1 A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES Electrical vo1e.5s 0j 44, AMY., CK NI r. SIGNATURE Mechanical Civil Protection & Control t^ /DATE 1 o Transmission & Distribution AND Telecontrol System Planning REPLACE CIRCUIT BREAKER B1L21, STRUCTURES AND DISCONNECTS Hawke's Bay Terminal Station April 2010 newfoundland lahrador h dro nalcor energy company

2 Replace Circuit Breaker B1L21, Structures and Disconnects Hawke's Bay Terminal Station Table of Contents 1 INTRODUCTION 1 2 PROJECT DESCRIPTION 2 3 EXISTING SYSTEM Age of Equipment or System : Major Work and/or Upgrades Anticipated Useful life Maintenance History : Outage Statistics Industry Experience Maintenance or Support Arrangements Vendor Recommendations Availability of Replacement Parts Safety Performance Environmental Performance Operating Regime 7 4 JUSTIFICATION Net Present Value Levelized Cost of Energy Cost Benefit Analysis Legislative or Regulatory Requirements Historical Information Forecast Customer Growth Energy Efficiency Benefits Losses during Construction Status Quo Alternatives 10 5 CONCLUSION Budget Estimate Project Schedule 11 Newfoundland and Labrador Hydro

3 1 INTRODUCTION The Great Northern Peninsula (GNP) is connected to the Island Interconnected System through a 138 kv transmission line TL-239 and a 69 kv transmission line TL-226. Both lines originate at the Deer Lake Terminal Station. Transmission line systems, in general, get renamed when they terminate at a terminal station before continuing on to another terminal station. The 69 kv transmission system serving the GNP is composed of four individual transmission lines, TL-226, TL-227, TL-262 and TL-221. The Hawke's Bay Terminal Station is supplied by transmission line TL-221 which originates at the Peters Barren Terminal Station. TL-221 is approximately 53 kilometers in length. The 69 kv oil filled circuit breaker, B1L21 is the main protection device at the termination of TL-221 in the Hawke's Bay Terminal Station. Figure 1 is a picture of the 69 kv oil filled circuit breaker. Figure 1: 69 kv Oil Filled Circuit Breaker at the Hawke's Bay Terminal Station Newfoundland and Labrador Hydro Page 1

4 2 PROJECT DESCRIPTION This project is required to replace the 69 kv oil filled circuit breaker B1L21 and its auxiliary equipment at the Hawke's Bay Terminal Station. The existing 69 kv oil filled circuit breaker will be replaced with a new sulfur hexachloride (SF6) gas insulated breaker. The auxiliary equipment to be replaced includes: three isolating disconnect switches; a high speed ground switch; and the wood pole structure on which the disconnect switches are mounted. There are also two capacitive voltage transformers mounted on the wood pole structure. They are used for protection and control of the transmission system and will be remounted on the new wood pole structure. There is sufficient space in the station to construct the new wood pole structure and install the circuit breaker and disconnect switches without immediately dismantling the existing equipment. This will minimize power outages to customers. Upon completion of this work, the termination of transmission line TL-221 will be relocated to the new wood pole structure and connected to the new circuit breaker. During the relocation of the line termination, diesel generation will be required to provide service to customers. Newfoundland and Labrador Hydro Page 2

5 3 EXISTING SYSTEM The Hawke's Bay Terminal Station was built in 1970 to provide electrical power to approximately 1,300 customers in the communities of Hawke's Bay, Port Saunders, Port aux Choix, Eddie's Cove West and River of Ponds. The terminal station has a 69/ kv 5/6 MVA transformer and a 69/ kv 2.5/3.3 MVA transformer. The transformers step the voltage down to 12.5kV for distribution to customers. The terminal station also consists of various other equipment including circuit breakers, disconnect switches, current transformer and potential transformers. The existing 69 kv circuit breaker has had several minor leaks in recent years and the circuit breaker's isolating disconnect switches have been experiencing jamming problems. The wood pole support structure where these isolating disconnect switches are mounted has also deteriorated and as a result has become unstable and warped which is a contributing factor to the jamming of the switches. At the Hawke's Bay Terminal Station there are also two 3 MW diesel generating units used for voltage support on the transmission system and for emergency power when there is a transmission system outage. Figure 2 shows part of the Interconnected Island System including Hawke ' s Bay. COOK'S HR. L'ANSE AUX L' ANSE-AU-LOUP. / MEADOWS ST. L' ANSE-AU-CLAIR LUNAIRE EDDIES ST. COVE E. rya1 ^' ANTHONY BEAR COVE \,1gb n GOOSE COVE ST. ANTHONY MAIN AIRPORT PLUM PT. BROOK CROQUE,`v HAWKES BAY RIVER OF PONDS BELLBURNS DANIELS HR. Figure 2: GNP Portion of the Island Interconnected System Newfoundland and Labrador Hydro Page 3

6 3.1 Age of Equipment or System The circuit breaker, disconnect switches, ground switch and wood pole support structure were installed in 1970 as part of the original station construction. 3.2 Major Work and/or Upgrades There have been no major upgrades to the circuit breakers, structures and disconnects. 3.3 Anticipated Useful life The anticipated useful life of the circuit breaker, disconnect switches and wood pole structure is 30 years. 3.4 Maintenance History The five-year maintenance history for the circuit breaker, disconnect switches and ground switch is shown in Tables 1 and 2. The corrective maintenance includes PCB testing and repair, replacement and upgrades of equipment accessories. The preventive maintenance includes regular preventive maintenance checks, oil sampling and dissolved gas analysis testing. Table 1: Five-Year Maintenance History For Circuit Breaker B1L21 Preventive Maintenance Corrective Maintenance Total Maintenance Year ($000) ($000) ($000) Newfoundland and Labrador Hydro Page 4

7 Table 2: Five-Year Maintenance History For Disconnects B1L21-1, B1L21-2, B1L21-BP and Ground Switch L21G Preventive Maintenance Corrective Maintenance Total Maintenance Year ($000) ($000) ($000) Outage Statistics Terminal equipment outages statistics are provided in two tables. Table 3 lists the performance of Hydro's 66 kv circuit breakers versus the CEA latest five years (2003 to 2007). Table 4 details the performance of the Hawke's Bay Delivery Point. Table 3: Hydro's 66 kv Circuit Breaker Performance Versus CEA latest five years Number of Outages Frequency (per a) Unavailability 66 kv Breakers ( ) CEA 66 kv Breakers ( ) Frequency (per a) is the number of failures per year. Unavailability is the percent of time per year the unit is available. Table 4: Performance of the Hawke's Bay Delivery Point Five Year Averages ( ) Forced Outages Only Delivery Point Affected T-SAIFI T-SAIDI Hawke's Bay Northern Region Hydro System CEA ( ) Newfoundland and Labrador Hydro Page 5

