SM6. instructions for use. IMB cubicle without earthing switch. MV distribution factory built assemblies at your service. Anglais

Size: px
Start display at page:

Download "SM6. instructions for use. IMB cubicle without earthing switch. MV distribution factory built assemblies at your service. Anglais"

Transcription

1 SM6 Anglais MV distribution factory built assemblies at your service instructions for use IMB cubicle without earthing switch

2 foreword... 3 symbols and conventions... 3 as per iso contact the Schneider Electric service unit for diagnosis and advice 3 4 distribution rules... safety rules general description... 5 IMB cubicle without earthing switch bottom right connection... 5 IMB cubicle without earthing switch bottom left connection... 5 handling instructions... 7 cubicle identification... accessories list weight... dimensions handling using slings... handling using a forklift stockage... 9 installation and operation recommendation installation instructions preparing the cubicles for switchboard assembly assembling the switchboard... securing to the floor layout in the substation... fitting the busbars after installing the cubicles cable entry for connection of low voltage auxiliaries... fitting the earth bars start---up instructions checks before energizing operating test before energizing energizing the bottom busbars operating instructions manual operation and position indication discharging a CI2 operating mechanism... padlocking keyed interlocks operating safety maintenance instructions preventive maintenance, cleaning instructions and power---up... replacing a voltage indicator block trouble--- shooting chart... options recovery of SF6 gas at end of life EN revision : 01 1

3 EN revision : 01

4 foreword symbols and conventions Caution: you will find all the symbols below throughout the document, indicating the hazard levels depending on the different types of situation. DANGER as per iso DANGER: failure to follow this instruction will result in death or serious injury. WARNING as per iso WARNING: failure to follow this instruction may result in death or serious injury. CAUTION as per iso CAUTION: failure to follow this instruction may result in injuries. This alert signal can also be used to indicate practices that could damage the SM6 unit. INFORMATION-ADVICE We draw your attention to this specific point EN revision : 01 3

5 contact the Schneider Electric service unit for diagnosis and advice Call your sales representative who willputyouincontactwith the closest SCHNEIDER ELECTRIC group service centre. You can log on to: electric.com distribution rules The aim of this publication is to enable the SM6 unit to be installed correctly. This document is not a commercial document. It is a strictly technical document drawn up by Schneider Electric. safety rules CAUTION WARNING All the operations described below must be performed in compliance with applicable safety standards, under the responsibility of a competent authority. Thecontractormustbecertified and authorised to manipulate and perform work on the SM6 unit. CAUTION Only undertake the work after having read and understood all the explanations given in this document. If you have any difficulty complying with these rules, please contact Schneider Electric EN revision : 01

6 general description IMB cubicle without earthing switch bottom right connection 1 : low voltage compartment 2 : top busbar compartment 3 :operatingmechanism compartment 4 : switchgear compartment: switch 5 : bottom busbar connection compartment A : top busbar connection pads B : voltage indicator C : bottom field distributor and busbar connection D : capacitive divider E : inspection windows F : front panel 2 A 4 5 C 1 3 B F D E IMB cubicle without earthing switch bottom left connection 1 : low voltage compartment 2 : top busbar compartment 3 :operatingmechanism compartment 4 : switchgear compartment: switch 5 : bottom busbar connection compartment A : top busbar connection pads B : voltage indicator C : bottom field distributor and busbar connection D : capacitive divider E : inspection windows F : front panel 2 A 4 5 C D 1 3 B F E EN revision : 01 5

7 EN revision : 01

8 handling instructions cubicle identification A D3 D2 B E D1 6 C F A :indicatorplate (for customer use). B : characteristics and designation C : manufacturer s name plate E : motor mechanism (option) plate F : danger symbol for electrical hazards serial number D1: riveted to the front plate of the operating mechanism compartment D2: glued to the back of the front plate of the low voltage compartment D3: glued to the upright of the frame accessories list accessories provided with the cubicle weight 130 kg switchboard accessories : (may vary depending on the cubicles making up the switchboard) 1operatinglever 2 end panels 1 bag of nuts and bolts for the end panels 1 wall clearance angle---iron cubicle accessories : 2 bags of field distributors for busbars >12kV(bagS2 : ) or 2 bags of fastening accessories for busbars ±12 kv (bag S6 : ) 1earthbar 1setofbusbars 1 bag of intercubicle connection accessories (bag S1 : ) Never attempt to move the cubicle by exerting force on the control panel EN revision : 01 7

9 dimensions handling using slings L L 60 MAXI 60 MAXI L = 375 mm mini. Whith low voltage enclosure and gutter. L = 920 mm mini. Whithout low voltage enclosure and gutter. handling using a forklift EN revision : 01

10 stockage 70 C C EN revision : 01 9

11 EN revision : 01

12 installation and operation recommendation switchgear ageing withstandinanmv substation depends on 3 main factors: H The need for proper implementation of connections: the new cold slip --- on and retractable technologies offer ease of installation, thereby promoting withstand over time. Their design enables operation in polluted environments with harsh atmospheres. H Theinfluenceoftherelative humidity factor: installation of heating resistors is essential in climates with high relative humidity and large temperature differences. H Ventilation control: the grids must be sized according to power loss in the substation. These grids must only be placed near the transformer, so as to prevent air circulating on the MV switchboard. operation We strongly recommend that you carry out at regular intervals (at least roughly every 2 years) afew operating cycles on the switching devices. Outside normal operating conditions (between -- 5 C and 40 C, absence of dust, corrosive gas, etc.), we recommend that you contact our Groupe Schneider service centre in order to examine themeasurestobetakento ensure proper installation operation. Our service centre is at your disposal at all times: H To conduct an installation diagnosis. H To suggest the appropriate maintenance operations. H To offer you maintenance contracts. H To suggest adaptations EN revision : 01 11

13 EN revision : 01

14 installation instructions preparing the cubicles for switchboard assembly Upon delivery : Switch closed. Front panel bolted. :bolt+washer : bolt+washer+nylstop nut : nut used to secure the front panel. B Unscrew the nut used to secure the front panel. Remove the front panel A and then the skids B. (the bolts cannot be re---used) A E D C Remove the low voltage compartment front plate C, the lifting rings D and the cross---members E. G H Remove top plate G (4 bolts). Remove top plate H. (cubicle without additional LV enclosure) assembling the switchboard nuts and bolts in bag S1: (HM6 x 16 bolts only) : screw+washer+ nut K L Fix the cubicles together. Bolt mounting direction K : lett--- hand cubicle L : right--- hand cubicle EN revision : 01 13

