1 SM6 Anglais MV distribution factory built assemblies at your service instructions for use DMVL cubicle

2 foreword... 3 symbols and conventions... 3 as per iso contact the Schneider Electric service unit for diagnosis and advice 3 4 distribution rules... safety rules general description... 5 DMVL : circuit--- breaker cubicle... 5 version DMVL--- A with EVOLIS circuit--- breaker... 5 handling instructions... 7 identification of the device... list and number of bags of accessories overall dimensions/weight... handling by slings handling by forks... handling storage... 9 installation and operation recommendation installation instructions preparingthecubiclebeforeassemblingtheswitchboard fitting the end plate assembling the switchboard... ground fastening installation of the switchboard in the substation fittingthebusbarafterinstallationofthecubiclesintheirfinalposition fitting the earth busbar access to the LV auxiliaries connection... ConnectionofMVcablesinaDMVL---A commissioning and operating instructions checking prior to energisation voltage presence checking phase balance... position of line disconnector operating lever circuit --- breaker off --- load operations... energisation of the downstream part of the installation de---energisation of the downstream part of the installation... operating safety padlocking devices... key --- locking maintenance instruction preventive maintenance, cleaning instructions and power---up fault / solution table... options spare parts... spare parts and options recovery of SF6 gas at end of life AAV55927 revision : 02 1

3 2 AAV55927 revision : 02

4 foreword symbols and conventions Caution: you will find all the symbols below throughout the document, indicating the hazard levels depending on the different types of situation. DANGER as per iso DANGER: failure to follow this instruction will result in death or serious injury. WARNING as per iso WARNING: failure to follow this instruction may result in death or serious injury. CAUTION as per iso CAUTION: failure to follow this instruction may result in injuries. This alert signal can also be used to indicate practices that could damage the SM6 unit. INFORMATION-ADVICE We draw your attention to this specific point. AAV55927 revision : 02 3

5 contact the Schneider Electric service unit for diagnosis and advice Call your sales representative who willputyouincontactwith the closest SCHNEIDER ELECTRIC group service centre. You can log on to: electric.com distribution rules The aim of this publication is to enable the SM6 unit to be installed correctly. This document is not a commercial document. It is a strictly technical document drawn up by Schneider Electric. safety rules CAUTION WARNING All the operations described below must be performed in compliance with applicable safety standards, under the responsibility of a competent authority. Thecontractormustbecertified and authorised to manipulate and perform work on the SM6 unit. CAUTION Only undertake the work after having read and understood all the explanations given in this document. If you have any difficulty complying with these rules, please contact Schneider Electric. 4 AAV55927 revision : 02

6 general description DMVL : circuit---breaker cubicle 1 : top busbar compartment 2 : monitoring compartment 3 : switchgear compartment: line disconnector 4 : control compartment 5 :bottombusbarorcable connection compartment A :earthbusbar connection pad B :topbusbar connection pads C : inspection viewports D :EVOLIStypeMV circuit --- breaker E : front panel N : rear extension plate N A 1 B 3 5 D 2 4 C E version DMVL --- A with EVOLIS circuit --- breaker (front panel removed) F : voltage presence indicator G : current transformers H : capacitive dividers J : downstream earthing switch K : MV cable connection pads L : circuit---breaker control plate M :specificsensors F G K L H J AAV55927 revision : 02 5

7 6 AAV55927 revision : 02

8 handling instructions identification of the device A : information plate B : characteristics and description C : rating plate Note: the circuit--- breaker characteristics are given on the latter. Serial number D1: riveted on the command cover D2: stuck behind the control covers D3: stuck on the frame upright 1 B A D1 D2 D3 D2 B C 1 1 : manual number list and number of bags of accessories supplied with the cubicle switchboard packing: (if necessary as per switchboard composition) 1operatinglever 2endplates 1bagofS4endplatescrews: Packing DMVL-- A (1--cable version): 1 bag of inter---cubicle connections S1: drycableflanges, cable version 3 flange supports, cable version 1bagofscrews S7: earth busbars 6 tinned bars 2 bags of busbars distribution blocks u12 kv S2: or 2 bags of busbar fasteners 12kV S6: phase --- to --- phase insulators with 8O ringseals(onlyfor25ka version) Packing DMVL-- A (2--cable version): 1 bag of inter---cubicle connections S1: drycableflanges, cable version 3 flange supports, cable version 1bagofscrews double cable earthbusbars 6 tinned bars 2 bags of busbar distribution blocks u12 kv S2: or 2 bags of busbar fasteners 12kV S6: phase --- to --- phase insulators with 8O ringseals(onlyfor25ka version) AAV55927 revision : 02 7

9 overall dimensions/weight average weight of an equipped cubicle: 400kg L1 L2 L handling by slings The handling lugs are reserved solely for handling of SM6 cubicles C Schneider Electric A : HM12 screws and nuts B : Schneider Electric SWL = 400 KG CE D CMU =400 KG CE Schneider Electric CMU =400 KG CE SWL: safe working load WARNING A B C : In case of deformation of holes (ovalisation) replace the lugs. L 60 max L L = 1130 mm min. Without compartment or trunking. L = 750 mm min. With compartment or trunking. 8 AAV55927 revision : 02

10 handling by forks handling CAUTION Do not handle the cubicle from the control front plate. storage 70 C C AAV55927 revision : 02 9

11 10 AAV55927 revision : 02

12 installation and operation recommendation ageing withstand of switchgear in an MV substation depends on 3 main factors: H The need for proper implementation of connections: the new cold slip---on or retractable technologies offer an ease of installation that promotes long---term withstand. Their design allows operation in polluted environments with harsh atmosphere. H Ventilation control: grid dimension must be appropriate to the power lost in the substation. These grids must be placed solely near the transformer to avoid circulation of air on the MV switchboard. H Incidence of the relative humidity factor: installation of heating resistors is essential in climates with a high degree of relative humidity and with large temperature differences. operation Our service centre is at your disposal at all times: H To carry out an installation diagnostic. H To propose if necessary appropriate servicing operations. H To propose maintenance contracts. H To propose adaptations. AAV55927 revision : 02 11

13 12 AAV55927 revision : 02

14 installation instructions preparing the cubicle before assembling the switchboard Delivery status: --- circuit --- breaker open --- line disconnector in earth position screw + washer screw + washer + nylstop nut C Remove the front panel B by lifting it up and pulling it forwards. Remove the tab C. (screws cannot be re---used) B Unscrew the four fixing screws on the covers of the monitoring compartment D and remove the compartment. D E F F Remove the 2 ½ cross---members E on the monitoring compartment (cubicle without LV compartment) Remove the 2 parts F and F. (12 screws) G H H Remove the 2 parts G. (cubicle without LV compartment, 12 screws) Remove the 2 or 4 handling parts H. AAV55927 revision : 02 13

15 fitting the end plate Refer to the switchboard parcel manual, as per the upgrade of the new standard IEC assembling the switchboard bag of screws S1: (HM 6x16 screws) M K L screw + washer + nut P top view K L Fix the cubicles to one another. The remaining screws are provided for mounting the earth busbar. Bolt mounting direction: K :leftcubicle L : right cubicle M : join up the 2 cubicles HM6x60 screws to be slightly tightened Tightening torque: 6 Nm. Remove the wiring shield N. Fit the assembling screw P on the switchboard (caution with LV wires). Put back the wiring shield. N ground fastening (screws to be provided by the contractor according to civil engineering) ,3x12,3 Do not fit any fixing screws on the ground on the circuit--- breaker side AAV55927 revision : 02

