1 DC Circuit Breaker TECHNICAL DESCRIPTION TRK Ed.1 of 23/07/13 CONTENTS 1. INTRODUCTION DESCRIPTION Description of circuit breaker Operating mode Variants and Accessories INTEGRATION CHARACTERISTICS Standards General features Power circuit Breaking capacity Control Circuit Auxiliary contacts Wiring diagram DIMENSIONS /9

2 1. INTRODUCTION The ARC 850 and ARC 1550 circuit breakers are direct current unipolar devices with a bi-directional over-current and trip free release. These are electromagnetic control devices. Products from 5000A ARC range have a common general architecture and differ by the size of the arc chute (function of the operating voltage). ARC Nominal voltage (10 2 V) Nominal current (10 2 A) Fig.1.1 Identification mode Their compactness make the A circuit breakers particularly adaptable to assembly in shielded cases of the industrial type cabinets for fixed installations. The circuit breaker design leads to an easy maintenance and high number of operations. The main wearing parts may be changed without completely dismantling the circuit breaker. 2. DESCRIPTION 2.1 Description of circuit breaker The circuit breaker consists of two main part assembly : - the body (also called frame - 1) which is common part of the range - the arc chute (2) with two main versions (for 750V and 1500V applications) Fig.2.1 ARC850 circuit breaker 2.2 Operating mode Mechanical operation Closing The energizing of the electromagnet causes the movement of the main contacts and the movable pole contact comes to the fixed pole contact. Opening by holding current cut off Due to the effect of springs the breaking of the holding current pull the moving pole contact arm to the "open" position. Opening by direct over-current release When the current travelling through the circuit breaker exceeds the release setting threshold, the equilibrium is broken and the movable pole contact arm is pulled back to the "open" position by the effect of return spring. Electrical operation During opening the electric arc develops between the contacts and then, under the effect of the magnetic field, progresses onto the horns. The arc is forced to enter the arc chute by thermodynamic and magnetic effects. The arc chute consists of metal plates which are intended to fraction the arc and to develop the back-electromotive force required for its extinction. 2/9

3 Operation counter In the standard version, a counter for the number of operations as a maintenance help is supplied. Longitudinal opening 2.3 Variants and Accessories Variant 1 : Arc chute The sizes of the 750V and 1500V arc chutes are linked to the number of metal plates in the stacking. 750V version Variant 3 : Electromagnet device 1500V version The electromagnet device is composed of two internal coils, one for closing, one for holding. The energising closing coil causes the movement of the moving pole contact which comes against the fixed pole contact. To rest in closed position, the holding coil should be supply before closing coil. Control voltages available to supply the electromagnet device are 48V, 110V and 125V. Note: A variant is available with magnetic holding instead of holding coil. Variant 2 : Arc chute moving. In the standard version of A DC circuit breaker, the way to move the 750V or 1500V arc chute is lateral as described in the picture, however a longitudinal version is available. Lateral opening Variant 4 : Tripping range The circuit breaker is equipped with an overcurrent release device which is operated directly by the magnetic field of the fault current which crosses the main circuit following two directions (bi-directional release). See below available tripping ranges where the threshold can be adjusted to 5000 A 5000 to A 7500 to A 9000 to A Note : It is possible to adapt an uni-directional release system. The minimum threshold setting is 2500 A. See unidirectional variant 3/9

4 Variant 5 : Uni-directional release device This variant allows to have only one way of tripping the circuit breaker in case of fault current by using permanent magnet device on tripping unit. This release operates only in one direction when current flowing into the circuit breaker top power connection. In the other direction, a permanent magnet is used to maintain the circuit breaker in closed position and to withstand short circuit current Option 1 : Over-current release signalling contact An over-current release signalling contact indicates the state of the circuit breaker : when this contact is in close state, the circuit breaker is open following an tripping event. Option 2 : Ultra-rapid release This option allows high-speed opening upon an external command via the discharge of a capacity into an electromagnet coil, which causes the breaking of the equilibrium between the lower end of the contact arm and the lever. In addition to the first function, there is an over-current release signalling contact. Option 3 : Indirect over-current or manual tripping option This option allows opening upon an external command via a manual action on lever, which causes the breaking of the equilibrium between the lower end of the contact arm and the main lever. In addition to the first function, there is an over-current release signaling contact This option, when it is chosen, replaces the over-current signalling contact / external high-speed release. 3. INTEGRATION The integration of the DC circuit breaker inside a cubicle is an important matter. Attention has to be paid on volume of free air around the product, evacuation of ionized gas and risk of flashover to metal parts. See outline drawing for more information. 4/9

5 4. CHARACTERISTICS 4.1 Standards The HSCB is compliant with: - EN : Railway applications Fixed installations D.C. switchgear - EN : Railway applications Insulation coordination - NF F : Fire behaviour-material choice - NF F : Fire behaviour-material choice and application for electric equipment 4.3 Power circuit Features ARC820 ARC1520 Nominal voltage (UN) 750V 1500V Rated insulation voltage (UNm) 900V 1800V Exceptional voltage Umax2 1000V 1950V Rated impulse withstand voltage (UNi) 1.2/50 µs Overvoltage category Pollution degree 20 kv OV3 PD3 4.2 General features Features Min Max Nominal Operating Temperature Tu -15 C +50 C Storage Temperature Ts -40 C +70 C Altitude Alt 1400m Humidity % 95% at 40 C Dielectric strength between poles (1mn / 50Hz) Dielectric strength between HV and ground/lv (1mn / 50Hz) Rated service current (INE) Overload (from stabilized) Overcurrent tripping device 8 kv rms 10 kv rms 5000 A 10 ka DC during 60s internal overcurrent tripping Bidirectional or unidirectional Mechanical endurance Weight Dimension (mm) HV connections LV connections Fire behaviour Cycles (at 25 C) ARC850 : 160 kg ARC1550: 185 kg ARC850 : 900x500x720 ARC1550 : 900x500x815 HV input and HV output : 5 11mm holes on electrical connection Fixed FCI connector type R-22-B-41-SNH068 (mobile connector supplied) In agreement with standard for installation in technical area 4.4 Breaking capacity Features Maximum prospective current (ka) (INSS) ARC * Time constant (TNC) (ms) Voltage (V) 900 Features ARC1550 Maximum prospective current (ka) (INSS) Time constant (TNC) (ms) Voltage (V) 1500 (*) : It is the peak current value ÎNSS for low inductive circuit. 5/9