15 securing to the floor ( nuts and bolts not included ) ,3x12,3 layout in the substation 100mm* 100mm* IMB IMB 20mm 20mm Switchboardinstalledtotheright of a wall. (*) minimum clearance for trouble--- free operation. Switchboard installed to the left of a wall. fitting the busbars after installing the cubicles in their operating location tools: 1 torquewrench(1to50nm.) 1 1/4---3/8 adapter 1 6 mm extension fitting 1 6 mm male hexagonal (Allan) fitting or 1 female hexagonal socket. Note: the example is for an IBM with a bottom right outgoing line. IMB Top busbar connection. Tightening torque : 28 Nm. IMB GBM Bottom busbar connection. Tightening torque : 28 Nm EN revision : 01

16 Version ±12 kv bag S6: mounted without field distributors Version > 12 kv bag S2: Field distributor positioned correctly. Field distributor positioned incorrectly (risk of damage). G H Refit top plate H (nuts inside the cubicle). Refit top plate G EN revision : 01 15

17 cable entry for connection of low voltage auxiliaries Note: the LV auxiliary wiring diagramsaregluedtotheinsideof the LV compartment. A Cable entry to the terminal block via holes A. Remove the knock---outs. Cubicle equipped with an LV cable trough (option). Proceed in the same manner after removing the trough top plate. Refit the LV compartment front plate, respecting the indications. fitting the earth bars Connect the earth bars together (HM8 x 35 mm bolts). Connection to substation earth in either of these two ways EN revision : 01

18 start-- up instructions checks before energizing H Check that nothing has been left inadvertently in the connection compartment. Refit the front panel. Refit the nylstop screw on the front panel. operating test before energizing see operating instructions section Operate the switch several times. energizing the bottom busbars As soon as the busbars have been energized, The voltage indicator lamps should go on EN revision : 01 17

19 EN revision : 01

20 operating instructions manual operation and position indication Position the lever as indicated for downward (opening) operations. Position the lever as indicated for upward (closing) operations. J CIT operating mechanism front plate. CI2 operating mechanism front plate J : charge d/uncharged indication Closing the switch (CIT operating mechanism). Charging the spring (CI2 operating mechanism) EN revision : 01 19

21 Closing the switch (CI2 operating mechanism). Opening the switch (CIT operating mechanism). Opening the switch (CI2 operating mechanism). discharging a CI2 operating mechanism A B B Cubicle de--energised : close the switch: button A then open: button B. Cubicle energised : press the open button B. CAUTION ATTENTION : this operation can damage the operating mechanism. Perform only when strictly necessary EN revision : 01

22 padlocking Padlocking of motor mechanism (option). Lock out the motor mechanism using a padlock before opening the switch. The motor mechanism can be locked in or out using the padlocks. Padlock the switch in open or closed position using 1, 2 or 3 padlocks (Ø 8 mm). Padlocking the front panel. keyed interlocks See the keyed interlock installation and operating instructions. operating safety To remove the front panel, always open the switch before removing the nut used to secure the panel. -- the switch must also be open with the front panel is refitted. -- make sure to replace the nut used to secure the front panel. If a CI2 motor mechanism is installed, lock out the motor mechanism before opening the switch EN revision : 01 21

23 EN revision : 01

24 maintenance instructions preventive maintenance, cleaning instructions and power --- up If necessary: contact the Schneider Electric group service centre. We strongly recommend that you carry out at regular intervals (at least roughly every 2 years) afew operating cycles on the switching devices. CAUTION Never lubricate the disconnector operating mechanism. If necessary: contact the Schneider Electric group service centre. In normal operating conditions (temperature between C and40 C) no special maintenance is required. CAUTION Never use solvents and alcohol. We recommend that you inspect each compartment (cable, fuse, busbar)* at regular intervals according to environmental conditions. If the insulating parts are dusty, that you remove the dust using a dry cloth. example : In harsher conditions (aggressive atmosphere, dust, temperature less than C or greater than 40 C) consult the nearest Schneider Electric service centre EN revision : 01 23

25 replacing a voltage indicator block Pull out the voltage indicator block (the switchboard can remain energized). trouble---shooting chart IMB cubicle H voltage indicator not illuminated H check the voltage indicator block H check that the bottom busbars are live H front panel cannot be opened or closed H check that the nut used tosecure the front panel has been removed and that the switch is open H switch cannot be operated H check that the switch is open EN revision : 01

26 motor mechanism (option) H electrical operation impossible H check the LV fuses (CIP2) H H (*) manual operation impossible following an electrical closing cycle for a voltage level less than ---15% rated value (*) insertion of lever impossible following an electrical closing cycle for a voltage level less than ---15% rated value (*)Operations is guaranteed for rated voltage ± 15% H H H H H check electrical interlocks S13 (lever insertion) and S28 (presence of front panel) check the configuration of the CIP1 subassembly (see diagram) use the operating lever to apply a torque in the closing direction until the end position is reached; manual operation should now be possible. if possible, carry out an electrical operation, using a backup power source if necessary to allow insertion of the operating lever push the back of the switch shaft in the closing direction using a large screwdriver (for safety reasons, remember to first lock out the electrical operating mechanism if necessary, push up and hold the locking blade that actuates contact S13) spare parts H voltage indicator (for other parts, please consult us: see Groupe Schneider Electric services). options (please consult us) H keyed interlocks H release coils H auxiliary contacts H motor mechanism H 50 W heating element H enlarged LV compartment and/or additional LV enclosure EN revision : 01 25

27 recovery of SF6 gas at end of life for disconnector cubicle The SF6 must be removed before any dismantling operation can be carried out in compliance with the procedures described in IEC and according to the following instructions. The gas must be treated in compliance with IEC H volume of gas to be recovered: 35 litres H internal gauge pressure: 40 kp A NB : SF6 gas recycling at the end of circuit-- breaker life, refer to its instruction for use. Remove the cover (A) from the control cabinet. control cover access B Remove the control cover (B). Remove the 3 screws retaining the operating mechanism. Cut the wiring to remove the operating mechanism. Drill 2 holes in the filler valve safety cap 4 mm, centreline 20 mm, max. depth 4 mm EN revision : 01

28 CAUTION pump the gas for at least 15 minutes. C Using a spanner wrench, remove the safety cap from the valve. Connect the special pumping equipment (C) EN revision : 01 27

29 EN revision : 01

30 group Schneider Electric service centers are there for: engineering and technical assistance start-up training preventive and corrective maintenance adaptation work spare parts Call your sales representative who will put you in touch with your nearest group Schneider Electric service centers. Schneider Electric Industries SAS 89, boulevard Franklin Roosevelt F Rueil--- Malmaison (France) Tel:+33(0) electric.com EN revision : 01 As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication. Conception, rédaction: Service Documentation Technique T&D Edition du : 24/04/2008

