SM6. instructions for use. DMV A---DMV D cubicle (1250A range) MV distribution factory built assemblies at your service. Anglais

Size: px
Start display at page:

Download "SM6. instructions for use. DMV A---DMV D cubicle (1250A range) MV distribution factory built assemblies at your service. Anglais"

Transcription

1 SM6 Anglais MV distribution factory built assemblies at your service instructions for use DMV A---DMV D cubicle (1250A range)

2 foreword... 3 symbols and conventions... 3 as per iso contact the Schneider Electric service unit for diagnosis and advice 3 4 distribution rules... safety rules general description... 5 DMV--- A: incoming/outgoing circuit--- breaker cubicle... 5 DMV--- D coupling circuit--- breaker cubicle... 6 handling instruction... 7 device identification... list and number of bags and accessories weight... overall dimensions handling by slings... handling by forks storage installation and operation recommendation installation instructions preparing the cubicle prior to switchboard assembly fitting the end plate... fixing the ground cubicle reassembly... fitting the earth bar access to LV auxiliaries connection... MV 1P cable P cables... installing he 3P cable connection of HV single---pole cables (cubicle with VT option) VT disassembly instructions VT disassembly instructions (continued)... VT reassembly instructions SEPAM relay commissioning instructions Sepam range, series 20, series 40 Quick start storage commissioning... identification installation connection... connection using the advanced MMI... operation the setting and configuration modes... use configuration and setting, commissioning modification of passwords... loss of passwords entering a parameter or setting... entering a numerical value commissioning and operating instructions checking prior to energisation voltage presence... phase balance monitoring operating lever position... circuit --- breaker no --- load operations energisation of the downstream part of the installation... de---energisation of the downstream part of the installation EN revision : 01 1

3 operating safety... padlocking the devices key --- locking maintenance instructions preventive maintenance, cleaning instructions and power---up... corrective maintenance anomaly / solution table... options spare parts... recovery of SF6 gas at end of life EN revision : 01

4 foreword symbols and conventions Caution: you will find all the symbols below throughout the document, indicating the hazard levels depending on the different types of situation. DANGER as per iso DANGER: failure to follow this instruction will result in death or serious injury. WARNING as per iso WARNING: failure to follow this instruction may result in death or serious injury. CAUTION as per iso CAUTION: failure to follow this instruction may result in injuries. This alert signal can also be used to indicate practices that could damage the SM6 unit. INFORMATION-ADVICE We draw your attention to this specific point EN revision : 01 3

5 contact the Schneider Electric service unit for diagnosis and advice Call your sales representative who willputyouincontactwith the closest SCHNEIDER ELECTRIC group service centre. You can log on to: electric.com distribution rules The aim of this publication is to enable the SM6 unit to be installed correctly. This document is not a commercial document. It is a strictly technical document drawn up by Schneider Electric. safety rules CAUTION WARNING All the operations described below must be performed in compliance with applicable safety standards, under the responsibility of a competent authority. Thecontractormustbecertified and authorised to manipulate and perform work on the SM6 unit. CAUTION Only undertake the work after having read and understood all the explanations given in this document. If you have any difficulty complying with these rules, please contact Schneider Electric EN revision : 01

6 general description DMV --- A: incoming/outgoing circuit---breaker cubicle (side screen removed) 1 : top busbar compartment 2 : monitoring compartment 3 : line disconnector switch switchgear compartment 4 : control compartment 5 : cable connection compartment A : earth bar connection plate B : top busbar connection plates C : inspection viewports D : Evolis type HV circuit --- breaker E : front panel G : capacitive dividers H : downstream earthing switch J : HV cable connection plates 2 4 D C E A B 1 3 G H J 5 front view (front panel removed) F : voltage indicator K : circuit--- breaker operating mechanism mounting plate L : protection relay of the SEPAM type against phase --- to --- phase and earth faults L F K EN revision : 01 5

7 DMV --- D coupling circuit---breaker cubicle 1 : top busbar compartment 2 : monitoring compartment 3 : line disconnector switch switchgear compartment 4 : control compartment 5 : bar connection compartment A : earth bar connection plate B : top busbar connection plates C : inspection viewports D : Evolis type HV circuit --- breaker E : front panel G : capacitive dividers J : bottom busbar connection plates 2 4 D C A B J G E front view (front panel removed) F : voltage indicator K : circuit--- breaker operating mechanism mounting plate L : protection relay of the SEPAM type against phase --- to --- phase and eart faults L F K EN revision : 01

8 handling instruction device identification A : information plate B : characteristics and designation C :firmplate NB: the circuit--- breaker characteristics are marked on the latter. Serial number: D1: riveted to the control cover D2: stuck behind the monitoring covers D3: stuck on the frame central upright A B D3 D1 D2 C list and number of bags and accessories supplied with the cubicle Switchboard packing list: (if necessary as per switchboard composition) 1operatinglever 2endplates 1bagofendplatescrews S4: DMV A packing list: (1 cable and 2 cables version) 1 bag of inter---cubicle connections S1: dry cable flanges, 2 cables version 3flangebrackets,2cablesversion 1bagofbasinscrews FA 1earthbar 6bars 3 connection angle brackets (2 holes) 6 splitter blocks 5 x 1250A bars (in version > 12 KV) 1basinkit 1basinearthbar 1 bag of busbar screws (1250A feeder) 3 cable glands, 2 cables version 3 busbar spacers (only for 25 KA) DMV A packing list: (3P cable version) 1 bag of inter---cubicle connections S1: P cable flange 1flangebracket 1bagofbasinscrews FA 1earthbar 6bars 3 connection angle brackets (2 holes) 6 splitter blocks for 1250A busbar (in version > 12 KV) 1basinkit 1basinearthbar 1 bag of busbar screws (1250A feeder) 2 cable glands, 2 cables version 13Pcablehorn 3 busbar spacers (only for 25 KA) DMV A packing list: 1 bag of inter---cubicle connections S1: earthbar 6bars 3 connection angle brackets (2 holes) 6 splitter blocks for 1250A busbar (in version > 12 KV) 1 basin earth bar 1 bag of busbar screws (1250A feeder) 3 busbar spacers (only for 25 KA) EN revision : 01 7

9 weight Mean weight of an equipped cubicle: 340kg. Do not handle the cubicle using the control front plate. overall dimensions NB: the basin (C) only concerns cubicle DMV-- A. (mounted with the customer) 295, L1 L2 L3 C C ,5 72, EN revision : 01

10 handling by slings The handling lugs are reserved solely for handling of SM6 cubicles. A : HM12 screws and nuts B : Schneider Electric maximum useful load = 400 KG CE Schneider Electric CMU =400 KG CE L CAUTION C : In event of hole deformation (ovalisation) replace the lugs. A Schneider Electric CMU =400 KG CE B C L = 750 mm mini. handling by forks EN revision : 01 9

11 storage 70 C C EN revision : 01

12 installation and operation recommendation switchgear ageing withstandinanmv substation depends on 3 main factors: H The need for proper implementation of connections: the new retractable and cold slip --- on technologies offer an ease of installation which encourages long---term withstand. Their design allows operation in polluted environments with severe atmosphere. H Ventilation control: grid dimension must be suited to the power lost in the substation. These grids must be placed near the transformer only, so as to prevent air circulation on the MV switchboard. H Theinfluenceoftherelative humidity factor: installation of heating resistors is essential in climates with a high relative humidity rate and with large temperature differences. operation We strongly recommend that you regularly carry out, (at least roughly every 2 years), a few operating cycles on the switching devices. Outside normal operating conditions (between -- 5 C and 40 C, no dust or corrosive gas, etc.), we recommend that you examine together with our Schneider Electric group services centre, the measures that must be taken to ensure proper operation of the installation. Our service centre is at your disposal at all times to: H Conduct an installation diagnosis. H To propose if necessary. --- suitable maintenance operations. --- maintenance contracts. --- adaptations EN revision : 01 11

13 EN revision : 01

14 installation instructions preparing the cubicle priortoswitchboard assembly Delivery state:--- circuit --- breaker open--- line disconnector in the earth position. screw + washer screw + washer + nylstop nut C A B D Remove the screw (A) (only in DMV-- D), then remove the front panel (B) by lifting it and pulling it forward Remove the lug (C). (Screws cannot be re---used). Unscrew the two screws fixing the cover of the monitoring compartment (D), and remove it. E F Remove the rear roof (E) fromthe cubicle (4 screws). Remove the roof from the wiring trunking (F) (4screw). G Remove the 2 handling parts (G) EN revision : 01 13

