MECHANICAL INTEGRITY CHECKING OF GENERATOR STATOR OVERHANG BY NATURAL FREQUENCY MEASUREMENT
|
|
- Gary Simon
- 5 years ago
- Views:
Transcription
1 MECHANICAL INTEGRITY CHECKING OF GENERATOR STATOR OVERHANG BY NATURAL FREQUENCY MEASUREMENT R.K.Bhatnagar, A.K.Mukherjee, National Thermal Power Corp., India INTRODUCTION Reliable operation of generator is highly dependent on the electrical and mechanical integrity of stator winding. Failure of generator stator conductor due to electrical or mechanical problems will lead to long force outage of the unit resulting into huge revenue loss. As per our experience, most of the epoxy mica insulated generator stator conductor failure occurs due to loss of mechanical integrity of either overhang conductor or core looseness. This paper describes our experience of ensuring mechanical integrity of epoxy mica insulated stator conductor at the overhang region. DESCRIPTION Singrauli Super Thermal power station is the first power station build by NTPC. It has installed capacity of 2000MW comprising of 5X200MW units and 2X500MW units. The Generators of 200MW units are designed by M/S Electrosila, Russia and manufactured by BHEL. The stator winding of generators are directly cooled by de-mineralized water passing through hollow conductors of the stator winding. Stator core and rotor are cooled by pressurized hydrogen gas. The rating of the generator is 235MVA, 15.75KV, 0.85lag, 3-phase, double star connection and 3000rpm. The generators are having 60 slots with 2 nos. stator windings per slot. Each stator winding conductor is made of both hollow and solid conductors. DM water passes through hollow conductors for conductor cooling. DM water pressure is maintained less than casing hydrogen pressure to prevent entry of water into the generator in case of hollow conductor leakage. For detecting hydrogen gas leakage through stator conductor, gas trap device has been provided. The stator winding conductors are insulated by F class epoxy based mica insulation. Overhang conductors of stator winding are supported on stator casing by fiber glass ring and fiber glass blocks. Conductors at overhang are tied with the fiber glass ring by polyester cord. Near the exit point of the conductor from core, one epoxy putty ring was made to reduce overhang conductor vibration. Top and side ripple spring has been provided in the slot to further reduce conductor vibration. OVERVIEW OF GENERATOR STATOR Iris Rotating Machine Conference 1
2 OBSERVATION The unit-3 Generator of SSTPS was commissioned on 28 th March On 23/12/04 stator conductor leakage was observed in the generator. The important observations are as given below:- On 23/12/04 consumption of hydrogen increased to 6 cyl. in 24Hrs. from 3 cyl. Small micro bubbles was observed to be coming out from the gas trap On 29/12/04 drops of water was found seeping from expansion tank cover Dissolved oxygen in stator water was 150ppb. Stator water flushing carried out through gas trap and dissolved oxygen of stator water increased to 700ppb. On 30/12/04 stator water flushing was stopped and dissolved oxygen was again reduced to 150ppb. Hydrogen was detected in expansion tank also (7%) after expansion tank vacuum was killed. The appearance of hydrogen gas bubbles in gas trap and expansion tank along with increase of hydrogen consumption indicates stator winding hollow conductor leakage. The reduction of Dissolved Oxygen of stator water from normal value of 2100ppb to 150ppb also supports the above analysis Machine was shut down on 31/12/04 at 0757Hrs. Leakage was detected in the connecting bar between 31 Top bar to C4 (B Ph.) bushing TE C C4 EE C1 PH TE NE TOP BAR BOTTOM BAR B PHASE ELECTRICAL CONNECTIONS OF STATOR WINDING Iris Rotating Machine Conference 2
3 Leaking bar FAILED OVERHANG CONNECTING BAR After removing the insulation, crack was detected in the first bend of copper conductor L shaped Aluminum support bracket just below the defective bar at 5 O clock position supporting phase connector 55B-C5 was found broken Some blocks of supporting bracket at 11 O clock position was found loose Black paste was found at the slot exit in top and bottom part of overhang Paste like fretting product was found in the putty ring area and overhang support area PASTE OBSERVED ON OVERHANG Minor cracks were also observed in the overhang support brackets After replacement of defective bends, machine was taken into service. Iris Rotating Machine Conference 3
