XXXXXXXXXXXXXXXXXXXX GENERATION INTERCONNECTION FACILITIES STUDY SHORT CIRCUIT ANALYSIS FOR PROPOSED GENERATION AT NEWMAN 115 kv BUS
|
|
- Bathsheba Day
- 6 years ago
- Views:
Transcription
1 XXXXXXXXXXXXXXXXXXXX GENERATION INTERCONNECTION FACILITIES STUDY SHORT CIRCUIT ANALYSIS FOR PROPOSED GENERATION AT NEWMAN 115 kv BUS El Paso Electric Company System Operations Department System Planning Section May 2003
2 I. INTRODUCTION XXXXXXXXXXXXXXXXXXXXXXXXXXX (XXX) has proposed the addition of a generating plant near EPE s Newman Substation. This proposed generation unit was analyzed in two phases. Phase I analyzed a 140 MW combustion turbine (CT) in Phase II analyzed a steam turbine integrated with the CT to form a Combined Cycle (CC) unit in In both phases, the unit was modeled as being interconnected at EPE s Newman 115 kv bus. When generating units are added to a transmission system, the available fault current on a system increases. Therefore, as part of the Generation Interconnection Facilities Study (GIFS), a short circuit study was performed to determine if the additional fault current on the EPE system due to the proposed generation does not exceed the interruption ratings of EPE s existing substation circuit breakers. In the powerflow analysis of the GIFS, the 2006 CT was modeled at a 140 MW generation output level. The 2009 CC unit was modeled at a 290 MW maximum generation output level. This Short Circuit Study was performed by El Paso Electric Company s Transmission & Distribution Division (EPE T&D). The Powerflow, Q-V, and Stability analyses for this study are also being performed by El Paso Electric Company s Transmission & Distribution Division (EPE T&D) and will be issued under a separate cover. Short Circuit Analysis for a 1 El Paso Electric Company
3 II. SHORT CIRCUIT STUDY MODELING The new generation proposed by XXX is sited at EPE s Newman 115 kv substation. The combustion and steam-turbine generator portion of the proposed combined-cycle plant will be connected to the 115 kv transmission through a 200 MVA, 18/115 kv step-up transformer per generator. Each of the two step-up transformers has an impedance of 7.5 % on a 120 MVA base. The step-up transformer impedance modeled in the short circuit analysis for both step-up transformers was: Z (step-up) = J per unit (100 MVA base) The new generators have the following reactance values on the generator MVA base: Combustion-Turbine: X d = Direct Axis Synchronous Reactance = per unit X d = Direct Axis Transient Reactance = per unit X d = Direct Axis Subtransient Reactance = per unit Steam-Turbine: X d = Direct Axis Synchronous Reactance = per unit X d = Direct Axis Transient Reactance = per unit X d = Direct Axis Subtransient Reactance = per unit These reactance values were converted to a 100 MVA base and used to model the new generators in the short circuit study. In addition to the new generation connected to the Newman 115 kv bus, one existing and four potential generation projects were also modeled in the analysis. These generation projects included the following: 135 MW of generation at Afton Substation interconnected to the Luna-Afton- Newman 345 kv line (existing). 614 MW of generation interconnected at the Luna 345 kv Substation. 160 MW of generation interconnected near Lordsburg, New Mexico. 150 MW of generation interconnected at Lordsburg, New Mexico. 130 MW of new generation interconnected at Afton 345 kv Substation and 14 MW of additional generation on the existing Afton generator. These additional generators were modeled in the study to provide a worst case scenario in the event that all are interconnected into EPE s system before the proposed Newman generation is interconnected. Short Circuit Analysis for a 2 El Paso Electric Company
4 Maximum fault currents were then determined at the Newman 115 kv bus and other EPE substations of interest or importance. These included the following: Diablo 345 kv Diablo 115 kv Newman 345 kv Rio Grande 115 kv Rio Grande 69 kv The resulting fault current was then compared to the circuit breaker interruption ratings of the breakers at each of the above mentioned substations. Among the proposed projects listed above is the addition of 14 MW of generation to the existing 135 MW generator at Afton. This existing generator will be combined with a proposed 130 MW generator and interconnected to the Luna-Afton-Newman 345 kv line. Together, these projects (135 MW +14 MW MW) represent a combinedcycle configuration with a modeled output of 279 MW. Because there are two transmission line interconnection configurations for this proposed project that are currently being studied as part of a different analysis, the results for this Short-Circuit Study will be presented in two different result groups. The Transmission Configuration 1 used to interconnect the 279 MW generation plant mentioned above involves the use of the existing Luna-Afton-Newman 345 kv transmission configuration. The existing Afton generator interconnects the Luna- Newman 345 kv line to now form two line segments, the Luna-Afton 345 kv line and the Afton to Newman 345 kv. In Transmission Configuration 2, EPE s Luna-Diablo 345 kv line is routed such that this existing line will be tied to Afton 345 kv substation to also form two line segments, the Luna-Afton 345 kv line and the Afton-Diablo 345 kv line Ultimately, a Study of the proposed Afton Project, currently in progress, will be used to determine which Transmission Configuration will be used to interconnect the 279 MW project described above. Because the study referenced above has not yet been completed, results of this Short- Circuit Study will be divided into two groups corresponding to each of the two Transmission Configurations described above. Short Circuit Analysis for a 3 El Paso Electric Company
5 III. RESULTS OF THE SHORT CIRCUIT ANALYSIS The circuit breakers used in the Southern New Mexico System at 345 kv, 115 kv, and 69 kv buses vary between the substations. The following is a list of the existing circuit breakers, along with the interruption rating, at each of the relevant substations: Breaker Breaker Interruption Substation Voltage Number Rating (Amps) Diablo B 40, B 40, B 40,000 Diablo B 40, B 40, B 40, B 40, B 40, B 31,500 Newman B 40, B 40, B 40, B 40,000 Newman , , , N , , , N , , N , , , N , , , N , , N , N ,000 Short Circuit Analysis for a 4 El Paso Electric Company
6 Breaker Breaker Interruption Substation Voltage Number Rating (Amps) Newman ,000 (continued) 115 N , N , , N , N ,000 Rio Grande B 40,000* B 23, B 23, B 40, B 40, B 23, B 23, B 40, B 40,000* B 23, B 23, B 40,000 Rio Grande ,000* , , , , , , , B 31, , , B 31, , ,000 * Currently these breakers have ratings ranging between 19,000-20,000 amperes. They are expected to be replaced with breakers having 40,000 ampere ratings as part of EPE s normal breaker replacement program. Short Circuit Analysis for a 5 El Paso Electric Company
