Optimizing Emergency Power Systems for Health Care Applications
|
|
- Dylan Gallagher
- 5 years ago
- Views:
Transcription
1 2018 Annual Conference Optimizing Emergency Power Systems for Health Care Applications aka: Using the latest code changes to improve system reliability and maybe even save some $$$...
2 Overview Michigan currently utilizes 2014 National Electrical Code (NEC) with a few amendments Amendments don t affect this discussion Some interesting changes in 2017 NEC will also be covered Health Care facilities with emergency generator powered loads must comply with NFPA 110 Level 1 requirements (2013)
3 Generator Labeling Requirements 2014 required marking on the generator set; 2017 softens it by allowing instructions Provides a means to verify available fault current from the alternator Allows designer to verify that what was specified and promised is supplied Marking (2017). Each generator shall be provided with a nameplate giving the manufacturer s name, the rated frequency, the number of phases if ac, the rating in kilowatts or kilovolt-amperes, the power factor, the normal volts and amperes corresponding to the rating, the rated ambient temperature, and the rated temperature rise. Nameplates or manufacturer s instructions shall provide the following information for all stationary generators and portable generators rated more than 15 kw (1) Subtransient, transient, synchronous, and zero sequence reactances (2) Power rating category (3) Insulation system class (4) Indication if the generator is protected against overload by inherent design, an overcurrent protective relay, circuit breaker, or fuse (5) Maximum short circuit current for inverter-based generators, in lieu of the synchronous, subtransient, and transient reactances 3
4 More Labeling (cont d new in 2014) Marking shall be provided by the manufacturer to indicate whether or not the generator neutral is bonded to the generator frame. Where the bonding of a generator is modified in the field, additional marking shall be required to indicate whether the generator neutral is bonded to the generator frame. Bonding practice is not standardized between manufacturers Designers should: State requirements on system 1-line Generally: If ground fault is required on any circuit upstream from an ATS, 4-pole ATS required (4-wire systems) If 4-pole ATS, bond at generator or where conductors from generator enter the building If 3-pole/4-wire, bond must be at utility source service entrance and generator cannot have bond at generator One N-G bond on any neutral bus SSwitched neutral 4
5 2017 Change: 700.6(D) Ground Fault. For systems with multiple emergency sources connected to a parallel bus, the ground fault sensor shall be permitted to be in an alternative location. Also allowed in article 701 and 702 systems in other words: all systems For multiple generator 4-wire system bond at neutral bus!
6 Alternator Protection Thermal Damage Characteristics (low Z fault) Alternator is more susceptible to damage than fully rated conductors NEMA MG1 requires I2t = 40 basis unless tested to validate different value End point is based on X d Time to damage depends on the nature of the fault Secondary damage due to overvoltage on single phase faults Single phase faults usually require faster tripping Generator submittals should include thermal damage information and demonstrate protection provided Electrical evaluation does not consider mechanical integrity of alternator and engine Must use prototype testing to validate design per NFPA 110 6
7 Alternator Protection Notice: All generators have similar damage curves Biggest difference is end point of curve (defined by X d) A generator can t make enough fault current to damage itself in less than: 8-10 seconds for a 3-phase fault As little as 1 second on a single phase fault Instantaneous trips never needed A generator can t damage a fully rated conductor set when it is properly protected A reason why NEC does not require cb at genset Single phase faults have a higher probability of alternator damage than 3-phase faults NEED overvoltage protection, properly set Trip relatively quickly, but not so quick as to nuisance trip on normally occurring conditions 7
8 Protecting a Generator Set Latest control systems from major US genset suppliers incorporate integrated protection specifically designed to protect the alternator Least risk to designer/owner as failure to protect the generator is responsibility on must incorporate a listing label Verify listing at submittal using file number at ul.com/certification directory 2017 NEC requires a label describing alternator protection (implied in previous versions) UL Certification directory describes listing details & requirements: Category (FTPM or NRGU may be used) Installation requirements vary with category and listing When proper alternator protection is provided no other protection is required for a fully rated feeder Masterspec text is generally not adequate to assure proper generator protection 8
9 Disconnect Means with Lock-out/Tag-out Article Generators shall be equipped with disconnect(s), lockable in the open position, by means of which the generator and all protective devices and control apparatus are able to be disconnected entirely for the circuits supplied by the generator except where both of the following conditions apply: 1) The driving means for the generator can be readily shut down, is rendered incapable of restarting, and is lockable in the OFF position in accordance with (2014 change). The generator is not arranged to operate in parallel with another generator or other source of voltage. 2) Article B (6) -- Where an outdoor housed generator set is equipped with a readily accessible disconnecting means located within sight of the building or structure supplied, an additional disconnecting means shall not be required where ungrounded conductors serve or pass through the building or structure. The disconnecting means shall meet the requirements of Per , location of disconnect for emergency circuits is required to be illuminated 9
10 2017 change Disconnecting Means and Shutdown of Prime Mover. (A) Disconnecting Means. Generators other than cord and plug-connected portable shall have one or more disconnecting means. Each disconnecting means shall simultaneously open all ungrounded conductors. Each disconnecting means shall be lockable in the open position in accordance with (B) Shutdown of Prime Mover. Generators shall have provisions to shut down the prime mover. The means of shutdown shall comply with all of the following: (1) Be equipped with provisions to disable all prime mover start control circuits to render the prime mover incapable of starting. (2) Initiate a shutdown mechanism that requires a mechanical reset. The provisions to shut down the prime mover shall be permitted to satisfy the requirements of (A) where it is capable of being locked in the open position in accordance with Generators with greater than 15kW rating shall be provided with an additional requirement to shut down the prime mover. This additional shutdown means shall be located outside the equipment room or generator enclosure and shall meet the requirements of (B)(1) and (B)(2). 10
11 Disconnects for Outdoor Gensets (B) (6) Outdoor Generator Sets. Where an outdoor housed generator set is equipped with a readily accessible disconnecting means in accordance with , and the disconnecting means is located within sight of the building or structure supplied, an additional disconnecting means shall not be required where ungrounded conductors serve or pass through the building or structure Most generator set installations will require the use of a disconnect device where the conductors enter the building or structure. Exceptions possible on sites with single management, qualified personnel for operation, and documented procedures 11
12 SUSE Breaker or Connection Box Requirements NEC requires disconnects to be suitable for use as service equipment ( B (6)) Bracing & Spacing Required Labels UL, Protection, Etc. Supply Side Barriers for SUSE (Not Shown) Neutral to Ground Link Wire Bend Space (Top or Bottom Connect) Ground Fault Provisions Ground Bus Adequate Lug Space Electrically solid to alternator frame & genset frame 2014 NEC does not require all these provisions when disconnect is on genset.
