1 A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES Insulator Replacements Electrical Mechanical. Civil Protection & Control Transmission & Distribution Telecontrol System Planning HYDRO THE POWER OF COMMITMENT NEWFOUNDLAND AND LABRADOR HYDRO

2 Table of Contents 1 INTRODUCTION PROJECT DESCRIPTION EXISTING SYSTEM Age of Equipment or System Major Work or Upgrades Anticipated Useful life Maintenance History Outage Statistics Industry Experience Maintenance or Support Arrangements Vendor Recommendations Availability of Replacement Parts Safety Performance Environmental Performance Operating Regime JUSTIFICATION Net Present Value Levelized Cost of Energy Cost Benefit Analysis Forecast Customer Growth Energy Efficient Benefits Legislative or Regulatory Requirements Historical Information Losses during Construction Status Quo Alternatives CONCLUSION Budget Estimate Project Schedule...12 Newfoundland and Labrador Hydro i

3 1 INTRODUCTION In the 1960s and 1970s Newfoundland and Labrador Hydro (Hydro) was using Canadian Porcelain (CP) and Canadian Ohio Brass (COB) pin type and suspension type insulators in distribution line construction. Industry experience has shown the porcelain in these insulators is prone to failure caused by cement growth. Cement growth is the expansion of the material which holds in place the pin that supports the connection of the insulator to the pole or to the conductor. Cement growth causes hairline cracks to appear in the porcelain, thereby, weakening the insulator. This leads to electrical and mechanical breakdown. Over the past ten years, Hydro has been replacing CP and COB insulators with Hydro's new standard 34.5 kv Post type clamp top or 35kV Hendrix vise top and the suspension type insulators will be replaced with the new standard Polymer. The Jackson s Arm Line 1 (L1) and Line 2 (L2) and the Hampden Line 1 (L1) distribution lines were built in Jackson s Arm L1 services the communities of Jackson s Arm, Wick s Cove, and Godfather s Cove while Jackson s Arm L2 services Schooner Cove, Sop s Arm, Burnt Head Cove, and Pollard s Point. Hampden L1 serves the communities of Hampden, Bay Side, and The Beaches and Rooms located in the vicinity of White Bay in the central area of Newfoundland. The Little Bay Line 2 (L2) distribution line was built in 1974 and serves the community of Beachside. Newfoundland and Labrador Hydro Page 1

4 2 PROJECT DESCRIPTION The project will include the replacement of 2,270 insulators on the Jackson's Arm distribution feeders L1 and L2 and on the Hampden distribution feeder L1. It will also include the replacement of 270 insulators on the Little Bay distribution feeder L2. Newfoundland and Labrador Hydro Page 2

5 3 EXISTING SYSTEM Jackson s Arm L1 is a 12.5 kv three-phase feeder that extends from the Jackson s Arm Terminal Station to the community of Godfather s Cove covering a distance of approximately five kilometers and serving approximately 200 customers. Jackson s Arm L2 is also a 12.5 kv three-phase feeder that extends from the Jackson s Arm Terminal Station to the community of Pollards Point covering a distance of approximately 20 kilometers and serving approximately 300 customers. Hampden L1 is a 12.5 kv three-phase feeder that extends from the Hampden Terminal Station to the community of The Beaches and Rooms covering a distance of 22 kilometers and serving approximately 300 customers. Little Bay Line 2 is a 12.5 kv single-phase feeder that is approximately 6.2 kilometers long and extends from the Beachside substation to the community of Beachside. It serves approximately 100 customers. The existing insulators were installed when the lines were first constructed, have deteriorated over time, and need to be replaced to ensure a reliable source of power to Hydro s customers. 3.1 Age of Equipment or System Jackson s Arm L1, L2 and Hampden L1 were constructed in 1968 and Little Bay L2 was constructed in Newfoundland and Labrador Hydro Page 3

6 3.2 Major Work or Upgrades There have been no major upgrades on Jackson s Arm L1, Jackson s Arm L2, Hampden L1, or Little Bay L2 since the installation of the lines. 3.3 Anticipated Useful life The estimated service life of distribution feeders, for depreciation purposes, is 30 years. Newfoundland and Labrador Hydro Page 4

7 3.4 Maintenance History Table 1 shows the maintenance history for the Jackson's Arm, Hampden and Little Bay systems. Table 1 Jackson s Arm, Hampden and Little Bay Maintenance History Year Preventive Maintenance ($000) Jackson's Arm L1 and L2 Corrective Maintenance ($000) Total Maintenance ($ 000) Hampden L Little Bay L Newfoundland and Labrador Hydro Page 5

8 3.5 Outage Statistics Hydro tracks all distribution system outages using industry standard indexes, System Average Interruption Frequency Index (SAIFI) and System Average Interruption Duration Index (SAIDI). SAIDI and SAIFI are explained as follows: SAIDI - SAIFI - Indicates the system average interruption duration for customers served per year or the average length of time a customer is without power in the respective distribution system per year. Indicates the average of sustained interruptions per customer served per year or the average number of power outages a customer has experienced in the respective distribution system per year. Table 2 below lists the 2003 to 2007 average SAIFI and SAIDI data for the Jackson s Arm, Hampden and Little Bay systems, the 2003 to 2007 corporate values, and the latest CEA five-year average (2002 to 2006) for comparison. These reliability statistics are not the justification for this project. The insulators on these distributions lines were identified as needing replacement during the last line inspections in Table 2 SAIFI and SAIDI Five Year Average Indices ( ) All Causes Defective Equipment SAIFI SAIDI SAIFI SAIDI Jackson s Arm System Line Line Hampden System L Little Bay System Line Hydro Corporate CEA ( ) Newfoundland and Labrador Hydro Page 6

9 3.6 Industry Experience As explained in the introduction of this document, the utility industry has experienced widespread failure of CP and COB insulators. 3.7 Maintenance or Support Arrangements A complete inspection of the Jackson s Arm L1 and L2, Hampden L1, and Little Bay L2 feeders is performed every nine years to evaluate the condition of the lines. The last inspection was performed in The inspection is completed by Hydro personnel and any corrective maintenance required is reported, scheduled and performed. 3.8 Vendor Recommendations There are no specific vendor recommendations for this project. The existing pin type insulators will be replaced with Hydro's new standard 34.5kV post-type clamp top or 35kV Hendrix vise top and the suspension type insulator will be replaced with the new standard Polymer. 3.9 Availability of Replacement Parts Availability of replacement parts is not a consideration for this project Safety Performance Mechanical breakdown of the insulators is a safety issue for the line workers of Hydro. The insulators are prone to hairline cracking in the porcelain thus reducing their mechanical strength and increasing the chance of breaking during climbing activities by maintenance crews. This increases the potential for injuries to Hydro personnel. Newfoundland and Labrador Hydro Page 7