7 The short circuit analysis was first performed with no new generation at Newman 115 kv (all other potential generation projects in). This gave the base case fault duties of the circuit breakers. The new generation at Newman 115 kv was then modeled in two phases. Phase I analyzed a 140 MW combustion turbine (CT) in Phase II analyzed a steam-turbine added to the combustion turbine configuration to form a Combined Cycle (CC) unit in In both phases the short circuit study was then reanalyzed (with all other potential generation projects in). The incremental between the three studies gave the impact of the new generators on the existing circuit breakers in the Southern New Mexico system. A. Short Circuit Results for Proposed New Generation at Newman 115 kv Using Transmission Configuration 1 Transmission Configuration 1 assumes that the transmission configuration of interconnecting the Afton generating station to the Luna-Afton-Newman 345 kv line will remain as it exists now, with the line divided into two segments: 1) Luna to Afton 345 kv substation 2) Afton to Newman 345 kv substation. The other proposed projects previously listed are also included in this configuration. The short circuit (fault) currents of Configuration 1 at all the substations which may be impacted due to the addition of the proposed Newman 5 project are listed below: No New Generation at Newman 115 kv Bus Versus Phase 1 CT Addition at Newman 115 kv Bus in 2006 Three Phase Line to Ground: No New Generation With New Generation Diablo 345 kv Bus 5, ,498.0 Diablo 115 kv Bus 19, ,070.0 Newman 345 kv Bus 8, ,348.0 Newman 115 kv Bus 25, ,755.0 Rio Grande 115 kv Bus 21, ,845.0 Rio Grande 69 kv Bus 19, ,051.0 Short Circuit Analysis for a 6 El Paso Electric Company
8 Single Phase Line to Ground: No New Generation With New Generation Diablo 345 kv Bus 4, ,958.0 Diablo 115 kv Bus 19, ,820.0 Newman 345 kv Bus 8, ,396.0 Newman 115 kv Bus 30, ,063.0 Rio Grande 115 kv Bus 22, ,373.0 Rio Grande 69 kv Bus 23, ,518.0 No New Generation at Newman 115 kv Bus Versus Phase 2 CC Plant at Newman 115 kv Bus in 2009 Three Phase Line to Ground: No New Generation With New Generation Diablo 345 kv Bus 5, ,562.0 Diablo 115 kv Bus 19, ,323.0 Newman 345 kv Bus 8, ,746.0 Newman 115 kv Bus 25, ,695.0 Rio Grande 115 kv Bus 21, ,430.0 Rio Grande 69 kv Bus 19, ,308.0 Single Phase Line to Ground: No New Generation With New Generation Diablo 345 kv Bus 4, ,992.0 Diablo 115 kv Bus 19, ,231.0 Newman 345 kv Bus 8, ,738.0 Newman 115 kv Bus 30, ,787.0 Rio Grande 115 kv Bus 22, ,819.0 Rio Grande 69 kv Bus 23, ,753.0 Short Circuit Analysis for a 7 El Paso Electric Company
9 As can be seen in the table below, the fault currents of six (6) existing circuit breakers at Rio Grande 115 kv exceed their interruption ratings during a single phase line to ground fault in SUBSTATION BREAKER NUMBER INTERRUPTION RATING SC FAULT CURRENT W/O NEWMAN 5 SC FAULT CURRENT WITH NEWMAN 5 Rio Grande B 23,000 22,818 23, B 23,000 22,818 23, B 23,000 22,818 23, B 23,000 22,818 23, B 23,000 22,818 23, B 23,000 22,818 23,373 Therefore, under Transmission Configuration 1, XXX will be responsible for the cost of replacing six new circuit breakers at the Rio Grande 115 kv bus. B. Short Circuit Results for Proposed New Generation at Newman 115 kv Using Transmission Configuration 2 Transmission Configuration 2 assumes that the transmission configuration of interconnecting the Afton generating station to the Luna-Afton-Newman 345 kv line will remain as it exists now, with the line divided into two segments: 1) Luna to Afton 345 kv substation 2) Afton to Newman 345 kv substation. However, this Configuration also interconnects the Afton plant to EPE s Luna-Diablo 345 kv line, also dividing the line into two segments, 1) Luna to Afton 345 kv substation 2) Afton to Diablo 345 kv substation. The other proposed projects previously listed are also included in this configuration. The short circuit (fault) currents under Configuration 2 at all the substations which may be impacted due to the addition of the proposed Newman 5 project are listed on the following page. Short Circuit Analysis for a 8 El Paso Electric Company
10 No New Generation at Newman 115 kv Bus Versus Phase 1 CT Addition at Newman 115 kv Bus in 2006 Three Phase Line to Ground: No New Generation With New Generation Diablo 345 kv Bus 7, ,876.0 Diablo 115 kv Bus 21, ,759.0 Newman 345 kv Bus 9, ,791.0 Newman 115 kv Bus 25, ,783.0 Rio Grande 115 kv Bus 22, ,019.0 Rio Grande 69 kv Bus 20, ,441.0 Single Phase Line to Ground: No New Generation With New Generation Diablo 345 kv Bus 6, ,025.0 Diablo 115 kv Bus 21, ,823.0 Newman 345 kv Bus 9, ,727.0 Newman 115 kv Bus 30, ,097.0 Rio Grande 115 kv Bus 23, ,549.0 Rio Grande 69 kv Bus 23, ,935.0 No New Generation at Newman 115 kv Bus Versus Phase 2 CC Plant at Newman 115 kv Bus in 2009 Three Phase Line to Ground: No New Generation With New Generation Diablo 345 kv Bus 7, ,022.0 Diablo 115 kv Bus 21, ,323.0 Newman 345 kv Bus 9, ,217.0 Newman 115 kv Bus 25, ,723.0 Rio Grande 115 kv Bus 22, ,692.0 Rio Grande 69 kv Bus 20, ,717.0 Single Phase Line to Ground: Short Circuit Analysis for a 9 El Paso Electric Company
11 No New Generation With New Generation Diablo 345 kv Bus 6, ,103.0 Diablo 115 kv Bus 21, ,231.0 Newman 345 kv Bus 9, ,086.0 Newman 115 kv Bus 30, ,821.0 Rio Grande 115 kv Bus 23, ,059.0 Rio Grande 69 kv Bus 23, ,186.0 As can be seen in the table below, the fault currents of six (6) existing circuit breakers at Rio Grande 115 kv exceed their interruption ratings during a single phase line to ground fault in These circuit breakers will have to be replaced due to the increased shortcircuit current resulting from the addition of another proposed project in Therefore, XXX is not responsible for the replacement of these breakers. BREAKER NUMBER INTERRUPTION RATING SC FAULT CURRENT W/O NEWMAN 5 SC FAULT CURRENT WITH NEWMAN 5 Rio Grande B 23,000 23,916 24, B 23,000 23,916 24, B 23,000 23,916 24, B 23,000 23,916 24, B 23,000 23,916 24, B 23,000 23,916 24,549 However, in the 2009 case, the fault current to at the Rio Grande 115 kv bus exceeds the interruption rating of one (1) existing circuit breaker. The table below shows that the overloading of this breaker is due to the addition of the proposed Newman 5 project. INTERRUPTION RATING SC FAULT CURRENT W/O NEWMAN 5 SC FAULT CURRENT WITH NEWMAN 5 SUBSTATION BREAKER NUMBER Rio Grande ,000 23,616 24,186 Therefore, under Transmission Configuration 2, XXX will be responsible for the cost of replacing one new circuit breaker at the Rio Grande 69 kv bus. Short Circuit Analysis for a 10 El Paso Electric Company
