4 018 (See App B) m Revised wording and clarification of requirements when selecting conductors
|
|
- Ethan Bishop
- 6 years ago
- Views:
Transcription
1 2012 Canadian Electrical Code Changes (CSA Errata not included) M = minor / S = significant / D = deleted N.m (Newton.metre) m New unit of torque Definitions cablebus m newly recognized wiring method ground fault circuit interupter (GFCI) m Revised definition ground fault circuit interupter Class A (GFCI) m New definition ground fault detection m New definition ground fault protection m Revised definition Grounding conductor m New App B note m Revised description of GFCI protection required (Class A) 2 310(2) m Revised wording on requirements 2 304(1) S New wording to clarify when working on live equipment may be acceptable. App B notes describes tasks to clarify what is "infeasible" and references Z S NEW rule requiring a roof top receptacle to provide power during maintenance of roof top units 4 004(1)(2) S New revisions, ampacities increased across the board (T1 T4), T4), Instructions for determining ampacities of underground runs clarified, some AppB notes brought forward as subrules. Additional subrule revision defining when IEEE 835 calculations must be used S Changes to subrules (9)(10)(12)(13)(21) Ampacity of single conductor cables in free air or in contact. New Table 66, Ampacity of Bare conductors in free air (See App B) S New rule, Conductor Temperature Limitations. This new rule prescribes how wire ampacity and temperature rating is based upon markings found on the equipment Equipment marked with a temp rating will result in the conductor ampacity being based on the corresponding temp column in Tables 1, 2, 3, or 4. See new explanation App B (See App B) S Revised wording and clarification of requirements when selecting conductors S New Rule regarding Induced voltages and Currents in single conductor runs, rewrite and consolidation from other Rules ( ), APP B (See App B) m Revised wording and clarification of requirements when selecting conductors (See App B) m Revised wording and clarification of requirements when selecting conductors (See App B) m Revised requirments for reduced neutrals
2 4 034 (1), (2), ans (3) m Copper sheathed cable recognized as approved (1) (See App B) m Revised wording and clarification of requirements when selecting conductors 4 042(4) S NEW subrule added, recognizes type "DLO" cable. "See App B" 4 040(2) S NEW subrule about DLO cable "See App B" m New reference to Rule (1) (1) ( c) S Revised to allow for new subrule (3) (3) S New subrule, Exterior service box acceptable on pole or building S Editorial, Rules rewritten to provide clarity. Conductors used must be acceptable as referred to in rule Reference to Table 19 removed, effectively no change. Subrule (b)(ii)(b) allows a splice in service cable for underground services, "where a cable transition is made to meet the requirements of Rule m Editorial changes to clarify wording. "Copper sheathed cable" added as an acceptable wiring method (1) (2) m Copper sheathed cable added as an acceptable wiring method c S Revision to allow a splice in consumers service neutrals, reference to 4 005, same as change to (1)(a)(vi) S New subrule, electric vehicle charging loads are taken at 100% for SFD service calculations (3) m Revised wording adds Rule reference 8 202(3)(d) S New subrule, Demand factor for electric vehicle charging equipment for apartment service calculation taken at 100% Scope m Major rewrite of scope Object m Major rewrite of object (2) m Revised description of ground fault detection S New requirements for ungrounded systems S Clarification of methods acceptable for the bonding of electrical equipment to the grounded system conductor (2) (a) S Revised requirement for interconnecting ground rods m Revised description of lightning rod terminology S Editorial changes to clarify DC system grounding requirments. New subrules to harmonize PV and renewable energy system grounding requirements with AC system requirements (now sized as per ) S Important rewrite of existing rule, system ground now sized to #6 when electrode conforms with Rule
3 (2) S Revised wording, parallel bond wires now required (4) m Size of sand particles changed when bedding UG ducts m Revised description of lightning rod terminology S Revised wording, all insulation types included (1), (2), (3) S Editorial, subrule revision when using parallel conductors. Parallel conductors must use same material per phase but each phase may be different conductor material. One splice per conductor permitted of each single conductor in parallel sets when required to comply with temp/ampacity reasons (reference made to 4 006) (4) S NEW requirement for support of internal conductors within armoured cable when used in vertical runs. Options provided to meet support requirements for cables in vertical runs. See App B explanation (3) S Revised subrule wording for clarity. New subrule prohibits fishing NMD cables in steel stud or steel cladded walls! (4) S Switches & receptacles with integral enclosure (no box). 150mm 300mm of cable loop required for future replacement. Appendix B note references other related rules, (7), (7) S Revised wording for clarity, NMSC cable may be fished except where steel stud wall / framing systems used (6) S NEW subrule permitting armoured cable with overall jacket to be pulled in raceways subject to (2) (3) S NEW subrule specifying minimum bending radius when armoured cable installed in conduit and tubing (not all raceways) as allowed by12 602(6) (3) S New revised subsection title, copper sheathed cable recognized S NEW subrules providing specifications for pulling armoured cable into conduit and tubing (not all raceways) (4) (d) S Table 10 renumbered as T10A S New requirements when securing liquid tite conduit (2) S Each compartment of multi compartment wireways to be treated as a separate wireway (2) S Revised subrule wording, Requirement to follow load/span ratings for cable trays, trays to be marked with ratings (3) m Revision to word "trays" now "tray" S NEW rules for installation of cable bus wiring system
