1 DT & FTS Decentral Systems omfort - Fan oil Units Flex-Geko omfort Edition Flexible solution for any requirement

2 Flex-Geko omfort Edition opyright note Disclosing, copying, distributing or taking any action in reliance on the contents of this document is strictly prohibited without express prior consent. Offenders will be held liable for the payment of damages. ll rights reserved in the event of the grant of a patent, utility model or design. Model sizes... 3 Fan coil unit components... 4 Unit selection... 5 Unit description... 6 E technology: Keyword Energy Efficiency... 8 Recirculating ir Unit Heating and ooling 4-pipe chilled and warm water Recirculating ir Unit Heating and ooling 2-pipe chilled and warm water Recirculating ir Unit Heating and ooling Direct Evaporator and 2-pipe warm water Recirculating ir Unit Heating or ooling 2-pipe chilled or warm water Recirculating ir Unit Heating or ooling 2-pipe chilled or warm water with Electric uxiliary Heating Recirculating ir Unit Heating 2-pipe warm water Recirculating-ir Unit Heating Full Electric Heating Recirculating ir Unit ooling 2-pipe chilled water Recirculating ir Unit ooling Direct Evaporator Mixed-ir Unit Heating and ooling 4-pipe chilled and warm water Mixed-ir Unit Heating and ooling Direct Evaporator and 2-pipe warm water Mixed-ir Unit Heating or ooling 2-pipe chilled or warm water Mixed-ir Unit 2-pipe warm water Mixed-ir Unit Heating Full Electric Heating in heat exchanger Samples for capacity definition coustics Sound power level and sound pressure level NR and N limiting curves Definition of Direction of irflow/installation Samples Dimensions of basic units without casing dimensions and Medium connections Dimensions for Unit asing ccessory sizes - Geko-Drive ccessory sizes - ir Side ccessories Valve control mode Overview of valves Selection table Valves (supplied separately) with modulating actuator (230 V~ and 24 V~)/3-point operation Valves with reversible actuator (230 V~) and 2 floating auxiliary switch/3-point operation Valves with thermoelectric actuators (230 V~ and 24 V~)/2-point open/close operation Valves with continuous actuator (24 V~, V) Thermostatic expansion valve Shut-off valves all valves ontrol via thermostat / miniature switch, controls by others Functions of thermostat and miniature switch ontrol system MTRIX System Description Overview of Features Mounting control panels Sensors/ccessories Global modules MTRIX.lock module MTRIX.P service software ontrol Panel for ll Groups Unit type code PR G Subject to change R5-01/2017

3 Flex-Geko omfort Edition Model sizes For wall and ceiling mounting Model size Width [mm] ir volume [m 3 /h] Sound pressure level 1) [d()] apacity 2) [kw] Heating capacity Q H ooling capacity Q K Motor type EnEff class 3) Heating ooling < , ,0 E D E F G D E F G D E F G D E F G < , ,4 E D E F G D E F G D E F G D E F G , ,3 E D E F G D E F G D E F G D E F G , ,2 E D E F G D E F G D E F G D E F G , ,7 E D E F G D E F G D E F G D E F G , ,6 E D E F G D E F G D E F G D E F G , ,7 E D E F G D E F G D E F G D E F G , ,8 E D E F G D E F G D E F G D E F G 1) mbient conditions see coustics on Page 70 2) apacity data only apply to medium water. Input parameters: PWW 70/50, tl1 = +20 ; PW 6/12, tl1 = 27, 46 % r.h.with other input parameters the following correction factors for approximate estimation of performance data should be applied. 3) EnEff class = Energy Efficiency lass according to EUROVENT refer to Page 10. orrection factors 4) The correction factors listed below can be used to calculate the capacity data in accordance with EUROVENT classification conditions: ooling in recirculating mode (2+4-pipe system): 1.00 Heating in recirculating mode (2-pipe system): 0.66 Heating in recirculating mode (4-pipe system): 1.25 Sound power level 5) +2 d 4) ll indicated correction factors are arithmetically calculated for different unit configurations and are provided for approximate calculations of capacity data using other parameters. Exact data and other parameters can be obtained from our staff. 5) Maximum indication due to EU- ROVENT zero tolerance. orrection factors f K for cooling capacity Q K hilled water temp. ir intake: t L1 [ ], ϕ 1 [% r.h.] orrection factors f H for heating capacity Q H (recirculating air t L1 = 20 ) Warm water temperature 2-pipe system ir intake: t L1 [ ] 4-pipe system ir intake: t L1 [ ] [ ] 32/40 30/40 27/46 26/50 24/50 [ ] / / / / / / / / / / / / / / / / orrection factors f H for heating capacity QH (mixed-air t L1 = 10 ) Warm water temperature 2-pipe system ir intake: t L1 [ ] 4-pipe system ir intake: t L1 [ ] [ ] / / / / / / / / PR G Subject to change R5-01/2017 3

4 Fan coil unit components For wall and ceiling mounting Flex-Geko omfort Edition Fig. 1: Unit components (depending on unit model) 1: Holding plate 2: Heat Exchanger 3: ontrol panel 4: Metal sheet electric control box 5: asic casing (rear wall with lateral sheet steel panels) 6: over sheet at discharge on front side 7: ottom panel at intake on front side 8: Filter element 9: Main drain pan for wall units 10: Fan with casing 11: Suction side front panel at bottom/rear intake 12: Pressure side front panel with frontal discharge 13: Pressure side front panel with top discharge (wall unit) and main drain pan for ceiling units and discharge frontal discharge 14: Mixed-air box* with actuator 15: Unit foot on left side for recirculating-air unit 16: Unit foot on right side for recirculating-air unit 17: Lateral ceiling drain pan 18: Lateral wall drain pan 19: Unit casing 20: Unit foot cover, left side 21: Unit foot cover, right side 22: Suction grille 23: Front casing for front side discharge 24: Front casing for front side intake 25: Front casing for front side intake and discharge *) The plant manufacturer / operator must operate the unit in accordance with EU Directive DencoHappel is a participant in the EUROVENT certification program. The certified products are listed in the corresponding EUROVENT lists. DencoHappel Flex-Geko recirculating-air units are certified in accordance with the hygienic requirements and regulations stipulated by VDI 6022, Sheet 1 (07/11) and SWKI V (04/06). Fans meets requirements of EU Regulation No. 327/2011 of the ommission as of 30th March 2011 to implement Directive 2009/125/EG (ErP-regulation). 4 PR G Subject to change R5-01/2017

5 ,0 8,0 7,0 6,0 5,0 4,5 4,0 3,5 3,0 2,5 2,0 1,5 1,0 0,9 0,8 0,7 0,6 0,5 4 Rohrreihen Kühlen, 2-Leiter-System Druckverluste im Wärmetauscher Wasservolumenstrom V W [l/h] bb GE Top-Geko nderungen vorbehalten Stand 08/00 (D) Flex-Geko omfort Edition Unit selection Unit Description 4 4-pipe chilled and warm water (4-pipe chilled and warm water with auxiliary electric heating)* 12 ooling and heating 2-pipe chilled water and electrical heating 16 Recirculating air ooling or Heating DX evaporator and 2-pipe warm water 20 2-pipe chilled or warm water 24 2-pipe chilled or warm water with auxiliary electric heating 28 Heating 2-pipe warm water (2-pipe warm water with auxiliary electric heating) 32 Full electric heating 36 ooling 2-pipe chilled water 40 Direct evaporator 44 Mixed air** ooling and heating ooling or heating Heating 4-pipe chilled and warm water (2-pipe chilled water and electrical heating)* 48 DX evaporator and 2-pipe warm water 52 2-pipe chilled or warm water (2-pipe chilled or warm water with auxiliary electric heating)* 56 2-pipe warm water (2-pipe warm water with auxiliary electric heating)* 60 Full electric heating 64 (2-pipe chilled water)* ooling (DX evaporator)* *On request DencoHappel will provide you data on the units indicated in brackets. **The plant manufacturer / operator must operate the unit in accordance with EU Directive DruckverlustDp [kpa] Technical Data, dimensions and specification of accessories 68 Valves 84 MTRIX ontrol System/Thermostat Switches 93 + PR G Subject to change R5-01/2017 5

6 Unit description Flex-Geko omfort Edition eiling unit Fig. 2 Wall unit with mixed-air box Fig. 3 Recirculating/mixed-air units* heating/cooling/filtering/ ventilating with 2/4-pipe system. Wall or ceiling installation (electrical and valve equipment depends on functions and requirements), basic unit made of sendzmirgalvanized metal sheet with sound and heat insulation made of polyehtylene omfort casing for ceiling unit, omfort unit casing wall, air discharge grille, air intake bottom/ air discharge grille (with air intake rear grille) Fig. 4 Fig. 5 omfort unit casing made of painted metal sheet, colour white (similar to RL 9002); plastic lateral parts and service panels, colour white (similar RL 9002) and grey (RL 7035); plastic air discharge grille, in grey (RL 7035), or version made of aluminium, naturally anodized Thermoelectric valves Modulating valves Valves 2 and 3-way valves with actuators for 2-point, 230/24 V~ 50/60 Hz 3-point, 230/24 V~ 50/60 Hz continuous 24 V~, control signal 0-10 V, mounted and wired by factory Fig. 6 Fig. 7 Geko-Drive Geko-Drive Motorized and regulated discharge profile for optimization of flow pattern and air throw in cooling mode, mounted by the factory (in combination with unit casing and MTRIX 4000) For more features see Page 79 Fig. 8 Speed and thermostat switches MTRIX control system ontrol / steering systems according to: unit configuration, fitted valves, internal/external electronic components Fig. 9 Fig. 10 *) On the part of the plant manufacturer / operator, the unit must be used in accordance with EU Directive PR G Subject to change R5-01/2017

7 Flex-Geko omfort Edition Unit description Heat exchanger for warm / chilled water Fig. 11 Fig. 12 Electric heater 230 V ~/N/PE 50 Hz/3 x 400 V~ 50/60 Hz Fig. 13 Fig. 14 Lateral wall /ceiling drain pan Fig. 15 Fig. 16 Heat exchanger for refrigerant entrifugal fan 230 V~ 50/60 Hz Lateral wall drain pan with humidity sensor for condensate pump 230 V ~ 50 Hz Heat exchanger copper tubes with aluminum fins, max operating pressure 16 bar, coolant water, max. glycol ratio 50 %, water as heating medium, max. inlet temperature 90, air vent and drain valves, optimized models for low heating, medium or high cooling medium temperatures and low-volume mass flow are available on request. Electric heater with welded stainless steel fins, 2-stage heating capacity, 2 contactors, 2 safety temperature limiters entrifugal fan can be selected either with or highly efficient E motors, with maintenancefree ball bearings, high pressure stability and long service life. onfiguration and number of fans depend on unit size and selection Lateral wall /ceiling drain pan for collecting all condensate from heat exchanger and valve piping, for pressureless condensate drainage, made of plastic Lateral wall drain pan with humidity sensor fitted with condensate pump For collecting condensate and drainage via condensate pump Filter element Mixed-air mechanism Filter element easy to replace, available in G1, G2 and G3 (EN 779) Fig. 17 Fig. 18 Mixed-air mechanism* with outside air intake connection made of galvanized metal sheet, condensateinsulated if temperature falls below dew point, aluminium mixing-air damper, cold air penetration guard via stable aluminium profile. *) The plant manufacturer / operator must operate the unit in accordance with EU Directive PR G Subject to change R5-01/2017 7

8 Unit description E technology: Keyword Energy Efficiency Flex-Geko omfort Edition What are E motors? E-motors (= electronically commutated motors) are D motors, where the rotor is not performed as a coil, like in usual motors ( = alternating current), but consists of a permanent magnet. Electronic control of the motor enables continuous operation, where the integrated electronics ensures alternating magnetic field which adjusts itself to the relevant speed (refer to Fig. 19). In such a way the motor operates at optimal conditions, resulting in maximum torque and minimum losses. The efficiency rate of the E motors used by DencoHapppel is twice as high as the comparable motors. The application of this technology in fan coil units makes it possible to achieve high efficiency rates for fan motors - especially in part-load mode. North pole Regulation Regulation oil oil South South North pole Flow direction Flow direction Fig. 19: Functional description of E motor (electr. commutation) This results in the reduction of electrical power consumption of an E fan by up to 84% omparison /E fan - Flex-Geko Electrical power consumption [W] % -79% -27% fan size 1 fan size 8 E fan size 1 E fan size % % -59% Volume flow [m³/h] Fig. 20: omparison - electrical power consumption E/ fan 8 PR G Subject to change R5-01/2017

9 Flex-Geko omfort Edition Unit description E technology: Keyword Energy Efficiency Further aspects: ontinuous operation Low generation of heat Established and usual high motor quality Same design for 50 and 60 Hz ontinuous fan controls (MTRIX and ET.E) E fans featuring continuous operating mode offer a few of benefits: Room temperature control is performed with a higher accuracy, because occurring temperature differences can be addressed with the accordingly adjusted fan speed. This effect is assisted by using 3-point regulation valves (only with MTRIX control system). Variable fan speed control can compensate for fluctuating conditions of heating and cooling medium. Example: season-related different inlet temperature of heat generator or fluctuating volume flow rates (hydraulics) With standard fans the fan speed, which is optimal for room temperature control, must be adapted to the available fan speed stages which often leads to rapid increase of motor RPM and thus electrical power consumption. With continuous speed regulation - "hard" fan speed changes are eliminated, which provides additional acoustical comfort. The MTRIX ET.E controls uses these features by making the following functions available, the customer can select between automatic and manual operation: utomatic mode: Room temperature control with continuous regulation ( V) of a continuously variable E fan. The fan continuously operates within the minimum and maximum air volumes. Using the display control panel OP50/51 a speed limitation can be activated (mute function) in order to prevent an acoustic overshoot in automatic mode. This upper RPM limit can be separately set for each control panel (only MTRIX controls). s an additional measure to avoid possible on-site acoustical resonance occurrences, up to three speed ranges can be hidden using only MTRIX.controls and service software. Manual mode MTRIX controls: OP 50/51 (control panel with display): continuous fan setting using rotary switch between minimum and maximum air volume flow rate. OP30/31 and OP44: (speed-stage control panel): 5-speed fan setting with speed 1 = minimum air volume flow rate and speed 5 = maximum air volume flow rate. Percentage values (regarding maximum air volume flow rate) for speeds 2-4 are preconfigured by the factory (default values) and can be changed on site by others using MTRIX.P. Manual mode miniature switch ET.E: 3-stage fan control with stage 1 = min. air volume flow and stage 3 = max. air volume flow. The control voltage (Volt) of stages 1-3 are preset by others (depending on selected unit) and can be changed on-site (with DencoHappel service tool or via MODbus interface). PR G Subject to change R5-01/2017 9

10 Unit description Keyword Energy Efficiency: EUROVENT Energy Label Flex-Geko omfort Edition EUROVENT Energy Label Within the framework of EU regulations (Eco-Design Directive) clear limits will be set in the future with respect to the energy efficiency of state-of-the-art technological standards. EUROVENT, as the European ssociation of Manufacturers of HV equipment, anticipates this development by having published Energy Label for fan coil units to include 5 energy efficiency classes ( to E) in January In this case the energy efficiency is composed of time-weighted relationship between cooling or heating output and consumed electrical power of the fan. If fan coil units are equipped with an energy-efficient temperature regulation system (MTRIX) the adjustment of fan speed is performed according to the situation-related heating or cooling demand. For the evaluation of energy efficiency - time percentage of the corresponding active speed stages must be considered. For the description of time-related conditions EUROVENT uses coefficient (maximum), (medium) and (minimum speed). These indicators vary, depending on heating or cooling operating mode. Fan stage oefficient Time share ooling Heating High (maximum) 5 % 5 % Medium 30 % 25 % Low (minimum) 65 % 70 % The energy efficiency relationship is composed of time-weighted shares and is presented in the example using the following formulas: ooling (FEER): Q FEER Q KHighSpeed + Q KMediumSpeed + Q = KLowSpeed Fan oil Energy Efficiency Ratio - total cooling capacity Pe HighSpeed + Pe MediumSpeed + QPe LowSpeed (= Energy efficiency relationship) Heating (FOP): FOP = Q HHighSpeed + Q HMediumSpeed + Q HLowSpeed Pe HighSpeed + Pe MediumSpeed + Pe LowSpeed Fan oil oefficient Of Performance (=Performance coefficient of fan coil unit) with Q K = Total cooling capacity with Q H = Heating capacity with Pe = Electrical power consumption of fan Higher numerical value of these indicators stands for especially outstanding energy efficiency. 10 PR G Subject to change R5-01/2017

11 Flex-Geko omfort Edition Unit description Keyword Energy Efficiency: EUROVENT Energy Label/Optimized heat exchanger For the corresponding energy label the EUROVENT determines the following classification: Example: Flex-Geko GF52.UWW1.SE01 [unit code for 4-pipe with E fan] ooling (FEER) *: FEER = 5% 4, % 3, % 2, 72 5% = 0, % 0, % 0, LSS Label Heating (FOP) *: FOP Label = 5% 4, % 3, % 2, 91 5% = 0, % 0, % 0, LSS *) ooling, heating and electrical output in [kw] under EUROVENT conditions: ooling: air intake 27 / 47% r.h., chilled water 7 / 12 Heating: air intake 20, warm water 70 / 60 Optimized heat exchangers for low-energy applications Flex-Geko offers today additional heat exchanger models especially for low-energy applications, such as heat pumps that are optimized for low heating medium or high cooling medium temperatures and low mass flows: 2-pipe system: additional capacity stage 4 * 4-pipe system: additional capacity stage 3 * *) Only unit models for water, without direct evaporator and/or electric heater id@ Data for all unit types can be calculated using our id@ layout software or provided by our sales representatives. PR G Subject to change R5-01/

12 Recirculating-ir Unit Heating and ooling 4-pipe chilled and warm water Sizes 1 to 8 WP 6/12 t L1 = +27 ϕ 1 = 46 % r.h. PWW 70/50 t L1 = +20 Flex-Geko omfort Edition Model size Speeds ir volume ooling capacity apacity stage 1 apacity stage 2 -motor E motor Heating capacity ooling capacity Q K Δp K Q H Δp H Q K Δp K Q H Δp H m 3 /h kw kpa kw kpa kw kpa kw kpa d() d() d() d() < < < Heating capacity Sound power Sound pressure * Sound power Sound pressure * motor E motor Motor design T integr. 0 T led out 1 terminal box (select sheet steel electric control box with MTRIX) Speed combination E H Min..Max (E motor) F <20 Metal-sheet electric control box with terminal block or for integrated controls Speed combination K L M O R Min..Max (E motor) S S 1 S 2 E Data for capacity stage 3 (S 3) are available on request (see Page 11). Order code G F U W W 1 Left 2 Right 3 Left 4 Right 0 With drainage 1 With condensate pump Wall eiling irculating air / supply air / irculating air / supply air / ** irculating air / - supply air / D irculating air / - supply air / ** Medium connect.*** ondensate line 1 G1 mat filter 2 G2 mat filter 3 G3 mat filter * mbient conditions see Page 70 coustics ** Only wall units *** Front connection side, facing discharge + only motor ++ ir volume flow S 1 and filter class G1 +++ Definition of air flow wall/ceiling see Page 74 Fig. 28 ir flow +++ Filter 12 PR G Subject to change R5-01/2017

13 Flex-Geko omfort Edition ccessories rrangement/installation Variant/ unit casing Vertical wall/ horizontal ceiling Vertical wall Vertical wall/ horizontal ceiling Vertical wall Vertical wall/ horizontal ceiling; with unit foot cover ** Suitable for air flow designation D Discharge grille luminium luminium luminium ode ccessories/valves Recirculating-ir Unit Heating and ooling 4-pipe system chilled and warm water Sizes 1 to 8 Variant Type ode Discharge plenum primary air connection DN100 insulated 022 Discharge plenum with round fitting DN200 insulated 042 Discharge bend insulated 062 Flexible canvas discharge connector 112 Discharge sound attenuator connector 212 Geko-Drive motorized regulated discharge profile *** ir intake plenum with primary air connection DN 125 ir intake plenum with round connection DN 200 Left 412 Right 422 not insulated 011 not insulated 031 Vertical wall; with unit foot cover ** Vertical wall/horizontal ceiling; with unit foot cover and intake front grille ** luminium ir intake bend not insulated 051 Intake flexible connection (transition piece required) Transition piece for intake flexible connection, telescopic and sound-attenuator connection Vertical wall, with unit foot cover and intake front grille ** Horizontal ceiling; closed rear side luminium Intake telescopic connection (transition piece required) not insulated 151 Intake sound attenuator connection for 211 recirculating-air unit (transition piece required) Seal cap for round insulated 713 fitting, DN 200 * ** Unit feet ZGF.0913 required Vertical stand-alone installation closed on rear side luminium Unit feet for recirculating-air units * 913 Spare filter (5 pieces) G1 813 G2 823 G3 833 Sizes 1 to 8 * 0, if irrespective of size Order code Z G F *** Note! Geko-Drive only together with unit casing! Valves MTRIX 2000 MTRIX 3000/4000 Terminal box Drive Operating voltage/circuit 2-point 230 V 2) T open/ close 24 V 1), 2) Q 3-point 230 V R open/ stop/ 24 V 1) N close 230 V + 2 contacts ontinuous 0/ V = 24 V 1) S onnection/shut-off Inlet/outlet flow with outside thread 0 Inlet/outlet with solder fitting 1 Inlet/outlet + ball trap with external thread 2 Inlet/outlet + ball trap with solder fitting 3 Inlet + ball trap/ outlet + shut-off valve with external thread 4 Inlet + ball trap/ outlet + shut-off valve with solder fitting 5 Heating circuit ooling circuit 2 3 k vs values ooling/heating ) ) Medium connection Left L Right R 1) 24 V-transformer to be provided by others 2) kvs-values for open/close actuators (T,Q) only kvs 1.6 and 2.5 possible Order code V G F ooling circuit Heating circuit PR G Subject to change R5-01/

14 on func send % ontrols Recirculating-ir Unit Heating and ooling 4-pipe system chilled and warm water, Sizes 1 to 8 DencoHappel MTRIX 2000 System features MTRIX 2000: Temperature assignment: (default ) Manual assignment of speed stage djustable regulating range hange-over between normal/economy mode on control panel Room temperature measurement using control panel External room temperature sensor can be connected Valve control (2-point) Temperature control via fan on/off and valve(s) Status messages using LED Group control Group switch-off switch-off in case of fault Motor temperature monitoring (T required) Network-enabled MTRIX OP21 ontrol panel for MTRIX 2000: Speed stage selection switch 0-(uto) Pure white casing, protection type IP20 Economy mode button LEDs for operation/fault/ext.control Integrated room temperature sensor Flex-Geko omfort Edition DencoHappel MTRIX 3000/4000 System features MTRIX 3000: Temperature assignment.: (default ) Speed (stage) assignment djustable regulating range hange-over between normal/economy mode on control panel Input for change-over between normal/economy mode or unit OFF with frost protection Room temperature measurement using control panel External room temperature sensor can be connected Valve control (2x2 or 2x3 point) Temperature control via fan and/or valve(s) Room frost protection Status messages using LED Status and fault signals using floating change-over contacts Unit individual and group control Isolation of individual units in case of fault Motor temperature monitoring (with speed stage motors T required) Network-enabled dditional features MTRIX 4000: Summer / winter compensation Noiseless valve control ool and/or heat request via volt-free contacts (related to water circuit) Stand alone unit control Inputs for operating mode: Normal mode Economy mode utonomous mode Unit OFF MTRIX OP30 ontrol panel for MTRIX 3000/4000 Pure white casing, protection type IP20 Setpoint temperature setting Speed-stage selection switch 0-(uto) (depends on motor type, with E motor up to 5 stages) LEDs for operation/fault/ext.control Integrated room temperature sensor MTRIX OP31 s for control panel OP30, but also with: Normal/economy mode buttons MTRIX OP44 s for control panel OP31, but also with button for: hangeover between recirculating-air/ mixed-air operation hange-over heating/cooling/automatic mode MTRIX OP50 ontrol panel for MTRIX 3000/4000 Pure white casing, protection type IP20 Menu-guided controls using rotation navigator LD display with plain-text display Status messages using pictograms Integrated room temperature sensor ontinuous speed regulation (only together with E motor) MTRIX OP51 s for control panel OP50, but also with: Integrated weekly clock timer with a holiday and special days programme D E F MTRIX.IR Infrared remote control for control system MTRIX 3000/4000 lack casing, RL 9004 LD display approx. 45x30 mm Function as in OP44 (without status, fault and external control signals, no integrated room temperature sensor) Maximum range 20 m Speed-stage selection switch 0-(uto) (depends on motor type, with E motor up to 5 stages) off - + N 14 PR G Subject to change R5-01/2017

15 Flex-Geko omfort Edition ontrols Recirculating-ir Unit Heating and ooling 4-pipe system chilled and warm water Sizes 1 to 8 With controller type: D0 = 7x2x0.8 J-Y(ST)Y D2 = 5x2x0.8 J-Y(ST)Y Master unit With controller type: D0 = 7x2x0.8 J-Y(ST)Y D2 = 4x2x0.8 J-Y(ST)Y Slave units D2: 1-15 D0: 1-3 3x1.5 mm 2 NYM 3x1.5 mm 2 NYM ooling/heating.medium 230 V ~ 50 Hz Without return air sensor * 0 With return air sensor * 5 Enclosed control panel Integrated control panel Order code MTRIX 2000 D D Z D e.g. 2x2x0.5 Helukabel Master unit With controller type: D2 = 4x2x0.8 J-Y(ST)Y D3/4 = e.g. 1x2x0.5 Helukabel Slave units x1.5 mm 2 NYM 3x1.5 mm 2 NYM ooling/heat.medium 230 V ~ 50 Hz Speed (E motor) Speed stages ( motor) Stand alone unit control with operating and Fault signal Group regulation with status and alarm signals Input unit OFF with room frost protection Input economy contact Supply temperature limitation Noiseless valve control ontact heat and cool request Geko-Drive ontinuous up to 3 speed onnection external sensor up to 5 speed Without return air sensor * 0 With return air sensor * 5 ontrol panel Enclosed control panel Integrated control panel Order code D 2 D 2 Z D * lternative room temperature sensor (see Page 98) Master unit Slave unit PR G Subject to change R5-01/

16 Recirculating-ir Unit Heating and ooling 2-pipe chilled water and electric heating Sizes 1 to 8 WP 6/12 t L1 = +27 ϕ 1 = 46 % r.h. Electric heater 230V~N/P/E 50Hz Flex-Geko omfort Edition Model size Speeds ++ ir volume ooling capacity apacity stage 1 apacity stage 2 apacity stage 3 motor E motor EX Speed L EX Speed M ooling capacity EX Speed L EX Speed M Q K Δp K Q H Q H Q K Δp K Q H Q H Q K Δp K Q H Q H m 3 /h kw kpa kw kw kw kpa kw kw kw kpa kw kw d() d() d() d() ooling capacity EX Speed L EX Speed M Sound power Sound pressure * Sound power Sound pressure * Metal sheet electric control box with terminal strip or for integ. ontrols Speed combination L M Min..Max (E motor) S S 1 S 2 S 3 motor E motor Motor design T integr. 0 T led out 1 E 1 Left 2 Right 3 Left 4 Right Wall eiling Medium connect.*** 0 With drainage 1 With condensate pump ondensate line irculating air / - supply air / irculating air / - supply air / ir flow G1 mat filter 2 G2 mat filter Filter Order code G F U W E * mbient conditions see Page 70 coustics *** Front connection side, facing discharge ** ir volume flow for S 1 and filter class G1 +++ Definition of air flow wall/ceiling see Page 74 Fig PR G Subject to change R5-01/2017