12 IV. Results and Conclusions A short circuit study was performed on the EPE system comparing the maximum fault current on the system at various substations: Newman 115 kv Substation and selected substations in the EPE system, both with and without the new generation proposed at Newman 115 kv. In addition, two transmission configurations were analyzed to model potential interconnections involving the interconnection of an additional 144 MW of proposed generation at the existing Afton Substation. Transmission Configuration 1 assumes that the transmission configuration of the Luna- Afton-Newman 345 kv line remains as it exists now, with the line divided into two segments 1) Luna to Afton 345 kv substation 2) Afton to Newman 345 kv substation. Transmission Configuration 2 assumes that the Afton substation is interconnected to the Luna-Afton-Newman 345 kv line as it is in Configuration 1 and it is also tied in to the Luna-Diablo 345 kv line as follows 1) Luna to Afton 345 kv substation 2) Afton to Diablo 345 kv substation Ultimately, a Study for the proposed Afton project that is currently in progress will determine which transmission configuration will be used to interconnect the additional 144 MW of the potential generation to the EPE system. The tables below show the results of the short circuit analyses for Transmission Configuration 1 and Transmission Configuration 2. A. Short Circuit Results for Proposed New Generation at Newman 115 kv Using Transmission Configuration 1 Maximum Fault Current With Proposed Minimum Circuit Breaker Generation Addition Substation Interruption Rating (Amps) (Amps) Diablo 345 kv Bus 40, ,562.0 Diablo 115 kv Bus 31, ,323.0 Newman 345 kv Bus 40, ,746.0 Newman 115 kv Bus 40, ,787.0 Rio Grande 115 kv Bus* 23, ,819.0 Rio Grande 69 kv Bus* 24, ,753.0 Short Circuit Analysis for a 11 El Paso Electric Company
13 Results of the analysis for Transmission Configuration 1 indicate that the fault current at the Rio Grande 115 kv bus for a single line-to-ground fault exceeded the breaker interruption rating of six existing breakers. From the list of circuit breakers at the Rio Grande 115 kv bus on page 5, the maximum fault current at this bus for a single line-toground fault exceeded the 23,000 ampere interruption rating of six breakers. This was due to the addition of the proposed CT at Newman 115 kv bus in Therefore, the addition of new generation at the Newman 115 kv bus in 2006 will require that six existing circuit breakers at the Rio Grande 115 kv Substation with 23,000 amp ratings be replaced with six new breakers with higher breaker interruption ratings in B. Short Circuit Results for Proposed New Generation at Newman 115 kv Using Transmission Configuration 2 Maximum Fault Current With proposed Minimum Circuit Breaker Generation Addition Substation Interruption Rating (Amps) (Amps) Diablo 345 kv Bus 40, ,022.0 Diablo 115 kv Bus 31, ,323.0 Newman 345 kv Bus 40, ,217.0 Newman 115 kv Bus 40, ,821.0 Rio Grande 115 kv Bus* 23, ,059.0 Rio Grande 69 kv Bus* 24, ,186.0 Results of the analysis for Transmission Configuration 2 indicate that fault currents for a single line-to-ground fault exceeded breaker interruption rating of six existing breakers at the Rio Grande 115 kv bus and one breaker at the Rio Grande 69 kv bus. From the list of circuit breakers at the Rio Grande 115 kv bus on page 5, the maximum fault current for a single line-to-ground fault exceeded the 23,000 ampere interruption rating of six breakers. In Transmission Configuration 2, the fault current exceeded 23,000 amps for a single line-to-ground fault due to the addition of proposed generation interconnected at the existing Afton Substation as modeled in this short circuit analysis in This potential project occurs in the study queue prior to the addition of new generation at the Newman 115 kv bus. Therefore, under this transmission configuration, the owner of this proposed project is responsible for the cost of replacing the six existing 23,000 amp circuit breakers at Rio Grande 115 kv Substation. However, the list of circuit breaker ratings at the Rio Grande 69 kv bus on page 6 indicates that the maximum fault current at this bus for a single line-to-ground fault exceeded the 24,000 amp circuit breaker interruption rating of one existing circuit breaker due to the addition of the proposed new generation at the Newman 115 kv bus in Therefore, under this configuration, XXX is responsible for the cost of replacing one 69 kv breaker at the Rio Grande 69 kv bus with a circuit breaker with an interruption rating above 24,000 amps in Short Circuit Analysis for a 12 El Paso Electric Company
14 The estimated costs to replace the breakers XXX will be responsible under each of the configurations analyzed are shown below: XXX ESTIMATED COSTS FOR BREAKER REPLACEMENT UNDER TRANSMISSION CONFIGURATION 1 SUBSTATION BREAKER NUMBER YEAR ESTIMATED COST (2003$) Rio Grande B 2006 $60, B 2006 $60, B 2006 $60, B 2006 $60, B 2006 $60, B 2006 $60,000 TOTAL XXX BREAKER REPLACEMENT COSTS $360,000 XXX ESTIMATED COSTS FOR BREAKER REPLACEMENT UNDER TRANSMISSION CONFIGURATION 2 SUBSTATION BREAKER NUMBER YEAR ESTIMATED COST (2003$) Rio Grande $40,000 TOTAL XXX BREAKER REPLACEMENT COSTS $40,000 Short Circuit Analysis for a 13 El Paso Electric Company
15 V. Certification This Short Circuit Analysis was performed pursuant with a Generation Interconnection Facilities Study requested by XXXXXXXXXXXXXXXXXXXXXXXXXXXX (XXX). The generator, step-up transformer and new transmission line parameters were supplied by XXX. The Short Circuit Analysis was performed by El Paso Electric Company s Transmission & Distribution Division (EPE T&D). Name: Title: Dennis H. Malone Manager, System Planning Signature: Dennis H. Malone Company: El Paso Electric Company Date: Short Circuit Analysis for a 14 El Paso Electric Company
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX TRANSMISSION/GENERATION FEASIBILITY STUDY SHORT CIRCUIT ANALYSIS
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX TRANSMISSION/GENERATION FEASIBILITY STUDY SHORT CIRCUIT ANALYSIS El Paso Electric Company System Operations Department System Planning Section September 2001 Short Circuit
More informationXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX TRANSMISSION AND FACILITIES STUDY. Short Circuit Analysis
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX TRANSMISSION AND FACILITIES STUDY Short Circuit Analysis System Operations Department System Planning Section March 2001 I. Introduction XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
More informationShort Circuit Analysis with New Generation Proposed by XXXXXXXXXXXXXXXXXXXXXX Pursuant to a Transmission and Facilities Study
Short Circuit Analysis with New Generation Proposed by XXXXXXXXXXXXXXXXXXXXXX Pursuant to a Transmission and Facilities Study Study Performed by El Paso Electric Company System Planning Section - 1 I.
