High-Impedance Differential Applications With Mismatched CTs
|
|
- Sydney Fletcher
- 5 years ago
- Views:
Transcription
1 High-Impedance Differential Applications With Mismatched CTs Russ Franklin, Alliant Energy Hossein Nabi-Bidhendi, ABB Inc. Michael J. Thompson and Héctor J. Altuve, Schweitzer Engineering Laboratories, Inc Alliant, ABB, and SEL Introduction High-impedance differential (87Z) is desirable for many reasons It requires matched ratio CTs Often, this is a limitation Options for using mismatched CTs have compromises Alliant set out to validate easiest option 87Z 2,000 W MOV
2 Outline Why mismatched CTs? 87Z fundamentals Summary of options High-current lab testing Conclusions Regulated Utility Profile 2016 Data IPL WPL Total Electric customers 489, , ,318 Wisconsin WPL Electric sales (000s MWh) 15,970 13,868 29,838 Summer peak demand (MW) 2,996 2,681 Iowa IPL Gas customers 224, , ,758 Gas sales (000s Dths) 63,388 61, ,228 Operating revenues (millions) $1,820 $1,459 $3,320 2
3 10 Years Estimated Capital Expenditures Updated November $6.8 billion $4.5 billion Other Other Gas Generation Gas Distribution Renewable Generation Gas Distribution Other Generation Gas Generation Electric Distribution Other Generation Electric Distribution Electric Distribution Strategy Grid Enhancements and Customer Need Reliability Distributed generation/renewable integration Integrate planning with generation and transmission Increase remote monitoring and control Eliminate lower voltage systems Increase life extension and rebuild rate Resiliency improvements including underground/hardening Customer Focused Customer data availability Utility as trusted advisor for technical solutions Advanced metering infrastructure in Iowa 3
4 Why 87Z? High performance Virtually no limit to number of branch circuits Simple CT wiring Extremely simple settings calculations Multiple owners Standardization Outage constraints Budget constraints Equipment failure Upgrades Why Mismatched CTs? 4
5 87Z Fundamentals Summing Junction 87Z 2,000 W 86a MOV 87 CT1 CT2 V S CT3 CT Saturated CT Path Differential Path Simple Settings Calculations Simplifying Assumption Complete Saturation I CT123 I CT4 I CT123 I CT4 CT 123 V CT123 V JCT V CT4 CT 4 V CT123 V JCT V CT4 CT 123 CT 4 V+ V+ Set point 0 VCT123 V JCT V CT4 0 V CT123 V JCT V CT4 V Summing Junction Voltage No Saturation V Improved margin Summing Junction Voltage Complete Saturation 5
6 Internal Fault Relay sees same signal regardless of fault current Rectangular waveform Height = MOV clamping voltage Width C Class (Iron) Volts Cycles Operate Quantity (Voltage) for Internal Fault Rectangular pulse ½ cycle COS filter Magnitude C100 = Pulse too narrow C 4 V C4 8 V C800 > 800 V 6
7 Tapping a CT to Match Ratios X1 X2 X3 X4 X5 240T 160T R W GND Turn-to-turn and turn-to-core voltage stress Lead-to-lead and lead-to-ground voltage stress Conductors in conduit Terminal block in breaker cabinet Wiring below this is protected by MOV To summing cabinet and relay panel 400T CT tapped at 240T 1.5 kv clamping voltage Insulation stress 2.5 kv Peak across winding 1.5 kv Peak to ground Consequences Damage Failure to trip Options to Mitigate Risk of Insulation Failure Apply MOV across the full winding Use tapped CT or auxiliary CT as autotransformer Change the relay Lower MOV clamping voltage Percentage restrained All options have drawbacks 7
8 Assessing Risk of Simply Tapping the CT Examine standard IEEE C57.13 Applied voltage routine test (2.5 kv Peak ) Induced voltage routine test (2.263 kv Peak ) Interturn overvoltage type test (3.5 kv Peak ) Check routine HiPot test levels on breaker Check with manufacturer Test CT under realistic conditions Utility Source Standard CT Test CT LeCroy Oscilloscope X1 X2 X1 X2 X3 X4 X5 GND High-Current Laboratory Tests Meter 87Z 8
9 High-Current Laboratory Tests 3 new CTs 5 shots minimum for each 12-cycle duration Retest afterward Voltage Waveforms 9
10 Voltage Waveforms X5 X5 I Dischg. CT X3-X5 X3 V X3-X5 I Sec X3 I Sec Equivalent Circuit CT X1-X3 V X1-X3 X1 X1 10
11 Conclusions 87Z is a popular scheme It requires matched ratio CTs Methods to accommodate mismatch have drawbacks Simplest method is to tap the CT No complex calculations Risk of insulation failure Manufacturers unwilling to certify their CTs Conclusions Alliant decided to assess risk in high-current laboratory Three C T CTs One 87Z relay with 1 kv clamping voltage At least five shots each CTs showed no sign of degradation after the tests Mixing 240T and 400T CTs has acceptable risk This combination is not necessarily worst case 11