17 Flex-Geko omfort Edition ccessories/valves Recirculating-ir Unit Heating and ooling 2-pipe chilled water and e-heating, model sizes 1 to 8 ccessories rrangement/ installation Variant/ unit casing Vertical wall/ horizontal ceiling Suitable for air flow designation Discharge grille luminium ode 013 Variant Type ode ir intake plenum with primary air connection DN 125 not insulated 011 ir intake bend not insulated 051 Vertical wall/ horizontal ceiling luminium 033 Transition piece for intake telescopic connection 131 Vertical wall/ horizontal ceiling; with unit foot cover ** luminium 053 Intake telescopic connection (transition piece required) not insulated 151 Vertical wall/horizontal ceiling; with unit foot cover and intake front grille ** Horizontal ceiling; closed on rear side luminium luminium Unit feet for recirculating-air units * 913 Spare filter (5 pieces) G1 813 G2 823 Vertical stand-alone installation closed on rear side luminium 233 ** Unit feet ZGF.0913 required Sizes 1 to 8 * 0, if irrespective of size Order code Z G F Valves MTRIX 500 MTRIX 2000 MTRIX 3000/4000 Terminal box Drive Operating voltage/circuit 2-point 230 V 2) T open/ close 1), 2) 24 V Q 3-point 230 V R open/ stop/ 24 V 1) N close 230 V + 2 contacts ontinuous 0/ V = 24 V 1) S onnection/shut-off Inlet/outlet flow with outside thread 0 Inlet/outlet with solder fitting 1 Inlet/outlet + ball trap with external thread 2 Inlet/outlet + ball trap with solder fitting 3 Inlet + ball trap/ outlet + shut-off valve with external thread 4 Inlet + ball trap/ outlet + shut-off valve with solder fitting 5 ooling circuit 2 3 k vs values ooling ) ) Medium connection Left L Right R 1) 24 V-transformer to be provided by others 2) kvs-values for open/close actuators (T,Q) only kvs 1.6 and 2.5 possible Order code V G F ooling circuit PR G Subject to change R5-01/

18 func send ontrols Recirculating-ir Unit Heating and ooling 2-pipe chilled water and e-heating, model sizes 1 to 8 Flex-Geko omfort Edition DencoHappel MTRIX 2000 not applicable DencoHappel MTRIX 4000 System features MTRIX 4000: Temperature assignment.: (default ) ssignment of speed stage djustable regulating range hange-over between normal/economy mode on control panel Input for change-over between normal/economy mode or unit OFF with frost protection Room temperature measurement using control panel External room temperature sensor can be connected Valve control (2 or 3 point) Temperature control via fan and/or valve Room frost protection Status messages using LED Status and alarm signal via volt free change-over contacts Unit individual and group control Isolation of individual units in case of fault Motor temperature monitoring (with speed stage motors T required) Network-enabled Summer / winter compensation Noiseless valve control ool request via volt free contact (related to water circuit) Stand alone unit control Inputs for operating mode: Normal mode Economy mode utonomous mode Unit OFF Regulation of multi-stage electrical heating with disconnection in case of over-temperature MTRIX OP30 ontrol panel for MTRIX 4000 Pure white casing, protection type IP20 Setpoint temperature setting Speed-stage selection switch 0-(uto) (depends on motor type, with E motor up to 5 stages) LEDs for operation/fault/ext.control Integrated room temperature sensor MTRIX OP31 s for control panel OP30, but also with: Normal/economy mode buttons MTRIX OP44 s for control panel OP31, but also with button for: hangeover between recirculating-air/ mixed-air operation hange-over heating/cooling/automatic mode MTRIX OP50 ontrol panel for MTRIX 4000 Pure white casing, protection type IP20 Menu-guided controls using rotation navigator LD display with plain-text display Status messages using pictograms Integrated room temperature sensor MTRIX OP51 s for control panel OP50, but also with: Integrated weekly clock timer with holiday and special days programme D E F MTRIX.IR Infrared remote control for control system MTRIX 4000 lack casing, RL 9004 LD display approx. 45x30 mm Function as in OP44 (without status, alarm and external control signals, no integrated room temperature sensor) Maximum range 20 m Speed-stage selection switch 0-(uto) (depends on motor type, with E motor up to 5 stages) % on off - + N 18 PR G Subject to change R5-01/2017

19 Flex-Geko omfort Edition ontrols Recirculating-ir Unit Heating and ooling 2-pipe chilled water and e-heating, model sizes 1 to 8 Master unit 230 V~ 50 Hz Slave units V~ 50 Hz 2x2x0.5 Helukabel e.g. 1x2x0.5 Helukabel 3x1.5 mm 2 NYM 3x1.5 mm 2 NYM ooling medium 230 V ~ 50 Hz 3x2.5 mm 2 NYM 3x2.5 mm 2 NYM 230 V ~ 50 Hz 230 V ~ 50 Hz Speed (E motor) Speeds Stand alone unit control with operating and Fault signal Input unit OFF with room frost protection Input economy contact Noiseless valve control ontact heat and cool request onnection external sensor ontinuous up to 3 speed Without return air sensor * 2 With return air sensor * 7 ontrol panel Enclosed control panel Integrated control panel Order code D 4 2 D 4 2 Z D * lternatively room temperature sensor (see Page 98) Master unit Slave unit PR G Subject to change R5-01/

20 Recirculating-ir Unit Heating and ooling Direct evaporator and 2-pipe warm water Sizes 1 to 8 t o = 10 t L1 = +27 ϕ 1 = 46 % r.h. Refrigerant: R410 PWW 70/50 t L1 = +20 Flex-Geko omfort Edition Model size Speeds ++ ir volume ooling capacity apacity stage 1 motor E motor Heating capacity Sound power Q K Q H Δp H m 3 /h kw kw kpa d() d() d() d() Sound pressure * Sound power Sound pressure * Metal sheet electric control box with terminal block or for integ. ontrols Speed combination M Min..Max (E motor) S S 1 motor E motor Motor design T integr. 0 T led out 1 E 1 Left 2 Right 3 Left 4 Right 0 With drainage 1 With condensate pump Wall eiling Medium connect.*** ondensate line irculating air / - supply air / irculating air / - supply air / ** irculating air / - supply air / D irculating air / - supply air / ** ir flow +++ Order code G F 1 U D W M 1 G1 mat filter 2 G2 mat filter * mbient conditions see Page 70 coustics ** Only wall units *** Front connection side, facing discharge ** ir volume flow for S 1 and filter class G1 +++ Definition of air flow wall/ceiling see Page 74 Fig. 28 Filter 20 PR G Subject to change R5-01/2017

21 Flex-Geko omfort Edition ccessories/valves Recirculating-ir Unit Heating and ooling DX evaporator and 2-pipe warm water, model sizes 1 to 8 ccessories rrangement/ installation Variant/ unit casing Vertical wall/ horizontal ceiling Suitable for air flow designation Discharge grille luminium ode Variant Type ode Discharge plenum primary air connection DN100 insulated 022 Discharge bend insulated 062 Vertical wall Vertical wall/ horizontal ceiling luminium Flexible canvas discharge connector 112 Geko-Drive motorized regulated discharge profile *** ir intake plenum with primary air connection DN 125 left 412 right 422 not insulated 011 Vertical wall Vertical wall/ horizontal ceiling; with unit foot cover ** D luminium ir intake bend not insulated 051 Intake flexible connection (transition piece required) Transition piece for intake flexible connection, telescopic connection Vertical wall; with unit foot cover ** 062 Intake telescopic connection (transition piece required) not insulated 151 Vertical wall/horizontal ceiling; with unit foot cover and intake front grille ** Vertical wall, with unit foot cover and intake front grille ** luminium Unit feet for recirculating-air units * 913 Spare filter (5 pieces) G1 813 G2 823 Horizontal ceiling; closed rear side luminium Vertical stand-alone installation closed on rear side luminium ** Unit feet ZGF.0913 required Sizes 1 to 8 * 0, if irrespective of size Order code Z G F *** Note! Geko-Drive only together with unit casing! Valves MTRIX 2000 MTRIX 3000/4000 Terminal box Drive Operating voltage/circuit 2-point 230 V 2) T open/ close 24 V 1), 2) Q 3-point open/ stop/ close 230 V R 24 V 1) N 230 V + 2 contacts ontinuous 0/ V = 24 V 1) S DX connection via expansion valve 3) 0 Expansion valve R410 3) E onnection/blocking (not DX) Inlet/outlet flow with outside thread 0 Inlet/outlet with solder fitting 1 Inlet/outlet + ball trap with external thread 2 Inlet/outlet + ball trap with solder fitting 3 Inlet + ball trap/ outlet + shut-off valve with external thread 4 Inlet + ball trap/ outlet + shut-off valve with solder fitting 5 DX connection 3) with/ without expansion valve Heat circuit k vs values ooling/heating ) ) DX without expansion valve3) 00 Setting of expansion valve3) S1-S8 Medium connection Left L right R 1) 24 V-transformer to be provided by others 2) kvs-values for open/close actuators (T,Q) only kvs 1.6 and 2.5 possible 3) Only cooling circuit Order code V G F 0 li i it H ti i it PR G Subject to change R5-01/

22 ontrols Recirculating-ir Unit Heating and ooling DX evaporator and 2-pipe warm water, model sizes 1 to 8 Flex-Geko omfort Edition DencoHappel MTRIX 2000 not applicable DencoHappel MTRIX 3000/4000 System features MTRIX 3000: Temperature assignment.: (default ) Speed (stage) assignment djustable regulating range hange-over between normal/economy mode on control panel Input for change-over between normal/economy mode or unit OFF with frost protection Room temperature measurement using control panel External room temperature sensor can be connected Valve control (2 or 3 point) Temperature control via fan and/or valve Room frost protection Status messages using LED Status and alarm signal via volt free change-over contacts Unit individual and group control Isolation of individual units in case of fault Motor temperature monitoring (with speed stage motors T required) Network-enabled MTRIX OP30 ontrol panel for MTRIX 3000/4000 Pure white casing, protection type IP20 Setpoint temperature setting Speed-stage selection switch 0-(uto) (depends on motor type, with E motor up to 5 stages) LEDs for operation/fault/ext.control Integrated room temperature sensor MTRIX OP31 s for control panel OP30, but also with: Normal/economy mode buttons MTRIX OP44 s for control panel OP31, but also with button for: hangeover between recirculating-air/ mixed-air operation hange-over heating/cooling/automatic mode D dditional features MTRIX 4000: Summer / winter compensation Noiseless valve control Heat request via volt-free contact (related to water circuit) Stand alone unit control Inputs for operating mode: Normal mode Economy mode utonomous mode Unit OFF MTRIX OP50 ontrol panel for MTRIX 3000/4000 Pure white casing, protection type IP20 Menu-guided controls using rotation navigator LD display with plain-text display Status messages using pictograms Integrated room temperature sensor ontinuous speed regulation (only together with E motor) MTRIX OP51 s for control panel OP50, but also with: Integrated weekly clock timer with holiday and special days programme MTRIX.IR E F Infrared remote control for control system MTRIX 3000/4000 lack casing, RL 9004 LD display approx. 45x30 mm Function as in OP44 (without status, fault and external control signals, no integrated room temperature sensor) Maximum range 20 m Speed-stage selection switch 0-(uto) (depends on motor type, with E motor up to 5 stages) % on off func - + send N 22 PR G Subject to change R5-01/2017

23 Flex-Geko omfort Edition ontrols Recirculating-ir Unit Heating and ooling DX evaporator and 2-pipe warm water, model sizes 1 to 8 Master unit Slave units x2x0.5 Helukabel e. g. 1x2x0.5 Helukabel 3x1.5 mm 2 NYM 3x1.5 mm 2 NYM Heating medium 230 V ~ 50 Hz 1x2x0.5 Helukabel 3x1.5 mm 2 NYM ooling medium RF Modules ompressors Speeds E motor Speed stages motor Stand alone unit control with operating and Fault signal Input unit OFF with room frost protection Input economy contact Noiseless valve control ontact heat and cool request onnection external sensor ontinuous up to 3 speed Without return air sensor * 3 With return air sensor * 8 ontrol panel Enclosed control panel Integrated control panel Order code D. 2. D. 2. Z D * lternatively room temperature sensor (see Page 98) Master unit Slave unit PR G Subject to change R5-01/

24 Recirculating-ir Unit Heating or ooling 2-pipe chilled or warm water Sizes 1 to 8 WP 6/12 t L1 = +27 ϕ 1 = 46 % r.h. PWW 70/50 t L1 = +20 Flex-Geko omfort Edition Model size Speeds ir volume ooling capacity apacity stage 1 apacity stage 2 apacity stage 3 -Motor E motor Heating capacity ooling capacity Heating capacity Q K Δp K Q H Δp H Q K Δp K Q H Δp H Q K Δp K Q H Δp H m 3 /h kw kpa kw kpa kw kpa kw kpa kw kpa kw kpa d() d() d() d() < < < ooling capacity Heating capacity Sound power Sound pressure * Sound power Sound pressure * terminal box (with MTRIX metal sheet electrical control box) Speed combination E H Min..Max (E motor) F < motor E motor Motor design Metal sheet electric control box with terminal strip or for integ. ontrols Speed combination T integr. 0 T led out K L M O R Min..Max (E motor) S S 1 S 2 S 3 E Data for capacity stage 4 (S 4) are available on request (see Page 11). Order code G F U W 1 Left 2 Right 3 Left 4 Right 0 With drainage 1 With condensate pump D Wall eiling irculating air / - supply air / irculating air / - supply air / ** irculating air / - supply air / irculating air / - supply air / ** 1 G1 mat filter 2 G2 mat filter 3 G2 mat filter Medium connect.*** ondensate line ir flow +++ Filter * mbient conditions see Page 70 coustics ** Only wall units *** Front connection side, facing discharge + only motor ** ir volume flow for S 1 and filter class G1 +++ Definition of air flow wall/ceiling see Page 74 Fig PR G Subject to change R5-01/2017

25 Flex-Geko omfort Edition ccessories rrangement/ installation Variant/ unit casing Vertical wall/ horizontal ceiling Vertical wall Vertical wall/ horizontal ceiling Vertical wall Vertical wall/ horizontal ceiling; with unit foot cover ** Suitable for air flow designation D Discharge grille luminium luminium luminium ode ccessories/valves Recirculating-ir Unit Heating or ooling 2-pipe system chilled or warm water Sizes 1 to 8 Variant Type ode Discharge plenum primary air connection DN100 insulated 022 Discharge plenum with round fitting DN200 insulated 042 Discharge bend insulated 062 Flexible canvas discharge connector 112 Discharge sound attenuator connector 212 Geko-Drive motorized regulated discharge profile *** ir intake plenum with primary air connection DN 125 ir intake plenum with round connection DN 200 left 412 right 422 not insulated 011 not insulated 031 Vertical wall; with unit foot cover ** Vertical wall/horizontal ceiling; with unit foot cover and intake front grille ** luminium ir intake bend not insulated 051 Intake flexible connection (transition piece required) Transition piece for intake flexible connection, telescopic and sound-attenuator connection Vertical wall, with unit foot cover and intake front grille ** Horizontal ceiling; closed rear side luminium Intake telescopic connection (transition piece required) not insulated 151 Intake sound attenuator connection for 211 recirculating-air unit (transition piece required) Seal cap for round insulated 713 fitting, DN 200 * ** Unit feet ZGF.0913 required Vertical stand-alone installation closed on rear side luminium Unit feet for recirculating-air units * 913 Spare filter (5 pieces) G1 813 G2 823 G3 833 Sizes 1 to 8 * 0, if irrespective of size Order code Z G F *** Note! Geko-Drive only together with unit casing! Valves MTRIX 2000 MTRIX 3000/4000 Terminal box Drive Operating voltage/circuit 2-point 230 V 2) T open/ close 24 V 1), 2) Q 3-point open/ stop/ close ontinuous 230 V R 24 V 1) N 230 V + 2 contacts 0/ V = 24 V 1) S onnection/shut-off Inlet/outlet flow with outside thread 0 Inlet/outlet with solder fitting 1 Inlet/outlet + ball trap with external thread 2 Inlet/outlet + ball trap with solder fitting 3 Inlet + ball trap/ outlet + shut-off valve with external thread 4 Inlet + ball trap/ outlet + shut-off valve with solder fitting 5 ool / heat circuit 3 k vs values ooling/heating ) ) Medium connection Left L Right R 1) 24 V-transformer to be provided by others 2) kvs-values for open/close actuators (T,Q) only kvs 1.6 and 2.5 possible Order code V G F 3 ooling/heating circuit PR G Subject to change R5-01/

26 on func send % ontrols Recirculating-ir Unit Heating or ooling 2-pipe system chilled or warm water Sizes 1 to 8 DencoHappel MTRIX 2000 System features MTRIX 2000: Extended temperature assignment.: (default ) Manual assignment of speed stage djustable regulating range hange-over between normal/economy mode on control panel Room temperature measurement using control panel External room temperature sensor can be connected Valve control (2-point) Temperature control with fan speed change-over and valve(s) Status messages using LED Group control Group switch-off switch-off in case of fault Motor temperature monitoring (T required) Network-enabled MTRIX OP21 ontrol panel for MTRIX 2000 Pure white casing, protection type IP20 Setpoint temperature setting Speed stage selection switch 0- (uto) Economy mode button LEDs for operation/fault/ext.control Integrated room temperature sensor Flex-Geko omfort Edition DencoHappel MTRIX 3000/4000 System features MTRIX 3000: Temperature assignment.: (default ) Speed (stage) assignment djustable regulating range hange-over between normal/economy mode on control panel Input for change-over between normal/economy mode or unit OFF with frost protection Room temperature measurement using control panel External room temperature sensor can be connected Valve control (2x2 or 2x3 point) Temperature control via fan and/or valve(s) Room frost protection Status messages using LED Status and fault signals using floating change-over contacts Unit individual and group control Isolation of individual units in case of fault Motor temperature monitoring (with speed stage motors T required) Network-enabled dditional features MTRIX 4000: Summer / winter compensation Noiseless valve control ool and/or heat request via volt-free contacts (related to water circuit) Stand alone unit control Inputs for operating mode: Normal mode Economy mode utonomous mode Unit OFF MTRIX OP30 ontrol panel for MTRIX 3000/4000 Pure white casing, protection type IP20 Setpoint temperature setting Speed-stage selection switch 0-(uto) (depends on motor type, with E motor up to 5 stages) LEDs for operation/fault/ext.control Integrated room temperature sensor MTRIX OP31 s for control panel OP30, but also with: Normal/economy mode buttons MTRIX OP44 s for control panel OP31, but also with button for: hangeover between recirculating-air/ mixed-air operation hange-over heating/cooling/automatic mode MTRIX OP50 ontrol panel for MTRIX 3000/4000 Pure white casing, protection type IP20 Menu-guided controls using rotation navigator LD display with plain-text display Status messages using pictograms Integrated room temperature sensor ontinuous speed regulation (only with E motor) MTRIX OP51 s for control panel OP50, but also with: Integrated weekly clock timer with a holiday and special days programme D E F MTRIX.IR Infrared remote control for control system MTRIX 3000/4000 lack casing, RL 9004 LD display approx. 45x30 mm Function as in OP44 (without status, fault and external control signals, no integrated room temperature sensor) Maximum range 20 m Speed-stage selection switch 0-(uto) (depends on motor type, with E motor up to 5 stages) off - + N 26 PR G Subject to change R5-01/2017

27 Flex-Geko omfort Edition ontrols Recirculating-ir Unit Heating or ooling 2-pipe system chilled or warm water Sizes 1 to 8 With controller type: D0 = 7x2x0.8 J-Y(ST)Y D2 = 5x2x0.8 J-Y(ST)Y Master unit With controller type: D0 = 7x2x0.8 J-Y(ST)Y D2 = 4x2x0.8 J-Y(ST)Y Slave units D2: 1-15 D0: 1-3 3x1.5 mm 2 NYM 3x1.5 mm 2 NYM ooling/heat.medium 230 V ~ 50 Hz 2x2x0.8 J-Y(ST)Y without return air sensor * 1 flow sensor with return air sensor * 6 Enclosed control panel Integrated control panel Order code MTRIX 2000 D D Z D e.g. 2x2x0.5 Helukabel Master unit With controller type: D2 = 4x2x0.8 J-Y(ST)Y D3/4 = e.g. 1x2x0.5 Helukabel Slave units x1.5 mm 2 NYM 3x1.5 mm 2 NYM ooling/heat.medium 230 V ~ 50 Hz 2x2x0.8 J-Y(ST)Y flow sensor Speed (E motor) Speed stages ( motor) Stand alone unit control with operating- and Fault signal Group regulation with status and alarm signals Input unit OFF with room frost protection Input economy contact Supply temperature limitation Noiseless valve control ontact heat and cool request Geko-Drive ontinuous up to 3 speed onnection external sensor up to 5 speed Without return air sensor * 0 With return air sensor * 5 ontrol panel Enclosed control panel Integrated control panel Order code D. 1. D. 1. Z D * lternatively room temperature sensor (see Page 98) Master unit Slave unit PR G Subject to change R5-01/

28 Recirculating-ir Unit Heating or ooling 2-pipe chilled or warm water with auxiliary electrical heating (EH), Model sizes 1 to 8 WP 6/12 t L1 = +27 ϕ 1 = 46 % r.h. PWW 70/50 t L1 = +20 Electric heater 230V~N/P/E 50Hz Flex-Geko omfort Edition Model size Speeds ++ ir volume ooling capacity apacity stage 1 apacity stage 2 apacity stage 3 E heating motor E motor Heating capacity ooling capacity Heating capacity Q K Δp K Q H Q H Q K Δp K Q H Q H Q K Δp K Q H Q H QH QH m 3 /h kw kpa kw kw kw kpa kw kw kw kpa kw kw kw kw d() d() d() d() ooling capacity Metal-sheet electric control box with terminal block or for integrated controls Speed stages combinations L M Min..Max (E motor) S 1 S 2 S 3 Heating capacity EX Speed L EX Speed M Sound power Sound pressure * Sound power Sound pressure * Motor design motor E motor T integr. 0 T led out 1 S E 1 Left 2 Right 3 Left 4 Right 0 With drainage 1 With condensate pump irculating air / - supply air / irculating air / - supply air / Wall eiling Medium connect.*** ondensate line ir flow G1 mat filter 2 G2 mat filter * mbient conditions see Page 70 coustics *** Front connection side, facing discharge ** ir volume flow for S 1 and filter class G1 +++ Definition of air flow wall/ceiling see Page 74 Filter Order code G F U W 28 PR G Subject to change R5-01/2017

29 Flex-Geko omfort Edition ccessories rrangement/ installation Variant/ unit casing Vertical wall/ horizontal ceiling Suitable for air flow designation ccessories/valves Recirculating-ir Unit Heating or ooling 2-pipe system chilled or warm water and auxiliary electric heating, sizes 1 to 8 Discharge grille luminium ode 013 Variant Type ode ir intake plenum with primary air connection DN 125 not insulated 011 ir intake bend not insulated 051 Vertical wall/horizontal ceiling luminium 033 Transition piece for intake telescopic connection 131 Vertical wall/horizontal ceiling; with unit foot cover ** luminium 053 Intake telescopic connection (transition piece required) not insulated 151 Vertical wall/horizontal ceiling; with unit foot cover and intake front grille ** Horizontal ceiling; closed on rear side luminium luminium Unit feet for recirculating-air units * 913 Spare filter (5 pieces) G1 813 G2 823 Vertical stand-alone installation closed on rear side luminium 233 ** Unit feet ZGF.0913 required Sizes 1 to 8 * 0, if irrespective of size Order code Z G F Valves MTRIX 2000 MTRIX 3000/4000 Terminal box Drive Operating voltage/circuit 2-point 230 V 2) T open/ close 24 V 1), 2) Q 3-point open/ stop/ close ontinuous 230 V R 24 V 1) N 230 V + 2 contacts 0/ V = 24 V 1) S onnection/shut-off Inlet/outlet flow with outside thread 0 Inlet/outlet with solder fitting 1 Inlet/outlet + ball trap with external thread 2 Inlet/outlet + ball trap with solder fitting 3 Inlet + ball trap/ outlet + shut-off valve with external thread 4 Inlet + ball trap/ outlet + shut-off valve with solder fitting 5 ool / heat circuit 3 k vs values ooling/heating ) ) Medium connection Left L Right R 1) 24 V-transformer to be provided by others 2) kvs-values for open/close actuators (T,Q) only kvs 1.6 and 2.5 possible Order code V G F 3 ooling/heating circuit PR G Subject to change R5-01/

30 func ontrols Recirculating-ir Unit Heating or ooling 2-pipe chilled or warm water and auxiliary electric heating, sizes 1 to 8 Flex-Geko omfort Edition DencoHappel MTRIX 2000 not applicable DencoHappel MTRIX 4000 System features MTRIX 4000: Temperature assignment.: (default ) ssignment of speed stage djustable regulating range hange-over between normal/economy mode on control panel Input for change-over between normal/economy mode or unit OFF with frost protection Room temperature measurement using control panel External room temperature sensor can be connected Valve control (2 or 3 point) Temperature control via fan and/or valve Room frost protection Status messages using LED Status and alarm signal via volt free change-over contacts Unit individual and group control Isolation of individual units in case of fault Motor temperature monitoring (with speed stage motors T required) Network-enabled Summer / winter compensation Noiseless valve control ool and/or heat request via volt-free contacts (related to water circuit) Stand alone unit control Inputs for operating mode: Normal mode Economy mode utonomous mode Unit OFF Regulation of multi-stage electrical heating with disconnection in case of over-temperature MTRIX OP30 ontrol panel for MTRIX 4000 Pure white casing, protection type IP20 Setpoint temperature setting Speed-stage selection switch 0-(uto) (depends on motor type, with E motor up to 5 stages) LEDs for operation/fault/ext.control Integrated room temperature sensor MTRIX OP31 s for control panel OP30, but also with: Normal/economy mode buttons MTRIX OP44 s for control panel OP31, but also with button for: hangeover between recirculating-air/mixed-air operation hange-over heating/cooling/automatic mode MTRIX OP50 ontrol panel for MTRIX 4000 Pure white casing, protection type IP20 Menu-guided controls using rotation navigator LD display with plain-text display Status messages using pictograms Integrated room temperature sensor MTRIX OP51 s for control panel OP50, but also with: Integrated weekly clock timer with holiday and special days programme D E F MTRIX.IR Infrared remote control for MTRIX 4000 lack casing, RL 9004 LD display approx. 45x30 mm Function as in OP44 (without status, alarm and external control signals, no integrated room temperature sensor) Maximum range 20 m Speed-stage selection switch 0-(uto) (depends on motor type, with E motor up to 5 stages) % on off send - + N 30 PR G Subject to change R5-01/2017

31 Flex-Geko omfort Edition ontrols Recirculating-ir Unit Heating or ooling 2-pipe chilled or warm water and auxiliary electric heating, sizes 1 to 8 Master unit 230 V~ 50 Hz Slave units V~ 50 Hz e.g. 2x2x0.5 Helukabel e. g. 1x2x0.5 Helukabel 3x1.5 mm 2 NYM 3x1.5 mm 2 NYM ooling/heat.medium 2x2x0.8 J-Y(ST)Y flow sensor 230 V ~ 50 Hz 3x2.5 mm 2 NYM 3x2.5 mm 2 NYM 230 V ~ 50 Hz 230 V ~ 50 Hz Speed E motor Speeds Stand alone unit control with operating- and Fault signal Input unit OFF with room frost protection Input economy contact Noiseless valve control ontact heat and cool request onnection external sensor ontinuous up to 3 speed Without return air sensor * 1 With return air sensor * 6 ontrol panel Enclosed control panel Integrated control panel Order code D 4 1 D 4 1 Z D * lternatively room temperature sensor (see Page 98) Master unit Slave unit PR G Subject to change R5-01/

