Steam Turbine Generator Core Isolation Issues at the Redhawk Combined Cycle Plant
|
|
- Alison Mitchell
- 5 years ago
- Views:
Transcription
1 Steam Turbine Generator Core Isolation Issues at the Redhawk Combined Cycle Plant Marques Montes Arizona Public Service Company Phoenix, AZ Includes material provided by John Demcko
2 Redhawk Power Plant
3 Redhawk Power Plant Located west of Phoenix near Palo Verde Two 530 MW Units Each unit consists of 2 combustion turbines and 1 steam turbine Commercial operation began in 2003
4 Part 1 End Winding Issues
5 Early Problems From commissioning onward, the STGs at Redhawk were unusually loud during operation. June STG manufacturer warns APS of possible high end turn vibration Sister unit at another site has a stator winding failure Manufacturer recommends immediate shutdown of both STGs at Redhawk Loss of 400MW for Summer Peak
6 The Plan Not Running STGs Summer 2003 Unacceptable Alternative Sought A Means to Monitor Real-time Stator Required We Obtained The Mfgr s Concurrence to Run with Monitoring Required Acceptable/Unacceptable Vibration Levels Defined
7 The Interim Solution Turn-key End Turn Vibration Monitoring Via Fiber Optics Based Accelerometers Vibration Reads at Frequent Intervals Communication with Mfgr When Alert Levels Reached
8 FOA Installed On NDE
9 2003 Results Temporary Instrumentation Config. STG1 Vibration Levels Acceptable STG2 Levels High & Increasing End Turn Structure Repairs Made In October Permanent FOA Instrumentation Package Installed For 2004 Season
10 Vibration, mils pk-pk 2003 Results - STG Redhawk STG2 End Turn Vibration FOA1 Radial 3:30 FOA3 Radial 7:30 FOA5 Radial 11: /28/03 0:00 8/7/03 0:00 8/17/03 0:00 8/27/03 0:00 9/6/03 0:00 9/16/03 0:00 9/26/03 0:00 10/6/03 0:00 Date & Time
11 2004 Results Units Not Operated Extensively Until June STG1 Vibration Higher Than Before End Turn Modifications STG2 Started Low But Climbed Throughout The Year To Well Above 2003 Alarm Level Additional End Turn/Phase Lug Work Scheduled Spring 2005
12 2004 Results - STG2 (June)
13 2004 Results - STG2 (July - December)
14 2005 & On End Turn Vibration Instrumentation Package Is An Effective & Necessary Tool Excessive Vibration Detected Early & Treated As A Warranty Issue STGs Ran Through 2003 & 2004 Peak End Turn Monitoring was Utilized To Assess Spring 2005 Repairs
15 Driven End Problem Arises We believed that with monitoring, vibration issues were under control. Then came April 3 rd, 2009 STG2 Operating Point was 137MW, +9.6MVAR & Vgen = 18.5kV when.
16 A Phase B to Ground Fault Develops
17 Followed by an evolving 3 phase fault
18 Fault Detail
19 Damage Is Substantial! 3Ph Fault Current from Yard is 75kA 0-pk Gen Contribution Unknown due to CT loc. Burning Last Seconds While Field Current Decays From DFR Record, The Worst Case Scenario Is Feared
20 Driven End Fault Damage - 1
21 Driven End Fault Damage - 2
22 Damage Assessment 3 Burned Series Connections On DE Rotor & Stator Badly Contaminated with Carbon & Melted Copper Driven End Turn Structure Repairable Work is Extensive & Labor Intensive
23 Repair Work Scope Strip Stator Bars Back to Expose Good Copper Perform Series Connection Braze Repairs Validate Repairs by Phase Resistance Test & Thermal Camera Insulate (Caps) Series Connections Remove & Reinstall All Series Blocking & Tie With Glass Roving & Epoxy Resin. Apply Red Eye Epoxy & Flooding Resin to the End Windings Install Nose Ring On ID of Series Connection/Caps Bump Test Verify Frequencies Final Electrical Testing (DC leakage, Hipot & Winding Resistance
24 Driven End Repair - 1
25 Driven End Repair - 2
26 STG2 Repaired & Returned To Service FOAs on both DE & NDE (12 total) Will Report To Plant Computer via Next Generation Monitor 4 Velocimeters Installed on Core In Quadrature (120Hz Audible Noise Very High) VibroSystM PCU-5000 Installation Commissioned 4 th Q 2010
27 Part II Cooler Leak and Core Isolation Inspection
28 March 2013 STG2 Cooler Leak Ongoing high vibration caused an air vane to break loose and fall onto a water to air cooler Many gallons of the water-glycol mix ( antifreeze ) were circulated through the machine As part of the repair process, the coolers were removed
29 Typical air vane.
30 Damaged cooler in the shop.
31 Close up shot of cooler damage
32 The Discovery During the post-incident inspection of the machine, it became apparent that the machine has virtually no core isolation. The support structure consists of the stator key bars welded to an annular support ring, aka the ring with ears Each ring with ears is solidly welded to the generator wrapper at 6 points.
