ECONET Fault and error manual

Size: px
Start display at page:

Download "ECONET Fault and error manual"

Transcription

1 Fault and error manual March 2009

2 Contents Basic data to get started...3 A Alarms 1. Ice alarm, GT Frost alarm, GT Pump alarm, P Pressure alarm, GP Liquid, temperature sensor alarm, GT 41, B Alarms 6. Air temperature sensor alarms, GT 00, 10, 20, Pump 1 or pump 2 alarm, P 40.1 or P Efficiency alarm...6 Other issues 9. Low heat recovery efficiency Pump continuous on 100%, P ECONET commissioning protocol...8 Fläkt Woods 8419 GB Specifications are subject of alteration without further notice.

3 Basic data to get started First, check following datas: Sensor Value Function Where to get the information Air temperatures GT 00: ºC Out door air, Thermometer AHU/ECONET controls GT 10: ºC Supply air Thermometer AHU/ECONET controls GT 20: ºC Exhaust air Thermometer AHU/ECONET controls GT 21: ºC Extract air Thermometer AHU/ECONET controls Liquid temperatures GT 40: ºC Supply coil in Thermometer or ECONET controls GT 41: ºC Supply coil out Thermometer or ECONET controls GT 42: ºC Exhaust coil out Thermometer or ECONET controls GT 30: ºC Primary heating in Thermometer or AHU controls GT 50: ºC Primary cooling in Thermometer or AHU controls Flows GF 10: m³/s Supply air Flow indicator, AHU/ECONET controls FO 10: Hz Supply air Frequency inverter GF 20: m³/s Exhaust air Flow indicator, AHU/ECONET controls FO 20: Hz, Exhaust air Frequency inverter GP 41: l/s Liquid flow ECONET controls FO 40: Hz Liquid flow Frequency inverter Others H.rec. signal V Heat recovery signal AHU/ECONETcontrols SV 40: % By pass valve, postion ECONET controls Fläkt Woods 8419 GB Specifications are subject of alteration without further notice.

4 A ALARMS 1. Ice alarm, GT 42 1.a. What? Low liquid temperature (GT 42) after the exhaust air coil. Risk of destroying the heat / cooling exchangers, set value for temperature alarm, standard +2 C. 1.b. Analysis SV 40: BY PASS VALVE SV 40 closed, Heat recovery signal 100% (10 V) SV 40 open error in valve or cabling heat recovery signal 0-30% cooling sequence manual position of valve, shall be in automatic position. GF 10, 20: AIR FLOW Exhaust air, GF 20<< supply air, GF 10 Exhaust air, GF 20<< of dimensioned. EXHAUST AIR COIL Frost formation on the exhaust air coil. GT 20: EXHAUST AIR TEMPERATURE Exhaust air temperature, GT 20 << of dimensioned. GP 41: LIQUID FLOW Liquid flow > 1/3 of supply air flow? Otherwise, ECONET does not increase the liquid flow due to the risk of ice formation check the parameters check the frequency inverter, shall be in automatic position. WHEN AT STATE NOT RUNNING When continuous Ice alarm the supplementary heating valve has to open during state not running, set value for opening SV 30 (heating valve) for example GT 42 = +10 C, look at ECONET functional description. A ALARMS 2. Frost alarm, GT 41 2.a. What? Low liquid temperature (GT 41) after the supply air coil. Risk of frost formation in the exhaust air coil, set value for temperature alarm, standard -10 C. 2.b. Analysis GT 10: SUPPLY AIR TEMPERATURE Set value = actual value GT 10 Set value > actual value GT 10 and SV 30 in position 100% reduced supplementary heating power too low heating temperature at SV 30 recovered heat from the exhaust air too low GP 41: LIQUID FLOW Liquid flow > 1/3 of supply air flow? GT 40 > GT C ECONET does not increase the liquid flow due to the risk of frost formation check the parameters GT 00 OUT DOOR AIR TEMPERATURE Out door air, GT 00 lower than dimensioning circumstances. WHEN AT STATE START UP Start sequense for AHU, first start ECONET and exhaust air unit, after some minutes start supply air unit. No or too slow availability of supplementary heating. OTHER ALARM Has there been another alarm before Frost Alarm? WHEN AT STATE START UP Start sequense for AHU, first start ECONET and exhaust air unit, after some minutes start supply air unit. OTHER ALARMS Has there been another alarm before Ice alarm? Fläkt Woods 8419 GB Specifications are subject of alteration without further notice.

5 A ALARMS 3. Pump alarm, P 40 3.a. What? The pump does not run, when it should. 3.b. Analysis POWER FAILURE (ELECTRICITY) Check. P 40: NO SIGNAL FROM PUMP Check cable. FO 40: FREQUENCY INVERTER FOR PUMP Inverter has to be on automatic. OVERVOLTAGE If there is an alarm when frequency on 50 Hz, it might be over voltage Why running on 50 Hz? Adjust max Hz to 45 Hz or lower. OTHER ALARM Has there been another alarm before the Pump alarm? A ALARMS 4. Pressure Alarm, GP 40 4.a. What? Low static pressure on suction side of pump (P 40) Risk of destroying components in the liquid circuit. Set value for alarm, standard 0,5 bar. 4.b. Analysis LEACKAGE IN LIQUID CIRCUIT Fix it. AIR IN THE LIQUID CIRCUIT Purge the air Check the air purging equipment Add liquid. A ALARMS 5. Liquid, temperature sensor alarm, GT 41, 42 5.a What? Component alarm, liquid temperatures, frost protection temperature (GT 41) or Ice protection temperature (GT 42). 5.b. Analysis CHECK CABLING CHECK SENSORS B ALARMS 6. Air temperature sensor alarm, GT 00, 10, 20, 21 and liquid temperature sensor alarm, GT 40 6.a What? Component alarm, liquid temperature at Pump (GT 40). Air temperature sensors for deliveries with temperature efficiency calculation. Component alarm, air temperatures, outdoor air temperature (GT 00) supply air temperature (GT 10) exhaust air temperature (GT 20) or extract air temperature (GT 21). 6.b. Analysis CHECK CABLING CHECK SENSORS 7. Pump 1 or Pump 2 alarm, P 40.1 or P a What? Only for deliveries with twin pump solution Component alarm, either one of the pumps or one of the frequency inverters (for the pumps). 7.b. Analysis CHECK PUMP AND FREQUENCY INVERTER replace the broken component COMPONET FAILURE, GP 40 Check the component. OTHER ALARM Has there been another alarm before the Pressure Alarm? Fläkt Woods 8419 GB Specifications are subject of alteration without further notice.