32 Recirculating-ir Unit Heating 2-pipe warm water Sizes 1 to 8 PWW 70/50 t L1 = +20 Flex-Geko omfort Edition Model size Speeds ir volume ooling capacity apacity stage 1 apacity stage 2 apacity stage 3 motor E motor Heating capacity ooling capacity Heating capacity Q K Δp K Q H Δp H Q K Δp K Q H Δp H Q K Δp K Q H Δp H m 3 /h kw kpa kw kpa kw kpa kw kpa kw kpa kw kpa d() d() d() d() < < < ooling capacity Heating capacity Sound power Sound pressure * Sound power Sound pressure * terminal box (with MTRIX metal sheet electrical control box) Speed combination E H Min..Max (E motor) F < motor E motor Motor design Metal sheet electric control box with terminal strip or for integ. ontrols Speed combination T integr. 0 T led out K L M O R Min..Max (E motor) S S 1 S 2 S 3 E Data for capacity stage 4 (S 4) are available on request (see Page 11). 1 Left 2 Right 3 Left 4 Right Wall eiling Medium connect.*** D irculating air / - supply air / irculating air / - supply air / irculating air / - supply air / irculating air / - supply air / ir flow +++ Order code G F U 0 W 0 1 G1 mat filter 2 G2 mat filter 3 G3 mat filter * mbient conditions see Page 70 coustics *** Front connection side, facing discharge + only motor ** ir volume flow for S 1 and filter class G1 +++ Definition of air flow wall/ceiling see Page 74 Filter 32 PR G Subject to change R5-01/2017

33 Flex-Geko omfort Edition ontrols Recirculating-ir Unit Heating 2-pipe warm water, model sizes 1 to 8 ccessories rrangement/ installation Variant/ unit casing Vertical wall/ horizontal ceiling Suitable for air flow designation Discharge grille luminium ode Variant Type ode Discharge plenum primary air connection DN100 Discharge plenum with round fitting DN200 not insulated 012 insulated 022 not insulated 032 insulated 042 Vertical wall/ horizontal ceiling 022 Discharge bend not insulated 052 insulated 062 Vertical wall/ horizontal ceiling luminium Flexible canvas discharge connector 112 Discharge telescopic connection not insulated 152 Vertical wall/ horizontal ceiling D 042 Discharge sound attenuator connector 212 Vertical wall/ horizontal ceiling; with unit foot cover ** Vertical wall/ horizontal ceiling; with unit foot cover ** luminium ir intake plenum with primary air connection DN 125 ir intake plenum with round connection DN 200 not insulated 011 not insulated 031 ir intake bend not insulated 051 ** Unit feet ZGF.0913 required Vertical wall/ horizontal ceiling; with unit foot cover and intake front grille ** Vertical wall/ horizontal ceiling; on front side with unit foot cover and intake front grille ** Horizontal ceiling; closed rear side Vertical stand-alone installation; closed on rear side luminium luminium luminium Intake flexible connection (transition piece required) Transition piece for intake flexible connection, telescopic and sound-attenuator connection Intake telescopic connection (transition piece required) Intake sound attenuator connection for recirculating-air unit (transition piece required) Seal cap for round fitting, DN 200 * not insulated insulated 713 Unit feet for recirculating-air units * 913 Spare filter (5 pieces) G1 813 G2 823 G3 833 Sizes 1 to 8 * 0, if irrespective of size Order code Z G F Valves MTRIX 500 MTRIX 2000 MTRIX 3000/4000 Terminal box Drive Operating voltage/circuit 2-point 230 V 2) T open/ close 1), 2) 24 V Q 3-point 230 V R open/ stop/ 24 V 1) N close 230 V + 2 contacts ontinuous 0/ V = 24 V 1) S onnection/shut-off Inlet/outlet flow with outside thread 0 Inlet/outlet with solder fitting 1 Inlet/outlet + ball trap with external thread 2 Inlet/outlet + ball trap with solder fitting 3 Inlet + ball trap/ outlet + shut-off valve with external thread 4 Inlet + ball trap/ outlet + shut-off valve with solder fitting 5 Heating circuit 2 3 k vs values Heating ) ) Medium connection Left L Right R 1) 24 V-transformer to be provided by others 2) kvs-values for open/close actuators (T,Q) only kvs 1.6 and 2.5 possible Order code V G F Heating circuit PR G Subject to change R5-01/

34 on func send % ontrols Recirculating-ir Unit Heating 2-pipe warm water, model sizes 1 to 8 Flex-Geko omfort Edition DencoHappel MTRIX 2000 System features MTRIX 2000: Extended temperature assignment.: (default ) Manual assignment of speed stage djustable regulating range hange-over between normal/economy mode on control panel Room temperature measurement using control panel External room temperature sensor can be connected Valve control (2-point) Temperature control via fan speed change and valve(s) Status messages using LED Group control Group switch-off switch-off in case of fault Motor temperature monitoring (T required) Network-enabled MTRIX OP21 ontrol panel for MTRIX 2000 Pure white casing, protection type IP20 Setpoint temperature setting Speed stage selection switch 0- (uto) Economy mode button LEDs for operation/fault/ext.control Integrated room temperature sensor DencoHappel MTRIX 3000/4000 System features MTRIX 3000: Temperature assignment.: (default ) Speed (stage) assignment djustable regulating range hange-over between normal/economy mode on control panel Input for change-over between normal/economy mode or unit OFF with frost protection Room temperature measurement using control panel External room temperature sensor can be connected Valve control (2x2 or 2x3 point) Temperature control via fan and/or valve(s) Room frost protection Status messages using LED Status and fault signals using floating change-over contacts Unit individual and group control Isolation of individual units in case of fault Motor temperature monitoring (with speed stage motors T required) Network-enabled dditional features MTRIX 4000: Summer / winter compensation Noiseless valve control ool and/or heat request via volt-free contacts (related to water circuit) Stand alone unit control Inputs for operating mode: Normal mode Economy mode utonomous mode Unit OFF MTRIX OP30 ontrol panel for MTRIX 3000/4000 Pure white casing, protection type IP20 Setpoint temperature setting Speed-stage selection switch 0-(uto) (depends on motor type, with E motor up to 5 stages) LEDs for operation/fault/ext.control Integrated room temperature sensor MTRIX OP31 s for control panel OP30, but also with: Normal/economy mode buttons MTRIX OP44 s for control panel OP31, but also with button for: hangeover between recirculating-air/ mixed-air operation hange-over heating/cooling/automatic mode MTRIX OP50 ontrol panel for MTRIX 3000/4000 Pure white casing, protection type IP20 Menu-guided controls using rotation navigator LD display with plain-text display Status messages using pictograms Integrated room temperature sensor ontinuous speed regulation (only together with E motor) MTRIX OP51 s for control panel OP50, but also with: Integrated weekly clock timer with a holiday and special days programme D E F MTRIX.IR Infrared remote control for MTRIX 3000/4000 lack casing, RL 9004 LD display approx. 45x30 mm Function as in OP44 (without status, fault and external control signals, no integrated room temperature sensor) Maximum range 20 m Speed-stage selection switch 0-(uto) (depends on motor type, with E motor up to 5 stages) off - + N 34 PR G Subject to change R5-01/2017

35 Flex-Geko omfort Edition ontrols Recirculating-ir Unit Heating 2-pipe warm water, model sizes 1 to 8 Master unit Slave units D2: 1-15 D2 = 5x2x0.8 J-Y(ST)Y D2 = 4x2x0.8 J-Y(ST)Y 3x1.5 mm 2 NYM 3x1.5 mm 2 NYM Heating medium 230 V ~ 50 Hz without return air sensor * 0 with return air sensor * 5 Enclosed control panel Integrated control panel Order code MTRIX 500 D T D Z D Order code MTRIX 2000 D D Z D e.g. 2x2x0.5 Helukabel Master unit With controller type: D2 = 4x2x0.8 J-Y(ST)Y D3/4 = e.g. 1x2x0.5 Helukabel Slave units x1.5 mm 2 NYM 3x1.5 mm 2 NYM Heating medium 230 V ~ 50 Hz Speed (E motor) Speed stages ( motor) ontinuous Stand alone unit control with operating and Fault signal Group regulation with status and alarm signal Input unit OFF with room frost protection Input economy contact Supply temperature limitation Noiseless valve control ontact heat request onnection external sensor to 3-speed up to 5 speed Without return air sensor * 0 With return air sensor * 5 ontrol panel Enclosed control panel Integrated control panel Order code D 0 D 0 Z D * lternatively room temperature sensor (see Page 98) Master unit Slave unit PR G Subject to change R5-01/

36 Recirculating-ir Unit Heating Full Electric Heating Sizes 1 to 8 Electric heater 3x400V~N/P/E 50Hz Flex-Geko omfort Edition Model size Speeds ir volume ooling capacity apacity stage 1 Full electric heating Sound power motor Q K Δp K Q H Δp H m 3 /h kw kpa kw kpa d() d() Metal-sheet electric control box with terminal block or for integrated controls Sound pressure * motor Motor design T integr. 0 T led out Speed combination M S 1 1 Right Wall 3 Right eiling Electric connection *** Recirculating air / supply air / irculating air / - supply air / ir flow G1 mat filter 2 G2 mat filter Filter Order code G F 1 U 0 E M 0 * mbient conditions see Page 70 coustics *** Front connection side, facing discharge ** ir volume flow for S 1 and filter class G1 +++ Definition of air flow wall/ceiling see Page PR G Subject to change R5-01/2017

37 Flex-Geko omfort Edition ccessories/valves Recirculating-ir Unit Heating Full electric heating, model sizes 1 to 8 ccessories rrangement/ installation Variant/ unit casing Vertical wall/ horizontal ceiling Suitable for air flow designation Discharge grille luminium ode 013 Variant Type ode Discharge plenum primary air connection DN100 not insulated 012 Discharge bend not insulated 052 Vertical wall/horizontal ceiling luminium 033 Discharge telescopic connection not insulated 152 Vertical wall/horizontal ceiling; with unit foot cover ** luminium 053 ir intake plenum with primary air connection DN 125 not insulated 011 Vertical wall/horizontal ceiling; with unit foot cover and intake front grille ** luminium 073 ir intake bend not insulated 051 Transition piece for intake telescopic connection 131 Horizontal ceiling; closed on rear side luminium 133 Intake telescopic connection (transition piece required) not insulated 151 Vertical stand-alone installation closed on rear side luminium 233 Unit feet for recirculating-air units * 913 ** Unit feet ZGF.0913 required Spare filter (5 pieces) G1 813 G2 823 Sizes 1 to 8 * 0, if irrespective of size Order code Z G F PR G Subject to change R5-01/

38 func send ontrols Recirculating-ir Unit Heating Full electric heating, model sizes 1 to 8 Flex-Geko omfort Edition DencoHappel MTRIX 2000 not applicable DencoHappel MTRIX 4000 System features MTRIX 4000: Temperature assignment.: (default ) ssignment of speed stage djustable regulating range hange-over between normal/economy mode on control panel Input for change-over between normal/economy mode or unit OFF with frost protection Room temperature measurement using control panel External room temperature sensor can be connected Temperature control via fan Room frost protection Status messages using LED Status and alarm signal via volt free change-over contacts Unit individual and group control Isolation of individual units in case of fault Motor temperature monitoring (T required) Network-enabled Summer / winter compensation Stand alone unit control Inputs for operating mode: Normal mode Economy mode utonomous mode Unit OFF Regulation of multi-stage electrical heating with disconnection in case of over-temperature Motor temperature monitoring (with speed stage motors T required) MTRIX OP30 ontrol panel for MTRIX 4000 Pure white casing, protection type IP20 Setpoint temperature setting Speed stage selection switch 0-(uto) LEDs for operation/fault/ext.control Integrated room temperature sensor MTRIX OP31 s for control panel OP30, but also with: Normal/economy mode buttons MTRIX OP50 ontrol panel for MTRIX 4000 Pure white casing, protection type IP20 Menu-guided controls using rotation navigator LD display with plain-text display Status messages using pictograms Integrated room temperature sensor MTRIX OP51 s for control panel OP50, but also with: Integrated weekly clock timer with holiday and special days programme MTRIX.IR Infrared remote control for control system MTRIX 4000 lack casing, RL 9004 LD display approx. 45x30 mm Function as in OP44 (without status, alarm and external control signals, no integrated room temperature sensor) Maximum range 20 m Speed stage selection switch 0-(uto) % on off - + E F N 38 PR G Subject to change R5-01/2017

39 Flex-Geko omfort Edition ontrols Recirculating-ir Unit Heating Full electric heating, model sizes 1 to 8 Master unit 3x400 V~ 50 Hz Slave units x400 V~ 50 Hz e.g. 2x2x0.5 Helukabel e. g. 1x2x0.5 Helukabel 3x1.5 mm 2 NYM 3x1.5 mm 2 NYM 230 V ~ 50 Hz 5x2.5 mm 2 NYM 5x2.5 mm 2 NYM 400 V ~ 50 Hz 400 V ~ 50 Hz Speeds Stand alone unit control with operating and Fault signal Input unit OFF with room frost protection Input economy contact ontact heat request onnection external sensor up to 3 speed Without return air sensor * 2 With return air sensor * 7 ontrol panel Enclosed control panel Integrated control panel Order code D 4 0 D 4 0 Z D * lternatively room temperature sensor (see Page 98) Master unit Slave unit PR G Subject to change R5-01/

40 Recirculating-ir Unit ooling 2-pipe chilled water Sizes 1 to 8 WP 6/12 t L1 = +27 ϕ 1 = 46 % r.h. Flex-Geko omfort Edition Model size Speeds ir volume ooling capacity apacity stage 1 apacity stage 2 apacity stage 3 -motor E motor Heating capacity ooling capacity Heating capacity Q K Δp K Q H Δp H Q K Δp K Q H Δp H Q K Δp K Q H Δp H m 3 /h kw kpa kw kpa kw kpa kw kpa kw kpa kw kpa d() d() d() d() < < < ooling capacity Heating capacity Sound power Sound pressure * Sound power Sound pressure * terminal box (with MTRIX metal sheet electrical control box) Speed combination E H Min..Max (E motor) F < motor E motor Motor design Metal sheet electric control box with terminal strip or for integ. ontrols Speed combination T integr. 0 T led out K L M O R Min..Max (E motor) S S 1 S 2 S 3 E Data for capacity stage 4 (S 4) are available on request (see Page 11). Order code G F U W 0 1 Left 2 Right 3 Left 4 Right 0 With drainage 1 With condensate pump Wall eiling irculating air / supply air / irculating air / - supply air / ** irculating air / - supply air / D irculating air / - supply air / ** 1 G1 mat filter 2 G2 mat filter 3 G2 mat filter * mbient conditions see Page 70 coustics ** Only wall units *** Front connection side, facing discharge + only motor ** ir volume flow for S 1 and filter class G1 Medium connect.*** ondensate line ir flow +++ Filter 40 PR G Subject to change R5-01/2017

41 Flex-Geko omfort Edition ccessories/valves Recirculating-ir Unit ooling 2-pipe system chilled water, model sizes 1 to 8 ccessories rrangement/ installation Variant/ unit casing Vertical wall/ horizontal ceiling Vertical wall Vertical wall/ horizontal ceiling Vertical wall Vertical wall/ horizontal ceiling; with unit foot cover ** Suitable for air flow designation D Discharge grille luminium luminium luminium ode Variant Type ode Discharge plenum primary air connection DN100 insulated 022 Discharge plenum with round fitting DN200 insulated 042 Discharge bend insulated 062 Flexible canvas discharge connector 112 Discharge sound attenuator connector 212 Geko-Drive motorized regulated discharge profile *** ir intake plenum with primary air connection DN 125 ir intake plenum with round connection DN 200 Left 412 Right 422 not insulated 011 not insulated 031 Vertical wall; with unit foot cover ** Vertical wall/horizontal ceiling; with unit foot cover and intake front grille ** luminium ir intake bend not insulated 051 Intake flexible connection (transition piece required) Transition piece for intake flexible connection, telescopic and sound-attenuator connection Vertical wall, with unit foot cover and intake front grille ** Horizontal ceiling; closed rear side luminium Intake telescopic connection (transition piece required) not insulated 151 Intake sound attenuator connection for 211 recirculating-air unit (transition piece required) Seal cap for round insulated 713 fitting, DN 200 * ** Unit feet ZGF.0913 required Vertical stand-alone installation closed on rear side luminium Unit feet for recirculating-air units * 913 Spare filter (5 pieces) G1 813 G2 823 G3 833 Sizes 1 to 8 * 0, if irrespective of size Order code Z G F *** Note! Geko-Drive only together with unit casing! Valves MTRIX 500 MTRIX 2000 MTRIX 3000/4000 Terminal box Drive Operating voltage/circuit 2-point 230 V 2) T open/ close 24 V 1), 2) Q 3-point open/ stop/ close ontinuous 230 V R 24 V 1) N 230 V + 2 contacts 0/ V = 24 V 1) S onnection/shut-off Inlet/outlet flow with outside thread 0 Inlet/outlet with solder fitting 1 Inlet/outlet + ball trap with external thread 2 Inlet/outlet + ball trap with solder fitting 3 Inlet + ball trap/ outlet + shut-off valve with external thread 4 Inlet + ball trap/ outlet + shut-off valve with solder fitting 5 ooling circuit 2 3 k vs values ooling ) ) Medium connection Left L Right R 1) 24 V-transformer to be provided by others 2) kvs-values for open/close actuators (T,Q) only kvs 1.6 and 2.5 possible Order code V G F ooling circuit PR G Subject to change R5-01/

42 on func send % ontrols Recirculating-ir Unit ooling 2-pipe system chilled water, model sizes 1 to 8 DencoHappel MTRIX 2000 System features MTRIX 500/2000: Extended temperature assignment.: (default ) Manual assignment of speed stage djustable regulating range hange-over between normal/economy mode on control panel Room temperature measurement using control panel External room temperature sensor can be connected Valve control (2-point) Temperature control via fan speed change and valve(s) Status messages using LED Group control Group switch-off switch-off in case of fault Motor temperature monitoring (T required) Network-enabled MTRIX OP21 ontrol panel for MTRIX 2000 Pure white casing, protection type IP20 Setpoint temperature setting Speed stage selection switch 0- (uto) Economy mode button LEDs for operation/fault/ext.control Integrated room temperature sensor Flex-Geko omfort Edition DencoHappel MTRIX 3000/4000 System features MTRIX 3000: Temperature assignment.: (default ) Speed (stage) assignment djustable regulating range hange-over between normal/economy mode on control panel Input for change-over between normal/economy mode or unit OFF with frost protection Room temperature measurement using control panel External room temperature sensor can be connected Valve control (2x2 or 2x3 point) Temperature control via fan and/or valve(s) Room frost protection Status messages using LED Status and fault signals using floating change-over contacts Unit individual and group control Isolation of individual units in case of fault Motor temperature monitoring (with speed stage motors T required) Network-enabled MTRIX OP30 ontrol panel for MTRIX 3000/4000 Pure white casing, protection type IP20 Setpoint temperature setting Speed-stage selection switch 0-(uto) (depends on motor type, with E motor up to 5 stages) LEDs for operation/fault/ext.control Integrated room temperature sensor MTRIX OP31 s for control panel OP30, but also with: Normal/economy mode buttons MTRIX OP44 s for control panel OP31, but also with button for: hangeover between recirculating-air/ mixed-air operation hange-over heating/cooling/automatic mode D MTRIX OP50 ontrol panel for MTRIX 3000 Pure white casing, protection type IP20 Menu-guided controls using rotation navigator LD display with plain-text display Status messages using pictograms Integrated room temperature sensor ontinuous speed regulation (only together with E motor) MTRIX OP51 s for control panel OP50, but also with: Integrated weekly clock timer with a holiday and special days programme E F MTRIX.IR Infrared remote control for MTRIX 3000 lack casing, RL 9004 LD display approx. 45x30 mm Function as in OP44 (without status, fault and external control signals, no integrated room temperature sensor) Maximum range 20 m Speed-stage selection switch 0-(uto) (depends on motor type, with E motor up to 5 stages) off - + N 42 PR G Subject to change R5-01/2017

43 Flex-Geko omfort Edition ontrols Recirculating-ir Unit ooling 2-pipe system chilled water, model sizes 1 to 8 D2 = 5x2x0.8 J-Y(ST)Y Master unit With controller type: D2 = 4x2x0.8 J-Y(ST)Y Slave units x1.5 mm 2 NYM 3x1.5 mm 2 NYM ooling medium 230 V ~ 50 Hz Without return air sensor * 0 With return air sensor * 5 Enclosed control panel Integrated control panel Order code MTRIX 2000 D D Z D e.g. 2x2x0.5 Helukabel Master unit With controller type: D2 = 4x2x0.8 J-Y(ST)Y D3/4 = e.g. 1x2x0.5 Helukabel Slave units x1.5 mm 2 NYM 3x1.5 mm 2 NYM ooling medium 230 V ~ 50 Hz Speed (E motor) Speed stages ( motor) Stand alone unit control with operating and Fault signal Group regulation with status and alarm signals Input unit OFF with room frost protection Input economy contact Supply temperature limitation Noiseless valve control ontact heat and cool request Geko-Drive ontinuous up to 3 speed onnection external sensor up to 5 speed Without return air sensor * 0 With return air sensor * 5 ontrol panel Enclosed control panel Integrated control panel Regulation of external heating valve on request Order code D 0 D 0 Z D * lternatively room temperature sensor (see Page 98) Master unit Slave unit PR G Subject to change R5-01/

44 Recirculating-ir Unit ooling Direct evaporator Sizes 1 to 8 t o = 10 t L1 = +27 ϕ 1 = 46 % r.h. Refrigerant: R410 Flex-Geko omfort Edition ++ apacity stage 1 motor E motor Motor design Model size Speeds ir volume ooling capacity Heating capacity Sound power Sound pressure * Sound power Sound pressure * motor E motor T integr. 0 T led out 1 E Q K Q H Δp H m 3 /h kw kw kpa d() d() d() d() Metal sheet electric control box with terminal block or for integ. ontrols Speed combination M Min..Max (E motor) S S 1 1 Left 2 Right 3 Left 4 Right 0 With drainage 1 With condensate pump irculating air / supply air / Wall eiling irculating air / - supply air / ** irculating air / - supply air / D irculating air / - supply air / ** Medium connect.*** ondensate line ir flow G1 mat filter 2 G2 mat filter Filter Order code G F 1 U D 0 M * mbient conditions see Page 70 coustics ** Only wall units *** Front connection side, facing discharge ** ir volume flow for S 1 and filter class G1 +++ Definition of air flow wall/ceiling see Page PR G Subject to change R5-01/2017

45 Flex-Geko omfort Edition ccessories/valves Recirculating-ir Unit ooling DX evaporator, model sizes 1 to 8 ccessories rrangement/ installation Variant/ unit casing Vertical wall/ horizontal ceiling Suitable for air flow designation Discharge grille luminium ode Variant Type ode Discharge plenum primary air connection DN100 insulated 022 Discharge bend insulated 062 * Vertical wall Vertical wall/ horizontal ceiling luminium Flexible canvas discharge connector 112 Geko-Drive motorized regulated discharge profile *** ir intake plenum with primary air connection DN 125 Left 412 Right 422 not insulated 011 Vertical wall Vertical wall/ horizontal ceiling; with unit foot cover ** D luminium ir intake bend not insulated 051 Intake flexible connection (transition piece required) Transition piece for intake flexible connection, telescopic connection Vertical wall; with unit foot cover ** 062 Intake telescopic connection (transition piece required) not insulated 151 Vertical wall/horizontal ceiling; with unit foot cover and intake front grille ** Vertical wall, with unit foot cover and intake front grille ** luminium Unit feet for recirculating-air units * 913 Spare filter (5 pieces) G1 813 G2 823 Horizontal ceiling; closed rear side luminium Vertical stand-alone installation closed on rear side luminium ** Unit feet ZGF.0913 required Sizes 1 to 8 * 0, if irrespective of size Order code Z G F *** Note! Geko-Drive only together with unit casing! Valves Expansion valve R410 Setting of expansion valve S1-S8 Medium connection Left L Right R Order code V G F E 0 0 ooling circuit PR G Subject to change R5-01/

46 func send ontrols Recirculating-ir Unit ooling DX evaporator, model sizes 1 to 8 Flex-Geko omfort Edition DencoHappel MTRIX 2000 not applicable DencoHappel MTRIX 3000/4000 System features MTRIX 3000: Temperature assignment.: (default ) Speed (stage) assignment djustable regulating range hange-over between normal/economy mode on control panel Input for change-over between normal/economy mode or unit OFF with frost protection Room temperature measurement using control panel External room temperature sensor can be connected Temperature control via fan Status messages using LED Status and alarm signal via volt free change-over contacts Unit individual and group control Isolation of individual units in case of fault Motor temperature monitoring (with speed stage motors T required) Network-enabled dditional features MTRIX 4000: Summer compensation Stand alone unit control Inputs for operating mode: Normal mode Economy mode utonomous mode Unit OFF MTRIX OP30 ontrol panel for MTRIX 3000/4000 Pure white casing, protection type IP20 Setpoint temperature setting Speed-stage selection switch 0-(uto) (depends on motor type, with E motor up to 5 stages) LEDs for operation/fault/ext.control Integrated room temperature sensor MTRIX OP31 s for control panel OP30, but also with: Normal/economy mode buttons MTRIX OP50 ontrol panel for MTRIX 3000/4000 Pure white casing, protection type IP20 Menu-guided controls using rotation navigator LD display with plain-text display Status messages using pictograms Integrated room temperature sensor ontinuous speed assignment (only in connection with E motor) MTRIX OP51 s for control panel OP50, but also with: Integrated weekly clock timer with holiday and special days programme MTRIX.IR Infrared remote control for control system MTRIX 3000/4000 lack casing, RL 9004 LD display approx. 45x30 mm Function as in OP44 (without status, alarm and external control signals, no integrated room temperature sensor) Maximum range 20 m Speed-stage selection switch 0-(uto) (depends on motor type, with E motor up to 5 stages) % on off - + E F N 46 PR G Subject to change R5-01/2017

47 Flex-Geko omfort Edition ontrols Recirculating-ir Unit ooling DX evaporator, model sizes 1 to 8 Master unit Slave units 1-15 e.g. 2x2x0.5 Helukabel e. g. 1x2x0.5 Helukabel 3x1.5 mm 2 NYM 3x1.5 mm 2 NYM ooling medium 230 V ~ 50 Hz 1x2x0.5 Helukabel 3x1.5 mm 2 NYM RF Modules ompressors Speeds E motor ontinuous up to 3 speed Speed stages motor Stand alone unit control with operating and Fault signal Input unit OFF Input economy contact onnection external sensor Without return air sensor * 4 With return air sensor * 9 ontrol panel Enclosed control panel Integrated control panel Regulation of external heating valve on request Order code D 0 D 0 Z D * lternatively room temperature sensor (see Page 98) Master unit Slave unit PR G Subject to change R5-01/

