Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION

Size: px
Start display at page:

Download "Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION"

Transcription

1 Medium Voltage Standby non-paralleling Control 1. GENERAL GUIDE FORM SPECIFICATION A. The requirements of the contract, Division 1, and part 16 apply to work in this section SECTIONS INCLUDE A. Medium Voltage 5KV and 15KV Metal-clad switchgear 1.02 RELATED SECTIONS 1.03 REFERENCES The medium voltage metal-clad switchgear and protection devices in this specification are designed and manufactured according to the following standards. A. ANSI C37.06 Switchgear AC High-voltage circuit breakers rated on a symmetrical current basis. B. ANSI C39.1 Electrical analog indicating instruments C. ANSI/IEEE C37.04, Rating structure for AC High-voltage circuit breakers rated on a symmetrical current basis. D. ANSI/IEEE C , Metal-clad and station type cubical switchgear E. ANSI/IEEE C57.13, Instrument transformers F. ANSI/IEEE C37.90, Standards for relays and relay systems associated with electrical power apparatus. G. NEMA SG 2, High Voltage fuse H. NEMA SG 4, Alternating current high voltage circuit breaker I. NEMA SG 5, Power switchgear assemblies 1.04 DEFINITIONS 1.05 SYSTEM DESCRIPTION A. [Indoor][Outdoor][protective aisle][common aisle] metal-clad automatic transfer switchgear intended for use on [5kv][15kv], 3 phase 3 wire. B. Metal-clad automatic transfer switchgear and breakers rated for [250][350][500][750]mva C. Enclosures and circuit breakers shall have a basic impulse rating of [60] [90] kv. control switchgear shall include Breakers, metering, and relays and shall be Factory tested. I

2 1.06 SUBMITTALS A. Manufacturer shall provide copies of the following documents to owner for review and evaluation with general requirements of Division 1 and Division 16: 1. Product data on specified product. 2. Shop drawings on specified product 3. Data sheets on all major components 1.07 PRODUCT RECORD DOCUMENTS A. Record drawings shall be provided the following information 1. Short circuit rating of bus and breakers 2. Outline dimension drawings 3. Device location schedule 4. Schematics 5. Point to Point wiring diagrams 6. Field interconnection drawing 1.08 OPERATION AND MAINTENANCE DRAWINGS A. Manufacturer shall provide copies of installation, operation and maintenance procedures to owner in accordance with general requirements QUALITY ASSURANCE A. Manufacturer shall have specialized in the manufacturing and assembly of like gear For a minimum of last [10] years. B. Manufacturer must be U.L. listed II

3 PART 2 PRODUCTS 2.01 MANUFACTURERS A. Custom Controls Inc. products has been used for the basis of this design. Other manufacturers products of equivalent quality, dimensions and operating features may be acceptable, at the engineers discretion, If they comply totally with all requirements specified in the contract documents 2.02 MANUFACTURED ASSEMBLIES A. Furnish individually mounted rear accessible Medium voltage metal-clad switchgear to provide Automatic transfer switch and close transition transfer controls COMPONENTS A. ENCLOSURE 1 - Switchgear shall consist of breaker and auxiliary units, as indicated I drawings, assembled to form a rigid, self-supporting, metal-enclosed structure. Outdoor metal-clad switchgear shall be enclosed in a weatherproof enclosure and shall include suitable weatherproof access doors, doors with provision for padlocking; protected ventilation openings as required; interior lighting, utility outlets with protective devices; and equipment heaters with protective devices. In each unit, major primary circuit parts (breaker, buses, transformers) shall be completely enclosed by grounded metal barriers, including a front barrier as part of the circuit breaker, 2. Switchgear units shall be arranged as shown on attached drawings. 3. For rigidity during fault conditions all connections to roll-out potential transformer trays and control power transformer trays shall be rigid bus bars insulated to full voltage rating of switchgear assembly. 4. Circuit breaker compartments shall be designed to house [5] [15] KV removable-element circuit breakers. Stationary primary disconnect contacts shall be silver-plated copper. Grounded metal safety shutters shall isolate all primary connections in compartment when breaker is withdrawn from connected position. 5. Furnish nameplates for each device as indicated in drawings. Nameplates shall be white letters on black background. There shall be a master nameplate that indicates equipment ratings, manufacturer's name, shop order number and general information.> B. MAIN BUS 1. The main bus shall be tin plated copper and rated as indicated in drawings. Bus bars shall have a continuous current rating based on temperature rise and documented by design tests. All joints will be tin plated with at least 2 bolts per joint. Bus bars will be braced to withstand magnetic stresses developed by currents equal to main power circuit breaker close, carry, and interrupt ratings. Access to bus bars shall be through removable front panels. Bus bars shall have fluidized bed epoxy flame retardant and non-hydroscopic insulation with a continuous current rating. III