6 4.5 Control Circuit 4.7 Wiring diagram Designations Cross section of wiring is 0.93 mm² or more Voltage variants Overvoltage protection device on holding coil Dielectric strength between LV and ground (1mn / 50Hz) Opening time at Un by holding current cut off Power 48 V DC, 110 V DC and 125 V DC Yes 2 kv rms < 40ms 0W when open 40 W at holding 5000 W when closing during 0,5s 4.6 Auxiliary contacts Designations Typ. Min Max Voltage (AC or DC) 50 V 250 V Current 10 ma 2 A Breaking current cycles under 1A, 90V, L/R=15ms cycles under 1A, 90V, L/R=40ms Mechanical endurance Insulation voltage between auxiliary contacts and earth Sequence Cycles 2000 V 4 NO + 6 NC Fig.4.7 Standard wiring* (*) for 48V supply, electromagnet wiring is modified, please consult us for more details 6/9

7 5. DIMENSIONS Overall dimensions of ARC /9

8 Overall dimensions of ARC 850 8/9

9 ARC 850 outline drawing Longitudinal tipping 9/9

TECHNICAL DESCRIPTION

TECHNICAL DESCRIPTION DC Circuit Breaker TECHNICAL DESCRIPTION TRK5650515200 Ed.1 of 21/02/13 CONTENTS 1. INTRODUCTION... 2 2. DESCRIPTION... 2 2.1 Description of circuit breaker... 2 2.2 Operating mode... 2 2.3 Variants and

More information

Contactors. CH1130/02 Series Single pole high-voltage contactor up to 3 kv Catalogue C170.en. Connect - Contact - Control

Contactors. CH1130/02 Series Single pole high-voltage contactor up to 3 kv Catalogue C170.en. Connect - Contact - Control Connect - Contact - Control 3 Contactors CH1130/02 Series Single pole high-voltage contactor up to 3 kv Catalogue C170.en More information at: schaltbau-gmbh.com 42 CH1130/02 Single pole high-voltage contactor

More information

GE Electrical Distribution. Gerapid High Speed DC Circuit Breakers. On the move. imagination at work

GE Electrical Distribution. Gerapid High Speed DC Circuit Breakers. On the move. imagination at work GE Electrical Distribution Gerapid High Speed DC Circuit Breakers On the move imagination at work Gerapid High Speed DC Circuit Breakers To stay up and running today, you need equipment that delivers both

More information

GE Energy Industrial Solutions. Gerapid High Speed DC Breaker Application Guide 1. 1

GE Energy Industrial Solutions. Gerapid High Speed DC Breaker Application Guide 1. 1 GE Energy Industrial Solutions Gerapid High Speed DC Breaker Application Guide g imagination at work 1. 1 Contents Pages Gerapid introduction 3 Gerapid applications 4 Gerapid key features and construction

More information

cor Long Run Experience

cor Long Run Experience Moulded Case Circuit Breakers Moulded Case Circuit Breakers 16-1250A cor Long Run Experience cor Breaking capacity (according to IEC 947-2 at 415V) Icu 100 D160L D250L D400L D630L 70 60 DH800 50 35 30

More information

xxx.1xx xxx.4xx0. AgNi contacts, specifically intended for resistive and slightly inductive loads as well as for motor loads

xxx.1xx xxx.4xx0. AgNi contacts, specifically intended for resistive and slightly inductive loads as well as for motor loads 22 Series - Modular contactors 25-40 - 63 22 SERIES Features 22.32.0.xxx.1xx0 22.32.0.xxx.4xx0 25 modular contactor - 2 pole 17.5 mm wide NO contact gap 3 mm, double break Continuous duty for the coil

More information

Semiconductor (AC) fuses

Semiconductor (AC) fuses Main characteristics 450 TO 700VAC / 63 TO 2800A Recognized Exceptionally low I 2 T, Watt losses. Non-magnetic construction, Highly reliable low voltage Trip-indicator system, conformity to UL, IEC, DIN

More information

Cat N 3. OVERALL DIMENSIONS

Cat N 3. OVERALL DIMENSIONS Cat N Motor driven remote control module 87045 LIMOGES Cedex - FRANCE Telephone : + 33 5 55 06 87 87 Fax: + 33 5 55 06 88 88 Cat N : : 4 062 91 CONTENTS PAGE 1. Description - Use...1 2. Product range...1

More information

Medium Voltage Distribution. Rollarc R400-R400D contactor 1 to 12 kv

Medium Voltage Distribution. Rollarc R400-R400D contactor 1 to 12 kv Medium Voltage Distribution Rollarc R400-R400D contactor to kv Description ield of application and utilisation range Description The Rollarc three-pole indoor contactor uses sulphur hexafluoride (S) gas

More information

High-Voltage Circuit-Breakers 3AP1/ kv up to 550 kv. Power Transmission and Distribution

High-Voltage Circuit-Breakers 3AP1/ kv up to 550 kv. Power Transmission and Distribution High-Voltage Circuit-Breakers AP/ 7.5 kv up to 550 kv Power Transmission and Distribution The AP/ High-Voltage Circuit-Breakers Now Applicable for 550 kv Decades of our experience in high-voltage switching

More information

Power systems Protection course

Power systems Protection course Al-Balqa Applied University Power systems Protection course Department of Electrical Energy Engineering Dr.Audih 1 Part 3 Protective Devices Fuses & Circuit Breakers 2 Introduction: Fuse Is advice used

More information

Contactors. Brochure. Contactors for industry, rolling stock and battery-powered vehicles Emergency disconnect switches