48 Mixed-ir Unit Heating and ooling 4-pipe chilled and warm water Sizes 1 to 8 WP 6/12 t L1 = +27 ϕ 1 = 46 % r.h. PWW 70/50 t L1 = +10 Flex-Geko omfort Edition Model size Speeds ir volume ooling capacity apacity stage 1 apacity stage 2 -motor E motor Heating capacity ooling capacity Q K Δp K Q H Δp H Q K Δp K Q H Δp H m 3 /h kw kpa kw kpa kw kpa kw kpa d() d() d() d() Heating capacity Sound power terminal box (select sheet steel electric control box with MTRIX) < < Speed combination E H Min..Max (E motor) F < Metal-sheet electric control box with terminal block or for integrated controls Speed combination K L M O R Min..Max (E motor) S S 1 S 2 Data for capacity stage 3 (S 3) are available on request (see Page 11). Order code G F M W W Sound pressure * Sound power Sound pressure * 1 Left 2 Right 3 Left 4 Right Wall eiling Medium connect.*** 0 With drainage ondensate 1 With condensate pump pipework Fresh / - circulating / - supply air / Fresh / circulating / supply air / ** Fresh / - circulating / - supply air / D Fresh / circulating / supply air / ** 1 G1 mat filter 2 G2 mat filter 3 G3 mat filter motor E motor Motor design T integr. 0 T led out 1 * mbient conditions refer to Page 70 coustics ** Only wall units *** Front connection side, facing discharge + only motor ** ir volume flow for S 1 and filter class G1 +++ Definition of air flow wall/ceiling see Page 74 E ir flow +++ Filter 48 PR G Subject to change R5-01/2017

49 Flex-Geko omfort Edition ccessories rrangement/ installation Variant/ unit casing Vertical wall/ horizontal ceiling; with unit foot cover and intake front grille Vertical wall; on front side with unit foot cover and intake front grille Suitable for air flow designation,, D Discharge grille luminium ode ccessories/valves Mixed-ir Unit Heating and ooling 4-pipe system chilled and warm water Sizes 1 to 8 Variant Type ode Discharge plenum primary air connection DN100 insulated 022 Discharge plenum with round fitting DN200 insulated 042 Discharge bend insulated 062 Flexible canvas discharge connector 112 Discharge sound attenuator connector 212 Geko-Drive motorized regulated discharge profile ** Intake fitting for sound attenuator for mixed-air units Left 412 Right Frame for in-wall installation for outside air intake connection 311 External weather grille, RL 9006 paint 331 Installation frame for weather protection grille 371 Seal cap for round fitting, DN 200 * Spare filter (5 pieces) insulated 713 G1 813 G2 823 G3 833 Sizes 1 to 8 * 0, if irrespective of size Order code Z G F ** NOTE! Geko-Drive only together with unit casing! Valves MTRIX 2000 MTRIX 3000/4000 Terminal box Drive Operating voltage/circuit 3-point 230 V R open/ stop/ 24 V 1) N close 230 V + 2 contacts ontinuous 0/ V = 24 V 1) S onnection/shut-off Inlet/outlet flow with outside thread 0 Inlet/outlet with solder fitting 1 Inlet/outlet + ball trap with external thread 2 Inlet/outlet + ball trap with solder fitting 3 Inlet + ball trap/ outlet + shut-off valve with external thread 4 Inlet + ball trap/ outlet + shut-off valve with solder fitting 5 Heating circuit ooling circuit 2 3 k vs values ooling/heating Medium connection Left L Right R 1) 24 V-transformer to be provided by others Order code V G F 3 ooling circuit Heating circuit PR G Subject to change R5-01/

50 func send ontrols Mixed-ir Unit Heating and ooling 4-pipe system chilled and warm water Sizes 1 to 8 Flex-Geko omfort Edition DencoHappel MTRIX 2000 not applicable DencoHappel MTRIX 4000 System features MTRIX 4000: Temperature assignment.: (default ) Speed (stage) assignment djustable regulating range hange-over between normal/economy mode on control panel Input for change-over between normal/economy mode or unit OFF with frost protection Room temperature measurement using control panel External room temperature sensor can be connected Valve control (2x3 point) Temperature control via fan and/or valve(s) Room frost protection Status messages using LED Status and alarm signal via volt free change-over contacts Unit individual and group control Isolation of individual units in case of fault Motor temperature monitoring (with speed stage motors T required) Network-enabled MTRIX OP30 ontrol panel for MTRIX 4000 Pure white casing, protection type IP20 Setpoint temperature setting Speed-stage selection switch 0-(uto) (depends on motor type, with E motor up to 5 stages) LEDs for operation/fault/ext.control Integrated room temperature sensor MTRIX OP31 s for control panel OP30, but also with: Normal/economy mode buttons MTRIX OP44 s for control panel OP31, but also with button for: hangeover between recirculating-air/ mixed-air operation hange-over heating/cooling/automatic mode D dditional features MTRIX 4000: Summer / winter compensation Noiseless valve control ool and/or heat request via volt-free contacts (related to water circuit) Stand alone unit control Inputs for operating mode: Normal mode Economy mode utonomous mode Unit OFF Mixing-air damper control open/close with frost protection MTRIX OP50 ontrol panel for MTRIX 4000 Pure white casing, protection type IP20 Menu-guided controls using rotation navigator LD display with plain-text display Status messages using pictograms Integrated room temperature sensor ontinuous speed assignment (only in connection with E motor) MTRIX OP51 s for control panel OP50, but also with: Integrated weekly clock timer with holiday and special days programme E F MTRIX.IR Infrared remote control for MTRIX 4000 lack casing, RL 9004 LD display approx. 45x30 mm Function as in OP44 (without status, alarm and external control signals, no integrated room temperature sensor) Maximum range 20 m Speed-stage selection switch 0-(uto) (depends on motor type, with E motor up to 5 stages) % on off - + N 50 PR G Subject to change R5-01/2017

51 Flex-Geko omfort Edition ontrols Mixed-ir Unit Heating and ooling 4-pipe system chilled and warm water Sizes 1 to 8 Master unit Slave units 1-15 e.g. 2x2x0.5 Helukabel e. g. 1x2x0.5 Helukabel 3x1.5 mm 2 NYM 3x1.5 mm 2 NYM ooling/heat.medium 230 V ~ 50 Hz Speed (E motor) Speed stages ( motor) Stand alone unit control with operating and Fault signal Input unit OFF with room frost protection Input economy contact Supply temperature limitation Noiseless valve control ontact heat and cool request Geko-Drive onnection external sensor ontinuous up to 3 speed up to 5 speed without return air sensor * 0 with return air sensor * 5 ontrol panel Enclosed control panel Integrated control panel Order code D 4 5 D 4 5 Z D * lternatively room temperature sensor (see Page 98) Master unit Slave unit PR G Subject to change R5-01/

52 Mixed-ir Unit Heating and ooling Direct Evaporator and 2-pipe warm water Sizes 1 to 8 t o = 10 t L1 = +27 ϕ 1 = 46 % r.h. Refrigerant: R410 PWW 70/50 t L1 = +10 Flex-Geko omfort Edition Model size Speeds ++ ir volume ooling capacity apacity stage 1 motor E motor Heating capacity Sound power Q K Q H Δp H m 3 /h kw kw kpa d() d() d() d() Sound pressure * Sound power Sound pressure * Metal sheet electric control box with terminal block or for integ. ontrols Speed combination M Min..Max (E motor) S S 1 Motor thermal contact 5-speed motor E motor T integr. 0 T led out 1 E 1 Left 2 Right 3 Left 4 Right Wall eiling Medium connect.*** 0 With drainage ondensate 1 With condensate pump pipework Fresh air / - circulating air / - supply air / Fresh air / - circulating air / - supply air / ** Fresh air / - circulating air / - supply air / D Fresh air / - circulating air / - supply air / ** 1 G1 mat filter 2 G2 mat filter ir flow +++ Filter Order code G F 1 M D W M * mbient conditions see Page 70 coustics ** Only wall units *** Front connection side, facing discharge ** ir volume flow for S 1 and filter class G1 +++ Definition of air flow wall/ceiling see Page PR G Subject to change R5-01/2017

53 Flex-Geko omfort Edition ccessories/valves Mixed-ir Unit Heating and ooling DX evaporator and 2-pipe warm water, model sizes 1 to 8 ccessories rrangement/ installation Variant/ unit casing Vertical wall/ horizontal ceiling; with unit foot cover and intake front grille Suitable for air flow designation, Discharge grille luminium ode Variant Type ode Discharge plenum primary air connection DN100 insulated 022 Discharge bend insulated 062 Vertical wall; on front side with unit foot cover and intake front grille, D 082 Flexible canvas discharge connector 112 Geko-Drive motorized regulated discharge profile ** left 412 right 422 Frame for in-wall installation for outside air intake connection 311 External weather grille, RL 9006 paint 331 Installation frame for weather protection grille 371 Spare filter (5 pieces) G1 813 G2 823 Sizes 1 to 8 * 0, if irrespective of size Order code Z G F ** NOTE! Geko-Drive only together with unit casing! Valves MTRIX 2000 MTRIX 3000/4000 Terminal box Drive Operating voltage/circuit 3-point 230 V R open/ stop/ 24 V 1) N close 230 V + 2 contacts ontinuous 0/ V = 24 V 1) S DX connection via expansion valve 3) 0 Expansion valve R410 3) E onnection/blocking (not DX) Inlet/outlet flow with outside thread 0 Inlet/outlet with solder fitting 1 Inlet/outlet + ball trap with external thread 2 Inlet/outlet + ball trap with solder fitting 3 Inlet + ball trap/ outlet + shut-off valve with external thread 4 Inlet + ball trap/ outlet + shut-off valve with solder fitting 5 DX connection 3) with/ without expansion valve Heating circuit 0 3 k vs values ooling/heating DX without 3) expansion valve 00 Setting of expansion valve 3) S1-S8 Medium connection Left L right R 1) 24 V-transformer to be provided by others 3) Only cooling circuit Order code V G F 0 3 ooling circuit Heating circuit PR G Subject to change R5-01/

54 func send ontrols Mixed-ir Unit Heating and ooling DX evaporator and 2-pipe warm water, model sizes 1 to 8 Flex-Geko omfort Edition DencoHappel MTRIX 2000 not applicable DencoHappel MTRIX 4000 System features MTRIX 4000: Temperature assignment.: (default ) Speed (stage) assignment djustable regulating range hange-over between normal/economy mode on control panel Input for change-over between normal/economy mode or unit OFF with frost protection Room temperature measurement using control panel External room temperature sensor can be connected Valve control (3-point) Temperature control via fan and/or valve Room frost protection Status messages using LED Status and alarm signal via volt free change-over contacts Unit individual and group control Isolation of individual units in case of fault Motor temperature monitoring (with speed stage motors T required) Network-enabled Summer / winter compensation Noiseless valve control Heat request via volt-free contact (related to water circuit) Stand alone unit control Inputs for operating mode: Normal mode Economy mode utonomous mode Unit OFF Mixing-air damper control open/close with frost protection MTRIX OP30 ontrol panel for MTRIX 4000 Pure white casing, protection type IP20 Setpoint temperature setting Speed-stage selection switch 0-(uto) (depends on motor type, with E motor up to 5 stages) LEDs for operation/fault/ext.control Integrated room temperature sensor MTRIX OP31 s for control panel OP30, but also with: Normal/economy mode buttons MTRIX OP44 s for control panel OP31, but also with button for: hangeover between recirculating-air/ mixed-air operation hange-over heating/cooling/automatic mode MTRIX OP50 ontrol panel for MTRIX 4000 Pure white casing, protection type IP20 Menu-guided controls using rotation navigator LD display with plain-text display Status messages using pictograms Integrated room temperature sensor ontinuous speed assignment (only in connection with E motor) MTRIX OP51 s for control panel OP50, but also with: Integrated weekly clock timer with holiday and special days programme D E F MTRIX.IR Infrared remote control for MTRIX 4000 lack casing, RL 9004 LD display approx. 45x30 mm Function as in OP44 (without status, alarm and external control signals, no integrated room temperature sensor) Maximum range 20 m Speed-stage selection switch 0-(uto) (depends on motor type, with E motor up to 5 stages) % on off - + N 54 PR G Subject to change R5-01/2017

55 Flex-Geko omfort Edition ontrols Mixed-ir Unit Heating and ooling DX evaporator and 2-pipe warm water, model sizes 1 to 8 Master unit Slave units 1-15 e.g. 2x2x0.5 Helukabel e. g. 1x2x0.5 Helukabel 3x1.5 mm 2 NYM 3x1.5 mm 2 NYM Heating medium 230 V ~ 50 Hz 1x2x0.5 Helukabel 3x1.5 mm 2 NYM ooling medium RF Modules ompressors Speed (E motor) Speed stages ( motor) Stand alone unit control with operating and Fault signal Input unit OFF with room frost protection Input economy contact Noiseless valve control ontact heat and cool request onnection external sensor ontinuous up to 3 speed Without return air sensor * 3 With return air sensor * 8 ontrol panel Enclosed control panel Integrated control panel Order code D 4 5 D 4 5 Z D * lternatively room temperature sensor (see Page 98) Master unit Slave unit PR G Subject to change R5-01/

56 Mixed-ir Unit Heating or ooling 2-pipe chilled or warm water Sizes 1 to 8 WP 6/12 t L1 = +27 ϕ 1 = 46 % r.h. PWW 70/50 t L1 = +10 Flex-Geko omfort Edition Model size Speeds ir volume ooling capacity apacity stage 1 apacity stage 2 apacity stage 3 motor E motor Heating capacity ooling capacity Heating capacity Q K Δp K Q H Δp H Q K Δp K Q H Δp H Q K Δp K Q H Δp H m 3 /h kw kpa kw kpa kw kpa kw kpa kw kpa kw kpa d() d() d() d() < < ooling capacity Heating capacity Sound power Sound pressure * Sound power Sound pressure * terminal box (with MTRIX metal sheet electrical control box) Speed combination E H Min..Max (E motor) F < motor E motor Motor design Metal sheet electric control box with terminal strip or for integ. ontrols Speed combination T integr. 0 T led out K L M O R Min..Max (E motor) S S 1 S 2 S 3 E Data for capacity stage 4 (S 4) are available on request (see Page 11). Order code G F M W 1 Left 2 Right 3 Left 4 Right Wall eiling Medium connect.*** 0 With drainage ondensate 1 With condensate pump pipework Fresh air / -circulating air / - supply air / Fresh air / -circulating air / **supply air / ** Fresh air / -circulating air / - supply air / D Fresh air / -circulating air / ** supply air / ** 1 G1 mat filter 2 G2 mat filter 3 G3 mat filter * mbient conditions see Page 70 coustics ** Only wall units *** Front connection side, facing discharge + only motor ** ir volume flow for S 1 and filter class G1 +++ Definition of air flow wall/ceiling see Page 74 ir flow +++ Filter 56 PR G Subject to change R5-01/2017

57 Flex-Geko omfort Edition ccessories rrangement/installation Variant/ unit casing Suitable for air flow designation Discharge grille ode ccessories/valves Mixed-ir Unit Heating or ooling 2-pipe system chilled or warm water Sizes 1 to 8 Variant Type ode Discharge plenum primary air connection DN100 insulated 022 Vertical wall/ horizontal ceiling; with unit foot cover and intake front grille Vertical wall; on front side with unit foot cover and intake front grille,, D luminium Discharge plenum with round fitting DN200 insulated 042 Discharge bend insulated 062 Flexible canvas discharge connector 112 Discharge sound attenuator connector 212 Geko-Drive motorized regulated discharge profile ** Intake fitting for sound attenuator for mixed-air units Left 412 Right Frame for in-wall installation for outside air intake connection 311 External weather grille, RL 9006 paint 331 Installation frame for weather protection grille 371 Seal cap for round fitting, DN 200 * Spare filter (5 pieces) insulated 713 G1 813 G2 823 G3 833 Sizes 1 to 8 * 0, if irrespective of size Order code Z G F ** NOTE! Geko-Drive only together with unit casing! Valves MTRIX 2000 MTRIX 3000/4000 Terminal box Drive 3-point open/ stop/ close ontinuous Operating voltage/circuit 230 V R 24 V 1) N 230 V + 2 contacts 0/ V = 24 V 1) S onnection/shut-off Inlet/outlet flow with outside thread 0 Inlet/outlet with solder fitting 1 Inlet/outlet + ball trap with external thread 2 Inlet/outlet + ball trap with solder fitting 3 Inlet + ball trap/ outlet + shut-off valve with external thread 4 Inlet + ball trap/ outlet + shut-off valve with solder fitting 5 ool / heat circuit 3 k vs values ooling/heating Medium connection Left L Right R 1) 24 V-transformer to be provided by others Order code V G F 3 ooling/heating circuit PR G Subject to change R5-01/

58 func send ontrols Mixed-ir Unit Heating or ooling 2-pipe system chilled or warm water Sizes 1 to 8 Flex-Geko omfort Edition DencoHappel MTRIX 2000 not applicable DencoHappel MTRIX 4000 System features MTRIX 4000: Temperature assignment.: (default ) Speed (stage) assignment djustable regulating range hange-over between normal/economy mode on control panel Input for change-over between normal/economy mode or unit OFF with frost protection Room temperature measurement using control panel External room temperature sensor can be connected Valve control (3-point) Temperature control via fan and/or valve Room frost protection Status messages using LED Status and alarm signal via volt free change-over contacts Unit individual and group control Isolation of individual units in case of fault Motor temperature monitoring (with speed stage motors T required) Network-enabled Summer / winter compensation Noiseless valve control ool and/or heat request via volt-free contacts (related to water circuit) Stand alone unit control Inputs for operating mode: Normal mode Economy mode utonomous mode Unit OFF Mixing-air damper control open/close with frost protection MTRIX OP30 ontrol panel for MTRIX 4000 Pure white casing, protection type IP20 Setpoint temperature setting Speed-stage selection switch 0-(uto) (depends on motor type, with E motor up to 5 stages) LEDs for operation/fault/ext.control Integrated room temperature sensor MTRIX OP31 s for control panel OP30, but also with: Normal/economy mode buttons MTRIX OP44 s for control panel OP31, but also with button for: hangeover between recirculating-air/ mixed-air operation hange-over heating/cooling/automatic mode MTRIX OP50 ontrol panel for MTRIX 4000 Pure white casing, protection type IP20 Menu-guided controls using rotation navigator LD display with plain-text display Status messages using pictograms Integrated room temperature sensor ontinuous speed assignment (only in connection with E motor) MTRIX OP51 s for control panel OP50, but also with: Integrated weekly clock timer with holiday and special days programme D E F MTRIX.IR Infrared remote control for control system MTRIX 4000 lack casing, RL 9004 LD display approx. 45x30 mm Function as in OP44 (without status, alarm and external control signals, no integrated room temperature sensor) Maximum range 20 m Speed-stage selection switch 0-(uto) (depends on motor type, with E motor up to 5 stages) % on off - + N 58 PR G Subject to change R5-01/2017

59 Flex-Geko omfort Edition ontrols Mixed-ir Unit Heating or ooling 2-pipe system chilled or warm water Sizes 1 to 8 Master unit Slave units 1-15 e.g. 2x2x0.5 Helukabel e. g. 1x2x0.5 Helukabel 230 V ~ 50 Hz 3x1.5 mm 2 NYM 3x1.5 mm 2 NYM ooling/heat.medium 1x2x0.8 J-Y(ST)Y flow sensor Speed (E motor) Speed stages ( motor) Stand alone unit control with operating and Fault signal Input unit OFF with room frost protection Input economy contact Supply temperature limitation Noiseless valve control ontact heat and cool request Geko-Drive onnection external sensor ontinuous up to 3 speed up to 5 speed Without return air sensor * 0 With return air sensor * 5 ontrol panel Enclosed control panel Integrated control panel Order code D 4 4 D 4 4 Z D * lternatively room temperature sensor (see Page 98) Master unit Slave unit PR G Subject to change R5-01/

60 Mixed-ir Unit Heating 2-pipe warm water Sizes 1 to 8 PWW 70/50 t L1 = +10 Flex-Geko omfort Edition Model size Speeds ir volume ooling capacity apacity stage 1 apacity stage 2 apacity stage 3 -motor E motor Heating capacity ooling capacity Heating capacity Q K Δp K Q H Δp H Q K Δp K Q H Δp H Q K Δp K Q H Δp H m 3 /h kw kpa kw kpa kw kpa kw kpa kw kpa kw kpa d() d() d() d() < < ooling capacity Heating capacity Sound power Sound pressure * Sound power Sound pressure * terminal box (with MTRIX metal sheet electrical control box) Speed combination E H Min..Max (E motor) F < motor E motor Motor design Metal sheet electric control box with terminal strip or for integ. ontrols Speed combination T integr. 0 T led out K L M O R Min..Max (E motor) S S 1 S 2 S 3 E Data for capacity stage 4 (S 4) are available on request (see Page 11). 1 Left 2 Right 3 Left 4 Right D Wall eiling Fresh air / - circulating air / - supply air / Fresh air / - circulating air / - supply air / Fresh air / - circulating air / - supply air / Fresh air / - circulating air / - supply air / 1 G1 mat filter 2 G2 mat filter 3 G3 mat filter Medium connect.*** ir flow +++ Filter Order code G F M 0 W 0 * mbient conditions see Page 70 coustics ** Only wall units *** Front connection side, facing discharge + only motor ** ir volume flow for S 1 and filter class G1 +++ Definition of air flow wall/ceiling see Page PR G Subject to change R5-01/2017

61 Flex-Geko omfort Edition ccessories/valves Mixed-ir Unit Heating 2-pipe warm water, model sizes 1 to 8 ccessories rrangement/installation Variant/ unit casing Vertical wall/ horizontal ceiling; with unit foot cover and intake front grille Suitable for air flow designation, Discharge grille luminium ode Variant Type ode Discharge plenum not insulated 012 primary air connection DN100 insulated 022 Discharge plenum with round fitting DN200 not insulated 032 insulated 042 Vertical wall/ horizontal ceiling; with unit foot cover and intake front grille, D 082 Discharge bend not insulated 052 insulated 062 Flexible canvas discharge connector 112 Discharge telescopic connection not insulated 152 Discharge sound attenuator connector 212 Geko-Drive motorized regulated discharge profile ** Intake fitting for sound attenuator for mixed-air units left 412 right Frame for in-wall installation for outside air intake connection 311 External weather grille, RL 9006 paint 331 Installation frame for weather protection grille 371 Seal cap for round fitting, DN 200 * Spare filter (5 pieces) insulated 713 G1 813 G2 823 G3 833 Sizes 1 to 8 * 0, if irrespective of size Order code Z G F Valves MTRIX 2000 MTRIX 3000/4000 Terminal box Drive 3-point open/ stop/ close ontinuous Operating voltage/circuit 230 V R 24 V 1) N 230 V + 2 contacts 0/ V = 24 V 1) S onnection/shut-off Inlet/outlet flow with outside thread 0 Inlet/outlet with solder fitting 1 Inlet/outlet + ball trap with external thread 2 Inlet/outlet + ball trap with solder fitting 3 Inlet + ball trap/ outlet + shut-off valve with external thread 4 Inlet + ball trap/ outlet + shut-off valve with solder fitting 5 Heating circuit 3 k vs values Heating Medium connection Left L right R 1) 24 V-transformer to be provided by others Order code V G F 3 Heating circuit PR G Subject to change R5-01/

62 func send ontrols Mixed-ir Unit Heating 2-pipe warm water, model sizes 1 to 8 Flex-Geko omfort Edition DencoHappel MTRIX 2000 not applicable DencoHappel MTRIX 4000 System features MTRIX 4000: Temperature assignment.: (default ) Speed (stage) assignment djustable regulating range hange-over between normal/economy mode on control panel Input for change-over between normal/economy mode or unit OFF with frost protection Room temperature measurement using control panel External room temperature sensor can be connected Valve control (3-point) Temperature control via fan and/or valve Room frost protection Status messages using LED Status and alarm signal via volt free change-over contacts Unit individual and group control Isolation of individual units in case of fault Motor temperature monitoring (with speed stage motors T required) Network-enabled Summer / winter compensation Noiseless valve control Heat request via volt-free contact (related to water circuit) Stand alone unit control Inputs for operating mode: Normal mode Economy mode utonomous mode Unit OFF Mixing-air damper control open/close with frost protection MTRIX OP30 ontrol panel for MTRIX 4000 Pure white casing, protection type IP20 Setpoint temperature setting Speed-stage selection switch 0-(uto) (depends on motor type, with E motor up to 5 stages) LEDs for operation/fault/ext.control Integrated room temperature sensor MTRIX OP31 s for control panel OP30, but also with: Normal/economy mode buttons MTRIX OP44 s for control panel OP31, but also with button for: hangeover between recirculating-air/ mixed-air operation hange-over heating/cooling/automatic mode MTRIX OP50 ontrol panel for MTRIX 4000 Pure white casing, protection type IP20 Menu-guided controls using rotation navigator LD display with plain-text display Status messages using pictograms Integrated room temperature sensor ontinuous speed assignment (only in connection with E motor) MTRIX OP51 s for control panel OP50, but also with: Integrated weekly clock timer with holiday and special days programme D E F MTRIX.IR Infrared remote for control system MTRIX 4000 lack casing, RL 9004 LD display approx. 45x30 mm Function as in OP44 (without status, alarm and external control signals, no integrated room temperature sensor) Maximum range 20 m Speed-stage selection switch 0-(uto) (depends on motor type, with E motor up to 5 stages) % on off - + N 62 PR G Subject to change R5-01/2017

63 Flex-Geko omfort Edition ontrols Mixed-ir Unit Heating 2-pipe warm water, model sizes 1 to 8 Master unit Slave units 1-15 e.g. 2x2x0.5 Helukabel e. g. 1x2x0.5 Helukabel 3x1.5 mm 2 NYM 3x1.5 mm 2 NYM Heating medium 230 V ~ 50 Hz Speed E motor Speed stages motor Stand alone unit control with operating and Fault signal Input unit OFF with room frost protection Input economy contact Supply temperature limitation Noiseless valve control ontinuous ontact heat and cool request onnection external sensor up to 3 speed up to 5 speed without return air sensor * 0 with return air sensor * 5 ontrol panel Enclosed control panel Integrated control panel Order code D 4 3 D 4 3 Z D * lternatively room temperature sensor (see Page 98) Master unit Slave unit PR G Subject to change R5-01/

64 Mixed-ir Unit Heating Full electric heating Sizes 1 to 8 Electric heater 3x400V~N/P/E 50Hz Flex-Geko omfort Edition ++ apacity stage 1 -motor Motor design Model size Speeds ir volume ooling capacity Full electric heating Sound power Sound pressure * motor T integr. 0 T led out Q K Δp K Q H Δp H m 3 /h kw kpa kw kpa d() d() Metal-sheet electric control box with terminal block or for integrated controls 1 Speed combination M S 1 1 Right Wall 3 Right eiling Electric connection *** Fresh air / - circulating air / - supply air / Fresh air / - circulating air / - supply air / ir flow G1 mat filter 2 G2 mat filter Filter Order code G F 1 M 0 E M 0 * mbient conditions see Page 70 coustics *** Front connection side, facing discharge ** ir volume flow for S 1 and filter class G1 +++ Definition of air flow wall/ceiling see Page PR G Subject to change R5-01/2017

