1 SM6 Anglais MV distribution factory built assemblies at your service instructions for use IMCandQMCcubicles

2 foreword... 3 symbols and conventions... 3 as per iso contact the Schneider Electric service unit for diagnosis and advice 3 4 distribution rules... safety rules general description... 5 IMC : switch cubicle... 5 QMC : combined fuse---switch cubicle... 5 handling instructions... 7 equipment identification... list and number of bags and accessories overall dimensions and weight... handling by slings handling with forklift... handling storage installation and operation recommendation installation instructions preparing the cubicles for switchboard assembly assembling the end plate... assembling the switchboard fixing to the floor... mounting in substation fitting the busbars after installing the cubicles at their final location cable entry for connection of low voltage auxiliaries fitting the earth collector... storing the operating lever HV cable connection in an IMC cubicle... assembling the connection basin fitting the basin and the earth bar... installing the cable HV cable connection in a QMC cubicle positioning fuses in a QMC cubicle... transformer protection commissioning instructions IMC/QMC cubicle status indication operating the equipment when de---energised... energisation of HV incoming cables voltage indicators... phase balance adaptater operating instructions manual operation IMC/QMC cubicle status indication discharging a CI2 operating mechanism... operating the earthing switch QMC cubicle fuse status indication... padlocking latching... safety operation maintenance instructions preventive maintenance, cleaning instructions and power---up corrective maintenance... replacing a voltage indicator block on a cubicle prior to U replacing a voltage indicator block... diagnostic chart EN revision : 02 1

3 spare parts... options recovery of SF6 gas at end of life... options and spare parts EN revision : 02

4 foreword symbols and conventions Caution: you will find all the symbols below throughout the document, indicating the hazard levels depending on the different types of situation. DANGER as per iso DANGER: failure to follow this instruction will result in death or serious injury. WARNING as per iso WARNING: failure to follow this instruction may result in death or serious injury. CAUTION as per iso CAUTION: failure to follow this instruction may result in injuries. This alert signal can also be used to indicate practices that could damage the SM6 unit. INFORMATION-ADVICE We draw your attention to this specific point EN revision : 02 3

5 contact the Schneider Electric service unit for diagnosis and advice Call your sales representative who willputyouincontactwith the closest SCHNEIDER ELECTRIC group service centre. You can log on to: electric.com distribution rules The aim of this publication is to enable the SM6 unit to be installed correctly. This document is not a commercial document. It is a strictly technical document drawn up by Schneider Electric. safety rules CAUTION WARNING All the operations described below must be performed in compliance with applicable safety standards, under the responsibility of a competent authority. Thecontractormustbecertified and authorised to manipulate and perform work on the SM6 unit. CAUTION Only undertake the work after having read and understood all the explanations given in this document. If you have any difficulty complying with these rules, please contact Schneider Electric EN revision : 02

6 general description IMC : switch cubicle 1 : busbar compartment 2 : monitoring compartment 3 :switchgearcompartmen switch and earthing switch 4 : control compartment 5 : cable connection compartment A : earth collector connecting pad B : busbar connecting pads C : current transformers D : voltage indicator E : phase separator screen F : inspection window G : front panel N : rear extension sheet metal N 2 4 D A 1 B 3 C E F G 5 QMC : combined fuse---switch cubicle 1 : busbar compartment 2 : monitoring compartment 3 : switchgear compartment switch and earthing switch 4 : control compartment 5 : cable connection compartment and positioning fuses A : earth collector connecting pad B : busbar connecting pads C : fuse blown tripping system D : voltage indicator E :fuses F : current transformers G : window for inspection of fuse installation and downstream earthing switch position indicator H : bottom field distributor and cable connection J : front panel N : rear extension sheet metal N 2 4 D G J A 1 B 3 C E F 5 H EN revision : 02 5

7 EN revision : 02

8 handling instructions equipment identification A D2 D3 B E D1 C list and number of bags and accessories supplied with cubicle switchboard pack : (where applicable --- depends on composition of switchboard) 1 operating handle 2endplates 1bagofendplatescrews S4 : A : information plate B : specifications and designations C : manufacturer s label E : motor drive system plate (option) IMC pack : 1 bag intercubicle connections S1 : bag busbar distributors >12 kv S2: or 1 bag busbar fixings ± 12 kv S6: bag back plate fixings S3 : backplates 3cablebushings 3 cable clamps 3 cable clamp supports 1setofbusbars 1 earth collector 1 basin kit cablebushings 1 cable clamps 1 cable clamp supports 1bagofscrews serial number D1: riveted to control compartment cover D2: glued to back of monitoring compartment cover D3: gluedtoframeupright QMC pack : 1setofbusbars 1 earth collector 3cablebushings 1 bag intercubicle connections S1 : bag busbar distributors >12 kv S2 : or 1 bag busbar fixings ± 12 kv S6 : EN revision : 02 7

9 overall dimensions and weight IMC:170 kg QMC:180 kg L1 L2 L EN revision : 02

10 handling by slings The handling lugs are reserved solely for handling of SM6 cubicles. A : HM12 screws and nuts B : Schneider Electric maximum useful load = 400 KG CE Schneider Electric CMU =400 KG CE C Schneider Electric CMU =400 KG CE CAUTION C : in event of hole deformation (ovalisation) replace the lugs. A B L=750 mm mini L L 60 maxi 60 maxi L= 1130 mm mini L= 970 mm mini. handling with forklift EN revision : 02 9

11 handling Do not grasp the operating mechanism front plate to manipulate the cubicle. storage 70 C C EN revision : 02

12 installation and operation recommendation switchgear ageing withstandinanmv substation depends on 3 main factors H The need for proper implementation of connections: the new cold slip --- on and retractable technologies offer ease of installation, thereby promoting withstand over time. Their design enables operation in polluted environments with harsh atmospheres. H Theinfluenceoftherelative humidity factor: installation of heating resistors is essential in climates with high relative humidity and large temperature differences. H Ventilation control: the grids must be sized according to power loss in the substation. These grids must only be placed near the transformer, so as to prevent air circulating on the MV switchboard. operation Our service centre is at your disposal at all times: H To conduct an installation diagnosis. H To suggest the appropriate maintenance operations. H To offer you maintenance contracts. H To suggest adaptations EN revision : 02 11

13 EN revision : 02

14 installation instructions preparing the cubicles for switchboard assembly Delivery state : earthing switch in closed position. :screw+washer : bolt + washer + Nylstop nut D C B A Remove the front panel A and then thebaseplatesb. (the screws are not re---usable) Remove the monitoring compartment cover C and the lifting eye bolts D. G H G Remove part GandG.(6screws) Remove part H. (7screws) assembling the end plate Refer to the switchboard parcel manual, as per the upgrade of the new standard IEC EN revision : 02 13

15 assembling the switchboard screw bag S1 : (HM6x16 mm screws) : screw+washer+ nut M K L vuededessus K L Fix the cubicles together. (the additional screws are for mounting the earth collector) Bolt mounting direction. K : left---hand cubicle L : right---hand cubicle M : to join the 2 cubicles. Screw HM6x60 to tighten moderately. Tightening torque : 6 Nm. fixing to the floor (screws to be provided by the contractor according to civil engineering) IMC ,3x12, ,3x12, QMC The shaded part represents the basin which juts out by a 100 mm underneath the cubicle. mounting in substation Installation of the switchboard to the right of the wall. (minimum dimension for correct operation of the equipment) Installation of the switchboard to the left of the wall. IM PM ou QM 140 mm 140 mm PM ou QM IM 21,5 à 100 mm 21,5 à 100 mm EN revision : 02