4 C. GROUND BUS 1. A ground bus 1/4 by 2 inch copper shall extend throughout assembly with connections to each breaker grounding contact and cable compartment ground terminal. Joints shall be made up as indicated in drawings. Station ground connection points shall be located in each end section. D. CIRCUIT BREAKERS 1. Circuit breakers shall be rated for 1200A. Circuit breakers shall be interchangeable. Circuit breakers shall be operated by an electrically charged, mechanically and electrically trip-free, stored-energy spring. A [handle] shall be used to manually charge the spring for slow closing of contacts for inspection or adjustment. 2. Circuit breakers shall be equipped with secondary disconnecting contacts which shall automatically engage in the connected position. 3. Each breaker compartment shall have a breaker rack-out device. Using rack-out device, a breaker will be self aligning and will be held rigidly in the operating position. In the disconnect position, breaker shall be easily removable from compartment. Breaker racking shall be accomplished with door closed and latched. Insert handle through a hole in front door to operate rack-out device. 4. An indicating tape shall show breaker position when racking breakers in or out of their connected positions. 5. Interlocks shall prevent moving breaker to or from operating position unless main contacts are open. Operating springs shall be discharged automatically when breaker is rolled fully into connected or disconnected position. Rack-out device shall have provisions to padlock in connected or disconnected position. When locked in disconnected position, breaker shall be removable from compartment using portable lifting device. Padlock shall not interfere with breaker operation. 6. Automatic shutters shall cover primary disconnect stabs when breaker is withdrawn to test/disconnect position. Shutters shall be positively driven by linkages connected to racking mechanism. A stationary barrier shall be located in front of the shutters for additional safety. 7. Breaker control voltage shall be 48 VDC. E. INSTRUMENT TRANSFORMERS 1. Current transformer ratios are listed in each switchgear units specification paragraphs. 2. Voltage transformers shall be draw-out type, with current-limiting fuses and with BIL rating equal to the switchgear. Transformer ratios are listed on drawings. 3. Secondary control wiring shall be No. 14, extra flexible, stranded, tinned-copper control wire, Type SIS cross linked polyethylene, rated 600 volts, except for specific circuits requiring larger wire. Crimp -type, insulated spade terminals shall be furnished on all wire ends, except where insulated ring terminals are used to connect to fuse blocks, instrument studs, or terminal block points with two ore more wire connections. IV

5 1- Medum voltage to include the following 1 Indoor Metal-clad medium voltage switchgear stacks 1 Drawout vacuum circuit breaker rated [5] [15] kv 1200a [250mva][500mva] with 48vdc spring charge motor, 48vdc close coil, 48vdc trip coil. 6 stage auxiliary switch, 6 stage cell position switch. 3- Surge arrestors 1- insulated 3 phase 3 wire main bus rated 1200 amp amp Load take-off stabs 1- Ground bus 2- Drawout Potential transformers with primary and secondary fuse protection 6- Current transformers with shorting type terminal blocks 1- Generator monitor Satec 290 Power meters reads: 3 Phase amperes, 3 phase voltage L-L,L-N, Power factor, Kilowatts, Watt-hours, Var-hours, Frequency, Amp demand, Kw demand, kva Communications Mod-bus 1- Drawout Overcurrent relay 50/51 1- Voltage sensing relay 1- Frequency sensing relay 1- Circuit breaker control switches with indicating lamps 1- Device 86 lockout relay 1- Breaker / Transformer drawer lift truck 1- Lot of terminal blocks and fusing 1- Auto start / stop PLC control 1- Generator Voltage Protective Relay (Device 27) An undervoltage solid state relay shall be included to respond to the true r.m.s. value of the generator voltage. This relay shall have an adjustable pick up range of 75% to 100% of nominal and an adjustable dropout of 80% to 95% of pickup. Dropout shall have zero differential for time delay reset. 1- Generator Frequency Protective Relay (Device 81) An underfrequency solid state relay utilizing full cycle zero crossing sensing shall be included to respond to the fundamental frequency of the system so as to ignore wave shape distortion resulting from solid state loads, The relay shall have an adjustable pick up range of 40 to 60 Hz and adjustable under frequency dropout range of 0.1 to 10 Hz below the pickup. 1- Mounting and wiring of customer supplied governor control 1- Speed adjust potentiometer V

6 1- Voltage adjust rheostat 2- Breaker position lamps with long life led G.E. ET Position Engine Control Switch Operation Stop / - In this position, the engine shall not be capable of starting and/or running. If the engine was shutdown due to the operation of a protective device, the shutdown malfunction shall be reset when the switch is moved to this position. If the engine is running when the switch is moved to this position, it shall immediately shut down. Off/Cooldown - In this position, the engine shall shut down after a cool down period. Automatic - In this position, the engine control shall be in available for full automatic operation upon receipt of a start signal. Manual - When placed in this position, the engine shall start, run. Generator may be manually placed on line utilizing the manual synch controls.when returned to the Automatic or off/cooldown position the circuit breaker will open and the engine will run for its cooldown period before shutting down. 1- lamp test pushbutton 1- DC circuit breaker with auxiliary contact to provide control power loss signal. 2- Form C run relay contacts wired to terminal strip for control Of remote auxilliary devices. 1- Form C Fault relay contacts wired to terminal strip for remote indication or alarm. 1- Auxiliary control relays 1-24 WINDOW ANNUNCIATOR VI

Contents. Page INTRODUCTION Power/Vac GUIDE FORM SPECIFICATION thru

Contents. Page INTRODUCTION Power/Vac GUIDE FORM SPECIFICATION thru Contents Page INTRODUCTION... 10-2 Power/Vac GUIDE FORM SPECIFICATION... 10-2 thru 10-12 10-1 Power/Vac Guide Form Specifications Guide Form Specifications INTRODUCTION Upon completion of the one-line

More information

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work Section 16435 - SWITCHBOARDS Introduction Part 1 - General Related Work Section 16070 Seismic Anchorage and Restraint Section 16075 Electrical Identification Section 16080 Power Distribution Acceptance

More information

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5 DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5 1.1. APPLICABLE PUBLICATIONS 1.1.1. Publications listed below (including amendments, addenda, revisions, supplements, and errata), form a part of this

More information

A system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment.