A Cost Benefit Analysis of Faster Transmission System Protection Schemes and Ground Grid Design
A Cost Benefit Analysis of Faster Transmission System Protection Schemes and Ground Grid Design Presented at the 2018 Transmission and Substation Design and Operation Symposium Revision presented at the
More informationCost Benefit Analysis of Faster Transmission System Protection Systems
Cost Benefit Analysis of Faster Transmission System Protection Systems Presented at the 71st Annual Conference for Protective Engineers Brian Ehsani, Black & Veatch Jason Hulme, Black & Veatch Abstract
More informationNew 115 kv Disconnect Switches at Bloomsburg MTS
115 kv Line tap from C9 to Bloomsburg MTS & New Bus Tie Switch CAA ID Number: 2007-EX353 Final Draft ASSESSMENT SUMMARY 1. GENERAL DESCRIPTION Norfolk TS and Bloomsburg MTS are supplied by a single 115
More informationGalapagos San Cristobal Wind Project. VOLT/VAR Optimization Report. Prepared by the General Secretariat
Galapagos San Cristobal Wind Project VOLT/VAR Optimization Report Prepared by the General Secretariat May 2015 Foreword The GSEP 2.4 MW Wind Park and its Hybrid control system was commissioned in October
More informationTransmission and Distribution Substation Projects. Operating Company: Entergy Gulf States - Texas. Customer: PID # 202
Transmission and Distribution Substation Projects Operating Company: Entergy Gulf States - Texas Customer: PID # 202 Funding Project Number: F4PPGS0386 Facility Study for PID # 202: Study for 146 MW Revision
More informationDynamic Control of Grid Assets
Dynamic Control of Grid Assets Panel on Power Electronics in the Smart Grid Prof Deepak Divan Associate Director, Strategic Energy Institute Director, Intelligent Power Infrastructure Consortium School
More informationATTACHMENT - DFO STATEMENT OF NEED
ATTACHMENT - DFO STATEMENT OF NEED Table of Contents Executive Summary... 3 1. Description of the Area... 5 1.1 Geographic Study Area... 5 1.2 Current System Configuration... 7 1.3 Distributed Generation...
More informationELECTRIC SERVICE RULES DISTRIBUTED GENERATION Issued Jan 2016
DISTRIBUTED GENERATION CHAPTER 5 500. SCOPE This chapter includes distributed or customer-owned generation connected in parallel and operating with Alliant Energy s electric distribution system. For all
More informationInterconnection Feasibility Study Report GIP-226-FEAS-R3
Interconnection Feasibility Study Report GIP-226-FEAS-R3 System Interconnection Request #226 70 MW Wind Generating Facility Kings County (L-6013) 2010 07 21 Control Centre Operations Nova Scotia Power
More informationTEN YEAR PLANNING GUIDE SHASTA LAKE ELECTRIC UTILITY
TEN YEAR PLANNING GUIDE SHASTA LAKE ELECTRIC UTILITY 2011-2020 P+ PowerPlus Engineering A Department of STAR Energy Services, LLC TEN YEAR PLANNING GUIDE 2011-2020 SHASTA LAKE ELECTRIC UTILITY CITY OF
More informationMEDIUM VOLTAGE PRODUCTS. Fault Current Limiters I S. -limiter and FC-Protector The worldʼs fastest switching devices
MEDIUM VOLTAGE PRODUCTS The worldʼs fastest switching devices 2 FAULT CURRENT LIMITERS THE WORLDʼ S FASTETST SWITCHING DEVICES The worldʼs fastest switching devices ABBʼs fault current limiters disconnect
More informationGenerator Interconnection Facilities Study For SCE&G Two Combustion Turbine Generators at Hagood
Generator Interconnection Facilities Study For SCE&G Two Combustion Turbine Generators at Hagood Prepared for: SCE&G Fossil/Hydro June 30, 2008 Prepared by: SCE&G Transmission Planning Table of Contents
More informationFinal Draft Report. Assessment Summary. Hydro One Networks Inc. Longlac TS: Refurbish 115/44 kv, 25/33/ General Description
Final Draft Report Assessment Summary Hydro One Networks Inc. : Refurbish 115/44 kv, 25/33/42 MVA DESN Station CAA ID Number: 2007-EX360 1.0 General Description Hydro One is proposing to replace the existing
More informationGuidelines for Modernizing Existing Electrical Switchgear in LV and MV Networks
Guidelines for Modernizing Existing Electrical Switchgear in LV and MV Networks by Georges Barbarin Executive summary Aging electrical switchgear infrastructure is a threat to the reliability of power
More information3. OPERATION 2.1. RESTRAINT CIRCUIT 2.6. INDICATING CIRCUIT 2.2. OPERATING CIRCUIT 2.7. SURGE PROTECTION CIRCUIT 2.3.