16 installation of the switchboard in the substation 140 mm DMVL --- A DMVL --- A 21,5 à 100 mm 21,5 à 100mm Installation of the switchboard to the right of the wall. (minimum dimension to ensure proper operation of the device) Installation of the switchboard to the left of the wall. fitting the busbar after installation of the cubicles in their final position general Bags of accessories: S2: or S6: Tools: 1x1to50Nmtorquewrench. 1x1/ /8 reduction gear. 1x6 mm socket end piece. 1x6 mm male hexagon socket or 1 female hexagon socket. Version 12 KV S6: Mounting without field distributor. Version > 12 KV S2: Correct position of the field distributor Incorrect position, risk of damage. AAV55927 revision : 02 15

17 Top busbar of a DMVL --- A Note: the spacers must only be installed for version 25 ka and on the part of the busbar located between the line disconnector and the busbar compartment insulators. bar A Spacer cross---sectional view Install the two spacers so that they are centred on the part of the busbar. Fitoneachsideofthe phase --- to --- phase spacer two O ring seals A. DMVL --- A Busbar mounting. Tightening torque: 28 Nm. 16 AAV55927 revision : 02

18 screw + washer screw + washer + nylstop nut F F Put back the two front roofs. Put back the 2 parts F and F. fitting the earth busbar Bag of screws S1: The earth busbars are connected to one another (HM 8x30 screws). 2 ways of earthing the substation frames. AAV55927 revision : 02 17

19 access to the LV auxiliaries connection screw + washer A B C The cables at the connection terminal block are accessed via the openings A. B : own current protection relay of the statimax. type (for setting, refer to the relay manual). C : user connection terminal block. After connection, put back the two ½ cross---members on the monitoring compartment. (cubicle without LV compartment) But back the covers on the monitoring compartment. Connection of MV cables in a DMVL --- A (1 cable) bag of screws S7: AV Disassemble the plinth. (4 screws) Disassemble the bottom plates. Fit the cable flanges on 3 bottom plates 1, 2 and 3. HM6X16 screws. (the remaining screws are provided for cable flanging). 18 AAV55927 revision : 02

20 2 3 Note: plates 2 and 3 must be fixed as shown above. Fit the first bottom plate (phase L1) behind the cubicle. Install the grommet. Cubicle DMVL--A with EVOLIS circuit --- breaker. Connection of cable phase 1 Tightening torque: 50 Nm. Flangethefirstcableandfitthe second bottom plate. (HM8x50 screws) Mount phases L2 and L3 following the same instructions as phase L1. Fix the cable earthing braids to the earth busbar. AAV55927 revision : 02 19

21 Connection of MV cables in a DMVL --- A (2 cables) bag of screws: S7: AV Disassemble the plinth. (4 screws) Disassemble the bottom plates. Fit the cable flanges on 3 bottom plates 1, 2 and 3. HM6X16 screws. (the remaining screws are provided for cable flanging) 2 3 Note: plates 2 and 3 must be fixed as shown above. Fit the first bottom plate (phase L1) behind the cubicle. 20 AAV55927 revision : 02

22 Install the grommet. Cubicle DMVL--A with EVOLIS circuit --- breaker. Connection of cable phase 1. Tightening torque: 50 Nm. Flangethefirstcableandfitthe second bottom plate. (HM8x50 screws). Mount phases L2 and L3 following the same instructions as phase L1. Fix the cable earthing braids to the earth busbar. AAV55927 revision : 02 21

23 22 AAV55927 revision : 02

24 commissioning and operating instructions checking prior to energisation Do not leave anything in the connection compartment. Putbackthefrontpanel. voltage presence VIPS: Voltage Presence Indicating System Incoming cubicle: On energisation of the upstream part of the installation, the voltage presence indicator lamps must light up. Outgoing cubicle: Once the line disconnector and then the circuit---breaker have been moved to the closed position, the voltage presence indicator lamps must light up. checking phase balance Note: the monitoring device is the same as that used by the RM6 equipment. Note: In event of monitoring between the old Voltage Presence Indicator and the new VPIS use the adapter, references FA Simplified type phase comparator. In phase balance: H the comparator lamp does not light up. H In phase unbalance: the comparator lamp lights up. AAV55927 revision : 02 23

25 position of line disconnector operating lever Position the lever as shown, for downward opening operations. Position the lever as shown, for upward closing operations. circuit --- breaker off --- load operations I O initial status: The line disconnector is in the open or earth position. The circuit---breaker is locked in the open position. B E 0 C Lock the lever entry E of the line disconnector with the wrench in B. Remove the wrench in B then place it in C. Release then charge the circuit --- breaker. (see the circuit--- breaker manual) I O I O O I Close the circuit---breaker by pressing the pushbutton I. Open the circuit--- breaker by pressing the pushbutton O. 24 AAV55927 revision : 02

26 I O 0 C B E Lock the circuit---breaker in the open position in C by pressing the pushbutton O. Remove the wrench in C and place it in B. Release the lever entry E ofthelinedisconnector. energisation of the downstream part of the installation initial status: The line disconnector is in the earth position. The circuit---breaker is locked in the open position. The front panel is in place. A E Movethelinedisconnectortothe open position using the operating lever. Note: for a DMVL--A, the downstream earthing switch opens simultaneously. Move the line disconnector to the closed position then lock the entry E of the line disconnector with the wrench in A. I O I O 0 O C Remove the wrench in A, placeit in C and release the circuit --- breaker. Charge the latter. (see the circuit--- breaker manual) Close the circuit---breaker by pressing on pushbutton I. The downstream part of the installation is energised. AAV55927 revision : 02 25

27 de---energisation of the downstream part of the installation I I initial status: The line disconnector is in the closed position. The circuit--- breaker is closed. O I O 0 C Open the circuit--- breaker by pressing the pushbutton O. Lock the circuit---breaker in the open position with the wrench in C by pressing the pushbutton O. A E Remove the wrench in C and place it in A. Release the lever entry E ofthelinedisconnector. Movethelinedisconnectortothe open position. Move the line disconnector to the earth position. The front panel can be removed. Note: for a DMVL--A, the downstream earthing switch closes simultaneously. 26 AAV55927 revision : 02

28 operating safety Operationimpossiblewhenthe circuit---breaker is closed. The front panel can only be removed or fitted when the line disconnector is in the earth position. Line disconnector in the open or closed position. It is impossible to remove the front panel. Once the front panel has been removed, you can move the line disconnector to the open position. However,youcannotmoveitto the closed position. padlocking devices From 1 to 3 Ø 8 mm padlocks per padlocking point. Padlocking the line disconnector in the earth position. Padlocking the line disconnector in the open position. Padlocking the line disconnector in the closed position. Padlocking the front panel (a single padlock). AAV55927 revision : 02 27

29 key --- locking (optional) H refer to the locking installation and operation manual no H for installation of a key--- lock on the circuit---breaker, refer to the relevant device manual. H if the key---lock option was not provided on ordering, contact the Schneider Electric group service centre. 28 AAV55927 revision : 02

