Cargill Power Markets LLC Transmission Service Study (OASIS # TSR and )

Size: px
Start display at page:

Download "Cargill Power Markets LLC Transmission Service Study (OASIS # TSR and )"

Transcription

1 Cargill Power Markets LLC Transmission Service Study (OASIS # TSR and ) Prepared by: Electric Power Research Institute (EPRI) Under contract with: Public Service Company of New Mexico April 10, 2014

2 Foreword This report was prepared for Cargill Power Markets LLC by the Electric Power Research Institute, Inc., ( EPRI ) pursuant to a consulting contract with Public Service Company of New Mexico ( PNM ) Transmission Operations. This document was prepared by EPRI for PNM. Neither EPRI, PNM, any member of EPRI, any cosponsor, nor any person acting on behalf of any of them: (a) makes any warranty or representation whatsoever, express or implied, (i) with respect to the use of any information, apparatus, method, process, or similar item disclosed in this document, including merchantability and fitness for a particular purpose, or (ii) that such use does not infringe on or interfere with privately owned rights, including any party's intellectual property, or (iii) that this document is suitable to any particular user's circumstance; or (b) assumes responsibility for any damages or other liability whatsoever (including any consequential damages, even if EPRI or any EPRI representative or PNM or any PNM representative has been advised of the possibility of such damages) resulting from your selection or use of this document or any information, apparatus, method, process, or similar item disclosed in this document. Any correspondence concerning this document, including technical and commercial questions should be referred to: Director, Transmission/Distribution Planning and Contracts Public Service Company of New Mexico 2401 Aztec Road, Z220 Albuquerque, NM Phone: (505) Fax: (505) iii

3 EXECUTIVE SUMMARY This Transmission System Impact Study ( Study ) report documents technical studies performed by Electric Power Research Institute, Inc., pursuant to a consulting contract with Public Service Company of New Mexico ( PNM ) for Cargill Power Markets LLC ( Transmission Customer ). The study was performed in accordance with a Study Agreement between PNM and Transmission Customer executed on January 17, 2014 for Transmission Service Requests ( TSR ) and (studied as a single clustered MW and 100 MW). Transmission Customer requested 128 MW of long-term firm transmission service ( TSR ) on the PNM transmission system between the Blackwater 345 KV station point of receipt and the Four Corners switchyard 345 kv point of delivery in the Arizona Public Service ( APS ) Balancing Authority Area ( Transmission Path ). A portion of the Transmission Path for this transmission service will be transmitted on PNM s 216-mile, 345 kv transmission line between Blackwater and BA stations. Due to engineering considerations, a transmission line of this length can require that measures be taken to control the voltage profile along the length of the line. By way of example, control of voltage near the midpoint of the line required installation of line shunt reactors at the Guadalupe switching station when this line was first commissioned. The Blackwater to BA 345 kv transmission line is thermally limit at 1076 MW, but due to other limiting factors lack of voltage support and equipment limitations the line is limited to less than the line s thermal capacity. Based on current transmission service commitments, delivery of designated network resource, PNM has reached its full amount of capacity that it can commit of 662 MW (does not include line losses) on the Blackwater to BA 345 kv line. This 662 MW level was determined, by previous study work, to be due to a voltage stability limit (using a 5% margin from the all-lines in-service, N-0, limit). As such, it is anticipated, based on previous study analysis, that a static VAR compensator (SVC) at the Guadalupe station will be required to provide the required voltage support. Thus, PNM engaged Electric Power Research Institute, Inc., ( EPRI ) to determine the necessary transmission upgrades to provide firm transmission service to accommodate the 128 MW TSR at Blackwater 345 kv station for a total of 790 MW (does not include line losses) on the Blackwater to BA 345 kv transmission line. The steady-state and dynamic simulations have shown that in order to allow for an additional 128 MW of injection at Blackwater a significant amount of reactive support is needed, namely a +175 / -75 MVAr SVC at Guadalupe driven by essentially the loading on this long radial line. All voltage support devices from BA station and onwards into the PNM transmission system have negligible effect on the ability to support MW injections from the Blackwater end. The transmission system upgrades required to accommodate the TSR at full output are summarized in the table below. The corresponding costs, as estimated by PNM, and construction time estimates are provided.

4 Transmission System Upgrade Cost Construction ($M) Time SVC +175/-75 MVAr months Expand Guadalupe Station 345 kv for SVC interconnection (3 Breakers) months Replace BA and Blackwater wavetraps months Remedial Action Scheme (RAS) months Total months Guadalupe Station SVC One Line design v

5 CONTENTS 1 INTRODUCTION STUDY CRITEIRA Thermal and Voltage Criterion Transient Stability Performance Standard Voltage Stability MODELING ASSUMPTIONS System Modeling Steady-State Analysis Contingencies SIMULATION RESULTS Steady-State QV Analysis Steady-State PV Analysis Time-Domain Simulations CONCLUSIONS AND RECOMENDATIONS REFERENCES A QV AND PV PLOTS... A-1 B TIME-DOMAIN SIMULATION PLOTS... B-1 OASIS # TSR and vii

6 1 INTRODUCTION This Transmission System Impact Study ( Study ) report documents technical studies performed by Electric Power Research Institute, Inc. ( EPRI ), pursuant to a consulting contract with Public Service Company of New Mexico ( PNM ) for Cargill Power Markets LLC ( Transmission Customer ). The study was performed in accordance with a Study Agreement between PNM and Transmission Customer executed on January 17, Transmission Customer requested 200 MW of long-term firm transmission service ( TSR ) on the PNM transmission system between the Blackwater 345 KV station point of receipt and the Four Corners switchyard 345 kv point of delivery in the Arizona Public Service ( APS ) Balancing Authority Area ( Transmission Path ). The request is for a five-year term of service commencing January 1, 2012 and ending January 1, PNM was able to provide 172 MW of transmission service on the Transmission Path resulting in 28 MW that PNM could not accommodate. Transmission Customer also has the next in queue TSR for 100 MW (TSR ) of longterm firm transmission service on the same Transmission Path for a period of five (5) years commencing on January 1, 2012 and terminating on January 1, Transmission Customer requested the remaining 28 MW TSR and the 100 MW TSR be studied as a single clustered. A portion of the Transmission Path for this transmission service will be transmitted on PNM s 216-mile, 345 kv transmission line between Blackwater and BA stations. Due to engineering considerations, a transmission line of this length can require that measures be taken to control the voltage profile along the length of the line. By way of example, control of voltage near the midpoint of the line required installation of line shunt reactors at the Guadalupe switching station when this line was first commissioned. The total thermal capacity of the Blackwater to BA 345 kv transmission line is 1076 MW. It should be noted, however, that typically most high-voltage transmission lines, and certainly this line, are limited by other factors such as stability, equipment limitations, and voltage control which present a real limit lower than the line s thermal capacity. Based on current commitments for transmission service, delivery of designated network resource, PNM has reached its full amount of capacity that it can commit of 662 MW (does not include line losses) on the Blackwater to BA 345 kv line (see Figure 1-1 below). This 662 MW level was determined, under a previous study, to be voltage stability limited (using a 5% margin from the all-lines in-service, N-0, limit). OASIS # TSR and

7 Figure 1-1: Transmission commitments on the Blackwater-BA 345kV Line The objective of the Study is to determine the necessary transmission upgrades to provide firm transmission service to accommodate the additional 128 MW TSR at Blackwater 345 kv station for a total of 790 MW (does not include line losses) on the Blackwater to BA 345 kv transmission. Based on previous study analysis, a static VAR compensator (SVC) at the Guadalupe station will be required to provide the required voltage support. Thus, PNM engaged with EPRI to study this scenario and to determine the preliminary size for the voltage support device. This report is organized into the following sections: Section 2 provides the study criteria Section 3 provides a brief overview of the models used and modeling assumptions. Section 4 provides an overview of the simulations performed. Section 5 provides an overall summary of the conclusions and recommendations. The SVC size is based on the assumption that the 300 MW of total injection at Blackwater is a wind generator that utilizes either a type 3 or 4 technology with enough reactive capability to be able to maintain at least unity power factor at the point of interconnection at the Blackwater 345 kv interconnection. 1-2

8 2 STUDY CRITEIRA 2.1 Thermal and Voltage Criterion The steady-state performance criteria applicable to powerflow analysis in the DISIS are shown in Table 2. The criteria are NERC/WECC performance requirements as well as applicable additions and exceptions for the New Mexico transmission system. Table 1. Power Flow Performance Criteria Area Conditions Loading Limits Voltage (p.u.) Voltage Drop Application kV and above Artesia 345 kv EPEC (Area 11) PNM (Area 10) Arroyo 345 kv PST source side Alamo, Sierra Blanca and Van Horn Normal < Normal Rating kV % 60 kv to 115 kv % Artesia 345kV % Arroyo 345kV PST source side Alamo, Sierra Blanca and Van Horn kV Contingency < Emergency Rating % Hidalgo, Luna, or other 345 kv buses 46 kv and above* Normal ALIS < Normal Rating ^ 6 %** 46 kv to 115 kv Contingency N-1 < Emergency Rating ^ 6 %** 230 kv and above Contingency N-2 < Emergency Rating ^ 10 % 46 kv and above* Normal ALIS < Normal Rating All buses Tri- State (zones ) % Contingency N-1 < Emergency Rating % Contingency N-2 < Emergency Rating % All buses 69 kv and above except Northeastern NM and Southern NM 69 kv and above in Northeastern NM and Southern NM *Taiban Mesa and Guadalupe 345 kv voltage 0.95 and 1.1 p.u. under normal and contingency conditions. **For PNM buses in southern New Mexico (Zones 104,130, 131, and 132), the allowable N-1 voltage drop is 7%. ^ Provided operator action can be utilized to adjust voltages back down to 1.05 pu All equipment loadings must be below their normal ratings under normal conditions the emergency ratings for both single and double contingency conditions. Additional reactive power support may also be required to comply with the stability performance criteria. 2.2 Transient Stability Performance Standard The NERC/WECC transient stability performance requirements for transmission contingencies are as follows: All machines will remain in synchronism. All voltage swings will be well damped. OASIS # TSR and