10 3.11 Environmental Performance Environmental performance is not a consideration for this project Operating Regime The Jackson s Arm, Hampden and Little Bay feeders are in continuous operation providing power to approximately 900 customers. Newfoundland and Labrador Hydro Page 8

11 4 JUSTIFICATION The insulators used on these lines have been failing throughout the industry, due to cement growth causing radial cracking and weakening of the insulators. Replacement of these insulators is essential to improve system reliability. 4.1 Net Present Value A Net Present Value calculation was not performed in this instance as only one viable alternative exists. 4.2 Levelized Cost of Energy This project will have no effect on the levelized cost of electricity. 4.3 Cost Benefit Analysis As there are no quantifiable benefits, a cost benefit analysis has not been performed. 4.4 Forecast Customer Growth Customer load growth does not affect this project. 4.5 Energy Efficient Benefits There are no energy efficiency benefits that can be attributed to this project. 4.6 Legislative or Regulatory Requirements There are no applicable legislative or regulatory requirements. Newfoundland and Labrador Hydro Page 9

12 4.7 Historical Information The table below lists insulator replacement projects in the last five years. Cost per unit has increased mainly due to increased contract labour costs. 4.8 Losses during Construction There are no anticipated energy losses during construction. Table 3 Five Year History of Insulator Replacement Projects - Cost per Unit Capital Actual Cost per Budget Expenditures Comments Year Units unit ($000) ($000) ($000) project , projects , projects , projects , projects 4.9 Status Quo The status quo is not an acceptable alternative. The existing equipment is in a deteriorated condition. Failure to replace the identified insulators could result in an increase in the number outages of varying durations to the customers in the area. Deteriorated insulators pose a significant risk to regulated operations personnel with the potential of failure during climbing activities by line workers Alternatives There are no viable alternatives to this upgrade work. Newfoundland and Labrador Hydro Page 10

13 5 CONCLUSION This project is required to ensure that a reliable energy supply is available for the customers served by the Jackson s Arm L1, L2, Hampden L1 and Little Bay L2 feeders. 5.1 Budget Estimate The estimate for these projects to be completed in 2009 is $874,200. Jackson s Arm and Hampden insulator replacements will be completed as one project. Table 4 Budget Estimate Jackson's Arm, Hampden and Little Bay Jackson s Arm Project Cost:($ x1,000) & Hampden Little Bay TOTAL Material Supply Labour Consultant Contract Work Other Direct Costs O/H, AFUDC & Escln Contingency TOTAL Newfoundland and Labrador Hydro Page 11

14 5.2 Project Schedule Table 5 Project Schedule Activity Milestone Initiation January 2009 Design Complete March 2009 Equipment Ordered April 2009 Installation Commences July 2009 Installation Complete August 2009 Project Closeout September 2009 Newfoundland and Labrador Hydro Page 12

A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES. Electrical. Mechanical. Civil. Protection & Control. System Planning

A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES. Electrical. Mechanical. Civil. Protection & Control. System Planning A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES Electrical vo1e.5s 0j 44, AMY., CK NI r. SIGNATURE Mechanical Civil Protection & Control t^ /DATE 1 o Transmission & Distribution AND Telecontrol

More information

A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES. Electrical. Mechanical. Civil. Protection & Control. Transmission & Distribution

A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES. Electrical. Mechanical. Civil. Protection & Control. Transmission & Distribution A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES Electrical.1_ UFSS#p A:_. DAVID/ IC, L re Mechanical Civil Protection & Control an LAND& 4^ Transmission & Distribution Telecontrol System Planning

More information

A REPORT TO. Electrical. Mechanical. Civil. Protection & Control. Transmission & Distribution. Telecontrol. System Planning

A REPORT TO. Electrical. Mechanical. Civil. Protection & Control. Transmission & Distribution. Telecontrol. System Planning A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES Electrical 4v ^c 0:01'1 S0^O c.. ^ '^ W E. G. PIERCY i^ x zoto/off/zq,.'ftrif4^#ft^^,' r Mechanical Civil Protection & Control Transmission &

More information

A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES. Electrical. Mechanical. Civil. Protection & Control. Transmission & Distribution

A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES. Electrical. Mechanical. Civil. Protection & Control. Transmission & Distribution A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES Electrical 4a >estro Mechanical re *.i Civil f ::^:s '1 E 1 t i^.l. al1.i 2 Or Protection & Control Transmission & Distribution Telecontrol System

More information

A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES. Electrical. Mechanical. Civil. Protection & Control. System Planning

A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES. Electrical. Mechanical. Civil. Protection & Control. System Planning A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES Electrical Mechanical Civil Protection & Control S1GNATLJL 2oü 4 "DAT Transmission & Distribution Telecontrol - System Planning OVERHAUL DIESEL

More information

A REPORT TO THE SoMo OF COMMISSIONERS OF PUBLIC UTILITIES. Electrical. Mechanical. Civil. System Planning. Overhaul Diesel Engines.

A REPORT TO THE SoMo OF COMMISSIONERS OF PUBLIC UTILITIES. Electrical. Mechanical. Civil. System Planning. Overhaul Diesel Engines. A REPORT TO THE SoMo OF COMMISSIONERS OF PUBLIC UTILITIES Electrical Mechanical ( Protection Civil & Control & Distribution System Planning Overhaul Diesel Engines Various Locations July 2012 newfoundland

More information

A REPORT TO. Electrical. Mechanical. Civil. Transmission & Distribution. System Planning REPLACE UNIT 2 STEAM SEAL REGULATOR

A REPORT TO. Electrical. Mechanical. Civil. Transmission & Distribution. System Planning REPLACE UNIT 2 STEAM SEAL REGULATOR A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES Electrical ^ ^^ t wiessio PBG n ^, wl I,,dn,w l.n Mechanical Civil T I.C LINS Protection & Control 41 41 4-01 "i"""11'"" ii. cl u Z`^ M 1K ' ^""

More information

A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES. Electrical. Mechanical. Civil. Protection & Control. Transmission & Distribution

