-in-open type key lock feature and using keys less than the number of the key-locked breakers, an effective and reliable interlock system is formed. can be supplied with a cylinder lock fitted or with a provision for Castell lock. In the latter case, use Lock Type FS (angular movement 65 o clockwise to trap key) Castell Locks Ltd. EXAMPLE: Prevention of parallel connection of two sources with a bus tie breaker. SOURCE SOURCE Breaker Breaker SOURCE SOURCE SOURCE SOURCE Breaker Breaker Breaker Breaker Bus-tie Breaker 3 Bus-tie Breaker 3 Bus-tie Breaker 3 Loads Loads Loads Loads Loads Loads Breaker 3 cannot be closed Breaker cannot be closed Breaker cannot be closed IP cover Mechanical interlock Mounted on the switchboard panel door to provide IP54 degree of protection as defined in IEC5. Horizontal type Wire Vertical type Contact MEM Ltd.(500V) for the details of vertical type with 3 ACBs. P C P C P C Rod N N N 60 P Select the required pitch from the table below: P N *Min 575mm If you require to drawout the ACB with AOR-B to the isolated position, an additional depth frame is required with the IP54 cover. Please specify at the time of ordering. Interlock Pitch of ACB P(mm) between (PC line to PC line) MACB06 MACB MACB6 MACB0 MACB5 MACB3 MACB40 * Minimum pitch (575mm) is possible if the proper insulating distance is obtained. For larger pitch (max. 00mm) contact MEM Ltd.(500V) for details. 3

7 Memshield Memshield - ACB Accessories Auxiliary switch assembly Close-Open cycle counter Auxiliary switches electrically indicate the open-closed status of the breaker. For Draw-out Type, the auxiliary switches operate in the CONNECTED and TEST positions only. However, where marine classification society s rules apply, they operate in the CONNECTED position only. Options include; A B, 5A 5B, 0A 0B. This device counts and indicates the number of close-open cycles. Key lock The key lock is available in two types: lock-in-open type to lock the breaker in the OPEN position, or lock-in-closed type to lock the breaker in the CLOSED position. Auxiliary Switch Ratings Rated Voltage Resistive Lamp **Inductive Motor AC5-500V 7A 5A 7A 7A DC30V 7A 5A 7A 7A DC5V 7A 5A 5A 5A DC50V 7A 5A.5A.5A Note: The minimum current limit is 0mA at 4V. DC ** (AC cos ø over 0.4 DC L/R below 0.007) Trip indication switch Operation of the trip indication switch varies depending on which device trips the breaker and whether or not the closing springs are charged. Rating Load Resistive Lamp Inductive Motor AC5-50V 7A.5A 6A A DC30V 6A 3A 6A 3A DC5V 0.6A 0.A 0.6A 0.A DC50V 0.3A 0.05A 0.3A 0.05A Note: * Optional. The trip indication switch can be made inoperative for a manual operation. Please specify at time of ordering. Breaker tripped by Overcurrent trip (OCR) Shunt trip Undervoltage trip * Manual opening by PUSH-TO-OPEN button Remote opening Undervoltage Condition Operation of trip indication switch Closing springs charged Switch is ON for 40ms, then reset to Switch remains ON until undervoltage condition is restored to normal. Switch remains ON until PUSH-TO- OPEN button is released Closing springs discharged Switch remains ON until closing springs are charged Switch remains ON until closing springs are charged after undervoltage condition has restored to normal Switch remains ON until closing springs are charged after PUSH-TO-OPEN button is released Automatic changeover controller An automatic mains/generator changeover system can be achieved by utilizing this device with a pair of mechanically interlocked ACBs, each fitted with a motor operator, shunt trip and auxiliary switch. If one or more phases fail on mains supply, the device will trip the mains circuit breaker and start the generator. Once up and running (85% of Ue) the generator circuit breaker will close. If mains voltage should return the generator circuit breaker will trip, mains circuit breaker will close and the generator will continue to run on 'No load' for a preset cool down period. Contact MEM Ltd. (500V) for further details. Specifications (Ue) System voltage level 0 ~ 440 V AC (Um) Mains fail voltage 75 ~ 5% Ue (Tf) Mains fail delay 0.5 ~ 8.0 sec. (Tr) Mains return delay 5 ~ 00 sec. (Tg) Generator cool down time 30 ~ 00 sec. Dimensions (W) 5 mm, (H) 43 mm, (D) 38 mm Power supply 4V DC 5% Maximum ripple An optional UPS backup supply is available for this unit. It contains rechargeable batteries which can supply enough power to energise a shunt trip and keep the unit powered for up to hour. Refer to page 45 for details. 4

8 Memshield - ACB Accessories for Draw-out Type Memshield Main circuit safety shutters Position switches When the breaker is drawn out the shutters automatically conceal and insulate the main circuit disconnect contacts on the cradle. Each shutter can be padlocked in the closed position. For safety during inspection and maintenance, up to three padlocks may be applied to each of the top and bottom shutters (padlocks not supplied). The top shutter and bottom shutter can be opened or closed independently by manual operation. Maintenance can be done in the open position. (The mechanism is released automatically by inserting the circuit breaker). The top shutter and bottom shutter can both be moved individually. The Position switches operate when the breaker is in CONNECTED position, TEST position, ISOLATED position or in the INSERT position, to electrically indicate the breaker position. These switches are divided into units () and () as shown below, and one switch can be selected from each unit. A max of units can be fitted on ACBs MACB06~0, 3 Pole. A max of 4 units fitted on any other ACB size. UNITS () UNITS () () CONNECTED () ISOLATED position position, indicator indicator switches switches ( max) ( max) () TEST position, () INSERT position, indicator switches indicator switches ( max) ( max) (3) CONNECTED (3) ISOLATED and and TEST position. INSERT position, indicator switches indicator switches (one each) (one each) TEST JUMPER The test jumper allows open-close tests on the removed breaker (The standard length of the cable is 5m) Position switch, operating sequence Connected position indicator switch Test position indicator switch Isolated position indicator switch Insert position indicator switch (Isolated) (Test) a-contacts "ON" Position switch ratings a-contacts "ON" (Connected) a-contacts "ON" a-contacts "ON" Load Resistive Lamp Inductive Motor AC50V 0A.5A 6A A DC30V 6A 3A 6A 3A DC5V 0.6A 0.A 0.6A 0.A DC50V 0.3A 0.05A 0.3A 0.05A MAL-INSERTION PREVENTION DEVICE Interchangeability exists within the Memshield range of. Because of this feature there is a possibility for a breaker of a different specification being placed into the cradle. This is effectively prevented by the use of the Mal-insertion Device. CONTROL CIRCUIT SAFETY SHUTTER The control circuit disconnect contacts have independent shutters for increased safety. They are not padlockable. BREAKER FIXING BLOCKS These provide reinforcement for the breaker mounting where vibration occurs. They are always fitted when the breaker is subject to marine classification society rules. DRAW-OUT POSITION PADLOCK The breaker can be padlocked in three positions, CONNECTED, TEST and ISOLATED. The padlocking device is fitted as standard. Padlocks not supplied (hasp diameter 8 or 6mm). 5