4 SECOND FAILURE:- Again in May-05, stator conductor leakage was detected. Machine was shut down in June-05. Leakage was observed in first bend of 11 Top to C6 connecting bar. In this occasion natural frequency testing of overhang conductor was carried out for the first time At 4 places natural frequency was observed to be around 100HZ. Strengthening of the overhang conductor was carried out to shift the natural frequency from 100HZ range. Defective bend was replaced Machine was taken into service and no problem was observed till date The machine was re-inspected 2006 and no problem was observed. ANALYSIS OF PROBLEM To detect the root cause of repeated failure fractography analysis of the cracked surface of copper conductor was carried out. The analysis indicates that the crack has developed due to fatigue. Fatigue has developed due to repetitive loading caused by conductor vibration at the overhang region. No sign of overheating or corrosion was observed. Failure of aluminum support bar also indicates presence of vibration in the overhang region. The fractography analysis of the fracture surface of the aluminum support indicates presence of beach mark caused by fatigue. The above observation indicates presence of high overhang conductor vibration. The presence of fretting product also indicates overhang conductor support looseness and subsequent vibration of the overhang conductor. During shut down of the machine in June-05, natural frequency testing of overhang conductors revels that at 4 places natural frequency was near 100HZ particularly at the places where failure has taken place. The matching of natural frequency with core vibration frequency i.e. 100HZ resulted in excessive conductor vibration due to resonance when the generator is in service. The presence of excessive overhang conductor vibration has caused repeated failure of overhang conductor. Overhang conductor of these types of generators are supported by fiberglass ring and blocks. Gaps between fiberglass ring and overhang conductors are filled by glass webbing soaked in epoxy resin. But when the support blocks are tightened, some micro gaps exist in tangential direction. Secondly epoxy resin shrinks when it is cured. Due to this property of resin, micro gaps are formed between conductors and its support after prolong operation. So when machine is in operation, due to presence of micro gaps between conductor and support, the support and conductor will not vibrate as a monolithic mass. This will cause further looseness of conductor and subsequent increase of amplitude of vibration. Conductor vibration will become severe when natural frequency of conductor approaches to 100HZ (core vibration frequency) and will result into failure. Iris Rotating Machine Conference 4
5 CONCLUSION Looseness of overhang conductor (where overhang conductor is supported by fiber glass blocks, rings and tied by lacing) will occur after prolong operation of the machine. By measuring natural frequency of overhang conductor during overhaul, this type of problem can be detected at a very early stage and corrective action can be taken to avoid premature failure of stator winding conductor. In NTPC we are carrying out measurement of natural frequency of epoxy mica insulated overhang conductor (where overhang conductor is supported by fiber glass blocks, rings and tied by lacing) of generators during generator overhaul and corrective actions were taken on the basis of natural frequency of conductor. Reference: 1. I. Culbert, et al. Handbook to Assess the Insulation Condition of Large Rotating Machines, EPRI Power Plant Reference Series, Volume 16, 1989 Iris Rotating Machine Conference 5
LEAP - Life Expectancy Analysis Program For Electrical Rotating Machines. Marcio Gennari ABB Brazil Automation Products Machines Service Osasco
LEAP - Life Expectancy Analysis Program For Electrical Rotating Machines Marcio Gennari ABB Brazil Automation Products Machines Service Osasco LEAP - Introduction ABB India (excellence center in insulation
More informationExcitation system is of Static Silicon Excitation System, including excitation transformer, thyristors, and AVR.
Turbo - Generator Type: QF Series 1. General The generator is a two pole, cylindrical rotor type synchronous machine, directly coupled with steam turbine. It has a closed-circuit cooling system to cool
More informationEPRI Generator Predictive Maintenance & Refurbishment Conference December 2, 1998
Recent Developments in Large Generator Repair Solutions and Monitoring Systems K. Weigelt D. J. Graves Generator & Motor Services, Inc. EPRI Generator Predictive Maintenance & Refurbishment Conference
More informationDevelopment of Large-capacity Indirect Hydrogen-cooled Turbine Generator and Latest Technologies Applied to After Sales Service
Development of Large-capacity Indirect Hydrogen-cooled Turbine Generator and Latest Technologies Applied to After Sales Service 39 KAZUHIKO TAKAHASHI *1 MITSURU ONODA *1 KIYOTERU TANAKA *2 SEIJIRO MURAMATSU,
More informationCustomer presentation, PG Service, BU Motors and Generators ABB LEAP Stator Winding-Condition & Lifetime assessment
Customer presentation, PG Service, BU Motors and Generators ABB LEAP Stator Winding-Condition & Lifetime assessment ABB LEAP Overview ABB LEAP - Benefits for customer Motivation to perform LEAP Failures
More informationLarge Air Cooled Generator Failure
