FOR ALL STAKEHOLDERS TO
|
|
- Morgan Lamb
- 5 years ago
- Views:
Transcription
1 Our Goal is FOR ALL STAKEHOLDERS TO HAVE A SUCCESSFUL PROJECT with us and that together we keep people and structures safe and buildings economically viable to serve the needs of our community. We strive for: EXCELLENT CUSTOMER SERVICE! and QUALITY INSPECTIONS! April 12th, 2017 ELECTRICAL CONSISTENCY MEETING OUR NEXT MEETING is May 10 th
2 l. Customer Service Tips a) Answer the phone; live is best but at least have a recorded message to let the customer have some expectations. b) Listen to the customer; listen attentively, we need to understand their needs and expectations to be successful. c) Focus on the positive; don t start the conversation negatively, if they do calmly diffuse it and move to a positive. Assure them you are there to help them move forward safely and successfully. d) If the customer has a complaint, assure them we are interested and will handle it as best and quickly as possible. Involve your support as needed and inform your customer. e) Always have your mind set on being helpful and accessible. Always be polite and respectful. When the rare case arises and you can t help them help themselves disengage and inform your manager.
3 ll. Consistency Questions 1. Does an ungrounded PV system require a grounding electrode system or interconnection to the premises grounding electrode system? If so, what code references support the requirement? Yes, a grounding electrode system is required and must be bonded to the ac grounding electrode system. See (A), (B), and (C), (ungrounded system), (grounded system)
4
5
6
7 2. A receptacle outlet is installed in a dwelling kitchen for the refrigerator & is within 6-feet of the kitchen sink. Does the receptacle outlet need to be GFCI protected? Yes, see A 7 of the NEC, but NO per NCEC A 7 if it is not serving the countertop (A6). 3. I installed a 20-amp duplex receptacle fed with a 20-amp multi-wire branch circuit. Each half of the duplex receptacle will have a 16-amp load for a total on the duplex of 32 amps. Is each half of the duplex receptacle rated 20 amps, or is the rating for the entire duplex receptacle? The inspector turned me down. We re not sure what the turn down was. Per UL 498 each receptacle is rated 20 amps, so that would not be the issue. This complies with
8 B, so again no issue. If you complied with and we don t see an issue. 4. I was turned down for not having the correct disconnect means for gas dispensers on my job. I had the E stops in and had the neutrals included on the breakers with lockouts for maintenance. What else is needed? From what info we have in the question it seems you may have neglected to account for the communications, data and video requirements. All disconnect requirements can be found in and.13 of the NCEC. 5. I have seen the intersystem bonding block used as a tap for the grounding electrode conductors. Is this listed for that purpose? My understanding is a block is only allowed for services with multiple disconnects and I am not
9 sure these units are considered bus-bars as (D)(1) states. No. The intersystem bonding termination is listed for grounding and bonding, but not as a splice or tap point for grounding electrode conductors. The intersystem bonding termination is for intersystem bonding conductor of other systems only. Code Reference: and B 6. I installed PVC conduits at a dispenser location beside the dispenser base. The inspector turned me down for not being 24 away. I think he was mistaken. The code only requires 24 of cover, not separation. Please clarify. For many years we have interpreted the cover to be required in all directions. Per the NCDOI/OSFM we were incorrect. The cover referred to by the code is only for vertical consideration.
10 We still strongly recommend that the 24 separation be maintained. PVC will not in itself contain an explosion and it is highly likely that the soil under the dispenser will have a mix of gas and vapors from small leaks over the time of service. This could create an unsafe condition. 7. I installed a surface mounted LED light in a clothes closet. It was 10 inches from the shelf. The inspector turned me down. I thought LED fixtures (luminaires) had the same clearances as fluorescents. What s required? LED luminaires do not have the same clearances in all cases as fluorescents in clothes closets. LED luminaires must be identified as suitable for installation within the closet storage space to be placed within 300 mm (12 in.) of the storage space. Code Reference: (A), (B), and (C)
11 8. As a rule, 4/0 Aluminum can be used for a two hundred amp 3 phase service even though it s rated for 180 amps, Article (3) allows the next larger size overcurrent protection (if less than 800). However, does it still apply to paralleled? Example two sets of 4/0 aluminum to feed a 400-amp service (separate raceways) would total 360 amps, next size up would be 400? Somewhere in the past I was taught when you paralleled you had to meet the full rating, (meaning you d have to use two sets of 250 Aluminum, for a total of 410 amps). I can t find that anywhere in the NEC. Am I remembering something that doesn t exist? Are two sets of 4/0 Aluminum okay for a 400amp service? B allows you to use the next standard size overcurrent device in this case (up to 800 amps). Your service would be limited to the load capability of the conductors which would be 360 amps not 400.