6 8. Efficiency alarm 8.a What? Only for deliveries with temperature efficiency cal culation. 8.b. Analysis CHECK CABLING CHECK SENSORS OTHER ISSUES 9 Low heat recovery efficiency 9.a What? Lower energy recovery efficiency than expected: The temperature heat recovery efficiency is calculated as: (GT 42-GT 41) x (GT 10-GT 00) h = (GT 40-GT 41) x (GT 20-GT 00) (GT 10-GT 00) h = (GT 20-GT 00) (GT 21-GT 20) h = (GT 00-GT 20) 9.b Analysis When the heating valve SV 30 is open When the heating valve SV 30 is closed When cooling recovery is calculated HEAT RECOVERY SIGNAL 100% (10 V) <100% (<10 V) no need of maximum heat recovery. GF 10, 20: AIR FLOW supply air flow = exhaust air flow supply air flow > exhaust air flow lower efficiency supply air flow < exhaust air flow higher efficiency GT 21: EXTRACT AIR TEMPERATURE GT 21 < GT GT 21 ~ GT 00 Exhaust air flow lower than the supply air flow GT 21 ~ GT 20 SV 40 open Exhaust air flow bigger than the supply air flow. GT 20: EXHAUST AIR TEMPERATURE check that the exhaust air temperature / humidity is similar to dimensioned exhaust air temperatur lower exhaust air temperature lower efficiency lower exhaust air humidity lower efficiency higher exhaust air temperature higher efficiency higher exhaust air humidity higher efficiency. GT 10: SUPPLY AIR TEMPERATURE check that the supply air temperature is similar to dimensioned. GP 41: LIQUID FLOW shall be 1/3 of the air flow l/s vs. m 3 /s < 1/3 of the supply air flow reduced heat recovery (Heat rec. signal< 100%) ECONET gets wrong air flow parameter fault > 1/3 of the supply air flow ice /frost formation mode ECONET gets wrong air flow parameter fault GT 40: LIQUID TEMPERATURE, SUPPLY COIL IN GT 40~GT C GT 40 ~ GT 41 high liquid flow low supply air flow GT 40 > GT 10 low liquid flow. GT 00: OUT DOOR AIR TEMPERATURE -10 C < GT 00 < 0 GT 00 < -10 C reduced heat recovery due to frost formation mode. Fläkt Woods 8419 GB Specifications are subject of alteration without further notice.

7 GT 41: LIQUID TEMPERATURE, SUPPLY COIL OUT GT 41 ~ GT C GT 41 ~ GT 40 high liquid flow low air flow GT 41~ GT 00 low liquid flow low supply air flow GT 41 < -3 C frost formation mode with high liquid flow. GT 42: LIQUID TEMPERATURE, EXHAUST COIL OUT GT 42 ~ GT C GT42 ~ GT 41 high liquid flow little/no exhaust air flow SV 40 open. SV 40: BY-PASS VALVE SV 40 closed, when heat recovery signal > 30% SV 40 open valve or cable fault cooling sequence manual / automatic position, shall be on automatic. 10. Pump continuous on 100%, P a. What? ECONET controls the liquid flow according to the need and the circumstances. Normally the pump runs on 30-60% of maximum when there is a need of maximum heat recovery, heat recovery signal =100% (10V). 10.b. Analysis GT 41: RISK OF FROST FORMATION GT41 < -3 C. G T 42: RISK OF ICE FORMATION GT 42 < +6 C. INDATA/PARAMETER LIST compare data found in the controls to the parameterlist. GF 10: CHECK THE SUPPLY AIR SIGNAL check type of signal flow/pressure linear signal, sensor/econet controls check k-factor, label on AHU/ECONET controls check wiring, for supply air GF 10 see below check the tubes. GP 41: PRESSURE SENSOR (Huba) is the sensor connected in a proper way? are the shut off valves in the right position? set value = actual value. SHUT OFF VALVES the shut off valves shall be open (except the shut off valve between the supplementary energy in/out, position depends on the connection) MMA valve shall always be 100 % open. P 40: PUMP ROTATION Pump running in the right direction? Compare with arrows found on the pump Check the pressure on the pressure side of the pump (4-6 bar). Air flow sensor, supply air GF20 X Air flow sensor, exhaust air GF10 G GO OUT Fläkt Woods 8419 GB Specifications are subject of alteration without further notice.

8 Liquid coupled heat exchanger EURT/STRZ-74 ECONET commissioning Project name AHU label Order number Date of start up Signed by Piping Ok Comments Mounting of pump unit Dip tray for pump Coils, connection Coils, drainage Air eliminator (automatic combined with a manual eliminator) Micro bubble eliminator Expansion vessel on suction side of oump P40 Anti-freeze liquid Ok Comments System filled up Air eliminated Static pressure in the system(> 1 bar) Opening pressure for expansion vessel (> 4 bar) Used anti freeze liquid for dimensioning Actual anti freeze liquid Supplementary heating Ok Comments Heat exhanger Heating energy connected Cooling exhanger Cooling energy connected Shut off valve, closed (closed circuit) Shut off valve, opened (opened circuit) Automation/electriffication made on site Ok Comments Cabling of controls between ECONET and AHU c.box Electricity to ECONET control Electricity to ECONET frequency converter Fläkt Woods 8419 GB Specifications are subject of alteration without further notice.

9 Liquid coupled heat exchanger EURT/STRZ-74 ECONET commissioning Supply air flow Ok Comments Components mounted and wired to the ECONET control box k-coeff label vs parameterlist Flow or pressure linear Scale, as in the parameterlist Check miniature switches Calibration of the transmitter Check the air tubes ECONET controls Ok Comments Data for project found in the control unit Instruction for control box Control box programmed with actual data Frequency converter programmed with actual data Calibration of the manometer to 0,5 bar Pump motor direction Check the wiring in the control box Other wiring/components LON card mounted and programmed Controls AHU/ECONET Ok Comments Start signal Heat recovery sequence Funtion of supplementary heating valve Cooling sequence Cooling recovery sequence Funtion of supplementary cooling valve A-alarms SV 40 closed/open Supply air flow to ECONET control box Optional Ext. delivery, efficiency and energy calculation Ok Comments GF 20 mounted and wired to the ECONET control box k-coeff label vs parameterlist Flow or pressure linear Scale, as in the parameterlist Check miniature swiches Calibration of the transmitter Check the air tubes GT 00 mounted and wired to the ECONET control box GT 10 mounted and wired to the ECONET control box GT 20 mounted and wired to the ECONET control box GT 21 mounted and wired to the ECONET control box Fläkt Woods 8419 GB Specifications are subject of alteration without further notice.