8 3.6 Industry Experience Hydro's communication with other major Canadian utilities concerning utility operating and maintenance issues confirm that Hydro's experiences with oil filled breakers of this vintage is similar to that of the other Canadian utilities. 3.7 Maintenance or Support Arrangements Operation and maintenance work is performed by Hydro Operations personnel. 3.8 Vendor Recommendations The manufacturer, Canadian General Electric recommends replacing the equipment when it reaches the end of its useful service life of 30 years. 3.9 Availability of Replacement Parts Replacement parts for the oil filled breaker and disconnects are no longer available from the manufacturer Safety Performance The disconnect switches have been experiencing jamming problems which make them unable to operate. An inoperable disconnect switch creates a safety hazard for personnel because malfunctioning parts can break off and fall onto the workers below. A worker may suffer an injury as a result of broken pieces from disconnect switches failing from above. Due to age and deterioration beyond repair the wood pole support structure is unstable and at risk of falling down which would cause equipment damage and expose workers to live conductors. Newfoundland and Labrador Hydro Page 6

9 Figure 3: Wood Pole Structure at the Hawke ' s Bay Terminal Station 3.11 Environmental Performance There are no environmental issues related to normal operation of oil filled circuit breakers and disconnect switches but leaks from the oil filled breaker is an environmental concern. Oil from a leaking circuit breaker seeps into the earth and therefore must be cleaned up Operating Regime The equipment is in full time continuous operation. Newfoundland and Labrador Hydro Page 7

10 4 JUSTIFICATION This project is justified on the requirement to replace failing or deteriorated equipment in order for Hydro to provide safe, least-cost and reliable electrical service. The 69 kv oil filled circuit breaker B1L21 in the Hawke's Bay Terminal Station has experienced several minor leaks in recent years and is beyond its useful service life. As the circuit breaker ages, it is at increased risk for more oil leaks, outages or even complete failure which negatively impacts the reliability of electrical service. Replacement of the circuit breaker will reduce the risk of failures and ensure reliable system operation. The three breaker isolating disconnect switches are inoperable due to jamming problems and are beyond their useful service life. Reliable and secure operation of the disconnect switches is essential to a safe work environment and for reliable and secure system operation. An inoperable disconnect switch does not allow isolation of the circuit breaker making it difficult, if not impossible, for maintenance work. A safety hazard also exists because malfunctioning parts can break off and fall onto the workers below. The disconnect switches must be replaced in order to maintain a safe and reliable operating condition. The wood pole support structure has deteriorated beyond repair and is at risk of failure. Failure of the wood pole structure could result in injury to workers, damage of equipment and interruption of service to the customers. Replacement of the wood pole support structure is required in order to eliminate safety hazards and the risk of interruption to system operation. 4.1 Net Present Value A net present value calculation was not performed as there is no viable alternative to replacing the circuit breaker, disconnect switches and structure. 4.2 Levelized Cost of Energy This project does not affect the levelized cost of energy as it does not involve any new source of generation. Newfoundland and Labrador Hydro Page 8

11 4.3 Cost Benefit Analysis A cost benefit analysis is not applicable to this project as there are no quantifiable benefits. 4.4 Legislative or Regulatory Requirements There are no legislative or regulatory requirements for this project. 4.5 Historical Information Similar projects for the replacement of switches and circuit breakers at Hydro's terminal stations are shown in Table 6. These projects did not require diesel generation to minimize customer outages. Newfoundland and Labrador Hydro Page 9

12 Replace Circuit Breaker 61L21, Structures and Disconnects at Hawke's Bay Terminal Station Table 6: Historical Information Year Capital Budget Actual Expenditures Units Cost per unit Comments ($000) ($000) ($000) 2010F N/A Replacement of disconnect switches at English Harbour West, Conne River and Corner Brook Frequency Converter Replacement of 69 kv circuit breaker at Howley Replacement of disconnect switches at Cow Head and Daniel's Harbour 4.6 Forecast Customer Growth Forecast customer load growth has no effect on this project. 4.7 Energy Efficiency Benefits There are no energy efficiency benefits associated with this project. 4.8 Losses during Construction There will be no production or revenue losses resulting from this project. 4.9 Status Quo The status quo is not an option. The breaker, disconnect switches and support structure must be replaced since continuous operation with the existing equipment presents unacceptable safety and reliability issues Alternatives There are no viable alternatives to this project. Newfoundland and Labrador Hydro Page 10

13 5 CONCLUSION This project is necessary to address the safety and reliability issues related to the deteriorated condition of the circuit breaker, disconnect switches and the supporting wood pole structures. 5.1 Budget Estimate The budget estimate for this project is shown in Table 7. Table 7: Budget Estimate Project Cost:($ x1,000) Beyond Total Material Supply Labour Consultant Contract Work Other Direct Costs O/H, AFUDC & Escln Contingency TOTAL Project Schedule The anticipated project schedule is shown in Table 8. Activity Table 8: Project Schedule Milestone Project Initiation, Design & Equipment Ordering June 2011 Project Safety Plan June 2011 Field Construction/Installations October 2011 Operations Installations October 2011 Commissioning November 2011 Project In Service November 2011 Project Completion and Close Out December 2011 Newfoundland and Labrador Hydro Page 11

A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES. Electrical. Mechanical. Civil. Protection & Control. Transmission & Distribution

A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES. Electrical. Mechanical. Civil. Protection & Control. Transmission & Distribution A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES Electrical.1_ UFSS#p A:_. DAVID/ IC, L re Mechanical Civil Protection & Control an LAND& 4^ Transmission & Distribution Telecontrol System Planning

More information

Insulator Replacements

Insulator Replacements A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES Insulator Replacements Electrical Mechanical. Civil Protection & Control Transmission & Distribution Telecontrol System Planning HYDRO THE POWER

More information

A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES. Electrical. Mechanical. Civil. Protection & Control. Transmission & Distribution

A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES. Electrical. Mechanical. Civil. Protection & Control. Transmission & Distribution A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES Electrical 4a >estro Mechanical re *.i Civil f ::^:s '1 E 1 t i^.l. al1.i 2 Or Protection & Control Transmission & Distribution Telecontrol System

More information

A REPORT TO. Electrical. Mechanical. Civil. Protection & Control. Transmission & Distribution. Telecontrol. System Planning

A REPORT TO. Electrical. Mechanical. Civil. Protection & Control. Transmission & Distribution. Telecontrol. System Planning A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES Electrical 4v ^c 0:01'1 S0^O c.. ^ '^ W E. G. PIERCY i^ x zoto/off/zq,.'ftrif4^#ft^^,' r Mechanical Civil Protection & Control Transmission &

More information

A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES. Electrical. Mechanical. Civil. Protection & Control. System Planning

A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES. Electrical. Mechanical. Civil. Protection & Control. System Planning A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES Electrical Mechanical Civil Protection & Control S1GNATLJL 2oü 4 "DAT Transmission & Distribution Telecontrol - System Planning OVERHAUL DIESEL

More information

A REPORT TO THE SoMo OF COMMISSIONERS OF PUBLIC UTILITIES. Electrical. Mechanical. Civil. System Planning. Overhaul Diesel Engines.