A system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment. General Unit substations shall be 500 kva minimum, 1500 kva maximum unless approved otherwise by the University. For the required configuration of University substations see Standard Electrical Detail

More information

Low Voltage Switchgear Type WL Low Voltage Metal-Enclosed Switchgear

Low Voltage Switchgear Type WL Low Voltage Metal-Enclosed Switchgear 13 Low Voltage Switchgear Siemens Type WL low voltage metal-enclosed switchgear is designed, constructed and tested to provide superior power distribution, power monitoring and control. At the heart of

More information

University of Houston Master Construction Specifications Insert Project Name

University of Houston Master Construction Specifications Insert Project Name SECTION 26 13 13 MEDIUM VOLTAGE SWITCHGEAR PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General

More information

CONTROLLIX CORPORATION CONTROLLIX.COM LOW VOLTAGE AUTOMATIC SWITCH CAPACITOR BANK SPECIFICATIONS

CONTROLLIX CORPORATION CONTROLLIX.COM LOW VOLTAGE AUTOMATIC SWITCH CAPACITOR BANK SPECIFICATIONS LOW VOLTAGE AUTOMATIC SWITCH CAPACITOR BANK SPECIFICATIONS I. SCOPE a. This specification describes the necessary requirements for the design, fabrication, and operation of automatically switched, low

More information

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE PAGE 261116-1 SECTION 261116 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application

5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application The most advanced Arc-Resistant Switchgear, designed and built to provide maximum safety in the event of an Internal Arcing Fault. 5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application Page 1

More information

A. Submittals shall be made in accordance with Division 1, Section

A. Submittals shall be made in accordance with Division 1, Section PART 1 - GENERAL 1.01 SCOPE A. The work of this section includes providing a fully enclosed metal-clad 12.47kV switchgear and auxiliary equipment as specified herein and as shown on the contract drawings.

More information

Electrical Switchgear Replacement Montgomery County Community College

Electrical Switchgear Replacement Montgomery County Community College Electrical Switchgear Replacement Montgomery County Community College ADDENDUM NO.1 #08-112014-SB01 November 12, 2014 The following clarifications, changes, additions or deletions for this project shall

More information

SWITCHGEAR DIVISION PRODUCT PROFILES

SWITCHGEAR DIVISION PRODUCT PROFILES SWITCHGEAR DIVISION PRODUCT PROFILES Metal-Enclosed Load-Interrupter Switchgear Product Profiles Three-Phase, Group-Operated Load-Interrupter Switches with Fuses in Single and Multi-Bay Assemblies Manual,

More information

SUBSTATION VACUUM CIRCUIT BREAKER (38KV)

SUBSTATION VACUUM CIRCUIT BREAKER (38KV) SUBSTATION VACUUM CIRCUIT BREAKER (38KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products for utilities

More information

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV) SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products

More information

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV) SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products for utilities

More information

Medium Voltage Equipment 5-15 kv GM-SG and 38 kv GM38 Metal-Clad Switchgear General

Medium Voltage Equipment 5-15 kv GM-SG and 38 kv GM38 Metal-Clad Switchgear General 13 SWITCHGEAR Medium Voltage Equipment -1 kv GM-SG and 38 kv GM38 Metal-Clad Switchgear General Overview Features Siemens, 7, 1 and 38kV class medium voltage, one- or two-high vacuum circuit breaker switchgear

More information

A. Submit manufacturer's literature and technical data before starting work.

A. Submit manufacturer's literature and technical data before starting work. SECTION 16425 SWITCHBOARD PART 1 GENERAL 1.01 SUMMARY A. Related Section: 1. 16450 - Grounding. 1.02 SUBMITTALS A. Submit manufacturer's literature and technical data before starting work. B. Submit Shop

More information

2018 Consultant s Handbook Division 26 Electrical 2413 Switchboards

2018 Consultant s Handbook Division 26 Electrical 2413 Switchboards 1 General 1.1 Switchboards shall be U.L. listed and labeled. 1.2 Each switchboard shall have its own main disconnecting means unless it is located in the same room as its source of origin. In most cases

More information

SIEMENS-ALLIS. Medium Voltage. Metalclad Switchgear. www. ElectricalPartManuals. com

SIEMENS-ALLIS. Medium Voltage. Metalclad Switchgear. www. ElectricalPartManuals. com SEMENS-ALLS Medium Voltage Metalclad Switchgear Page 2 Typical Arrangements Auxiliary Cell Over 2000A Breaker Cell A Breaker Cell Over A Breaker Cell --!1 A Breaker Cell Over 2000A Breaker Cell Auxiliary

More information

Specification Guide. for RMVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers

Specification Guide. for RMVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers Specification Guide for RMVAC Direct Replacement AC Medium Voltage Circuit Breakers Table of Contents 1.0 General Work Scope... 3 2.0 Standards... 3 3.0 Supplier Qualifications... 4 4.0 Circuit Breaker

More information

Design Standard. Purpose: Design Standard:

Design Standard. Purpose: Design Standard: Design Standard Purpose: This design standard has the purpose of creating a consistent application of motor-control centers throughout the East Side Union High School District, therefore achieving a standard

More information

University of Houston Master Construction Specifications Insert Project Name

University of Houston Master Construction Specifications Insert Project Name SECTION 26 24 14 600 VOLT DRAWOUT SWITCHGEAR PART 1 - GENERAL 1.01 SECTION INCLUDES: A. Individually mounted rear-accessible low voltage switchgear ANSI rated switchgear and low voltage power circuit breakers

More information

POWERCON CORPORATION

POWERCON CORPORATION POWERCON CORPORATION 5kV &15Kv METAL-CLAD SWITCHGEAR BROCHURE #PC042 ELECTRONIC VERSION CREATED: 6/30/96 Powercon Corporation P.O. Box 477 1551 Florida Avenue Severn, Maryland 21144 Baltimore: 410-551-6500

More information

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation Basis of Design This section applies to the design relating to low voltage switchboards. Design Criteria UW Class N1 facilities main switchboards shall be rear accessible. The main, tie and feeder breakers

More information

A. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein.

A. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein. 16425 SWITCHBOARD ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 26 24 13 An optional keynote to

More information

BGE STRATEGIC CUSTOMER ENGINEERING

BGE STRATEGIC CUSTOMER ENGINEERING TABLE OF CONTENTS 1. GENERAL.. 2 2. BGE SUPPLY FEEDER.. 4 3. SWITCHGEAR ENCLOSURE AND ASSEMBLY... 5 4. SWITCHGEAR MANUFACTURERS.. 8 5. CIRCUIT BREAKER.. 8 6. SWITCHGEAR EQUIPMENT.... 10 7. MAIN AND GROUND

More information

SafeGear TM Motor Control Center Arc resistant metal-clad construction

SafeGear TM Motor Control Center Arc resistant metal-clad construction SafeGear TM Motor Control Center Arc resistant metal-clad construction Contents Description 2 SafeGear TM MCC applications 3 Electrical features 3 Standards 3 Standard service conditions 4 HCV vacuum contactor

More information

Power/Vac OEM Express Switchgear

Power/Vac OEM Express Switchgear g Power/Vac OEM Express Switchgear Metalclad Switchgear 4.16kV-250 MVA through 13.8kV-1500 MVA DEA-275 FULLY ASSEMBLED MECHANICALLY COMPLETE SWITCHGEAR WITHOUT DEVICES AND WIRE. POWER/VAC OEM EXPRESS SWITCHGEAR

More information

SECTION MOTOR CONTROLLERS

SECTION MOTOR CONTROLLERS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 29 11 MOTOR CONTROLLERS SPEC WRITER NOTE: Delete between // ---- // if not applicable to project. Also, delete any other item or paragraph not applicable to

More information

SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Brochure

SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Brochure 2017 SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Brochure SafeGear Motor Control Center Arc resistant Metal-Clad construction Brochure Table of Contents 1. Description 1 1 2. SafeGear

More information

Medium Voltage Metal-Enclosed Switches

Medium Voltage Metal-Enclosed Switches Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Introduction Product Selection Guide....................................2 Medium Voltage Switch MVS Product Description......................................

More information

Medium Voltage Metal-Enclosed Switches

Medium Voltage Metal-Enclosed Switches Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Medium Voltage Switch MVS Product Description............................................. 2 Application Description..........................................

More information

Metal-Enclosed Switches. Medium Voltage. Medium Voltage Metal-Enclosed Switches Contents

Metal-Enclosed Switches. Medium Voltage. Medium Voltage Metal-Enclosed Switches Contents January 2003 Vol. 1, Ref. No. [1011] -1 Medium Voltage Metal-Enclosed Switches Contents Description Page MVS................................... -2 and Breaker MSB........................ -3 Metal-Enclosed

More information

SIEMENS. Series 8100oT Vacuum Controllers. www. ElectricalPartManuals. com. Bulletin CC

SIEMENS. Series 8100oT Vacuum Controllers. www. ElectricalPartManuals. com. Bulletin CC c c SIEMENS Series 8100oT Vacuum Controllers Bulletin CC3802-02 Technological Development Vacuum technology has developed rapidly in recent years and is becoming widely accepted for medium voltage motor

More information

Descriptive bulletin. Medium voltage load interrupter switchgear Reliable, low maintenance and economical for distribution applications

Descriptive bulletin. Medium voltage load interrupter switchgear Reliable, low maintenance and economical for distribution applications Descriptive bulletin Medium voltage load interrupter switchgear Reliable, low maintenance and economical for distribution applications General overview Reliable, low maintenance and economical Load Interrupter

More information

Power Break II Switchboard

Power Break II Switchboard Power Break II Switchboard Now available with PowerBreak II Circuit Breakers through 4000A GE s Power Break II Switchboard is now available with the new Power Break II Insulated Case Circuit Breaker (800A

More information

MEDIUM VOLTAGE SWITCHGEAR SECTION

MEDIUM VOLTAGE SWITCHGEAR SECTION PART 1 GENERAL 1.01 Summary A. This specification covers the design and functional requirements for 5 kv medium voltage outdoor sheltered aisle metal-clad switchgear with vacuum circuit breakers. The switchgear

More information

7. SERVICES OVER 600 VOLTS

7. SERVICES OVER 600 VOLTS 7. SERVICES OVER 600 VOLTS 7.1 GENERAL The Company shall always be consulted to obtain required design criteria where service is contemplated.preliminary plans of the Customer shall be submitted for review

More information

MEDIUM VOLTAGE AIR INSULATED ARC-RESISTANT LOAD BREAK AND DISCONNECT SWITCHES

MEDIUM VOLTAGE AIR INSULATED ARC-RESISTANT LOAD BREAK AND DISCONNECT SWITCHES MEDIUM VOLTAGE AIR INSULATED ARC-RESISTANT LOAD BREAK AND DISCONNECT SWITCHES Description JRS arc-resistant fused/non-fused load break and fused/non-fused disconnect switches are available for applications

More information

Chapter 6 Generator-Voltage System

Chapter 6 Generator-Voltage System Chapter 6 Generator-Voltage System 6-1. General The generator-voltage system described in this chapter includes the leads and associated equipment between the generator terminals and the low-voltage terminals