9 Following fault clearing for single contingencies, voltage on load buses may not dip more than 25% of the pre-fault voltage or dip more than 20% of the pre-fault voltage for more than 20 cycles. For N-2 and breaker failure contingencies, voltage on load buses may not dip more than 30% of the pre-fault voltage or dip more than 20% of the pre-fault voltage for more than 40 cycles Fault clearing times used in this study are shown in Table 3. Table 2 PNM Fault Clearing Times Fault Type Voltage (kv) Clearing Time (near-far end breakers) Cycles Cycles Cycles 3 Phase Normally Cleared Fault Type 1 Phase Stuck Breaker Voltage Clearing Time (normally opened breaker both near and far (kv) end breaker opened due to stuck breaker both near and far end Cycles Cycles 2.3 Voltage Stability The voltage stability limit will be determined by the maximum reactive margin (QV) and maximum loadability (PV). The voltage stability limit is defined as the maximum transfer MW value at 0 MVAr margin for V-Q analysis or 0 MW margin for P-V analysis divided by 1.05 for n-1 outages. 2-2

10 3 MODELING ASSUMPTIONS This section gives an account of the models used and the modeling assumptions made for the analysis presented in section System Modeling The following WECC models were provided by PNM as a starting point for the study: 1. rev-bc.sav the powerflow case 2. typ2015hw_01.dyd the corresponding dynamics data for the powerflow case Both files were provided in GE PSLF TM format. For this work GE PSLF TM version was used. The base case powerflow is shown in Figure 2-1. In order to prepare the case for the study the following modifications were taken: The collector model for the Transmission Customer 172 MW Wind Turbine Generators ( WTGs ) at Blackwater 345 kv was slightly refined to reflect a typical expected collector system for a wind power plant of that size, namely: 1. Assuming 118, 1.5 MW wind turbine generator (WTG) at 1.67 MVA each 2. Assuming each WTG step-up transformer to be 1.75 MVA with an impedance of j pu 3. Assuming the collector system to be j / j 0.08 pu on 100 MVA (this is based on appropriately scaling the equivalent collector model from Taiban Mesa) 4. Assuming an 8% on 100 MVA substation-transformer with an X/R ratio of This wind power plant is assumed to have a power factor capability of +/ pf at the turbines and to hold close to unity power factor at the point of common coupling without controlling the voltage. The turbines were assumed to be type 3 WTGs. 6. The typical Low Voltage Ride Through ( LVRT") settings for the GE 1.5 MW WTGs was assumed for the units (the same as for Taiban Mesa). Adding the Additional 128 MW Injection: For the proposed additional 128 MW injection at Blackwater, a second WTG power plant composed of MW WTGs in parallel to the existing WTGs was simulated The same modeling assumptions are used as for the original 172 MW injection. The additional 128 MW were dispatched against the San Juan generation. The case with this additional injection is shown in Figure 3-2 note, an SVC at Guadalupe is required to solve the all-lines-in-service case. Important Note: Presently, the major manufacture of type 2 WTGs has ceased to offer this product anymore to the international market. Furthermore, type 1 WTGs although still sold by OASIS # TSR and

11 several vendors, in general, are not being deployed in either the North American or European markets. As such, the analysis here is based on a type 3 WTGs with constant power factor control. It is extremely important to realize that the results here are highly dependent on these assumptions. Should the customer in the end decide to go with type 1 WTGs it is almost certain that a second dynamic reactive device such as a large SVC or STATCOM will be required by the Transmission Customer as part of the WTGs facilities. 3.2 Steady-State Analysis Analysis was performed to determine the maximum reactive margin (QV) and maximum loadability (PV) the acceptable voltage stability limits. For the purposes of the QV analysis the same models as discussed above were used. For the purposes of the PV analysis the following assumptions were made: 1. Real power was injected in increments of 5 MW (i.e. 5 MW, then 10 MW, etc.) at unity power factor (i.e. 0 MVAr for all injection levels) at the Blackwater 345 kv bus. 2. The PNM swing bus at San Juan (near Four Corners) was allowed to absorb the injected power so that the power is essentially being transferred from Blackwater, through BA to the Four Corners area. 3.3 Contingencies PNM currently uses single-pole switching to allow the BA to Blackwater 345 kv line to remain in service for temporary single-phase-to-ground faults. From a transient stability perspective this is a much less severe event than 3-phase faults at the BA end of the BA Norton or BA Rio Puerco lines and tripping of those lines. Furthermore, 3-phase faults on the BA Blackwater line (certainly on the portion between Taiban Mesa to Blackwater) will lead to clearing of the line and tripping of all elements (generation and HVDC) on the line, since these devices cannot operate in an island with no load and large amounts of MW injection. Thus, these scenarios were not investigated. However, it should be understood that Transmission Customer is responsible for ensuring adequate islanding protection to transfer trip all the turbines in the wind power plants following such a scenario to avoid damage of their equipment under an islanding scenario and potential consequential damage to the transmission equipment. Thus, the main transmission contingencies that are likely to be onerous for the proposed MW injection at Blackwater are: 1. BA to Rio Puerco 345 kv 2. BA 345/115 kv Transformer 3. BA to Norton 345 kv 4. Rio Puerco West Mesa 345 kv 5. Rio Puerco San Juan 345 kv 6. Rio Puerco Four Corners 345 kv These are the contingencies that were focused on in this study. 3-4

12 Figure 3-1: Base case powerflow. OASIS # TSR and

13 Figure 3-2: Powerflow case including the New Wind plant of 128 MW at Blackwater. 3-6

14 4 SIMULATION RESULTS The results of the steady-state and dynamic simulations are reported in this section. Note: The BA to Blackwater 345 kv line has wavetraps installed at the BA and Blackwater stations. These series devices have a continuous rating of 717 MVA (1200 A). These devices would need to be replaced to handle the additional 128 MW power injection at Blackwater. The analysis here assumes this change. 4.1Steady-State QV Analysis QV analysis was performed first to look at the reactive margin at both Guadalupe and Blackwater 345 kv substations for the all-lines in-service (N-0) and the four N-1 scenarios listed in section 3.3. The QV plots are provided in Appendix A. The results are summarized in Table 4-1. From these results the following can be discern: 1. The amount of reactive support needed would be slightly less at Blackwater as compared to Guadalupe. 2. The base case (with 172 MW of injection at Blackwater) is only marginally stable for many of the outages out of Rio Puerco. In fact a simple power flow solution attempt will show that the case diverges and is thus very close to instability. 3. To achieve the required 300 MW injection at Blackwater at least 127 MVAr of injection at Guadalupe is required to maintain stability, and at least 155 MVAr to maintain a reasonable voltage profile on the BA-Blackwater line. This is based on the worst outage (Rio Puerco to San Juan RP-SJ or Rio Puerco to West Mesa RP - WM). 4. For the Rio Puerco to San Juan outage (RP-SJ) the QV curve at Blackwater has quite a high-voltage nose. That is, instability occurs around 1.05 pu. This suggests that regulating voltage for this scenario with a reactive supporting device at Blackwater may be more difficult. Table 4-1: Results of QV analysis. A negative margin means that the case is stable and has those VArs in reserve, while a positive number means the case in unstable and requires that many VArs to acquire a solution. Guadalupe 345 kv (172 MW injection at BW) Guadalupe 345 kv (300 MW injection at BW) Contingency Reactive Margin Reactive Margin Reactive Need for 1.04 pu Voltage N MVAr 111 MVAr 147 MVAr BA - RP 0 MVAr 124MVAr 156 MVAr BA 345/115 TX -3 MVAr 121 MVAr 155 MVAr BA - NR 0 MVAr 125 MVAr 160 MVAr RP - WM -4 MVAr 120 MVAr 154 MVAr RP - SJ 0 MVAr 127 MVAr 155 MVAr RP - FC 3 MVAr 116 MVAr 144 MVAr Blackwater 345 kv (172 MW injection at BW) Blackwater 345 kv (300 MW injection at BW) Contingency Reactive Margin Reactive Margin Reactive Need for 1.04 pu Voltage N MVAr 87 MVAr 100 MVAr BA - RP 0 MVAr 102 MVAr 112 MVAr BA 345/115 TX -2 MVAr 98 MVAr 108 MVAr BA - NR 0 MVAr 109 MVAr 111 MVAr RP - WM -2 MVAr 95 MVAr 106 MVAr RP - SJ 0 MVAr 143 MVAr 147 MVAr RP - FC 2 MVAr 100 MVAr 108 MVAr 4-7

15 4.2 Steady-State PV Analysis The WECC planning criteria for voltage stability [1] requires that the loading level of an interface be no more than 95% of the collapse point of the PV curve for the worst N-1 outage. In this present case under study this translates to the following: all else remaining the same, the amount of MW injected at Blackwater that can be served is 95% of the value which will cause divergence of the powerflow solution under the worst N-1 outage condition. Thus two PV scenarios were simulated: 1. Starting with the base case the Transmission Customer plant was removed and instead a generator was used at the Blackwater 345 kv bus with zero MVAr output. The MW output of this generator was incrementally increased (in 5 MW increments) until the system powerflow solution diverged for each of the four N-1 contingencies in section 3.3. The PNM area swing, San Juan, absorbed the power injection, thus the power was transferred from Blackwater to the Four Corners area. 2. Ran the same case above, this time with a +175 / -75 MVAr SVC at Guadalupe. The simulation results are shown in Appendix A. The goal of this study is to determine the reactive compensation need at Guadalupe to accommodate the 128 MW TSR at Blackwater 345 kv station for a total of 790 MW (does not include line losses) on the Blackwater to BA 345 kv transmission line. As mentioned above the actual MW injection capability is equal to 95% of the value at which the PV curve diverges that is a powerflow solution is no longer achievable. The PV plots in Appendix A thus show two dashed vertical lines on each plot: 1. A dashed red line that represented the desired injection level; 172 MW without the SVC at Guadalupe and 300 MW with the SVC 2. A dashed magenta line at 95% of the PV nose, based on the WECC criteria The worst outage is the Rio Puerco West Mesa 345 kv line; based on the PV results. For this outage, based on the WECC criteria, based on steady-state analysis, for a total of 300 MW of injection at Blackwater, in addition to the existing 200 MW from the HVDC, and with the additional 90 MW of injection at Guadalupe and 200 MW at Taiban Mesa (for a total MW injection of 790 MW at BA, excluding losses) a +175 MVAr voltage support device is needed at Guadalupe. Based on the dynamic simulations, and operating experience of PNM, this reactive supporting device needs to be a smoothly controlled shunt reactive compensation device. To achieve true smooth control the device needs to be a static var compensator (SVC) with a thyristor controlled reactor (TCR). SVCs that incorporate only thyristor switched capacitors are not capable of smooth vernier control, they are discrete devices. Furthermore, if a TCR based SVC is to be implemented then it makes sense from an operational stand point to include some inductive range for potential overvoltage conditions during light load scenarios and when the wind power plant is off-line. The marginal cost of this additional inductive range is minimal since the TCR is needed anyway for smooth regulation. For outage of the SVC, there would not be enough time for operator intervention to curtail transfers on the BA to Blackwater 345 kv line. A Remedial Action Scheme (RAS) will be required to trip the Guadalupe to Blackwater 345 kv line, to alleviate all stability problems 4-8

