1 GE Industrial Solutions User/Installation Manual for 4.76kV -15kV SecoBloc
2 Index General Scope...3 Standards...3 Operating conditions...3 Technical specification...3 Basic structure Features...4 Operation...4 Circuit Breaker Compartment...5 Interlocks...6 Transportation and storage Condition on delivery...7 Transport...7 Storage...7 Dimensions and Weight...8 Circuit Breaker Installation and Removal...9 Preparations...9 Move the circuit breaker from test position to connected position...10 Move the truck from connected position to test position...10 Circuit Breaker Operation...10 Trouble Shooting...11 Accessories / Operating Tools...11 Installation details of SecoBloc with switchgear...12 Busbar Installation...13 Recommended Torque Values...13 Ring CT Installation...14
3 General Scope SecoBloc modules are completely assembled compartments designed to house GE s SecoVac VB2+ vacuum circuit breakers. The modules can be stacked for two-high switchgear configurations, and mounted side-by side to form switchgear lineups. The OEM is responsible for supplying a rear section for main bus and cable connections, as well as the main and riser bus itself. The switchgear is for applications in kv power systems up to 3000A, with maximum short time withstand current up to 40kA and are compliant with the IEEE C standard for 60Hz. SecoBloc - BM: Breaker compartment enclosure. Standards and specifications The product complies with IEEE C Operating conditions The switchgear is designed for normal service conditions of indoor switchgear as per publication IEEE C The following limit values, among others, apply: Ambient temperature Maximum + 40 C 24h-Medium +35 C Minimum -15 C Humidity Highest average value measured over 24 hours Relative humidity 95% Highest average value measured over 1 month Relative humidity 90% The maximum site altitude is 1000 m above sea level Technical Specification Parameter Unit Rating Rated Voltage kv 4.76/8.25/15 Rated Frequency Hz 60 Rated Power-Frequency Withstand Voltage (1min) kv 36 Rated Lightning Impulse Withstand Voltage (peak) kv 95 Rated Current A 1200/2000/3000 Rated Short-time Withstand Current(3s) ka 31.5/ 40 Rated Peak Withstand Current ka 82/ 104 3
4 Basic Structure SecoBloc modules are designed for use in constructing MV switchgear arrangements and applications. Each unit of SecoBloc consists of circuit breaker compartment with integrated LV compartment. Features High quality steel sheets of 11 gauge (3 mm) thickness are used for the enclosure. Primary disconnects are supported by high-dielectric epoxy bushings, designed to mount ring-type current transformers. Front compartment doors are supplied as standard. Compartment door can be used for mounting LV equipment. Refer dimensional drawings for space allowance. The grounded internal barriers provide dead-front access to the circuit breaker when the busbars are energized. Doors and cover plates are treated against corrosion and then coated with high quality paint. The finishing coat is ANSI 61 grey color. Operation The circuit breaker can be placed in 3 positions: Connected position->circuit breaker racked in and locked in position, primary circuit connected, control plug connected Test position->circuit breaker racked out and locked in position, primary circuit disconnected, control plug connected Disconnected position->the circuit breaker can be unlocked and removed from the cubicle. Travel between connected and test positions is 200mm (7.87 inches). 1. Breaker Compartment 2. Space for LV Components 3. Metallic Shutter 4. Circuit breaker 5. Top and Bottom primary contact Insulators (Spouts) 6. Fixed contact 7. Ground bus connection 4
5 Circuit Breaker compartment The circuit breaker compartment contains all the necessary interfaces for the operation of the drawout VCB. Compartment is constructed of grounded metal barriers on all sides. The metallic shutters inside the compartment are moved by an actuating bracket mounted on the drawout VCB. The shutters are opened while racking to connected position, and are closed when the breaker is racked to the Test/Disconnect position or removed from the panel. From the Inspection window on the door, mechanical indicators for ON/OFF and Charged/Discharged and ON/OFF push buttons located on the circuit breaker can be observed. Figure 2: Circuit breaker compartment with and without VCB. 1. Secondary Wiring Socket 2. Top Shutter 3. Wiring Duct Cover 4. Bottom Shutter 5. Guide Rail 6. Secondary Wiring Plug 7. Front Facia 8. Racking Mechanism The drawout circuit breaker element consists of 1. Undercarriage Assembly 2. Primary Disconnect 3. Primary Finger Assembly 4. Secondary Disconnect The under carriage assembly establishes the mechanical connection between the panel and the circuit breaker. The circuit breaker element is moved by a racking handle manually or by a motor (optional feature), between the connected or test/disconnected positions. Auxiliary Switches (TOC) are provided in undercarriage to indicate connected and Test/Disconnected position. 1 Figure 3: SecoVac Drawout Vacuum Circuit Breaker 5
6 SecoBloc can be used for top or bottom Compartment. In circuit breaker compartment provision for mounting terminal blocks is provided on front as shown below in Figure 4. Suitable to mount terminal blocks type GE EB25, EB27, Marathon 1500 and Phoenix OTTA6 Provision for Terminal Block mounting Figure 4: Provision for mounting terminal blocks in circuit breaker compartment Provision for Terminal Block mounting Interlocks The SecoBloc module is equipped with IEEE required interlocks to block incorrect operations that could put the operator at risk and compromise the efficiency and reliability of equipment. These interlocks inhibit operations as shown in table 2: Table 2: Standard and optional interlocks offered in SecoBloc SecoBloc BM Interlocks Mechanical (M)/ Electrical (E) Standard (S) / Optional (O) Pad Lock of breaker rack in and out (Insertion of the circuit breaker racking-in/out crank lever) (Figure5) M S Circuit breaker secondary disconnect plug removal -truck in connected or undefined position (Figure 6) M S Circuit breaker racking-in - (circuit breaker secondary plug not connected) E O Pad Lock Figure 5: Padlock for breaker rack in/out Interlock lever and Roller Figure 6: Interlock for secondary disconnect pulg removal The secondary disconnect plug cannot be removed in connected position due to the interlock lever shown in Figure 6. Circuit breaker rack-in Interlock is provided in the under-carriage of the circuit breaker. 6