More informationEL PASO ELECTRIC COMPANY SHORT CIRCUIT ANALYSIS FOR XXX S PROPOSED GENERATION INTERCONNECTION
EL PASO ELECTRIC COMPANY SHORT CIRCUIT ANALYSIS FOR XXX S PROPOSED GENERATION INTERCONNECTION El Paso Electric Company System Operations Department System Planning Section August 2006 I. INTRODUCTION The
More informationGeneration Interconnection Feasibility Study For XXXXXXXXXXXXXXXXXXXXXX MW generator at new Western Refinary Substation
Generation Interconnection Feasibility Study For XXXXXXXXXXXXXXXXXXXXXX 131-250 MW generator at new Western Refinary Substation System Planning Section April, 2005 TABLE OF CONTENT 1 EXECUTIVE SUMMARY
More informationEL PASO ELECTRIC COMPANY (EPE) FACILITIES STUDY FOR PROPOSED HVDC TERMINAL INTERCONNECTION AT NEW ARTESIA 345 KV BUS
EL PASO ELECTRIC COMPANY (EPE) FACILITIES STUDY FOR PROPOSED HVDC TERMINAL INTERCONNECTION AT NEW ARTESIA 345 KV BUS El Paso Electric Company System Operations Department System Planning Section May 2004
More informationXXXXXXXXXXXXXXXX Transmission Interconnection Feasibility Study
XXXXXXXXXXXXXXXX Transmission Interconnection Feasibility Study System Operations Department System Planning Section March 2002 Table of Contents: 1.0 EXECUTIVE SUMMARY 4 2.0 COST ESTIMATES 8 2.1 Cost
More informationXXXXXXXXXXXXXXXXXXXXXXXXX TRANSMISSION/GENERATION FEASIBILITY STUDY FATAL FLAW AND FEASIBILITY ANALYSIS
XXXXXXXXXXXXXXXXXXXXXXXXX TRANSMISSION/GENERATION FEASIBILITY STUDY FATAL FLAW AND FEASIBILITY ANALYSIS System Operations Department System Planning Section June 2001 TABLE OF CONTENTS 1.0 Executive Summary...Page
More informationEL PASO ELECTRIC COMPANY (EPE) GENERATOR INTERCONNECTION SYSTEM IMPACT STUDY FOR PROPOSED XXXXXXXXXXXXXXXXXX GENERATION ON THE AMRAD-ARTESIA 345 KV
EL PASO ELECTRIC COMPANY (EPE) GENERATOR INTERCONNECTION SYSTEM IMPACT STUDY FOR PROPOSED XXXXXXXXXXXXXXXXXX GENERATION ON THE AMRAD-ARTESIA 345 KV LINE El Paso Electric Company System Planning Department
More information120 MW SOLAR-THERMAL PLANT GENERATOR INTERCONNECTION FEASIBILITY STUDY. May 2008 Prepared by: EL PASO ELECTRIC COMPANY
. 120 MW SOLAR-THERMAL PLANT GENERATOR INTERCONNECTION May 2008 Prepared by: EL PASO ELECTRIC COMPANY Foreword This report was prepared for XXXXXXXXXXXXXXXXXXX by System Planning at El Paso Electric Company.
More informationXXXXXXXXXXXXXXXXXXXXXXXXXXXX TRANSMISSION/GENERATION FEASIBILITY STUDY FATAL FLAW AND FEASIBILITY ANALYSIS
XXXXXXXXXXXXXXXXXXXXXXXXXXXX TRANSMISSION/GENERATION FEASIBILITY STUDY FATAL FLAW AND FEASIBILITY ANALYSIS El Paso Electric Company System Operations Department System Planning Section September 2001 TABLE
More informationEl PASO ELECTRIC COMPANY 2014 BULK ELECTRIC SYSTEM TRANSMISSION ASSESSMENT FOR YEARS
El Paso Electric Company El PASO ELECTRIC COMPANY 2014 BULK ELECTRIC SYSTEM TRANSMISSION ASSESSMENT FOR YEARS 2015 2024 A Review on System Performance Following Extreme Bulk Electric System Events of the
More informationXXXXXXXXXXXXXX 99 MW WIND PARK GENERATOR INTERCONNECTION FEASIBILITY STUDY. September 2008 Prepared by: EL PASO ELECTRIC COMPANY
XXXXXXXXXXXXXX 99 MW WIND PARK GENERATOR INTERCONNECTION FEASIBILITY STUDY September 2008 Prepared by: EL PASO ELECTRIC COMPANY Foreword This report was prepared for XXXXXXXXXXXXX (XXX) of XXXXXXXX by
More informationEl Paso Electric Company
Feasibility Study XXXXXX Solar Generation Prepared for El Paso Electric Company Prepared by TRC Engineers, LLC 249 Eastern Avenues Augusta, ME 04330 (207) 621-7000 Project Number: 202327 May 2013 FOREWORD
More information300 MW SOLAR PHOTOVOLTAIC PLANT, GENERATOR INTERCONNECTION FEASIBILITY STUDY
300 MW SOLAR PHOTOVOLTAIC PLANT, GENERATOR INTERCONNECTION FEASIBILITY STUDY El Paso Electric Company System Planning August 2006 TABLE OF CONTENTS 1.0 EXECUTIVE SUMMARY...Page 1 2.0 PURPOSE...Page 7 3.0
More informationENERGY RESOURCE INTERCONNECTION SERVICE STUDY DRAFT REPORT
ENERGY RESOURCE INTERCONNECTION SERVICE STUDY DRAFT REPORT ART320W 320 MW Wind Powered Project Prepared for: El Paso Electric Company Prepared by: TRC Engineers, LLC 249 Western Avenue Augusta, ME 04330
More informationSYSTEM IMPACT STUDY REPORT LA450S GENERATION STUDY. El Paso Electric Company
SYSTEM IMPACT STUDY REPORT LA450S GENERATION STUDY Prepared for: El Paso Electric Company Prepared by: Engineers, LLC 1526 Cole Boulevard Building 3, Suite 150 Lakewood, CO 80401 (303) 395-4018 FOREWORD
More informationSYSTEM IMPACT RESTUDY H252W ERIS REPORT. El Paso Electric Company
SYSTEM IMPACT RESTUDY H252W ERIS REPORT Prepared for: El Paso Electric Company Prepared by: Engineers, LLC 1526 Cole Boulevard Building 3, Suite 150 Lakewood, CO 80401 (303) 395-4018 FOREWORD This report
More informationSYSTEM IMPACT STUDY EC300W ERIS FINAL REPORT. El Paso Electric Company
SYSTEM IMPACT STUDY EC300W ERIS FINAL REPORT Prepared for: El Paso Electric Company Prepared by: Engineers, LLC 1526 Cole Boulevard Building 3, Suite 150 Lakewood, CO 80401 (303) 395-4018 FOREWORD This
More informationProject #148. Generation Interconnection System Impact Study Report
Project #148 Generation Interconnection System Impact Study Report June 05, 2012 Electric Transmission Planning Table of Contents Table of Contents... 2 Executive Summary... 3 Energy Resource Interconnection
More informationFeasibility Study. Shaw Environmental, Inc. 12MW Landfill Gas Generation Interconnection. J.E.D. Solid Waste Management Facility. Holopaw Substation