41-348.1H Type SA-1 2.1. RESTRAINT CIRCUIT The restraint circuit of each phase consists of a center-tapped transformer, a resistor, and a full wave rectifier bridge. The outputs of all the rectifiers are
More informationSmall Generator Interconnection Program Interconnection Technical Requirements
General Program Information What is the purpose of the PGE Small Generator Interconnection Program? How do I initiate a distribution interconnection request for my project? The purpose of our Small Generator
More informationNet Metering Interconnection Requirements
Net Metering Interconnection Requirements Customer Generation Capacity Not Exceeding 100 kw Date: 2017-07-01 Version: 1 Revision History Date Rev. Description July 1, 2017 1 Initial Release Newfoundland
More informationDynamic Line Rating as a Means to Enhance Transmission Grid Resilience
Dynamic Line Rating as a Means to Enhance Transmission Grid Resilience McCall, J. Goodwin, T. Lindsey Manufacturing Tip Goodwin Consulting LLC USA Canada CIGRE US National Committee 2015 Grid of the Future
More informationNet Metering Interconnection Requirements. Customer Generation Capacity Not Exceeding 100 kw. Date: Version: 1
Net Metering Interconnection Requirements Customer Generation Capacity Not Exceeding 100 kw Date: 2017-07-01 Version: 1 Revision History Date Rev. Description July 01, 2017 1 Initial release Newfoundland
More informationService Requested 150 MW, Firm. Table ES.1: Summary Details for TSR #
Executive Summary Firm point to point transmission service has been requested by Transmission Service Request (TSR) #75669514, under the SaskPower Open Access Transmission Tariff (OATT). The TSR consists
More informationUpdated Transmission Expansion Plan for the Puget Sound Area to Support Winter South-to-North Transfers
Updated Transmission Expansion Plan for the Puget Sound Area to Support Winter South-to-North Transfers Puget Sound Area Study Team Bonneville Power Administration, Puget Sound Energy, Seattle City Light,
More informationEMERGING REQUIREMENTS
EB-00-0 Exhibit D Schedule Page of EMERGING REQUIREMENTS 0 EQUIPMENT STANDARDIZATION THESL plans, designs and constructs distribution system assets in accordance with approved standards. The standards
More informationInterconnection System Impact Study Report Request # GI
Executive Summary Interconnection System Impact Study Report Request # GI-2008-23 34 MW Solar Generation Ranch at Hartsel, Colorado Public Service Company of Colorado Transmission Planning August 19, 2010
More informationHydro Plant Risk Assessment Guide
September 2006 Hydro Plant Risk Assessment Guide Appendix E8: Battery Condition Assessment E8.1 GENERAL Plant or station batteries are key components in hydroelectric powerplants and are appropriate for
More information100 MW Wind Generation Project
A subsidiary of Pinnacle West Capital Corporation 100 MW Wind Generation Project CUSTOMER FINAL Feasibility Study Results By Transmission Planning, APS December 21, 2007 Executive Summary This Feasibility
More informationDynamic Control of Grid Assets
Dynamic Control of Grid Assets ISGT Panel on Power Electronics in the Smart Grid Prof Deepak Divan Associate Director, Strategic Energy Institute Director, Intelligent Power Infrastructure Consortium School
More informationSmall wonder. Station service voltage transformers for small power requirements
Small wonder Station service voltage transformers for small power requirements MATHEW PAUL An estimated 1.3 billion people worldwide have no access to electricity. In small communities, this is often due