12 9. I have a project very like a recent project completed in another part of the county. At the prior location, we were required to complete an Industrial Machinery Declaration for some equipment there, and it was very cumbersome and confusing. Now at the new project we are being told we must go through the same process all over again. Is this going to have to be done again, this is exhaustive and no one can provide explanation on the process, the state has already ruled this is not needed. The process is as outlined on our web at meckpermit.com. This process was vetted by our attorney for compliance with the General Statutes. If you have difficulty with the process please resource your inspector, electrical supervisor or the electrical CA. The declaration will need to be made to exclude the equipment from our inspection. Per OSHA you still need to comply with having the equipment labeled by one of their recognized testing labs. The declaration we ask for allows you to bypass our
13 inspection and the enforcement becomes their responsibility and the owner s liability. 10. Are feeder SER cables installed into the top of meter enclosures located inside building electrical rooms of a multi-family structure required to be enclosed in drywall construction with at least a 15 min fire rating, in 3A and 5A buildings? How about in 1 and 2 type construction? B 4 refers us to 334 Part ll for this answer. NFPA and NCBC construction types differ. lll A and V A for NC are NFPA lll and V, type l and ll match. The types do not always directly match (2) allows the cables in multifamily dwellings lll, lv and V construction without enclosure. In other than dwellings cables must be concealed by a finish that has a 15-minute flash rating in lll, lv and V. Type l and ll buildings require the cables to be in raceways.
14 11. Can a GEC and an EGC be the same conductor, and if so, in what applications would this be compliant? Per Exception it could. On the primary of the transformer would be an example. 12. Are equipment grounding conductors required to be increased proportionately if the ungrounded conductors are increased due to ambient temperature de-rating concerns? B states that any increase in ungrounded conductors requires a proportional increase in the e.g. conductor. 13. On a single trade permit I have a 1 hr. wall with a low voltage cable through a PVC conduit sleeve and fire caulk installed inside the PVC sleeve. Is this a proper installation and how do we know, or this a Building Inspector concern?
15 The contractor will need to provide you a UL approved detail for the penetration if it is not shown on the approved plans. This should come from the project designer as a bulletin when plans are required for the project. 14. I have a job with high pile racking. It was originally permitted with no emergency lighting in the aisles. The fixtures are 2x4 LED high bays with individual occupancy sensors. The Electrical Contractor has gone back and installed battery-backup inverters for each fixture that will act as an emergency light. However, the occupancy sensors are still in play, so even in the event of a power outage, the lights do not come on until the Occ sensor is triggered. Is there a reference in the 2011 NEC that prohibits this? What about 2014?
16 Per NCDOI/OSFM, No. NCEC , 2012 NCBC & I am installing a 2400w 120v Insta hot water heater. I ran #12 wire and put it on a 20A breaker. My Inspector says that I can't fully load the circuit breaker, so I need to install a 25A breaker. Is this correct? I had another Inspector fail me on a similar install where I used #10 wire and a 30A breaker because he said the breaker was too large covers the circuit involved. Per the nameplate 2400w, 120v we have a 20-amp load. Since this unit is not a continuous load your installation was correct. 16. I've been running into several jobs where the contractor is installing a #6 bare copper
17 wire to the ground rod. Doesn't Mecklenburg require a #4 minimum? A allows a #6 and we will also. The issue is being subjected to physical damage. We have accepted an unprotected #4 solid in areas subjected to physical damage. 17. I'm running speaker wires in PVC conduit around a pool deck. My Inspector says I need to have the conduit at least 18" deep. Why? It's only speaker wires. First let s recognize that no underground other than what is necessary for pool equipment can be within 5 of the pool wall (680.10). Your question does not pinpoint your exact location of equipment and conduit(s). No outlets should be within 10 of the pool wall ( D). If the speakers are for underwater we need to comply with A. If the inspector
18 considered your system as a network powered broadband comm. system, then table C would apply. If that was not the case, then would apply. 18. Do we require breaker locks for water heaters if the panel is within sight of the water heater? does not require a lock when the breaker or switch is in sight. 19. My inspector turned me down for putting 2 wall sconces above the tub area in the master bathroom, she said they cannot be there, was she correct? What if I put them on a GFCI? A and D covers these sconces. Their position is the key. They may need to be damp or wet location rated and/or they may violate
19 other provisions such as chain suspended. Putting them on GFCI is a great idea. 20. Can an under counter wine cooler/mini fridge also be on the kitchen small appliance circuit? Or would 422/440 and or apply? Yes, no, maybe. For example, if the given appliance has a max ocp of 15 amps on the nameplate then no. It must be fused at 15 amps and the required 20-amp small appliance circuit would not work. Make a note on the rough inspection. 21. If I use an AFCI receptacle outlet for my dining receptacles, where should this device be installed if I have hit the kitchen small appl. and then to the dining? Can I put it at the first outlet in the dining where AFCI is required? Or
20 would it be required to be in the kitchen at the first outlet on the circuit? As stated in (A)(4)(c) it would be required at the first outlet on the circuit and must meet all requirements of (A)(4). 22) Is a zoning permit required to be on site for temporary power? A zoning permit is not a requirement for temporary power. 23) What is the minimum bonding conductor? What is maximum length? It depends on the particular application (A)(3) allows for 14 AWG, while (H) allows for 10 AWG. Also, the maximum length is regarding one and two family dwellings, where the bonding conductor
21 or grounding electrode conductor, shall be as short as practicable, not to exceed 20 in length. 24) I got questioned by one of our job foremen about ratings on PVC LB s. We had 2-4 LB s that we were going to use for 2 parallels of aluminums on a riser. He noticed inside the LB is was stamped 3-300MCM max. According to this you can t even use 4 with MCM copper for a 400 amp service anymore. I did some research and all that I could find was in a Mike Holt forum that said once you get over #6 wire, an LB is considered an angle pull box so you would have to have 24 between the conduit entrances. 4 LBs have 15 to 17 between them so that could explain the reduced wire capacity due to bending radius. I just checked a 2 LB and it says 3-3/0 max. If I understand this correctly
22 the only way to go through a wall now is either to use a vertical trough or a large pull box. Can you tell me how Mecklenburg County s interprets this please? I have always thought that an LB had the same capacity as the conduit as long as the conductors were not spliced in the LB. I had not seen this wire rating inside of the LB until recently. Conduit bodies fall under (2) and (3), in your particular application. The manufacturer is required to mark the max. size conductors per (3). That section is new to the 2014 NEC. Unfortunately, you are confined to the maximum wire size listed on the conduit body. In most cases the only alternatives are to provide a trough or an oversized LB. In any case we want to be sure we have sufficient wire bending space and do not damage the conductors.