15 fitting the end plate preparation (only if the cubicle is at the end of the switchboard) Bag of screws S4: (HM 6x12 screws only) Fit 10 cage nuts on the cubicle (See following assembly) : insertthecagenutfrom the outside of the cubicle into the specially provided rectangular hole. 2 : topple the cage nut inside the cubicle. 3 : push the cage nut in the direction of the arrow to place the top of the cage behind the plate. 4 : nut correctly placed. fitting the end plate Fit the end plate. Mounting direction of the screw and nylstop nut (Nylstop inside the cubicle) EN revision : 01

16 Note: according to the accessibility of the fixing points and of cubicle configuration, a certain number of cage nuts are mounted in the factory to simplify installation of the end plate. screw + washer screw + washer + nylstop nut right end the switchboard left end of the switchboard Fit the screws and cage nuts as well as the screws with nylstop nuts. switchboard assembly bag of screws S1: (HM 6x16 screws) M K L screw+washer+nut srew+wast front view K L Fix the cubicles to one another (the remaining screws are provided for fitting the earth bar) Bolt mounting direction. K left cubicle L right cubicle M connect the 2 cubicles. HM6 x 60 screws to be tightened moderately. Tightening torque: 6 Nm EN revision : 01 15

17 fixing the ground (screws to be provided by the contractor according to civil engineering). Basin position only for a DMV--A cubicle. 12,3 X 12, front of the cubicle installing the switchboard in the substation DMV D DMV A DMV D DMV A * 20 mm 20 mm Installing the switchboard to the right of the wall.* (minimum dimension to ensure proper device operation). Installing the switchboard to the left of the wall EN revision : 01

18 fitting the busbar after installing the cubicles at the final position 2 holes angle bracket U Fit the 3 connection angle brackets on the core of the device using the M8 x 30 screws (6 socket hexagon shape) without locking them. mounting the bars Must be complied with. Position the bars as shown opposite (top view). Version 12 KV V Mount the bars, then the screws. Tightening torque: 28 Nm. Block the screws V fixing the connection angle brackets, after having mounted all the bars. Tightening torque: 28 Nm EN revision : 01 17

19 assembling in version less than or equal to 12 kv series 25 KV only Slide a spacer between the bars of the 3 phases for lengths 625 mm. 625 mm = = Position the spacer in the middle of the busbar. Version > at 12 KV The remaining screws are not used. Correctly position the field splitter blocks on the connection angle bracket. (use the polarising slots to lock them in place). Incorrect assembly EN revision : 01

20 V Fit the bars and the screws. Tightening torque: 28 Nm. Block the screws V fixing the connection angle brackets, after having mounted all the bars. Tightening torque: 28 Nm. top busbar of a DMV --- A DMV--A top busbar of a DMV --- D DMV--D EN revision : 01 19

21 bottom busbar of a DMV D customer reception customer disassembly bar mounting Tightening torque: 28 Nm and 50 Nm. A : 28 Nm B : 50 Nm B A A A EN revision : 01

22 cubicle reassembly Re--use and put back in the same place the screws retrieved on disassembly. E F Put back the rear roof of the cubicle (E) (4screws). Put back the roof of the wiring trunking (F) ofthelvcompartment (4 screws). fitting the earth bar bag of screws The earth bars are connected to one another (HM 8x30 screws ). 2 ways of earthing the substation frames. access to LV auxiliaries connection E C D The cables at the connection terminal block are accessed via opening (C) E : user connection terminal block. D : SEPAM type protection relays (for setting, see overleaf) EN revision : 01 21

23 F C D After connection, put back the roof (F) for the wiring trunking. Put back the two screws fixing the cover of the monitoring compartment (D). MV 1P cable DMV --- A cubicle Basin kit ( FA) DMV--A delivered on cubicle pallet Bag of screws (1 or 2 cable version ( FA) Bag of 3P cable screws ( FA) preparing the basin plate Side plates A: V B fit the cage nuts to fix the basin plates. Rear plates B fit the cage nuts to fix the rear bottom plates. Fit HM8X40 screws+ M8 nut (V) to fix the cable earthing braid earth bar. Front plate C fit cage nuts to fix the front bottom plates. A C A mountingthebasinonthe cubicle A Fit the 2 side plates (A) on cubicles (fixing 4 M6 x 16 screws) EN revision : 01

24 B D Fit the rear plate (B) andfixitby2 screws, (M6 x 16). Fit the earth bar (D). C Fitthefrontplate(C) andfixallthe plates to one another by 12 screws (M6 x 16). 1P cables 1 or 2 cables version Preparing and mounting the bottom plate. screw + washer cage nuts F E On the front bottom plate (E) fit3 cage nuts. On the rear bottom plate (F) fit 3 cage nuts. Fix the bottom plates (E) and (F) by4screws,(m6x16) EN revision : 01 23

25 G G Fit the 3 cable glands (G). (1 or 2 cables version) H Fit the cable flange brackets. (H) phase 1 (1 or 2 cable version). Fix by 2 screws, (M6 x16). Fit by 3 x M8 cage nuts on the cable flange bracket (H) EN revision : 01

26 Installing 1 cable (1 cable version). Installing 2 cables. (2 cables version) Connecting the L1 phase cable. (1 cable version). Couple de serrage 75 Nm EN revision : 01 25

27 Connecting the L1 phase cable. (2 cables version). Tightening torque 75 Nm. J Fit the cable flange (J). (1 or 2 cables version) (3 HM8 X 60 screws). Fit phases L2 and L3 as per the same instructions as phase L1. Fix the cable braids on the earth bar EN revision : 01

28 installing he 3P cable E F On the bottom plates (E) and(f), cut or break the edges of the middle phase for 3P cable. Fix the plates (E) and(f) by 4 screws (M6 x 16). K G Fit the 2 cable glands (G). Fit the cable gland (K) EN revision : 01 27

29 L Fit the cable flange bracket (L) HM8 screws. Installing the 3P cable. Connect the strand of phase L1 then L2, andl3. Tightening torque: 75 Nm EN revision : 01

30 Fit the cable flange (M8 screws). Fix the cable braid or braids on the earth bar EN revision : 01 29

31 EN revision : 01

32 connection of HV single-- pole cables (cubicle with VT option) VT disassembly instructions A Remove the panel (A) onthefront face. B C Disconnect the metal foils (B) and the wires of the VT secondaries (C). Disconnect MV cables by unscrewing the VT screws EN revision : 01 31

33 VT disassembly instructions (continued) Slide the VT beam outside the cubicle and rest it on the floor or......on a base positioned at the same level as the bottom of the cubicle. RemovetheVTsfromthesupport beam Fit the thank and the HV cables. (see the installation instructions) chapter connection of HV single--pole cables EN revision : 01

34 VT reassembly instructions Once the tank is in position and HV cables connected, put the VTs back on the support beam. Put the VT beam back inside the cubicle. Reconnect the metal foils and the wires of the VT secondaries. A Reconnect the VT MV cables. Putthefrontfacepanel(A) back in position EN revision : 01 33

35 EN revision : 01

36 SEPAM relay commissioning instructions Sepam range, series 20, series 40 Quick start storage WARNING Risk of electrocution, burns or explosion. H Cut the power supply to the Sepam and the equipment in which it is installed prior to intervention. H Always use a suitable voltage detection device to check that the power supply has been cut. H Re---install all devices, doors and protection covers before re---energising the Sepam. H Re---install all the protection devices before re---energising the primary equipment. Failure to comply with these instructions may cause serious or fatal injuries or damage to the equipment. Sepam canbestoredinits original packaging, in a suitable room: H Temperature between C and +70 C (or F and +160 F), H Humidity 90% A regular check (at least once a year) of storage conditions is recommended. commissioning Sepam after unpacking, must be energised as soon as possible, particularly in the case of high humidity 90%. Prolonged storage of Sepam not supplied and without packaging may damage the device. identification Each Sepam is delivered in unit packaging including the basic unit and its connector. The other optional accessories such as modules, current or voltage input connectors and leads are delivered in separate containers. To identify a Sepam check the 2 labels on the right---hand side---plate of the basic unit defining the functional and material aspects of the product. hardware reference and description sepam/basic UMI/ 30V/ 70 C sepam/ihm de base/ 30V/ 70 C Origin: France model Man--- Machine Interface Supply voltage serial no SEPAM code software reference and description Substation / Sous---station English/French Modbus type of application operating language C04 } additional information (not systematic) S10 XX 520 X 33 XXX SEPAM code EN revision : 01 35