16 associated with the SVC outage. Powerflow analysis confirms this result and a time domain simulation also demonstrates this result as shown in the next section. It should be noted that an SVC solution at Blackwater was not considered. Although, the QV analysis showed that a slightly smaller amount of reactive compensation might be needed at Blackwater, none-the-less, the more technically sound location appears to be Guadalupe. The reason for this is twofold: 1. As indicated in the QV analysis results for at least one of the cases the nose of the QV curve is at a very high-voltage (1.05 pu), which is indicative of voltage instability at highvoltages and thus difficultly regulating voltage with a reactive supporting device at Blackwater. 2. With an SVC at Guadalupe the overall BA to Blackwater 345 kv line voltage profile is much better than with the SVC at Blackwater. This is illustrated by the steady-state powerflow solutions shown in Figures 4-1 and 4-2, respectively. In these figures the voltage profile on the line is shown for one of the worst contingencies (Rio Puerco to West Mesa) for the case of the SVC being placed at the two alternative locations. Clearly, for the case of the SVC at Guadalupe the voltage profile across the line is better and more flat (i.e. roughly the same from BA to Blackwater). 4-9

17 Figure 4-1: Steady-state solution for new wind case (i.e. 300 MW injection at Blackwater) with an SVC at Guadalupe and a Rio Puerco to West Mesa 345 kv line out of service. 4-10

18 Figure 4-2: Steady-state solution for new wind case (i.e. 300 MW injection at Blackwater) with an SVC at Blackwater and a Rio Puerco to West Mesa 345 kv line out of service. 4-11

19 4.3Time-Domain Simulations Time domain simulations were performed on the base case (i.e. no SVC at Guadalupe and 172 MW of injection from Transmission Customer generator at Blackwater) and the new wind injection case (i.e / -75 MVAr SVC at Guadalupe MW of injection from wind power plants at Blackwater). Two outages were simulated, namely the BA to Norton 345 kv and the Rio Puerco to West Mesa 345 kv line outage. The latter was determined to be the worst outage from the PV analysis. A total of six simulations (pre- and post-128 MW injection) were performed, as follows: 1. Outage of BA to Norton 345 kv line with a 3-phase fault at the BA side, fault clears in 4 cycles. 2. Outage of Rio Puerco to West Mesa 345 kv line without a fault, just opening the line. 3. Outage of Rio Puerco to West Mesa 345 kv line with a 3-phase fault at Rio Puerco, fault clears in 4 cycles. For the SVC at Guadalupe the svsmo1 model [2], which is the latest WECC approved model for SVCs, was used. Typically parameters were used for the SVC settings. For now it was assumed that the SVC does not have a slow-susceptance regulator or coordinated MSC/MSR switching. However, should this device be pursued such additional features would be prudent and can be easily added. At the very least the SVC can be designed to automatically control the shunt reactors at Guadalupe. The results of the simulations are shown in Appendix B. Table 4-2 summarizes the results. It can be seen clearly that the addition of the SVC ensures stability up to the 300 MW injection level. Consider Figure 4-1. In this figure is shown the 345 kv voltages at BA, Guadalupe, Rio Puerco and Blackwater for four (4) different simulations: 1. With the SVC in-service blue line, 2. The SVC is tripped at 1 second red dashed-line, 3. The SVC is tripped at 1 second and the line from Guadalupe to Blackwater (and all connected equipment) is tripped 12 cycles later black dashed-line 4. As above (case 3) with the additional action that the 65 MVAr shunt reactor at Guadalupe is switched in with the RAS magenta dashed-line. All these cases are with at the 300 MW injection level at Blackwater 345 kv station. What can be observed from the figure is as follows: The case with the SVC is stable and flat. Once the SVC trips the case is unstable. When the SVC trips the line becomes unstable (red dashed-line); however, by tripping the entire Guadalupe to Blackwater 345 kv line in this case we are able to ensure stability for the rest of the system. This is why a RAS scheme is needed to trip the line in the event of the loss of the SVC. In the case with the RAS implemented, the final steady-state voltage at Guadalupe is slightly high (above 1.05 pu). However, this can be easily remedied, if desired, by switching in one of the Guadalupe shunt reactors at the same time as switching out the 4-12

20 Guadalupe to Blackwater 345 kv line. This is illustrated by the last simulation shown by the magenta dashed-line. Figure 4-3: Simulations for (i) blue line with SVC, (ii) red dashed-line SVC tripped, (iii) black dashed-line SVC tripped and RAS implemented, and (iv) magenta dashed-line SVC tripped, RAS implemented, and one Guadalupe reactor switched in

21 Table 4-2: Results of time-domain simulations Wind MW Total MW Injection at Injection at Clearing Case Name Blackwater BA Disturbance Fault Time System Response bcbr3p BA - Norton 345 kv BA 4 cycles System is stable bcrw Rio Puerco - West Mesa 345 kv no fault N/A System is stable bcrw3p Rio Puerco - West Mesa 345 kv RP 4 cycles System is stable bcnwsvcbr3p BA - Norton 345 kv BA 4 cycles System is stable bcnwsvcrw Rio Puerco - West Mesa 345 kv no fault N/A System is stable bcnwsvcrw3p Rio Puerco - West Mesa 345 kv RP 4 cycles System is stable 4-14

22 5 CONCLUSIONS AND RECOMENDATIONS Presently, PNM has committed 626 MW of transfer capability on the Blackwater to BA 345 kv line, with 200 MW injected by the HVDC at Blackwater, 90 MW injected at Guadalupe by the Aragonne Mesa wind power plant, 200 MW injected at Taiban Mesa by the Lone Mesa wind power plant and 172 MW of injection at Blackwater by the Transmission Customer project. The purpose of this study was to determine the necessary transmission upgrades to provide firm transmission service to accommodate the 128 MW of injection at Blackwater. The analysis has shown that in order to allow for a further 128 MW of injection at Blackwater a significant amount of reactive support is needed, namely a +175 / -75 MVAr SVC at Guadalupe driven by essentially the loading on this long and radial line. All voltage support devices from BA station and onwards into the PNM transmission system have negligible effect on the ability to support MW injections from Blackwater. The SVC size is based on the assumption that the 300 MW of total injection at Blackwater will come from wind generation that utilizes either a type 3 or 4 technology with enough reactive capability to be able to maintain at least unity power factor at the point of common coupling at the 345 kv interconnection. It should also be noted that the STATCOM at Argonne Mesa wind power plant exhibits some somewhat strange behavior during the course of system dynamic response, in all the cases, which leads to some rather large voltage swings at that wind power plant. It s unclear if this is real (i.e. the control strategy of the device is truly so erratic) or it is a problem with the user-written model. There are two other insights that may be gleaned from a perusal of the results and a careful look at the steady-state and dynamic response of the BA Blackwater line: There are many dynamic devices on this line. The HVDC at Blackwater, which has an ac voltage control loop. The wind power plant at Taiban Mesa, which regulates the voltage at Taiban Mesa using the GE WindVAR system. The shunt reactors at Guadalupe. The STATCOM at Argonne Mesa. The eventual new wind power plants at Blackwater, and finally the proposed new SVC at Guadalupe. All these devices are also trying to in one way or another regulate voltage on the same line, admittedly at different points of the line. This is thus very complicate system. It is essential that a close look be taken at ensuring that all these devices are properly coordinated and a clear operating strategy is put into place on how to coordinate the voltage set-point on all these devices so that they do not fight each other nor lead to unintended consequences. Three of the four sources of MW injection on the line are from wind power plants. This clearly means that the MW levels on the line are continuously varying. As such, a smoothly controllable device such as an SVC is much more preferable than discretely switched capacitor banks for the reactive support at Guadalupe. This is because operationally the SVC can automatically regulate itself as the wind power levels go up and down hourly and daily, as opposed to constantly switch devices in and out all day and thereby causing excessive wear on the switching devices. Furthermore, switched devices may not be fast enough to response following severe disturbances. 5-1

23 If even more MW injection is sought in the future at Blackwater, a serious consideration should be given to having two coordinated dynamic reactive support devices (e.g. SVCs) at Guadalupe and Blackwater, and allowing those two devices to solely control and regulate the voltage at these points. This would markedly simplify the operational aspects of voltage regulation on the line, as well as be more technically sound since once the MW injection goes significantly higher it is not feasible to assume that a larger device at Guadalupe will be capable of ensure proper voltage regulation at Blackwater where the MWs are being injected. The transmission system upgrades required to accommodate the TSR at full output are summarized in Table 5-1 below. The corresponding costs, as estimated by PNM, and construction time estimates are provided. Table 5-1 Transmission System Upgrades Transmission System Upgrade Cost Construction ($M) Time SVC +175/-75 MVAr months Expand Guadalupe Station 345 kv for SVC interconnection (3 Breakers) months Replace BA and Blackwater wavetraps months Remedial Action Scheme (RAS) months Total months Guadalupe Station SVC One Line design A-5-2

24 6 REFERENCES [1] WECC Voltage Stability Criteria, Undervoltage Load Shedding Strategy, and Reactive Power Reserve Monitoring Methodology, Approved April 28, 2010; %20Stability%20Criteria%20-%20Guideline.pdf [2] Generic Static Var System Models for the Western Electricity Coordinating Council, April 18th, Documents/GenericStaticVarSystemModelsforWECC.pdf 6-1

25 A QV AND PV PLOTS QV Plots Base Case 172 MW Injection at Blackwater: A-1

26 A-2

27 A-3

28 A-4

29 QV Plots New Case with 300 MW total Injection at Blackwater: A-5

30 A-6

31 A-7

32 PV Plots Base Case 172 MW Injection at Blackwater: A-8

33 A-9

34 A-10

35 PV Plots New Case with 300 MW total Injection at Blackwater: A-11

36 A-12

37 A-13

38 A-14

39 B TIME-DOMAIN SIMULATION PLOTS B-1

40 Time( sec ) vbug B-A vbug GUADLUPE vbus WESTMESA vbus RIOPUERC vbug BLACKWTR vbug TAIBANMS SPP 2000SC MODEL. 2001CASE 8/14/ Winter Post-project Case 3-Phase fault on B-A-Norton 345 kv line at B-A 345 kv; Trip B-A-Norton 345 kv line in 4 cycles. bcbn3p.chf Page 1 C:\MyProjects\PSAS\PNM Wed Mar 26 01:07:

41 Time( sec ) pg LONEMS pg ARGONNEG pg TRANS_WIND paci SPS EQ SPP 2000SC MODEL. 2001CASE 8/14/ Winter Post-project Case 3-Phase fault on B-A-Norton 345 kv line at B-A 345 kv; Trip B-A-Norton 345 kv line in 4 cycles. bcbn3p.chf Page 1 C:\MyProjects\PSAS\PNM Wed Mar 26 01:07:

42 Time( sec ) qg LONEMS qg ARGONNEG qg TRANS_WIND qaci SPS EQ SPP 2000SC MODEL. 2001CASE 8/14/ Winter Post-project Case 3-Phase fault on B-A-Norton 345 kv line at B-A 345 kv; Trip B-A-Norton 345 kv line in 4 cycles. bcbn3p.chf Page 1 C:\MyProjects\PSAS\PNM Wed Mar 26 01:07:

43 Time( sec ) vt LONEMS vt ARGONNEG vt TRANS_WIND vt SPP 2000SC MODEL. 2001CASE 8/14/ Winter Post-project Case 3-Phase fault on B-A-Norton 345 kv line at B-A 345 kv; Trip B-A-Norton 345 kv line in 4 cycles. bcbn3p.chf Page 1 C:\MyProjects\PSAS\PNM Wed Mar 26 01:07:

44 Time( sec ) vbug B-A vbug GUADLUPE vbus WESTMESA vbus RIOPUERC vbug BLACKWTR vbug TAIBANMS SPP 2000SC MODEL. 2001CASE 8/14/ Winter Post-project Case Trip Rio Puerco - West Mesa line in 4 cycles bcrw.chf Page 1 C:\MyProjects\PSAS\PNM Wed Mar 26 01:07:

45 Time( sec ) pg LONEMS pg ARGONNEG pg TRANS_WIND paci SPS EQ SPP 2000SC MODEL. 2001CASE 8/14/ Winter Post-project Case Trip Rio Puerco - West Mesa line in 4 cycles bcrw.chf Page 1 C:\MyProjects\PSAS\PNM Wed Mar 26 01:07:

46 Time( sec ) qg LONEMS qg ARGONNEG qg TRANS_WIND qaci SPS EQ SPP 2000SC MODEL. 2001CASE 8/14/ Winter Post-project Case Trip Rio Puerco - West Mesa line in 4 cycles bcrw.chf Page 1 C:\MyProjects\PSAS\PNM Wed Mar 26 01:07:

47 Time( sec ) vt LONEMS vt ARGONNEG vt TRANS_WIND vt SPP 2000SC MODEL. 2001CASE 8/14/ Winter Post-project Case Trip Rio Puerco - West Mesa line in 4 cycles bcrw.chf Page 1 C:\MyProjects\PSAS\PNM Wed Mar 26 01:07:

48 Time( sec ) vbug B-A vbug GUADLUPE vbus WESTMESA vbus RIOPUERC vbug BLACKWTR vbug TAIBANMS SPP 2000SC MODEL. 2001CASE 8/14/ Winter Post-project Case 3-Phase fault on Rio Puerco-West Mesa 345 kv line at RP 345 Trip Rio Puerco - West Mesa line in 4 cycles bcrw3p.chf Page 1 C:\MyProjects\PSAS\PNM Wed Mar 26 01:07:

49 Time( sec ) pg LONEMS pg ARGONNEG pg TRANS_WIND paci SPS EQ SPP 2000SC MODEL. 2001CASE 8/14/ Winter Post-project Case 3-Phase fault on Rio Puerco-West Mesa 345 kv line at RP 345 Trip Rio Puerco - West Mesa line in 4 cycles bcrw3p.chf Page 1 C:\MyProjects\PSAS\PNM Wed Mar 26 01:07:

50 Time( sec ) qg LONEMS qg ARGONNEG qg TRANS_WIND qaci SPS EQ SPP 2000SC MODEL. 2001CASE 8/14/ Winter Post-project Case 3-Phase fault on Rio Puerco-West Mesa 345 kv line at RP 345 Trip Rio Puerco - West Mesa line in 4 cycles bcrw3p.chf Page 1 C:\MyProjects\PSAS\PNM Wed Mar 26 01:07:

51 Time( sec ) vt LONEMS vt ARGONNEG vt TRANS_WIND vt SPP 2000SC MODEL. 2001CASE 8/14/ Winter Post-project Case 3-Phase fault on Rio Puerco-West Mesa 345 kv line at RP 345 Trip Rio Puerco - West Mesa line in 4 cycles bcrw3p.chf Page 1 C:\MyProjects\PSAS\PNM Wed Mar 26 01:07:

52 Time( sec ) vbug B-A vbug GUADLUPE vbus WESTMESA vbus RIOPUERC vbug BLACKWTR vbug TAIBANMS SPP 2000SC MODEL. 2001CASE 8/14/ Winter Post-project Case 3-Phase fault on B-A-Norton 345 kv line at B-A 345 kv; Trip B-A-Norton 345 kv line in 4 cycles. bcnwsvcbn3p.chf Page 1 C:\MyProjects\PSAS\PNM Wed Mar 26 01:07:

53 Time( sec ) pg LONEMS pg ARGONNEG pg TRANS_WIND paci SPS EQ SPP 2000SC MODEL. 2001CASE 8/14/ Winter Post-project Case 3-Phase fault on B-A-Norton 345 kv line at B-A 345 kv; Trip B-A-Norton 345 kv line in 4 cycles. bcnwsvcbn3p.chf Page 1 C:\MyProjects\PSAS\PNM Wed Mar 26 01:07:

54 Time( sec ) qg LONEMS qg ARGONNEG qg TRANS_WIND qaci SPS EQ SPP 2000SC MODEL. 2001CASE 8/14/ Winter Post-project Case 3-Phase fault on B-A-Norton 345 kv line at B-A 345 kv; Trip B-A-Norton 345 kv line in 4 cycles. bcnwsvcbn3p.chf Page 1 C:\MyProjects\PSAS\PNM Wed Mar 26 01:07:

55 Time( sec ) vt LONEMS vt ARGONNEG vt TRANS_WIND vt NEW_WIND SPP 2000SC MODEL. 2001CASE 8/14/ Winter Post-project Case 3-Phase fault on B-A-Norton 345 kv line at B-A 345 kv; Trip B-A-Norton 345 kv line in 4 cycles. bcnwsvcbn3p.chf Page 1 C:\MyProjects\PSAS\PNM Wed Mar 26 01:07:

56 Time( sec ) Bsvc GUADLUPE v Qsvc GUADLUPE v vr GUADLUPE v SPP 2000SC MODEL. 2001CASE 8/14/ Winter Post-project Case 3-Phase fault on B-A-Norton 345 kv line at B-A 345 kv; Trip B-A-Norton 345 kv line in 4 cycles. bcnwsvcbn3p.chf Page 1 C:\MyProjects\PSAS\PNM Wed Mar 26 01:07:

57 Time( sec ) vbug B-A vbug GUADLUPE vbus WESTMESA vbus RIOPUERC vbug BLACKWTR vbug TAIBANMS SPP 2000SC MODEL. 2001CASE 8/14/ Winter Post-project Case Trip Rio Puerco - West Mesa line in 4 cycles bcnwsvcrw.chf Page 1 C:\MyProjects\PSAS\PNM Wed Mar 26 01:07:

58 Time( sec ) pg LONEMS pg ARGONNEG pg TRANS_WIND paci SPS EQ SPP 2000SC MODEL. 2001CASE 8/14/ Winter Post-project Case Trip Rio Puerco - West Mesa line in 4 cycles bcnwsvcrw.chf Page 1 C:\MyProjects\PSAS\PNM Wed Mar 26 01:07:

59 Time( sec ) qg LONEMS qg ARGONNEG qg TRANS_WIND qaci SPS EQ SPP 2000SC MODEL. 2001CASE 8/14/ Winter Post-project Case Trip Rio Puerco - West Mesa line in 4 cycles bcnwsvcrw.chf Page 1 C:\MyProjects\PSAS\PNM Wed Mar 26 01:07:

60 Time( sec ) vt LONEMS vt ARGONNEG vt TRANS_WIND vt NEW_WIND SPP 2000SC MODEL. 2001CASE 8/14/ Winter Post-project Case Trip Rio Puerco - West Mesa line in 4 cycles bcnwsvcrw.chf Page 1 C:\MyProjects\PSAS\PNM Wed Mar 26 01:07:

61 Time( sec ) Bsvc GUADLUPE v Qsvc GUADLUPE v vr GUADLUPE v SPP 2000SC MODEL. 2001CASE 8/14/ Winter Post-project Case Trip Rio Puerco - West Mesa line in 4 cycles bcnwsvcrw.chf Page 1 C:\MyProjects\PSAS\PNM Wed Mar 26 01:07:

62 Time( sec ) vbug B-A vbug GUADLUPE vbus WESTMESA vbus RIOPUERC vbug BLACKWTR vbug TAIBANMS SPP 2000SC MODEL. 2001CASE 8/14/ Winter Post-project Case 3-Phase fault on Rio Puerco-West Mesa 345 kv line at RP 345 Trip Rio Puerco - West Mesa line in 4 cycles bcnwsvcrw3p.chf Page 1 C:\MyProjects\PSAS\PNM Wed Mar 26 01:07:

63 Time( sec ) pg LONEMS pg ARGONNEG pg TRANS_WIND paci SPS EQ SPP 2000SC MODEL. 2001CASE 8/14/ Winter Post-project Case 3-Phase fault on Rio Puerco-West Mesa 345 kv line at RP 345 Trip Rio Puerco - West Mesa line in 4 cycles bcnwsvcrw3p.chf Page 1 C:\MyProjects\PSAS\PNM Wed Mar 26 01:07:

64 Time( sec ) qg LONEMS qg ARGONNEG qg TRANS_WIND qaci SPS EQ SPP 2000SC MODEL. 2001CASE 8/14/ Winter Post-project Case 3-Phase fault on Rio Puerco-West Mesa 345 kv line at RP 345 Trip Rio Puerco - West Mesa line in 4 cycles bcnwsvcrw3p.chf Page 1 C:\MyProjects\PSAS\PNM Wed Mar 26 01:07:

65 Time( sec ) vt LONEMS vt ARGONNEG vt TRANS_WIND vt NEW_WIND SPP 2000SC MODEL. 2001CASE 8/14/ Winter Post-project Case 3-Phase fault on Rio Puerco-West Mesa 345 kv line at RP 345 Trip Rio Puerco - West Mesa line in 4 cycles bcnwsvcrw3p.chf Page 1 C:\MyProjects\PSAS\PNM Wed Mar 26 01:07:

66 Time( sec ) Bsvc GUADLUPE v Qsvc GUADLUPE v vr GUADLUPE v SPP 2000SC MODEL. 2001CASE 8/14/ Winter Post-project Case 3-Phase fault on Rio Puerco-West Mesa 345 kv line at RP 345 Trip Rio Puerco - West Mesa line in 4 cycles bcnwsvcrw3p.chf Page 1 C:\MyProjects\PSAS\PNM Wed Mar 26 01:07:

ABB Inc. Public Service Company of New Mexico Broadview Full Buildout Affected PSLF Study

ABB Inc. Public Service Company of New Mexico Broadview Full Buildout Affected PSLF Study ABB Inc. Public Service Company of New Mexico Broadview Full Buildout Affected PSLF Study Final Report ABB Power Systems Consulting June 27, 2016 LEGAL NOTICE This document, prepared by ABB Inc, is an

More information

ENERGY RESOURCE INTERCONNECTION SERVICE STUDY DRAFT REPORT

ENERGY RESOURCE INTERCONNECTION SERVICE STUDY DRAFT REPORT ENERGY RESOURCE INTERCONNECTION SERVICE STUDY DRAFT REPORT ART320W 320 MW Wind Powered Project Prepared for: El Paso Electric Company Prepared by: TRC Engineers, LLC 249 Western Avenue Augusta, ME 04330

More information

New Mexico Transmission Expansion Concepts For Wind Resources

New Mexico Transmission Expansion Concepts For Wind Resources New Mexico Transmission Expansion Concepts For Wind Resources May 2008 Update Electric Services Transmission Operations FOREWORD This document contains PNM s latest concepts for expanding the transmission

More information

March 2017 to June 2017 Preliminary Interconnection Cluster Window System Impact Study 49.9 MW IA-PNM May 2018

March 2017 to June 2017 Preliminary Interconnection Cluster Window System Impact Study 49.9 MW IA-PNM May 2018 March 2017 to June 2017 Preliminary Interconnection Cluster Window System Impact Study 49.9 MW IA-PNM-2017-11 May 2018 Prepared by: Public Service Company of New Mexico Foreword This report is prepared

More information

ABB POWER SYSTEMS CONSULTING

ABB POWER SYSTEMS CONSULTING ABB POWER SYSTEMS CONSULTING DOMINION VIRGINIA POWER Offshore Wind Interconnection Study 2011-E7406-1 R1 Summary Report Prepared for: DOMINION VIRGINIA POWER Report No.: 2011-E7406-1 R1 Date: 29 February

More information

EL PASO ELECTRIC COMPANY (EPE) FACILITIES STUDY FOR PROPOSED HVDC TERMINAL INTERCONNECTION AT NEW ARTESIA 345 KV BUS

EL PASO ELECTRIC COMPANY (EPE) FACILITIES STUDY FOR PROPOSED HVDC TERMINAL INTERCONNECTION AT NEW ARTESIA 345 KV BUS EL PASO ELECTRIC COMPANY (EPE) FACILITIES STUDY FOR PROPOSED HVDC TERMINAL INTERCONNECTION AT NEW ARTESIA 345 KV BUS El Paso Electric Company System Operations Department System Planning Section May 2004

More information

Verde Transmission, LLC. Verde Project. System Impact Study Report

Verde Transmission, LLC. Verde Project. System Impact Study Report Verde Transmission, LLC Verde Project System Impact Study Report March 2017 Prepared by: Public Service Company of New Mexico Foreword This report was prepared for Verde Transmission, LLC by the PNM Transmission/

More information

EL PASO ELECTRIC COMPANY (EPE) GENERATOR INTERCONNECTION SYSTEM IMPACT STUDY FOR PROPOSED XXXXXXXXXXXXXXXXXX GENERATION ON THE AMRAD-ARTESIA 345 KV

EL PASO ELECTRIC COMPANY (EPE) GENERATOR INTERCONNECTION SYSTEM IMPACT STUDY FOR PROPOSED XXXXXXXXXXXXXXXXXX GENERATION ON THE AMRAD-ARTESIA 345 KV EL PASO ELECTRIC COMPANY (EPE) GENERATOR INTERCONNECTION SYSTEM IMPACT STUDY FOR PROPOSED XXXXXXXXXXXXXXXXXX GENERATION ON THE AMRAD-ARTESIA 345 KV LINE El Paso Electric Company System Planning Department

More information

Clean Line Energy Partners, LLC. Western Spirit Clean Line 345 kv. System Impact Study

Clean Line Energy Partners, LLC. Western Spirit Clean Line 345 kv. System Impact Study Clean Line Energy Partners, LLC Western Spirit Clean Line 345 kv System Impact Study February, 2017 Prepared by: Public Service Company of New Mexico Foreword This report was prepared for the Clean Line

More information

100 MW Wind Generation Project

100 MW Wind Generation Project A subsidiary of Pinnacle West Capital Corporation 100 MW Wind Generation Project CUSTOMER FINAL Feasibility Study Results By Transmission Planning, APS December 21, 2007 Executive Summary This Feasibility

More information

EL PASO ELECTRIC COMPANY SHORT CIRCUIT ANALYSIS FOR XXX S PROPOSED GENERATION INTERCONNECTION

EL PASO ELECTRIC COMPANY SHORT CIRCUIT ANALYSIS FOR XXX S PROPOSED GENERATION INTERCONNECTION EL PASO ELECTRIC COMPANY SHORT CIRCUIT ANALYSIS FOR XXX S PROPOSED GENERATION INTERCONNECTION El Paso Electric Company System Operations Department System Planning Section August 2006 I. INTRODUCTION The

More information

XXXXXXXXXXXXXXXXXXXXXXXXX TRANSMISSION/GENERATION FEASIBILITY STUDY FATAL FLAW AND FEASIBILITY ANALYSIS

XXXXXXXXXXXXXXXXXXXXXXXXX TRANSMISSION/GENERATION FEASIBILITY STUDY FATAL FLAW AND FEASIBILITY ANALYSIS XXXXXXXXXXXXXXXXXXXXXXXXX TRANSMISSION/GENERATION FEASIBILITY STUDY FATAL FLAW AND FEASIBILITY ANALYSIS System Operations Department System Planning Section June 2001 TABLE OF CONTENTS 1.0 Executive Summary...Page

More information

El Paso Electric Company

El Paso Electric Company Feasibility Study XXXXXX Solar Generation Prepared for El Paso Electric Company Prepared by TRC Engineers, LLC 249 Eastern Avenues Augusta, ME 04330 (207) 621-7000 Project Number: 202327 May 2013 FOREWORD

More information

Elbert County 500 MW Generation Addition Interconnection Feasibility Study Report OASIS POSTING # GI

Elbert County 500 MW Generation Addition Interconnection Feasibility Study Report OASIS POSTING # GI Executive Summary Elbert County 500 MW Generation Addition Interconnection Feasibility Study Report OASIS POSTING # GI-2003-2 Xcel Energy Transmission Planning January 2004 This Interconnection Feasibility

More information

Project #148. Generation Interconnection System Impact Study Report

Project #148. Generation Interconnection System Impact Study Report Project #148 Generation Interconnection System Impact Study Report June 05, 2012 Electric Transmission Planning Table of Contents Table of Contents... 2 Executive Summary... 3 Energy Resource Interconnection

More information

El PASO ELECTRIC COMPANY 2014 BULK ELECTRIC SYSTEM TRANSMISSION ASSESSMENT FOR YEARS

El PASO ELECTRIC COMPANY 2014 BULK ELECTRIC SYSTEM TRANSMISSION ASSESSMENT FOR YEARS El Paso Electric Company El PASO ELECTRIC COMPANY 2014 BULK ELECTRIC SYSTEM TRANSMISSION ASSESSMENT FOR YEARS 2015 2024 A Review on System Performance Following Extreme Bulk Electric System Events of the

More information

Gateway South Transmission Project

Gateway South Transmission Project Phase 1 Comprehensive Progress Report Volume 1 - Technical Report Report Prepared by PacifiCorp Transmission Planning Department November 21, 2008 WECC1-V4 Phase 1 Comprehensive Progress Report Executive

More information

Generation Interconnection Feasibility Study For XXXXXXXXXXXXXXXXXXXXXX MW generator at new Western Refinary Substation

Generation Interconnection Feasibility Study For XXXXXXXXXXXXXXXXXXXXXX MW generator at new Western Refinary Substation Generation Interconnection Feasibility Study For XXXXXXXXXXXXXXXXXXXXXX 131-250 MW generator at new Western Refinary Substation System Planning Section April, 2005 TABLE OF CONTENT 1 EXECUTIVE SUMMARY

More information

SYSTEM IMPACT STUDY EC300W ERIS FINAL REPORT. El Paso Electric Company

SYSTEM IMPACT STUDY EC300W ERIS FINAL REPORT. El Paso Electric Company SYSTEM IMPACT STUDY EC300W ERIS FINAL REPORT Prepared for: El Paso Electric Company Prepared by: Engineers, LLC 1526 Cole Boulevard Building 3, Suite 150 Lakewood, CO 80401 (303) 395-4018 FOREWORD This

More information

Service Requested 150 MW, Firm. Table ES.1: Summary Details for TSR #

Service Requested 150 MW, Firm. Table ES.1: Summary Details for TSR # Executive Summary Firm point to point transmission service has been requested by Transmission Service Request (TSR) #75669514, under the SaskPower Open Access Transmission Tariff (OATT). The TSR consists

More information

THE NECESSITY OF THE 500 KV SYSTEM IN NWE S TRANSMISSION SYSTEM TO MAINTAIN RELIABLE SERVICE TO MONTANA CUSTOMERS

THE NECESSITY OF THE 500 KV SYSTEM IN NWE S TRANSMISSION SYSTEM TO MAINTAIN RELIABLE SERVICE TO MONTANA CUSTOMERS THE NECESSITY OF THE 500 KV SYSTEM IN NWE S TRANSMISSION SYSTEM TO MAINTAIN RELIABLE SERVICE TO MONTANA CUSTOMERS 2/27/2018 ELECTRIC TRANSMISSION PLANNING Table of Contents Table of Contents... 2 Executive

More information

Interconnection System Impact Study Report Request # GI

Interconnection System Impact Study Report Request # GI Executive Summary Interconnection System Impact Study Report Request # GI-2008-23 34 MW Solar Generation Ranch at Hartsel, Colorado Public Service Company of Colorado Transmission Planning August 19, 2010

More information

Generator Interconnection Facilities Study For SCE&G Two Combustion Turbine Generators at Hagood

Generator Interconnection Facilities Study For SCE&G Two Combustion Turbine Generators at Hagood Generator Interconnection Facilities Study For SCE&G Two Combustion Turbine Generators at Hagood Prepared for: SCE&G Fossil/Hydro June 30, 2008 Prepared by: SCE&G Transmission Planning Table of Contents