23 25) Can we partially approve residential projects? That is not our common practice, however it is sometimes allowed with approval from the residential supervisor or manager. 26) Is the neutral service conductor required to be insulated? I was turned down for using a bare aluminum conductor in a PVC nipple between a meter can and a 200A panel feeding a residence. What gives? The question seems simple but it takes a lot of digging. Look at ; Part II. Overhead Service Conductors Insulation or Covering. Individual conductors shall be insulated or covered. Exception: The grounded conductor of a multiconductor cable shall be permitted to be bare.
24 Look at ; Part III. Underground Service Conductors Installation. (A) Insulation. Underground service conductors shall be insulated for the applied voltage. Exception: A grounded conductor shall be permitted to be uninsulated as follows: (1) Bare copper used in a raceway (2) Bare copper for direct burial where bare copper is approved for the soil conditions (3) Bare copper for direct burial without regard to soil conditions where part of a cable assembly identified for underground use (4) Aluminum or copper-clad aluminum without individual insulation or covering where part of a cable assembly identified for underground use in a raceway or for direct burial Look at ;
25 Part IV. Service-Entrance Conductors Insulation of Service-Entrance Conductors. Service entrance conductors entering or on the exterior of buildings or other structures shall be insulated. Exception: A grounded conductor shall be permitted to be uninsulated as follows: (1) Bare copper used in a raceway or part of a service cable assembly (2) Bare copper for direct burial where bare copper is approved for the soil conditions (3) Bare copper for direct burial without regard to soil conditions where part of a cable assembly identified for underground use (4) Aluminum or copper-clad aluminum without individual insulation or covering where part of a cable assembly or identified for underground use in a raceway, or for direct burial (5) Bare conductors used in an auxiliary gutter
26 Look at ; Part III. Construction Specifications Conductors. (D) Insulated. Conductors, not specifically permitted elsewhere in this Code to be covered or bare, shall be insulated. So in this question, a bare conductor is not allowed. lll. HAZ LOC Part 5
ELECTRICAL CONSISTENCY MEETING
ELECTRICAL CONSISTENCY MEETING Date: 10/14/2015 Our Goal is FOR ALL STAKEHOLDERS TO HAVE A SUCCESSFUL PROJECT with us and that together we keep people and structures safe and economically viable to serve
More informationMECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 9/14/11 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions
MECKLENBURG COUNTY Land Use and Environmental Service Agency Code Enforcement 9/14/11 ELECTRICAL CONSISTENCY MEETING Code Consistency Questions 1. I recently installed a 45-KVA transformer, 480-volt primary
More informationMECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 2/8/12 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions
MECKLENBURG COUNTY Land Use and Environmental Service Agency Code Enforcement 2/8/12 ELECTRICAL CONSISTENCY MEETING Code Consistency Questions 1. I am inspecting a building addition. They have a 480V to
More informationCHAPTER V RESIDENTIAL WIRING
CHAPTER V RESIDENTIAL WIRING 5.1. THE SERVICE ENTRANCE Buildings and other structures receive the electrical energy through the service entrance. In residential wiring, the electric company supply this
More informationCorrections most seen on plan review October 18, 2017 David Rankin Seattle Department of Construction and Inspections
Corrections most seen on plan review October 18, 2017 David Rankin Seattle Department of Construction and Inspections One-Line / Riser Diagrams Drawings are not reviewed prior to submission. Because of
More informationPretest Module 24 Three-phase Service Entrance
Pretest Module 24 Three-phase Service Entrance 1. What is the most widely used three-phase service entrance system? 2. What are the three most common voltage combinations for three-phase, four-wire systems?
More informationSpring Test 10 due 05/11/2013
Spring Test 10 due 05/11/2013 Multiple Choice Identify the letter of the choice that best completes the statement or answers the question. 1. When installed in an agricultural building that houses livestock
More informationWestern Section IAEI Code Panel Questions
Western Section IAEI 2013 Code Panel Questions 1. Do the factory wings that many fluorescent troffers have designed to fold out over the grid meet the requirements for securely fastened to the framing?