7 Transport and Storage Condition on delivery At the time of shipment, the factory- assembled SecoBloc module and drawout circuit breaker element are packed separately. The SecoBloc modules and breakers are verified in the factory for accuracy as per order requirement, and compliance with routine testing as per IEEE C Hang the Units Using All 4 Lifting Hooks Transport SecoBloc modules are shipped as individual units. The modules are equipped with four (4) lifting hooks (Figure 7). Only perform loading operations when all precautionary measures to protect personnel and materials have been taken, utilizing the following equipment: Crane with capacity to lift 2 tons (per single module) Fork-lift truck and/or manual trolley Lifting ropes/slings of appropriate load capacity (minimum of 600kg (1322lb) )with shackles Maintain an angle of at least 60 from the front for the ropes leading to the crane hook Figure 7: Lifting Single Panel (1) Lifting hooks (qty.4) Storage It is recommended that the SecoBloc module be immediately placed in its permanent indoor location. If this is not possible, the following precautions must be taken to assure proper storage. 1. The module should be protected against moisture and condensation, by storing indoors in a dry room, with temperatures between as -30 C C. If modules are to be used for outdoor metalclad switchgear, heaters should be installed and energized to prevent condensation. 2. The modules should be stored in a clean location, free from corrosive gases or fumes; particular care, for example, should be taken to protect the equipment from moisture and cement dust, as this combination is present at construction sites and has a very corrosive effect on many parts. Damage is possible if stored on side/back or top. 7
8 Dimensions and Weight Table3: Overall dimension different configurations of SecoBloc Width (max) - mm Depth (max) - mm Height (max) - mm Weight (kgs (lbs) 1200A,31.5 ka 914 (36) 1205 (47.45) 1100 (43.31) 514 (1133) SecoBloc BM 1200A, 40 ka 914 (36) 1205 (47.45) 1100 (43.31) 522 (1150) 2000A, 40 ka 914 (36) 1205 (47.45) 1100 (43.31) 574 (1265) 3000A, 40 ka 914 (36) 1205 (47.45) 1100 (43.31) 605(1333) D C A B BM A B C D 1200A,31.5 ka 258 (10.16) 947 (37.28) 275 (10.83) 468 (18.43) 1200/2000/3000A, 40 ka 271 (10.67) 934 (36.77) 310 (12.21) 483 (19.015) Figure 8: general outline diagram of SecoBloc for 1200A/2000/3000, 31.5/40 ka (All dimensions are in mm (inches) 8
9 Circuit Breaker Installation and Removal Preparations: Before start up, the following work should be completed. a. Visually inspect the overall condition of the module for damage. b. Ensure there are no unnecessary materials or tools inside of the compartment. c. Wipe the compartment body and the insulation parts, clean with a soft cloth d. Inspect and test the VB2+ circuit breaker per Instruction Book DEH Lift Truck Guide Arms Cell Mounted Guide Rails Lift Truck Locking Lever Insert circuit breaker truck into the switchgear a. Check the interlocking mechanism on the lift truck and apply lubricant on the moving parts to ensure smooth operation. b. Place the circuit breaker on lifting truck guide arms and ensure the locking tabs on the sides of the circuit breaker engage the slots on the lifting truck. (See Figure 9). Figure 11: Unlock circuit breaker from lifting truck Figure 9: Circuit breaker element on the lifting truck c. Move the lifting truck to the front of the switchgear; rotate the handle to adjust the height of the lifting truck platform (clockwise for up, counterclockwise for down), (See Figure 10). Figure 12: Lock circuit breaker in switchgear d. Release the lifting truck locking lever, and then remove the lifting truck. Alignment of the lifting truck rail with the bloc. Figure 10: Lifting truck lock with switchgear 9
10 Move the circuit breaker from test position to connected position a. Insert the secondary plug of the truck into the socket at the top of the circuit breaker compartment and lock it. (See Figure 13 and Figure 14). b. Make sure the circuit breaker is in open position (if it is not open, press breaker manual open push button). d. Turn the handle clockwise (approximately 20 turns) until it cannot be rotated any further, at the same time a click sound will be heard, then the breaker is in the connected position. The breaker position indicator will change the status from TEST to CONNECTED (Figure 16). Figure 13: Release secondary plug from VCB Move the truck from connected position to test position a. Make sure the circuit breaker is in open position (if it is not in open position, open by pressing the trip pushbutton). b. Reverse steps of moving the breaker to service position. c. The breaker position indicator will chang the status from CONNECTED to TEST (Figure 16). Figure 14: Insert secondary plug into cell-mounted socket c. Close the door and insert the racking handle into the racking access hole located at the bottom of the door (Figure 15) until the racking socket is engaged with the racking drive screw CONNECTED Position INTERMEDIATE Position DISCONNECTED Position Figure 16: Position indicator on SecoBloc -BM CONNECTED Position INTERMEDIATE Position DISCONNECTED Position Figure 15: Racking handle insertion on door 1. Circuit breaker door 2. Racking handle insertion hole 3. Racking handle Circuit breaker operation For operation instructions refer SecoVac VB2+ instruction manual. 10