A REPORT TO THE SoMo OF COMMISSIONERS OF PUBLIC UTILITIES. Electrical. Mechanical. Civil. System Planning. Overhaul Diesel Engines. A REPORT TO THE SoMo OF COMMISSIONERS OF PUBLIC UTILITIES Electrical Mechanical ( Protection Civil & Control & Distribution System Planning Overhaul Diesel Engines Various Locations July 2012 newfoundland

More information

A REPORT TO. Electrical. Mechanical. Civil. Transmission & Distribution. System Planning REPLACE UNIT 2 STEAM SEAL REGULATOR

A REPORT TO. Electrical. Mechanical. Civil. Transmission & Distribution. System Planning REPLACE UNIT 2 STEAM SEAL REGULATOR A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES Electrical ^ ^^ t wiessio PBG n ^, wl I,,dn,w l.n Mechanical Civil T I.C LINS Protection & Control 41 41 4-01 "i"""11'"" ii. cl u Z`^ M 1K ' ^""

More information

A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES. Electrical. Mechanical. Civil. Protection & Control. - Transmission & Distribution

A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES. Electrical. Mechanical. Civil. Protection & Control. - Transmission & Distribution A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES Muskrat Falls Project - Exhibit 114 Page 1 of 47 Electrical Mechanical /''.., Civil Protection & Control - Transmission & Distribution Telecontrol

More information

A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES. Electrical. Mechanical. Civil. Protection & Control. Transmission & Distribution

A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES. Electrical. Mechanical. Civil. Protection & Control. Transmission & Distribution A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES Electrical Q^sss^ - Mechanical Civil SIONATURI Zo \r or o', Protection & Control Transmission & Distribution Telecontrol System Planning ARC FLASH

More information

Quarterly Regulatory Report December 31, 2014 Appendix E Annual Report on Key Performance Indicators A REPORT TO 2014 ANNUAL REPORT

Quarterly Regulatory Report December 31, 2014 Appendix E Annual Report on Key Performance Indicators A REPORT TO 2014 ANNUAL REPORT 1\1LH 2013 Amended General Rate Application Information - 'kt ) p iled:p ''Gelb- Board Secretary: Quarterly Regulatory Report December 31, 2014 Appendix E A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC

More information

APPENDIX L Table 1. Storage and Distribution Study Petroleum Product Storage Facilities - Newfoundland and Labrador

APPENDIX L Table 1. Storage and Distribution Study Petroleum Product Storage Facilities - Newfoundland and Labrador APPENDIX L Table 1 Storage and Distribution Study Petroleum Product Storage Facilities - Newfoundland and Labrador - 2004 Owner/ Feeder Visitation Photo Region Location Type of Facility Operator Terminal(s)

More information

A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES. Electrical. Mechanical. Civil. Transmission & Distribution. Telecontrol.

A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES. Electrical. Mechanical. Civil. Transmission & Distribution. Telecontrol. A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES Electrical Mechanical Civil Protecti on & Contro l MAV1PJ1 Transmission & Distribution Telecontrol System Planning Upgrade Circuit Breakers July

More information

June Substation Refurbishment and Modernization. Prepared by: Substatiort Refu14bislrment and Modernization NP 2012 CBA

June Substation Refurbishment and Modernization. Prepared by: Substatiort Refu14bislrment and Modernization NP 2012 CBA 2.1 2012 Substatiort Refu14bislrment and Modernization NP 2012 CBA 2012 Substation Refurbishment and Modernization June 2011 Prepared by: Peter Feehan, P.Eng. A FORTIS COMPANY 2.1 2012 Substation Refurbishment

More information

Director Corporate Services & Board Secretary. Newfoundland and Labrador Hydro 2015 Capital Budget Application

Director Corporate Services & Board Secretary. Newfoundland and Labrador Hydro 2015 Capital Budget Application \ I newfoundland labrador k_hy dro a nalcor energy company Hydro Place. 500 Columbus Drive. P.O. Box 12400. St. John's. NL Canada A1B 4K7 t. 709.737.1400 f. 709.737.1800 www.n1h.nl.ca September 12, 2014

More information

We trust the foregoing is satisfactory. If you have any questions or comments, please contact the undersigned.

We trust the foregoing is satisfactory. If you have any questions or comments, please contact the undersigned. \ newfoundland labrador hydro a nalcor energy company Hydro Place. 00 Columbus Drive. P.O. Box 00. St. John's. NL Canada AB K t. 0..00 f. 0..00 www.nh.nl.ca December, 0 The Board of Commissioners of Public

More information

Elbert County 500 MW Generation Addition Interconnection Feasibility Study Report OASIS POSTING # GI

Elbert County 500 MW Generation Addition Interconnection Feasibility Study Report OASIS POSTING # GI Executive Summary Elbert County 500 MW Generation Addition Interconnection Feasibility Study Report OASIS POSTING # GI-2003-2 Xcel Energy Transmission Planning January 2004 This Interconnection Feasibility

More information

ATCO ELECTRIC LTD. (Transmission System) SERVICE QUALITY AND RELIABILITY PERFORMANCE, MEASURES AND INDICES Revision 0

ATCO ELECTRIC LTD. (Transmission System) SERVICE QUALITY AND RELIABILITY PERFORMANCE, MEASURES AND INDICES Revision 0 ATCO ELECTRIC LTD. (Transmission System) SERVICE QUALITY AND RELIABILITY PERFORMANCE, MEASURES AND INDICES 2018-04-24 - Revision 0 EUB Decision 2007-071 Board Direction 52 For questions or comments regarding

More information

OCTOBER 17, Emera Maine Representative: Jeffrey Fenn, P.E., LR/SGC Engineering LLC

OCTOBER 17, Emera Maine Representative: Jeffrey Fenn, P.E., LR/SGC Engineering LLC OCTOBER 17, 2018 Emera Maine s Local System Plan Bangor Hydro District Needs Assessment/Potential Solutions Local Planning Advisory Committee Meeting Emera Maine Representative: Jeffrey Fenn, P.E., LR/SGC

More information

PJM Sub Regional RTEP Committee Mid-Atlantic January 22, Esam Khadr, Sr. Director Electric Delivery Planning, PSE&G

PJM Sub Regional RTEP Committee Mid-Atlantic January 22, Esam Khadr, Sr. Director Electric Delivery Planning, PSE&G PJM Sub Regional RTEP Committee Mid-Atlantic January 22, 2016 Esam Khadr, Sr. Director Electric Delivery Planning, PSE&G PSE&G System Characteristics New Jersey utility characterized by densely populated