65 Flex-Geko omfort Edition ccessories Mixed-ir Unit Heating Full electric heating, model sizes 1 to 8 ccessories rrangement/ installation Variant/ unit casing Vertical wall/ horizontal ceiling; with unit foot cover and intake front grille Suitable for air flow designation, Discharge grille luminium ode 073 Variant Type ode Discharge plenum primary air connection DN100 not insulated 012 Discharge bend not insulated 052 Discharge telescopic connection not insulated 152 Frame for in-wall installation for outside air intake connection 311 External weather grille, RL 9006 paint 331 Installation frame for weather protection grille 371 Spare filter (5 pieces) G1 813 G2 823 Sizes 1 to 8 * 0, if irrespective of size Order code Z G F PR G Subject to change R5-01/

66 func send ontrols Mixed-ir Unit Heating Full electric heating, model sizes 1 to 8 Flex-Geko omfort Edition DencoHappel MTRIX 2000 not applicable DencoHappel MTRIX 4000 System features MTRIX 4000: Temperature assignment.: (default ) ssignment of speed stage djustable regulating range hange-over between normal/economy mode on control panel Input for change-over between normal/economy mode or unit OFF with frost protection Room temperature measurement using control panel External room temperature sensor can be connected Temperature control via fan Room frost protection Status messages using LED Status and alarm signal via volt free change-over contacts Unit individual and group control Isolation of individual units in case of fault Motor temperature monitoring (with speed stage motors T required) Network-enabled Summer / winter compensation Stand alone unit control Inputs for operating mode: Normal mode Economy mode utonomous mode Unit OFF Mixing-air damper control open/close with frost protection Regulation of multi-stage electrical heating with disconnection in case of over-temperature MTRIX OP30 ontrol panel for MTRIX 4000 Pure white casing, protection type IP20 Setpoint temperature setting Speed stage selection switch 0-(uto) LEDs for operation/fault/ext.control Integrated room temperature sensor MTRIX OP31 s for control panel OP30, but also with: Normal/economy mode buttons MTRIX OP44 s for control panel OP31, but also with button for: hangeover between recirculating-air/ mixed-air operation hange-over heating/cooling/automatic mode MTRIX OP50 ontrol panel for MTRIX 4000 Pure white casing, protection type IP20 Menu-guided controls using rotation navigator LD display with plain-text display Status messages using pictograms Integrated room temperature sensor MTRIX OP51 s for control panel OP50, but also with: Integrated weekly clock timer with holiday and special days programme D E F MTRIX.IR Infrared remote control for control system MTRIX 4000 lack casing, RL 9004 LD display approx. 45x30 mm Function as in OP44 (without status, alarm and external control signals, no integrated room temperature sensor) Maximum range 20 m Speed stage selection switch 0-(uto) % on off - + N 66 PR G Subject to change R5-01/2017

67 Flex-Geko omfort Edition ontrols Mixed-ir Unit Heating Full electric heating, model sizes 1 to 8 Master unit 3x400 V~ 50 Hz Slave units x400 V~ 50 Hz e.g. 2x2x0.5 Helukabel e. g. 1x2x0.5 Helukabel 3x1.5 mm 2 NYM 3x1.5 mm 2 NYM 230 V ~ 50 Hz 5x2.5 mm 2 NYM 5x2.5 mm 2 NYM 400 V ~ 50 Hz 400 V ~ 50 Hz Speeds Stand alone unit control with operating and Fault signal Input unit OFF with room frost protection Input economy contact ontact heat request onnection external sensor up to 3 speed Without return air sensor * 2 With return air sensor * 7 ontrol panel Enclosed control panel Integrated control panel Order code D 4 3 D 4 3 Z D * lternatively room temperature sensor (see Page 98) Master unit Slave unit PR G Subject to change R5-01/

68 in heat exchanger * for chilled and warm water Flex-Geko omfort Edition ooling, 2-pipe system, S 1 Pressure Drop Δp [kpa] ,0 8,0 7,0 6,0 5,0 4,5 4,0 3,5 3,0 2,5 2,0 1,5 1,0 0,9 0,8 0,7 0,6 0,5 Size/S* 2/1 1/1 5/1 4/1 3/1 8/1 7/1 6/1 ooling, 2-pipe system, S 2 + S 3 Pressure Drop Δp [kpa] ,0 8,0 7,0 6,0 5,0 4,5 4,0 3,5 3,0 2,5 2,0 1,5 1,0 0,9 0,8 0,7 0,6 0,5 Size/S* 2/2 1/2 1/3 5/2 4/2 3/2 8/2 5/3 7/2 4/3 6/2 3/3 8/3 2/3 7/3 6/ Water flow rate V w [l/h] Water flow rate V w [l/h] Heating, 2-pipe system, S 1 + S 2 Pressure Drop Δp [kpa] ,0 8,0 7,0 6,0 5,0 4,5 4,0 3,5 3,0 2,5 2,0 1,5 1,0 0,9 0,8 0,7 0,6 Size/S* 2/1 5/1 1/1 4/1 3/1 2/2 1/2 8/1 5/2 7/1 4/2 6/1 3/2 8/2 7/2 6/2 Heating, 2-pipe system, S 3 Pressure Drop Δp [kpa] ,0 8,0 7,0 6,0 5,0 4,5 4,0 3,5 3,0 2,5 2,0 1,5 1,0 0,9 0,8 0,7 0,6 Size/S* 1/3 5/3 4/3 3/3 2/3 8/3 7/3 6/3 0,5 0, Water flow rate V w [l/h] Water flow rate V w [l/h] ooling, 4-pipe system, S 2 + S 3 Pressure Drop Δp [kpa] ,0 8,0 7,0 6,0 5,0 4,5 4,0 3,5 3,0 2,5 2,0 1,5 1,0 0,9 0,8 0,7 0,6 0,5 Size/S* 1/1 4/1 3/1 2/1 2/2 1/2 8/1 7/1 6/1 5/1 5/2 4/2 3/2 8/2 7/2 6/2 Heating, 4-pipe system, S 1 + S 2 Pressure Drop Δp [kpa] ,0 8,0 7,0 6,0 5,0 4,5 4,0 3,5 3,0 2,5 2,0 1,5 1,0 0,9 0,8 0,7 0,6 0,5 G/LG* Size/S* 2/1 2/2 3/1 3/2 4/1 4/2 5/1 5/2 6/1 7/1 8/1 2/1 1/2 8/2 7/2 6/ Water flow rate V w [l/h] Water flow rate V w [l/h] Size = model size, S = capacity stage * Data for additional capacity stage 3+4 (S3, S4) are available on request (see page 11). 68 PR G Subject to change R5-01/2017

69 Flex-Geko omfort Edition Samples for capacity definition The tables on pages Page 12 to Page 64 specify heating capacity for pumped warm water 70/50 and air intake temperature t L1 = +20 for recirculating units and t L1 =+10 for mixed units as well as cooling capacity for chilled water 6/12 and air intake condition t L1 =+27 /46 % r.h. apacity for other operating conditions can be determined using the correction factors on Page 3. Sample calculation for recirculating Flex-Geko FU omfort Edition, cooling or heating with 2-pipe system with a heating capacity of min. 4.5 kw for warm water (WWP) 70/50/+15 and cooling capacity with chilled water 8/12 (24 /50 % r.h.) Heating capacity with PWW 70/50 and t L1 = + 15 Q H (70/50/+15) = new heating capacity f H (70/50/+15) = 1.13 (s. Page 3) Q H (70/50/+20) = 4.6 (see Page 24) ooling capacity with WW 8/12 and t L1 = +24 /50% r.f. Q K (8/12/+24/50%) = new cooling capacity f K (8/12/+24/50%) = 0.73 (s. Page 3) Q K (6/12/+27/46%) = 2.4 (see Page 24) Selected unit type: GF31.UW1.001 See Page 24 Sample speed 3 = 470 m 3 /h Q H (70/50/+15) = f H (70/50/+15) Q H (70/50/+20) Q H (70/50/+15) = kw = 5.2 kw Q K (8/12/+24/50%) = f K (8/12/+24/50%) Q K (6/12/+27/46%) Q K (8/12/+24/50%) = kw = 1.8 kw Power and current consumption Model Speed ir volume flow motor E motor size [m 3 /h] apacity [W] urrent [] apacity [W] urrent [] PR G Subject to change R5-01/

70 coustics Motor Flex-Geko omfort Edition Model size Speed Sound power level (d) Sound pressure level *) Octave centre frequency [Hz] not rated rated not rated rated according to [d] d() [d] d() NR N <20 <20 < <20 <20 < <20 < <20 <20 <20 <20 38 <30 29 < <20 <20 < <20 < <20 < <20 < < <20 <20 <20 <20 40 < <20 <20 < <20 < <20 <20 <20 39 <30 30 < <20 <20 < <20 < <20 <20 < <20 < <20 <20 < <20 < < <20 < <20 < < *) Sound pressure level relates to a reverberation field of a 100 m 3 room and reverberation time of 0.5 s =for values used in the sample calculation, see Page 72/Page 73, Data for S 1 and filter class G1 70 PR G Subject to change R5-01/2017

71 Flex-Geko omfort Edition coustics E Motor Model size Speed Sound power level (d) Sound pressure level *) Octave centre frequency [Hz] not rated rated not rated rated according to [d] d() [d] d() NR N 1 <20 < <20 < < < < <20 <20 < < <20 < <20 < <20 < <20 < < <20 <20 < <20 < < <20 <20 <20 < < <20 < <20 <20 < < <20 <20 < < <20 < <20 < *) Sound pressure level relates to a reverberation field of a 100 m 3 room and reverberation time of 0.5 s Data for S 1 and filter class G1 PR G Subject to change R5-01/

72 Sound power level and sound pressure level Flex-Geko omfort Edition Sound pressure level d() The sound pressure specifications in the tables on pages 6-61 and Page 70/Page 71 apply to the reverberation sound field of a room with a volume of 100 m 3 and reverberation time of 0.5 s. To determine the expected sound pressure level at the installation location, refer to the - rated sound power level in conjunction with the conversion diagram in Fig.. Example: In a conference room with dimensions of (20 x 10 x 4 m) 6 assette fan coil units with model size 3 should be installed. The units are to be operated at speed 2, i.e. the sound power level amounts to 35 d(), see page 64. Determining the sound pressure level 1. ased on the room volume (800 m 3 ), an absorption surface of approx. 100 m 2 Sabin is estimated in accordance with the diagram Fig. Homes, offices, hotel rooms, conference rooms. 2. The mean distance to the fan coils is assumed to be approx. 3 m and the direction coefficient to be 4, Fig. 23. The intersection of the dotted sample lines in the diagram Fig. makes up the sound level difference: ΔL~11 d. 3. The anticipated -rated sound pressure level L P for the unit is thus: L P = L W ΔL = 35 d() 11 d = 24 d() Increase in sound level of 6 units amounts to approx. 8 d and is specified in the diagram Fig. 22. Thus, the anticipated sound pressure level in the room amounts to: L Pges. = L P + 8 d = 24 d() + 8 d = 32 d() The value for increased requirements, as specified in Fig. 21, is thus reached. Table -sound pressure level LP 1) specifies standard values according to VDI 2081 Room type -sound level d() average reverberati on time s partment * ** (Hotel room) night 35/30 30/ Residential rooms day uditoriums TV studio oncert halls Operas Theatre inema Lecture halls Reading rooms Seminar rooms lassrooms Offices onference rooms Leisure rooms reak rooms small offices Large offices hurch Museum Service halls IT/Telecommunication room Laboratory Restaurants 40 to 55 2) 1.0 Kitchens 45 to 60 2) 1.5 Sales rooms 45 to 60 2) 1.0 Fig. 21 * = Minimum requirements ** = Increased requirements 1) lso refer to applicable building regulations, DIN standards and VDI guidelines (e.g. DIN 4109, DIN 1946, VDI 2058) 2) Depending on use Sound level increase (d) Sound level increase in d Fig Direction coefficient Number of units 8 Fig. 23 Direction coefficient 2 (hemispherical radiation) Unit is mounted stand-alone in the middle of a surface Direction coefficient 4 (quarter-spherical radiation): Unit borders with 2 indoor surfaces Direction coefficient 8 (eight-spherical radiation): Unit borders with 3 indoor surfaces onversion of sound power level in sound pressure level 0 5 Schallpegelgifferenz Sound level difference DL=LW ΔL=LW - LP - LP [d] [d] Fig. 24 Unit Gerät borders grenzt with anthree drei Raumflächen indoor surfaces Free field Freifeld Gerät Unit borders grenzt an with zwei two Raumflächen indoor surfaces Unit is Gerät mounted ist frei stand-alone in der Mitte in einer the middle Fläche of a surface 0, bstand Distance von from dersound Schallquelle source [ m [m] ] Direction Richtungsfaktor coefficient Factory halls and swimming pools Fabrik- u. Schwimmhallen School classrooms Residential areas, offices, hotel rooms Reading rooms, TV studios Schulräume Krankenzimmer, kleine Kirchen Wohnräume, üros, Hotelzimmer Konferenzräume, Theater Lesesäle, Fernsehstudios Rundfunkstudios Musikzimmer Radio studios m a = 0,03 a = 0,05 a = 0,1 a = 0,15 a = 0,25 a = 0,4 große Kirchen Kaufhäuser Raumvolumen Room [ m[m 3 ] Large churches Hospital wards, small churches onference rooms, theatres Department stores, malls oncert halls bsorption factor α wall surface that absorbs all sound waves that hit it has an absorption factor of a = 1. The above am values represent the relationship between the actual and ideal absorption performance of a wall. They represent mean values. bsorption surface m2 (Sabin) This surface completely absorbs all sound waves that hit it. It is not identical to the entire room surface. bsorbtionsfläche bsorption surface [ m 2 [m Sabin 2 Sabin] ] 72 PR G Subject to change R5-01/2017

73 Flex-Geko omfort Edition NR and N limiting curves Limiting curves If narrower frequency components or outstanding single tones with high intensity peaks occur in a broad frequency range (e.g. on a fan), the d() specification (sum level) is not sufficient as the latter does not sufficiently address the annoying noise nature. Thus, for the purposes of noise evaluation, so-called limiting curves (curves which produce the same level of inconvenience) are added. These curves also consider the combination of noise frequencies. lthough various noise-rating curves are in place, NR (Noise Rating) curves specified in Fig. 26 became internationally accepted. Today N curves (Noise riteria) are only used for noise rating in the US, as specified in diagram Fig. 27. If the observance of a particular NR or N limiting curve is required for a room, the measured sound pressure may not exceed this limiting curve in any octave. The sum level across all eight octaves bands as per DIN is always around 7 to 10 d higher than the value in the limiting curve. For HV equipment the difference of the sound pressure level lies in the medium range at 5 d() because the noise spectrum does not always reach the same limiting curve in all octaves. Sound pressure level in d ISO NR evaluation curves Octave band/mean frequency Example The requirement of NR 28 or N 26 must be observed. The basis is the tabulated data on Page 70. In order to identify the sound pressure level in the individual octaves, the sound power values should be entered for size 3 and speed 2 in a table, see Fig. 25. In order to obtain the sound pressure levels in the individual octaves, 11 d must be subtracted from the sound power specifications entered in Fig. 25. The new values can now be entered in the nomograms Fig. 26 (NR) or Fig. 27 (N). The highest point in the NR evaluation stands at NR 20 (500 Hz) and N 18 (500 Hz) in the N evaluation. The requirement of NR 28 (NR 20 lies below NR 28) or N 26 (N 18 is below N 26), is thus met. Octave medium frequency for size 3 and speed [Hz] <20 <20 20 [d] [d] <9 <9 9 [d] Fig. 25 Fig. 26 Sound pressure level in d N evaluation curves Octave band/mean frequency Fig. 27 PR G Subject to change R5-01/

74 Definition of irflow/installation Samples Flex-Geko omfort Edition Designation of air flow D Recirculating air Mixed air Fig. 28 Wall units Recirculating-air units with unit casing (cooling/heating) Fig. 29 Fig. 30 Fig. 31 Fig. 32 Recirculating-air units with casing by others (cooling/heating) Fig. 33 Fig. 34 Fig. 35 Fig. 36 Mixed-air units (cooling/heating) eiling units Recirculating-air units with unit casing ooling/heating Heating Fig. 37 Fig. 38 Fig. 39 Fig. 40 Recirculating-air unit with casing Recirculating-air unit with casing by others Mixed-air unit ooling/heating ooling/heating Heating ooling/heating Fig. 41 Fig. 42 Fig. 43 Fig PR G Subject to change R5-01/2017

75 Flex-Geko omfort Edition Dimensions of basic units without casing Unit for ceiling installation * Lateral condensate pan for ceiling cooling units b-64 b+88 b (228**)*** * Space need for field-provided piping on site ** only with frontal air intake ***dditional space demand, if required, of 5 mm (unit height) with cooling units for pitched installation towards condensate connection side 56 Drain connection 63, mm long Ø 20 mm 127 Fig. 45 Fig. 46 Unit for wall installation Lateral drain pan for wall cooling units * Space need for field-provided piping on site ** only with frontal air intake ***dditional space demand, if required, of 5 mm (unit height) with cooling units for pitched installation towards condensate connection side Drain connection mm long Ø 20 mm 56 Fig. 47 Fig. 48 Mounting dimensions for wall and ceiling units b+66 Mixed-air mechanism ir flow Symbol, 92 16,5 34 8,4 30 8,4 12,5 ir flow Symbol, D ,5 16,5 92 Fig. 49 Fig. 50 Model size b [mm] Max. weight [kg] PR G Subject to change R5-01/

76 Dimensions and medium connections Flex-Geko omfort Edition Mounting clearances for units with and without casing Service opening with installation in suspended ceiling chtung! b * Vertical units with unit casing and rear wall for removing casing: 520 mm Wall units with unit casing for opening access panel: 140 mm Wall units with casing by others for installing flexible connection: mm Model size b [mm] [mm] Depending on unit configuration and installed air-side accessories a larger service opening may be necessary! Fig. 51 Fig. 52 Medium connections (warm/chilled water) 2-pipe system for wall and ceiling installation heat exchanger for LG 1-4, internal screw thread ½ 1 - filter removal direction (unit with suction below / back) 2 - filter removal direction (unit with front suction) 1/ D Power size Heat exchanger content Model size Model size Dimension [mm] D S 1 S 2 S 3 S 4 [l] [l] [l] [l] Medium connections (warm/chilled water) 4-pipe system for wall and ceiling installation heat exchanger for LG 1-3, internal screw thread ½ 1 - filter removal direction (unit with suction below / back) 2 - filter removal direction (unit with front suction) 1/ E F G H J K L M Dimension ll sizes S 1 S 2+3 [mm] [mm] right Left E F G H J K L M Heat exchanger content Model size ooling circuit Heating circuit S 1 S 2 S 3 S 1 S 2+3 [l] [l] [l] [l] [l] Fig. 53 Fig. 54 Medium connections (refrigerant) 2-pipe system for wall and ceiling installation heat exchanger for LG filter removal direction (unit with suction below / back) 2 - filter removal direction (unit with front suction) Medium connections (refrigerant/warm water) 4-pipe system for wall and ceiling installation heat exchanger for LG 1, heating circuit internal screw thread ½ 1 - filter removal direction (unit with suction below / back) 2 - filter removal direction (unit with front suction) Size 1-3 Size 4-8 Size 1-3 Size 4-8 Einspritzung: Injection: Ø Ø mm mm Suction: bsaugung: Ø Ø mm mm Injection: Einspritzung: Ø Ø mm mm Suction: bsaugung: Ø Ø mm mm Einspritzung: Injection: Ø Ø mm mm 1/2 Suction: bsaugung: Ø Ø mm mm Injection: Einspritzung: Ø Ø mm mm 1/2 Suction: bsaugung: Ø Ø mm mm Fig. 55 Fig PR G Subject to change R5-01/2017

77 Flex-Geko omfort Edition Dimensions of unit casing L omfort casing for recirculating-air units with plastic or aluminium discharge grille olour white RL 9002 with grey RL 7035 in recess X Suitable for air flow designation Wall and ceiling installation Model size Order-Nr plastic Order-Nr lu Weight [kg] 1 ZGF.1012 ZGF ZGF.2012 ZGF ZGF.3012 ZGF ZGF.4012 ZGF ZGF.5012 ZGF ZGF.6012 ZGF ZGF.7012 ZGF ZGF.8012 ZGF Wall and ceiling installation Model size Order-Nr plastic Weight [kg] 1 ZGF ZGF ZGF ZGF ZGF ZGF ZGF ZGF Wall and ceiling installation Model size Order-Nr plastic Order-Nr lu Weight [kg] 1 ZGF.1032 ZGF ZGF.2032 ZGF ZGF.3032 ZGF ZGF.4032 ZGF ZGF.5032 ZGF ZGF.6032 ZGF ZGF.7032 ZGF ZGF.8032 ZGF Wall and ceiling installation Model size Order-Nr plastic Weight [kg] 1 ZGF D 2 ZGF ZGF ZGF ZGF ZGF ZGF ZGF entral ceiling mounting (closed on the rear side) Model size Order-Nr plastic Order-Nr lu Weight [kg] 1 ZGF.1132 ZGF ZGF.2132 ZGF ZGF.3132 ZGF ZGF.4132 ZGF ZGF.5132 ZGF ZGF.6132 ZGF ZGF.7132 ZGF ZGF.8132 ZGF Vertical stand-alone installation (with rear panel) Model size Order-Nr plastic Order-Nr lu Weight [kg] 1 ZGF.1232 ZGF ZGF.2232 ZGF ZGF.3232 ZGF ZGF.4232 ZGF ZGF.5232 ZGF ZGF.6232 ZGF ZGF.7232 ZGF ZGF.8232 ZGF Model size L (mm) X (mm) PR G Subject to change R5-01/

78 Dimensions of unit casing Flex-Geko omfort Edition L omfort casing with foot cover for recirculating-air units with plastic or aluminium discharge grille olour white RL 9002 with grey RL 7035 in recess X Suitable for air flow designation Wall and ceiling installation Model size Order-Nr plastic Order-Nr lu Weight [kg] 1 ZGF.1052 ZGF ZGF.2052 ZGF ZGF.3052 ZGF ZGF.4052 ZGF ZGF.5052 ZGF ZGF.6052 ZGF ZGF.7052 ZGF ZGF.8052 ZGF Wall and ceiling installation Model size Order-Nr plastic Weight [kg] 1 ZGF ZGF ZGF ZGF ZGF ZGF ZGF ZGF L omfort unit casing with foot casing and air intake grille for recirculating and mixed units with plastic or aluminium discharge grille olour white RL 9002 with grey RL 7035 in recess X Suitable for air flow designation 104 Wall and ceiling installation Model size Order-Nr plastic Order-Nr lu Weight [kg] 1 ZGF.1072 ZGF ZGF.2072 ZGF ZGF.3072 ZGF ZGF.4072 ZGF ZGF.5072 ZGF ZGF.6072 ZGF ZGF.7072 ZGF ZGF.8072 ZGF Wall and ceiling installation Model size Order-Nr plastic Weight [kg] 1 ZGF ZGF ZGF ZGF ZGF ZGF ZGF ZGF Model size L (mm) X (mm) PR G Subject to change R5-01/2017

79 Flex-Geko omfort Edition ccessory sizes Geko-Drive What is Geko-Drive? Geko-Drive is a modern motorized discharge profile for optimization of flow velocity and air throw in cooling mode. Depending on fan speed (stage) as well as supply and room temperature, the main function is to improve air throw and indoor air flow and thence enhance room comfort. Variable cross-section Discharge profile is performed for most favorable air flow and reaches optimal discharge velocity even at low speed or speed stage. Geko-Drive is delivered already mounted by factory With unit casing for an optimum air routing system MTRIX 4000 controlling for automatic air throw adjustment vailable for only cooling or cooling and heating units using water as medium Model size Order No. Medium connection Left Right 1 ZGF.1412 ZGF Weight [kg] 2 ZGF.2412 ZGF ZGF.3412 ZGF ZGF.4412 ZGF ZGF.5412 ZGF ZGF.6412 ZGF ZGF.7412 ZGF ZGF.8412 ZGF Fig. 57 Example (computational fluid dynamics FD): Due to low cooling demand in part-load range, automatic regulation selects low fan speed (stage). This can lead to a situation when air discharge velocity is not adequate to reach an effective air throw and penetration depth up to ceiling. In an extreme case this can even lead an airside short circuit, when cold air is discharged from unit, falls down due to a missing impulse and sucked again into the unit. To avoid this, the speed (stage) would have to be increased which is not really desirable in terms of possibly low noise level and current draw. Geko-Drive works against above-mentioned scenario by reducing air discharge cross-section using continuous regulation, in such a way air flow velocity is increased without having to raise speed (stage) and at the same time air flow is evenly distributed on walls and ceiling (oanda-effect). Thus, an appreciable increase in penetration depth of the room can be reached as far as comfort is concerned and non-critical temperature and velocity-related distribution in occupied zone are ensured. with Geko- Drive Occupied zone* without Geko- Drive Occupied zone* Temperature in * conforming with DIN EN Fig. 58 PR G Subject to change R5-01/

80 ccessory sizes ir-side accessories Flex-Geko omfort Edition Ø 98 Fig. 59 b Hole size connection frame: b+24 x 144 Drill hole Ø 6.4 Discharge plenum with primary air connection DN 100 Model Order No. Weight size not insulated insulated [kg] 1 ZGF.1012 ZGF /1.9 2 ZGF.2012 ZGF /1.8 3 ZGF.3012 ZGF /2.0 4 ZGF.4012 ZGF /2.3 5 ZGF.5012 ZGF /2.6 6 ZGF.6012 ZGF /2.9 7 ZGF.7012 ZGF /3.2 Ø Model size 1 Model augröße size 2, Discharge plenum with round fitting DN Fig b + 40 Hole size connection frame: b+24 x 144 Drill hole Ø 6.4 Model size Model size Model size Model Order No. Weight size not insulated insulated [kg] 1 ZGF.1032 ZGF /1.9 2 ZGF.2032 ZGF /2.6 3 ZGF.3032 ZGF /3.1 4 ZGF.4032 ZGF /3.8 5 ZGF.5032 ZGF /4.4 6 ZGF.6032 ZGF /5.1 7 ZGF.7032 ZGF /5.7 8 ZGF.8032 ZGF / Discharge bend 160 Fig. 61 b Hole size connection frame: b+24 x 144 Drill hole Ø 6.4 Model Order No. Weight size not insulated insulated [kg] 1 ZGF.1052 ZGF /1.3 2 ZGF.2052 ZGF /1.6 3 ZGF.3052 ZGF /1.8 4 ZGF.4052 ZGF /2.1 5 ZGF.5052 ZGF /2.4 6 ZGF.6052 ZGF /2.6 7 ZGF.7052 ZGF /2.9 8 ZGF.8052 ZGF / b Hole size connection frame: b+24 x 144 Drill hole Ø 6.4 flexible connection Order No. ir intake * Discharge 1 ZGF.1111 ZGF Model size Weight [kg] 2 ZGF.2111 ZGF ZGF.3111 ZGF ZGF.4111 ZGF ZGF.5111 ZGF ZGF.6111 ZGF ZGF.7111 ZGF ZGF.8111 ZGF Fig. 62 * Transition piece ZGF#131 required Model size b (mm) PR G Subject to change R5-01/2017