4 (3) S NEW subrule re bonding of metal connectors when used to terminate non metallic wiring systems (8) S NEW subrule, Outlet box not required for switch or receptacle with integral enclosure, NMD only (9) S NEW subrule, For pendant ceiling fans weighing less than 16 kg, the box supporting it shall be approved and marked for fan support. See App B (7) S New sunrule re: switches and receptacles approved with an integral enclosure (8)(9) S New subrules, outlet box shall be approved when used to support ceiling fans.fans and accessories over 16kg shall be supported independently of outlet box (3) m Revised, inclusion of " or cable tray" (7) m Revised wording and clarification of requirements when selecting conductors (4) S NEW subrule enclosures housing o/c devices, controllers, or external switches shall be approved when CT devices or energy metering devices are also installed S NEW subrule, rating of OC device shall not exceed 15A, 20A, 30A for #14, 12, 10 AWG copper and 15a for #12 aluminum conductors except as provided by other Code rules (1) m Revised wording for clarity (2) m Switches must be approved m Revised wording and clarification of requirements when selecting conductors (1) S Revised subrule, Class 2 conductors shall be selected to comply with 4 006, Class 2 conductors smaller than #14 can be listed equipment wires if installed in raceways (1) S New EX markings from IEC, Equipment Protection Levels (EPL's) (2) S EPL Type "Ga" acceptable S EPL Type "Ga" or "Gb" acceptable (3) S Revision of HL cable sealing (1) S EPL Type "Ga" or "Gb" or "Gc" acceptable (2) m Rewording for clarification (1) m Copper sheathed cable approved (3) m Automatic requirement for cable seal when length exceeds 10m is deleted (1) m Rewording for clarification S Editorial, clarification on acceptable wiring methods in Class2 Div2. Acceptable armoured cables expanded to include "copper sheathed cable" and aluminum sheathed cables. New installation requirements when using type CIC cable in Class II Div 2
5 18 302(1) S Editorial, clarification in Subrule (1) of acceptable wiring methods in Class III Div 1 locations. Use of Types "copper sheathed RC" aluminum sheathed RA recognized (a) m Clarification that ground fault "detection" required S Editorial, clarification of acceptable wiring methods, Class III, Div 2. Acceptable armoured cables expanded to include "copper sheathed cable" and aluminum sheathed cables. New installation requirements when using type CIC cable S Total revision, wording replaced by NEW Table m Rule deleted to m Renumbered back when deleted (1) S Subrule revision, Clarification of hazardous areas and de classification of showrooms provided 50mm curbs installed (2) S Editorial, clarification of lighting fixture types over hazardous areas non hazardous types OK if protected by guards or location when fixture 3.6m or higher (1) m Aluminum sheathed and copper sheathed cable approved (2) m Revised wording and clarification of requirements when selecting conductors (1) m Revised wording and clarification of requirements when selecting conductors (3) m Revised wording and clarification of requirements when selecting conductors (5) m Copper sheathed cable approved (1) and (3) m Revised wording and clarification of requirements when selecting conductors (1) m Revised wording and clarification of requirements when selecting conductors (2) m Copper sheathed cable added (3) m Copper sheathed cable approved (6) S NEW subrule, Branch circuits that supply receptacles which are deemed essential (life/safety) shall not supply any other receptacles not deemed essential (8) S NEW subrule, Clarification that non electrical equipment in patient care environment shall be bonded if it could become energized (6) m Revised wording for clarification (2) m Item (2) deleted eg: description of prime mover requirements S NEW Rules for "Cellulose Nitrate Film Storage" Note, Section 48 Movie has been deleted S NEW Rules for "Cellulose Nitrate Film Storage" Note, Section 48 Movie has been deleted S NEW Rules for "Cellulose Nitrate Film Storage" Note, Section 48 Movie has been deleted.
6 S NEW Rules for "Cellulose Nitrate Film Storage" Note, Section 48 Movie has been deleted S NEW Rules for "Cellulose Nitrate Film Storage" Note, Section 48 Movie has been deleted (1) m Copper sheathed cable approved m Revised wording and clarification of requirements when selecting conductors (12) S New subrule, All receptacles installed in a child care facility shall be tamper resistant (1) and (2) S Exterior receptacle cover plates shall be approved for "wet" locations , New Subsection S NEW rule requiring receptacles for maintenance of roof top electrical equipment (d) m Revision to new receptacle designations (e) S Clarification of receptacle requirements in laundry rooms and spaces (o) S Receptacle required when mandated by BC Building Code and local By=Laws (d) (iii), (iv) and (v) (See App B) S Revision to new receptacle designations AND RE: Island and Peninsula receptacles. Significant change by addition of the word "continuous". See App B (h) S Subrule reworded to clarify where Tamper Resistant receptacles are NOT required ( c) m Revision now requires garage door opener receptacle (b) m Clarification of branch circuit requirement in laundry room and spaces (g) S NEW subrule, dedicated branch circuit for vehicle charging receptacle in single dwelling see (o) (b) m Revision to new receptacle designations (g) S AFCI protection of receptacle in BR supplying sump pump not required (5) m Clarification that 40 A breaker OK to supply 50 A range recptacle to m New sub section heading, new requirements for "Bare element water heaters" m Rewording for clarification (4) S Subrule (4) wording revised, new methods listed for providing disconnecting means at fluorescents over 150 V to ground (2) m Revised wording and clarification of requirements when selecting conductors (1) m Revised wording and clarification of requirements when selecting conductors (c) m Revised wording and clarification of requirements when selecting conductors (1) and (2) m Revised wording and clarification of requirements when selecting conductors m Revised wording and clarification of requirements when selecting conductors (4) m Editorial, Rules rewritten to provide clarity. Conductors used must be acceptable as referred to in rule Reference to Table 19 removed, effectively no change.