A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES. Electrical. Mechanical. Civil. Protection & Control. Transmission & Distribution A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES Electrical Q^sss^ - Mechanical Civil SIONATURI Zo \r or o', Protection & Control Transmission & Distribution Telecontrol System Planning ARC FLASH

More information

A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES. Electrical. Mechanical. Civil. Protection & Control. - Transmission & Distribution

A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES. Electrical. Mechanical. Civil. Protection & Control. - Transmission & Distribution A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES Muskrat Falls Project - Exhibit 114 Page 1 of 47 Electrical Mechanical /''.., Civil Protection & Control - Transmission & Distribution Telecontrol

More information

EMERGING REQUIREMENTS

EMERGING REQUIREMENTS EB-00-0 Exhibit D Schedule Page of EMERGING REQUIREMENTS 0 EQUIPMENT STANDARDIZATION THESL plans, designs and constructs distribution system assets in accordance with approved standards. The standards

More information

OKLAHOMA CORPORATION COMMISSION REGULATED ELECTRIC UTILITIES 2018 RELIABILITY SCORECARD

OKLAHOMA CORPORATION COMMISSION REGULATED ELECTRIC UTILITIES 2018 RELIABILITY SCORECARD OKLAHOMA CORPORATION COMMISSION REGULATED ELECTRIC UTILITIES 2018 RELIABILITY SCORECARD June 1, 2018 Table of Contents 1.0 Introduction...3 2.0 Summary...3 3.0 Purpose...3 4.0 Definitions...4 5.0 Analysis...5

More information

OKLAHOMA CORPORATION COMMISSION REGULATED ELECTRIC UTILITIES 2017 RELIABILITY SCORECARD

OKLAHOMA CORPORATION COMMISSION REGULATED ELECTRIC UTILITIES 2017 RELIABILITY SCORECARD OKLAHOMA CORPORATION COMMISSION REGULATED ELECTRIC UTILITIES 2017 RELIABILITY SCORECARD May 1, 2017 Table of Contents 1.0 Introduction...3 2.0 Summary...3 3.0 Purpose...3 4.0 Definitions...4 5.0 Analysis...5

More information

Electricity Industry Code Minimum Service Standards & Guaranteed Service Levels Quarterly Report July September 2008

Electricity Industry Code Minimum Service Standards & Guaranteed Service Levels Quarterly Report July September 2008 Electricity Industry Code Minimum Service Standards & Guaranteed Service Levels Quarterly Report July September 2008 2 Table of Contents Administrative Data...3 Network Performance...3 Reliability Measures

More information

TEN YEAR PLANNING GUIDE SHASTA LAKE ELECTRIC UTILITY

TEN YEAR PLANNING GUIDE SHASTA LAKE ELECTRIC UTILITY TEN YEAR PLANNING GUIDE SHASTA LAKE ELECTRIC UTILITY 2011-2020 P+ PowerPlus Engineering A Department of STAR Energy Services, LLC TEN YEAR PLANNING GUIDE 2011-2020 SHASTA LAKE ELECTRIC UTILITY CITY OF

More information

ELECTRIC SYSTEM RELIABILITY ANNUAL REPORT

ELECTRIC SYSTEM RELIABILITY ANNUAL REPORT ELECTRIC SYSTEM RELIABILITY ANNUAL REPORT 2016 LIBERTY UTILITIES (CALPECO ELECTRIC) LLC (U 933 E) Prepared for California Public Utilities Commission July 15, 2017 EXECUTIVE SUMMARY The Electric System

More information

June Substation Refurbishment and Modernization. Prepared by: Substatiort Refu14bislrment and Modernization NP 2012 CBA

June Substation Refurbishment and Modernization. Prepared by: Substatiort Refu14bislrment and Modernization NP 2012 CBA 2.1 2012 Substatiort Refu14bislrment and Modernization NP 2012 CBA 2012 Substation Refurbishment and Modernization June 2011 Prepared by: Peter Feehan, P.Eng. A FORTIS COMPANY 2.1 2012 Substation Refurbishment

More information

P.O BOX 429, NUKU ALOFA, Tel: (676) Fax: (676)

P.O BOX 429, NUKU ALOFA, Tel: (676) Fax: (676) P.O BOX 429, NUKU ALOFA, Tel: (676) 27-390 Fax: (676) 23-047 Email: jvanbrink@tongapower.to 22 October 2012 Lord Dalgety Electricity Commission Tu atakilangi Nuku alofa Dear Lord Dalgety Compliance Reporting

More information

ATCO ELECTRIC LTD. (Transmission System) SERVICE QUALITY AND RELIABILITY PERFORMANCE, MEASURES AND INDICES Revision 0

ATCO ELECTRIC LTD. (Transmission System) SERVICE QUALITY AND RELIABILITY PERFORMANCE, MEASURES AND INDICES Revision 0 ATCO ELECTRIC LTD. (Transmission System) SERVICE QUALITY AND RELIABILITY PERFORMANCE, MEASURES AND INDICES 2018-04-24 - Revision 0 EUB Decision 2007-071 Board Direction 52 For questions or comments regarding

More information

PROJECTS $500K AND OVER FOR 2014

PROJECTS $500K AND OVER FOR 2014 Page of PROJECTS $00K AND OVER FOR 0 STANDARDIZATION PORTFOLIO Table : Standardization Projects Estimate Estimated Cost Project Title Number ($ Millions) Grounding Compliance Program. Porcelain Insulator

More information

We trust the foregoing is satisfactory. If you have any questions or comments, please contact the undersigned.