More informationWestern Section 101 st Annual Meeting Hot Springs, Arkansas September 21, 2005 Charlie Trout Code Breakfast
Western Section 101 st Annual Meeting Hot Springs, Arkansas September 21, 2005 Charlie Trout Code Breakfast 1.Question: An add on unit for a hydromassage bathtub consists of a small 1-gallon water heater
More informationHave You Been Grounded Lately
Have You Been Grounded Lately Thurs, Oct. 26, 2017 9:15-10:15 Phil Simmons Author, Electrical Grounding and Bonding Author Cengage Learning Phil Simmons Have You Been Grounded Lately 2017 NEC Changes Relative
More informationSECTION 1: Field Inspection Guide for Rooftop Photovoltaic (PV) Systems
COUNTY OF SANTA CRUZ PLANNING DEPARTMENT 701 OCEAN STREET, 4 th FLOOR, SANTA CRUZ, CA 95060 (831) 454-2580 FAX: (831) 454-2131 TDD: (831) 454-2123 KATHLEEN MOLLOY PREVISICH, PLANNING DIRECTOR Photovoltaic
More informationFee $20 Course: NEC Changes 1 This course is valid for these credentials: Credential Description Cred Code Credit Hours
www.garyklinka.com Page 1 of 18 Instructions: Fee $20 1. Print these pages. 2. Circle the correct answers and transfer them to the answer sheet. 3. Page down to the last page for the verification forms
More informationMicroinverters and AC PV modules are becoming. Microinverters and AC PV Modules. Different Beasts. Perspectives on PV.
Perspectives on PV Microinverters and AC PV Modules Are Different Beasts by John Wiles Microinverters and AC PV modules are becoming very common in residential and small commercial PV systems. See photos
More informationPentahead bolts See note 2. Conduit run as specified. Company facility. Refer to drawing SS8.6-2 or SS8.6-3 STANDARD SERVICE INSTALLATION
PULL BOX F SECONDARY SYSTEM Typical grade Pentahead bolts See note 2 Conduit run as specified Plastic or fiberglass for grass areas or Polymer concrete for light duty areas (see notes 2, 3, & 4) Company
More informationNEC 2011 Code Changes
NEC 2011 Code Changes Articles 280.21-300.50 CHANGES FROM 2008 TO 2011 CODE ARE IN RED Chapter 2 - Wiring and Protection ARTICLE 280 Surge Arresters, Over 1kV III. Connecting Surge Arresters 280.21 Connection
More informationSpring Test 7 due 05/03/2013
Spring Test 7 due 05/03/2013 Multiple Choice Identify the choice that best completes the statement or answers the question. 1. A raceway contains two 3-phase, 3-wire circuits that supply 38 ampere continuous
More informationSolar PV Standard Electrical Plan
*** Provide this document to the inspector along with ALL system installation instructions *** Project Address: Permit Number: SCOPE: Standard plan for installation of solar PV systems utilizing 2 wire
More informationChapter 2 Wiring and Protection Article 200 Use and Identification of Grounded Neutral Conductor Chapter 1 General...9
Article 90 Introduction...1 90.1 Purpose of the NEC...1 90.2 Scope of the NEC...2 90.3 Code Arrangement...4 90.4 Enforcement...5 90.5 Mandatory Requirements and Explanatory Material...6 90.6 Formal Interpretations...6
More informationGET GROUNDED. Renewable Energy System Grounding Basics
GET GROUNDED Renewable Energy System ing Basics by Christopher Freitas ASK TEN RENEWABLE ENERGY INSTALLERS ABOUT SYSTEM GROUNDING and you ll likely get ten different opinions as to what the National Electrical
More informationD9-3. No. WIRING DIAGRAM CONNECTIONS FOR UNDERGROUND SELF CONTAINED METERS JRH JED krich95 LINE LINE ABCN SOURCE SOURCE GROUND GROUND STUD STUD SOURCE
SOURCE 20V 240V STUD (PER NEC) A customer supplied and installed teaser wire is required from the neutral lug to a 5th terminal mounted on the left side of the meter block between the line and load terminals.
More information2014 NEC Analysis Part 2
www.garyklinka.com Page 1 of 24 Instructions: Fee $65 1. Print these pages. 2. Circle the correct answers and transfer them to the answer sheet. 3. Page down to the last page for the verification forms
More informationSupply-Side PV Connections
Perspectives on PV Supply-Side PV Connections by John Wiles Plan reviewers and inspectors throughout the country are seeing increasing numbers of supply-side connected utility interactive photovoltaic
More information9/7/2010. Objectives. Article 90. Introduction NEC Significant Changes. Review significant revisions in the 2011 NEC
2011 NEC Significant Changes Courtesy of NJATC Courtesy of NFPA Presented By: Michael J. Johnston Executive Director of Standards and Safety, NECA Objectives Review significant revisions in the 2011 NEC
More information2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE
2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE PAGE 1 OF 5 This Reference provides a very comprehensive list of aspects of a solar PV installation that could be reviewed, clarifying
More informationElectrical Tech Note 105 Agricultural Engineering Department Michigan State University
Electrical Tech Note 105 Agricultural Engineering Department Michigan State University Journey Exam Study Guide and Sample Questions 1 Based on the 2002 NEC, Part 8 of PA 230, and the 2003 MRC The Journey
More informationSOME REVIEW - QUESTIONS 2011 NATIONAL ELECTRICAL CODE
SOME REVIEW - QUESTIONS 2011 NATIONAL ELECTRICAL CODE J & W Educational Services 1340 Hickory Hill Dr. Watkinsville, Ga 30677 Jim Allison (706) 769-7112 jandw@uga.edu http://www.ugaed.com What is the Code
More informationData Bulletin. Wire Temperature Ratings and Terminations INTRODUCTION WHY ARE TEMPERATURE RATINGS IMPORTANT?
Data Bulletin March 2002 Lexington, KY, USA Wire Temperature Ratings and Terminations INTRODUCTION WHY ARE TEMPERATURE RATINGS IMPORTANT? Table 1: Insulation Type Figure 1: Figure 2: Ampacity of a 1/0
More information2011 NEC Significant Changes Part 1 The following course will summarize many of the important changes to the NEC code.