9 Memshield Memshield ACB - Spring Charged Operation Manual charging type Rating of motor charging type The closing springs are manually charged by pumping the charging handle. When the PUSH TO CLOSE button is pressed, the closing springs are released, quickly closing the breaker. (An electrical latch release can be provided for remote closing applications. The closing springs must be charged manually prior to remote close operation). Motor charging type The motor automatically charges the closing springs. The latch release coil is energised by a remote push button, releasing the springs and quickly closing the circuit breaker. With the breaker closed, the motor automatically starts to charge the springs again for the next closing operation. Manual charging is also possible. Separate charging and closing circuits are available on request. Breaker Rated voltage Min & max Inrush Steady-State Charging Closing List No operation current current time command voltage (peak value) (AC, A, current r.m.s. value) (peak value) MACB06 MACB MACB6 MACB0 MACB5 (V) (V) (A) (A) (S) (A) AC (40V) (40V) AC (0V) (0V) AC (0V) (0V) DC (0V) (0V) DC (5V) (5V) DC (00V) (00V) DC (48V) (48V) DC (4V) (4V) AC (40V) (40V) AC (0V) (0V) AC (0V) (0V) DC (0V) (0V) DC (5V) (5V) DC (00V) (00V) DC (48V) (48V) DC (4V) (4V) MACB3 MACB40 AC (40V) (40V) AC (0V) (0V) AC (0V) (0V) DC (0V) (0V) DC (5V) (5V) DC (00V) (00V) DC (48V) (48V) DC (4V) (4V) Motor charging and closing operation CHARGING OF CLOSING SPRINGS When the closing springs are DISCHARGED, the spring charged switch in series with the motor is closed. Control voltage is applied to terminals and and the motor starts to charge the springs. When the closing springs are fully charged, the spring charged switch in series with the motor opens and cuts the supply to the motor. *CLOSING THE ACB *ANTI-PUMPING FUNCTION 3 * Refers to standard circuit 3 When the springs are charged, the spring charged ON switch in series with the LRC is closed. Apply voltage across terminals 3 and, through PB (close). The latch release coil (LRC) is energized and the closing springs are released to close the ACB. Open the spring charged ON SW. by releasing the closing spring and cuts the supply to the LRC by AUX SW. b-contact. Once the closing springs have been released, the spring discharged switch is closed. If a close signal is continually applied across terminals and 3, the holding relay (HC) is energized and self holds when the HC a-contact closes. The HC b-contact opens, cutting the supply to the LRC. ACB can not re-close without opening the PB (close). 6

10 Memshield ACB - Spring Charged Operation Memshield Motor circuit Source Ry Ry etc For spring charge indication Interlock switch PB (Close) Source for motor Ry Ry etc For spring charge indication Interlock switch PB (Close) Source for L.R.C R AXT-C Spring charged switch C C HC R AXT-C Spring charged switch C C HC M B 04 B AMT-C 05 R HC D D D A 4 M AMT-C B B R HC D D D A 4 AXT-C 0 Spring charged switch ON LRC AXT-BA 03 Aux.Sw. 4 AXT-C Spring charged switch AXT-C 0 Spring charged switch ON LRC AXT-BA 03 4 Aux.Sw. AXT-C Spring charged switch Standard circuit 4 Split supply circuit 4 Power transformer (external) The maximum rated control power voltage applicable to the motor charging type is 50V AC. If a higher voltage than this value is applied, a power transformer is required. MEM Ltd. (500V) can offer the following transformers. (please specify on order). AUTOMATIC CLOSING SPRING RELEASE Rated Transformer Control Voltage Type Cap. Volt ratio AC350-35V TSE -30M 300VA 380 / 0V AC40-470V TSE -30M 300VA 450 / 0V SPRING CHARGED SWITCH JIG FOR SLOW-CLOSING The closing springs are automatically released when the breaker is drawn out from the TEST position to the ISOLATED position. This switch electrically indicates the charged condition of the closing springs. Ratings Resistive Motor AC5V-50V 7A 4A DC5V-50V 0.4A 0.05A Jigs can be supplied with the breaker for inspection and maintenance purposes (they are required when changing the arcing contacts of the ACB). Slow-closing operation can be made by the charging handle when the slow-close jigs are installed. 7

11 4 Memshield Memshield ACB - Electrical Tripping Devices Shunt trip (SHT) The shunt trip device allows the ACB to be remotely opened. Instantaneous operating and continuously rated versions are available. (Contact MEM Ltd. (500V) for details of continuous rated type). Memshield ACB can be fitted with shunt trip and UVT. Shunt Trip Ratings (instantaneous operating type) Shunt Trip Rated Voltage Operational Voltage Peak Excitation Opening Time Current (max) (V) (V) (A) (ms) AVT- AC (450V) 30 AC (380V) 30 AC (0V) 30 AC (0V) 30 DC (0V) 30 DC (00V) 30 DC (48V) 30 DC (4V) 30 Capacitor trip Combined with the shunt trip device, the capacitance trip device enables the ACB to be remotely tripped after a voltage (ac) drop due to a power failure, short circuit, etc, provided that the remote trip operation occurs within 30 seconds after the voltage drop. Type AQT-A AQT-B Rated Voltage AC 00-0V 0~40V Operational Voltage 70 to 0% 70-0% Rated frequency 50/60Hz 50/60Hz Rated Voltage of Shunt Trip used DC0-5V DC50~30 Power Consumption (Inrush) 00VA 00VA Outline Dimensions (mm) SWITCH RED NEON 4.0 ON 3 INPUT CAPACITOR CHARGE OUTPUT CAPACITOR TRIP DEVICE 4 - ø4.5 CSK mtg. holes FRONT VIEW SIDE VIEW Control Circuit Power Source 8 SHT ACB AUX SW 7 PB (OPEN) or OCR etc ON R C NL Power Switch Di Di R Di 8