More informationUtility Distribution Planning 101
Utility Distribution Planning 101 Michael Coddington, National Renewable Energy Laboratory Webinar for National Association of State Utility Consumer Advocates June 5, 2018 1 Webinar Overview Overview
More informationMIPSYCON 2014 Can a Grid be Smart without Communications? A Look at an Integrated Volt Var Control (IVVC) Implementation
MIPSYCON 2014 Can a Grid be Smart without Communications? A Look at an Integrated Volt Var Control (IVVC) Implementation David Aldrich Beckwith Electric Company Goals Flatten voltage profile across entire
More informationIowa State University Electrical and Computer Engineering. E E 452. Electric Machines and Power Electronic Drives
Electrical and Computer Engineering E E 452. Electric Machines and Power Electronic Drives Laboratory #12 Induction Machine Parameter Identification Summary The squirrel-cage induction machine equivalent
More information2000 Cooper Bussmann, Inc. Page 1 of 9 10/04/00
DO YOU KNOW THE FACTS ABOUT SINGLE-POLE INTERRUPTING RATINGS? YOU MAY BE IN TROUBLE! Typical plant electrical systems use three-phase distribution schemes. As an industry practice, short-circuit calculations
More informationElectric Power Research Institute, USA 2 ABB, USA
21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2016 Grid of the Future Symposium Congestion Reduction Benefits of New Power Flow Control Technologies used for Electricity
More informationFEBRUARY 14, 2017 Joslyn Hi-Voltage Capacitor switches customer presentation
FEBRUARY 14, 2017 Joslyn Hi-Voltage Capacitor switches customer presentation agenda Fundamentals Compelling value Product line overview VerSaVac (VSV) Product features and benefits Design Ratings Applications
More informationGenerator Interconnection System Impact Study For
Generator Interconnection System Impact Study For Prepared for: January 15, 2015 Prepared by: SCE&G Transmission Planning Table of Contents General Discussion... Page 3 I. Generator Interconnection Specifications...
More information2015 Grid of the Future Symposium
21, rue d Artois, F-75008 PARIS CIGRE US National Committee http ://www.cigre.org 2015 Grid of the Future Symposium Flexibility in Wind Power Interconnection Utilizing Scalable Power Flow Control P. JENNINGS,
More information2.0 CONSTRUCTION 3.0 OPERATION. SA-1 Generator Differential Relay - Class 1E 2.5 TRIP CIRCUIT
41-348.11C SA-1 Generator Differential Relay - Class 1E 2.0 CONSTRUCTION The type SA-1 relay consists of: Restraint Circuit Sensing Circuit Trip Circuit Surge Protection Circuit Operating Circuit Amplifier
More informationImplementing a Microgrid Using Standard Utility Control Equipment
Implementing a Microgrid Using Standard Utility Control Equipment Tom Fenimore Duke Energy Andy Gould and Larry Wright Schweitzer Engineering Laboratories, Inc. Copyright Duke Energy and SEL 2016 Overview
More informationSafeGear TM Motor Control Center Arc resistant metal-clad construction Motor Control Center Descriptive bulletin
SafeGear TM Motor Control Center Arc resistant metal-clad construction Motor Control Center Descriptive bulletin Contents 1. Introduction 2 2. Product highlights 2 3. Available configuration/competitive
More informationGeneration Interconnection Facilities Study For
Generation Interconnection Facilities Study For Prepared for: Prepared by: SCE&G Transmission Planning May 27, 2015 TABLE OF CONTENTS General Discussion... Page 3 Generator Interconnection Specifications...