SM6. instructions for use. QMB cubicles. MV distribution factory built assemblies at your service. Anglais

SM6. instructions for use. QMB cubicles. MV distribution factory built assemblies at your service. Anglais SM6 Anglais MV distribution factory built assemblies at your service instructions for use QMB cubicles foreword... 3 symbols and conventions... 3 as per iso 3864---2... contact the Schneider Electric service

More information

SM6. instructions for use. SM cubicle. MV distribution factory built assemblies at your service. Anglais

SM6. instructions for use. SM cubicle. MV distribution factory built assemblies at your service. Anglais SM6 Anglais MV distribution factory built assemblies at your service instructions for use SM cubicle foreword... 3 symbols and conventions... 3 as per iso 3864---2... contact the Schneider Electric service

More information

SM6. instructions for use. DMVL cubicle. MV distribution factory built assemblies at your service. Anglais

SM6. instructions for use. DMVL cubicle. MV distribution factory built assemblies at your service. Anglais SM6 Anglais MV distribution factory built assemblies at your service instructions for use DMVL cubicle foreword... 3 symbols and conventions... 3 as per iso 3864---2... contact the Schneider Electric service

More information

SM6. instructions for use. GAM cubicle (1250A) MV distribution factory built assemblies at your service. Anglais

SM6. instructions for use. GAM cubicle (1250A) MV distribution factory built assemblies at your service. Anglais SM6 Anglais MV distribution factory built assemblies at your service instructions for use GAM cubicle (1250A) foreword... 3 symbols and conventions... 3 as per iso 3864---2... contact the Schneider Electric

More information

Information for the modified document

Information for the modified document Information for the modified document émetteur : Esref OZYUZUCULER date :03-05 - 2001 Recipient SM6 --- 36kV STT KG K ToK FaZ OrY MRK(TR) E&S S OyR MeM er Number : 7897176EN Index : D0 Product : SM6-36

More information

SM6. instructions for use. IMCandQMCcubicles. MV distribution factory built assemblies at your service. Anglais

SM6. instructions for use. IMCandQMCcubicles. MV distribution factory built assemblies at your service. Anglais SM6 Anglais MV distribution factory built assemblies at your service instructions for use IMCandQMCcubicles foreword... 3 symbols and conventions... 3 as per iso 3864---2... contact the Schneider Electric

More information

SM6. instructions for use. DM1 S cubicle. MV distribution factory built assemblies at your service. Anglais

SM6. instructions for use. DM1 S cubicle. MV distribution factory built assemblies at your service. Anglais SM6 Anglais MV distribution factory built assemblies at your service instructions for use DM1 S cubicle foreword... 3 symbols and conventions... 3 as per iso 3864---2... contact the Schneider Electric

More information

SM6. instructions for use. DMV S cubicle. MV distribution factory built assemblies at your service. Anglais

SM6. instructions for use. DMV S cubicle. MV distribution factory built assemblies at your service. Anglais SM6 Anglais MV distribution factory built assemblies at your service instructions for use DMV S cubicle foreword... 3 symbols and conventions... 3 as per iso 3864---2... contact the Schneider Electric

More information

SM6. instructions for use. DMV A---DMV D cubicle (1250A range) MV distribution factory built assemblies at your service. Anglais

SM6. instructions for use. DMV A---DMV D cubicle (1250A range) MV distribution factory built assemblies at your service. Anglais SM6 Anglais MV distribution factory built assemblies at your service instructions for use DMV A---DMV D cubicle (1250A range) foreword... 3 symbols and conventions... 3 as per iso 3864---2... contact the

More information

circuit breaker instructions for use SF draw --- out circuit---breakers in F400 MV distribution circuit breaker Anglais at your service

circuit breaker instructions for use SF draw --- out circuit---breakers in F400 MV distribution circuit breaker Anglais at your service circuit breaker Anglais MV distribution circuit breaker at your service instructions for use SF draw --- out circuit---breakers in F400 foreword... 3 symbols and conventions... 3 as per iso 3864---2...

More information

Medium Voltage Distribution FBX. Assembling a 1250A busbar Instructions.

Medium Voltage Distribution FBX. Assembling a 1250A busbar Instructions. Medium Voltage Distribution FBX Assembling a 1250A busbar Instructions www.schneider-electric.com Contents Introduction... 3 Our Service Unit: our specialists, and suitably adapted services...... 3 Overview...

More information

MCset kv Medium voltage equipment

MCset kv Medium voltage equipment Maintenance Guide PE90014 PE90006 MCset 1-2 - 3 17.5 kv Medium voltage equipment Air-insulated switchboards Metal-enclosed switchgear with moving parts PE90007 PE90008 PE90009 PE90007 Maintenance Guide

More information

circuit-- breaker instructions for use SF1 fixed or in SM6 circuit --- breaker MV distribution circuit breaker at your service Anglais

circuit-- breaker instructions for use SF1 fixed or in SM6 circuit --- breaker MV distribution circuit breaker at your service Anglais circuit-- breaker Anglais MV distribution circuit breaker at your service instructions for use SF1 fixed or in SM6 circuit --- breaker foreword... 3 symbols and conventions... 3 as per iso 3864---2...

More information

MCset 4-24 kv Withdrawable SF6 circuit breaker

MCset 4-24 kv Withdrawable SF6 circuit breaker Medium Voltage switchgear MCset 4-24 kv Withdrawable SF6 circuit breaker Instruction for use Contents General 2 Glossary 2 Symbols 2 Recommendations 3 General description 4 AD4 unit 4 AD4 unit with toroidal

More information

Medium voltage NEX switchgear Withdrawable circuit breaker. Quite simply efficient

Medium voltage NEX switchgear Withdrawable circuit breaker. Quite simply efficient Medium voltage NEX switchgear Withdrawable circuit breaker Quite simply efficient NEX, a simple and flexible solution NEX is the result of worldwide acquired experience and provides you with a high level

More information

circuit breakers instructions for use SF2 fixed MV distribution circuit breaker at your service Anglais

circuit breakers instructions for use SF2 fixed MV distribution circuit breaker at your service Anglais circuit breakers nglais MV distribution circuit breaker at your service instructions for use SF2 fixed foreword... 3 symbols and conventions... 3 as per iso 3864---2... contact the Schneider lectric service

More information

MCset 17.5 kv. Civil engineering guide April Medium Voltage Distribution

MCset 17.5 kv. Civil engineering guide April Medium Voltage Distribution Medium Voltage Distribution MCset 17.5 kv ir insulated switchboard Withdrawable switchgear SF6 or vaccum technology Civil engineering guide pril 2012 Contents General 2 Glossary 2 Dimensions and weights

More information

CGMCOSMOS. Reliable innovation. Personal solutions. Fully gas insulated modular and compact (RMU)system.