We trust the foregoing is satisfactory. If you have any questions or comments, please contact the undersigned. \ newfoundland labrador hydro a nalcor energy company Hydro Place. 00 Columbus Drive. P.O. Box 00. St. John's. NL Canada AB K t. 0..00 f. 0..00 www.nh.nl.ca December, 0 The Board of Commissioners of Public

More information

FORTISBC INC. PRUDENCY REVIEW KETTLE VALLEY SUBSTATION EXHIBIT A2 5

FORTISBC INC. PRUDENCY REVIEW KETTLE VALLEY SUBSTATION EXHIBIT A2 5 ALANNA GILLIS ACTING COMMISSION SECRETARY Commission.Secretary@bcuc.com web site: http://www.bcuc.com SIXTH FLOOR, 900 HOWE STREET, BOX 250 VANCOUVER, BC CANADA V6Z 2N3 TELEPHONE: (604) 660 4700 BC TOLL

More information

The Energy Queensland Group Notice of no non-network options

The Energy Queensland Group Notice of no non-network options The Energy Queensland Group Notice of no non-network options 24 September 2018 MCE Mount Crosby East Establish new substation to replace Mount Crosby Substation (SSMTC) Page 1 of 1 DISCLAIMER While care

More information

EH2741 Communication and Control in Electric Power Systems Lecture 3. Lars Nordström Course map

EH2741 Communication and Control in Electric Power Systems Lecture 3. Lars Nordström Course map EH2741 Communication and Control in Electric Power Systems Lecture 3 Lars Nordström larsn@ics.kth.se 1 Course map 2 1 Outline 1. Repeating Power System Control 2. Power System Topologies Transmission Grids

More information

DFO STATEMENT OF NEED REPORT

DFO STATEMENT OF NEED REPORT APPENDIX E DFO STATEMENT OF NEED REPORT Table of Contents 1.0 Executive Summary... 1 2.0 Description of the Area... 2 2.1 Geographic Study Area... 2 2.2 2016 System Configuration... 2 3.0 Area Loading

More information

Transmission and Distribution Substation Projects. Operating Company: Entergy Gulf States - Texas. Customer: PID # 202

Transmission and Distribution Substation Projects. Operating Company: Entergy Gulf States - Texas. Customer: PID # 202 Transmission and Distribution Substation Projects Operating Company: Entergy Gulf States - Texas Customer: PID # 202 Funding Project Number: F4PPGS0386 Facility Study for PID # 202: Study for 146 MW Revision

More information

Summer Reliability Assessment Report Electric Distribution Companies Perspective

Summer Reliability Assessment Report Electric Distribution Companies Perspective Energy Association of Pennsylvania Summer Reliability Assessment Report Electric Distribution Companies Perspective to the Pennsylvania Public Utility Commission June 9, 2011 Harrisburg, PA Terrance J.

More information

System Status Briefing

System Status Briefing System Status Briefing Phakamani Hadebe Interim Group Chief Executive 3 May 2018 Contents 1 Performance summary 2 Operational highlights 3 Generation performance 4 Distribution overview 5 Transmission

More information

2011 Substation Refurbishment and Modernization. June 2010

2011 Substation Refurbishment and Modernization. June 2010 Z,1 Substatiort Refurbish~nent and Modernization NP 2011 CBA 2011 Substation Refurbishment and Modernization June 2010 Prepared by: Peter Feehan, P.Eng. 2.1 2011 Substation Refurbishment and Modernization

More information

Net Metering Interconnection Requirements. Customer Generation Capacity Not Exceeding 100 kw. Date: Version: 1

Net Metering Interconnection Requirements. Customer Generation Capacity Not Exceeding 100 kw. Date: Version: 1 Net Metering Interconnection Requirements Customer Generation Capacity Not Exceeding 100 kw Date: 2017-07-01 Version: 1 Revision History Date Rev. Description July 01, 2017 1 Initial release Newfoundland

More information

Header. Reasonableness Test RT 007/11 Balhannah & Uraidla 66 / 33 kv Substations. RT Balhannah and Uraidla - Final Draft Page 1 of 8

Header. Reasonableness Test RT 007/11 Balhannah & Uraidla 66 / 33 kv Substations. RT Balhannah and Uraidla - Final Draft Page 1 of 8 Header Reasonableness Test RT 007/11 Balhannah & Uraidla 66 / 33 kv Substations RT 007-11 Balhannah and Uraidla - Final Draft Page 1 of 8 DISCLAIMER The purpose of this document is to inform customers,

More information

BEFORE THE PUBLIC SERVICE COMMISSION OF THE STATE OF UTAH ROCKY MOUNTAIN POWER. Exhibit Accompanying Rebuttal Testimony of Dana M.

BEFORE THE PUBLIC SERVICE COMMISSION OF THE STATE OF UTAH ROCKY MOUNTAIN POWER. Exhibit Accompanying Rebuttal Testimony of Dana M. Exhibit RMP (DMR-1R) BEFORE THE PUBLIC SERVICE COMMISSION OF THE STATE OF UTAH ROCKY MOUNTAIN POWER Exhibit Accompanying Rebuttal Testimony of Dana M. Ralston Lakeside U12 Combustion Turbine Exhaust Cylinder

More information

EMERGING REQUIREMENTS

EMERGING REQUIREMENTS Page of 0 EMERGING REQUIREMENTS EXTERNALLY INITIATED PLANT RELOCATIONS THESL distributes electricity to residential, commercial, and industrial customers via overhead and underground infrastructure. This

More information

An Inside Look at Electric Reliability 2016 Electric Reliability Report

An Inside Look at Electric Reliability 2016 Electric Reliability Report An Inside Look at Electric Reliability 2016 Electric Reliability Report Stockton, Bakersfield, California California November November 6, 2017 3, 2016 Welcome 2 David Meier Senior Manager, Stockton Division

More information

R.S.USHA CHIEF ENGINEER/ PLANNING & RC. Encl: Report and detailed estimate. To The Chief Engineer/D/Madurai Region

R.S.USHA CHIEF ENGINEER/ PLANNING & RC. Encl: Report and detailed estimate. To The Chief Engineer/D/Madurai Region TAMIL NADU GENERATION AND DISTRIBUTION CORPORATION LTD ABSTRACT --------------------------------------------------------------------------------------------------------- Electricity - Madurai Region -

More information

Reasonableness Test RT 015 /11 Salisbury Substation 11kV Feeders

Reasonableness Test RT 015 /11 Salisbury Substation 11kV Feeders Reasonableness Test RT 015 /11 Salisbury Substation 11kV Feeders Reasonableness Test: Salisbury Substation 11kV Feeders DISCLAIMER The purpose of this document is to inform customers, Interested Parties,

More information

2016 ELECTRIC SYSTEM RELIABILITY REPORT CITY OF ANAHEIM PUBLIC UTILITIES DEPARTMENT

2016 ELECTRIC SYSTEM RELIABILITY REPORT CITY OF ANAHEIM PUBLIC UTILITIES DEPARTMENT 2016 ELECTRIC SYSTEM RELIABILITY REPORT CITY OF ANAHEIM PUBLIC UTILITIES DEPARTMENT Contents Overview... 3 1.0 Electric System Reliability... 4 1.1 Annual Reliability Data with Utility Comparisons... 4

