Instructions for the BCEA Rotary heat exchanger

Size: px
Start display at page:

Download "Instructions for the BCEA Rotary heat exchanger"

Transcription

1 Instructions for the Rotary heat exchanger 1. General The heat recovery section is a rotary heat exchanger with high temperature and humidification efficiencies. The heat exchanger operates with an efficiency of up to 82% on equal supply air and exhaust air flows. The efficiency is regulated by varying the rpm of the rotor. The drive motor is supplied for constant speed or variable speed control. 2. Installation 2.1 Mounting Make sure that you connect each duct connection of the unit to the appropriate duct or passage of the adjacent functional unit section. 2.2 Filter Make sure that the filters have been installed before starting the air handling unit. 2.3 Purging sector The heat exchanger is supplied as standard with an adjustable purging sector. The purging sector is factory-preset in the max. position and can be set to the appropriate angle setting at the site, contingent on the differential pressure between P1 and P3, See the following figure and Table 1 to the right. The airflow through a correctly adjusted purging sector can be read in Table 2 and 3. Extract air Outdoor air Index, Connection Points. Exhaust air Supply air Table 1 Pressure Angle differential ( ) P 1 P 3 (Pa) Table 2 High efficiency 250 mm deep rotor Table 3 Standard efficiency 200 mm deep rotor Air flow through purging sector, (m 3 /s) Air flow through purging sector, (m 3 /s) 004 0, , , , , , , ,07 Specifications are subject to alteration without notice. 1

2 2.4 Commissioning Direction of rotation Before starting the heat exchanger, slip off its drive belt and run the motor briefly to check that it is rotating in the direction indicated by the arrow on the casing. If it is rotating in the wrong direction, move lead 2A to 2B or vice versa Variable speed control If the heat exchanger is equipped with speed control, the rotor speed will vary steplessly from approx rpm to rpm depending on the size of heat exchanger. The cubicle containing the automated equipment for speed control, purging operation, etc. is mounted on the drive motor. For electrical wiring details, see Section 5.1 (Control of the motors, variable speed) and Section 5.2 (Control of the motors, constant speed) To adjust the purging sector a) Remove the tape (1) over the groove of the stop screw. b) Back off the stop screw (2). c) Slide the sector plate (3) upward to the desired position. d) Retighten the set screw (2). e) Apply new fabric tape to seal the groove of the set screw. 3. Maintenance 3.1 Cleaning Inspect the heat exchanger at least every six months and clean if necessary. Cleaning is permissible only by means of vacuum-cleaning with a soft nozzle or blowing with compressed air. The rotor bearings are maintenance-free. 3.2 Bristled seal While cleaning, check that there is no play between the rotor and the bristled seal. If the seal is worn, it should be replaced. If the bristled seal of the rotor has been removed and is to be reused, it is important that you refit it with the bristles leaning toward the direction of rotation. The bristles adapt themselves to a nap that suits one direction of rotation. This direction should not be reversed afterward. After you have replaced or adjusted the rotor seal, the heat exchanger should be run for 30 minutes to allow the seal to adapt to the rotor surface. The brush seal must not be hard up against the rotor, causing it to turn sluggishly. 4. Technical data 4.1 Motor data Rated output (kw) Current at the rated output 0,04 0,45 A, 1-fas 230V 2 Specifications are subject to alteration without notice.

3 5. Electrical Wiring 5.1 Speed Control of the Rotary Heat Exchanger Motor. Variable Speed Control, Part No General The speed controller is mounted in a plastic enclosure with factory-fitted grommets for the various cables and a transparent cover. The control system is fitted inside the casing of the rotary heat exchanger and controls a heat exchanger motor of Japan Servo manufacture, with tachometer generator. Output range: 25 70W. The controller variably regulates the speed of the heat exchanger motor between 70 and 1400 rpm. The standard transmission ratio will enable a rotor speed range from approx rpm to rpm depending on the size of heat exchanger. Performance is controlled by switching in and out of the "standby mode" and a control signal. The controller regulates the motor rpm in a capacity-linear manner in proportion to the input signal. Thus the speed change, per volt of signal change, will be slight for input signals less than 50% and great for those more than 50%. A rotation monitor and a purging operation function are incorporated into the controller. Alarms are indicated by a red LED and group alarms are initiated by means of alternating potential-free contact. Electrical installation (See the diagram below.) Power supply cable: 3 x 1.5, voltage: 230 V +/-10%, 50/60Hz. Control cable from the logic equipment cubicle for: Stand-by mode from potential-free contacts. Control signal: 0 10 V DC, 2 10 V DC, 0 20 ma or 4 20 ma for speed control. Group alarm function output, if specified. Separate alarm cable, if specified. The motor cable and rotation monitor sensor cable are factoryconnected if the controller is supplied with the heat exchanger. Setting The only setting that need be made is selecting the type of control signal. This can be set by means of the dip switch (see figure to the right) on the circuit board. Functions 1 0 ON V DC V DC ma ma 1 1 Stand-by mode: Closure between terminals 16 and 17 puts the controller on stand-by. The motor will start when the control signal exceeds 10%. Beyond that point, the speed will variably follow the control signal in a capacity-linear manner up to max. motor rpm. Start function: On closure of the stand-by mode contacts, the heat exchanger will operate at max. rpm for one minute and then adjust itself to the speed called for by the control signal. The start function will switch in regardless of whether or not a control signal is present. The purpose of this function is to counteract any shocking chill when the air handling unit is started up. Control signal: The speed of the heat exchanger motor is controlled in a capacity-linear manner between min. and max speeds ( rpm). If the control signal is less than 10% of the max. input signal, the exchanger motor will not start. If the signal is at 10%, the motor will run at min. rpm. On a control signal of 100%, the motor will run at max. rpm. Purging operation: If the controller has been in the stand-by mode for 4 hours and during that time the control signal has not exceeded the 10% limit, the heat exchanger will start up and run at max. rpm for 1 minute to purge the rotor and rid its passages of contaminants. Rotation monitor: The rotation monitor sensor transmits an impulse to the controller every time the magnet on the heat exchanger rotor passes it. If the sensor has not sensed any impulse within 4 minutes while the control signal is above 10%, the heat exchanger motor will stop and the rotation monitor alarm will trip. Tacho-monitor: The controller senses the rpm of the heat exchanger rotor across the input from the tacho-generator mounted on the motor. If no impulses are obtained 10 seconds after the output voltage has reached max., the heat exchanger motor will stop and the tacho-monitor Specifications are subject to alteration without notice. 3