30 maintenance instruction preventive maintenance, cleaning instructions and power --- up If necessary: contact the Schneider Electric group service centre. We strongly recommend that you carry out at regular intervals (at least roughly every 2 years) afew operating cycles on the switching devices. CAUTION Never lubricate the disconnector operating mechanism. If necessary: contact the Schneider Electric group service centre. In normal operating conditions (temperature between C and40 C) no special maintenance is required. CAUTION Never use solvents and alcohol. We recommend that you inspect each compartment (cable, fuse, busbar)* at regular intervals according to environmental conditions. If the insulating parts are dusty, that you remove the dust using a dry cloth. example : In harsher conditions (aggressive atmosphere, dust, temperature less than C or greater than 40 C) consult the nearest Schneider Electric service centre. AAV55927 revision : 02 29

31 fault / solution table H the voltage presence indicator does not light up H check the voltage presence indicator H check that the line disconnector and the circuit--- breaker are closed (for an outgoing cubicle) H check that the incoming cables are energised H the front panel does not open or cannot be placed H check that the line disconnector is in the earth position H impossible to move the line disconnector to the earth H check that the line disconnector is in the open position position H impossible to move the line disconnector to the closed H check that the line disconnector is in the open position position H impossible to operate the circuit---breaker H see circuit--- breaker manual H accidental manual closure of the downstream earthing disconnector arm H re---open the downstream earthing disconnector by operating the contact---holder arm, then re--- initialise the system using a screwdriver to insert the operating lever. options (consult us) H auxiliary contacts on disconnector. H monitoring compartment. H protection by statimax relay or by SEPAM programmable electronic unit. H H 1 to 3 voltage transformers. key --- locks. heating element. spare parts H voltagepresenceindicator. (for other actions, consult us: see the nearest Schneider Electric group service centre). spare parts and options H Voltagepresenceindicator. H CIT operating mechanism. H 48Vdc operating kit. H Fuses. (for other actions, consult us: see the Schneider Electric group service centre) 30 AAV55927 revision : 02

32 recovery of SF6 gas at end of life for disconnector cubicle The SF6 must be removed before any dismantling operation can be carried out in compliance with the procedures described in IEC and according to the following instructions. The gas must be treated in compliance with IEC H volume of gas to be recovered: 35 litres H internal gauge pressure: 40 kp A Remove the cover (A) from the control cabinet. control cover access B Remove the control cover (B). Remove the 3 screws retaining the operating mechanism. Cut the wiring to remove the operating mechanism. Drill 2 holes in the filler valve safety cap 4 mm, centreline 20 mm, max. depth 4 mm AAV55927 revision : 02 31

33 CAUTION pump the gas for at least 15 minutes. C Using a spanner wrench, remove the safety cap from the valve. Connect the special pumping equipment (C). 32 AAV55927 revision : 02

34 group Schneider Electric service centers are there for: engineering and technical assistance start-up training preventive and corrective maintenance adaptation work spare parts Call your sales representative who will put you in touch with your nearest group Schneider Electric service centers. Schneider Electric Industries SAS 89, boulevard Franklin Roosevelt F Rueil--- Malmaison (France) Tel:+33(0) electric.com AAV55927 revision : 02 As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication. Conception, rédaction: Service Documentation Technique T&D Edition du : 19/05/2008

SM6. instructions for use. GAM cubicle (1250A) MV distribution factory built assemblies at your service. Anglais

SM6. instructions for use. GAM cubicle (1250A) MV distribution factory built assemblies at your service. Anglais SM6 Anglais MV distribution factory built assemblies at your service instructions for use GAM cubicle (1250A) foreword... 3 symbols and conventions... 3 as per iso 3864---2... contact the Schneider Electric

More information

SM6. instructions for use. SM cubicle. MV distribution factory built assemblies at your service. Anglais

SM6. instructions for use. SM cubicle. MV distribution factory built assemblies at your service. Anglais SM6 Anglais MV distribution factory built assemblies at your service instructions for use SM cubicle foreword... 3 symbols and conventions... 3 as per iso 3864---2... contact the Schneider Electric service

More information

SM6. instructions for use. IMB cubicle without earthing switch. MV distribution factory built assemblies at your service. Anglais

SM6. instructions for use. IMB cubicle without earthing switch. MV distribution factory built assemblies at your service. Anglais SM6 Anglais MV distribution factory built assemblies at your service instructions for use IMB cubicle without earthing switch foreword... 3 symbols and conventions... 3 as per iso 3864---2... contact the

More information

SM6. instructions for use. QMB cubicles. MV distribution factory built assemblies at your service. Anglais

SM6. instructions for use. QMB cubicles. MV distribution factory built assemblies at your service. Anglais SM6 Anglais MV distribution factory built assemblies at your service instructions for use QMB cubicles foreword... 3 symbols and conventions... 3 as per iso 3864---2... contact the Schneider Electric service

More information

SM6. instructions for use. DMV S cubicle. MV distribution factory built assemblies at your service. Anglais

SM6. instructions for use. DMV S cubicle. MV distribution factory built assemblies at your service. Anglais SM6 Anglais MV distribution factory built assemblies at your service instructions for use DMV S cubicle foreword... 3 symbols and conventions... 3 as per iso 3864---2... contact the Schneider Electric

More information

SM6. instructions for use. IMCandQMCcubicles. MV distribution factory built assemblies at your service. Anglais

SM6. instructions for use. IMCandQMCcubicles. MV distribution factory built assemblies at your service. Anglais SM6 Anglais MV distribution factory built assemblies at your service instructions for use IMCandQMCcubicles foreword... 3 symbols and conventions... 3 as per iso 3864---2... contact the Schneider Electric

More information

SM6. instructions for use. DM1 S cubicle. MV distribution factory built assemblies at your service. Anglais

SM6. instructions for use. DM1 S cubicle. MV distribution factory built assemblies at your service. Anglais SM6 Anglais MV distribution factory built assemblies at your service instructions for use DM1 S cubicle foreword... 3 symbols and conventions... 3 as per iso 3864---2... contact the Schneider Electric

More information

SM6. instructions for use. DMV A---DMV D cubicle (1250A range) MV distribution factory built assemblies at your service. Anglais

SM6. instructions for use. DMV A---DMV D cubicle (1250A range) MV distribution factory built assemblies at your service. Anglais SM6 Anglais MV distribution factory built assemblies at your service instructions for use DMV A---DMV D cubicle (1250A range) foreword... 3 symbols and conventions... 3 as per iso 3864---2... contact the

More information

Information for the modified document

Information for the modified document Information for the modified document émetteur : Esref OZYUZUCULER date :03-05 - 2001 Recipient SM6 --- 36kV STT KG K ToK FaZ OrY MRK(TR) E&S S OyR MeM er Number : 7897176EN Index : D0 Product : SM6-36

More information

Medium Voltage Distribution FBX. Assembling a 1250A busbar Instructions.

Medium Voltage Distribution FBX. Assembling a 1250A busbar Instructions. Medium Voltage Distribution FBX Assembling a 1250A busbar Instructions www.schneider-electric.com Contents Introduction... 3 Our Service Unit: our specialists, and suitably adapted services...... 3 Overview...