13 Should circuit breakers be installed on generator sets? We have seen that: Circuit breakers generally don t provide required alternator protection Generators can provided with breakers as a listed assembly, but UL doesn t verify that they actually protect the alternator NEC specifically allows other options Environmental issues with CB s Circuit breakers are not required to meet generator disconnect requirements For outdoor generator installations they generally don t meet the within sight rule as installed You probably need one or more where the conductors enter the building or structure Coordination for emergency systems can be difficult with multiple breaker manufacturers Less of an issue for essential electrical systems (0.1 S rule) (A) Constant-Voltage Generators. Constant-voltage generators, except ac generator exciters, shall be protected from overload by inherent design, circuit breakers, fuses, protective relays, or other identified overcurrent protective means suitable for the conditions of use. (2011, 2014 & 2017) (B) (5) (b) Exception: Exception to (5)b: Overcurrent protection shall be permitted at the source or for the equipment, provided that the overcurrent protection complies with the requirements of (requires selective coordination) (B) Overcurrent Protection Provided. Where a generator set is protected with a listed overcurrent protective device or a combination of a current transformer and protective relay conductors shall be allowed to be tapped from the load side of the protected terminals in accordance with (B). (2017) 13
14 Impact of NEC Tap Rules See (F) 14
15 Here s one that might make you smile Intended to allow a qualified designer to make judgements on the best way to meet the objectives of selective coordination Applies to any system Selective Coordination. Emergency system(s) overcurrent devices shall be selectively coordinated with all supply-side overcurrent protective devices. Selective coordination shall be selected by a licensed professional engineer or other qualified persons engaged primarily in the design, installation, or maintenance of electrical systems. The selection shall be documented and made available to those authorized to design, install, inspect, maintain, and operate the system. 15
16 2017 Failsafe Starting & Alarming Requires a change to the decades old practices of using a normally open contact that closes to start a generator. Most suppliers looking at going to a NC contact that opens. How do you deal with multiple switches? What do you do about the non-emergency transfer switches? No requirement that limits use of a NC to emergency Requires additional alarm lamps in the remote annunciator indicators for each emergency ATS and fire pump ATS Specs need updating 16
17 Fire Pump Applications New for 2017: Start circuit from fire pump and emergency ATS to generator set must be continuously monitored, and be fail safe Same rules apply to emergency circuits Fire pump power conductors from a generator should be protected for short circuit, and are not allowed to have overload protection Generators are required to be protected; but conductors from generator have only overload protection (remember, gensets can t damage themselves in less than 1 sec.) Best practice is to have listed protection for the generator and use tap rules in compliance to (A) (2) Note that generator sets serving fire pumps, and the fire pump circuit can t have ground fault trips 695(G). 17
18 2017 Provisions for Temporary Source Temporary Source of Power for maintenance or repair of the Alternate Power Source. The permanent switching means to connect a portable or temporary or alternate source of power shall comply with the following: 1. Connection to the portable or temporary source shall not require modification of permanent system wiring 2. Transfer of power shall be in accordance with The connection point for the portable or temporary alternate source shall be marked with phase rotation and system bonding requirements. 4. Mechanical or electrical interlocking shall prevent interconnection of power sources. 5. The switching source shall include a contact point that shall annunciate at a location remote from the generator or at another facility monitoring system that the permanent emergency power source is disconnected from the emergency system. Figure 700.3(F) Motivation: Time required to make temporary connections and, Deterioration of connection points for feeders 18
19 2017 Permanent Load Bank Connection 700.3(F)(1) requires that connection to a load bank be done without disturbing normal power connections. Easy way to do that is to have a dedicated load bank connection On the generator or remote from the generator at an accessible location Should trip if normal power fails while on load bank Some suppliers are building a combination of load bank and manual ATS into one box. Remember to locate field connections in an accessible location Good idea for any critical generator installation 19
20 2017 requirements for permanent provisions for both a temporary generator and a load bank connection (unless a load bank is permanently connected to genset. Load bank should accept trip signal if genset gets a remote start or if desired, if genset is overloaded. 20
21 Same functions using interlocked circuit breaker design Mixed Blessing Design Nice to have a canned solution BUT, Breakers need to coordinate with downstream for emergency, legally required, fire pumps Breakers aren t particularly good switches 21
22 2017 Disconnect Illumination Many outdoor generator sets don t incorporate lighting, and if the genset disconnect is in the building, it is often also not in an area that is lighted Best practice is to have emergency lighting in the enclosure of an outdoor generator, and in the area where the generator disconnect is located Where an emergency system is installed, emergency illumination shall be provided in the area of the disconnecting means required by and , as applicable, where the disconnecting means are installed indoors. Exception: Alternative means that ensure that the emergency lighting illumination level is maintained shall be permitted. 22