4 Alarms Rotation monitor: The alarm will trip after 4 minutes if no pulse has been received from the rotation monitor sensor during this period even though the control signal exceeds10%. The red LED (LD3) steadily shines and the yellow LED (LD4) flashes. The alarm relay is closed between terminals 9 and 11. Tacho-monitor: The alarm will trip if no pulse has been obtained from the tacho-generator 10 seconds after the output voltage has reached max. The red LED (LD3) steadily shines and the yellow LED (LD4) is off. The alarm relay is closed between terminals 9 and 11. Power failure: None of the LEDs are lit. The alarm relay is closed between terminals 9 and 11. To reset the alarms The alarms can be reset by switching off the stand-by mode or power supply and then switching it back on. If the LON is connected, resetting can be done across the LON network. The LEDs Yellow LED: LD1. No used. Green LED: LD2. Steadily shines while the controller is on stand-by. Closure between terminals 16 and 17. Red LED: LD3. Steadily shines if any alarm has tripped. Red LED in combination with yellow LED (LD4) indicates which alarm has tripped. Rotation monitor alarm: Red LED steadily shines yellow LED flashes. Tacho-monitor alarm: Red LED steadily shines yellow LED is off. Yellow LED: LD4. Steadily shines if the input signal is greater than 10% and the heat exchanger motor is to rotate. The LED will blink off 1 second and on, every time the magnet on the rotor passes the rotation monitor sensor. A yellow LED in combination with a red LED (LD3) indicates which alarm has tripped. 5.2 Speed Control of the Rotary Heat Exchanger Motor. Constant Speed, Part No General The speed controller is located in a cubicle in the casing of the heat exchanger. The controller has a built-in thermostat that switches the rotary heat exchanger in and out. The temperature is registered in the outdoor air intake section of the unit. The controller can be switched on standby and off by means of external, potential-free contact. It has a built-in rotation monitor and purging function. Group alarm output via alternating, potential-free contact. Electrical wiring (See the figure to right and below.) The terminal block is of springaction type without any tightening screw. Connect to a 230 V AC ±10%, 50 Hz power supply. Connect the control cable from the logic equipment cubicle for: standby from potential-free contact, output group alarm function. Motor cable, sensor cable for the speed monitor and the temperature sensor cable are factory-wired. Technical data Mains power supply 230 V +/- 10%, 50/60 Hz Power supply fuse..... Min. 2AT, max. 10 AT Ambient temperature C through +50 C Enclosure dimensions.. W x H x D = 230 x 80 x 65 mm Degree of protection.... IP 54 Alarm relay. Max. 250 V AC, 2 AT Fuse at motor output. Fine wire fuse 20 x 5 mm, 2 AT Rotation monitor sensor Part. no Setting Potentiometer P1 can be set for switching off the heat exchanger at the desired temperature. Factory setting:15 C. Potentiometer P2 can be set to the appropriate switch-on and switch-off differential. Factory setting: 0.25 C. Start/Stopp temp 0±30 C P1 Drift Stopp Differens 0,25±4,0 C P2 P1 P2 t C 4 Specifications are subject to alteration without notice.

5 Functions Operational readiness: When the potential-free contacts are closed, the controller is ready for operation. If the contacts are opened, the motor will stop and the alarm and purging operation will be blocked. Control: The heat exchanger will be switched off if a rising outdoor temperature is registered by the temperature sensor in the outdoor air intake section of the air handling unit. The switch-off temperature can be reset on potentiometer P1. The difference between the switch-off and switch-on temperatures can be preset on potentiometer P2. Rotation monitor: The controller receives a pulse every time the magnet on the rotor periphery passes the sensor. If the temperature is lower than the preset switch-off value (P1), and the pulses have ceased for more than 5 min., the controller will switch out the heat exchanger and an alarm will be initiated. Purging operation: If the controller has been ready for operation for 4 hours, and the outdoor temperature has been higher than the switch-off value that has been preset on P1, the heat exchanger will start up and run at full speed for one minute to purge the rotor surfaces clean of dust. To check the purging operation function: If the outdoor temperature is higher than the switch-off value preset on P1 at the time that the power supply is switched on, purging operation will start after 30 seconds. Alarms Rotation monitor: An alarm with flashing red LED (lit 75% of one second) will appear if pulses from the rotation monitor sensor cease for more than 5 minutes. The alarm relay will alternate. Sensor error: An alarm with flashing red LED (lit 25% of one second) if pulse transmission is interrupted or if the conductor from the sensor is short-circuited. Power failure: The alarm relay alternates. To reset alarms: Alarms can be reset by opening and closing the standby contacts or by briefly opening the mains power supply. LEDs Green LED: Steadily shines when the unit is ready for operation. Yellow LED: Steadily shines if the outdoor temperature is lower than the switch-off value preset on potentiometer P1. The LED is off for one second every time the rotation monitor sensor receives an impulse. Red LED: Flashes (lit 75% of one second) if the thermostat calls for rotor operation and pulses from the rotation monitor sensor cease for more than 5 minutes. Flashes (lit 25% of one second) if pulse transmission is interrupted or if the conductor from the sensor is shortcircuited. Technical data mains power supply 230 V AC ±10%, 50 Hz Fuse - power supply 10A Operating temperature 20 till +50 C Dimensions of the enclosure B x H x D = 230 x 80 x 65 mm Degree of protection IP54 Alarm relay Potential-free, alternating 250 V AC 10A Fuse motor output Fine-wire fuse, 20 x 5 mm, 1.25 AT Specifications are subject to alteration without notice. 5

Instructions for the BASIC BCVA Rotary heat exchanger, Sizes

Instructions for the BASIC BCVA Rotary heat exchanger, Sizes Instructions for the BASIC BCVA Rotary heat exchanger, Sizes 080 120 1. General The BCVA heat recovery unit is a rotary heat exchanger that offers high temperature efficiency. The heat exchanger operates

More information

PUR (A, B, C, D) INSTRUCTION FOR VARIABLE SPEED WITH WIRING DIAGRAM FOR EMX P10 ROTOR SIZE

PUR (A, B, C, D) INSTRUCTION FOR VARIABLE SPEED WITH WIRING DIAGRAM FOR EMX P10 ROTOR SIZE PUR (A, B, C, D) INSTRUCTI FOR VARIABLE SPEED WITH WIRING DIAGRAM FOR EMX P10 ROTOR SIZE 030 089 2 Installation and commissioning VARIABLE SPEED DESCRIPTI, CTROL CTENTS Safety instructions/scrapping...

More information

Technical data. WARNING! Residual voltage is present for 1 minute after disconnecting mains voltage.