Contactors. Brochure. Contactors for industry, rolling stock and battery-powered vehicles Emergency disconnect switches 3 Brochure Contactors Contactors for industry, rolling stock and battery-powered vehicles Emergency disconnect switches More information here: schaltbau-gmbh.com WE CONTROL ELECTRIC ARCS RELIABLY The quality

More information

MULTI 9 System Catalog IEC Rated C60N/H/L Circuit Breakers

MULTI 9 System Catalog IEC Rated C60N/H/L Circuit Breakers IEC Rated C60N/H/L Circuit Breakers Standard Features Fast Closing Allows increased withstand to the high inrush currents of some loads Trip-free mechanism: Contacts cannot be held in the on position when

More information

C 1. SPECTRONIC SP - Air circuit breakers. Summary. C2. General characteristics. C3. Fixed circuit breaker. C4. Withdrawable circuit breakers

C 1. SPECTRONIC SP - Air circuit breakers. Summary. C2. General characteristics. C3. Fixed circuit breaker. C4. Withdrawable circuit breakers SPETRONI SP - Air circuit breakers Summary 2. General characteristics 3. Fixed circuit breaker 4. Withdrawable circuit breakers 5. haracteristics 6. RV23: protection and control unit 6. RV+ : protection

More information

GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector

GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector Catalog 0500CT9702R409 2009 Class 525/580 CONTENTS Description............................................. Page General Characteristics...................................

More information

01 Spectra Plus - Introduction

01 Spectra Plus - Introduction 01 Spectra Plus - Introduction Standard features Conforming to IS13947-2/EN60947 2 Compact dimensions Available in 3P & 4P High performance microprocessor protection release Wide overload setting from

More information

Motorized switch-disconnectors OTM 40 to 125 Amperes

Motorized switch-disconnectors OTM 40 to 125 Amperes Motorized switch-disconnectors OTM to 125 mperes With the new range of motorized-switch disconnectors, BB offers now a full range from to 2500 mperes. Thanks to the design, OTM...125 are a good solution

More information

HVX Series. 36 kv Medium Voltage Vacuum circuit breaker. Make the most of your energy SM. Medium Voltage Distribution Catalogue 2015

HVX Series. 36 kv Medium Voltage Vacuum circuit breaker. Make the most of your energy SM. Medium Voltage Distribution Catalogue 2015 Medium Voltage Distribution Catalogue 205 HVX Series 36 kv Medium Voltage Vacuum circuit breaker Fixed, middle rolling and floor rolling ranges of circuit breaker and disconnector Make the most of your

More information

Live Tank Circuit Breakers Buyer s Guide

Live Tank Circuit Breakers Buyer s Guide Live Tank Circuit Breakers Buyer s Guide Live Tank Circuit Breakers Buyer s Guide Edition 2, 2003-06 0-1 Contents Table of Contents Products Chapter-Page Introduction A-2 Explanations B-1 Puffer, Auto-Puffer

More information

RESIDUAL CURRENT CIRCUIT BREAKER

RESIDUAL CURRENT CIRCUIT BREAKER Quality Features Mid Trip - Different knob position to indicate whether the device is Switched OFF by a fault or Switched OFF manually Inscription Window - Ensures circuit identification and hence reduces

More information

Circuit breakers and switch-disconnectors NT06 to NT16 and NW08 to NW63

Circuit breakers and switch-disconnectors NT06 to NT16 and NW08 to NW63 Functions and characteristics Circuit breakers and switch-disconnectors NT06 to NT16 and NW08 to NW63 NT and NW selection criteria Masterpact NT Masterpact NW NT06, NT08, NT10, NT12, NT16 NT06, NT08, NT10

More information

AF40... AF96 3-pole contactors Technical data

AF40... AF96 3-pole contactors Technical data Main pole - Utilization characteristics according to IEC Standards IEC 60947- / 60947-4- and EN 60947- / 60947-4- Rated operational voltage Ue max. 690 V Rated frequency (without derating) 50 / 60 Hz Conventional

More information

US catalog. R contactors Control of AC and DC power circuits up to 5000 A

US catalog. R contactors Control of AC and DC power circuits up to 5000 A US catalog R contactors Control of AC and DC power circuits up to 5000 A Motor rated operational powers and currents The currents given below concern standard three-phase four-pole cage motors (1500 r.p.m.

More information

Controls. THERMAL OVERLOAD RELAYS RW..D (up to 40A)

Controls. THERMAL OVERLOAD RELAYS RW..D (up to 40A) Controls THERMAL OVERLOAD RELAYS RW..D (up to 0A) 0800 7 9 Thermal Overload Relays RW..D (up to 0A) THERMAL OVERLOAD RELAYS RW..D (up to 0A) Summary Introduction RW7-D Thermal Overload Relay from 0.8 up

More information

3TM Vacuum Contactors

3TM Vacuum Contactors Catalog Extract HG 11.23 Edition 2016 Catalog Extract Medium-Voltage Equipment siemens.com/3tm R-HG11-343.psd 2 Siemens HG 11.23 2016 Contents Medium-Voltage Equipment Catalog Extract HG 11.23 2016 Contents

More information

VD4/R. Medium Voltage vacuum circuit-breakers for secondary distribution

VD4/R. Medium Voltage vacuum circuit-breakers for secondary distribution VD4/R Medium Voltage vacuum circuit-breakers for secondary distribution DESCRIPTION CIRCUIT-BREAKER SELECTION AND ORDERING SPECIFIC PRODUCT CHARACTERISTICS OVERALL DIMENSIONS ELECTRIC CIRCUIT DIAGRAM

More information

Low voltage Direct Current Network. Compact NSX DC PV. Circuit breakers and switch disconnectors for solar application.