81 Flex-Geko omfort Edition ccessory sizes ir-side accessories 160 Fig. 63 b Hole size connection frame: b+24 x 144 Drill hole Ø 6.4 Transition piece for intake flexible connection, telescopic and sound-attenuator connection Model size Order No. Weight [kg] 1 ZGF ZGF ZGF ZGF ZGF ZGF ZGF ZGF Telescopic connection b not insulated Fig b Hole size connection frame: b+24 x 144 Drill hole Ø 5.3 Order No. ir intake * Discharge 1 ZGF.1151 ZGF Model size * Transition piece ZGF#131 required Weight [kg] 2 ZGF.2151 ZGF ZGF.3151 ZGF ZGF.4151 ZGF ZGF.5151 ZGF ZGF.6151 ZGF ZGF.7151 ZGF ZGF.8151 ZGF Sound attenuator fitting 80 Discharge sound attenuator connection Intake sound attenuator connection for recirculating-air units 198 Fig b + 40 b Hole size connection frame: b+24 x 144 Drill hole Ø 5.3 Order No. ir intake * Discharge 1 ZGF.1211 ZGF Model size Weight [kg] 2 ZGF.2211 ZGF ZGF.3211 ZGF ZGF.4211 ZGF ZGF.5211 ZGF ZGF.6211 ZGF ZGF.7211 ZGF ZGF.8211 ZGF ir intake plenum with primary air connection DN 125, not insulated Fig Ø 123 b Hole size connection frame: b+24 x 144 Drill hole Ø 6.4 Model size Order No. Weight [kg] 1 ZGF ZGF ZGF ZGF ZGF ZGF ZGF ZGF Model size b (mm) PR G Subject to change R5-01/

82 ccessory sizes ir-side accessories Flex-Geko omfort Edition Model size 1 ir intake plenum with round connection Model augröße size 2, DN 200, not insulated Model size Order No. Weight [kg] Fig. 67 Hole size connection frame: b+24 x 144 Drill hole Ø 6.4 Model size Model size Model size ZGF ZGF ZGF ZGF ZGF ZGF ZGF ZGF ir intake bend 120 not insulated 217 Fig. 68 b Hole size connection frame: b+24 x 144 Drill hole Ø 6.4 Model size Order No. Weight [kg] 1 ZGF ZGF ZGF ZGF ZGF ZGF ZGF ZGF Intake sound attenuator for mixed-air units 130 8, , ,5 b b ,5 213,5 109, ,5 12,5 12,5 575 Model size Order No. Weight [kg] 1 ZGF ZGF ZGF ZGF ZGF ZGF ZGF ZGF Fig. 69 Frame for in-wall installation for outside air intake connection Fig. 70 b + 43 b Model size Order No. Weight [kg] 1 ZGF ZGF ZGF ZGF ZGF ZGF ZGF ZGF Model size b (mm) PR G Subject to change R5-01/2017

83 Flex-Geko omfort Edition ccessory sizes ir-side accessories External weather grill RL 9006 painted Model size Order No. Weight [kg] 1 ZGF ZGF ll drill holes = ZGF ZGF ZGF b + 9 b ZGF ZGF Fig ZGF b + 41 b Frame for in-wall installation for weather-protection grille Model size Order No. Weight [kg] 1 ZGF ZGF ZGF ZGF ZGF ZGF Fig ZGF ZGF over cap for round fitting DN 200, insulated Fig. 73 Ø 200 Model size Order No. 1-8 ZGF.0713 Unit feet for recirculating-air units Fig. 74 Model size Order No. 1-8 ZGF.0913 Filter fitted with plastic frame (G1/G2) Filter hoses (wire frame required only G3) Spare filter set G1/G2 - omplete filter; G3 - filter hoses; 1 set = 5 pieces Fig. 75 Model size Order No. G1 G2 G3 1 ZGF.1813 ZGF.1823 ZGF ZGF.2813 ZGF.2823 ZGF ZGF.3813 ZGF.3823 ZGF ZGF.4813 ZGF.4823 ZGF ZGF.5813 ZGF.5823 ZGF ZGF.6813 ZGF.6823 ZGF ZGF.7813 ZGF.7823 ZGF ZGF.8813 ZGF.8823 ZGF.8833 Model size b (mm) c (mm) PR G Subject to change R5-01/

84 Valve control mode Flex-Geko omfort Edition 2-Point open/close operation 3-way valve warmer 2-Point open/close operation Setpoint cooler warmer Fig. 76 Fig. 76 Temperature is obtained in room with 2-point control mode. R V M Setpoint cooler Fig. 77 Fig. 77 Temperature is obtained in the centre with 2-point control behavior at air outlet. Fig. 78: (2-point open/close operation) 2-way valve Fig. 79 The valve is either open or closed. Fig Performance viewed over time Fig. 80 Set command for valve + = valve open 0 = valve closed Fig. 80 Fig. 81: (2-point open/close operation) 3-Point modulating operation 3-way valve warmer setpoint cooler Fig Point modulating operation Fig. 82 Room temperature is controlled with 3-point control mode. warmer R V M setpoint cooler Fig. 83 Fig. 83 Temperature is controlled in centre in 3-point mode at air outlet. Fig. 84: (3-point modulating operation) 2-Wege-Ventil Fig. 85 Fig. 85 The valve setting corresponds in percent to the mass flow ( %) + 0 Fig. 86 Set command for valve + = valve direction open - = valve direction close Performance viewed over time Fig. 87: (3-point modulating operation) Fig PR G Subject to change R5-01/2017

85 Flex-Geko omfort Edition Overview of valves Selection table The following selection table presents all available valves models with main features and compatible control equipment. The following symbols are used: = Valve type compatible with the corresponding control panel or electric equipment. = Valve type not compatible with the corresponding control panel or electrical equipment. Valve Type Function type ontrol type Voltage MTRIX 2000 ompatible control equipment MTRIX 3000 MTRIX 4000 Thermostat switch Field-provided controls atalogue Page R 3 point (modulating) 230 V~ 86 (only 2-pipe system) N 3 point (modulating) 3 point (modulating) 24 V~ (only 2-pipe system; transformer by others required) 230 V~ (transformer by others required) (transformer by others required) (2 volt free auxiliary switches) (only 2-pipe system) T 2 point (modulating) 230 V~ 88 Q 2 point (modulating) 24 V~ 88 S continuous 24 V~ (analogsignal V) (transformer by others required) (transformer by others required) (transformer by others required) 88 E continuous W/o additional power source self-acting valve (can not be regulated) 89 PR G Subject to change R5-01/

86 Overview of valves Flex-Geko omfort Edition Valves with reversible actuator (230 V~) and 2 floating auxiliary switches/3-point operation 40 ~ 116,5 Fig (66) M R V 3-way valve Size for G 3/4" in brackets 2-way valve Two and three-way valves with a modulating motor drive for water-side regulation (3-point modulating operation). onnecting cable, plastic motor casing, brass valve body (G 1/2") or red brass (G 3/4"), stainless steel spindle and cone. Volt free auxiliary switch: Switch S1 (valve message 100% open), Switch S2 (valve position message % ) Technical Data Rated pressure Max. allowed ambient temperature Max. water inlet temperature 16 bar Operating voltage 230 V~/50/60 Hz Power Input 7 V Protection class IP 43 Running time 150 s at 50 Hz (125 s at 60 Hz) Load capacity for auxiliary switch Water with a max. 50% glycol rate is allowed. Do not mount the actuator upside down! max. 5(1) /250 V max. 100 m/24 V Valve values ~ 116,5 k vs -value [m 3 /h] Δp max [kpa] Valve Exter. thread ) /800 2) G 1/2" ) /800 2) G 1/2" ) /800 2) G 1/2" ) /250 2) G 1/2" ) /250 2) G 1/2" 56 (66) ) /100 2) G 3/4" ) /100 2) G 3/4" Fig. 89 Size for G 3/4" in brackets 1) max. allowed pressure difference, at which the valve closes against pressure (for 2-way valves) 2) for 3-way valves k VS = 0,25 k VS = 0,63 k VS = 1,6 k VS = 0,4 k VS = 1,0 k VS = 2,5 30 k VS = 4,0 ontrol valve can ship loose with or without connected pipework. Order No. Fig. 90 Pressure Druckverlust drop Δp [kpa] Δp (kpa) Wasservolumenstrom Water flow rate V [l/h] V (l/h) 2000 k vs - value Separately supplied valves Separately supplied valves with piping Two-way 3-way Two-way 3-way VGF.203.0# VGF.303.0# VGF.204.0# VGF.304.0# VGF.206.0# VGF.306.0# VGF.210.0# VGF.310.0# VGF.216.0# VGF.316.0# VGF.225.0# VGF.325.0# VGF.240.0# VGF.340.0# With mounted valves for a 4-pipe system the order number must be specified with the designation for the actuator, valve body and the k vs value of the heating valve, e.g. VGF #. The symbol "#" is reserved for medium connection left (L) and right (R) (see Unit type code Page 102). Note: The max. pressure drop in heat exchanger with fully open valve should not exceed 25 kpa in cooling mode and 20 kpa in heating mode. 86 PR G Subject to change R5-01/2017

87 Flex-Geko omfort Edition Overview of valves Valves with thermoelectric actuators (230 V~ and 24 V~)/2-point open/close operation 42 3-way valve Two and three-way valves with a thermoelectric actuators for water-side regulation (2-point modulating operation). onnecting cable and plastic motor casing, brass valve body, stainless steel spindle and cone. 40 ~ 92 Fig (66) M R V Size for G 3/4" in brackets Technical Data 230 V~ 24 V~ Rated pressure 16 bar Max. allowed ambient temperature 50 Max. water inlet temperature 110 Operating voltage 230 V~/50/60 Hz 24 V~/50/60 Hz Starting current Operating current Power Input 3 V 3 V Protection class IP 43 Running time pprox. 3 min Water with a max. 50% glycol rate is allowed. Do not mount the actuator upside down! ~ way valve k vs -value [m 3 /h] Valve values Δp max [kpa] Valve Exter. thread ) /150 2) G 1/2" ) /50 2) G 3/4" 1) max. allowed pressure difference, at which the valve closes against pressure (for 2-way valves) 2) for 3-way valves Fig. 92 Pressure Druckverlust drop Δp [kpa] Δp [kpa] ,8 0,6 0,5 0,4 0,3 56 (66) Size for G 3/4" in brackets k = 1,6 vs k = 2,5 vs ontrol valve can ship loose with or without connected pipework. Order No. k vs - value Separately supplied valves Separately supplied valves with piping Two-way 3-way Two-way 3-way Operating voltage 230 V~ VGF.T216.0# VGF.T316.0# VGF.T225.0# VGF.T325.0# Operating voltage 24 V~ VGF.Q216.0# VGF.Q316.0# VGF.Q225.0# VGF.Q325.0# With mounted valves for a 4-pipe system the order number must be specified with the designation for the actuator, valve body and the k vs value of the heating valve, e.g. VGF.T316T325.0#. The symbol "#" is reserved for medium connection left (L) and right (R) (see Unit type code Page 102). Note: The max. pressure drop in heat exchanger with fully open valve should not exceed 25 kpa in cooling mode and 20 kpa in heating mode Wasservolumenstrom Water flow rate V w [l/h] V (l/h) w Fig. 93 PR G Subject to change R5-01/

88 Overview of valves Valves with continuous actuator (24 V~, V) Flex-Geko omfort Edition way valve Two and three-way valves with a continuous actuator for water-side regulation. onnecting cable and plastic motor casing, brass valve body (G 1/2") or red brass (G 3/4"), stainless steel spindle and cone. 40 ~ 92 Fig (66) M R V Size for G 3/4" in brackets Technical Data Rated pressure Max. allowed ambient temperature Max. water inlet temperature 16 bar Operating voltage 24 V~/50/60 Hz nalog control signal ( ) V Power Input 1.4 V Protection class IP 40 Running time 150 s at 50 Hz (125 s at 60 Hz) Water with a max. 50% glycol rate is allowed. Do not mount the actuator upside down! Valve values way valve k vs -value [m 3 /h] Δp max [kpa] Valve Exter. thread ) /800 2) G 1/2" ) /800 2) G 1/2" ~ ) /800 2) G 1/2" ) /250 2) G 1/2" ) /250 2) G 1/2" ) /100 2) G 3/4" ) /100 2) G 3/4" 1) max. allowed pressure difference, at which the valve closes against pressure (for 2-way valves) 56 (66) 2) for 3-way valves Size for G 3/4" in brackets Fig. 95 k VS = 0,25 k VS = 0,63 k VS = 1,6 k VS = 0,4 k VS = 1,0 k VS = 2, k VS = 4,0 ontrol valve can ship loose with or without connected pipework. Order No. k vs - value Separately supplied valves Separately supplied valves with piping Two-way 3-way Two-way 3-way Fig. 96 Pressure Druckverlust drop Δp [kpa] Δp (kpa) Water Wasservolumenstrom flow rate V [l/h] V (l/h) VGF.S203.0# VGF.S303.0# VGF.S204.0# VGF.S304.0# VGF.S206.0# VGF.S306.0# VGF.S210.0# VGF.S310.0# VGF.S216.0# VGF.S316.0# VGF.S225.0# VGF.S325.0# VGF.S240.0# VGF.S340.0# With mounted valves for a 4-pipe system the order number must be specified with the designation for the actuator, valve body and the k vs value of the heating valve, e.g. VGF.S316S310.0#. The symbol "#" is reserved for medium connection left (L) and right (R) (see Unit type code Page 102). Note: The max. pressure drop in heat exchanger with fully open valve should not exceed 25 kpa in cooling mode and 20 kpa in heating mode. 88 PR G Subject to change R5-01/2017

89 Flex-Geko omfort Edition Overview of valves Thermostatic expansion valve 75 47,5 Fig Ø Thermostatic expansion valve with external pressure equalization for best possible evaporator charging is especially designed for multiple injection through liquid distributor: variable capacity from 0.3 to 21.5 kw via exchangeable nozzle sets regardless of ambient temperature regulation of expansion valve is performed with high sensitivity for smallest possible overheating stable control performance through special adsorbing filling with attenuating features long service life thanks to welded stainless steel membrane superheating. Technical Data Refrigerant: R410 Max. test pressure: 32 bar (simultaneously for all connections) Max. suction pressure: 29 bar Max. ambient temperature: 100 Max. sensor temperature: 140 Static superheating: approx. 3 K apillary tube length: 1.5 m asing/membrane head: brass/stainless steel Solder connections: copper pipe Depending on size of the basic unit thermostatic expansion valves are equipped with the following nozzle sizes and connections: Model size Nozzle size Liquid connection Suction gas connection Pressure equalization line Sleeve Sleeve Sleeve Ø 6 mm Ø 12 mm Ø 6 mm Ø 10 mm Ø 12 mm Ø 6 mm Ø 10 mm Ø 12 mm Ø 6 mm Ø 10 mm Ø 12 mm Ø 6 mm Ø 10 mm Ø 12 mm Ø 6 mm Ø 10 mm Ø 12 mm Ø 6 mm Ø 10 mm Ø 12 mm Ø 6 mm Ø 10 mm Ø 12 mm Ø 6 mm ttention! In general, thermostatic expansion valves are designed for operation below 0 of evaporation temperature. Due to safety reasons and in order to prevent condensation on non-insulated components of basic casing, the operation with evaporation temperatures < 2 is not allowed. PR G Subject to change R5-01/

90 Overview of valves Shut-off valves Flex-Geko omfort Edition k vs -value 1.45 SW19 ll valves, except the thermostatic expansion valves, can be optionally supplied with shut off valves at the return line. 3/4" 51 MNG 3/4" 32 These valves are used for shutting off the cooling or heating medium as well as for adjusting and equalizing medium flow rate. Depending on rated size of the control valve, shutoff valves are used with k vs -value of 1.45 or k vs - value k vs -value 2.20 onnection 3/4" SW /4" 33 Technical Data: Rated pressure: 10 bar Max. water inlet temperature: 130 ph-value: s medium - water with a max. 50% glycol rate is allowed. Depending on the fitted valves, the shut-off valves are supplied with outer thread connection (designation number 4, see unit type code Page 102) or with connecting nut and solder fitting (designation number 5, refer to unit type code Page 102): 3/4" 15 ontrol valve Shut-off valve Fig k vs -values onnection thread k vs -values onnection thread Solder fitting for u pipe ,60 G 1/2" 1.45 G 3/4" Ø 15 The setting of the necessary medium flow rate is carried out on the basis of the following diagrams. The pre-setting corresponds to the number of rotations to the left of the adjusting screw starting from the right stop position (valve closed). k vs -value 1.45 Pre-setting k vs -value 2.20 Pre-setting 50 1/4 1/ / /2 1 11/2 2 21/ Δp [kpa] Δp [kpa] Water flow rate m W [kg/h] Water flow rate m W [kg/h] Presetting 1/4 1/ / kv values Presetting 1/ / / kv values Fig PR G Subject to change R5-01/2017

91 Flex-Geko omfort Edition Overview of valves all cocks 26 3/ SW 27 3/4 ll valves, except thermostatic expansion valves, can be optionally supplied with ball cocks. These are necessary to shut off cooling or heating medium. Material: Valve body: all: Gasket: brass brass, ground rubber 63 Technical data: Rated pressure: 10 bar Max. water inlet temperature: 110 k vs -value 6.70 m³/h Water and water/glycol are allowed as medium. 3/4 15 Depending on the fitted valves, ball cocks are supplied with outer thread connection (designations 2 and 4, see Unit type code Page 102) or with connecting nut and solder fitting (designations 3 and 5, see Unit type code Page 102). all valve 18 k vs values onnection thread Solder fitting for u pipe 6.70 G 3/4" Ø 15 Fig. 100 The servicing of the ball cock is performed via a flat-bladed screwdriver Δp [kpa] 10 9,0 8,0 7,0 6,0 5,0 4,5 4,0 3,5 3,0 2,5 2,0 1,5 1,0 0,9 0,8 0,7 0,6 0, Water flow rate m W [kg/h] Fig. 101 PR G Subject to change R5-01/

92 ontrol via thermostat / miniature switch, controls by others Flex-Geko omfort Edition Terminal box with connections for fan coil units Terminal box Metal sheet electric control box Order code basic unit GFxx.xxxx.xx GFxx.xxxx.xx GFxx.xxxx.xx GFxx.xxxx.Exx GFxx.xxxx.Hxx GFxx.xxxx.Kxx GFxx.xxxx.Lxx GFxx.xxxx.Mxx GFxx.xxxx.Oxx GFxx.xxxx.Rxx In order to carry out connection to the control system all components such as fan(s) and valve(s) are wired in the terminal box. Depending on the selected unit configuration and valve equipment, the terminal box is either made of plastic or sheet steel. The selection is performed using the unit type code, as illustrated. The following table illustrates possible variants. Using thermostat and miniature switches of series standard control is provided for fan coil units. The switches can be used with: Valve type Switch type Return-air Order code sensor w/o with E motor motor ooling and Heating ooling or Heating Heating ooling 4-pipe system chilled and warm water 2-pipe system chilled or warm water 2-pipe system warm water 2-pipe system chilled water lternatively to a return air sensor, a room temperature sensor can also be connected to a ET type switch. If a return air sensor is used, the fan must be operating continuously. Possible install. MT4D (fan continuous mode) 0 2 ET.E 0 5 J, MT2Z (fan and valve control) order contact temperature thermostat 0 4 separately (using order number ) MT2D (fan continuous mode) order contact temperature thermostat separately using order number ET.E with flow sensor (flow sensor included in the package) 1 6 J, MT2Z (fan and valve control) 0 4 MT2D (continuous fan mode) 0 3 ET.E 0 5 J, MS 0 1, MT2Z (fan and valve control) 0 4 MT2D (continuous fan mode) 0 3 ET 0 5 J, MS 0 1, Please consider: In connection with thermostat / miniature switches only 2-point open/close valve actuators can be used (T). If a ET.E switch is installed, a return air sensor or room temperature sensor must be connected! Switches ship loose Relay kit is necessary if a maximum four fan coil units with motors are switched in parallel. Mixing of different FU types and sizes is allowed. The ET.E relay kit is absolutely required using model size 8 in connection with the switch. With kit 2 Without kit 0 Switches installed Order code D 0 1 Slave unit with relay kit Order code D Z D NOTIE! If you want to use several units with an motor with one switch you will need a relay kit for each unit. For units with cooling function we recommend fan continuous operation (fin drying) 92 PR G Subject to change R5-01/2017

93 Flex-Geko omfort Edition ontrol via thermostat / miniature switch, controls by others Operation of thermostat and speed switches Switch type Functions MS On/off switch Fan speed selection switch casing: white, similar to RL 9016 ontrol elements: grey, similar to RL 7044 Protection class IP 30 MT On/off switch Fan speed selection switch Setpoint setting room temperature (mechanical setting range limitation as accessory on request) Thermostat with neutral zone (only MT4D) casing: white, similar to RL 9016 ontrol elements: grey, similar to RL 7044 Protection class IP 30 ET.E Fan speed selection switch standby auto or E fan control External valve control possible (e.g. floor heating, chilled ceiling) Setpoint setting for room temperature ( setting range limitation) Thermostat with settable neutral zone Input for unit enabling via volt free dry contact by others Room frost protection, connection possibilities for external room or return-air sensor and flow sensor Integrated room temperature sensor Interface MODbus RS485 RTU Factory pre-configured casing: white, similar to RL 9016 Protection class IP 30 Sensors Room temperature sensor Flow sensor Return-air sensor ontact thermostat Functions Thermistor sensor for on-wall mounting NT-sensor element; resistance coefficient at 25 = 10 kω casing: white, similar to RL 9010 Protection class IP 20 Dimensions in mm (W x H x D): 84 x 84 x 22 Thermistor sensor for mounting at inlet with clip NT-sensor element; resistance coefficient at 25 = 10 kω Sensor dimensions (D x L): 6.25 x 27 mm; cable length 2.5 m Max. ambient temperature 100 Thermistor sensor for mounting in unit NT-sensor element; resistance coefficient at 25 = 10 kω Sensor dimensions (D x L): 6.25 x 27 mm; cable length 2.5 m Max. ambient temperature 60 ontact temperature thermostat for change-over between heating or cooling mode For mounting on pipework with diameter from 15 mm to 28 mm Operating voltage 250 V 50/60 Hz Dimensions in mm (W x H x D): 79 x 50 x 44 dditional sensors which are supplied loose and wired on-site by others should be ordered optionally (not in connection with the above-mentioned switch types MT and MS). NOTIE! Flow and return air sensor are integrated in the relevant controls packages and do not have to be selected separately if ordered using the package number. PR G Subject to change R5-01/

94 System Description Flex-Geko omfort Edition Overview Normal/ economy mode buttons Speed stage selection switch Valve actuator type 2 point (modulating) 3 point (modulating) LEDs for status/fault/ external control Setpoint temperature switch MTRIX 2000 MTRIX 2000 control system supports all basic functions (heating/cooling) of recirculating-air fan coil unit and can be used in the following unit types: 2-pipe units only heating 2-pipe units only cooling 2-pipe units cooing or heating (change over) 4-pipe unit cooling and heating The assignment of speed stage can be carried out manually in a 3-speed mode or automatically in a 3-speed mode based on the deviation of actual temperature from the setpoint. Valves with on/off or 2-point modulating control behavior and a supply voltage of 230 V can be activated to control the heating and/or cooling capacity. With 2- pipe units 3-point modulating valve actuators can alternatively be controlled as well. The operation of 24 V valve actuators is possible as well (transformer by others required). The direct connection of an external room temperature sensor is not possible with changeover units, but can be performed via a Global Module. n alarm signal can also be processed by a Global module. Direct tapping is not possible. dditionally, the MTRIX 2000 enables monitoring of the fan motor via thermal contacts with external leads as well as the condensate water level for cooling units with a condensate pump. n alarm signal can also be processed by a Global module. Direct tapping via floating contacts is not possible. The connected sensors are monitored as well. The OP2000 control panel enables the setpoint values to be set quickly and easily without extensive prior experience. Mechanical limit stops can be used to limit the setting range for the setpoint temperature and speed stage. Room temperature is measured via a sensor integrated in the control panel. If the control panel is positioned in an unfavorable location (such as by the door), an external temperature sensor or return air sensor can be connected (not possible on changeover systems). System faults are signaled centrally via the red malfunction LED and output using a changeover contact. If economy mode is activated, it is displayed via the yellow LED integrated into the button. In addition to protection class IP20 (OP21 ), an OP21 l control panel in protection class IP54 for moist areas can be used. The connection in the unit is made via plug-in cage clamps. Electronics, fans and valves (230V) are fused separately via two pre-fuses on the power supply. fuse of 10 type must be supplied to provide the necessary circuit protection. The MTRIX 2000 can be used for controlling individual recirculating-air units and recirculating-air unit groups as well. The integrated MTRIX.Net bus system enables integration of up to 16 several groups to one network. The combination with MTRIX 3000 controllers and connection of Global Modules and communication interfaces is also possible. 94 PR G Subject to change R5-01/2017

95 Flex-Geko omfort Edition System Description / 5 Valve actuator 2 point 3 point MTRIX 3000 The MTRIX 3000 control system is based on the MTRIX 2000 system and provides the following additional functions. These features are described as follows: 3-point valves with modulating control behavior can be applied on 4-pipe systems. Mixed operation is also possible (2-point cooling valve / 3-point modulating heating valve or 3-point modulating cooling valve / 2-point heating valve). Status and alarm signals are relayed via two change-over contacts on the unit. The maximum load on the contacts at 230 V is 4 ohmic / 2 inductive. The supply air temperature can be limited for heating and cooling. Fixed and sliding limits can be defined. n external temperature sensor or return air sensor can be connected to all system types. n additional control input enables the following operating modes that can be set externally: Normal/economy operation or Unit OFF with frost protection Various types of control panels are available. The range varies from a simple variant with setpoint temperature and fan operating mode selection using infrared remote control to a control panel with display. The display unit can also be supplied with an integrated weekly timer. MTRIX 4000 The MTRIX 4000 control system is based on the MTRIX 2000/3000 system and provides the following additional functions. These features are described as follows: In order to provide enhanced selection of heating/cooling duty - a five speed and continuous (E) fan motor control is enabled. For applications with highest comfort requirements electronic control elements provide absolutely silent valve control. Four additional control inputs enable external assignment of the following operating modes: Normal operation Economy mode Free mode Unit OFF with frost protection ompulsory setting of a fan speed It is also possible to connect the outdoor sensor for activation of summer compensation. Outdoor air temperature reading is automatically transmitted to all units connected within the MTRIX.Net. PR G Subject to change R5-01/

96 Overview of Features Flex-Geko omfort Edition Performance characteristics MTRIX 2000 MTRIX 3000 MTRIX 4000 Unit type 2-pipe systems: only heating, only cooling ; heating or cooling 4-pipe system heating and cooling Fan up to 3 speeds up to 5 speeds continuous (E motor) Temperature related fan speed switching Minimum speed 1 Motor monitoring with external thermal contacts Valve control 2 and 4-pipe system: on/off actuators 2-pipe system: 3-point modulating actuator 4-pipe system: 3-point modulating actuators Silent control (semiconductor relay) External heating valve with cooling unit with fan switch off Electric heater 1-speed 2-speed Frost protection Indoor nti-freeze Protection Unit anti-freeze protection Summer/winter compensation * * Supply temperature limitation Min/Max limitation heating Min/Max limitation cooling ontrol inputs Economy mode or door or window contact * Measuring outside temperature Economy mode and door or window contact and unit OFF and autonomous operating mode via local sensor connection * * using MTRIX.I Measuring inlet temperature via local sensor connection Measuring return air temperature Measuring supply air temperature via local sensor connection via local sensor connection ** Messages/signals larm condensate level too high with unit switch off Heating and/or cooling request * * Status signal via change-over contact * Fault signal via change-over contact * Mixing-air damper control Open/close or continuous Exhaust fan control 1 speed via relay output via power unit / exhaust air controller hiller control up to 2 speeds via MTRIX.RF module ontrol modes Room temperature control Supply ir Temperature ontrol MTRIX.Net bus system Geko-Drive continuous via add-on module MTRIX Geko-Drive * can be extended by: MTRIX.DI MTRIX.I MTRIX.DO MTRIX.RF MTRIX.EM MTRIX.LON Service tool MTRIX.P ontrol panels MTRIX OP21x * only with add-on module ** not with heating or cooling units MTRIX OP30x MTRIX OP31x MTRIX OP44x MTRIX OP50x/51x 96 PR G Subject to change R5-01/2017