33 Core key bar welded to ring with ears
34 Ring with ears
35 These circular connections are where the rings with ears are welded to the wrapper.
36
37 Vibration in the core is transferred to the wrapper through the inadequate core isolation. The wrapper vibrates at 120 Hz like a speaker cone. Near field acoustic data from Redhawk ST2
38 Proposed Solutions After the cooler leak was repaired, the unit was placed back into service. We explored our options on mitigating the excessive vibration caused by the lack of core isolation: Harmonic dampener Wrapper reinforcement Generator replacement
39 What did we decide?
40 Stator ready to be scrapped.
41 New generator
42 New Generator Acoustic Results 23 db reduction in sound pressure level in the 125 Hz (120 Hz) range!
43 Conclusions We believe that the susceptibility of stator end winding failure on these units is due to a flawed design that inadequately isolates the core from the rest of the machine. This excessive vibration also contributed to the failure of the air vane that led to a massive cooler leak. This design flaw would have been prohibitively expensive to repair. Generator replacement was chosen as the best option to protect the reliability of the system. Monitoring the core and end windings of a machine for vibration can give you insight into a potential problem.
44 Questions?
CIGRE SC A1 & EPFL Joint Colloquium on Large Electrical Machines Lausanne, Switzerland 7 September 2005
CIGRE SC A1 & EPFL Joint Colloquium on Large Electrical Machines Lausanne, Switzerland 7 September 2005 CASE STUDIES OF FIBER OPTIC ACCELEROMETER USED FOR END-WINDING VIBRATION MONITORING ON TURBO-GENERATORS
More informationLarge Air Cooled Generator Failure
Large Air Cooled Generator Failure Henry Tarnecky AVP - Sr. Engineering Specialist, FM Global 2017 IRIS Rotating Machinery Conference FM Global Basics Commercial/Industrial Property Insurer Mutual Co.,
More informationArtesis MCM Case Studies. March 2011
Artesis MCM Case Studies March 2011 Case 1 Automotive Company: Automobile Manufacturer A Equipment: Pump Stator Isolation Breakdown Decreasing current unbalance level Case 1 Automotive Company: Automobile
More information100 MW Wind Generation Project
A subsidiary of Pinnacle West Capital Corporation 100 MW Wind Generation Project CUSTOMER FINAL Feasibility Study Results By Transmission Planning, APS December 21, 2007 Executive Summary This Feasibility
More informationMECHANICAL INTEGRITY CHECKING OF GENERATOR STATOR OVERHANG BY NATURAL FREQUENCY MEASUREMENT
MECHANICAL INTEGRITY CHECKING OF GENERATOR STATOR OVERHANG BY NATURAL FREQUENCY MEASUREMENT R.K.Bhatnagar, A.K.Mukherjee, National Thermal Power Corp., India akmukherjee04@ntpceoc.co.in INTRODUCTION Reliable
More informationAppendix G Examples and Recommended Methods
Reporting Outages to the Generating Availability Data System (GADS) Introduction The examples in this appendix illustrate the reporting of outages and deratings to GADS. They are based on a fictional 600
More informationTransmission Planning & Engineering P.O. Box MS 3259 Phoenix, Arizona
Transmission Planning & Engineering P.O. Box 53933 MS 3259 Phoenix, Arizona 85072-3933 March 9, 2016 Mr. Philip Augustin Chair, WECC Technical Studies Subcommittee Mr. Enoch Davies WECC Technical Staff
More informationi-pcgrid Workshop 2017
i-pcgrid Workshop 2017 Potential Impacts of Flexible Ramping Need on Transmission Planning March 2017 Chifong Thomas Director, Transmission Planning and Strategy Smart Wires Inc. USA Flexible Capacity
More informationNEIL Turbine Generator Risk Assessment. Todd Raymond Loss Risk Analysis Manager Nuclear Service Organization April 16-17, 2013
NEIL Turbine Generator Risk Assessment Todd Raymond Loss Risk Analysis Manager Nuclear Service Organization April 16-17, 2013 Program Origin Large Losses due to Turbine Generator Failures in recent years
More informationDevelopment and Operational Advantages of a Solid State Circuit Breaker with Current Limiting
Development and Operational Advantages of a Solid State Circuit Breaker with Current Limiting Breaker Technology Operational Advantages Development Schedule Dave Richardson, Ph.D.,P.E. Powell Power Electronic
More informationExcitation system is of Static Silicon Excitation System, including excitation transformer, thyristors, and AVR.