10 Fläkt Woods Group Brings Air to Life Fläkt Woods is a global company providing solutions for ventilation and air climate for buildings as well as fan solutions for Industry and Infrastructure applications. Fläkt Woods Group has 20 manufacturing/engineering operations worldwide, sales offices in 30 countries and representation in 95 countries. Head offices Buildings Air Climate Industry Air Movement FWG_ECONET Fault and error manual_ _se_8419 Condesign Info Productions AB ABF5503 Fläkt Woods AB Kung Hans väg 12 SE SOLLENTUNA Sweden t f Sales Offices available World Wide See our website for details. Due to a policy of continuous development and improvement the right is reserved to supply products which may differ from those illustrated and described in this publication. Certified dimensions will be supplied on request on receipt of order. Fläkt Woods Axial Way COLCHESTER, CO4 5ZD United Kingdom t f

ECONET. Exchanger Package

ECONET. Exchanger Package Exchanger Package May 2007 Table of Contents Scope of delivery...3 Assembly and installation...5 Spare parts list...7 8490 GB 2007.05 Page 2 Subject to alteration. ECONET Exchanger Package, scope of delivery

More information

ECONET PREMIUM START UP ON SITE ROUTINE FOR ECONET START UP: THE ECONET SYSTEM SHALL BE STARTED UP BY AUTHORIZED PERSONEL PROTOCOL BEFORE START UP

ECONET PREMIUM START UP ON SITE ROUTINE FOR ECONET START UP: THE ECONET SYSTEM SHALL BE STARTED UP BY AUTHORIZED PERSONEL PROTOCOL BEFORE START UP ECONET PREMIUM ROUTINE FOR ECONET START UP: 1. Protocol, before start up 2. 10 most important issues. Start up protocol THE ECONET SYSTEM SHALL BE STARTED UP BY AUTHORIZED PERSONEL PROTOCOL BEFORE START

More information

ECONET premium EQ STAZ-74, EQRZ-05, EQL STYZ-74, LQRZ-05 » INSTALLATION AND MAINTENANCE MANUAL. liquid-coupled heat exchanger ECONET premium

ECONET premium EQ STAZ-74, EQRZ-05, EQL STYZ-74, LQRZ-05 » INSTALLATION AND MAINTENANCE MANUAL. liquid-coupled heat exchanger ECONET premium AIR COMFORT AIR TREATMENT 9603 GB 2015.05.20 ECONET premium EQ STAZ-74, EQRZ-05, EQL STYZ-74, LQRZ-05» INSTALLATION AND MAINTENANCE MANUAL Content page liquid-coupled heat exchanger ECONET premium Integrated

More information

ECONET PREMIUM EQ STAZ-74, EQRZ-05, EQL STYZ-74, LQRZ-05

ECONET PREMIUM EQ STAZ-74, EQRZ-05, EQL STYZ-74, LQRZ-05 ECONET PREMIUM EQ STAZ-74, EQRZ-05, EQL STYZ-74, LQRZ-05 INSTALLATION AND MAINTENANCE MANUAL Content Page Liquid-coupled heat exchanger ECONET Premium Integrated pump and energy exchange package. Safety

More information

Heat recovery ventilators with rotating exchanger, automatic control and EC motor, designed for vertical ducts and installation in technical room

Heat recovery ventilators with rotating exchanger, automatic control and EC motor, designed for vertical ducts and installation in technical room RIRS V EKO Heat recovery ventilators with rotating exchanger, automatic control and EC motor, designed for vertical ducts and installation in technical room Common characteristics: Efficient low-noise

More information

Air Handling Unit Construction Checklist

Air Handling Unit Construction Checklist Air Handling Unit Construction Checklist Project: Date: AHU Tag: Location: Submittal / Approvals Submittal. The above equipment and systems integral to them are complete and ready for functional testing.

More information

Roof Units. Specification. Construction. Performance. Impellers. Size range. Ancillary Equipment

Roof Units. Specification. Construction. Performance. Impellers. Size range. Ancillary Equipment Roof Extract Units Roof Units Specification The Flaktwoods Colchester range of roof extract units are designed to satisfy the consultants functional requirement for a direct drive fan unit of guaranteed

More information

ECONET EXCHANGER PACKAGE EQRZ-05 AND LQRZ-05

ECONET EXCHANGER PACKAGE EQRZ-05 AND LQRZ-05 ECONET EXCHANGER PACKAGE EQRZ-05 AND LQRZ-05 INSTALLATION AND MAINTENANCE INSTRUCTIONS CONTENTS PAGE SCOPE OF DELIVERY...1 ECONET EXCHANGER PACKAGE... 2 ASSEMBLY AND INSTALLATION...4 SPARE PARTS LIST...5

More information

Technical data. WARNING! Residual voltage is present for 1 minute after disconnecting mains voltage.

Technical data. WARNING! Residual voltage is present for 1 minute after disconnecting mains voltage. INSTALLATI Speed-controlled drive system manufacturer EMS Model Units included S for rotary heat exchanger EURA, size 20 60. Page Content 1 Technical data 1 Units included............motor, Control unit

More information

Centriflow Plus EC. Technical data

Centriflow Plus EC. Technical data Technical data Centriflow Plus CTLOGUE Contents General description...3 General survey chart...4 Design description Fan Impeller...5 Inlet cone and supporting frame...5 EC motor...5 ir flow sensor...6

More information

CONFIGURABLE HIGH-EFFICIENCY HEAT RECOVERY UNITS CADB/T-HE PRO-REG Series

CONFIGURABLE HIGH-EFFICIENCY HEAT RECOVERY UNITS CADB/T-HE PRO-REG Series False-ceiling models CADB/T-HE 4 to 33 Heat Recovery Compact heat recovery unit with high-efficiency (up to 93%) counter-flow heat exchanger, EUROVENT certified. The casing is made from plasticised galvanised

More information

PH120. Rooftop Packaged. R410a Refrigerant PERFORMANCE DATA OUTDOOR COIL ENTERING TEMPERATURE 0 C

PH120. Rooftop Packaged. R410a Refrigerant PERFORMANCE DATA OUTDOOR COIL ENTERING TEMPERATURE 0 C PH120 R410a Refrigerant Rooftop Packaged INDOOR COIL ENTERING AIR TEMP 0 c DB WB 21 23 25 27 29 31 PERFORMANCE DATA OUTDOOR COIL ENTERING TEMPERATURE 0 C 30 35 40 45 Cap Cap Cap Cap 17 115.3 70.7 11.5

More information

For commissioning, maintenance and function checks of solar thermal systems Part no

For commissioning, maintenance and function checks of solar thermal systems Part no Operating instructions Solar service case For commissioning, maintenance and function checks of solar thermal systems Part no. 7248 299 Contents of the case A Compass B Information labels C Service labels

More information

Quick guide. Plug-in fans GPPM with FC101_106 August 2014

Quick guide. Plug-in fans GPPM with FC101_106 August 2014 Quick guide Plug-in fans GPPM with FC101_106 August 2014 Fläkt Woods permanent magnet motors and speed controllers for plug fans GPPM 1. General Fläkt Woods offers a wide range of permanent magnet motors

More information

RoomMaster ABR-2. Installation

RoomMaster ABR-2. Installation Installation List of contents General General... 3 Specification... 3 Accessories... 3 Dimensions and weight... 3 Delivery and transport... 4 Disassembling the unit... 4 Positioning the unit... 5 Reduced

More information

TWA S/K/P. Incorporating. R410A Air cooled water chillers with axial fans and scroll compressors from 189 kw to 1007 kw

TWA S/K/P. Incorporating. R410A Air cooled water chillers with axial fans and scroll compressors from 189 kw to 1007 kw TWA 212-1102 S/K/P Incorporating R410A Air cooled water chillers with axial fans and scroll compressors from 189 kw to 1007 kw The complete solution to all your cooling needs TWA 212-1102 S/K/P Index

More information

CHILLER START UP PROCEDURE FORM DOC. N (DOC.N BELOW TO BE RETURN TO AERMEC)

CHILLER START UP PROCEDURE FORM DOC. N (DOC.N BELOW TO BE RETURN TO AERMEC) CHILLER START UP PROCEDURE FORM DOC. N 061103 (DOC.N 071103 BELOW TO BE RETURN TO AERMEC) 1. Preliminary Operation WARNING: The following operation must be done without the power supply (unit with the

More information

Chiller. AQL/AQH 40 to 75. Air Cooled Water Chillers Cooling Only and Heat Pump Engineering Data Manual to 77.2 kw to 75.