More informationCIS-IEEE 2017 Conference Renewable Energy Session Renewable Energy s Impact of Power Systems
CIS-IEEE 2017 Conference Renewable Energy Session Renewable Energy s Impact of Power Systems Ben Huckaba, P.E. President & Principal Engineer 317-273-9841 benh@alphaeng.us Indiana University Bloomington,
More informationTHE NECESSITY OF THE 500 KV SYSTEM IN NWE S TRANSMISSION SYSTEM TO MAINTAIN RELIABLE SERVICE TO MONTANA CUSTOMERS
THE NECESSITY OF THE 500 KV SYSTEM IN NWE S TRANSMISSION SYSTEM TO MAINTAIN RELIABLE SERVICE TO MONTANA CUSTOMERS 2/27/2018 ELECTRIC TRANSMISSION PLANNING Table of Contents Table of Contents... 2 Executive
More informationProtection with distributed generation, experience with the Mont-Soleil wind farm project
Protection with distributed generation, experience with the Mont-Soleil wind farm project Florian Romanens IEEE Workshop 28 April 2011 Kursaal Bern Content BKW FMB Energie AG Mont-Soleil project Overview
More informationElbert County 500 MW Generation Addition Interconnection Feasibility Study Report OASIS POSTING # GI
Executive Summary Elbert County 500 MW Generation Addition Interconnection Feasibility Study Report OASIS POSTING # GI-2003-2 Xcel Energy Transmission Planning January 2004 This Interconnection Feasibility
More informationHawai'i Island Planning and Operations MEASURES TO IMPROVE RELIABILITY WITH HIGH DER
1 Hawai'i Island Planning and Operations MEASURES TO IMPROVE RELIABILITY WITH HIGH DER Lisa Dangelmaier Hawaii Electric Light lisa.dangelmaier@hawaiielectriclight.com Hawai'i Electric Light System Overview
More informationModernising the Great Western railway
Report by the Comptroller and Auditor General Department for Transport and Network Rail Modernising the Great Western railway HC 781 SESSION 2016-17 9 NOVEMBER 2016 4 Key facts Modernising the Great Western
More informationGuideline for Parallel Grid Exit Point Connection 28/10/2010
Guideline for Parallel Grid Exit Point Connection 28/10/2010 Guideline for Parallel Grid Exit Point Connection Page 2 of 11 TABLE OF CONTENTS 1 PURPOSE... 3 1.1 Pupose of the document... 3 2 BACKGROUND
More informationExpected Energy Not Served (EENS) Study for Vancouver Island Transmission Reinforcement Project (Part I: Reliability Improvements due to VITR)
Report-BCTC-R009A Expected Energy Not Served (EENS) Study for Vancouver Island Transmission Reinforcement Project (Part I: Reliability Improvements due to VITR) December 8, 2005 Prepared by Wenyuan Li
More informationCUSTOMER/ TWIN ARROWS PROJECT
A subsidiary of Pinnacle West Capital Corporation CUSTOMER/ TWIN ARROWS PROJECT V1 Facility Study Report APS Contract 52149 Prepared by: Arizona Public Service Company Transmission & Distribution Asset
More informationRULE 21 GENERATING FACILITY INTERCONNECTION APPLICATION SMUD s Distribution System - (SMUD FORM 2655)
- (SMUD FORM 2655) A. Applicability: This Generating Facility Interconnection Application (Application) shall be used to request the interconnection of a Generating Facility to Sacramento Municipal Utility
More informationPROFITABILITY THRESHOLDS OF RESILIENT MICROGRIDS (and how to exceed them) Baltimore, MD October 27th, 2018
PROFITABILITY THRESHOLDS OF RESILIENT MICROGRIDS (and how to exceed them) Baltimore, MD October 27th, 2018 Agenda About HARC Resilience and microgrids Microgrid Design Considerations with Uncertainty HARC
More information(by authors Jouko Niiranen, Slavomir Seman, Jari-Pekka Matsinen, Reijo Virtanen, and Antti Vilhunen)
Technical Paper: Low voltage ride-through testing of wind turbine converters at ABB helps wind turbines meet the requirements of IEC 61400-21 more quickly (by authors Jouko Niiranen, Slavomir Seman, Jari-Pekka
More informationAdvance 27 ANSI 27 kv switchgear
Advance 27 ANSI 27 kv switchgear Table of contents Advance 27...3 AMVAC breaker...4 Instrument transformers...5 Current transformers...5 27 kv voltage transformers...6 Distribution protection and control...7
More informationTransmission Competitive Solicitation Questions Log Question / Answer Matrix Harry Allen to Eldorado 2015
No. Comment Submitted ISO Response Date Q&A Posted 1 Will the ISO consider proposals that are not within the impedance range specified? Yes. However, the benefits estimated and studies performed by the
More informationRESERVOIR SOLUTIONS. GE Power. Flexible, modular Energy Storage Solutions unlocking value across the electricity network
GE Power RESERVOIR SOLUTIONS Flexible, modular Energy Storage Solutions unlocking value across the electricity network TRENDS DISRUPTING THE POWER SECTOR FROM GENERATION TO T&D DECARBONIZATION DIGITIZATION