More information

circuit breaker instructions for use SF draw --- out circuit---breakers in F400 MV distribution circuit breaker Anglais at your service

circuit breaker instructions for use SF draw --- out circuit---breakers in F400 MV distribution circuit breaker Anglais at your service circuit breaker Anglais MV distribution circuit breaker at your service instructions for use SF draw --- out circuit---breakers in F400 foreword... 3 symbols and conventions... 3 as per iso 3864---2...

More information

MCset 4-24 kv Withdrawable SF6 circuit breaker

MCset 4-24 kv Withdrawable SF6 circuit breaker Medium Voltage switchgear MCset 4-24 kv Withdrawable SF6 circuit breaker Instruction for use Contents General 2 Glossary 2 Symbols 2 Recommendations 3 General description 4 AD4 unit 4 AD4 unit with toroidal

More information

MCset kv Medium voltage equipment

MCset kv Medium voltage equipment Maintenance Guide PE90014 PE90006 MCset 1-2 - 3 17.5 kv Medium voltage equipment Air-insulated switchboards Metal-enclosed switchgear with moving parts PE90007 PE90008 PE90009 PE90007 Maintenance Guide

More information

Medium voltage NEX switchgear Withdrawable circuit breaker. Quite simply efficient

Medium voltage NEX switchgear Withdrawable circuit breaker. Quite simply efficient Medium voltage NEX switchgear Withdrawable circuit breaker Quite simply efficient NEX, a simple and flexible solution NEX is the result of worldwide acquired experience and provides you with a high level

More information

circuit-- breaker instructions for use SF1 fixed or in SM6 circuit --- breaker MV distribution circuit breaker at your service Anglais

circuit-- breaker instructions for use SF1 fixed or in SM6 circuit --- breaker MV distribution circuit breaker at your service Anglais circuit-- breaker Anglais MV distribution circuit breaker at your service instructions for use SF1 fixed or in SM6 circuit --- breaker foreword... 3 symbols and conventions... 3 as per iso 3864---2...

More information

MCset 17.5 kv. Civil engineering guide April Medium Voltage Distribution

MCset 17.5 kv. Civil engineering guide April Medium Voltage Distribution Medium Voltage Distribution MCset 17.5 kv ir insulated switchboard Withdrawable switchgear SF6 or vaccum technology Civil engineering guide pril 2012 Contents General 2 Glossary 2 Dimensions and weights

More information

AIR INSULATED METAL ENCLOSED SWITCHGEAR AND CONTROLGEAR

AIR INSULATED METAL ENCLOSED SWITCHGEAR AND CONTROLGEAR AIR INSULATED METAL ENCLOSED SWITCHGEAR AND CONTROLGEAR ANGLER SWITCHING DEVICES CONTENTS 1. General 2. Switchgear Types - Switch Disconnector - Disconnector 3. Cubicle Types - Cubicle with Switch Disconnector

More information

0MV vacuum circuit breaker. 0Evolis 24 kv. 0User 0Manual. Creation Printed on 2008/07/17

0MV vacuum circuit breaker. 0Evolis 24 kv. 0User 0Manual. Creation Printed on 2008/07/17 0MV vacuum circuit breaker 0Evolis 24 kv 0User 0Manual 02008 07897530EN-C0.book Page 1 Jeudi, 15. mai 2008 11:34 11 Contents Evolis description 2 Front view circuit breaker 2 Front view lateral circuit

More information

CBGS-0. Medium voltage distribution

CBGS-0. Medium voltage distribution Medium voltage distribution CBGS-0 Gas Insulated metal-enclosed Switchgear SF6 circuit breaker technology Up to 24/36 kv - 1250/1600/2000 A - 25/31.5 ka Transmission Wind Airports Oil & Gas Mining & Distribution

More information

NEX - 24 kv Withdrawable Circuit Breaker

NEX - 24 kv Withdrawable Circuit Breaker Air Insulated Medium Voltage Equipment NEX - 24 kv Withdrawable Circuit Breaker Installation drawings file Contents bj Fitting the upper main busbars 1250 A busbar - 800 mm cubicle Assembly 1250 A busbar

More information

SFset with VIP 400/410 built-in control unit Medium Voltage Circuit Breaker

SFset with VIP 400/410 built-in control unit Medium Voltage Circuit Breaker SFset with VIP 400/410 built-in control unit Medium Voltage Circuit Breaker Instructions for use 07897543EN01 Rev.04 11/2017 SFset- Instructions for use Table of contents Presentation Presentation...

More information

PIX. Operation - Replacement of Fuses Replacement of Voltage Transformers Technical manual. Medium Voltage Distribution

PIX. Operation - Replacement of Fuses Replacement of Voltage Transformers Technical manual. Medium Voltage Distribution Medium Voltage Distribution PIX Withdrawable Voltage Transformer Operation - Replacement of Fuses Replacement of Voltage Transformers Technical manual Nr. Edition 11/2011 www.schneider-electric.com Schneider

More information

CGMCOSMOS. Reliable innovation. Personal solutions. Fully gas insulated modular and compact (RMU)system.

CGMCOSMOS. Reliable innovation. Personal solutions. Fully gas insulated modular and compact (RMU)system. MV Switchgear for CGMCOSMOS Fully gas insulated modular and compact (RMU)system Up to 24 kv Up to 27 kv mediumvoltage mediumvoltageag AG Langackerstrasse Langackerstrasse 25 25 CH CH 6330 6330 Cham Cham

More information

GHA. Gas-Insulated Switchgear. Gas-Insulated Switchgear. Switchgear extension and replacement of a panel

GHA. Gas-Insulated Switchgear. Gas-Insulated Switchgear. Switchgear extension and replacement of a panel Gas-Insulated Switchgear GHA Gas-Insulated Switchgear Switchgear extension and replacement of a panel During this work, essential parts of the switchgear remain in operation No. AGS 535 066-01 Edition

More information

circuit breakers instructions for use SF2 fixed MV distribution circuit breaker at your service Anglais

circuit breakers instructions for use SF2 fixed MV distribution circuit breaker at your service Anglais circuit breakers nglais MV distribution circuit breaker at your service instructions for use SF2 fixed foreword... 3 symbols and conventions... 3 as per iso 3864---2... contact the Schneider lectric service

More information

Secondary Distribution Switchgear FBX. SF6 Gas-insulated switchboards CB function. Instructions Installation - Commissioning Operating - Maintenance

Secondary Distribution Switchgear FBX. SF6 Gas-insulated switchboards CB function. Instructions Installation - Commissioning Operating - Maintenance Secondary Distribution Switchgear FBX SF6 Gas-insulated switchboards CB function Instructions Installation - Commissioning Operating - Maintenance Contents 1 Schneider Electric at your service... 1 1.1

More information

Medium Voltage Distribution Maintenance Guide I 2013 Premset. 15 kv compact modular vacuum switchgear with Shielded Solid Insulation System

Medium Voltage Distribution Maintenance Guide I 2013 Premset. 15 kv compact modular vacuum switchgear with Shielded Solid Insulation System Medium Voltage Distribution Maintenance Guide I 2013 Premset 15 kv compact modular vacuum switchgear with Shielded Solid Insulation System Schneider Electric Services, by your side all day long Installation

More information

Secondary Distribution Switchgear FBX. SF6 Gas-insulated switchboards. Instructions Operation - Maintenance

Secondary Distribution Switchgear FBX. SF6 Gas-insulated switchboards. Instructions Operation - Maintenance Secondary Distribution Switchgear FBX SF6 Gas-insulated switchboards Instructions Operation - Maintenance Contents 1 Schneider Electric at your service................... 1 1.1 Our Service Unit: our specialists,

More information

SFset with VIP 400/410 built-in control unit Medium Voltage Circuit Breaker

SFset with VIP 400/410 built-in control unit Medium Voltage Circuit Breaker SFset with VIP 400/410 built-in control unit Medium Voltage Circuit Breaker Instructions for use 11/2017 18 0 2 ing A r p s e l b a l i va SFset- Instructions for use Table of contents Presentation Presentation...