23 NFPA 110 (2013) Requirements covering the performance of emergency and standby power systems (gensets, ATS, and switchgear) providing an alternate source of electrical power to loads in buildings and facilities in the event that the primary power source fails. Covers installation, maintenance, operation, and testing requirements as they pertain to the performance of the emergency power supply system (EPSS). Intent of standard is to achieve maximum system reliability 23
24 Achieving Reliability Proper System Design Prototype Testing Factory Testing Field Testing In-Service Testing If you do these things well, you will get the best reliability! 24
25 Basics & Terminology Class - minimum time, in hours, for which the EPSS is designed to operate at its rated load without being refueled or recharged. Type - maximum time that the EPSS will permit the load terminals of the transfer switch to be without acceptable electrical power. Level - two levels of equipment installation, performance, and maintenance. Level 1 systems shall be installed where failure of the equipment to perform could result in loss of human life or serious injuries Level 2 systems shall be installed where failure of the EPSS to perform is less critical to human life and safety 25
26 Prototype Test Requirements Manufacturer of genset must certify compliance All manufacturers in North America do this Bad news: There s no common agreement on detailed requirements for prototype test Designer MUST interpret requirements What is reasonable, required, appropriate to needs of the application?
27 Factory Testing Critical, and often not careful enough Objectives: verify that machine is built correctly and performs as well or better than prototype Provides data to verify field installation is proper Recommended Required testing Complete standard production testing Cold start test (engine warm but not at operating temp) 2-hour full load test (0.8 pf), recording data continuously Transient tests at quarter load steps with recordings Test engine protection equipment Certified test report with all data recordings 27
28 Initial Field Testing Follow NFPA 110 Requirements Installation of equipment is complete Genset is in cold start condition (coolant heaters running) Simulate power failure at a transfer switch, observe proper system operation with genset starting and accepting load Be sure to record all data throughout test Apply expected load for at least 1.5 hours Remove start signal and observe proper system operation Conduct full load test 30% of rated load for 30 minutes, then 50% for 30 minutes, and finally 100% for 60 minutes (at 0.8 pf if not tested at 0.8 in the factory) Record data at 15 minute intervals throughout the test Cycle crank test Test engine safeties if not tested at the factory 28
29 Regular Testing & Maintenance NFPA 110 requirements for Level 1 systems Record-keeping required and is critical Inspect equipment weekly using manufacturer s inspection list or NFPA110 recommendation Test with load once per month for at least 30 minutes Minimum 30% load or recommended exhaust temperature If this can t be met, can do annual test at 50% for 30 min. & 75% for an hour TEST ATS equipment, too Test once every 36 months for duration of assigned Class (up to 4 hours) Test requires switching of loads to genset(s), Minimum 30% load for 3 hours and one hour at 75% Best practice is to test annually at full load for at least 2 hours using a load bank if necessary 29
30 Field Testing Objective is to verify that the system will deliver power to loads as designed NFPA 110 requirements have been softened over the years we recommend being more demanding Requirements: Verify each ATS will start the generator system Generator will start and pick up loads within 10 seconds Generator set will carry system loads 30
31 Common Shortcomings Inadequate prototype testing No total genset short circuit testing No total genset endurance testing Adequate transient performance Use of torsional calculations rather than testing Inadequate Cooling system testing Standard factory testing NETA testing that is unnecessary and potentially damaging 31
32 Big Things to take back to work Show the planned bonding for the generator neutral on every project, and remember: ONLY ONE N-G BOND ON NEUTRAL CONDUCTORS Required alternator protection can be done with any listed device; and circuit breakers generally don t protect generators Use listed and labeled protection from genset supplier Disconnect requirements can be met using E-stop For outdoor gensets, best location for N-G bond is where conductors enter building For outdoor generators use remote CB in building rather than mount on genset 2017 requirements for permanent load bank and temporary generator connections are a very good idea, even when they re not required. Design, install, test and maintain systems per NFPA 110 Level 1 requirements Especially prototype testing and in-service testing 32
33 Questions? Contacts: Gary Olson Local contact: Bruce Otte
90.2 Scope. The installation of electrical conductors, equipment and raceways for:
NEC Generator Primer Rules on the installation of generators and transfer switches 1 90.2 Scope The installation of electrical conductors, equipment and raceways for: public and private premises Conductors
More informationNEC REQUIREMENTS FOR GENERATORS
PROFESSIONAL DEVELOPMENT SEMINAR SERIES NEC REQUIREMENTS FOR GENERATORS (Based on NEC 2005 with limited 2008 commentary) AIA certified Continuing Education Units (CEU) Available GPS-140 National Electric
More informationAlternator protection, part 1: Understanding code requirements
Power topic #6002 Part 1 of 3 Technical information from Cummins Power Generation Alternator protection, part 1: Understanding code requirements > White paper By Gary Olson, Technical Counsel This paper
More informationDER Commissioning Guidelines Community Scale PV Generation Interconnected Using Xcel Energy s Minnesota Section 10 Tariff Version 1.