Chiller. AQL/AQH 40 to 75. Air Cooled Water Chillers Cooling Only and Heat Pump Engineering Data Manual to 77.2 kw to 75. Chiller AQL/ to 75 Air Cooled Water Chillers Only and Heat Pump Engineering Data Manual.0 to 75.8 kw 39.9 to 77.2 kw Outstanding Strength Points R410A Refrigerant. New simpler refrigerant circuit layout.

More information

ifan Copford Box Range

ifan Copford Box Range Setting the Standard for Energy Management ifan Copford Box Range Energy Management by demand Introduction The ifan is designed to offer environmental management through a controllable solution for the

More information

ECONOVENT Rotary heat exchanger Instruction for variable speed EMX-R PUM with wiring diagram

ECONOVENT Rotary heat exchanger Instruction for variable speed EMX-R PUM with wiring diagram ECOVENT Rotary heat exchanger Instruction for variable speed EMX-R PUM 060-340 with wiring diagram Contents Variable speed PUM 060 340 General information...............................................

More information

Reversible air-to-water heat pump HEAT PUMP HEATING (30/35 C 40/45 C)

Reversible air-to-water heat pump HEAT PUMP HEATING (30/35 C 40/45 C) Simple, reliable efficient heat pump! Equipped with µconnect controller HFC R410A CERTITA CERTIFIED * Cooling capacity: 5 to 16.5 kw Heating capacity: 6 to 19 kw *except 75HT OPTION HEAT PUMP HEATING (30/35

More information

Kitchen exhaust fan GLEB

Kitchen exhaust fan GLEB Kitchen exhaust fan GLEB Contents General description...3 Quick selection...5 Design description...5 Material and design...6 Fan impeller...6 Motor...6...6 Quality...6 Specification...6 Technical data

More information

Air Handling Units. Geniox. Accessories

Air Handling Units. Geniox. Accessories Air Handling Units Geniox Accessories The right accessories are important to optimise your Geniox air handling unit to the task at hand. SystemairCAD provides you with a wide selection of accessories.

More information

PowerLink GW series Eddy Current Dynamometer User Manual

PowerLink GW series Eddy Current Dynamometer User Manual PowerLink GW series Eddy Current Dynamometer User Manual XiangYi (Hong Kong) Power Testing Instrument Co. Ltd. 0 GW Series Eddy Current Dynamometer User Manual Transport, Storage, use of environmental

More information

Fuel Cell Lab Manual. Non Conventional Energy Systems Facility. Non Conventional Energy Systems Facility. Boiler House

Fuel Cell Lab Manual. Non Conventional Energy Systems Facility. Non Conventional Energy Systems Facility. Boiler House Fuel Cell Lab Manual Non Conventional Energy Systems Facility Boiler House Department of Mechanical Engineering IIT Kanpur System Description The Nexa system provides up to 1200 watts of unregulated DC

More information

OPERATING AND MAINTENANCE INSTRUCTIONS for the GOLD Air Handling Unit, Sizes Applicable to Program Version 1.20 and newer versions

OPERATING AND MAINTENANCE INSTRUCTIONS for the GOLD Air Handling Unit, Sizes Applicable to Program Version 1.20 and newer versions OPERATING AND MAINTENANCE INSTRUCTIONS for the GOLD Air Handling Unit, Sizes 11-52 Applicable to Program Version 1.20 and newer versions Specifications are subject to alteration without notice. www.swegon.se

More information

Instructions for the BCEA Rotary heat exchanger

Instructions for the BCEA Rotary heat exchanger Instructions for the Rotary heat exchanger 1. General The heat recovery section is a rotary heat exchanger with high temperature and humidification efficiencies. The heat exchanger operates with an efficiency

More information

RAY TYPE 1 PRODUCT MANUAL

RAY TYPE 1 PRODUCT MANUAL 2 RAY TYPE 1 PRODUCT MANUAL CONTENT CONTENT... 3 ABOUT RAY... 4 HOW TO USE RAY... 6 Charging current... 6 To start charging... 6 To stop charging... 6 SAFETY PRECAUTIONS... 7 Warning... 7 Caution... 7

More information

HPR. Heat recovery units. from 700 to m³/h R410A HIGH EFFICIENCY WITH ENTHALPY EXCHANGER AND BUILT-IN HEAT PUMP SYSTEM

HPR. Heat recovery units. from 700 to m³/h R410A HIGH EFFICIENCY WITH ENTHALPY EXCHANGER AND BUILT-IN HEAT PUMP SYSTEM 1 Lmf Clima 216 FERRARO GROUP HPR Heat recovery units HIGH EFFICIENCY WITH ENTHALPY EXCHANGER AND BUILT-IN HEAT PUMP SYSTEM from 7 to 23. m³/h Supporting structure in extruded aluminium profiles and curtain

More information

ROOF FAN ROOFMASTER STEC

ROOF FAN ROOFMASTER STEC AIR COMFORT AIR MOVEMENT ROOF FANS ROOF FAN ROOFMASTER STEC INSULATED VERSION» TECHNICAL CATALOGUE 2 STEC Roofmaster - Technical Catalogue CONTENTS GENERAL DESCRIPTION Application/specification... 3 Features...

More information

DCV-CF DCV-CF. DCV-CF Pressure control with airflow measuring CFL Version B03. Pressure controlwith airflow measuring. Product description

DCV-CF DCV-CF. DCV-CF Pressure control with airflow measuring CFL Version B03. Pressure controlwith airflow measuring. Product description DCV-CF Pressure controlwith airflow measuring 24VAC + Communication Pressure control with airflow measuring DCV-CF DIN 24VAC + Communication AIN AOUT SMART DAMPERS & MEASURING UNITS PRESSURE & FLOW DCV-CF

More information

APP EOLE4. Applicable to program versions TAC5 Version DT & DG 2.7.0

APP EOLE4. Applicable to program versions TAC5 Version DT & DG 2.7.0 APP EOLE4 Applicable to program versions TAC5 Version DT 2.8.2 & DG 2.7.0 2 THE APP EOLE4 INTERFACE This interface can be used on Android, IOS and PC. Download the app from the App Store/Google Play or

More information

SB 2000 PUSH TO SEARCH NEXT STAG E. Aerotech, Inc. FORM: QM 1320

SB 2000 PUSH TO SEARCH NEXT STAG E. Aerotech, Inc. FORM: QM 1320 Inlet Controller SB 2000 USER'S MANUAL AUTO OPEN MANUAL PUSH TO SEARCH NEXT STAG E CLOSE Aerotech, Inc. FORM: QM 1320 4215 Legion Dr. Mason, MI 48854-1036 USA Rev. 3, Sept. 1997 Ph. (517) 676-7070 Fax

More information

Ventilation in balance

Ventilation in balance Ventilation in balance AIRLINQ - DIGITAL BMS PARAMETERS FOR BACNET TM /IP. BACNET TM MS/TP BASIC INFORMATION The present document is only valid for air handling units with firmware version 6. or newer.