Large Air Cooled Generator Failure Henry Tarnecky AVP - Sr. Engineering Specialist, FM Global 2017 IRIS Rotating Machinery Conference FM Global Basics Commercial/Industrial Property Insurer Mutual Co.,
More informationGlobal VPI Insulated Indirectly Hydrogen-Cooled Turbine Generator for Single-Shaft Type Combined Cycle Power Generation Facilities
Global VPI Insulated Indirectly Hydrogen-Cooled Turbine Generator for Single-Shaft Type Combined Cycle Power Generation Facilities YAMAZAKI Masaru NIIKURA Hitoshi TANIFUJI Satoshi ABSTRACT Fuji Electric
More informationExtended requirements on turbogenerators
, Siemens AG, Mülheim/Ruhr, Germany Extended requirements on turbogenerators due to changed operational regimes siemens.com Table of Content Evaluation of current operation regimes Extended requirements
More informationSteam Turbine Generator Core Isolation Issues at the Redhawk Combined Cycle Plant
Steam Turbine Generator Core Isolation Issues at the Redhawk Combined Cycle Plant Marques Montes Arizona Public Service Company Phoenix, AZ Includes material provided by John Demcko Redhawk Power Plant
More informationGenerators for the age of variable power generation
6 ABB REVIEW SERVICE AND RELIABILITY SERVICE AND RELIABILITY Generators for the age of variable power generation Grid-support plants are subject to frequent starts and stops, and rapid load cycling. Improving
More informationLarge Electric Motor Reliability: What Did the Studies Really Say? Howard W Penrose, Ph.D., CMRP President, MotorDoc LLC
Large Electric Motor Reliability: What Did the Studies Really Say? Howard W Penrose, Ph.D., CMRP President, MotorDoc LLC One of the most frequently quoted studies related to electric motor reliability
More informationDevelopment and Performance Evaluation of High-reliability Turbine Generator
Hitachi Review Vol. 52 (23), No. 2 89 Development and Performance Evaluation of High-reliability Turbine Generator Hiroshi Okabe Mitsuru Onoda Kenichi Hattori Takashi Watanabe, Dr. Eng. Hisashi Morooka
More information4.1. Manufacturing field F2 Preformed and field coil windings
4.1 Manufacturing field F2 Preformed and field coil windings 4.1.2.2 Manufacturing field F2 - Preformed and field coil windings 4.1.2.2.1 Range of services preformed coils One of the most important areas
More information2 Pole 1222MVA Turbo-Generator & 4 Pole 1690MVA Turbo-Generator
2 Pole 1222MVA Turbo-Generator & 4 Pole 1690MVA Turbo-Generator 27. August, 2008 Generator Design Team Chong Whie Cho 2008 CIGRE SESSION 42, Paris CONTENTS Introduction 2-Pole 1222MVA Generator - Specifications
More informationPump Coupling & Motor bearing damage detection using Condition Monitoring at DTPS
Journal of Physics: Conference Series Pump Coupling & Motor bearing damage detection using Condition Monitoring at DTPS To cite this article: H M Bari et al 2012 J. Phys.: Conf. Ser. 364 012022 View the
More informationDesign specifications
Design specifications Design To relevant standards: IEC, VDE, DIN, ISO, EN With squirrel-cage or slipring rotor Degree of protection IP 55 / IP 65 Cooling method IC511, suitable for both indoor and outdoor
More informationCHAPTER 3 CAUSES AND EFFECTS OF ELECTRICAL FAULTS
22 CHAPTER 3 CAUSES AND EFFECTS OF ELECTRICAL FAULTS 3.1 INTRODUCTION A large number of asynchronous motors are used in industrial processes even in sensitive applications. Consequently, a defect can induce
More informationSubstation Equipment (Bushings)
Substation Equipment (Bushings) Mark B. Goff, P.E. Tennessee Valley Authority ABSTRACT Bushings provide a point of interface such that electrical current can pass to and from an electrical apparatus. Much
More informationExpert en Acoustique et Vibration
Expert en Acoustique et Vibration The operator s assessment of Condition Monitoring Rémi Stein, Erelia, GDF Suez Group Frédéric Giordano,, AREVA EWEA 2011, March 17, 2011 Stakes and goals Operating 230
More informationXFL70 FLOW RATE (LPM) Flow Rate (GPM)
Pump Specifications XFL70 Series ¾ HP Submersible Effluent Pump For Hazardous Locations Class 1, Division 1 Groups C & D Class 1, Zone 1 and Groups IIA & IIB 50 XFL70 FLOW RATE (LPM) 0 50 100 150 200 250
More informationCondition Monitoring of Electrical Machines ABB MACHsense Solution
Condition Monitoring of Electrical Machines ABB MACHsense Solution Overview Typical failures in motor Traditional condition monitoring methods Shortfall Solutions ABB MACHsense service July 26, 2012 Slide
More informationXLE50 FLOW RATE (LPM) Flow Rate (GPM)
Pump Specifications XLE50 Series ½ HP Submersible Sewage Pump For Hazardous Locations Class 1, Division 1 Groups C & D Class 1, Zone 1 and Groups IIA & IIB 25 XLE50 FLOW RATE (LPM) 0 100 200 300 400 500
More informationEE5940: Wind Essen.als. Materials and Structural Reliability Sue Mantell Mechanical Engineering
EE5940: Wind Essen.als Materials and Structural Reliability Sue Mantell Mechanical Engineering Focus on Rotor Blades Overview the most complex structural component of a wind turbine Quick overview of Loads