More information

I B D Q I B D Q O I B D Q O

I B D Q I B D Q O I B D Q O Extension offer: new possible combinations 2 and 3 functions RM6 free combination: offers all types of configurations which fit to every application. Free choice: type of each functional unit. Free choice:

More information

CPG.0 Single busbar gas-insulated cubicles

CPG.0 Single busbar gas-insulated cubicles MV Switchgear Primary Distribution CPG.0 Single busbar gas-insulated cubicles Up to 36 kv CPG System The quality of products designed, manufactured and installed by Ormazabal is underpinned by the implementation

More information

The Key Link for all your Distributions Needs. A Comprehensive Range for All Your Needs

The Key Link for all your Distributions Needs. A Comprehensive Range for All Your Needs [ MV Air-insulated Switchgear Range ] 1 PIX CUSTOMER BENEFITS Compact, versatile and highly reliable designs Choice of vacuum or SF6 switching technology Wide range of applications Enhanced operator safety

More information

PIX-H Metal-clad switchgear up to 17.5kV

PIX-H Metal-clad switchgear up to 17.5kV AIR INSULATED SWITCHGEAR PIX-H Metal-clad switchgear up to 17.5kV for high rated applications Technical Specifications AREVA T&D Summary - Technical description... 3 - Standards... 6 - PIX in detail...

More information

MNS Light F. Low-voltage switchgear with fixed units. ABB LV Systems

MNS Light F. Low-voltage switchgear with fixed units. ABB LV Systems MNS Light F Low-voltage switchgear with fixed units ABB LV Systems Cubicle design MNS Light F switchgear is a flexible system with a large selection of cubicle variants that can be built together in optional

More information

Evolis offer Merlin Gerin

Evolis offer Merlin Gerin Medium voltage distribution Evolis offer Merlin Gerin Installation guide 200757a General contents Evolis circuit breaker full version 3 Circuit breaker installation 3 Cradle installation and earthing 3

More information

Cloud-connected solution for utility-scale renewable power

Cloud-connected solution for utility-scale renewable power Cloud-connected solution for utility-scale renewable power Conext SmartGen TM Power System Global power conversion system for the next generation of PV and Energy Storage power plants connected to smart

More information

SF6 Load Break Switch 2017 FIL3 - S. Indoor Medium Voltage LBS With or without fuse 12kV- 24kV FIL3 D FIL3. 24KV SF6 Load Break Switch

SF6 Load Break Switch 2017 FIL3 - S. Indoor Medium Voltage LBS With or without fuse 12kV- 24kV FIL3 D FIL3. 24KV SF6 Load Break Switch FIL3 - S FIL3 D Indoor Medium Voltage LBS With or without fuse 12kV- 24kV FIL3 24KV SF6 Load Break Switch Content 1. About Us 2. Load Break Switch Introduction 3. FIL3 product overview 3.1. Advantages

More information

CABINETS AND ENCLOSURES. XL³ 400 and XL³ 800 GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES

CABINETS AND ENCLOSURES. XL³ 400 and XL³ 800 GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES O S O O CABINETS AND ENCLOSURES XL³ 400 and XL³ 800 GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES II With its extensive ranges, the Legrand offer meets your quality standards and

More information

24 kv. A brief summary of the. range

24 kv. A brief summary of the. range Medium-Voltage distribution - 24 kv Metal-enclosed withdrawable switchgears MCset4 - SF6 technology NEX24 - vacuum technology 2008 Maintenance and Services Guide October 2008 PE90002 24 kv A brief summary

More information

Low-voltage switchgear MNS Light W. Installation, handling and operation. ABB LV Systems

Low-voltage switchgear MNS Light W. Installation, handling and operation. ABB LV Systems Low-voltage switchgear MNS Light W Installation, handling and operation ABB LV Systems MNS Light W switchgear is a flexible system that is primarily designed for motor control. The rated service voltage

More information

Cloud-connected solution for utility-scale renewable power

Cloud-connected solution for utility-scale renewable power Cloud-connected solution for utility-scale renewable power Conext SmartGen TM Power System Global power conversion system for the next generation of PV and Energy Storage power plants connected to smart

More information

Electrical network protection VIP30, VIP35. User s manual 12/2008

Electrical network protection VIP30, VIP35. User s manual 12/2008 Electrical network protection VIP30, VIP35 User s manual 1/008 Safety instructions ANSI symbol. IEC symbol. Safety symbols and messages Read these instructions carefully and look at the equipment to become

More information

CPG.1 Gas insulated, single busbar cubicle range Up to 27 kv / 2000 A / 31.5 ka Up to 38 kv / 2000 A / 31.5 ka IEEE Standards

CPG.1 Gas insulated, single busbar cubicle range Up to 27 kv / 2000 A / 31.5 ka Up to 38 kv / 2000 A / 31.5 ka IEEE Standards Medium Voltage Switchgear Primary Distribution CPG.1 Gas insulated, single busbar cubicle range Up to 27 kv / 2000 A / 31.5 ka General description Presentation Ormazabal s CPG System includes the CPG.1

More information

Medium Voltage Distribution PIX. Air Insulated Switchgear up to 24 kv PARS TABLEAU

Medium Voltage Distribution PIX. Air Insulated Switchgear up to 24 kv PARS TABLEAU Medium Voltage Distribution PIX Air Insulated Switchgear up to kv PIX Air Insulated Switchgear up to kv The PIX system has been designed in accordance with international (IEC) standards, and gives an optimal

More information

Energy Australia Chamber Substation indoor switchgear. installation,operation and maintenance instructions version 1.

Energy Australia Chamber Substation indoor switchgear. installation,operation and maintenance instructions version 1. Energy Australia Chamber Substation indoor switchgear installation,operation and maintenance instructions version 1.6 / February 2009 1 Details of revision Version Comment Date 1.0 First Draft Issue May

More information

Medium Voltage Distribution PIX kv. Additional equipment Instructions.