Turbo - Generator Type: QF Series 1. General The generator is a two pole, cylindrical rotor type synchronous machine, directly coupled with steam turbine. It has a closed-circuit cooling system to cool
More informationEssential Reliability Services From PV Plants
Essential Reliability Services From PV Plants Mahesh Morjaria, Ph. D. VP, PV Systems Enabling a world powered by reliable, affordable solar electricity. Utility-Scale PV Plants Support Grid Stability &
More informationSulzer Dowding & Mills
Sulzer Turbo Services Company overview Sulzer today Sulzer Pumps Market leader in pump technology and solutions Sulzer Metco Market leader in surface technology Sulzer Chemtech Market leader for separation,
More informationAGN 076 Alternator Bearings
Application Guidance Notes: Technical Information from Cummins Generator Technologies AGN 076 Alternator Bearings BEARING TYPES In the design of STAMFORD and AvK alternators, the expected types of rotor
More informationExtended requirements on turbogenerators
, Siemens AG, Mülheim/Ruhr, Germany Extended requirements on turbogenerators due to changed operational regimes siemens.com Table of Content Evaluation of current operation regimes Extended requirements
More informationNew 115 kv Disconnect Switches at Bloomsburg MTS
115 kv Line tap from C9 to Bloomsburg MTS & New Bus Tie Switch CAA ID Number: 2007-EX353 Final Draft ASSESSMENT SUMMARY 1. GENERAL DESCRIPTION Norfolk TS and Bloomsburg MTS are supplied by a single 115
More informationSteam Turbine Seal Rub
Steam Turbine Seal Rub Date : November 19, 2014 Steam Turbine Seal Rub Vibration data helps to identify a steam turbine seal rub. Sotirios Christofi Deputy Manager, Head of Mechanical Maintenance, Thessaloniki
More informationMcNary Northshore Fishway Hydro Project. History & Lessons Learned
McNary Northshore Fishway Hydro Project History & Lessons Learned May 6, 2017 21 th Annual TECHNICAL SEMINAR Machines, Maintenance, and Management: Keeping Hydro Facilities Up and Running History & Lessons
More informationSkylight solar shade screen study at John Brooks, Inc. An Interior Design Showroom in Scottsdale Arizona.
Skylight solar shade screen study at John Brooks, Inc. An Interior Design Showroom in Scottsdale Arizona. Curtis Fawley, Arizona Sky Shades 7/25/2014 www.arizonaskyshades.com In cooperation with Efficiency
More informationPJM Sub Regional RTEP Committee Mid-Atlantic January 22, Esam Khadr, Sr. Director Electric Delivery Planning, PSE&G
PJM Sub Regional RTEP Committee Mid-Atlantic January 22, 2016 Esam Khadr, Sr. Director Electric Delivery Planning, PSE&G PSE&G System Characteristics New Jersey utility characterized by densely populated
More informationPrimary Heat Transport (PHT) Motor Rotor Retaining Ring Failure
1 Primary Heat Transport (PHT) Motor Rotor Retaining Ring Failure Ali Malik Components & Equipment Eng. Ontario Power Generation - Darlington Nuclear 2 Ontario Power Generation Darlington Darlington Nuclear
More informationCERTIFICATES OF COMPETENCY IN THE MERCHANT NAVY - MARINE ENGINEER OFFICER
CERTIFICATES OF COMPETENCY IN THE MERCHANT NAVY - MARINE ENGINEER OFFICER EXAMINATIONS ADMINISTERED BY THE SCOTTISH QUALIFICATIONS AUTHORITY ON BEHALF OF MARITIME AND COASTGUARD AGENCY CHIEF ENGINEER (UNLIMITED)
More informationSIGENTICS HV Series S-modyn
SIGENTICS HV Series S-modyn High-voltage 3-phase salient pole generators siemens.com/sigentics Answers for industry. SIGENTICS: 4-pole generators for industrial turbines The energy business is characterized
More information2 Pole 1222MVA Turbo-Generator & 4 Pole 1690MVA Turbo-Generator
2 Pole 1222MVA Turbo-Generator & 4 Pole 1690MVA Turbo-Generator 27. August, 2008 Generator Design Team Chong Whie Cho 2008 CIGRE SESSION 42, Paris CONTENTS Introduction 2-Pole 1222MVA Generator - Specifications
More informationPF Coil 2-6 Supply. Main technical aspects. P. Valente
PF Coil 2-6 Supply Main technical aspects P. Valente PF Coils EI Information Meeting Cadarache, 19 February 2013 This presentation is intended for reference purposes only and is not a legally binding document
More informationThe Development of Competitive Renewable Energy Zones in Texas
The Development of Competitive Renewable Energy Zones in Texas Warren Lasher Manager, System Assessment 4/23/2008 North American Electric Grids The ERCOT Region is one of 3 NERC grid interconnections.