37 installation connection composition of Sepam basic unit, H A basic unit connector: --- power supply, --- output relay, --- input CSH30 / 120 / 200 or ACE990. Screw connector shown (CCA620), or eyelet lug connector (CCA622). H B current input connector TC 1A / 5 A (CCA630), or current input connector LPCT (CCA670), or voltage input connector (CCT640, series 20 only), H C communication module link connection (green), H D inter---module remote link connection (black). 2 optional input/output modules (MES108 or MES114), H L --- M module MES108 or MES114 connectors, H K module MES114 connector. H E voltage input connector (series 40 only), screw connectors shown (CCA626) or eyelet lug connectors (CCA627). 2 L K M i26 i14 i25 i24 i13 i23 i22 i12 i11 i CSH E B A D C EN revision : 01

38 connection basic unit The connections for Sepam are made on removable connectors placed on the rear face. All connectors can be locked by screwing. Connectors CCA670 and CCT640 are placed according to the principle described opposite. cabling screw connectors: without tip H 1 wire with a cross---section of 0.2 to 2.5 mm 2 maximum ( AWG ) or 2 wirrs with a cross---section of 0.2 to 1 mm 2 maximum ( AWG ), v stripping length: 8 to 10 mm.: with tip H recommended cabling with Telemecanique tip: DZ5--CE015D for 1 x 1.5 mm 2 wire (AWG 16), DZ5--CE025D for 1 x 2.5 mm 2 wire (AWG 12), AZ5--DE010D for 2 x 1 mm 2 wires (2 x AWG 18) H tube length: 8.2 mm, H stripping length: 8 mm. Cabling of connectors CCA622, CCA627: H eyelet or fork lugs 6.35 mm (1/4 ) H wire with a cross---section of 0.2 to 2.5 mm 2 maximum ( AWG ), H stripping length: 6 mm H use a suitable tool to crimp the lugs on the wires, H 2 eyelet or fork lugs maximum per terminal. Tightening torque: 0.7 to 1 Nm. Installing the optional module MES108 or MES114 H Insert the 2 pins of the MES module into the housings 1 of the basic unit. H Flatten the module against the unit to plug it onto connector 2. H Screw in fixing screw EN revision : 01 37

39 using the advanced MMI operation After tripping of the protection device on a fault (e.g. phase overcurrent) H the Trip indicator light is on, H the I>51 indicator light is on, H the display (advanced MMI option) displays: H a Phase fault message, H the value of the broken currents, H thedateandtimeoffault appearance, H press key to display the last 16 alarm messages not acknowledged, H press key to clear the message (acknowledgement), H press key to reset the protection device. access to measurements and parameters Measurements and parameters areaccessibleviathe measurement, diagnosis, status and protection keys. They are arranged in a series of screensasshowninthediagram opposite. H These data are divided up into categories in 4 loops, associated with the 4 keys below H key : measurements, H key : switchgear diagnosis and additional measurements, to apply the voltage to Sepam Io menu choice measurement measurement numerical value mean I measurement bargraph max I rms I bargraph clear clear clear reset série 20 série 40 H key : general parameters, H key : protection device settings. H Press the key to move to the next screen in the loop. When a screen has more than 4 lines, you must use the cursor keys to move around in this screen EN revision : 01

40 the setting and configuration modes there are 3 levels of use H the operator level. Used to access in read mode all screens. requires no password. H the setter level. requires introduction of the 1 st password (key ). Allows setting of protection devices (key ). H the configurer level. requires introduction of the 2 nd password (key ). Also allows modification of the general parameters (key ). Only the configurer can modify the passwords. Passwords have 4 digits. An expert MMI (Man---Machine Interface) is available (in addition to the basic or advanced MMI incorporated in the product) on the PC screen equipped with the SFT2841 software and connected to the RS 232 link on the front face of the Sepam (running in a Windows environment V95 or NT). All the information used for the same task is grouped on the same screen to simplify use. Menus and icons allow direct, rapid access to the relevant information EN revision : 01 39

41 use configuration and setting, commissioning Using passwords Sepam has 2 4--digit passwords. H The first password symbolised by a keyallows modification of protection device settings. H The second password symbolised by two keys allows modification of protection device settings and modification of all general parameters. entering passwords press key to bring up the following screen: passwords validation abandon The 2 passwords are: 0000 Press key to place the cursor on the first digit O X X X Scroll down the digits using the cursor keys then validate to move to the next digit by pressing key.when the password corresponding to your level of accreditation has been entered, press key to place the cursor on the validation box. Repress key to confirm. When the Sepam is in the setting mode, one key appears at the top of the display. When the Sepam is in the configuration mode, two keys appear at the top of the display. Access to the configuration and ettingmodesisde--activated. H by pressing key H automatically if no key has been activated for more than 5 mn. 50/51 2 B Off On tripping curve = threshold = time delay= independent 120 A 100 ms courbe = independent time delay 0ms validation return time abandon modification of passwords Only the configuration accreditation level (2 keys) or the SFT2841 authorises modification of passwords. Passwords are modified in the general parameters screen, key EN revision : 01

42 loss of passwords If factory passwords have been modified and the last passwords introduced have been permanently lost by the user, contact the Schneider Electric group service centre. entering a parameter or setting principle applicable to all screens of Sepam (example: phase overcurrent protection) H Introduction of the password. H Access to the relevant screen by successively pressing key. H Move the cursor using key to access the relevant field (e.g. a curve). H Press key to confirm this choice, then choose the type of curve by pressing key or and confirm by pressing key H Press key to reach the following fields until you reach the validation box. H Press key to validate the setting. entering a numerical value (example current threshold value) H With the cursor placed on the relevant fieldusing keys confirm the choice by pressing key H thefirstdigittobesetis selected, set the value by pressing keys (choice ). H Press key to confirm the choice and move to the next digit. The values are entered with 3 significant digits and a dot. The unit (e.g. A or ka) is chosen using the last digit. H Press key to confirm the input and key to access the next field. H All the values entered will be effective only after validation at the bottom of the screen and by pressing key EN revision : 01 41

43 EN revision : 01

44 commissioning and operating instructions checking prior to energisation Ensure that the connection compartment is empty. A B Put front panel (B) backinto place.for the DMV--D cubicles, put back the screw (A) Tightening torque : 8 Nm. voltage presence Incoming cubicle: On energisation of the upstream part of the installation, the voltage indicator lamps must come on. Outgoing cubicle: Once the line disconnector and the circuit---breaker havr been moved to the closed position, the voltage indicator lamps must come on. phase balance monitoring Note: the monitoring devivce is the same as that used by the RM6 equipment. Phase comparator of the simplified. In phase balance: H the comparator lamp does not come on. In phase unbalance: H the comparator lamp comes on EN revision : 01 43

45 operating lever position line disconnector Position the lever as shown, for downward opening operations. Position the lever as shown, for upward closing operations. circuit --- breaker no---load operations initial status: the line disconnector is in the open or earth position The circuit---breaker is open. B E C Lock the lever inlet (E) of the line disconnector with key (B) Remove the key in (B) thenplaceit in (C) Release then charge the circuit --- breaker (see Evolis manual). O I O I Close the circuit--- breaker by pressing pushbutton I. Open the circuit--- breaker by pressing pushbutton O EN revision : 01

46 C B E Lock the circuit---breaker in the open position with the key in (C). Remove the key in (C) thenplaceit in (B). Release the lever inlet (E) ofthe line disconnector energisation of the downstream part of the installation initial state: The line disconnector is in the earth position. The circuit---breaker is open. The front panel is in place. E A Movethelinedisconnectortothe open position using the operating lever. Note: InthecaseofaDMV--A, the downstream earhting switch opens simultaneously. Move the line disconnector to the closed position, then lock the inlet (E) of the line disconnector with the key (A). C O I O I Remove the key in (A), then place it in (C), after which release the circuit---breaker and charge it (see the Evolis manual). Close the circuit--- breaker by pressing pushbutton I. Thefront part of the installation is energised EN revision : 01 45

47 de---energisation of the downstream part of the installation C initial state: The line disconnector is in the closed position. The circuit--- breaker is closed. O I O I Open the circuit--- breaker by pressing pushbutton O. Lock the circuit---breaker in the open position with the key in (C). E A Remove the key (C), then place it in (A) Release the lever entry (E) ofthe line disconnector. Movethelinedisconnectortothe open position. Movethelinedisconnectortothe earth position. The front panel can be removed. NB: For a DMV--A, the downstream earthing switch closes simultaneously EN revision : 01