Low voltage Direct Current Network. Compact NSX DC PV. Circuit breakers and switch disconnectors for solar application. Low voltage Direct Current Network Compact NSX DC PV Circuit breakers and switch disconnectors for solar application Catalogue 2012 Compact NSX DC PV A complete DC offer for solar application from 80

More information

DSE201 Compact design with enhanced protection

DSE201 Compact design with enhanced protection DSE201 Compact design with enhanced protection The best of safety DSE201 6 ka: the highest level of reliability The 1P+N electronic residual current circuit-breakers with overcurrent protection (RCBOs)

More information

IP20 degree of protection; IP40 degree of protection after installation in a distribution box

IP20 degree of protection; IP40 degree of protection after installation in a distribution box RI 50 RI 50 is used for the protection of installations and devices (overload and short circuit), and as a disconnector in case of electric shock Simple and quick fixing to a 35 mm mounting rail in accordance

More information

www. ElectricalPartManuals. com 3 to 17.5 kv Fluarc FG2 mastering electrical power FG2 630 A and 1250 A withdrawable FG2 630 A fixed

www. ElectricalPartManuals. com 3 to 17.5 kv Fluarc FG2 mastering electrical power FG2 630 A and 1250 A withdrawable FG2 630 A fixed FG2 630 A and 1250 A withdrawable FG2 3150 A 50 ka withdrawable FG2 630 A and 1250 A withdrawable FG2 630 A fixed Fluarc FG2 3 to 17.5 kv mastering electrical power description presentation The Fluarc

More information

LEXIC Curv LIMOGES Cedex. Cats N (s) : /68/87/88, /48, /84/85, /76/77/95/96/97, /71/72 1.

LEXIC Curv LIMOGES Cedex. Cats N (s) : /68/87/88, /48, /84/85, /76/77/95/96/97, /71/72 1. 87045 LIMOGES Cedex Téléphone : 05 55 06 87 87 Télécopie : 05 55 06 88 88 LEXIC MCB s DX-H 80A, 100A, 125A Curv urves B and C CONTENTS PAGES 1. Description, use...1 2. Range...1 3. Overall dimensions...1

More information

System pro M compact Miniature Circuit Breaker S 200 M UC for DC and AC applications

System pro M compact Miniature Circuit Breaker S 200 M UC for DC and AC applications System pro M compact Miniature Circuit Breaker S 200 M UC for DC and AC applications 2CDC021031S0011 2CDC021033S0011 The miniature circuit breaker S 200 M UC extends the established ABB System pro M compact

More information

PVGard 600 and 1000 Vdc solar photovoltaic circuit breakers

PVGard 600 and 1000 Vdc solar photovoltaic circuit breakers Supersedes October 2013 photovoltaic circuit breakers Contents Description Page Product description........................ 1 PVGard 600 Vdc........................... 2 Technical data...........................

More information

Series KTU7 UL489 Molded Case Circuit Breakers

Series KTU7 UL489 Molded Case Circuit Breakers Series KTU7 UL489 Molded Case Circuit Breakers Versatile, convenient and space saving for a variety of applications Sprecher+Schuh s KTU7 series of UL Molded Case Circuit Breakers are UL489 and CE listed

More information

Contactor-Fuse Combination 3TL62 / 63 / 66

Contactor-Fuse Combination 3TL62 / 63 / 66 Contactor-Fuse Combination TL6 / 6 / 66 Medium-Voltage Equipment Selection and Ordering Data Catalog HG. 00 Answer for energy. Contactor-Fuse Combination TL6 / 6 / 66 R-HG-.tif Siemens HG. 00 Contactor-Fuse

More information

C60H-DC. C curve IEC Direct current (DC) Breaking capacity (Icu) according to IEC Type 1P 110 V 220 V 250 V 440 V 500 V

C60H-DC. C curve IEC Direct current (DC) Breaking capacity (Icu) according to IEC Type 1P 110 V 220 V 250 V 440 V 500 V DC circuit supplementary protectors for feeders / distribution systems C60H-DC C curve DB123430 DB123525 DB405571 IEC 60947-2 PB107193-34.eps PB107194-34.eps The C60H-DC supplementary protectors are used

More information

Micro Contactor MA Series

Micro Contactor MA Series Relay-sized contactor, making it the world s smallest >3mm contact clearance acc. to IEC 60335-1 for Safety Applications Reversing contactor with mechanical interlock 3 Pole and 1 Aux. Contact NO or NC

More information

Voltage limiting device HVL

Voltage limiting device HVL Datasheet Voltage limiting device HVL 60-0.3 1 2 3 3 Equivalent circuit of voltage limiting device Type HVL 60-0.3 1 MO-surge arrester 2 Trigger electronics 3 Thyristor Product Description The HVL 60-0.3

More information

DPX 160 Thermal magnetic and trip-free switches DPX-I 160

DPX 160 Thermal magnetic and trip-free switches DPX-I 160 87045 LIMOGES Cedex Phone : +33 05 55 06 87 87 FAX : +33 05 55 06 88 88 DPX 160 CONTENTS PAGES 1. USE 1 2. RANGE 1 3. DIMENSIONS 1 3. DIMENSIONS (NEXT) 2 4. OVERVIEW 2 5. CONNECTION 2 6. ELECTRICAL AND

More information

OTEC Transfer switch open transition

OTEC Transfer switch open transition Specification sheet OTEC Transfer switch open transition 40 1200 amp Description OTEC transfer switches are designed for operation and switching of electrical loads between primary power and Standby generator

More information

Solid Dielectric, Three Phase Reclosers CATALOG VS11

Solid Dielectric, Three Phase Reclosers CATALOG VS11 Solid Dielectric, Three Phase Reclosers Providing electronic, three phase overcurrent protection for systems rated through 38kV, 800A continuous current, 12.5kA symmetrical interrupting Reliable performance

More information

Molded Vacuum Reclosers The recloser you want, all in one package. Single- and Three-Phase Molded Vacuum Reclosers, 15 38kV

Molded Vacuum Reclosers The recloser you want, all in one package. Single- and Three-Phase Molded Vacuum Reclosers, 15 38kV The recloser you want, all in one package. Single- and Three-Phase, 15 38kV The need for automated reclosers has never been greater, but many of today s reclosers come with penalties. They weigh too much,