16 fitting the busbars after installing the cubicles at their final location accessories bag S2 : or S6 : Tools : 1 torque wrench 1 to 50 Nm. 1 1/ /8 instrument transformer 1 6 mm socket 1 6 mm hexagon male drive socket for voltages > 12 kv 1 hexagon female drive socket for voltages < 12 kv Busbar connection with cubicle on left. Tightening torque : 28 Nm. Busbar connection with cubicle on right. Tightening torque : 28 Nm. Versions ±12 kv S6 : Mounting without field splitter. Version > 12kV S2 : Correct position of the field splitter. Incorrect position, riskof detérioration. NB : The busbar spacers must only be installed for version 25 ka. A bar cross---section view of the s Install the two busbar spacers so they are centred on the busbar portion. Fit two O ring seals (A) oneach side of the busbar spacer between phases EN revision : 02 15

17 : vis+rondelles+écrou nylstop H : vis+rondelle G G Replace top part H. (nuts inside cubicle) Replace part GandG. cable entry for connection of low voltage auxiliaries A Cable entry to the auxiliary terminal block is via holes A on top. Cubicle equipped with a wiring duct. (option) Proceed in the same manner after removing the trough top plate. Replace the monitoring compartment cover, complying with the markings of each cubicle EN revision : 02

18 fitting the earth collector screw bag S1 : The collectors are connected together. (remaining HM8x35 mm screws in bag S1 : ) Two ways to earth the substation exposed conductive parts. storing the operating lever A Fix the hook (A) and the wall. (screws not supplied) The operating lever has to be hooked (B). B HV cable connection in an IMC cubicle (3 one---pole cables) 1 : copper cable or aluminium cable To limit the effort on the cable connection you have to ajust the lenght at the bending radius of the cable. 1 EUIC (short inner end, cold fitted). They must be manufactured according to the standard : IEC Mount the cable clamp supports.nuts and bolts in bag S3 : (HM6 x 16 bolts). The remaining nuts and bolts are for cable clamping EN revision : 02 17

19 Removethetwophaseseparator screens. Lift them, tilt them and withdraw them. Install the cable bushing. L1 Connect the cable to phase L1. The screws are permanent. Tightening torque : 50 Nm. Clamp the first cable. (HM8x50 mm screw) 1 2 Fit the back plate 2 at the rear of the cubicle. H Fit phases L2 and L3 by the same procedure as L1. Connect the 3 cable earthing braids to the earth collector. (the screws are permanent) EN revision : 02

20 Position the back plates so that the slots A are not face--to--face. connection alternative 1 three---pole cable clamping the tab of part 1 secures part assembling the connection basin Fasten together the various plates making up the basin kit. Fit the cage nuts to fix the bottom plates. Fit the flange support and the cable gland EN revision : 02 19

21 fitting the basin and the earth bar Install and fix the basin (10 screws). Position the earth bar A on the lefthand side of the basin (2 clips) and fix it to the earth bar already placed in the cubicle. (HM6 x 30 screws) A installing the cable Cut out the cable gland and flange the cable to the bottom of the basin. connection L1 Put the phase --- to --- phase insulation screen back into place before going on to the next strand. Connect the cable earthing braid(s) to the earth bar (HM6 x 30 screws). Connect the strand of phase L1. The screws are permanent Tightening torque : 50 Nm EN revision : 02

22 HV cable connection in a QMC cubicle Do not use cable clamp supports. Open the earthing switch using the operating handle. Demount the plinth. (4 screws) Demount the basin. (8 screws) Invert and replace the basin. Replace the plinth. (re---use the same screws) Install and cut the 3 cable bushings. Connect the cables in the order L1, L2 and L3. (the screws are permanent) Tightening torque : 50 Nm. Close the earthing switch EN revision : 02 21

23 positioning fuses in a QMC cubicle Reminder: Check the condition of fuses before placing them. Raise the cover of the top field distributor by means of the fuse. Insert the bottom end of the fuse into the bottom tulip contact. NB : -- When changing a fuse, all 3 fuses should be changed at the same time. -- Do not re--use fuses that have already been used. Then insert the top end of the fuse into the top contact and check that the cover of the field distributor has closed properly. Turn the label to face the front. Do not grasp the fuse in the middle. fuse mounting direction Install the striker fuses which trip the switch when they blow. Percuteur Striker pin Schlagstift Percussore Theendofthefusewiththestriker pinismarkedasshownabove. The specifications and the mounting orientation of the fuse areprintedonthefusebody. Turn the label to face the front. (striker pin at the top) EN revision : 02

24 transformer protection Fuse ratings for SM6 protection units such as the QMC depend, among other things, on the following criteria : H Service voltage H Transformer rating. H Fuse technology (manufacturer). H Different types of fuses with medium loaded striker may be installed: ---Solefuse fuses as per standard UTE NFC CF Fusarc fuses as per IEC recommendation and DIN dimensions dimensions of fuses Soléfuse (UTE standard) CF Fusarc (DIN standard) Ø45 Ø Ø55 Example: for the protection of a 400 kva transformer at 10 kv, select either Solefuse fuses rated 43A or CF Fusarc fuses rated 50A. Please consult us on installation rated voltage (kv) rating (A) ,2 6,3 à , ,3 à 63 2 weight (Kg) rated voltage (kv) 33 L rating (A) L (mm) (mm) weight (Kg) 7, ,3 12 6,3 à ,4 80 à ,3 24 6,3 à ,4 50 à EN revision : 02 23

25 selection table (rating in (A), no overload, C <θ <40 C) Please consult us for overloads and operation over 40 C. (*) please, consult us. type of fuse service voltage (kv) transformer rating (KVA) UTE NFC standards: , Solefuse General case, UTE NFC standard Solefuse General case, IEC standard CF Fusarc and SIBA* 3, * 200* 7, , * 5, ,5 31, * 160* , * 160* 6, , * 10 6, , * 200* * 160* 13,8 6, ,5 31, * 125* 125* 17,5 15 6, , * 125* 20 6,3 6, , * 125* ,3 6, , * rated voltage (kv) reference list FUSARC CF Reference list of fuse inside QM cubicle according to IEC standard. Please consult us for all other type of fuses. SIBA Ur.7,2 Kv Ur.12 Kv Ur.24 Kv Ur.7,2 Kv Ur.12Kv Ur.17,5Kv Ur.24 Kv Ir(A) ref Ir(A) ref Ir(A) ref Ir(A) ref Ir(A) ref Ir(A) ref Ir(A) ref BN 6, M0 6, M M M M M M M M M0 31, M0 31, M M M M M M M M M M EN revision : 02

26 commissioning instructions IMC/QMC cubicle status indication Do not leave anything in the connection compartment. Check on all phases that : H thefuseispositionedcorrectly. H the cover of the field distributor is closed properly. A Replace the front panel A. operating the equipment when de---energised (see operating instructions) Operate the earthing switch several times. Operate the switch several times. energisation of HV incoming cables The equipment must be open. (see operating instructions) EN revision : 02 25

27 voltage indicators A B A : voltage presence indicator lamp (1 for each phase). B : connection point used to connect a phase concordance unit. As soon as the cables have been energized, the voltage indicator lamps should go on. characteristics The voltage presence indication is ensured in the voltage range defiried by IEC phase balance adaptater Note: the monitoring devivce is thesameasthatusedby the RM6 equipment. Note: inthecaseofacontrol between old presence of tension and new VPIS to use the adaptater : FA Phase comparator of the simplified. In phase balance : H the comparator lamp does not come on. In phase unbalance: H the comparator lamp comes on EN revision : 02

28 operating instructions manual operation IMC/QMC cubicle status indication Position the handle as shown for downward opening operations. Position the handle as shown for upward closing operations. CIT operating mechanism, front panel. CI1 operating mechanism, front panel. J CI2 operating mechanism, front panel. J : identification of charging state EN revision : 02 27

