Generator Interconnection Facilities Study For SCE&G Two Combustion Turbine Generators at Hagood

Size: px
Start display at page:

Download "Generator Interconnection Facilities Study For SCE&G Two Combustion Turbine Generators at Hagood"

Transcription

1 Generator Interconnection Facilities Study For SCE&G Two Combustion Turbine Generators at Hagood Prepared for: SCE&G Fossil/Hydro June 30, 2008 Prepared by: SCE&G Transmission Planning

2 Table of Contents 1. Introduction General Discussion Generator Information Steady State Contingency Analysis Short Circuit Analysis Stability Analysis Cost Estimates and Completion Dates Recommendations and Conclusions Addendum Appendix: Generator Datasheet... 17

3 Generator Interconnection Facilities Study For SCE&G two gas turbine Generators at Hagood 1. Introduction A Generator Interconnection Facilities Study is normally performed after the Generation Interconnection Feasibility Study and System Impact Study. At the request of the customer, and because of the size of the generator units, the study process was expedited by consolidating the Feasibility and System Impact studies into the Facilities Study. The Facilities Study specifies and estimates the cost of the equipment, engineering, procurement and construction work needed to implement the conclusions of the Interconnection System Impact Study in accordance with good utility practice to physically and electrically connect the Interconnection Facility to the Transmission System. A Generator Interconnection Facilities Study also identifies the electrical switching configuration of the connection equipment, including, but not limited to: the transformer, switchgear, metering, and other station equipment. The Facilities Study also identifies the nature and estimated cost of any Transmission Provider's Interconnection Facilities and Network Upgrades necessary to accomplish the interconnection. In addition, the Facilities Study provides an estimate of the time required to complete the construction and installation of such facilities. 2. General Discussion This Generation Interconnection Facilities study was requested by SCE&G Fossil/Hydro. Due to the small size of the requested combustion turbines (CT s) which have a maximum capability of MVA each, and the fact that the generation site is located in an existing generation station facility, any feasibility issues should be minimal. Also, the existing generation site is located in a special geographic region such that the amount of generation and load in this region is presently not balanced. Transmission Planning Engineers expect to identify minimal impacts to SCE&G s Transmission system. Transmission Planning therefore agrees with the customer s request to consolidate the System Feasibility and System Impact studies into this Facilities Study. In this study, SCE&G Fossil/Hydro requested a two gas turbine generation configuration at the Hagood 115kV bus. Each gas turbine has a maximum output of 27 MW, to be installed before May 30, SCE&G Generation Group requested this generation to be interconnected to the existing transmission grid at Hagood. Both generation units will be connected through a single generator step up transformer to the Hagood station 115 kv bus (refer to diagram 1 below). 3

4 Diagram 1. Hagood Substation showing arrangement of Hagood units 2 and 3 and equipment ratings NERC Reliability Standards require that SCE&G Fossil/Hydro consult with SCE&G Transmission Planning to determine the appropriate transformer tap position. For the purposes of this study it was assumed that the transformer tap position would be the same as for the similarly sized Bushy Park CT s. 3. Generator Information The gas turbine generator manufacturer s design data used in this study are included in the Appendix. 4

5 4. Steady State Contingency Analysis 4.1. Power Flow Model Assumptions Transmission Planning performed steady-state contingency analysis for the 2008 and 2010 summer peak load conditions was selected for study as the in-service year for the generators. Additional analysis was performed for 2010 as well. There are several key assumptions made in the 2008 and 2010 base case that affect the results. Those assumptions are: 1. A.M. Williams is generating with a net output of 593 MW 2. Faber Place CT is not generating (it is scheduled to be retired before Hagood units 2 and 3 are in service) 3. Westvaco Cogen is generating with a net output of 90 MW 4. Bushy Park CT s are generating with a net output of 52 MW 5. Thomas Island-Hobcaw 115kV UG Cable is complete and energized. 6. All transmission capacitor banks in the Charleston area are in service and on voltage control. 7. The total net output from Hagood Station, including unit 1 as well as the two proposed units 2 and 3 is 134 MW. Also, in order to simulate a worse case MVA output of Hagood units 2 and 3, a power factor of 0.85 was simulated at Hagood units 2 and 3 by forcing 17 MVAR output from each unit. This assumes the following output schedule for the Hagood Units: Table Output of Hagood Units for 2008 and 2010 peak Summer Power Flow Models Unit Net MW Output Net MVAR Net MVA Output Output Power Factor Hagood #1 88 Determined by Power Flow Solution Determined by Power Flow Solution Determined by Power Flow Solution Hagood # Hagood # The modeled highside tap ratio for the GSU for Hagood units 2 and 3 is: Significant Network improvements are planned in the Charleston area that affect the power flow associated with the addition of Hagood units 2 and 3. These improvements are scheduled for completion before the summer of 2010, and are included in the 2010 summer peak model used for this study. These improvements are: 1. Rebuild the 115kV Line from Charleston Transmission to Charlotte Street Sub as a double circuit and a fold in one of these circuits at Hagood. 5

6 2. Construct a dedicated 115kV Circuit to the Savage Rd Sub Summer Peak Contingency Analysis Results N-0 (Base case) Results No overloaded facilities were identified in the 2008 summer peak base case with the addition of the proposed units at Hagood N-1 Results Table Overloaded Facilities with the Addition of Hagood Units 2&3 (N-1) 2008 Summer Contingency Overloaded Facility Loading without Hagood #2 and #3* Loading with addition of Hagood #2 and #3* Outage Church Creek Savage Rd 115 kv Line Hagood Grove St 115 kv Line 177 MVA (94%) 196 MVA (103%)** *Percent Loading based on 8 hour Emergency MVA Rating **This overloaded condition assumes that the Savage Rd load is served from the Bee St source post contingency. If the Savage Rd load is not served from the Bee St source post contingency, the Hagood Grove St 115 kv Line will not be overloaded. An operating procedure exists that should be executed after the operation of the Church Ck - St. Andrews 115kV Line due to a fault on the Church Ck Savage Rd section of this line. This operating procedure causes the Savage Rd load to be served from the Queensboro source. Table Highly Loaded Facilities with the Addition of Hagood Units 2&3 (N-1) 2008 Summer Contingency Highly Loaded Facility Loading without Hagood #2 and #3* Loading with addition of Hagood #2 and #3* Outage Church Creek Savage Rd 115 kv Line Grove St Bee St 115 kv Line 161 MVA (85%) 179 MVA (94%) Outage Charleston Transmission Kinder Morgan Tap 115kV Line Outage Kinder Morgan Tap Meeting St Tap 115kV Line Hagood Grove St 115 kv Line 156 MVA (82%) 174 MVA (92%) Hagood Grove St 115 kv Line 154 MVA (81%) 172 MVA (91%) *Percent Loading based on 8 hour Emergency MVA Rating 6

7 N-2 Results: Table Overloaded Facilities with the Addition of Hagood Units 2&3 (N-2) 2008 Summer Contingency Overloaded Facility Loading without Hagood #2 and #3* Loading with addition of Hagood #2 and #3* Outage: 1) Accabee Faber Place 115 kv Line #1 2) Accabee Faber Place 115 kv Line #2 Outage: 1) Charleston Transmission Kinder Morgan Tap 115kV 2) Church Creek Bee Street 115 kv Hagood Grove St 115 kv Line Hagood Grove St 115 kv Line 170 MVA (90%) 191 MVA (101%) 188 MVA (99%) 200 MVA (106%) Summer Peak Contingency Analysis Results N-0 (Base case) Results No overloaded or highly loaded facilities were identified in the 2010 summer peak basecase with the addition of the proposed units at Hagood N-1 Results Single contingency analysis identified no overloaded or highly loaded facilities due to the addition of Hagood units 2 and 3 in the 2010 summer peak model N-2 Results Double contingency analysis identified no overloaded or highly loaded facilities due to the addition of Hagood units 2 and 3 in the 2010 summer peak model. 7