11 Trouble shooting Diagnosis and trouble shooting for malfunctioning during operations Malfunction Reason Resolution The circuit breaker cannot be racked into connected position from test position The circuit breaker cannot be racked out to test position from connected position The circuit breaker cannot be closed The circuit breaker cannot be opened 1. The locking handles on the circuit breaker are not in position. 2. The circuit breaker is closed 3. Shutter is not completely open 4. Secondary plug is disconnected 1. Adjust the frame and handles 2. Open the circuit breaker 3. Visually check shutter drive mechanism 4. Insert in the secondary plug 1. The circuit breaker is closed 1. Open the circuit breaker 1. The secondary plug is not inserted 2. No control power supply 3. The circuit breaker is not fully in test /connected position 4. The closing spring has not been charged 1. No control power supply 2. Opening coil not working 1. Insert and lock secondary plug 2. Turn on control power supply 3. Rack circuit breaker to test or connected position 4. Charge the closing spring 1. Turn on control power supply 2. Check power supply for opening release **See VB2+ Instruction Book for additional circuit breaker opening and closing Trouble Shooting information.** Accessories / operating tools The accessories / operating tools are list as below: Name Unit Comments Rack in/out handle Piece Used to rack the breaker in or out though opening in bloc door. 11
12 Installation details of SecoBloc with Switchgear Installation with Switchgear SecoBloc BM can be mounted on top or bottom, and customer can connect to the rear, top, bottom and foundation plan (as shown in Figure 17, 18 and 19) Bottom mounting Grounding contact detail Figure 19: Foundation plan of SecoBloc BM (All dimension are in mm (inches) Bolt location for stacking modules Figure 17: SecoBloc stacking details Bolting locations for rear attachment of OEM furnished rear section While coupling the SecoBloc with OEM furnished rear section, be sure to maintain relief holes of min dia of 25 mm(1 in.) for A and 16.5mm (0.65 in.) for B( in Figure19), to avoid interference with the bolt head at locations shown in Figure 20. Connection-1 and 2: Bolt M10x25, M10 Spring washer, M10 washer/ quantity: 18(8+10) NOs. Figure18: Mounting details Rear, Top and Bottom of SecoBloc BM (All dimension are in mm (inches)) Figure 20: Hole/Relief details of switchgear - BM (All dimensions are in mm) 12
13 Figure 21: Mounting details Busbar and ground bus of SecoBloc BM (All dimension are in mm (Inches) Figure 22: Shows the critical dimensions to be maintained from breaker locking lever slot on frame to fixed contact surface Figure 23: Engagement of fix contact and moving contact Busbar Installation Customer shall design the main horizontal and riser bus bars for the panel to be assembled with the accessories and spout. Recommended branch busbar sizes are described in table 4. Bus shall be constructed of electrical grade copper, and silver or tin plated at all connecting joints. All bus must be insulated per IEEE C (Figure 20) using M10 (location A in Figure 21) and M16 (location B in Figure 21), 8.8 Grade MS hardware with the recommended torque values in table 5. Use M10 hardware for grounding connection (location C in Figure 21) Rating Material Busbar size In inches In mm 1200A Copper 0.19X6, 1/phase 5X150, 1/phase 2000A Copper 0.38X6, 1/phase 10X150, 1/phase Figure 22 and Table 6 shows the critical dimension to be maintained from breaker locking lever slot on frame to fixed contact surface, Figure 23 shows the engagement between fix contact of SecoBloc and moving contact of Breaker. Engagement dimension 20±5mm must be ensured when breaker is in connected position. Rating A (in mm) B (in mm) 1200A, 31.5kA SecoBloc BM 764 (30.1 in.) 1052 (41.42 in.) 1200A, 40kA SecoBloc BM 752 (29.61 in.) 1052 (41.42 in.) 2000A, 40kA SecoBloc BM 752 (29.61 in.) 1052 (41.42 in.) Recommended torque values Following table indicates torque values to be used for tightening the fasteners indicated in these documents. Table 6: Recommended torque Limits in N -m (ft-lb) Without Bolt size lubrication(oil) With lubrication(oil) M8 25(18.44) 10(7.37) M10 45(33.19) 25(18.44) M12 85(82.69) 45(33.19) M16 170(125.39) 94(69.33) 13
14 Ring type CT Installation SecoBloc can accommodate a maximum 4 ring type, standard accuracy class, CT s per phase (2 on each spout/bushing). CT s must be ordered separately or furnished by the OEM. To mount these CT s on the spout bushing, shutters must be open or removed (as shown in in Figure 25), tighten the bolt with M10 x100(for 1 CT/Spout) or M10x185 (for 2 CT/Spout) hardware and move the shutter down. Standard CTs offered by GE ITI for the rating 1200/2000/3000A Ring type CT is shown in Figure 25 and Shutter Assembly 2. Spout Bushing 3. Ring Type CT 4. Fixing Hardware Figure 24: Ring CT Mounting on Spout bushing of SecoBloc - BM Figure 25: Ring CT Rating and Mounting details for the SecoBloc for 1200 /2000A Figure 26: Ring CT Rating and Mounting details for the SecoBloc for 3000A 14
15 GE Industrial Solutions 41 Woodford Avenue Plainville, CT * Trademark of General Electric Company These instructions do not purport to cover all details or variations in equipment nor, to provide contingency to be met in connection with installation, operation, or maintenance. Should further information be desired, or should particular problems arise which are not covered sufficiently for the purchaser s purposes, the matter should be referred to GE DEH-50002
SecoVac * Ground & Test Device
GE Industrial Solutions DEH-50007 Installation, Operation and Maintenance Manual SecoVac * Ground & Test Device For 5kV-15kV IEEE Metal-clad Switchgear Table of Contents 1. Introduction...6 Safety Precautions...6