CGMCOSMOS. Reliable innovation. Personal solutions. Fully gas insulated modular and compact (RMU)system. MV Switchgear for CGMCOSMOS Fully gas insulated modular and compact (RMU)system Up to 24 kv Up to 27 kv mediumvoltage mediumvoltageag AG Langackerstrasse Langackerstrasse 25 25 CH CH 6330 6330 Cham Cham

More information

AIR INSULATED METAL ENCLOSED SWITCHGEAR AND CONTROLGEAR

AIR INSULATED METAL ENCLOSED SWITCHGEAR AND CONTROLGEAR AIR INSULATED METAL ENCLOSED SWITCHGEAR AND CONTROLGEAR ANGLER SWITCHING DEVICES CONTENTS 1. General 2. Switchgear Types - Switch Disconnector - Disconnector 3. Cubicle Types - Cubicle with Switch Disconnector

More information

NEX - 24 kv Withdrawable Circuit Breaker

NEX - 24 kv Withdrawable Circuit Breaker Air Insulated Medium Voltage Equipment NEX - 24 kv Withdrawable Circuit Breaker Installation drawings file Contents bj Fitting the upper main busbars 1250 A busbar - 800 mm cubicle Assembly 1250 A busbar

More information

0MV vacuum circuit breaker. 0Evolis 24 kv. 0User 0Manual. Creation Printed on 2008/07/17

0MV vacuum circuit breaker. 0Evolis 24 kv. 0User 0Manual. Creation Printed on 2008/07/17 0MV vacuum circuit breaker 0Evolis 24 kv 0User 0Manual 02008 07897530EN-C0.book Page 1 Jeudi, 15. mai 2008 11:34 11 Contents Evolis description 2 Front view circuit breaker 2 Front view lateral circuit

More information

Secondary Distribution Switchgear FBX. SF6 Gas-insulated switchboards CB function. Instructions Installation - Commissioning Operating - Maintenance

Secondary Distribution Switchgear FBX. SF6 Gas-insulated switchboards CB function. Instructions Installation - Commissioning Operating - Maintenance Secondary Distribution Switchgear FBX SF6 Gas-insulated switchboards CB function Instructions Installation - Commissioning Operating - Maintenance Contents 1 Schneider Electric at your service... 1 1.1

More information

GHA. Gas-Insulated Switchgear. Gas-Insulated Switchgear. Switchgear extension and replacement of a panel

GHA. Gas-Insulated Switchgear. Gas-Insulated Switchgear. Switchgear extension and replacement of a panel Gas-Insulated Switchgear GHA Gas-Insulated Switchgear Switchgear extension and replacement of a panel During this work, essential parts of the switchgear remain in operation No. AGS 535 066-01 Edition

More information

Secondary Distribution Switchgear FBX. SF6 Gas-insulated switchboards. Instructions Operation - Maintenance

Secondary Distribution Switchgear FBX. SF6 Gas-insulated switchboards. Instructions Operation - Maintenance Secondary Distribution Switchgear FBX SF6 Gas-insulated switchboards Instructions Operation - Maintenance Contents 1 Schneider Electric at your service................... 1 1.1 Our Service Unit: our specialists,

More information

CBGS-0. Medium voltage distribution

CBGS-0. Medium voltage distribution Medium voltage distribution CBGS-0 Gas Insulated metal-enclosed Switchgear SF6 circuit breaker technology Up to 24/36 kv - 1250/1600/2000 A - 25/31.5 ka Transmission Wind Airports Oil & Gas Mining & Distribution

More information

CPG.1 Gas insulated, single busbar cubicle range Up to 27 kv / 2000 A / 31.5 ka Up to 38 kv / 2000 A / 31.5 ka IEEE Standards

CPG.1 Gas insulated, single busbar cubicle range Up to 27 kv / 2000 A / 31.5 ka Up to 38 kv / 2000 A / 31.5 ka IEEE Standards Medium Voltage Switchgear Primary Distribution CPG.1 Gas insulated, single busbar cubicle range Up to 27 kv / 2000 A / 31.5 ka General description Presentation Ormazabal s CPG System includes the CPG.1

More information

SFset with VIP 400/410 built-in control unit Medium Voltage Circuit Breaker

SFset with VIP 400/410 built-in control unit Medium Voltage Circuit Breaker SFset with VIP 400/410 built-in control unit Medium Voltage Circuit Breaker Instructions for use 07897543EN01 Rev.04 11/2017 SFset- Instructions for use Table of contents Presentation Presentation...

More information

PIX. Operation - Replacement of Fuses Replacement of Voltage Transformers Technical manual. Medium Voltage Distribution

PIX. Operation - Replacement of Fuses Replacement of Voltage Transformers Technical manual. Medium Voltage Distribution Medium Voltage Distribution PIX Withdrawable Voltage Transformer Operation - Replacement of Fuses Replacement of Voltage Transformers Technical manual Nr. Edition 11/2011 www.schneider-electric.com Schneider

More information

The Key Link for all your Distributions Needs. A Comprehensive Range for All Your Needs

The Key Link for all your Distributions Needs. A Comprehensive Range for All Your Needs [ MV Air-insulated Switchgear Range ] 1 PIX CUSTOMER BENEFITS Compact, versatile and highly reliable designs Choice of vacuum or SF6 switching technology Wide range of applications Enhanced operator safety

More information

SFset with VIP 400/410 built-in control unit Medium Voltage Circuit Breaker

SFset with VIP 400/410 built-in control unit Medium Voltage Circuit Breaker SFset with VIP 400/410 built-in control unit Medium Voltage Circuit Breaker Instructions for use 11/2017 18 0 2 ing A r p s e l b a l i va SFset- Instructions for use Table of contents Presentation Presentation...

More information

PIX-H Metal-clad switchgear up to 17.5kV

PIX-H Metal-clad switchgear up to 17.5kV AIR INSULATED SWITCHGEAR PIX-H Metal-clad switchgear up to 17.5kV for high rated applications Technical Specifications AREVA T&D Summary - Technical description... 3 - Standards... 6 - PIX in detail...