More information

VS Range Gamme VS. 100% electronic voltage sensors. Capteurs de tension 100% électronique. Technical argumentation. Argumentation technique

VS Range Gamme VS. 100% electronic voltage sensors. Capteurs de tension 100% électronique. Technical argumentation. Argumentation technique Technical argumentation Argumentation technique VS Range Gamme VS 1SBC146011C1701 Technical Presentation VS range 1.0 - Version 1.0 100% electronic voltage sensors Capteurs de tension 100% électronique

More information

USER MANUAL. GE Consumer & Industrial Power Protection. High Speed DC Circuit Breaker

USER MANUAL. GE Consumer & Industrial Power Protection. High Speed DC Circuit Breaker GE Consumer & Industrial Power Protection High Speed DC Circuit Breaker Gerapid 2607, 4207, 6007, 8007 with arc chutes 1X2, 1X4, 2X2, 2X3, 2X4 USER MANUAL 2010-06-07 S47183-E rev.03 Design and specifications

More information

Medium voltage products HD4/R - HD4/RE MV gas circuit-breakers for secondary distribution. Power and productivity for a better world TM

Medium voltage products HD4/R - HD4/RE MV gas circuit-breakers for secondary distribution. Power and productivity for a better world TM Medium voltage products HD4/R - HD4/RE MV gas circuit-breakers for secondary distribution Power and productivity for a better world TM Table of contents 4 1. Description 11 2. How to choose and order

More information

Low Voltage A GE Power Controls Company. General catalogue

Low Voltage A GE Power Controls Company. General catalogue Low Voltage A GE Power Controls Company General catalogue this is a blanc page Miniature circuit breakers A Miniature circuit breakers AC miniature circuit breakers Benefits of the new MCB s A 3 The AEG

More information

PA39 TYPE PANEL POWER METERS APPLICATION CHOICE OF MEASURING RANGE TECHNICAL DATA. Additional errors

PA39 TYPE PANEL POWER METERS APPLICATION CHOICE OF MEASURING RANGE TECHNICAL DATA. Additional errors PANEL POWER METERS PA39 TYPE Additional errors acc. EN 60051-1 standard Power consumption: - voltage circuit 3 VA - current circuit 0.25 VA Protection Grade acc. to EN60529 Front protection grade: - IP

More information

SPECIFICATIONS FOR 220KV OUT DOOR CIRCUIT BREAKERS. The networks are mainly of outdoor type. The basic parameters are set out below:

SPECIFICATIONS FOR 220KV OUT DOOR CIRCUIT BREAKERS. The networks are mainly of outdoor type. The basic parameters are set out below: SPECIFICATIONS FOR 220KV OUT DOOR CIRCUIT BREAKERS. A. SYSTEM INFORMATION A-1 System Conditions The networks are mainly of outdoor type. The basic parameters are set out below: Nominal system voltage between

More information

Selective main circuit breakers S 750 series Technical Data

Selective main circuit breakers S 750 series Technical Data Selective main circuit breakers S 750 series Technical Data When connecting aluminium conductors ( 4 mm 2 ) ensure that the contact surfaces of the conductors are cleaned, brushed and treated with grease.

More information

System pro M compact Supplementary protector S 200 PR for ring-tongue applications acc. to UL1077

System pro M compact Supplementary protector S 200 PR for ring-tongue applications acc. to UL1077 Data Sheet System pro M compact Supplementary protector S 200 PR for ring-tongue applications acc. to UL1077 2CDC021026S0011 2CDC021016S0012 The S 200 PR is a high-performance supplementary protector with

More information

RESIDUAL CURRENT CIRCUIT BREAKERS OFI (10 ka)

RESIDUAL CURRENT CIRCUIT BREAKERS OFI (10 ka) Residual current circuit breakers RESIDUAL CURRENT CIRCUIT BREAKERS OFI (10 ka) They react to both alternating sine-wave residual current and pulsating direct current (type A) For protection: against accidental

More information

Voltage limiting device HVL

Voltage limiting device HVL Datasheet Voltage limiting device HVL 120-0.3 1 2 3 3 Equivalent circuit of voltage limiting device Type HVL 120-0.3 1 MO-surge arrester 2 Trigger electronics 3 Thyristor Product Description The HVL 120-0.3

More information

DX³ RCBO 6000A Phase + Neutral, neutral on right

DX³ RCBO 6000A Phase + Neutral, neutral on right 87045 LIMOGES Cedex Telephone number: +33 5 55 06 87 87 Fax: +33 5 55 06 88 88 DX³ RCBO 6000A CONTENTS PAGE 1. Description, use... 1 2. Range... 1 3. Overall dimensions... 1 4. Preparation Connection...

More information

Latch for Contactors 4-pole see page 36. Ratings Rated Aux. Contacts Type Coil voltage 2) AC2 Current Built-in Additional 24 24V= DC 5

Latch for Contactors 4-pole see page 36. Ratings Rated Aux. Contacts Type Coil voltage 2) AC2 Current Built-in Additional 24 24V= DC 5 3-pole DC Operated Ratings Rated Aux. Contacts Type Coil voltage 1) AC2 Current Built-in Additional 24 24V= DC 5 AC3 see 48 60V= DC 6 380V AC1 page 34 110 110V= DC 7 400V 660V 220 220V= DC 8 415V 690V

More information

87045 LIMOGES Cedex. 2. PRODUCT RANGE (continued) 1. DESCRIPTION - USE. Breaking capacity : Symbol : Technology : 3. OVERALL DIMENSIONS

87045 LIMOGES Cedex. 2. PRODUCT RANGE (continued) 1. DESCRIPTION - USE. Breaking capacity : Symbol : Technology : 3. OVERALL DIMENSIONS 87045 LIMOGES Cedex Phone : + 33 5 55 06 87 87 Fax : + 33 5 55 06 88 88 R.C.B.O. DX 6000 A Phase + Neutral,, neutral on right side Cat. n (s) : 077 31 077 44-077 77 077 84 078 79 079 01-083 95 084 06 084