48 operating safety CAUTION It is possible to operate the circuit-- breaker with the panel removed. NB: Operationpossiblewhenthe circuit-- breaker is closed, but this is not recommended. Open the circuit-- breaker first. When the line disconnector is in the open or closed position, the front panel cannot be removed. The front panel can only be removedorfittediftheline disconnector is in the earth position. With the front panel removed, the line disconnector can be moved to the open position. However, it cannot be moved to the closed position. padlocking the devices With 1 to 3 x 8mmpadlocksper locking point. Padlocking the line disconnector in the earth position. Padlocking the line disconnector in the open position. Padlocking the front panel (only 1 padlock). Padlocking the line disconnector in the closed position EN revision : 01 47

49 key --- locking (optional) H Refer to the lock installation and operating manual no H To install a key --- lock on the circuit---breaker, refer to the manual for the relevant device. H If the key---lock option is not included in the order, contact the Schneider Electric group services centre EN revision : 01

50 maintenance instructions preventive maintenance, cleaning instructions and power --- up If necessary: contact the Schneider Electric group service centre. We strongly recommend that you carry out at regular intervals (at least roughly every 2 years) afew operating cycles on the switching devices. CAUTION Never lubricate the disconnector operating mechanism. If necessary: contact the Schneider Electric group service centre. In normal operating conditions (temperature between C and 40 C) no special maintenance is required. CAUTION Never use solvents and alcohol. We recommend that you inspect each compartment (cable, fuse, busbar)* at regular intervals according to environmental conditions. If the insulating parts are dusty, that you remove the dust using a dry cloth. example : In harsher conditions (aggressive atmosphere, dust, temperature less than C or greater than 40 C) consult the nearest Schneider Electric service centre EN revision : 01 49

51 corrective maintenance replacing a voltage indicator pack removing This operation is possible with the switch energised. Disassemble the 2 screws (A) fixing the voltage indicator pack A Extract the voltage indicator pack and disconnect the connector (B) at its rear. C B fitting On the characteristics label (C) check that the new pack matches the rated voltage for your network. H 10 kv to 24 kv Fit the new voltage indicator pack in the opposite direction to disassembly. Tightening torque: 0,1 mdan anomaly / solution table H the voltage indicator does not light up H check the voltage indicator H check that the line disconnector switch and the circuit---breaker are H closed (for an outgoing cubicle) H check that the incoming cables are energised H the front panel does not open or cannot be fitted H check that the line disconnector switch is in the earth position H impossible to move the line disconnector switch to the earth position H check that the line disconnector switch is in the open position H impossible to move the line disconnector switch to the closed position H check that the line disconnector switch is in the open position H impossible to operate the circuit---breaker H consult the circuit---breaker manual EN revision : 01

52 options (consult us) H Auxiliary contacts on disconnector. H Monitoring compartment. H options(key---locks). H Heating element. spare parts H Voltage indicator (for other operations, consult us: see the nearest Schneider Electric group service centre) EN revision : 01 51

53 recovery of SF6 gas at end of life for disconnector cubicle The SF6 must be removed before any dismantling operation can be carried out in compliance with the procedures described in IEC and according to the following instructions. The gas must be treated in compliance with IEC H volume of gas to be recovered: 35 litres H internal gauge pressure: 40 kp A NB : SF6 gas recycling at the end of circuit-- breaker life, refer to its instruction for use. Remove the cover (A) from the control cabinet. control cover access B Remove the control cover (B). Remove the 3 screws retaining the operating mechanism. Cut the wiring to remove the operating mechanism. Drill 2 holes in the filler valve safety cap 4 mm, centreline 20 mm, max. depth 4 mm EN revision : 01

54 CAUTION pump the gas for at least 15 minutes. C Using a spanner wrench, remove the safety cap from the valve. Connect the special pumping equipment (C) EN revision : 01 53

55 EN revision : 01

56 EN revision : 01 55

57 EN revision : 01

58 group Schneider Electric service centers are there for: engineering and technical assistance start-up training preventive and corrective maintenance adaptation work spare parts Call your sales representative who will put you in touch with your nearest group Schneider Electric service centers. Schneider Electric Industries SAS 89, boulevard Franklin Roosevelt F Rueil--- Malmaison (France) Tel:+33(0) electric.com EN revision : 01 As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication. Conception, rédaction: Service Documentation Technique T&D Edition du : 24/04/2008

SM6. instructions for use. GAM cubicle (1250A) MV distribution factory built assemblies at your service. Anglais

SM6. instructions for use. GAM cubicle (1250A) MV distribution factory built assemblies at your service. Anglais SM6 Anglais MV distribution factory built assemblies at your service instructions for use GAM cubicle (1250A) foreword... 3 symbols and conventions... 3 as per iso 3864---2... contact the Schneider Electric

More information

SM6. instructions for use. DMVL cubicle. MV distribution factory built assemblies at your service. Anglais

SM6. instructions for use. DMVL cubicle. MV distribution factory built assemblies at your service. Anglais SM6 Anglais MV distribution factory built assemblies at your service instructions for use DMVL cubicle foreword... 3 symbols and conventions... 3 as per iso 3864---2... contact the Schneider Electric service

More information

SM6. instructions for use. SM cubicle. MV distribution factory built assemblies at your service. Anglais

SM6. instructions for use. SM cubicle. MV distribution factory built assemblies at your service. Anglais SM6 Anglais MV distribution factory built assemblies at your service instructions for use SM cubicle foreword... 3 symbols and conventions... 3 as per iso 3864---2... contact the Schneider Electric service

More information

SM6. instructions for use. IMB cubicle without earthing switch. MV distribution factory built assemblies at your service. Anglais

SM6. instructions for use. IMB cubicle without earthing switch. MV distribution factory built assemblies at your service. Anglais SM6 Anglais MV distribution factory built assemblies at your service instructions for use IMB cubicle without earthing switch foreword... 3 symbols and conventions... 3 as per iso 3864---2... contact the

More information

SM6. instructions for use. QMB cubicles. MV distribution factory built assemblies at your service. Anglais

SM6. instructions for use. QMB cubicles. MV distribution factory built assemblies at your service. Anglais SM6 Anglais MV distribution factory built assemblies at your service instructions for use QMB cubicles foreword... 3 symbols and conventions... 3 as per iso 3864---2... contact the Schneider Electric service

More information

SM6. instructions for use. DMV S cubicle. MV distribution factory built assemblies at your service. Anglais

SM6. instructions for use. DMV S cubicle. MV distribution factory built assemblies at your service. Anglais SM6 Anglais MV distribution factory built assemblies at your service instructions for use DMV S cubicle foreword... 3 symbols and conventions... 3 as per iso 3864---2... contact the Schneider Electric

More information

SM6. instructions for use. DM1 S cubicle. MV distribution factory built assemblies at your service. Anglais

SM6. instructions for use. DM1 S cubicle. MV distribution factory built assemblies at your service. Anglais SM6 Anglais MV distribution factory built assemblies at your service instructions for use DM1 S cubicle foreword... 3 symbols and conventions... 3 as per iso 3864---2... contact the Schneider Electric

More information

SM6. instructions for use. IMCandQMCcubicles. MV distribution factory built assemblies at your service. Anglais

SM6. instructions for use. IMCandQMCcubicles. MV distribution factory built assemblies at your service. Anglais SM6 Anglais MV distribution factory built assemblies at your service instructions for use IMCandQMCcubicles foreword... 3 symbols and conventions... 3 as per iso 3864---2... contact the Schneider Electric

More information

Information for the modified document

Information for the modified document Information for the modified document émetteur : Esref OZYUZUCULER date :03-05 - 2001 Recipient SM6 --- 36kV STT KG K ToK FaZ OrY MRK(TR) E&S S OyR MeM er Number : 7897176EN Index : D0 Product : SM6-36

More information

circuit breaker instructions for use SF draw --- out circuit---breakers in F400 MV distribution circuit breaker Anglais at your service

circuit breaker instructions for use SF draw --- out circuit---breakers in F400 MV distribution circuit breaker Anglais at your service circuit breaker Anglais MV distribution circuit breaker at your service instructions for use SF draw --- out circuit---breakers in F400 foreword... 3 symbols and conventions... 3 as per iso 3864---2...