More information

SF6 Load Break Switch 2017 FIL3 - S. Indoor Medium Voltage LBS With or without fuse 12kV- 24kV FIL3 D FIL3. 24KV SF6 Load Break Switch

SF6 Load Break Switch 2017 FIL3 - S. Indoor Medium Voltage LBS With or without fuse 12kV- 24kV FIL3 D FIL3. 24KV SF6 Load Break Switch FIL3 - S FIL3 D Indoor Medium Voltage LBS With or without fuse 12kV- 24kV FIL3 24KV SF6 Load Break Switch Content 1. About Us 2. Load Break Switch Introduction 3. FIL3 product overview 3.1. Advantages

More information

Medium Voltage Distribution PIX. Air Insulated Switchgear up to 24 kv PARS TABLEAU

Medium Voltage Distribution PIX. Air Insulated Switchgear up to 24 kv PARS TABLEAU Medium Voltage Distribution PIX Air Insulated Switchgear up to kv PIX Air Insulated Switchgear up to kv The PIX system has been designed in accordance with international (IEC) standards, and gives an optimal

More information

SYSclad switchboard equipped with draw out type vacuum circuit breaker closed dooroperationoperation. SYSclad 12 17,5kV A.

SYSclad switchboard equipped with draw out type vacuum circuit breaker closed dooroperationoperation. SYSclad 12 17,5kV A. SYSclad switchboard equipped with draw out type vacuum circuit breaker closed dooroperationoperation 630 3150A SYSclad 12 17,5kV 16 31,5kA Generalities SYSclad is a medium voltage switchboard metal clad

More information

Evolis offer Merlin Gerin

Evolis offer Merlin Gerin Medium voltage distribution Evolis offer Merlin Gerin Installation guide 200757a General contents Evolis circuit breaker full version 3 Circuit breaker installation 3 Cradle installation and earthing 3

More information

Medium voltage products UniSec DY800 New 24 kv air-insulated medium voltage switchgear to e-distribuzione specifications

Medium voltage products UniSec DY800 New 24 kv air-insulated medium voltage switchgear to e-distribuzione specifications Medium voltage products UniSec Y800 New 24 kv air-insulated medium voltage switchgear to e-istribuzione specifications UniSec Y800 ubicles available Unit e-istribuzione specifications (Ed. 4) UniSec IS/1

More information

Operating conditions. Generalities. Normal operating conditions

Operating conditions. Generalities. Normal operating conditions Generalities Operating conditions In addition to its technical characteristics, SM6 meets requirements concerning safety of life and property as well as ease of installation, operation and protecting the

More information

Cable arrangement 15 Preparation for cable installation. 15 Installation of the cables 16 Finishing of the cable installation. 17 Examples.

Cable arrangement 15 Preparation for cable installation. 15 Installation of the cables 16 Finishing of the cable installation. 17 Examples. Transportation and storage.. 3 General. 3 Unpacking at installation site....... 3 Transfer of cubicles at installation site... 3 Weight.. 4 Temporary storage. 4 Erection at site 5 General. 5 The switchgear

More information

I B D Q I B D Q O I B D Q O

I B D Q I B D Q O I B D Q O Extension offer: new possible combinations 2 and 3 functions RM6 free combination: offers all types of configurations which fit to every application. Free choice: type of each functional unit. Free choice:

More information

CGMCOSMOS Fully gas-insulated modular and compact (RMU) system Up to 24 kv

CGMCOSMOS Fully gas-insulated modular and compact (RMU) system Up to 24 kv Medium Voltage Switchgear Secondary Distribution CGMCOSMOS Fully gas-insulated modular and compact (RMU) system MV Switchgear Secondary Distribution Networks General description Introduction Ormazabal

More information

Medium Voltage Distribution PIX kv. Additional equipment Instructions.

Medium Voltage Distribution PIX kv. Additional equipment Instructions. Medium Voltage Distribution PIX 12-17.5-24 kv Additional equipment Instructions www.schneider-electric.com Contents 1 Schneider Electric at your service... 4 1.1 Your contacts... 4 2 State of delivery

More information

The vacuum circuit breaker for commercial buildings, industrial plants and utilities

The vacuum circuit breaker for commercial buildings, industrial plants and utilities The vacuum circuit breaker for commercial buildings, industrial plants and utilities EasyPact EXE The easy choice for more value 2 EasyPact EXE EasyPact EXE, a medium voltage vacuum circuit breaker optimizing

More information

Low-voltage switchgear MNS Light W. Installation, handling and operation. ABB LV Systems

Low-voltage switchgear MNS Light W. Installation, handling and operation. ABB LV Systems Low-voltage switchgear MNS Light W Installation, handling and operation ABB LV Systems MNS Light W switchgear is a flexible system that is primarily designed for motor control. The rated service voltage

More information

Galaxy VM. Battery Breaker Box Installation 09/

Galaxy VM. Battery Breaker Box Installation 09/ Galaxy VM Battery Breaker Box Installation 09/2016 www.schneider-electric.com Legal Information The Schneider Electric brand and any registered trademarks of Schneider Electric Industries SAS referred

More information

B kv T&D GAS INSULATED SWITCHGEAR

B kv T&D GAS INSULATED SWITCHGEAR GAS INSULATED SWITCHGEAR B 105 170 300 kv The increasing demand for electrical power in cities and industrial centers necessitates the installation of a compact and efficient distribution and transmission

More information

DT-6C MEDIUM VOLTAGE SWITCHGEAR COMPACT RING MAIN UNIT. User Manual: DT-6C / DT-6+ C

DT-6C MEDIUM VOLTAGE SWITCHGEAR COMPACT RING MAIN UNIT. User Manual: DT-6C / DT-6+ C DT-6C MEDIUM VOLTAGE SWITCHGEAR COMPACT RING MAIN UNIT User Manual: DT-6C / DT-6+ C SGC - SwitchGear Company nv. - Moorstraat 24 - B-9850 Nevele - Belgium +32 (0)9/321.91.12 - Fax +32 (0)9/321.91.13 -

More information

B kv Gas-insulated Substations

B kv Gas-insulated Substations 72.5 145 kv Gas-insulated Substations The increasing demand for electrical power in cities and industrial centres requires the installation of a compact and efficient distribution and transmission network.