More information

P.O BOX 429, NUKU ALOFA, Tel: (676) Fax: (676)

P.O BOX 429, NUKU ALOFA, Tel: (676) Fax: (676) P.O BOX 429, NUKU ALOFA, Tel: (676) 27-390 Fax: (676) 23-047 Email: jvanbrink@tongapower.to 22 October 2012 Lord Dalgety Electricity Commission Tu atakilangi Nuku alofa Dear Lord Dalgety Compliance Reporting

More information

Sub Regional RTEP Committee Western Region ATSI

Sub Regional RTEP Committee Western Region ATSI Sub Regional RTEP Committee Western Region ATSI February 20, 2019 1 ATSI Needs Stakeholders must submit any comments within 10 days of this meeting in order to provide time necessary to consider these

More information

Upgrade Power Transformers

Upgrade Power Transformers - A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES Upgrade Power Transformers Electrical Mechanical I SIGATUREJ Protection & Control / Transmission & Distribution Civil Telecontrol System Planning

More information

DFO STATEMENT OF NEED REPORT

DFO STATEMENT OF NEED REPORT APPENDIX E DFO STATEMENT OF NEED REPORT Table of Contents 1.0 Executive Summary... 1 2.0 Description of the Area... 2 2.1 Geographic Study Area... 2 2.2 2016 System Configuration... 2 3.0 Area Loading

More information

2011 Substation Refurbishment and Modernization. June 2010

2011 Substation Refurbishment and Modernization. June 2010 Z,1 Substatiort Refurbish~nent and Modernization NP 2011 CBA 2011 Substation Refurbishment and Modernization June 2010 Prepared by: Peter Feehan, P.Eng. 2.1 2011 Substation Refurbishment and Modernization

More information

Generation Interconnection Facilities Study For

Generation Interconnection Facilities Study For Generation Interconnection Facilities Study For Prepared for: Prepared by: SCE&G Transmission Planning May 27, 2015 TABLE OF CONTENTS General Discussion... Page 3 Generator Interconnection Specifications...

More information

100 MW Wind Generation Project

100 MW Wind Generation Project A subsidiary of Pinnacle West Capital Corporation 100 MW Wind Generation Project CUSTOMER FINAL Feasibility Study Results By Transmission Planning, APS December 21, 2007 Executive Summary This Feasibility

More information

15 Nelson-Marlborough Regional Plan

15 Nelson-Marlborough Regional Plan 15 Nelson-Marlborough Regional Plan 15.1 Regional overview 15.2 Nelson-Marlborough transmission system 15.3 Nelson-Marlborough demand 15.4 Nelson-Marlborough generation 15.5 Nelson-Marlborough significant

More information

EMERGING REQUIREMENTS

EMERGING REQUIREMENTS Page of 0 EMERGING REQUIREMENTS EXTERNALLY INITIATED PLANT RELOCATIONS THESL distributes electricity to residential, commercial, and industrial customers via overhead and underground infrastructure. This

More information

Seabrook Substation Reliability Improvement Project

Seabrook Substation Reliability Improvement Project New England Division Seabrook Substation Reliability Improvement Project 1. Project Summary Description Seabrook Substation is critical to ISO-New England as a Pool Transmission Facility, to grid availability

More information

Sub Regional RTEP Committee Mid-Atlantic

Sub Regional RTEP Committee Mid-Atlantic Sub Regional RTEP Committee Mid-Atlantic July 26, 2016 Reliability Analysis Update MetEd Transmission Zone N-1 First Energy Planning Criteria (FERC Form 715): The North Boyertown West Boyertown 69 kv is

More information

POWER SYSTEM OPERATING INCIDENT REPORT TRIP OF 220 KV C BUSBAR AT GORDON POWER STATION ON 26 NOVEMBER 2011

POWER SYSTEM OPERATING INCIDENT REPORT TRIP OF 220 KV C BUSBAR AT GORDON POWER STATION ON 26 NOVEMBER 2011 POWER SYSTEM OPERATING INCIDENT REPORT TRIP OF 220 KV C BUSBAR AT GORDON POWER STATION ON 26 NOVEMBER 2011 PREPARED BY: Electricity System Operations Planning and Performance DATE: 22 March 2012 FINAL

More information

POWER SYSTEM INCIDENT REPORT NORTHERN POWER STATION STABILISER OUTAGE APRIL AND MAY 2010

POWER SYSTEM INCIDENT REPORT NORTHERN POWER STATION STABILISER OUTAGE APRIL AND MAY 2010 POWER SYSTEM INCIDENT REPORT NORTHERN POWER STATION STABILISER OUTAGE APRIL AND MAY PREPARED BY: ESOPP VERSION:. DATE: November FINAL OUTAGE APRIL AND MAY Disclaimer (a) Purpose - This report has been

More information

Emera Maine Representative: Jeffrey Fenn, P.E., SGC Engineering LLC

Emera Maine Representative: Jeffrey Fenn, P.E., SGC Engineering LLC OCTOBER 22, 2015 Emera Maine s Local System Plan Bangor Hydro District Needs Assessment/Potential Solutions Local Planning Advisory Committee Meeting Emera Maine Representative: Jeffrey Fenn, P.E., SGC

More information

POWER SYSTEM OPERATING INCIDENT REPORT MULTIPLE CONTINGENCY EVENT IN NORTH WEST TASMANIA ON 6 APRIL 2012

POWER SYSTEM OPERATING INCIDENT REPORT MULTIPLE CONTINGENCY EVENT IN NORTH WEST TASMANIA ON 6 APRIL 2012 POWER SYSTEM OPERATING INCIDENT REPORT MULTIPLE CONTINGENCY EVENT IN NORT WEST TASMANIA ON 6 APRIL 2012 PREPARED BY: Systems Capability DATE: 28 September 2012 FINAL IN NORT WEST TASMANIA ON 6 APRIL 2012

More information

FINAL FACILITY STUDY. 230/69/13.8 kv Transformer Addition(s) at Badwater Substation 2009 T1. September 10, 2010

FINAL FACILITY STUDY. 230/69/13.8 kv Transformer Addition(s) at Badwater Substation 2009 T1. September 10, 2010 FINAL FACILITY STUDY 230/69/13.8 kv Transformer Addition(s) at Badwater Substation 2009 T1 September 10, 2010 I. Introduction This is a revised facility study performed for Transmission Queue Request 2009

More information

15 Nelson-Marlborough Regional Plan

15 Nelson-Marlborough Regional Plan 15 Nelson-Marlborough Regional Plan 15.1 Regional overview 15.2 Nelson-Marlborough transmission system 15.3 Nelson-Marlborough demand 15.4 Nelson-Marlborough generation 15.5 Nelson-Marlborough significant

More information

SSF Section Location of Change SSF Issue Change(s) Comments Chapter Part B All Multiple Formatting, spelling and minor Changes applied -