More information

Regulation and shut-off damper SPB and SPC

Regulation and shut-off damper SPB and SPC SPB / SP -type multi leaf damper is a robust and reliable regulation and shut-off device to be used for different purposes in air handling systems. SPB SP.01.13 Area of application Multi leaf dampers are

More information

VT-SENSOR AIR VELOCITY AND TEMP

VT-SENSOR AIR VELOCITY AND TEMP home VTSENSOR AIR VELOCITY AND TEMP Ultra low velocity pressure measurement Traceable Calibration Certificate Excellent repeatability Self compensating zero Climate chamber compensated Long term span stability

More information

AIR VOLUME TRANSMITTER / CONTROLLER IML

AIR VOLUME TRANSMITTER / CONTROLLER IML 1131.60en 03.04.2013 AIR VOLUME TRANSMITTER / CONTROLLER IML IML air volume transmitter is designed for detecting and controlling air volumes in air handling units and room spaces. Air volumes are calculated

More information

Troubleshooting. CryoSmart 1 - CryoSmart 20

Troubleshooting. CryoSmart 1 - CryoSmart 20 Troubleshooting CryoSmart 1 - CryoSmart 20 ASTORI TECNICA di Astori Claudia & C. s.n.c. - Via Stelle, 11-25020 Poncarale (BS) - Italy Phone no.: +39 030 2540240 - Fax no.: +39 030 2640812 E-mail: info@astorioscar.com

More information

SLH 1202 to Air-to-Water Reverse Cycle Heat Pumps. With Screw Compressors. 261 to 775 kw. 287 to 853 kw

SLH 1202 to Air-to-Water Reverse Cycle Heat Pumps. With Screw Compressors. 261 to 775 kw. 287 to 853 kw Air-to-Water Reverse Cycle Heat Pumps SLH 1202 to 3804 With Screw Compressors 261 to 775 kw 287 to 853 kw Technical Brochure TM SLH-A.2GB Date : November 2004 Supersedes : TM SLH-A.1GB/05.04 Design Features

More information

Air-Cooled Liquid Chiller with integrated hydraulic module

Air-Cooled Liquid Chiller with integrated hydraulic module Air-Cooled Liquid Chiller with integrated hydraulic module Cooling only: CGAN 200-250 - 300-400 - 450-490 - 500-600 - 700-800 - 900-925 Reversible: CXAN 200-250 - 300-400 - 450-490 - 500-600 - 700-800

More information

Off grid Low frequency inverter

Off grid Low frequency inverter Off grid Low frequency inverter 210/220/230 V( LS series) Off-grid inverters (LS-E SERIES) 1-2 KW Eco Green Energy off-grid inverters proposes you its off-grid inverters. With a large range from 1 KW to

More information

Instructions for the BASIC BCVA Rotary heat exchanger, Sizes

Instructions for the BASIC BCVA Rotary heat exchanger, Sizes Instructions for the BASIC BCVA Rotary heat exchanger, Sizes 080 120 1. General The BCVA heat recovery unit is a rotary heat exchanger that offers high temperature efficiency. The heat exchanger operates

More information

CROWN ENERGY RECOVERY UNIT www.flaktwoods.com/oandm Safety, Installation, Operation and Maintenance Instructions Part No. 404443 Version C CONTENTS... Page Summary... 3 1 Receiving the Equipment... 3 1.1

More information

Accessories. Series REC

Accessories. Series REC Accessories Series REC 5-7-9 ACCESSORIES REC Series RBA BAF RBE CV3 PC3 SRE PSD CSA GIU TPA O. REC 5 REC 5-6 - 5BT11 5BT6 1CO71 1CO73 1SE96 5PR 1KR6 5SU137 5TE1 REC 5-12 5BT12 5BT122 5BT121 1CO71 1CO73

More information

Air Master BCP. Pool air handling units. Optimized energy consumption Electronic control. Description. Principle schemes

Air Master BCP. Pool air handling units. Optimized energy consumption Electronic control. Description. Principle schemes Cooling capacity: Heating capacity: 92,1 to 179,9 kw 69, to 148,7 kw Heating and dehumidification of covered pools Optimized energy consumption Electronic control Description Principle schemes The range

More information

HIGH EFFICIENCY ROTARY WHEEL - HELPING TO SAVE ENERGY AND REDUCE CARBON EMISSIONS.

HIGH EFFICIENCY ROTARY WHEEL - HELPING TO SAVE ENERGY AND REDUCE CARBON EMISSIONS. XBOXER THERMAL WHEEL HEAT RECOVERY UNITS HIGH EFFICIENCY ROTARY WHEEL - HELPING TO SAVE ENERGY AND REDUCE CARBON EMISSIONS. 118 029 2085 8200 XBOXER THERMAL WHEEL BENEFITS HIGH EFFICIENCY Up to 85% efficient

More information

Manual for Control Panel

Manual for Control Panel - 1 - Manual for Control Panel ver.4.0 MODEL: BP2006 Pro.:2006.12.Rev.:2007.08 http://www.olb.kr - 2 - Contents. 1. Front Operation. 2. Parts Names. 3. Initial setting cost. 4. Temperature setting method.

More information

Ventilation in balance

Ventilation in balance Ventilation in balance AIRLINQ - DIGITAL BMS PARAMETERS FOR MODBUS RTU RS485 BASIC INFORMATION The present document is only valid for air handling units with firmware version 6. or newer. The firmware

More information

ROOFMASTER STEF-HT ROOF FAN

ROOFMASTER STEF-HT ROOF FAN fire safety Air movement Roof Fans ROOFMASTER STEF-HT ROOF FAN» Technical CATALOGuE Contents ROOFMASTER STEF-HT...3 Performance Data...4 Performance Table...5 General description...6 Fan Chart-explanation

More information

UPS. MEGALINE UPS MODULAR SINGLE-PHASE from 1250 to VA THE GLOBAL SPECIALIST IN ELECTRAL AND DIGITAL BUILDING INFRASTRUCTURES

UPS. MEGALINE UPS MODULAR SINGLE-PHASE from 1250 to VA THE GLOBAL SPECIALIST IN ELECTRAL AND DIGITAL BUILDING INFRASTRUCTURES UPS MEGALINE UPS MODULAR SINGLE-PHASE from 1250 to 10000 THE GLOBAL SPECIALIST IN ELECTRAL AND DIGITAL BUILDING INFRASTRUCTURES Modular UPS redundant and upgradable up to 10k with perfomance and functions

More information

Fault Codes. J control

Fault Codes. J control J control Timer Temp Fault Codes 12 11 10 9 8 7 6 5 4 3 2 1 30 29 28 27 26 25 24 23 22 21 20 Enter unit inspection mode by pushing the UP and DOWN buttons simultaneously for two seconds. Ensure that the

More information

1 AIR HANDLING UNIT TYPE AIR ACCESS 75

1 AIR HANDLING UNIT TYPE AIR ACCESS 75 SUPPLY 1 AIR HANDLING UNIT TYPE AIR ACCESS 75 Location : EXTERNAL Position : SIDE BY SIDE SLIDING PANELS for COMPLETE ACCESSIBILITY MULTI SERVICE BULKHEAD for HYDRAULIC AND ELECTRICAL CONNECTIONS Self-supporting

More information

Each pump shall be equipped with carbon/graphite vanes. A vacuum relief valve shall be incorporated into the design of the pump.

