1 SPETRONI SP - Air circuit breakers Summary 2. General characteristics 3. Fixed circuit breaker 4. Withdrawable circuit breakers 5. haracteristics 6. RV23: protection and control unit 6. RV+ : protection and control unit.10 Auxiliaries Order odes 18. Overall dimensions 21. Weights 22. RV andwiring diagram

2 SPETRONI SP - Air circuit breakers ircuit Breakers 400 to 2500A - Series SP Rated short- circuit breaking capacity: Icu 55 to 60kA (415V) omplete range - Fixed or withdrawable versions - 3 or 4 poles - Electrical or manual control The SPETRONI range combines the legendary reliability of our air circuit breakers with: - A design adapted to the new panel boards - Protection relay: RV 23, RV+ Main advantages - lever design combining longevity and reliability - Maximum service: total selectivity is ensured, even at closing on short circuit - Simple and efficient servicing on site - Safety ensured by fully visible breaking. onformity The circuit breakers SP are built according to the following standards: IE 947-2, BS, EI, NBN, NF and VDE. ertification: Bureau Vé ritas, Lloyd s Register of Shipping, ASEFA. ertification: Germanischer Lloyd (in accordance with IE ) Tropicalisation - lass I (standard): Relative humidity of 80% at 40 (Hot and dry or damp climate of temperature zones). - lass II: Relative humidity of 95% at 45 (hot and damp climate). Anti-corrosion treatment For special atmospheres, consult us. Rated short-circuit breaking capacity following IE (415V) Icu (ka) SP 800 SP 1000 SP 1250 SP 1600 SP 2000 SP Ith ) A(

3 SPETRONI SP - Air circuit breakers Fixed circuit breaker Description Fitted at the factory with a control panel providing an IP30 degree of protection. For panel mounting, a seal and a cover permit IP3X protection with the door closed. Installation - Fixed to vertical uprights or on horizontal surface. - Main connections ). - onnections to auxiliary circuits by terminals located at the front of the unit ) max 24 terminals). - Supplied with 12 terminals as standard, mounted on the right. Power supply orientation Up to 415V, connections are made either to the upper or lower terminal clamps. Above 415V, connect to the upper terminals. 1 Local trip and reset push button (BPDL). 2 ircuit breaker position indicator. Red = closed - Green = open. 3 Trip lever prior to withdrawal or plugged- in operations. 4 Auxiliary switches. 5 RV 23 or RV+ releases. 6 Volmetric releases: shunt and undervoltage releases. 7 Locking in connected position or locking in withdrawn position. 8 Fixed auxiliary terminal block. 9 Electrical control. 10 urrent transformer. 11 Position contact withdrawn- inserted. 12 EX trip actuator. 13 Digital ammeter )optional(. 14 Distinct fault signalling )optional(. 15 Arc chute. 16 Isolating shutter. 17 Reinforced ground plug. 18 Primary jaw. 19 Fault contact.

4 SPETRONI SP - Air circuit breakers Withdrawable circuit breaker Description The circuit breaker is mounted on a cradle fitted with slides allowing two positions: inserted and withdrawn- isolated. The insertion and withdrawal operations are performed by a screw-nut system, operated by two removable cranks. Automatic tripping of the breaker on withdrawal is ensured by a safety device at the insertion of the cranks. For panel mounting, a seal and a cover, permit IP3x protection with the door closed. The circuit breaker may be withdrawn either with the door closed or open. Installation - Fixing to the vertical uprights by rear surface or on a horizontal surface by adding L pieces on side faces. - Main connections (see table on page D. 27). - The auxiliary circuits disconnect automatically and simultaneously with the main circuit. - onnections to the auxiliary circuits are made laterally with clips (maximum 24 terminals) - Standard unit equipped with 12 terminals. 8 Power supply orientation Up to 415V, connections are made either to the upper or lower terminal clamps. Above 415V, connect to the upper terminals

5 SPETRONI SP - Air circuit breakers haracteristics ircuit Breakers 5 SP 800 SP 1000 SP 1250 SP 1600 SP 2000 SP 2500 Rated insulation voltage Ui (V) Rated impulse voltage Uimp (kv) Rated maximum nominal voltage Ue (V) Rated thermal current Ith 40 (A) (A) (A) Rated ultimate short-circuit breaking capacity Icu Alternating current 50/ 60Hz 240/ 415V (ka) V (ka) V ) (ka) Rated service short-circuit breaking capacity Ics Alternating current 50/ 60Hz 240/ 415V (ka) V (ka) V (1) (ka) Rated peak short-circuit making capacity (max) Icm (ka peak) Rated short time withstand current Icw: 1 sec. 415V (ka eff.) V (ka eff.) Utilization category B B B B B B Number of poles Suitable for isolation (visible breaking indication) Endurance (number of operating cycles) Mechanical (total) # operating cycles Electrical (at 415V) ) ( # operating cycles Mean time between maintenances # operating cycles Power dissipation (withdrawable, 3 poles) (W) th pole conventional thermal curren (A) ) 1250 ) Pollution degree Dimensions in mm ) fixed version( 3poles Height (mm) Width (mm) Depth (mm) poles Height (mm) Width (mm) Depth (mm) ) 1( On request. ) 2( To guarantee this number of operations, it is necessary to check the spark ) 3( Neutral reduced to the left. arrestors and the arc chutes as shown in the table above ) Replace them when necessary( This can be done easily on site Switches SP 800 SP 1000 SP 1250 SP 1600 SP 2000 SP 2500 Rated thermal current at 40 Ith (A) Rated peak short-circuit making current Icm k(ka peak) Rated short time withstand current Icw: 1 sec. 415V ) ka eff.( V (ka eff.) Dimensions in mm (fixed circuit breaker): See circuit breaker table above

6 SPETRONI SP - Air circuit breakers RV 23: Protection unit for SP400 to SP2500 Standard protection - Overload protection (LT) - Short-circuit protection (ST-I) - Ground fault protection (GF) Setting ranges Setting points LT (x In) LTD (s) delay at 6 lr ST (x ln) Time delay (ms) I (x ln) OFF GF (xin) Time delay (ms) Ir= kxin Front face options The RV unit may supplied with following modules. 6 Optional distinct fault signalling (LT, ST- I, GF) This option displays locally by LED and dry contacts the origin of the fault. Optional Load monitoring threshold setting :( ) x Ir Optional Ammeter A digital ammeter permanently displays the maximum current value. Description The current of other phases is available locally. The RV 23 unit meets the requirements of the IE standard. This unit is powered by the current transformers and performs all the necessary three or four pole overcurrent protections. The RV 23 is designed for : - 3 pole or 4 pole protection: 3P/ 3P+ N - 3 pole with half neutral protection: 3P+ N50% - 3 pole or 4 pole ground fault protection Internal Options Auxiiary power supply 24V D - 15W or 24V A - 15 VA RV front face options Note In RV03 unit there are no LT delay setting and GF protection

7 SPETRONI SP - Air circuit breakers RV 23: Protection unit for SP400 to SP2500 Setting and operating current values Operating limits - IE 7 LT Threshold in k x In k= times the current transformer rating LT Time delay s. at6ir Time in seconds ST Threshold times the LT value( Ir) ST Time delay s Instantaneous threshold( I) times the LT value( lr) Multiples of current setting