7 32 102(1)(c) S Subrule revised, rigid PVC without concrete encasement or direct burial permitted for conductors of a FA system. Previously allowed only in combustible buildings (b) Editorial, subrule rewritten to provide clarity. Conductors used must be acceptable as referred to in rule and reference to Table 19 removed, effectively no change (1) S Editorial, clarification that the fire pump transfer switch shall be used solely for the fire pump (1) ( c) m Editorial, revised wording corrects referece error in 2009 Code (2) S HV Breakers and LB Switches now only require contacts visible in open position. Where this design is not possible the additional requirements are unchanged (3) S Subrule revision, Clarification of requirements for a remote station ground electrode (1) and (4) m Revised wording and clarification of requirements when selecting conductors (1), (2) and (3) m Copper sheathed cable approved, Revised wording and clarification on selection of conductors (5) m Rewording of auxillary power requirements Scope m Revision to scope, reference to CSA No.33 exemption to Code deleted (1) m Copper sheathed cable now approved (1) m Copper sheathed cable now approved (1) m Revised wording and clarification of requirements when selecting conductors Rule title revised m (2)(c) S Subrule revised, rigid PVC without concrete encasement or direct burial permitted for conductors of a emergency system (3) S Subrule revision, Allows ENT in combustible buildings for Life Safety systems (3) m Wording clarification S New subrule, Conductors supplying Life Safety equipment shall be protected against fire exposure. See App B Examples same protection that is required for high buildings (renumbering of rules from ) Section 48 Deleted m S New terms replaces "rated open circuit" S Important change on how to calculate the voltage rating of the voltaic output source in relation to the voltage rating of equipment conductors etc rating S NEW Rule on voltage drop from voltaic source to utilization with number choices as how to calculate S Clarification on the current rating for the voltaic circuit S NEW wording regarding overcurrent protecting
8 S NEW rule requiring arc fault protection for photo voltaic DC source and output circuits S NEW rule regarding disconnecting means S Major rewriting of rule concerning wiring methods referenced RVP RVPU conductors S Clean up and new subrule (2) requiring tools to open attachment plugs S NEW rule re methods of interconnection of modules shall NOT interupt bonding arrangements S Interconnection to utility referenced to section S New rule re Solar voltaic grounding references section S New rule re power conditioning units references to section (2) m Revised wording and clarification of requirements when selecting conductors (1) m Revised wording and clarification of requirements when selecting conductors m Revised wording and clarification of requirements when selecting conductors (1) m Revised wording and clarification of requirements when selecting conductors m New definitions for infrared radiant heaters (2) (3) S NEW Subrule (3) "Where service conductors or feeders are used to supply an electric thermal storage heating system, duct heater, or an electric furnace, the connected heating load shall be calculated at 100% demand factor." As per subrule (4), this applies to residential commercial is still at 75% (3) m Revise wording and clarification of requirements when selecting conductors m New subrules re thermostat location ( BC amendment wording) (3), (4), and (5) S Revised rule requiring disconnects for central heating units (now required) (9) m DELETED, (re nailing panels to ceiling joists) S NEW rules for infra radiant heaters with metal sheath Section 64 ALL NEW SECTION S NEW section 64 re renewable energy systems (4) S NEW Amusement Parks etc. Subrule (4) Deals with modern wiring methods of single conductor cables/connections (2) S Splash pads are considered pools (kid water parks) S Definitions for splash pads (7) m Spas and Hot tubs must be GFCI (4)(e) S Spas and hot tubs. Emergency shut off and alarm devices can be field wired (1) m Revise wording and clarification of requirements when selecting conductors (4) S GFCI protection for heat trace under mobile homes can be Class B (4) (1) m Reference to NEMA Standard WD6 deleted
9 (1) m Revise wording and clarification of requirements when selecting conductors (2) m Revise wording and clarification of requirements when selecting conductors (2) m Revise wording and clarification of requirements when selecting conductors (10 and (2) m Revise wording and clarification of requirements when selecting conductors (1) m Revise wording and clarification of requirements when selecting conductors (c) S Subrule (c) has been deleted. The branch cct for a cathodic protection rectifier no longer needs to be supplied from a source that is capable of being locked in the ON position S NEW Disconnecting Means Several new requirements regarding cathodic protection (1) m Revise wording and clarification of requirements when selecting conductors definitions m Revision to definition of Electric vehicle inlet S NEW rule re permanently and cord connected equipment to comply with section DELETED (1) S Change requiring a sigle receptacle 5 20R for vehicle charging S NEW rule if the vehicle is a power producing source (3) S NEW subrule re charging equipment near flammable liquids and reference to sec S NEW rule height of vehicle charging equipment Table 1 Table 2 S S Major changes to conductor ampacities. See & App B Explanation, (2) (heading changes) Major changes to conductor ampacities. See & App B Explanation, (2)(heading changes) Table 3 S Major changes to conductor ampacities. See & App B Explanation, (2) (heading changes) Table 4 S Major changes to conductor ampacities. See & App B Explanation, (2) (heading changes) Table 5A S Completely re written. New intermediate temperatures added Most correction factors changed thereby reducing the derating of conductors for a given temperature. This results in higher ampacities (heading changes) Table 5B S Heading changed. Instead of "in contact", "spaced less than 25% of the largest cable diameter" Also, references cable tray, Table 5D S Reference to 4 004(9) added. Table 6 S Additional conductor types added Table 10 S Renamed Table 10 A Table 10 B S NEW Table for PV equipment conductors
10 Table 11 m New conductor types added, Notes revised Table 12 S New ampacities for some conductors, new columns added Table 12 A S Title revised Table 12 E NEW S NEW Table 12 E for type DLO conductors Table 17 DELETED S Deleted table for grounding conductor sizes Table 19 m New conductor types added, Notes revised and New notes added, Types copper sheathed cable, aluminum sheathed cable and Type ACG90 and ACGWU90 added Table 44 S Additional motor sizes added, revised ampacities for some sizes Table 64 S Delete existing table, replace with new rewritten table, New notes added Table 66 NEW S NEW Table Ampacities of Bare or Covered Conductors in Free Air Diagram 1 m Type TT 30R added, other new receptacle designations added APPENDIX B NOTES S Example of when it might not be feasible to disconnect power before work. Reference to Z S New notes regarding cable ampacities underground, IEEE (1) (d) and (2) (d) S Better explanation for underground installations and ampacities S Explanation of effects of temperature rating of equipment on the conductor ampacity S Lengthy, good explanation regarding induced voltages and sheath currents, single conductor cables S Explanation of cold temperatures and handling conductors (4) S Explanation of self contained devices without a box S Explanation of pulling armoured cable into raceways (8) S Explanation of self contained devices without a box (7) S Explanation of self contained devices without a box (9) S Info regarding boxes marked "Acceptable for Fan Support" (2) S Explanation of filling up the interior of panel past certain percentage to allow for heat dissipation S Table for "T" and "L" designations for AC DC switches /090/100/150 S Introduction of equipment protection levels in hazardous locations (3) S Sealing requirements/options for intrinsically safe and non incendive wiring systems (12) S Explanation of tamper resistant receptacles in child care facilities S Explanation of "WET LOCATION" cover plates S Explanation of new requirements for receptacles near roof top equipment (h) S Explanation on location requirements for TR receptacles.