Technical data. WARNING! Residual voltage is present for 1 minute after disconnecting mains voltage. INSTALLATI Speed-controlled drive system manufacturer EMS Model Units included S for rotary heat exchanger EURA, size 20 60. Page Content 1 Technical data 1 Units included............motor, Control unit

More information

ROTARY HEAT EXCHANGER EQRB

ROTARY HEAT EXCHANGER EQRB ROTARY HEAT EXCHANGER EQRB INSTALLATI AND MAINTENANCE INSTRUCTIS INSTALLATIS INSTRUCTI, DRIVE SYSTEM EMX-R, EQRB SIZE 020-090 SAFETY INSTRUCTIS IMPORTANT! During installation Read the instruction manual

More information

PUR (A, B, C, D) INSTRUCTION FOR VARIABLE SPEED WITH WIRING DIAGRAM, EMX-R ROTOR SIZE TECHNICAL DATA

PUR (A, B, C, D) INSTRUCTION FOR VARIABLE SPEED WITH WIRING DIAGRAM, EMX-R ROTOR SIZE TECHNICAL DATA PUR (A, B, C, D) INSTRUCTI FOR VARIABLE SPEED WITH WIRING DIAGRAM, EMX-R ROTOR SIZE 125-250 TECHNICAL DATA 2 Installation and commissioning Content Page General description... 3 Control- and operation

More information

RE-PR3-E-86&105 3-Phase Panel Mount 86 and 105kW

RE-PR3-E-86&105 3-Phase Panel Mount 86 and 105kW Page 1 of 6 3-Phase Panel Mount 86 and 105kW Features: Benefits: 0-10Vdc, 0-5Vdc, 4-20mA or manual via potentiometer control input Over temperature protection with auto reset Enclosed panel mounting Efficient

More information

Installation Instructions, TBLZ-1-23-aa Pressure Transducer GOLD/COMPACT/MIRUVENT

Installation Instructions, TBLZ-1-23-aa Pressure Transducer GOLD/COMPACT/MIRUVENT Installation Instructions, TBLZ-1-23-aa Pressure Transducer GOLD/COMPACT/MIRUVENT 1. General The pressure transducer is designed for use in ventilation systems intended for variable flow by keeping the

More information

IBC control. MicroMax MANUAL. With adjustable boost function and threshold value. Since Set of EMC-glands as an option

IBC control. MicroMax MANUAL. With adjustable boost function and threshold value. Since Set of EMC-glands as an option Made in Since 1983 S w e d e n MANUAL Set of EMC-glands as an option CONTROL UNIT FOR ROTARY HEAT EXCHANGER MicroMax Article no. F21009301 With adjustable boost function and threshold value IBC control

More information

ECONOVENT Rotary heat exchanger Instruction for variable speed EMX-R PUM with wiring diagram

ECONOVENT Rotary heat exchanger Instruction for variable speed EMX-R PUM with wiring diagram ECOVENT Rotary heat exchanger Instruction for variable speed EMX-R PUM 060-340 with wiring diagram Contents Variable speed PUM 060 340 General information...............................................

More information

Starting System DS-102 Series 200. Elmatik AS P.O.Box 309 NO-3471, Slemmestad T F

Starting System DS-102 Series 200. Elmatik AS P.O.Box 309 NO-3471, Slemmestad T F Starting System DS-102 Series 200 Elmatik AS P.O.Box 309 NO-3471, Slemmestad T - +47 31 28 37 83 F - +47 31 28 37 93 www.elmatik.no post@elmatik.no CONTENT 1. INTRODUCTION 3 2. TECHNICAL SPECIFICATIONS

More information

PURA INSTALLATION AND MAINTENANCE INSTRUCTION

PURA INSTALLATION AND MAINTENANCE INSTRUCTION PURA INSTALLATION AND MAINTENANCE INSTRUCTION 2 Installation and maintenance Content Page Delivery Version PURA... 3 Handling, Loads on the Unit, Inspection Facilities... 4 Connection, Checks, Rotor Seals...

More information

Differential Pressure Transmitter

Differential Pressure Transmitter Specifications/Instructions Differential Pressure Transmitter General Model PY9000D is a differential pressure transmitter that uses a ceramic cantilever sensor. Deflection of the ceramic cantilever caused

More information

INFRESCO 2KW VARIABLE CONTROLLER Issue 3

INFRESCO 2KW VARIABLE CONTROLLER Issue 3 X20018 INFRESCO 2KW VARIABLE CONTROLLER Issue 3 infresco User Manual Date 19/08/14 Page 1 of 6 KEY FEATURES Soft Start up to 30% extended life of Lamp Variable Control Ability to find comfort level Simple

More information

DEVICE STATE/BYPASSED FAILURE OVERLOAD

DEVICE STATE/BYPASSED FAILURE OVERLOAD Technical specifications Type 5. 7. Control electronics Rated values Terminal Rated control supply voltage A1A2 V AC 115 230 115 230 Tolerance % -15+10-15+10 Rated control supply STANDBY ma 15 15 Rated

More information

MODEL 520 REMOTE START ENGINE MANAGEMENT SYSTEM

MODEL 520 REMOTE START ENGINE MANAGEMENT SYSTEM MODEL 520 REMOTE START ENGINE MANAGEMENT SYSTEM DSE 520 ISSUE 4 4/4/02 MR 1 TABLE OF CONTENTS Section Page INTRODUCTION... 4 CLARIFICATION OF NOTATION USED WITHIN THIS PUBLICATION.... 4 1. OPERATION...

More information

RE-PR1-F 1-Phase Din-Rail Mount 1.5, 3 & 6kW

RE-PR1-F 1-Phase Din-Rail Mount 1.5, 3 & 6kW Page 1 of 5 RE-PR1-F 1-Phase Din-Rail Mount 1.5, 3 & Features: Benefits: 0-10Vdc or 0-5Vdc control input Over temperature protection with auto reset Din-rail mounting Efficient electronic switching No

More information

MANUAL CONTROL UNIT FOR ROTATING HEAT EXCHANGER. MicroMax. Article no. F IBC control Made in Sweden

MANUAL CONTROL UNIT FOR ROTATING HEAT EXCHANGER. MicroMax. Article no. F IBC control Made in Sweden MANUAL CONTROL UNIT FOR ROTATING HEAT EXCHANGER MicroMax Article no. F21009201 IBC control Made in Sweden TABLE OF CONTENTS Installation instructions 2 Mounting 2 Safety instructions 3 Manufacturer's