8 SPETRONI SP - Air circuit breakers RV+ : Protection unit for SP400 to SP2500 Standard protection - Overload protection (LT) - Short-circuit protection (ST-I) - Ground fault protection (GF) Setting ranges I STD inst. GFD 8 Description The RV+ base on microprossesor unit meets the requirements of the IE standard. This unit is powered by the current transformers and performs all the necessary three or four pole overcurrent protections. The RV+ is designed for : - 3 pole or 4 pole protection: 3P/ 3P+ N - 3 pole with neutral protection: 3P+ N50 %,100%,200% - 3 pole or 4 pole ground fault protection Note In RV03 unit there are no LT delay setting and GF protection

9 SPETRONI SP - Air circuit breakers RV+ : Protection unit for SP4 00 to SP2500 Setting and operating current values ~ 1.25 Operating limits according to IE Ir=kxIn k = LT time delay sat6Ir 10 t (s) ST pick-up xir I t OFF 2 ItON ST time delay s I/Ir xir Inst. pick-up OFF xir Grand fault curve GF time delay s 2 ( ItOFF) 2 t (s) GF time delay s 2 ( ItON) GF pick-up OFFxIn I/In 2

10 SPETRONI SP - Auxiliaries Electrical control The electrical control is integrated within the overall dimensions of the circuit breaker. An easy adaption can be made to manual control. Breaker mechanism driven by a device with a universal motor. Automatic disconnection of the motor at the end of the operation. Making via a relay. Tripping by shunt trip or undervoltage release. Manual emergency control. Automatic reset. Manual reset after tripping due to fault. 10 haracteristics Rated service voltage Un Alternating current 50Hz Alternating current 60Hz Directcurrent Operating voltage Operating time at making Power consumption Breakertype Alternatingcurrent Directcurrent V V V ms VA W Note In case of continuous signal to close, interrupt this signal during 0. 3 sec minimum, to allow electrical control to reset properly V from085to11un at Un SP800 to1600 SP2000 and Electrical control 48V: section of the supply cables to be specified in accordance with the distance from the supply Section (mm) Distance from supply (m) ,

11 SPETRONI SP - Auxiliaries Voltmetric releases Two types of releases enable the remote controlled operation of the circuit breaker. SHUNT TRIP RELEASE EA-EA1-EB Actuates the breaking of the circuit breaker ) the power supply is cut by an auxiliary contact(. UNDERVOLTAGE RELEASE UVR-UVRD Actuates the breaking of the circuit breaker when the power supply voltage falls to a value between 35 and 70% of its rated value. UVR: Instantaneous action. UVRD: action delayed by 250 ms or 0. 6 s, alternating current power supply. Other delaying devices available upon request. 11 / ( ms) ( ms) 1st 2st 2st

12 SPETRONI SP - Auxiliaries Auxiliary switches AS - SAS Actuated at the same time as the main poles, the auxiliary contacts indicate the open or closed position of the circuit breaker. Mounting possibilities: - Either 6 AS changeover switches - or 3 SAS special changeover switches for D applications (it is not possible to combine AS and SAS). For low voltage contacts, 4 to 30V - 1 to 100mA, consult the sales office. 12 haracteristics Thermal current Ith (A) Interrupting capacity Alternating current cos ϕ V (A eff.) 127V (A eff.) 220V (A eff.) 380V (A eff.) Direct current L/ R 0. 01s 48V 0 (A) 120V (A) 220V (A) AS SAS Fault contact ) Bell alarm( BA ommon fault signals for overload and short- circuit. Possibility of two changeover switches BA1, BA2 activated by RMS 7 or RMS 9. After release it is necessary to reset the contacts by pushing the local mechanical push button situated on the control panel (BPDL). haracteristics Thermal current Ith (A) Interrupting capacity Alternating current cos ϕ V (A eff.) 127V (A eff.) 220V (A eff.) 380V (A eff.) Direct current L/ R 0. 01s 48V (A) 120V (A) 220V (A) BA

13 SPETRONI SP - Air circuit breakers Position contacts for withdrawable circuit breakers Equipment for withdrawable circuit breakers Auxiliary secondary disconnect system Safety contact in connected position AE 12 Indicates that the closing of the breaker can be actuated; the breaker is in onnected position, operating cranks not inserted. Possibility of a changeover switch. onnection by clips of mm. Includes a fixed part (female sockets) mounted on the cradle and a moving part (male sockets) mounted on the circuit breaker - Device permits connection of 6 circuits of 10 A per block. - Mounting of 4 devices maximum. Isolating shutter 13 onnected position contact AE Indicates the position of the circuit breaker in its cradle. Possibility of 2 changeover switches AE 51, AE 52. onnection by clips of mm. Withdrawn position contact AD Indicates the position of the circuit breaker in its cradle. Possibility of 2 changeover switches AD 61, AD 62. onnection by clips of 6. 5 mm. haracteristics Thermal current Ith (A) 20 Interrupting capacity Alternating current cos ϕ V 127V 220V 380V (A eff.) (A eff.) (A eff.) (A eff.) Direct current L/ R 0. 01s 48V 120V 220V (A) (A) (A) Prevents access to energised parts when the circuit breaker is in withdrawn position. Provided with a padlocking system (padlock not provided). Test position cord Use in place of secondary disconnects. Possibility of equipping the circuit breaker with a connector for testing the auxiliaries in the disconnected position. Reinforced ground plug Reinforces the natural electrical continuity between the cradle mass and the circuit breaker ) Icc 25kA s(. Remove the lower right wire secondary disconnection block.

14 SPETRONI SP - Order codes ircuit breakers Without Protection FIXED with rear horizontal terminals Front terminal kit SP 800 SP 1000 SP 1250 SP 1600 SP 2000 SP P P P P WITHDRAWABLE Moving part + Fixed part cradle with front terminals radle with rear horizontal terminals 3P P P P P P Higher value for 690V version RV protection unit 3P P RV RV RV+ urrent transformer Rating A SP 800 SP1000 SP 1250 SP 1600 SP 2000 SP

15 SPETRONI SP - Order codes Switches SP 800 SP 1000 SP 1250 SP 1600 SP 2000 SP 2500 FIXED with rear horizontal terminals Front terminals kit 3P P P P WITHDRAWABLE Moving part + Fixed part cradle with front terminals radle with rear horizontal terminals Higher value for 690V version 3P P P P P P P P

16 SPETRONI SP - Order codes Electrical auxiliaries Electrical control Shunt trip release Undervoltage trip release Use 4 connection terminals or secondary disconnections Use 2 connection terminals or secondary disconnections Use 2 connection terminals or secondary disconnections 16 SP A 50Hz V V ST A 50-60Hz,D / 127V V UV A 50-60Hz,D / 127V V V V A 60Hz V V V D V V