29 manual operation of the switch Closing the switch. (CIT / CI1 operating mechanisms) Charging the spring. (CI2 operating mechanism) Closing the switch. (CI2 operating mechanism) Opening the switch. (CIT operating mechanism) Opening the switch. (CI1/CI2 operating mechanisms) EN revision : 02

30 discharging a CI2 operating mechanism A B B Cubicle de--energised : Close the switch: button A then open: button B. Cubicle energised : Press the open button B. CAUTION This operation can damage the operating mechanism. Perform only when strictly necessary. operating the earthing switch These operations can be performed only if the switch operating mechanism is in the OPEN and DISCHARGED position. (for CI2 see previous sections) Close the earthing switch (for CIT / CI1 / CI2 operating mechanisms) after verifying that there is no voltage present. (see presence of voltage) Open the earthing switch. QMC cubicle fuse status indication Fuses serviceable. (white indicator) At least one fuse unserviceable. (red indicator) EN revision : 02 29

31 padlocking Note : if the cubicle is fitted with a CI2 operating mechanism, the latter can be discharged if necessary (see previous sections) Padlocking the motor drive. (option) Padlock the motor drive out of servicebeforeopeningtheswitch. It can be padlocked in service or out of service. Padlock the switch open or closed using 1, 2 or mm dia. padlocks. Padlock the earthing switch open or closed using 1, 2 or mm dia. padlocks. Padlocking the front panel. latching See lock installation and operating manual en. safety operation The front panel can be fitted or removed only with the earthing switch closed EN revision : 02

32 maintenance instructions preventive maintenance, cleaning instructions and power --- up If necessary: contact the Schneider Electric group service centre. We strongly recommend that you carry out at regular intervals (at least roughly every 2 years) afew operating cycles on the switching devices. CAUTION Never lubricate the disconnector operating mechanism. If necessary: contact the Schneider Electric group service centre. In normal operating conditions (temperature between C and40 C) no special maintenance is required. CAUTION Never use solvents and alcohol. We recommend that you inspect each compartment (cable, fuse, busbar)* at regular intervals according to environmental conditions. If the insulating parts are dusty, that you remove the dust using a dry cloth. example : In harsher conditions (aggressive atmosphere, dust, temperature less than C or greater than 40 C) consult the nearest Schneider Electric service centre EN revision : 02 31

33 corrective maintenance Replacement of fuses: H the cubicle must be de---energised. H switch open. H earthing switch closed. Open the front panel to obtain access to the fuses. Important note : IEC standard recommends replacement of the 3 MV fuses if any one of them blows. replacing a voltage indicator block on a cubicle prior to U Disengage the top end of the fuse. Then lift the fuse completely out. To fit the replacement fuses see the section on positioning fuses in a QMC cubicle. Extract the indicator unit by hand thiscanbedonewiththe switchboard live. replacing a voltage indicator block VIPS type on a cubicle after U removal This operation can be conducted with an enegised switch. install remove the 2 fixing screws from the voltage indicator block (A). On the electrical data label (C), make sure that the new block correctly corresponds to the rated network voltage H 1,7kVà3kV H 3kVà7,2kV H 10 kv à 24 kv A B Remove the voltage indicator block and unplug the incoming connector (B) from it. C Install the new voltage indicator bock in the reverse order for removal. Tightening torque 0,1 mdan EN revision : 02

34 diagnostic chart IMCandQMCcubicles H voltage indicator does not light up H incoming cables are not live H H H H check the lamp units check that the switch is closed check that the fuses are present check the condition of the fuses H frontpanelwillnotopenorcannotbefitted H check that the earthing switch is closed H earthing switch cannot be operated H check that the switch is open H switch cannot be operated H check that the earthing switch is open motor drive (option) H electrical malfunction H check the LV fuses (CIP2) S13 = switch handle entry S14 = earthing switch handle entry H (*) manual operation impossible after electrical closing cycle for voltage down more than 15% H (*) handle insertion impossible after electrical closing cycleforvoltageupmorethan15% (*) operation is guaranteed at the nominal voltage +15%. H check the electrical interlocks S (insertion of handle) H check that the earthing switch operating shaft is fully open H check that contact S14 is not disabling the power supply. Adjust if necessary H check the configuration of the CIP1 plate (see diagram) H use the operating handle to apply a closing torque as far as the end stop the manual opening operation can then be performed H operate electrically if possible, if necessary using a back---up power supply H to allow insertion of the operating handle turn the switch shaft in the closing direction using a large screwdriver (as a precaution disable the electrical operating mechanism. If necessary hold up thelockingbladethatactsoncontacts13) EN revision : 02 33

35 spare parts H fuses (UTE or DIN) H voltage indicator For other parts, please consult us: see groupe Schneider Electric service centers options (please consult us) For IM cubicles H motor mechanism H auxiliary contacts H LV compartment or incoming cables compartment from top H keyed interlocks H 50 W heating element H extra height plinth H relay Flair Din H low voltage cabinet H enlarged LV compartment H phase concordance tester H kit two dry single cables a phase H T200S for remote control For QM cubicles H motor mechanism with shunt trip release H auxiliary contacts H LV compartment or incoming cables compartment from top H keyed interlocks H 50 W heating element H extra height plinth H relay Flair Din H contact for fuse blown indication H enlarged LV compartment H undervoltage or shunt type opening release For PM cubicles H motor mechanism H auxiliary contacts H LV compartment or incoming cables compartment from top H keyed interlocks H 50 W heating element H extra height plinth H relay Flair Din H low voltage cabinet H fuse blown mechanical signalling EN revision : 02

36 recovery of SF6 gas at end of life for disconnector cubicle The SF6 must be removed before any dismantling operation can be carried out in compliance with the procedures described in IEC and according to the following instructions. The gas must be treated in compliance with IEC H volume of gas to be recovered: 35 litres H internal gauge pressure: 40 kp A NB : SF6 gas recycling at the end of circuit-- breaker life, refer to its instruction for use. Remove the cover (A) from the control cabinet. control cover access B Remove the control cover (B). Remove the 3 screws retaining the operating mechanism. Cut the wiring to remove the operating mechanism. Drill 2 holes in the filler valve safety cap 4 mm, centreline 20 mm, max. depth 4 mm EN revision : 02 35

37 CAUTION pump the gas for at least 15 minutes. C Using a spanner wrench, remove the safety cap from the valve. Connect the special pumping equipment (C). options and spare parts H voltage indicator H H H CIT operating mechanism Kit machansim 48Vcc Fuses (For other parts, please consult us: see groupe Schneider Electric service centers.) EN revision : 02

38 group Schneider Electric service centers are there for: engineering and technical assistance start-up training preventive and corrective maintenance adaptation work spare parts Call your sales representative who will put you in touch with your nearest group Schneider Electric service centers. Schneider Electric Industries SAS 89, boulevard Franklin Roosevelt F Rueil--- Malmaison (France) Tel:+33(0) electric.com EN revision : 02 As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication. Conception, rédaction: Service Documentation Technique T&D Edition du : 24/04/2008

SM6. instructions for use. GAM cubicle (1250A) MV distribution factory built assemblies at your service. Anglais

SM6. instructions for use. GAM cubicle (1250A) MV distribution factory built assemblies at your service. Anglais SM6 Anglais MV distribution factory built assemblies at your service instructions for use GAM cubicle (1250A) foreword... 3 symbols and conventions... 3 as per iso 3864---2... contact the Schneider Electric

More information

SM6. instructions for use. DMVL cubicle. MV distribution factory built assemblies at your service. Anglais