8 5. Short Circuit Analysis 5.1. Short Circuit Model Assumptions Transmission Planning performed short circuit analyses based on 2008 and 2010 transmission system conditions. The 2008 base case was selected for study as the in-service year for the generators. Additional analysis was performed for 2010 as well. The 2010 base case was selected because of planned transmission improvements in and around Hagood that are scheduled to be completed in These improvements are: 1. Rebuild the 115kV Line from Charleston Transmission to Charlotte Street Sub as a double circuit and a fold in one of these circuits at Hagood. 2. Construct a dedicated 115kV Circuit to the Savage Rd Sub Short Circuit Analysis Results System Impedance at point of Interconnection 2008 Conditions The short circuit system equivalent impedance from the SCE&G Transmission System that will be seen at the Hagood 115kV bus in 2008 is: Table System Equivalent Impedances for Hagood units 2 & 3 Short Circuit Study Z positive (p.u.) X/R Z negative (p.u.) X/R Z zero (p.u.) X/R j j j These values are calculated on a 100 MVA base. These values do not include the contribution of the Hagood units 2 and Overstressed Breaker Analysis 2008 Conditions An analysis of the effect of the increased fault current in the SCE&G area for 2008 conditions indicates that no breakers on the SCE&G transmission system will become overstressed in 2008 due to the addition of the two Hagood units 2 and 3. 8

9 Short Circuit Analysis Results The short circuit system equivalent impedance from the SCE&G Transmission System that will be seen at the Hagood 115kV bus in 2010 is: System Impedance at point of Interconnection 2010 Conditions Table System Equivalent Impedances for Hagood units 2 & 3 Short Circuit Study Z positive (p.u.) X/R Z negative (p.u.) X/R Z zero (p.u.) X/R j j j These values are calculated on a 100 MVA base. These values do not include the contribution of the Hagood units 2 and Overstressed Breaker Analysis 2010 Conditions These values are calculated on a 100 MVA base. These values do not include the contribution of the Hagood units 2 and 3. An analysis of the effect of the increased fault current in the SCE&G area for 2010 conditions indicates that no breakers on the SCE&G transmission system will become overstressed in 2010 due to the addition of the two Hagood units 2 and 3. 9

10 6. Stability Analysis 6.1. Overview of Stability Analysis The stability study of the connection of the Hagood units 2 and 3 CT s to the SCE&G transmission system assessed the ability of these generators to remain in synchronism following selected transmission system contingencies. Also reviewed were the adequacy of damping of generation/transmission oscillations and the impact of the proposed generator on the stability performance of other system generators. System voltage responses were examined for indications of voltage instability. In addition, generator frequency responses and the effects of protective system performance were evaluated. The stability study used the higher winter peak capability of the CT s in order to verify that the winter capability would not result in stability issues. Rotor angle responses of SCE&G generators were simulated in order to determine if angular instability could result from likely contingencies. Generator frequency deviations were examined in order to determine if generator frequency protection could result in generator tripping. The results of the loss of the Hagood unit 2 and 3 CT s were examined in order to determine if any resulting underfrequency relay operations would lead to system load shedding. Also, the effects of each contingency were examined in order to determine if SCE&G voltages were adversely affected, particularly with respect to the V. C. Summer Nuclear Station offsite power supplies. SCE&G system responses were examined in order to identify any resulting voltage instability, transient stability limits, system operating limits, or interconnection reliability operating limits. Generator response plots are not included but are available for review upon request. An initial 30 second steady state simulation for the selected connection configuration was performed in order to establish that steady state conditions existed prior to fault conditions. The simulation of each contingency repeated the steady state condition for 1 second prior to introducing permanent fault conditions so that the responses could be compared to the initial steady state condition. In order to determine the effects on all system generators, contingencies were simulated under system peak load conditions. Contingencies were selected in order to satisfy each of four categories as specified by NERC Reliability Standards TPL-001 through TPL-004. The results of the stability analysis are described in the following sections and are summarized following the detailed results Results of Peak Summer Load Stability Analysis. A.1. Steady state conditions (NERC Category A condition) 10

11 The interconnection of the Hagood unit 2 and 3 generators was shown to result in system steady state conditions. Generator rotor angles and frequencies showed no deviations throughout the 30 second simulation. System voltages showed no deviations throughout the simulation period. There was no indication of generator or system voltage instability. No system stability limits were encountered. Nor were any transient stability limits, system operating limits (SOL s), or interconnection reliability operating limits (IROL s) found. This condition is compliant with NERC Reliability Standard TPL A.2. Normal clearing of a three phase fault on the existing Hagood #1 generator 13.2kV terminals (NERC Category B-1 Contingency) Following a 1 second steady state period, a permanent fault was simulated at the Hagood #1 generator 13.2 kv terminals. This results in the opening of the generator step up transformer high side breaker 5 cycles after the appearance of the fault along with the dropping of the Hagood #1 generator. Rotor angle oscillations were moderate and well damped with no indication of angular instability. Likewise, system frequency responses were also moderate and well damped with no indication of system underfrequency load shedding or generator under/overfrequency operations. Local system voltages were initially depressed by the presence of the fault. However all voltages recovered once the fault was cleared and there was no indication of generator or system voltage instability. No system stability limits were encountered. Nor were any transient stability limits, system operating limits (SOL s), or interconnection reliability operating limits (IROL s) found. This contingency is compliant with NERC Reliability Standard TPL Steady state conditions were reestablished with no further system operations. A.3. Normal clearing of a three phase fault in the Hagood units 2 & 3 generator step up transformer 13.8kV winding (NERC Category B-3 Contingency) Following a 1 second steady state period, a permanent fault was simulated at the Hagood units 2 and 3 generator step up transformer 13.8 kv windings. This results in the opening of the generator step up transformer high side breaker 5 cycles after the appearance of the fault along with the dropping of the Hagood units 2 and 3 CT s. Rotor angle oscillations were moderate and well damped with no indication of angular instability. Likewise, system frequency responses were also moderate and well damped with no indication of system underfrequency load shedding or generator under/overfrequency operations. Local system voltages were initially depressed by the presence of the fault. However all voltages recovered once the fault was cleared and there was no indication of generator or 11

12 system voltage instability. No system stability limits were encountered. Nor were any transient stability limits, system operating limits (SOL s), or interconnection reliability operating limits (IROL s) found. This contingency is compliant with NERC Reliability Standard TPL Steady state conditions were reestablished with no further system operations. A.4. Normal clearing of a three phase fault on the Hagood-Bee St. 115kV transmission line (NERC Category B-2 contingency) Following a 1 second steady state period, a permanent fault was simulated at the Hagood end of the Hagood-Bee St. 115kV transmission line. This line was selected for a transmission line fault simulation because it is the more heavily loaded of the two Hagood 115kV transmission lines. This is a more severe disturbance than the two previous simulations in that the transmission line reclosed from the Bee St. end onto the fault after the initial fault clearing. The Hagood end of the transmission line did not reclose on the fault due to the time delay inherent in the hot line reclosing scheme. As in the previous cases, rotor angle oscillations were moderate and well damped with no indication of angular instability. Likewise, system frequency responses were also moderate and well damped with no indication of system underfrequency load shedding or generator under/overfrequency operations. However, the Hagood units 2 and 3 CT s did demonstrate a brief overfrequency excursion ranging from approximately 60.9Hz to 61.1 Hz for a period of seconds or 2 cycles. It is recommended that any generator overfrequency protection be calibrated to exclude this condition. The simulation continued with the assumption that the Hagood #2&3 CT s remained on line during this condition. Local system voltages were initially depressed by the presence of the fault. However all voltages recovered once the fault was cleared and there was no indication of generator or system voltage instability. No system stability limits were encountered. Nor were any transient stability limits, system operating limits (SOL s), or interconnection reliability operating limits (IROL s) found. This contingency is compliant with NERC Reliability Standard TPL Steady state conditions were reestablished with no further system operations. A.5. Normal clearing of a single phase to ground fault on the Hagood 115kV bus (NERC Categories C-1 contingency) For this simulation, a single phase to ground fault was applied to the Hagood 115kV bus with normal bus differential relay clearing after 8 cycles. A single phase to ground fault is less severe than a three phase fault but can require a longer fault clearing time of 8 cycles as opposed to 6 cycles. Clearing of the fault is accomplished by opening all of the breakers connected to the bus with the result of tripping the existing Hagood CT along with the new Hagood units 2 and 3 CT s plus the connected transmission lines. 12