17 SPETRONI SP - Order codes Auxiliaries Accessories Signalling contacts Secondary terminals Interlocking Fixed circuit breaker: block of 12 terminals (maximum 1 additional block) Left mounting Withdrawable circuit breaker: block of 6 terminals ) 2 additional blocks maximum(. Tripped position By Ronis lock (supplied) By lock (not supplied) By padlocks (not supplied) Moving part Withdrawn position Fixed part By Ronis lock (supplied) NO N NO/ N Fixed and moving part assembly By lock (not supplied) AS AS AS AS 4 Isolating shutter 3P 4P SP Source changeover mechanical interlock Linkage permitting interlock: - 2 circuit breakers at 660 mm - 3 devices (on request) AS SP Fixed circuit breaker AS SAS 1 ) SAS 2 ) 1( SAS 3 ) 1( BA BA 2 Reinforced ground plug 25kA s For withdrawable circuit breaker Test position cord Replace the secondary disconnection device Withdrawable circuit breaker able system permitting interlock between: fixed circuit breaker withdrawable circuit breaker Operation counter ) 1 ( To fit 1, 2 or 3 SAS contacts, use adaption no ircuit breaker contact positions in the cradle onnection terminals or secondary disconnections to use: - by NO or N contact: 2 terminals - by NO/ N contact switches: 3 terminals " onnected position contact AE, one changeover contact NO/ N " Withdrawn position contact AD, one changeover contact NO/ N For each position two contacts are possible. Use an adaption no for 2 AE + 2 AD Use 3 secondary terminals per contact. Door gasket Factory fitted onnected cranks not inserted contact AE Permits IP3x protection when panel mounted A changeover contact NO/ N Use 3 secondary disconnection terminals

18 ط 9 ط 9 SPETRONI SP - Overall dimensions Fixed circuit breaker Front connection Rear horizontal connection Neutral E Door Gasket 4x 18 4x Panel cut out for fitting gasket Rear horizontal connections Front connections SP neutral of SP SP neutral of SP Legend Type Number of poles A B D SP 400 to SP E = minimum clearance distance above the arc chutes. Ue 500V Ue 690V I = Insulating screen 150 mm 150 mm M = Metallic screen 150 mm 200 mm SP SP

19 SPETRONI SP - Overall dimensions Withdrawable circuit breaker Front connection 10, ط 4 x 5 D B B Neutral to 1600 E Withdrawable door open Withdrawable door closed, 105 ط 4x Gasket 19 Panel cut out for gasket fitting Rear horizontal connection 800 to Withdrawable door closed 12 ط Door cut-out onnection terminals Legend Type Number of poles A B D SP 800 to SP E = minimum clearance distance above the arc chutes. Ue 500V Ue 690V I = Insulating screen 100 mm 100 mm M = Metallic screen 150 mm 200 mm SP 400 to 1600 neutral of SP SP

20 SPETRONI SP - Overall dimensions Source changeover switches IDS Fixed circuit breakers without chassis Type Number of poles A SP 400 to SP White area: overall dimensions of interlocking system. left alignment of circuit breaker fixation. 20 Withdrawable circuit breaker without chassis Type Number of poles A SP 400 to SP White area: overall dimensions of interlocking system. left alignment of circuit breaker fixation.

21 SPETRONI SP - onnections/ Weights onnection possibilities Fixed versions Rear horizontal terminals Rear vertical terminals Front terminals Withdrawable versions Rear horizontal terminals Rear vertical terminals Front terminals X = standard O = on request SP X O X SP X O X Weight of circuit breakers (in kg) Weight of switches (in kg) Fixed circuit breaker Withdrawable circuit breaker manual control electrical control manual control electrical control SP P P SP P P SP P P SP P P SP P P SP2500 3P P Fixed circuit breaker Withdrawable circuit breaker manual control electrical control manual control electrical control SP P P SP P P SP P P SP P P SP P P SP2500 3P P

22 SPETRONI SP - RV diagram RV: Protection and measurement unit Diagrams are shown without power supply, circuit breaker open, connected, reset and cranks not inserted. 22 Legend AE connected position contact AD withdrawn position contact AE 12 cranks not inserted contact BA1 - BA2 fault contact, overload and short-circuit with local reset after fault tripping MV(UV) undervoltage release UVRD time delayed undervoltage release RA resistor for selected voltages in direct current EA(ST) shunt trip release K relay FE1. 2 limit switch close FD limited switch reset M. m motor RH 50 resistor for 380V 21 interlock contact coupled with emergency control AS - SAS auxiliary switches BPO Tripping push-button BPF losing push-button

23 SPETRONI SP - Wiring diagram Open losed onnected Disconnected Disconnected cranks notinserted green M or or or 4 23 red Voltmetric releases Electrical control Auxiliary contacts Positioning contacts Electrical control External wiring: wire cross section 2. 5 mm 2 ) for 48V power supply, the wire length is max. 20 m(. For 48V: connection of electrical control on the circuit breaker and the 2 2 contact by 2. 5 mm wires. End user connections Fixed circuit breaker onnection by terminals 6. 3 x terminals maximum Letters in alphabetical order followed by increasing numbers Auxiliary contacts Six normal or three special auxiliary contacts. Withdrawable circuit breaker onnections by terminals 6. 3 x AS Bridge connected during installation For the electrical control of EA1, EA, EB, D1, D2, MVR, MV, RMS 7, use the allocated terminals. Other accessories: numbers are increasing clockwise ) use reserved terminals if they are available(. LEFT RIGHT LEFT RIGHT 50 N 49 MV or MVR REAR D2 FRONT D1 EA1 or EA or EB or MV. MVR E F G H Electrical control

24 Notes 24

cor Long Run Experience

cor Long Run Experience Moulded Case Circuit Breakers Moulded Case Circuit Breakers 16-1250A cor Long Run Experience cor Breaking capacity (according to IEC 947-2 at 415V) Icu 100 D160L D250L D400L D630L 70 60 DH800 50 35 30

More information

Spectronic-SP Air Circuit Breaker

Spectronic-SP Air Circuit Breaker Spectronic- Air Circuit Breaker Circuit Breakers 800 to 2500A Series Rated Short circuit breaking capacity : lcs 50 to 55KA ( 4 15V) Complete range Fixed with manual control 3 or 4 poles Electrical control

More information

GE Consumer & Industrial. M-PACT New Air Circuit Breaker A

GE Consumer & Industrial. M-PACT New Air Circuit Breaker A GE onsumer & Industrial M-PT New ir ircuit reaker 400-4000 M-PT M-PT ir ircuit reaker 400-4000 1 ir circuit breakers 400-4000.4 Fixed ircuit reaker.6 Withdrawable ircuit reaker.7 haracteristics.9 State

More information

Spectronic SP Air Circuit Breaker. Protecting people, property & productivity

Spectronic SP Air Circuit Breaker. Protecting people, property & productivity Spectronic SP Air Circuit Breaker Protecting people, property & productivity Spectronic SP Air Circuit Breaker Circuit Breakers 800 to 2500A Series SP Rated short circuit breaking capacity : lcs 50 / 55KA

More information

Spectronic SP Air Circuit Breaker. Protecting people, property & productivity

Spectronic SP Air Circuit Breaker. Protecting people, property & productivity Protecting people, property & productivity Circuit Breakers 800 to 2500A Series SP Rated short circuit breaking capacity : lcs 50 / 55KA ( 415V) Complete range Fixed with manual control 3 or 4 Poles The

More information

01 Spectra Plus - Introduction

01 Spectra Plus - Introduction 01 Spectra Plus - Introduction Standard features Conforming to IS13947-2/EN60947 2 Compact dimensions Available in 3P & 4P High performance microprocessor protection release Wide overload setting from

More information

GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector

GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector Catalog 0500CT9702R409 2009 Class 525/580 CONTENTS Description............................................. Page General Characteristics...................................