More information

Medium Voltage. ANSI C37.20 and NEMA SG-5

Medium Voltage. ANSI C37.20 and NEMA SG-5 Medium Voltage ANSI C37.20 and NEMA SG-5 ANSI C37.20 and NEMA SG-5 Medium Voltage Metal-Clad Switchgear Medium Voltage ANSI C37.20 and NEMA SG-5 04 General 06 Application Data 08 Features 10 Circuit Compartment

More information

ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position

ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position LET S BE PACIFIC November 0 Volume Number 5 ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position Federal Pacific has the capability to engineer, fabricate and assemble

More information

POWER-ZONE 4 Low Voltage Metal-Enclosed Drawout Switchgear with MASTERPACT NW Low Voltage Power Circuit Breakers

POWER-ZONE 4 Low Voltage Metal-Enclosed Drawout Switchgear with MASTERPACT NW Low Voltage Power Circuit Breakers POWER-ZONE 4 Low Voltage Metal-Enclosed Drawout Switchgear with MASTERPACT NW Low Voltage Power Circuit Breakers Class 6037 CONTENTS Schneider Electric Brands Description Page Product Description..................................................

More information

GE Energy Connections Industrial Solutions. DET-882 Application and Technical Guide. SecoGear

GE Energy Connections Industrial Solutions. DET-882 Application and Technical Guide. SecoGear GE Energy Connections Industrial Solutions DET-882 Application and Technical Guide SecoGear Me - Switchgear HAZARD CLASSIFICATIONS The following important highlighted information appears throughout this

More information

DIVISION 26 ELECTRICAL SECTION CIRCUIT BREAKERS

DIVISION 26 ELECTRICAL SECTION CIRCUIT BREAKERS DIVISION 26 ELECTRICAL SECTION 26 28 19 PART 1 GENERAL 1.01 DESCRIPTION A. Furnish and install circuit breakers in switchboards, distribution panelboards, and separate enclosures for overcurrent protection

More information

VOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS

VOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS VOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS A. 11 KV SWITCHGEAR 1.0 SWITCHGEAR ASSEMBLY 1.1 Make : 1.2 Type : 1.3 Reference Standard : 1.4 Voltage (Nom./Max.) KV : 1.5 Phase, Frequency No,Hz.

More information

1. The term "withstand" means "the unit will remain in place without separation of any parts from the device when subjected to the seismic forces.

1. The term withstand means the unit will remain in place without separation of any parts from the device when subjected to the seismic forces. SECTION 262816 - ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Fusible switches. 2. Nonfusible switches. 3. Receptacle switches. 4. Shunt trip switches. 5.

More information

A. Work Included: Provide low voltage switchboard work as shown, scheduled, indicated, and as specified.

A. Work Included: Provide low voltage switchboard work as shown, scheduled, indicated, and as specified. SECTION 26 24 13 LOW VOLTAGE SWITCHBOARDS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General

More information

Specification Guide. for RMAX. Direct Replacement. AC Low Voltage. Power Circuit Breakers

Specification Guide. for RMAX. Direct Replacement. AC Low Voltage. Power Circuit Breakers Specification Guide for RMAX Direct Replacement AC Low Voltage Power Circuit Breakers Table of Contents 1.0 General Work Scope...3 2.0 Standards... 3 3.0 Supplier Qualifications... 3 4.0 Mechanical and

More information

Three-Phase Pole Mounted Recloser

Three-Phase Pole Mounted Recloser Three-Phase Pole Mounted Recloser Page 1 of 8 Table of Contents 1 GENERAL... 3 2 CONSTRUCTION... 3-5 3 BUSHINGS... 5 4 LINE CONNECTOR... 5 5 TOOLS....5 6 NAMEPLATES..6 7 PAINT... 6 8 EXTERNAL HARDWARE

More information

Detail Bill of Material Page 1 of 1 Project Name: Amphi School - MVS Replacement Negotiation No: TU700213X7K2 General Order

Detail Bill of Material Page 1 of 1 Project Name: Amphi School - MVS Replacement Negotiation No: TU700213X7K2 General Order Amphitheater High School Medium Voltage Switchgear Replacement Basis of Design 8/21/17 1of3 Detail Bill of Material Page 1 of 1 Project Name: Amphi School - MVS Replacement Negotiation No: TU700213X7K2

More information

Typical Specification

Typical Specification Engineered to Order Built to Last Typical Specification VAULT VRPFI, TWO POSITION, ROTARY PUFFER SWITCHGEAR PART 1- GENERAL 1.1 DESCRIPTION A. The switch shall consist of manually operated load interrupting,

More information

www. ElectricalPartManuals. com

www. ElectricalPartManuals. com ---- ----------- --- Page 2 Description and Application VacCiad-W Metal-Clad Switchgear is an integrated assembly of drawout vacuum circuit breakers, bus, and control devices coordinated electrically and

More information

CITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-112 SUBSTATION CLASS VACUUM CIRCUIT BREAKERS OCTOBER 2008

CITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-112 SUBSTATION CLASS VACUUM CIRCUIT BREAKERS OCTOBER 2008 CITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-112 SUBSTATION CLASS VACUUM CIRCUIT BREAKERS OCTOBER 2008 SPECIFICATION NO: ELE_112_R1.doc Page 1 of 3 Rev. 10/28/2008 SPECIFICATION