13 Rotor angle oscillations were moderate and well damped with no indication of angular instability. Likewise, system frequency responses were also moderate and well damped with no indication of system underfrequency load shedding or generator under/overfrequency operations. Local system voltages were initially depressed by the presence of the fault. However all voltages recovered once the fault was cleared and there was no indication of generator or system voltage instability. No system stability limits were encountered. Nor were any transient stability limits, system operating limits (SOL s), or interconnection reliability operating limits (IROL s) found. This contingency is compliant with NERC Reliability Standard TPL Steady state conditions were reestablished with no further system operations. A.6. Delayed clearing of a three phase to due to breaker failure on the Hagood 115kV bus (NERC Categories D-4 and D-10 contingencies) In this simulation, a fault was applied to the Hagood 115kV bus with the failure of the bus differential lockout relay to operate. This resulted in a Zone 2 relay operation from the remote ends of the Hagood Bee St. and Hagood Faber Place 115kV transmission lines. In addition, the existing Hagood CT and the new Hagood 2 and 3 CT s were isolated from the SCE&G System by the initial operation of these breakers. The generator tripping would have been initiated as intended by turbine overspeed, generator overfrequency, or out of step protection. It is recommended that a review of the generator protection systems be reviewed with the results of this study to verify that adequate protection is in place for the Hagood units 2 and 3 as well as for the existing Hagood CT. Otherwise, a generator rotor out of step condition could result if these generators are not tripped quickly enough. The remaining SCE&G generator rotor angle oscillations were moderate and were adequately damped with no indication of angular instability. Local system voltages were initially depressed by the presence of the fault. All voltages recovered once the fault was cleared and there was no indication of generator or system voltage instability. However, due to the delayed clearing of the fault, local area voltages were depressed for an extended period of time. It is possible that station service loads at the A.M. Williams, Bushy Park, Faber Place CT, Westvaco, Canadys, Wateree, and Jasper generating stations could be adversely affected. This is due solely to the delayed clearing of the fault and does not result from the addition of the Hagood units2 and 3 generators. There was no indication of voltage instability. Likewise, system frequency responses were also moderate and adequately damped with no indication of system underfrequency load shedding or generator under/overfrequency operations. 13

14 No system stability limits were encountered. Nor were any transient stability limits, system operating limits (SOL s), or interconnection reliability operating limits (IROL s) found. This contingency is compliant with NERC Reliability Standard TPL Steady state conditions were reestablished with no further system operations Hagood units 2 and 3 CT Stability Study Results Peak System Load Cases Summary A.1. Steady state conditions 1. Generator rotor angles demonstrate steady state condition. 2. Generator frequencies show no deviation. 3. There was no negative impact on V.C. Summer offsite power. 4. There were no resulting voltage instability, transient stability limits, SOL s, or IROL s. 5. NERC Reliability Standard TPL-001 compliance demonstrated. A.2. Normal clearing of a three phase fault on the existing Hagood #1 generator 13.2kV terminals (NERC Category B-1 contingency) 1. There was no indication of transient instability. 2. There was no indication of voltage instability. 3. There was no negative impact on V.C. Summer offsite power. 4. There was no indication of system UFLS or generator OFLS operation. 5. There were no resulting voltage instability, transient stability limits, SOL s, or IROL s. 6. NERC Reliability Standard TPL-002 compliance demonstrated. A.3. Normal clearing of a three phase fault in the Hagood 2 and 3 generator step up transformer 13.8kV winding (NERC Category B-3 contingency) 1. There was no indication of transient instability. 2. There was no indication of voltage instability. 3. No negative impact on V.C. Summer offsite power. 4. There was no indication of system UFLS or generator OFLS operation. 5. No resulting voltage instability, transient stability limits, SOL s, or IROL s. 6. NERC Reliability Standard TPL-002 compliance demonstrated. A.4. Normal clearing of a three phase fault on the most heavily loaded Hagood transmission line (NERC Category B-2 contingency) 1. There was no indication of transient instability. 2. There was no indication of voltage instability. 3. There was no negative impact on V.C. Summer offsite power. 14

15 4. There was no indication of system UFLS or generator OFLS operation. 5. The Hagood units 2 and 3 overfrequency protection settings should be reviewed. 6. There were no resulting voltage instability, transient stability limits, SOL s, or IROL s. 7. NERC Reliability Standard TPL-002 compliance demonstrated. A.5. Normal clearing of a single phase to ground fault on the Hagood 115kV bus (NERC Categories C-1 contingency) 1. There was no indication of transient instability. 2. There was no indication of voltage instability. 3. There was no negative impact on V.C. Summer Offsite power. 4. There was no indication of system UFLS or generator OFLS operation. 5. There were no resulting voltage instability, transient stability limits, SOL s or IROL s. 6. NERC Reliability Standard TPL-003 compliance demonstrated. A.6 Delayed clearing due to breaker failure of a three phase fault on the Hagood 115kV bus. (NERC Category D-4 and D-10 contingencies) 1. There was no indication of transient instability. 2. There was no indication of voltage instability. 3. There was no negative impact on V.C. Summer offsite power. 4. All Hagood CT s will intentionally trip on turbine overspeed, generator overfrequency, or out of step protection. It is recommended that the generator protection be reviewed for adequacy. 5. There was no indication of system UFLS or other generator OFLS operation. 6. Local generators may encounter station service low voltages due to the delayed clearing of the fault, not due to the addition of the Hagood units 2 and 3 generators. 7. There was no resulting voltage instability, transient stability limits, SOL s, or IROL s. 8. NERC Reliability Standard TPL-004 compliance demonstrated. 7. Cost Estimates and Completion Dates Power Delivery Engineering has provided the following cost estimates for the projects required for the interconnection of the proposed Hagood units 2 and 3 in 2008 dollars: Table 7.1. Cost Estimates for Interconnection Facilities One 115 kv Terminal with Gas Breaker $350, kv Bus Work (100 ft Extension) $200,000 Grounding and Other $200,000 Total $750,000 15

16 8. Recommendations and Conclusions Significant Network improvements are planned in the Charleston area that affect the power flow with the addition of Hagood units 2 and 3. These improvements are: 1. Rebuild the115kv Line from Charleston Transmission to Charlotte Street Sub as a double circuit and a fold in one of these circuits at Hagood 2. Construct a dedicated 115kV Circuit from Church Creek Transmission to the Savage Road Substation. These Improvements are scheduled for completion before the Summer of With these improvements, no overloaded or highly loaded facilities are indicated by the N-0, N-1 and N-2 steady-state analyses due to the addition of the proposed Hagood units 2 and 3. Before these projects are completed, however, the Hagood units 2 and 3 may have to reduce output following certain events to unload heavily loaded lines or to mitigate severe effects of a possible second contingency. These events include: 1. Loss of any section of the Charleston Transmission Charlotte Street 115kV Line 2. Loss of any section of the Church Creek St Andrews Rd. 115kV Line 3. Loss of either one of the two Faber Place Charleston Transmission 115kV Lines 4. Loss of any section of the Hagood Bee St 115kV Line It is recommended that the generator protection be reviewed for adequacy. Contingency events were identified that will require turbine overspeed, generator overfrequency, and/or generator out of step protection to be calibrated to trip the generators in the event of delayed clearing of local faults. In addition nearby generators may encounter station service low voltages due to the delayed clearing of fault. However, this condition is not due to the addition of the Hagood units 2 and 3 generators. No other stability or regulatory compliance related issues were identified in the study. 9. Addendum During the latter stages of this study, the in-service date of the Hagood units 2 and 3 was postponed until later in 2008 or early This postponement does not affect the results of this study. 16

17 Appendix Generator Datasheet 17

Generator Interconnection System Impact Study For

Generator Interconnection System Impact Study For Generator Interconnection System Impact Study For Prepared for: January 15, 2015 Prepared by: SCE&G Transmission Planning Table of Contents General Discussion... Page 3 I. Generator Interconnection Specifications...