More information

Specification for 70mm pole pitch Air circuit breaker up to 1600 A

Specification for 70mm pole pitch Air circuit breaker up to 1600 A Specification for 70mm pole pitch Air circuit breaker up to 1600 A Protective device for low voltage electrical installation Last update :2011-07-08-1 - Table of contents: 1 General...3 2 Compliance with

More information

DPX moulded case circuit breakers

DPX moulded case circuit breakers BREAKING AND PROTECTION DEVICES 10 / 2011 DPX moulded case circuit breakers DPX moulded case circuit breakers offer optimum solutions for the protection requirements of commercial and industrial installations.

More information

ME 07 Air Circuit Breakers. ME 07 - Air Circuit Breakers. Low Voltage. Low Voltage. Low Voltage

ME 07 Air Circuit Breakers. ME 07 - Air Circuit Breakers. Low Voltage. Low Voltage. Low Voltage Low Voltage ME 07 - Air Circuit Breakers ME 07 Air Circuit Breakers Low Voltage AEG Niederspannungstechnik GmbH & Co KG Berliner Platz 2-6 D-24534 Neumünster (Germany) Tel. +49/43211-0 Fax +49/43211-144

More information

3 - Protection components Motor circuit-breakers

3 - Protection components Motor circuit-breakers Contents 0 - Protection components Motor circuit-breakers protection components for the motor protection Thermal-magnetic motor circuit-breakers Selection guide..............................................page

More information

DPX 1600 Electronic release

DPX 1600 Electronic release 87045 LIMOGES Cedex Phone :+33 05 55 06 87 87 Fax :+33 05 55 06 88 88 DPX 1600 CONTENTS PAGES 1. USE 1 2. RANGE 1 3. DIMENSIONS 1 3. DIMENSIONS (NEXT) 2 4. OVERVIEW 2 5. CONNECTION 2 6. ELECTRICAL AND

More information

DMX 3 -I 2500 switch disconnectors

DMX 3 -I 2500 switch disconnectors 8704 LIMOGES Cedex Telephone : 0 0 87 87 Fax : 0 0 88 88 DMX 3 200 circuit breakers DMX 3 -I 200 switch disconnectors References: 0 28 20 / 21 / 22 / 23 / 24 / 2 / 2 / 30 / 31/ 32/ 33/ 34 / 3 / 3 / 40

More information

DPX 630 Electronic release

DPX 630 Electronic release 87045 LIMOGES Cedex Phone :+33 05 55 06 87 87 Fax :+33 05 55 06 88 88 DPX 630 CONTENTS PAGES 1. USE 1 2. RANGE 1 3. DIMENSIONS 1 4. OVERVIEW 2 5. CONNECTION 2 6. ELECTRICAL AND MECHANICAL CHARACTERISTICS

More information

DPX Thermal magnetic and trip-free switches DPX 3 -I 630

DPX Thermal magnetic and trip-free switches DPX 3 -I 630 87045 LIMOGES Cedex Phone :+33 05 55 06 87 87 Fax :+33 05 55 06 88 88 DPX 3 630 CONTENTS PAGES 1. USE 1 2. RANGE 1 3. DIMENSIONS 1 4. OVERVIEW 2 5. ELECTRICAL AND MECHANICAL CHARACTERISTICS 2 6. CONFORMITY

More information

DRX 125 Circuit breaker (not adjustable)

DRX 125 Circuit breaker (not adjustable) 87045 LIMOGES Cedex Téléphone : 05 55 06 87 87 Télécopie : 05 55 06 88 88 272 20/21/22/23/24/25/26/27/55/56/57/58/59/60 INDEX PAGES 1. USE 1 2. RANGE 1 3. DIMENSIONS 1 3. DIMENSIONS (continuation) 2 4.

More information

DPX 630 Thermal magnetic and trip-free switches DPX-I 630

DPX 630 Thermal magnetic and trip-free switches DPX-I 630 87045 LIMOGES Cedex Phone :+33 05 55 06 87 87 Fax :+33 05 55 06 88 88 DPX 630 CONTENTS PAGES 1. USE 1 2. RANGE 1 3. DIMENSIONS 1 4. OVERVIEW 2 5. CONNECTION 2 6. ELECTRICAL AND MECHANICAL CHARACTERISTICS

More information

DRX 100 B/N/H Circuit breaker (not adjustable)

DRX 100 B/N/H Circuit breaker (not adjustable) 87045 LIMOGES Cedex Téléphone : 05 55 06 87 87 Télécopie : 05 55 06 88 88 INDEX PAGES 1. USE 1 2. RANGE 1 3. DIMENSIONS 1 3. DIMENSIONS (continuation) 2 4. MOUNTING 2 5. CABLING 3 6. ELECTRIC AND MECHANICAL

More information

6300A 15 Optibreak B1 & B2 Optibreak B1 & B2 50/60 Hz Ue Icu [v] [ka] 415 65 690 40 4h 4i 1. Open / close Indication 2. Charge and Discharge Indicator 3. Release the reset button 4. Laser Nameplate

More information

DRX 250 B/N/H Circuit breaker (not adjustable)

DRX 250 B/N/H Circuit breaker (not adjustable) 87045 LIMOGES Cedex Téléphone : 05 55 06 87 87 Télécopie : 05 55 06 88 88 References rences: /18/19/20/21/22/23/24/25/26/27/28/29/ 32/33 INDEX PAGES 1. USE 1 2. RANGE 1 3. DIMENSIONS 1 4. MOUNTING 2 5.

More information

Circuit breakers and switch-disconnectors NT06 to NT16 and NW08 to NW63

Circuit breakers and switch-disconnectors NT06 to NT16 and NW08 to NW63 Functions and characteristics Circuit breakers and switch-disconnectors NT06 to NT16 and NW08 to NW63 NT and NW selection criteria Masterpact NT Masterpact NW NT06, NT08, NT10, NT12, NT16 NT06, NT08, NT10

More information

(p. 47) (p. 155) (p. 155)

(p. 47) (p. 155) (p. 155) 0 286 56 + 0 288 02 (p. 47) 0 286 74 + 0 288 02 (p. 155) 0 287 56 + 0 288 02 (p. 155) Dimensions see e-catalogue Elecical characteristics p. 162 Automatic air circuit breakers must be equipped with eleconic

More information

New DMX 3. Efficient protection up to A AIR CIRCUIT BREAKERS PRODUCT GUIDE

New DMX 3. Efficient protection up to A AIR CIRCUIT BREAKERS PRODUCT GUIDE New DMX 3 Efficient protection up to 4 000 A AIR CIRCUIT BREAKERS PRODUCT GUIDE NEW DMX 3 ACBs UP TO 4 000 A EFFICIENT PROTECTION AND CONTROL FOR ALL TYPE OF BUILDINGS 02 Electrical panel equipped with

More information

DPX Thermal magnetic and trip-free switches DPX 3 -I 250

DPX Thermal magnetic and trip-free switches DPX 3 -I 250 87045 LIMOGES Cedex Phone :+33 05 55 06 87 87 Fax :+33 05 55 06 88 88 DPX 3 250 Reference(s) : 420 205/ 207/ 208/209/ 215/ 217/ 218/ 219/ 235/ 237/ CONTENTS PAGES 1. USE 1 2. RANGE 1 3. DIMENSIONS 1 3.