2 PART 1 American Electrical Institute 2013 2011 NEC Significant Changes Part 1 The following course will summarize many of the important changes to the NEC code. The 2011 Code has added 3 new articles:
More informationInstalling a Downstream Distribution Panelboard
Job Sheet 5 Installing a Downstream Distribution Panelboard OBJECTIVE To install a downstream distribution panelboard (DDP) on the Mobile Workstation. To mechanically and electrically connect the DDP to
More informationSee Part 3 for the Introduction for Article 314
See Part 3 for the Introduction for Article 314 76 314.25 Covers and Canopies When the installation is complete, each outlet box must be provided with a cover or faceplate, unless covered by a fixture
More informationThe 84 th NC Electrical Institute Code Questions April 9 th & 10 th 2013 North Raleigh Hilton Raleigh, NC
The 84 th NC Electrical Institute Code Questions April 9 th & 10 th 2013 North Raleigh Hilton Raleigh, NC www.ncdoi.com www.ncbeec.org NC DEPARTMENT OF INSURANCE NC STATE BOARD OF EXAMINERS OF ELECTRICAL
More informationGenerator Fire Safety: Generator assemblies should be located outside the building.
SECTION 33 70 00 - ELECTRICAL DISTRIBUTION PACKAGED GENERATOR ASSEMBLIES Generator Fire Safety: Generator assemblies should be located outside the building. All fuel piping from the outside of the building
More informationTemporarily Approved Solar Photovoltaic System Electrical Schematics
March 20, 2019 Page 1 of 10 Temporarily Approved Solar Photovoltaic System Electrical Schematics This document is intended as a temporary interpretation of approved solar photovoltaic electrical schematics
More information90.2 Scope. The installation of electrical conductors, equipment and raceways for:
NEC Generator Primer Rules on the installation of generators and transfer switches 1 90.2 Scope The installation of electrical conductors, equipment and raceways for: public and private premises Conductors
More informationPHOTOVOLTAIC ELECTRICAL POWER SYSTEMS INSPECTOR/INSTALLER CHECKLIST
PHOTOVOLTAIC ELECTRICAL POWER SYSTEMS INSPECTOR/INSTALLER CHECKLIST The following checklist is an outline of the general requirements found in the 2005 National Electrical Code (NEC) Article 690 for Photovoltaic
More informationSection 6 Electric Metering: Residential
Section 6 Electric Metering: Residential 6.1. Scope This section provides specific information for residential metering that is not covered by the basic requirements in Section 5, Electric Metering: General.
More information2016 Photovoltaic Solar System Plan Review List
Building Division 555 Santa Clara Street Vallejo CA 94590 707.648.4374 2016 Photovoltaic Solar System Plan Review List GENERAL PROJECT INFORMATION PLAN CHECK NO DATE JOB ADDRESS CITY ZIP REVIEWED BY PHONE
More informationDefinitions of and have been revised. a. automatic b. nonautomatic c. none of the above d. both a and b
www.garyklinka.com Page 1 of 12 Instructions: Fee $25 1. Print these pages. 2. Circle the correct answers and transfer them to the answer sheet. 3. Page down to the last page for the verification forms
More informationA Look at the 2017 NEC Significant Changes
A Look at the 2017 NEC Significant Changes A Look at the 2017 NEC Significant Changes Michael J. Johnston NECA James T. Dollard Local 98 Philadelphia Electrical JATC This session is eligible for 1 Continuing
More informationENGINEERING SPECIFICATION
December 206 ENGINEERING SPECIFICATION No. of 6 DATE: 2-9-6 CATEGORY SUBJECT TABLE OF CONTENTS. Overview... 2 2. General Requirements for Service... 3 3. Definitions... 3 4. Abbreviations... 5 5. References
More informationSECTION LOW VOLTAGE DISTRIBUTION EQUIPMENT
SECTION 16400 LOW VOLTAGE DISTRIBUTION EQUIPMENT A. General 1. The University does not accept Series-Rated equipment for power distribution switchboards, distribution panels and branch circuit panelboards.
More information2011 NEC Code Updates Part 3
www.garyklinka.com Page 1 of 22 Instructions: Fee $35 1. Print these pages. 2. Circle the correct answers and transfer them to the answer sheet. 3. Page down to the last page for the verification forms
More informationLearning Module 10: Loadcenters. 101 Basic Series
Learning Module 10: Loadcenters 101 Basic Series What You Will Learn We ll step through each of these topics in detail: What Does a Loadcenter Do? 4 Applications 4 Basic Circuitry and Wiring 5 Residential
More informationSOLAR PV STANDARD PLAN - COMPREHENSIVE Central/String Inverter Systems for One and Two Family Dwellings
SCOPE: Use this plan ONLY for utility-interactive central/string inverter systems not exceeding a total combined system ac inverter output rating of 10kW on the roof of a one- or two-family dwelling or
More informationUnderstanding National Electric Code (NEC) tap rules How do they apply to circuit breaker terminals?
White paper Understanding National Electric Code (NEC) tap rules How do they apply to circuit breaker terminals? Darryl Moser, Business Development Manager, DEM Sales, ABB, Electrification Products Division
More informationSINGLE PHASE WIRING SPECIFICATIONS
SINGLE PHASE WIRING SPECIFICATIONS 1-866-MEC-ELEC (1-866-632-3532) Office Locations: Hondo Office 237 Hwy 173 N Hondo, TX 78661-0370 Fax 830.426.3335 Dilley Office 1718 W. FM 117 Dilley, TX 78017 Fax 830.965.1425
More informationFig. 1. Sample calculation for determining the proper conductor size needed to serve a motor controller and avoid voltage drop problems.