More information

South Carolina Electric and Gas Company Planned Transmission Projects $2M and above Total 5 Year Budget

South Carolina Electric and Gas Company Planned Transmission Projects $2M and above Total 5 Year Budget Project 1 of 34 Aiken Trans - Aiken Hampton 115 kv Line: Upgrade 1272A Upgrade the 115 kv line between Aiken and Aiken Hampton substations from 336 ACSR to 1272 ACSR. Total line length approximately 3.7

More information

THE NECESSITY OF THE 500 KV SYSTEM IN NWE S TRANSMISSION SYSTEM TO MAINTAIN RELIABLE SERVICE TO MONTANA CUSTOMERS

THE NECESSITY OF THE 500 KV SYSTEM IN NWE S TRANSMISSION SYSTEM TO MAINTAIN RELIABLE SERVICE TO MONTANA CUSTOMERS THE NECESSITY OF THE 500 KV SYSTEM IN NWE S TRANSMISSION SYSTEM TO MAINTAIN RELIABLE SERVICE TO MONTANA CUSTOMERS 2/27/2018 ELECTRIC TRANSMISSION PLANNING Table of Contents Table of Contents... 2 Executive

More information

100 MW Wind Generation Project

100 MW Wind Generation Project A subsidiary of Pinnacle West Capital Corporation 100 MW Wind Generation Project CUSTOMER FINAL Feasibility Study Results By Transmission Planning, APS December 21, 2007 Executive Summary This Feasibility

More information

South Carolina Electric and Gas Company Planned Transmission Projects $2M and above Total 5 Year Budget

South Carolina Electric and Gas Company Planned Transmission Projects $2M and above Total 5 Year Budget Project 1 of 28 Blythewood 115 kv Switching Station: Construct 03087A Construct Blythewood Switching Station with four 115 kv line terminals, with plans to expand to 230 kv at a future date. Fold in the

More information

System Impact Study Report

System Impact Study Report Report For: NTE Carolinas II, LLC ( Customer ) Queue #: 42432-01 Service Location: Rockingham County, NC Total Output: 477 MW (summer) / 540 MW (winter) Commercial Operation Date: 12/1/2020 42432-01 SIS

More information

PJM Generator Interconnection Request Queue #R60 Robison Park-Convoy 345kV Impact Study September 2008

PJM Generator Interconnection Request Queue #R60 Robison Park-Convoy 345kV Impact Study September 2008 PJM enerator Interconnection Request Queue #R60 Robison Park-Convoy 345kV Impact Study 504744 September 2008 PJM Interconnection 2008. All rights reserved R60 Robison Park-Convoy 345kV Impact Study eneral

More information

Guide. Services Document No: GD-1401 v1.0. Issue Date: Title: WIND ISLANDING. Previous Date: N/A. Author: Heather Andrew.

Guide. Services Document No: GD-1401 v1.0. Issue Date: Title: WIND ISLANDING. Previous Date: N/A. Author: Heather Andrew. Guide Department: Interconnection Services Document No: GD-1401 v1.0 Title: WIND ISLANDING Issue Date: 11-24-2014 Previous Date: N/A Contents 1 PURPOSE... 2 2 SCOPE AND APPLICABILITY... 2 3 ROLES AND RESPONSIBILITIES...

More information

Generation Interconnection Facilities Study For

Generation Interconnection Facilities Study For Generation Interconnection Facilities Study For Prepared for: Prepared by: SCE&G Transmission Planning May 27, 2015 TABLE OF CONTENTS General Discussion... Page 3 Generator Interconnection Specifications...

More information

DUKE ENERGY PROGRESS TRANSMISSION SYSTEM PLANNING SUMMARY

DUKE ENERGY PROGRESS TRANSMISSION SYSTEM PLANNING SUMMARY DUKE ENERGY PROGRESS TRANSMISSION SYSTEM PLANNING SUMMARY Transmission Department Transmission Planning Duke Energy Progress TABLE OF CONTENTS I. SCOPE 3 II. TRANSMISSION PLANNING OBJECTIVES 3 III. TRANSMISSION

More information

CUSTOMER/ TWIN ARROWS PROJECT

CUSTOMER/ TWIN ARROWS PROJECT A subsidiary of Pinnacle West Capital Corporation CUSTOMER/ TWIN ARROWS PROJECT V1 Facility Study Report APS Contract 52149 Prepared by: Arizona Public Service Company Transmission & Distribution Asset

More information

CONNECTION ASSESSMENT & APPROVAL PROCESS. Cardinal Substation Modification of 115kV Substation

CONNECTION ASSESSMENT & APPROVAL PROCESS. Cardinal Substation Modification of 115kV Substation CONNECTION ASSESSMENT & APPROVAL PROCESS ASSESSMENT SUMMARY Applicant: Project: Cardinal Substation Modification of 115kV Substation CAA ID: 2002 EX071 Long Term Forecasts & Assessments Department\ Consistent

More information

Project #148. Generation Interconnection System Impact Study Report

Project #148. Generation Interconnection System Impact Study Report Project #148 Generation Interconnection System Impact Study Report June 05, 2012 Electric Transmission Planning Table of Contents Table of Contents... 2 Executive Summary... 3 Energy Resource Interconnection

More information

Interconnection System Impact Study Report Request # GI

Interconnection System Impact Study Report Request # GI Executive Summary Interconnection System Impact Study Report Request # GI-2008-23 34 MW Solar Generation Ranch at Hartsel, Colorado Public Service Company of Colorado Transmission Planning August 19, 2010

More information

Final Draft Report. Assessment Summary. Hydro One Networks Inc. Longlac TS: Refurbish 115/44 kv, 25/33/ General Description

Final Draft Report. Assessment Summary. Hydro One Networks Inc. Longlac TS: Refurbish 115/44 kv, 25/33/ General Description Final Draft Report Assessment Summary Hydro One Networks Inc. : Refurbish 115/44 kv, 25/33/42 MVA DESN Station CAA ID Number: 2007-EX360 1.0 General Description Hydro One is proposing to replace the existing

More information

MILLIGAN SOLAR PROJECT

MILLIGAN SOLAR PROJECT February 16, 2009 Page 1 of 18 A subsidiary of Pinnacle West Capital Corporation MILLIGAN SOLAR PROJECT FINAL Feasibility Study Report APS Contract 52115 Prepared by: Arizona Public Service Company Transmission

More information

Interconnection Feasibility Study Report GIP-226-FEAS-R3

Interconnection Feasibility Study Report GIP-226-FEAS-R3 Interconnection Feasibility Study Report GIP-226-FEAS-R3 System Interconnection Request #226 70 MW Wind Generating Facility Kings County (L-6013) 2010 07 21 Control Centre Operations Nova Scotia Power

More information

PJM Generator Interconnection R81 Emilie (Fords Mill) MW Impact Study Re-Study

PJM Generator Interconnection R81 Emilie (Fords Mill) MW Impact Study Re-Study PJM Generator Interconnection R81 Emilie (Fords Mill) 100.9 MW Impact Study Re-Study August 2008 DMS # 498781 General Queue R81 Emilie (Fords Mills) is a Fairless Energy, LLC request to obtain an additional

More information

CHAPTER 3 TRANSIENT STABILITY ENHANCEMENT IN A REAL TIME SYSTEM USING STATCOM

CHAPTER 3 TRANSIENT STABILITY ENHANCEMENT IN A REAL TIME SYSTEM USING STATCOM 61 CHAPTER 3 TRANSIENT STABILITY ENHANCEMENT IN A REAL TIME SYSTEM USING STATCOM 3.1 INTRODUCTION The modeling of the real time system with STATCOM using MiPower simulation software is presented in this

More information

South Carolina Electric and Gas Company Planned Transmission Projects $2M and above Total 5 Year Budget

South Carolina Electric and Gas Company Planned Transmission Projects $2M and above Total 5 Year Budget Project 1 of 24 Queensboro 115 kv Switching Station: Construct 0062A,B,C,D Build 4-terminal 115 kv switching station at Queensboro substation. Terminate the existing Queensboro St. Andrews, Church Creek

More information

PID 274 Feasibility Study Report 13.7 MW Distribution Inter-Connection Buras Substation