12 Memshield Memshield Overcurrent Protection Relay (AORB) Multi-function Protection Device Protection functions Adjustable Long Time-delay LTD. The LTD function protects against overload. Select HOT or COLD start. The HOT start characteristic takes account of accumulated heating caused by previous loads. Adjustable Short Time-delay STD The STD function is intended to give discrimination with other devices during short circuits. The STD characteristic is user-selectable between 'definite timedelay' and 'I t ramp' characteristics. (HOT start characteristics are not The 'definite time-delay' is suitable for available on M type) co-ordination with other definite time delay devices. The 'ramp' characteristic allows closer co-ordination with thermal-magnetic MCCBs. When the STD is set to 'I t ON', the 'ramp' characteristic is in operation up to 000% of the base Pick-up current of LTD current for L & M (general feeder protection) type OCRs and up to 500% for S (generator protection) type OCRs. time Above these levels the definite time-delay Fluctuating current load profile comes into operation. The STD is set to 'I t ' at the time of manufacture. current tripping time tripping time time Conventional electronic relay without thermal memory time Microprocessor based relay with thermal memory. Simulates true heating effect of conductor. 3 Adjustable Instantaneous Trip INST. The INST. function protects against short circuits, without a built-in time-delay, It is user-selectable between 'INST.' or 'MCR'. The MCR (Making Current Release) function operates only during the closing cycle of the ACB and is disabled once the ACB has fully closed. 4 Adjustable Pre-Trip Alarm PRE-TRIP The PRE-TRIP alarm gives warning (via a voltage free contact) of impending trip due to overload. On L and M type OCRs, it has a definite time delay and on S type OCRs, it has an inverse time delay. PRE-TRIP signal automatically resets when the current drops below pick-up current (IP). 5 Adjustable Ground Fault GFT The GFT pick-up current can be set between 0% to 40% of the CT rated primary current and the definite time delay between 80 to 000ms. 6 Neutral Phase Protection N-phase Available on 3 & 4 pole ACBs for use on 3-phase, 4 wire systems. The N-phase current setting is 0% to 00% of the CT rated primary current. Please specify at time of ordering. 7 OCR Sealing Facility Unauthorised access to the OCR adjustment dials can be prevented by use of an optional sealing cover. This is placed over the dials and secured by two screws. The screw heads have holes drilled in them for a sealing wire to be fitted. (Wire and seal are not provided). NON setting and FAIL-SAFE Each of the overcurrent protection functions (LTD, STD, INST/MCR) can be disabled by setting the respective pick up dial to 'NON' position. (For example, the INST setting is often set to 'NON' to improve selectivity levels.) If the STD and INST functions are both set to 'NON' (thereby removing all short-circuit protection), the in-built FAIL-SAFE function will trip the ACB on fault currents exceeding 6 times the base current [I0], instantaneously. 3 If the STD and MCR functions are both set to 'NON', the in-built FAIL-SAFE function will trip the ACB on fault currents exceeding 0 times the base current, [I0], (on L and M type OCRs) and 5 times the base current, [I0] (on S type OCRs). Trip time is the STD time setting. Base current [Io] The base current, [I0], is used as the reference for deciding the current and time settings of the LTD, STD, INST. and PRE-TRIP functions. On AOR-BL and AOR-BM type OCRs, it can be set by means of a dial on the front to 50, 63, 80 or 00%, of the rated CT primary current (ICT). On AOR-BS, it is factory set according to the full load current of the generator (which should be specified at time of order). Base current selection procedures are as follows: (Refer to tables on P.4, 6, 8 for available values of [ICT] and [I0]. For General Feeder Circuits For Generator Protection Calculate the maximum full load current, [ILOAD], through the ACB. Check the generator full load current, [IGEN]. Select the required rated primary current, The base current, [I0], will be equal to [ICT], of the OCR, (note that [ILOAD] must [IGEN] and should be used as a reference not be greater than [ICT]. for the pick-up current settings of the 3 Decide what the base current, [I0] should other protection characteristics. be and use this as a reference for the LTD, 3 Select the OCR with the protection and STD, INST and PRE-TRIP current settings. indication functions required for the 4 Select the OCR with the protection and particular application. indication functions required for the particular application. Note: The ground fault pick-up current, [IG] is a factor of [ICT], not [I0]. 0

Section Contents. 1. Introduction 2-5. Salient features, internal & general appearance of Drawout ACB

Section Contents. 1. Introduction 2-5. Salient features, internal & general appearance of Drawout ACB 1 Section Contents PAGES 1. Introduction 2-5 Salient features, internal & general appearance of Drawout ACB 2. Ratings & Specifications 6-9 Free air & enclosed thermal current ratings for AC & DC applications

More information

Specification for 70mm pole pitch Air circuit breaker up to 1600 A

Specification for 70mm pole pitch Air circuit breaker up to 1600 A Specification for 70mm pole pitch Air circuit breaker up to 1600 A Protective device for low voltage electrical installation Last update :2011-07-08-1 - Table of contents: 1 General...3 2 Compliance with

More information

INSTRUCTION MANUAL FOR AIR CIRCUIT BREAKERS (With Draw-out Cradle and Type AGR-11B,21B,22B,31B Overcurrent Protective Device)

INSTRUCTION MANUAL FOR AIR CIRCUIT BREAKERS (With Draw-out Cradle and Type AGR-11B,21B,22B,31B Overcurrent Protective Device) INSTRUCTION MANUAL FOR AIR CIRCUIT BREAKERS (With Draw-out Cradle and Type AGR-11B,21B,22B,31B Overcurrent Protective Device) Types: AR208S AR212S AR216S AR220S AR325S AR332S AR440S AR440SB AR212H AR216H

More information

Rated Impulse withstand voltage U imp Main circuit Between terminals, AC3500V for 1 minute 12kV terminal group to earth Control circuits

Rated Impulse withstand voltage U imp Main circuit Between terminals, AC3500V for 1 minute 12kV terminal group to earth Control circuits 7 Technical Data Dielectric strength Circuit Withstand voltage (at 50/60 Hz) Rated Impulse withstand voltage U imp Main circuit Between terminals, AC3500V for 1 minute 12kV terminal group to earth Control

More information

Low voltage moulded case circuit breaker EB2

Low voltage moulded case circuit breaker EB2 Low voltage moulded case circuit breaker EB2 Product series description unit condition Model-type Number of poles Nominal current ratings Electrical characteristics Rated operational voltage Rated insulation

More information

C 1. SPECTRONIC SP - Air circuit breakers. Summary. C2. General characteristics. C3. Fixed circuit breaker. C4. Withdrawable circuit breakers

C 1. SPECTRONIC SP - Air circuit breakers. Summary. C2. General characteristics. C3. Fixed circuit breaker. C4. Withdrawable circuit breakers SPETRONI SP - Air circuit breakers Summary 2. General characteristics 3. Fixed circuit breaker 4. Withdrawable circuit breakers 5. haracteristics 6. RV23: protection and control unit 6. RV+ : protection

More information

INSTRUCTION MANUAL FOR AIR CIRCUIT BREAKERS (With Draw-out Cradle and Type AGR-11B,21B,22B,31B Overcurrent Protective Device)

INSTRUCTION MANUAL FOR AIR CIRCUIT BREAKERS (With Draw-out Cradle and Type AGR-11B,21B,22B,31B Overcurrent Protective Device) INSTRUCTION MANUAL FOR AIR CIRCUIT BREAKERS (With Draw-out Cradle and Type AGR-11B,21B,22B,31B Overcurrent Protective Device) Types: AR650S, AR663S, AR663H Notice Be sure to read this manual before installing,

More information

(Example) In case of DC24 to 48V, it is operating time for DC24V.