More information1. HVOF Coating. Tungsten Carbide Typical Chemical Composition Typical HVOF Parameters
1. HVOF Coating Tungsten Carbide Typical Chemical Composition Typical HVOF Parameters Innovations of SJVN Hard coating plant installed at NJHPS which is 1 st ever hard coating plant provided at a Hydel
More informationLEAP - Life Expectancy Analysis Program For Electrical Rotating Machines. Marcio Gennari ABB Brazil Automation Products Machines Service Osasco
LEAP - Life Expectancy Analysis Program For Electrical Rotating Machines Marcio Gennari ABB Brazil Automation Products Machines Service Osasco LEAP - Introduction ABB India (excellence center in insulation
More informationMILLIGAN SOLAR PROJECT
February 16, 2009 Page 1 of 18 A subsidiary of Pinnacle West Capital Corporation MILLIGAN SOLAR PROJECT FINAL Feasibility Study Report APS Contract 52115 Prepared by: Arizona Public Service Company Transmission
More informationPERFORMANCE LOSS INVESTIGATION USING THERMAL IMAGING
283 PERFORMANCE LOSS INVESTIGATION USING THERMAL IMAGING PRESENTER AND AUTHOR: SCOTT MCPHERSON LEAD FIELD ENGINEER SULZER PUMPS (US) INC Tel: 281 417 7109 E-MAIL: Scott.Mcpherson@Sulzer.com ABSTRACT An
More informationCUSTOMER/ TWIN ARROWS PROJECT
A subsidiary of Pinnacle West Capital Corporation CUSTOMER/ TWIN ARROWS PROJECT V1 Facility Study Report APS Contract 52149 Prepared by: Arizona Public Service Company Transmission & Distribution Asset
More informationFinal Draft Report. Assessment Summary. Hydro One Networks Inc. Longlac TS: Refurbish 115/44 kv, 25/33/ General Description
Final Draft Report Assessment Summary Hydro One Networks Inc. : Refurbish 115/44 kv, 25/33/42 MVA DESN Station CAA ID Number: 2007-EX360 1.0 General Description Hydro One is proposing to replace the existing
More informationAn Investigation into a new method to repair motor cores and improve Efficiency
An Investigation into a new method to repair motor cores and improve Efficiency Henk de Swart Marthinusen & Coutts Dennis Willemse, Gerhard Bergh, Thava Perumal Sasol Introduction A South African based
More informationGenerator Interconnection Facilities Study For SCE&G Two Combustion Turbine Generators at Hagood
Generator Interconnection Facilities Study For SCE&G Two Combustion Turbine Generators at Hagood Prepared for: SCE&G Fossil/Hydro June 30, 2008 Prepared by: SCE&G Transmission Planning Table of Contents
More informationREDUCING VULNERABILITY OF AN ELECTRICITY INTENSIVE PROCESS THROUGH AN ASYNCHRONOUS INTERCONNECTION
REDUCING VULNERABILITY OF AN ELECTRICITY INTENSIVE PROCESS THROUGH AN ASYNCHRONOUS INTERCONNECTION Summary Abhay Kumar Mata Prasad R C Maheshwari Asea Brown Boveri Ltd. 4th Floor, 71 Nehru Place, New Delhi
More informationNoxon Rapids Reactor Project. Scott Wilson June 9, 2016 Tracy Rolstad
Noxon Rapids Reactor Project Scott Wilson June 9, 2016 Tracy Rolstad Voltage Performance at Noxon (ALIS) 0.000 MW 0.000 Mvar 0.000 MW 0.000 Mvar 0.000 MW 0.000 Mvar 0.000 MW 0.000 Mvar 0.000 MW 0.000 Mvar
More informationTHE NECESSITY OF THE 500 KV SYSTEM IN NWE S TRANSMISSION SYSTEM TO MAINTAIN RELIABLE SERVICE TO MONTANA CUSTOMERS
THE NECESSITY OF THE 500 KV SYSTEM IN NWE S TRANSMISSION SYSTEM TO MAINTAIN RELIABLE SERVICE TO MONTANA CUSTOMERS 2/27/2018 ELECTRIC TRANSMISSION PLANNING Table of Contents Table of Contents... 2 Executive
More informationAppendix D Black Hills Project Summary
Page 1 of 28 Appendix D Black Hills Project Summary Table of Contents Black Hills Project Summary... D-1 Boone-Nyberg 115 kv Project... D-3 Rattlesnake Butte 115 kv Substation Terminal... D-6 Fountain
More informationFletcher Moorland Ltd. Electric Motor Repair Specification
Fletcher Moorland Ltd Electric Motor Repair Specification Fletcher Moorland promotes best practice and reliability throughout its business. As an SKF certified rebuilder for electric motors we ensure each
More informationPJM Generator Interconnection Request Queue #R60 Robison Park-Convoy 345kV Impact Study September 2008
PJM enerator Interconnection Request Queue #R60 Robison Park-Convoy 345kV Impact Study 504744 September 2008 PJM Interconnection 2008. All rights reserved R60 Robison Park-Convoy 345kV Impact Study eneral
More informationTOLTEC POWER PARTNERSHIP TOLTEC POWER PROJECT INTERCONNECTION STUDY SYSTEM IMPACT STUDY
TOLTEC POWER PARTNERSHIP TOLTEC POWER PROJECT INTERCONNECTION STUDY SYSTEM IMPACT STUDY January 7, 2002 Prepared by Jorge Chacon (Consultant) Tucson Electric Power Company Ed Beck ii EXECUTIVE SUMMARY
More informationREDUCING THE OCCURRENCES AND IMPACT OF FREIGHT TRAIN DERAILMENTS
REDUCING THE OCCURRENCES AND IMPACT OF FREIGHT TRAIN DERAILMENTS D-Rail Final Workshop 12 th November - Stockholm Monitoring and supervision concepts and techniques for derailments investigation Antonella