Each pump shall be equipped with carbon/graphite vanes. A vacuum relief valve shall be incorporated into the design of the pump. 1 General Model MS300-4-530 expandable/modular central vacuum system consisting of 4 Becker or approved equivalent VTLF2.250 vacuum pumps mounted on a common skid with expandable automatic alternating

More information

MPPT Solar Integrated Inverters (500VA~2500VA) User Manual THE SOLAR TECH CO.,LTD. Solar Integrated Inverter Series 500VA~2500VA 13.

MPPT Solar Integrated Inverters (500VA~2500VA) User Manual THE SOLAR TECH CO.,LTD. Solar Integrated Inverter Series 500VA~2500VA 13. MPPT Solar Integrated Inverters (500VA~2500VA) User Manual THE SOLAR TECH CO.,LTD. - 1 - Table of Contents 1. SALIENT FEATURES...3 2.. PRODUCT INSTALLATION & PRECAUTIONS...3 2.1. PRODUCT INSTALLATION &

More information

ROTARY HEAT EXCHANGER EQRB

ROTARY HEAT EXCHANGER EQRB ROTARY HEAT EXCHANGER EQRB INSTALLATI AND MAINTENANCE INSTRUCTIS INSTALLATIS INSTRUCTI, DRIVE SYSTEM EMX-R, EQRB SIZE 020-090 SAFETY INSTRUCTIS IMPORTANT! During installation Read the instruction manual

More information

Midea VRFs/ Midea V5X. Timothy Huang Senior Engineer

Midea VRFs/ Midea V5X. Timothy Huang Senior Engineer Midea VRFs/ Midea V5X Timothy Huang Senior Engineer VRF Product Overview General Features V5X Key Technologies V5X VRF product strategy VRF line-up Fresh air solutions Selection software Unique Innovations

More information

VLH 504 to Air-to-Water Reverse Cycle Heat Pumps. 126 to 294 kw. 133 to 307 kw

VLH 504 to Air-to-Water Reverse Cycle Heat Pumps. 126 to 294 kw. 133 to 307 kw Air-to-Water Reverse Cycle Heat Pumps VLH 504 to 1204 126 to 294 kw 133 to 307 kw Technical Brochure TM VLH-N.3GB Date : June 2005 Supersedes : TM VLH-N.2GB/07.04 Specifications Advantages Range extension

More information

PHP-C Pressureless Expansion System Overview Description: The PHP-C balanced pressure expansion equipment is sized according to the total system volume and the boiler or chiller load. The PHP-C vessel

More information

VLS (Cooling Only) VLH (Heat Pump Version) VLR (Total Heat Recovery Version)

VLS (Cooling Only) VLH (Heat Pump Version) VLR (Total Heat Recovery Version) R u Air Cooled Water Chillers VLS (Cooling Only) VLH (Heat Pump Version) VLR (Total Heat Recovery Version) Models 524 to 1204 137 to 308 kw 150 to 336 kw Engineering Data Manual EDM VL410-W.2GB Date :

More information

About Control Systems

About Control Systems Control Systems Motor starters and System Control Panels control the operation of the system, both operation of the vacuum producers and cleaning of the filter. A variety of other control functions can

More information

Flex Series. Modular Air-cooled Chillers and Heat Pumps Cooling Capacity kw Heating Capacity kw

Flex Series. Modular Air-cooled Chillers and Heat Pumps Cooling Capacity kw Heating Capacity kw Flex Series Modular Air-cooled Chillers and Heat Pumps Cooling Capacity 38-329 kw Heating Capacity 47-354 kw 1 Trane Flex Series Modular air/water chillers and heat pumps units with axial fans and scroll

More information

Drained coolant must be stored in a clean container for disposal or reuse.

Drained coolant must be stored in a clean container for disposal or reuse. Cooling System, Draining and Filling Special tools, testers and auxiliary items required Adapter (V.A.G 1274/8) Adapter V.A.G 1274 tester (V.A.G 1274/10) Hose clamp pliers (V.A.G 1921) Cooling system charge

More information

GENERAL INFORMATION. H-1649, H-1650, H-1651 H-1653, H-1654 Easy-Count. uline.com. that may hurt accuracy:

GENERAL INFORMATION. H-1649, H-1650, H-1651 H-1653, H-1654 Easy-Count. uline.com. that may hurt accuracy: π H-1649, H-1650, H-1651 H-1653, H-1654 Easy-Count counting scale 1-800-295-5510 uline.com 1-800-295-5510 GENERAL INFORMATION Avoid placing the scale in locations that may hurt accuracy: 1. Temperature

More information

AZURA. Air/water multifunctional chiller&heat pump, kw

AZURA. Air/water multifunctional chiller&heat pump, kw AZURA STM Air/water multifunctional chiller&heat pump, 31-211 kw General Air/water unit with indipendent production of chilled water and hot water equipped with axial fans and hermetic scroll compressors.

More information

CMR CONTROLS AIR MANAGEMENT SYSTEMS PRESSURE VELOCITY SENSORS AND CONTROLS PRECISION COMPONENTS FOR VENTILATION AND PROCESS AIR CONTROL

CMR CONTROLS AIR MANAGEMENT SYSTEMS PRESSURE VELOCITY SENSORS AND CONTROLS PRECISION COMPONENTS FOR VENTILATION AND PROCESS AIR CONTROL Home AIR MANAGEMENT SYSTEMS PRESSURE VELOCITY SENSORS AND CONTROLS PRECISION COMPONENTS FOR VENTILATION AND PROCESS AIR CONTROL CMR TRANSDUCER manufacture accuracy AND REPEATABILITY IS most important The

More information

V-SENSOR LOW AIR VELOCITY SENSOR

V-SENSOR LOW AIR VELOCITY SENSOR home VSENSOR LOW AIR VELOCITY SENSOR Ultra low velocity pressure measurement Traceable Calibration Certificate Excellent repeatability Self compensating zero Climate chamber compensated Long term span

More information

SNMP dedicated to ORVALDI Solar Infini

SNMP dedicated to ORVALDI Solar Infini SNMP dedicated to ORVALDI Solar Infini User s Manual Management Software for Solar Inverter Table of Contents 1. 2. 3. Overview...1 1.1 Introduction...1 1.2 Features...1 1.3 Overlook...1 1.4 Installation

More information

Operator's manual ATSc Instrumentation en-gb

Operator's manual ATSc Instrumentation en-gb Operator's manual ATSc Instrumentation en-gb 68 57 Issue.0 Preface................................ Function............................... Instrument panel........................ 4 Switch...............................