More informationPower/Vac OEM Express Switchgear
g Power/Vac OEM Express Switchgear Metalclad Switchgear 4.16kV-250 MVA through 13.8kV-1500 MVA DEA-275 FULLY ASSEMBLED MECHANICALLY COMPLETE SWITCHGEAR WITHOUT DEVICES AND WIRE. POWER/VAC OEM EXPRESS SWITCHGEAR
More informationGE CONSUMER & INDUSTRIAL
GE CONSUMER & INDUSTRIAL GE POWER/VAC MANUAL GROUND AND TEST DEVICE Types PVV-1200/2000-10 PVV-3000-10 PVV-1200-20 PVV-2000-20 PVV-1200/2000-20 PVV-3000-20 PVV-1200/2000/3000-20 Instruction Number GEK-86125B
More informationwith Vacuum Circuit Breaker HAF
M E T A L - C L A D S W I T C H G E A R Safety and Reliability with Vacuum Circuit Breaker HAF Flexible Design and Compact with Vacuum Circuit Breaker HVF Easy Installation and Maintenance We build a better
More informationGE Consumer & Industrial Power Protection. New. SecoGear kV Metal-clad Switchgear. GE imagination at work
GE Consumer & Industrial Power Protection New SecoGear 12-24kV GE imagination at work General SecoGear metal-clad switchgear is designed and manufactured with advance technology and has been comprehensively
More informationMetal Clad Air Insulated Switchgear
Metal Clad Air Insulated Switchgear 1/ SecoGear Metal Clad Switchgear Features Fully metal-clad Equipped with Embedded pole VCB Full Front access (can be installed against wall) Perfect interlocking system
More informationSpecification Guide. for RMVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers
Specification Guide for RMVAC Direct Replacement AC Medium Voltage Circuit Breakers Table of Contents 1.0 General Work Scope... 3 2.0 Standards... 3 3.0 Supplier Qualifications... 4 4.0 Circuit Breaker
More informationSubmersible Vacuum Fault Interrupters
Submersible Vacuum Fault Interrupters UG Distribution Medium Voltage Vacuum Fault Interrupters Functional Specification Guide PS024002EN Functional Specification for 2.4kV to 17.5kV UG Distribution Medium
More informationLow Voltage Switchgear Type WL Low Voltage Metal-Enclosed Switchgear
13 Low Voltage Switchgear Siemens Type WL low voltage metal-enclosed switchgear is designed, constructed and tested to provide superior power distribution, power monitoring and control. At the heart of
More informationMedium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION
Medium Voltage Standby non-paralleling Control 1. GENERAL GUIDE FORM SPECIFICATION A. The requirements of the contract, Division 1, and part 16 apply to work in this section. 1.01 SECTIONS INCLUDE A. Medium
More informationMEDIUM VOLTAGE CE-B METAL CLAD SWITCHBOARDS. CE-B-C-en-REV
CE--C-en-REV.04 2016.1 MEDIUM VOLTAGE MEDIUM VOLTAGE APPLICATION CE- Metal Clad switchboards family are designed for use in public and industrial distribution system up to 40,5kV for the operation and
More informationMASTERCLAD. Metalclad Indoor Switchgear 27 kv with Type VR Vacuum Circuit Breakers Class Instruction Bulletin. Retain for future use.
Instruction Bulletin Retain for future use. MASTERCLAD Metalclad Indoor Switchgear 27 kv with Type VR Vacuum Circuit Breakers Class 6055 HAZARD CATEGORIES AND SPECIAL SYMBOLS Read these instructions carefully
More informationMEDIUM VOLTAGE CE-B36 METAL CLAD SWITCHBOARDS. CE - B36 - C - en - REV
CE - B36 - C - en - REV.00 2011.9 EDIU VOLTAGE EDIU VOLTAGE APPLICATION CE-B etal Clad switchboards are designed for use in public and industrial distribution system up to 36kV for the operation and protection
More informationMASTERCLAD Metal-Clad Indoor Switchgear
Instruction Bulletin 6055-30 MASTERCLAD Metal-Clad Indoor Switchgear 4.76 15.0 kv Series 5 With Type VR Vacuum Circuit Breakers Class 6055 MASTERCLAD Metal-Clad Indoor Switchgear Bulletin 6055-30 SQUARE
More informationKYN28A-12 (GZS1) A.C METALCLAD REMOVABLE SWITCHGEAR FOR INDOOR USE CHINATCS
KYN28A-12 (GZS1) A.C METALCLAD REMOVABLE SWITCHGEAR FOR INDOOR USE CHINATCS 2001.09 KYN28A-12 (GZS1) A.C Metalclad Removable Switchgear for Indoor Use --------The Leader in Switchgear Up to 12kV 1. The
More informationPower Break Circuit Breakers
Draw Out 800-4000 Amperes GEH-46988 Installation Instructions Power Break Circuit Breakers POWER BREAK Draw Out Circuit Breaker (SOOA 4000A) DESCRIPTION Types TC, and THC Power Break draw out circuit breakers
More informationPIX-H Metal-clad switchgear up to 17.5kV
AIR INSULATED SWITCHGEAR PIX-H Metal-clad switchgear up to 17.5kV for high rated applications Technical Specifications AREVA T&D Summary - Technical description... 3 - Standards... 6 - PIX in detail...
More informationPATENT PENDING. Phone: (877) Operation and Service Manual
PATENT PENDING Phone: (877) 544-2291 Operation and Service Manual 2 IMPORTANT NOTICE This document contains information intended to aid in the proper installation, operation, and maintenance of the product
More informationSafe and Reliable. Flexible, Compact Design. Easy Installation and Maintenance
M E T A L - C L A D S W I T C H G E A R Safe and Reliable Flexible, Compact Design Easy Installation and Maintenance We build a better future! Hyundai HMS medium-voltage metal-clad switchgears and control-gears,
More informationSYSclad switchboard equipped with draw out type vacuum circuit breaker closed dooroperationoperation. SYSclad 12 17,5kV A.
SYSclad switchboard equipped with draw out type vacuum circuit breaker closed dooroperationoperation 630 3150A SYSclad 12 17,5kV 16 31,5kA Generalities SYSclad is a medium voltage switchboard metal clad
More informationME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position
LET S BE PACIFIC November 0 Volume Number 5 ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position Federal Pacific has the capability to engineer, fabricate and assemble
More informationSecoVac * Vacuum Circuit Breaker
GE DEH-50001 Installation, Operation and Maintenance Manual SecoVac * Vacuum Circuit Breaker For 5kV-15kV IEEE Metal-clad Switchgear Table of Contents 1. Introduction... 7 2. Safety Instruction... 8 3.