More informationCost Benefit Analysis of Faster Transmission System Protection Systems
Cost Benefit Analysis of Faster Transmission System Protection Systems Presented at the 71st Annual Conference for Protective Engineers Brian Ehsani, Black & Veatch Jason Hulme, Black & Veatch Abstract
More informationTURBOGENERATOR DYNAMIC ANALYSIS TO IDENTIFY CRITICAL SPEED AND VIBRATION SEVERITY
U.P.B. Sci. Bull., Series D, Vol. 77, Iss. 3, 2015 ISSN 1454-2358 TURBOGENERATOR DYNAMIC ANALYSIS TO IDENTIFY CRITICAL SPEED AND VIBRATION SEVERITY Claudiu BISU 1, Florian ISTRATE 2, Marin ANICA 3 Vibration
More informationBattery Energy Storage System addressing the Power Quality Issue in Grid Connected Wind Energy Conversion System 9/15/2017 1
Battery Energy Storage System addressing the Power Quality Issue in Grid Connected Wind Energy Conversion System 9/15/2017 1 CONTENTS Introduction Types of WECS PQ problems in grid connected WECS Battery
More informationIntroduction to Condition-Based Maintenance Best Practices
Introduction to Condition-Based Maintenance Best Practices Maintenance Strategy Breakdown Maintenance Preventive Maintenance (Time Base) Predictive Maintenance Proactive Maintenance Rationalizing Spending
More informationMYERS 3MW VERTICAL DISCHARGE WASTEWATER PUMPS. Sewage, high-capacity sump, effluent
The Myers heavy-duty series pumps are designed for residential raw sewage and light commercial applications. The non-clogging two-vane impeller delivers high-efficiency pumping and easily handles trashy
More informationHigh-Impedance Differential Applications With Mismatched CTs
High-Impedance Differential Applications With Mismatched CTs Russ Franklin, Alliant Energy Hossein Nabi-Bidhendi, ABB Inc. Michael J. Thompson and Héctor J. Altuve, Schweitzer Engineering Laboratories,
More informationA Cost Benefit Analysis of Faster Transmission System Protection Schemes and Ground Grid Design
A Cost Benefit Analysis of Faster Transmission System Protection Schemes and Ground Grid Design Presented at the 2018 Transmission and Substation Design and Operation Symposium Revision presented at the
More informationPLACE FOR TITLE AUTHORS. Potassium Carbonate Pump Failure High Axial Movement due to Uncontrolled (unbalanced) forces.
PLACE FOR TITLE Potassium Carbonate Pump Failure High Axial Movement due to Uncontrolled (unbalanced) forces. AUTHORS Ibrahim AbdAl-Wahab Ammonia Sector Head Misr Fertilizer Production Company Hatem AbdelRahman
More informationDocument #: DOC_PRD-1002 Origination Date: 8/22/07. Rev: Revision Date: Signature: Title: MHV & SHV High Voltage Test Procedure
Title: MHV & SHV High Voltage Test Procedure Scope: This document describes the test procedure and results for the voltage rating verification of the coaxial MHV and SHV style high voltage connectors and
More informationPJM Generator Interconnection R81 Emilie (Fords Mill) MW Impact Study Re-Study
PJM Generator Interconnection R81 Emilie (Fords Mill) 100.9 MW Impact Study Re-Study August 2008 DMS # 498781 General Queue R81 Emilie (Fords Mills) is a Fairless Energy, LLC request to obtain an additional
More informationEMEA Aftermarket Press Event. EMEA Aftermarket Press Event June 17, June 17, 2009
EMEA Aftermarket Press Event EMEA Aftermarket Press Event June 17, 2009 June 17, 2009 Insist Turbo on Fundamentals Genuine Agenda Comparison between a Genuine Garrett VNT Turbo and a Remanufactured VNT
More informationWorld s Largest Air-cooled Turbogenerator in operation
Titre de la diapositive! Paragraphe World s Largest Air-cooled Turbogenerator in operation Yves Sabater Table of content! Turbogenerators cooling technologies State of the art! 400 MVA air-cooled generator
More informationGuideline for Parallel Grid Exit Point Connection 28/10/2010
Guideline for Parallel Grid Exit Point Connection 28/10/2010 Guideline for Parallel Grid Exit Point Connection Page 2 of 11 TABLE OF CONTENTS 1 PURPOSE... 3 1.1 Pupose of the document... 3 2 BACKGROUND
More informationHawai'i Island Planning and Operations MEASURES TO IMPROVE RELIABILITY WITH HIGH DER
1 Hawai'i Island Planning and Operations MEASURES TO IMPROVE RELIABILITY WITH HIGH DER Lisa Dangelmaier Hawaii Electric Light lisa.dangelmaier@hawaiielectriclight.com Hawai'i Electric Light System Overview
More informationRULE 21 GENERATING FACILITY INTERCONNECTION APPLICATION SMUD s Distribution System - (SMUD FORM 2655)
- (SMUD FORM 2655) A. Applicability: This Generating Facility Interconnection Application (Application) shall be used to request the interconnection of a Generating Facility to Sacramento Municipal Utility
More informationWestern Power s list of exemptions from compliance from Technical Rules granted after 1 July 2007.