11 26 712(d)(iv)&(v) S RE: Island and Peninsula receptacles. "It is intended by the rule that a continuous counter surface is one which is not interrupted by sinks, ranges, and other build in equipment." (g) S Explanation of sump pump receptacle located in sleeping area need not be on AFCI S Explanation of marking regarding "Bare Element Water Heaters" S Explanation regarding protection from exposure to fire for conductors from an emergency generator (1) S Explanation of the 125% rating for this rule in regards to temperature (2) S Example of calculation for temperature variance for voltage rating of solar conductors (1) S Explanation of maximum short circuit current available when solar panels connected in parallel S Explanation of the use of flexible cable for solar panels and mechanical protection (5) S Explanation of FT1 rating for RPV and RPVU for use in buildings Section 64 S Section 64 " Renewable Energy Systems" comprehensive notes on the complete section (4) S Clarification of type of GFCI required for heat trace receptacles mounted under the trailer
Spring Test 10 due 05/11/2013
Spring Test 10 due 05/11/2013 Multiple Choice Identify the letter of the choice that best completes the statement or answers the question. 1. When installed in an agricultural building that houses livestock
More informationBulletin Wiring methods for Solar Photovoltaic Systems Rule and , Tables 11 and 19
-4-0 Bulletin -4-0 Wiring methods for Solar Photovoltaic Systems Rule -018 and -020, Tables 11 and 19 Scope Issued May 2012 (1) Introduction (2) New cable types RPV & RPVU (3) Wiring methods within photovoltaic
More information90.2 Scope. The installation of electrical conductors, equipment and raceways for:
NEC Generator Primer Rules on the installation of generators and transfer switches 1 90.2 Scope The installation of electrical conductors, equipment and raceways for: public and private premises Conductors
More informationCHAPTER V RESIDENTIAL WIRING
CHAPTER V RESIDENTIAL WIRING 5.1. THE SERVICE ENTRANCE Buildings and other structures receive the electrical energy through the service entrance. In residential wiring, the electric company supply this
More informationPretest Module 24 Three-phase Service Entrance
Pretest Module 24 Three-phase Service Entrance 1. What is the most widely used three-phase service entrance system? 2. What are the three most common voltage combinations for three-phase, four-wire systems?
More informationSUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS - ELECTRICAL
SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS - ELECTRICAL This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly.
More informationChapter 2 Wiring and Protection Article 200 Use and Identification of Grounded Neutral Conductor Chapter 1 General...9
Article 90 Introduction...1 90.1 Purpose of the NEC...1 90.2 Scope of the NEC...2 90.3 Code Arrangement...4 90.4 Enforcement...5 90.5 Mandatory Requirements and Explanatory Material...6 90.6 Formal Interpretations...6
More informationNEC 2011 Code Changes
NEC 2011 Code Changes Articles 280.21-300.50 CHANGES FROM 2008 TO 2011 CODE ARE IN RED Chapter 2 - Wiring and Protection ARTICLE 280 Surge Arresters, Over 1kV III. Connecting Surge Arresters 280.21 Connection
More information9/7/2010. Objectives. Article 90. Introduction NEC Significant Changes. Review significant revisions in the 2011 NEC
2011 NEC Significant Changes Courtesy of NJATC Courtesy of NFPA Presented By: Michael J. Johnston Executive Director of Standards and Safety, NECA Objectives Review significant revisions in the 2011 NEC
More information2016 Photovoltaic Solar System Plan Review List
Building Division 555 Santa Clara Street Vallejo CA 94590 707.648.4374 2016 Photovoltaic Solar System Plan Review List GENERAL PROJECT INFORMATION PLAN CHECK NO DATE JOB ADDRESS CITY ZIP REVIEWED BY PHONE
More informationDefinitions of and have been revised. a. automatic b. nonautomatic c. none of the above d. both a and b
www.garyklinka.com Page 1 of 12 Instructions: Fee $25 1. Print these pages. 2. Circle the correct answers and transfer them to the answer sheet. 3. Page down to the last page for the verification forms
More informationHave You Been Grounded Lately
Have You Been Grounded Lately Thurs, Oct. 26, 2017 9:15-10:15 Phil Simmons Author, Electrical Grounding and Bonding Author Cengage Learning Phil Simmons Have You Been Grounded Lately 2017 NEC Changes Relative
More informationFee $20 Course: NEC Changes 1 This course is valid for these credentials: Credential Description Cred Code Credit Hours
www.garyklinka.com Page 1 of 18 Instructions: Fee $20 1. Print these pages. 2. Circle the correct answers and transfer them to the answer sheet. 3. Page down to the last page for the verification forms
More informationBulletin Wiring methods for Solar Photovoltaic Systems Rules, 2-034, , and , Tables 11 and 19
Bulletin 50-4-4 Wiring methods for Solar Photovoltaic Systems Rules, 2-034, 50-014, 50-018 and 50-020, Tables 11 and 19 Scope (1) Introduction (2) New cable types RPV & RPVU (3) Wiring methods within photovoltaic
More informationBulletin Wiring methods for Solar Photovoltaic Systems Rules and , Tables 11 and 19
Bulletin 50-4-1 Wiring methods for Solar Photovoltaic Systems Rules 50-018 and 50-020, Tables 11 and 19 Issued December 2012 Supersedes Bulletin 50-4-0 (1) (2) (3) (4) (5) Scope Introduction New cable
More informationSolar PV Standard Electrical Plan
*** Provide this document to the inspector along with ALL system installation instructions *** Project Address: Permit Number: SCOPE: Standard plan for installation of solar PV systems utilizing 2 wire
More informationElectrical Tech Note 111 Biosystems & Agricultural Engineering Department Michigan State University
Electrical Tech Note 111 Biosystems & Agricultural Engineering Department Michigan State University Electrical Code Changes in Michigan 1 (Based on Part 8, P.A. 230, the 2005 NEC and the 2003 MRC) This
More informationBulletin Wiring methods for solar photovoltaic systems Rules 2-034, , , , , Tables 11 and 19
Bulletin 64-4-1 Wiring methods for solar photovoltaic systems Rules 2-034, 64-066, 64-210, 64-216, 64-220, Tables 11 and 19 Scope (1) Introduction (2) Cable types RPV & RPVU (3) Wiring methods within photovoltaic
More informationMECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 2/8/12 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions
MECKLENBURG COUNTY Land Use and Environmental Service Agency Code Enforcement 2/8/12 ELECTRICAL CONSISTENCY MEETING Code Consistency Questions 1. I am inspecting a building addition. They have a 480V to
More informationThis is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly.
SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS (ELEC) This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly.
More informationELECTRIC VEHICLE CHARGING FOR BUILDINGS
PLANNING & DEVELOPMENT SERVICES Office of the Chief Building Official BULLETIN 2015-004-BU/EL June 25, 2015 ELECTRIC VEHICLE CHARGING FOR BUILDINGS This bulletin provides clarification of requirements
More informationSpring Test 7 due 05/03/2013
Spring Test 7 due 05/03/2013 Multiple Choice Identify the choice that best completes the statement or answers the question. 1. A raceway contains two 3-phase, 3-wire circuits that supply 38 ampere continuous
More informationPhotovoltaic Solar Plan Review
PAIGE B. VAUGHAN, CBO Director of Building and Safety Phone (310) 605-5509 Fax Line (310) 605-5598 E-mail:lbutler@comptoncity.org Building & Safety Department Photovoltaic Solar Plan Review Plan Check
More informationElectric & Gas Service Requirements (Greenbook) Overview
INTRODUCTION The Greenbook contents and standard documents are updated regularly to provide users with the most current information possible. In conjunction with this effort, the 2016 Greenbook was reviewed
More informationMecklenburg County Common Code Defects
Electrical Code Defects Improper Over Current Protection Code Description 310.15 Ampacities for s Rated 0 2000 Volts. (A) General. (1) Tables or Engineering Supervision. Ampacities for conductors shall
More informationA Look at the 2017 NEC Significant Changes
A Look at the 2017 NEC Significant Changes A Look at the 2017 NEC Significant Changes Michael J. Johnston NECA James T. Dollard Local 98 Philadelphia Electrical JATC This session is eligible for 1 Continuing
More informationWestern Section 101 st Annual Meeting Hot Springs, Arkansas September 21, 2005 Charlie Trout Code Breakfast
Western Section 101 st Annual Meeting Hot Springs, Arkansas September 21, 2005 Charlie Trout Code Breakfast 1.Question: An add on unit for a hydromassage bathtub consists of a small 1-gallon water heater
More informationSolar PV Standard Electric Plan
*** Provide this document to the inspector along with ALL system installation instructions *** SCOPE: Standard plan for the installation of microinverter solar PV systems, not exceeding a total AC output
More informationWestern Section IAEI Code Panel Questions
Western Section IAEI 2013 Code Panel Questions 1. Do the factory wings that many fluorescent troffers have designed to fold out over the grid meet the requirements for securely fastened to the framing?
More informationArc Fault Circuit Interrupter (AFCI) FACT SHEET
Arc Fault Circuit Interrupter (AFCI) FACT SHEET THE AFCI The AFCI is an arc fault circuit interrupter. AFCIs are newly-developed electrical devices designed to protect against fires caused by arcing faults
More informationElectrical Equipment and Terminology
Youth Explore Trades Skills Description Understanding the language of the electrical trade and knowing what electrical equipment is named and its purpose are very important. Anyone who is exposed to a
More informationTEMPORARY ELECTRIC WIRING FOR CARNIVALS, CONVENTIONS, EXHIBITIONS, FAIRS AND SIMILAR USES
INFORMATION BULLETIN / PUBLIC - ELECTRICAL CODE REFERENCE NO.: LAMC 93.0230 Effective: 3-24-69 DOCUMENT NO. P/EC 2002-006 Revised: 11-17-00 Previously Issued As: RGA #7-69 TEMPORARY ELECTRIC WIRING FOR
More informationSECTION 1: Field Inspection Guide for Rooftop Photovoltaic (PV) Systems
COUNTY OF SANTA CRUZ PLANNING DEPARTMENT 701 OCEAN STREET, 4 th FLOOR, SANTA CRUZ, CA 95060 (831) 454-2580 FAX: (831) 454-2131 TDD: (831) 454-2123 KATHLEEN MOLLOY PREVISICH, PLANNING DIRECTOR Photovoltaic
More informationCHAPTER 10 ELECTRICAL. Notes:
CHAPTER 10 ELECTRICAL 1001.0 General Requirements. Electrical wiring and equipment shall comply with the requirements of NFPA 70, National Electrical Code (NEC), or local ordinances. 1002.0 Solar Photovoltaic
More informationPHOTOVOLTAIC ELECTRICAL POWER SYSTEMS INSPECTOR/INSTALLER CHECKLIST
PHOTOVOLTAIC ELECTRICAL POWER SYSTEMS INSPECTOR/INSTALLER CHECKLIST The following checklist is an outline of the general requirements found in the 2005 National Electrical Code (NEC) Article 690 for Photovoltaic
More information2011 NEC Code Updates Part 3
www.garyklinka.com Page 1 of 22 Instructions: Fee $35 1. Print these pages. 2. Circle the correct answers and transfer them to the answer sheet. 3. Page down to the last page for the verification forms
More informationMicroinverters and AC PV modules are becoming. Microinverters and AC PV Modules. Different Beasts. Perspectives on PV.