More informationSUBSTATION VACUUM CIRCUIT BREAKER (38KV)
SUBSTATION VACUUM CIRCUIT BREAKER (38KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products for utilities
More informationMEDIUM VOLTAGE CE-B METAL CLAD SWITCHBOARDS. CE - B - C - en - REV
MEDIUM VOLTAGE MEDIUM VOLTAGE APPLICATION CE-B Metal Clad switchboards are designed for use in public and industrial distribution system up to 24kV for the operation and protection of lines, generators,
More informationSUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)
SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products for utilities
More informationSUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)
SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products
More informationTest Cabinet (Inspection Box) Instructions. for Testing Accessories on Manually and Electrically Operated EntelliGuard G Low Voltage Circuit Breakers
DEH41480 Test Cabinet (Inspection Box) for Testing Accessories on Manually and Electrically Operated EntelliGuard G Low Voltage Circuit Breakers Instructions 1 Table of Contents Section 1. Introduction
More informationGE Industrial Solutions. DEH Installation and Maintenance Manual AKD-20 AR / Entellisys AR Exhaust Plenum System
GE Industrial Solutions DEH-41474 Installation and Maintenance Manual AKD-20 AR / Entellisys AR Exhaust Plenum System Table of Contents General Information... ii Hazard Classifications... ii Trademarks...
More informationSpecification Guide. for RMAX. Direct Replacement. AC Low Voltage. Power Circuit Breakers
Specification Guide for RMAX Direct Replacement AC Low Voltage Power Circuit Breakers Table of Contents 1.0 General Work Scope...3 2.0 Standards... 3 3.0 Supplier Qualifications... 3 4.0 Mechanical and
More informationSafeGear Motor Control Center Arc Resistant Metal-Clad Construction Brochure
2017 SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Brochure SafeGear Motor Control Center Arc resistant Metal-Clad construction Brochure Table of Contents 1. Description 1 1 2. SafeGear
More informationOperation and Maintenance Manual
DEH-41482 GE Energy Industrial Solutions Low Voltage Switchgear Remote Racking Operator For AKR Circuit Breakers Cat. # AKREGRR 115 VAC, 60/50 Hertz Operation and Maintenance Manual TABLE OF CONTENTS Section
More informationInstruction for Installation and Operation
KYN79 (i-ax) Metalclad Removable AC Metal-Enclosed Switchgear Instruction for Installation and Operation K 15 24 SM 01 02 Tianshui Changcheng Switchgear Factory January, 2007 Warning: This instruction
More informationBHARAT HEAVY ELECTRICALS LIMITED, JHANSI
BHARAT HEAVY ELECTRICALS LIMITED, JHANSI DESIGN, MANUFACTURING, TESTING, SUPPLY INSTALLATION AND COMMISSIONING OF 11KV VACUUM CIRCUIT BREAKER NOTE : 1 VENDOR must submit complete information against clause
More informationMetal-Clad Indoor Switchgear
Instruction Bulletin Bulletin 6055-10 Metal-Clad Indoor Switchgear 4.76 15.0 kv Series 3 With Type VAD-3 Vacuum Circuit Breakers 1 NOTICE Read these instructions carefully and look at the equipment to
More information5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application
The most advanced Arc-Resistant Switchgear, designed and built to provide maximum safety in the event of an Internal Arcing Fault. 5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application Page 1
More information2018 Consultant s Handbook Division 26 Electrical 2413 Switchboards
1 General 1.1 Switchboards shall be U.L. listed and labeled. 1.2 Each switchboard shall have its own main disconnecting means unless it is located in the same room as its source of origin. In most cases
More informationMedium Voltage Equipment 5-15 kv GM-SG and 38 kv GM38 Metal-Clad Switchgear General
13 SWITCHGEAR Medium Voltage Equipment -1 kv GM-SG and 38 kv GM38 Metal-Clad Switchgear General Overview Features Siemens, 7, 1 and 38kV class medium voltage, one- or two-high vacuum circuit breaker switchgear
More informationL Frame - Assembly Guidelines
GE Energy Connections L Frame - ssembly Guidelines Product User ssembly Instructions Manual Table of Contents Introduction... 3 Index... 4 Section 1. L Frame Outline & Interface Dimensions...4 Outline
More informationProTrip Conversion Kits. For GE Types AK-15, AK-25, and AKU- 25 Low-Voltage Power Circuit Breakers INTRODUCTION. DEH Installation Instructions
DEH 40026 Installation Instructions g ProTrip Conversion Kits For GE Types AK-15, AK-25, and AKU- 25 Low-Voltage Power Circuit Breakers INTRODUCTION GE Conversion Kits are designed for upgrading existing
More informationVacuum Circuit Breakers (Vehicle) Type HKR 7.5kV to 15kV. Instructions Installation Operation Maintenance SGIM-9928C
Vacuum Circuit Breakers (Vehicle) Type HKR 7.5kV to 15kV Instructions Installation Operation Maintenance SGIM-9928C Hazardous voltages and high-speed moving parts. Will cause death, serious injury or equipment
More informationAdvance design OEM L-Frames, cell kits, & enclosures Metal-clad switchgear components OEM catalog & pricing
Advance design OEM L-Frames, cell kits, & enclosures Metal-clad switchgear components OEM catalog & pricing Introduction A modular system of switchgear building blocks and cassettes provide untouchable
More informationPosition Switch Kits Accessory Kits for EntelliGuard* Retrofill Circuit Breakers
GE Industrial Solutions Position Switch Kits Accessory Kits for EntelliGuard* Retrofill Circuit Breakers This position switch actuator, mounted on the cassette using simple hardware, is an actuator or
More informationAIR INSULATED EXTENDABLE SWITCHGEAR UP TO 12KV GUIDE
AIR INSULATED EXTENDABLE SWITCHGEAR UP TO 12KV GUIDE Certificate Number FM35831 APPLICATION Typical Uses and Classification The MSGair switchgear is used in transformer and switching substations mainly
More informationType SIMOPRIME A4, up to 24 kv, Air-Insulated Medium-Voltage Switchgear
Circuit-Breaker www.siemens.com/energy Switchgear Type SIMOPRIME A4, up to 24 kv, Air-Insulated Medium-Voltage Switchgear s Technology Circuit-Breaker Switchgear Type SIMOPRIME, up to 17.5 kv, Air-Insulated
More informationATLV MaxSG. Low Voltage Metal Enclosed Switchgear
ATLV MaxSG Low Voltage Metal Enclosed Switchgear ABB, INC. Product General Description MaxSG Switchgear ABB MaxSG switchgear is a further continuation in the development of innovative products from ABB,
More informationVacClad-W type VCP-W 5 and 15 kv, 36-inch-wide switchgear components
Supersedes July 2002 Contents Page Procedure for identifying parts... 2 Customer ordering instructions.... 2 Distributor ordering instructions.... 2 Front panel components.... 3 Breaker pan assembly....