More information

LV switch-disconnectors. Interpact Merlin Gerin 40 to 2500 A. Catalogue. We do more with electricity

LV switch-disconnectors. Interpact Merlin Gerin 40 to 2500 A. Catalogue. We do more with electricity LV switch-disconnectors Catalogue Merlin Gerin 40 to 2500 A We do more with electricity LV switch-disconnectors The various low-voltage applications 2 from 40 to 2500 A 4 Compact from 80 to 1250 A 5 Masterpact

More information

GE Consumer & Industrial Power Protection. New. SecoGear kV Metal-clad Switchgear. GE imagination at work

GE Consumer & Industrial Power Protection. New. SecoGear kV Metal-clad Switchgear. GE imagination at work GE Consumer & Industrial Power Protection New SecoGear 12-24kV GE imagination at work General SecoGear metal-clad switchgear is designed and manufactured with advance technology and has been comprehensively

More information

Technical data. Miniature Circuit Breakers. System pro M. System pro M

Technical data. Miniature Circuit Breakers. System pro M. System pro M Technical data System pro M System pro M 1 Prior to connection of aluminium conductors ensure that their contact points are cleaned, brushed and coated with grease. The contact terminals must be tighten

More information

AF09... AF38 4-pole Contactors AC / DC Operated - with Screw Terminals

AF09... AF38 4-pole Contactors AC / DC Operated - with Screw Terminals AF09... AF38 4-pole Contactors AC / DC Operated - with Screw Terminals 25 to 55 A culus CE Application AF09... AF38 4-pole contactors are used for controlling power circuits up to 600 V AC and 240 V DC.

More information

Breakers and Switches. Switches Change-over and transfer switches

Breakers and Switches. Switches Change-over and transfer switches Breakers and Switches Switches Change-over and transfer switches Change-over and transfer switches 16...2500 A Contents: 4 Product overview, features 8 Technical data 8 Manual, motorized and automatic

More information

REFERENCE CP_TSSPEC_138 0 DATE: JUNE 2006 PAGE: 1 OF 17 TITLE SPECIFICATION FOR POLE- MOUNTED AUTO-RECLOSERS TABLE OF CONTENTS

REFERENCE CP_TSSPEC_138 0 DATE: JUNE 2006 PAGE: 1 OF 17 TITLE SPECIFICATION FOR POLE- MOUNTED AUTO-RECLOSERS TABLE OF CONTENTS TITLE SPECIFICATION FOR POLE- MOUNTED DATE: JUNE 2006 PAGE: 1 OF 17 TABLE OF CONTENTS Page FOREWORD...2 INTRODUCTION...3 1 SCOPE...3 2 NORMATIVE S...3 3 DEFINITIONS AND ABBIATIONS...3 4 REQUIREMENTS...3

More information

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV) SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV) For more than four decades, Myers Power Products has led the switchgear market in quality for the electric industry, delivering highly reliable products for utilities

More information

Instruction Manual Gerapid 2607/4207/6007/8007

Instruction Manual Gerapid 2607/4207/6007/8007 g GE Industrial Systems Plainville, CT USA Instruction Manual Gerapid 607/407/6007/8007 User s Guide High Speed DC Circuit Breaker Type Gerapid 607-407 with Arc chute X and X4 General. Warnings Table

More information

NXPLUS C Single busbar. Maintenance-free for lifetime

NXPLUS C Single busbar. Maintenance-free for lifetime NXPLUS C Single busbar Maintenance-free for lifetime Energy Distribution Welcome! Page 2 Content Overview Technical data Typicals Panel design Circuit-Breaker panel Busbar Operation Metering Low-voltage

More information

P.1 CONTENTS. Industrial Earth Leakage Protection. Page

P.1 CONTENTS. Industrial Earth Leakage Protection. Page Industrial earth leakage protection P 1 P.1.01 GB CONTENTS Page Introduction 3 Earth leakage protection 4 Immunized earth leakage protection 5 Measurement in TRMS and Class A 6 Immunity against transient

More information

INTRODUCTION. The plug-in connection on the cables and lightning arrestors, allows for easy installation and replacement.

INTRODUCTION. The plug-in connection on the cables and lightning arrestors, allows for easy installation and replacement. INTRODUCTION The Power Systems 44 kv MiniSub TM is the most compact system at this voltage available. Utilizing a deadfront termination and lightning arrestor setup, it eliminates the line top or side

More information

LR9 F OVERLOAD RELAYS

LR9 F OVERLOAD RELAYS Issued November 2009 DATA SHEET LR9 F OVERLOAD RELAYS Based on Schneider MKTED2050EN Catalogue General 6 Motor protection Operating conditions There are many possible causes of electric motor failure.

More information

Type CDG 14 Extremely Inverse Time Overcurrent and Earth Fault Relay

Type CDG 14 Extremely Inverse Time Overcurrent and Earth Fault Relay Type DG 14 Extremely Inverse Time Overcurrent and Earth Fault Relay Type DG 14 Extremely Inverse Time Overcurrent and Earth Fault Relay DG 14 drawn out from the case The type DG 14 relay is a heavily damped

More information

Type SDV7 distribution circuit breaker family

Type SDV7 distribution circuit breaker family www.usa.siemens.com/sdv7 Type SDV7 distribution circuit breaker family 5.5 kv to 8.0 kv Answers for infrastructure. Table of contents Introduction 0 Vacuum interrupters 0 Simple current path 05 Low-maintenance

More information

Reverse power relay and protection assemblies

Reverse power relay and protection assemblies Reverse power relay and protection Page 1 Issued June 1999 Changed since July 1998 Data subject to change without notice (SE980053) (SE980054) Features Micro-processor based time directionalcurrent relay/protection

More information

High voltage products PASS M0S 252 kv Innovative solution for transmission substation up to 252 kv

High voltage products PASS M0S 252 kv Innovative solution for transmission substation up to 252 kv High voltage products PASS M0S 252 kv Innovative solution for transmission substation up to 252 kv PASS M0S 252 kv Innovation In today s market, the HV substation is increasingly becoming a key element

More information

Basic function. Rated current. Appropriate for three-phase motors of output 2) [kw] I n. = 400 V a.c. 2) Appropriate for three-phase motors

Basic function. Rated current. Appropriate for three-phase motors of output 2) [kw] I n. = 400 V a.c. 2) Appropriate for three-phase motors MOTOR STARTERS SM Basic function Switching and protection of motors up to A Protection against short-circuit and protection against overload The device responds to phase failure The device is provided

More information

Medium Voltage Metal-Enclosed Switches

Medium Voltage Metal-Enclosed Switches Medium Voltage Metal-Enclosed Switches Outdoor Medium Voltage Switch.1 Introduction Product Selection Guide....................................2 Medium Voltage Switch MVS Product Description......................................