More information

HP21 SERVICE SUPPLEMENT UNIT INFORMATION. TSC6 Two-Speed Control

HP21 SERVICE SUPPLEMENT UNIT INFORMATION. TSC6 Two-Speed Control SERVICE UNIT INFORMATION SUPPLEMENT HP21 Corp. 9426 L10 Litho U.S.A. All HP21-4 and -5 units (single and three phase) are equipped with a TSC6 two-speed control. The TSC6 (A14) two-speed control contains

More information

Fire Fighting Diesel Pump Control Panel in Compliance with EN Standard User Manual

Fire Fighting Diesel Pump Control Panel in Compliance with EN Standard User Manual Fire Fighting Diesel Pump Control Panel in Compliance with EN 12845 Standard User Manual Electronic Control Panel Display Panel door-lock Control Buttons Siren Figure 1. Diesel Control Panel - External

More information

MANUAL. MiniMax V / VK

MANUAL. MiniMax V / VK MANUAL CONTROL UNIT FOR ROTATING HEAT EXCHANGER MiniMax V / VK Revised 2014-10-07 Version 1.3.1 F21037901GB Declaration of Manufacturer The manufacturer s assurance of the agreement of the product with

More information

ECONOVENT PUM Installation and maintenance instructions for rotary heat exchangers

ECONOVENT PUM Installation and maintenance instructions for rotary heat exchangers Plant: Heat exchanger designation: ECONOVENT PUM Installation and maintenance instructions for rotary heat exchangers Contents Design, Condition on delivery........................................3 Handling,

More information

Installation Instructions, TBLZ-1-23-aa Pressure Transducer GOLD/COMPACT/MIRUVENT

Installation Instructions, TBLZ-1-23-aa Pressure Transducer GOLD/COMPACT/MIRUVENT Installation Instructions, TBLZ-1-23-aa Pressure Transducer GOLD/COMPACT/MIRUVENT 1. General The pressure transducer is designed for use in ventilation systems intended for variable flow by keeping the

More information

Advantage-D. Operating Instructions and Maintenance Manual. Central Vacuum Systems (Expandable/Modular Models) (Ver.

Advantage-D. Operating Instructions and Maintenance Manual. Central Vacuum Systems (Expandable/Modular Models) (Ver. Advantage-D Series 3 Central Vacuum Systems (Expandable/Modular Models) (Ver. 8/05) Operating Instructions and Maintenance Manual DESCRIPTION The Becker Advantage-D and Advantage-L central vacuum systems

More information

Burden Fuse Rating Resistor SAF / SAK6 1NM 10mm M8 12NM SAF / SAK10 2NM 16mm M8 12NM

Burden Fuse Rating Resistor SAF / SAK6 1NM 10mm M8 12NM SAF / SAK10 2NM 16mm M8 12NM Contents Section Page 1.0 Introduction 1 2.0 Specification 1-4 3.0 Installation 5-8 4.0 Programming 9-10 5.0 Menus 10-12 6.0 Fault Finding/Diagnostics 12-13 7.0 Communication 13 8.0 Setting Up 13-16 1.0

More information

DC-Motor Controller. User Manual

DC-Motor Controller. User Manual Jægergårdsgade 152/05A DK-8000 Aarhus C DENMARK WWW.WAHLBERG.DK Forside DC-Motor Controller User Manual Firmware V4.00 Product content 1 Controller box - for controlling a DC-motor. 1 PowerCON TRUE1 female

More information

MANUAL CONTROL UNIT FOR ROTATING HEAT EXCHANGERS. MicroStart. IBC control

MANUAL CONTROL UNIT FOR ROTATING HEAT EXCHANGERS. MicroStart. IBC control MANUAL CONTROL UNIT FOR ROTATING HEAT EXCHANGERS MicroStart IBC control PAGE REFERENCE Functional description 1 Technical data 2 Functions 2-3 - Push-button - DIP-switches - Operation indications - Alarm

More information

EPS/ELA-Series User Manual EPS/ELA 250W

EPS/ELA-Series User Manual EPS/ELA 250W EPS/ELA-Series User Manual EPS/ELA 250W EPS Stromversorgung GmbH Tel: +49 (0)821 570451 0 Index 3 Page: 1 Table of contents: Page 1. Features of ELA-Series... 3 1.1 Basic Functions... 3 1.2 Options...

More information

SDS Enclosed Star-Delta Starter User Guide

SDS Enclosed Star-Delta Starter User Guide SDS Enclosed Star-Delta Starter User Guide (7.5kW~90kW) V2.0.0 PLEASE NOTE: AS STANDARD AND UNLESS OTHERWISE SPECIFIED, THIS PRODUCT IS EQUIPPED WITH A BASIC LOW INTEGRITY EMERGENCY STOP CIRCUIT STOPPING

More information

WALL MOUNTED type SPLIT TYPE ROOM AIR CONDITIONER. Models

WALL MOUNTED type SPLIT TYPE ROOM AIR CONDITIONER. Models SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTED type Models Indoor unit ASH9LSACW ASH12LSACW Outdoor unit AOH9LSAC AOH12LSAC CONTENTS SPECIFICATIONS...................... 1 DIMENSIONS..........................

More information

VEGAMET 307 / 308. TIB Technical Information Operating Instructions VEGAMET 308. Signal conditioning instrument. for continuous level measurement

VEGAMET 307 / 308. TIB Technical Information Operating Instructions VEGAMET 308. Signal conditioning instrument. for continuous level measurement VEGAMET 37 / 38 TIB Technical Information Operating Instructions Signal conditioning instrument for continuous level measurement 2 4 6 8 1 for connection of a capacitive measuring electrode or a pressure

More information

Modulating Furnace Information. Warning on Meter Setting - Read First!

Modulating Furnace Information. Warning on Meter Setting - Read First! Modulating Furnace Information Pressure Transducer Pressure DC Volts 0.00" 0.25 0.20" 0.63 0.25" 0.72 0.30" 0.82 0.35" 0.91 0.40" 1.00 0.45" 1.09 0.50" 1.19 0.55" 1.28 0.60" 1.38 0.65" 1.47 0.70" 1.56

More information

Truck and Transport IP Red Seal Practice Exam PRACTICE EXAM 4

Truck and Transport IP Red Seal Practice Exam PRACTICE EXAM 4 Truck and Transport IP Red Seal Practice Exam PRACTICE EXAM 4 1. Which of these sensors directly measures engine load? a. Manifold absolute pressure sensor. b. Coolant sensor (ECT). c. Vehicle speed sensor.