SM6. instructions for use. DMVL cubicle. MV distribution factory built assemblies at your service. Anglais SM6 Anglais MV distribution factory built assemblies at your service instructions for use DMVL cubicle foreword... 3 symbols and conventions... 3 as per iso 3864---2... contact the Schneider Electric service

More information

SM6. instructions for use. QMB cubicles. MV distribution factory built assemblies at your service. Anglais

SM6. instructions for use. QMB cubicles. MV distribution factory built assemblies at your service. Anglais SM6 Anglais MV distribution factory built assemblies at your service instructions for use QMB cubicles foreword... 3 symbols and conventions... 3 as per iso 3864---2... contact the Schneider Electric service

More information

SM6. instructions for use. IMB cubicle without earthing switch. MV distribution factory built assemblies at your service. Anglais

SM6. instructions for use. IMB cubicle without earthing switch. MV distribution factory built assemblies at your service. Anglais SM6 Anglais MV distribution factory built assemblies at your service instructions for use IMB cubicle without earthing switch foreword... 3 symbols and conventions... 3 as per iso 3864---2... contact the

More information

SM6. instructions for use. SM cubicle. MV distribution factory built assemblies at your service. Anglais

SM6. instructions for use. SM cubicle. MV distribution factory built assemblies at your service. Anglais SM6 Anglais MV distribution factory built assemblies at your service instructions for use SM cubicle foreword... 3 symbols and conventions... 3 as per iso 3864---2... contact the Schneider Electric service

More information

SM6. instructions for use. DM1 S cubicle. MV distribution factory built assemblies at your service. Anglais

SM6. instructions for use. DM1 S cubicle. MV distribution factory built assemblies at your service. Anglais SM6 Anglais MV distribution factory built assemblies at your service instructions for use DM1 S cubicle foreword... 3 symbols and conventions... 3 as per iso 3864---2... contact the Schneider Electric

More information

SM6. instructions for use. DMV S cubicle. MV distribution factory built assemblies at your service. Anglais

SM6. instructions for use. DMV S cubicle. MV distribution factory built assemblies at your service. Anglais SM6 Anglais MV distribution factory built assemblies at your service instructions for use DMV S cubicle foreword... 3 symbols and conventions... 3 as per iso 3864---2... contact the Schneider Electric

More information

Information for the modified document

Information for the modified document Information for the modified document émetteur : Esref OZYUZUCULER date :03-05 - 2001 Recipient SM6 --- 36kV STT KG K ToK FaZ OrY MRK(TR) E&S S OyR MeM er Number : 7897176EN Index : D0 Product : SM6-36

More information

SM6. instructions for use. DMV A---DMV D cubicle (1250A range) MV distribution factory built assemblies at your service. Anglais

SM6. instructions for use. DMV A---DMV D cubicle (1250A range) MV distribution factory built assemblies at your service. Anglais SM6 Anglais MV distribution factory built assemblies at your service instructions for use DMV A---DMV D cubicle (1250A range) foreword... 3 symbols and conventions... 3 as per iso 3864---2... contact the

More information

MCset 4-24 kv Withdrawable SF6 circuit breaker

MCset 4-24 kv Withdrawable SF6 circuit breaker Medium Voltage switchgear MCset 4-24 kv Withdrawable SF6 circuit breaker Instruction for use Contents General 2 Glossary 2 Symbols 2 Recommendations 3 General description 4 AD4 unit 4 AD4 unit with toroidal

More information

circuit breaker instructions for use SF draw --- out circuit---breakers in F400 MV distribution circuit breaker Anglais at your service

circuit breaker instructions for use SF draw --- out circuit---breakers in F400 MV distribution circuit breaker Anglais at your service circuit breaker Anglais MV distribution circuit breaker at your service instructions for use SF draw --- out circuit---breakers in F400 foreword... 3 symbols and conventions... 3 as per iso 3864---2...

More information

Medium Voltage Distribution FBX. Assembling a 1250A busbar Instructions.

Medium Voltage Distribution FBX. Assembling a 1250A busbar Instructions. Medium Voltage Distribution FBX Assembling a 1250A busbar Instructions www.schneider-electric.com Contents Introduction... 3 Our Service Unit: our specialists, and suitably adapted services...... 3 Overview...

More information

MCset kv Medium voltage equipment

MCset kv Medium voltage equipment Maintenance Guide PE90014 PE90006 MCset 1-2 - 3 17.5 kv Medium voltage equipment Air-insulated switchboards Metal-enclosed switchgear with moving parts PE90007 PE90008 PE90009 PE90007 Maintenance Guide

More information

circuit-- breaker instructions for use SF1 fixed or in SM6 circuit --- breaker MV distribution circuit breaker at your service Anglais

circuit-- breaker instructions for use SF1 fixed or in SM6 circuit --- breaker MV distribution circuit breaker at your service Anglais circuit-- breaker Anglais MV distribution circuit breaker at your service instructions for use SF1 fixed or in SM6 circuit --- breaker foreword... 3 symbols and conventions... 3 as per iso 3864---2...

More information

CGMCOSMOS. Reliable innovation. Personal solutions. Fully gas insulated modular and compact (RMU)system.

CGMCOSMOS. Reliable innovation. Personal solutions. Fully gas insulated modular and compact (RMU)system. MV Switchgear for CGMCOSMOS Fully gas insulated modular and compact (RMU)system Up to 24 kv Up to 27 kv mediumvoltage mediumvoltageag AG Langackerstrasse Langackerstrasse 25 25 CH CH 6330 6330 Cham Cham

More information

Contents. The RM6 range

Contents. The RM6 range Ring Main Unit RM6 24 kv Catalogue 2009 The RM6 range Contents Presentation Applications 2 Range advantages 4 Experience of a world leader 6 Protecting the environment 7 Quality - Standards 8 The RM6 range

More information

0MV vacuum circuit breaker. 0Evolis 24 kv. 0User 0Manual. Creation Printed on 2008/07/17

0MV vacuum circuit breaker. 0Evolis 24 kv. 0User 0Manual. Creation Printed on 2008/07/17 0MV vacuum circuit breaker 0Evolis 24 kv 0User 0Manual 02008 07897530EN-C0.book Page 1 Jeudi, 15. mai 2008 11:34 11 Contents Evolis description 2 Front view circuit breaker 2 Front view lateral circuit

More information

Medium voltage NEX switchgear Withdrawable circuit breaker. Quite simply efficient

Medium voltage NEX switchgear Withdrawable circuit breaker. Quite simply efficient Medium voltage NEX switchgear Withdrawable circuit breaker Quite simply efficient NEX, a simple and flexible solution NEX is the result of worldwide acquired experience and provides you with a high level

More information

MCset 17.5 kv. Civil engineering guide April Medium Voltage Distribution

MCset 17.5 kv. Civil engineering guide April Medium Voltage Distribution Medium Voltage Distribution MCset 17.5 kv ir insulated switchboard Withdrawable switchgear SF6 or vaccum technology Civil engineering guide pril 2012 Contents General 2 Glossary 2 Dimensions and weights

More information

PIX-H Metal-clad switchgear up to 17.5kV

PIX-H Metal-clad switchgear up to 17.5kV AIR INSULATED SWITCHGEAR PIX-H Metal-clad switchgear up to 17.5kV for high rated applications Technical Specifications AREVA T&D Summary - Technical description... 3 - Standards... 6 - PIX in detail...