More informationT- VACR Fixed (up to 40kA) T-VAC Draw out (up to 40kA)
Instructions for the Use, Operation and Maintenance of Types T-VAC and T-VACR Vacuum Circuit Breakers Effective November 2017 T- VACR Fixed (up to 25kA) T-VAC Draw out (up to 25kA) T- VACR Fixed (up to
More informationVacuum Circuit Breakers (Vehicle)
Vacuum Circuit Breakers (Vehicle) Type 5 HVR 4.16kV Instructions Installation Operation Maintenance SGIM-9948D Hazardous voltages and high-speed moving parts. Will cause death, serious injury or equipment
More informationInstructions for installation, operation, and maintenance of 38 kv type VacClad-W arc resistant metal-clad switchgear
Contents Description Page Introduction.... 4 Installing indoor switchgear.... 6 A further description of arc-resistant VacClad-W switchgear.... 13 Adjusting and testing.... 20 Operation of the system....
More informationCircuit-Breaker Switchgear Type SIMOPRIME, up to 17.5 kv, Air-Insulated Medium-Voltage Switchgear.
Circuit-Breaker Switchgear Type SIMOPRIME, up to 17.5 kv, Air-Insulated Medium-Voltage Switchgear www.siemens.com/energy Technology s Contents Application Page Benefits 2 Typical uses 2 and 3 Technical
More informationMedium voltage switchgear SafeGear HD 63 ka arc resistant metal-clad switchgear. ABB Group February 25, 2015 Slide 1
Medium voltage switchgear SafeGear HD 63 ka arc resistant metal-clad switchgear ABB Group February 25, 2015 Slide 1 SafeGear HD arc resistant switchgear 63 ka arc resistant metal-clad air insulated switchgear
More informationSecoVac * R Retrofill Vacuum Circuit Breaker
GE DEH-5000 User Manual SecoVac * R Retrofill Vacuum Circuit Breaker 5-5kV 200A & 2000A Table of Contents. Introduction...5 Definitions...5 2. Safety...6 3. Receiving...7 Inspecting for Damage...7 Filing
More informationDesign Standard. Purpose: Design Standard:
Design Standard Purpose: This design standard has the purpose of creating a consistent application of motor-control centers throughout the East Side Union High School District, therefore achieving a standard
More informationUser manual W-VACi. W-VACi 12 / 17.5 / 24 kv IEC Vacuum Circuit Breakers
User manual W-VACi W-VACi 12 / 17.5 / 24 kv IEC Vacuum Circuit Breakers 65A7355H01 Rev.04 January 2013 www.eaton.com 2 Table of contents 1 Safety... 5 1.1 Safety precautions...5 1.2 Safety practices...5
More informationAll rights reserved. Neither this catalogue nor any part of it may be copied using any method or for any purposes. Most studies are legally protected.
Issued: January 2013 Copyright by ZPUE Katowice S.A. All rights reserved. Neither this catalogue nor any part of it may be copied using any method or for any purposes. Most studies are legally protected.
More informationMV Metalclad Switchgear 4760V-15000V 20KA-63KA. AC Power Circuit Breaker Rating Structure. Test Procedures for Power Circuit Breakers
Contents Key Features and Benefits Codes and Standards Value Addition by Application of PVAC-E GE Components Inside Design Features on PVAC-E Switchgear PVAC-E Switchgear Configuration PVAC-E Switchgear
More informationVacuum Circuit Breakers (Vehicle) Type MSV 5kV. Instructions Installation Operation Maintenance SGIM-9988
Vacuum Circuit Breakers (Vehicle) Type MSV 5kV Instructions Installation Operation Maintenance SGIM-9988 Hazardous voltages and high-speed moving parts. Will cause death, serious injury or equipment damage.
More informationMetal Clad VCBs ~ Mk1
Metal Clad VCBs ~ Mk1 DUVI 150/40 ROLL ON FLOOR VCBs Range: 6kV, 00A, 1.5kA, 12kV, 150A, 40kA ( 4A000A Bus-Bars ) ` Widest range for MV (up to 6kV) Distribution Networks Megawin make metal clad VCB Panels
More information36kV Gas Insulated Medium Voltage Switchgear
GE Industrial Solutions 36kV Gas Insulated Medium Voltage Switchgear User Manual Safety first! Important recommendations: Switchgear should be installed in a clean, dry, ventilated room suitable for electrical
More informationVacuum Circuit Breaker (Vehicle)
Vacuum Circuit Breaker (Vehicle) Type 5 HVU-250 4.76kV Instructions Installation Operation Maintenance SGIM-9998A Hazardous voltages and high-speed moving parts. Will cause death, serious injury or equipment
More informationEISHO TEK. Vacuum Circuit Breaker
EISHO TEK Vacuum Circuit Breaker TYPE:SV1-12 INSTRUCTION MANUAL Operation and Maintenance Version TAIWAN CALSONIC SAFETY PRECAUTIONS For safety reason, this equipment should be handled by personnel who
More informationSwitchgear Skid, C1192
CUSTOM SOLUTIONS 15kV Modular Stairs stored on floor in front of battery bay Ground grid stored on front tongue of trailer Stairs deployed for unit access Storage box for fencing materials and other parts
More informationGE Energy Connections Industrial Solutions. DET-882 Application and Technical Guide. SecoGear
GE Energy Connections Industrial Solutions DET-882 Application and Technical Guide SecoGear Me - Switchgear HAZARD CLASSIFICATIONS The following important highlighted information appears throughout this
More informationVacuum Circuit Breakers (Vehicle) Type FSV 5kV to 15kV. Instructions Installation Operation Maintenance SGIM-9968
Vacuum Circuit Breakers (Vehicle) Type FSV 5kV to 15kV Instructions Installation Operation Maintenance SGIM-9968 Hazardous voltages and high-speed moving parts. Will cause death, serious injury or equipment