More informationPressurized Air Cooled Generators
PGI Orlando Dec. 13, 2016 Pressurized Air Cooled Generators Mike Zborovsky New App Generator Portfolio Owner siemens.com Pressurized Air-Cooled Generator (SGenX-2000P) Table of content Introduction 3 Portfolio
More informationNew Generator Products
GE Power and Water New Generator Products Generator User s Conference Anthony Arrao John Yagielski General Electric Company Schenectady, NY USA November 2015 copied or distributed in whole or in part,
More informationPretest Module 21 Units 1-3 AC Generators & Three-Phase Motors
Pretest Module 21 Units 1-3 AC Generators & Three-Phase Motors 1. What are the two main parts of a three-phase 2. Which part of a three-phase squirrel-cage induction motor is a hollow core? 3. What are
More informationREAP CARE ROTATING ELECTRICAL ASSET PROGNOSTIC CARE
REAP CARE ROTATING ELECTRICAL ASSET PROGNOSTIC CARE Longevity approach Assess & Avoid Failures ROTATING ELECTRICAL ASSET PROGNOSTIC CARE Failure Statistics Failure Statistics Failure Statistics BEARING
More informationPerformance Analysis of Medium Voltage Induction Motor Using Stator Current Profile
Performance Analysis of Medium Voltage Induction Motor Using Stator Current Profile W.Rajan Babu 1, Dr.C.S.Ravichandran 2, V.Matheswaran 3 Assistant Professor, Department of EEE, Sri Eshwar College of
More informationNew Robotic Technologies for Inspecting Two Pole Electric Generators while the Rotor Remains in Place
Journal of Power and Energy Engineering, 2015, 3, 123-127 Published Online April 2015 in SciRes. http://www.scirp.org/journal/jpee http://dx.doi.org/10.4236/jpee.2015.34018 New Robotic Technologies for
More informationFault Diagnosis of Lakvijaya Power Plant: A Case Study of an Anti-Rotational Pin Failure
Journal of Engineering and Technology of the Open University of Sri Lanka (JET-OUSL), Vol. 4, No.1, 2016 Fault Diagnosis of Lakvijaya Power Plant: A Case Study of an Anti-Rotational Pin Failure N.C Tantrigoda
More informationIncreasing the Power of the Turbogenerator in the Process Of Modernization in the Mining and Energy Industry
Increasing the Power of the Turbogenerator in the Process Of Modernization in the Mining and Energy Industry Vangelica Jovanovska 1, Mila Arapcheska 1 1 Faculty of Biotechnical Sciences, University St.
More informationSolution Overview. Asset Condition Monitoring. Extend operational life and reduce downtime
Solution Overview Asset Condition Monitoring Extend operational life and reduce downtime QUALITROL Integrated Monitoring Server : Data Integration Diagram SMARTSUB Substation Condition Monitoring: Transformer
More informationFL7M-A Series. Aluminum-chip Immunity DC 2-wire Type Cylindrical Proximity Sensors. Specifications. click FEATURES ORDER GUIDE
6 FL7M-A Series FEATURES Workpieces Reliably Sensed Even if Aluminum or Cast Iron Chips Accumulate on the Sensing Head. This DC 2-wire type proximity sensor can be directly connected to programmable controllers
More informationOIP Transformer Outdoor Bushings Type COT(C) 125 COT (C) kV to 550kV up to 5000A IEC
OIP Transformer Outdoor Bushings Type COT(C) 125 COT (C) 1800 24kV to 550kV up to 5000A IEC 60137-2008 Features If you need any transformer bushing proven in operation conditions around the world, Trench
More informationWind Turbine Generator System. General Specification for HQ2000
Wind Turbine Generator System General Specification for HQ2000 April 15, 2010 Hyundai Heavy Industries Co., Ltd Electro Electric Systems h t t p : / / w w w. h y u n d a i - e l e c. c o. k r 1. General
More informationGenerator Termination Bus-bar Arrangement - Design requirements: Utility Perspective
Generator Termination Bus-bar Arrangement - Design requirements: Utility Perspective D. K. Chaturvedi (NTPC) Harshvardhan Senghani (NTPC) K Venugopal (CS Electric) This paper appraise user on the termination
More informationWorld s Largest Air-cooled Turbogenerator in operation
Titre de la diapositive! Paragraphe World s Largest Air-cooled Turbogenerator in operation Yves Sabater Table of content! Turbogenerators cooling technologies State of the art! 400 MVA air-cooled generator
More informationKontakt. Turnkey solutions for hydropower plants An overview of the ABB portfolio
Kontakt Turnkey solutions for hydropower plants An overview of the ABB portfolio ABB is the world s leading provider of products and integrated solutions for power and automation technologies for hydropower
More informationBattery Energy Storage System addressing the Power Quality Issue in Grid Connected Wind Energy Conversion System 9/15/2017 1
Battery Energy Storage System addressing the Power Quality Issue in Grid Connected Wind Energy Conversion System 9/15/2017 1 CONTENTS Introduction Types of WECS PQ problems in grid connected WECS Battery
More informationMcNary Northshore Fishway Hydro Project. History & Lessons Learned