More information

Experiences with Wind Power Plants with Low SCR

Experiences with Wind Power Plants with Low SCR 1 Experiences with Wind Power Plants with Low SCR Lessons learned from the analysis, design and connection of wind power plants to weak electrical grids IEEE PES General Meeting Denver CO, 26 March 2015

More information

SYSTEM IMPACT RESTUDY H252W ERIS REPORT. El Paso Electric Company

SYSTEM IMPACT RESTUDY H252W ERIS REPORT. El Paso Electric Company SYSTEM IMPACT RESTUDY H252W ERIS REPORT Prepared for: El Paso Electric Company Prepared by: Engineers, LLC 1526 Cole Boulevard Building 3, Suite 150 Lakewood, CO 80401 (303) 395-4018 FOREWORD This report

More information

300 MW SOLAR PHOTOVOLTAIC PLANT, GENERATOR INTERCONNECTION FEASIBILITY STUDY

300 MW SOLAR PHOTOVOLTAIC PLANT, GENERATOR INTERCONNECTION FEASIBILITY STUDY 300 MW SOLAR PHOTOVOLTAIC PLANT, GENERATOR INTERCONNECTION FEASIBILITY STUDY El Paso Electric Company System Planning August 2006 TABLE OF CONTENTS 1.0 EXECUTIVE SUMMARY...Page 1 2.0 PURPOSE...Page 7 3.0

More information

PJM Generator Interconnection Request Queue #R60 Robison Park-Convoy 345kV Impact Study September 2008

PJM Generator Interconnection Request Queue #R60 Robison Park-Convoy 345kV Impact Study September 2008 PJM enerator Interconnection Request Queue #R60 Robison Park-Convoy 345kV Impact Study 504744 September 2008 PJM Interconnection 2008. All rights reserved R60 Robison Park-Convoy 345kV Impact Study eneral

More information

Status of PNM s Completed Transmission Construction Projects 11/30/2017

Status of PNM s Completed Transmission Construction Projects 11/30/2017 Status of s Completed Transmission Construction Projects Second Tah Ta Hey 115/345 kv Transformer Yah Ta Hey Switching Station On January 9, 2015, filed with the NMPRC under NMPRC Rule 440 information

More information

XXXXXXXXXXXXXXXX Transmission Interconnection Feasibility Study

XXXXXXXXXXXXXXXX Transmission Interconnection Feasibility Study XXXXXXXXXXXXXXXX Transmission Interconnection Feasibility Study System Operations Department System Planning Section March 2002 Table of Contents: 1.0 EXECUTIVE SUMMARY 4 2.0 COST ESTIMATES 8 2.1 Cost

More information

Updated Transmission Expansion Plan for the Puget Sound Area to Support Winter South-to-North Transfers

Updated Transmission Expansion Plan for the Puget Sound Area to Support Winter South-to-North Transfers Updated Transmission Expansion Plan for the Puget Sound Area to Support Winter South-to-North Transfers Puget Sound Area Study Team Bonneville Power Administration, Puget Sound Energy, Seattle City Light,

More information

CHAPTER 3 TRANSIENT STABILITY ENHANCEMENT IN A REAL TIME SYSTEM USING STATCOM

CHAPTER 3 TRANSIENT STABILITY ENHANCEMENT IN A REAL TIME SYSTEM USING STATCOM 61 CHAPTER 3 TRANSIENT STABILITY ENHANCEMENT IN A REAL TIME SYSTEM USING STATCOM 3.1 INTRODUCTION The modeling of the real time system with STATCOM using MiPower simulation software is presented in this

More information

PUBLIC SERVICE COMPANY OF NEW MEXICO (PNM)

PUBLIC SERVICE COMPANY OF NEW MEXICO (PNM) PUBLIC SERVICE COMPANY OF NEW MEXICO (PNM) Determination and Posting Of Total Transmission Capability (TTC) & Available Transmission Capability (ATC) On The Open Access Same-Time Information System (OASIS)

More information

Grid code Compliance and Renewable Energy Projects. Mick Barlow, Business Development Director, S&C Electric, United Kingdom

Grid code Compliance and Renewable Energy Projects. Mick Barlow, Business Development Director, S&C Electric, United Kingdom Grid code Compliance and Renewable Energy Projects Mick Barlow, Business Development Director, S&C Electric, United Kingdom Why Grid Codes? Permit the development of and operation of an efficient and economical

More information

TRANSMISSION LOSS MINIMIZATION USING ADVANCED UNIFIED POWER FLOW CONTROLLER (UPFC)

TRANSMISSION LOSS MINIMIZATION USING ADVANCED UNIFIED POWER FLOW CONTROLLER (UPFC) TRANSMISSION LOSS MINIMIZATION USING ADVANCED UNIFIED POWER FLOW CONTROLLER (UPFC) Nazneen Choudhari Department of Electrical Engineering, Solapur University, Solapur Nida N Shaikh Department of Electrical

More information

Transmission Competitive Solicitation Questions Log Question / Answer Matrix Harry Allen to Eldorado 2015

Transmission Competitive Solicitation Questions Log Question / Answer Matrix Harry Allen to Eldorado 2015 No. Comment Submitted ISO Response Date Q&A Posted 1 Will the ISO consider proposals that are not within the impedance range specified? Yes. However, the benefits estimated and studies performed by the

More information

15 Nelson-Marlborough Regional Plan

15 Nelson-Marlborough Regional Plan 15 Nelson-Marlborough Regional Plan 15.1 Regional overview 15.2 Nelson-Marlborough transmission system 15.3 Nelson-Marlborough demand 15.4 Nelson-Marlborough generation 15.5 Nelson-Marlborough significant

More information

Blackwater 345 kv. Cluster OASIS ID No. POI SIS FacS Location Page No. Table of Contents 1 DISIS # 8 ABQ Feb-18 Central 2

Blackwater 345 kv. Cluster OASIS ID No. POI SIS FacS Location Page No. Table of Contents 1 DISIS # 8 ABQ Feb-18 Central 2 Cluster OASIS ID No. POI SIS FacS Location Page No. Table of Contents DISIS # 8 ABQ Feb-8 Central 2 IA-PNM-26-3 La Ladera 5 kv IA-PNM-27- Route 66 5 kv IA-PNM-27-2 New 23 kv sta on Ambrosia to WM 23 kv

More information

Research on Transient Stability of Large Scale Onshore Wind Power Transmission via LCC HVDC

Research on Transient Stability of Large Scale Onshore Wind Power Transmission via LCC HVDC Research on Transient Stability of Large Scale Onshore Wind Power Transmission via LCC HVDC Rong Cai, Mats Andersson, Hailian Xie Corporate Research, Power and Control ABB (China) Ltd. Beijing, China rong.cai@cn.abb.com,

More information

Consulting Agreement Study. Completed for Transmission Customer

Consulting Agreement Study. Completed for Transmission Customer Completed for Transmission Customer Proposed Resource & Transmission Carbon County, MT & 230 kv Transmission in North Wyoming August 2016 Table of Contents 1.0 Description... 1 2.0 Overall Assumptions...

More information

Interconnection Feasibility Study Report GIP-226-FEAS-R3

Interconnection Feasibility Study Report GIP-226-FEAS-R3 Interconnection Feasibility Study Report GIP-226-FEAS-R3 System Interconnection Request #226 70 MW Wind Generating Facility Kings County (L-6013) 2010 07 21 Control Centre Operations Nova Scotia Power

More information

XXXXXXXXXXXXXXXXXXXXXXXXXXXX TRANSMISSION/GENERATION FEASIBILITY STUDY FATAL FLAW AND FEASIBILITY ANALYSIS

XXXXXXXXXXXXXXXXXXXXXXXXXXXX TRANSMISSION/GENERATION FEASIBILITY STUDY FATAL FLAW AND FEASIBILITY ANALYSIS XXXXXXXXXXXXXXXXXXXXXXXXXXXX TRANSMISSION/GENERATION FEASIBILITY STUDY FATAL FLAW AND FEASIBILITY ANALYSIS El Paso Electric Company System Operations Department System Planning Section September 2001 TABLE

More information

Four Corners Queue Transmission Interconnection Study

Four Corners Queue Transmission Interconnection Study Four Corners Queue Transmission Interconnection Study Facility Study Results By Arizona Public Service Company Transmission Planning & Interconnection Development March 22, 2016 Version 1 FACILITIES STUDY

More information

Overview of Flexible AC Transmission Systems

Overview of Flexible AC Transmission Systems Overview of Flexible AC Transmission Systems What is FACTS? Flexible AC Transmission System (FACTS): Alternating current transmission systems incorporating power electronic-based and other static controllers

More information

Operational Planning Study Report. RTA to BCH transfer limit updates For Kitimat 4 Capacitor Banks

Operational Planning Study Report. RTA to BCH transfer limit updates For Kitimat 4 Capacitor Banks Operational Planning Study Report RTA to BCH transfer limit updates For Kitimat 4 Capacitor Banks Report No. T&S Planning 2013-062 British Columbia Hydro and Power Authority British Columbia Hydro and

More information

Interconnection System Impact Study Final Report February 19, 2018

Interconnection System Impact Study Final Report February 19, 2018 Interconnection System Impact Study Final Report February 19, 2018 Generator Interconnection Request No. TI-17-0225 248.4 MW (Alternate Project Output of 217.35 MW) Wind Energy Generating Facility In Goshen

More information

Islanding of 24-bus IEEE Reliability Test System

Islanding of 24-bus IEEE Reliability Test System Islanding of 24-bus IEEE Reliability Test System Paul Trodden February 14, 211 List of Figures 1 24-bus IEEE RTS, with line (3,24) tripped and buses 3,24 and line (3,9) uncertain....................................

More information

Interconnection Feasibility Study Report Request # GI Draft Report 600 MW Wind Generating Facility Missile Site 230 kv Substation, Colorado

Interconnection Feasibility Study Report Request # GI Draft Report 600 MW Wind Generating Facility Missile Site 230 kv Substation, Colorado Executive Summary Interconnection Feasibility Study Report Request # GI-2016-6 Draft Report 600 MW Wind Generating Facility Missile Site 230 kv Substation, Colorado Public Service Company of Colorado Transmission

More information

Merchant Transmission Interconnection PJM Impact Study Report. PJM Merchant Transmission Request Queue Position X3-028.

Merchant Transmission Interconnection PJM Impact Study Report. PJM Merchant Transmission Request Queue Position X3-028. Merchant Transmission Interconnection PJM Impact Study Report For PJM Merchant Transmission Request Queue Position X3-028 Breed 345 kv October/2014 System Impact Study Breed 345 kv Merchant Transmission

More information

Guide. Services Document No: GD-1401 v1.0. Issue Date: Title: WIND ISLANDING. Previous Date: N/A. Author: Heather Andrew.