Western Power s list of exemptions from compliance from Technical Rules granted after 1 July 2007. No Date of Exemption To whom Exemption was granted Clause to which Exemption has been granted Concise
More informationAVIATION INVESTIGATION REPORT A02P0010 CABIN ENTERTAINMENT SYSTEM FIRE
AVIATION INVESTIGATION REPORT A02P0010 CABIN ENTERTAINMENT SYSTEM FIRE AIR CANADA AIRBUS A-330-300 C-GFAF VANCOUVER INTERNATIONAL AIRPORT, BRITISH COLUMBIA 17 JANUARY 2002 The Transportation Safety Board
More informationGenerator. Jason S DiSanto. 6B Users Conference San Antonio, TX June 19-22, 2017
Generator Jason S DiSanto 6B Users Conference San Antonio, TX June 19-22, 2017 GE Power 2017, General Electric Company. GE Proprietary Information - The information contained in this document is General
More informationA system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment.
General Unit substations shall be 500 kva minimum, 1500 kva maximum unless approved otherwise by the University. For the required configuration of University substations see Standard Electrical Detail
More informationCustomer presentation, PG Service, BU Motors and Generators ABB LEAP Stator Winding-Condition & Lifetime assessment
Customer presentation, PG Service, BU Motors and Generators ABB LEAP Stator Winding-Condition & Lifetime assessment ABB LEAP Overview ABB LEAP - Benefits for customer Motivation to perform LEAP Failures
More informationGuide. Services Document No: GD-1401 v1.0. Issue Date: Title: WIND ISLANDING. Previous Date: N/A. Author: Heather Andrew.
Guide Department: Interconnection Services Document No: GD-1401 v1.0 Title: WIND ISLANDING Issue Date: 11-24-2014 Previous Date: N/A Contents 1 PURPOSE... 2 2 SCOPE AND APPLICABILITY... 2 3 ROLES AND RESPONSIBILITIES...
More informationMJH. Model. Up to kva. Power. Up to V. Voltages. Frame 400 ± Pole 4, 6, 8. (over contact MM) Cooling IC 01
MJH Model Power Voltages MJH Up to 12.500 kva Up to 15.000 V Frame 400 ± 1.250 Pole 4, 6, 8 Cooling IC 01 (over contact MM) IP Enclosure Main Applications Sector IP 23. Available up to IP 44 with filters.