More information

MCset 4-24 kv Withdrawable SF6 circuit breaker

MCset 4-24 kv Withdrawable SF6 circuit breaker Medium Voltage switchgear MCset 4-24 kv Withdrawable SF6 circuit breaker Instruction for use Contents General 2 Glossary 2 Symbols 2 Recommendations 3 General description 4 AD4 unit 4 AD4 unit with toroidal

More information

MCset kv Medium voltage equipment

MCset kv Medium voltage equipment Maintenance Guide PE90014 PE90006 MCset 1-2 - 3 17.5 kv Medium voltage equipment Air-insulated switchboards Metal-enclosed switchgear with moving parts PE90007 PE90008 PE90009 PE90007 Maintenance Guide

More information

Medium voltage NEX switchgear Withdrawable circuit breaker. Quite simply efficient

Medium voltage NEX switchgear Withdrawable circuit breaker. Quite simply efficient Medium voltage NEX switchgear Withdrawable circuit breaker Quite simply efficient NEX, a simple and flexible solution NEX is the result of worldwide acquired experience and provides you with a high level

More information

Medium Voltage Distribution FBX. Assembling a 1250A busbar Instructions.

Medium Voltage Distribution FBX. Assembling a 1250A busbar Instructions. Medium Voltage Distribution FBX Assembling a 1250A busbar Instructions www.schneider-electric.com Contents Introduction... 3 Our Service Unit: our specialists, and suitably adapted services...... 3 Overview...

More information

circuit-- breaker instructions for use SF1 fixed or in SM6 circuit --- breaker MV distribution circuit breaker at your service Anglais

circuit-- breaker instructions for use SF1 fixed or in SM6 circuit --- breaker MV distribution circuit breaker at your service Anglais circuit-- breaker Anglais MV distribution circuit breaker at your service instructions for use SF1 fixed or in SM6 circuit --- breaker foreword... 3 symbols and conventions... 3 as per iso 3864---2...

More information

MCset 17.5 kv. Civil engineering guide April Medium Voltage Distribution

MCset 17.5 kv. Civil engineering guide April Medium Voltage Distribution Medium Voltage Distribution MCset 17.5 kv ir insulated switchboard Withdrawable switchgear SF6 or vaccum technology Civil engineering guide pril 2012 Contents General 2 Glossary 2 Dimensions and weights

More information

SFset with VIP 400/410 built-in control unit Medium Voltage Circuit Breaker

SFset with VIP 400/410 built-in control unit Medium Voltage Circuit Breaker SFset with VIP 400/410 built-in control unit Medium Voltage Circuit Breaker Instructions for use 07897543EN01 Rev.04 11/2017 SFset- Instructions for use Table of contents Presentation Presentation...

More information

AIR INSULATED METAL ENCLOSED SWITCHGEAR AND CONTROLGEAR

AIR INSULATED METAL ENCLOSED SWITCHGEAR AND CONTROLGEAR AIR INSULATED METAL ENCLOSED SWITCHGEAR AND CONTROLGEAR ANGLER SWITCHING DEVICES CONTENTS 1. General 2. Switchgear Types - Switch Disconnector - Disconnector 3. Cubicle Types - Cubicle with Switch Disconnector

More information

SFset with VIP 400/410 built-in control unit Medium Voltage Circuit Breaker

SFset with VIP 400/410 built-in control unit Medium Voltage Circuit Breaker SFset with VIP 400/410 built-in control unit Medium Voltage Circuit Breaker Instructions for use 11/2017 18 0 2 ing A r p s e l b a l i va SFset- Instructions for use Table of contents Presentation Presentation...

More information

Electrical network protection VIP30, VIP35. User s manual 12/2008

Electrical network protection VIP30, VIP35. User s manual 12/2008 Electrical network protection VIP30, VIP35 User s manual 1/008 Safety instructions ANSI symbol. IEC symbol. Safety symbols and messages Read these instructions carefully and look at the equipment to become

More information

CBGS-0. Medium voltage distribution

CBGS-0. Medium voltage distribution Medium voltage distribution CBGS-0 Gas Insulated metal-enclosed Switchgear SF6 circuit breaker technology Up to 24/36 kv - 1250/1600/2000 A - 25/31.5 ka Transmission Wind Airports Oil & Gas Mining & Distribution

More information

GHA. Gas-Insulated Switchgear. Gas-Insulated Switchgear. Switchgear extension and replacement of a panel

GHA. Gas-Insulated Switchgear. Gas-Insulated Switchgear. Switchgear extension and replacement of a panel Gas-Insulated Switchgear GHA Gas-Insulated Switchgear Switchgear extension and replacement of a panel During this work, essential parts of the switchgear remain in operation No. AGS 535 066-01 Edition

More information

0MV vacuum circuit breaker. 0Evolis 24 kv. 0User 0Manual. Creation Printed on 2008/07/17

0MV vacuum circuit breaker. 0Evolis 24 kv. 0User 0Manual. Creation Printed on 2008/07/17 0MV vacuum circuit breaker 0Evolis 24 kv 0User 0Manual 02008 07897530EN-C0.book Page 1 Jeudi, 15. mai 2008 11:34 11 Contents Evolis description 2 Front view circuit breaker 2 Front view lateral circuit

More information

CPG.0 Single busbar gas-insulated cubicles

CPG.0 Single busbar gas-insulated cubicles MV Switchgear Primary Distribution CPG.0 Single busbar gas-insulated cubicles Up to 36 kv CPG System The quality of products designed, manufactured and installed by Ormazabal is underpinned by the implementation

More information

PIX-H Metal-clad switchgear up to 17.5kV

PIX-H Metal-clad switchgear up to 17.5kV AIR INSULATED SWITCHGEAR PIX-H Metal-clad switchgear up to 17.5kV for high rated applications Technical Specifications AREVA T&D Summary - Technical description... 3 - Standards... 6 - PIX in detail...

More information

DPX moulded case circuit breakers

DPX moulded case circuit breakers BREAKING AND PROTECTION DEVICES 10 / 2011 DPX moulded case circuit breakers DPX moulded case circuit breakers offer optimum solutions for the protection requirements of commercial and industrial installations.

More information

Secondary Distribution Switchgear FBX. SF6 Gas-insulated switchboards CB function. Instructions Installation - Commissioning Operating - Maintenance

Secondary Distribution Switchgear FBX. SF6 Gas-insulated switchboards CB function. Instructions Installation - Commissioning Operating - Maintenance Secondary Distribution Switchgear FBX SF6 Gas-insulated switchboards CB function Instructions Installation - Commissioning Operating - Maintenance Contents 1 Schneider Electric at your service... 1 1.1

More information

SYSclad switchboard equipped with draw out type vacuum circuit breaker closed dooroperationoperation. SYSclad 12 17,5kV A.

SYSclad switchboard equipped with draw out type vacuum circuit breaker closed dooroperationoperation. SYSclad 12 17,5kV A. SYSclad switchboard equipped with draw out type vacuum circuit breaker closed dooroperationoperation 630 3150A SYSclad 12 17,5kV 16 31,5kA Generalities SYSclad is a medium voltage switchboard metal clad

More information

NEXT STEP B) SAFETY :

NEXT STEP B) SAFETY : SUMMARY : EVOLUTION OF MV/LV SUBSTATIONS COMPACT SUBSTATIONS J. M. Solans, C. Prevé, R. Farrán, R. Muñoz. SCHNEIDER ELECTRIC S.A. - SPAIN INTRODUCTION The recent liberalisation of the electricity supply

More information

circuit breakers instructions for use SF2 fixed MV distribution circuit breaker at your service Anglais

circuit breakers instructions for use SF2 fixed MV distribution circuit breaker at your service Anglais circuit breakers nglais MV distribution circuit breaker at your service instructions for use SF2 fixed foreword... 3 symbols and conventions... 3 as per iso 3864---2... contact the Schneider lectric service

More information

CGMCOSMOS. Reliable innovation. Personal solutions. Fully gas insulated modular and compact (RMU)system.

CGMCOSMOS. Reliable innovation. Personal solutions. Fully gas insulated modular and compact (RMU)system. MV Switchgear for CGMCOSMOS Fully gas insulated modular and compact (RMU)system Up to 24 kv Up to 27 kv mediumvoltage mediumvoltageag AG Langackerstrasse Langackerstrasse 25 25 CH CH 6330 6330 Cham Cham

More information

24 kv. A brief summary of the. range

24 kv. A brief summary of the. range Medium-Voltage distribution - 24 kv Metal-enclosed withdrawable switchgears MCset4 - SF6 technology NEX24 - vacuum technology 2008 Maintenance and Services Guide October 2008 PE90002 24 kv A brief summary

More information

Medium Voltage Distribution PIX kv. Additional equipment Instructions.

Medium Voltage Distribution PIX kv. Additional equipment Instructions. Medium Voltage Distribution PIX 12-17.5-24 kv Additional equipment Instructions www.schneider-electric.com Contents 1 Schneider Electric at your service... 4 1.1 Your contacts... 4 2 State of delivery

More information

B kv Gas-insulated Substations

B kv Gas-insulated Substations 72.5 145 kv Gas-insulated Substations The increasing demand for electrical power in cities and industrial centres requires the installation of a compact and efficient distribution and transmission network.