Guide. Services Document No: GD-1401 v1.0. Issue Date: Title: WIND ISLANDING. Previous Date: N/A. Author: Heather Andrew. Guide Department: Interconnection Services Document No: GD-1401 v1.0 Title: WIND ISLANDING Issue Date: 11-24-2014 Previous Date: N/A Contents 1 PURPOSE... 2 2 SCOPE AND APPLICABILITY... 2 3 ROLES AND RESPONSIBILITIES...

More information

Project #94. Generation Interconnection System Impact Study Report Revision

Project #94. Generation Interconnection System Impact Study Report Revision Project #94 Generation Interconnection System Impact Study Report Revision October 2, 2009 Electric Transmission Planning Table of Contents Table of Contents...2 Executive Summary...3 Energy Resource Interconnection

More information

XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX TRANSMISSION/GENERATION FEASIBILITY STUDY SHORT CIRCUIT ANALYSIS

XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX TRANSMISSION/GENERATION FEASIBILITY STUDY SHORT CIRCUIT ANALYSIS XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX TRANSMISSION/GENERATION FEASIBILITY STUDY SHORT CIRCUIT ANALYSIS El Paso Electric Company System Operations Department System Planning Section September 2001 Short Circuit

More information

Short Circuit Analysis with New Generation Proposed by XXXXXXXXXXXXXXXXXXXXXX Pursuant to a Transmission and Facilities Study

Short Circuit Analysis with New Generation Proposed by XXXXXXXXXXXXXXXXXXXXXX Pursuant to a Transmission and Facilities Study Short Circuit Analysis with New Generation Proposed by XXXXXXXXXXXXXXXXXXXXXX Pursuant to a Transmission and Facilities Study Study Performed by El Paso Electric Company System Planning Section - 1 I.

More information

NEWFOUNDLAND AND LABRADOR HYDRO GULL ISLAND TO SOLDIERS POND HVDC INTERCONNECTION DC SYSTEM STUDIES VOLUME 1

NEWFOUNDLAND AND LABRADOR HYDRO GULL ISLAND TO SOLDIERS POND HVDC INTERCONNECTION DC SYSTEM STUDIES VOLUME 1 Page 1 of 76 NEWFOUNDLAND AND LABRADOR HYDRO GULL ISLAND TO SOLDIERS POND HVDC INTERCONNECTION DC SYSTEM STUDIES VOLUME 1 Page 2 of 76 NEWFOUNDLAND AND LABRADOR HYDRO GULL ISLAND TO SOLDIERS POND HVDC

More information

Interconnection Feasibility Study Report GIP-222-FEAS-R3

Interconnection Feasibility Study Report GIP-222-FEAS-R3 Interconnection Feasibility Study Report GIP-222-FEAS-R3 System Interconnection Request #222 48 MW Steam Generating Facility Pictou County (53N) 2010 07 30 Control Centre Operations Nova Scotia Power Inc.

More information

XXXXXXXXXXXXXX 99 MW WIND PARK GENERATOR INTERCONNECTION FEASIBILITY STUDY. September 2008 Prepared by: EL PASO ELECTRIC COMPANY

XXXXXXXXXXXXXX 99 MW WIND PARK GENERATOR INTERCONNECTION FEASIBILITY STUDY. September 2008 Prepared by: EL PASO ELECTRIC COMPANY XXXXXXXXXXXXXX 99 MW WIND PARK GENERATOR INTERCONNECTION FEASIBILITY STUDY September 2008 Prepared by: EL PASO ELECTRIC COMPANY Foreword This report was prepared for XXXXXXXXXXXXX (XXX) of XXXXXXXX by

More information

Stability Study for the Mt. Olive Hartburg 500 kv Line

Stability Study for the Mt. Olive Hartburg 500 kv Line Stability Study for the Mt. Olive Hartburg 500 kv Line Peng Yu Sharma Kolluri Transmission & Distribution Planning Group Energy Delivery Organization Entergy Sevices Inc April, 2011 New Orleans, LA 1.

More information

Islanding of 24-bus IEEE Reliability Test System

Islanding of 24-bus IEEE Reliability Test System Islanding of 24-bus IEEE Reliability Test System Paul Trodden February 17, 211 List of Figures 1 24-bus IEEE RTS, with line (3,24) tripped and buses 3,24 and line (3,9) uncertain....................................

More information

Hamdy S. K. El-Goharey, Walid A. Omran, Adel T. M. Taha

Hamdy S. K. El-Goharey, Walid A. Omran, Adel T. M. Taha 1 Military Technical College Kobry El-Kobbah, Cairo, Egypt 10 th International Conference on Electrical Engineering I. ICEENG 2016 Voltage Stability Investigation of the Egyptian Grid With High Penetration

More information

Feasibility Study Report

Feasibility Study Report Generator Interconnection Request Feasibility Study Report For: Customer --- Service Location: Rutherford County Total Output: 79.2 MW Commercial Operation Date: 9/1/2014 In-Service Date (if given): 9/1/2014

More information

PID 274 Feasibility Study Report 13.7 MW Distribution Inter-Connection Buras Substation

PID 274 Feasibility Study Report 13.7 MW Distribution Inter-Connection Buras Substation PID 274 Feasibility Study Report 13.7 MW Distribution Inter-Connection Buras Substation Prepared by: Entergy Services, Inc. T & D Planning L-ENT-17A 639 Loyola Avenue New Orleans, LA 70113 Rev Issue Date

More information

XXXXXXXXXXXXXXXXXXXX GENERATION INTERCONNECTION FACILITIES STUDY SHORT CIRCUIT ANALYSIS FOR PROPOSED GENERATION AT NEWMAN 115 kv BUS

XXXXXXXXXXXXXXXXXXXX GENERATION INTERCONNECTION FACILITIES STUDY SHORT CIRCUIT ANALYSIS FOR PROPOSED GENERATION AT NEWMAN 115 kv BUS XXXXXXXXXXXXXXXXXXXX GENERATION INTERCONNECTION FACILITIES STUDY SHORT CIRCUIT ANALYSIS FOR PROPOSED GENERATION AT NEWMAN 115 kv BUS El Paso Electric Company System Operations Department System Planning

More information

Generator Interconnection System Impact Study For

Generator Interconnection System Impact Study For Generator Interconnection System Impact Study For Prepared for: January 15, 2015 Prepared by: SCE&G Transmission Planning Table of Contents General Discussion... Page 3 I. Generator Interconnection Specifications...

More information

TransWest Express Project

TransWest Express Project TransWest Express Project Phase One--Feasibility Study Final Study Report November 2006 A subsidiary of Pinnacle West Capital Corporation Executive Summary On October 21, 2005 Arizona Public Service Company

More information

IEEE T&D FACTS Panel Session Part II (08TD0140) Wednesday, April 23, 2008

IEEE T&D FACTS Panel Session Part II (08TD0140) Wednesday, April 23, 2008 IEEE T&D FACTS Panel Session Part II (08TD0140) Wednesday, April 23, 2008 Improving Power System Dynamic Performance in Laredo, TX Prepared by Paul Hassink (AEP) Paul Marken (GE) Rob O Keefe (AEP) Gerardo

More information

Interconnection Feasibility Study Report GIP-157-FEAS-R2

Interconnection Feasibility Study Report GIP-157-FEAS-R2 Interconnection Feasibility Study Report GIP-157-FEAS-R2 System Interconnection Request #157 100.5 MW Wind Generating Facility Guysborough County (L-6515) 2009 09 14 Control Centre Operations Nova Scotia

More information

THE TRES AMIGAS PROJECT

THE TRES AMIGAS PROJECT UNITING THE NATION S ELECTRIC POWER GRID THE TRES AMIGAS PROJECT Project Development, Business Case, and Benefits -ERCOT Presentation Jan 22, 2010 Agenda Project Overview Project Objective Project Description,

More information

Final Draft Report. Assessment Summary. Hydro One Networks Inc. Longlac TS: Refurbish 115/44 kv, 25/33/ General Description

Final Draft Report. Assessment Summary. Hydro One Networks Inc. Longlac TS: Refurbish 115/44 kv, 25/33/ General Description Final Draft Report Assessment Summary Hydro One Networks Inc. : Refurbish 115/44 kv, 25/33/42 MVA DESN Station CAA ID Number: 2007-EX360 1.0 General Description Hydro One is proposing to replace the existing

More information

XXXX. Knob Hill Wind Farm Project. Interconnection System Impact Study

XXXX. Knob Hill Wind Farm Project. Interconnection System Impact Study XXXX Knob Hill Wind Farm Project Report No. August 2010 British Columbia Hydro and Power Authority British Columbia Hydro and Power Authority 2010. All rights reserved.. DISCLAIMER OF WARRANTY, LIMITATION

More information

High Lonesome Mesa 100 MW Wind Generation Project (OASIS #IA-PNM ) Interconnection Facility Study. Final Report November 2, 2007

High Lonesome Mesa 100 MW Wind Generation Project (OASIS #IA-PNM ) Interconnection Facility Study. Final Report November 2, 2007 High Lonesome Mesa 100 MW Wind Generation Project (OASIS #IA-PNM-2006-02) Interconnection Facility Study Final Report November 2, 2007 Prepared by: Public Service Company of New Mexico Electric Services

More information

Q95 Vicksburg 69kV. System Impact Study. APS Contract No Arizona Public Service Company Transmission Planning.