More informationAdvanced Maintenance Technologies
Advanced Maintenance Technologies Vibration Analysis Consultants Ray W. Wonderly Certified Vibration Specialist Services: Vibration Analysis Consulting Laser Alignment Services Predictive/Planned Maintenance
More informationAppendix B. Chapter 11. by Resonance
Appendix B. Chapter 11. Fan Housing Vibration Caused by Resonance Application of Modal & Vibration Analysis Ken Singleton KSC Consulting LLC Background Four FD fans were installed at the site to meet environmental
More informationCarbon Brush Performance on Slip Rings
Carbon Brush Performance on Slip Rings Richard D. Hall Morgan AM&T Roland P. Roberge Morgan AM&T Gary Lozowski Morgan AM&T Mining Electrical Maintenance and Safety Association September 9, 2010 Clearwater,
More information1. Electronic Stabilizer and Technical Development. 2. Electronic Stabilizer General
SPW TPW6B series SCR Electronic Voltage Stabilizer/Power Conditioner for Industries Use Applications: Printing Specific /Medical Specific /Control Numerical Machine/Elevator Specific /Testing Specific/UPS
More informationGE Power & Water Power Generation Services
GE Power & Water Power Generation Services Generator Lifecycle Services Generating powerful solutions. Breathing new life into your aging generator. Reduce Maintenance Costs Increase Reliability Increase
More informationDesign specifications
Design specifications Design To relevant standards: IEC, VDE, DIN, ISO, EN With squirrel-cage or slipring rotor Degree of protection IP 55 / IP 65 Cooling method IC511, suitable for both indoor and outdoor
More informationPower-GEN Middle East
Power-GEN Middle East High efficiency gas turbine testing & validation Marcus H. Scholz Abu Dhabi, UAE 12-14, October 2014 GE Power & Water 2014, General Electric Company. GE Proprietary Information -
More informationSupplemental Report on the NCTPC Collaborative Transmission Plan
Supplemental Report on the NCTPC 2007-2017 Collaborative Transmission Plan May 16, 2008 1 Table of Contents I. Executive Summary...1 II. Richmond-Fort Bragg Woodruff Street 230 kv Line...2 II.A. Need for
More informationQ95 Vicksburg 69kV. System Impact Study. APS Contract No Arizona Public Service Company Transmission Planning.
A subsidiary of Pinnacle West Capital Corporation Q95 Vicksburg 69kV System Impact Study APS Contract No. 52246 By Arizona Public Service Company Transmission Planning December 1, 2010 Version 2.6 Final
More informationCSDA Best Practice. Hi-Cycle Concrete Cutting Equipment. Effective Date: Oct 1, 2010 Revised Date:
CSDA Best Practice Title: Hi-Cycle Concrete Cutting Equipment Issue No: CSDA-BP-010 : Oct 1, 2010 Revised : Introduction Hi-cycle/high frequency concrete cutting equipment has become more prevalent in
More informationPlanning for Renewables
Planning for Renewables Victor Aguirre Manager, Resource Planning 2017 IRP Workshop November 2, 2016 TEP and UNSE System San Juan U2 170 MW reduction by 2018 San Juan U1 170 MW option to exit in 2022 Navajo
More informationBRCP6SM ITT. CentriPro. 6-10" Submersible Motors. For 6" and Larger Deep Well Pumps. Engineered for life
ITT BRCP6SM CentriPro 6-10" Submersible s For 6" and Larger Deep Well Pumps Engineered for life Single Phase, 6" s (1.15 S.F.) and Required Control Boxes Diameter F.L. S.F. Control Box HP kw Volts Order
More informationLoad Modeling for Power System Studies
Load Modeling for Power System Studies WECC Load Modeling Task Force Dmitry Kosterev Bonneville Power Administration Transmission Planning Timescale of Interest Our primary interest is the fast dynamic
More informationBackground. The function of wear rings. Wear Rings. Throat Bushing
Fluid processing industries have embraced the use of composite materials in pumps to reduce vibration, increase mechanical seal life and MTBR (mean time between repair), reduce the risk of seizure, increase
More informationEE5940: Wind Essen.als. Materials and Structural Reliability Sue Mantell Mechanical Engineering
EE5940: Wind Essen.als Materials and Structural Reliability Sue Mantell Mechanical Engineering Focus on Rotor Blades Overview the most complex structural component of a wind turbine Quick overview of Loads
More informationFirst Applications on AltaLink s Network. Roggero Ciofani, P. Eng. Colin Clark, P. Eng.
First Applications on AltaLink s Network Roggero Ciofani, P. Eng. Colin Clark, P. Eng. Overview Technology Overview Applications and Alternatives Advantages Alberta Special Considerations Operational Implications
More informationOctober 17, Please contact the undersigned directly with any questions or concerns regarding the foregoing.
California Independent System Operator Corporation The Honorable Kimberly D. Bose Secretary Federal Energy Regulatory Commission 888 First Street, NE Washington, DC 20426 October 17, 2017 Re: California
More informationCooling System. Table of Contents
Sub-Headings Safety 2 s 2 Cautions 2 Notes 2 Introduction 2 General Specifications 2 Engine 2 Coolant 2 Routine Maintenance 2 Hose Connections 4 Radiator, Charge Air and Heater Cores 4 Cooling System Leaks
More informationElbert County 500 MW Generation Addition Interconnection Feasibility Study Report OASIS POSTING # GI
Executive Summary Elbert County 500 MW Generation Addition Interconnection Feasibility Study Report OASIS POSTING # GI-2003-2 Xcel Energy Transmission Planning January 2004 This Interconnection Feasibility
More informationDepartment of Market Quality and Renewable Integration November 2016
Energy Imbalance Market March 23 June 3, 216 Available Balancing Capacity Report November 1, 216 California ISO Department of Market Quality and Renewable Integration California ISO i TABLE OF CONTENTS
More informationFor Sale: Used Steam Turbine Generator Sets. Offer Ref. STG MW Steam Turbine Genset Condensing-Extraction type
Sonnenberger Str.16 Tel. +49 (0) 611-701888 www.lohrmann.com 65193 Wiesbaden - Germany Fax +49 (0) 611-701895 info@lohrmann.com For Sale: Used Steam Turbine Generator Sets Offer Ref. STG - 25.02 10 MW
More informationHonorable Mayor Smith and members of the City Council; City Manager Brenda Fischer. Approval of Contract: Brindlee Mountain Fire Apparatus
To: From: Honorable Mayor Smith and members of the City Council; City Manager Brenda Fischer Wade Brannon, Fire Chief; Date: 6/21/2011 RE: Approval of Contract: Brindlee Mountain Fire Apparatus REQUEST
More informationBeyond 60% - Pioneering H-class Efficiency with World Class Flexibility
SCC5-8000H / Irsching 4 Beyond 60% - Pioneering H-class Efficiency with World Class Flexibility Irsching General Manager for GT Power Plant Solutions Europe, Africa, Asia and Australia Siemens AG 2011.