More information

PIX. Operation - Replacement of Fuses Replacement of Voltage Transformers Technical manual. Medium Voltage Distribution

PIX. Operation - Replacement of Fuses Replacement of Voltage Transformers Technical manual. Medium Voltage Distribution Medium Voltage Distribution PIX Withdrawable Voltage Transformer Operation - Replacement of Fuses Replacement of Voltage Transformers Technical manual Nr. Edition 11/2011 www.schneider-electric.com Schneider

More information

Key features. DESIGNS: - Conservator type - Hermetically sealed

Key features. DESIGNS: - Conservator type - Hermetically sealed Package Substations OTDS manufactures a large range of oil filled hermitically sealed and conservator type transformers to be used in conjunction with our package substations. We are able to utalise the

More information

SF6 Load Break Switch 2017 FIL3 - S. Indoor Medium Voltage LBS With or without fuse 12kV- 24kV FIL3 D FIL3. 24KV SF6 Load Break Switch

SF6 Load Break Switch 2017 FIL3 - S. Indoor Medium Voltage LBS With or without fuse 12kV- 24kV FIL3 D FIL3. 24KV SF6 Load Break Switch FIL3 - S FIL3 D Indoor Medium Voltage LBS With or without fuse 12kV- 24kV FIL3 24KV SF6 Load Break Switch Content 1. About Us 2. Load Break Switch Introduction 3. FIL3 product overview 3.1. Advantages

More information

Compact NR630. NR100F to NR630F

Compact NR630. NR100F to NR630F Low voltage switchgear Compact NR NR100F NR630F The Compact NS range has revolutionised the world of moulded-case circuit breakers. For installations not requiring the high performance levels of the NS

More information

UniGear. Technical Guide

UniGear. Technical Guide UniGear Technical Guide CONTENTS 0 CONTENTS 1.1 Compartments 1/2 1.2 Components of the structure 1/3 1.2.1 Hot-galvanized steel sheet 1/3 1.2.2 Painted steel sheet 1/4 1.2.3 Copper 1/5 1.2.4 Insulating

More information

STANDARDIZED LOW VOLTAGE SWITCHBOARDS UP TO 690V-6300A-100KA

STANDARDIZED LOW VOLTAGE SWITCHBOARDS UP TO 690V-6300A-100KA CB-02 STANDARDIZED LOW VOLTAGE SWITCHBOARDS UP TO 690V-6300A-100KA POWER CENTER PC MOTOR CONTROL CENTER MCC32 MOTOR CONTROL CENTER MCCF Premises 10.000mq Offices 2.000mq Warehouse 1.200mq Open Area 15.000mq

More information

NEX - 24 kv Withdrawable Circuit Breaker

NEX - 24 kv Withdrawable Circuit Breaker Air Insulated Medium Voltage Equipment NEX - 24 kv Withdrawable Circuit Breaker Installation drawings file Contents bj Fitting the upper main busbars 1250 A busbar - 800 mm cubicle Assembly 1250 A busbar

More information

OPERATING AND MAINTENANCE MANUAL. Primary Current Injection Test Set. 750ADM-H mk2

OPERATING AND MAINTENANCE MANUAL. Primary Current Injection Test Set. 750ADM-H mk2 OPERATING AND MAINTENANCE MANUAL Product: Type: Primary Current Injection Test Set 750ADM mk2 750ADM-H mk2 DESIGNED AND MANUFACTURED BY: T & R Test Equipment Limited 15-16 Woodbridge Meadows, Guildford,

More information

AIR INSULATED EXTENDABLE SWITCHGEAR UP TO 12KV GUIDE

AIR INSULATED EXTENDABLE SWITCHGEAR UP TO 12KV GUIDE AIR INSULATED EXTENDABLE SWITCHGEAR UP TO 12KV GUIDE Certificate Number FM35831 APPLICATION Typical Uses and Classification The MSGair switchgear is used in transformer and switching substations mainly

More information

Protection and control VIP30, VIP35. Relays technical manual

Protection and control VIP30, VIP35. Relays technical manual Protection and control VIP30, VIP35 Relays technical manual contents 1. presentation of the VIP30 and VIP35...3 2. use and settings...4 3. sensors and operating ranges... 4. connection scheme...9 5. assembly

More information

Metal Clad Switchgears

Metal Clad Switchgears SNC Series Metal Clad Switchgears > up to 36 kv Rated Voltage > up to 2500 A Rated Current > up to 40 ka Rated Short Time Withstand Current > LSC-2B, PM, AFLR > In Confirmity with IEC 62271-1, 100, 102,

More information

Galaxy VM. Battery Breaker Box Installation 09/

Galaxy VM. Battery Breaker Box Installation 09/ Galaxy VM Battery Breaker Box Installation 09/2016 www.schneider-electric.com Legal Information The Schneider Electric brand and any registered trademarks of Schneider Electric Industries SAS referred

More information

Low-voltage switchgear MNS Light W. Installation, handling and operation. ABB LV Systems

Low-voltage switchgear MNS Light W. Installation, handling and operation. ABB LV Systems Low-voltage switchgear MNS Light W Installation, handling and operation ABB LV Systems MNS Light W switchgear is a flexible system that is primarily designed for motor control. The rated service voltage

More information

Secondary Distribution Switchgear FBX. SF6 Gas-insulated switchboards. Instructions Operation - Maintenance

Secondary Distribution Switchgear FBX. SF6 Gas-insulated switchboards. Instructions Operation - Maintenance Secondary Distribution Switchgear FBX SF6 Gas-insulated switchboards Instructions Operation - Maintenance Contents 1 Schneider Electric at your service................... 1 1.1 Our Service Unit: our specialists,

More information

Pulsar EXtreme 2200C / 3200C

Pulsar EXtreme 2200C / 3200C www.mgeups.com MGE UPS SYSTEMS Pulsar EXtreme 00C / 300C Installation and user manual P O W E R P R O V I D E R L E I B E R R U P T N T N I E U T H 3400753EN/AA - Page Introduction Thank you for selecting

More information

DISTRIBUTION SOLUTIONS. GSec Gas-insulated switching and isolating apparatus

DISTRIBUTION SOLUTIONS. GSec Gas-insulated switching and isolating apparatus DISTRIBUTION SOLUTIONS GSec Gas-insulated switching and isolating apparatus GSec is a three-position SF6 gas-insulated switchdisconnector designed for use in medium voltage switchgear for secondary distribution

More information

Evolis offer Merlin Gerin

Evolis offer Merlin Gerin Medium voltage distribution Evolis offer Merlin Gerin Installation guide 200757a General contents Evolis circuit breaker full version 3 Circuit breaker installation 3 Cradle installation and earthing 3

More information

GMA. Medium-voltage switchgear

GMA. Medium-voltage switchgear Medium-voltage switchgear Gas-insulated switchgear up to 24 kv - 2500 A - 31.5 ka Earthing without automatically CLOSE / OPEN of the Circuit Breaker Operation - Maintenance Technical Manual No. AGS 531

More information

Low voltage Direct Current Network. Compact NSX DC PV. Circuit breakers and switch disconnectors for solar application.

Low voltage Direct Current Network. Compact NSX DC PV. Circuit breakers and switch disconnectors for solar application. Low voltage Direct Current Network Compact NSX DC PV Circuit breakers and switch disconnectors for solar application Catalogue 2012 Compact NSX DC PV A complete DC offer for solar application from 80

More information

Cable arrangement 15 Preparation for cable installation. 15 Installation of the cables 16 Finishing of the cable installation. 17 Examples.

Cable arrangement 15 Preparation for cable installation. 15 Installation of the cables 16 Finishing of the cable installation. 17 Examples. Transportation and storage.. 3 General. 3 Unpacking at installation site....... 3 Transfer of cubicles at installation site... 3 Weight.. 4 Temporary storage. 4 Erection at site 5 General. 5 The switchgear

More information

UniSec Operation and maintenance manual

UniSec Operation and maintenance manual Medium voltage products UniSec Operation and maintenance manual Safety 3 For your safety! 3 Skilled personnel 3 Critical messages 3 Contact us! 3 1. Introduction 4 1.1 General aspects 4 1.2 Operation and

More information

CPG.1 Gas insulated, single busbar cubicle range Up to 27 kv / 2000 A / 31.5 ka Up to 38 kv / 2000 A / 31.5 ka IEEE Standards

CPG.1 Gas insulated, single busbar cubicle range Up to 27 kv / 2000 A / 31.5 ka Up to 38 kv / 2000 A / 31.5 ka IEEE Standards Medium Voltage Switchgear Primary Distribution CPG.1 Gas insulated, single busbar cubicle range Up to 27 kv / 2000 A / 31.5 ka General description Presentation Ormazabal s CPG System includes the CPG.1

More information

I B D Q I B D Q O I B D Q O

I B D Q I B D Q O I B D Q O Extension offer: new possible combinations 2 and 3 functions RM6 free combination: offers all types of configurations which fit to every application. Free choice: type of each functional unit. Free choice:

More information

GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector

GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector Catalog 0500CT9702R409 2009 Class 525/580 CONTENTS Description............................................. Page General Characteristics...................................