More information

SERVICES INNOVATION. Montreal Symposium March 29, Jack Simpson Director, Generation & Capacity Planning

SERVICES INNOVATION. Montreal Symposium March 29, Jack Simpson Director, Generation & Capacity Planning SERVICES INNOVATION Montreal Symposium March 29, 2017 Jack Simpson Director, Generation & Capacity Planning UTILITY LANDSCAPE IS CHANGING 2 Innovation CUSTOMER NEEDS ARE CHANGING GREATER RELIABILITY STORM

More information

PJM Sub Regional RTEP Committee Mid-Atlantic January 22, Esam Khadr, Sr. Director Electric Delivery Planning, PSE&G

PJM Sub Regional RTEP Committee Mid-Atlantic January 22, Esam Khadr, Sr. Director Electric Delivery Planning, PSE&G PJM Sub Regional RTEP Committee Mid-Atlantic January 22, 2016 Esam Khadr, Sr. Director Electric Delivery Planning, PSE&G PSE&G System Characteristics New Jersey utility characterized by densely populated

More information

A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES. Electrical. Mechanical. Civil. Transmission & Distribution. Telecontrol.

A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES. Electrical. Mechanical. Civil. Transmission & Distribution. Telecontrol. A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC UTILITIES Electrical Mechanical Civil Protecti on & Contro l MAV1PJ1 Transmission & Distribution Telecontrol System Planning Upgrade Circuit Breakers July

More information

ABB Automation & Power World: April 18-21, 2011 WPS System Planning. ABB Inc. April 21, 2011 Slide 1

ABB Automation & Power World: April 18-21, 2011 WPS System Planning. ABB Inc. April 21, 2011 Slide 1 ABB Automation & Power World: April 18-21, 2011 WPS-131-1 1 Reliability Based Transmission System Planning ABB Inc. April 21, 2011 Slide 1 WPS-131-1 Reliability Based Transmission System Planning Speaker

More information

ATTACHMENT - DFO STATEMENT OF NEED

ATTACHMENT - DFO STATEMENT OF NEED ATTACHMENT - DFO STATEMENT OF NEED Table of Contents Executive Summary... 3 1. Description of the Area... 5 1.1 Geographic Study Area... 5 1.2 Current System Configuration... 7 1.3 Distributed Generation...

More information

Quarterly Regulatory Report December 31, 2014 Appendix E Annual Report on Key Performance Indicators A REPORT TO 2014 ANNUAL REPORT

Quarterly Regulatory Report December 31, 2014 Appendix E Annual Report on Key Performance Indicators A REPORT TO 2014 ANNUAL REPORT 1\1LH 2013 Amended General Rate Application Information - 'kt ) p iled:p ''Gelb- Board Secretary: Quarterly Regulatory Report December 31, 2014 Appendix E A REPORT TO THE BOARD OF COMMISSIONERS OF PUBLIC

More information

Review of Electric Utility Hurricane Preparedness and Restoration Actions ORLANDO UTILITIES COMMISSION RESPONSES TO STAFF'S SECOND DATA REQUEST

Review of Electric Utility Hurricane Preparedness and Restoration Actions ORLANDO UTILITIES COMMISSION RESPONSES TO STAFF'S SECOND DATA REQUEST BEFORE THE FLORIDA PUBLIC SERVICE COMMISSION In re: Staff's Second Data Request on OUC' s Review of Electric Utility Hurricane Preparedness and Restoration Actions Docket No. 20170215-EU Filed: January

More information

Net Metering Interconnection Requirements

Net Metering Interconnection Requirements Net Metering Interconnection Requirements Customer Generation Capacity Not Exceeding 100 kw Date: 2017-07-01 Version: 1 Revision History Date Rev. Description July 1, 2017 1 Initial Release Newfoundland

More information

Out of Sight Out of Mind Revisited. EEI Transmission, Distribution, & Metering Conference October 14, 2009 Ken Hall Hall Energy Consulting

Out of Sight Out of Mind Revisited. EEI Transmission, Distribution, & Metering Conference October 14, 2009 Ken Hall Hall Energy Consulting Out of Sight Out of Mind Revisited EEI Transmission, Distribution, & Metering Conference October 14, 2009 Ken Hall Hall Energy Consulting 1 Presentation Outline Customer Expectations Storms and Outages:

More information

TORONTO TRANSIT COMMISSION REPORT NO.

TORONTO TRANSIT COMMISSION REPORT NO. Form Revised: February 2005 TORONTO TRANSIT COMMISSION REPORT NO. MEETING DATE: September 27, 2012 SUBJECT: NOTICE OF AWARD PROCUREMENT AUTHORIZATION - ARTICULATED BUSES INFORMATION ITEM RECOMMENDATION

More information

Terry Blackwell Page 1 of 5. Education North Carolina State University BS, Electrical Engineering Power Systems emphasis

Terry Blackwell Page 1 of 5. Education North Carolina State University BS, Electrical Engineering Power Systems emphasis Terry Blackwell Page 1 of 5 Education 1977 North Carolina State University BS, Electrical Engineering Power Systems emphasis Professional Qualifications 1977 PE-Professional Engineer Business Experience

More information

Sub Regional RTEP Committee Western Region ATSI

Sub Regional RTEP Committee Western Region ATSI Sub Regional RTEP Committee Western Region ATSI February 20, 2019 1 ATSI Needs Stakeholders must submit any comments within 10 days of this meeting in order to provide time necessary to consider these

More information

2016 Annual Performance Report Energy Distributors

2016 Annual Performance Report Energy Distributors 2016 Annual Performance Report Energy Distributors April 2017 2016 Annual Performance Report Energy Distributors Economic Regulation Authority 2017 This document is available from the Economic Regulation

More information

High Lonesome Mesa 100 MW Wind Generation Project (OASIS #IA-PNM ) Interconnection Facility Study. Final Report November 2, 2007

High Lonesome Mesa 100 MW Wind Generation Project (OASIS #IA-PNM ) Interconnection Facility Study. Final Report November 2, 2007 High Lonesome Mesa 100 MW Wind Generation Project (OASIS #IA-PNM-2006-02) Interconnection Facility Study Final Report November 2, 2007 Prepared by: Public Service Company of New Mexico Electric Services