PID 274 Feasibility Study Report 13.7 MW Distribution Inter-Connection Buras Substation PID 274 Feasibility Study Report 13.7 MW Distribution Inter-Connection Buras Substation Prepared by: Entergy Services, Inc. T & D Planning L-ENT-17A 639 Loyola Avenue New Orleans, LA 70113 Rev Issue Date

More information

Hawai'i Island Planning and Operations MEASURES TO IMPROVE RELIABILITY WITH HIGH DER

Hawai'i Island Planning and Operations MEASURES TO IMPROVE RELIABILITY WITH HIGH DER 1 Hawai'i Island Planning and Operations MEASURES TO IMPROVE RELIABILITY WITH HIGH DER Lisa Dangelmaier Hawaii Electric Light lisa.dangelmaier@hawaiielectriclight.com Hawai'i Electric Light System Overview

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Interconnected Electric System Protection Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Interconnected Electric System Protection Requirements Applicability 1 Section 502.3 applies to: the legal owner of a generating unit directly connected to the transmission system with a maximum authorized real power rating greater than 18 MW; the legal owner

More information

Project #94. Generation Interconnection System Impact Study Report Revision

Project #94. Generation Interconnection System Impact Study Report Revision Project #94 Generation Interconnection System Impact Study Report Revision October 2, 2009 Electric Transmission Planning Table of Contents Table of Contents...2 Executive Summary...3 Energy Resource Interconnection

More information

Q95 Vicksburg 69kV. System Impact Study. APS Contract No Arizona Public Service Company Transmission Planning.

Q95 Vicksburg 69kV. System Impact Study. APS Contract No Arizona Public Service Company Transmission Planning. A subsidiary of Pinnacle West Capital Corporation Q95 Vicksburg 69kV System Impact Study APS Contract No. 52246 By Arizona Public Service Company Transmission Planning December 1, 2010 Version 2.6 Final

More information

EL PASO ELECTRIC COMPANY (EPE) FACILITIES STUDY FOR PROPOSED HVDC TERMINAL INTERCONNECTION AT NEW ARTESIA 345 KV BUS

EL PASO ELECTRIC COMPANY (EPE) FACILITIES STUDY FOR PROPOSED HVDC TERMINAL INTERCONNECTION AT NEW ARTESIA 345 KV BUS EL PASO ELECTRIC COMPANY (EPE) FACILITIES STUDY FOR PROPOSED HVDC TERMINAL INTERCONNECTION AT NEW ARTESIA 345 KV BUS El Paso Electric Company System Operations Department System Planning Section May 2004

More information

TRANSMISSION PLANNING CRITERIA

TRANSMISSION PLANNING CRITERIA CONSOLIDATED EDISON COMPANY OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003-3502 Effective Date: TRANSMISSION PLANNING CRITERIA PURPOSE This specification describes Con Edison s Criteria for assessing

More information

Falcon-Midway 115 kv Line Uprate Project Report

Falcon-Midway 115 kv Line Uprate Project Report Falcon-Midway 115 kv Line Uprate Project Report 12/1/2008 1 Background The function of this project is to uprate the 26.7 miles of Tri-State s 115 kv line between Midway and Falcon substations from 50

More information

VACAR STABILITY STUDY OF PROJECTED 2014/2015 WINTER PEAK LOAD CONDITIONS

VACAR STABILITY STUDY OF PROJECTED 2014/2015 WINTER PEAK LOAD CONDITIONS VACAR STABILITY STUDY OF PROJECTED 2014/2015 WINTER PEAK LOAD CONDITIONS April 2009 Prepared by VACAR Stability Working Group: Kirit Doshi Anthony Williams John O Connor Joe Hood Art Brown Dominion Virginia

More information

ABB POWER SYSTEMS CONSULTING

ABB POWER SYSTEMS CONSULTING ABB POWER SYSTEMS CONSULTING DOMINION VIRGINIA POWER Offshore Wind Interconnection Study 2011-E7406-1 R1 Summary Report Prepared for: DOMINION VIRGINIA POWER Report No.: 2011-E7406-1 R1 Date: 29 February

More information

Georgia Transmission Corporation Georgia Systems Operations Corporation

Georgia Transmission Corporation Georgia Systems Operations Corporation Georgia Transmission Corporation Georgia Systems Operations Corporation Reactive Power Requirements for Generating Facilities Interconnecting to the Georgia Integrated Transmission System with Georgia

More information

S o u t h w e s t P o w e r P o o l D i s t u r b a n c e P e r f o r m a n c e R e q u i r e m e n t s. Revision 3.0

S o u t h w e s t P o w e r P o o l D i s t u r b a n c e P e r f o r m a n c e R e q u i r e m e n t s. Revision 3.0 S o u t h w e s t P o w e r P o o l D i s t u r b a n c e P e r f o r m a n c e R e q u i r e m e n t s Revision 3.0 July 21, 2016 Revision History Version Number Author Change Description Comments 1.0

More information

Interconnection Feasibility Study

Interconnection Feasibility Study Interconnection Feasibility Study Mount Mabel Wind Energy Project Report No: T&S Planning 2015-054 December 2015 British Columbia Hydro and Power Authority British Columbia Hydro and Power Authority 2015.

More information

REDUCING VULNERABILITY OF AN ELECTRICITY INTENSIVE PROCESS THROUGH AN ASYNCHRONOUS INTERCONNECTION

REDUCING VULNERABILITY OF AN ELECTRICITY INTENSIVE PROCESS THROUGH AN ASYNCHRONOUS INTERCONNECTION REDUCING VULNERABILITY OF AN ELECTRICITY INTENSIVE PROCESS THROUGH AN ASYNCHRONOUS INTERCONNECTION Summary Abhay Kumar Mata Prasad R C Maheshwari Asea Brown Boveri Ltd. 4th Floor, 71 Nehru Place, New Delhi

More information

Midway/Monument Area TTC Study

Midway/Monument Area TTC Study Midway/Monument Area TTC Study (includes the following lines: Midway Geesen 115 kv, Geesen Falcon 115 kv, Falcon Fuller 115 kv, Fuller Black Squirrel 115 kv, and Black Squirrel Monument 115 kv) Johnny

More information

NEWFOUNDLAND AND LABRADOR HYDRO GULL ISLAND TO SOLDIERS POND HVDC INTERCONNECTION DC SYSTEM STUDIES VOLUME 1

NEWFOUNDLAND AND LABRADOR HYDRO GULL ISLAND TO SOLDIERS POND HVDC INTERCONNECTION DC SYSTEM STUDIES VOLUME 1 Page 1 of 76 NEWFOUNDLAND AND LABRADOR HYDRO GULL ISLAND TO SOLDIERS POND HVDC INTERCONNECTION DC SYSTEM STUDIES VOLUME 1 Page 2 of 76 NEWFOUNDLAND AND LABRADOR HYDRO GULL ISLAND TO SOLDIERS POND HVDC

More information

Transmission Competitive Solicitation Questions Log Question / Answer Matrix Harry Allen to Eldorado 2015

Transmission Competitive Solicitation Questions Log Question / Answer Matrix Harry Allen to Eldorado 2015 No. Comment Submitted ISO Response Date Q&A Posted 1 Will the ISO consider proposals that are not within the impedance range specified? Yes. However, the benefits estimated and studies performed by the

More information

PJM Sub Regional RTEP Committee Mid-Atlantic January 22, Esam Khadr, Sr. Director Electric Delivery Planning, PSE&G

PJM Sub Regional RTEP Committee Mid-Atlantic January 22, Esam Khadr, Sr. Director Electric Delivery Planning, PSE&G PJM Sub Regional RTEP Committee Mid-Atlantic January 22, 2016 Esam Khadr, Sr. Director Electric Delivery Planning, PSE&G PSE&G System Characteristics New Jersey utility characterized by densely populated

More information

Interconnection System Impact Study Final Report February 19, 2018

Interconnection System Impact Study Final Report February 19, 2018 Interconnection System Impact Study Final Report February 19, 2018 Generator Interconnection Request No. TI-17-0225 248.4 MW (Alternate Project Output of 217.35 MW) Wind Energy Generating Facility In Goshen

More information

AMERICAN ELECTRIC POWER 2017 FILING FERC FORM 715 ANNUAL TRANSMISSION PLANNING AND EVALUATION REPORT PART 4 TRANSMISSION PLANNING RELIABILITY CRITERIA