Feasibility Study Shaw Environmental, Inc. 12MW Landfill Gas Generation Interconnection J.E.D. Solid Waste Management Facility Holopaw Substation September 2013 1 of 12 Table of Contents GENERAL... 3 SHORT
More informationLegal Name of the Customer (or, if an individual, individual's name): Name: Contact Person: Mailing Address: Physical Address: City: State: Zip Code:
Generating Facility Level 2 or 3 Interconnection Review (For Generating Facilities with Electric Nameplate Capacities no Larger than 20 MW) Instructions An Interconnection Customer who requests a Utah
More informationElbert County 500 MW Generation Addition Interconnection Feasibility Study Report OASIS POSTING # GI
Executive Summary Elbert County 500 MW Generation Addition Interconnection Feasibility Study Report OASIS POSTING # GI-2003-2 Xcel Energy Transmission Planning January 2004 This Interconnection Feasibility
More informationPID 274 Feasibility Study Report 13.7 MW Distribution Inter-Connection Buras Substation
PID 274 Feasibility Study Report 13.7 MW Distribution Inter-Connection Buras Substation Prepared by: Entergy Services, Inc. T & D Planning L-ENT-17A 639 Loyola Avenue New Orleans, LA 70113 Rev Issue Date
More informationProject #94. Generation Interconnection System Impact Study Report Revision
Project #94 Generation Interconnection System Impact Study Report Revision October 2, 2009 Electric Transmission Planning Table of Contents Table of Contents...2 Executive Summary...3 Energy Resource Interconnection
More informationPJM Generator Interconnection R81 Emilie (Fords Mill) MW Impact Study Re-Study
PJM Generator Interconnection R81 Emilie (Fords Mill) 100.9 MW Impact Study Re-Study August 2008 DMS # 498781 General Queue R81 Emilie (Fords Mills) is a Fairless Energy, LLC request to obtain an additional
More informationWheeler Ridge Junction Substation Project Description and Functional Specifications for Competitive Solicitation
Wheeler Ridge Junction Substation Project Description and Functional Specifications for Competitive Solicitation 1. Description In the 2013-2014 Transmission Planning Cycle, the ISO approved the construction
More informationInterconnection Feasibility Study Report GIP-226-FEAS-R3
Interconnection Feasibility Study Report GIP-226-FEAS-R3 System Interconnection Request #226 70 MW Wind Generating Facility Kings County (L-6013) 2010 07 21 Control Centre Operations Nova Scotia Power
More informationRULE 21 GENERATING FACILITY INTERCONNECTION APPLICATION SMUD s Distribution System - (SMUD FORM 2655)
- (SMUD FORM 2655) A. Applicability: This Generating Facility Interconnection Application (Application) shall be used to request the interconnection of a Generating Facility to Sacramento Municipal Utility
More informationPJM Generator Interconnection Request Queue #R60 Robison Park-Convoy 345kV Impact Study September 2008
PJM enerator Interconnection Request Queue #R60 Robison Park-Convoy 345kV Impact Study 504744 September 2008 PJM Interconnection 2008. All rights reserved R60 Robison Park-Convoy 345kV Impact Study eneral
More informationGENERATING FACILITY INTERCONNECTION APPLICATION. Part 1 Introduction and Overview
Part 1 Introduction and Overview A. Applicability: This Generating Facility Interconnection Application (Application) is used to request the interconnection of a Generating Facility to Southern California
More informationNew Mexico Transmission Expansion Concepts For Wind Resources
New Mexico Transmission Expansion Concepts For Wind Resources May 2008 Update Electric Services Transmission Operations FOREWORD This document contains PNM s latest concepts for expanding the transmission
More informationABB POWER SYSTEMS CONSULTING
ABB POWER SYSTEMS CONSULTING DOMINION VIRGINIA POWER Offshore Wind Interconnection Study 2011-E7406-1 R1 Summary Report Prepared for: DOMINION VIRGINIA POWER Report No.: 2011-E7406-1 R1 Date: 29 February
More informationNORTH CAROLINA INTERCONNECTION REQUEST APPLICATION FORM. Utility: Duke Energy Progress
NORTH CAROLINA INTERCONNECTION REQUEST APPLICATION FORM ATTACHMENT 2 Utility: Duke Energy Progress Designated Utility Contact: Attention: Customer Owned Generation Mail Code ST13A E-Mail Address: Customerownedgeneration@duke-energy.com
More informationCUSTOMER/ TWIN ARROWS PROJECT
A subsidiary of Pinnacle West Capital Corporation CUSTOMER/ TWIN ARROWS PROJECT V1 Facility Study Report APS Contract 52149 Prepared by: Arizona Public Service Company Transmission & Distribution Asset
More informationVerde Transmission, LLC. Verde Project. System Impact Study Report
Verde Transmission, LLC Verde Project System Impact Study Report March 2017 Prepared by: Public Service Company of New Mexico Foreword This report was prepared for Verde Transmission, LLC by the PNM Transmission/
More informationFeasibility Study Report
Generator Interconnection Request Feasibility Study Report For: Customer --- Service Location: Rutherford County Total Output: 79.2 MW Commercial Operation Date: 9/1/2014 In-Service Date (if given): 9/1/2014
More informationRequest for Payment Instructions Wholesale Distribution Access Tariff (WDAT) Attachment I - GIP
Grid Interconnection & Contract Development Request for Payment Instructions Wholesale Distribution Access Tariff (WDAT) Attachment I - GIP Submittal Instructions Prior to submitting your application and
More informationEE 456 Design Project
F-2014 EE 456 Design Project PROJECT REPORT MALUWELMENG, CONNIE SHARP, MEGAN Table of Contents Introduction... 2 Assignment I... 2 Setup... 2 Simulation... 2 Assignment II... 3 Problems... 3 Solution...