More information

User Manual. Solar Charge Controller 3KW

User Manual. Solar Charge Controller 3KW User Manual Solar Charge Controller 3KW 1 CONTENTS 1 ABOUT THIS MANUAL... 3 1.1 Purpose... 3 1.2 Scope... 3 1.3 SAFETY INSTRUCTIONS... 3 2 INTRODUCTION... 4 2.1 Features... 4 2.2 Product Overview... 5

More information

High voltage products PASS M0S 252 kv Innovative solution for transmission substation up to 252 kv

High voltage products PASS M0S 252 kv Innovative solution for transmission substation up to 252 kv High voltage products PASS M0S 252 kv Innovative solution for transmission substation up to 252 kv PASS M0S 252 kv Innovation In today s market, the HV substation is increasingly becoming a key element

More information

Installation manual wall-mounted distributor

Installation manual wall-mounted distributor EN Installation manual wall-mounted distributor EN 60003233 Issue 11.2016 2016-14-11 Table of contents 1 About this manual 3 1.1 Structure of the warnings 3 1.2 Symbols used 4 1.3 Signal words used 4 2

More information

Date Issued: 10 August 2009 Status: ISSUED Review Date: 10 August 2011 Ref: NS5.3 DISTRIBUTED GENERATION TECHNICAL REQUIREMENTS TABLE OF CONTENTS

Date Issued: 10 August 2009 Status: ISSUED Review Date: 10 August 2011 Ref: NS5.3 DISTRIBUTED GENERATION TECHNICAL REQUIREMENTS TABLE OF CONTENTS Date Issued: 10 August 2009 Status: ISSUED Review Date: 10 August 2011 Ref: NS5.3 DISTRIBUTED GENERATION TECHNICAL REQUIREMENTS TABLE OF CONTENTS 1. PURPOSE AND SCOPE OF THIS DOCUMENT... 3 2. DEFINITIONS...

More information

Medium Voltage Distribution Maintenance Guide I 2013 Premset. 15 kv compact modular vacuum switchgear with Shielded Solid Insulation System

Medium Voltage Distribution Maintenance Guide I 2013 Premset. 15 kv compact modular vacuum switchgear with Shielded Solid Insulation System Medium Voltage Distribution Maintenance Guide I 2013 Premset 15 kv compact modular vacuum switchgear with Shielded Solid Insulation System Schneider Electric Services, by your side all day long Installation

More information

SWITCHGEAR FOR SERVICE UP TO 36kV (CABLE AND OVERHEAD CONDUCTOR CONNECTED)

SWITCHGEAR FOR SERVICE UP TO 36kV (CABLE AND OVERHEAD CONDUCTOR CONNECTED) PRODUCED BY THE OPERATIONS DIRECTORATE OF ENERGY NETWORKS ASSOCIATION Issue 3 2012 SWITCHGEAR FOR SERVICE UP TO 36kV (CABLE AND OVERHEAD CONDUCTOR CONNECTED) www.energynetworks.org 2012 Energy Networks

More information

Fuse state indicator MEg72. User manual

Fuse state indicator MEg72. User manual Fuse state indicator MEg72 User manual MEg Měřící Energetické paráty, a.s. 664 31 Česká 390 Czech Republic Fuse state indicator MEg72 User manual Fuse state indicator MEg72 INTRODUCTION The fuse state

More information

Energy Australia Chamber Substation indoor switchgear. installation,operation and maintenance instructions version 1.

Energy Australia Chamber Substation indoor switchgear. installation,operation and maintenance instructions version 1. Energy Australia Chamber Substation indoor switchgear installation,operation and maintenance instructions version 1.6 / February 2009 1 Details of revision Version Comment Date 1.0 First Draft Issue May

More information

Specification for 70mm pole pitch Air circuit breaker up to 1600 A

Specification for 70mm pole pitch Air circuit breaker up to 1600 A Specification for 70mm pole pitch Air circuit breaker up to 1600 A Protective device for low voltage electrical installation Last update :2011-07-08-1 - Table of contents: 1 General...3 2 Compliance with

More information

MESG 12 / 17.5 / 24 / 36 KV

MESG 12 / 17.5 / 24 / 36 KV MESG 12 / 17.5 / 24 / 36 KV Medium Voltage Air Insulated Metal Enclosed Switchgear up to 36 kv- up to 1250 A - up to 25 ka for 1 sec. with SF6 or vacuum circuit breakers. 750 METAL ENCLOSED 1 1 ) GENERAL

More information

Cloud-connected solution for utility-scale renewable power

Cloud-connected solution for utility-scale renewable power Cloud-connected solution for utility-scale renewable power Conext SmartGen TM Power System Global power conversion system for the next generation of PV and Energy Storage power plants connected to smart

More information

abb SafeLink SF 6 Insulated Ring Main Unit Installation and Operating Instructions Switchgear Division Auckland, New Zealand SLMIO ver 2.

abb SafeLink SF 6 Insulated Ring Main Unit Installation and Operating Instructions Switchgear Division Auckland, New Zealand SLMIO ver 2. Installation and Operating Instructions Switchgear Division Auckland, New Zealand SLMIO ver 2.12 Product Overview ABB's type-tested ring main unit (RMU) is an SF 6 insulated RMU utilising the latest developments

More information

Galaxy Receiving and Unpacking 09/

Galaxy Receiving and Unpacking 09/ Galaxy 5500 20 120 kva 400 V Receiving and Unpacking 09/2015 www.schneider-electric.com Legal Information The Schneider Electric brand and any registered trademarks of Schneider Electric Industries SAS

More information

Pulsar EXtreme CLA 1500C

Pulsar EXtreme CLA 1500C www.mgeups.com MGE UPS SYSTEMS Pulsar EXtreme CLA 500C Installation and user manual 503998EN/AA - Page Introduction Thank you for selecting an MGE UPS SYSTEMS product to protect your electrical equipment.

More information

Cloud-connected solution for utility-scale renewable power

Cloud-connected solution for utility-scale renewable power Cloud-connected solution for utility-scale renewable power Conext SmartGen TM Power System Global power conversion system for the next generation of PV and Energy Storage power plants connected to smart

More information

Operating instructions. sonnenprotect for operators. KD-337 Part no Version X00.

Operating instructions. sonnenprotect for operators. KD-337 Part no Version X00. Operating instructions for operators sonnenprotect 1300 KD-337 Part no. 22010 Version X00 info@sonnenbatterie.de www.sonnenbatterie.de EN IMPORTANT Read this documentation carefully before operation. Retain

More information

User Manual Rittal PMC UPS 6kVA

User Manual Rittal PMC UPS 6kVA User Manual Rittal PMC UPS 6kVA Germany Rittal GmbH & Co. KG Auf dem Stützelberg D-35745 Herborn Tel.: ++49-27 72-5 05-0 Fax: ++49-27 72-5 05-23 19 Internet: www.rittal.de 26 Contents 1. Introduction...