97 Flex-Geko omfort Edition Mounting control panels s the control panel is divided in two parts, its cover should only be snapped on the mounting plate for commissioning. This provides optimum protection against dirt and damage for the control panels during the construction phase. The cable connection is established via cage clamps. This enables quick and easy use of solid and flexible cores. To mount the control panel in a standard flush-mounted socket, corresponding drill holes need to be provided in the mounting plate. The control panel can also be fitted directly on the wall (cable laid under plaster or in cavity wall). ontrol panel can be mounted on the basic unit using the ZE OP installation kit. For this case an external room or return temperature sensor must be provided. IP54 control panels for moisture proof applications are available on request. To prevent dirt accumulation or accidental operation, control panel covers are available as accessory items. PR G Subject to change R5-01/

98 Sensors/ccessories Flex-Geko omfort Edition Room temperature sensor order Nr Thermistor sensor for on-wall mounting NT sensor element casing: white, similar to RL 9010 Resistance coefficient at 25 = 10 kω IP 20 class Dimensions in mm (W x H x D): 84 x 84 x 22 Fig. 102 The room temperature sensor replaces the room temperature sensor in the MTRIX OP XX control panels. The additional sensor must be fitted if the control panel is integrated in the FU or mounted in a location that is unsuitable for accurate temperature measurement. External sensor order-nr Fig. 103 Thermistor sensor for measuring ambient temperature e.g. for summer/winter compensation (according to DIN 1946 part 2/3) NT sensor element Impact resistant white plastic casing for outdoor wall mounting PG bolts Resistance coefficient at 25 = 10 kω IP 54 class Dimensions in mm (W x H x D): 65 x 50 x 37.5 Unit cap White order nr.opd. (for OP21/OP30/OP31/OP44) Light grey order-nr.opd.i (for OP21I/OP30I/OP31I/OP44I) For covering operating elements of control panel The control panel cover is hung into the guide slots of the control panel and protects the control panel from dirt accumulation and accidental operation. Fig PR G Subject to change R5-01/2017

99 Flex-Geko omfort Edition MTRIX controls Global Modules The global modules of the MTRIX control system are designated for input and output of MTRIX system signals. Global modules enable the transmission of messages and unit status information to external units as well as control via such external units. The modules can be integrated anywhere within the MTRIX network. network can contain and simultaneously operate a maximum of 2 MTRIX modules of the same type (DI,DO,I) or 16 modules (LON). The modules are supplied with the default factory configuration. onfigurations with other settings can be performed using the MTRIX.P software. Technical Data. Power supply 24 V D ± 15 % Protection class IP 20 Operating temperature 0 to +45 Fusing 10 T Fixation Mounting rail MTRIX.DI max. current consumption 0.1 MTRIX.DI dimensions 106 mm x 90 mm x 58 mm MTRIX.DO max. current consumption 0.14 MTRIX.DO contact load 250 V/5 (ohmic); 2 (inductive) MTRIX.DO dimensions 160 mm x 90 mm x 58 mm MTRIX.I rated current consumption 0.03 MTRIX.I dimensions 160 mm x 90 mm x 58 mm MTRIX.LON rated current consumption MTRIX.LON dimensions 106 mm x 90 mm x 58 mm Digital input module MTRIX.DI The digital input module MTRIX.DI is used to receive 8 independent digital control signals. Factory configuration: Input Valid for losed contact results in 1 ll groups HV Mode Heating 2 ll groups HV Mode ooling 3 ll groups normal operation 4 ll groups Economy mode 5 Group 0 Fan in speed 3 6 Group 0 Secondary-air louvre close 7 Group 0 Secondary-air louvre open 8 Group % mixed-air operation Digital output module MTRIX.DO The module is fitted with 8 separate digital outputs with volt-free changeover contacts. Factory configuration: Output Valid for Relay on signals 1 ll groups Operating principle 2 Group 0 Fault signal 3 Group 0 Frost alarm 4 Group 1 Fault signal 5 Group 1 Frost alarm 6 Group 2 Fault signal 7 Group 2 Frost alarm 8 ll groups Fault signal PR G Subject to change R5-01/

100 MTRIX controls Flex-Geko omfort Edition nalog input module MTRIX.I The module is equipped with 8 independent analog inputs that are controlled using 0 10 V/2..10 V signals or can be fitted with NT sensors (10 k Ohm/25 ). Factory configuration: Eingang valid for Parameter rt Filter value 1 ll groups Outdoor temperature MTRIX.LON module NT 0 Measured range 2 ll groups Inlet temperature NT 0 3 Group 0 Room set point V Group 1 Room set point V Group 2 Room set point V Group 1 Outdoor-air rate V % 7 Group 2 Outdoor-air rate V % 8 Group 3 Outdoor-air rate V % Group 2 Group 3 Group 1 Group 4 Group 16 The MTRIX.LON communication module is part of the global modules of the MTRIX control system and is used for connecting the MTRIX control system to a network structure in accordance with the LON WORKS standard. It enables the connection of HV equipment to a building management system or other facility management systems. The modules also enables external systems such as dampers/louvres or lighting systems to be regulated via the MTRIX OP50/51 control panel. The module can be integrated at any point within the MTRIX network. Service software MTRIX.P MTRIX.P service software provides further comprehensive functions for settings, commissioning and data recording of the MTRIX controller system. The service software can be connected via the service interface which is integrated in all control panels, controllers, global modules, clock timer and communication modules. Your P must have a US port; the enclosed adapter establishes the connection between the P and the service interface. The following main functions are available: utomatic scanning of network with display of found users Display of errors as text hanging parameters as e.g. temperature limits, times or control mode Display of actual values Display of current unit status, e.g. HV Mode or valve position Manual control of actuators for fans and valves Reading, saving and writing configuration data Online display of module, status and network data Recording and saving of temperature curves and switch states of driven components with sample rate Offline settings Programming of required inputs and outputs (controllers, global modules) ctivation of messaging and network data onfiguration of controller and control panel functions Input of sensor correction factors Selection of 6 different languages P system requirements: P with 233 MHz processor frequency or higher 20 M available disk space Minimum monitor resolution of 800 x 600 pixels US interface for N adaptor The software is compatible with the following operating systems: Windows 98 Second Edition; Windows 2000; Windows XP Together with main software on a D, the installation instructions and interface module for connection to the P US port are also included. 100 PR G Subject to change R5-01/2017

101 Flex-Geko omfort Edition MTRIX controls MTRIX.OP71 control panel for all groups The MTRIX.OP71 control panel is designed for operation from one central point. This control panel can be integrated at any location within the MTRIX network and can be simultaneously operated in 16 groups. Up to 16 unit groups can be assigned to one cluster: One unit group per each cluster Each cluster to include up to 16 unit groups. lear text menus and "push&turn" function enable easy handling during operation or configuration. maximum of 16 unit groups can be individually grouped to clusters. Using a control panel the desired setpoints for temperature, fan speed, etc. can be assigned for each cluster. Thanks to comprehensive features of the control panel, the necessary room or return air sensors are located in the respective groups (group locations). Local control panels (OP2xx, OP3xx, OP4xx, OP5x) can be additionally integrated in individual groups. Their functional scope can be defined and adjusted using the control panel for all groups. Thus, a relative daily setpoint can be entered via a local control panel, whereas the standard setpoint is assigned via the OP71. The integrated clock timer enables to assign 8 weekly programmes to clusters at any sequence. Each weekly programme enables to enter four switching times per day (2 x On/2 x Off), that can also be set to be valid for the whole day. In addition, it is possible to set 8 special switching days with up to four switching times (2 x On/2 x Off) per designated switching day. Holidays / bank holidays can be set using the calendar annual programme. On holidays the unit can be set to operate in "unit off" or economy mode. The summer / winter time changeover is performed automatically. The control unit is currently supplied with 7 selectable languages: German English French Dutch Polish zech Hungarian. Two different variants are available: MTRIX.OP71 with IP20 protection type; colour white (similar to RL 9016) MTRIX.OP71I with IP54 protection type; colour light grey (similar to RL 7035). PR G Subject to change R5-01/

102 Unit type code Flex-Geko omfort Edition Unit type code ontrols package Valve code G F 1 1. U 0 W D V G F. R R L Model size 1 = Model size 1 2 = Model size 2 3 = Model size 3 4 = Model size 4 5 = Model size 5 6 = Model size 6 7 = Model size 7 8 = Model size 8 apacity stage 1 = apacity stage 1 2 = apacity stage 2 3 = apacity stage 3 4 = apacity stage 4 erodynamic function U = Recirculating-air unit M = Mixed-air unit Medium function Heating only 0W = PWW 0E = Electric full heating 0F = PWW + E-add-on heating ooling only W0 = hilled water pump D0 = Direct Expansion ooling or heating W = Pumped chilled - warm water W = PW - PWW + E-add-on heating ooling and heating Warm water = Pumped chilled - warm water WE = PW - Electric heater WF = PW - PWW + E-add-on heating DW = Direct evaporator - PWW oil connection * Wall 1 = Left 2 = Right eiling 3 = Left 4 = Right Speeds Terminal box = Speed 1, 2, 3 = Speed 2, 3, 4 = Speed 3, 4, 5 E = Speed 1, 3, 5 H = Speed 1, 2, 3, 4, 5 F = Min..Max (E motor) terminal box Metal sheet electric control box with terminal block or for controls K = Speed 1, 2, 3 L = Speed 2, 3, 4 M = Speed 3, 4, 5 O = Speed 1, 3, 5 R = Speed 1, 2, 3, 4, 5 S = Min..Max (E motor) metal switch box with terminal block or for controls Motor/thermal contacts Standard motor (ball bearings ) with integ. therm. contact 0 = Standard motor (ball bearings) with external therm. contact 1 = E = E motor (ball bearings) ondensate pump 0 = with condensate drain 1 = with condensate pump ir flow ** = irculating air: irculating air / - supply air / Mixed air: Fresh air / - circulating air / - supply air / = irculating air: irculating air / - supply air / Mixed air: Fresh air / - circulating air / - supply air / = irculating air: irculating air / - supply air / Mixed air: Fresh air / - circulating air / - supply air / D = irculating air: irculating air / - supply air / Filter Mixed air: 1 = G1 mat filter 2 = G2 mat filter 3 = G3 mat filter Fresh air / irculating air / - supply air / ontroller type 0=Terminal box 2 = MTRIX = MTRIX = MTRIX 4000 ontroller package no. Terminal IP20 = OP21 = OP30 = OP31 D = OP44 E = OP50 F = OP51 N = IR 1 = MS 2 = MT4D 3 = MT2D 4 = MT2Z J = ET.E U = OP20 Z = without control panel Unit type Single/master unit, control panel = Enclosed = installed = Master unit without control panel Slave unit D = W/o control panel asing code Z G F Model size 1 = Model size 1 2 = Model size 2 3 = Model size 3 4 = Model size 4 5 = Model size 5 6 = Model size 6 7 = Model size 7 8 = Model size 8 ccessory class = omfort casing E = Economy casing Operating mode 0 = DX-connection w/o expansion valve (only cooling circuit) R = 3-point 230 V T = 2-point 230 V N = 3-point 24 V Q = 2-point 24 V S = 0-10 V, 24 V = 3-point 230 V + 2 contacts E = Expansion valve R410 (only cooling circuit) Valve body 0 = DX-connection with or w/o expansion valve (only cool circuit) 2 = 2-way 3 = 3-way K vs -value 00 = W/o expansion valve (only cooling circuit) 03 = K vs 0.25 (R, N, S, ) 04 = K vs 0.40 (R, N, S, ) 06 = K vs 0.63 (R, N, S, ) 10 = K vs 1.0 (R, N, S, ) 16 = K vs 1.6 (R, N, S,, T, Q) 25 = K vs 2.5 (R, N, S,, T, Q) 40 = K vs 4.0 (R, N, S, ) S1- S8 ooling/heating circuit = Setting expansion valve (only cooling circuit) onnection/shut-off 0 = Inlet/outlet flow with outside thread 1 = Inlet/outlet with solder fitting 2 = Inlet/outlet + ball trap with external thread 3 = Inlet/outlet + ball trap with solder fitting 4 = Inlet + ball trap/ outlet + shut-off valve with external thread 5 = Inlet + ball trap/ outlet + shut-off valve with solder fitting Medium connection L = Left R = right Heating circuit asing design ** 01 = irculating air / - supply air / (for recirculating-air units, air flow ) 02 = irculating air / - supply air / (for recirculating-air units, air flow ) 03 = irculating air / - supply air / (for recirculating-air units, air flow ) 04 = irculating air / - supply air / (for recirculating-air units, air flow D) 05 = irculating air / - supply air / + foot cover (for recirculating-air units, air flow ) 06 = irculating air / - supply air / + foot cover (for recirculating-air units, air flow ) 07 = irculating air / - supply air / + unit foot cover + air intake grille (for recirculating units, air flow - mixed air units, air flow, ) 08 = irculating air / - supply air / + unit foot cover + air intake grille (for recirculating units, air flow - mixed air units, air flow, D) 13 = irculating air - supply air + with a rear shift (for recirculating-air units, ceiling, air flow ) 23 = irculating air - supply air + rear wall (for recirculating units, vertical floor installation, air flow ) Discharge 1 = Rigid grille 2 = djustable grille 3 = Rigid aluminium grille (discharge top/front) Note! The models highlighted in grey are available on request. *) Front connection side, facing discharge **) ir flow is first indicated for a wall unit and then for a ceiling unit Refer to definition Page 74 Fig PR G Subject to change R5-01/2017

103 Flex-Geko omfort Edition Unit type code PR G Subject to change R5-01/

104 DencoHappel is a global company with expertise in air treatment, air conditioning and air filtration. Our nearest sales and service teams will be glad to discuss ideas and develop creative and effective solutions with you.

Product Brochure Fan coil units for suspended ceilings HyPower-Geko. Energy efficient Powerful Hygienic Low noise

Product Brochure Fan coil units for suspended ceilings HyPower-Geko. Energy efficient Powerful Hygienic Low noise Product Brochure Fan coil units for suspended ceilings HyPower-Geko Energy efficient Powerful Hygienic Low noise Optimal climate: Hygienic. Efficient. Sustainable. The HyPower-Geko fan coil units generate

More information

DATA & FACTS Unit Heaters MultiMAXX HB. Quick Selection and Fast Delivery

DATA & FACTS Unit Heaters MultiMAXX HB. Quick Selection and Fast Delivery DATA & FACTS Unit Heaters MultiMAXX HB Quick Selection and Fast Delivery Table of Contents MultiMAXX HB Unit Type Code... 3 About this Catalogue... 4 Overview of Capacity... 5 Unit Description... 6 Unit

More information

Air-Cooled Liquid Chiller with integrated hydraulic module

Air-Cooled Liquid Chiller with integrated hydraulic module Air-Cooled Liquid Chiller with integrated hydraulic module Cooling only: CGAN 200-250 - 300-400 - 450-490 - 500-600 - 700-800 - 900-925 Reversible: CXAN 200-250 - 300-400 - 450-490 - 500-600 - 700-800

More information

MAJOR 2 NCH. Ductable units. High pressure and high capacity ductable units RANGE NCH Y NCH NCH I COADIS COMBI. Motor optional

MAJOR 2 NCH. Ductable units. High pressure and high capacity ductable units RANGE NCH Y NCH NCH I COADIS COMBI. Motor optional Y + U I COADIS COMBI High pressure and high ductable units Motor optional is a non independent air conditioning terminal unit for heating and cooling offices and hotels. With reduced dimensions and designed

More information

Fan coil units Model DECO. - heating - cooling - ventilation

Fan coil units Model DECO. - heating - cooling - ventilation Fan coil units Model DEO - heating - cooling - ventilation Fan coil units omfortable indoor climate In buildings, pleasant working and living conditions are to a large degree determined by the indoor climate.

More information

TECHNICAL DOCUMENTATION WOLF AIR HEATERS LH-EC / LH. 30m 3 /h

TECHNICAL DOCUMENTATION WOLF AIR HEATERS LH-EC / LH. 30m 3 /h TECHNICAL DOCUMENTATION WOLF AIR HEATERS LH-EC / LH 30m 3 /h THE EXTENSIVE EQUIPMENT RANGE from system supplier WOLF offers the ideal solution for commercial and industrial buildings, new build and modernisation

More information

A 601 A B C. 1. How it works

A 601 A B C. 1. How it works 601 W4 DXN6P25 Variable flow-control 6-way valve, series DXN6_ For 4-pipes climate ceilings with change-over Pressure independent variable flow-control Integrated flow measurement Power supply U v : 24Volt

More information

next dx next dx rcgroupairconditioning NEXT DX: Direct expansion close control air conditioners equipped with scroll compressors and Plug-fans.

next dx next dx rcgroupairconditioning NEXT DX: Direct expansion close control air conditioners equipped with scroll compressors and Plug-fans. NEXT DX: Direct expansion close control air conditioners equipped with scroll compressors and Plug-fans. Cooling Capacity: 6,4 97,4 next dx C rcgroupairconditioning R410 E C UP FLOW DOWN FLOW MIN FETURES

More information

CENTRIFUGAL FAN COIL UNIT VCE

CENTRIFUGAL FAN COIL UNIT VCE CENTRIFUGAL FAN COIL UNIT VCE 0,51 kw 11,00 kw 0,85 kw 23,75 kw 129 m 3 /h 2003 m 3 /h VCE DESIGN QUALITY COMFORTRELIABILITY 3VERSION12 SIZE DESIGN VCEx0 vertical with cabinet Air intake: bottom vertical

More information

NSM. R134a HIGH EFFICIENCY ALSO AT PARTIAL LOADS ENERGY SAVING MICRO-CHANNEL COIL QUICK AND EASY INSTALLATION NIGHT MODE.

NSM. R134a HIGH EFFICIENCY ALSO AT PARTIAL LOADS ENERGY SAVING MICRO-CHANNEL COIL QUICK AND EASY INSTALLATION NIGHT MODE. NSM ir/water chillers for outdoor installation with free cooling glycol free Screw compressors, shell and tube heat exchangers and axial fans from 306 2028kW 1402/9603 glycol free R134a HIGH EFFIIENY LSO

More information

DATA & FACTS Unit Heaters MultiMAXX HE. Fresh Air for Commercial and Industrial Companies

DATA & FACTS Unit Heaters MultiMAXX HE. Fresh Air for Commercial and Industrial Companies DATA & FACTS Unit Heaters MultiMAXX HE Fresh Air for Commercial and Industrial Companies Unit Description About this Catalogue MultiMAXX HE Dear Customer, This catalogue focuses on the MultiMAXX HE unit

More information

VLH 504 to Air-to-Water Reverse Cycle Heat Pumps. 126 to 294 kw. 133 to 307 kw

VLH 504 to Air-to-Water Reverse Cycle Heat Pumps. 126 to 294 kw. 133 to 307 kw Air-to-Water Reverse Cycle Heat Pumps VLH 504 to 1204 126 to 294 kw 133 to 307 kw Technical Brochure TM VLH-N.3GB Date : June 2005 Supersedes : TM VLH-N.2GB/07.04 Specifications Advantages Range extension

More information

Air/Water chillers for outdoor installation Screw compressors, shell and tube heat exchangers and axial fans Cooling capacity kW 1402/9603

Air/Water chillers for outdoor installation Screw compressors, shell and tube heat exchangers and axial fans Cooling capacity kW 1402/9603 NEW NSM ir/water chillers for outdoor instation Screw compressors, shell and tube heat exchangers and axial fans ooling capacity 302 2100kW 1402/9603 cooling only R134a ermec participate in the EUROVENT

More information

fåçìëíêá~ä=~áê=åççäéêë=qvo pí~åç~êç=åççäéêë=ïáíü=ëí~áåäéëë=ëíééä=íìäáåö

fåçìëíêá~ä=~áê=åççäéêë=qvo pí~åç~êç=åççäéêë=ïáíü=ëí~áåäéëë=ëíééä=íìäáåö fåçìëíêá~ä=~áê=åççäéêë= pí~åç~êç=åççäéêë=ïáíü=ëí~áåäéëë=ëíééä=íìäáåö O `çåíéåíë= page Model indication..................................2 Eurovent.......................................2 Capacities......................................2

More information

Guide Specifications. General. Casing. Coil/Drain pan. Fan/Motor

Guide Specifications. General. Casing. Coil/Drain pan. Fan/Motor Guide Specifications General CR-A series ducted concealed chilled water fan coil units have an air flow range from 45 to 3060 cubic meters per hour with a capacity range from kw up to 9 kw. The CR-A series

More information

Total cooling capacity kw Total heating capacity kw Features

Total cooling capacity kw Total heating capacity kw Features Room Fan Coils Idrofan Quality Management Systems 42N Total cooling capacity 0.75-6.35 kw Total heating capacity 0.60-9.50 kw The new generation 42N_S product range combines aesthetic and attractive design

More information

^áêëçåâ=ìåáí=åççäéêë=qvoj^ pí~åç~êç=åççäéêë=ïáíü=pí~áåäéëë=píééä=íìäáåö

^áêëçåâ=ìåáí=åççäéêë=qvoj^ pí~åç~êç=åççäéêë=ïáíü=pí~áåäéëë=píééä=íìäáåö ^áêëçåâ=ìåáí=åççäéêë= pí~åç~êç=åççäéêë=ïáíü=pí~áåäéëë=píééä=íìäáåö O `çåíéåíë= page Model indication................................ 2 Eurovent...................................... 2 Capacities.....................................

More information

Fans Air Handling Units Air Distribution Products Fire Safety Air Curtains and Heating Products Water terminals SYSCOIL. Centrifugal fan coil units

Fans Air Handling Units Air Distribution Products Fire Safety Air Curtains and Heating Products Water terminals SYSCOIL. Centrifugal fan coil units Fans Air Handling Units Air Distribution Products Fire Safety Air Curtains and Heating Products Water terminals SYSCOIL Centrifugal fan coil units SYSCOIL Fan coil units Compact, slim fan coil units. Available

More information

PVHRU Max Quiet. Engineering Solutions. Packaged Void Heat Reclaim Unit. Acoustic Testing Laboratory College of Science & Technology

PVHRU Max Quiet. Engineering Solutions. Packaged Void Heat Reclaim Unit. Acoustic Testing Laboratory College of Science & Technology AIR HANDLERS LTD PVHRU Max Quiet Packaged Void Heat Reclaim Unit 1262 Acoustic Testing Laboratory College of Science & Technology Engineering Solutions The Company Air Handlers has been trading since May

More information

Homepage > Products > Chilled Beams and Multi Service Chilled Beams > Active Chilled Beams > SMART BEAM > Type SMART BEAM SMART BEAM

Homepage > Products > Chilled Beams and Multi Service Chilled Beams > Active Chilled Beams > SMART BEAM > Type SMART BEAM SMART BEAM Homepage > Products > Chilled Beams and Multi Service Chilled Beams > Active Chilled Beams > SMART BEAM > Type SMART BEAM SMART BEAM MULTI-SERVICE ACTIVE CHILLED BEAM WITH TWO-WAY AIR DISCHARGE AND HORIZONTAL

More information

CBU144. Compact Booster Unit - single pump To ensure the quality of potable water according to EN1717. Product specification sheet

CBU144. Compact Booster Unit - single pump To ensure the quality of potable water according to EN1717. Product specification sheet CBU144 Compact Booster Unit - single pump To ensure the quality of potable water according to EN1717 Product specification sheet Version The Compact Booster Unit consists of the following modules, that

More information

Swimming Pool CSR2 Heat Recovery Equipment

Swimming Pool CSR2 Heat Recovery Equipment Swimming Pool CSR2 Heat Recovery Equipment LIFETIME WARRANTY OVER 90% HEAT RECOVERY LOW CARBON British manufacturing at its best EcoAir Box is a trademark of IPT +44 (01527) 492770 www.ecoairbox.co.uk

More information

Fan coil units MAJOR 2 CV/CH

Fan coil units MAJOR 2 CV/CH CH 41 D CV 1 D MAJOR 2: Design and performance HEE impeller for increased performance Motor optional MAJOR 2 is a non-independant chilled and/or hot water supplied air conditioning Comfort unit for the

More information

fåçìëíêá~ä=~áê=åççäéêë=qelo pí~åç~êç=åççäéêë=ïáíü=`ì=íìäáåö

fåçìëíêá~ä=~áê=åççäéêë=qelo pí~åç~êç=åççäéêë=ïáíü=`ì=íìäáåö = pí~åç~êç=åççäéêë=ïáíü=`ì=íìäáåö O `çåíéåíë= page Model indication..................................2 Eurovent.......................................2 Capacities......................................2

More information

Low Profile Unit Cooler

Low Profile Unit Cooler Low Profile Unit Cooler Publication No. 100.13 January, 2004 MEA Air Defrost - 3,900 to 39,000 BTUH Electric Defrost - 3,600 to 28,000 BTUH Hot Gas Defrost - 3,600 to 28,000 BTUH Small to Medium Walk -

More information

Individual climate control. Fan coil units Model DECO

Individual climate control. Fan coil units Model DECO Individual climate control Fan coil units Model DECO Fan coil units Comfortable indoor climate In buildings a pleasant work and living environment are, to a large degree, determined by the quality of the

More information

Chiller, Close control and Water terminals. Air Conditioning. Light Commercial, Commercial and Industrial

Chiller, Close control and Water terminals. Air Conditioning. Light Commercial, Commercial and Industrial Chiller, Close control and Water terminals Air Conditioning Light Commercial, Commercial and Industrial Water Terminals 133 Water Terminals Fan coils & Cassette Centrifugal fan-coil SYSCOIL Ductable fan-coil

More information

Engineering Data Manual. New : available with EC motor. High Static Pressure Ductable Fan Coil Unit. Models 07 to to 4650 m 3 /h

Engineering Data Manual. New : available with EC motor. High Static Pressure Ductable Fan Coil Unit. Models 07 to to 4650 m 3 /h Engineering Data Manual New : available with EC motor VH High Static Pressure Ductable Fan Coil Unit Models 07 to 27 800 to 4650 m 3 /h General Characteristics Presentation On model VH 07, coils have 4

More information

Submittal. RBHR Horizontal Low Profile Concealed with Plenum FCU-RBHR Top View (Drain Pan Omitted) Bottom View. Front View.

Submittal. RBHR Horizontal Low Profile Concealed with Plenum FCU-RBHR Top View (Drain Pan Omitted) Bottom View. Front View. Horizontal Low Profile oncealed with Plenum FU-RBHR-1.0 05-11-17 Top View (rain Pan Omitted) Left hand unit shown. ll dimensions are inches [millimeters]. [8] 26 [6] 21 [533] 27 [686] 31 [787] 41 [1041]

More information

CMTE. Tangential Fan Coil Series with Electronic Controlled Motor

CMTE. Tangential Fan Coil Series with Electronic Controlled Motor Tangential Fan Coil Series with Electronic Controlled Motor Designed by Very Low Electric Energy Consumption High Efficiency Extremely Low Noise Level Infra Red Remote Control Step-less Fan Speed Control

More information

NSM. R134a NEW HIGH EFFICIENCY ALSO AT PARTIAL LOADS ENERGY SAVING MICRO-CHANNEL COIL QUICK AND EASY INSTALLATION NIGHT MODE.