Perspectives on PV Microinverters and AC PV Modules Are Different Beasts by John Wiles Microinverters and AC PV modules are becoming very common in residential and small commercial PV systems. See photos
More informationSINGLE PHASE WIRING SPECIFICATIONS
SINGLE PHASE WIRING SPECIFICATIONS 1-866-MEC-ELEC (1-866-632-3532) Office Locations: Hondo Office 237 Hwy 173 N Hondo, TX 78661-0370 Fax 830.426.3335 Dilley Office 1718 W. FM 117 Dilley, TX 78017 Fax 830.965.1425
More informationTHREE PHASE WIRING SPECIFICATIONS
THREE PHASE WIRING SPECIFICATIONS 1-866-MEC-ELEC (1-866-632-3532) Office Locations: Hondo Office 237 Hwy 173 N Hondo, TX 78661-0370 Fax 830.426.3335 Dilley Office 1718 W. FM 117 Dilley, TX 78017 Fax 830.965.1425
More informationAGRICULTURAL UNDERGROUND SERVICE 500 HP OR LESS
Prepared by: ABB1 AGRICULTURAL UNDERGROUND SERVICE 500 HP OR LESS 05619 Asset Type: Electric Metering Function: Design and Construction Issued by: Lisseth Villareal (LDV2) Date: 07-31-15 Rev. #10: This
More information2010 National Electric Code
PDHonline Course E361 (4 PDH) 2010 National Electric Code Instructor: Thomas Mason, P.E. 2012 PDH Online PDH Center 5272 Meadow Estates Drive Fairfax, VA 22030-6658 Phone & Fax: 703-988-0088 www.pdhonline.org
More informationCode developments. Tim Pope Senior Project Manager, CE Code, Part I CSA Group Management Corp. All Rights Reserved.
Code developments Tim Pope Senior Project Manager, CE Code, Part I 2018 CSA Group Management Corp. All Rights Reserved. Agenda CSA Group Canadian Electrical Safety System What s new in the 2018 Code? Learn
More informationSOLAR PHOTOVOLTAIC SYSTEMS INSPECTOR CHECKLIST
SOLAR PHOTOVOLTAIC SYSTEMS INSPECTOR CHECKLIST The following checklist is an outline of the general requirements found in the 1999 National Electrical Code (NEC) Article 690 for Photovoltaic (PV) Power
More informationAMENDMENT ELECTRIC SERVICE MANUAL 2014
AMENDMENT (Pages 20,43,50,72,74,,76,78,83,86,99) ELECTRIC SERVICE MANUAL 2014 Effective April 1, 2015 18-7 6.0 SERVICE AND SERVICE ENTRANCES (General), Continued Conductor Sizing It is recommended that
More information(The actual state exam will be closer to 50 questions in 4 hours time) Master Electrician Practice Test
(The actual state exam will be closer to 50 questions in 4 hours time) Master Electrician Practice Test 1. Accessible as applied to wiring methods means capable of being removed or exposed without damaging
More informationMECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 9/14/11 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions
MECKLENBURG COUNTY Land Use and Environmental Service Agency Code Enforcement 9/14/11 ELECTRICAL CONSISTENCY MEETING Code Consistency Questions 1. I recently installed a 45-KVA transformer, 480-volt primary
More information2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE
2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE PAGE 1 OF 5 This Reference provides a very comprehensive list of aspects of a solar PV installation that could be reviewed, clarifying
More information9. Non-Residential Services (Commercial, Industrial, and Agricultural)
Section 9 2016 Electric Service Requirements, 3rd Edition Section 9 Non-Residential Services Directory Page 9.1 General Requirements 68 9.2 Direct-Connect Metering, Single Installations 69 9.3 Direct-Connect
More information2014 NEC Analysis Part 2
www.garyklinka.com Page 1 of 24 Instructions: Fee $65 1. Print these pages. 2. Circle the correct answers and transfer them to the answer sheet. 3. Page down to the last page for the verification forms
More informationENGINEERING SPECIFICATION
December 206 ENGINEERING SPECIFICATION No. of 6 DATE: 2-9-6 CATEGORY SUBJECT TABLE OF CONTENTS. Overview... 2 2. General Requirements for Service... 3 3. Definitions... 3 4. Abbreviations... 5 5. References
More informationContinued from Part 2 Rules
Continued from Part 2 Rules 26 50. 51 250.94 Grounding (Bonding) of Communications Systems An accessible bonding point must be provided at service equipment or the disconnecting means of separate buildings
More informationSOLAR PV STANDARD PLAN - COMPREHENSIVE Central/String Inverter Systems for One and Two Family Dwellings
SCOPE: Use this plan ONLY for utility-interactive central/string inverter systems not exceeding a total combined system ac inverter output rating of 10kW on the roof of a one- or two-family dwelling or
More informationCHAPTER 10 ELECTRICAL
1001.0 General Requirements. 1001.1 Electrical Wiring and Equipment. Electrical wiring and equipment shall comply with the requirements of NFPA 70, National Electrical Code (NEC), or local ordinances.
More informationThe 84 th NC Electrical Institute Code Questions April 9 th & 10 th 2013 North Raleigh Hilton Raleigh, NC
The 84 th NC Electrical Institute Code Questions April 9 th & 10 th 2013 North Raleigh Hilton Raleigh, NC www.ncdoi.com www.ncbeec.org NC DEPARTMENT OF INSURANCE NC STATE BOARD OF EXAMINERS OF ELECTRICAL
More informationGenerator Fire Safety: Generator assemblies should be located outside the building.