AMERICAN ELECTRIC POWER 2017 FILING FERC FORM 715 ANNUAL TRANSMISSION PLANNING AND EVALUATION REPORT PART 4 TRANSMISSION PLANNING RELIABILITY CRITERIA AMERICAN ELECTRIC POWER 2017 FILING FERC FORM 715 ANNUAL TRANSMISSION PLANNING AND EVALUATION REPORT PART 4 TRANSMISSION PLANNING RELIABILITY CRITERIA AEP Texas (comprised of its Central and North Divisions

More information

The Energy Queensland Group Notice of no non-network options

The Energy Queensland Group Notice of no non-network options The Energy Queensland Group Notice of no non-network options 24 September 2018 MCE Mount Crosby East Establish new substation to replace Mount Crosby Substation (SSMTC) Page 1 of 1 DISCLAIMER While care

More information

SYSTEM IMPACT STUDY EC300W ERIS FINAL REPORT. El Paso Electric Company

SYSTEM IMPACT STUDY EC300W ERIS FINAL REPORT. El Paso Electric Company SYSTEM IMPACT STUDY EC300W ERIS FINAL REPORT Prepared for: El Paso Electric Company Prepared by: Engineers, LLC 1526 Cole Boulevard Building 3, Suite 150 Lakewood, CO 80401 (303) 395-4018 FOREWORD This

More information

Operational Planning Study Report. RTA to BCH transfer limit updates For Kitimat 4 Capacitor Banks

Operational Planning Study Report. RTA to BCH transfer limit updates For Kitimat 4 Capacitor Banks Operational Planning Study Report RTA to BCH transfer limit updates For Kitimat 4 Capacitor Banks Report No. T&S Planning 2013-062 British Columbia Hydro and Power Authority British Columbia Hydro and

More information

Interconnection Feasibility Study Report GIP-222-FEAS-R3

Interconnection Feasibility Study Report GIP-222-FEAS-R3 Interconnection Feasibility Study Report GIP-222-FEAS-R3 System Interconnection Request #222 48 MW Steam Generating Facility Pictou County (53N) 2010 07 30 Control Centre Operations Nova Scotia Power Inc.

More information

Gateway South Transmission Project

Gateway South Transmission Project Phase 1 Comprehensive Progress Report Volume 1 - Technical Report Report Prepared by PacifiCorp Transmission Planning Department November 21, 2008 WECC1-V4 Phase 1 Comprehensive Progress Report Executive

More information

Q85 Generation Interconnection

Q85 Generation Interconnection A subsidiary of Pinnacle West Capital Corporation Q85 Generation Interconnection Interconnection Facilities Study AMENDED APS Contract No. 52386 By Arizona Public Service Company Transmission Planning

More information

TECHNICAL SPECIFICATION FOR INDEPENDENT POWER PRODUCERS. NB Power Customer Service and Distribution. June 2008

TECHNICAL SPECIFICATION FOR INDEPENDENT POWER PRODUCERS. NB Power Customer Service and Distribution. June 2008 NB Power Customer Service and Distribution June 2008 Prepared by: Steven Wilcox Revised by: Steven Wilcox TABLE OF CONTENTS 1.0 Introduction 4 2.0 NB Power Policy on Independent Power Production 4 3.0

More information

XXXX. Knob Hill Wind Farm Project. Interconnection System Impact Study

XXXX. Knob Hill Wind Farm Project. Interconnection System Impact Study XXXX Knob Hill Wind Farm Project Report No. August 2010 British Columbia Hydro and Power Authority British Columbia Hydro and Power Authority 2010. All rights reserved.. DISCLAIMER OF WARRANTY, LIMITATION

More information

Dunvegan Hydroelectric Project. For Glacier Power Limited. Preliminary Interconnection Study

Dunvegan Hydroelectric Project. For Glacier Power Limited. Preliminary Interconnection Study ` Dunvegan Hydroelectric Project For Glacier Power Limited Preliminary Interconnection Study Prepared by Pung Toy, P. Eng. and Ata Rehman, P. Eng. September 24, 2004 Table of Contents Table of Contents...

More information

Elbert County 500 MW Generation Addition Interconnection Feasibility Study Report OASIS POSTING # GI

Elbert County 500 MW Generation Addition Interconnection Feasibility Study Report OASIS POSTING # GI Executive Summary Elbert County 500 MW Generation Addition Interconnection Feasibility Study Report OASIS POSTING # GI-2003-2 Xcel Energy Transmission Planning January 2004 This Interconnection Feasibility

More information

XXXX. Kokish River Hydroelectric Project. Interconnection System Impact Study

XXXX. Kokish River Hydroelectric Project. Interconnection System Impact Study XXXX Kokish River Hydroelectric Project Report No. August 2010 British Columbia Hydro and Power Authority British Columbia Hydro and Power Authority 2010. All rights reserved.. DISCLAIMER OF WARRANTY,

More information

EL PASO ELECTRIC COMPANY (EPE) GENERATOR INTERCONNECTION SYSTEM IMPACT STUDY FOR PROPOSED XXXXXXXXXXXXXXXXXX GENERATION ON THE AMRAD-ARTESIA 345 KV

EL PASO ELECTRIC COMPANY (EPE) GENERATOR INTERCONNECTION SYSTEM IMPACT STUDY FOR PROPOSED XXXXXXXXXXXXXXXXXX GENERATION ON THE AMRAD-ARTESIA 345 KV EL PASO ELECTRIC COMPANY (EPE) GENERATOR INTERCONNECTION SYSTEM IMPACT STUDY FOR PROPOSED XXXXXXXXXXXXXXXXXX GENERATION ON THE AMRAD-ARTESIA 345 KV LINE El Paso Electric Company System Planning Department

More information

An Introduction to Completing a NERC PRC Study

An Introduction to Completing a NERC PRC Study An Introduction to Completing a NERC PRC-019-2 Study For Synchronous and Distributed Generation Sources PRESENTED BY: MATTHEW MANLEY TEXAS A&M PROTECTIVE RELAYING CONFERENCE MARCH 26-29, 2018 Presentation

More information

Supplemental Report on the NCTPC Collaborative Transmission Plan

Supplemental Report on the NCTPC Collaborative Transmission Plan Supplemental Report on the NCTPC 2007-2017 Collaborative Transmission Plan May 16, 2008 1 Table of Contents I. Executive Summary...1 II. Richmond-Fort Bragg Woodruff Street 230 kv Line...2 II.A. Need for

More information

Interconnection Feasibility Study Report GIP-023-FEAS-R1. Generator Interconnection Request # MW Wind Generating Facility Inverness (L6549), NS

Interconnection Feasibility Study Report GIP-023-FEAS-R1. Generator Interconnection Request # MW Wind Generating Facility Inverness (L6549), NS Interconnection Feasibility Study Report GIP-023-FEAS-R1 Generator Interconnection Request # 23 100 MW Wind Generating Facility Inverness (L6549), NS February 16, 2006 Control Centre Operations Nova Scotia

More information

El PASO ELECTRIC COMPANY 2014 BULK ELECTRIC SYSTEM TRANSMISSION ASSESSMENT FOR YEARS

El PASO ELECTRIC COMPANY 2014 BULK ELECTRIC SYSTEM TRANSMISSION ASSESSMENT FOR YEARS El Paso Electric Company El PASO ELECTRIC COMPANY 2014 BULK ELECTRIC SYSTEM TRANSMISSION ASSESSMENT FOR YEARS 2015 2024 A Review on System Performance Following Extreme Bulk Electric System Events of the

More information

Feasibility Study. Shaw Environmental, Inc. 12MW Landfill Gas Generation Interconnection. J.E.D. Solid Waste Management Facility. Holopaw Substation

Feasibility Study. Shaw Environmental, Inc. 12MW Landfill Gas Generation Interconnection. J.E.D. Solid Waste Management Facility. Holopaw Substation Feasibility Study Shaw Environmental, Inc. 12MW Landfill Gas Generation Interconnection J.E.D. Solid Waste Management Facility Holopaw Substation September 2013 1 of 12 Table of Contents GENERAL... 3 SHORT