More information

SECTION 16311A INTEGRATED UNIT SUBSTATIONS (IUS) SECONDARY LESS THAN 1000 V

SECTION 16311A INTEGRATED UNIT SUBSTATIONS (IUS) SECONDARY LESS THAN 1000 V INTEGRATED UNIT SUBSTATIONS (IUS) SECONDARY LESS THAN 1000 V PART 1 GENERAL 1.01 SCOPE A. The Contractor shall furnish and install the integrated unit substation (IUS) complete from the incoming line terminals

More information

16.13 Unit Substation to 15kV Construction Standards Page 1 of 7

16.13 Unit Substation to 15kV Construction Standards Page 1 of 7 Construction Standards Page 1 of 7.1 General.1 New buildings are to be provided with an indoor unit substation designed to accept 15kV and 25kV primary voltages, however, the primary voltage connected

More information

ATLV MaxSG. Low Voltage Metal Enclosed Switchgear

ATLV MaxSG. Low Voltage Metal Enclosed Switchgear ATLV MaxSG Low Voltage Metal Enclosed Switchgear ABB, INC. Product General Description MaxSG Switchgear ABB MaxSG switchgear is a further continuation in the development of innovative products from ABB,

More information

MASTERCLAD Metal-Clad Indoor Switchgear

MASTERCLAD Metal-Clad Indoor Switchgear Instruction Bulletin 6055-30 MASTERCLAD Metal-Clad Indoor Switchgear 4.76 15.0 kv Series 5 With Type VR Vacuum Circuit Breakers Class 6055 MASTERCLAD Metal-Clad Indoor Switchgear Bulletin 6055-30 SQUARE

More information

SECTION 16426B. RELATED SECTIONS Section 16671A Transient Voltage Surge Suppression Section Microprocessor-Based Metering Equipment

SECTION 16426B. RELATED SECTIONS Section 16671A Transient Voltage Surge Suppression Section Microprocessor-Based Metering Equipment METAL-ENCLOSED DRAWOUT SWITCHGEAR (DSLII) LOW VOLTAGE PART 1 GENERAL 1.01 1.02 1.03 1.04 SCOPE The Contractor shall furnish and install, where indicated on the drawings, a deadfront type, low voltage metal-enclosed

More information

A comparison of metal-enclosed load interrupter (ME) switchgear and metal-clad (MC) switchgear

A comparison of metal-enclosed load interrupter (ME) switchgear and metal-clad (MC) switchgear Robert J. Gustin Eaton Fellow Application Engineer, P. E. Southfield, Michigan Definitions Metal-enclosed load interrupter switchgear type ME Metal-enclosed switchgear is defined in ANSI C37.20.3-1987,

More information

GE Industrial Solutions. User/Installation Manual for 4.76kV -15kV SecoBloc

GE Industrial Solutions. User/Installation Manual for 4.76kV -15kV SecoBloc GE Industrial Solutions User/Installation Manual for 4.76kV -15kV SecoBloc Index General Scope...3 Standards...3 Operating conditions...3 Technical specification...3 Basic structure Features...4 Operation...4

More information

SPECIAL SPECIFICATION 5066 Packaged Engine Generator System

SPECIAL SPECIFICATION 5066 Packaged Engine Generator System 2004 Specifications CSJ 2121-04-072 SPECIAL SPECIFICATION 5066 Packaged Engine Generator System 1. Description. Furnish and install packaged engine generator system complete with transfer switch and service

More information

Critical Power Switchboards. Selection and Application Guide

Critical Power Switchboards. Selection and Application Guide Selection and Application Guide Siemens RCIII (rear connected) switchboards utilizing Siemens Type SB Encased Breakers are a perfect solution for your critical power distribution needs. Whether your installation

More information

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS SECTION 26 28 16 ENCLOSED SWITCHES AND PART 1 - GENERAL 1.1 SUMMARY A. Section includes the following individually mounted, enclosed switches and circuit breakers rated 600V AC and less: 1. Fusible switches.

More information

Integrated Power Solutions

Integrated Power Solutions Integrated Power Solutions Low & Medium Voltage Distribution Power Distribution Centers Skid-Mounted Substations Custom Control & Automation ESS Metron Proposal 64000V1 DATE: PAGES (including cover): 7

More information

IN2 Enclosed Switches and Circuit Breakers

IN2 Enclosed Switches and Circuit Breakers Illinois Math and Science Academy DigitalCommons@IMSA Project Manuals IN2 2015 IN2 Enclosed Switches and Circuit Breakers Illinois Mathematics and Science Academy Follow this and additional works at: http://digitalcommons.imsa.edu/facility_in2_manuals

More information

Horizontal Circuit Switchers

Horizontal Circuit Switchers > Transformer Protection > CIRCUIT SWITCHERS C A T A L O G B U L L E T I N General Application Southern States Types CSH and CSH-B Horizontal Circuit Switchers provide an economical, versatile, space saving

More information

AMVAC TM technical guide Vacuum circuit breaker with magnetic actuator mechanism

AMVAC TM technical guide Vacuum circuit breaker with magnetic actuator mechanism AMVAC TM technical guide Vacuum circuit breaker with magnetic actuator mechanism AMVAC Universal applications: Medium voltage motor starting applications Capacitor switching Retrofit applications to replace

More information

33KV INDOOR SWITCHGEAR

33KV INDOOR SWITCHGEAR 33KV INDOOR SWITCHGEAR September 2017 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, Sector-II, Bidhannagar, Kolkata 700091. CIN:

More information

UBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5

UBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5 Page 1 of 5 1.0 GENERAL 1.1 Coordination Requirements.1 UBC Building Operations Electrical Technical Support.2 UBC Energy & Water Services 2.0 REQUIREMENTS FOR COMMISSIONING AND TESTING 2.1 Testing.1 Unit