McNary Northshore Fishway Hydro Project History & Lessons Learned May 6, 2017 21 th Annual TECHNICAL SEMINAR Machines, Maintenance, and Management: Keeping Hydro Facilities Up and Running History & Lessons
More informationFailure of Transformer Cable box A case study
Failure of Transformer Cable box A case study Presented by Janardan Choudhary, Executive Director (O&M) 1 INTRODUCTION The 280 MW Dhauliganga Power Station, NHPC Ltd, situated at remote place of Pithoragarh
More informationMCE TM Product Information 5 kv Electric Motor Analyzer
www.pdma.com MCE TM Product Information 5 kv Electric Motor Analyzer Portable and battery powered Monitors Power Circuit, Insulation, Stator, Rotor, and Air Gap Variable test voltage from 250 to 5000 V
More informationWilo SP Series Submersible Utility Pumps ETT. ETT Installation and operating instructions
Wilo SP Series Submersible Utility Pumps ETT ETT24-10.25 Installation and operating instructions 1. PREINSTALLATION CHECK Inspect this pump before it is used. Occasionally, pumps can be damaged during
More informationDEVELOPMENT OF VIBRATION CONDITION MONITORING SYSTEM APPLYING OPTICAL SENSORS FOR GENERATOR WINDING INTEGRITY OF POWER UTILITIES
Advanced Materials Development and Performance (AMDP2011) International Journal of Modern Physics: Conference Series Vol. 6 (2012) 98-103 World Scientific Publishing Company DOI: 10.1142/S2010194512003005
More informationSynchronous motors. Main spindle motors for SINAMICS S120 1FE1 standard type built-in motors Water cooling. 6/86 Siemens NC /2008
Synchronous motors Main spindle motors for SINAMICS S2 FE standard type built-in motors Siemens AG 27 Overview Benefits (continued) 7 Compatible system of SINUMERIK, SINAMICS and motor, therefore fast
More informationSulzer Dowding & Mills
Sulzer Turbo Services Company overview Sulzer today Sulzer Pumps Market leader in pump technology and solutions Sulzer Metco Market leader in surface technology Sulzer Chemtech Market leader for separation,
More informationCONTENTS 1 GENERAL 2 STANDARDS. 3 TECHNICAL FEATURES 3.1 Basic Design Data 3.2 Standard Accessories 3.3 Tolerances
CONTENTS 1 GENERAL 2 STANDARDS 3 TECHNICAL FEATURES 3.1 Basic Design Data 3.2 Standard Accessories 3.3 Tolerances 4 MOTOR DESIGN 4.1 Stator Casing 4.2 Stator Core with Winding 4.3 Stator Winding and Insulation
More informationCSDA Best Practice. Hi-Cycle Concrete Cutting Equipment. Effective Date: Oct 1, 2010 Revised Date:
CSDA Best Practice Title: Hi-Cycle Concrete Cutting Equipment Issue No: CSDA-BP-010 : Oct 1, 2010 Revised : Introduction Hi-cycle/high frequency concrete cutting equipment has become more prevalent in
More informationCONTENTS 1 GENERAL 2 STANDARDS. 3 TECHNICAL FEATURES 3.1 Basic Technical Data 3.2 Standard Accessories 3.3 Tolerances
CONTENTS 1 GENERAL 2 STANDARDS 3 TECHNICAL FEATURES 3.1 Basic Technical Data 3.2 Standard Accessories 3.3 Tolerances 4 MOTOR DESIGN 4.1 Stator Casing 4.2 Stator Core with Winding 4.3 Stator Winding 4.4
More informationPrimary Heat Transport (PHT) Motor Rotor Retaining Ring Failure
1 Primary Heat Transport (PHT) Motor Rotor Retaining Ring Failure Ali Malik Components & Equipment Eng. Ontario Power Generation - Darlington Nuclear 2 Ontario Power Generation Darlington Darlington Nuclear
More informationAbrupt Stoppage of Turbine Rotor, running on Barring after Major Overhauling
Abrupt Stoppage of Turbine Rotor, running on Barring after Major Overhauling Presented by Ravi Reddy, BVL Power Systems BVL Power Systems RANGA REDDY : Executive President Authors Mr Ranga Reddy is a Mechanical
More informationUnit - I AN ISO 9001 : 2008 COMPANY
Unit - I 2 Mission GMC is committed to serving customers with products that incorporate innovative and new technologies and to fully satisfy all customer needs and requirements. Our goal is to maintain
More informationArtesis MCM Case Studies. March 2011
Artesis MCM Case Studies March 2011 Case 1 Automotive Company: Automobile Manufacturer A Equipment: Pump Stator Isolation Breakdown Decreasing current unbalance level Case 1 Automotive Company: Automobile
More informationNEIL Turbine Generator Risk Assessment. Todd Raymond Loss Risk Analysis Manager Nuclear Service Organization April 16-17, 2013
NEIL Turbine Generator Risk Assessment Todd Raymond Loss Risk Analysis Manager Nuclear Service Organization April 16-17, 2013 Program Origin Large Losses due to Turbine Generator Failures in recent years
More informationA Homopolar Inductor Motor/Generator and Six-step Drive Flywheel Energy Storage System
A Homopolar Inductor Motor/Generator and Six-step Drive Flywheel Energy Storage System Perry Tsao, Matt Senesky, Seth Sanders University of California, Berkeley Perry s thesis defense presented www-power.eecs.berkeley.edu
More informationBefore you go through this booklet, we request you to go through the following general instruction before commissioning your hydraulic systems.