More information

Secondary Distribution Switchgear FBX. SF6 Gas-insulated switchboards. Instructions Operation - Maintenance

Secondary Distribution Switchgear FBX. SF6 Gas-insulated switchboards. Instructions Operation - Maintenance Secondary Distribution Switchgear FBX SF6 Gas-insulated switchboards Instructions Operation - Maintenance Contents 1 Schneider Electric at your service................... 1 1.1 Our Service Unit: our specialists,

More information

circuit breakers instructions for use SF2 fixed MV distribution circuit breaker at your service Anglais

circuit breakers instructions for use SF2 fixed MV distribution circuit breaker at your service Anglais circuit breakers nglais MV distribution circuit breaker at your service instructions for use SF2 fixed foreword... 3 symbols and conventions... 3 as per iso 3864---2... contact the Schneider lectric service

More information

Secondary Distribution Switchgear FBX. SF6 Gas-insulated switchboards CB function. Instructions Installation - Commissioning Operating - Maintenance

Secondary Distribution Switchgear FBX. SF6 Gas-insulated switchboards CB function. Instructions Installation - Commissioning Operating - Maintenance Secondary Distribution Switchgear FBX SF6 Gas-insulated switchboards CB function Instructions Installation - Commissioning Operating - Maintenance Contents 1 Schneider Electric at your service... 1 1.1

More information

CPG.0 Single busbar gas-insulated cubicles

CPG.0 Single busbar gas-insulated cubicles MV Switchgear Primary Distribution CPG.0 Single busbar gas-insulated cubicles Up to 36 kv CPG System The quality of products designed, manufactured and installed by Ormazabal is underpinned by the implementation

More information

AIR INSULATED METAL ENCLOSED SWITCHGEAR AND CONTROLGEAR

AIR INSULATED METAL ENCLOSED SWITCHGEAR AND CONTROLGEAR AIR INSULATED METAL ENCLOSED SWITCHGEAR AND CONTROLGEAR ANGLER SWITCHING DEVICES CONTENTS 1. General 2. Switchgear Types - Switch Disconnector - Disconnector 3. Cubicle Types - Cubicle with Switch Disconnector

More information

PIX. Operation - Replacement of Fuses Replacement of Voltage Transformers Technical manual. Medium Voltage Distribution

PIX. Operation - Replacement of Fuses Replacement of Voltage Transformers Technical manual. Medium Voltage Distribution Medium Voltage Distribution PIX Withdrawable Voltage Transformer Operation - Replacement of Fuses Replacement of Voltage Transformers Technical manual Nr. Edition 11/2011 www.schneider-electric.com Schneider

More information

DISTRIBUTION SOLUTIONS. GSec Gas-insulated switching and isolating apparatus

DISTRIBUTION SOLUTIONS. GSec Gas-insulated switching and isolating apparatus DISTRIBUTION SOLUTIONS GSec Gas-insulated switching and isolating apparatus GSec is a three-position SF6 gas-insulated switchdisconnector designed for use in medium voltage switchgear for secondary distribution

More information

SFset with VIP 400/410 built-in control unit Medium Voltage Circuit Breaker

SFset with VIP 400/410 built-in control unit Medium Voltage Circuit Breaker SFset with VIP 400/410 built-in control unit Medium Voltage Circuit Breaker Instructions for use 07897543EN01 Rev.04 11/2017 SFset- Instructions for use Table of contents Presentation Presentation...

More information

Operating conditions. Generalities. Normal operating conditions

Operating conditions. Generalities. Normal operating conditions Generalities Operating conditions In addition to its technical characteristics, SM6 meets requirements concerning safety of life and property as well as ease of installation, operation and protecting the

More information

Galaxy VM. Battery Breaker Box Installation 09/

Galaxy VM. Battery Breaker Box Installation 09/ Galaxy VM Battery Breaker Box Installation 09/2016 www.schneider-electric.com Legal Information The Schneider Electric brand and any registered trademarks of Schneider Electric Industries SAS referred

More information

RM6. instructions for use. MV distribution factory built assemblies at your service ENGLISH

RM6. instructions for use. MV distribution factory built assemblies at your service ENGLISH RM6 ENGLISH MV distribution factory built assemblies at your service instructions for use foreword... 3 symbols and conventions... 3 distribution rules... safety rules... 4 4 maintenance rules... 4 general

More information

abb SafeLink SF 6 Insulated Ring Main Unit Installation and Operating Instructions Switchgear Division Auckland, New Zealand SLMIO ver 2.

abb SafeLink SF 6 Insulated Ring Main Unit Installation and Operating Instructions Switchgear Division Auckland, New Zealand SLMIO ver 2. Installation and Operating Instructions Switchgear Division Auckland, New Zealand SLMIO ver 2.12 Product Overview ABB's type-tested ring main unit (RMU) is an SF 6 insulated RMU utilising the latest developments

More information

DPX moulded case circuit breakers

DPX moulded case circuit breakers BREAKING AND PROTECTION DEVICES 10 / 2011 DPX moulded case circuit breakers DPX moulded case circuit breakers offer optimum solutions for the protection requirements of commercial and industrial installations.

More information

The vacuum circuit breaker for commercial buildings, industrial plants and utilities

The vacuum circuit breaker for commercial buildings, industrial plants and utilities The vacuum circuit breaker for commercial buildings, industrial plants and utilities EasyPact EXE The easy choice for more value 2 EasyPact EXE EasyPact EXE, a medium voltage vacuum circuit breaker optimizing

More information

CBGS-0. Medium voltage distribution

CBGS-0. Medium voltage distribution Medium voltage distribution CBGS-0 Gas Insulated metal-enclosed Switchgear SF6 circuit breaker technology Up to 24/36 kv - 1250/1600/2000 A - 25/31.5 ka Transmission Wind Airports Oil & Gas Mining & Distribution

More information

General. Main electric circuits Fuses compartment Operating mechanisms Cables connection compartment

General. Main electric circuits Fuses compartment Operating mechanisms Cables connection compartment General The switchgear must be suitable for 36 kv rated voltage and specifically conceived for the secondary distribution substations in M.V. with either ring or radial type networks. The switchgear must

More information

DX³ RCCBs - ID 4P up to 100 A

DX³ RCCBs - ID 4P up to 100 A 87045 LIMOGES Cedex Telephone number: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 DX³ s - ID CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation - Connection...

More information

SFset with VIP 400/410 built-in control unit Medium Voltage Circuit Breaker

SFset with VIP 400/410 built-in control unit Medium Voltage Circuit Breaker SFset with VIP 400/410 built-in control unit Medium Voltage Circuit Breaker Instructions for use 11/2017 18 0 2 ing A r p s e l b a l i va SFset- Instructions for use Table of contents Presentation Presentation...

More information

Medium Voltage Distribution Maintenance Guide I 2013 Premset. 15 kv compact modular vacuum switchgear with Shielded Solid Insulation System

Medium Voltage Distribution Maintenance Guide I 2013 Premset. 15 kv compact modular vacuum switchgear with Shielded Solid Insulation System Medium Voltage Distribution Maintenance Guide I 2013 Premset 15 kv compact modular vacuum switchgear with Shielded Solid Insulation System Schneider Electric Services, by your side all day long Installation

More information

NEX - 24 kv Withdrawable Circuit Breaker

NEX - 24 kv Withdrawable Circuit Breaker Air Insulated Medium Voltage Equipment NEX - 24 kv Withdrawable Circuit Breaker Installation drawings file Contents bj Fitting the upper main busbars 1250 A busbar - 800 mm cubicle Assembly 1250 A busbar

More information

Medium Voltage Distribution PIX kv. Additional equipment Instructions.