(Example) In case of DC24 to 48V, it is operating time for DC24V. 7 9 8 Closing coil (CC) The closing coil is a device to close the breaker by remote control. An interlock to prevent pumping is provided electrically. CC circuit diagram Rated voltage (Applicable voltage

More information

INSTRUCTION MANUAL FOR AIR CIRCUIT BREAKERS (With Draw-out Cradle and Type AGR-11B Overcurrent Protective Device)

INSTRUCTION MANUAL FOR AIR CIRCUIT BREAKERS (With Draw-out Cradle and Type AGR-11B Overcurrent Protective Device) INSTRUCTION MANUAL FOR AIR CIRCUIT BREAKERS (With Draw-out Cradle and Type AGR-11B Overcurrent Protective Device) Types: KA208S KA212S KA216S KA220S KA325S KA332S KA440S KA212H KA216H KA220H KA316H KA320H

More information

INSTRUCTION MANUAL FOR AIR CIRCUIT BREAKERS (With Draw-out Cradle and Type AGR-31B Overcurrent Protective Device)

INSTRUCTION MANUAL FOR AIR CIRCUIT BREAKERS (With Draw-out Cradle and Type AGR-31B Overcurrent Protective Device) INSTRUCTION MANUAL FOR AIR CIRCUIT BREAKERS (With Draw-out Cradle and Type AGR-31B Overcurrent Protective Device) Types: AR208S AR212S AR216S AR220S AR325S AR332S AR440S AR440SB AR212H AR216H AR220H AR316H

More information

DPX moulded case circuit breakers

DPX moulded case circuit breakers BREAKING AND PROTECTION DEVICES 10 / 2011 DPX moulded case circuit breakers DPX moulded case circuit breakers offer optimum solutions for the protection requirements of commercial and industrial installations.

More information

Air Circuit Breaker Instruction Manual

Air Circuit Breaker Instruction Manual Innovators in Protection Technology Air Circuit Breaker Instruction Manual AGR-31B Overcurrent Protection Device 06-M55EC INSTRUCTION MANUAL FOR AIR CIRCUIT BREAKERS (With Draw-out Cradle and Type AGR-31B

More information

DMX 3 -I 2500 switch disconnectors

DMX 3 -I 2500 switch disconnectors 8704 LIMOGES Cedex Telephone : 0 0 87 87 Fax : 0 0 88 88 DMX 3 200 circuit breakers DMX 3 -I 200 switch disconnectors References: 0 28 20 / 21 / 22 / 23 / 24 / 2 / 2 / 30 / 31/ 32/ 33/ 34 / 3 / 3 / 40

More information

GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector

GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector Catalog 0500CT9702R409 2009 Class 525/580 CONTENTS Description............................................. Page General Characteristics...................................

More information

High Breaking Capacity

High Breaking Capacity Air Circuit Breaker Small Light Weight High Breaking Capacity High Ability Digital APR Safety Convenience HiAN 2000 ~ 3200AF HiAN 6 ~ 1600AF CONTENTS HiAN Type 04 - Feature 06 - Rating 08 - Selection of

More information

ME 07 Air Circuit Breakers. ME 07 - Air Circuit Breakers. Low Voltage. Low Voltage. Low Voltage

ME 07 Air Circuit Breakers. ME 07 - Air Circuit Breakers. Low Voltage. Low Voltage. Low Voltage Low Voltage ME 07 - Air Circuit Breakers ME 07 Air Circuit Breakers Low Voltage AEG Niederspannungstechnik GmbH & Co KG Berliner Platz 2-6 D-24534 Neumünster (Germany) Tel. +49/43211-0 Fax +49/43211-144

More information

Page. Circuit-Breakers M4 2 for motor protection. Auxiliary contacts 3 Signalling switch Auxiliary releases

Page. Circuit-Breakers M4 2 for motor protection. Auxiliary contacts 3 Signalling switch Auxiliary releases Circuit Breakers M4 Page Circuit-Breakers M4 2 for motor protection Auxiliary contacts 3 Signalling switch Auxiliary releases Insulated 3-pole busbar system 4 Terminal block DIN-rail adapters 5 Busbar

More information

Air Circuit Breaker Instruction Manual

Air Circuit Breaker Instruction Manual Innovators in Protection Technology Air Circuit Breaker Instruction Manual AGR-21B/22B Protection Relays 06-M55EB INSTRUCTION MANUAL FOR AIR CIRCUIT BREAKERS (With Draw-out Cradle and Type AGR-21B, 22B

More information

3 - Protection components Motor circuit-breakers

3 - Protection components Motor circuit-breakers Contents 0 - Protection components Motor circuit-breakers protection components for the motor protection Thermal-magnetic motor circuit-breakers Selection guide..............................................page

More information

INSTRUCTION MANUAL FOR AIR CIRCUIT BREAKERS (With Draw-out Cradle and Type AGR-11B Overcurrent Protective Device)

INSTRUCTION MANUAL FOR AIR CIRCUIT BREAKERS (With Draw-out Cradle and Type AGR-11B Overcurrent Protective Device) INSTRUCTION MANUAL FOR AIR CIRCUIT BREAKERS (With Draw-out Cradle and Type AGR-11B Overcurrent Protective Device) Types: AR650S,AR663S,AR663H Notice Be sure to read this manual before installing, operating,

More information

5. OVERCURRENT RELEASE (OCR)

5. OVERCURRENT RELEASE (OCR) 5. OVERCURRENT RELEASE (OCR) Options available for the type AR ACBs include a highly reliable, multi-functional overcurrent release (OCR) with a built-in 8- bit microprocessor. This OCR is supplied with

More information

01 Spectra Plus - Introduction

01 Spectra Plus - Introduction 01 Spectra Plus - Introduction Standard features Conforming to IS13947-2/EN60947 2 Compact dimensions Available in 3P & 4P High performance microprocessor protection release Wide overload setting from

More information

Air Circuit Breakers DH series General information

Air Circuit Breakers DH series General information General information Air circuit breakers Description The newly designed air circuit breakers have excellent features as follows: The height and depth dimensions are identical in all sizes up to 3200AF

More information

GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Standard Features

GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Standard Features Standard Features Table : Standard Features GV2ME GV2P GV3P GV7RE/GV7RS 0. to 32 A Up to 20 hp @ 460 V 0 SCCR @ 480 V Push Button Operator 0. to 30 A Up to 5 hp @ 460 V 50 SCCR @ 480 V Rotary Handle Operator

More information

INSTRUCTION MANUAL FOR AIR CIRCUIT BREAKERS (With Draw-out Cradle and Type AGR-31B Overcurrent Protective Device)

INSTRUCTION MANUAL FOR AIR CIRCUIT BREAKERS (With Draw-out Cradle and Type AGR-31B Overcurrent Protective Device) INSTRUCTION MANUAL FOR AIR CIRCUIT BREAKERS (With Draw-out Cradle and Type AGR-31B Overcurrent Protective Device) Types: AR650S,AR663S,AR663H Notice Be sure to read this manual before installing, operating,