More information

B. E. S. & T. UNDERTAKING

B. E. S. & T. UNDERTAKING Standards of Perfomrance Level by the Distribution Licensee Format for Quarterly Return to be submitted to the Commission by the Distribution Licensee Annexure -I Sr. SOP Regulation of Cases/compaints

More information

FINAL FACILITY STUDY. 230/69/13.8 kv Transformer Addition(s) at Badwater Substation 2009 T1. September 10, 2010

FINAL FACILITY STUDY. 230/69/13.8 kv Transformer Addition(s) at Badwater Substation 2009 T1. September 10, 2010 FINAL FACILITY STUDY 230/69/13.8 kv Transformer Addition(s) at Badwater Substation 2009 T1 September 10, 2010 I. Introduction This is a revised facility study performed for Transmission Queue Request 2009

More information

100 MW Wind Generation Project

100 MW Wind Generation Project A subsidiary of Pinnacle West Capital Corporation 100 MW Wind Generation Project CUSTOMER FINAL Feasibility Study Results By Transmission Planning, APS December 21, 2007 Executive Summary This Feasibility

More information

CI Number: ACE CI Page 1 of 9. Title: Metro Voltage Support - Add Capacitor Bank

CI Number: ACE CI Page 1 of 9. Title: Metro Voltage Support - Add Capacitor Bank 216 ACE CI 46587 Page 1 of 9 CI Number: 46587 Title: Metro Voltage Support Add Capacitor Bank Start Date: 215/6 InService Date: 216/12 Final Cost Date: 217/6 Function: Transmission Forecast Amount: 3,373,511

More information

Director Corporate Services & Board Secretary. Newfoundland and Labrador Hydro 2015 Capital Budget Application

Director Corporate Services & Board Secretary. Newfoundland and Labrador Hydro 2015 Capital Budget Application \ I newfoundland labrador k_hy dro a nalcor energy company Hydro Place. 500 Columbus Drive. P.O. Box 12400. St. John's. NL Canada A1B 4K7 t. 709.737.1400 f. 709.737.1800 www.n1h.nl.ca September 12, 2014

More information

Expected Energy Not Served (EENS) Study for Vancouver Island Transmission Reinforcement Project (Part I: Reliability Improvements due to VITR)

Expected Energy Not Served (EENS) Study for Vancouver Island Transmission Reinforcement Project (Part I: Reliability Improvements due to VITR) Report-BCTC-R009A Expected Energy Not Served (EENS) Study for Vancouver Island Transmission Reinforcement Project (Part I: Reliability Improvements due to VITR) December 8, 2005 Prepared by Wenyuan Li

More information

Emera Maine Representative: Jeffrey Fenn, P.E., SGC Engineering LLC

Emera Maine Representative: Jeffrey Fenn, P.E., SGC Engineering LLC OCTOBER 22, 2015 Emera Maine s Local System Plan Bangor Hydro District Needs Assessment/Potential Solutions Local Planning Advisory Committee Meeting Emera Maine Representative: Jeffrey Fenn, P.E., SGC

More information

TARIFF DECISION FOR SASOL OIL (PTY) LTD S SECUNDA TO NATREF INTEGRATED (SNI) PIPELINE

TARIFF DECISION FOR SASOL OIL (PTY) LTD S SECUNDA TO NATREF INTEGRATED (SNI) PIPELINE TARIFF DECISION FOR SASOL OIL (PTY) LTD S SECUNDA TO NATREF INTEGRATED (SNI) PIPELINE 10 MAY 2018 Page 1 of 19 TABLE OF CONTENTS Introduction... 6 Applicable Law... 6 The Methodology... 6 Decision-Making

More information

A Guide to the medium General Service. BC Hydro Last Updated: February 24, 2012

A Guide to the medium General Service. BC Hydro Last Updated: February 24, 2012 A Guide to the medium General Service Conservation Rate BC Hydro Last Updated: February 24, 2012 Executive summary The way Medium General Service (MGS) accounts pay for electricity is changing. MGS is

More information

Welcome. Liberty Utilities Reliability Reporting Workshop. October 3 & 6, 2017

Welcome. Liberty Utilities Reliability Reporting Workshop. October 3 & 6, 2017 Welcome Liberty Utilities Reliability Reporting Workshop October 3 & 6, 2017 1 Agenda Purpose of Workshops System Overview Key Utility Initiatives Reliability Performance Plans for Reliability Improvements

More information

Building a 21 st Century Electric Grid. February 23, 2018

Building a 21 st Century Electric Grid. February 23, 2018 Building a 21 st Century Electric Grid February 23, 2018 1 DTE strives to provide customers with a 21 st century electric grid that is safe, highly reliable, affordable and accessible 2 Our investment

More information

KEY PERFORMANCE INDICATORS YUKON ENERGY CORPORATION 2014 ANNUAL REPORT

KEY PERFORMANCE INDICATORS YUKON ENERGY CORPORATION 2014 ANNUAL REPORT KEY PERFORMANCE INDICATORS YUKON ENERGY CORPORATION 2014 ANNUAL REPORT TABLE OF CONTENTS Page Executive Summary 2 Operational Performance 4 Reliability Performance 8 Environmental Performance 13 Health

More information

Dunvegan Hydroelectric Project. For Glacier Power Limited. Preliminary Interconnection Study

Dunvegan Hydroelectric Project. For Glacier Power Limited. Preliminary Interconnection Study ` Dunvegan Hydroelectric Project For Glacier Power Limited Preliminary Interconnection Study Prepared by Pung Toy, P. Eng. and Ata Rehman, P. Eng. September 24, 2004 Table of Contents Table of Contents...