More informationLevel 2, Level 3 & Level 4 Interconnection Request Application Form (Greater than 25 kw to 10 MVA or less)
Level 2, Level 3 & Level 4 Interconnection Request Application Form (Greater than 25 kw to 10 MVA or less) Interconnection Customer Contact Information Name Alternative Contact Information (if different
More informationTHE NECESSITY OF THE 500 KV SYSTEM IN NWE S TRANSMISSION SYSTEM TO MAINTAIN RELIABLE SERVICE TO MONTANA CUSTOMERS
THE NECESSITY OF THE 500 KV SYSTEM IN NWE S TRANSMISSION SYSTEM TO MAINTAIN RELIABLE SERVICE TO MONTANA CUSTOMERS 2/27/2018 ELECTRIC TRANSMISSION PLANNING Table of Contents Table of Contents... 2 Executive
More informationFeasibility Study for the Q MW Solar Project
Feasibility Study for the Q171 74.5 MW Solar Project August 2018 Bulk Transmission Planning, Florida i This document and any attachments hereto ( document ) is made available by Duke Energy Florida, LLC
More informationGenerator Interconnection Facilities Study For SCE&G Two Combustion Turbine Generators at Hagood
Generator Interconnection Facilities Study For SCE&G Two Combustion Turbine Generators at Hagood Prepared for: SCE&G Fossil/Hydro June 30, 2008 Prepared by: SCE&G Transmission Planning Table of Contents
More informationCIS-IEEE 2017 Conference Renewable Energy Session Renewable Energy s Impact of Power Systems
CIS-IEEE 2017 Conference Renewable Energy Session Renewable Energy s Impact of Power Systems Ben Huckaba, P.E. President & Principal Engineer 317-273-9841 benh@alphaeng.us Indiana University Bloomington,
More informationFeasibility Study Report
Report For: Fresh Air Energy II, LLC ( Customer ) Queue #: Service Location: Chester County, SC Total Output Requested By Customer: 74.5 MW Commercial Operation Date Requested By Customer: 1/7/2019 Feasibility
More informationMILLIGAN SOLAR PROJECT
February 16, 2009 Page 1 of 18 A subsidiary of Pinnacle West Capital Corporation MILLIGAN SOLAR PROJECT FINAL Feasibility Study Report APS Contract 52115 Prepared by: Arizona Public Service Company Transmission
More informationPSNH INTERCONNECTION REQUEST
PSNH INTERCONNECTION REQUEST Send the completed Interconnection Request and required attachments to: Public Service of New Hampshire Attn: Michael Motta, Senior Engineer Supplemental Energy Sources P.
More informationFinal Draft Report. Assessment Summary. Hydro One Networks Inc. Longlac TS: Refurbish 115/44 kv, 25/33/ General Description
Final Draft Report Assessment Summary Hydro One Networks Inc. : Refurbish 115/44 kv, 25/33/42 MVA DESN Station CAA ID Number: 2007-EX360 1.0 General Description Hydro One is proposing to replace the existing
More informationInterconnection Feasibility Study Report GIP-222-FEAS-R3
Interconnection Feasibility Study Report GIP-222-FEAS-R3 System Interconnection Request #222 48 MW Steam Generating Facility Pictou County (53N) 2010 07 30 Control Centre Operations Nova Scotia Power Inc.
More informationGenerator Interconnection System Impact Study For
Generator Interconnection System Impact Study For Prepared for: January 15, 2015 Prepared by: SCE&G Transmission Planning Table of Contents General Discussion... Page 3 I. Generator Interconnection Specifications...
More informationInterconnection System Impact Study Report Request # GI
Executive Summary Interconnection System Impact Study Report Request # GI-2008-23 34 MW Solar Generation Ranch at Hartsel, Colorado Public Service Company of Colorado Transmission Planning August 19, 2010
More informationGeneration Interconnection Facilities Study For
Generation Interconnection Facilities Study For Prepared for: Prepared by: SCE&G Transmission Planning May 27, 2015 TABLE OF CONTENTS General Discussion... Page 3 Generator Interconnection Specifications...
More informationSPS Planning Criteria and Study Methodology
SPS Planning Criteria and Study Methodology SPS subscribes to the Southwest Power Pool ("SPP") Reliability Criteria, which incorporates compliance with the appropriate North American Electric Reliability
More informationTransmission Improvements Plan for 575 MW Network Service Request Wansley CC 7 Generation Facility (OASIS # ) Georgia Transmission Corporation
Transmission Improvements Plan for 575 MW Network Service Request CC 7 Generation Facility (OASIS # 143556) Georgia Transmission Corporation November 11, 2010 CC7 TIP 11-11-2010 (2).docx PROBLEM STATEMENT
More informationAn Alternative to Reduce Medium-Voltage Transient Recovery Voltage Peaks
An Alternative to Reduce Medium-Voltage Transient Recovery Voltage Peaks D. M. Nobre W. L. A. Neves B. A. de Souza Departamento de Engenharia Elétrica - UFPB Av. Aprígio Veloso, 882 Bodocongó 58.109-970,
More informationTRANSMISSION PLANNING CRITERIA
CONSOLIDATED EDISON COMPANY OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003-3502 Effective Date: TRANSMISSION PLANNING CRITERIA PURPOSE This specification describes Con Edison s Criteria for assessing
More informationMaryland Level 2, Level 3 & Level 4 Interconnection Request Application Form (Greater than 10 kw to 10 MW or less)
Maryland Level 2, Level 3 & Level 4 Interconnection Request Application Form (Greater than 10 kw to 10 MW or less) Interconnection Customer Contact Information Name: Address: Alternative Contact Information
More informationCHAPER 5 POWER FLOW STUDY IN THE INTEGRATED GRID NETWORK
91 CHAPER 5 POWER FLOW STUDY IN THE INTEGRATED GRID NETWORK CHAPTER CONTENTS: 5.1 INTRODUCTION 5.2 CONDUCTION OF VARIOUS POWER FLOW STUDIES ON THE MODEL 5.3 EXPERIMENTS CONDUCTED FOR VARIOUS POWER FLOW
More informationTransmission Planning & Engineering P.O. Box MS 3259 Phoenix, Arizona
Transmission Planning & Engineering P.O. Box 53933 MS 3259 Phoenix, Arizona 85072-3933 March 9, 2016 Mr. Philip Augustin Chair, WECC Technical Studies Subcommittee Mr. Enoch Davies WECC Technical Staff
More informationPUD ELECTRIC SYSTEM INTERCONNECTION
APPENDIX A PROCEDURES & REQUIREMENTS for OKANOGAN PUD ELECTRIC SYSTEM INTERCONNECTION Version 4.0 December 2011 Version 4.0 12/28/2011 Page 1 of 15 TABLE OF CONTENTS DEFINITIONS 1.0 Introduction 2.0 Procedures
More informationShippensburg University
Shippensburg University 1871 Old Main Drive Shippensburg, PA 17257 SUPPLEMENT 1 Electrical Coordination Study Professional: Entech Engineering, Inc. 4 South Fourth Street P.O. Box 32 Reading, PA 19603
More informationConsulting Agreement Study. Completed for Transmission Customer
Completed for Transmission Customer Proposed Resource & Transmission Carbon County, MT & 230 kv Transmission in North Wyoming August 2016 Table of Contents 1.0 Description... 1 2.0 Overall Assumptions...