More information

MV Metalclad Switchgear 4760V-15000V 20KA-63KA. AC Power Circuit Breaker Rating Structure. Test Procedures for Power Circuit Breakers

MV Metalclad Switchgear 4760V-15000V 20KA-63KA. AC Power Circuit Breaker Rating Structure. Test Procedures for Power Circuit Breakers Contents Key Features and Benefits Codes and Standards Value Addition by Application of PVAC-E GE Components Inside Design Features on PVAC-E Switchgear PVAC-E Switchgear Configuration PVAC-E Switchgear

More information

SECTION MOTOR STARTERS (AMPGARD) MEDIUM VOLTAGE

SECTION MOTOR STARTERS (AMPGARD) MEDIUM VOLTAGE MOTOR STARTERS (AMPGARD) MEDIUM VOLTAGE PART 1 GENERAL 1.01 1.02 1.03 1.04 SCOPE The Contractor shall furnish and install the medium voltage motor starters as specified herein and as shown on the contract

More information

Digital Paralleling. PowerCommand Medium Voltage Digital Paralleling Systems

Digital Paralleling. PowerCommand Medium Voltage Digital Paralleling Systems Digital Paralleling PowerCommand Medium Voltage Digital Paralleling Systems PowerCommand THE POWER OF ONE Traditional power systems often combine engines, alternators, controls, paralleling equipment,

More information

MASTERCLAD. Metalclad Indoor Switchgear 27 kv with Type VR Vacuum Circuit Breakers Class Instruction Bulletin. Retain for future use.

MASTERCLAD. Metalclad Indoor Switchgear 27 kv with Type VR Vacuum Circuit Breakers Class Instruction Bulletin. Retain for future use. Instruction Bulletin Retain for future use. MASTERCLAD Metalclad Indoor Switchgear 27 kv with Type VR Vacuum Circuit Breakers Class 6055 HAZARD CATEGORIES AND SPECIAL SYMBOLS Read these instructions carefully

More information

Solar Power Switchgear & Energy Storage Renewable Energy Systems

Solar Power Switchgear & Energy Storage Renewable Energy Systems 7 Solar Power Switchgear & Energy Storage Renewable Energy Systems - Solution Brochure www.apt-power.com 433 N. 36 th Street PROVIDING A COMPREHENSIVE Lafayette, IN 47905 www.apt-power.com 433 APPROACH

More information

www. ElectricalPartManuals. com Section 13 Switchgear Low Voltage

www. ElectricalPartManuals. com Section 13 Switchgear Low Voltage Switchgear Low Voltage Introduction...13-1 AKD-10 Low-Voltage Switchgear...13-3 AKD-20 Low-Voltage Switchgear...13-3 Low Voltage Switchgear GE low-voltage switchgear is heavy-duty equipment built to ANSI

More information

Switchgear. Low Voltage

Switchgear. Low Voltage January 2001 Vol. 1, Ref. No. [0923] -1 Low Voltage Switchgear Contents Description Page Magnum DS Metal-Enclosed Product Description........................................... -2 Application Description........................................

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION MOTORS, STARTERS & DRIVES

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION MOTORS, STARTERS & DRIVES PART 0 DESIGN STANDARDS 0.01 GENERAL DESIGN GUIDELINES A. Coordinate starter needs for mechanical equipment prior to 50% CD and confirm again for 100% CD submittal. B. Coordinate temperature controls requirements

More information

OTEC Transfer switch open transition

OTEC Transfer switch open transition Specification sheet OTEC Transfer switch open transition 40 1200 amp Description OTEC transfer switches are designed for operation and switching of electrical loads between primary power and Standby generator

More information

Medium voltage switchgear SafeGear HD 63 ka arc resistant metal-clad switchgear. ABB Group February 25, 2015 Slide 1

Medium voltage switchgear SafeGear HD 63 ka arc resistant metal-clad switchgear. ABB Group February 25, 2015 Slide 1 Medium voltage switchgear SafeGear HD 63 ka arc resistant metal-clad switchgear ABB Group February 25, 2015 Slide 1 SafeGear HD arc resistant switchgear 63 ka arc resistant metal-clad air insulated switchgear

More information

Type SDV6 distribution circuit breaker. Top performance - proven reliability. Answers for energy.

Type SDV6 distribution circuit breaker. Top performance - proven reliability. Answers for energy. Type SDV6 distribution circuit breaker Top performance - proven reliability Answers for energy. Table of contents Introduction 2-4 Type 3AH3 stored-energy operating mechanism 6 Vacuum interrupters 7 Ratings

More information

SECTION PANELBOARDS

SECTION PANELBOARDS SECTION 16470 PANELBOARDS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. The general provisions of the contract including General and Special Conditions and General Requirements shall apply to all work under

More information

Type MC Metal-Clad Switchgear

Type MC Metal-Clad Switchgear 0HGLXP9ROWDJH 0HWDO&ODG6ZLWFKJHDU 7\SH0& Type MC Metal-Clad Switchgear Introduction The increasing use of higher voltages for electrical distribution and application in both industrial and commercial applications

More information

SUBSTATION EQUIPMENT - Page 1 of 8

SUBSTATION EQUIPMENT - Page 1 of 8 BATTERY BANKS 1. GENERAL: JEA utilizes a 125 volt DC system for the control and operation of its transmission and distribution substations. JEA has standardized on lead acid type battery banks to supply

More information

SECTION SWITCHGEAR. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section.