Q95 Vicksburg 69kV. System Impact Study. APS Contract No Arizona Public Service Company Transmission Planning. A subsidiary of Pinnacle West Capital Corporation Q95 Vicksburg 69kV System Impact Study APS Contract No. 52246 By Arizona Public Service Company Transmission Planning December 1, 2010 Version 2.6 Final

More information

Concepts And Application Of Flexible Alternating Current Transmission System (FACTS) In Electric Power Network

Concepts And Application Of Flexible Alternating Current Transmission System (FACTS) In Electric Power Network Concepts And Application Of Flexible Alternating Current Transmission System (FACTS) In Electric Power Network Nwozor Obinna Eugene Department of Electrical and Computer Engineering, Federal University

More information

SPS Planning Criteria and Study Methodology

SPS Planning Criteria and Study Methodology SPS Planning Criteria and Study Methodology SPS subscribes to the Southwest Power Pool ("SPP") Reliability Criteria, which incorporates compliance with the appropriate North American Electric Reliability

More information

Interconnection Feasibility Study Report GIP-084-FEAS-R2

Interconnection Feasibility Study Report GIP-084-FEAS-R2 Interconnection Feasibility Study Report GIP-084-FEAS-R2 System Interconnection Request #84 50 MW Wind Generating Facility Pictou County (L-7004) August 17, 2007 Control Centre Operations Nova Scotia Power

More information

Midway/Monument Area TTC Study

Midway/Monument Area TTC Study Midway/Monument Area TTC Study (includes the following lines: Midway Geesen 115 kv, Geesen Falcon 115 kv, Falcon Fuller 115 kv, Fuller Black Squirrel 115 kv, and Black Squirrel Monument 115 kv) Johnny

More information

Session 10 NERC Interconnection Requirements

Session 10 NERC Interconnection Requirements GE Energy Session 10 NERC Interconnection Requirements UVIG Short Course 2014 Portland, Oregon Jason MacDowell NERC Standards Recently Adopted NERC GVSDT* standards MOD (Model Validation): MOD-025: Verification

More information

Dynamic Control of Grid Assets

Dynamic Control of Grid Assets Dynamic Control of Grid Assets Panel on Power Electronics in the Smart Grid Prof Deepak Divan Associate Director, Strategic Energy Institute Director, Intelligent Power Infrastructure Consortium School

More information

A Case Study on Aggregate Load Modeling in Transient Stability Studies

A Case Study on Aggregate Load Modeling in Transient Stability Studies A Case Study on Aggregate Load Modeling in Transient Stability Studies Presented by: Daniel Feltes Siemens PTI Coauthors: Carlos Grande-Moran, Bernardo Fernandes, James Feltes, Ming Wu and Robert Wells

More information

Connection Engineering Study Report for AUC Application: AESO Project # 1674

Connection Engineering Study Report for AUC Application: AESO Project # 1674 APPENDIX A CONNECTION ASSESSMENT Connection Engineering Study Report for AUC Application: AESO Project # 1674 Executive Summary Project Overview FortisAlberta Inc. (FortisAlberta) submitted a System

More information

COMPARISON OF STATCOM AND TCSC ON VOLTAGE STABILITY USING MLP INDEX

COMPARISON OF STATCOM AND TCSC ON VOLTAGE STABILITY USING MLP INDEX COMPARISON OF AND TCSC ON STABILITY USING MLP INDEX Dr.G.MadhusudhanaRao 1. Professor, EEE Department, TKRCET Abstract: Traditionally shunt and series compensation is used to maximize the transfer capability

More information

Feasibility Study Report

Feasibility Study Report Report For: Fresh Air Energy II, LLC ( Customer ) Queue #: Service Location: Chester County, SC Total Output Requested By Customer: 74.5 MW Commercial Operation Date Requested By Customer: 1/7/2019 Feasibility

More information

Experience on Technical Solutions for Grid Integration of Offshore Windfarms

Experience on Technical Solutions for Grid Integration of Offshore Windfarms Experience on Technical Solutions for Grid Integration of Offshore Windfarms Liangzhong Yao Programme Manager AREVA T&D Technology Centre 18 June 2007, DTI Conference Centre, London Agenda The 90MW Barrow

More information

120 MW SOLAR-THERMAL PLANT GENERATOR INTERCONNECTION FEASIBILITY STUDY. May 2008 Prepared by: EL PASO ELECTRIC COMPANY

120 MW SOLAR-THERMAL PLANT GENERATOR INTERCONNECTION FEASIBILITY STUDY. May 2008 Prepared by: EL PASO ELECTRIC COMPANY . 120 MW SOLAR-THERMAL PLANT GENERATOR INTERCONNECTION May 2008 Prepared by: EL PASO ELECTRIC COMPANY Foreword This report was prepared for XXXXXXXXXXXXXXXXXXX by System Planning at El Paso Electric Company.

More information

Dynamic Scheduling NI A F S NI S. Where:

Dynamic Scheduling NI A F S NI S. Where: Dynamic Scheduling FERC Order 888 defines dynamic scheduling: which is the electronic transfer of the time-varying electricity consumption corresponding to a load or the time-varying generation associated

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Interconnected Electric System Protection Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Interconnected Electric System Protection Requirements Applicability 1 Section 502.3 applies to: the legal owner of a generating unit directly connected to the transmission system with a maximum authorized real power rating greater than 18 MW; the legal owner

More information

SYSTEM IMPACT STUDY REPORT LA450S GENERATION STUDY. El Paso Electric Company

SYSTEM IMPACT STUDY REPORT LA450S GENERATION STUDY. El Paso Electric Company SYSTEM IMPACT STUDY REPORT LA450S GENERATION STUDY Prepared for: El Paso Electric Company Prepared by: Engineers, LLC 1526 Cole Boulevard Building 3, Suite 150 Lakewood, CO 80401 (303) 395-4018 FOREWORD

More information

Large Load Serving Study Report for La Plata Electric Association, Inc. Alternatives. Addendum. San Juan Major Project

Large Load Serving Study Report for La Plata Electric Association, Inc. Alternatives. Addendum. San Juan Major Project Large Load Serving Study Report for La Plata Electric Association, Inc. Alternatives Addendum San Juan Major Project Tri-State Generation and Transmission Association Power System Planning December, 2008

More information

Interconnection Feasibility Study Report GIP-IR373-FEAS-R1

Interconnection Feasibility Study Report GIP-IR373-FEAS-R1 Interconnection Feasibility Study Report GIP-IR373-FEAS-R1 Generator Interconnection Request 373 109.5 MW Wind Generating Facility South Canoe Lake, NS Mar. 2, 2012 Control Centre Operations Nova Scotia

More information

FIRSTENERGY S PROPOSED SOLUTION AND REQUEST FOR CONSTRUCTION DESIGNATION

FIRSTENERGY S PROPOSED SOLUTION AND REQUEST FOR CONSTRUCTION DESIGNATION PJM RTEP - Artificial Island Area FIRSTENERGY S PROPOSED SOLUTION AND REQUEST FOR CONSTRUCTION DESIGNATION Part 1 Report REDACTED VERSION FirstEnergy Corp. Energy Delivery, Transmission Planning and Protection

More information

Interconnection Feasibility Study

Interconnection Feasibility Study Interconnection Feasibility Study Mount Mabel Wind Energy Project Report No: T&S Planning 2015-054 December 2015 British Columbia Hydro and Power Authority British Columbia Hydro and Power Authority 2015.

More information

XXXX. Kokish River Hydroelectric Project. Interconnection System Impact Study

XXXX. Kokish River Hydroelectric Project. Interconnection System Impact Study XXXX Kokish River Hydroelectric Project Report No. August 2010 British Columbia Hydro and Power Authority British Columbia Hydro and Power Authority 2010. All rights reserved.. DISCLAIMER OF WARRANTY,

More information

15 Nelson-Marlborough Regional Plan

15 Nelson-Marlborough Regional Plan 15 Nelson-Marlborough Regional Plan 15.1 Regional overview 15.2 Nelson-Marlborough transmission system 15.3 Nelson-Marlborough demand 15.4 Nelson-Marlborough generation 15.5 Nelson-Marlborough significant

More information

4,1 '~ ~ ~ 1I1f lc/)~ul I Central Electricity Authority

4,1 '~ ~ ~ 1I1f lc/)~ul I Central Electricity Authority ,.,.;i')!i,:;;',;~~~. 'ffrff mm I Government of India ~ ~.I Ministry of Power 4,1 '~ ~ ~ 1I1f lc/)~ul I Central Electricity Authority III ~~~~~~I"1",~~1 ;J' :. r System Planning & Project Appraisal Division

More information

Interconnection Feasibility Study Report GIP-369-FEAS-R1

Interconnection Feasibility Study Report GIP-369-FEAS-R1 Interconnection Feasibility Study Report GIP-369-FEAS-R1 System Interconnection Request #369 50 MW Wind Generating Facility Cumberland County (L-6513) 2012-02-09 Control Centre Operations Nova Scotia Power

More information

NETSSWorks Software: An Extended AC Optimal Power Flow (AC XOPF) For Managing Available System Resources

NETSSWorks Software: An Extended AC Optimal Power Flow (AC XOPF) For Managing Available System Resources NETSSWorks Software: An Extended AC Optimal Power Flow (AC XOPF) For Managing Available System Resources Marija Ilic milic@netssinc.com and Jeffrey Lang jeffrey.lang@netssinc.com Principal NETSS Consultants

More information

Dynamic Reactive Power Control for Wind Power Plants

Dynamic Reactive Power Control for Wind Power Plants Dynamic Reactive Power Control for Wind Power Plants Ernst Camm, Charles Edwards, Ken Mattern, Stephen Williams S&C Electric Company, 6601 N. Ridge Blvd, Chicago IL 60626 USA ecamm@sandc.com, cedwards@sandc.om,

More information

ELG4125: Flexible AC Transmission Systems (FACTS)

ELG4125: Flexible AC Transmission Systems (FACTS) ELG4125: Flexible AC Transmission Systems (FACTS) The philosophy of FACTS is to use power electronics for controlling power flow in a transmission network, thus allowing the transmission line to be loaded

More information

2015 Grid of the Future Symposium

2015 Grid of the Future Symposium 21, rue d Artois, F-75008 PARIS CIGRE US National Committee http ://www.cigre.org 2015 Grid of the Future Symposium Flexibility in Wind Power Interconnection Utilizing Scalable Power Flow Control P. JENNINGS,

More information

PJM Generator Interconnection R81 Emilie (Fords Mill) MW Impact Study Re-Study

PJM Generator Interconnection R81 Emilie (Fords Mill) MW Impact Study Re-Study PJM Generator Interconnection R81 Emilie (Fords Mill) 100.9 MW Impact Study Re-Study August 2008 DMS # 498781 General Queue R81 Emilie (Fords Mills) is a Fairless Energy, LLC request to obtain an additional

More information

Grid Stability Analysis for High Penetration Solar Photovoltaics

Grid Stability Analysis for High Penetration Solar Photovoltaics Grid Stability Analysis for High Penetration Solar Photovoltaics Ajit Kumar K Asst. Manager Solar Business Unit Larsen & Toubro Construction, Chennai Co Authors Dr. M. P. Selvan Asst. Professor Department

More information

CHAPTER 5 FAULT AND HARMONIC ANALYSIS USING PV ARRAY BASED STATCOM

CHAPTER 5 FAULT AND HARMONIC ANALYSIS USING PV ARRAY BASED STATCOM 106 CHAPTER 5 FAULT AND HARMONIC ANALYSIS USING PV ARRAY BASED STATCOM 5.1 INTRODUCTION Inherent characteristics of renewable energy resources cause technical issues not encountered with conventional thermal,

More information