More informationObservations from Avista Short Circuit Analysis WECC Short Circuit Workgroup January 2018 Tracy Rolstad
Observations from Avista Short Circuit Analysis WECC Short Circuit Workgroup January 2018 Tracy Rolstad The Driver (TPL-001, R2.3) With apologies to Protection folks this is all about a Planner s perspective.
More informationInterconnection Feasibility Study Report GIP-157-FEAS-R2
Interconnection Feasibility Study Report GIP-157-FEAS-R2 System Interconnection Request #157 100.5 MW Wind Generating Facility Guysborough County (L-6515) 2009 09 14 Control Centre Operations Nova Scotia
More informationQ0044 interconnection at
Generation Interconnection Feasibility Study Report for Q0044 interconnection at Utah County Utah on PacifiCorp s Transmission System (138 kv Transmission System) September 15, 2004 Page 1 1.0 Description
More informationInterconnection Feasibility Study Report GIP-023-FEAS-R1. Generator Interconnection Request # MW Wind Generating Facility Inverness (L6549), NS
Interconnection Feasibility Study Report GIP-023-FEAS-R1 Generator Interconnection Request # 23 100 MW Wind Generating Facility Inverness (L6549), NS February 16, 2006 Control Centre Operations Nova Scotia
More informationCHAPTER 4 PROTECTION REQUIREMENTS
CHAPTER 4 PROTECTION REQUIREMENTS CHAPTER 4 PROTECTION REQUIREMENTS 4.1 General Means of protection for automatic disconnection against phase and earth faults shall be provided on the customer main switch.
More informationSystem Impact Study Report
Report For: NTE Carolinas II, LLC ( Customer ) Queue #: 42432-01 Service Location: Rockingham County, NC Total Output: 477 MW (summer) / 540 MW (winter) Commercial Operation Date: 12/1/2020 42432-01 SIS
More informationMarch 2017 to June 2017 Preliminary Interconnection Cluster Window System Impact Study 49.9 MW IA-PNM May 2018
March 2017 to June 2017 Preliminary Interconnection Cluster Window System Impact Study 49.9 MW IA-PNM-2017-11 May 2018 Prepared by: Public Service Company of New Mexico Foreword This report is prepared
More informationLarge Load Serving Study Report for La Plata Electric Association, Inc. Alternatives. Addendum. San Juan Major Project
Large Load Serving Study Report for La Plata Electric Association, Inc. Alternatives Addendum San Juan Major Project Tri-State Generation and Transmission Association Power System Planning December, 2008
More informationPOWER SYSTEM INCIDENT REPORT: TRIP OF NO 1 AND 2 NEW OSBORNE 66 KV BUSBARS ON 26 SEPTEMBER 2010
POWER SYSTEM INCIDENT REPORT: TRIP OF NO 1 AND 2 NEW OSBORNE 66 KV BUSBARS ON 26 SEPTEMBER 2010 PREPARED BY: Electricity System Operations Planning and Performance FINAL Disclaimer (a) Purpose - This report
More informationFeasibility Study. Customer Kingman Area Photovoltaic Generation Project Interconnection
Feasibility Study Customer Kingman Area Photovoltaic Generation Project Interconnection October, 2009 October 2009 i EXECUTIVE SUMMARY CONCLUSION Customer has requested network resource interconnection
More informationInterconnection System Impact Study Final Report February 19, 2018
Interconnection System Impact Study Final Report February 19, 2018 Generator Interconnection Request No. TI-17-0225 248.4 MW (Alternate Project Output of 217.35 MW) Wind Energy Generating Facility In Goshen
More informationLevel 2, Level 3 & Level 4 Interconnection Request Application Form (Greater than 10 kva to 10 MVA or less)
Section 466.APPENIX C Levels 2 to 4 Application Level 2, Level 3 & Level 4 Interconnection Request Application Form (Greater than 10 kva to 10 MVA or less) Interconnection Customer Contact Information
More informationTOLTEC POWER PARTNERSHIP TOLTEC POWER PROJECT INTERCONNECTION STUDY SYSTEM IMPACT STUDY
TOLTEC POWER PARTNERSHIP TOLTEC POWER PROJECT INTERCONNECTION STUDY SYSTEM IMPACT STUDY January 7, 2002 Prepared by Jorge Chacon (Consultant) Tucson Electric Power Company Ed Beck ii EXECUTIVE SUMMARY
More informationSolar Photovoltaic Inverter Current Distribution during Fault on Distribution and Transmission System
Solar Photovoltaic Inverter Current Distribution during Fault on Distribution and Transmission System Rishabh Pandey, Uttam Singh, Varun Sachdeva, Jaikaran Singh Department of Electronic and Communication
More informationInterconnection Feasibility Study Report GIP-084-FEAS-R2
Interconnection Feasibility Study Report GIP-084-FEAS-R2 System Interconnection Request #84 50 MW Wind Generating Facility Pictou County (L-7004) August 17, 2007 Control Centre Operations Nova Scotia Power
More informationAMERICAN ELECTRIC POWER 2017 FILING FERC FORM 715 ANNUAL TRANSMISSION PLANNING AND EVALUATION REPORT PART 4 TRANSMISSION PLANNING RELIABILITY CRITERIA
AMERICAN ELECTRIC POWER 2017 FILING FERC FORM 715 ANNUAL TRANSMISSION PLANNING AND EVALUATION REPORT PART 4 TRANSMISSION PLANNING RELIABILITY CRITERIA AEP Texas (comprised of its Central and North Divisions
More informationAPPENDIX E: Project Need and Description
APPENDIX E: Project Need and California ISO/MID E-1 Intentionally left blank California ISO/MID E-2 Lakeville 115 kv Bus Upgrade Installation of a sectionalizing breaker to be installed on 115 kv bus section
More informationAPPENDIX E: Project Need and Description
APPENDIX E: Project Need and California ISO/MID E-1 Intentionally left blank California ISO/MID E-2 Tyler 60 kv Shunt Capacitor Installation of a 2x10 MVAR capacitor bank at Tyler 60 kv bus Objectives
More informationElectrical Handbook Fault Calculations Using The Mva Method
Electrical Handbook Fault Calculations Using The Mva Method In the power systems analysis field of electrical engineering, a per-unit system is the Calculations are simplified because quantities expressed