More informationCONNECTION ASSESSMENT & APPROVAL PROCESS. Cardinal Substation Modification of 115kV Substation
CONNECTION ASSESSMENT & APPROVAL PROCESS ASSESSMENT SUMMARY Applicant: Project: Cardinal Substation Modification of 115kV Substation CAA ID: 2002 EX071 Long Term Forecasts & Assessments Department\ Consistent
More informationEnergy Storage and Distribution
Energy Storage and Distribution Pre-saturated Core Fault Current Limiter An Energy Technologies Institute project Delivered by GridON 02 03 Energy Technologies Institute www.eti.co.uk Pre-saturated Core
More informationA DOUG s View of Electric Utility Industry MICHAEL SHEEHAN, P.E. FAILTE GROUP NOVEMBER 2014
A DOUG s View of Electric Utility Industry MICHAEL SHEEHAN, P.E. FAILTE GROUP NOVEMBER 2014 Agenda Portland March 3 2 10:00 10:15 Welcome and Introduction 10:15 10:30 A DOUG s View 10:30 11:00 Standards
More information41-747G. Figure 1: Type DGF Relay without case (Photo)
Figure 1: Type DGF Relay without case (Photo) 2 183A113 EDSK 205342 Figure 2: Internal Schematic of the Type DGF Relay in the FT21 Case. When a ground appears in the generator field, the dc milliammeter
More informationProject #148. Generation Interconnection System Impact Study Report
Project #148 Generation Interconnection System Impact Study Report June 05, 2012 Electric Transmission Planning Table of Contents Table of Contents... 2 Executive Summary... 3 Energy Resource Interconnection
More informationEnergy Storage Interconnection Initiative
Energy Storage Interconnection Initiative Stakeholder Call November 25, 2014 Agenda Time Agenda Item Speaker 10:00-10:10 Introduction, Stakeholder Process Tom Cuccia 10:10-10:30 Applying the GIDAP to energy
More informationLLC FACILITIES STUDY TRANSMISSION SERVICE REQUEST
Cleco Power LLC FACILITIES STUDY TRANSMISSION SERVICE REQUEST OASIS 71956063 0 Rev Issue Date Description of Revision Table of Contents 1. Purpose...3 2. System Impact Study Conclusions...3 2.1 The Pineville
More informationInterconnection Feasibility Study Report GIP-023-FEAS-R1. Generator Interconnection Request # MW Wind Generating Facility Inverness (L6549), NS
Interconnection Feasibility Study Report GIP-023-FEAS-R1 Generator Interconnection Request # 23 100 MW Wind Generating Facility Inverness (L6549), NS February 16, 2006 Control Centre Operations Nova Scotia
More informationTechnology Roadmap for zzzzzzzzz Grid Automation
IEEE Nashville Chapter Technology Roadmap for zzzzzzzzz Grid Automation November 2010 2010 by R. W. Beck, An SAIC Company. All Rights Reserved. Projected Expenditures 2010-2030 Substation Transmission
More informationCHAPTER 4 PROTECTION REQUIREMENTS
CHAPTER 4 PROTECTION REQUIREMENTS CHAPTER 4 PROTECTION REQUIREMENTS 4.1 General Means of protection for automatic disconnection against phase and earth faults shall be provided on the customer main switch.
More informationDeploying Power Flow Control to Improve the Flexibility of Utilities Subject to Rate Freezes and Other Regulatory Restrictions
21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2013 Grid of the Future Symposium Deploying Power Flow Control to Improve the Flexibility of Utilities Subject to Rate
More informationDunvegan Hydroelectric Project. For Glacier Power Limited. Preliminary Interconnection Study
` Dunvegan Hydroelectric Project For Glacier Power Limited Preliminary Interconnection Study Prepared by Pung Toy, P. Eng. and Ata Rehman, P. Eng. September 24, 2004 Table of Contents Table of Contents...
More informationC. Figure 1. CA-16 Front View Figure 2. CA-16 Rear View
Figure 1. CA-16 Front View Figure 2. CA-16 Rear View 2 2.1. Restraint Elements Each restraint element consists of an E laminated electromagnet with two primary coils and a secondary coil on its center
More informationMILLIGAN SOLAR PROJECT
February 16, 2009 Page 1 of 18 A subsidiary of Pinnacle West Capital Corporation MILLIGAN SOLAR PROJECT FINAL Feasibility Study Report APS Contract 52115 Prepared by: Arizona Public Service Company Transmission
More informationIFC Workshop on Distributed Generation, 13 February 2013, Moscow, Russia
Integration of Distributed Energy Resources Into the Electric Grid: Some Issues and Solutions Larry Adams Senior Electrical & Controls Engineer Spirae, Inc. IFC Workshop on Distributed Generation, 13 February
More informationWESTERN INTERCONNECTION TRANSMISSION TECHNOLGOY FORUM
1 1 The Latest in the MIT Future of Studies Recognizing the growing importance of energy issues and MIT s role as an honest broker, MIT faculty have undertaken a series of in-depth multidisciplinary studies.