More information

Pressure chlorine changeover unit C 7520

Pressure chlorine changeover unit C 7520 BW 2 24 04 / 1 Content 1. Scope of delivery 2. Device description 3. Installation 4. Operation 5. Shutdown 6. Maintenance 7. Troubleshooting 1 Scope of delivery The chlorine gas changeover unit C 7520

More information

Sky Wing. Contents. Power Roof Ventilator

Sky Wing. Contents. Power Roof Ventilator Power Roof Ventilator Contents Quick Guide... 14 General, Advantages of the... 15 Specification... 16 Technical Description of the... 17 LTSA Roof duct... 19 Electrical and Control Equipment, Control Functions...

More information

INSTRUCTION MANUAL ACTUATOR CLASSE I TYPE MA, MB

INSTRUCTION MANUAL ACTUATOR CLASSE I TYPE MA, MB ACTUATOR CLASSE I TYPE MA, MB CONTENTS Page : 2/13 PRODUCT DESCRIPTION General description 3 Product specification 5 INSTALLATION Storage 6 Unpacking 7 Handling 7 Installation : Mechanical 7 Installation

More information

User manual MTS-32. QUI-1013 Version 1.5 January

User manual MTS-32. QUI-1013 Version 1.5 January Version 1.5 January 2015 User manual MTS-32 Page 2 Contents 1. Introduction... 3 2. Principles of operation... 3 2.1 Principles of MTS-32 ventilation... 3 2.2 Principles of sorbent tube sample collection

More information

CONTROL UNITS VEHICLE EXHAUST GASES. Pure advantages

CONTROL UNITS VEHICLE EXHAUST GASES. Pure advantages CONTROL UNITS VEHICLE EXHAUST GASES Movex s control s offers a good working environment, adapted to all types of facilities. The right choice of control s is energy-saving and provides the lowest possible

More information

Open Chassis Star-Delta Starter User Guide

Open Chassis Star-Delta Starter User Guide Open Chassis Star-Delta Starter User Guide (7.5kW~90kW) V2.0.1 Contents 1 Safety information... 1 2 Technical Data... 2 3 Supply & Motor Connections & Circuit Diagrams... 5 4 Control Connections & Operation...

More information

DUST ALERT BinMaster Price Book binmaster.com Subject to change without notice 1

DUST ALERT BinMaster Price Book binmaster.com Subject to change without notice 1 DUST ALERT - 3000 BinMaster Price Book 01-2019 binmaster.com Subject to change without notice 1 DUST ALERT - 3000 Dust Alert - 3000 The Dust Alert with integrated electronics and sensing probe utilizes

More information

Installation Instructions Spector compact Conductivity Transmitter System LRGT 16-1

Installation Instructions Spector compact Conductivity Transmitter System LRGT 16-1 Installation Instructions 810701-00 Spector compact Conductivity Transmitter System LRGT 16-1 IMPORTANT NOTES...4 SAFETY NOTES...4 Danger...4 EXPLANATORY NOTES...4 Scope of supply...4 System description...4

More information

Rotary heat exchanger EURA, 20 53

Rotary heat exchanger EURA, 20 53 Rotary heat exchanger EURA, 0 5 Fig. Adjustment At a constant speed, check that the rotor is rotating in the right direction. The direction of rotation is indicated on the casing. If the purging sector

More information

VA-908x Series Electric Rotary Actuators for Two-Position and Modulating Service

VA-908x Series Electric Rotary Actuators for Two-Position and Modulating Service VA-908x Series Electric Rotary Actuators for Two-Position and Modulating Service Installation Instructions VA-908x Code No. LIT-12011566 Issued August 24, 2009 Applications The VA-908x Series Electric

More information

Start-up instructions

Start-up instructions E l e k t r o n i k s y s t e m e G m b H Development and production of electronical systems Eichelreuth 13 Phone: +49 8641 598360 83224 Grassau Fax: +49 8641 598364 E-Mail: info@rs-steiner.com Internet:

More information

Tecomotive - tinycwa User Manual

Tecomotive - tinycwa User Manual Tecomotive - tinycwa User Manual Overview Contents - tinycwa controller - Fuse holder - Fuses (15A/30A) - Connector 8 pin (controller) - Connector 4 pin (water pump) - Connector 2 pin (temperature sensor)

More information

Application Engineering

Application Engineering Application Engineering February, 2009 Copeland Digital Compressor Controller Introduction The Digital Compressor Controller is the electronics interface between the Copeland Scroll Digital Compressor

More information

SBC V In-Car Charger Dual Input (Solar MPPT & DC)

SBC V In-Car Charger Dual Input (Solar MPPT & DC) SBC-5926 12V In-Car Charger Dual Input (Solar MPPT & DC) Operation manual Keep this manual in a safe place for quick reference at all times. This manual contains important safety and operation instructions

More information

OPERATING INSTRUCTIONS

OPERATING INSTRUCTIONS Series II OPERATING INSTRUCTIONS and MAINTENANCE MANUAL TANK MOUNTED DUPLEX MODELS (Version 5/99) CENTRAL VACUUM SYSTEMS DESCRIPTION The Becker Advantage-D and Advantage-L central vacuum systems are available

More information

RVP-R- VAV controller. In explosion-proof version

RVP-R- VAV controller. In explosion-proof version VAV controller In explosion-proof version RVP-R- SMAY LLC / 29 Ciep³ownicza St. / 31-587 Cracow / Poland tel. +48 12 378 18 00 / fax. +48 12 378 18 88 / e-mail: info@smay.eu Intended use VAV control units

More information

PUM(O,R,V) AND PUML INSTALLATION AND MAINTENANCE INSTRUCTIONS FOR ROTARY HEAT EXCHANGERS ROTOR SIZE (460/500)

PUM(O,R,V) AND PUML INSTALLATION AND MAINTENANCE INSTRUCTIONS FOR ROTARY HEAT EXCHANGERS ROTOR SIZE (460/500) PUM(O,R,V) AND PUML INSTALLATION AND MAINTENANCE INSTRUCTIONS FOR ROTARY HEAT EXCHANGERS ROTOR SIZE 060 420 (460/500) 2 Installation and maintenance Content Page 1. Description - Unit design... 3 2. Handling

More information

VALVE CONTROLLERS Controllers for Dust Extr 2010 / 2011 action Technology

VALVE CONTROLLERS Controllers for Dust Extr 2010 / 2011 action Technology VALVE CONTROLLERS Controllers for Dust Extraction 2010 Technology / 2011 Valve controllers for all cases HESCH has the skills and technology to tackle any control task for dedusting of filter and dust

More information

ROTARY HEAT EXCHANGER

ROTARY HEAT EXCHANGER ROTARY HEAT EXCHANGER Energy Recovery Ventilation Specialist Beijing Holtop Artificial Environment Technology Co., Ltd ISO9001 CE EUROVENT COMPANY BRIEF INTRODUCTION TO COMPANY ENERGY RECOVERY VENTILATION