More informationISCORMA-3, Cleveland, Ohio, September 2005
Dyrobes Rotordynamics Software https://dyrobes.com ISCORMA-3, Cleveland, Ohio, 19-23 September 2005 APPLICATION OF ROTOR DYNAMIC ANALYSIS FOR EVALUATION OF SYNCHRONOUS SPEED INSTABILITY AND AMPLITUDE HYSTERESIS
More informationHybrid Wind Solar Generator
Jerry Bell Resource Adequacy Planning Department Planning Committee December 14th, 2017 How did this concept arise? Wind units rarely use their full inverter capability If wind units capacity factors in
More informationISO Rules Part 500 Facilities Division 502 Technical Requirements Section Interconnected Electric System Protection Requirements
Applicability 1 Section 502.3 applies to: the legal owner of a generating unit directly connected to the transmission system with a maximum authorized real power rating greater than 18 MW; the legal owner
More informationTurbine, Generator & Auxiliaries - Course 234
Turbine, Generator & Auxiliaries - Course 234 STEAM VALVE HYDRAULIC CONTROL The movement of large control valves to regulate the steam supply to modern steam turbines, requires amplification of the control
More informationSmarter Network Storage: Introduction to grid-scale storage and applications, the DNO perspective
Smarter Network Storage: Introduction to grid-scale storage and applications, the DNO perspective 2 Storage: the DNO perspective Context to the storage boom Smarter Network Storage: What have we achieved?
More information4 submersible pumps powered by renewable energy sources
submersible pumps powered by renewable energy sources ENGLISH TCH technology applied to renewable energy The pumps, owered by renewable energy sources, is a new range coming from the TCH pumps with built-in
More informationTeepak Totally Enclosed Tube Ventilated High Voltage Induction Motors. A Regal Brand.
Teepak Totally Enclosed Tube Ventilated High Voltage Induction Motors A Regal Brand www.regalbeloit.com Specifications Range Poles Voltage : Upto 3000 KW : Upto 14 Pole : Upto 11000 Volt Frame : 450 1000
More informationEnergy storage - two Canadian Case Studies ESA Annual Conference, Washington, June 4th. Alex Bettencourt Managing Director
Energy storage - two Canadian Case Studies ESA Annual Conference, Washington, June 4th Alex Bettencourt Managing Director National Association Made Up of Entire Industry Utilities Industry Academia / R&D
More informationGeneration Connections Industry Workshop 2017
Generation Connections Industry Workshop 2017 1 Introduction- Topics to be covered Background: SONI & NIE Networks Generation Connections Guide Renewable Generation Update Phase 1 Review UR Connections
More informationTOT1A: Metering Point Relocation Comprehensive Progress Report (WECC Path 30)
TOT1A: Metering Point Relocation Comprehensive Progress Report (WECC Path 30) Submitted to TOT1A Stakeholders and TOT1A Interconnected Utilities And Western Electricity Coordinating Council June 6, 2013
More informationApplication Note. Case study Early fault detection of unique pump bearing faults at a major US refinery
Application Note Case study Early fault detection of unique pump bearing faults at a major US refinery Application Note Case study Early fault detection of unique pump bearing faults at a major US refinery
More informationCGD8800X CGD8800X220 Combustible Gas Detector
CGD8800X CGD8800X220 Combustible Gas Detector Background and Purpose The CGD8800X Combustible Gas Detector offers significantly improved hydrocarbon detection while featuring visual concentration indicators
More informationGrid Stability Analysis for High Penetration Solar Photovoltaics
Grid Stability Analysis for High Penetration Solar Photovoltaics Ajit Kumar K Asst. Manager Solar Business Unit Larsen & Toubro Construction, Chennai Co Authors Dr. M. P. Selvan Asst. Professor Department
More information