More informationData Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931
Data Bulletin 0931DB0101 July 2001 Cedar Rapids, IA, USA Ground-Censor Ground-Fault Protection System Type GC Class 931 09313063 GT Sensor Shunt Trip of Circuit Interrupter Window Area for Conductors GC
More information16kA Solid Dielectric, Triple Option Reclosers Catalog VLT12
16kA Solid Dielectric, Triple Option Reclosers Providing electronic overcurrent protection for single or three phase operation on systems rated through 27kV, 630A continuous current, 16kA symmetrical interrupting
More informationFeasibility Study Report
Report For: Orion Renewable Resources LLC ( Customer ) Queue #: Service Location: Rockingham County, NC Total Output Requested By Customer: 100 MW Commercial Operation Date Requested By Customer: 11/1/2019
More informationAmerican Electric Power s Energy Storage Deployments
American Electric Power s Energy Storage Deployments 1 2 American Electric Power : Company Profile The Evolution of the Electric Utility System Before Smart Grid: One-way power flow, simple interactions,
More informationThe Power Potential Project A guide to participating
The Power Potential Project 0 A guide to participating A technical guide to the services for synchronous and non-synchronous DER participants Page 1 of 17 Table of Contents Our vision... 3 1. Introduction...
More informationBattery Technology for Data Centers and Network Rooms: Site Planning
Battery Technology for Data Centers and Network Rooms: Site Planning White Paper # 33 Executive Summary The site requirements and costs for protecting information technology and network environments are
More information15 Nelson-Marlborough Regional Plan
15 Nelson-Marlborough Regional Plan 15.1 Regional overview 15.2 Nelson-Marlborough transmission system 15.3 Nelson-Marlborough demand 15.4 Nelson-Marlborough generation 15.5 Nelson-Marlborough significant
More informationUniversal Interconnection Technology Technology Roadmap Workshop. Associated Barriers to Distributed Generation
Universal Interconnection Technology Technology Roadmap Workshop Associated Barriers to Distributed Generation 7/25-26/2002 1 DG System Topics System Coordination Issues Present Day UIT System Issues Power
More informationPID 274 Feasibility Study Report 13.7 MW Distribution Inter-Connection Buras Substation
PID 274 Feasibility Study Report 13.7 MW Distribution Inter-Connection Buras Substation Prepared by: Entergy Services, Inc. T & D Planning L-ENT-17A 639 Loyola Avenue New Orleans, LA 70113 Rev Issue Date
More informationDirect On Line (DOL) Motor Starter. Direct Online Motor Starter
Direct On Line (DOL) Motor Starter Direct Online Motor Starter Different starting methods are employed for starting induction motors because Induction Motor draws more starting current during starting.
More informationWisconsin Public Utility Institute. June 28, Minimum Distribution Charges. Larry Vogt. Director, Rates Mississippi Power
Wisconsin Public Utility Institute June 28, 2017 Minimum Distribution Charges Larry Vogt Director, Rates Mississippi Power 1 Costs of Service vs. Cost Recovery Residential Service Example Assuming that
More informationWhen Grids Get Smart - ABB s Vision for the Power System of the Future
When Grids Get Smart - ABB s Vision for the Power System of the Future When Grids Get Smart ABB s Vision for the Power System of the Future There is a convergence occurring between the business realities
More informationZero Emission Bus Impact on Infrastructure
Zero Emission Bus Impact on Infrastructure California Transit Association (CTA) Fall Conference Nov 17, 2016 Russ Garwacki Director, Pricing Design & Research 626.302.6673 Russell.Garwacki@sce.com Barbara
More informationIllinois State Report
July 2016 Illinois State Report Table of Contents 1. Planning Generation Portfolio Analysis Transmission Analysis Load Forecast Gas Pipeline Information 2 Executive Summary (July 2016) Existing Capacity:
More informationCurrent accuracy class. Sensor principles
Indoor Combi Sensor 12, 17.5 and 25 kv 1250 A and 3200 A KEVCD Highest voltage for equipment kv 12.24 Rated continuous primary current A 1250.3200 Rated transformation ratio for current measurement, K
More informationInterconnection Feasibility Study Report Request # GI Draft Report 600 MW Wind Generating Facility Missile Site 230 kv Substation, Colorado