More information

DPX earth leakage DPX 3 -I earth leakage

DPX earth leakage DPX 3 -I earth leakage 87045 LIMOGES Cedex Phone :+33 05 55 06 87 87 Fax :+33 05 55 06 88 88 DPX 3 250 + earth leakage Reference(s) : 420 225/ 227/ 228/229/ 255/ 257/ 258/ 259/ 285/ 287/ CONTENTS PAGES 1. USE 1 2. RANGE 1 3.

More information

Overview of Low voltage equipment - Moulded-case & Air circuit-breakers

Overview of Low voltage equipment - Moulded-case & Air circuit-breakers Overview of Low voltage equipment - Moulded-case & Air circuit-breakers Moulded-case circuit-breakers for distribution (1) R16 and R20 Icu = 16 ka @ 220/230 V (2) All the versions with Icu = 35 ka are

More information

Memshield - ACB Ratings & Specifications

Memshield - ACB Ratings & Specifications Memshield Memshield - ACB Ratings & Specifications Rating and specifications Current rating, A List No Number of poles RATED CURRENT (A) [In] IEC, BS, VDE, AS Neutral pole ampere frame (A) RATED PRIMARY

More information

Vistop TM isolating switches 63 to 160A

Vistop TM isolating switches 63 to 160A DX 3 - IS main switches 16 to 125A Vistop TM isolating switches 63 to 160A 225 15 225 18 4 064 00 4 064 59 Pack Cat. No. Main switches AC 22 A category as per EN607-3 Grey handle Accept 1 signalling auxiliary

More information

GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Standard Features

GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Standard Features Standard Features Table : Standard Features GV2ME GV2P GV3P GV7RE/GV7RS 0. to 32 A Up to 20 hp @ 460 V 0 SCCR @ 480 V Push Button Operator 0. to 30 A Up to 5 hp @ 460 V 50 SCCR @ 480 V Rotary Handle Operator

More information

Page. Circuit-Breakers M4 2 for motor protection. Auxiliary contacts 3 Signalling switch Auxiliary releases

Page. Circuit-Breakers M4 2 for motor protection. Auxiliary contacts 3 Signalling switch Auxiliary releases Circuit Breakers M4 Page Circuit-Breakers M4 2 for motor protection Auxiliary contacts 3 Signalling switch Auxiliary releases Insulated 3-pole busbar system 4 Terminal block DIN-rail adapters 5 Busbar

More information

Protection components

Protection components Presentation, characteristics Presentation 1 2 3 motor circuit-breakers are 3-pole thermal-magnetic circuit-breakers standards IEC 60947-2 and IEC 60947-4-1. Connection These circuit-breakers are designed

More information

Thermal magnetic and trip-free switches

Thermal magnetic and trip-free switches 87045 LIMOGES Cedex Phone : 33 05 55 06 87 87 Fax : 33 05 55 06 88 88 DPX 3 1600 Reference(s : 422 250 /251/ 252/ 253/ 254/ 255 /256/ 262/263/ 264/ 265/ 266/ 267/268/ 269/ 270/ 271/ 272/ 273/ 278/ 287/

More information

DPX Thermal magnetic and trip-free switches DPX 3 -I 160

DPX Thermal magnetic and trip-free switches DPX 3 -I 160 87045 LIMOGES Cedex Phone :+33 05 55 06 87 87 Fax :+33 05 55 06 88 88 DPX 3 160 CONTENTS PAGES 1. USE 1 2. RANGE 1 3. DIMENSIONS 1 4. OVERVIEW 2 5. ELECTRICAL AND MECHANICAL CHARACTERISTICS 3 6. CONFORMITY

More information

Essential equipment for all your requirements

Essential equipment for all your requirements NEW CTX CONTACTORS Essential equipment for all your requirements 9 A TO 310 A THREE-POLE INDUSTRIAL CONTACTORS CTX three-pole industrial contactors, a sense of family The new range of CTX contactors provides

More information

DPX 160 Thermal magnetic and trip-free switches DPX-I 160

DPX 160 Thermal magnetic and trip-free switches DPX-I 160 87045 LIMOGES Cedex Phone : +33 05 55 06 87 87 FAX : +33 05 55 06 88 88 DPX 160 CONTENTS PAGES 1. USE 1 2. RANGE 1 3. DIMENSIONS 1 3. DIMENSIONS (NEXT) 2 4. OVERVIEW 2 5. CONNECTION 2 6. ELECTRICAL AND

More information

Power protection solutions

Power protection solutions Power protection solutions DMX A.C.Bs UP TO 4000 A In high power installations, the role of the main enclosure is to: - House protection devices and provide for their connection - Provide management and

More information

DPX Magnetic only

DPX Magnetic only 87045 LIMOGES Cedex Phone :+33 5 55 06 87 87 Fax :+33 5 55 06 88 88 CONTENTS PAGES 1. USE 1 2. RANGE 1 3. DIMENSIONS 1 3. DIMENSIONS (NEXT) 2 4. ELECTRICAL AND MECHANICAL CHARACTERISTICS 3 5. CONFORMITY

More information

Breaking and protection devices

Breaking and protection devices Power guide: A complete set of technical documentation Breaking and protection devices 01 Sustainable development 08 Protection against external disturbances 02 Power balance and choice of power supply

More information

Characteristics of LV circuit breakers Releases, tripping curves, and limitation

Characteristics of LV circuit breakers Releases, tripping curves, and limitation Characteristics of LV circuit breakers Releases, tripping curves, and limitation Make, Withstand & Break Currents A circuit breaker is both a circuit-breaking device that can make, withstand and break

More information

Miniature circuit breakers. Residential current circuit breaker. Busbar systems. Comfort functions/energy control. Residential enclosures

Miniature circuit breakers. Residential current circuit breaker. Busbar systems. Comfort functions/energy control. Residential enclosures .2....6 special versions High performance range H for 000V/AC Circuit breaker for 7V/DC DC circuit breaker up to 0V/DC Miniature circuit breakers A.7.8.0 Technical data Economy range N, V/AC Standard range

More information

MOULDED CASE CIRCUIT BREAKERS BC160N

MOULDED CASE CIRCUIT BREAKERS BC160N D MOULDED CASE CIRCUIT BREAKERS BC160N D BC160N COMMERCIAL INFORMATION Circuit breakers...d4 Switch-disconnectors...D5 Connecting sets......d6 Mounting sets......d6 Switches...D7 Shunt trips...d7 Undervoltage

More information

Low voltage moulded case circuit breaker EB2

Low voltage moulded case circuit breaker EB2 Low voltage moulded case circuit breaker EB2 Product series description unit condition Model-type Number of poles Nominal current ratings Electrical characteristics Rated operational voltage Rated insulation

More information

Circuit-Breakers M4 166 for motor protection. Auxiliary contacts 167 Signalling switch Auxiliary releases

Circuit-Breakers M4 166 for motor protection. Auxiliary contacts 167 Signalling switch Auxiliary releases Index Page Circuit-Breakers M4 166 for motor protection Auxiliary contacts 167 Signalling switch Auxiliary releases Insulated 3-pole busbar system 168 Terminal block DIN-rail adapters 169 Busbar adapters