Community Scale PV Generation Interconnected Using Xcel Energy s Minnesota Section 10 Tariff Version 1.3, 5/16/18 1.0 Scope This document is currently limited in scope to inverter interfaced PV installations
More informationIN2 Enclosed Switches and Circuit Breakers
Illinois Math and Science Academy DigitalCommons@IMSA Project Manuals IN2 2015 IN2 Enclosed Switches and Circuit Breakers Illinois Mathematics and Science Academy Follow this and additional works at: http://digitalcommons.imsa.edu/facility_in2_manuals
More informationSUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS - ELECTRICAL
SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS - ELECTRICAL This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly.
More informationSECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 29 21 ENCLOSED SWITCHES AND CIRCUIT BREAKERS SPEC WRITE NOTE: Delete between // // if not applicable to project. Also delete any other item or paragraph not
More informationInstallation and Construction Notes for EVSE4
Installation and Construction Notes for EVSE4 You need to read and understand this if you want to build an EVSE that will be safe and need to pass a building inspectors review. Before beginning this process
More informationMedium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION
Medium Voltage Standby non-paralleling Control 1. GENERAL GUIDE FORM SPECIFICATION A. The requirements of the contract, Division 1, and part 16 apply to work in this section. 1.01 SECTIONS INCLUDE A. Medium
More informationService Entrance Methods
Service Section Typical switchboards consist of a service section, also referred to as the main section, and one or more distribution sections. The service section can be fed directly from the utility
More informationThis is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly.
SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS (ELEC) This is intended to provide uniform application of the codes by the plan check staff and to help the public apply the codes correctly.
More informationLow Voltage Automatic Transfer Switch Systems
Suitable for Emergency, Peak and Prime Power System Applications Low Voltage Automatic Transfer Switch Systems THE POWER AUTHORITY THE POWER AUTHORITY ASCO s experience and commitment to excellence in
More informationSECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS
SECTION 26 28 16 ENCLOSED SWITCHES AND PART 1 - GENERAL 1.1 SUMMARY A. Section includes the following individually mounted, enclosed switches and circuit breakers rated 600V AC and less: 1. Fusible switches.
More information1. Division 26 Section "Elevator Shunt-Trip Fused Disconnect Switches".
SECTION 26 28 16 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification Sections,
More informationSECTION PANELBOARDS
SECTION 16470 PANELBOARDS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. The general provisions of the contract including General and Special Conditions and General Requirements shall apply to all work under
More informationINTERCONNECTION STANDARDS FOR PARALLEL OPERATION OF SMALL-SIZE GENERATING FACILITIES KILOWATTS IN THE STATE OF NEW JERSEY
INTERCONNECTION STANDARDS FOR PARALLEL OPERATION OF SMALL-SIZE GENERATING FACILITIES 10-100 KILOWATTS IN THE STATE OF NEW JERSEY January 1, 2005 Rockland Electric Company 390 West Route 59 Spring Valley,
More informationCUSTOMER / ACCOUNT INFORMATION Electric Utility Customer Information (As shown on utility bill)
GENERATOR INTERCONNECTION APPLICATION Category 2 (Combined) For All Projects with Aggregate Generator Output of More Than 20 kw but Less Than or Equal to 150 kw Also Serves as Application for Category
More informationQuick Start Guide TS 910 & TS 920
Quick Start Guide TS 910 & TS 920 DANGER HAZARD OF ELECTRICAL SHOCK, EXPLOSION, OR ARC FLASH Read and understand this quick start guide before installing and operating the transfer switch The installer
More information1. The term "withstand" means "the unit will remain in place without separation of any parts from the device when subjected to the seismic forces.
SECTION 262816 - ENCLOSED SWITCHES AND CIRCUIT BREAKERS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Fusible switches. 2. Nonfusible switches. 3. Receptacle switches. 4. Shunt trip switches. 5.