More information

Power & High Voltage Joslyn Hi-Voltage Overhead Reclosers & Switches H-220. Series HVI Hi-Velocity Interrupter Attachment

Power & High Voltage Joslyn Hi-Voltage Overhead Reclosers & Switches H-220. Series HVI Hi-Velocity Interrupter Attachment Use load interrupter attachments to enable loop sectionalizing, line dropping, load breaking and transformer-magnetizing current interruption. Increase the capability of your disconnect switches by adding

More information

AF09... AF30 3-pole Contactors up to 20 HP / 480 VAC

AF09... AF30 3-pole Contactors up to 20 HP / 480 VAC AF0... AF0 -pole Contactors up to 20 HP / 480 VAC Contactors and Overload Relays Overview...2 AF0... AF0 -pole Contactors Ordering Details...4 Main Technical Data...20 DC Circuit switching...2 Main Accessory

More information

CONTENT. EPE METALCLAD SWITCHGEARS AMS SERIES 12kV AMS METALCLAD SWITCHGEAR 24kV AMS METALCLAD SWITCHGEAR 40.5KV AMS METALCLAD SWITCHGEAR

CONTENT. EPE METALCLAD SWITCHGEARS AMS SERIES 12kV AMS METALCLAD SWITCHGEAR 24kV AMS METALCLAD SWITCHGEAR 40.5KV AMS METALCLAD SWITCHGEAR CONTENT EPE METLCLD SWITCHGERS SERIES EPE 1220 / - 12KV METLCLD SWITCHGER EPE 10D - 12KV METLCLD SWITCHGER EPE 24-24KV METLCLD SWITCHGER EPE 36-36KV METLCLD SWITCHGER EPE METLCLD SWITCHGERS MS SERIES 12

More information

HB3 Generator Circuit-Breaker Switchgear

HB3 Generator Circuit-Breaker Switchgear Catalog HB3 Edition 2017 HB3 Generator Circuit-Breaker Switchgear Medium-Voltage Switchgear siemens.com/generatorswitchgear R-HB1-001.tif R-HB3 001.tif R-HB3 003.tif R-HB3 002.jpg 2 HB3 Generator Circuit-Breaker

More information

3AK OPERATING INSTRUCTIONS. Vacuum circuit-breaker module 3AK1 and 3AK3

3AK OPERATING INSTRUCTIONS. Vacuum circuit-breaker module 3AK1 and 3AK3 3AK Vacuum circuit-breaker module 3AK1 and 3AK3 OPERATING INSTRUCTIONS Order no.: 9229 9923 176 0B Ordering location: IC LMV LP PO P C41 AG 09.2013 en Siemens AG 2006. All rights reserved. For your safety

More information

SDV7. Outdoor distribution circuit breaker family 15.5 kv to 38.0 kv. usa.siemens.com/sdv7

SDV7. Outdoor distribution circuit breaker family 15.5 kv to 38.0 kv. usa.siemens.com/sdv7 0 000 0000000 0000 000000 0000 000 0000000 0000 000000 0000 000 0000000 SDV7 Outdoor distribution circuit breaker family 5.5 kv to 8.0 kv usa.siemens.com/sdv7 SDV7 Brochure Brochure SDV7 The type SDV7

More information

FUSES. Safety through quality

FUSES. Safety through quality Safety through quality HH HIGH VOLTAGE Over many decades SIBA has developed a global product line of High Voltage Fuses that are comprehensive for any and all applications. Superior engineering, advanced

More information

Cat. N (s) : /65/66/83/84, /94/95/96/99, /01/02/06/07/11/12/13/14. Pollution degree : C / + 40 C. .

Cat. N (s) : /65/66/83/84, /94/95/96/99, /01/02/06/07/11/12/13/14. Pollution degree : C / + 40 C. . 87045 LIMOGES Cedex Telephone : (+33) 05 55 06 87 87 Fax : (+ 33) 05 55 06 88 88 R.C.C.B. s 0090 00/01/02/06/07/11/12/13/14 0/01/02/06/07/11/12/13/14/18/19/23/24/25/26/ /18/19/23/24/25/26/45/46 45/46 0090

More information

PASS M0. Innovative solutions for distribution substations up to 170 kv

PASS M0. Innovative solutions for distribution substations up to 170 kv PASS M0 Innovative solutions for distribution substations up to 170 kv The concept In the today s changing market, the substation is becoming more and more a key element to meet end users requirements

More information

Benefits, typical uses

Benefits, typical uses R-HA26-013. eps Switchgear Type 8BT1, up to 24kV,Air-Insulated Contents Application Page Application Benefits 2 Typical uses 2 and 3 Technical Data Ratings 4 Classification, dimensions, 5 room planning

More information

Type HS PEXLIM-P Surge Arresters Maximum System Voltage 123 kv to 800 kv

Type HS PEXLIM-P Surge Arresters Maximum System Voltage 123 kv to 800 kv Type HS PEXLIM-P Surge Arresters Maximum System Voltage 123 kv to 800 kv HS PEXLIM-P Metal Oxide Surge Arrester HS PEXLIM-P Surge Arresters are used for the protection of switchgear, transformers and other

More information

Contact us. ABB France Electrification Products Division Low Voltage Products and Systems 3, rue Jean Perrin F Chassieu cedex / France

Contact us. ABB France Electrification Products Division Low Voltage Products and Systems 3, rue Jean Perrin F Chassieu cedex / France Contact us ABB France Electrification Products Division Low Voltage Products and Systems 3, rue Jean Perrin F-69687 Chassieu cedex / France You can find the address of your local sales organisation on

More information

ZF SERIES HV GAS INSULATED SWITCHGEAR (GIS) tgood.com. Energy. Fast.