Hello, We are proud to be on your suppliers list. During few years we came to know that most of our customers are satisfied by Yuken Hydraulic Products but some of our customers had minor problems and
More informationCiMEC Technologies Pvt. Ltd., 23/H, Meldi Estate, Gota, Ahmedabad, Gujarat. Discipline Electrical Testing Issue Date
Last Amended on - Page 1 of 6 I. CABLES AND ACCESSORIES 1. PVC Insulated Cables Tests on Conductor: Annealing Test (copper) IS 10810 (Part 1):1984 (RA 2011) 0 to 50 % Tensile Test (Aluminium) IS 10810
More informationGenerator. Jason S DiSanto. 6B Users Conference San Antonio, TX June 19-22, 2017
Generator Jason S DiSanto 6B Users Conference San Antonio, TX June 19-22, 2017 GE Power 2017, General Electric Company. GE Proprietary Information - The information contained in this document is General
More informationAPS-10 to 15 Series. PBT Resin Square Type, 2-wire/3-wire DC System. Type. Proximity Sensor. Features
Series Features PBT Resin, -wire/-wire DC System - Front/Upper/Side surface detection - High reliability based on long history of various adoptions - / NPN output Type DC Type/-wire DC System Form Form
More informationCooling System. Water Pump. Radiator
The cooling system is engineered to remove waste heat from the engine cylinder block and cylinder head to prevent damage caused by overheating of those components. The waste heat is transferred through
More informationAdvanced Maintenance Technologies
Advanced Maintenance Technologies Vibration Analysis Consultants Ray W. Wonderly Certified Vibration Specialist Services: Vibration Analysis Consulting Laser Alignment Services Predictive/Planned Maintenance
More informationField Experience & Reliability Tests for the New EasyDry Condenser Bushing LUKAS MUGGLI
Field Experience & Reliability Tests for the New EasyDry Condenser Bushing LUKAS MUGGLI T. Schütte, ABB Schweiz Ltd, High Voltage Components, Bushings, 2015-10-19 INMR2015 - Munich Field experience and
More informationPretest Module 21 Units 1-4 AC Generators & Three-Phase Motors
Pretest Module 21 Units 1-4 AC Generators & Three-Phase Motors 1. What are the two main parts of a three-phase motor? Stator and Rotor 2. Which part of a three-phase squirrel-cage induction motor is a
More informationSensing distance. 4mm. 4mm. 7mm. 12mm. 20mm
DC2-wire Square Proximity Sensors FL2R/SSeries This DC2-wire Square Proximity sensor Can Be Directly Connected to Programmable Controllers and Units. Wide Range of Models Available. Reduced wiring costs
More informationIntroduction. Lubrication Related Failures. Gear Couplings. Failure Analysis All Types (Page 1 of 7)
All Types (Page 1 of 7) Introduction A gear coupling serves as a mechanical device which connects shafts of two separate machines and accommodates small amounts of shaft misalignment. Commercial gear couplings
More informationVACUUM PUMP. Please read the operating manual carefully before using.