SSF Section Location of Change SSF Issue Change(s) Comments Chapter Part B All Multiple Formatting, spelling and minor Changes applied - SSF Update December 2017 Summary of Changes This table only mentions SSF chapters that were updated. All other SSF chapters were checked and confirmed as still being uptodate. SSF Section Location of Change

More information

New Jersey State Report

New Jersey State Report New Jersey State Report July 2017 Table of Contents 1. Planning Generation Portfolio Analysis Transmission Analysis Load Forecast 2. Markets Capacity Market Results Market Analysis 3. Operations Emissions

More information

Sub Regional RTEP Committee South

Sub Regional RTEP Committee South Sub Regional RTEP Committee South December 18, 2017 Baseline Reliability and Supplemental Projects Second Review 2 Date Project Last Presented: 10/30/2017 SRRTEP Problem Statement: DOM End of Life Criteria

More information

A 500kV AIS Switchyard Rejuvenation in British Columbia using Hybrids

A 500kV AIS Switchyard Rejuvenation in British Columbia using Hybrids A 500kV AIS Switchyard Rejuvenation in British Columbia using Hybrids Author Company Email Presenter T.A. Messinger BC Hydro toly.messinger@bchydro.com E. Burt BC Hydro ed.burt@bchydro.com P.Glaubitz Siemens

More information

Emera Maine Representative: Jeffrey Fenn, P.E., SGC Engineering LLC

Emera Maine Representative: Jeffrey Fenn, P.E., SGC Engineering LLC OCTOBER 22, 2014 Emera Maine s Local System Plan Bangor Hydro District Needs Assessment/Potential Solutions Local Planning Advisory Committee Meeting E M i R t ti Emera Maine Representative: Jeffrey Fenn,

More information

New 115 kv Disconnect Switches at Bloomsburg MTS

New 115 kv Disconnect Switches at Bloomsburg MTS 115 kv Line tap from C9 to Bloomsburg MTS & New Bus Tie Switch CAA ID Number: 2007-EX353 Final Draft ASSESSMENT SUMMARY 1. GENERAL DESCRIPTION Norfolk TS and Bloomsburg MTS are supplied by a single 115

More information

Muskrat Falls Project - Exhibit 26 Page 1 of 14 FORCED OUTAGE RATES 2006 UPDATE

Muskrat Falls Project - Exhibit 26 Page 1 of 14 FORCED OUTAGE RATES 2006 UPDATE Page 1 of 14 FORCED OUTAGE RATES 2006 UPDATE System Planning December 2006 1 Page 2 of 14 1. INTRODUCTION The Forced Outage Rates (FOR) used as a basis for STRATEGIST modeling are derived from the Canadian

More information

1 GENERAL Project Description Labrador Island Transmission Link (LIL) Language and Units Site Climate Data...

1 GENERAL Project Description Labrador Island Transmission Link (LIL) Language and Units Site Climate Data... SLI Doc. No. 505573-8600-40EW-0001 02 26-Aug-2014 iii TABLE OF CONTENTS PAGE 1 GENERAL... 1 1.1 Project Description... 2 1.1.1 Labrador Island Transmission Link (LIL)... 3 1.2 Language and Units... 4 1.3

More information

Appendix D Black Hills Project Summary

Appendix D Black Hills Project Summary Page 1 of 28 Appendix D Black Hills Project Summary Table of Contents Black Hills Project Summary... D-1 Boone-Nyberg 115 kv Project... D-3 Rattlesnake Butte 115 kv Substation Terminal... D-6 Fountain

More information

Pump Station 7 Improvements

Pump Station 7 Improvements Project Business Case ID: C04 2/18/2017 Pump Station 7 Project Purpose: The purpose of this project is to ensure that Pump Station 7 continues to operate in an efficient and effective manner following

More information

Supplemental Report on the NCTPC Collaborative Transmission Plan

Supplemental Report on the NCTPC Collaborative Transmission Plan Supplemental Report on the NCTPC 2007-2017 Collaborative Transmission Plan May 16, 2008 1 Table of Contents I. Executive Summary...1 II. Richmond-Fort Bragg Woodruff Street 230 kv Line...2 II.A. Need for

More information

May 11, Ms. Kavita Kale Executive Secretary Michigan Public Service Commission 7109 West Saginaw Highway Post Office Box Lansing, MI 48909

May 11, Ms. Kavita Kale Executive Secretary Michigan Public Service Commission 7109 West Saginaw Highway Post Office Box Lansing, MI 48909 Amy C. Monopoli Counsel Regulatory & Legislative Phone: 774-452-4227 amonopoli@itctransco.com May 11, 2017 Ms. Kavita Kale Executive Secretary Michigan Public Service Commission 7109 West Saginaw Highway

More information

Net Metering Interconnection Requirements. Customer Generation Capacity Not Exceeding 100 kw. Date: Version: 1

Net Metering Interconnection Requirements. Customer Generation Capacity Not Exceeding 100 kw. Date: Version: 1 Net Metering Interconnection Requirements Customer Generation Capacity Not Exceeding 100 kw Date: 2017-07-01 Version: 1 Revision History Date Rev. Description July 01, 2017 1 Initial release Newfoundland

More information

Falcon-Midway 115 kv Line Uprate Project Report

Falcon-Midway 115 kv Line Uprate Project Report Falcon-Midway 115 kv Line Uprate Project Report 12/1/2008 1 Background The function of this project is to uprate the 26.7 miles of Tri-State s 115 kv line between Midway and Falcon substations from 50

More information

South Carolina Electric and Gas Company Planned Transmission Projects $2M and above Total 5 Year Budget

South Carolina Electric and Gas Company Planned Transmission Projects $2M and above Total 5 Year Budget Project 1 of 28 Blythewood 115 kv Switching Station: Construct 03087A Construct Blythewood Switching Station with four 115 kv line terminals, with plans to expand to 230 kv at a future date. Fold in the

More information

Final Draft Report. Assessment Summary. Hydro One Networks Inc. Longlac TS: Refurbish 115/44 kv, 25/33/ General Description

Final Draft Report. Assessment Summary. Hydro One Networks Inc. Longlac TS: Refurbish 115/44 kv, 25/33/ General Description Final Draft Report Assessment Summary Hydro One Networks Inc. : Refurbish 115/44 kv, 25/33/42 MVA DESN Station CAA ID Number: 2007-EX360 1.0 General Description Hydro One is proposing to replace the existing

More information

Service Requested 150 MW, Firm. Table ES.1: Summary Details for TSR #

Service Requested 150 MW, Firm. Table ES.1: Summary Details for TSR # Executive Summary Firm point to point transmission service has been requested by Transmission Service Request (TSR) #75669514, under the SaskPower Open Access Transmission Tariff (OATT). The TSR consists

More information

Sub Regional RTEP Committee South

Sub Regional RTEP Committee South Sub Regional RTEP Committee South October 30, 2017 Baseline Reliability and Supplemental Projects First Preliminary Review 2 Dominion: Baseline Violation 115 kv Line #43 Staunton to Harrisonburg End of