ZF SERIES HV GAS INSULATED SWITCHGEAR (GIS) tgood.com. Energy. Fast. ZF SERIES HV GAS INSULATED SWITCHGEAR (GIS) tgood.com Energy. Fast. TGOOD produces over 5000 switchgear units annually for projects around the globe PRODUCT OVERVIEW High performance alternative to air

More information

MEDIUM VOLTAGE NETWORKS

MEDIUM VOLTAGE NETWORKS MEDIUM VOLTAGE NETWORKS LIGHTNING ARRESTERS & INSULATORS SICAME GROUP OUR EXPERIENCE With 25 years of experience in the field of over protection for medium lines, DERVASIL designs and manufactures zinc

More information

DATA SHEET FOR 1 TYPE COMPARTMENTALISED / NON - COMPARTMENTALISED. ( a ) CIRCUIT BREAKER FEEDERS FULLY DRAWOUT / NON DRAWOUT

DATA SHEET FOR 1 TYPE COMPARTMENTALISED / NON - COMPARTMENTALISED. ( a ) CIRCUIT BREAKER FEEDERS FULLY DRAWOUT / NON DRAWOUT 44LK-500/E.04/002A/A4 PROJECT NO 44LK-500 CHKD. BY VDV VDV A CLIMATIC CONDITIONS THIS DATA SHEET IS APPLICABLE FOR IN UTILITY BOILER PACKAGE DESIGN AMBIENT TEMPERATURE 45 C 2 ALTITUDE ( ABOVE MSL ) 6.7

More information

Metal Clad Air Insulated Switchgear

Metal Clad Air Insulated Switchgear Metal Clad Air Insulated Switchgear 1/ SecoGear Metal Clad Switchgear Features Fully metal-clad Equipped with Embedded pole VCB Full Front access (can be installed against wall) Perfect interlocking system

More information

2 pole 10 A PCB mount A1 A

2 pole 10 A PCB mount A1 A Series - Miniature general purpose relays - 0 A Features Printed circuit mount, general purpose, & Pole relays. - Pole 0 A. - Pole 0 A. - Pole A AC coils & DC coils Cadmium Free contacts (preferred version)

More information

SOLENOID VALVES AND PNEUMATIC VALVES

SOLENOID VALVES AND PNEUMATIC VALVES A S E R I E S Catalogue 001 Directly operated solenoid valves Series A / way, 3/ way monostable, stable (with magnetic memory) Ports M5, G1/8, cartridge ø 4 The Series A solenoid valves are of the directly

More information

Using new Magnetically Actuated Vacuum Interrupter technology for safe and reliable medium voltage circuit breaker switching in mines

Using new Magnetically Actuated Vacuum Interrupter technology for safe and reliable medium voltage circuit breaker switching in mines Using new Magnetically Actuated Vacuum Interrupter technology for safe and reliable medium voltage circuit breaker switching in mines Abstract: The development of the magnetically actuated vacuum interrupter

More information

Magnetic Overcurrent Circuit Breaker

Magnetic Overcurrent Circuit Breaker Magnetic Overcurrent Circuit Breaker 808-... Description ngle pole miniaturised magnetic circuit breakers with unique highspeed operating mechanism and push/pull on/off manual actuation. Fitted with electrically

More information

0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N

0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 55 Series - General purpose relays 7-10 A 55 Features 55.12 55.13 55.14 Printed circuit mount, general purpose 2, 3 & 4 Pole relays 55.12-2 Pole 10 A 55.13-3 Pole 10 A 55.14-4 Pole 7 A AC coils & DC coils

More information

ELECTRIC TRACTION.

ELECTRIC TRACTION. ELECTRIC TRACTION www.koncar.hr MODERNISATION ELECTRIC TRACTION VEHICLES Company KON AR - ELECTRIC VEHICLES Inc. upgrades electric locomotives, electric multiple unit and electric tramcars. Upgrading proceedings

More information

Liquid or convection cooled models available CAN bus serial interface

Liquid or convection cooled models available CAN bus serial interface The Bel Power Solutions 700DNC150-56-xG () is a 15000 Watts DC/DC converter that creates DC voltages in hybrid and electric vehicles necessary to power low voltage accessories. Attractive reverse energy

More information

Breakers and Switches. Switches Switch-disconnectors OT and OTM

Breakers and Switches. Switches Switch-disconnectors OT and OTM Breakers and Switches Switches Switch-disconnectors OT and OTM Switch-disconnectors OT16...4000 and OTM40...2500 Features Product overview 4 High performance, compact solution 6 Technical data Switch-disconnectors,

More information

Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kv, Gas-Insulated

Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kv, Gas-Insulated www.siemens.com/medium-voltage-switchgear Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS up to 40.5 kv, Gas-Insulated Medium-Voltage Switchgear Catalog HA 35.5 203 Answers f infrastructure and cities.

More information

Low Voltage Systems MNS and MNS is PowerCenter

Low Voltage Systems MNS and MNS is PowerCenter Low Voltage Systems MNS and MNS is PowerCenter For our customers, it s all about saving space maximizing functionality for power distribution systems while reducing equipment footprint. ABB has answered

More information

SF6 Gas-Insulated Metal Enclosed Switchgear

SF6 Gas-Insulated Metal Enclosed Switchgear SF6 Gas-Insulated Metal Enclosed Switchgear 24-36 kv, 3 sec (LSC2A, PM) Standard IEC 62271-200 Nature is Our Most Valuable Partner GIS-EN-12-01 SF6 Gas-Insulated Metal Enclosed Switchgear CONTENTS 1.INTRODUCTION...

More information