More information

abb SafeLink SF 6 Insulated Ring Main Unit Installation and Operating Instructions Switchgear Division Auckland, New Zealand SLMIO ver 2.

abb SafeLink SF 6 Insulated Ring Main Unit Installation and Operating Instructions Switchgear Division Auckland, New Zealand SLMIO ver 2. Installation and Operating Instructions Switchgear Division Auckland, New Zealand SLMIO ver 2.12 Product Overview ABB's type-tested ring main unit (RMU) is an SF 6 insulated RMU utilising the latest developments

More information

OPERATING INSTRUCTION

OPERATING INSTRUCTION 11/05 Form #271 99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 OPERATING INSTRUCTION Visit us at www.testequipmentdepot.com MODEL 3132 ANALOG INSULATION-CONTINUITY TESTER

More information

HST -LS Interlocking device (Translation of Original Manual)

HST -LS Interlocking device (Translation of Original Manual) Installation and Operating Manual for Components HST -LS Interlocking device (Translation of Original Manual) HST-LS Ident.-No.: 10268 HST-LS Ident.-No.: 10269 HST-LS, pictured Ident-Nr. 10269 The image

More information

Medium Voltage Distribution Maintenance Guide I 2013 Premset. 15 kv compact modular vacuum switchgear with Shielded Solid Insulation System

Medium Voltage Distribution Maintenance Guide I 2013 Premset. 15 kv compact modular vacuum switchgear with Shielded Solid Insulation System Medium Voltage Distribution Maintenance Guide I 2013 Premset 15 kv compact modular vacuum switchgear with Shielded Solid Insulation System Schneider Electric Services, by your side all day long Installation

More information

CGMCOSMOS-2LV. MEDIUM-VOLTAGE SF 6 GAS-INSULATED RING MAIN UNIT UP TO 12 kv LIB

CGMCOSMOS-2LV. MEDIUM-VOLTAGE SF 6 GAS-INSULATED RING MAIN UNIT UP TO 12 kv LIB IG-179-GB GENERAL INSTRUCTIONS FOR IG-179-GB General Instructions MEDIUM-VOLTAGE SF 6 GAS-INSULATED RING MAIN UNIT UP TO 12 kv LIB Transformer Substations Primary Distribution Switchgear Secondary Distribution

More information

Galaxy Receiving and Unpacking 09/

Galaxy Receiving and Unpacking 09/ Galaxy 5500 20 120 kva 400 V Receiving and Unpacking 09/2015 www.schneider-electric.com Legal Information The Schneider Electric brand and any registered trademarks of Schneider Electric Industries SAS

More information

DR-6C MEDIUM VOLTAGE SWITCHGEAR COMPACT RING MAIN UNIT. User Manual: DR-6C / DR-6+ C THE SPECIALIST IN MEDIUM VOLTAGE SWITCHGEAR

DR-6C MEDIUM VOLTAGE SWITCHGEAR COMPACT RING MAIN UNIT. User Manual: DR-6C / DR-6+ C THE SPECIALIST IN MEDIUM VOLTAGE SWITCHGEAR DR-6C MEDIUM VOLTAGE SWITCHGEAR COMPACT RING MAIN UNIT User Manual: DR-6C / DR-6+ C THE SPECIALIST IN MEDIUM VOLTAGE SWITCHGEAR DW645314 SGC - SwitchGear Company nv. - Moorstraat 24 - B-9850 Nevele - Belgium

More information

CPG.0 Single busbar gas-insulated cubicles

CPG.0 Single busbar gas-insulated cubicles MV Switchgear Primary Distribution CPG.0 Single busbar gas-insulated cubicles Up to 36 kv CPG System The quality of products designed, manufactured and installed by Ormazabal is underpinned by the implementation

More information

OPERATING INSTRUCTION

OPERATING INSTRUCTION 99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com 8/05 Form #270 OPERATING INSTRUCTION MODEL 3005 DIGITAL INSULATION-CONTINUITY TESTER

More information

Vacuum Circuit-Breakers, Type HVX kv, of cassette design, cassette with motor drive

Vacuum Circuit-Breakers, Type HVX kv, of cassette design, cassette with motor drive Vacuum Circuit-Breakers, Type HVX 12 24 kv, of cassette design, cassette with motor drive Operating Instructions No. 531 321, Edition 09/00 Table of Contents 1 General 4 1.1 Operating Conditions 4 2 Design,

More information

Electrical network protection VIP30, VIP35. User s manual 12/2008

Electrical network protection VIP30, VIP35. User s manual 12/2008 Electrical network protection VIP30, VIP35 User s manual 1/008 Safety instructions ANSI symbol. IEC symbol. Safety symbols and messages Read these instructions carefully and look at the equipment to become

More information

INSTRUCTION MANUAL ANALOGUE INSULATION TESTER KEW 3131M KYORITSU ELECTRICAL INSTRUMENTS WORKS,LTD., TOKYO JAPAN

INSTRUCTION MANUAL ANALOGUE INSULATION TESTER KEW 3131M KYORITSU ELECTRICAL INSTRUMENTS WORKS,LTD., TOKYO JAPAN INSTRUCTION MANUAL ANALOGUE INSULATION TESTER KEW 3131M KYORITSU ELECTRICAL INSTRUMENTS WORKS,LTD., TOKYO JAPAN Contents 1. Safety Precautions... 1 2. Features... 3 3. Specifications... 4 4. Instrument

More information

UniSec Operation and maintenance manual

UniSec Operation and maintenance manual Medium voltage products UniSec Operation and maintenance manual Safety 3 For your safety! 3 Skilled personnel 3 Critical messages 3 Contact us! 3 1. Introduction 4 1.1 General aspects 4 1.2 Operation and

More information

ACROBAT SWING STAND MODEL

ACROBAT SWING STAND MODEL Mounting instructions Directions for use ACROBAT SWING STAND MODEL Dr. Mach GmbH u. Co.KG, Flossmannstrasse 28, D-85560 Ebersberg Tel.: +49 (0)8092 2093 0, Fax +49 (0)8092 2093 50 Internet: www.dr-mach.com,

More information

Energy Australia Chamber Substation indoor switchgear. installation,operation and maintenance instructions version 1.

Energy Australia Chamber Substation indoor switchgear. installation,operation and maintenance instructions version 1. Energy Australia Chamber Substation indoor switchgear installation,operation and maintenance instructions version 1.6 / February 2009 1 Details of revision Version Comment Date 1.0 First Draft Issue May

More information

VD4 Installation and service instructions kv A ka

VD4 Installation and service instructions kv A ka Medium voltage products VD4 Installation and service instructions 12... 36 kv - 630... 3150 A - 16... 50 ka Index For your safety! 1 I. Introduction 2 II. Programme for environmental protection 2 1. Packing

More information

SD, SE, SDE, SCO series Multipole switchgear for rail vehicles: Disconnecting switches, Earthing Switches, Disconnector with Earthing Switches,

SD, SE, SDE, SCO series Multipole switchgear for rail vehicles: Disconnecting switches, Earthing Switches, Disconnector with Earthing Switches, 4 Electrics for Rolling Stock Multipole switchgear for rail vehicles: Disconnecting switches, Earthing Switches, Disconnector with Earthing Switches, Change-Over-Switches 600 V to 3 kv Catalogue F84.en

More information

For your safety! Foreword

For your safety! Foreword Medium voltage products UniSec DY800 in accordance with Enel specifications Installation, service and maintenance instructions for 24 kv prefabricated assemblies with arc-proof metal enclosures and multi-function