Executive Summary Interconnection Feasibility Study Report Request # GI-2016-6 Draft Report 600 MW Wind Generating Facility Missile Site 230 kv Substation, Colorado Public Service Company of Colorado Transmission
More informationJoint Con Edison LIPA Offshore Wind Power Integration Project Feasibility Assessment
Joint Con Edison LIPA Offshore Wind Power Integration Project Feasibility Assessment For NPCC Governmental / Regulatory Affairs Advisory Group May 21 st, 2009 ON IT Executive Summary Engineers from Con
More informationTRANSMISSION PLANNING CRITERIA
CONSOLIDATED EDISON COMPANY OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003-3502 Effective Date: TRANSMISSION PLANNING CRITERIA PURPOSE This specification describes Con Edison s Criteria for assessing
More informationGrounding Of Standby & Emergency Power Systems
July / August 2007 ELECTRICAL LINE 53 Grounding Of Standby & Emergency Power Systems By Andrew Cochran Power continuity is essential in many industrial and commercial installations where a trip out due
More informationMICHIGAN ELECTRIC UTILITY
MICHIGAN ELECTRIC UTILITY Generator Interconnection Requirements Category 5 Projects with Aggregate Generator Output Greater Than 2 MW August 3, 2009 Page 1 of 39 Introduction Category 5 Greater than 2MW
More informationAdvanced Protective Relay Training
Advanced Protective Relay Training Contact us Today for a FREE quotation to deliver this course at your company?s location. https://www.electricityforum.com/onsite-training-rfq A properly designed protection
More informationSafeGear Motor Control Center Arc Resistant Metal-Clad Construction Descriptive Bulletin
2017 SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Descriptive Bulletin SafeGear Motor Control Center Arc resistant Metal-Clad construction Descriptive Bulletin Table of Contents
More informationDistribution Feeder Upgrade Deferral Through use of Energy Storage Systems
1 Distribution Feeder Upgrade Deferral Through use of Energy Storage Systems Tan Zhang, Student Member, IEEE, Alexander E. Emanuel, Life Fellow, IEEE and John. A. Orr, Life Fellow, IEEE Abstract A method
More informationGeneration Interconnection Feasibility Study For XXXXXXXXXXXXXXXXXXXXXX MW generator at new Western Refinary Substation
Generation Interconnection Feasibility Study For XXXXXXXXXXXXXXXXXXXXXX 131-250 MW generator at new Western Refinary Substation System Planning Section April, 2005 TABLE OF CONTENT 1 EXECUTIVE SUMMARY
More informationGenerator Efficiency Optimization at Remote Sites
Generator Efficiency Optimization at Remote Sites Alex Creviston Chief Engineer, April 10, 2015 Generator Efficiency Optimization at Remote Sites Summary Remote generation is used extensively to power
More informationUK Research Activities on Advanced Distribution Automation. Dr. Graham Ault
UK Research Activities on Advanced Distribution Automation Dr. Graham Ault Outline Introduction and Background (ADA vs. ANM) UK Nationally Coordinated Activities in ANM UK Research & Development Activities
More informationWheeler Ridge Junction Substation Project Description and Functional Specifications for Competitive Solicitation
Wheeler Ridge Junction Substation Project Description and Functional Specifications for Competitive Solicitation 1. Description In the 2013-2014 Transmission Planning Cycle, the ISO approved the construction
More informationPower Quality and Protective Device Coordination: Problems & Solutions Part 1 Undersizing of Utility Main Service Transformers
Power Quality and Protective Device Coordination: Problems & Solutions Part 1 Undersizing of Main Service s INTRODUCTION by Robert E. Fuhr, P.E. The use of electronic equipment has dramatically increased
More informationAIR CORE REACTORS. Phoenix Electric Corporation
AIR CORE REACTORS Phoenix Electric Corporation PHOENIX ELECTRIC CORPORATION designs and manufactures Dry Type Air Core Reactors for operation on systems rated through 800 kv. All reactors are custom designed
More informationTransient Stability Analysis Tool (TSAT) Update April 11, Hongming Zhang EMS Network Applications Manager
Transient Stability Analysis Tool (TSAT) Update April 11, 2016 Hongming Zhang EMS Network Applications Manager Agenda Peak Online TSAT Introduction: Where we are on Wide-wide System Model (WSM) -TSAT online
More information