Operating Manual 231672 Please read the operating manual carefully before using. I. Pump components Oil Fill Cap Handle Inlet Fitting Exhaust Fitting Power Switch Sight Glass Fan Cover Die-Cast Aluminum
More informationTransformer High Current Bushings Type CFPT & CFCT 36kV up to 40kA IEC
Transformer High Current Bushings Type CFPT & CFCT 36kV up to 40kA IEC 60137-2008 High current bushings for transformer Features Bushing Type CFPT version Porcelain Insulator Trench RIG technology for
More informationOperation mode. Sensing distance N.O. N.C. N.O. N.C. N.O. N.C. 7mm
6 Specifications FL7N/M Series DC 2-wire Type (shielded/unshielded) Cylindrical Proximity Sensors FEATURES Rigid Structure, Highly Water-proof DC 2-wire Type with Improved Visibility Indicator Lamps. DC
More informationSelection & Application guidelines. Condensing Units 50 Hz - 1, 2, 4 cylinders R22 - R134a - R404A / R507 REFRIGERATION AND AIR CONDITIONING
Selection & Application guidelines Condensing Units 50 Hz - 1, 2, 4 cylinders R22 - R134a - R404A / R507 REFRIGERATION AND AIR CONDITIONING www.danfoss.com 50 HZ BLUESTAR PRODUCT PROGRAMME....... p 3 Product
More informationSlip-ring motors MAR Series
Slip-ring motors MAR Series ABOUT US DAC Electric is a fairly young but highly experienced combination of professionals from all over the world. The founders, from the Netherlands and the Czech Republic,
More informationDavey 4 Submersible Borehole Pumps and Motors 4 BOREHOLE PUMPS AND MOTORS APPLICATIONS. Model Numbers: J Series
4 BOREHOLE PUMPS AND MOTORS APPLICATIONS Domestic water supply Turf watering Irrigation Stock watering Dewatering Water treatment Why choose the davey 4 SUBMERSIBLE BOREHOLE PUMP? Proven and reliable design
More informationCast resin transformers
Product catalogue Cast resin transformers according to IEC/EN 60076, VDE 0532, DIN 42523 Power range up to 8 MVA Voltage range up to 36 kv Conductor material: copper or aluminum Protection types: IP 00
More information4.2 Component Identification
Digital Control Panels Deep Sea Electronics 5220 4.1 General 4.2 Component Identification 4.3 The YML5220 Controller 4.4 Description of Controls 4.5 Navigation 4.5.1 General Navigation 4.5.2 The Event
More informationImpact of Burnout Ovens on Reliability. Mechanical Impact of High Temperature Stripping Of Induction Motor Stators
Mechanical Impact of High Temperature Stripping Of Induction Motor Stators Howard W Penrose, Ph.D., CMRP Vice President, Engineering and Reliability Services Dreisilker Electric Motors, Inc. Introduction
More informationAlternating Current Motors in Detail
Alternating Current Motors in Detail Overview/Objectives: o Advanced motor component descriptions/details o Design, materials and construction o Starting and operation o Temperature effects on performance
More informationINTER PLANT STANDARD STEEL INDUSTRY. CODE OF PRACTICE FOR REPAIR OF SQUIRRELCAGE HT MOTORS (6.6 kv) (First Revision) Corresponding IS does not exist
INTER PLANT STANDARD STEEL INDUSTRY IPSS CODE OF PRACTICE FOR REPAIR OF SQUIRRELCAGE HT MOTORS (6.6 kv) (First Revision) Corresponding IS does not exist IPSS:1-03-023-07 Formerly : IPSS:1-03-023-95 0.
More informationPROBLEMS WITH NEWER GENERATORS
PROBLEMS WITH NEWER GENERATORS CLYDE MAUGHAN, PRESIDENT MAUGHAN GENERATOR CONSULTANTS SCHENECTADY, NEW YORK Phone: 518 377 5351 Email: clyde@maughan.com Web: clyde.maughan.com 1 PRELUDE A FEW COMMENTS
More informationCentro América Application of EMI Diagnostics to Diesel Generators
Application of EMI Diagnostics to Diesel Generators CATEGORIAS *Experiencias con características de lotes de combustibles * Control de eficiencia de motores * Aliados clave para operadores de motores *
More informationFirst Applications on AltaLink s Network. Roggero Ciofani, P. Eng. Colin Clark, P. Eng.
First Applications on AltaLink s Network Roggero Ciofani, P. Eng. Colin Clark, P. Eng. Overview Technology Overview Applications and Alternatives Advantages Alberta Special Considerations Operational Implications
More informationDesign details Design. Installation types. Shaft seal. Impeller type. Drive. Bearings
ma-porter ode Description Starting aid 1) Without start capacitor With start capacitor 5 Size 5 DN 6 DN 65 01 Impeller size SE Motor version SE Single-phase motor with float switch NE Single-phase motor
More informationDOUBLE ECCENTRIC DOUBLE FLANGED BUTTERFLY VALVES. TIS asia
DOUBLE ECCENTRIC DOUBLE FLANGED BUTTERFLY VALVES VALVES DEDICATED TO THE WATER DISTRIBUTION NETWORK AND HYDROPOWER SECTOR WE DO NOT SELL JUST VALVES, WE SELL A SOLUTION FOR THE EFFICIENCY OF THE WATER
More informationIGBT Modules for Electric Hybrid Vehicles
IGBT Modules for Electric Hybrid Vehicles Akira Nishiura Shin Soyano Akira Morozumi 1. Introduction Due to society s increasing requests for measures to curb global warming, and benefiting from the skyrocketing
More informationSchuyler McElrath Gas Turbine Consultant JASC: Jansen s Aircraft Systems Controls, Inc
Fuel flexibility and reliability in Combined Cycle gas turbine applications Schuyler McElrath Gas Turbine Consultant JASC: Jansen s Aircraft Systems Controls, Inc schuyler@jasc-controls.com www.jasc-controls.com
More informationSafe, fast HV circuit breaker testing with DualGround technology
Safe, fast HV circuit breaker testing with DualGround technology Substation personnel safety From the earliest days of circuit breaker testing, safety of personnel has been the highest priority. The best
More informationExperimental evaluation of a highspeed multi-megawatt SMPM machine. Daniel M. Saban, PE PhD
Experimental evaluation of a highspeed multi-megawatt SMPM machine Daniel M. Saban, PE PhD saban@ieee.org Agenda Machine Description Testing Stator-only Open circuit No-load Short circuit Partial load,
More informationCONTENTS About the company 1. Low-voltage arresters LVA type 2. Metal-oxide surge arresters for distribution systems. 3.