Power to the Pump By Mike Holt, NEC Consultant Why some fire pump requirements are "backward" One of the principal NEC requirements for circuit protection is that you shut down the equipment rather than
More informationTHREE PHASE WIRING SPECIFICATIONS
THREE PHASE WIRING SPECIFICATIONS 1-866-MEC-ELEC (1-866-632-3532) Office Locations: Hondo Office 237 Hwy 173 N Hondo, TX 78661-0370 Fax 830.426.3335 Dilley Office 1718 W. FM 117 Dilley, TX 78017 Fax 830.965.1425
More informationChapter 4 Utility Systems Electrical
Chapter 4 Utility Systems Electrical Utility Systems Electrical The electrical supply to your home begins outside, where you will see either an overhead feed and piping down the side of your home or (if
More information(The actual state exam will be closer to 50 questions in 4 hours time) Master Electrician Practice Test
(The actual state exam will be closer to 50 questions in 4 hours time) Master Electrician Practice Test 1. Accessible as applied to wiring methods means capable of being removed or exposed without damaging
More informationThis is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly.
SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS (ELEC) This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly.
More informationSUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS - ELECTRICAL
SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS - ELECTRICAL This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly.
More information2014 NEC Changes Part 1 (Homestudy)
2014 NEC Changes Part 1 (Homestudy) Wisconsin Electrical License This course will review the first half of the most important National Electrical Code changes from the 2014 NEC. Changes in Articles 100-404.2
More information2011 NEC Changes Part 2 (Homestudy) (Homestudy)
2011 NEC Changes Part 2 (Homestudy) (Homestudy) North Carolina Electrical License This course will review the second half of the most important National Electrical Code changes from the 2011 NEC. Changes
More informationCode Compliance. Perspectives on PV. Back to the Grid, Designing PV Systems for
Perspectives on PV A series of articles on photovoltaic (PV) power systems and the National Electrical Code by John Wiles Back to the Grid, Designing PV Systems for Code Compliance 20 IAEI NEWS January.February
More informationELECTRIC SERVICE RULES DISTRIBUTED GENERATION Issued Jan 2016
DISTRIBUTED GENERATION CHAPTER 5 500. SCOPE This chapter includes distributed or customer-owned generation connected in parallel and operating with Alliant Energy s electric distribution system. For all
More information2014 NEC Changes (Homestudy)
2014 NEC Changes (Homestudy) Idaho Electrical License This course will review the most important National Electrical Code changes from the 2014 NEC. Changes in Articles 100 - Chapter 9 will be covered.
More informationINSPECTION REQUIREMENTS: PHOTOVOLTAIC (PV) RESIDENTIAL
Photovoltaic (PV) Residential Page 1 of 10 Revision Date: 07/18/2018 INSPECTION REQUIREMENTS: PHOTOVOLTAIC (PV) RESIDENTIAL INSPECTION CODE: 703 SCOPE: RESIDENTIAL APPLICABLE CODES: 2016 CBC, CRC, CPC,
More informationRESIDENTIAL SUBDIVISION SERVICE REQUIREMENTS SECTION VI RESIDENTIAL SUBDIVISION SERVICE REQUIREMENTS
SECTION VI SERVICE REQUIREMENTS This section discusses the requirements for establishing electric service to new residential subdivisions in Palo Alto. Subdivisions are normally constructed on dedicated
More informationWestern Section IAEI Code Panel Questions
Western Section IAEI 2013 Code Panel Questions 1. Do the factory wings that many fluorescent troffers have designed to fold out over the grid meet the requirements for securely fastened to the framing?
More informationPhotovoltaic Solar Plan Review
PAIGE B. VAUGHAN, CBO Director of Building and Safety Phone (310) 605-5509 Fax Line (310) 605-5598 E-mail:lbutler@comptoncity.org Building & Safety Department Photovoltaic Solar Plan Review Plan Check
More informationSOLAR PHOTOVOLTAIC SYSTEMS INSPECTOR CHECKLIST
SOLAR PHOTOVOLTAIC SYSTEMS INSPECTOR CHECKLIST The following checklist is an outline of the general requirements found in the 1999 National Electrical Code (NEC) Article 690 for Photovoltaic (PV) Power
More informationArc Fault Circuit Interrupter (AFCI) FACT SHEET
Arc Fault Circuit Interrupter (AFCI) FACT SHEET THE AFCI The AFCI is an arc fault circuit interrupter. AFCIs are newly-developed electrical devices designed to protect against fires caused by arcing faults
More informationWIRING DESIGN & PROTECTION REQUIREMENTS CHECKLIST
WIRING DESIGN & PROTECTION REQUIREMENTS CHECKLIST Use & Identification of Grounded and Grounding Conductors YES NO N/A Grounded conductors are identifiable and distinguishable from all other conductors.