Medium Voltage Distribution PIX kv. Additional equipment Instructions. Medium Voltage Distribution PIX 12-17.5-24 kv Additional equipment Instructions www.schneider-electric.com Contents 1 Schneider Electric at your service... 4 1.1 Your contacts... 4 2 State of delivery

More information

Vacuum Circuit-Breakers, Type HVX kv, of cassette design, cassette with motor drive

Vacuum Circuit-Breakers, Type HVX kv, of cassette design, cassette with motor drive Vacuum Circuit-Breakers, Type HVX 12 24 kv, of cassette design, cassette with motor drive Operating Instructions No. 531 321, Edition 09/00 Table of Contents 1 General 4 1.1 Operating Conditions 4 2 Design,

More information

Low-voltage switchgear MNS Light W. Installation, handling and operation. ABB LV Systems

Low-voltage switchgear MNS Light W. Installation, handling and operation. ABB LV Systems Low-voltage switchgear MNS Light W Installation, handling and operation ABB LV Systems MNS Light W switchgear is a flexible system that is primarily designed for motor control. The rated service voltage

More information

CABINETS AND ENCLOSURES. XL³ 400 and XL³ 800 GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES

CABINETS AND ENCLOSURES. XL³ 400 and XL³ 800 GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES O S O O CABINETS AND ENCLOSURES XL³ 400 and XL³ 800 GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES II With its extensive ranges, the Legrand offer meets your quality standards and

More information

Galaxy 300 Battery Breaker Kit G3HTBKIT1

Galaxy 300 Battery Breaker Kit G3HTBKIT1 Installation 990 5739 001 03/2016 990 5739 001 Galaxy 300 Battery Breaker Kit G3HTBKIT1 What s in This Document Important Safety Instructions SAVE THESE INSTRUCTIONS...1 Safety Precautions...2 Specifications...4

More information

SYSclad switchboard equipped with draw out type vacuum circuit breaker closed dooroperationoperation. SYSclad 12 17,5kV A.

SYSclad switchboard equipped with draw out type vacuum circuit breaker closed dooroperationoperation. SYSclad 12 17,5kV A. SYSclad switchboard equipped with draw out type vacuum circuit breaker closed dooroperationoperation 630 3150A SYSclad 12 17,5kV 16 31,5kA Generalities SYSclad is a medium voltage switchboard metal clad

More information

Cat. N (s) : /65/66/83/84, /94/95/96/99, /01/02/06/07/11/12/13/14. Pollution degree : C / + 40 C. .

Cat. N (s) : /65/66/83/84, /94/95/96/99, /01/02/06/07/11/12/13/14. Pollution degree : C / + 40 C. . 87045 LIMOGES Cedex Telephone : (+33) 05 55 06 87 87 Fax : (+ 33) 05 55 06 88 88 R.C.C.B. s 0090 00/01/02/06/07/11/12/13/14 0/01/02/06/07/11/12/13/14/18/19/23/24/25/26/ /18/19/23/24/25/26/45/46 45/46 0090

More information

Energy Australia Chamber Substation indoor switchgear. installation,operation and maintenance instructions version 1.

Energy Australia Chamber Substation indoor switchgear. installation,operation and maintenance instructions version 1. Energy Australia Chamber Substation indoor switchgear installation,operation and maintenance instructions version 1.6 / February 2009 1 Details of revision Version Comment Date 1.0 First Draft Issue May

More information

Evolis offer Merlin Gerin

Evolis offer Merlin Gerin Medium voltage distribution Evolis offer Merlin Gerin Installation guide 200757a General contents Evolis circuit breaker full version 3 Circuit breaker installation 3 Cradle installation and earthing 3

More information

Key features. DESIGNS: - Conservator type - Hermetically sealed

Key features. DESIGNS: - Conservator type - Hermetically sealed Package Substations OTDS manufactures a large range of oil filled hermitically sealed and conservator type transformers to be used in conjunction with our package substations. We are able to utalise the

More information

CGM.3 System. Medium Voltage SF 6 gas-insulated cubicles up to 38 kv according to IEEE and CSA standards

CGM.3 System. Medium Voltage SF 6 gas-insulated cubicles up to 38 kv according to IEEE and CSA standards CGM.3 System Medium Voltage SF 6 gas-insulated cubicles up to 38 kv according to IEEE and CSA standards General Instructions IG-183-EN, version 03; 06/03/2013 Legal Deposit: BI-0272/2013 CAUTION! When

More information

Medium Voltage Distribution PIX. Air Insulated Switchgear up to 24 kv PARS TABLEAU

Medium Voltage Distribution PIX. Air Insulated Switchgear up to 24 kv PARS TABLEAU Medium Voltage Distribution PIX Air Insulated Switchgear up to kv PIX Air Insulated Switchgear up to kv The PIX system has been designed in accordance with international (IEC) standards, and gives an optimal

More information

XL Distribution enclosures WORKSHOP SPECIFICATIONS

XL Distribution enclosures WORKSHOP SPECIFICATIONS 800 Distribution enclosures WORKSHOP SPECIFICATIONS With its extensive ranges, the Legrand offer meets your quality standards and provides real freedom and simplicity of installation together with acknowledged

More information

Compact NR630. NR100F to NR630F

Compact NR630. NR100F to NR630F Low voltage switchgear Compact NR NR100F NR630F The Compact NS range has revolutionised the world of moulded-case circuit breakers. For installations not requiring the high performance levels of the NS

More information

GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector

GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector Catalog 0500CT9702R409 2009 Class 525/580 CONTENTS Description............................................. Page General Characteristics...................................

More information

Electrical network protection VIP30, VIP35. User s manual 12/2008

Electrical network protection VIP30, VIP35. User s manual 12/2008 Electrical network protection VIP30, VIP35 User s manual 1/008 Safety instructions ANSI symbol. IEC symbol. Safety symbols and messages Read these instructions carefully and look at the equipment to become

More information

Cloud-connected solution for utility-scale renewable power

Cloud-connected solution for utility-scale renewable power Cloud-connected solution for utility-scale renewable power Conext SmartGen TM Power System Global power conversion system for the next generation of PV and Energy Storage power plants connected to smart

More information

TX³ RCCBs 2P up to 100 A

TX³ RCCBs 2P up to 100 A 87045 LIMOGES Cedex Telephone number: +33 (0)5 55 06 87 87 Fax: +33 (0)5 55 06 88 88 TX³ RCCBs CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation - Connection...

More information

UniSec Operation and maintenance manual

UniSec Operation and maintenance manual Medium voltage products UniSec Operation and maintenance manual Safety 3 For your safety! 3 Skilled personnel 3 Critical messages 3 Contact us! 3 1. Introduction 4 1.1 General aspects 4 1.2 Operation and

More information

FUSOMAT Visible breaking and tripping fuse switches from 250 to 1250 A

FUSOMAT Visible breaking and tripping fuse switches from 250 to 1250 A Fuse protection The solution for > Motor load break > Protection of industrial cabinet > Electrical distribution fusom_063_b_1_cat Strong points > Tripping upon overload > High breaking capacity > Improved

More information

HVX Series. 36 kv Medium Voltage Vacuum circuit breaker. Make the most of your energy SM. Medium Voltage Distribution Catalogue 2015

HVX Series. 36 kv Medium Voltage Vacuum circuit breaker. Make the most of your energy SM. Medium Voltage Distribution Catalogue 2015 Medium Voltage Distribution Catalogue 205 HVX Series 36 kv Medium Voltage Vacuum circuit breaker Fixed, middle rolling and floor rolling ranges of circuit breaker and disconnector Make the most of your

More information

1. Safety practices General Introduction Standards...3

1. Safety practices General Introduction Standards...3 1. Safety practices...2 2. General...3 2.1 Introduction...3 2.2 Standards...3 3. Technical data...3 3.1 Designation...3 3.2 Electrical ratings and dimensions...4 3.3 Fixation...6 3.4 Connecting terminals...6

More information

Cable arrangement 15 Preparation for cable installation. 15 Installation of the cables 16 Finishing of the cable installation. 17 Examples.