More information

Introduction. Standard Features. GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Introduction

Introduction. Standard Features. GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Introduction Introduction Introduction Schneider Electric offers a complete line of products for the manual control and protection of motors. This catalog covers those devices designed to meet IEC standards for protection

More information

Selection and Application Guide Supplement. WL UL Pole Circuit Breakers. usa.siemens.com/wlbreaker

Selection and Application Guide Supplement. WL UL Pole Circuit Breakers. usa.siemens.com/wlbreaker Selection and Application Guide Supplement WL UL1066 4-Pole Circuit Breakers usa.siemens.com/wlbreaker WL Power Circuit Breaker Table of Contents Ratings for UL 1066 (ANSI C37) Circuit Breakers Frame size

More information

TeSys contactors. Use in category DC-1 (resistive loads; time constant L/R y 1 ms) Rated operational current Ie. to be wired in series

TeSys contactors. Use in category DC-1 (resistive loads; time constant L/R y 1 ms) Rated operational current Ie. to be wired in series Selection 3-pole shockproof contactors FG d.c. supply Selection guide for utilisation categories DC-1 to DC-5 Use in category DC-1 (resistive loads; time constant L/R y 1 ms) Rated operational current

More information

DPX Electronic + earth leakage

DPX Electronic + earth leakage 87045 LIMOGES Cedex Phone :+33 5 55 06 87 87 Fax :+33 5 55 06 88 88 DPX 3 250 Electronic + earth leakage CONTENTS PAGES 1. USE 1 2. RANGE 1 3. DIMENSIONS 1 3. DIMENSIONS (NEXT) 2 4. ELECTRICAL AND MECHANICAL

More information

Masterpact NW DC Circuit Breakers

Masterpact NW DC Circuit Breakers Masterpact NW DC Circuit Breakers Catalog 0613CT0501 R06/15 2015 Class 0613 CONTENTS Description............................................. Page General Information..........................................

More information

K50H004UP cam changeover switch - 4-pole A - screw mounting

K50H004UP cam changeover switch - 4-pole A - screw mounting Characteristics cam changeover switch - 4-pole - 60-50 A - screw mounting Main Range of product Product or component type Component name [Ith] conventional free air thermal current Mounting location Fixing

More information

FUSOMAT Visible breaking and tripping fuse switches from 250 to 1250 A

FUSOMAT Visible breaking and tripping fuse switches from 250 to 1250 A Fuse protection The solution for > Motor load break > Protection of industrial cabinet > Electrical distribution fusom_063_b_1_cat Strong points > Tripping upon overload > High breaking capacity > Improved

More information

schneider-electric.com/sg K60 Circuit Breakers The affordable way to stay safe from electrocution and electrical overloads schneider-electric.

schneider-electric.com/sg K60 Circuit Breakers The affordable way to stay safe from electrocution and electrical overloads schneider-electric. K0 Circuit Breakers The affordable way to stay safe from electrocution and electrical overloads Overview K0 Circuit Breaker Technical Specification MCB RCCB K0 Circuit Breaker K0N K0H ID K Number of poles

More information

Masterpact NW Circuit breakers and switch-disconnectors from 800 to 6300 A

Masterpact NW Circuit breakers and switch-disconnectors from 800 to 6300 A Low voltage electrical distribution Masterpact NW Circuit breakers and switch-disconnectors from 800 to 6300 A User manual 09/2009 User manual for circuit breakers and switch-disconnectors Masterpact

More information

Thermal-magnetic Miniature Circuit Breaker 4230-T...

Thermal-magnetic Miniature Circuit Breaker 4230-T... Thermal-magnetic Miniature Circuit Breaker 420-T... Description Single pole and multipole thermal-magnetic miniature circuit breakers (MCBs) in accordance with EN 60947-2, UL 077 and UL 489 for DIN rail

More information

Circuit Breakers. Switching & Controls. Selection Guide NC1V Series Dimensions Accessories

Circuit Breakers. Switching & Controls. Selection Guide NC1V Series Dimensions Accessories Switching & ontrols Selection Guide... 922 1V Series... 923 Dimensions... 929 Accessories... 932 ircuit Breakers Switches & Pilot Lights Signaling Lights Relays & Sockets Timers ontactors Terminal Blocks

More information

Low Voltage. EasyPact CVS. Moulded-case circuit breakers from 16 to 100 A

Low Voltage. EasyPact CVS. Moulded-case circuit breakers from 16 to 100 A Low Voltage EasyPact CVS Moulded-case circuit breakers from 16 to 100 A Catalogue 2013 EasyPact CVS Contents Functions and characteristics A-1 Installation recommendations B-1 Dimensions and connection

More information

Circuit Breakers. Switching & Controls. Selection Guide NC1V Series Dimensions...

Circuit Breakers. Switching & Controls.  Selection Guide NC1V Series Dimensions... Switching & ontrols Selection Guide... 1028 1V Series... 1029 Dimensions... 1035 www.ide.com/circuitbreaker ircuit Breakers Switches & Pilot Lights Signaling Lights Relays & Sockets Timers ontactors Terminal

More information

Get detailed information on many digital or printed supports, or contact your Area Commercial Manager

Get detailed information on many digital or printed supports, or contact your Area Commercial Manager The RX 3 and DX-E ranges provide essential functions for the protection requirements of people and property in residential and small commercial buildings Two breaking capacities, 4500 and 6000 (IEC 60898-1)

More information

LEXIC Curv LIMOGES Cedex. Cats N (s) : /68/87/88, /48, /84/85, /76/77/95/96/97, /71/72 1.

LEXIC Curv LIMOGES Cedex. Cats N (s) : /68/87/88, /48, /84/85, /76/77/95/96/97, /71/72 1. 87045 LIMOGES Cedex Téléphone : 05 55 06 87 87 Télécopie : 05 55 06 88 88 LEXIC MCB s DX-H 80A, 100A, 125A Curv urves B and C CONTENTS PAGES 1. Description, use...1 2. Range...1 3. Overall dimensions...1

More information

COMMERCIAL INFORMATION TECHNICAL INFORMATION BA511*33

COMMERCIAL INFORMATION TECHNICAL INFORMATION BA511*33 BA511*33 COMMERCIAL INFORMATION Type designation specification for ordering...146 (design and circuit breaker and switch-disconnector accessories selection, circuit breaker rated current selection) Connecting

More information

VD4/R. Medium Voltage vacuum circuit-breakers for secondary distribution

VD4/R. Medium Voltage vacuum circuit-breakers for secondary distribution VD4/R Medium Voltage vacuum circuit-breakers for secondary distribution DESCRIPTION CIRCUIT-BREAKER SELECTION AND ORDERING SPECIFIC PRODUCT CHARACTERISTICS OVERALL DIMENSIONS ELECTRIC CIRCUIT DIAGRAM

More information

15 16 MCCBs for Power Distribution Technical Specification Frame 100A 250A 250A 400A 400A 630A 800 / 1000 / 1250 Type C DN0-100 D DN1-250 N DN2-250 D N S H DN3B-400 DN3-400 D N D N S V DN3-630 DN4-1250