SECTION SWITCHGEAR. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes metal-enclosed,

More information

Issued Revised Approved Reviewed September 9, 1984 December 2008 G. Saini J. Fuller

Issued Revised Approved Reviewed September 9, 1984 December 2008 G. Saini J. Fuller Specification Medium Voltage Metalclad Switchgear Medium Voltage Number: 5342-02.01.310 Issued Revised Approved Reviewed September 9, 1984 December 2008 G. Saini J. Fuller Rev. 2 SCOPE This specification

More information

POWERCON CORPORATION

POWERCON CORPORATION POWERCON CORPORATION 38,000 VOLT METAL-CLAD SWITCHGEAR BROCHURE #PC-041 ELECTRONIC VERSION CREATED: 6/30/96 Powercon Corporation P.O. Box 477 1551 Florida Avenue Severn, Maryland 21144 Baltimore: 410-551-6500

More information

Page 2 DS LOW VOLTAGE POWER CIRCUIT BREAKERS Digitrip Trip Unit Inside Wiring Guide Outside Wiring Guide Shutter Drawout Unit Position Indicator Escut

Page 2 DS LOW VOLTAGE POWER CIRCUIT BREAKERS Digitrip Trip Unit Inside Wiring Guide Outside Wiring Guide Shutter Drawout Unit Position Indicator Escut Page 1 Supersedes Renewal Parts Data 33-790-1G pages 1-20 dated December, 1988 Mailed to: C, D, E/33-700 Westinghouse DS and DSL Low Voltage Power Circuit Breakers and Cell Parts Contents Pages DS Breaker

More information

Horizontal Circuit Switchers

Horizontal Circuit Switchers > Transformer Protection > CIRCUIT SWITCHERS C A T A L O G B U L L E T I N General Application Southern States Types CSH and CSH-B Horizontal Circuit Switchers provide an economical, versatile, space saving

More information

SECTION MOTOR CONTROLLERS

SECTION MOTOR CONTROLLERS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 29 11 SPEC WRITER NOTE: Use this section only for NCA projects. Delete between // ---- // if not applicable to project. Also, delete any other item or paragraph

More information

A. This Section includes ac, enclosed controllers rated 600 V and less, of the following types:

A. This Section includes ac, enclosed controllers rated 600 V and less, of the following types: SECTION 262913 600 VOLT ENCLOSED CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 0 Specification

More information

Transfer switch OTEC open or delayed transition

Transfer switch OTEC open or delayed transition Transfer switch OTEC open or delayed transition 40-1000 Amp Description OTEC transfer switches are designed for operation and switching of electrical loads between primary power and standby generator sets.

More information

DS/DSII Low Voltage Switchgear. Renewal Parts. Cutler-Hammer. Renewal Parts. Effective: October Page 1

DS/DSII Low Voltage Switchgear. Renewal Parts. Cutler-Hammer. Renewal Parts. Effective: October Page 1 New Information Supersedes Data 33-790-1H, dated October 1996 DS/DSII Low Voltage Switchgear Page 1 DS Switchgear Assembly DSII Switchgear Assembly Contents Pages DS Switchgear (Front View) 2 DSII Switchgear

More information

SECTION DC POWER SUPPLY/BATTERY CHARGER

SECTION DC POWER SUPPLY/BATTERY CHARGER SECTION 26 33 05 PART 1 - GENERAL 1.1 THE REQUIREMENT A. The CONTRACTOR shall provide the single-phase heavy-duty industrial battery charger and all accessories required, complete and operable, in accordance

More information

CLIENT: PROJECT: PO#: ESTIMATOR:

CLIENT: PROJECT: PO#: ESTIMATOR: GENERATOR CONTROL DATA SHEET CLIENT: PROJECT: PO#: ESTIMATOR: PRIME MOVER FUEL: RPM: GOVERNOR SPEED ADJUST RHEOSTAT SUPPLIED WITH GOVERNOR: LOAD SHARING: REMOTE: PRIME MOVER PROTECTION LOW OIL PRESSURE

More information

A. Products shall be designed, manufactured, tested, and installed in compliance with the following standards:

A. Products shall be designed, manufactured, tested, and installed in compliance with the following standards: SECTION 26 29 13 ENCLOSED MOTOR CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General

More information

MEDIUM-VOLTAGE SWITCHGEAR

MEDIUM-VOLTAGE SWITCHGEAR REVISION RECORD SECTION 16341 Medium-Voltage Switchgear REV DATE PAGE PARA NO. DESCRIPTION APPROVED BY 28SEP01 ALL Initial issue. 1 29SEP03 ALL General update with miscellaneous changes in entire document.

More information

BTPC Bypass isolation transfer switch open or closed transition

BTPC Bypass isolation transfer switch open or closed transition Specification sheet BTPC Bypass isolation transfer switch open or closed transition 150 4000 amps Description BTPC bypass isolation transfer switches combine a drawout automatic transfer switch with isolation

More information

Selection and Application Guide E50001-U229-A320-X-US00. GM38 Switchgear. 38kV. Power Transmission & Distribution

Selection and Application Guide E50001-U229-A320-X-US00. GM38 Switchgear. 38kV. Power Transmission & Distribution Selection and Application Guide E50001-U229-A320-X-US00 GM38 Switchgear 38kV Power Transmission & Distribution Table of Contents Introduction.................01 02 Overview....................03 05 Construction.................06

More information

Cutler-Hammer May 2001

Cutler-Hammer May 2001 Low-Voltage Power Circuit Breakers Magnum DS General Description Index Page General Description Magnum DS............. A1-1 General Description DSII/DSLII............... A1-7 Technical Data Magnum DS.

More information