More information

Southwest Power Pool, Inc TPL Stability Study. MAINTAINED BY SOUTHWEST POWER POOL ENIGINEERING GROUP Modeling Group

Southwest Power Pool, Inc TPL Stability Study. MAINTAINED BY SOUTHWEST POWER POOL ENIGINEERING GROUP Modeling Group Southwest Power Pool, Inc. 2011 TPL Stability Study MAINTAINED BY SOUTHWEST POWER POOL ENIGINEERING GROUP Modeling Group PUBLISHED: 12/19/2011 Approved by TWG: 12/19/2011 2 2011 Stability Study Revisions

More information

Feasibility Study Report

Feasibility Study Report Generator Interconnection Request Feasibility Study Report For: Customer --- Service Location: Rutherford County Total Output: 79.2 MW Commercial Operation Date: 9/1/2014 In-Service Date (if given): 9/1/2014

More information

TOLTEC POWER PARTNERSHIP TOLTEC POWER PROJECT INTERCONNECTION STUDY SYSTEM IMPACT STUDY

TOLTEC POWER PARTNERSHIP TOLTEC POWER PROJECT INTERCONNECTION STUDY SYSTEM IMPACT STUDY TOLTEC POWER PARTNERSHIP TOLTEC POWER PROJECT INTERCONNECTION STUDY SYSTEM IMPACT STUDY January 7, 2002 Prepared by Jorge Chacon (Consultant) Tucson Electric Power Company Ed Beck ii EXECUTIVE SUMMARY

More information

CHAPER 5 POWER FLOW STUDY IN THE INTEGRATED GRID NETWORK

CHAPER 5 POWER FLOW STUDY IN THE INTEGRATED GRID NETWORK 91 CHAPER 5 POWER FLOW STUDY IN THE INTEGRATED GRID NETWORK CHAPTER CONTENTS: 5.1 INTRODUCTION 5.2 CONDUCTION OF VARIOUS POWER FLOW STUDIES ON THE MODEL 5.3 EXPERIMENTS CONDUCTED FOR VARIOUS POWER FLOW

More information

15 Nelson-Marlborough Regional Plan

15 Nelson-Marlborough Regional Plan 15 Nelson-Marlborough Regional Plan 15.1 Regional overview 15.2 Nelson-Marlborough transmission system 15.3 Nelson-Marlborough demand 15.4 Nelson-Marlborough generation 15.5 Nelson-Marlborough significant

More information

FIRSTENERGY S PROPOSED SOLUTION AND REQUEST FOR CONSTRUCTION DESIGNATION

FIRSTENERGY S PROPOSED SOLUTION AND REQUEST FOR CONSTRUCTION DESIGNATION PJM RTEP - Artificial Island Area FIRSTENERGY S PROPOSED SOLUTION AND REQUEST FOR CONSTRUCTION DESIGNATION Part 1 Report REDACTED VERSION FirstEnergy Corp. Energy Delivery, Transmission Planning and Protection

More information

New 115 kv Disconnect Switches at Bloomsburg MTS

New 115 kv Disconnect Switches at Bloomsburg MTS 115 kv Line tap from C9 to Bloomsburg MTS & New Bus Tie Switch CAA ID Number: 2007-EX353 Final Draft ASSESSMENT SUMMARY 1. GENERAL DESCRIPTION Norfolk TS and Bloomsburg MTS are supplied by a single 115

More information

AQUILA NETWORKS WESTPLAINS ENERGY COLORADO CATEGORY C CONTINGENCY STUDIES

AQUILA NETWORKS WESTPLAINS ENERGY COLORADO CATEGORY C CONTINGENCY STUDIES AQUILA NETWORKS WESTPLAINS ENERGY COLORADO CATEGORY C CONTINGENCY STUDIES 2008-2012 April 2008 Table of Contents 1.0 INTRODUCTION... 2 2.0 RESULTS... 2 2.1 CATEGORY C NO SOLVE CASES... 2 2.2 CATEGORY C

More information

ATTACHMENT Y STUDY REPORT

ATTACHMENT Y STUDY REPORT Attachment Y Study Edwards Unit 1: 90 MW Coal Retirement December 31, 2012 ATTACHMENT Y STUDY REPORT 7/5/2013 PUBLIC / EXECUTIVE SUMMARY MISO received an Attachment Y Notification of Potential Generation

More information

SYSTEM IMPACT RESTUDY H252W ERIS REPORT. El Paso Electric Company

SYSTEM IMPACT RESTUDY H252W ERIS REPORT. El Paso Electric Company SYSTEM IMPACT RESTUDY H252W ERIS REPORT Prepared for: El Paso Electric Company Prepared by: Engineers, LLC 1526 Cole Boulevard Building 3, Suite 150 Lakewood, CO 80401 (303) 395-4018 FOREWORD This report

More information

Western Area Power Administration Sierra Nevada Region

Western Area Power Administration Sierra Nevada Region Western Area Power Administration Sierra Nevada Region 2014 Annual Ten-Year Transmission Plan Assessment Report November 20, 2014 For information or questions regarding this Transmission Assessment Report,

More information

A Case Study on Aggregate Load Modeling in Transient Stability Studies

A Case Study on Aggregate Load Modeling in Transient Stability Studies A Case Study on Aggregate Load Modeling in Transient Stability Studies Presented by: Daniel Feltes Siemens PTI Coauthors: Carlos Grande-Moran, Bernardo Fernandes, James Feltes, Ming Wu and Robert Wells

More information

APPENDIX E: Project Need and Description

APPENDIX E: Project Need and Description APPENDIX E: Project Need and California ISO/MID E-1 Intentionally left blank California ISO/MID E-2 Lakeville 115 kv Bus Upgrade Installation of a sectionalizing breaker to be installed on 115 kv bus section

More information

Feasibility Study Report

Feasibility Study Report Report For: Orion Renewable Resources LLC ( Customer ) Queue #: Service Location: Rockingham County, NC Total Output Requested By Customer: 100 MW Commercial Operation Date Requested By Customer: 11/1/2019

More information

APPENDIX E: Project Need and Description

APPENDIX E: Project Need and Description APPENDIX E: Project Need and California ISO/MID E-1 Intentionally left blank California ISO/MID E-2 Tyler 60 kv Shunt Capacitor Installation of a 2x10 MVAR capacitor bank at Tyler 60 kv bus Objectives

More information

Feasibility Study Report

Feasibility Study Report Report For: Fresh Air Energy II, LLC ( Customer ) Queue #: Service Location: Chester County, SC Total Output Requested By Customer: 74.5 MW Commercial Operation Date Requested By Customer: 1/7/2019 Feasibility

More information

Guidelines for connection of generators:

Guidelines for connection of generators: Guidelines for connection of generators: Greater than 30 kva, and not greater than 10 MW, to the Western Power distribution network January, 2017. EDM 32419002 / DM 13529244 Page 1 of 14 Contents 1 INTRODUCTION...

More information

Jemena Electricity Networks (Vic) Ltd

Jemena Electricity Networks (Vic) Ltd Jemena Electricity Networks (Vic) Ltd Embedded Generation - Technical Access Standards Embedded Generation - 5 MW or Greater ELE SP 0003 Public 1 October 2014 TABLE OF CONTENTS TABLE OF CONTENTS Abbreviations...