More information320A Single Phase URD Meter Loop Installations
320A Single Phase URD Meter Loop Installations Location: The meter loop shall be mounted on the side of the pedestal facing the consumer's lot. (The side being one of the four flat surfaces of the pedestal
More information2010 National Electric Code
PDHonline Course E361 (4 PDH) 2010 National Electric Code Instructor: Thomas Mason, P.E. 2012 PDH Online PDH Center 5272 Meadow Estates Drive Fairfax, VA 22030-6658 Phone & Fax: 703-988-0088 www.pdhonline.org
More informationSolar PV Standard Electric Plan
*** Provide this document to the inspector along with ALL system installation instructions *** SCOPE: Standard plan for the installation of microinverter solar PV systems, not exceeding a total AC output
More informationChapter 8 Interior Wiring and Lighting
Chapter 8 Interior Wiring and Lighting Review Questions 1. What tool if any, is used to remove a fuse that is to be replaced? 1. Pliers 2. Screwdriver 3. Fuse puller 4. None 2. OSHA has established specific
More informationCHAPTER 10 ELECTRICAL. Notes:
CHAPTER 10 ELECTRICAL 1001.0 General Requirements. Electrical wiring and equipment shall comply with the requirements of NFPA 70, National Electrical Code (NEC), or local ordinances. 1002.0 Solar Photovoltaic
More informationSECTION 300 OVERHEAD SERVICE
SECTION 300 OVERHEAD SERVICE 300.01 General Company provides, installs, and maintains service drop to point of delivery approved by Company. Customer provides point of attachment which is acceptable to
More informationThe Green Meter Adapter (GMA) program will become effective on January 15, Customers may start applying for a GMA on January 15, 2018.
SUMMARY This bulletin introduces a new PG&E program that allows the installation of an electric meter socket adapter that will accept a wired connection directly from a residential customer s Photo Voltaic
More informationSolar PV Standard Plan Simplified Microinverter and ACM Systems for One- and Two-Family Dwellings
TOOLKIT DOCUMENT #4 Solar Standard Plan Simplified Microinverter and M Systems for One- and Two-Family Dwellings SCOPE: Use this plan ONLY for systems using utility-interactive Microinverters or Modules
More informationTable of Contents. Electrical Service Requirements. 1. General Requirements
Table of Contents 1. General Requirements 1.1 General Definition.................................................... 1 1 1.2 Booklet Purpose and Organization....................................... 1-1
More informationContents. Obtaining Electric Service from Your Cooperative...1. Bonding Frames of Major Appliances...4. Voltage Drop...8. Drawings...
Contents Obtaining Electric Service from Your Cooperative...1 Bonding Frames of Major Appliances...4 Voltage Drop...8 Drawings...14 Agricultural Buildings...23 Optional Standby Systems...42 Grounding &
More informationPHOTOVOLTAIC SYSTEMS
PV WORKSHEET STANDARD STRING ARRAY Solar photovoltaic (PV) systems have widely gained acceptance as an alternative energy source. Installations range from small arrays supplying bus stop luminaires to
More informationCHAPTER 10 ELECTRICAL
1001.0 General Requirements. 1001.1 Electrical Wiring and Equipment. Electrical wiring and equipment shall comply with the requirements of NFPA 70, National Electrical Code (NEC), or local ordinances.
More informationNew Service. From... BARRON. Spooner Office: P.O. Box 261 Spooner, WI Barron Office: P.O. Box 40 Barron, WI
New Service Guidelines and Diagrams From... BARRON www.barronelectric.com email: janderson@barronelectric.com Barron Office: P.O. Box 40 Barron, WI 54812-0040 Spooner Office: P.O. Box 261 Spooner, WI 54801-0261
More informationLoad Side PV Connections
Perspectives on PV Load Side PV Connections 705.12(D) in the 2014 NEC by John Wiles Through the exceptional efforts of the members of NFPA NEC Code-Making Panel 4 working with the proposals and comments
More informationElectrical Tech Note 106
Electrical Tech Note 106 Biosystems & Agricultural Engineering Department Michigan State University Master Exam Study Guide and Sample Questions 1 Based on the 2014 NEC, Part 8 of PA 230, PA 407, and the
More informationRevised: April 2018 ¹ SERVICE TO WIRELESS DEVICE ANTENNA ATTACHMENTS ON CUSTOMER SERVICE POLES (SHEET 1) CUSTOMER: 1. An overcurrent protective device including a disconnect switch shall
More informationTEMPORARY ELECTRIC WIRING FOR CARNIVALS, CONVENTIONS, EXHIBITIONS, FAIRS AND SIMILAR USES
INFORMATION BULLETIN / PUBLIC - ELECTRICAL CODE REFERENCE NO.: LAMC 93.0230 Effective: 3-24-69 DOCUMENT NO. P/EC 2002-006 Revised: 11-17-00 Previously Issued As: RGA #7-69 TEMPORARY ELECTRIC WIRING FOR
More informationElectrical Tech Note 111 Biosystems & Agricultural Engineering Department Michigan State University
Electrical Tech Note 111 Biosystems & Agricultural Engineering Department Michigan State University Electrical Code Changes in Michigan 1 (Based on Part 8, P.A. 230, the 2005 NEC and the 2003 MRC) This
More informationSolar PV Standard Plan Simplified Microinverter and ACM Systems for Oneand Two-Family Dwellings
County of Santa Barbara Your City logo here Solar Standard Plan Simplified Microinverter and M Systems for Oneand Two-Family Dwellings SCOPE: Use this plan ONLY for systems using utility-interactive Microinverters
More informationNEC REQUIREMENTS FOR GENERATORS
PROFESSIONAL DEVELOPMENT SEMINAR SERIES NEC REQUIREMENTS FOR GENERATORS (Based on NEC 2005 with limited 2008 commentary) AIA certified Continuing Education Units (CEU) Available GPS-140 National Electric
More informationRESIDENTIAL UNDERGROUND AND OVERHEAD SERVICE REQUIREMENTS SECTION II RESIDENTIAL UNDERGROUND AND OVERHEAD SERVICE REQUIREMENTS
SECTION II This section discusses the City of Palo Alto's requirements for establishing electric service to new or upgraded residential installations. The same requirements apply to both underground and
More informationTable of Contents. Unit 3 Magnetism Unit 1 Matter Unit 4 Electricity Unit 2 Electron Theory Unit 5 Electromagnetism...