More information

Circuit Reliability Review

Circuit Reliability Review Circuit Reliability Review Laguna Beach January 2018 Building a Smarter Grid for Southern California Southern California Edison is developing an electric grid to support California s transition to a clean

More information

Rate Schedules. Effective 1/1/2019

Rate Schedules. Effective 1/1/2019 Rate Schedules 2019 Effective 1/1/2019 SUMMARY OF RATE SCHEDULES REVISIONS FOR RATES EFFECTIVE JANUARY 1, 2019 (1) Rate component changes for Residential and Heating Service rate schedules. (2) General

More information

Appendix G Examples and Recommended Methods

Appendix G Examples and Recommended Methods Reporting Outages to the Generating Availability Data System (GADS) Introduction The examples in this appendix illustrate the reporting of outages and deratings to GADS. They are based on a fictional 600

More information

Final Project Assessment Report (FPAR)

Final Project Assessment Report (FPAR) Final Project Assessment Report (FPAR) Kangaroo Island Submarine Cable 23 December 2016 SA Power Networks www.sapowernetworks.com.au Disclaimer This Final Project Assessment Report (FPAR) has been prepared

More information

SECTION 9: ELECTRICAL POWER DISTRIBUTION. ESE 470 Energy Distribution Systems

SECTION 9: ELECTRICAL POWER DISTRIBUTION. ESE 470 Energy Distribution Systems SECTION 9: ELECTRICAL POWER DISTRIBUTION ESE 470 Energy Distribution Systems 2 Introduction The Electrical Grid 3 Three main components to the electrical grid Generation ESE 450 Transmission Transmission

More information

2016 Load & Capacity Data Report

2016 Load & Capacity Data Report Caution and Disclaimer The contents of these materials are for information purposes and are provided as is without representation or warranty of any kind, including without limitation, accuracy, completeness

More information

TRANSMISSION PLANNING CRITERIA

TRANSMISSION PLANNING CRITERIA CONSOLIDATED EDISON COMPANY OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003-3502 Effective Date: TRANSMISSION PLANNING CRITERIA PURPOSE This specification describes Con Edison s Criteria for assessing

More information

Fund and 2015 revenue bonds Est. State and Local Taxes: $2,810,000

Fund and 2015 revenue bonds Est. State and Local Taxes: $2,810,000 PORT OF SEATTLE MEMORANDUM COMMISSION AGENDA Item No. 6b ACTION ITEM Date of Meeting August 4, 2015 DATE: TO: FROM: Dave Soike, Director, Aviation Facilities and Capital Programs Wayne Grotheer, Director,

More information

Construction Sector Indices

Construction Sector Indices STATISTICAL RELEASE UGANDA BUREAU OF STATISTICS January to April 212 Construction Sector Indices HIGHLIGHTS Annual Changes show that the prices for the Whole Construction Sector (covering material prices,

More information

STAFF REPORT ACTION REQUIRED

STAFF REPORT ACTION REQUIRED Insert TTC logo here STAFF REPORT ACTION REQUIRED Overhaul of 30 Canadian Light Rail Vehicles (CLRV) and Maintaining non-overhauled Streetcars in a State of Good Repair Date: March 23, 2016 To: From: TTC

More information

Regional Transit Extension Studies. Hampton Roads Transportation Planning Organization Passenger Rail Task Force Meeting December 17, 2013

Regional Transit Extension Studies. Hampton Roads Transportation Planning Organization Passenger Rail Task Force Meeting December 17, 2013 Regional Transit Extension Studies Hampton Roads Transportation Planning Organization Passenger Rail Task Force Meeting December 17, 2013 Topics Virginia Beach Transit Extension Study (VBTES) Naval Station

More information

POWER SYSTEM OPERATING INCIDENT REPORT TRIP OF 220 KV C BUSBAR AT GORDON POWER STATION ON 26 NOVEMBER 2011

POWER SYSTEM OPERATING INCIDENT REPORT TRIP OF 220 KV C BUSBAR AT GORDON POWER STATION ON 26 NOVEMBER 2011 POWER SYSTEM OPERATING INCIDENT REPORT TRIP OF 220 KV C BUSBAR AT GORDON POWER STATION ON 26 NOVEMBER 2011 PREPARED BY: Electricity System Operations Planning and Performance DATE: 22 March 2012 FINAL

More information

3 Award of Contracts for the Supply of Vehicle Tires

3 Award of Contracts for the Supply of Vehicle Tires Clause 3 in Report No. 9 of Committee of the Whole was adopted, without amendment, by the Council of The Regional Municipality of York at its meeting held on May 21, 2015. 3 Award of Contracts for the

More information

OCTOBER 17, Emera Maine Representative: Jeffrey Fenn, P.E., LR/SGC Engineering LLC

OCTOBER 17, Emera Maine Representative: Jeffrey Fenn, P.E., LR/SGC Engineering LLC OCTOBER 17, 2018 Emera Maine s Local System Plan Bangor Hydro District Needs Assessment/Potential Solutions Local Planning Advisory Committee Meeting Emera Maine Representative: Jeffrey Fenn, P.E., LR/SGC

More information

PRESS RELEASE June 25, 2004

PRESS RELEASE June 25, 2004 120 Torbay Road, Suite E-210, P.O. Box 21040, St. John=s, NL. A1A 5B2 Tel: (709) 726-8600 - Fax: (709) 726-9604 PRESS RELEASE June 25, 2004 The Newfoundland and Labrador Board of Commissioners of Public

More information

Pump Station 7 Improvements

Pump Station 7 Improvements Project Business Case ID: C04 2/18/2017 Pump Station 7 Project Purpose: The purpose of this project is to ensure that Pump Station 7 continues to operate in an efficient and effective manner following

More information

PJM Generation Interconnection Request Queue #A55 Lakewood 230kV Facilities Study Report

PJM Generation Interconnection Request Queue #A55 Lakewood 230kV Facilities Study Report PJM Generation Interconnection Request Queue #A55 Lakewood 230kV Facilities Study Report 155697 September 2001 Table of Contents DESCRIPTION PAGE 1.0 Introduction 3 2.0 Description of Facilities Included

More information

STAFF REPORT ACTION REQUIRED

STAFF REPORT ACTION REQUIRED STAFF REPORT ACTION REQUIRED Procurement Authorization Amendment Purchase of 18 Forty Foot Low Floor Clean Diesel City Buses Date: July 29, 215 To: From: TTC Board Chief Executive Officer Summary This

More information

Emera Maine Representative: Jeffrey Fenn, P.E., SGC Engineering LLC

Emera Maine Representative: Jeffrey Fenn, P.E., SGC Engineering LLC OCTOBER 22, 2014 Emera Maine s Local System Plan Bangor Hydro District Needs Assessment/Potential Solutions Local Planning Advisory Committee Meeting E M i R t ti Emera Maine Representative: Jeffrey Fenn,

More information

Decision on Merced Irrigation District Transition Agreement

Decision on Merced Irrigation District Transition Agreement California Independent System Operator Corporation Memorandum To: ISO Board of Governors From: Karen Edson, Vice President Policy & Client Services Date: March 13, 2013 Re: Decision on Merced Irrigation