More information

8803214-8803999 DIODE BOARD The diode board is located inside the lower control box. D15 D8 D7 D14 D5 D13 ART_2181 J1 14 8 D9 D10 7 1 R2 R1 R3 R4 TB1 8601 D11 D3 D12 D4 D1 D2 J1 Plug Pin Identification

More information

DIODE BOARD The diode board is located inside the lower control box. D15 D8 D7 D14 D5 D13 ART_2181 J1 14 8 D9 D10 7 1 R2 R1 R3 R4 TB1 8601 D11 D3 D12 D4 D1 D2 J1 Plug Pin Identification PIN # WIRE # SIGNAL

More information

Operating Instructions Pedestrian Turnstile Type MPT 33

Operating Instructions Pedestrian Turnstile Type MPT 33 Operating Instructions Pedestrian Turnstile Type MPT 33 Contents 1. Delivery...2 2. Safety...2 3 Description and operation...3 4. Foundation...4-5 5. Assembly and installation...6-9 6. Electrical connection...10-11

More information

CI-tronic Soft Start Motor Controller Type MCI 25B with Brake

CI-tronic Soft Start Motor Controller Type MCI 25B with Brake Data sheet CI-tronic Soft Start Motor Controller Type MCI 25B with Brake MCI 25B motor controller with brake is designed for soft starting and braking of 3 phase AC motors. The digital controlled soft

More information

Tecomotive - tinycwa - User Manual Intercooler Version

Tecomotive - tinycwa - User Manual Intercooler Version Tecomotive - tinycwa - User Manual Intercooler Version Operation Overview When activated the controller is measuring the coolant temperature and the rate of increase with the connected temperature sensor.

More information

T: +44 (0) F: +44 (0) E:

T: +44 (0) F: +44 (0) E: CONTROL UNIT AE s control s offers a good working environment, adapted to all types of facilities. The right choice of control s is energy-saving and provides the lowest possible noise levels. automation

More information

Te 803 Electronic Controller. Service, Operation & Technical Information Manual

Te 803 Electronic Controller. Service, Operation & Technical Information Manual Te 803 Electronic Controller Service, Operation & Technical Information Manual WARNING! Technical descriptions and data given in this document are accurate, to the best of our knowledge, but can be subject

More information

CONTROL UNITS LOCAL EXTRACTORS LOCAL EXTRACTORS. Pure advantage

CONTROL UNITS LOCAL EXTRACTORS LOCAL EXTRACTORS. Pure advantage CONTROL UNITS LOCAL EXTRACTORS Fumex s control unit offers a good working environment, adapted to all types of facilities. The right choice of control units is also very energy-saving and provides the

More information

HIB Enclosed Inverter User Guide

HIB Enclosed Inverter User Guide HIB Enclosed Inverter User Guide (0.75kW~22kW) V1.2.0 Contents 1 Safety information...1 2 Technical Data...2 3 Motor Connection...4 4 Operation...5 5 Single phase circuit diagram...7 6 Three phase circuit

More information

Therm-L-Tec Building Systems LLC. Therm-L-Tech. Power Operated Retrofit Kit 230 VAC or 440/480 VAC 50/60 Hz Installation and Setup Manual

Therm-L-Tec Building Systems LLC. Therm-L-Tech. Power Operated Retrofit Kit 230 VAC or 440/480 VAC 50/60 Hz Installation and Setup Manual Therm-L-Tec Building Systems LLC Therm-L-Tech Power Operated Retrofit Kit 230 VAC or 440/480 VAC 50/60 Hz Installation and Setup Manual Rev. A 01/2015 Index Index 1 Electrical Requirements for Therm-L-Tec

More information

System 6000 Electropneumatic Converters for DC ranges I/P Converter Type 6102 Type 5288

System 6000 Electropneumatic Converters for DC ranges I/P Converter Type 6102 Type 5288 System 6000 Electropneumatic Converters for DC ranges I/P Converter Type 6102 Type 5288 Fig. 1 Type 6102-51 Rack-mounting Unit Fig. 2 Type 6102-52 Rack-mounting Unit Fig. 3 Type 6102-53 Field Unit Fig.

More information

Ch 4 Motor Control Devices

Ch 4 Motor Control Devices Ch 4 Motor Control Devices Part 1 Manually Operated Switches 1. List three examples of primary motor control devices. (P 66) Answer: Motor contactor, starter, and controller or anything that control the

More information

PREMIER POWER PACK INSTRUCTION MANUAL EN54-4 POWER SUPPLY UNIT INSTRUCTION MANUAL. GLT.MAN-138 Issue: /05/2016 N.R.P.J.

PREMIER POWER PACK INSTRUCTION MANUAL EN54-4 POWER SUPPLY UNIT INSTRUCTION MANUAL. GLT.MAN-138 Issue: /05/2016 N.R.P.J. EN54-4 POWER SUPPLY UNIT INSTRUCTION MANUAL GLT.MAN-138 CONTENTS Introduction to the Premier Power Pack PSU... 2 Changes to EN54-4 (The Fire Alarm Equipment Power Supply Standard)... 3 Indications... 4

More information

See «Overview of types» 90 s / 60 mm 150 s / 100 mm Manual triggering of the adaption by pressing the «Adaption» button or with the PC-Tool

See «Overview of types» 90 s / 60 mm 150 s / 100 mm Manual triggering of the adaption by pressing the «Adaption» button or with the PC-Tool echnical data sheet LHA-MF.. Multifunctional linear actuators for adjusting air dampers and slide valves in ventilation and air-conditioning systems for building services installations For air control

More information

& HIGH CURRENT DC POWER SUPPLIES INSTRUCTION MANUAL

& HIGH CURRENT DC POWER SUPPLIES INSTRUCTION MANUAL 72-6850 & 72-6852 HIGH CURRENT DC POWER SUPPLIES INSTRUCTION MANUAL Table of Contents Introduction 2 Specification 2 Safety 4 EMC 5 Installation 6 Connections 6 Operation 7 Maintenance and Repair 8 www.tenma.com

More information

Model DS1000/DT20 System

Model DS1000/DT20 System Model DS1000/DT20 System Installation, Commissioning and Operation Manual Alpha Moisture Systems Alpha House 96 City Road Bradford BD8 8ES England Tel: +44 1274 733100 Fax: +44 1274 733200 Email: mail@amsytems.co.uk