More informationInstructions for VCP-W Simple Electrical Ground & Test Device (SEG&TD) with simplified interlock scheme - bottom terminal set version
IB131018EN Instructions for VCP-W Simple Electrical Ground & Test Device (SEG&TD) with simplified interlock scheme - bottom terminal set version Contents Description Page 1. Introduction...2 2. Description...2
More informationwith Vacuum Circuit Breaker HAF
M E T A L - C L A D S W I T C H G E A R Safety and Reliability with Vacuum Circuit Breaker HAF Flexible Design and Compact with Vacuum Circuit Breaker HVF Easy Installation and Maintenance We build a better
More informationMEDIUM VOLTAGE AIR INSULATED ARC-RESISTANT LOAD BREAK AND DISCONNECT SWITCHES
MEDIUM VOLTAGE AIR INSULATED ARC-RESISTANT LOAD BREAK AND DISCONNECT SWITCHES Description JRS arc-resistant fused/non-fused load break and fused/non-fused disconnect switches are available for applications
More informationEntelliGuard Power Circuit Breaker Accessories. Network Interlock for Ampere Circuit Breakers. Introduction. Operation
DEH41118 Installation Instructions R01 R02 g EntelliGuard Power Circuit Breaker Accessories Network Interlock for 3200-5000 Ampere Circuit Breakers Introduction The Network Interlock provides a means of
More informationInstructions for the Use, Operation and Maintenance of Types VCP-TL and VCP-TRL Linear Magnetic Vacuum Circuit Breakers
Instructions for the Use, Operation and Maintenance of Types VCP-TL and VCP-TRL Linear Magnetic Vacuum Circuit Breakers Effective May 2016 VCP-TRL Fixed (shown with optional protective relay installed)
More informationGeneral. Main electric circuits Fuses compartment Operating mechanisms Cables connection compartment
General The switchgear must be suitable for 36 kv rated voltage and specifically conceived for the secondary distribution substations in M.V. with either ring or radial type networks. The switchgear must
More informationVoltage Rated operating voltage [kv] Rated power frequency withstand voltage [kv] Rated lightning impulse withstand voltage [kv]
BasisBlock MC 1 Standards and Regulations IEC 62271-200 ; VDE 0671-200 ; BS EN 62271-200 Technical Data MC1-12 MC1-24 Voltage Rated operating voltage [kv] 12 24 Rated power frequency withstand voltage
More informationMedium Voltage Metal-Enclosed Switches
Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Introduction Product Selection Guide....................................2 Medium Voltage Switch MVS Product Description......................................
More informationTECHNICAL SPECIFICATION OF 11KV SF6 / VCB METAL ENCLOSED, INDOOR (PANEL TYPE) / OUTDOOR RING MAIN UNIT (RMU). (IEC standard equipment)
TECHNICAL SPECIFICATION OF 11KV SF6 / VCB METAL ENCLOSED, INDOOR (PANEL TYPE) / OUTDOOR RING MAIN UNIT (RMU). (IEC standard equipment) 1 SCOPE OF SUPPLY This specification covers design, manufacture, shop
More informationVacuum Circuit Breakers (Vehicle)
Vacuum Circuit Breakers (Vehicle) Type DTR 7.5kV to 15kV Instructions Installation Operation Maintenance SGIM-9938B Hazardous voltages and high-speed moving parts. Will cause death, serious injury or equipment
More informationProduct Specification Guide. Title: Southern States 72 kv RLSwitcher Vertical Interrupter Style Reactor Switcher
TABLE OF CONTENTS PAGE 1.0 SCOPE... 2 2.0 STANDARDS... 2 3.0 DESIGN REQUIREMENTS... 2 3.01 Service Conditions... 2 3.02 Ratings... 3 3.03 Interrupter... 3 3.04 SF6 Gas System... 4 3.05 Terminal Pads...
More informationPOWERCON CORPORATION
POWERCON CORPORATION 38,000 VOLT METAL-CLAD SWITCHGEAR BROCHURE #PC-041 ELECTRONIC VERSION CREATED: 6/30/96 Powercon Corporation P.O. Box 477 1551 Florida Avenue Severn, Maryland 21144 Baltimore: 410-551-6500
More informationMESG 12 / 17.5 / 24 / 36 KV
MESG 12 / 17.5 / 24 / 36 KV Medium Voltage Air Insulated Metal Enclosed Switchgear up to 36 kv- up to 1250 A - up to 25 ka for 1 sec. with SF6 or vacuum circuit breakers. 750 METAL ENCLOSED 1 1 ) GENERAL
More information33KV INDOOR SWITCHGEAR
33KV INDOOR SWITCHGEAR September 2017 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, Sector-II, Bidhannagar, Kolkata 700091. CIN:
More informationMV Air Insulated Switchgear TAP17. Technical Data TGOOD
MV Air Insulated Switchgear TAP17 Technical Data TGOOD 2017.1 Operating environmental conditions Place of installation: Indoor or outdoor Ambient temperature: 25 ~ +40 (higher or lower temperature optional)
More informationSafeGear TM Motor Control Center Arc resistant metal-clad construction
SafeGear TM Motor Control Center Arc resistant metal-clad construction Contents Description 2 SafeGear TM MCC applications 3 Electrical features 3 Standards 3 Standard service conditions 4 HCV vacuum contactor
More informationAir-insulated switchgear UniGear type ZS1
Air-insulated switchgear UniGear type ZS1 ABB Power Technologies / 1-7074 D 12-03-2003 - Air-insulated switchgear UniGear type ZS1 ABB Power Technologies / 2-7075 D 1 2-03-2003 - Rated voltage kv 12 17.5
More informationMedium Voltage Metal-Enclosed Switches
Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Medium Voltage Switch MVS Product Description............................................. 2 Application Description..........................................