More information

Chiller. SWS/SWR 1602 to Water Cooled Chillers Cooling Only and Condenserless Versions Engineering Data Manual.

Chiller. SWS/SWR 1602 to Water Cooled Chillers Cooling Only and Condenserless Versions Engineering Data Manual. Chiller SWS/SWR 1602 to 4802 Water Cooled Chillers Only and Condenserless Versions Engineering Data Manual 272 to 1118 kw Specifications General The SWS water cooled screw chillers are equipped with high

More information

Installation Instructions, TBLZ-1-23-aa Pressure Transducer GOLD/COMPACT/MIRUVENT

Installation Instructions, TBLZ-1-23-aa Pressure Transducer GOLD/COMPACT/MIRUVENT Installation Instructions, TBLZ-1-23-aa Pressure Transducer GOLD/COMPACT/MIRUVENT 1. General The pressure transducer is designed for use in ventilation systems intended for variable flow by keeping the

More information

Swimming Pool CSR2 Heat Recovery Equipment

Swimming Pool CSR2 Heat Recovery Equipment Swimming Pool CSR2 Heat Recovery Equipment LIFETIME WARRANTY OVER 90% HEAT RECOVERY LOW CARBON British manufacturing at its best EcoAir Box is a trademark of IPT +44 (01527) 492770 www.ecoairbox.co.uk

More information

JM Aerofoil Multi-Stage 50 Hz

JM Aerofoil Multi-Stage 50 Hz JM Aerofoil Multi-Stage 5 Hz JM AEROFOIL - MULTI-STAGE CONTENTS Page: JM Aerofoil Multi-Stage - Introduction -5 Multi-Staging Motor Frame Size Schedules - Three Phase 7-8 Performance Curves SK1- SK135

More information

LK Manifold Shunt VS2

LK Manifold Shunt VS2 LK Manifold Shunt VS2 Design LK Manifold Shunt VS2 is a shunt unit with a two way control valve used in systems with a primary pump. The shunt unit is mountable from both the left and right of LK Manifolds.

More information

Technical Specification SENTINEL PRO

Technical Specification SENTINEL PRO Technical Specification SENTINEL PRO Contents 1 GENERAL DESCRIPTION... 3 1.1 Main features of the UPS unit... 4 1.2 Standard Versions... 4 1.3 ER Versions for extended autonomy... 4 2 SENTINEL PRO SERIES

More information

Aquavar e-abii. TECHNICAL BROCHURE BAQUAeABII VARIABLE SPEED CONSTANT PRESSURE SYSTEMS

Aquavar e-abii. TECHNICAL BROCHURE BAQUAeABII VARIABLE SPEED CONSTANT PRESSURE SYSTEMS TECHNICAL BROCHURE BAQUAeABII * Available up to 1 GPM systems Aquavar e-abii VARIABLE SPEED CONSTANT PRESSURE SYSTEMS 1 HP thru 5 HP - Pressure Booster Packages 1AB2 and 2AB2 Prewired Pump/Controller Kits

More information

SE8300 Series Installation Guide 24 Vac Low Voltage

SE8300 Series Installation Guide 24 Vac Low Voltage Installation Guide 24 Vac Voltage mercial and Hotel/Lodging HVAC Fan Coil Applications CONTENTS Installation 2 Configurable BI/UI Universal Inputs Overview 3 Setup Screen Display 3 Terminal Identification

More information

BAS Construction Checklist

BAS Construction Checklist BAS Construction Checklist Project: Building: Location: Submittal / Approvals Submittal. The above equipment and systems integral to them are complete and ready for functional testing. The checklist items

More information

E-Series and EF-Series Systems

E-Series and EF-Series Systems E-Series and EF-Series Systems Site Preparation Guide NetApp, Inc. 495 East Java Drive Sunnyvale, CA 94089 U.S. Telephone: +1 (408) 822-6000 Fax: +1 (408) 822-4501 Support telephone: +1 (888) 463-8277

More information

VFD - Mitsubishi. VFD Manuals. Mitsubishi D700 VFD Installation. Mitsubishi FR-D700 VFD User Manual. Mitsubishi D700 Parallel Braking Resistors

VFD - Mitsubishi. VFD Manuals. Mitsubishi D700 VFD Installation. Mitsubishi FR-D700 VFD User Manual. Mitsubishi D700 Parallel Braking Resistors VFD - Mitsubishi VFD Manuals Mitsubishi D700 VFD Installation Mitsubishi FR-D700 VFD User Manual Mitsubishi D700 Parallel Braking Resistors VFD Wiring Diagram - Apollo Mitsubishi VFD to Interpreter Mitsubishi

More information

CH5000 Heat Recovery Ventilator

CH5000 Heat Recovery Ventilator ADVANCED COMMERCIAL Heat Recovery Ventilator PRODUCT SPECIFICATIONS & TECHNICAL DATA Features NOMINAL CAPACITY 3500-5500 CFM CASING Double-wall cabinet White exterior paint, 22-gauge galvanized steel -gauge

More information

NEBBinar: A TAB Professional s Wish List: Equipment Procedures & Issues. March 27, 2014

NEBBinar: A TAB Professional s Wish List: Equipment Procedures & Issues. March 27, 2014 NEBBinar: A TAB Professional s Wish List: Equipment Procedures & Issues March 27, 2014 0 Moderator Tom Hanlon NEBB s TAB Committee Tom has forty years of experience in refrigeration systems control system

More information

Solar Inverter/Charger

Solar Inverter/Charger Solar Inverter/Charger PV1100 PLUS Table of Contents 1. General Information...1 1.1 Brief Introduction. 1 1.2 Inverter Schematic Diagram.1 1.3 Inverter Components Instructions... 2 2. Fault Code...3 3.

More information

Compresseur scroll. Refrigerant R410A SYSAQUAC. Air Cooled Condensing Units Models 25 to to 136.0kW

Compresseur scroll. Refrigerant R410A SYSAQUAC. Air Cooled Condensing Units Models 25 to to 136.0kW Compresseur scroll Refrigerant R410A SYSAQUAC Air Cooled Condensing Units Models 25 to 125 32.0 to 136.0kW SYSAQUA Condensation 1 Key Points R410A refrigerant, Units are optimized for partial load operation,

More information

Cooling system components, removing and installing

Cooling system components, removing and installing 19-1 Cooling system components, removing and installing Note: When the engine is warm the cooling system is under pressure. If necessary release pressure before starting repair work. Hoses are secured

More information

Control panel. For 3 three-phase electric pumps with thermal protection and exchanger

Control panel. For 3 three-phase electric pumps with thermal protection and exchanger AUTOCLAVES PRODUCTS Control panel For 3 three-phase electric pumps with thermal protection and exchanger General features: Electromechanic panel with electronic control Sequence exchanger for 2 electro

More information

Volkswagen New Beetle 1.8 Liter 4-Cyl. 5V Turbo OBD II Engine Mechanical 19 Engine-Cooling system (Page GR-19)

Volkswagen New Beetle 1.8 Liter 4-Cyl. 5V Turbo OBD II Engine Mechanical 19 Engine-Cooling system (Page GR-19) 19 Engine-Cooling system (Page GR-19) Cooling system components, removing and installing Continued coolant circulation pump (V51), checking Coolant hose connection diagram Coolant pump, removing and installing

More information

Mitsubishi. VFD Manuals

Mitsubishi. VFD Manuals Mitsubishi VFD Manuals Mitsubishi D700 VFD Installation Mitsubishi FR-D700 VFD User Manual Mitsubishi D700 Parallel Braking Resistors VFD Wiring Diagram - Apollo Mitsubishi VFD to Interpreter Mitsubishi

More information

Table of Contents 1. OVERVIEW OPERATION FUNCTION SPECIFICATIONS INSTRUMENT LAYOUT INSTALLATION...