More information

Moulded case circuit breakers

Moulded case circuit breakers Moulded case circuit breakers CONTENT Range 4 Protection Releases 5 Salient Features 8 Accessories, 4 Technical data 2 Time Current Characteristics 5 Overall Dimensions 7 SN4 SN3 SN2 SN 3 RANGE Moulded

More information

Data sheet. CI-TI TM Contactors and Motor Starters Circuit Breakers CTI B1427

Data sheet. CI-TI TM Contactors and Motor Starters Circuit Breakers CTI B1427 Data sheet CI-TI TM Contactors and Motor Starters Circuit Breakers November 2002 DKACT.PD.C00.L2.02 520B1427 Introduction Circuit breakers/manual motor starters cover the power ranges 0.09-12.5 kw This

More information

Low voltage. Masterpact NT and NW. LV power circuit breakers and switch-disconnectors Draw-out Type & Fixed Type. Catalogue

Low voltage. Masterpact NT and NW. LV power circuit breakers and switch-disconnectors Draw-out Type & Fixed Type. Catalogue Low voltage Masterpact NT and NW LV power circuit breakers and switch-disconnectors Draw-out Type & Fixed Type Catalogue 2015 Functions and characteristics Circuit breakers and switch-disconnectors NT06

More information

Industrial contactors CTX-1

Industrial contactors CTX-1 87045 LIMOGES Cedex Telephone number: +33 5 55 06 87 87 Fax: +33 5 55 06 88 88 Industrial contactors /04/05/10/12/14/15/20/22/24/25/30/32/34/35/40/42/44/45 CONTENTS PAGE 1. Use... 1 2. Range... 1 3. Electrical

More information

Masterpact NW DC Circuit Breakers

Masterpact NW DC Circuit Breakers Masterpact NW DC Circuit Breakers Catalog 0613CT0501R1/07 2007 Class 0613DC CONTENTS Description..............................................Page Contents General Information Line 1.........................................

More information

Low voltage Direct Current Network. Compact NSX DC PV. Circuit breakers and switch disconnectors for solar application.

Low voltage Direct Current Network. Compact NSX DC PV. Circuit breakers and switch disconnectors for solar application. Low voltage Direct Current Network Compact NSX DC PV Circuit breakers and switch disconnectors for solar application Catalogue 2012 Compact NSX DC PV A complete DC offer for solar application from 80

More information

Electronic circuit breaker EBU10-T

Electronic circuit breaker EBU10-T Description The electronic circuit protector type EBU10-T (Electronic Breaker Unit) provides selective overcurrent protection in AC 230 V UPS systems. It consists of an MCB approved for short circuit interruptions

More information

Type CDG 14 Extremely Inverse Time Overcurrent and Earth Fault Relay

Type CDG 14 Extremely Inverse Time Overcurrent and Earth Fault Relay Type DG 14 Extremely Inverse Time Overcurrent and Earth Fault Relay Type DG 14 Extremely Inverse Time Overcurrent and Earth Fault Relay DG 14 drawn out from the case The type DG 14 relay is a heavily damped

More information

125 to 4000 A. Functions. Conformity to standards. Approvals and certifications (1) General characteristics. Available on request

125 to 4000 A. Functions. Conformity to standards. Approvals and certifications (1) General characteristics. Available on request 125 to 4000 A sirco_353_a_1_cat sirco_296_a_1_cat sirco_300_b switches are manually operated or motorised multipolar load break switches. They break on and off under load and provide safety isolation for

More information

DX³ 4-pole RCBO 6000 A/10 ka

DX³ 4-pole RCBO 6000 A/10 ka 87045 LIMOGES Cedex Telephone number: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 DX³ 4-pole RCBO CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation - Connection...

More information

K30H001YP cam star-delta switch - 3-pole A - screw mounting

K30H001YP cam star-delta switch - 3-pole A - screw mounting Characteristics cam star-delta switch - 3-pole - 60-32 A - screw mounting Main Range of product Product or component type Component name [Ith] conventional free air thermal current Mounting location Fixing

More information

Compact NR630. NR100F to NR630F

Compact NR630. NR100F to NR630F Low voltage switchgear Compact NR NR100F NR630F The Compact NS range has revolutionised the world of moulded-case circuit breakers. For installations not requiring the high performance levels of the NS

More information

The breakers offer thermal-magnetic trip protection according to Z and K characteristics.

The breakers offer thermal-magnetic trip protection according to Z and K characteristics. Series High Performance Circuit Breakers Description The high performance MCB offers a compact solution to circuit protection. The devices are DIN rail mounted. The is available with application-specific

More information

Low voltage moulded case circuit breaker EB2

Low voltage moulded case circuit breaker EB2 Low voltage moulded case circuit breaker EB2 Product series description unit condition Model-type Number of poles Nominal current ratings Electrical characteristics Rated operational voltage Rated insulation

More information

Basic function. Rated current. Appropriate for three-phase motors of output 2) [kw] I n. = 400 V a.c. 2) Appropriate for three-phase motors

Basic function. Rated current. Appropriate for three-phase motors of output 2) [kw] I n. = 400 V a.c. 2) Appropriate for three-phase motors MOTOR STARTERS SM Basic function Switching and protection of motors up to A Protection against short-circuit and protection against overload The device responds to phase failure The device is provided

More information

(1,5 modules per pole)

(1,5 modules per pole) 87045 LIMOGES Cedex Telephone: +33 5 55 06 87 87 FAX: +33 5 55 06 88 88 DX 3 MCB 36kA, 80A CONTENTS PAGES 1. Description - Use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation - Connection...

More information

OSS - TN, TBN Type. Information to Order. Features. External View ATS(60~600A) OSS P- A B C D. Rated Current. D Operating Voltage

OSS - TN, TBN Type. Information to Order. Features. External View ATS(60~600A) OSS P- A B C D. Rated Current. D Operating Voltage Information to Order A Rated Current 06 1 60A 100A 2 4 400A 6 600A B Type TN : TN-Type TBN : TBN-Type C Number of Poles 2 : 2P 3 : 3P 4 : 4P OSS - 6 - - P- A B C D D Operating Voltage A1 : AC 110V A2 :

More information

C60H-DC C curve. Catalogue numbers

C60H-DC C curve. Catalogue numbers distriution systems PB104013-34 The supplementary protectors are used in direct current circuits (Industrial control and automations, transport, renewale energy...). They comine the following functions

More information

DATA SHEET FOR 1 TYPE COMPARTMENTALISED / NON - COMPARTMENTALISED. ( a ) CIRCUIT BREAKER FEEDERS FULLY DRAWOUT / NON DRAWOUT

DATA SHEET FOR 1 TYPE COMPARTMENTALISED / NON - COMPARTMENTALISED. ( a ) CIRCUIT BREAKER FEEDERS FULLY DRAWOUT / NON DRAWOUT 44LK-500/E.04/002A/A4 PROJECT NO 44LK-500 CHKD. BY VDV VDV A CLIMATIC CONDITIONS THIS DATA SHEET IS APPLICABLE FOR IN UTILITY BOILER PACKAGE DESIGN AMBIENT TEMPERATURE 45 C 2 ALTITUDE ( ABOVE MSL ) 6.7

More information

MCCB Accessories to suit AF

MCCB Accessories to suit AF MCCB s MCCB Accessories to suit 125-630AF Accessory fitting combinations INTERNAL General purpose types Micro-switch types Auxiliary Heavy duty types Bridge -contact types Auxiliary Shunt UVT Internal