More informationUniversity of Houston Master Construction Specifications Insert Project Name
SECTION 26 13 13 MEDIUM VOLTAGE SWITCHGEAR PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General
More informationPhotovoltaic Solar Plan Review
PAIGE B. VAUGHAN, CBO Director of Building and Safety Phone (310) 605-5509 Fax Line (310) 605-5598 E-mail:lbutler@comptoncity.org Building & Safety Department Photovoltaic Solar Plan Review Plan Check
More informationQuick Start Guide TS 910
Quick Start Guide TS 910 DANGER HAZARD OF ELECTRICAL SHOCK, EXPLOSION, OR ARC FLASH Read and understand this quick start guide before installing and operating the transfer switch The installer is responsible
More informationMAGNETIC MOTOR STARTERS
Chapter 6 MAGNETIC MOTOR STARTERS 1 The basic use for the magnetic contactor is for switching power in resistance heating elements, lighting, magnetic brakes, or heavy industrial solenoids. Contactors
More informationDesign considerations for generator set mounted paralleling breakers
Our energy working for you. Design considerations for generator set mounted paralleling breakers White Paper Hassan Obeid, Application Group Cummins Power Generation Cummins Power Systems has been delivering
More informationCorrections most seen on plan review October 18, 2017 David Rankin Seattle Department of Construction and Inspections
Corrections most seen on plan review October 18, 2017 David Rankin Seattle Department of Construction and Inspections One-Line / Riser Diagrams Drawings are not reviewed prior to submission. Because of
More informationLegal Name of the Customer (or, if an individual, individual's name): Name: Contact Person: Mailing Address: Physical Address: City: State: Zip Code:
Generating Facility Level 2 or 3 Interconnection Review (For Generating Facilities with Electric Nameplate Capacities no Larger than 20 MW) Instructions An Interconnection Customer who requests a Utah
More information2014 NEC Changes Part 4
www.garyklinka.com Page 1 of 14 Instructions: Fee $25 1. Print these pages. 2. Circle the correct answers and transfer them to the answer sheet. 3. Page down to the last page for the verification forms
More informationDISCONNECT SWITCH REQUIREMENTS FOR DISTRIBUTED GENERATION CUSTOMERS
Prepared by: SXZO DISCONNECT SWITCH REQUIREENTS FOR DISTRIBUTED GENERATION CUSTOERS 060559 Department: Electric Distribution Section: Design and Construction Approved by: D.Jantz (DWJ7) Date: 8/15/17 Rev.
More information2016 Photovoltaic Solar System Plan Review List
Building Division 555 Santa Clara Street Vallejo CA 94590 707.648.4374 2016 Photovoltaic Solar System Plan Review List GENERAL PROJECT INFORMATION PLAN CHECK NO DATE JOB ADDRESS CITY ZIP REVIEWED BY PHONE
More informationDocument Requirements for Engineering Review- PV Systems v1.1 12/6/2018
Document Requirements for Engineering Review- PV Systems v1.1 12/6/2018 Outlined below are the engineering documents and their associated minimum detail requirements for a Distributed Energy Resource (DER)
More informationDESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5
DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5 1.1. APPLICABLE PUBLICATIONS 1.1.1. Publications listed below (including amendments, addenda, revisions, supplements, and errata), form a part of this
More informationASCO Low Voltage Automatic Transfer Switch Systems
ASCO Low Voltage Automatic Transfer Switch Systems Suitable for Emergency, Peak and Prime Power System Applications ASCO s experience and commitment to excellence in designing and building Emergency Power
More informationSECTION MOTOR CONTROLLERS
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 29 11 SPEC WRITER NOTE: Use this section only for NCA projects. Delete between // ---- // if not applicable to project. Also, delete any other item or paragraph
More informationWIRING DESIGN & PROTECTION REQUIREMENTS CHECKLIST
WIRING DESIGN & PROTECTION REQUIREMENTS CHECKLIST Use & Identification of Grounded and Grounding Conductors YES NO N/A Grounded conductors are identifiable and distinguishable from all other conductors.
More informationData Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931
Data Bulletin 0931DB0101 July 2001 Cedar Rapids, IA, USA Ground-Censor Ground-Fault Protection System Type GC Class 931 09313063 GT Sensor Shunt Trip of Circuit Interrupter Window Area for Conductors GC
More information2000 Cooper Bussmann, Inc. Page 1 of 9 10/04/00
DO YOU KNOW THE FACTS ABOUT SINGLE-POLE INTERRUPTING RATINGS? YOU MAY BE IN TROUBLE! Typical plant electrical systems use three-phase distribution schemes. As an industry practice, short-circuit calculations
More informationCHAPTER 10 ELECTRICAL. Notes:
CHAPTER 10 ELECTRICAL 1001.0 General Requirements. Electrical wiring and equipment shall comply with the requirements of NFPA 70, National Electrical Code (NEC), or local ordinances. 1002.0 Solar Photovoltaic
More informationINSTRUCTIONS FOR THE RELIANCE CONTROLS ARM SERIES AUTOMATIC TRANSFER SWITCH
INSTRUCTIONS FOR THE RELIANCE CONTROLS ARM SERIES AUTOMATIC TRANSFER SWITCH THE RELIANCE CONTROLS ARM SERIES AUTOMATIC TRANSFER SWITCH IS NOT FOR "DO-IT-YOURSELF" INSTALLATION. It must be installed by
More informationSECTION MOTOR CONTROLLERS