Table of Contents 1. OVERVIEW OPERATION FUNCTION SPECIFICATIONS INSTRUMENT LAYOUT INSTALLATION... Table of Contents 1. OVERVIEW... 2 2. OPERATION FUNCTION... 2 3. SPECIFICATIONS... 3 4. INSTRUM LAYOUT... 4 4.1 OPERATION KEY...4 4.2 INDICATORS...4 5. INSTALLATION... 5 5.1. ENVIRONM CONDITIONS...5 5.2

More information

Hydrovar and Packaged Hydrovar

Hydrovar and Packaged Hydrovar Hydrovar and Packaged Hydrovar MOTOR MOUNT VARIABLE SPEED PUMP CONTROLLER AND INTEGRATED PUMP PACKAGES BRHYDROVAR R3 Goulds Water Technology Hydrovar and Packaged Hydrovar Hydrovar Variable Speed Drives

More information

Udiag BST300 Battery Tester User Manual

Udiag BST300 Battery Tester User Manual Udiag BST300 Battery Tester User Manual www.udiagtech.com Content 1 Introduction... 3 1.1 Product Introduction... 3 1.2 Specification... 3 1.3 Product Function... 3 2 Operating Instruction... 4 2.1 Battery

More information

OPERATING INSTRUCTIONS AND SYSTEM DESCRIPTION FOR THE TC-10 TEMPERATURE CONTROL SYSTEM

OPERATING INSTRUCTIONS AND SYSTEM DESCRIPTION FOR THE TC-10 TEMPERATURE CONTROL SYSTEM OPERATING INSTRUCTIONS AND SYSTEM DESCRIPTION FOR THE TC-10 TEMPERATURE CONTROL SYSTEM VERSION 3.9 npi 2018 npi electronic GmbH, Bauhofring 16, D-71732 Tamm, Germany Phone +49 (0)7141-9730230; Fax: +49

More information

Technical Specifications. Sentinel PRO 700 VA up to 3000 VA 1000 VA ER-2200 VA ER-3300 VA ER

Technical Specifications. Sentinel PRO 700 VA up to 3000 VA 1000 VA ER-2200 VA ER-3300 VA ER Technical Specifications Sentinel PRO 700 VA up to 3000 VA 1000 VA ER-2200 VA ER-3300 VA ER Sentinel PRO CONTENTS 1. GENERAL DESCRIPTION... 2 1.1. Main features of the UPS unit... 3 1.2. Standard Versions...

More information

ErP METAL TUBE FANS - ROPERA EC FEATURES ELECTRICAL SUPPLY TEMPERATURE RANGE SIZES FEATURES AND CONSTRUCTION PRODUCT CODE INSTALLATION

ErP METAL TUBE FANS - ROPERA EC FEATURES ELECTRICAL SUPPLY TEMPERATURE RANGE SIZES FEATURES AND CONSTRUCTION PRODUCT CODE INSTALLATION 95 METAL TUBE FANS - ROPERA EC FEATURES mm to 355 mm diameter Air flow up to.56 m 3 /s Static pressures up to 7 Pa Casing - galvanized sheet steel Backward curved impeller Easy electrical connection via

More information

BRIVIS DUCTED INVERTER SERVICE MANUAL DRCi

BRIVIS DUCTED INVERTER SERVICE MANUAL DRCi BRIVIS DUCTED INVERTER SERVICE MANUAL DRCi 1 TABLE OF CONTENTS TABLE OF CONTENTS... 2 IMPORTANT NOTE... 3 FAULT FINDING AND DIAGNOSTICS... 3 ABBREVIATIONS... 3 PCB S... 4 OUTDOOR MAIN PCB... 4 INDOOR PCB...

More information

Table of Contents. Chapter 1 Product Summary... 2

Table of Contents. Chapter 1 Product Summary... 2 Table of Contents Chapter 1 Product Summary... 2 1.1 Product Profile... 2 1.2 Product Function... 2 1.3 Technical Parameters... 2 1.4 Working Environment Requirement... 3 Chapter 2 Tester Structure...

More information

8 Troubleshooting and Maintenance

8 Troubleshooting and Maintenance 8 Troubleshooting and Maintenance 8.1 Troubleshooting 8.1.1 Troubleshooting of LED Indicators See Tab. 7-4 State Descriptions of LED Indicators for the definition. Fault Type LED indicators and LCD screen

More information

Manual for Inverter system type PCI05

Manual for Inverter system type PCI05 - 1- Manual for Inverter system type PCI05 SAFETY INSTRUCTIONS This manual must be read before installation, use or work on the product. This product contains dangerous voltages that when touched can cause

More information

FTS420 USER INSTRUCTION MANUAL

FTS420 USER INSTRUCTION MANUAL DC TO AC POWER INVERTER FTS420 USER INSTRUCTION MANUAL Applicable for: 420W User s Manual. Description: Power Inverter is a kind of products which change the DC electricity to AC electricity then offer

More information

KCR1. Kiln Controller Handbook. Kilncare Ltd. The Kiln Works 907 Leek New Road Baddeley Green Stoke-on-Trent Staffordshire, ST2 7HQ United Kingdom

KCR1. Kiln Controller Handbook. Kilncare Ltd. The Kiln Works 907 Leek New Road Baddeley Green Stoke-on-Trent Staffordshire, ST2 7HQ United Kingdom KCR1 Kiln Controller Handbook Issue: a b Date: 04Sep2008 05Sep2008 Kilncare Ltd. The Kiln Works 907 Leek New Road Baddeley Green Stoke-on-Trent Staffordshire, ST2 7HQ United Kingdom Tel: 01782 535915 Tel:

More information

DOUBLE SKIN MODULAR AIR HANDLING UNIT. Round Edge (ADM-AHU)

DOUBLE SKIN MODULAR AIR HANDLING UNIT. Round Edge (ADM-AHU) DOUBLE SKIN MODULAR AIR HANDLING UNIT Round Edge (ADM-AHU) AIR HANDLING UNIT Acson Double Skin Modular Air Handling Unit is designed based on a modular concept, making it suitable for breaking down into

More information