More information

Galaxy 300 Battery Breaker Kit G3HTBKIT1

Galaxy 300 Battery Breaker Kit G3HTBKIT1 Installation 990 5739 001 03/2016 990 5739 001 Galaxy 300 Battery Breaker Kit G3HTBKIT1 What s in This Document Important Safety Instructions SAVE THESE INSTRUCTIONS...1 Safety Precautions...2 Specifications...4

More information

Cloud-connected solution for utility-scale renewable power

Cloud-connected solution for utility-scale renewable power Cloud-connected solution for utility-scale renewable power Conext SmartGen TM Power System Global power conversion system for the next generation of PV and Energy Storage power plants connected to smart

More information

MNS Light F. Low-voltage switchgear with fixed units. ABB LV Systems

MNS Light F. Low-voltage switchgear with fixed units. ABB LV Systems MNS Light F Low-voltage switchgear with fixed units ABB LV Systems Cubicle design MNS Light F switchgear is a flexible system with a large selection of cubicle variants that can be built together in optional

More information

1 This instrument must only be used by a competent and trained person and operated in strict accordance with the instructions.

1 This instrument must only be used by a competent and trained person and operated in strict accordance with the instructions. 1 This instrument must only be used by a competent and trained person and operated in strict accordance with the instructions. KYORITSU will not accept liability for any damage or injury caused by misuse

More information

Metal Clad Switchgears

Metal Clad Switchgears SNC Series Metal Clad Switchgears > up to 36 kv Rated Voltage > up to 2500 A Rated Current > up to 40 ka Rated Short Time Withstand Current > LSC-2B, PM, AFLR > In Confirmity with IEC 62271-1, 100, 102,

More information

24 k B788 ELEKTROTECHNISCHE WERKE FRITZ DRIESCHER & SÖHNE GMBH

24 k B788 ELEKTROTECHNISCHE WERKE FRITZ DRIESCHER & SÖHNE GMBH 788 Instructions for Installation, Operation and Maintenance for DRIESCHER - Air - Insulated Medium - Voltage Compact Switchgears for Substations Rated voltage 12 kv and 24 kv Rated current 630 A 24 k

More information

Type Operating Instructions. Bedienungsanleitung Manuel utilisateur

Type Operating Instructions. Bedienungsanleitung Manuel utilisateur Water flow rate transmitter Wasser-Durchfluss-Transmitter Transmetteur de débit d eau Operating Instructions Bedienungsanleitung Manuel utilisateur We reserve the right to make technical changes without

More information

ormaset-m PREFABRICATED METALLIC TRANSFORMER SUBSTATION

ormaset-m PREFABRICATED METALLIC TRANSFORMER SUBSTATION IG-199-GB GENERAL INSTRUCTIONS FOR IG-199-GB General Instructions ormaset-m Transformer Substations Primary Distribution Switchgear Secondary Distribution Switchgear Protection and Automation Low Voltage

More information

DISTRIBUTION SOLUTIONS. GSec Gas-insulated switching and isolating apparatus

DISTRIBUTION SOLUTIONS. GSec Gas-insulated switching and isolating apparatus DISTRIBUTION SOLUTIONS GSec Gas-insulated switching and isolating apparatus GSec is a three-position SF6 gas-insulated switchdisconnector designed for use in medium voltage switchgear for secondary distribution

More information

Schneider Electric PV Skid. Optimized solar power conversion system tailored to enhance any North American PV power plant

Schneider Electric PV Skid. Optimized solar power conversion system tailored to enhance any North American PV power plant Schneider Electric PV Skid Optimized solar power conversion system tailored to enhance any North American PV power plant 1 PV Skid solution Integrated solution designed for optimal performance in any environment

More information

ormaset-m Prefabricated metallic transformer substation

ormaset-m Prefabricated metallic transformer substation Prefabricated metallic transformer substation General Instructions IG-199-EN, version 03; 6/11/2013 Legal Deposit: BI-1401/2013 CAUTION! When medium-voltage equipment is operating, certain components are

More information

Operating instructions Actuator and Emergency exit AZ/AZM 200-B30 AZ/AZM 201-B About this document. Content

Operating instructions Actuator and Emergency exit AZ/AZM 200-B30 AZ/AZM 201-B About this document. Content 1. About this document Operating instructions............pages 1 to 10 Original 1.1 Function This operating instructions manual provides all the information you need for the mounting, set-up and commissioning

More information

CGM.3 System. Medium Voltage SF 6 gas-insulated cubicles up to 38 kv according to IEEE and CSA standards

CGM.3 System. Medium Voltage SF 6 gas-insulated cubicles up to 38 kv according to IEEE and CSA standards CGM.3 System Medium Voltage SF 6 gas-insulated cubicles up to 38 kv according to IEEE and CSA standards General Instructions IG-183-EN, version 03; 06/03/2013 Legal Deposit: BI-0272/2013 CAUTION! When

More information

Air-insulated switchgear UniGear type ZS1

Air-insulated switchgear UniGear type ZS1 Air-insulated switchgear UniGear type ZS1 ABB Power Technologies / 1-7074 D 12-03-2003 - Air-insulated switchgear UniGear type ZS1 ABB Power Technologies / 2-7075 D 1 2-03-2003 - Rated voltage kv 12 17.5

More information

e 2 ALPHA Medium Voltage Switchgear K Catalogue EN

e 2 ALPHA Medium Voltage Switchgear K Catalogue EN e 2 ALPHA Medium Voltage Switchgear K-1.2.3 Catalogue EN WE CREATE IDEAS WITH POWER! ELEKTROMETAL ENERGETYKA SA provides solutions for electrical power engineering. Our services are carried out by a team

More information

Steve Summers Region Sales Manager

Steve Summers Region Sales Manager Steve Summers Region Sales Manager Institute For Animal Healthcare LV Switchgear Package Package Subs LV Switchboards PDU s LV sub Distribution MCC s MV Switchgear Established in 1972 manufacturing control

More information

XL Distribution enclosures WORKSHOP SPECIFICATIONS

XL Distribution enclosures WORKSHOP SPECIFICATIONS 800 Distribution enclosures WORKSHOP SPECIFICATIONS With its extensive ranges, the Legrand offer meets your quality standards and provides real freedom and simplicity of installation together with acknowledged

More information

MESG 12 / 17.5 / 24 / 36 KV

MESG 12 / 17.5 / 24 / 36 KV MESG 12 / 17.5 / 24 / 36 KV Medium Voltage Air Insulated Metal Enclosed Switchgear up to 36 kv- up to 1250 A - up to 25 ka for 1 sec. with SF6 or vacuum circuit breakers. 750 METAL ENCLOSED 1 1 ) GENERAL

More information

Medium voltage compact switchgears. rated voltage 12 and 25 kv rated current 400 and 630 A

Medium voltage compact switchgears. rated voltage 12 and 25 kv rated current 400 and 630 A Medium voltage compact switchgears rated voltage 12 and 25 kv rated current 400 and 630 A 1 General The new air-insulated DRIESCHER medium voltage compact switchgears are ideal for application in secondary

More information

Operating instructions. sonnenprotect for operators. KD-337 Part no Version X00.