Medium Voltage Distribution PIX kv. Additional equipment Instructions. Medium Voltage Distribution PIX 12-17.5-24 kv Additional equipment Instructions www.schneider-electric.com Contents 1 Schneider Electric at your service... 4 1.1 Your contacts... 4 2 State of delivery

More information

Galaxy VX Battery Breaker Trip Board (GVXBBTB) and Battery Breaker Capacitor Board (GVXBBCB)

Galaxy VX Battery Breaker Trip Board (GVXBBTB) and Battery Breaker Capacitor Board (GVXBBCB) Installation 990 91076 001 12/2017 Galaxy VX Battery Breaker Trip Board (GVXBBTB) and The battery breaker trip board is the interface from the battery bank to the UPS battery auxiliary inputs/outputs and

More information

CGM.3 System. Medium Voltage SF 6 gas-insulated cubicles up to 38 kv according to IEEE and CSA standards

CGM.3 System. Medium Voltage SF 6 gas-insulated cubicles up to 38 kv according to IEEE and CSA standards CGM.3 System Medium Voltage SF 6 gas-insulated cubicles up to 38 kv according to IEEE and CSA standards General Instructions IG-183-EN, version 03; 06/03/2013 Legal Deposit: BI-0272/2013 CAUTION! When

More information

UniSec Operation and maintenance manual

UniSec Operation and maintenance manual Medium voltage products UniSec Operation and maintenance manual Safety 3 For your safety! 3 Skilled personnel 3 Critical messages 3 Contact us! 3 1. Introduction 4 1.1 General aspects 4 1.2 Operation and

More information

Key features. DESIGNS: - Conservator type - Hermetically sealed

Key features. DESIGNS: - Conservator type - Hermetically sealed Package Substations OTDS manufactures a large range of oil filled hermitically sealed and conservator type transformers to be used in conjunction with our package substations. We are able to utalise the

More information

HVX Series. 36 kv Medium Voltage Vacuum circuit breaker. Make the most of your energy SM. Medium Voltage Distribution Catalogue 2015

HVX Series. 36 kv Medium Voltage Vacuum circuit breaker. Make the most of your energy SM. Medium Voltage Distribution Catalogue 2015 Medium Voltage Distribution Catalogue 205 HVX Series 36 kv Medium Voltage Vacuum circuit breaker Fixed, middle rolling and floor rolling ranges of circuit breaker and disconnector Make the most of your

More information

Schneider Electric PV Skid. Optimized solar power conversion system tailored to enhance any North American PV power plant

Schneider Electric PV Skid. Optimized solar power conversion system tailored to enhance any North American PV power plant Schneider Electric PV Skid Optimized solar power conversion system tailored to enhance any North American PV power plant 1 PV Skid solution Integrated solution designed for optimal performance in any environment

More information

NEXT STEP B) SAFETY :

NEXT STEP B) SAFETY : SUMMARY : EVOLUTION OF MV/LV SUBSTATIONS COMPACT SUBSTATIONS J. M. Solans, C. Prevé, R. Farrán, R. Muñoz. SCHNEIDER ELECTRIC S.A. - SPAIN INTRODUCTION The recent liberalisation of the electricity supply

More information

Steve Summers Region Sales Manager

Steve Summers Region Sales Manager Steve Summers Region Sales Manager Institute For Animal Healthcare LV Switchgear Package Package Subs LV Switchboards PDU s LV sub Distribution MCC s MV Switchgear Established in 1972 manufacturing control

More information

Compact NR630. NR100F to NR630F

Compact NR630. NR100F to NR630F Low voltage switchgear Compact NR NR100F NR630F The Compact NS range has revolutionised the world of moulded-case circuit breakers. For installations not requiring the high performance levels of the NS

More information

The vacuum circuit breaker for commercial buildings, industrial plants and utilities

The vacuum circuit breaker for commercial buildings, industrial plants and utilities The vacuum circuit breaker for commercial buildings, industrial plants and utilities EasyPact EXE The easy choice for more value 2 EasyPact EXE EasyPact EXE, a medium voltage vacuum circuit breaker optimizing

More information

e 2 ALPHA -2S Medium Voltage Double Busbar Switchgear K Catalogue EN

e 2 ALPHA -2S Medium Voltage Double Busbar Switchgear K Catalogue EN e 2 ALPHA -2S Medium Voltage Double Busbar Switchgear K-11.1.2 Catalogue EN We Create Ideas With Power! e 2 ALPHA-2S double busbar switchgear is designed for use in primary and secondary electric energy

More information

UniGear. Technical Guide

UniGear. Technical Guide UniGear Technical Guide CONTENTS 0 CONTENTS 1.1 Compartments 1/2 1.2 Components of the structure 1/3 1.2.1 Hot-galvanized steel sheet 1/3 1.2.2 Painted steel sheet 1/4 1.2.3 Copper 1/5 1.2.4 Insulating

More information

abb SafeLink SF 6 Insulated Ring Main Unit Installation and Operating Instructions Switchgear Division Auckland, New Zealand SLMIO ver 2.

abb SafeLink SF 6 Insulated Ring Main Unit Installation and Operating Instructions Switchgear Division Auckland, New Zealand SLMIO ver 2. Installation and Operating Instructions Switchgear Division Auckland, New Zealand SLMIO ver 2.12 Product Overview ABB's type-tested ring main unit (RMU) is an SF 6 insulated RMU utilising the latest developments

More information

TGI Vacuum Circuit-Breaker Air isolator Earthing switch

TGI Vacuum Circuit-Breaker Air isolator Earthing switch TGI Vacuum Circuit-Breaker Air isolator Earthing switch PATENT Versatile Visible isolation Simple Removable Index 3 in 1 2 Simple and versatile 4 Operations sequence ON Commissioning 8 Operations sequence

More information

STANDARDIZED LOW VOLTAGE SWITCHBOARDS UP TO 690V-6300A-100KA

STANDARDIZED LOW VOLTAGE SWITCHBOARDS UP TO 690V-6300A-100KA CB-02 STANDARDIZED LOW VOLTAGE SWITCHBOARDS UP TO 690V-6300A-100KA POWER CENTER PC MOTOR CONTROL CENTER MCC32 MOTOR CONTROL CENTER MCCF Premises 10.000mq Offices 2.000mq Warehouse 1.200mq Open Area 15.000mq

More information

Galaxy VM. Battery Breaker Box Installation 09/

Galaxy VM. Battery Breaker Box Installation 09/ Galaxy VM Battery Breaker Box Installation 09/2016 www.schneider-electric.com Legal Information The Schneider Electric brand and any registered trademarks of Schneider Electric Industries SAS referred

More information

with Vacuum Circuit Breaker HAF

with Vacuum Circuit Breaker HAF M E T A L - C L A D S W I T C H G E A R Safety and Reliability with Vacuum Circuit Breaker HAF Flexible Design and Compact with Vacuum Circuit Breaker HVF Easy Installation and Maintenance We build a better

More information

Metal Clad Switchgears

Metal Clad Switchgears SNC Series Metal Clad Switchgears > up to 36 kv Rated Voltage > up to 2500 A Rated Current > up to 40 ka Rated Short Time Withstand Current > LSC-2B, PM, AFLR > In Confirmity with IEC 62271-1, 100, 102,

More information

DPX moulded case circuit breakers

DPX moulded case circuit breakers BREAKING AND PROTECTION DEVICES 10 / 2011 DPX moulded case circuit breakers DPX moulded case circuit breakers offer optimum solutions for the protection requirements of commercial and industrial installations.