More informationRequest for Payment Instructions Rule 21 Export Submittal Instructions
Grid Interconnection & Contract Development Request for Payment Instructions Rule 21 Export Submittal Instructions Prior to submitting your application and fee or deposit, please complete and submit this
More informationFeasibility Study for the Q MW Solar Project
Feasibility Study for the Q174 74.5 MW Solar Project August 2018 Bulk Transmission Planning, Florida i This document and any attachments hereto ( document ) is made available by Duke Energy Florida, LLC
More informationFeasibility Study Report
Report For: Orion Renewable Resources LLC ( Customer ) Queue #: Service Location: Rockingham County, NC Total Output Requested By Customer: 100 MW Commercial Operation Date Requested By Customer: 11/1/2019
More information100 MW Wind Generation Project
A subsidiary of Pinnacle West Capital Corporation 100 MW Wind Generation Project CUSTOMER FINAL Feasibility Study Results By Transmission Planning, APS December 21, 2007 Executive Summary This Feasibility
More informationGenerating unit functional document submission form
Generating unit functional document submission form The below form must be completed and returned to generator.reports@aeso.ca. Supporting information to assist generating unit owners to complete this
More informationGeorgia Transmission Corporation Georgia Systems Operations Corporation
Georgia Transmission Corporation Georgia Systems Operations Corporation Reactive Power Requirements for Generating Facilities Interconnecting to the Georgia Integrated Transmission System with Georgia
More informationMaryland Level 2, Level 3 & Level 4 Interconnection Request Application Form (Greater than 10 kw to 10 MW or less)
Maryland Level 2, Level 3 & Level 4 Interconnection Request Application Form (Greater than 10 kw to 10 MW or less) Interconnection Customer Contact Information Name: Address: City: Telephone (aytime):
More informationAnalysis of Power System Impacts and Frequency Response Performance: February 1-4, 2011 Texas and Southwestern U.S. Cold Snap
Analysis of Power System Impacts and Frequency Response Performance: February 1-4, 2011 Texas and Southwestern U.S. Cold Snap September, 2011 1 NERC s Mission NERC s Mission The North American Electric
More informationSTATE OF MINNESOTA OFFICE OF ADMINISTRATIVE HEARINGS FOR THE PUBLIC UTILITIES COMMISSION PUC DOCKET NO. E002/TL OAH DOCKET NO.
STATE OF MINNESOTA Direct Testimony and Schedule OFFICE OF ADMINISTRATIVE HEARINGS FOR THE PUBLIC UTILITIES COMMISSION Amanda King IN THE MATTER OF THE ROUTE PERMIT APPLICATION FOR THE CAPX00 HAMPTON ROCHESTER
More informationEL PASO ELECTRIC COMPANY SYSTEM EXPANSION PLAN
EL PASO ELECTRIC COMPANY SYSTEM EXPANSION PLAN 2019-2028 Produced by System Planning 2018 GENERAL EL PASO ELECTRIC COMPANY 2019-2028 SYSTEM EXPANSION PLAN Executive Summary El Paso Electric Company s
More informationTexas A&M Microgrid and Electrical System Study. Cushing Memorial Library & Archives
Texas A&M Microgrid and Electrical System Study Cushing Memorial Library & Archives Introduction of Texas A&M Microgrid Study Purpose Why are we studying the TAMU electrical system? Process How do we want
More informationManitoba Hydro Generation Interconnection Exploratory Study Notice September 28, 2006
Manitoba Hydro Generation Interconnection Exploratory Study Notice September 28, 2006 As per the Manitoba Hydro Open Access Interconnection Tariff, the Transmission Owner has contracted TransGrid Solutions
More informationThe Effect Of Distributed Generation On Voltage Profile and Electrical Power Losses Muhammad Waqas 1, Zmarrak Wali Khan 2
International Journal of Engineering Works Kambohwell Publisher Enterprises Vol., Issue 1, PP. 99-103, Dec. 015 www.kwpublisher.com The Effect Of Distributed Generation On Voltage Profile and Electrical
More informationPerformance Analysis of Transient Stability on a Power System Network
Performance Analysis of Transient Stability on a Power System Network Ramesh B Epili 1, Dr.K.Vadirajacharya 2 Department of Electrical Engineering Dr. Babasaheb Ambedkar Technological University, Lonere
More informationFIRSTENERGY S PROPOSED SOLUTION AND REQUEST FOR CONSTRUCTION DESIGNATION
PJM RTEP - Artificial Island Area FIRSTENERGY S PROPOSED SOLUTION AND REQUEST FOR CONSTRUCTION DESIGNATION Part 1 Report REDACTED VERSION FirstEnergy Corp. Energy Delivery, Transmission Planning and Protection
More informationCost Benefit Analysis of Faster Transmission System Protection Systems
Cost Benefit Analysis of Faster Transmission System Protection Systems Presented at the 71st Annual Conference for Protective Engineers Brian Ehsani, Black & Veatch Jason Hulme, Black & Veatch Abstract
More informationInterconnection Feasibility Study Report GIP-369-FEAS-R1
Interconnection Feasibility Study Report GIP-369-FEAS-R1 System Interconnection Request #369 50 MW Wind Generating Facility Cumberland County (L-6513) 2012-02-09 Control Centre Operations Nova Scotia Power
More informationMarket Congestion Planning Study (South)- Robustness Analysis. Economic Planning Users Group Meeting August 11 th, 2017
Market Congestion Planning Study (South)- Robustness Analysis Economic Planning Users Group Meeting August 11 th, 2017 Key Takeaways The benefit calculations were updated due to a flowgate rating correction
More informationCOMPARISON OF DIFFERENT SOFTWARE PACKAGES IN POWER FLOW AND SHORT-CIRCUIT SIMULATION STUDIES. A Project
COMPARISON OF DIFFERENT SOFTWARE PACKAGES IN POWER FLOW AND SHORT-CIRCUIT SIMULATION STUDIES A Project Presented to the faculty of the Department of Electrical and Electronic Engineering California State
More information