More information

CITY OF ELK GROVE CITY COUNCIL STAFF REPORT

CITY OF ELK GROVE CITY COUNCIL STAFF REPORT CITY OF ELK GROVE CITY COUNCIL STAFF REPORT AGENDA ITEM NO. 10.2 AGENDA TITLE: Receive Update on Citywide Light Emitting Diode (LED) Streetlight Conversion and Provide Guidance on Next Steps MEETING DATE:

More information

Form Revised: February 2005 TORONTO TRANSIT COMMISSION REPORT NO. MEETING DATE: August 30, SUBJECT: Scarborough Rt Strategic Plan

Form Revised: February 2005 TORONTO TRANSIT COMMISSION REPORT NO. MEETING DATE: August 30, SUBJECT: Scarborough Rt Strategic Plan Form Revised: February 2005 TORONTO TRANSIT COMMISSION REPORT NO. MEETING DATE: August 30, 2006 SUBJECT: Scarborough Rt Strategic Plan RECOMMENDATIONS It is recommended that the Commission: 1. Endorse

More information

ERCOT Overview. Paul Wattles Senior Analyst, Market Design & Development. Solar Energy Industries Association July 11, 2012

ERCOT Overview. Paul Wattles Senior Analyst, Market Design & Development. Solar Energy Industries Association July 11, 2012 ERCOT Overview Paul Wattles Senior Analyst, Market Design & Development Solar Energy Industries Association History of Electric Reliability Council of Texas, Inc. 1941 Utilities band together to aid war

More information

Operating Results Q Asian Insulators Public Company Limited

Operating Results Q Asian Insulators Public Company Limited Operating Results Q2-2010 Asian Insulators Public Company Limited 254 Seri Thai Road, Kannayaow, Bangkok 10230 Thailand http://www.asianinsulators.com Tel. (66) 0-2517-1451 Fax. (66) 0-2517-1465 E-mail

More information

Metal Bulletin Conference

Metal Bulletin Conference Sakura Ferroalloys Project Metal Bulletin Conference Singapore, 01 st April 2015 P R E S E N T E D BY: T I A A N VA N A S W EG E N D I R E C TO R A S S M A N G C H A I R M A N S A KU R A F E R R OALLOY

More information

PHILIPPINE DISTRIBUTION CODE 2017 EDITION

PHILIPPINE DISTRIBUTION CODE 2017 EDITION PHILIPPINE DISTRIBUTION CODE 2017 EDITION PDC 2017- Background Revised the PDC 2001 Starts of revision in 2010 April 18 and 24, 2012 conducted a series of expository presentation for Visayas and Mindanao

More information

Florida Public Service Commission 2011 Hurricane Season Preparation Briefing

Florida Public Service Commission 2011 Hurricane Season Preparation Briefing Florida Public Service Commission 2011 Hurricane Season Preparation Briefing OUC The Reliable One May 4, 2011 Byron Knibbs Vice President, Sustainable Services (407) 434-2194 bknibbs@ouc.com 1 Florida

More information

Rates and Rules Applicable to Electric Service in all Territory Served by Rocky Mountain Power in the State of Wyoming

Rates and Rules Applicable to Electric Service in all Territory Served by Rocky Mountain Power in the State of Wyoming First Revision of Sheet No. A-1 Canceling Original Sheet No. A-1 P.S.C. No. 16 Title Page Rates and Rules Applicable to Electric Service in all Territory Served by Rocky Mountain Power in the State of

More information

Utility Distribution Planning 101

Utility Distribution Planning 101 Utility Distribution Planning 101 Michael Coddington, National Renewable Energy Laboratory Webinar for National Association of State Utility Consumer Advocates June 5, 2018 1 Webinar Overview Overview

More information

Rogers Road to Clubhouse 230kV New Transmission Line April 1, 2016

Rogers Road to Clubhouse 230kV New Transmission Line April 1, 2016 New Transmission Line April 1, 2016 The enclosed information is proprietary to PSE&G and is provided solely for your use. It should not be copied, reproduced, or shared with others without PSE&G s prior

More information

Government of Sierra Leone. Directions in. Energy. Opportunities for Investment and Partnerships

Government of Sierra Leone. Directions in. Energy. Opportunities for Investment and Partnerships Government of Sierra Leone Directions in Energy Opportunities for Investment and Partnerships Background to Energy Transmission and Distribution In 2011, as part of the reforms in the energy sector the

More information

Docket No EI Date: May 22, 2014

Docket No EI Date: May 22, 2014 Docket No. 140032-EI Big Bend Units 1 through 4 are pulverized coal steam units that currently use distillate oil 2 for start-ups and for flame stabilization. The Company seeks to use natural gas in place

More information

Distribution lines Overload Control to Increase Reliability and Power Loss Reduction

Distribution lines Overload Control to Increase Reliability and Power Loss Reduction Distribution lines Overload Control to Increase Reliability and Power Loss Reduction SHRIRANG KARANDIKAR Vice President (Business Development) Kalpataru Power Transmission Ltd. Santacruz (East), Mumbai-400055

More information

Signs of recovery in the Russian construction market

Signs of recovery in the Russian construction market Milena Bernardi - m.bernardi@tiledizioni.it Signs of recovery in the Russian construction market Fig. 1 - Construction output in Russia (y-o-y % change) Despite a slowdown with respect to the period April-

More information

COMPARISON OF ELECTRICITY PRICES IN MAJOR NORTH AMERICAN CITIES. Rates in effect April 1, 2011

COMPARISON OF ELECTRICITY PRICES IN MAJOR NORTH AMERICAN CITIES. Rates in effect April 1, 2011 COMPARISON OF ELECTRICITY PRICES IN MAJOR NORTH AMERICAN CITIES Rates in effect April 1, 2011 Amended November 2011 TABLE OF CONTENTS INTRODUCTION 3 METHOD 7 HIGHLIGHTS 9 Residential Customers 9 Small-Power

More information

15 Nelson-Marlborough Regional Plan

15 Nelson-Marlborough Regional Plan 15 Nelson-Marlborough Regional Plan 15.1 Regional overview 15.2 Nelson-Marlborough transmission system 15.3 Nelson-Marlborough demand 15.4 Nelson-Marlborough generation 15.5 Nelson-Marlborough significant

More information

Pike County Light & Power Company Summer Reliability Outlook

Pike County Light & Power Company Summer Reliability Outlook Pike County Light & Power Company 2013 Summer Reliability Outlook June 28, 2013 System Overview Pike County Light & Power Company ( PCL&P or the Company ) is an electric distribution company ( EDC ) which

More information