More information

cor Long Run Experience

cor Long Run Experience Moulded Case Circuit Breakers Moulded Case Circuit Breakers 16-1250A cor Long Run Experience cor Breaking capacity (according to IEC 947-2 at 415V) Icu 100 D160L D250L D400L D630L 70 60 DH800 50 35 30

More information

(p. 47) (p. 155) (p. 155)

(p. 47) (p. 155) (p. 155) 0 286 56 + 0 288 02 (p. 47) 0 286 74 + 0 288 02 (p. 155) 0 287 56 + 0 288 02 (p. 155) Dimensions see e-catalogue Elecical characteristics p. 162 Automatic air circuit breakers must be equipped with eleconic

More information

DPX 1600 Electronic release

DPX 1600 Electronic release 87045 LIMOGES Cedex Phone :+33 05 55 06 87 87 Fax :+33 05 55 06 88 88 DPX 1600 CONTENTS PAGES 1. USE 1 2. RANGE 1 3. DIMENSIONS 1 3. DIMENSIONS (NEXT) 2 4. OVERVIEW 2 5. CONNECTION 2 6. ELECTRICAL AND

More information

New DMX 3. Efficient protection up to A AIR CIRCUIT BREAKERS PRODUCT GUIDE

New DMX 3. Efficient protection up to A AIR CIRCUIT BREAKERS PRODUCT GUIDE New DMX 3 Efficient protection up to 4 000 A AIR CIRCUIT BREAKERS PRODUCT GUIDE NEW DMX 3 ACBs UP TO 4 000 A EFFICIENT PROTECTION AND CONTROL FOR ALL TYPE OF BUILDINGS 02 Electrical panel equipped with

More information

Low voltage moulded case circuit breaker EB2

Low voltage moulded case circuit breaker EB2 Low voltage moulded case circuit breaker EB2 Product series description unit condition Model-type Number of poles Nominal current ratings Electrical characteristics Rated operational voltage Rated insulation

More information

Moulded case circuit breakers

Moulded case circuit breakers Moulded case circuit breakers CONTENT Range 4 Protection Releases 5 Salient Features 8 Accessories, 4 Technical data 2 Time Current Characteristics 5 Overall Dimensions 7 SN4 SN3 SN2 SN 3 RANGE Moulded

More information

6300A 15 Optibreak B1 & B2 Optibreak B1 & B2 50/60 Hz Ue Icu [v] [ka] 415 65 690 40 4h 4i 1. Open / close Indication 2. Charge and Discharge Indicator 3. Release the reset button 4. Laser Nameplate

More information

DATA SHEET FOR 1 TYPE COMPARTMENTALISED / NON - COMPARTMENTALISED. ( a ) CIRCUIT BREAKER FEEDERS FULLY DRAWOUT / NON DRAWOUT

DATA SHEET FOR 1 TYPE COMPARTMENTALISED / NON - COMPARTMENTALISED. ( a ) CIRCUIT BREAKER FEEDERS FULLY DRAWOUT / NON DRAWOUT 44LK-500/E.04/002A/A4 PROJECT NO 44LK-500 CHKD. BY VDV VDV A CLIMATIC CONDITIONS THIS DATA SHEET IS APPLICABLE FOR IN UTILITY BOILER PACKAGE DESIGN AMBIENT TEMPERATURE 45 C 2 ALTITUDE ( ABOVE MSL ) 6.7

More information

Motor Protection Circuit Breakers

Motor Protection Circuit Breakers Motor Protection Circuit Breakers About us Larsen & Toubro is a technologydriven USD 9.8 billion company that infuses engineering with imagination. The Company offers a wide range of advanced solutions

More information

VOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS

VOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS VOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS A. 11 KV SWITCHGEAR 1.0 SWITCHGEAR ASSEMBLY 1.1 Make : 1.2 Type : 1.3 Reference Standard : 1.4 Voltage (Nom./Max.) KV : 1.5 Phase, Frequency No,Hz.

More information

Characteristics of LV circuit breakers Releases, tripping curves, and limitation

Characteristics of LV circuit breakers Releases, tripping curves, and limitation Characteristics of LV circuit breakers Releases, tripping curves, and limitation Make, Withstand & Break Currents A circuit breaker is both a circuit-breaking device that can make, withstand and break

More information

DPX 630 Electronic release

DPX 630 Electronic release 87045 LIMOGES Cedex Phone :+33 05 55 06 87 87 Fax :+33 05 55 06 88 88 DPX 630 CONTENTS PAGES 1. USE 1 2. RANGE 1 3. DIMENSIONS 1 4. OVERVIEW 2 5. CONNECTION 2 6. ELECTRICAL AND MECHANICAL CHARACTERISTICS

More information

5. OVERCURRENT RELEASE (OCR)

5. OVERCURRENT RELEASE (OCR) 5. OVERCURRENT RELEASE (OCR) Options available for the type AR ACBs include a highly reliable, multi-functional overcurrent release (OCR) with a built-in 8- bit microprocessor. This OCR is supplied with

More information

Terasaki (Europe) Ltd

Terasaki (Europe) Ltd Terasaki (Europe) Ltd Terasaki Europe Ltd was established in 97 and is located near Glasgow, Scotland U.K. From head office at our 7,00 square metre facility, Terasaki Europe controls an International

More information

Circuit-Breakers M4 166 for motor protection. Auxiliary contacts 167 Signalling switch Auxiliary releases

Circuit-Breakers M4 166 for motor protection. Auxiliary contacts 167 Signalling switch Auxiliary releases Index Page Circuit-Breakers M4 166 for motor protection Auxiliary contacts 167 Signalling switch Auxiliary releases Insulated 3-pole busbar system 168 Terminal block DIN-rail adapters 169 Busbar adapters

More information

Protection components

Protection components Presentation, characteristics Presentation 1 2 3 motor circuit-breakers are 3-pole thermal-magnetic circuit-breakers standards IEC 60947-2 and IEC 60947-4-1. Connection These circuit-breakers are designed

More information

15-I73E CAT REF.

15-I73E CAT REF. & www.terasaki.co.jp 5-I7E CAT REF. TABLE OF CONTENTS General - Introduction - General - Selection Chart - Ratings and Specifications - Air Circuit Breakers for DC50V-00V - Moulded Case Circuit Breakers

More information

Circuit breakers and switch-disconnectors NT06 to NT16 and NW08 to NW63

Circuit breakers and switch-disconnectors NT06 to NT16 and NW08 to NW63 Functions and characteristics Circuit breakers and switch-disconnectors NT06 to NT16 and NW08 to NW63 NT and NW selection criteria Masterpact NT Masterpact NW NT06, NT08, NT10, NT12, NT16 NT06, NT08, NT10

More information

Innovators in Protection Technology Moulded Case Circuit Breaker Instruction Manual

Innovators in Protection Technology Moulded Case Circuit Breaker Instruction Manual Innovators in Protection Technology Moulded Case Circuit Breaker Instruction Manual 11-M61E TABLE OF CONTENTS HANDLING & MAINTENANCE Storage 1 Transport 1 STANDARD ENVIRONMENT 1 INSTALLATION AND CONNECTION