Cable arrangement 15 Preparation for cable installation. 15 Installation of the cables 16 Finishing of the cable installation. 17 Examples. Transportation and storage.. 3 General. 3 Unpacking at installation site....... 3 Transfer of cubicles at installation site... 3 Weight.. 4 Temporary storage. 4 Erection at site 5 General. 5 The switchgear

More information

GHA. Gas-Insulated Switchgear. Gas-Insulated Switchgear. Switchgear extension and replacement of a panel

GHA. Gas-Insulated Switchgear. Gas-Insulated Switchgear. Switchgear extension and replacement of a panel Gas-Insulated Switchgear GHA Gas-Insulated Switchgear Switchgear extension and replacement of a panel During this work, essential parts of the switchgear remain in operation No. AGS 535 066-01 Edition

More information

MNS Light F. Low-voltage switchgear with fixed units. ABB LV Systems

MNS Light F. Low-voltage switchgear with fixed units. ABB LV Systems MNS Light F Low-voltage switchgear with fixed units ABB LV Systems Cubicle design MNS Light F switchgear is a flexible system with a large selection of cubicle variants that can be built together in optional

More information

Modular medium-voltage switchgear. NorMax

Modular medium-voltage switchgear. NorMax Modular medium-voltage switchgear NorMax NorMax MODULAR MEDIUM-VOLTAGE SWITCHGEAR 2 NorMax Modular medium-voltage switchgear Contents Subject Page Table of contents 2 Introduction and main features 2 Technical

More information

ARTICLE BEGINNING SERVICE PRECAUTIONS

ARTICLE BEGINNING SERVICE PRECAUTIONS Page 1 of 96 ARTICLE BEGINNING SERVICE PRECAUTIONS WARNING: WARNING: CAUTION: When performing any inspection or service procedure on this vehicle, ensure following service precautions are followed to prevent

More information

Prisma Plus G enclosures IP30, IP31, IP43 enclosures

Prisma Plus G enclosures IP30, IP31, IP43 enclosures Prisma Plus G IP30, IP31, IP43 Prisma Plus G IP30, IP31, IP43 Presentation For safe and upgradeable electrical switchboards > Safety of people and property > Continuity of service > Optimization and upgradeability

More information

87045 LIMOGES Cedex. 2. PRODUCT RANGE (continued) 1. DESCRIPTION - USE. Breaking capacity : Symbol : Technology : 3. OVERALL DIMENSIONS

87045 LIMOGES Cedex. 2. PRODUCT RANGE (continued) 1. DESCRIPTION - USE. Breaking capacity : Symbol : Technology : 3. OVERALL DIMENSIONS 87045 LIMOGES Cedex Phone : + 33 5 55 06 87 87 Fax : + 33 5 55 06 88 88 R.C.B.O. DX 6000 A Phase + Neutral,, neutral on right side Cat. n (s) : 077 31 077 44-077 77 077 84 078 79 079 01-083 95 084 06 084

More information

The Key Link for all your Distributions Needs. A Comprehensive Range for All Your Needs

The Key Link for all your Distributions Needs. A Comprehensive Range for All Your Needs [ MV Air-insulated Switchgear Range ] 1 PIX CUSTOMER BENEFITS Compact, versatile and highly reliable designs Choice of vacuum or SF6 switching technology Wide range of applications Enhanced operator safety

More information

I B D Q I B D Q O I B D Q O

I B D Q I B D Q O I B D Q O Extension offer: new possible combinations 2 and 3 functions RM6 free combination: offers all types of configurations which fit to every application. Free choice: type of each functional unit. Free choice:

More information

Cloud-connected solution for utility-scale renewable power

Cloud-connected solution for utility-scale renewable power Cloud-connected solution for utility-scale renewable power Conext SmartGen TM Power System Global power conversion system for the next generation of PV and Energy Storage power plants connected to smart

More information

NEXT STEP B) SAFETY :

NEXT STEP B) SAFETY : SUMMARY : EVOLUTION OF MV/LV SUBSTATIONS COMPACT SUBSTATIONS J. M. Solans, C. Prevé, R. Farrán, R. Muñoz. SCHNEIDER ELECTRIC S.A. - SPAIN INTRODUCTION The recent liberalisation of the electricity supply

More information

GE Industrial Solutions. User/Installation Manual for 4.76kV -15kV SecoBloc

GE Industrial Solutions. User/Installation Manual for 4.76kV -15kV SecoBloc GE Industrial Solutions User/Installation Manual for 4.76kV -15kV SecoBloc Index General Scope...3 Standards...3 Operating conditions...3 Technical specification...3 Basic structure Features...4 Operation...4

More information

B kv Gas-insulated Substations

B kv Gas-insulated Substations 72.5 145 kv Gas-insulated Substations The increasing demand for electrical power in cities and industrial centres requires the installation of a compact and efficient distribution and transmission network.

More information

VD4 Installation and service instructions kv A ka

VD4 Installation and service instructions kv A ka Medium voltage products VD4 Installation and service instructions 12... 36 kv - 630... 3150 A - 16... 50 ka Index For your safety! 1 I. Introduction 2 II. Programme for environmental protection 2 1. Packing

More information

CPG.1 Gas insulated, single busbar cubicle range Up to 27 kv / 2000 A / 31.5 ka Up to 38 kv / 2000 A / 31.5 ka IEEE Standards

CPG.1 Gas insulated, single busbar cubicle range Up to 27 kv / 2000 A / 31.5 ka Up to 38 kv / 2000 A / 31.5 ka IEEE Standards Medium Voltage Switchgear Primary Distribution CPG.1 Gas insulated, single busbar cubicle range Up to 27 kv / 2000 A / 31.5 ka General description Presentation Ormazabal s CPG System includes the CPG.1

More information

vertical fuse switch disconnectors

vertical fuse switch disconnectors SWITCHGEAR ARS vertical fuse switch disconnectors - touch protection IP 30 from the front - fibre glass extra strenghtened, self extinguishing thermoplastics - double clearance between open contacts -

More information

Central Inverter SUNNY CENTRAL 500HE-20/630HE-20/720HE-20/ 760HE-20/800HE-20

Central Inverter SUNNY CENTRAL 500HE-20/630HE-20/720HE-20/ 760HE-20/800HE-20 Central Inverter SUNNY CENTRAL 500HE-20/630HE-20/720HE-20/ 760HE-20/800HE-20 Maintenance Manual SC500-800HE20-WH-en-10 98-4110410 Version 1.0 EN SMA Solar Technology AG Table of Contents Table of Contents

More information

cpg.0 GIS-type medium-voltage switchgear with full insulation in SF 6 gas, up to 40.5 kv in accordance with IEC Standards

cpg.0 GIS-type medium-voltage switchgear with full insulation in SF 6 gas, up to 40.5 kv in accordance with IEC Standards GIS-type medium-voltage switchgear with full insulation in SF 6 gas, up to 40.5 kv in accordance with IEC Standards General Instructions IG-123-EN, version 09; 04/09/2017 CAUTION! When medium-voltage equipment

More information

Galaxy VM. Classic Battery Cabinet Installation GVMCBCWUE, GVMCBC2WUE, GVMCBC2WUF, GVMCBC3WUF 07/2017.