More information

2016 Load & Capacity Data Report

2016 Load & Capacity Data Report Caution and Disclaimer The contents of these materials are for information purposes and are provided as is without representation or warranty of any kind, including without limitation, accuracy, completeness

More information

Review of Electric Utility Hurricane Preparedness and Restoration Actions ORLANDO UTILITIES COMMISSION RESPONSES TO STAFF'S SECOND DATA REQUEST

Review of Electric Utility Hurricane Preparedness and Restoration Actions ORLANDO UTILITIES COMMISSION RESPONSES TO STAFF'S SECOND DATA REQUEST BEFORE THE FLORIDA PUBLIC SERVICE COMMISSION In re: Staff's Second Data Request on OUC' s Review of Electric Utility Hurricane Preparedness and Restoration Actions Docket No. 20170215-EU Filed: January

More information

Eyre Peninsula electricity supply options investigation

Eyre Peninsula electricity supply options investigation 20 November 2017 South Australia s electricity transmission specialist Eyre Peninsula electricity supply options investigation Project Assessment Draft Report Port Lincoln Public Forum electranet.com.au

More information

Outer Metro 115 kv Transmission Development Study. (Scott Co, Carver Co and Hennepin Co)

Outer Metro 115 kv Transmission Development Study. (Scott Co, Carver Co and Hennepin Co) Outer Metro 115 kv Transmission Development Study. (Scott Co, Carver Co and Hennepin Co) Participants: Great River Energy Xcel Energy Inc. Executive Summary This study is done to address various load serving

More information

OKLAHOMA CORPORATION COMMISSION REGULATED ELECTRIC UTILITIES 2018 RELIABILITY SCORECARD

OKLAHOMA CORPORATION COMMISSION REGULATED ELECTRIC UTILITIES 2018 RELIABILITY SCORECARD OKLAHOMA CORPORATION COMMISSION REGULATED ELECTRIC UTILITIES 2018 RELIABILITY SCORECARD June 1, 2018 Table of Contents 1.0 Introduction...3 2.0 Summary...3 3.0 Purpose...3 4.0 Definitions...4 5.0 Analysis...5

More information

South Carolina Electric and Gas Company Planned Transmission Projects $2M and above Total 5 Year Budget

South Carolina Electric and Gas Company Planned Transmission Projects $2M and above Total 5 Year Budget Project 1 of 34 Aiken Trans - Aiken Hampton 115 kv Line: Upgrade 1272A Upgrade the 115 kv line between Aiken and Aiken Hampton substations from 336 ACSR to 1272 ACSR. Total line length approximately 3.7

More information

ELECTRIC SYSTEM RELIABILITY ANNUAL REPORT

ELECTRIC SYSTEM RELIABILITY ANNUAL REPORT ELECTRIC SYSTEM RELIABILITY ANNUAL REPORT 2016 LIBERTY UTILITIES (CALPECO ELECTRIC) LLC (U 933 E) Prepared for California Public Utilities Commission July 15, 2017 EXECUTIVE SUMMARY The Electric System

More information

Dunvegan Hydroelectric Project. For Glacier Power Limited. Preliminary Interconnection Study

Dunvegan Hydroelectric Project. For Glacier Power Limited. Preliminary Interconnection Study ` Dunvegan Hydroelectric Project For Glacier Power Limited Preliminary Interconnection Study Prepared by Pung Toy, P. Eng. and Ata Rehman, P. Eng. September 24, 2004 Table of Contents Table of Contents...

More information

CI Number: ACE CI Page 1 of 9. Title: Metro Voltage Support - Add Capacitor Bank

CI Number: ACE CI Page 1 of 9. Title: Metro Voltage Support - Add Capacitor Bank 216 ACE CI 46587 Page 1 of 9 CI Number: 46587 Title: Metro Voltage Support Add Capacitor Bank Start Date: 215/6 InService Date: 216/12 Final Cost Date: 217/6 Function: Transmission Forecast Amount: 3,373,511

More information

National Grid UK Electricity Transmission plc. NATIONAL SAFETY INSTRUCTION and Guidance

National Grid UK Electricity Transmission plc. NATIONAL SAFETY INSTRUCTION and Guidance National Grid UK Electricity Transmission plc NATIONAL SAFETY INSTRUCTION and HIGH VOLTAGE METAL CLAD SWITCHGEAR WITH SPOUTS Copyright National Grid plc 2014, all rights reserved. No part of this publication

More information

Out of Sight Out of Mind Revisited. EEI Transmission, Distribution, & Metering Conference October 14, 2009 Ken Hall Hall Energy Consulting

Out of Sight Out of Mind Revisited. EEI Transmission, Distribution, & Metering Conference October 14, 2009 Ken Hall Hall Energy Consulting Out of Sight Out of Mind Revisited EEI Transmission, Distribution, & Metering Conference October 14, 2009 Ken Hall Hall Energy Consulting 1 Presentation Outline Customer Expectations Storms and Outages:

More information

Interconnection System Impact Study Report Request # GI

Interconnection System Impact Study Report Request # GI Executive Summary Interconnection System Impact Study Report Request # GI-2008-23 34 MW Solar Generation Ranch at Hartsel, Colorado Public Service Company of Colorado Transmission Planning August 19, 2010

More information

and Board Secretary Newfoundland and Labrador Hydro 2017 Capital Budget Application Revision

and Board Secretary Newfoundland and Labrador Hydro 2017 Capital Budget Application Revision ANir I newfoundland labrador a nalcor energy company September 7, 2016 Hydro Place. 500 Columbus Drive. P.O. Box 12400. St. John's. NI Canada AlB 4K7 t. 709.737.1400 f. 709.737.1800 www.n1h.nl.ca Board

More information

2015 WDC Disturbance and Protection Standards Overview

2015 WDC Disturbance and Protection Standards Overview NERC Update 2015 WDC Disturbance and Protection Standards Overview Rich Bauer Senior Manager Reliability Risk Management / Event Analysis IEEE PSRC meeting Denver, Co May 12, 2016 2 System Protection and

More information

NEWFOUNDLAND AND LABRADOR HYDRO GULL ISLAND TO SOLDIERS POND HVDC INTERCONNECTION DC SYSTEM STUDIES VOLUME 1

NEWFOUNDLAND AND LABRADOR HYDRO GULL ISLAND TO SOLDIERS POND HVDC INTERCONNECTION DC SYSTEM STUDIES VOLUME 1 Page 1 of 76 NEWFOUNDLAND AND LABRADOR HYDRO GULL ISLAND TO SOLDIERS POND HVDC INTERCONNECTION DC SYSTEM STUDIES VOLUME 1 Page 2 of 76 NEWFOUNDLAND AND LABRADOR HYDRO GULL ISLAND TO SOLDIERS POND HVDC