More information

FUSOMAT Visible breaking and tripping fuse switches from 250 to 1250 A

FUSOMAT Visible breaking and tripping fuse switches from 250 to 1250 A Fuse protection The solution for > Motor load break > Protection of industrial cabinet > Electrical distribution fusom_063_b_1_cat Strong points > Tripping upon overload > High breaking capacity > Improved

More information

Air Circuit Breakers. U-Series. Instruction Manual. Type covered in this manual. Notice

Air Circuit Breakers. U-Series. Instruction Manual. Type covered in this manual. Notice U-Series Air Circuit Breakers Instruction Manual Type covered in this manual UAN Type : UAN06, UAN08, UAN10, UAN12, UAN16, UAN20, UAN25, UAN32, UAN40, UAN50 UAS Type : UAS06, UAS08, UAS10, UAS12, UAS16,

More information

Selection and Application Guide Supplement. WL UL Pole Circuit Breakers. usa.siemens.com/wlbreaker

Selection and Application Guide Supplement. WL UL Pole Circuit Breakers. usa.siemens.com/wlbreaker Selection and Application Guide Supplement WL UL1066 4-Pole Circuit Breakers usa.siemens.com/wlbreaker WL Power Circuit Breaker Table of Contents Ratings for UL 1066 (ANSI C37) Circuit Breakers Frame size

More information

Essential Loads also use stand by generator systems mostly in process industries as they relate to high restarting times or high down times.

Essential Loads also use stand by generator systems mostly in process industries as they relate to high restarting times or high down times. The need for continuous power supply and its reliability has increased rapidly over the years, especially in all those areas where uninterrupted power supply is a must. Modern systems are power dependent.

More information

Modular contactors and relays

Modular contactors and relays pages /4 to / pages /8 and /9 pages /10 and /11 pages /12 and /13 Presentation and standards Presentation Designed for use in modular panels and enclosures, these contactors feature : i Easy installation

More information

Innovators in Protection Technology ACB. Double Breaker

Innovators in Protection Technology ACB. Double Breaker Innovators in Protection Technology ACB Double Breaker World Class Air Terasaki s TemPower2 A.C.B is the result of an intensive market research program which took into account the requirements of switchboard

More information

AF series contactors (9 2650)

AF series contactors (9 2650) R E32527 R E39322 contactors General purpose and motor applications AF series contactors (9 2650) 3- & 4-pole contactors General purpose up to 2700 A Motor applications up to 50 hp, 900 kw NEMA Sizes 00

More information

MULTI 9 System Catalog IEC Rated C60N/H/L Circuit Breakers

MULTI 9 System Catalog IEC Rated C60N/H/L Circuit Breakers IEC Rated C60N/H/L Circuit Breakers Standard Features Fast Closing Allows increased withstand to the high inrush currents of some loads Trip-free mechanism: Contacts cannot be held in the on position when

More information

TeSys contactors. Use in category DC-1 (resistive loads; time constant L/R y 1 ms) Rated operational current Ie. to be wired in series

TeSys contactors. Use in category DC-1 (resistive loads; time constant L/R y 1 ms) Rated operational current Ie. to be wired in series Selection 3-pole shockproof contactors FG d.c. supply Selection guide for utilisation categories DC-1 to DC-5 Use in category DC-1 (resistive loads; time constant L/R y 1 ms) Rated operational current

More information

Overview of Low voltage equipment - Moulded-case & Air circuit-breakers

Overview of Low voltage equipment - Moulded-case & Air circuit-breakers Overview of Low voltage equipment - Moulded-case & Air circuit-breakers Moulded-case circuit-breakers for distribution (1) R16 and R20 Icu = 16 ka @ 220/230 V (2) All the versions with Icu = 35 ka are

More information

FUJI Magnetic Contactors and Motor Starters

FUJI Magnetic Contactors and Motor Starters FUJI Magnetic Contactors and Motor Starters Technical Information AEH28a CONTENTS Chapter Contactors and Starters - International standards... 4-2 Ratings and specifications... 8-3 Performance and characteristics...

More information

SECTION MICROPROCESSOR TRIP UNITS FOR LV CIRCUIT BREAKERS. This section is organized as indicated below. Select desired Paragraphs.

SECTION MICROPROCESSOR TRIP UNITS FOR LV CIRCUIT BREAKERS. This section is organized as indicated below. Select desired Paragraphs. SECTION 16904 MICROPROCESSOR TRIP UNITS FOR LV CIRCUIT BREAKERS PART 2 PRODUCTS 01 MANUFACTURERS A. B. C. Eaton * * The listing of specific manufacturers above does not imply acceptance of their products

More information

14-I73E CAT REF.

14-I73E CAT REF. & www.terasaki.co.jp -I7E CAT REF. TABLE OF CONTENTS General - Introduction - General - Selection Chart - Ratings and Specifications - Air Circuit Breakers for DC50V-00V - Moulded Case Circuit Breakers

More information

INSTRUCTION MANUAL FOR AR-E AIR CIRCUIT BREAKERS (Fixed type and Type AGR-12B Overcurrent Protective Device)

INSTRUCTION MANUAL FOR AR-E AIR CIRCUIT BREAKERS (Fixed type and Type AGR-12B Overcurrent Protective Device) INSTRUCTION MANUAL FOR AR-E AIR CIRCUIT BREAKERS (Fixed type and Type AGR-12B Overcurrent Protective Device) Types: AR206E AR208E AR210E AR212E AR216E Notice Be sure to read this manual before installing,

More information

MCCB Accessories to suit AF

MCCB Accessories to suit AF MCCB s MCCB Accessories to suit 125-630AF Accessory fitting combinations INTERNAL General purpose types Micro-switch types Auxiliary Heavy duty types Bridge -contact types Auxiliary Shunt UVT Internal

More information

Power protection solutions

Power protection solutions Power protection solutions DMX A.C.Bs UP TO 4000 A In high power installations, the role of the main enclosure is to: - House protection devices and provide for their connection - Provide management and

More information

Innovators in Protection Technology. TemBreak. Total Protection, Complete Control. Catalogue No I20E

Innovators in Protection Technology. TemBreak. Total Protection, Complete Control. Catalogue No I20E Innovators in Protection Technology TemBreak Total Protection, Complete Control Catalogue No. 05 - I0E Terasaki (Europe) Ltd Terasaki Europe Ltd was established in 97 and is located near Glasgow, Scotland

More information

Index. Manual Motor Starters 1. Auxiliary Contact Blocks 1. Trip Alarm Auxiliary 1. Switch. Shunt Release 1. Under-voltage Release 2.