More information

SB 2000 PUSH TO SEARCH NEXT STAG E. Aerotech, Inc. FORM: QM 1320

SB 2000 PUSH TO SEARCH NEXT STAG E. Aerotech, Inc. FORM: QM 1320 Inlet Controller SB 2000 USER'S MANUAL AUTO OPEN MANUAL PUSH TO SEARCH NEXT STAG E CLOSE Aerotech, Inc. FORM: QM 1320 4215 Legion Dr. Mason, MI 48854-1036 USA Rev. 3, Sept. 1997 Ph. (517) 676-7070 Fax

More information

Troubleshooting Bosch Proportional Valves

Troubleshooting Bosch Proportional Valves Troubleshooting Bosch Proportional Valves An Informative Webinar Developed by GPM Hydraulic Consulting, Inc. Instructed By Copyright, 2009 GPM Hydraulic Consulting, Inc. TABLE OF CONTENTS Bosch Valves

More information

Eclipse Solar Suitcase

Eclipse Solar Suitcase Eclipse Solar Suitcase Renogy 100W 200W 2775 E. Philadelphia St., Ontario, CA 91761 1-800-330-8678 Version 1.0 Important Safety Instructions Please save these instructions. This manual contains important

More information

Installation and operating instructions. Solar charge controller MPPT 10 A / 20 A Z Z

Installation and operating instructions. Solar charge controller MPPT 10 A / 20 A Z Z Installation and operating instructions Solar charge controller MPPT 10 A / 20 A EN 1 Contents 1. About these instructions... 3 1.1 Applicability... 3 1.2 Users... 3 1.3 Description of symbols... 3 2.

More information

MODEL 422 Submersible Pump Controller

MODEL 422 Submersible Pump Controller MODEL 422 Submersible Pump Controller Monitors True Motor Power (volts x current x power factor) Detects Motor Overload or Underload Operates on 120 or 240VAC, Single-phase or 3-phase Built-in Trip and

More information

Accessories for Stand-alone inverter SUNNY ISLAND GENMAN

Accessories for Stand-alone inverter SUNNY ISLAND GENMAN Accessories for Stand-alone inverter SUNNY ISLAND GENMAN Technical Description GenMan-TEN082730 98-2001230 Version 3.0 EN SMA Solar Technology AG Table of Contents Table of Contents 1 Notes on this manual..............................

More information

Pure Sine Wave Inverter GP-HS1500. Owner s Manual

Pure Sine Wave Inverter GP-HS1500. Owner s Manual Pure Sine Wave Inverter GP-HS1500 Owner s Manual 2 Table of Contents Introduction 3 Specifications 4 Name and Main Function 5 Installation 7 Operation 9 Operating Limits 13 Troubleshooting 13 Maintenance

More information

CONTENTS TABLE OF CONTENTS... 1 INTRODUCTION... 2 SEC 1 - SPECIFICATIONS... 3 SEC 2 - DESCRIPTION... 5 SEC 3 - OPERATING INSTRUCTIONS...

CONTENTS TABLE OF CONTENTS... 1 INTRODUCTION... 2 SEC 1 - SPECIFICATIONS... 3 SEC 2 - DESCRIPTION... 5 SEC 3 - OPERATING INSTRUCTIONS... CONTENTS SUBJECT PAGE TABLE OF CONTENTS... 1 INTRODUCTION... 2 SEC 1 - SPECIFICATIONS... 3 SEC 2 - DESCRIPTION... 5 SEC 3 - OPERATING INSTRUCTIONS... 8 SEC 4 - BATTERY CHARGING NOTES... 9 SEC 5 - VERIFICATION

More information

Technical Data and Operating Instructions Thermal Dry Running Protection ATLS-T1

Technical Data and Operating Instructions Thermal Dry Running Protection ATLS-T1 Technical Data and Operating Instructions Thermal Dry Running Protection ATLS-T1 Operational data for thermal dry running protection according to order data sheet Order No.: Ident No. ATLS-T1: Machine

More information

World Class Power Solutions. Rectifiers. For Stationary Battery Systems in Nuclear Power Plants

World Class Power Solutions. Rectifiers. For Stationary Battery Systems in Nuclear Power Plants World Class Power Solutions Rectifiers For Stationary Battery Systems in Nuclear Power Plants General 2 1.1 Application Electronically controlled rectifier assemblies are used in conjunction with suitable

More information

Mobile recleanable HEPA filter units for a flow of m 3 / h

Mobile recleanable HEPA filter units for a flow of m 3 / h Mobile recleanable HEPA filter units for a flow of 3.000 m 3 / h Page 1/11 consisting of Mobile online recleanable HEPA filter block, Type M-RHF hightec 1 x 2 and Mobile air conveyor block, Page 2/11 RHF

More information

Operating Instructions Overcurrent Protection - Tester

Operating Instructions Overcurrent Protection - Tester Operating Instructions Overcurrent Protection - Tester WWW.LECOM.CN CONTENTS Table of contents 1. ORDER REFERENCE...2 1.1. Standard set...2 1.2. Options...3 2. INTRODUCTION...4 2.1. General description...4

More information

VOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS

VOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS VOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS A. 11 KV SWITCHGEAR 1.0 SWITCHGEAR ASSEMBLY 1.1 Make : 1.2 Type : 1.3 Reference Standard : 1.4 Voltage (Nom./Max.) KV : 1.5 Phase, Frequency No,Hz.

More information

BLHV, BLHV-1. High Voltage Step Motor Driver. User s Guide. (714) fax: (714) website:

BLHV, BLHV-1. High Voltage Step Motor Driver. User s Guide. (714) fax: (714) website: BLHV, BLHV-1 High Voltage Step Motor Driver User s Guide A N A H E I M A U T O M A T I O N 910 East Orangefair Lane, Anaheim, CA 92801 e-mail: info@anaheimautomation.com #L010015 (714) 992-6990 fax: (714)

More information

SOLAR LIGHTING CONTROLLER SUNLIGHT MODELS INCLUDED IN THIS MANUAL SL-10 SL-10-24V SL-20 SL-20-24V

SOLAR LIGHTING CONTROLLER SUNLIGHT MODELS INCLUDED IN THIS MANUAL SL-10 SL-10-24V SL-20 SL-20-24V SOLAR LIGHTING CONTROLLER OPERATOR S MANUAL SUNLIGHT MODELS INCLUDED IN THIS MANUAL SL-10 SL-10-24V SL-20 SL-20-24V 10A / 12V 10A / 24V 20A / 12V 20A / 24V 1098 Washington Crossing Road Washington Crossing,