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 29 11 MOTOR CONTROLLERS SPEC WRITER NOTE: Delete between // ---- // if not applicable to project. Also, delete any other item or paragraph not applicable to
More informationD. Operation and Maintenance Data. In addition to items specified in Division 1 Section "Operation and Maintenance Data," include the following:
SECTION 16211 - ELECTRICITY METERING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationLevel 2, Level 3 & Level 4 Interconnection Request Application Form (Greater than 10 kva to 10 MVA or less)
Section 466.APPENIX C Levels 2 to 4 Application Level 2, Level 3 & Level 4 Interconnection Request Application Form (Greater than 10 kva to 10 MVA or less) Interconnection Customer Contact Information
More information8300 Series Installation Guidelines
1-800-443-4859 8300 Series Installation Guidelines WARNING: RISK OF ELECTRICAL SHOCK OR BURNS. THIS CONVERTER ASSEMBLY SHOULD BE INSTALLED BY A QUALIFIED ELECTRICIAN OR CERTIFIED RV TECHNICIAN. IMPROPER
More informationUniversity of Houston Master Construction Specifications Insert Project Name SECTION ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL
SECTION 23 04 10 ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section
More informationTRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 03/05/09 TSEWG TP-11: UFC N BEST PRACTICES
TSEWG TP-11: UFC 3-500-10N BEST PRACTICES UFC 3-500-10N was developed by NAVFAC and was used as the starting point for the tri-services development of UFC 3-500-10, Design: Electrical Engineering. UFC
More informationRULE 21 GENERATING FACILITY INTERCONNECTION APPLICATION SMUD s Distribution System - (SMUD FORM 2655)
- (SMUD FORM 2655) A. Applicability: This Generating Facility Interconnection Application (Application) shall be used to request the interconnection of a Generating Facility to Sacramento Municipal Utility
More informationA. This Section includes ac, enclosed controllers rated 600 V and less, of the following types:
SECTION 262913 600 VOLT ENCLOSED CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 0 Specification
More information9/7/2010. Objectives. Article 90. Introduction NEC Significant Changes. Review significant revisions in the 2011 NEC
2011 NEC Significant Changes Courtesy of NJATC Courtesy of NFPA Presented By: Michael J. Johnston Executive Director of Standards and Safety, NECA Objectives Review significant revisions in the 2011 NEC
More informationMaryland Level 2, Level 3 & Level 4 Interconnection Request Application Form (Greater than 10 kw to 10 MW or less)
Maryland Level 2, Level 3 & Level 4 Interconnection Request Application Form (Greater than 10 kw to 10 MW or less) Interconnection Customer Contact Information Name: Address: City: Telephone (aytime):
More informationApplication Note Three Phase String Inverters NEC 2014 Compliance
Application Note Three Phase String Inverters NEC 2014 Compliance Version 2.0 July 07, 2014 The technical information and cross references of this document are subject to a continuous improvement and the
More informationA. Submit manufacturer's literature and technical data before starting work.
SECTION 16425 SWITCHBOARD PART 1 GENERAL 1.01 SUMMARY A. Related Section: 1. 16450 - Grounding. 1.02 SUBMITTALS A. Submit manufacturer's literature and technical data before starting work. B. Submit Shop
More informationMulti-Institutional Academic Health Science & Research Center Evansville, IN
SECTION 263213 - ENGINE GENERATORS PART 1 - GENERAL 1 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationDefinitions. Scope. Customer Generation Interconnection Requirements
Updated 02/1 Page 1 Scope The purpose of this document is to describe Idaho Power s requirements for the installation and testing of Customer Generation acilities that are interconnected with Idaho Power
More informationMaryland Level 2, Level 3 & Level 4 Interconnection Request Application Form (Greater than 10 kw to 10 MW or less)
Maryland Level 2, Level 3 & Level 4 Interconnection Request Application Form (Greater than 10 kw to 10 MW or less) Interconnection Customer Contact Information Name: Address: Alternative Contact Information
More informationCONTINUING EDUCATION FOR OREGON ELECTRICIANS NEC Code Change Part 2 Course # Hours
AMERICAN ELECTRICAL INSTITUTE 2017 PART 2 3 CONTINUING EDUCATION FOR OREGON ELECTRICIANS 2017 NEC Code Change Part 2 Course #90817 8 Hours AMERICAN ELECTRICAL INSTITUTE N16 W23217 Stone Ridge Drive, Suite
More informationWISCONSIN ELECTRICIANS
Wisconsin Contractors Institute 2017 PART 2 3 CONTINUING EDUCATION FOR WISCONSIN ELECTRICIANS 2017 NEC Code Change Part 2 8 Hours WISCONSIN CONTRACTORS INSTITUTE N16 W23217 Stone Ridge Drive, Suite 290
More informationDIVISION 26 ELECTRICAL SECTION CIRCUIT BREAKERS
DIVISION 26 ELECTRICAL SECTION 26 28 19 PART 1 GENERAL 1.01 DESCRIPTION A. Furnish and install circuit breakers in switchboards, distribution panelboards, and separate enclosures for overcurrent protection
More informationStandby Power Systems
Source: Power Quality in Electrical Systems Chapter 13 Standby Power Systems The term standby power systems describes the equipment interposed between the utility power source and the electrical load to
More informationA member-consumer with a QF facility shall not participate in the Cooperative s electric heat rate program.