Index. Manual Motor Starters 1. Auxiliary Contact Blocks 1. Trip Alarm Auxiliary 1. Switch. Shunt Release 1. Under-voltage Release 2. Index Index Page Manual Motor Starters 1 Auxiliary Contact Blocks 1 Trip Alarm Auxiliary 1 Switch Shunt Release 1 Under-voltage Release 2 Accessories 2 Busbar Connectors 2 Enclosures 2 Leistung, kw C mv

More information

KD LV Motor Protection Relay

KD LV Motor Protection Relay 1. Protection Features KD LV Motor Protection Relay Overload (for both cyclic and sustained overload conditions) Locked rotor by vectorial stall Running stall / jam Single phasing / Unbalance Earth leakage

More information

PIX-H Metal-clad switchgear up to 17.5kV

PIX-H Metal-clad switchgear up to 17.5kV AIR INSULATED SWITCHGEAR PIX-H Metal-clad switchgear up to 17.5kV for high rated applications Technical Specifications AREVA T&D Summary - Technical description... 3 - Standards... 6 - PIX in detail...

More information

MEDIUM VOLTAGE CE-B36 METAL CLAD SWITCHBOARDS. CE - B36 - C - en - REV

MEDIUM VOLTAGE CE-B36 METAL CLAD SWITCHBOARDS. CE - B36 - C - en - REV CE - B36 - C - en - REV.00 2011.9 EDIU VOLTAGE EDIU VOLTAGE APPLICATION CE-B etal Clad switchboards are designed for use in public and industrial distribution system up to 36kV for the operation and protection

More information

3VU13, 3VU16 Circuit-Breakers

3VU13, 3VU16 Circuit-Breakers 3VU3, 3VU6 Circuit-Breakers Description The 3VU3, 3VU6 circuit-breakers are compact circuit-breakers for currents up to 80 A which operate according to the current limiting principle. The devices are used

More information

Motor Protection Circuit Breakers 3VU13 and 3VU16

Motor Protection Circuit Breakers 3VU13 and 3VU16 Motor Protection Circuit Breakers 3VU13 and 3VU16 3VU13/3VU16 is suitable for use in fuseless motor feeders upto 11KW/22KW (25A/63A) respectively. 3VU motor protection circuit breakers are used for protection

More information

AF series contactors (9 2650)

AF series contactors (9 2650) R E32527 R E39322 contactors General purpose and motor applications AF series contactors (9 2650) 3- & 4-pole contactors General purpose up to 2700 A Motor applications up to 50 hp, 900 kw NEMA Sizes 00

More information

Prisma ipm Switchboard Air Circuit Breaker (ACB) Moulded-case Circuit Breaker (MCCB) Contactor Power meter

Prisma ipm Switchboard Air Circuit Breaker (ACB) Moulded-case Circuit Breaker (MCCB) Contactor Power meter 3 Prisma ipm Switchboard Air Circuit Breaker (ACB) Moulded-case Circuit Breaker (MCCB) Contactor Power meter The easy choice for quality, value, and peace of mind Schneider Electric makes it an easy choice

More information

TECHNICAL SPECIFICATIONS OF PCC PANEL

TECHNICAL SPECIFICATIONS OF PCC PANEL S. no. TECHNICAL SPECIFICATIONS OF PCC PANEL Technical parameters AS PER SPECIFICATION CONSTRUCTIONAL FEATURES TO BE FILLED BY THE SUPPLIER 1 Manufacturer s name To be specified by supplier 2 Rated operational

More information

OSS - TN, TBN Type. Information to Order. Features. External View ATS(60~600A) OSS P- A B C D. Rated Current. D Operating Voltage

OSS - TN, TBN Type. Information to Order. Features. External View ATS(60~600A) OSS P- A B C D. Rated Current. D Operating Voltage Information to Order A Rated Current 06 1 60A 100A 2 4 400A 6 600A B Type TN : TN-Type TBN : TBN-Type C Number of Poles 2 : 2P 3 : 3P 4 : 4P OSS - 6 - - P- A B C D D Operating Voltage A1 : AC 110V A2 :

More information

SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Brochure

SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Brochure 2017 SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Brochure SafeGear Motor Control Center Arc resistant Metal-Clad construction Brochure Table of Contents 1. Description 1 1 2. SafeGear

More information

Approved Standards. Motor Contactor. Main contactor. Accessoires. 21 Motor Contactor J7KN

Approved Standards. Motor Contactor. Main contactor. Accessoires. 21 Motor Contactor J7KN Motor Contactor Main contactor AC & DC operated Integrated auxiliary contacts Screw fixing and snap fitting (35 mm DIN rail) up to 45 kw Range from 4 to 110 kw (AC 3, 380/415V) Finger proof ( VBG 4) Accessoires

More information

MEDIUM VOLTAGE CE-B METAL CLAD SWITCHBOARDS. CE-B-C-en-REV

MEDIUM VOLTAGE CE-B METAL CLAD SWITCHBOARDS. CE-B-C-en-REV CE--C-en-REV.04 2016.1 MEDIUM VOLTAGE MEDIUM VOLTAGE APPLICATION CE- Metal Clad switchboards family are designed for use in public and industrial distribution system up to 40,5kV for the operation and

More information

MOULDED CASE CIRCUIT BREAKERS BC160N

MOULDED CASE CIRCUIT BREAKERS BC160N D MOULDED CASE CIRCUIT BREAKERS BC160N D BC160N COMMERCIAL INFORMATION Circuit breakers...d4 Switch-disconnectors...D5 Connecting sets......d6 Mounting sets......d6 Switches...D7 Shunt trips...d7 Undervoltage

More information

The need for continuous power supply and its reliability has increased rapidly over the years, especially in all those areas where uninterrupted

The need for continuous power supply and its reliability has increased rapidly over the years, especially in all those areas where uninterrupted 110 The need for continuous power supply and its reliability has increased rapidly over the years, especially in all those areas where uninterrupted power supply is a must. Modern systems are power dependent.

More information

18-I73E CAT REF.

18-I73E CAT REF. & www.terasaki.co.jp 1-I73E CAT REF. TABLE OF CONTENTS General 1-1 Introduction 1- General 1-3 Selection Chart 1- Ratings and Specifications -1 Air Circuit Breakers for DC350V-00V - Moulded Case Circuit

More information

MEDIUM VOLTAGE CE-B METAL CLAD SWITCHBOARDS. CE - B - C - en - REV

MEDIUM VOLTAGE CE-B METAL CLAD SWITCHBOARDS. CE - B - C - en - REV MEDIUM VOLTAGE MEDIUM VOLTAGE APPLICATION CE-B Metal Clad switchboards are designed for use in public and industrial distribution system up to 24kV for the operation and protection of lines, generators,

More information

DPX Thermal magnetic and trip-free switches DPX 3 -I 160

DPX Thermal magnetic and trip-free switches DPX 3 -I 160 87045 LIMOGES Cedex Phone :+33 05 55 06 87 87 Fax :+33 05 55 06 88 88 DPX 3 160 CONTENTS PAGES 1. USE 1 2. RANGE 1 3. DIMENSIONS 1 4. OVERVIEW 2 5. ELECTRICAL AND MECHANICAL CHARACTERISTICS 3 6. CONFORMITY