More informationBenefits, typical uses
R-HA26-013. eps Switchgear Type 8BT1, up to 24kV,Air-Insulated Contents Application Page Application Benefits 2 Typical uses 2 and 3 Technical Data Ratings 4 Classification, dimensions, 5 room planning
More informationOur brand POWER DYNAMIC PASSION COMMITMENT CREATIVITY. A strong brand for strong products: 8PU Premium. MV Energy
Our brand A strong brand for strong products: The ENERGOLINE brand represents our product portfolio of INDUSTRIAL SWITCHGEAR SYSTEMS. Our products are characterized by a high degree of safety, flexibility
More informationIB PowlVac ITE-HK Remote Racking Device
IB-51802 PowlVac ITE-HK Remote Racking Device for use with ITE-HK 5kV & 15kV Circuit Breakers and PowlVac ITE-HK 5kV & 15kV Replacement Circuit Breakers Powered by Safety PowlVac ITE-HK Remote Racking
More informationProduct Specification Guide. Title: Southern States 362 kv RLSwitcher Vertical Interrupter Style Reactor Switcher
TABLE OF CONTENTS PAGE 1.0 SCOPE... 2 2.0 STANDARDS... 2 3.0 DESIGN REQUIREMENTS... 2 3.01 Service Conditions... 2 3.02 Ratings... 2 3.03 Interrupter... 3 3.04 SF6 Gas System... 4 3.05 Terminal Pads...
More informationSwitchgear Type 8BT1, up to 24 kv, air-insulated. Medium Voltage Switchgear Catalog HA 26.
www.siemens.com/medium-voltage-switchgear Switchgear Type 8BT1, up to 24 kv, air-insulated Medium Voltage Switchgear Catalog HA 26.31 2012 Answers for infrastructure and cities. R-HA26-013. eps Contents
More informationType 2 Arc Resistant WL Low Voltage Metal-Enclosed Switchgear
Type 2 Arc Resistant WL Low Voltage Metal-Enclosed Switchgear IMPORTANT The information contained herein is general in nature and not intended for specific application purposes. It does not relieve the
More informationVacuum Circuit Breaker
Vacuum Circuit Breaker 12/24kV VECTOR series Vacuum Circuit Breaker VMS series Metal-clad Switchgear Medium Voltage Systems 003 FM 73638 12/24kV VECTOR VCB Features of the VECTOR Vacuum Circuit Breaker:
More information50 / 75 / 150 DHP [Cable or Hard Bus Application] Ground and Test Device
Instruction Book IB182217EN Supersedes May 2016 Effective October 2018 50 / 75 / 150 DHP [Cable or Hard Bus Application] 150 DHP (Cable Type Device) 150 DHP (Hard Bus Type Device) DISCLAIMER OF WARRANTIES
More informationGE Electrical Distribution. Gerapid High Speed DC Circuit Breakers. On the move. imagination at work
GE Electrical Distribution Gerapid High Speed DC Circuit Breakers On the move imagination at work Gerapid High Speed DC Circuit Breakers To stay up and running today, you need equipment that delivers both
More informationMetal-Enclosed Switches. Medium Voltage. Medium Voltage Metal-Enclosed Switches Contents
January 2003 Vol. 1, Ref. No. [1011] -1 Medium Voltage Metal-Enclosed Switches Contents Description Page MVS................................... -2 and Breaker MSB........................ -3 Metal-Enclosed
More informationMCset 4-24 kv Withdrawable SF6 circuit breaker
Medium Voltage switchgear MCset 4-24 kv Withdrawable SF6 circuit breaker Instruction for use Contents General 2 Glossary 2 Symbols 2 Recommendations 3 General description 4 AD4 unit 4 AD4 unit with toroidal
More informationPublication No.: PSG
TABLE OF CONTENTS PAGE 1.0 SCOPE...2 2.0 STANDARDS...2 3.0 DESIGN REQUIREMENTS...2 3.01 Service Conditions... 2 3.02 Ratings... 3 3.03 Resistors... 3 3.04 Interrupter... 4 3.05 SF 6 Gas System... 4 3.06
More informationB kv T&D GAS INSULATED SWITCHGEAR
GAS INSULATED SWITCHGEAR B 105 170 300 kv The increasing demand for electrical power in cities and industrial centers necessitates the installation of a compact and efficient distribution and transmission
More informationLow Voltage WavePro TM and EntelliGuard TM Circuit Breakers Remote Racking Operator
GE Consumer & Industrial Electrical Distribution Operation & Maintenance Manual GEK-99986 Catalog # WPEGRRLV 115 VAC, 60/50 Hz Low Voltage WavePro TM and EntelliGuard TM Circuit Breakers Remote Racking
More informationThree-Phase Pole Mounted Recloser
Three-Phase Pole Mounted Recloser Page 1 of 8 Table of Contents 1 GENERAL... 3 2 CONSTRUCTION... 3-5 3 BUSHINGS... 5 4 LINE CONNECTOR... 5 5 TOOLS....5 6 NAMEPLATES..6 7 PAINT... 6 8 EXTERNAL HARDWARE
More informationThe vacuum circuit breaker for commercial buildings, industrial plants and utilities
The vacuum circuit breaker for commercial buildings, industrial plants and utilities EasyPact EXE The easy choice for more value 2 EasyPact EXE EasyPact EXE, a medium voltage vacuum circuit breaker optimizing
More informationCGMCOSMOS. Reliable innovation. Personal solutions. Fully gas insulated modular and compact (RMU)system.
MV Switchgear for CGMCOSMOS Fully gas insulated modular and compact (RMU)system Up to 24 kv Up to 27 kv mediumvoltage mediumvoltageag AG Langackerstrasse Langackerstrasse 25 25 CH CH 6330 6330 Cham Cham
More informationVacuum Circuit Breakers (Vehicle)
Vacuum Circuit Breakers (Vehicle) Type MSV 5kV Instructions Installation Operation Maintenance SGIM-9988A Hazardous voltages and high-speed moving parts. Will cause death, serious injury or equipment damage.
More information