More information

Generation Interconnection Feasibility Study For XXXXXXXXXXXXXXXXXXXXXX MW generator at new Western Refinary Substation

Generation Interconnection Feasibility Study For XXXXXXXXXXXXXXXXXXXXXX MW generator at new Western Refinary Substation Generation Interconnection Feasibility Study For XXXXXXXXXXXXXXXXXXXXXX 131-250 MW generator at new Western Refinary Substation System Planning Section April, 2005 TABLE OF CONTENT 1 EXECUTIVE SUMMARY

More information

Service Requested 150 MW, Firm. Table ES.1: Summary Details for TSR #

Service Requested 150 MW, Firm. Table ES.1: Summary Details for TSR # Executive Summary Firm point to point transmission service has been requested by Transmission Service Request (TSR) #75669514, under the SaskPower Open Access Transmission Tariff (OATT). The TSR consists

More information

Interconnection Feasibility Study Report GIP-369-FEAS-R1

Interconnection Feasibility Study Report GIP-369-FEAS-R1 Interconnection Feasibility Study Report GIP-369-FEAS-R1 System Interconnection Request #369 50 MW Wind Generating Facility Cumberland County (L-6513) 2012-02-09 Control Centre Operations Nova Scotia Power

More information

2012 LOCAL TRANSMISSION PLAN:

2012 LOCAL TRANSMISSION PLAN: Colorado PUC E-Filings System 2012 LOCAL TRANSMISSION PLAN: TRANSMISSION COORDINATION AND PLANNING COMMITTEE ANNUAL TRANSMISSION ASSESSMENT FOR BLACK HILLS/COLORADO ELECTRIC UTILITY COMPANY, L.P., D/B/A

More information

South Carolina Regional Transmission Planning. Stakeholder Meeting. Web Conference

South Carolina Regional Transmission Planning. Stakeholder Meeting. Web Conference South Carolina Regional Transmission Planning Stakeholder Meeting Web Conference June 1, 2017 2:00 4:00 PM 1 Purpose and Goals for Today s Meeting Review of Current Transmission Expansion Plans Update

More information

Q217 Generator Interconnection Project

Q217 Generator Interconnection Project Q217 Generator Interconnection System Impact Study APS Contract No. 52588 By Arizona Public Service Company Transmission Planning November 25, 2013 Version 2.0 Prepared by Utility System Efficiencies,

More information

Small Generator Interconnection Program Interconnection Technical Requirements

Small Generator Interconnection Program Interconnection Technical Requirements General Program Information What is the purpose of the PGE Small Generator Interconnection Program? How do I initiate a distribution interconnection request for my project? The purpose of our Small Generator

More information

Islanding of 24-bus IEEE Reliability Test System

Islanding of 24-bus IEEE Reliability Test System Islanding of 24-bus IEEE Reliability Test System Paul Trodden February 14, 211 List of Figures 1 24-bus IEEE RTS, with line (3,24) tripped and buses 3,24 and line (3,9) uncertain....................................

More information

Interconnection Feasibility Study Report Request # GI Draft Report 600 MW Wind Generating Facility Missile Site 230 kv Substation, Colorado

Interconnection Feasibility Study Report Request # GI Draft Report 600 MW Wind Generating Facility Missile Site 230 kv Substation, Colorado Executive Summary Interconnection Feasibility Study Report Request # GI-2016-6 Draft Report 600 MW Wind Generating Facility Missile Site 230 kv Substation, Colorado Public Service Company of Colorado Transmission

More information

TransWest Express Project

TransWest Express Project TransWest Express Project Phase One--Feasibility Study Final Study Report November 2006 A subsidiary of Pinnacle West Capital Corporation Executive Summary On October 21, 2005 Arizona Public Service Company

More information

Updated Transmission Expansion Plan for the Puget Sound Area to Support Winter South-to-North Transfers

Updated Transmission Expansion Plan for the Puget Sound Area to Support Winter South-to-North Transfers Updated Transmission Expansion Plan for the Puget Sound Area to Support Winter South-to-North Transfers Puget Sound Area Study Team Bonneville Power Administration, Puget Sound Energy, Seattle City Light,

More information

Interconnection System Impact Study

Interconnection System Impact Study Interconnection System Impact Study Pennask and Shinnish Creek Wind Project Report No: T&S Planning 2014 072 December 2014 DRAFT British Columbia Hydro and Power Authority British Columbia Hydro and Power

More information

Guideline for Parallel Grid Exit Point Connection 28/10/2010

Guideline for Parallel Grid Exit Point Connection 28/10/2010 Guideline for Parallel Grid Exit Point Connection 28/10/2010 Guideline for Parallel Grid Exit Point Connection Page 2 of 11 TABLE OF CONTENTS 1 PURPOSE... 3 1.1 Pupose of the document... 3 2 BACKGROUND

More information

North Oregon Coast Area Study. Adam Lint

North Oregon Coast Area Study. Adam Lint North Oregon Coast Area Study Adam Lint PAGE 2 North Oregon Coast System Overview - Clatsop Study Covers: Transmission Switching Stations (Clatsop District): Astoria Lewis and Clark 115 kv Distribution

More information

Shunt Capacitor Bank Protection in UHV Pilot Project. Qing Tian

Shunt Capacitor Bank Protection in UHV Pilot Project. Qing Tian Shunt Capacitor Bank Protection in UHV Pilot Project Qing Tian 2012-5 INTRODUCTION State Grid Corp. of China, the largest electric power provider in the country, has first build a 1000 kv transmission

More information

Appendix D Black Hills Project Summary

Appendix D Black Hills Project Summary Page 1 of 28 Appendix D Black Hills Project Summary Table of Contents Black Hills Project Summary... D-1 Boone-Nyberg 115 kv Project... D-3 Rattlesnake Butte 115 kv Substation Terminal... D-6 Fountain

More information

Fifteenth National Power Systems Conference (NPSC), IIT Bombay, December 2008

Fifteenth National Power Systems Conference (NPSC), IIT Bombay, December 2008 Performance Evaluation of Composite Islanding and Load Management System using Real Time Digital Simulator Sachin Srivastava, Meera K.S, R.S. Shivakumara Aradhya and Sunil Verma Abstract A Composite Islanding

More information

SPS Planning Criteria and Study Methodology

SPS Planning Criteria and Study Methodology SPS Planning Criteria and Study Methodology SPS subscribes to the Southwest Power Pool ("SPP") Reliability Criteria, which incorporates compliance with the appropriate North American Electric Reliability

More information

Q87 Generation Interconnection

Q87 Generation Interconnection A subsidiary of Pinnacle West Capital Corporation Version 1.0 Q87 Generation Interconnection Interconnection Facilities Study APS Contract No. 52365 By Arizona Public Service Company Transmission Planning

More information

Dynamic Reactive Power Control for Wind Power Plants

Dynamic Reactive Power Control for Wind Power Plants Dynamic Reactive Power Control for Wind Power Plants Ernst Camm, Charles Edwards, Ken Mattern, Stephen Williams S&C Electric Company, 6601 N. Ridge Blvd, Chicago IL 60626 USA ecamm@sandc.com, cedwards@sandc.om,

More information

REPORT. System Impact Assessment Report. Thierry Mine Development CONNECTION ASSESSMENT & APPROVAL PROCESS CAA ID

REPORT. System Impact Assessment Report. Thierry Mine Development CONNECTION ASSESSMENT & APPROVAL PROCESS CAA ID REPORT IESO_PRO_0499 System Impact Assessment Report Thierry Mine Development CONNECTION ASSESSMENT & APPROVAL PROCESS CAA ID 2008-309 Applicant: Richview Resources Inc Market Facilitation Department 2009

More information

PES Cook Islands KEMA Grid Study Final Report

PES Cook Islands KEMA Grid Study Final Report Integrating PV Solar and Wind generation with the TAU electric system Te Aponga Uira O Tumu-Te_Varovaro Contents 1. Executive summary... 2 2. Introduction... 5 2.1 Proposed wind turbine sites... 6 2.2

More information

Session 10 NERC Interconnection Requirements

Session 10 NERC Interconnection Requirements GE Energy Session 10 NERC Interconnection Requirements UVIG Short Course 2014 Portland, Oregon Jason MacDowell NERC Standards Recently Adopted NERC GVSDT* standards MOD (Model Validation): MOD-025: Verification

More information

Interconnection Feasibility Study Report GIP-157-FEAS-R2

Interconnection Feasibility Study Report GIP-157-FEAS-R2 Interconnection Feasibility Study Report GIP-157-FEAS-R2 System Interconnection Request #157 100.5 MW Wind Generating Facility Guysborough County (L-6515) 2009 09 14 Control Centre Operations Nova Scotia

More information

Distributed Energy Resources

Distributed Energy Resources Distributed Energy Resources WECC Data Subcommittee Rich Hydzik, Avista (ERSWG/DER Subgroup Lead) June 29, 2018 Why Are We Concerned About DER? Concern about changing generation fleet Large coal fired

More information