More information

DNX 3 MCB 4500 A / 6 ka Phase + Neutral, neutral on left side

DNX 3 MCB 4500 A / 6 ka Phase + Neutral, neutral on left side 87045 LIMOGES Cedex Telephone number: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 DNX 3 MCB 4500 A / 6 ka CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation

More information

Thermal-Magnetic Circuit Breaker 2210-S291-P9M A

Thermal-Magnetic Circuit Breaker 2210-S291-P9M A Thermal-Magnetic Circuit Breaker 0-S9-P9M-40033-...A Description Single pole thermal-magnetic circuit breaker with trip-free mechanism and toggle actuation. Two-chamber construction with cascade contact

More information

Circuit protection and control devices 0.5 to 6300 A

Circuit protection and control devices 0.5 to 6300 A Electrical distribution Circuit protection and control devices 0.5 to 6300 A LV product characteristics 2009 m TOOLS schneider-electric.com The technical guide This international site allows you to access

More information

Magnum IEC Low Voltage Air Circuit Breakers

Magnum IEC Low Voltage Air Circuit Breakers Magnum IEC Low Voltage Air Circuit Breakers Product Focus Up to 690 Vac 42 ka to 100 ka Icu 800 to 6300 Amperes EN 60947-2 A Global Source for Innovative Electrical Power Distribution Solutions Proven

More information

Practical and completely safe

Practical and completely safe FUSE RRIERS >>> Practical and completely safe Isolating fuse carriers 058 06 058 28 Dimensions (p. 0) onform to standard IE 60269-2/2. and to NF 63-2. Isolators conform to IE 60947-3. Icc: - 20 k with

More information

Section Contents. 1. Introduction 2-5. Salient features, internal & general appearance of Drawout ACB

Section Contents. 1. Introduction 2-5. Salient features, internal & general appearance of Drawout ACB 1 Section Contents PAGES 1. Introduction 2-5 Salient features, internal & general appearance of Drawout ACB 2. Ratings & Specifications 6-9 Free air & enclosed thermal current ratings for AC & DC applications

More information

MV Air Insulated Switchgear TAP17. Technical Data TGOOD

MV Air Insulated Switchgear TAP17. Technical Data TGOOD MV Air Insulated Switchgear TAP17 Technical Data TGOOD 2017.1 Operating environmental conditions Place of installation: Indoor or outdoor Ambient temperature: 25 ~ +40 (higher or lower temperature optional)

More information

SIRCOVER and SIRCOVER BY-PASS. Changeover switches with fully visualised breaking from 125 to 3200 A. 274 General Catalogue SOCOMEC

SIRCOVER and SIRCOVER BY-PASS. Changeover switches with fully visualised breaking from 125 to 3200 A. 274 General Catalogue SOCOMEC and Manual Changeover Switches BY-PSS appli_114_a svr_099_b_1_cat svr_059_a_1_cat Changeover switches with fully visualised breaking from 125 to 3200 Function products are manually operated multipolar

More information

Phase + Neutral, neutral on right side

Phase + Neutral, neutral on right side 87045 LIMOGES Cedex Telephone number: +33 5 55 06 87 87 Fax: +33 5 55 06 88 88 DX 3 MCB 6000 A / 10 ka Cat.. N (s): 4 074 67 / 68 / 69 / 70 / 71 / 72 / 73 / 74 / 75 / 76 / 77 / 78 / 79 ; 4 077 33 / 34

More information

MULTI 9 System Catalog IEC Rated C60N/H/L Circuit Breakers

MULTI 9 System Catalog IEC Rated C60N/H/L Circuit Breakers IEC Rated C60N/H/L Circuit Breakers Standard Features Fast Closing Allows increased withstand to the high inrush currents of some loads Trip-free mechanism: Contacts cannot be held in the on position when

More information

AF40... AF96 3-pole contactors Technical data

AF40... AF96 3-pole contactors Technical data Main pole - Utilization characteristics according to IEC Standards IEC 60947- / 60947-4- and EN 60947- / 60947-4- Rated operational voltage Ue max. 690 V Rated frequency (without derating) 50 / 60 Hz Conventional

More information

PIX-H Metal-clad switchgear up to 17.5kV

PIX-H Metal-clad switchgear up to 17.5kV AIR INSULATED SWITCHGEAR PIX-H Metal-clad switchgear up to 17.5kV for high rated applications Technical Specifications AREVA T&D Summary - Technical description... 3 - Standards... 6 - PIX in detail...

More information

K50F003UP cam changeover switch - 3-pole A - screw mounting

K50F003UP cam changeover switch - 3-pole A - screw mounting Characteristics cam changeover switch - 3-pole - 60-50 A - screw mounting Complementary Main Range of product Product or component type Component name [Ith] conventional free air thermal current Product

More information

K63F003UP cam changeover switch - 3-pole A - screw mounting

K63F003UP cam changeover switch - 3-pole A - screw mounting Characteristics cam changeover switch - 3-pole - 60-63 A - screw mounting Complementary Main Range of product Product or component type Component name [Ith] conventional free air thermal current Product

More information

Overcurrent releases - description, specifications, characteristics specifications specifications description...

Overcurrent releases - description, specifications, characteristics specifications specifications description... BA5*37 COMMERCIAL INFORMATION Type designation specification for ordering...68 (design and circuit breaker and switch-disconnector accessories selection, circuit breaker rated current selection) Connecting

More information

Breakers and Switches. Tmax XT Moulded-case circuit-breakers Simply extraordinary

Breakers and Switches. Tmax XT Moulded-case circuit-breakers Simply extraordinary Breakers and Switches Tmax XT Moulded-case circuit-breakers Simply extraordinary Tmax XT Simply extraordinary ABB is proud to present you the result of a long and intense research and development project:

More information

DPX Electronic. Fiche technique : F01362EN/02 Mise à jour le : 15/12/2011 Créé le : 15/06/2011

DPX Electronic. Fiche technique : F01362EN/02 Mise à jour le : 15/12/2011 Créé le : 15/06/2011 87045 LIMOGES Cedex Phone :+33 5 55 06 87 87 Fax :+33 5 55 06 88 88 DPX 3 250 Electronic Reference(s): 420 302/305/307/309/312/315/317/319/332/335/ CONTENTS PAGES 1. USE 1 2. RANGE 1 3. DIMENSIONS 1 3.

More information

up to 63 A (1 module per pole)

up to 63 A (1 module per pole) 87045 LIMOGES Cedex Telephone: +33 5 55 06 87 87 FAX: +33 5 55 06 88 88 Direct current MCB DX 3 16kA, up to 63 A (1 module per pole) CONTENTS PAGE 1. Description - Use... 1 2. Range... 1 3. Overall dimensions...

More information

AF09... AF30 3-pole Contactors up to 25 HP / 600 VAC

AF09... AF30 3-pole Contactors up to 25 HP / 600 VAC AF09... AF0 -pole Contactors up to 25 HP / 600 VAC Contactors and Overload Relays Overview.../0 AF09... AF0 -pole Contactors.../2 Main Technical Data.../8 Main Accessory Fitting Details.../2 Main Accessory.../24

More information