More information

Latch for Contactors 4-pole see page 36. Ratings Rated Aux. Contacts Type Coil voltage 2) AC2 Current Built-in Additional 24 24V= DC 5

Latch for Contactors 4-pole see page 36. Ratings Rated Aux. Contacts Type Coil voltage 2) AC2 Current Built-in Additional 24 24V= DC 5 3-pole DC Operated Ratings Rated Aux. Contacts Type Coil voltage 1) AC2 Current Built-in Additional 24 24V= DC 5 AC3 see 48 60V= DC 6 380V AC1 page 34 110 110V= DC 7 400V 660V 220 220V= DC 8 415V 690V

More information

DPX Thermal magnetic and trip-free switches DPX 3 -I 630

DPX Thermal magnetic and trip-free switches DPX 3 -I 630 87045 LIMOGES Cedex Phone :+33 05 55 06 87 87 Fax :+33 05 55 06 88 88 DPX 3 630 CONTENTS PAGES 1. USE 1 2. RANGE 1 3. DIMENSIONS 1 4. OVERVIEW 2 5. ELECTRICAL AND MECHANICAL CHARACTERISTICS 2 6. CONFORMITY

More information

Masterpact NW Circuit breakers and switch-disconnectors from 800 to 6300 A

Masterpact NW Circuit breakers and switch-disconnectors from 800 to 6300 A Low voltage electrical distribution Masterpact NW Circuit breakers and switch-disconnectors from 800 to 6300 A User manual 09/2009 User manual for circuit breakers and switch-disconnectors Masterpact

More information

SECTION MOTOR CONTROL

SECTION MOTOR CONTROL SECTION 26 24 19 MOTOR CONTROL PART 1 - GENERAL 1.1 SECTION INCLUDES A. Manual motor starters B. Magnetic motor starters C. Combination magnetic motor starters D. Solid-state reduced voltage motor starters

More information

Molded Case Circuit Breaker

Molded Case Circuit Breaker & The Ultimate Safety Breaker Molded Case Circuit Breaker www.terasaki.co.jp Catalogue No. 13!5E ! Safety Notice Carefully read instruction manual to ensure proper installation, connection, operation,

More information

PowerPact M-, P- and R-Frame, and Compact NS630b NS3200 Circuit Breakers

PowerPact M-, P- and R-Frame, and Compact NS630b NS3200 Circuit Breakers PowerPact M-, P- and R-Frame, and Compact NS630b NS3200 Circuit Breakers Catalog 0612CT0101 R02/14 2014 Class 0612 CONTENTS Description............................................. Page General Information..........................................

More information

15 16 MCCBs for Power Distribution Technical Specification Frame 100A 250A 250A 400A 400A 630A 800 / 1000 / 1250 Type C DN0-100 D DN1-250 N DN2-250 D N S H DN3B-400 DN3-400 D N D N S V DN3-630 DN4-1250

More information

Introduction. Standard Features. GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Introduction

Introduction. Standard Features. GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Introduction Introduction Introduction Schneider Electric offers a complete line of products for the manual control and protection of motors. This catalog covers those devices designed to meet IEC standards for protection

More information

Wall mounted switchgear

Wall mounted switchgear Contents Safepact 2... pages /2 to / Enclosed MCCBs 6 to 60A... page /2 Enclosed switch disconnectors 100 to 60A... page / Earth leakage.... page /4 Auxiliaries and accessories... page /5 Enclosed Interpact...page

More information

Breaking and protection devices

Breaking and protection devices Power guide: A complete set of technical documentation Breaking and protection devices 01 Sustainable development 08 Protection against external disturbances 02 Power balance and choice of power supply

More information

Innovators in Protection Technology. TemBreak. Total Protection, Complete Control. Catalogue No I20EJ

Innovators in Protection Technology. TemBreak. Total Protection, Complete Control. Catalogue No I20EJ Innovators in Protection Technology TemBreak Total Protection, Complete Control Catalogue No. 0 - IEJ Mission Statement. Terasaki aims to be the best supplier of circuit breakers and associated equipment

More information

Power Break II Switchboard

Power Break II Switchboard Power Break II Switchboard Now available with PowerBreak II Circuit Breakers through 4000A GE s Power Break II Switchboard is now available with the new Power Break II Insulated Case Circuit Breaker (800A

More information

Low Voltage Air Circuit Breakers 630AF~6300AF 15A

Low Voltage Air Circuit Breakers 630AF~6300AF 15A Low Voltage Air Circuit Breakers 6AF~60AF A Mitsubishi Presents the WS Series, Satisfied with the High Demands of the st Century Global Market. Best-Solution Various line-up and high flexibility High-Performance

More information

ATyS. 63 to 3200 A. Functions. Conformity to standards. General characteristics. Changeover switches. Functions

ATyS. 63 to 3200 A. Functions. Conformity to standards. General characteristics. Changeover switches. Functions to 00 A Accessories Enclosed Characteristics M e atysm_007_a cat M s atysm_0_a cat products are and 4pole switches remotely controlled by volt free contacts ( ) or automatic transfer switches ( ). They

More information

DPX 630 Thermal magnetic and trip-free switches DPX-I 630

DPX 630 Thermal magnetic and trip-free switches DPX-I 630 87045 LIMOGES Cedex Phone :+33 05 55 06 87 87 Fax :+33 05 55 06 88 88 DPX 630 CONTENTS PAGES 1. USE 1 2. RANGE 1 3. DIMENSIONS 1 4. OVERVIEW 2 5. CONNECTION 2 6. ELECTRICAL AND MECHANICAL CHARACTERISTICS

More information

1 Phase electronic contactor (SC 1)

1 Phase electronic contactor (SC 1) 1 Phase electronic contactor (SC 1) - Rated operational voltage up to 600VAC 50/60 Hz - Rated operational current up to 15/30A/50/63A AC-1 - Control voltage from or - Compact modular design 22.5, 45, or

More information

AF40... AF96 3-pole contactors Technical data

AF40... AF96 3-pole contactors Technical data Main pole - Utilization characteristics according to IEC Standards IEC 60947- / 60947-4- and EN 60947- / 60947-4- Rated operational voltage Ue max. 690 V Rated frequency (without derating) 50 / 60 Hz Conventional

More information

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION Medium Voltage Standby non-paralleling Control 1. GENERAL GUIDE FORM SPECIFICATION A. The requirements of the contract, Division 1, and part 16 apply to work in this section. 1.01 SECTIONS INCLUDE A. Medium

More information

Horizontal Circuit Switchers

Horizontal Circuit Switchers > Transformer Protection > CIRCUIT SWITCHERS C A T A L O G B U L L E T I N General Application Southern States Types CSH and CSH-B Horizontal Circuit Switchers provide an economical, versatile, space saving

More information

A system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment.

A system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment. General Unit substations shall be 500 kva minimum, 1500 kva maximum unless approved otherwise by the University. For the required configuration of University substations see Standard Electrical Detail

More information

Critical Power Switchboards. Selection and Application Guide