Electric Tariff _2nd Revised Sheet No. 72 Filed with Iowa Utilities Board Cancels _1st Sheet No. _72 Cooperative is a member of Central Iowa Power Cooperative (CIPCO), a generation and transmission cooperative
More informationTransfer switch OTEC and OTECSE open transition
Specification sheet OTEC and OTECSE open transition 125-600 Amp Description OTEC transfer es are designed for operation and ing of electrical loads between primary power and standby generator sets. They
More informationCPS 3Phs String Inverters NEC 2014 Compliance
Application Note: NEC 2014 Compliance Revision: 062016 CPS 3Phs String Inverters NEC 2014 Compliance This application note describes the major changes within the NFPA 70, National Electric Code, specifically
More informationMotor Protection. Presented By. Scott Peele PE
Motor Protection Presented By Scott Peele PE Motor Protection Overload on the motor load Fuses Heater Magnetic relay Short Circuit on motor circuit Fuses Breakers Single Phasing Overload Protection NEC
More informationENTRANCE EQUIPMENT ER D PAGE 1 OF 5
PAGE 1 OF 5 USE: Requirements for entrance equipment. PREVIOUS REVISION 07-01-98 ORIGINATED 03-94 PREVIOUS NUMBER ER 100 (12-01-81) LATEST REVISION: Updated meter socket labeling specification and instrument
More informationUNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation
Basis of Design This section applies to the design relating to low voltage switchboards. Design Criteria UW Class N1 facilities main switchboards shall be rear accessible. The main, tie and feeder breakers
More informationSelection Guide Motor Control Device Solutions
Selection Guide Motor Control Device Solutions Expect more and get it from c3controls. Our portfolio of Motor Control Devices consists of worldclass products designed and manufactured to meet your requirements
More informationDISTRIBUTED RESOURCE GENERATION Feed-In-Tariff Single Phase
PAGE 1 OF 7 USE: Requirements and guidelines for interconnection of single phase customer owned, (DR) Distributed Resource generation source, to NIPSCO s electric system, configured for. LATEST REVISION:
More informationSECTION LOW VOLTAGE DISTRIBUTION EQUIPMENT
SECTION 16400 LOW VOLTAGE DISTRIBUTION EQUIPMENT A. General 1. The University does not accept Series-Rated equipment for power distribution switchboards, distribution panels and branch circuit panelboards.
More informationLevel 2, Level 3 & Level 4 Interconnection Request Application Form (Greater than 25 kw to 10 MVA or less)
Level 2, Level 3 & Level 4 Interconnection Request Application Form (Greater than 25 kw to 10 MVA or less) Interconnection Customer Contact Information Name Alternative Contact Information (if different
More informationMichigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE
PAGE 261116-1 SECTION 261116 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationA. Work Included: Provide low voltage switchboard work as shown, scheduled, indicated, and as specified.
SECTION 26 24 13 LOW VOLTAGE SWITCHBOARDS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General
More informationREQUIREMENTS FOR PARALLEL OPERATION FOR CUSTOMERS WITH GENERATION NOT EXCEEDING 50 kw
REQUIREMENTS FOR PARALLEL OPERATION FOR CUSTOMERS WITH GENERATION NOT EXCEEDG 50 kw FOREWARD Requirements for Parallel Operations for Customers with Generation Not Exceeding 50 kw is intended to be used
More informationGENERATOR INTERCONNECTION APPLICATION
GENERATOR INTERCONNECTION APPLICATION FOR ALL PROJECTS WITH AGGREGATE GENERATOR OUTPUT OF MORE THAN 150 KW BUT LESS THAN OR EQUAL TO 550 KW Also Serves as Application for Category 3 Net Metering (Note:
More informationMar H: SUPPLEMENTAL PARALLELING GEAR (16315-H)
2101 Commonwealth Blvd, Suite B Ann Arbor, MI 48105-5759 www.med.umich.edu/facilities/plan/ 263010-H: SUPPLEMENTAL PARALLELING GEAR (16315-H) Related Sections Basis Guideline: N/A For an explanation of
More informationMICHIGAN ELECTRIC UTILITY
MICHIGAN ELECTRIC UTILITY Generator Interconnection Requirements Category 3 Projects with Aggregate Generator Output Greater Than 150 kw, but Less Than or Equal to 550 kw August 3, 2009 Page 1 Introduction
More information4-Day Power System Analysis, Coordination, System Studies
4-Day Power System Analysis, Coordination, System Studies Contact us Today for a FREE quotation to deliver this course at your company?s location. https://www.electricityforum.com/onsite-training-rfq Our
More informationWhite Paper Load Banks for Power System Testing
White Paper s for Power System Testing A load bank provides a consistent and repeatable electrical load that can be accurately controlled, measured and recorded. Load banks convert or dissipate the resultant
More informationINSTRUCTIONS FOR THE RELIANCE Fast/Tran TM ARL0909 & ARL0909R
INSTRUCTIONS FOR THE RELIANCE Fast/Tran TM ARL0909 & ARL0909R THE RELIANCE Fast/Tran IS NOT FOR "DO-IT-YOURSELF" INSTALLATION. It must be installed by a qualified electrician thoroughly familiar with all
More informationDiesel generator set. QSB5 series engine Hz EPA Tier 3 emissions. Specification sheet. Description. Features
Specification sheet Diesel generator set QSB5 series engine 50-125 kw @ 60 Hz EPA Tier 3 emissions Description Cummins generator sets are fully integrated power generation systems providing optimum performance,
More informationA system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment.