Introduction...x How to Use This Textbook...xi About the Author...xii About the Graphic Illustrator...xiii Mike Holt Enterprises Team...xiv Chapter 1 Electrical Fundamentals... 1 Unit 1 Matter... 3 Introduction...
More informationOptimizing Emergency Power Systems for Health Care Applications
2018 Annual Conference Optimizing Emergency Power Systems for Health Care Applications aka: Using the latest code changes to improve system reliability and maybe even save some $$$... Overview Michigan
More informationCOMMERCIAL QUICK REFERENCE
COMMERCIAL QUICK REFERENCE PROVO CITY POWER STANDARDS ELECTRICAL ENGINEERING UPDATED: 2016 SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTIFICATION. 18" MIN. OF TAIL. (NEUTRAL CONDUCTOR MUST BE WHITE OR
More informationMecklenburg County Common Code Defects
Electrical Code Defects Improper Over Current Protection Code Description 310.15 Ampacities for s Rated 0 2000 Volts. (A) General. (1) Tables or Engineering Supervision. Ampacities for conductors shall
More informationPUBLIC UTILITY DISTRICT NO. 1 OF LEWIS COUNTY METERING SPECIFICATIONS
PUBLIC UTILITY DISTRICT NO. 1 OF LEWIS COUNTY METERING SPECIFICATIONS 1. General Metering Requirements a. Interpretation The District s metering requirements shall not be interpreted to conflict with the
More informationWISCONSIN ELECTRICIANS
Wisconsin Contractors Institute 2017 PART 2 3 CONTINUING EDUCATION FOR WISCONSIN ELECTRICIANS 2017 NEC Code Change Part 2 8 Hours WISCONSIN CONTRACTORS INSTITUTE N16 W23217 Stone Ridge Drive, Suite 290
More informationSolar PV Standard Plan Simplified Microinverter and ACM Systems for One- and Two-Family Dwellings
TOOLKIT DOCUMENT #4 Your City logo here Solar Standard Plan Simplified Microinverter and M Systems for One- and Two-Family Dwellings SCOPE: Use this plan ONLY for systems using utility-interactive Microinverters
More informationSolar PV Standard Plan Simplified Microinverter and ACM Systems for One- and Two-Family Dwellings
TOOLKIT DOCUMENT #4 Your City logo here Solar Standard Plan Simplified Microinverter and M Systems for One- and Two-Family Dwellings SCOPE: Use this plan ONLY for systems using utility-interactive Microinverters
More informationSolar PV Standard Plan Simplified Central/String Inverter Systems for One- and Two-Family Dwellings
Your City logo here Solar PV Standard Plan Simplified Central/String Inverter Systems for One- and Two-Family Dwellings SCOPE: Use this plan ONLY for utility-interactive central/string inverter systems
More informationSolar PV Standard Plan Simplified Central/String Inverter Systems for One- and Two-Family Dwellings
PV TOOLKIT DOCUMENT #3 Solar PV Standard Plan Simplified Central/String Inverter Systems for One- and Two-Family Dwellings SCOPE: Use this plan ONLY for utility-interactive central/string inverter systems
More informationADVANCED CALCULATIONS
ADVANCED CALCULATIONS 101. Why is it permissible in some cases to fuse a #14 AWG motor conductor with a 60 amp breaker when normally a #14 AWG should only be fused at 15 amps? a) the motor can't start
More informationSTOUGHTON UTILITIES ELECTRIC SERVICE RULES AND INFORMATION
CHAPTER 1 - GENERAL INFORMATION 100. Purpose 101. Codes and rules 102. Continuity of service 103. Frequency, Voltage, and Amperage Limitations 104. High voltages 105. Unusual capacity requirements 106.
More informationMetering and Service Installation:
Table of Contents 1. Metering Installation Requirements, General... 1 2. Type of Service... 2 3. Definitions... 2 4. Who Provides Metering Equipment?... 2 5. Establishment of Service... 2 6. Meter Access...
More informationAMENDMENT ELECTRIC SERVICE MANUAL 2014
AMENDMENT (Pages 20,43,50,72,74,,76,78,83,86,99) ELECTRIC SERVICE MANUAL 2014 Effective April 1, 2015 18-7 6.0 SERVICE AND SERVICE ENTRANCES (General), Continued Conductor Sizing It is recommended that
More informationAGRICULTURAL UNDERGROUND SERVICE 500 HP OR LESS
Prepared by: ABB1 AGRICULTURAL UNDERGROUND SERVICE 500 HP OR LESS 05619 Asset Type: Electric Metering Function: Design and Construction Issued by: Lisseth Villareal (LDV2) Date: 07-31-15 Rev. #10: This
More information