Galaxy VM. Classic Battery Cabinet Installation GVMCBCWUE, GVMCBC2WUE, GVMCBC2WUF, GVMCBC3WUF 07/2017. Galaxy VM Classic Battery Cabinet Installation GVMCBCWUE, GVMCBC2WUE, GVMCBC2WUF, GVMCBC3WUF 07/2017 www.schneider-electric.com Legal Information The Schneider Electric brand and any registered trademarks

More information

Switching DC Power Supply

Switching DC Power Supply 99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com Model 1693, 1694 Switching DC Power Supply INSTRUCTION MANUAL 1 Safety Summary

More information

Schneider Electric PV Skid. Optimized solar power conversion system tailored to enhance any North American PV power plant

Schneider Electric PV Skid. Optimized solar power conversion system tailored to enhance any North American PV power plant Schneider Electric PV Skid Optimized solar power conversion system tailored to enhance any North American PV power plant 1 PV Skid solution Integrated solution designed for optimal performance in any environment

More information

24 k B788 ELEKTROTECHNISCHE WERKE FRITZ DRIESCHER & SÖHNE GMBH

24 k B788 ELEKTROTECHNISCHE WERKE FRITZ DRIESCHER & SÖHNE GMBH 788 Instructions for Installation, Operation and Maintenance for DRIESCHER - Air - Insulated Medium - Voltage Compact Switchgears for Substations Rated voltage 12 kv and 24 kv Rated current 630 A 24 k

More information

INSTALLATION MANUAL. Instructions, precautions, suggestions for installing and servicing resin transformers in full compliance with safety rules

INSTALLATION MANUAL. Instructions, precautions, suggestions for installing and servicing resin transformers in full compliance with safety rules INSTALLATION MANUAL Instructions, precautions, suggestions for installing and servicing resin transformers in full compliance with safety rules ING TABLE OF CONTENTS 1. General information 2 1.1 Standards

More information

A E. P.M.G. range. Low Voltage Alternators - 4 pole. Installation and maintenance

A E. P.M.G. range. Low Voltage Alternators - 4 pole. Installation and maintenance A E This manual concerns the P.M.G. alternator which which you you have have just just purchased. We wish to draw your attention to the contents of this maintenance manual. SAFETY MEASURES Before using

More information

Compact System NRGS 11-2 NRGS Original Installation Instructions English

Compact System NRGS 11-2 NRGS Original Installation Instructions English Compact System NRGS 11-2 NRGS 16-2 EN English Original Installation Instructions 810366-05 1 Contents Important Notes Page Usage for the intended purpose...4 Safety note...4 LV (Low Voltage) Directive

More information

COMPACT AND EXTENSIBLE RING MAIN UNIT. insulated Ring Main Unit with load break switch or integrated vacuum circuit breaker

COMPACT AND EXTENSIBLE RING MAIN UNIT. insulated Ring Main Unit with load break switch or integrated vacuum circuit breaker DR-6/DT-6 COMPACT AND EXTENSIBLE RING MAIN UNIT BUILT TO LAST! DR-6/DT-6 Compact and/or extensible SF 6 insulated Ring Main Unit with load break switch or integrated vacuum circuit breaker SAFETY, RELIABILITY,

More information

UniGear. Technical Guide

UniGear. Technical Guide UniGear Technical Guide CONTENTS 0 CONTENTS 1.1 Compartments 1/2 1.2 Components of the structure 1/3 1.2.1 Hot-galvanized steel sheet 1/3 1.2.2 Painted steel sheet 1/4 1.2.3 Copper 1/5 1.2.4 Insulating

More information

Phase + Neutral, neutral on left side

Phase + Neutral, neutral on left side 87045 LIMOGES Cedex Téléphone : 05 55 06 87 87 Télécopie : 05 55 06 88 88 DX 3 MCB 10000 A / 16 ka CONTENTS PAGE 1. Description, use...1 2. Range...1 3. Overall dimensions...1 4. Preparation - Connection...1

More information

Dead Tank Outdoor Vacuum Circuit Breaker, Type VOX

Dead Tank Outdoor Vacuum Circuit Breaker, Type VOX Dead Tank Outdoor Vacuum Circuit Breaker, Type VOX Class 6065 Instruction Bulletin 6065-13 11/2011 Retain for future use. Hazard Categories and Special Symbols Read these instructions carefully and look

More information

SafeLink The Ultimate RMU. Rex de Bruyn PTMV New Zealand. ABB Ltd - Page 1 ABB

SafeLink The Ultimate RMU. Rex de Bruyn PTMV New Zealand. ABB Ltd - Page 1 ABB Rex de Bruyn PTMV New Zealand SafeLink The Ultimate RMU Ltd - Page 1 TheSafe Range of Ring Main Switchgear SafeLink : 12kV Compact Fuse Technology SafeRing : 12-24kV Fuse & Circuit Breaker Technology SafePlus

More information

Air-insulated switchgear UniGear type ZS1

Air-insulated switchgear UniGear type ZS1 Air-insulated switchgear UniGear type ZS1 ABB Power Technologies / 1-7074 D 12-03-2003 - Air-insulated switchgear UniGear type ZS1 ABB Power Technologies / 2-7075 D 1 2-03-2003 - Rated voltage kv 12 17.5

More information

WORKSHOP SPECIFICATIONS

WORKSHOP SPECIFICATIONS WORKSHOP SPECIFICATIONS DPX 3 160 & 250 MOULDED CASE CIRCUIT BREAKERS THE GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES DPX 3 RANGE Not only do DPX³ 160 and DPX 3 250 MCCBs provide

More information

B kv T&D GAS INSULATED SWITCHGEAR

B kv T&D GAS INSULATED SWITCHGEAR GAS INSULATED SWITCHGEAR B 105 170 300 kv The increasing demand for electrical power in cities and industrial centers necessitates the installation of a compact and efficient distribution and transmission

More information

Two-way cable interlock kit for Magnum drawout circuit breakers

Two-way cable interlock kit for Magnum drawout circuit breakers iwarning (1) ONLY QUALIFIED ELECTRICAL PERSONNEL SHOULD BE PERMITTED TO WORK ON THE EQUIPMENT. (2) ALWAYS DE-ENERGIZE PRIMARY AND SECONDARY CIRCUITS IF A CIRCUIT BREAKER CANNOT BE REMOVED TO A SAFE WORK

More information

GE Consumer & Industrial Power Protection. New. SecoGear kV Metal-clad Switchgear. GE imagination at work

GE Consumer & Industrial Power Protection. New. SecoGear kV Metal-clad Switchgear. GE imagination at work GE Consumer & Industrial Power Protection New SecoGear 12-24kV GE imagination at work General SecoGear metal-clad switchgear is designed and manufactured with advance technology and has been comprehensively

More information

SF6 Load Break Switch 2017 FIL3 - S. Indoor Medium Voltage LBS With or without fuse 12kV- 24kV FIL3 D FIL3. 24KV SF6 Load Break Switch

SF6 Load Break Switch 2017 FIL3 - S. Indoor Medium Voltage LBS With or without fuse 12kV- 24kV FIL3 D FIL3. 24KV SF6 Load Break Switch FIL3 - S FIL3 D Indoor Medium Voltage LBS With or without fuse 12kV- 24kV FIL3 24KV SF6 Load Break Switch Content 1. About Us 2. Load Break Switch Introduction 3. FIL3 product overview 3.1. Advantages

More information

Low voltage Direct Current Network. Compact NSX DC PV. Circuit breakers and switch disconnectors for solar application.

Low voltage Direct Current Network. Compact NSX DC PV. Circuit breakers and switch disconnectors for solar application. Low voltage Direct Current Network Compact NSX DC PV Circuit breakers and switch disconnectors for solar application Catalogue 2012 Compact NSX DC PV A complete DC offer for solar application from 80

More information

ACROBAT SWING STAND MODEL

ACROBAT SWING STAND MODEL Mounting instructions Directions for use ACROBAT SWING STAND MODEL Dr. Mach GmbH u. Co.KG, Flossmannstrasse 28, D-85560 Ebersberg Tel.: +49 (0)8092 2093 0, Fax +49 (0)8092 2093 50 Internet: www.dr-mach.com,

More information