More information

LV switch-disconnectors. Interpact Merlin Gerin 40 to 2500 A. Catalogue. We do more with electricity

LV switch-disconnectors. Interpact Merlin Gerin 40 to 2500 A. Catalogue. We do more with electricity LV switch-disconnectors Catalogue Merlin Gerin 40 to 2500 A We do more with electricity LV switch-disconnectors The various low-voltage applications 2 from 40 to 2500 A 4 Compact from 80 to 1250 A 5 Masterpact

More information

Vacuum Circuit-Breakers, Type HVX kv, of cassette design, cassette with motor drive

Vacuum Circuit-Breakers, Type HVX kv, of cassette design, cassette with motor drive Vacuum Circuit-Breakers, Type HVX 12 24 kv, of cassette design, cassette with motor drive Operating Instructions No. 531 321, Edition 09/00 Table of Contents 1 General 4 1.1 Operating Conditions 4 2 Design,

More information

Operating conditions. Generalities. Normal operating conditions

Operating conditions. Generalities. Normal operating conditions Generalities Operating conditions In addition to its technical characteristics, SM6 meets requirements concerning safety of life and property as well as ease of installation, operation and protecting the

More information

Prisma Plus G enclosures IP30, IP31, IP43 enclosures

Prisma Plus G enclosures IP30, IP31, IP43 enclosures Prisma Plus G IP30, IP31, IP43 Prisma Plus G IP30, IP31, IP43 Presentation For safe and upgradeable electrical switchboards > Safety of people and property > Continuity of service > Optimization and upgradeability

More information

Medium Voltage Distribution Catalogue Flusarc Make the most of your energy

Medium Voltage Distribution Catalogue Flusarc Make the most of your energy Medium Voltage Distribution Catalogue 2012 Flusarc 40.5 Make the most of your energy Flusarc switchgear 40.5 kv - 630 A - 20 ka General contents Overview 3 General characteristics 7 Description 11 Installation

More information

Modular medium-voltage switchgear. NorMax

Modular medium-voltage switchgear. NorMax Modular medium-voltage switchgear NorMax NorMax MODULAR MEDIUM-VOLTAGE SWITCHGEAR 2 NorMax Modular medium-voltage switchgear Contents Subject Page Table of contents 2 Introduction and main features 2 Technical

More information

TX³ RCCBs 2P up to 100 A

TX³ RCCBs 2P up to 100 A 87045 LIMOGES Cedex Telephone number: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 TX³ RCCBs CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation - Connection...

More information

CGMCOSMOS Fully gas-insulated modular and compact (RMU) system Up to 24 kv

CGMCOSMOS Fully gas-insulated modular and compact (RMU) system Up to 24 kv Medium Voltage Switchgear Secondary Distribution CGMCOSMOS Fully gas-insulated modular and compact (RMU) system MV Switchgear Secondary Distribution Networks General description Introduction Ormazabal

More information

GAE MCC Modular-C. Catalogue Standardized Motor Control Centres. PT Guna Era Manufaktura

GAE MCC Modular-C. Catalogue Standardized Motor Control Centres. PT Guna Era Manufaktura Modular-C\Standardized Motor Control Centres\ M600204.15 PT Guna Era Manufaktura Catalogue 2015 GAE MCC Modular-C Standardized Motor Control Centres General Definition Type-tested low-voltage switchgear

More information

24 k B788 ELEKTROTECHNISCHE WERKE FRITZ DRIESCHER & SÖHNE GMBH

24 k B788 ELEKTROTECHNISCHE WERKE FRITZ DRIESCHER & SÖHNE GMBH 788 Instructions for Installation, Operation and Maintenance for DRIESCHER - Air - Insulated Medium - Voltage Compact Switchgears for Substations Rated voltage 12 kv and 24 kv Rated current 630 A 24 k

More information

MESG 12 / 17.5 / 24 / 36 KV

MESG 12 / 17.5 / 24 / 36 KV MESG 12 / 17.5 / 24 / 36 KV Medium Voltage Air Insulated Metal Enclosed Switchgear up to 36 kv- up to 1250 A - up to 25 ka for 1 sec. with SF6 or vacuum circuit breakers. 750 METAL ENCLOSED 1 1 ) GENERAL

More information

MEDIUM VOLTAGE CE-B METAL CLAD SWITCHBOARDS. CE - B - C - en - REV

MEDIUM VOLTAGE CE-B METAL CLAD SWITCHBOARDS. CE - B - C - en - REV MEDIUM VOLTAGE MEDIUM VOLTAGE APPLICATION CE-B Metal Clad switchboards are designed for use in public and industrial distribution system up to 24kV for the operation and protection of lines, generators,

More information

Date Issued: 10 August 2009 Status: ISSUED Review Date: 10 August 2011 Ref: NS5.3 DISTRIBUTED GENERATION TECHNICAL REQUIREMENTS TABLE OF CONTENTS

Date Issued: 10 August 2009 Status: ISSUED Review Date: 10 August 2011 Ref: NS5.3 DISTRIBUTED GENERATION TECHNICAL REQUIREMENTS TABLE OF CONTENTS Date Issued: 10 August 2009 Status: ISSUED Review Date: 10 August 2011 Ref: NS5.3 DISTRIBUTED GENERATION TECHNICAL REQUIREMENTS TABLE OF CONTENTS 1. PURPOSE AND SCOPE OF THIS DOCUMENT... 3 2. DEFINITIONS...

More information

Low voltage Direct Current Network. Compact NSX DC PV. Circuit breakers and switch disconnectors for solar application.

Low voltage Direct Current Network. Compact NSX DC PV. Circuit breakers and switch disconnectors for solar application. Low voltage Direct Current Network Compact NSX DC PV Circuit breakers and switch disconnectors for solar application Catalogue 2012 Compact NSX DC PV A complete DC offer for solar application from 80

More information

AIR INSULATED EXTENDABLE SWITCHGEAR UP TO 12KV GUIDE

AIR INSULATED EXTENDABLE SWITCHGEAR UP TO 12KV GUIDE AIR INSULATED EXTENDABLE SWITCHGEAR UP TO 12KV GUIDE Certificate Number FM35831 APPLICATION Typical Uses and Classification The MSGair switchgear is used in transformer and switching substations mainly

More information

SYSclad switchboard equipped with draw out type vacuum circuit breaker closed dooroperationoperation. SYSclad 12 17,5kV A.

SYSclad switchboard equipped with draw out type vacuum circuit breaker closed dooroperationoperation. SYSclad 12 17,5kV A. SYSclad switchboard equipped with draw out type vacuum circuit breaker closed dooroperationoperation 630 3150A SYSclad 12 17,5kV 16 31,5kA Generalities SYSclad is a medium voltage switchboard metal clad

More information

CGMCOSMOS-2LV. MEDIUM-VOLTAGE SF 6 GAS-INSULATED RING MAIN UNIT UP TO 12 kv LIB

CGMCOSMOS-2LV. MEDIUM-VOLTAGE SF 6 GAS-INSULATED RING MAIN UNIT UP TO 12 kv LIB IG-179-GB GENERAL INSTRUCTIONS FOR IG-179-GB General Instructions MEDIUM-VOLTAGE SF 6 GAS-INSULATED RING MAIN UNIT UP TO 12 kv LIB Transformer Substations Primary Distribution Switchgear Secondary Distribution

More information

MEDIUM VOLTAGE CE-B36 METAL CLAD SWITCHBOARDS. CE - B36 - C - en - REV

MEDIUM VOLTAGE CE-B36 METAL CLAD SWITCHBOARDS. CE - B36 - C - en - REV CE - B36 - C - en - REV.00 2011.9 EDIU VOLTAGE EDIU VOLTAGE APPLICATION CE-B etal Clad switchboards are designed for use in public and industrial distribution system up to 36kV for the operation and protection

More information

Galaxy 300 Battery Breaker Kit G3HTBKIT1

Galaxy 300 Battery Breaker Kit G3HTBKIT1 Installation 990 5739 001 03/2016 990 5739 001 Galaxy 300 Battery Breaker Kit G3HTBKIT1 What s in This Document Important Safety Instructions SAVE THESE INSTRUCTIONS...1 Safety Precautions...2 Specifications...4

More information

B kv Gas-insulated Substations

B kv Gas-insulated Substations 72.5 145 kv Gas-insulated Substations The increasing demand for electrical power in cities and industrial centres requires the installation of a compact and efficient distribution and transmission network.