More information

Galaxy VX Battery Breaker Trip Board (GVXBBTB) and Battery Breaker Capacitor Board (GVXBBCB)

Galaxy VX Battery Breaker Trip Board (GVXBBTB) and Battery Breaker Capacitor Board (GVXBBCB) Installation 990 91076 001 12/2017 Galaxy VX Battery Breaker Trip Board (GVXBBTB) and The battery breaker trip board is the interface from the battery bank to the UPS battery auxiliary inputs/outputs and

More information

Phase + Neutral, neutral on left side

Phase + Neutral, neutral on left side 87045 LIMOGES Cedex Téléphone : 05 55 06 87 87 Télécopie : 05 55 06 88 88 DX 3 MCB 10000 A / 16 ka CONTENTS PAGE 1. Description, use...1 2. Range...1 3. Overall dimensions...1 4. Preparation - Connection...1

More information

EVlink Parking EVF1 - EVW1

EVlink Parking EVF1 - EVW1 EVlink Parking EVF1 - EVW1 Parking Charging Stations User Manual 07/2013 EVF1ppppppp EVW1ppppppp DOCA0063EN-01 www.schneider-electric.com This document contains general descriptions and/or general technical

More information

The Key Link for all your Distributions Needs. A Comprehensive Range for All Your Needs

The Key Link for all your Distributions Needs. A Comprehensive Range for All Your Needs [ MV Air-insulated Switchgear Range ] 1 PIX CUSTOMER BENEFITS Compact, versatile and highly reliable designs Choice of vacuum or SF6 switching technology Wide range of applications Enhanced operator safety

More information

TECHNICAL DESCRIPTION

TECHNICAL DESCRIPTION DC Circuit Breaker TECHNICAL DESCRIPTION TRK5650523200 Ed.1 of 23/07/13 CONTENTS 1. INTRODUCTION... 2 2. DESCRIPTION... 2 2.1 Description of circuit breaker... 2 2.2 Operating mode... 2 2.3 Variants and

More information

The vacuum circuit breaker for commercial buildings, industrial plants and utilities

The vacuum circuit breaker for commercial buildings, industrial plants and utilities The vacuum circuit breaker for commercial buildings, industrial plants and utilities EasyPact EXE The easy choice for more value 2 EasyPact EXE EasyPact EXE, a medium voltage vacuum circuit breaker optimizing

More information

CGM.3 System. Medium Voltage SF 6 gas-insulated cubicles up to 38 kv according to IEEE and CSA standards

CGM.3 System. Medium Voltage SF 6 gas-insulated cubicles up to 38 kv according to IEEE and CSA standards CGM.3 System Medium Voltage SF 6 gas-insulated cubicles up to 38 kv according to IEEE and CSA standards General Instructions IG-183-EN, version 03; 06/03/2013 Legal Deposit: BI-0272/2013 CAUTION! When

More information

NS Feeder pillar up to 3200A

NS Feeder pillar up to 3200A NS Feeder pillar up to 3200A Advanced technology for low voltage, outdoor distribution Merlin Gerin Modicon Telemecanique Outdoor electrical distribution with advanced technology Merlin Gerin low voltage,

More information

CABINETS AND ENCLOSURES. XL³ 400 and XL³ 800 GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES

CABINETS AND ENCLOSURES. XL³ 400 and XL³ 800 GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES O S O O CABINETS AND ENCLOSURES XL³ 400 and XL³ 800 GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES II With its extensive ranges, the Legrand offer meets your quality standards and

More information

Compact System NRGS 11-2 NRGS Original Installation Instructions English

Compact System NRGS 11-2 NRGS Original Installation Instructions English Compact System NRGS 11-2 NRGS 16-2 EN English Original Installation Instructions 810366-05 1 Contents Important Notes Page Usage for the intended purpose...4 Safety note...4 LV (Low Voltage) Directive

More information

TGI Vacuum Circuit-Breaker Air isolator Earthing switch

TGI Vacuum Circuit-Breaker Air isolator Earthing switch TGI Vacuum Circuit-Breaker Air isolator Earthing switch PATENT Versatile Visible isolation Simple Removable Index 3 in 1 2 Simple and versatile 4 Operations sequence ON Commissioning 8 Operations sequence

More information

RESIDUAL CURRENT CIRCUIT BREAKER

RESIDUAL CURRENT CIRCUIT BREAKER Quality Features Mid Trip - Different knob position to indicate whether the device is Switched OFF by a fault or Switched OFF manually Inscription Window - Ensures circuit identification and hence reduces

More information

DX³ RCCBs - ID 4P up to 100 A

DX³ RCCBs - ID 4P up to 100 A 87045 LIMOGES Cedex Telephone number: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 DX³ s - ID CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation - Connection...

More information

School of Electrical and Information Engineering. ELEC High Voltage. University of Sydney. Dr Keith Mitchell. Engineering

School of Electrical and Information Engineering. ELEC High Voltage. University of Sydney. Dr Keith Mitchell. Engineering University of Sydney School of Electrical and Information Engineering Dr Keith Mitchell ELEC 5205 - High Voltage Engineering ELEC 5205 - High Voltage Engineering 3. Switchgear Types of Power System Switchgear

More information

Functions provided by measuring relays in railway equipment

Functions provided by measuring relays in railway equipment Functions provided by measuring relays in railway equipment 1-Current relays -Minimum current relays (During normal operation, if the current is present these relays are in operating position and switch

More information

University of Houston Master Construction Specifications Insert Project Name

University of Houston Master Construction Specifications Insert Project Name SECTION 26 13 13 MEDIUM VOLTAGE SWITCHGEAR PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General

More information

MARTINDALE INSTRUCTIONS ELITE FUSE FINDER KIT ELECTRIC. Trusted by professionals. 4.4 Storage Conditions

MARTINDALE INSTRUCTIONS ELITE FUSE FINDER KIT ELECTRIC. Trusted by professionals. 4.4 Storage Conditions 4.4 Storage Conditions The FD650/R and FD500/T or FD600/T should be kept in warm dry conditions away from direct sources of heat or sunlight, with the battery removed and in such a manner as to preserve

More information

User s Manual. ACS550-CC Packaged Drive with Bypass Supplement for ACS550-01/U1 Drives User s Manual

User s Manual. ACS550-CC Packaged Drive with Bypass Supplement for ACS550-01/U1 Drives User s Manual User s Manual ACS550-CC Packaged Drive with Bypass Supplement for ACS550-01/U1 Drives User s Manual ii ACS550-CC Packaged Drive with Bypass ACS550 Drive Manuals GENERAL MANUALS ACS550-01/U1 Drives User's

More information

Vacuum Circuit-Breakers, Type HVX kv, of cassette design, cassette with motor drive

Vacuum Circuit-Breakers, Type HVX kv, of cassette design, cassette with motor drive Vacuum Circuit-Breakers, Type HVX 12 24 kv, of cassette design, cassette with motor drive Operating Instructions No. 531 321, Edition 09/00 Table of Contents 1 General 4 1.1 Operating Conditions 4 2 Design,

More information

Air-insulated switchgear UniGear type ZS1

Air-insulated switchgear UniGear type ZS1 Air-insulated switchgear UniGear type ZS1 ABB Power Technologies / 1-7074 D 12-03-2003 - Air-insulated switchgear UniGear type ZS1 ABB Power Technologies / 2-7075 D 1 2-03-2003 - Rated voltage kv 12 17.5

More information

DT-6C MEDIUM VOLTAGE SWITCHGEAR COMPACT RING MAIN UNIT. User Manual: DT-6C / DT-6+ C

DT-6C MEDIUM VOLTAGE SWITCHGEAR COMPACT RING MAIN UNIT. User Manual: DT-6C / DT-6+ C DT-6C MEDIUM VOLTAGE SWITCHGEAR COMPACT RING MAIN UNIT User Manual: DT-6C / DT-6+ C SGC - SwitchGear Company nv. - Moorstraat 24 - B-9850 Nevele - Belgium +32 (0)9/321.91.12 - Fax +32 (0)9/321.91.13 -

More information

Installation manual portable distributors

Installation manual portable distributors EN Installation manual portable distributors EN 60003206 Issue 11.2016 15/11/2016 Table of contents 1 About this manual 3 1.1 Structure of the warnings 3 1.2 Symbols used 4 1.3 Signal words used 4 2 Intended

More information

ATyS d M Remotely operated Transfer Switching Equipment from 40 to 160 A

ATyS d M Remotely operated Transfer Switching Equipment from 40 to 160 A ATyS d M Remotely operated Transfer Switching Equipment Transfer switches new The solution for > Applications with an external ATS/AMF controller > Building Management Systems (BMS) atys-md_002_b_1_cat

More information

, , PREPARATION - CONNECTION. Mounting:. On symmetrical EN rail or DIN 35 rail

, , PREPARATION - CONNECTION. Mounting:. On symmetrical EN rail or DIN 35 rail 87045 LIMOGES Cedex Telephone number: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 DX 3 4500 A / 6 ka CONTENTS PAGES 1. Description, use...1 2. Range...1 3. Overall dimensions...1 4. Preparation - Connection...1

More information

Steve Summers Region Sales Manager

Steve Summers Region Sales Manager Steve Summers Region Sales Manager Institute For Animal Healthcare LV Switchgear Package Package Subs LV Switchboards PDU s LV sub Distribution MCC s MV Switchgear Established in 1972 manufacturing control

More information