Operating instructions. sonnenprotect for operators. KD-337 Part no Version X00. Operating instructions for operators sonnenprotect 1300 KD-337 Part no. 22010 Version X00 info@sonnenbatterie.de www.sonnenbatterie.de EN IMPORTANT Read this documentation carefully before operation. Retain

More information

UniPack compact secondary substations (CSS) upto 36 kv For safe, reliable and space saving power distribution solutions

UniPack compact secondary substations (CSS) upto 36 kv For safe, reliable and space saving power distribution solutions UniPack compact secondary substations (CSS) upto 36 kv For safe, reliable and space saving power distribution solutions ABB a global leader ABB is a global leader in power and automation technologies that

More information

GE Industrial Solutions. User/Installation Manual for 4.76kV -15kV SecoBloc

GE Industrial Solutions. User/Installation Manual for 4.76kV -15kV SecoBloc GE Industrial Solutions User/Installation Manual for 4.76kV -15kV SecoBloc Index General Scope...3 Standards...3 Operating conditions...3 Technical specification...3 Basic structure Features...4 Operation...4

More information

Cloud-connected solution for utility-scale renewable power

Cloud-connected solution for utility-scale renewable power Cloud-connected solution for utility-scale renewable power Conext SmartGen TM Power System Global power conversion system for the next generation of PV and Energy Storage power plants connected to smart

More information

e 2 ALPHA -2S Medium Voltage Double Busbar Switchgear K Catalogue EN

e 2 ALPHA -2S Medium Voltage Double Busbar Switchgear K Catalogue EN e 2 ALPHA -2S Medium Voltage Double Busbar Switchgear K-11.1.2 Catalogue EN We Create Ideas With Power! e 2 ALPHA-2S double busbar switchgear is designed for use in primary and secondary electric energy

More information

PIX High. Medium-voltage switchgear. Air-insulated switchgear kv ( 50 ka) Assembly - Operation - Maintenance Technical Manual

PIX High. Medium-voltage switchgear. Air-insulated switchgear kv ( 50 ka) Assembly - Operation - Maintenance Technical Manual Medium-voltage switchgear PIX High Air-insulated switchgear 7.5 kv ( 50 ka) Assembly - Operation - Maintenance Technical Manual No. AGS 53 50-0 Edition /04 www.schneider-electric.com Manufacturer: Schneider

More information

Modular medium-voltage switchgear. NorMax

Modular medium-voltage switchgear. NorMax Modular medium-voltage switchgear NorMax NorMax MODULAR MEDIUM-VOLTAGE SWITCHGEAR 2 NorMax Modular medium-voltage switchgear Contents Subject Page Table of contents 2 Introduction and main features 2 Technical

More information

AIR INSULATED EXTENDABLE SWITCHGEAR UP TO 12KV GUIDE

AIR INSULATED EXTENDABLE SWITCHGEAR UP TO 12KV GUIDE AIR INSULATED EXTENDABLE SWITCHGEAR UP TO 12KV GUIDE Certificate Number FM35831 APPLICATION Typical Uses and Classification The MSGair switchgear is used in transformer and switching substations mainly

More information

SMC BATTERY CHARGER USER S MANUAL SMC USER S MANUAL

SMC BATTERY CHARGER USER S MANUAL SMC USER S MANUAL SMC BATTERY CHARGER SMC 1 INDEX 1 INDEX... 1 2 INTRODUCTION... 2 2.1 INTRODUCTION AND REFERENCES... 2 2.2 GLOSSARY... 2 2.3 DATA LABEL... 2 2.4 HOW TO USE THE USER'S MANUAL... 2 2.5 RESPONSIBILITY DISCLAIMER...

More information

Galaxy VX Battery Breaker Trip Board (GVXBBTB) and Battery Breaker Capacitor Board (GVXBBCB)

Galaxy VX Battery Breaker Trip Board (GVXBBTB) and Battery Breaker Capacitor Board (GVXBBCB) Installation 990 91076 001 12/2017 Galaxy VX Battery Breaker Trip Board (GVXBBTB) and The battery breaker trip board is the interface from the battery bank to the UPS battery auxiliary inputs/outputs and

More information

NEXT STEP B) SAFETY :

NEXT STEP B) SAFETY : SUMMARY : EVOLUTION OF MV/LV SUBSTATIONS COMPACT SUBSTATIONS J. M. Solans, C. Prevé, R. Farrán, R. Muñoz. SCHNEIDER ELECTRIC S.A. - SPAIN INTRODUCTION The recent liberalisation of the electricity supply

More information

STAND FOOT - STAND TUBE

STAND FOOT - STAND TUBE Mounting instructions Directions for use STAND FOOT - STAND TUBE Stand lamps: Mach 130 / Mach 130F Soloflex Triaflex / Triaflex R96 Trigenflex / Trigenflex R96 GmbH u. Co., Flossmannstrasse 28, D-85560

More information

HVX Series. 36 kv Medium Voltage Vacuum circuit breaker. Make the most of your energy SM. Medium Voltage Distribution Catalogue 2015

HVX Series. 36 kv Medium Voltage Vacuum circuit breaker. Make the most of your energy SM. Medium Voltage Distribution Catalogue 2015 Medium Voltage Distribution Catalogue 205 HVX Series 36 kv Medium Voltage Vacuum circuit breaker Fixed, middle rolling and floor rolling ranges of circuit breaker and disconnector Make the most of your

More information

Unified requirements for systems with voltages above 1 kv up to 15 kv

Unified requirements for systems with voltages above 1 kv up to 15 kv (1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) (Corr.1 June 2018) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements

More information

Galaxy VM. Modular Battery Cabinets Installation GVMMODBCW, GVMMODBCN 09/

Galaxy VM. Modular Battery Cabinets Installation GVMMODBCW, GVMMODBCN 09/ Galaxy VM Installation GVMMODBCW, GVMMODBCN 09/2018 www.schneider-electric.com Legal Information The Schneider Electric brand and any registered trademarks of Schneider Electric Industries SAS referred

More information

Simple and smart power factor correction

Simple and smart power factor correction Simple and smart power factor correction VarSet Low voltage capacitor banks VarSet I 2 Do you need an easy solution to immediately boost your facility s energy efficiency and productivity? Are products

More information