More information

XL Distribution enclosures WORKSHOP SPECIFICATIONS

XL Distribution enclosures WORKSHOP SPECIFICATIONS 800 Distribution enclosures WORKSHOP SPECIFICATIONS With its extensive ranges, the Legrand offer meets your quality standards and provides real freedom and simplicity of installation together with acknowledged

More information

Cable arrangement 15 Preparation for cable installation. 15 Installation of the cables 16 Finishing of the cable installation. 17 Examples.

Cable arrangement 15 Preparation for cable installation. 15 Installation of the cables 16 Finishing of the cable installation. 17 Examples. Transportation and storage.. 3 General. 3 Unpacking at installation site....... 3 Transfer of cubicles at installation site... 3 Weight.. 4 Temporary storage. 4 Erection at site 5 General. 5 The switchgear

More information

NPS/003/010 - Technical Specification for 400V Assemblies (LVAC Boards) utilised in Major Substations

NPS/003/010 - Technical Specification for 400V Assemblies (LVAC Boards) utilised in Major Substations Version:- 3.0 Date of Issue:- Dec 2013 Page 1 of 13 NPS/003/010 - Technical Specification for 400V Assemblies (LVAC Boards) utilised in Major Substations 1. Purpose This document is the technical specification

More information

1. Safety practices General Introduction Standards...3

1. Safety practices General Introduction Standards...3 1. Safety practices...2 2. General...3 2.1 Introduction...3 2.2 Standards...3 3. Technical data...3 3.1 Designation...3 3.2 Electrical ratings and dimensions...4 3.3 Fixation...6 3.4 Connecting terminals...6

More information

The switchboard that your installation deserves

The switchboard that your installation deserves The switchboard that your installation deserves Blokset : Low voltage switchboard for electrical distribution and motor control 2 A tried and tested switchboard Blokset switchboards have long guaranteed

More information

DISTRIBUTION SOLUTIONS. GSec Gas-insulated switching and isolating apparatus

DISTRIBUTION SOLUTIONS. GSec Gas-insulated switching and isolating apparatus DISTRIBUTION SOLUTIONS GSec Gas-insulated switching and isolating apparatus GSec is a three-position SF6 gas-insulated switchdisconnector designed for use in medium voltage switchgear for secondary distribution

More information

GMA. Medium-voltage switchgear

GMA. Medium-voltage switchgear Medium-voltage switchgear Gas-insulated switchgear up to 24 kv - 2500 A - 31.5 ka Earthing without automatically CLOSE / OPEN of the Circuit Breaker Operation - Maintenance Technical Manual No. AGS 531

More information

TABLE OF CONTENTS FOREWORD...3 INTRODUCTION SCOPE NORMATIVE REFERENCES DEFINITIONS AND ABBREVIATIONS REQUIREMENTS...

TABLE OF CONTENTS FOREWORD...3 INTRODUCTION SCOPE NORMATIVE REFERENCES DEFINITIONS AND ABBREVIATIONS REQUIREMENTS... TITLE SPECIFICATION FOR PORTABLE DATE: JULY 2006 PAGE: 1 OF 25 TABLE OF CONTENTS Page FOREWORD...3 INTRODUCTION...4 1 SCOPE...4 2 NORMATIVE S...4 3 DEFINITIONS AND ABBIATIONS...4 4 REQUIREMENTS...5 4.1

More information

Contents. The RM6 range

Contents. The RM6 range Ring Main Unit RM6 24 kv Catalogue 2009 The RM6 range Contents Presentation Applications 2 Range advantages 4 Experience of a world leader 6 Protecting the environment 7 Quality - Standards 8 The RM6 range

More information

cpg.0 GIS-type medium-voltage switchgear with full insulation in SF 6 gas, up to 40.5 kv in accordance with IEC Standards

cpg.0 GIS-type medium-voltage switchgear with full insulation in SF 6 gas, up to 40.5 kv in accordance with IEC Standards GIS-type medium-voltage switchgear with full insulation in SF 6 gas, up to 40.5 kv in accordance with IEC Standards General Instructions IG-123-EN, version 09; 04/09/2017 CAUTION! When medium-voltage equipment

More information

e 2 ALPHA Medium Voltage Switchgear K Catalogue EN

e 2 ALPHA Medium Voltage Switchgear K Catalogue EN e 2 ALPHA Medium Voltage Switchgear K-1.2.3 Catalogue EN WE CREATE IDEAS WITH POWER! ELEKTROMETAL ENERGETYKA SA provides solutions for electrical power engineering. Our services are carried out by a team

More information

Type Operating Instructions. Bedienungsanleitung Manuel utilisateur

Type Operating Instructions. Bedienungsanleitung Manuel utilisateur Water flow rate transmitter Wasser-Durchfluss-Transmitter Transmetteur de débit d eau Operating Instructions Bedienungsanleitung Manuel utilisateur We reserve the right to make technical changes without

More information

ormaset-m PREFABRICATED METALLIC TRANSFORMER SUBSTATION

ormaset-m PREFABRICATED METALLIC TRANSFORMER SUBSTATION IG-199-GB GENERAL INSTRUCTIONS FOR IG-199-GB General Instructions ormaset-m Transformer Substations Primary Distribution Switchgear Secondary Distribution Switchgear Protection and Automation Low Voltage

More information

10/2015 CUBICLE AND METAL-CLAD MEDIUM VOLTAGE SWITCHGEARS WEGA 07 WEGA 12 WEGA 17 WEGA 24 WEGA 36

10/2015 CUBICLE AND METAL-CLAD MEDIUM VOLTAGE SWITCHGEARS WEGA 07 WEGA 12 WEGA 17 WEGA 24 WEGA 36 10/2015 CUBICLE AND METAL-CLAD MEDIUM VOLTAGE SWITCHGEARS WEGA 07 WEGA 12 WEGA 17 WEGA 24 WEGA 36 Gdańsk, October 2015 Improving the competitiveness of the company ELMOR through investments introducing

More information

A E. P.M.G. range. Low Voltage Alternators - 4 pole. Installation and maintenance

A E. P.M.G. range. Low Voltage Alternators - 4 pole. Installation and maintenance A E This manual concerns the P.M.G. alternator which which you you have have just just purchased. We wish to draw your attention to the contents of this maintenance manual. SAFETY MEASURES Before using

More information