More information

STRAIT OF BELLE ISLE

STRAIT OF BELLE ISLE NEWOUNDLAND AND LABADO COAST List of s, Buoys and 211 H154 Pointe iche 50 41 54.6 057 24 36.8 l W 5s 29.3 15 White octagonal tower, red upper portion. 19.8 lash 0.2 s; eclipse 4.8 s. Edn 07/10 211.1 Little

More information

Grounding Of Standby & Emergency Power Systems

Grounding Of Standby & Emergency Power Systems July / August 2007 ELECTRICAL LINE 53 Grounding Of Standby & Emergency Power Systems By Andrew Cochran Power continuity is essential in many industrial and commercial installations where a trip out due

More information

REDUCING VULNERABILITY OF AN ELECTRICITY INTENSIVE PROCESS THROUGH AN ASYNCHRONOUS INTERCONNECTION

REDUCING VULNERABILITY OF AN ELECTRICITY INTENSIVE PROCESS THROUGH AN ASYNCHRONOUS INTERCONNECTION REDUCING VULNERABILITY OF AN ELECTRICITY INTENSIVE PROCESS THROUGH AN ASYNCHRONOUS INTERCONNECTION Summary Abhay Kumar Mata Prasad R C Maheshwari Asea Brown Boveri Ltd. 4th Floor, 71 Nehru Place, New Delhi

More information

The Long-Range Transmission Plan

The Long-Range Transmission Plan The Long-Range Transmission Plan 2015 2025 Matt Koenig Presentation to ESPWG / TPAS October 29 th, 2015 Long-Range Transmission Plan Driver of the Plan is to maintain local reliability 10-year planning

More information

SUBJECT: CONTRACT C080S, HOIST REPLACEMENT AT BUS MAINTENANCE DIVISIONS 3, 5, 9, 10, AND 18, PETERSON HYDRAULICS AND ROTARY LIFT, A JOINT VENTURE

SUBJECT: CONTRACT C080S, HOIST REPLACEMENT AT BUS MAINTENANCE DIVISIONS 3, 5, 9, 10, AND 18, PETERSON HYDRAULICS AND ROTARY LIFT, A JOINT VENTURE æ Metro Metropolitan Transportation Authority One Gateway Plaza Los Angeles, CA 9 012-2952 3~ 213-922.2000 Tel metro. net OPERATIONS COMMITTEE NOVEMBER 15, 2007 SUBJECT: CONTRACT C080S, HOIST REPLACEMENT

More information

Transmission Improvements Plan for 575 MW Network Service Request Wansley CC 7 Generation Facility (OASIS # ) Georgia Transmission Corporation

Transmission Improvements Plan for 575 MW Network Service Request Wansley CC 7 Generation Facility (OASIS # ) Georgia Transmission Corporation Transmission Improvements Plan for 575 MW Network Service Request CC 7 Generation Facility (OASIS # 143556) Georgia Transmission Corporation November 11, 2010 CC7 TIP 11-11-2010 (2).docx PROBLEM STATEMENT

More information

THE NECESSITY OF THE 500 KV SYSTEM IN NWE S TRANSMISSION SYSTEM TO MAINTAIN RELIABLE SERVICE TO MONTANA CUSTOMERS

THE NECESSITY OF THE 500 KV SYSTEM IN NWE S TRANSMISSION SYSTEM TO MAINTAIN RELIABLE SERVICE TO MONTANA CUSTOMERS THE NECESSITY OF THE 500 KV SYSTEM IN NWE S TRANSMISSION SYSTEM TO MAINTAIN RELIABLE SERVICE TO MONTANA CUSTOMERS 2/27/2018 ELECTRIC TRANSMISSION PLANNING Table of Contents Table of Contents... 2 Executive

More information

Reasonableness Test RT 015 /11 Salisbury Substation 11kV Feeders

Reasonableness Test RT 015 /11 Salisbury Substation 11kV Feeders Reasonableness Test RT 015 /11 Salisbury Substation 11kV Feeders Reasonableness Test: Salisbury Substation 11kV Feeders DISCLAIMER The purpose of this document is to inform customers, Interested Parties,

More information

POWER SYSTEM OPERATING INCIDENT REPORT SIMULTANEOUS TRIP OF 5A6 MT PIPER BANNABY 500 KV LINE AND MT PIPER NO. 2 UNIT ON 9 FEBRUARY 2012

POWER SYSTEM OPERATING INCIDENT REPORT SIMULTANEOUS TRIP OF 5A6 MT PIPER BANNABY 500 KV LINE AND MT PIPER NO. 2 UNIT ON 9 FEBRUARY 2012 POWER SYSTEM OPERATING INCIDENT REPORT SIMULTANEOUS TRIP OF 5A6 MT PIPER BANNABY 500 KV LINE AND MT PIPER NO. 2 PREPARED BY: Electricity System Operations Planning and Performance DATE: 5 June 2012 FINAL

More information

System Impact Study Report

System Impact Study Report Report For: NTE Carolinas II, LLC ( Customer ) Queue #: 42432-01 Service Location: Rockingham County, NC Total Output: 477 MW (summer) / 540 MW (winter) Commercial Operation Date: 12/1/2020 42432-01 SIS

More information

2012 Water Consumption Statistics Report. Water Services Department

2012 Water Consumption Statistics Report. Water Services Department 212 Water Consumption Statistics Report Water Services Department Issued: December 213 TABLE OF CONTENTS 212 Water Consumption Statistics Report December 213 212 GVWD Statistics Book - Notes...3 Annual

More information

PJM Generator Interconnection R81 Emilie (Fords Mill) MW Impact Study Re-Study

PJM Generator Interconnection R81 Emilie (Fords Mill) MW Impact Study Re-Study PJM Generator Interconnection R81 Emilie (Fords Mill) 100.9 MW Impact Study Re-Study August 2008 DMS # 498781 General Queue R81 Emilie (Fords Mills) is a Fairless Energy, LLC request to obtain an additional

More information

Expected Energy Not Served (EENS) Study for Vancouver Island Transmission Reinforcement Project (Part I: Reliability Improvements due to VITR)

Expected Energy Not Served (EENS) Study for Vancouver Island Transmission Reinforcement Project (Part I: Reliability Improvements due to VITR) Report-BCTC-R009A Expected Energy Not Served (EENS) Study for Vancouver Island Transmission Reinforcement Project (Part I: Reliability Improvements due to VITR) December 8, 2005 Prepared by Wenyuan Li

More information

Attention: Ms. Cheryl Blundon Director Corporate Services and Board Secretary

Attention: Ms. Cheryl Blundon Director Corporate Services and Board Secretary July 18, 2002 The Board of Commissioners of Public Utilities Prince Charles Building 120 Torbay Road P.O. Box 21040 St. John s, Newfoundland A1A 5B2 Attention: Ms. Cheryl Blundon Director Corporate Services