CONTENTS About the company 4 1. Low-voltage arresters LVA type 5 2. Metal-oxide surge arresters for distribution systems. 6 2.1 PA-DM type 6 Dimensions of arresters of PA-DM 9 2.2 PA-DH types 10 Dimensions
More informationDemonstrate knowledge of electrical theory for Electrical Service Technician B
Demonstrate knowledge of electrical theory for Electrical Service Technician B 10937 version 4 Page 1 of 5 Level 3 Credits 3 Purpose 'Electrical Service Technician B' (EST B) refers to a class of electrical
More informationInternal Report: Tecnam P92 ES (ZK-CDL) Nose Leg Failure 25/07/2015
0753 West Airport 25 November 2015 Internal Report: Tecnam P92 ES (ZK-CDL) Nose Leg Failure 25/07/2015 Summary On 25/07/2015 the nose leg on Tecnam P92ES, registered ZK-CDL, failed due to fatigue and collapsed
More informationA REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES. Electrical. Mechanical. Civil. Protection & Control. System Planning
A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES Electrical vo1e.5s 0j 44, AMY., CK NI r. SIGNATURE Mechanical Civil Protection & Control t^ /DATE 1 o Transmission & Distribution AND Telecontrol
More informationTable of Contents. 4. Before a New Turbocharger is Installed
Table of Contents 1. Turbocharger Overview ------------------------------------------------------------------ 1.1. Definition -----------------------------------------------------------------------------
More informationFruitland 250,370 and 500 Pump Rebuild Procedure
Fruitland 250,370 and 500 Pump Rebuild Procedure - Drain oil by removing drain plug and check any contaminations in oil. - Remove the four bolts and aluminum sealing washers that connect the outer cover
More information11kV Compact Switchgear. tec - range. Minimum to Zero SF6 Insulation Gas. Outec Controls
11kV Compact Switchgear tec - range Minimum to Zero SF6 Insulation Gas. Outec Controls 1 tec xx - 11kV Switchgear Contents 1 tec CB - SF6 Free Switchgear... 3 1.1 Description:... 3 1.2 1.3 Features the
More informationAnnex A-4 DIESEL UNITS INDEX TO SYSTEM/COMPONENT CAUSE CODES BALANCE OF PLANT GENERATOR DIESEL ENGINE
Annex A-4 DIESEL UNITS INDEX TO SYSTEM/COMPONENT CAUSE CODES Electrical 3600-3690 Power Station Switchyard 3700-3730 Generator 4500-4580 Exciter 4600-4609 Cooling System 4610-4650 Controls 4700-4750 Miscellaneous
More informationJohn Holland, President, International Copper Association. Copper Demand in Asia Growth Trends and Drivers for New Applications
John Holland, President, International Copper Association Copper Demand in Asia Growth Trends and Drivers for New Applications Contents Asia Copper Consumption Overview Assessing Growing Copper Markets
More informationBENEFITS. Maximum unit power with excellent performance for high winds. - Class IA/WZII/WZIII.
GAMESA G80-2.0 MW BENEFITS Maximum unit power with excellent performance for high winds - Class IA/WZII/WZIII. - Pitch and variable speed technology to maximize energy production. - Production of lighter
More informationThe introduction of Lead Crystal Battery
The introduction of Lead Crystal Battery (1). Brief Introduction of Lead Crystal Battery Lead crystal battery is based on an in-depth study of both lead acid batteries and gel batteries features and defects,
More informationEnergy storage - two Canadian Case Studies ESA Annual Conference, Washington, June 4th. Alex Bettencourt Managing Director
Energy storage - two Canadian Case Studies ESA Annual Conference, Washington, June 4th Alex Bettencourt Managing Director National Association Made Up of Entire Industry Utilities Industry Academia / R&D
More information6 Submersible Motors Standard
Applications These motors are built for dependable operation in 6 diameter or larger water wells. Basic Features Double flanged NEMA mounting design Stainless steel splined shaft StatorShield Franklin
More informationINSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS FRM34418 (REV. B) 09/17 UNILITE DISTRIBUTOR This product is applicabl e to pre-1966 California and pre-1968 federally certified passenger cars. It is also applicable to non-emission
More information34 th Hands-On Relay School
34 th Hands-On Relay School Generation Track Overview Lecture Generator Design, Connections, and Grounding 1 Generator Main Components Stator Core lamination Winding Rotor Shaft Poles Slip rings Stator
More information