More information

MAKING MODERN LIVING POSSIBLE. Pressure switch BCP. Technical brochure

MAKING MODERN LIVING POSSIBLE. Pressure switch BCP. Technical brochure MAKING MODERN LIVING POSSIBLE Pressure switch BCP Technical brochure Contents Page Pressure switch, BCP Introduction...............................................................................3 Features...................................................................................3

More information

See «Overview of types»

See «Overview of types» echnical data sheet SHA-.. Multifunctional linear actuators for adjusting air dampers and slide valves in ventilation and air conditioning systems in buildings For air dampers up to approx. 3 m Actuating

More information

DKG-114 MANUAL AND REMOTE START UNIT

DKG-114 MANUAL AND REMOTE START UNIT DKG-114 MANUAL AND REMOTE START UNIT FEATURES Both manual and remote controlled engine starting and stopping, Automatic shutdown on fault condition, Optional cooldown cycle on remote start operation, Optional

More information

Application Engineering

Application Engineering Application Engineering March 2011 Copeland Digital Compressor Controller Introduction The Digital Compressor Controller is the electronics interface between the Copeland Scroll Digital compressor or the

More information

Induction Power Supplies

Induction Power Supplies Induction Power Supplies 7.5kW; 135 400kHz 480V version (Integral Heat Station) User s Guide Model 7.5-135/400-3-480 SMD Control Brds Rev. D 5/08 Table of Contents 1. Specifications and features...3 2.

More information

AIR-TO-AIR HEAT EXCHANGERS MODEL Q2 TECHNICAL SPECIFICATION

AIR-TO-AIR HEAT EXCHANGERS MODEL Q2 TECHNICAL SPECIFICATION AIR-TO-AIR HEAT EXCHANGERS MODEL Q2 TECHNICAL SPECIFICATION ADDRESS AND CONTACT DATA Heatex AB Bronsyxegatan 13 S-213 75 MALMÖ Sweden Telephone: +46 410 710 500 info@heatex.com www.heatex.com DISCLAIMER

More information

TRIPS AND FAULT FINDING

TRIPS AND FAULT FINDING WWW.SDS.LTD.UK 0117 9381800 Trips and Fault Finding Chapter 6 6-1 TRIPS AND FAULT FINDING Trips What Happens when a Trip Occurs When a trip occurs, the drive s power stage is immediately disabled causing

More information

BLD75-1. Bilevel Step Motor Driver. User s Guide. 910 East Orangefair Lane, Anaheim, CA

BLD75-1. Bilevel Step Motor Driver. User s Guide. 910 East Orangefair Lane, Anaheim, CA BLD75-1 Bilevel Step Motor Driver User s Guide A N A H E I M A U T O M A T I O N 910 East Orangefair Lane, Anaheim, CA 92801 e-mail: info@anaheimautomation.com (714) 992-6990 fax: (714) 992-0471 website:

More information

Operating Instructions. Angle Seat Control Valve. Type 7020

Operating Instructions. Angle Seat Control Valve. Type 7020 Operating Instructions Angle Seat Control Valve Type 7020 With: Digital Positioner Type 8048 Electro-pneumatic Positioner Type 8047 Pneumatic Positioner Type 8047 Version: 02/2006 Manual-7020e.doc Art.-No:

More information

Submittal Data Information

Submittal Data Information Effective: NOVEMBER 3, 2014 JOB CONTRACTOR ITEM NO. Submittal Data Information TDX - Taco Duplex Starter ENGINEER REP. 301-2693 Supersedes: NEW TDX - TACO DUPLEX STARTER 1Ø, 230V, 1/10-15HP 3Ø, 200-460V,

More information

DUAL 60V 20A POWER FLEX POWER SUPPLY INSTRUCTION MANUAL

DUAL 60V 20A POWER FLEX POWER SUPPLY INSTRUCTION MANUAL 72-7570 DUAL 60V 20A POWER FLEX POWER SUPPLY INSTRUCTION MANUAL Table of Contents Specification 1 Safety 3 EMC 4 Installation 5 Connections 5 Operation 6 Maintenance 8 Specification General specifications

More information

CI-tronic Soft starters for Danfoss commercial compressor applications Type MCI 15C, MCI 25C, MCI 50CM-3 I-O

CI-tronic Soft starters for Danfoss commercial compressor applications Type MCI 15C, MCI 25C, MCI 50CM-3 I-O Data sheet CI-tronic Soft starters for Danfoss commercial compressor applications Type, MCI 25C, MCI 50CM-3 I-O The MCI compressor soft starters are designed for soft starting of 3 phase compressors. During

More information

Power consumption In operation At rest For wire sizing

Power consumption In operation At rest For wire sizing echnical data sheet LHK24A-SZ Modulating SuperCap linear actuator with emergency setting function and extended functionalities for adjusting air dampers and sliders in ventilation and air-conditioning

More information

STRA-24 for chilled beams

STRA-24 for chilled beams STRA- Installation and commissioning manual STRA- for chilled beams STRA- is the room controller for the pressure independent (Pi) and constant air volume chilled beams. It is possible to set different

More information

Installation- and maintenance instruction BENTOFLEX ST 108 PL

Installation- and maintenance instruction BENTOFLEX ST 108 PL Installation- and maintenance instruction BENTOFLEX ST 108 PL 1 171 625 30 03-01 178 001 13 DESCRIPTION COMPONENTS 1. Reset button 2. Control box 3. Ignition transformer 4. Ignition cables 5. Nozzle assembly

More information

DPS280 / DVS280 Series

DPS280 / DVS280 Series 1 2 3 4 5 6 7 8 Do not use corrosive or flammable gases or liquid with this product. Please use within the rated pressure range. Do not apply pressure beyond recommended maximum pressure, permanent damage

More information

5001TCP SPEED CONTROLLER

5001TCP SPEED CONTROLLER VARIABLE SPEED DRIVE CONTROLLER INSTALLATION AND SETTING UP MANUAL 5001TCP SPEED CONTROLLER With PC101 Torque Limit Control WARNING Disconnect all incoming power before working on this equipment. Follow

More information

MODEL RMS INSTALLATION INSTRUCTIONS. CONTENTS Page A. Introduction 1. Usage 2 2. How it operates 2

MODEL RMS INSTALLATION INSTRUCTIONS. CONTENTS Page A. Introduction 1. Usage 2 2. How it operates 2 CONVEYOR COMPONENTS COMPANY Division of Material Control, Inc. 130 Seltzer Road, PO Box 167 Croswell, MI 48422 USA PHONE: (810) 679-4211 TOLL FREE (800) 233-3233 FAX: (810) 679-4510 Email: info@conveyorcomponents.com

More information