More information

West Station-West Cañon 115 kv Transmission Project

West Station-West Cañon 115 kv Transmission Project West Station-West Cañon 115 kv Transmission Project Project Sponsor: Additional Project Participants: Project Description: Black Hills Colorado Electric New 115 kv line from West Station to West Cañon

More information

UTILITIES. Newfoundland and Labrador Hydro Schedule of Rates, Rules and Regulations

UTILITIES. Newfoundland and Labrador Hydro Schedule of Rates, Rules and Regulations UTILITIES Newfoundland and Labrador Hydro Schedule of Rates, Rules and Regulations Updated April 1, 2018 TABLE OF CONTENTS Rules Description Page No. UTILITY Newfoundland Power...UT-1 INDUSTRIAL Island

More information

Newfoundland and Labrador Vehicle Efficiency and Cost Calculator (VECC) Methodology Report

Newfoundland and Labrador Vehicle Efficiency and Cost Calculator (VECC) Methodology Report Newfoundland and Labrador Vehicle Efficiency and Cost Calculator (VECC) Methodology Report Department of Municipal Affairs and Environment Government of Newfoundland and Labrador September 2017 Table of

More information

BEFORE THE PUBLIC SERVICE COMMISSION OF THE STATE OF UTAH ROCKY MOUNTAIN POWER. Exhibit Accompanying Rebuttal Testimony of Dana M.

BEFORE THE PUBLIC SERVICE COMMISSION OF THE STATE OF UTAH ROCKY MOUNTAIN POWER. Exhibit Accompanying Rebuttal Testimony of Dana M. Exhibit RMP (DMR-1R) BEFORE THE PUBLIC SERVICE COMMISSION OF THE STATE OF UTAH ROCKY MOUNTAIN POWER Exhibit Accompanying Rebuttal Testimony of Dana M. Ralston Lakeside U12 Combustion Turbine Exhaust Cylinder

More information

Sub-Regional RTEP Committee PJM South

Sub-Regional RTEP Committee PJM South Sub-Regional RTEP Committee PJM South SRRTEP - South December 1, 2016 www.pjm.com PJM Baseline Project B2185 Update Problem: NERC Category B Violation (DVP Analysis) The 2017 summer base case indicates

More information

OKLAHOMA CORPORATION COMMISSION REGULATED ELECTRIC UTILITIES 2017 RELIABILITY SCORECARD

OKLAHOMA CORPORATION COMMISSION REGULATED ELECTRIC UTILITIES 2017 RELIABILITY SCORECARD OKLAHOMA CORPORATION COMMISSION REGULATED ELECTRIC UTILITIES 2017 RELIABILITY SCORECARD May 1, 2017 Table of Contents 1.0 Introduction...3 2.0 Summary...3 3.0 Purpose...3 4.0 Definitions...4 5.0 Analysis...5

More information

High Lonesome Mesa 100 MW Wind Generation Project (OASIS #IA-PNM ) Interconnection Facility Study. Final Report November 2, 2007

High Lonesome Mesa 100 MW Wind Generation Project (OASIS #IA-PNM ) Interconnection Facility Study. Final Report November 2, 2007 High Lonesome Mesa 100 MW Wind Generation Project (OASIS #IA-PNM-2006-02) Interconnection Facility Study Final Report November 2, 2007 Prepared by: Public Service Company of New Mexico Electric Services

More information

2018 Load & Capacity Data Report

2018 Load & Capacity Data Report Caution and Disclaimer The contents of these materials are for information purposes and are provided as is without representation or warranty of any kind, including without limitation, accuracy, completeness

More information

Department of Legislative Services

Department of Legislative Services Department of Legislative Services Maryland General Assembly 2006 Session HB 38 FISCAL AND POLICY NOTE House Bill 38 (Delegate Hubbard) Health and Government Operations Procurement - Diesel-Powered Nonroad

More information

Interconnection Feasibility Study Report GIP-222-FEAS-R3

Interconnection Feasibility Study Report GIP-222-FEAS-R3 Interconnection Feasibility Study Report GIP-222-FEAS-R3 System Interconnection Request #222 48 MW Steam Generating Facility Pictou County (53N) 2010 07 30 Control Centre Operations Nova Scotia Power Inc.

More information

Generator Interconnection Facilities Study For SCE&G Two Combustion Turbine Generators at Hagood

Generator Interconnection Facilities Study For SCE&G Two Combustion Turbine Generators at Hagood Generator Interconnection Facilities Study For SCE&G Two Combustion Turbine Generators at Hagood Prepared for: SCE&G Fossil/Hydro June 30, 2008 Prepared by: SCE&G Transmission Planning Table of Contents

More information

Transmission and Distribution Substation Projects. Operating Company: Entergy Gulf States - Texas. Customer: PID # 202

Transmission and Distribution Substation Projects. Operating Company: Entergy Gulf States - Texas. Customer: PID # 202 Transmission and Distribution Substation Projects Operating Company: Entergy Gulf States - Texas Customer: PID # 202 Funding Project Number: F4PPGS0386 Facility Study for PID # 202: Study for 146 MW Revision

More information

An Inside Look at Electric Reliability 2016 Electric Reliability Report

An Inside Look at Electric Reliability 2016 Electric Reliability Report An Inside Look at Electric Reliability 2016 Electric Reliability Report Stockton, Bakersfield, California California November November 6, 2017 3, 2016 Welcome 2 David Meier Senior Manager, Stockton Division

More information

EH2741 Communication and Control in Electric Power Systems Lecture 3. Lars Nordström Course map

EH2741 Communication and Control in Electric Power Systems Lecture 3. Lars Nordström Course map EH2741 Communication and Control in Electric Power Systems Lecture 3 Lars Nordström larsn@ics.kth.se 1 Course map 2 1 Outline 1. Repeating Power System Control 2. Power System Topologies Transmission Grids

More information

Net Metering Interconnection Requirements

Net Metering Interconnection Requirements Net Metering Interconnection Requirements Customer Generation Capacity Not Exceeding 100 kw Date: 2017-07-01 Version: 1 Revision History Date Rev. Description July 1, 2017 1 Initial Release Newfoundland

More information

CA-NP-003. Newfoundland Power 2013/2014 General Rate Application Page 1 of 1

CA-NP-003. Newfoundland Power 2013/2014 General Rate Application Page 1 of 1 Requests for Information CA-NP-003 NP 2013/2014 GRA 1 2 3 4 5 6 Q. [ELG] Please provide the Company s depreciation request based on an ALG calculation procedure rather than the proposed ELG calculation

More information

Building a 21 st Century Electric Grid. February 23, 2018

Building a 21 st Century Electric Grid. February 23, 2018 Building a 21 st Century Electric Grid February 23, 2018 1 DTE strives to provide customers with a 21 st century electric grid that is safe, highly reliable, affordable and accessible 2 Our investment

More information