SECTION 33 70 00 - ELECTRICAL DISTRIBUTION PACKAGED GENERATOR ASSEMBLIES Generator Fire Safety: Generator assemblies should be located outside the building. All fuel piping from the outside of the building
More information2011 NEC Changes Part 2 (Homestudy) (Homestudy)
2011 NEC Changes Part 2 (Homestudy) (Homestudy) North Carolina Electrical License This course will review the second half of the most important National Electrical Code changes from the 2011 NEC. Changes
More informationSolar PV Standard Plan Simplified Central/String Inverter Systems for One- and Two-Family Dwellings
Your City logo here Solar PV Standard Plan Simplified Central/String Inverter Systems for One- and Two-Family Dwellings SCOPE: Use this plan ONLY for utility-interactive central/string inverter systems
More informationSolar PV Standard Plan Simplified Central/String Inverter Systems for One- and Two-Family Dwellings
PV TOOLKIT DOCUMENT #3 Solar PV Standard Plan Simplified Central/String Inverter Systems for One- and Two-Family Dwellings SCOPE: Use this plan ONLY for utility-interactive central/string inverter systems
More informationFOR ALL STAKEHOLDERS TO
Our Goal is FOR ALL STAKEHOLDERS TO HAVE A SUCCESSFUL PROJECT with us and that together we keep people and structures safe and buildings economically viable to serve the needs of our community. We strive
More informationNEC 2014 Code Changes
NEC 2014 Code Changes Articles 310 310.120 CHANGES FROM 2011 TO 2014 CODE ARE IN RED ARTICLE 310 Conductors for General Wiring I. General 310.2 Definitions Electrical Ducts Electrical conduits, or other
More informationInstalling a Downstream Distribution Panelboard
Job Sheet 5 Installing a Downstream Distribution Panelboard OBJECTIVE To install a downstream distribution panelboard (DDP) on the Mobile Workstation. To mechanically and electrically connect the DDP to
More informationICOMIA Global Conformity Guideline for ISO/ABYC Standards and Canadian TP 1332 requirements. Guideline Number 3 Electrical
ICOMIA Global Conformity Guideline for ISO/ABYC Standards and Canadian TP 1332 requirements 1. PURPOSE sponsored by ABYC, BMF, ICOMIA, IMCI, and NMMA Author: Wieger de Wit Guideline Number 3 Electrical
More informationCOMMERCIAL QUICK REFERENCE
COMMERCIAL QUICK REFERENCE PROVO CITY POWER STANDARDS ELECTRICAL ENGINEERING UPDATED: 2016 SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTIFICATION. 18" MIN. OF TAIL. (NEUTRAL CONDUCTOR MUST BE WHITE OR
More informationData Bulletin. Wire Temperature Ratings and Terminations INTRODUCTION WHY ARE TEMPERATURE RATINGS IMPORTANT?
Data Bulletin March 2002 Lexington, KY, USA Wire Temperature Ratings and Terminations INTRODUCTION WHY ARE TEMPERATURE RATINGS IMPORTANT? Table 1: Insulation Type Figure 1: Figure 2: Ampacity of a 1/0
More informationPART A General Conductor Requirements
PART A General Conductor Requirements 6.1 Conductor Insulation Property Table 310.13 of the NEC provides information on conductor properties such as permitted use, maximum operating temperature, and other
More informationSOLAR PV INSTALLATIONS
Winnipeg Information Bulletin 2016-003-B/E/S/Z SOLAR PV INSTALLATIONS An Information Bulletin is currently being created for City of Winnipeg guidelines for Solar PV Installations and will be published
More informationThe Green Meter Adapter (GMA) program will become effective on January 15, Customers may start applying for a GMA on January 15, 2018.
SUMMARY This bulletin introduces a new PG&E program that allows the installation of an electric meter socket adapter that will accept a wired connection directly from a residential customer s Photo Voltaic
More informationSee Part 3 for the Introduction for Article 314
See Part 3 for the Introduction for Article 314 76 314.25 Covers and Canopies When the installation is complete, each outlet box must be provided with a cover or faceplate, unless covered by a fixture
More informationBusway Construction. Bus Bars
Busway Construction Bus Bars A better understanding of what busway is can be gained by examining its construction. A typical Siemens Sentron busway section has three or four formed aluminum or copper bars
More informationElectrical Tech Note 105 Agricultural Engineering Department Michigan State University
Electrical Tech Note 105 Agricultural Engineering Department Michigan State University Journey Exam Study Guide and Sample Questions 1 Based on the 2002 NEC, Part 8 of PA 230, and the 2003 MRC The Journey
More informationGrounding Systems. Equipment Grounding & Grounded Conductors
Grounding Systems Equipment Grounding & Grounded Conductors Definitions A Grounded or Earthed system is one that is connected to the earth Grounded Conductor is a conductor that normally carries current
More informationGreen Building Technology
Green Building Technology Renewable Energy Sources and Design/Specification Guidelines Presented by: Kurt Uhlir & Brian Kustwin Why Renewables? Reduction of SO 2 and NOX along with greenhouse gases such
More informationIET Wiring Regulations (BS 7671:2008+A3:2015) - SECTION 717 MOBILE OR TRANSPORTABLE UNITS
IET Wiring Regulations (BS 7671:2008+A3:2015) - SECTION 717 MOBILE OR TRANSPORTABLE UNITS 717.1 Scope The particular requirements of this section apply to a.c. and d.c. installations for mobile or transportable
More informationSection 6 Electric Metering: Residential
Section 6 Electric Metering: Residential 6.1. Scope This section provides specific information for residential metering that is not covered by the basic requirements in Section 5, Electric Metering: General.
More informationUNDERGROUND SERVICES - SECONDARY
UNDERGROUND SERVICES - SECONDARY Contents - Underground Services... U-1 General Requirements for Underground Service...U-2 Names of Parts for Underground Service... U-3 Service Termination in a Service
More informationRequirements for Secondary Voltage Revenue Metering (750 V and less)
Requirements for Secondary Voltage Revenue Metering (750 V and less) To view the latest revision of this document go to: http://www.bchydro.com/ext/metering/ January 28, 2010 Copyright 2008 by BC Hydro.
More informationDESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5
DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5 1.1. APPLICABLE PUBLICATIONS 1.1.1. Publications listed below (including amendments, addenda, revisions, supplements, and errata), form a part of this
More informationLoad Side PV Connections
Perspectives on PV Load Side PV Connections 705.12(D) in the 2014 NEC by John Wiles Through the exceptional efforts of the members of NFPA NEC Code-Making Panel 4 working with the proposals and comments
More informationSignificant Changes to the Philippine Electrical Code 2009 Edition
Significant Changes to the Philippine Electrical Code 2009 Edition Jaime V. Mendoza, MTM Board Member 2 PEC 2009 (8 th Edition) BEE Resolution No. 12 Series of 2009 Adoption of the Revised (8 th Edition)
More informationChapter 5. Imagine That Engineering Inc. Assured Equipment Grounding Conductor Program (AEGCP) Ground Fault Circuit Interrupter (GFCI)
Chapter 5 Imagine That Engineering Inc. Assured Equipment Grounding Conductor Program (AEGCP) Ground Fault Circuit Interrupter (GFCI) Imagine That Engineering Inc. has adopted this program for equipment
More informationThe following are specific provisions of 1910(a)(2) that could be seen in the LBM sector
Know the Rules on Temporary Wiring OSHA Standard 1910.305, Wiring methods, components, and equipment for general use, addresses wiring methods, components, and equipment for general use as one of several
More informationELECTRIC SERVICE RULES DISTRIBUTED GENERATION Issued Jan 2016
DISTRIBUTED GENERATION CHAPTER 5 500. SCOPE This chapter includes distributed or customer-owned generation connected in parallel and operating with Alliant Energy s electric distribution system. For all
More informationWIRING DESIGN & PROTECTION REQUIREMENTS CHECKLIST
WIRING DESIGN & PROTECTION REQUIREMENTS CHECKLIST Use & Identification of Grounded and Grounding Conductors YES NO N/A Grounded conductors are identifiable and distinguishable from all other conductors.