General Unit substations shall be 500 kva minimum, 1500 kva maximum unless approved otherwise by the University. For the required configuration of University substations see Standard Electrical Detail
More informationProduct Overview. Product Identification. Amps One CT Two CTs Three CTs
AH06 (optional mounting bracket for small, medium, and large CTs) DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Follow safe electrical work practices. See NFPA 70E in the USA, or applicable
More informationManaging Electric Vehicle Supply Equipment (EVSE) Installations
Managing Electric Vehicle Supply Equipment (EVSE) Installations Introduction to Electric Vehicle EVSE Electric vehicles create a need to build an infrastructure that will supply the added load of charging.
More informationSelective Coordination
Circuit Breaker Curves The following curve illustrates a typical thermal magnetic molded case circuit breaker curve with an overload region and an instantaneous trip region (two instantaneous trip settings
More informationCaterpillar 1500kW XQ1500
Caterpillar 1500kW XQ1500 #4375 Diesel 480V EPA Tier 2 www.globalpwr.com Generator Features 2007 Caterpillar 1500 kw XQ1500 Diesel Generator. This XQ package features a sound attenuated enclosure, CAT
More information2018 Consultant s Handbook Division 26 Electrical 2413 Switchboards
1 General 1.1 Switchboards shall be U.L. listed and labeled. 1.2 Each switchboard shall have its own main disconnecting means unless it is located in the same room as its source of origin. In most cases
More informationData Bulletin. Wire Temperature Ratings and Terminations INTRODUCTION WHY ARE TEMPERATURE RATINGS IMPORTANT?
Data Bulletin March 2002 Lexington, KY, USA Wire Temperature Ratings and Terminations INTRODUCTION WHY ARE TEMPERATURE RATINGS IMPORTANT? Table 1: Insulation Type Figure 1: Figure 2: Ampacity of a 1/0
More informationMICHIGAN ELECTRIC UTILITY
MICHIGAN ELECTRIC UTILITY Generator Interconnection Requirements Category 4 Projects with Aggregate Generator Output Greater Than 550 kw or More, but Less Than or Equal to 2 MW August 3, 2009 Page 1 Introduction
More informationOTEC Transfer switch open transition
Specification sheet OTEC Transfer switch open transition 40 1200 amp Description OTEC transfer switches are designed for operation and switching of electrical loads between primary power and Standby generator
More informationFused Coordination Panelboard
Fused Coordination Panelboard SOLUTIONS GUIDE SOLUTIONS GUIDE Branch Circuit Protection Introducing Mersen s Fused Coordination Panelboard Selective Coordination is required in several locations as defined
More informationA. Products shall be designed, manufactured, tested, and installed in compliance with the following standards:
SECTION 26 29 13 ENCLOSED MOTOR CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General
More informationDiesel generator set QSX15 series engine
Specification sheet Diesel generator set QSX15 series engine 410 kw 455 kw 60 Hz Data Center Continuous EPA Emissions Description Cummins commercial generator sets are fully integrated power generation
More informationENGINEERING SPECIFICATION
December 206 ENGINEERING SPECIFICATION No. of 6 DATE: 2-9-6 CATEGORY SUBJECT TABLE OF CONTENTS. Overview... 2 2. General Requirements for Service... 3 3. Definitions... 3 4. Abbreviations... 5 5. References
More informationMEDIUM-VOLTAGE SWITCHGEAR
REVISION RECORD SECTION 16341 Medium-Voltage Switchgear REV DATE PAGE PARA NO. DESCRIPTION APPROVED BY 28SEP01 ALL Initial issue. 1 29SEP03 ALL General update with miscellaneous changes in entire document.
More informationDiesel generator set QSK23 series engine
Specification sheet Diesel generator set QSK23 series engine 600 kw - 800 kw Standby Description Cummins commercial generator sets are fully integrated power generation systems providing optimum performance,
More informationDevices for Branch Circuits and Feeders
Devices for Branch Circuits and Feeders Branch Circuit Overcurrent Protective Devices and s Fusible Solutions: When selecting fusible overcurrent protective devices, the type of fuse holder or switch is
More informationGenerator Fire Safety: Generator assemblies should be located outside the building.
SECTION 33 70 00 - ELECTRICAL DISTRIBUTION PACKAGED GENERATOR ASSEMBLIES Generator Fire Safety: Generator assemblies should be located outside the building. All fuel piping from the outside of the building
More information3.2. Current Limiting Fuses. Contents
.2 Contents Description Current Limiting Applications................. Voltage Rating.......................... Interrupting Rating....................... Continuous Current Rating................ Fuse
More informationSuggestion on How to Use
Suggestion on How to Use Industry Trainers are encouraged to use this material in their sessions Download both the PowerPoint file (.ppt) and script file (.pdf) Print the script file (.pdf) and read the
More informationIce Rink Renovation & New Clubhouse
SECTION 262913 - ENCLOSED CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationA. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein.
16425 SWITCHBOARD ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 26 24 13 An optional keynote to
More informationDiesel generator set QSK23 series engine
Specification sheet Diesel generator set QSK23 series engine 545 kw - 725 kw 60 Hz Data Center Continuous Description Cummins commercial generator sets are fully integrated power generation systems providing
More informationSelective Coordination Requirements
Selective Coordination Requirements Background Selective coordination of all upstream overcurrent protective devices in the supplying circuit paths is required by the NEC for a limited number of specific
More information