NSM. R134a NEW HIGH EFFICIENCY ALSO AT PARTIAL LOADS ENERGY SAVING MICRO-CHANNEL COIL QUICK AND EASY INSTALLATION NIGHT MODE. NEW NSM ir/water chillers for outdoor installation with free cooling Screw compressors, shell and tube heat exchangers and axial fans from 306 2028kW 1402/9603 free cooling R134a HIGH EFFIIENY LSO T PRTIL

More information

Technical Catalogue. Cassette Fan Coils Climmy Comfort 3

Technical Catalogue. Cassette Fan Coils Climmy Comfort 3 Technical Catalogue Cassette Fan Coils Climmy Comfort 3 CONTENTS INTRODUCTION Version Fan Coil Page 3 Page 4 Page 6 Page 7 Page 8 Page 12 Page 13 Page 15 Page 16 Page 18 Page 19 Page 20 Page 22 -ECM Version

More information

UTA STANDARD. Ductable units. Range. Air handling unit with high available static pressure. NEW Eco-Design Filter. V3000 control Fresh air management

UTA STANDARD. Ductable units. Range. Air handling unit with high available static pressure. NEW Eco-Design Filter. V3000 control Fresh air management Ductable units NEW Eco-Design Filter Air handling unit with high available static pressure V3000 control Fresh air management The range of air handling units is designed for suspended ceiling heating and

More information

CENTRIFLOW 3D WITH EC MOTOR >> Technical catalogue

CENTRIFLOW 3D WITH EC MOTOR >> Technical catalogue CENTRIFLOW 3D Plug Fan WITH EC MOTOR >> Technical catalogue air comfort CentriFlow 3D 2 GMEC CentriFlow 3D - Technical Catalogue Contents GENERL Description and survey chart pplication... 3 General Survey

More information

MEDIUM SILHOUETTE UNIT COOLERS AIR AND ELECTRIC DEFROST MODELS

MEDIUM SILHOUETTE UNIT COOLERS AIR AND ELECTRIC DEFROST MODELS 1 Catalog KM-MCD-0818A Replaces KM-CSA-101A, KM-DSA-101A, KM-MSA-1213A, KM-CSE-101A and KM-MSE-101A DSA, CSA, MSA, CSE, AND MSE SERIES MEDIUM SILHOUETTE UNIT COOLERS AIR AND ELECTRIC DEFROST MODELS MEDIUM

More information

Heat Exchangers. Evaporator Catalogue

Heat Exchangers. Evaporator Catalogue Heat Exchangers Evaporator Catalogue Version 30: January 2015 Heat Exchangers Thermocoil Catalogue V30 2015 Evaporators Page 2 INDEX EVAPORATORS PAGE Evaporator Design and Info 4 Quick Find List (Sorted

More information

VAV terminal units. Type TVM. For dual duct systems PD TVM 1

VAV terminal units. Type TVM. For dual duct systems PD TVM 1 X X testregistrierung VAV terminal units Type Variant -S Rectangular connection on the room end For dual duct systems VAV dual duct terminal units for dual duct systems with variable volume flows in buildings

More information

D M S 760 C01 A A 1 1

D M S 760 C01 A A 1 1 CONTENTS Description Features Options Available Selection Method Product Data Cooling Performance Data (85 F Ambient Cooling Performance Data (95 F Ambient) Cooling Performance Data (105 F Ambient)..............................

More information

Fan coil unit NBS 100/150

Fan coil unit NBS 100/150 Fan coil unit /150 Ferdinand Schad KG Steigstraße 25-27 D-78600 Kolbingen Telephone +49 (0) 74 63-980 - 0 Fax +49 (0) 74 63-980 - 200 info@schako.de www.schako.de Contents Description...3 Advantages...3

More information

COMFORT AIR CURTAIN. SensAir

COMFORT AIR CURTAIN. SensAir COMFORT AIR CURTAIN SensAir SensAir comfort air curtain Revolutionary climate separation The SensAir comfort air curtain sets a new standard in the field of climate separation. The highest level of comfort

More information

1 DESCRIPTION 2 WORKING PRINCIPLE 2.1 REGULATION ST

1 DESCRIPTION 2 WORKING PRINCIPLE 2.1 REGULATION ST PRESSURE INDEPENDENT ONTROL VLVE - P.I..V. ST.01.34.00 RT. 2136 RT. 2137 1 DESRIPTION The valves art. 2136 and 2137, better known by the acronym PIV (Pressure Independent ontrol Valve), have been designed

More information

1 AIR HANDLING UNIT TYPE AIR ACCESS 75

1 AIR HANDLING UNIT TYPE AIR ACCESS 75 SUPPLY 1 AIR HANDLING UNIT TYPE AIR ACCESS 75 Location : EXTERNAL Position : SIDE BY SIDE SLIDING PANELS for COMPLETE ACCESSIBILITY MULTI SERVICE BULKHEAD for HYDRAULIC AND ELECTRICAL CONNECTIONS Self-supporting

More information

Submittal DIMENSIONS SIZE FAN SIZE L W H C D E F G J K [406] [508] 25 [635] [406] 16 [406] 16 [406] 39-1/2 [1003] 44-1/2 [1130] 51 [1295] 59 [1499]

Submittal DIMENSIONS SIZE FAN SIZE L W H C D E F G J K [406] [508] 25 [635] [406] 16 [406] 16 [406] 39-1/2 [1003] 44-1/2 [1130] 51 [1295] 59 [1499] BC--1.0 03-01-1 Belt Drive Blower Coil Unit, Basic Unit Discharge ARGT. 1 4. See page 1 for filter rack details. 5. Base rail is optional on he base unit. See page 13. Base rails must be used with mixing

More information

Blue e+ chillers with the principle

Blue e+ chillers with the principle Blue e+ chillers with the principle Blue e+ chillers The world s most efficient range of chillers. The principle: Efficient Energy savings of up to 70% thanks to DC inverter technology Flexible Worldwide

More information

SECTION AIR TERMINAL UNITS

SECTION AIR TERMINAL UNITS SECTION 23 36 00 AIR TERMINAL UNITS PART 1 - GENERAL 1.1 SUMMARY A. Section includes constant volume terminal units, variable volume terminal units, dual duct terminal units, fan powered terminal units,

More information

High-efficiency Drinking Water Pump. Rio-Eco Therm N. Type Series Booklet

High-efficiency Drinking Water Pump. Rio-Eco Therm N. Type Series Booklet High-efficiency Drinking Water Pump Rio-Eco Therm N Type Series Booklet Legal information/copyright Type Series Booklet Rio-Eco Therm N All rights reserved. The contents provided herein must neither be

More information

Küba SG industrial

Küba SG industrial 66 Küba Blue Line : Specific advantages The is a master of customisation. No matter how great the demand for power, the is the answer. Its versatility allows the Küba SG industrial to master the most complex

More information

QUOTATION BLADE 7 LX. Product code GEAL6S2BAA

QUOTATION BLADE 7 LX. Product code GEAL6S2BAA 1 of 10 Mattei rotary vane compressors are the result of 90 years of investments in research and development to improve performance and lessen the impact on the environment. Designed for industrial continuous

More information

COMFORT AIR CURTAIN. SensAir

COMFORT AIR CURTAIN. SensAir COMFORT AIR CURTAIN SensAir SensAir comfort air curtain A new wave in climate separation SensAir air curtains are the ideal solution for retailers and other end-users to combat the issue of climate separation

More information

BHH Product Specifications

BHH Product Specifications BHH Product Specifications HORIZONTAL BELT DRIVE DIRECT EXPANSION BLOWER COIL UNITS ALL S 3, 4, and 5 Ton 208/230 3 60 and 460 3 60 supply voltage Units are ETL listed to U.S. and Canadian safety standards

More information

HYDROCIAT LW. Use. Range. Water-cooled chillers. Screw compressors CIAT shell and tubes direct expansion evaporator HPS (High Power System) equipment

HYDROCIAT LW. Use. Range. Water-cooled chillers. Screw compressors CIAT shell and tubes direct expansion evaporator HPS (High Power System) equipment Screw compressors CIAT shell and tubes direct expansion evaporator (High Power System) equipment Cooling capacity: 370 to 1 170 kw Heating capacity: 500 to 1 400 kw Heating Cooling Heat recovery Use The

More information

Goedhart FC38. Standard air coolers Cu/Al. R404A - Coolants. engineering for a better world. GEA Heat Exchangers. Goedhart FC38S.

Goedhart FC38. Standard air coolers Cu/Al. R404A - Coolants. engineering for a better world. GEA Heat Exchangers. Goedhart FC38S. Goedhart FC38S Goedhart FC38D Goedhart FC38L Goedhart FC38 Standard air coolers Cu/Al R404A - Coolants engineering for a better world GEA Heat Exchangers Paragraph Styles Goedhart FC38 The range GEA Goedhart

More information

Chiller. AQL/AQH 40 to 75. Air Cooled Water Chillers Cooling Only and Heat Pump Engineering Data Manual to 77.2 kw to 75.

Chiller. AQL/AQH 40 to 75. Air Cooled Water Chillers Cooling Only and Heat Pump Engineering Data Manual to 77.2 kw to 75. Chiller AQL/ to 75 Air Cooled Water Chillers Only and Heat Pump Engineering Data Manual.0 to 75.8 kw 39.9 to 77.2 kw Outstanding Strength Points R410A Refrigerant. New simpler refrigerant circuit layout.

More information

BRIZA 22 HYBRID HEATING & COOLING

BRIZA 22 HYBRID HEATING & COOLING BRIZA 22 HYBRID HEATING & COOLING Built-in Ceiling: BABC/BT BABC/FT Built-in Wall: BABW/BT BABW/BF BABW/FT BABW/FF INFO SHEET BRIZA 22 HYBRID, COMPACT FANCOIL With EC Greentech EBM-PAPST technology Europe

More information

Viento OPERATION MANUAL

Viento OPERATION MANUAL OPERATION MANUAL FläktGroup Product Range T y p e n s c h l ü s s e l 2 FläktGroup DC-2015-0450-GB 2018-05/R4 Subject to modifications Unit code Accessories L. A 1 U 2. 1 1 1 LZ. 1 0. A 1 Series: for door

More information

Slot diffusers, Round duct diffusers. IMP Klima

Slot diffusers, Round duct diffusers. IMP Klima , Round duct diffusers 04 Round duct diffusers 176 , Round duct diffusers SLOT DIFFUSERS, ROUND DUCT DIFFUSERS SWIRL DIFFUSERS, VARIABLE SWIRL DIFFUSERS CIRCULAR DIFFUSERS, SQUARE DIFFUSERS VENTILATING

More information

Variable speed drives

Variable speed drives 5 192 Variable speed drives SED2 Variable speed drives for speed control of three-phase a.c. motors actuating fans or pumps. Range: 0.75 kw to 90 kw for IP20/21 version, 1.1 kw to 90 kw for IP54 version.

More information

SLH 1202 to Air-to-Water Reverse Cycle Heat Pumps. With Screw Compressors. 261 to 775 kw. 287 to 853 kw

SLH 1202 to Air-to-Water Reverse Cycle Heat Pumps. With Screw Compressors. 261 to 775 kw. 287 to 853 kw Air-to-Water Reverse Cycle Heat Pumps SLH 1202 to 3804 With Screw Compressors 261 to 775 kw 287 to 853 kw Technical Brochure TM SLH-A.2GB Date : November 2004 Supersedes : TM SLH-A.1GB/05.04 Design Features

More information

Air Handling Units. Geniox. Accessories

Air Handling Units. Geniox. Accessories Air Handling Units Geniox Accessories The right accessories are important to optimise your Geniox air handling unit to the task at hand. SystemairCAD provides you with a wide selection of accessories.

More information

Fan Coil Units. Technical Data ECDEN FWL-DT/DF

Fan Coil Units. Technical Data ECDEN FWL-DT/DF Fan Coil Units Technical Data ECDEN10-400 FWL-DT/DF Fan Coil Units Technical Data ECDEN10-400 FWL-DT/DF TABLE OF CONTENTS FWL-DT/DF 1 Features.............................................................

More information

Submittal 30 [762] 36 [914] 40 [1016] 50 [1270] 60 [1524] 70 [1778]

Submittal 30 [762] 36 [914] 40 [1016] 50 [1270] 60 [1524] 70 [1778] FCU-THBP-1.0 08-22-18 THBP Horizontal Low Profile Plenum Return Top View (Drain Pan Omitted) Bottom View Front View Left hand unit shown. All dimensions are inches [millimeters]. Side View Unit Size A

More information

Dual discharge air coolers THOR-D. Standard coolers in a revolutionary design

Dual discharge air coolers THOR-D. Standard coolers in a revolutionary design Dual discharge air coolers THOR-D Standard coolers in a revolutionary design O jççéä=áåçáå~íáçå `çåíéåíë= page Model indication................................ 2 Eurovent......................................

More information

42AM. Air heaters. product selection. the best solution for heating large spaces. ensures buildings warm up ultra-fast

42AM. Air heaters. product selection. the best solution for heating large spaces. ensures buildings warm up ultra-fast product selection the best solution for heating large spaces ensures buildings warm up ultra-fast excellent diffusion via patented JET+ double deflection technology ir heaters 4M Translation of the original

More information

BRIZA EC 12 HYBRID. World s slimmest fan coil HEATING AND COOLING

BRIZA EC 12 HYBRID. World s slimmest fan coil HEATING AND COOLING World s slimmest fan coil wall and ceiling installation 2-or 4-Pipe system heating and / or cooling with or without enclosure easy installation 24VDC EC motor silent, powerful, economical, sustainable

More information

CALEFFI. Mixing valves and actuators series 01169/17 GB. replaces dp 01169/09. Function

CALEFFI. Mixing valves and actuators series 01169/17 GB. replaces dp 01169/09. Function Mixing valves and actuators 610-611 - 612-63 series RIT ISO 01 M 214 LI 01169/17 replaces dp 01169/09 unction The mixing valves allow the centralisation heating system to be regulated by mixing the boiler

More information

HYDROCIAT LW R134a. Water cooled chillers USE RANGE

HYDROCIAT LW R134a. Water cooled chillers USE RANGE Screw compressors CIAT direct expansion shell and tubes evaporator equipment (High Power System) Cooling or heating Heat recovery ENVIRONMENTALLY HFC R134a PROTECTION DE FRIENDLY L'ENVIRONNEMENT Cooling

More information

AHTW Compact. Heat Recovery Air Handling Unit. BIM & REVIT Engineering Solutions. Acoustic Testing Laboratory College of Science & Technology

AHTW Compact. Heat Recovery Air Handling Unit. BIM & REVIT Engineering Solutions. Acoustic Testing Laboratory College of Science & Technology HANDLERS LTD AHTW Compact Heat Recovery Air Handling Unit 1262 Acoustic Testing Laboratory College of Science & Technology BIM & REVIT Engineering Solutions The Company Air Handlers has been trading since

More information

LOW PROFILE UNIT COOLER

LOW PROFILE UNIT COOLER Publication No. RU-RLX-0817C Next-Gen All-Temp LOW PROFILE UNIT COOLER Small to Medium Walk-Ins Cooler and Freezer Applications Air Defrost 4,100 to 45,900 BTUH Electric Defrost 2,700 to 33,000 BTUH Defrost

More information

AHPHX Compact. Heat Recovery Air Handling Unit. BIM & REVIT Engineering Solutions. Acoustic Testing Laboratory College of Science & Technology

AHPHX Compact. Heat Recovery Air Handling Unit. BIM & REVIT Engineering Solutions. Acoustic Testing Laboratory College of Science & Technology HANDLERS LTD AHPHX Compact Heat Recovery Air Handling Unit 1262 Acoustic Testing Laboratory College of Science & Technology BIM & REVIT Engineering Solutions The Company Air Handlers has been trading since

More information

Air Master BCP. Pool air handling units. Optimized energy consumption Electronic control. Description. Principle schemes

Air Master BCP. Pool air handling units. Optimized energy consumption Electronic control. Description. Principle schemes Cooling capacity: Heating capacity: 92,1 to 179,9 kw 69, to 148,7 kw Heating and dehumidification of covered pools Optimized energy consumption Electronic control Description Principle schemes The range

More information

COMFORT AIR CURTAIN. SensAir

COMFORT AIR CURTAIN. SensAir COMFORT AIR CURTAIN SensAir SensAir comfort air curtain A new wave in climate separation SensAir air curtains are the ideal solution for retailers and other end-users to combat the issue of climate separation

More information

Submittal. Front View Side View

Submittal. Front View Side View RBHO Horizontal Low Profile Concealed Free Return Submittal FCU-RBHO-1.0 07-25-18 Top View (Drain Pan Omitted) Bottom View Front View Side View Left hand unit shown. All dimensions are inches [millimeters].

More information

The World Leading Air-conditioning Company

The World Leading Air-conditioning Company The World Leading Air-conditioning Company Table of Contents DESCRIPTIONS Model Number Nomenclature Features & Benefits Physical Dimension Fan Performance Curve (4 Row) - 40LMA024 with AC Motor - 40LMA040

More information

Chassis Access Fans Motors Speed Control Coils The Condensate Tray Insulation Spigots Controls Enclosure Control Valves Filters Rev A

Chassis Access Fans Motors Speed Control Coils The Condensate Tray Insulation Spigots Controls Enclosure Control Valves Filters Rev A Chassis panelwork is all In House manufactured from nominally 1.2mm Galvanised steel. Where at all possible, flanges are formed inward facing to prevent exposure to bare metal edges. Sufficient forms and

More information

AIR COOLED CHILLERS WATER COOLED CHILLERS

AIR COOLED CHILLERS WATER COOLED CHILLERS AIR COOLED CHILLERS WATER COOLED CHILLERS STANDARD UNIT SPECIFICATIONS OF COMMERCIAL AIR COOLED CHILLERS General Description & Assembly Air Cooled Chillers are commercial packaged systems complete with

More information

TECHNICAL MANUAL SOFFIO Ducted units

TECHNICAL MANUAL SOFFIO Ducted units TECHNICAL MANUAL SOFFIO Ducted units Page 1 INDEX 1-INTRODUCTION... 4 2-OPERATING LIMITS... 4 3- KEY TO READING CODES... 5 4-TECHNICAL SPECS... 6 5-TECHNICAL DATA (AC motors)... 7 5.1-Unit 2 pipes with

More information

Centrifugal performance characteristics with axial flow pattern: RADAX VAR

Centrifugal performance characteristics with axial flow pattern: RADAX VAR High pressure in-line mixed-flow fans RADAX VAR Centrifugal performance characteristics with axial flow pattern: RADAX VAR COMPACT PRESSURE-RESISTANT UNIVERSAL In their compact casing, the RADAX VAR impellers

More information

Cubic unit cooler. SKB semi-industrial range

Cubic unit cooler. SKB semi-industrial range Cubic unit cooler SKB semi-industrial range Heatcraft reserves itself the right to make changes at any time without preliminary notice - Photos non-contractual The SKB range is designed for commercial

More information

Ocelot vertical fan coil unit

Ocelot vertical fan coil unit Ocelot vertical fan coil unit 250mm Deep vertical Waterside control Cased unit DUNHAM BUSH OCELOT VERTICAL CASED FAN COIL UNIT The Dunham Bush Ocelot fan coil unit is a fully cased vertical unit suitable

More information

HTC. Air cooled Condensers. Capacities kw. Ripple Fin tubing Floating coil block suspension

HTC. Air cooled Condensers. Capacities kw. Ripple Fin tubing Floating coil block suspension Air cooled Condensers New condenser generation with better performance Capacities 9-1060 kw Ripple Fin tubing Floating coil block suspension Eurovent certified Capacities based on ENV 327 voor R404A *DX

More information

ERP 2015 Regulation (EU) Compliant with. No. 327/2011. Cert. n Heating. Meltemi Door Curtains

ERP 2015 Regulation (EU) Compliant with. No. 327/2011. Cert. n Heating. Meltemi Door Curtains Compliant with ERP 015 Regulation (EU) No. 7/011 Cert. n 0545 Heating Door Curtains The range of SBIN door curtains offers imum flexibility in the protection of doors and open access compartments. By connecting

More information

Cubic unit cooler. SKB semi-industrial range

Cubic unit cooler. SKB semi-industrial range HFC W Glycol READY Cubic unit cooler SKB semi-industrial range Heatcraft reserves itself the right to make changes at any time without preliminary notice - Photos non-contractual The SKB range is designed

More information

3 Specification Magneta Smedegaard

3 Specification Magneta Smedegaard 3 Specification Magneta Smedegaard 3.1 Variable Speed Circulator Pumps Main applications Heating, ventilation, air-conditioning, refrigerating and circulation systems - One-pipe and two-pipe systems -

More information

TWA S/K/P. Incorporating. R410A Air cooled water chillers with axial fans and scroll compressors from 189 kw to 1007 kw

TWA S/K/P. Incorporating. R410A Air cooled water chillers with axial fans and scroll compressors from 189 kw to 1007 kw TWA 212-1102 S/K/P Incorporating R410A Air cooled water chillers with axial fans and scroll compressors from 189 kw to 1007 kw The complete solution to all your cooling needs TWA 212-1102 S/K/P Index

More information

Resolair 64 and 68. Comfort air conditioning unit with highly efficient regenerative heat storage packages. AIR VOLUME FLOW: 3,900 23,100 m³/h

Resolair 64 and 68. Comfort air conditioning unit with highly efficient regenerative heat storage packages. AIR VOLUME FLOW: 3,900 23,100 m³/h Comfort air conditioning unit with highly efficient regenerative heat storage packages 68 10 01 - simplified illustration Automatically selects the most economical operating mode! 64 and 68 AIR OLUME FLOW:

More information

RERV & RERVX RERVLP. Rotary Energy Recovery Ventilators. Low Profile Indoor Rotary Energy Recovery Ventilators

RERV & RERVX RERVLP. Rotary Energy Recovery Ventilators. Low Profile Indoor Rotary Energy Recovery Ventilators Version: Dec. 01, 2004 RERV & RERVX Rotary Energy Recovery Ventilators Indoor and Outdoor Installations 250 20,000 CFM Capacities RERVLP Low Profile Indoor Rotary Energy Recovery Ventilators Ideal for

More information

CAV controllers. Type VFL. Volume flow limiter for insertion into ducting K

CAV controllers. Type VFL. Volume flow limiter for insertion into ducting K .1 X X testregistrierung CAV controllers Type Aerodynamic damper blade Sticker showing volume flow rates Set the volume flow rate Insert Volume flow limiter for insertion into ducting Circular, mechanical

More information

TECHNICAL MANUAL ESTRO BLDC ESTRO BLDC FAN COILS - BRUSHLESS TECHNOLOGY. 1.5 kw kw

TECHNICAL MANUAL ESTRO BLDC ESTRO BLDC FAN COILS - BRUSHLESS TECHNOLOGY. 1.5 kw kw GB TECHNICAL MANUAL ESTRO BLDC ESTRO BLDC FAN COILS - BRUSHLESS TECHNOLOGY 1.5 kw - 9.0 kw TABLE OF CONTENTS 1 Generalities... 3 2 Models and constructive components...4-5 3 Accessories available... 6

More information

HEAT-RECOVERY UNITS WITH ENTHALPY/ROTARY HEAT EXCHANGER TECHNICAL MANUAL

HEAT-RECOVERY UNITS WITH ENTHALPY/ROTARY HEAT EXCHANGER TECHNICAL MANUAL UT REC - R HEAT-RECOVERY UNITS WITH ENTHALPY/ROTARY HEAT EXCHANGER TECHNICAL MANUAL 1 CONTENTS GENERAL FEATURES... 3 Scope of the unit... 3 Available configurations... 3 Description of the components...

More information

LindabPodium. Supply air beam. lindab we simplify construction

LindabPodium. Supply air beam. lindab we simplify construction lindab we simplify construction Lindab 03.2016 Lindab Ventilation. All forms of reproduction without written permission are forbidden. is the registered trademark of Lindab AB. Lindab's products, systems,

More information

FRESH BREEZE FAN-FILTER UNIT TECHNICAL DATA

FRESH BREEZE FAN-FILTER UNIT TECHNICAL DATA FRESH BREEZE FAN-FILTER UNIT TECHNICAL DATA Fresh Breeze Fan-Filter Unit Range of Application... 3 Sizes... 3 Characteristics... 3 Fresh Breeze product line... 3 Areas of application... 3 Technical Data

More information

HWT 1402/9603. free cooling

HWT 1402/9603. free cooling irwater chillers for outdoor installation with free cooling Screw compressors, shell and tube heat exchangers and axial fans NSM Cooling capacity 306-2001kW HWT 14029603 free cooling HIGH EFFICIENCY LSO

More information

R EGI S TERED. Function

R EGI S TERED. Function Z series zone valves R EGI S TERE S EN ISO 900:000 ert. n FM 64 UNI EN ISO 900:000 ert. n 0003 LEFFI 0/09 N Replaces 0/04 N Function Z-one valves are used to automatically shut-off the flow or redirect

More information

Alfa Laval Optigo CS. Commercial air coolers - Slim line

Alfa Laval Optigo CS. Commercial air coolers - Slim line Alfa Laval Optigo CS Commercial air coolers - Slim line Optigo CS Alfa Laval Optigo Simply fresh, today and tomorrow Optigo is the Alfa Laval platform for commercial air cooler ranges. Common distinctive

More information

YFCN Fan Coil Unit centrifugal fan 2 & 4 pipe system A complete range from 1.0 kw to 7.6 kw

YFCN Fan Coil Unit centrifugal fan 2 & 4 pipe system A complete range from 1.0 kw to 7.6 kw Fan Coil Unit centrifugal fan 2 & 4 pipe system complete range from 1.0 kw to 7.6 kw Water Systems Wired controls R Remote three speeds controller TR R + Electronic thermostat and Summer/Winter switch

More information

CAV controllers. Type EN. For the precise control of normal and high constant volume flows. 01/2017 DE/en PD EN 1

CAV controllers. Type EN. For the precise control of normal and high constant volume flows. 01/2017 DE/en PD EN 1 X X testregistrierung CAV controllers Type For the precise control of normal and high constant volume flows Rectangular self-powered volume flow controllers for the control of supply air or extract air

More information

Airsock unit coolers THOR-A. Standard coolers in a revolutionary design

Airsock unit coolers THOR-A. Standard coolers in a revolutionary design Airsock unit coolers THOR-A Standard coolers in a revolutionary design O jççéä=áåçáå~íáçå `çåíéåíë= page Model indication................................ 2 Eurovent......................................

More information

AQVSL/AQVSH STAR 85 to 140

AQVSL/AQVSH STAR 85 to 140 Chiller QVSL/ STR 85 to 140 ir Cooled Water Chillers Cooling Only and Heat Pump Engineering Data Manual 82 to 157 kw 83 to 168 kw Outstanding Strength Points Units with R410 refrigerant (it will be the

More information

CAV controllers. Type RN. For the precise control of constant volume flow rates PD RN 1

CAV controllers. Type RN. For the precise control of constant volume flow rates PD RN 1 X X testregistrierung CAV controllers Type For the precise control of constant volume flow rates Circular self-powered volume flow controllers for the control of supply air or extract air in constant air

More information

CALEFFI. Motorized ball valves with 3-wire control series ACCREDITED 01131/13 NA. Replaces 01131/07 NA

CALEFFI. Motorized ball valves with 3-wire control series ACCREDITED 01131/13 NA. Replaces 01131/07 NA Motorized ball valves with -wire control 644-644 series SO 900 M 64 SO 900 No. 000 0/ N Replaces 0/07 N unction Zone valves are used to automatically shut-off the flow, redirect or modulate hot and chilled

More information