More informationARKANSAS ELECTRICIANS
CONTINUING EDUCATION FOR ARKANSAS ELECTRICIANS 2014 NEC Code Change 8 Hours AMERICAN ELECTRICAL INSTITUTE N16 W23217 Stone Ridge Drive, Suite 290 Waukesha, WI 53188 855-780-5046 www.aeitraining.com DISCLAIMER
More informationCorrections most seen on plan review October 18, 2017 David Rankin Seattle Department of Construction and Inspections
Corrections most seen on plan review October 18, 2017 David Rankin Seattle Department of Construction and Inspections One-Line / Riser Diagrams Drawings are not reviewed prior to submission. Because of
More informationDIVISION 311 MISCELLANEOUS ELECTRICAL RULES
DIVISION 311 MISCELLANEOUS ELECTRICAL RULES 918-311-0000 Design, Planning and Lay Out of Electrical Installations by Supervising Electricians A licensed supervising electrician may design, plan and lay
More informationElectrical and Power Transmission Installers, Other CIP Task Grid. Secondary Competency Task List. Level 1 Level 2 Level 3
1 100 BASIC SAFETY 101 Demonstrate proper use of personal protective equipment. 5 102 Identify causes of job site accidents. 5 103 Identify job site hazards. 5 104 Working safely with job hazards. 5 105
More informationThe Reliable Choice. Field Pocket Guide
The Reliable Choice Field Pocket Guide Allowable Ampacities of STABILOY Brand XHHW-2 and Copper 75 C (167 F) 90 C (194 F) 75 C (167 F) 90 C (194 F) Conductor Size (AWG or kcmil) Types RHW, THHW, THW, THWN,
More informationSTREAMLINED SOLAR CHECKLIST Owner Name:
STREAMLINED SOLAR CHECKLIST Owner Name: Address: DEPARTMENT OF PUBLIC WORKS AND PLANNING ALAN WEAVER, DIRECTOR This checklist must be completed by the contractor or an authorized agent of the contractor
More informationBID SPECIFICATIONS 2018 TERMINAL BUILDING STANDBY GENERATOR PROJECT
BID SPECIFICATIONS 2018 TERMINAL BUILDING STANDBY GENERATOR PROJECT The County of Hancock, Maine is seeking bids from qualified firms for the purchase and installation of at least a 20KW backup generator
More informationThe New 2017 National Electric Safety Code Overview and Significant Changes. Presented by. Mickey Gunter October 28, 2016
The New 2017 National Electric Safety Code Overview and Significant Changes Presented by Mickey Gunter October 28, 2016 NESC Technical Subcommittees Subcommittee 1 Coordination, Definitions Subcommittee
More informationPretest Module 29 High Voltage Unit 1
Pretest Module 29 High Voltage Unit 1 1. Is a person qualified to work on high-voltage installations when this module is completed? 2. What is the code definition of high-voltage? 3. What is the IEEE definition
More informationFACT SHEET Standard: Electrical Safety
What is a Ground Fault Circuit Interrupter? FACT SHEET The ground-fault circuit interrupter, or GFCI, is a fast-acting circuit breaker designed to shut off electric power in the event of a ground-fault
More informationChapter 8 Interior Wiring and Lighting
Chapter 8 Interior Wiring and Lighting Review Questions 1. What tool if any, is used to remove a fuse that is to be replaced? 1. Pliers 2. Screwdriver 3. Fuse puller 4. None 2. OSHA has established specific
More informationRevised: April 2018 ¹ SERVICE TO WIRELESS DEVICE ANTENNA ATTACHMENTS ON CUSTOMER SERVICE POLES (SHEET 1) CUSTOMER: 1. An overcurrent protective device including a disconnect switch shall
More informationTable of Contents. Unit 3 Magnetism Unit 1 Matter Unit 4 Electricity Unit 2 Electron Theory Unit 5 Electromagnetism...
Introduction...x How to Use This Textbook...xi About the Author...xii About the Graphic Illustrator...xiii Mike Holt Enterprises Team...xiv Chapter 1 Electrical Fundamentals... 1 Unit 1 Matter... 3 Introduction...
More informationInstalling Power Components
This chapter provides instructions on how to install and reinstall power components in the Cisco NCS 4016 chassis. It also covers connecting and disconnecting power and powering on the chassis. The Cisco
More informationResidential Photovoltaic (PV) Packet
Development Services Department Building Division 311 Vernon Street Roseville, California 95678-2649 (916) 774-5332 Fax (916) 774-5394 Residential Photovoltaic (PV) Packet The Roseville Municipal Code
More informationThe Use of Electricity In Mines Regulations
The Use of Electricity In Mines Regulations Repealed by Chapter E-6.3 Reg 4 (effective February 28, 1996). Formerly Chapter E-7.1 Reg 5. Table of Contents 1 Title 2 CSA Standard adopted with amendment
More information2011 NEC Significant Changes Part 1 The following course will summarize many of the important changes to the NEC code.
2 PART 1 American Electrical Institute 2013 2011 NEC Significant Changes Part 1 The following course will summarize many of the important changes to the NEC code. The 2011 Code has added 3 new articles:
More information